Page 1: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

DS110

OUTSULATION® PLUS MD SYSTEM® An Exterior Wall Insulation and Finish System With Moisture Drainage That Incorporates Continuous Insulation and An Air/Water-Resistive Barrier

Outsulation Plus MD System Installation Details

Page 2: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

NOTE

DETAIL

TABLE OF CONTENTSDETAIL

OUTSULATION PLUS MD SYSTEM OPMD 0.0.01AWRB APPLICATION OPMD 0.0.02OPENING PREPARATION- OPMD 0.0.03 AQUAFLASH® SYSTEM OPTIONOPENING PREPARATION- OPMD 0.0.04 BACKSTOP® NT™ OPTIONOPENING FLASHING INTEGRATION OPMD 0.0.05INSIDE/OUTSIDE CORNERS OPMD 0.0.06OUTSIDE CORNER - HIGH IMPACT OPMD 0.0.07GRADE TERMINATION OPMD 0.0.08TERMNATION AT CONCRETE CURB OPMD 0.0.09TERMINATION AT ADA COMPLIANT OPMD 0.0.10 SIDEWALKEPS PREPARATION AT OPMD 0.0.11 WALL PENETRATIONSSTOREFRONT WINDOW SILL - JAMB OPMD 0.0.12SELF FLASHING WINDOW SILL - JAMB OPMD 0.0.13STOREFRONT AND FLANGED OPMD 0.0.14 WINDOW HEADHEAD J-TRACK OPTION OPMD 0.0.15TERMINATION AT OPMD 0.0.16 WOOD FRAMED DECKTERMINATION AT OPMD 0.0.17 WATERPROOF DECKPREPARATION AT PARAPET/ OPMD 0.0.18 WALL INTERSECTIONTERMINATION AT PARAPET - OPMD 0.0.19 CAP FLASHINGTERMINATION AT PARAPET - OPMD 0.0.20 SOLID SUBSTRATETERMINATION AT SLOPED ROOF OPMD 0.0.21TERMINATION AT ROOF STOP OPMD 0.0.22 FLASHINGVERTICAL WALL/ SUSPENDED OPMD 0.0.23 SOFFIT TRANSITIONTRANSITION AT SOFFIT/ OPMD 0.0.24 FASCIA INTERSECTIONFASCIA/ UNINSULATED SOFFIT OPMD 0.0.25 TRANSITIONTERMINATION AT OPMD 0.0.26 UNINSULATED SOFFIT VENTHORIZONTAL SLIP JOINT OPMD 0.0.27 WITHOUT WEEPSHORIZONTAL SLIP JOINT OPMD 0.0.28 WITH WEEPSHORIZONTAL JOINT - OPMD 0.0.29 SUBSTRATE CHANGEHORIZONTAL TERMINATION OPMD 0.0.30 AT STONE VENEER

HORIZONTAL TERMINATION OPMD 0.0.31 AT STUCCOHORIZONTAL TERMINATION OPMD 0.0.32 AT WOOD SIDINGVERTICAL EXPANSION JOINT- OPMD 0.0.33 EIFSTHROUGH-WALL EXPANSION JOINT OPMD 0.0.34VERTICAL EXPANSION JOINT - OPMD 0.0.35 FLUSH OPTIONVERTICAL EXPANSION JOINT - OPMD 0.0.36 RECESSED OPTIONVERTICAL EXPANSION JOINT - OPMD 0.0.37 DOUBLE SEAL OPTIONVERTICAL TERMINATION OPMD 0.0.38 AT STONE VENEERPENETRATIONS OPMD 0.0.39SIGN ATTACHMENT OPMD 0.0.40AESTHETIC REVEALS OPMD 0.0.41RECESSED GRAPHICS OPMD 0.0.42PROJECTING GRAPHICS OPMD 0.0.43EPS SHAPES OPMD 0.0.44

DRYVIT MAKES NO REPRESENTATION REGARDINGCONFORMITY OF ITS SUGGESTIONS TO MODEL BUILDINGCODES, ENGINEERING CRITERIA, SPECIFIC APPLICATIONS,OR PROJECT LOCATIONS. ALL COMPONENTS INDICATEDIN ILLUSTRATIONS, AS WELL AS OTHERS THAT MAY BEREQUIRED FOR THE INTEGRITY OF THE SYSTEM SHALL BEDESIGNED, DETAILED, AND ENGINEERED BYREPRESENTATIVES OF THE ARCHITECT, OWNER, ORCONTRACTOR TO BE IN CONFORMANCE WITH MODELCODES, ARCHITECTURAL, AND ENGINEERINGREQUIREMENTS PERTAINING TO SPECIFIC BUILDINGPROJECTS.

DRYVIT MAKES NO WARRANTY, EXPRESSED OR IMPLIED,AS TO THE ARCHITECTURAL DESIGN, ENGINEERING, ORWORKMANSHIP OF PROJECTS UTILIZING DRYVIT SYSTEMSOR PRODUCTS.

THE LIABILITIES OF DRYVIT SHALL BE AS STATED IN THEOUTSULATION PLUS MD LIMITED COMMERCIALWARRANTY. CONTACT DRYVIT FOR A FULL ANDCOMPLETE COPY OF THE WARRANTY.

Outsulation® Plus MD System®The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

©Dryvit Systems, Inc. 1969Issued: 10/2016

Page 3: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

DRYVIT ADHESIVE IN VERTICAL NOTCHEDTROWEL CONFIGURATION APPLIED TOBACK OF EPS

Outsulation® Plus MD System®

OPMD 0.0.01

Outsulation Plus MD SystemNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. AS AN OPTION DRYVIT DRAINAGETRACK™ CAN BE USED AT SYSTEMTERMINATION AT GRADE, REFER TOOPMD 0.0.08 FOR CONFIGURATION.

3. DRYVIT DRAINAGE TRACK SHALL ONLYBE USED AT GRADE LEVEL TERMINATIONS.

NORMAL IMPACT

HIGH IMPACT

EPS INSULATION BOARD

APPROVED SUBSTRATE

DRYVIT AIR/WATER-RESISTIVE BARRIER COATING

DRYVIT BASE COAT

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT BASE COAT

DRYVIT FINISH

DRYVIT ADHESIVE IN VERTICAL NOTCHED TROWELCONFIGURATION APPLIED TO BACK OF EPS

DRYVIT DRAINAGE STRIP™ ADHERED WITH DABSOF DRYVIT AP ADHESIVE (SEE NOTES 2 AND 3)

EPS INSULATION BOARD

APPROVED SUBSTRATE

DRYVIT AIR/WATER - RESISTIVE BARRIER COATING

DRYVIT BASE COAT

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT BASE COAT

DRYVIT FINISH

FRAMING BY OTHERS

DRYVIT DRAINAGE STRIP ADHERED WITH DABSOF DRYVIT AP ADHESIVE (SEE NOTES 2 AND 3)

DRYVIT PANZER REINFORCING MESH

DRYVIT BASE COAT

OUTSULATIONPLUS MD SYSTEM

BY OTHERSFRAMING BY OTHERS

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 4: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

DRYVIT BACKSTOP® NT™ - TEXTURE

APPROVED SUBSTRATE

FRAMING BY OTHERS

Outsulation® Plus MD System®

OPMD 0.0.02

NOTE:1. FOR ADDITIONAL AIR/WATER-RESISTIVEBARRIER DETAILS, REFER TO DRYVITPUBLICATION DS840.

DRYVIT BACKSTOP NT - TEXTUREOVER DRYVIT GRID TAPE™

AWRB Application

DRYVIT AIR/WATER - RESISTIVEBARRIER COATING

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 5: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

STEP #1 STEP #2

STEP #4STEP #3

Opening Preparation -AquaFlash® System OptionOutsulation® Plus MD System®

OPMD 0.0.03

NOTE:1. DRYVIT AQUAFLASH SHALL EXTEND TOINTERIOR FACE OF OPENING.

2. REFER TO HEAD, SILL AND JAMB DETAILSFOR FLASHING INTEGRATION.

3. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHING TAPE™MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

4. INSTALL WINDOW UNIT AND ASSOCIATEDFLASHINGS PER MANUFACTURER'SRECOMMENDATIONS, CODE REQUIREMENTS ANDPROJECT DOCUMENTS.

5. AQUAFLASH SYSTEM CONSISTS OF AQUAFLASHMESH AND AQUAFLASH LIQUID.

6. FOR ADDITIONAL AIR/WATER-RESISTIVE BARRIERDETAILS, REFER TO DRYVIT PUBLICATION DS840.

5

INSTALL DIAGONAL STRIP OF DRYVITAQUAFLASH MESH AT CORNERSAND EMBED IN AQUAFLASH LIQUID(SEE NOTES 1 AND 3)

APPLY DRYVIT AQUAFLASH®SYSTEM (SEE NOTES 1 AND 3)

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

INSTALL DRYVIT AQUAFLASHSYSTEM AT HEADS(SEE NOTES 1, 3 AND 4)

INSTALL DRYVIT AQUAFLASHSYSTEM AT JAMBS(SEE NOTES 1 AND 3)

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 6: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

OPMD 0.0.04

STEP #1

Outsulation® Plus MD System®

STEP #2

APPLY DRYVIT GRID TAPE™(SEE NOTES 1 AND 2)

TROWEL APPLY DRYVITBACKSTOP NT-TEXTURE(SEE NOTE 2)

6" (153 MM) MIN.(TYP.)

STEP #3

APPLY DRYVIT AQUAFLASH®SYSTEM (SEE NOTES 2, 3 AND 5)

STEP #4

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING APPLIED TOFACE OF WALL (SEE NOTE 5)

NOTE:1. APPLY DRYVIT GRID TAPE ON HEAD, JAMB, ANDCORNERS OF OPENINGS AND SHEATHING JOINTS.

2. TROWEL APPLY DRYVIT BACKSTOP NT-TEXTUREOVER THE DRYVIT GRID TAPE ALL THE WAY TO INSIDEFACE OF OPENING. ALL VOIDS MUST BE FILLED;MULTIPLE PASSES MAY BE REQUIRED. AS AN OPTION,DRYVIT GRID TAPE AND DRYVIT BACKSTOP NT-TEXTUREMAY ALSO BE APPLIED AT THE SILL PRIOR TO DRYVITAQUAFLASH SYSTEM OR FLASHING TAPE APPLICATION.

3. DRYVIT FLASHING TAPE SURFACE CONDITIONER™AND DRYVIT FLASHING TAPE™ MAY BE USED IN LIEU OFDRYVIT AQUAFLASH SYSTEM AT SILL, INCLUDINGCORNER SPLICES.

4. INSTALL WINDOW UNIT AND ASSOCIATEDFLASHINGS PER MANUFACTURER'SRECOMMENDATIONS, CODE REQUIREMENTSAND PROJECT DOCUMENTS.

5. REFER TO HEAD, SILL, AND JAMB DETAILSFOR FLASHING INTEGRATION.

6. FOR ADDITIONAL AIR/WATER-RESISTIVEBARRIER DETAILS, REFER TO DRYVITPUBLICATION DS840.

Opening Preparation -Backstop® NT™ Option

4" (102 MM) MIN.(TYP.)

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 7: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

OPMD 0.0.05

STEP #1

Opening Flashing IntegrationOutsulation® Plus MD System®

REFER TO OPMD 0.0.03, AND OPMD 0.0.04FOR PREPARATION OF OPENING PRIORTO FLASHING INSTALLATION

STEP #2 STEP #3

REFER TO OPMD 0.0.12 &OPMD 0.0.13 FOR JAMBDETAIL

NOTE:1. REFER TO OPMD 0.0.12 AND OPMD 0.0.13FOR INTEGRATION OF FLASHING.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

3. FOR ADDITIONAL AIR/WATER-RESISTIVEBARRIER DETAILS, REFER TO DRYVITPUBLICATION DS840.

INSTALL WINDOW UNIT ANDASSOCIATED FLASHINGS ANDAPPLY DRYVIT AQUAFLASHSYSTEM OVER VERTICAL LEG OFFLASHING (SEE NOTES 1 AND 2)

APPLY DRYVIT AQUAFLASH®SYSTEM SPLICES LAPPING OVERLIP OF SILL PAN FLASHING.(SEE NOTES 1 AND 2)

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 8: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

OPMD 0.0.06

Inside/Outside CornersOutsulation® Plus MD System®

8"(203 MM)

MIN. MUST OVERLAP8" (203 MM) MIN.

(SEE NOTE 3)

MUST OVERLAP8" (203 MM) MIN.

(SEE NOTES 2, 3 AND 4) 8"(203 MM)

MIN.

NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD OR STANDARDPLUS MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.

2. DOUBLE WRAP OUTSIDE CORNERS WITHREINFORCING MESH OR USE CORNER MESH.

3. DO NOT LAP REINFORCING MESH WITHIN8" (203 MM) OF A CORNER.

4. OUTSIDE INSULATION BOARD EDGESSHALL BE OFFSET.

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

APPROVED SUBSTRATE

DRYVIT BACKSTOP® NT™-TEXTUREOVER DRYVIT GRID TAPE™

DRYVIT BASE COAT

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT ADHESIVE IN VERTICAL NOTCHED TROWELCONFIGURATION APPLIED TO BACK OF EPS

EPS INSULATION

DRYVIT FINISH

DRYVIT BASE COAT

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT BASE COAT

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

EPS INSULATION

APPROVED SUBSTRATE

DRYVIT ADHESIVE IN VERTICAL NOTCHED TROWELCONFIGURATION APPLIED TO BACK OF EPS

DRYVIT BACKSTOP NT-TEXTUREOVER DRYVIT GRID TAPE

DRYVIT FINISH

DRYVIT BASE COAT

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 9: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

OPMD 0.0.07

Outside Corner-High Impact

8"(203 MM)

MIN.

NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARDOR STANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. OUTSIDE INSULATION BOARD EDGESSHALL BE OFFSET.

DRYVIT FINISH

DRYVITBACKSTOP® NT™-TEXTUREOVER DRYVIT GRID TAPE™

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWELCONFIGURATION APPLIEDTO BACK OF EPS

APPROVED SUBSTRATE

DRYVIT BASE COAT

DRYVIT PANZER 20REINFORCING MESH EMBEDDEDIN DRYVIT BASE COAT

DRYVIT STANDARDREINFORCING MESHOVERLAP 8" (203 MM) MIN.AT CORNER

EPS INSULATION

DRYVIT BASE COAT

DRYVIT CORNER MESH™

8"(203 MM)

MIN.

Outsulation® Plus MD System®

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 10: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

8" (203 MM)MIN.

Outsulation® Plus MD System® Grade Termination

2'-0" (610 MM)MAX.

(SEE NOTE 2)

OPMD 0.0.08

OUTSULATION PLUSMD SYSTEM

BY OTHERS

NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. EXPANSION JOINT IS REQUIRED ALONGTOP OF FOUNDATION IF 2'-0" (610 MM) DIMENSION IS EXCEEDED.

3. ENSURE BOTTOM EDGE OF DRAINAGESTRIP IS LEFT FREE TO DRAIN.

4. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

DRYVIT DETAIL MESH® WRAPPEDTO BACKSIDE OF EPS MIN. 2" (51 MM)

EPS INSULATION

DRYVIT BASE COAT

DRYVIT AQUAFLASH® SYSTEM (SEE NOTE 4)

SLOPE GRADE AWAYFROM FOUNDATION WALL

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT BACKSTOP® NT™-TEXTUREOVER DRYVIT GRID TAPE™

DRYVIT DRAINAGE STRIP™ ADHEREDWITH DABS OF DRYVIT AP ADHESIVE(SEE NOTE 3)

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT ADHESIVE IN VERTICAL NOTCHEDTROWEL CONFIGURATION APPLIED TO

BACK OF EPS

APPROVED SUBSTRATE

5. DRAINAGE TRACK USAGE IS LIMITED TOTHE BASE OF THE SYSTEM AT FINISHEDGRADE LEVEL.

6. LIGHTLY SAND SURFACE OF DRAINAGETRACK TO MAXIMIZE ADHESION.

8" (203 MM)MIN.

DRAINAGETRACK OPTION

2'-0" (610 MM)MAX.

(SEE NOTE 2)

SEE NOTES 4,5 & 6)

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 11: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

Outsulation® Plus MD System® Termination At Concrete Curb

OPMD 0.0.09

BY OTHERS

DRYVIT FINISH

DRYVIT REINFORCINGMESH EMBEDDED INDRYVIT BASE COAT

EPS INSULATION

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT ADHESIVE IN VERTICAL NOTCHEDTROWEL CONFIGURATION APPLIED TO

BACK OF EPS

APPROVED SUBSTRATE

NOTE:1. DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSED TOABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD OR STANDARD PLUS MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.

2. ENSURE BOTTOM EDGE OF DRAINAGE STRIP ISLEFT FREE TO DRAIN.

3. LIGHTLY SAND SURFACE OF DRAINAGETRACK TO MAXIMIZE ADHESION.

4. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

5. DRYVIT DRAINAGE TRACK SHALL ONLY BEUSED AT GRADE LEVEL TERMINATIONS.

DRAINAGETRACK OPTION

DRYVIT AQUAFLASH SYSTEM ORDRYVIT BACKSTOP NT-TEXTURE OVER

GRID TAPE (SEE NOTES 3, 4 AND 5)

DRYVIT DRAINAGE TRACKSET IN DRYVIT AP ADHESIVE

OUTSULATIONPLUS MD SYSTEM

DRYVIT BASE COAT

2" (51 MM) MIN.

DRYVIT DRAINAGE STRIP™ ADHERED WITHDABS OF DRYVIT AP ADHESIVE (SEE NOTE 2)

DRYVIT AQUAFLASH® SYSTEM

DRYVIT BACKSTOP® NT™TEXTURE OVER DRYVIT

GRID TAPE™

DRYVIT DETAIL MESH® WRAPPEDTO BACKSIDE OF EPS MIN. 2" (51 MM)

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 12: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

Termination At ADA Compliant Sidewalk

OPMD 0.0.10

NOTE:1. DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSED TOABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD OR STANDARD PLUS MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. USE OF THIS DETAIL IS LIMITED TOSLAB-ON-GRADE APPLICATIONS.

3. INCORPORATE MEASURES TO PROTECTSTRUCTURE FROM MOISTURE INTRUSION,DAMPNESS, AND FROST HEAVE.

OUTSULATION PLUSMD SYSTEM

BY OTHERS

DRYVIT FINISH

DRYVIT STANDARD REINFORCINGMESH EMBEDDED IN DRYVIT BASECOAT

EPS INSULATION

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT ADHESIVE APPLIED INVERTICAL NOTCHED TROWELCONFIGURATION TO BACK OF EPS

APPROVED SUBSTRATE

DRYVIT BASE COAT

3/4" (19 MM) MIN. (SEE NOTE 4)

DRYVIT BASE COAT

DRYVIT DETAIL MESH® WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM)

DRYVIT AQUAFLASH® SYSTEM

METAL PROTECTION SHEET,BY OTHERS

ADA COMPLIANT SIDEWALK SLOPEDAWAY FOR POSITIVE DRAINAGE

FULLY ADHERED FOUNDATIONWATERPROOFING MEMBRANE,

BY OTHERSCOMPRESSIBLE FILLER BOARD,BY OTHERS

2" (51 MM) MAX.OVERLAP

DRYVIT DRAINAGE STRIP™ ADHERED WITHDABS OF DRYVIT AP ADHESIVE

Outsulation® Plus MD System®4. TO PREVENT DEBRIS ACCUMULATION, IT ISRECOMMENDED TO TERMINATE SYSTEM 2"ABOVE SIDEWALK.

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 13: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

EPS INSULATION(SEE NOTE 2)

DRYVIT DETAIL MESH® WRAPPEDTO BACKSIDE OF EPS MIN. 2" (51 MM)

DRYVIT DETAIL REINFORCING MESH9 1/2" (241 MM) X 12" (305 MM) (TYP.)(SEE NOTE 3)

OPMD 0.0.11

EPS Preparation At Wall PenetrationsOutsulation® Plus MD System®NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARDOR STANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. LOCATE INSULATION BOARDS SUCHTHAT BOARD EDGES DO NOT ALIGN WITHCORNERS OF PENETRATION.

3. APPLY A PIECE OF 9 1/2" (241 MM) X 12"(305 MM) DETAIL REINFORCING MESHDIAGONALLY AT EACH CORNER.

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 14: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

Storefront Window Sill - JambOutsulation® Plus MD System®NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD OR STANDARDPLUS MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

3. DRYVIT BACKSTOP® NT-TEXTURE OVERGRID TAPE™ IS AN ALTERNATIVE OPTIONAT JAMB AND HEAD CONDITION PERDETAIL OPMD 0.0.04.

4. EDGE WRAPPING METHOD ISACCEPTABLE AT SILL AND JAMB IN LIEUOF BACK WRAPPING. DRYVITREINFORCING MESH MUST BE FULLYEMBEDDED IN DRYVIT BASE COAT AT EPSEDGE AND MUST EXTEND ONTOSUBSTRATE 2" (51 MM) MIN.

OPMD 0.0.12

2 1/2"(64 MM) MIN.

1/2" (12.7 MM)

SILL PAN FLASHINGDETAIL

AIR SEAL PER MANUFACTURER'SREQUIREMENTS, BY OTHERS

DRYVIT COMPATIBLESEALANT, BY OTHERS

WRAP DRYVIT DETAILMESH® 2" (51 MM) MIN.

AT BACKSIDE OF EPS(SEE NOTE 4)

CONTINUOUS FLASHING, BYOTHERS, TURN UP 1/2" (12.7 MM) MIN.AT JAMBS - SEE DETAIL BELOW

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT FINISH

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT BASE COAT

DRYVIT COMPATIBLESEALANT, BY OTHERS

DRYVIT AQUAFLASH®SYSTEM (SEE NOTE 2)

EPS INSULATION BOARD

EPS SHAPE (OPTIONAL)

DRYVIT BASE COAT

APPROVED SUBSTRATE

DRYVITAIR/WATER-RESISTIVE

BARRIER COATING

WRAP DRYVIT DETAIL MESH® 2" (51 MM) MIN. AT BACKSIDE OF EPS(SEE NOTE 4)

SLOPED SHIM ASREQUIRED, BY OTHERS

3/4" MIN.(19 MM )DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 2 AND 3)

FRAMING BY OTHERS

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 15: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

OPMD 0.0.13

Self Flashing Window Sill - Jamb

FRAMING BY OTHERS

DRYVIT AQUAFLASH® SYSTEM(SEE NOTES 2 AND 3)

NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD OR STANDARDPLUS MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

3. DRYVIT BACKSTOP® NT™-TEXTURE OVERDRYVIT GRID TAPE™ IS AN ALTERNATIVEOPTION AT JAMB AND HEAD CONDITION PERDETAIL OPMD 0.0.04.

4. ADHESIVE ONLY APPLICATION IS ACCEPTABLEWHEN USING DRYVIT AQUAFLASH SYSTEM.

5. EDGE WRAPPING METHOD IS ACCEPTABLE INLIEU OF BACK WRAPPING. DRYVIT REINFORCINGMESH MUST BE FULLY EMBEDDED IN DRYVITBASE COAT AT EPS EDGE AND EXTEND ONTOSUBSTRATE 2" (51 MM) MIN.

APPROVED SUBSTRATE

SILL PAN FLASHING,BY OTHERS

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT BASE COAT

DRYVIT FINISH

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT COMPATIBLE SEALANT,BY OTHERS

DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACE(S) TO RECEIVE SEALANT

DRYVIT DETAIL MESHWRAPPED TO BACKSIDE

OF EPS MIN. 2" (51 MM)

EPS INSULATION

DRYVIT DETAIL MESH® WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM)

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS

3/4" (19 MM ) MIN.

3/4"(19 MM) MIN.

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL

CONFIGURATION

EPS SHAPE (OPTIONAL)

TRANSITION FLASHING,BY OTHERS

DRYVIT AQUAFLASHSYSTEM (SEE NOTE 2)

DRYVIT COMPATIBLESEALANT, BY OTHERS

PROVIDE AIR SEAL, BY OTHERS,AROUND INTERIOR OF WINDOW

PER WINDOW MANUFACTURER'SREQUIREMENTS

Outsulation® Plus MD System®

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 16: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

OPMD 0.0.14

Storefront and Flanged Window Head

APPROVED SUBSTRATE

DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKERROD AND WEEP TUBES EVERY24" (610 MM). BY OTHERS

SEALANT AND FLASHING,BY OTHERS

3/4" (19 MM)

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS

EPS INSULATION BOARD

DRYVIT BASE COAT

DRYVIT AQUAFLASH® SYSTEMOR DRYVIT BACKSTOP® NT™TEXTURE OVER DRYVIT GRID

TAPE™ (SEE NOTE 2)

DRYVIT AQUAFLASH® SYSTEMOVER CONTINUOUS FLASHINGWITH END DAMS

AIR SEAL PERMANUFACTURER'SREQUIREMENTS,BY OTHERS

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT(SEE NOTE 1)

DRYVIT DETAIL MESH® WRAPPEDTO BACKSIDE OF EPS MIN. 2" (51 MM)

DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACE(S) TO RECEIVE SEALANT

DRYVIT FINISH

EPS SHAPE (OPTIONAL)

OUTSULATIONPLUS MD SYSTEM

BY OTHERS

FLANGED WINDOW

WINDOWINTEGRALFLASHING

STOREFRONT WINDOW

DRYVIT DRAINAGE STRIP™ ADHEREDWITH DABS OF DRYVIT AP ADHESIVE

NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OFDRYVIT AQUAFLASH SYSTEM.

Outsulation® Plus MD System®

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 17: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

OPMD 0.0.15

OUTSULATION PLUSMD SYSTEM

BY OTHERS

Head J-Track OptionOutsulation® Plus MD System®

EPS INSULATION

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT ADHESIVE INVERTICAL NOTCHED TROWELCONFIGURATION APPLIED TOBACK OF EPS

APPROVED SUBSTRATE

J-TRACK ATTACHED WITHDRYVIT AP ADHESIVE (SEE NOTE 2 AND 3)

SEALANT, BY OTHERS

DRYVIT AQUAFLASH® SYSTEMOR DRYVIT BACKSTOP® NT™TEXTURE OVER DRYVIT GRID

TAPE™ (SEE NOTE 4)

DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKER ROD,BY OTHERS

DRYVIT FINISH

DRYVIT REINFORCINGMESH EMBEDDED INDRYVIT BASE COAT

DRYVIT BASE COAT

3/4" (19 MM) MIN.

4. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

3/4" (19 MM)

6" (152 MM)

6" (152 MM)

NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD OR STANDARDPLUS MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.

2. LIGHTLY SAND SURFACE OF J-TRACK TOMAXIMIZE ADHESION.

3. LENGTH OF TRACK NOT TO EXCEED 10 FT.(3.O M)

DRYVIT DEMANDIT® ORCOLOR PRIME ON SURFACESTO RECEIVE SEALANT

DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 18: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

OPMD 0.0.16

Termination at Wood Framed DeckOutsulation® Plus MD System®NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

3. DETAIL DOES NOT APPLY TO CANTILEVEREDDECKS. CANTILEVERED DECKS REQUIRE JOBSPECIFIC FLASHING DETAILS.

2" (51 MM)MIN.

FLASHING NO. 2, BY OTHERS

FLASHING NO. 3, BY OTHERS

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

APPROVED SUBSTRATE

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS

1" (25 MM)MIN.

2-1/2"(64 MM)MIN.

DRYVIT COMPATIBLESEALANT, BY OTHERS

FLASHING NO. 1,BY OTHERS

DECK BOARD

END JOIST

DRYVIT DEMANDIT®OR COLOR PRIME™ON SURFACE(S) TORECEIVE SEALANT

2" (51 MM) MIN.

DRYVIT COMPATIBLESEALANT WITH BOND

BREAKER, BY OTHERS

DRYVIT DETAIL MESH® WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM)

DRYVIT DRAINAGE STRIP™ADHERED WITH DABS OFDRYVIT AP ADHESIVE

DRYVIT FINISH

DRYVIT AQUAFLASH® SYSTEM OVERCONTINUOUS FLASHING (NOTE 2)

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT BASE COAT

EPS INSULATION BOARD

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 19: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

Outsulation® Plus MD System® Termination at Waterproof Deck

OPMD 0.0.17

NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. ENSURE BOTTOM EDGE OF DRAINAGESTRIP IS LEFT FREE TO DRAIN.

DRYVIT ADHESIVE IN VERTICAL NOTCHEDTROWEL CONFIGURATION APPLIED TOBACK OF EPS

DRYVIT DETAIL MESH® WRAPPEDTO BACKSIDE OF EPS MIN. 2" (51 MM )

SLOPE CONCRETE DECK SURFACEAWAY FROM VERTICAL WALL

2" (51 MM)MIN.

DRYVIT FINISH

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT DRAINAGE STRIP™ADHERED WITH DABS OF DRYVITAP ADHESIVE (SEE NOTE 2)

EPS INSULATION BOARD

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT BASE COAT

COMPATIBLE WATERPROOF DECKCOATING, BY OTHERS

CANT STRIP, BY OTHERS

FRAMING BYOTHERS

APPROVEDSUBSTRATE

OUTSULATIONPLUS MD SYSTEM

BY OTHERS

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 20: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

Outsulation® Plus MD System® Preparation At Parapet/ Wall Intersection

OPMD 0.0.18

NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD OR STANDARDPLUS MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

APPROVED SUBSTRATE

FRAMING BY OTHERS

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

FLASHING SLEEVE,BY OTHERS

DRYVIT AQUAFLASH®SYSTEM (SEE NOTE 2)

8"(203 MM)

DRYVIT AQUAFLASH®SYSTEM (SEE NOTE 2)

STEP #1 STEP #2

STEP #3

6"(152 MM)

6"(152 MM)

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 21: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

Outsulation® Plus MD System® Termination At Parapet - Cap Flashing

ROOFASSEMBLY

OPMD 0.0.19

NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD OR STANDARDPLUS MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

EPS SHAPE OPTION(SEE NOTE 4)

EPS INSULATION BOARD

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)(SEE NOTE 3)

DRYVIT FINISH

ROOF ASSEMBLY, BY OTHERS

2 1/2" (64 MM) MIN.

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATION

APPLIED TO BACK OF EPS

FRAMING,BY OTHERS

DRYVIT AQUAFLASH®SYSTEM (SEE NOTE 2)

METAL CAP FLASHING,BY OTHERS

DRYVIT BASE COAT

APPROVED SUBSTRATE

DRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT BASE COAT

DRYVIT COMPATIBLE SEALANT,BY OTHERS

3. EDGE WRAPPING METHOD IS ACCEPTABLEIN LIEU OF BACK WRAPPING. DRYVITREINFORCING MESH MUST BE FULLYEMBEDDED IN DRYVIT BASE COAT AT EPSEDGE AND EXTEND ONTO SUBSTRATE 2"(51 MM) MIN.

4. MAXIMUM THICKNESS OF EPS BUILT OUTSHAPES SHALL NOT EXCEED 13" (330 MM) ATANY POINT MEASURED FROM THESUBSTRATE.

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 22: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

Outsulation® Plus MD System® Termination At Parapet - Solid Substrate

OPMD 0.0.20

NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD OR STANDARDPLUS MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

DRYVIT REINFORCINGMESH EMBEDDED INDRYVIT BASE COAT

DRYVIT BASE COAT

EPS INSULATIONBOARD

DRYVIT AQUAFLASH® SYSTEM (SEE NOTE 2)

APPROVEDSUBSTRATE

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT DETAIL MESH®WRAPPED TO BACKSIDE OF

EPS MIN. 2" (51 MM)

METAL CAP FLASHING,BY OTHERS

APPROVED SEALANT,BY OTHERS

DRYVIT FINISH

DRYVIT ADHESIVE INVERTICAL NOTCHED

TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS

DRYVIT COMPATIBLE SEALANTW/CLOSED CELL BACKER RODAND WEEP TUBES EVERY24" (610 MM) BY OTHERS

DRYVIT DRAINAGE STRIP™SET IN DABS OF DRYVIT AP

ADHESIVE

ROOF FLASHING AND COUNTERFLASHING, BY OTHERS

8"(203 MM)

MIN.

ROOF ASSEMBLY,BY OTHERS

DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACE(S) TO

RECEIVE SEALANT

3/4" (19 MM) MIN.

3. EDGE WRAPPING METHOD IS ACCEPTABLEIN LIEU OF BACK WRAPPING. DRYVITREINFORCING MESH MUST BE FULLYEMBEDDED IN DRYVIT BASE COAT AT EPSEDGE AND EXTEND ONTO SUBSTRATE 2"(51 MM) MIN.

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 23: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

2"(51 MM)

MIN.

OPMD 0.0.21

Termination at Sloped RoofOutsulation® Plus MD System®

3/4"(19 MM)

MIN.

110

100

ROOF DIVERTER(SEE NOTE 2)

12"(305 MM)

6"(152 MM)

6"(152 MM)

DRYVIT FINISH

NOTE:1. EXTEND DIVERTER FLASHING (KICKOUT)A MINIMUM OF 1" (25 MM) BEYOND FACEOF THE SYSTEM.

2. ROOF DIVERTER TO BE MADE FROMCORROSION RESISTANT MATERIAL MIN.24 GAGE WITH WATER TIGHT SEAMS.

3. EXTEND ROOFING UNDERLAYMENT5" (127 MM) UP VERTICAL WALL BEHINDMETAL FLASHING.

4. METAL FLASHINGS ARE 10" (254 MM) X2" (51 MM) LONGER THAN THE EXPOSEDPORTION OF THE ROOFING SHINGLE AND AREBENT IN HALF TO ALLOW FOR TWO 5" (127 MM)LEGS. ALTHOUGH NOT SHOWN, METALFLASHINGS ARE STEP FLASHED(INTERWOVEN) WITH ROOFING SHINGLES.

5. FOR ADDITIONAL SLOPED ROOF DETAILS,REFER TO DRYVIT PUBLICATION DS106.

6. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

DRYVIT AIR/WATER-RESISTIVE BARRIER COATINGDRYVIT ADHESIVE IN VERTICAL NOTCHED TROWELCONFIGURATION APPLIED TO BACK OF EPSEPS INSULATION BOARDDRYVIT BASE COAT

DRYVIT REINFORCING MESH EMBEDDED IN DRYVIT BASE COATDRYVIT AQUAFLASH® SYSTEM OVER FLASHING (SEE NOTE 6)DRYVIT DRAINAGE STRIP™ ADHERED WITHDABS OF DRYVIT AP ADHESIVEDRYVIT DETAIL MESH® WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)

ROOF STEP FLASHING, BY OTHERS (SEE NOTE 4)

ROOFING SHINGLES

ROOFING UNDERLAYMENT, BY OTHERS(SEE NOTE 3)

DRYVIT COMPATIBLE SEALANTWITH BOND BREAKER, BY OTHERS)

DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACE(S) TO RECEIVE SEALANT

GUTTER SYSTEM SLOPED AWAY FROM WALL

ROOF DIVERTER FLASHING, BY OTHERS(SEE NOTE 1 & 2)

FRAMING BYOTHERS

APPROVEDSUBSTRATE

OUTSULATION PLUS MD SYSTEM

BY OTHERS

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 24: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

2" (51 MM) MIN.

OPMD 0.0.22

Termination at Roof Stop Flashing

3/4"(19 MM)

MIN.

NOTE:1. EXTEND ROOF STOP FLASHING 1" (25 MM)MINIMUM BEYOND FACE OF THE SYSTEM.

2. ROOF STOP TO BE MADE FROM CORROSIONRESISTANT MATERIAL MIN. 24 GAGE WITHWATER TIGHT SEAMS.

3. EXTEND ROOFING UNDERLAYMENT5" (127 MM) UP VERTICAL WALL BEHINDMETAL FLASHING.

DRIP EDGE FLASHING, BY OTHERS

DRYVIT FINISH

DRYVIT REINFORCING MESH EMBEDDED IN DRYVIT BASE COAT

DRYVIT AQUAFLASH® SYSTEM OVER FLASHINGS (SEE NOTE 4)

FRAMING BY OTHERS

APPROVED SUBSTRATE

DRYVIT ADHESIVE IN VERTICAL NOTCHED TROWELCONFIGURATION APPLIED TO BACK OF EPS

EPS INSULATION BOARD

DRYVIT BASE COAT

DRYVIT AIR/WATER-RESISTIVE BARRIER COATING

DRYVIT DETAIL MESH® WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)

ROOF/WALL FLASHING, BY OTHERS

ROOFING, BY OTHERS

DRYVIT COMPATIBLE SEALANTWITH BOND BREAKER, BY OTHERS

DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACE(S) TO RECEIVE SEALANT

ROOF STOP FLASHING, BY OTHERS(SEE NOTE 2)

ROOFING UNDERLAYMENT, BY OTHERS(SEE NOTE 3)

DRYVIT DRAINAGE STRIP™ ADHERED WITHDABS OF DRYVIT AP ADHESIVE

Outsulation® Plus MD System®4. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

OUTSULATION PLUS MDSYSTEM

BY OTHERS

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 25: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

OPMD 0.0.23

Vertical Wall/ Suspended Soffit TransitionOutsulation® Plus MD System®NOTE:1. DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSED TOABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD OR STANDARD PLUS MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT.

3. DRYVIT AIR/WATER-RESISTIVE BARRIER ISREQUIRED OVER VERTICAL SUBSTRATES.APPLICATION OVER HORIZONTAL SOFFITSUBSTRATE IS OPTIONAL UNLESS REQUIRED ASPART OF A CONTINUOUS AIR BARRIER SYSTEM.

4. SEALANT JOINT IS REQUIRED FOR SUSPENDEDSOFFITS. OPTIONAL FOR RIGIDLY FRAMED.

3/4" (19 MM) MIN.

DRYVIT DETAIL MESH® WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM)

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT ADHESIVEAPPLIED TO BACK OF EPS

DRYVIT BASE COAT

EPS INSULATION BOARD

DRYVIT FINISH

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING (SEE NOTE 3)

APPROVED SUBSTRATE

FRAMING BY OTHERS

DRYVIT COMPATIBLE SEALANT WITHCLOSED CELL BACKER ROD, BY OTHERS(SEE NOTE 2 AND 4)

DRYVIT AQUAFLASH® SYSTEM

DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKER ROD,

BY OTHERS (SEE NOTE 2 AND 4)

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 26: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

OPMD 0.0.24

Transition At Soffit/ Fascia IntersectionOutsulation® Plus MD System®NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. ENSURE BOTTOM EDGE OF DRAINAGESTRIP IS LEFT FREE TO DRAIN.

3. DRYVIT AIR/WATER-RESISTIVE BARRIER ISREQUIRED OVER VERTICAL SUBSTRATES,APPLICATION OVER HORIZONTAL SOFFITSUBSTRATE IS OPTIONAL UNLESS REQUIRED ASPART OF A CONTINUOUS AIR BARRIER SYSTEM.

FRAMING BY OTHERS

APPROVED SUBSTRATE

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT BASE COAT

EPS INSULATION BOARD

DRYVIT FINISH

DRYVIT AIR/WATER-RESISTIVE BARRIERCOATING (SEE NOTE 3)

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS

DRYVIT FINISH

DRYVIT ADHESIVEAPPLIED TO BACK

OF EPS

DRYVIT DRAINAGE STRIP™ADHERED WITH DABS OF DRYVIT

AP ADHESIVE (SEE NOTE 2)

DRYVIT DETAIL MESH® WRAPPEDTO BACKSIDE OF EPS MIN. 2" (51 MM)

DRYVIT BACKSTOP® NT™-TEXTUREOVER DRYVIT GRID TAPE™

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 27: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

OPMD 0.0.25

Outsulation® Plus MD System® Fascia/ Uninsulated Soffit Transition

NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. SOFFITS WITHOUT EPS INSULATIONREQUIRE EXPANSION JOINTS EVERY20 FT (6 M).

3. REFER TO DRYVIT PUBLICATION DS 173 FORSPECIFIC REQUIREMENTS FOR SOFFIT AREAS.

4. BOTTOM EDGE OF DRYVIT DRAINAGE STRIPSHALL BE MASKED DURING INSTALLATION TOPREVENT CLOGGING OF DRAINAGE CHANNELS.

DRYVIT DRAINAGE STRIP™ADHERED WITH DABS OF DRYVITAP ADHESIVE (SEE NOTE 4)

DRYVIT BACKSTOP® NT-TEXTURE™OVER DRYVIT GRID TAPE™

FRAMING BY OTHERS

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS

DRYVIT BASE COAT

EPS INSULATION BOARD

DRYVIT DETAIL MESH® WRAPPEDTO BACKSIDE OF EPS MIN. 2" (51 MM)

DRYVIT FINISH

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

APPROVED SUBSTRATE

1" (25 MM) MAX.

CASING BEAD, BY OTHERS

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 28: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

OPMD 0.0.26

Termination at Uninsulated Soffit VentOutsulation® Plus MD System®

FRAMING, BY OTHERS

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

APPROVED SUBSTRATE

DRYVIT FINISH

NOTE:1. CONTROL JOINTS ARE RECOMMENDEDEVERY 20 FT (6.1 M).

2. REFER TO DRYVIT PUBLICATION DS173FOR SPECIFIC REQUIREMENTS FORSOFFIT AREAS.

3. SEAL ALL BUTT JOINTS,INTERSECTIONS, AND ENDS OF VENTSWITH COMPATIBLE SEALANT.

4. SEE DRYVIT PUBLICATION DS842 FORADDITIONAL DIRECT APPLIED DETAILS.

DRYVIT BASE COAT

DRYVIT BASE COAT

SOFFIT VENT, BY OTHERS

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 29: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

BY OTHERS

Outsulation® Plus MD System®

OPMD 0.0.27

Horizontal Slip Joint without WeepsNOTE:1. DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSED TOABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD OR STANDARD PLUS MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. LOCATE EXTERNAL SEALANT JOINT WITHIN2" (51 MM) OF BREAK IN SHEATHING.

3. EXPANSION JOINT IN THE OUTSULATIONPLUS MD SYSTEM IS NECESSARY WHERESIGNIFICANT DIFFERENTIAL MOVEMENT ISEXPECTED AT FLOOR LINES.

4. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHING TAPE™MAY BE USED IN LIEU OF DRYVIT AQUAFLASHSYSTEM OVER PREPARED JOINT.

5. SEALANT SHOULD NOT BE IN DIRECT CONTACTWITH ASPHALTIC ADHESIVE ON DRYVIT FLASHINGTAPE. COVER DRYVIT FLASHING TAPE LAPS WITHPOLYETHYLENE TAPE OR BACKER ROD.

6. FOR STEEL FRAMED CONSTRUCTION:EXPANSION JOINT IS INTENDED TOACCOMMODATE MOVEMENT AT SLIIPCONNECTION. FOR WOOD FRAMEDCONSTRUCTION: EXPANSION JOINT IS INTENDEDTO ACCOMMODATE CROSS GRAIN SHRINKAGEFOR FLOOR BEAMS.

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

APPROVED SUBSTRATE

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATION

APPLIED TO BACK OF EPS

DRYVIT DETAIL MESH®WRAPPED TO BACKSIDE OFEPS MIN. 2" (51 MM)

CLOSED CELL BACKERROD, BY OTHERS

(SEE NOTE 2)

DRYVIT AQUAFLASH®SYSTEM (SEE NOTE 4)

SLIP TYPECONNECTION(SEE NOTE 6)

3/4" (19 MM) MIN.

OUTSULATIONPLUS MD SYSTEM

DRYVIT BASE COAT

DRYVIT REINFORCINGMESH EMBEDDED INDRYVIT BASE COAT

DRYVIT FINISH

DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)

EPS INSULATION BOARD

SLOPE SURFACEOUTSIDE OF SEALANT 1:5MIN. OUTWARD TO DRAIN

DRYVIT COMPATIBLESEALANT WITH CLOSEDCELL BACKER ROD, BYOTHERS (SEE NOTE 5)

DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT

DRYVIT DRAINAGE STRIP™ ADHEREDWITH DABS OF DRYVIT AP ADHESIVEALONG TOP OF STRIP ONLY

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 30: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

Outsulation® Plus MD System®

OPMD 0.0.28

Horizontal Slip Joint with Weeps

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

APPROVED SUBSTRATE

DRYVIT AQUAFLASH SYSTEM(SEE NOTE 4 AND 5)

CLOSED CELL BACKERROD, BY OTHERS

(SEE NOTE 3) DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATION

APPLIED TO BACK OF EPS

WEEPS AT 2'-0" O.C., BY OTHERS

NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. EXPANSION JOINT IN THE OUTSULATIONPLUS MD SYSTEM IS NECESSARY WHERESIGNIFICANT DIFFERENTIAL MOVEMENT ISEXPECTED AT FLOOR LINES.

3. LOCATE EXTERNAL SEALANT JOINTWITHIN 2" (51 MM) OF BREAK IN SHEATHING.

4. STOP AQUAFLASH SHORT OF SEALANTBOND LINE.

5. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

6. FOR STEEL FRAMED CONSTRUCTION:EXPANSION JOINT IS INTENDED TOACCOMMODATE MOVEMENT AT SLIIPCONNECTION. FOR WOOD FRAMEDCONSTRUCTION: EXPANSION JOINT ISINTENDED TO ACCOMMODATE CROSSGRAIN SHRINKAGE FOR FLOOR BEAMS.

SLIP TYPECONNECTION(SEE NOTE 6)

SLOPE SURFACE 1:5 MIN.OUTWARD TO DRAIN

OUTSULATIONPLUS MDSYSTEM

BY OTHERS

DRYVIT DETAIL MESH®WRAPPED TO BACKSIDE

OF EPS MIN. 2" (51 MM) DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT BASE COAT

DRYVIT REINFORCINGMESH EMBEDDED INDRYVIT BASE COAT

EPS INSULATION BOARD

DRYVIT FINISH

DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)

3/4" (19 MM) MIN.

DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKERROD, BY OTHERS (SEE NOTE 3)

DRYVIT AQUAFLASH®SYSTEM (SEE NOTE 5)

DRYVIT DRAINAGE STRIP™ ADHERED WITH DABS OFDRYVIT AP ADHESIVE ALONG TOP OF STRIP ONLY

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 31: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

OUTSULATION PLUSMD SYSTEM

BY OTHERS

Outsulation® Plus MD System®

OPMD 0.0.29

Horizontal Joint - Substrate ChangeNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD OR STANDARDPLUS MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM OVER PREPAREDJOINT AT CHANGE IN SUBSTRATE.

3. SEALANT SHALL NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVE ONDRYVIT FLASHING TAPE. COVER DRYVITFLASHING TAPE LAPS WITH POLYETHYLENETAPE OR BACKER ROD.

4. REFER TO DETAIL OPMD 0.0.28 FORCONFIGURATION REQUIRING WEEPS.

3/4" (19 MM ) MIN.

4

DRYVIT DRAINAGE STRIP™™ADHERED WITH DABS OFDRYVIT AP ADHESIVE ALONGTOP OF STRIP ONLY

DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACES TORECEIVE SEALANT

DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKERROD, BY OTHERS (SEE NOTE 3)

SLOPE SURFACE OUTSIDE OFSEALANT 1:5 MIN. OUTWARDTO DRAIN

DRYVIT FINISH

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT BASE COAT

DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)

EPS INSULATION BOARD

FRAMING

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT ADHESIVE IN VERTICAL NOTCHEDTROWEL CONFIGURATION APPLIED TO

BACK OF EPS

APPROVED SUBSTRATE

DRYVIT BACKSTOP® NT™-TEXTUREOVER GRID TAPE™

DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 2)

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 32: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

Outsulation® Plus MD System®

OPMD 0.0.30

Horizontal Termination at Stone VeneerNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OF HIGHIMPACT ZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

3. FOR INSTALLATION OF DRYVITAIR/WATER-RESISTIVE BARRIER COATINGBENEATH CLADDINGS OTHER THAN DRYVITEIFS, REFER TO DRYVIT PUBLICATION DS840.

CONTINUOUS FLASHING,BY OTHERS

SEALANT WITH BOND BREAKER,BY OTHERS

FRAMING BY OTHERS

DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 2)

APPROVED SUBSTRATE

PAPER BACKED EXPANDED METAL LATHOR OTHER SLIP SHEET, BY OTHERS

DRYVIT DRAINAGE STRIP™™ADHERED WITH DABS OFDRYVIT AP ADHESIVE

DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACE(S) TORECEIVE SEALANT

DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKERROD AND WEEP TUBES EVERY24" (610 MM). BY OTHERS

STONE VENEER SYSTEM,BY OTHERS

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWELCONFIGURATION APPLIED TOBACK OF EPS

DRYVIT FINISH

DRYVIT BASE COAT

DRYVIT REINFORCINGMESH EMBEDDED INDRYVIT BASE COAT

DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)

EPS INSULATION BOARD

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING EXTENDEDBEHIND FLASHING (SEE NOTE 3)

3/4" (19 MM) MIN.

OUTSULATIONPLUS MD SYSTEM

BY OTHERS

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 33: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

Outsulation® Plus MD System®

OPMD 0.0.31

Horizontal Termination at StuccoNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OF HIGHIMPACT ZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

3. FOR INSTALLATION OF DRYVITAIR/WATER-RESISTIVE BARRIERCOATING BENEATH CLADDINGS OTHERTHAN DRYVIT EIFS, REFER TO DRYVITPUBLICATION DS840.

DRYVIT DRAINAGE STRIP™ADHERED WITH DABS OFDRYVIT AP ADHESIVE

DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACE(S) TORECEIVE SEALANT

DRYVIT FINISHDRYVIT BASE COAT

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)

DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKER RODAND WEEP TUBES EVERY24" (610 MM), BY OTHERS

CONTINUOUS FLASHING,BY OTHERS

FRAMING BY OTHERS

DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 2)

APPROVED SUBSTRATE

SEALANT WITH BOND BREAKER,BY OTHERS

CEMENT PLASTER,BY OTHERS

PAPER BACKED EXPANDED METAL LATHOR OTHER SLIP SHEET, BY OTHERS

3/4" (19 MM) MIN.

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWELCONFIGURATION APPLIED TOBACK OF EPSEPS INSULATION BOARD

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING EXTENDEDBEHIND FLASHING (SEE NOTE 3)

OUTSULATIONPLUS MD SYSTEM

BY OTHERS

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 34: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

Outsulation® Plus MD System®

OPMD 0.0.32

Horizontal Termination at Wood Siding

FRAMING BY OTHERS

DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 2)

APPROVED SUBSTRATE

SEALANT WITH BOND BREAKER,BY OTHERS

LAP SIDING, BY OTHERS

DRYVIT COMPATIBLE SEALANTWITH CLOSED CELL BACKERROD AND WEEP TUBES EVERY24" (610 MM). BY OTHERS

CONTINUOUS FLASHING,BY OTHERS

DRYVIT DRAINAGE STRIP™ADHERED WITH DABS OFDRYVIT AP ADHESIVE

DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACE(S) TORECEIVE SEALANT

3/4" (19 MM) MIN.

NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARDOR STANDARD PLUS MESH. LOCATIONOF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

3. FOR INSTALLATION OF DRYVITAIR/WATER-RESISTIVE BARRIER COATINGBENEATH CLADDINGS OTHER THAN DRYVITEIFS, REFER TO DRYVIT PUBLICATION DS840.

DRYVIT FINISH

DRYVIT BASE COAT

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWELCONFIGURATION APPLIED TOBACK OF EPSEPS INSULATION BOARD

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING EXTENDEDBEHIND FLASHING (SEE NOTE 3)

OUTSULATIONPLUS MD SYSTEM

BY OTHERS

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 35: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

OPMD 0.0.33

Outsulation® Plus MD System® Vertical Expansion Joint - EIFS

3/4" (19 MM) MIN.

NOTE:1. DRYVIT RECOMMENDS THAT GROUND FLOORAPPLICATIONS AND ALL FACADES EXPOSED TOABNORMAL STRESS, HIGH TRAFFIC, ORDELIBERATE IMPACT HAVE THE BASE COATREINFORCED WITH PANZER® MESH PRIOR TOSTANDARD OR STANDARD PLUS MESH.LOCATION OF HIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. EIFS EXPANSION JOINTS ARE REQUIRED INCONTINUOUS ELEVATIONS AT INTERVALS NOTEXCEEDING 75 FT (23 M).

3

DRYVIT BASE COAT

DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)

DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACES TORECEIVE SEALANT

DRYVIT FINISH

DRYVIT COMPATIBLESEALANT WITH CLOSED CELLBACKER ROD, BY OTHERS

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

FRAMING BY OTHERS

APPROVED SUBSTRATE

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWELCONFIGURATION APPLIED TOBACK OF EPSEPS INSULATION BOARD

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING EXTENDEDBEHIND FLASHING (SEE NOTE 3)

OUTSULATIONPLUS MD SYSTEM

BY OTHERS

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 36: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

OPMD 0.0.34

Outsulation® Plus MD System® Through-Wall Expansion Joint

NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

3. SEALANT SHALL NOT BE IN DIRECT CONTACTWITH ASPHALTIC ADHESIVE ON DRYVITFLASHING TAPE. COVER DRYVIT FLASHINGTAPE LAPS WITH POLYETHYLENE TAPE ORBACKER ROD.

4. LOCATE EXTERNAL SEALANT JOINT WITHIN2" (51 MM) OF SUBSTRATE JOINT.

DRYVIT DEMANDIT® OR COLOR PRIME™ON SURFACES TO RECEIVE SEALANT

DRYVIT FINISH

DRYVIT COMPATIBLE SEALANT WITH CLOSEDCELL BACKER ROD, BY OTHERS (SEE NOTE 3)

FRAMING BY OTHERS

DRYVIT AIR/WATER-RESISTIVE BARRIER COATING

APPROVED SUBSTRATE

DRYVIT ADHESIVE IN VERTICAL NOTCHED TROWELCONFIGURATION APPLIED TO BACK OF EPS

DRYVIT BASE COAT

DRYVIT DETAIL MESH® WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM )

EPS INSULATION BOARD

DRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT BASE COAT

DRYVIT AIR/WATER-RESISTIVE BARRIER COATING

DRYVIT ADHESIVE IN VERTICAL NOTCHED TROWELCONFIGURATION APPLIED TO BACK OF EPS

OPTIONAL SECONDARY SEAL, BY OTHERS

DRYVIT DEMANDIT OR COLOR PRIME ONSURFACES TO RECEIVE SEALANT

DRYVIT COMPATIBLE SEALANT WITH CLOSEDCELL BACKER ROD, BY OTHERS (SEE NOTE 3)

DRYVIT DETAIL MESH WRAPPED TOBACKSIDE OF EPS MIN. 2" (51 MM)

DRYVIT AQUAFLASH SYSTEM (SEE NOTE 2)

OPTIONAL SECONDARY SEAL, BY OTHERS

CLOSED CELL BACKER ROD, BY OTHERS (SEE NOTE 4)

DRYVIT AQUAFLASH® SYSTEM (SEE NOTE 2)

3/4" (19 MM) MIN.

3/4" (19 MM ) MIN.

FRAMING BY OTHERS

APPROVED SUBSTRATE

DRYVIT FINISH

DRYVIT BASE COAT

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

EPS INSULATION BOARD

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 37: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

OPMD 0.0.35

Outsulation® Plus MD System® Vertical Expansion Joint - Flush Option

3/4" (19 MM) MIN.

NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

3. SEALANT SHALL NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVE ONDRYVIT FLASHING TAPE. COVER DRYVITFLASHING TAPE LAPS WITH POLYETHYLENETAPE OR BACKER ROD.

DRYVIT AQUAFLASH®SYSTEM (SEE NOTE 2)

FRAMING BY OTHERS

APPROVED SUBSTRATE

DRYVIT BASE COAT

DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)

DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACES TORECEIVE SEALANT

DRYVIT FINISH

DRYVIT COMPATIBLESEALANT WITH CLOSED CELLBACKER ROD, BY OTHERS(SEE NOTE 3)

DRYVIT BACKSTOP® NT™-TEXTURE OVER DRYVIT

GRID TAPE™ DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT ADHESIVE INVERTICAL NOTCHED TROWELCONFIGURATION APPLIED TOBACK OF EPS

EPS INSULATION BOARD

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 38: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

OPMD 0.0.36

Outsulation® Plus MD System® Vertical Expansion Joint - Recessed Option

3/4" (19 MM) MIN.

NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OF HIGHIMPACT ZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

3. SEALANT SHALL NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVE ONDRYVIT FLASHING TAPE. COVER DRYVITFLASHING TAPE LAPS WITH POLYETHYLENETAPE OR BACKER ROD.

DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 2)

FRAMING BY OTHERS

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

APPROVED SUBSTRATE

DRYVIT ADHESIVE INVERTICAL NOTCHED TROWELCONFIGURATION APPLIED TOBACK OF EPS

DRYVIT BASE COAT

DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)

EPS INSULATION BOARD

DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACES TORECEIVE SEALANT

DRYVIT FINISH

DRYVIT COMPATIBLESEALANT WITH CLOSED CELLBACKER ROD, BY OTHERS(SEE NOTE 3)

DRYVIT BACKSTOP® NT™-TEXTURE OVER DRYVIT

GRID TAPE™

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 39: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

OPMD 0.0.37

Outsulation® Plus MD System®

3/4" (19 MM) MIN.

Vertical Expansion Joint - Double Seal Option

REAR SEAL

FACE SEAL

VENT

NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD OR STANDARDPLUS MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

3. SEALANT SHALL NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVE ONDRYVIT FLASHING TAPE. COVER DRYVITFLASHING TAPE LAPS WITH POLYETHYLENETAPE OR BACKER ROD.

APPROVED SUBSTRATE

DRYVIT BASE COAT

DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)

DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACES TORECEIVE SEALANT

DRYVIT FINISH

DRYVIT COMPATIBLESEALANT WITH CLOSED CELLBACKER ROD, BY OTHERS(SEE NOTE 3)

REAR SEAL

FACE SEAL

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT ADHESIVE INVERTICAL NOTCHED TROWELCONFIGURATION APPLIED TOBACK OF EPS

EPS INSULATION BOARD

VENT

DRYVIT AQUAFLASH®SYSTEM (SEE NOTE 2)

FRAMING BY OTHERS

DRYVIT BACKSTOP® NT™-TEXTURE OVER DRYVIT

GRID TAPE™

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 40: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

OPMD 0.0.38

Outsulation® Plus MD System®

3/4" (19 MM) MIN.

Vertical Termination At Stone Veneer

NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. FOR INSTALLATION OF DRYVITAIR/WATER-RESISTIVE BARRIER COATINGBENEATH CLADDINGS OTHER THANDRYVIT EIFS, REFER TO DRYVITPUBLICATION DS840.

FRAMING BY OTHERS

APPROVED SUBSTRATE

DRYVIT BASE COAT

DRYVIT DETAIL MESH®WRAPPED TO BACKSIDEOF EPS MIN. 2" (51 MM)

DRYVIT DEMANDIT® OR COLORPRIME™ ON SURFACES TORECEIVE SEALANT

DRYVIT FINISH

DRYVIT COMPATIBLESEALANT WITH CLOSED CELLBACKER ROD, BY OTHERS

BEDDING COAT AND STONEVENEER SYSTEM, BY OTHERS

DRYVIT REINFORCING MESHEMBEDDED IN BASE COAT

PAPER BACKED EXPANDEDMETAL LATH, BY OTHERS

ANGLE STOP FOR STONEVENEER SYSTEM, BY OTHERS

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWELCONFIGURATION APPLIED TOBACK OF EPSEPS INSULATION BOARD

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING EXTENDEDBEHIND ANGLE STOP (SEE NOTE 2)

OUTSULATIONPLUS MD SYSTEM

BY OTHERS

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 41: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

Outsulation® Plus MD System®

OPMD 0.0.39

PenetrationsNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. DRYVIT FLASHING TAPE SURFACECONDITIONER™ AND DRYVIT FLASHINGTAPE™ MAY BE USED IN LIEU OF DRYVITAQUAFLASH SYSTEM.

3. SEALANT SHALL NOT BE IN DIRECTCONTACT WITH ASPHALTIC ADHESIVE ONDRYVIT FLASHING TAPE. COVER DRYVITFLASHING TAPE LAPS WITH POLYETHYLENETAPE OR BACKER ROD.

3/4" (19 MM) MIN.

EPS INSULATION BOARD

APPROVED SUBSTRATE

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT BASE COAT

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT FINISH

DRYVIT ADHESIVE IN VERTICAL NOTCHEDTROWEL CONFIGURATION APPLIED TOBACK OF EPS

OPTIONAL SECONDARY SEAL, BY OTHERS

FRAMING BY OTHERS

DRYVIT COMPATIBLE SEALANT WITHCLOSED CELL BACKER ROD, BY OTHERS(SEE NOTE 3)

DRYVIT DEMANDIT OR COLOR PRIMEON SURFACES TO RECEIVE SEALANT

DRYVIT DETAIL MESH® WRAPPEDTO BACKSIDE OF EPS MIN. 2"(51 MM)

DRYVIT AQUAFLASH® SYSTEM(SEE NOTE 2)

OUTSULATION PLUS MDSYSTEM

BY OTHERS

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 42: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

OPMD 0.0.40

Sign AttachmentOutsulation® Plus MD System®NOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVE THEBASE COAT REINFORCED WITH PANZER®MESH PRIOR TO STANDARD OR STANDARDPLUS MESH. LOCATION OF HIGH IMPACTZONES SHOULD BE INDICATED ONCONTRACT DRAWINGS.

2. PERIMETER OF PIPE SLEEVE IS SEALED TOPREVENT WATER ENTRY INTO WALL.

1/2" (12.7 MM) MIN.

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT BASE COAT

DRYVIT FINISH

SCREW/BOLT ATTACHMENT TO BUILDINGFRAMING/BLOCKING, BY OTHERS

NEOPRENE WASHER, BY OTHERS

SIGN FIXTURE, BY OTHERS

DRYVIT COMPATIBLE SEALANT AND BONDBREAKER TAPE, BY OTHERS (SEE NOTE 2)

NON-CORROSIVE PIPE SLEEVE, BYOTHERS, SET IN SEALANT

BLOCKING, SECURED TO FRAMING

FRAMING BY OTHERS

APPROVED SUBSTRATE

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS

EPS INSULATION BOARD

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

OUTSULATIONPLUS MD SYSTEM

BY OTHERS

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc. Issued: 10/2016

Page 43: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

Outsulation® Plus MD System®

OPMD 0.0.41

Aesthetic RevealsNOTE:1. DRYVIT RECOMMENDS THAT GROUNDFLOOR APPLICATIONS AND ALL FACADESEXPOSED TO ABNORMAL STRESS, HIGHTRAFFIC, OR DELIBERATE IMPACT HAVETHE BASE COAT REINFORCED WITHPANZER® MESH PRIOR TO STANDARD ORSTANDARD PLUS MESH. LOCATION OFHIGH IMPACT ZONES SHOULD BEINDICATED ON CONTRACT DRAWINGS.

2. SLOPE BOTTOM EDGE OF REVEAL FORPOSITIVE DRAINAGE.

EPS INSULATION BOARD

DRYVIT BASE COAT

DRYVIT REINFORCING MESH EMBEDDEDIN DRYVIT BASE COAT

DRYVIT FINISH

3/4" (19 MM) MIN.

DRYVIT DETAIL MESH® EMBEDDED IN DRYVIT BASECOAT. OVERLAP REINFORCING MESH 2 1/2" (64 MM)

DRYVIT BASE COAT

2 1/2" (64 MM)

2 1/2" (64 MM)

DRYVIT DETAIL MESH® OVERLAPED 2 1/2" (64 MM)

DRYVIT AIR/WATER-RESISTIVE BARRIER COATINGDRYVIT ADHESIVE IN VERTICAL NOTCHED TROWELCONFIGURATION APPLIED TO BACK OF EPS

OUTSULATION PLUS MDSYSTEM

BY OTHERSFRAMING BY OTHERS

APPROVED SUBSTRATE

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 44: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

Outsulation® Plus MD System®

OPMD 0.0.42

Recessed Graphics

EPS INSULATION BOARD

APPROVED SUBSTRATE

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT BASE COAT

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT FINISH

FRAMING BY OTHERS

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATION

APPLIED TO BACK OF EPS

DRYVIT BASE COAT

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT FINISH

BY OTHERS

3/4" (19 MM) MIN.OUTSULATION

PLUS MD SYSTEM

OVERLAP 2 1/2" (64 MM)

EPS INSULATION BOARD

APPROVED SUBSTRATE

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATION

APPLIED TO BACK OF EPS

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

SLOPE GRAPHIC FORPOSITIVE DRAINAGE

BY OTHERS

OUTSULATION PLUSMD SYSTEM

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 45: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

Outsulation® Plus MD System®

OPMD 0.0.43

Projecting GraphicsNOTE:1. MAXIMUM THICKNESS OF EPS BUILTOUT SHAPES SHALL NOT EXCEED13 INCHES (330 MM) AT ANY POINTMEASURED FROM THE SUBSTRATE.

BY OTHERS

OUTSULATION PLUS MDSYSTEM

OVERLAP MESH2 1/2"(64 MM )

SLOPE GRAPHIC FORPOSITIVE DRAINAGE

EPS INSULATION BOARD

APPROVED SUBSTRATE

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT BASE COAT

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT FINISH

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATIONAPPLIED TO BACK OF EPS

DRYVIT ADHESIVE

EPS INSULATION BOARD

APPROVED SUBSTRATE

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT BASE COAT

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT FINISH

FRAMING BY OTHERS

DRYVIT ADHESIVE IN VERTICALNOTCHED TROWEL CONFIGURATION

APPLIED TO BACK OF EPS

EPS SHAPE (SEE NOTE 1)

OUTSULATION PLUSMD SYSTEM

BY OTHERS

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.

Dryvit Systems, Inc.Issued: 10/2016

Page 46: Outsulation Plus MD System Installation Details - Dryvit · Outsulation Plus MD System Installation Details . NOTE DETAIL TABLE OF CONTENTS DETAIL OUTSULATION PLUS MD SYSTEM OPMD

OPMD 0.0.44

EPS Shapes

BYOTHERS

OUTSULATION PLUS MDSYSTEM

OVERLAP MESH2 1/2" (64 MM) MIN.

DRYVIT ADHESIVE APPLIED TO BACKOF EPS SHAPE

EPS SHAPE MEETING DRYVITSPECIFICATION DS131 (SEE NOTE 1)

FRAMING BY OTHERS

DRYVIT ADHESIVE APPLIED IN VERTICALNOTCHED TROWEL CONFIGURATION TO BACK OF

INSULATION BOARD

EPS INSULATION BOARD

APPROVED SUBSTRATE

DRYVIT AIR/WATER-RESISTIVEBARRIER COATING

DRYVIT BASE COAT

DRYVIT REINFORCING MESHEMBEDDED IN DRYVIT BASE COAT

DRYVIT DETAIL MESH OVERLAPONTO EXISTING TO BEFEATHERED OUT FLAT PRIOR TOFINISH APPLICATION

NOTES:1. MAXIMUM THICKNESS OF EPS BUILT OUTSHAPES SHALL NOT EXCEED 13" (330 MM)AT ANY POINT MEASURED FROM THESUBSTRATE.

DRYVIT FINISH

SLOPE SURFACE 6:12MIN. FOR POSITIVEDRAINAGE. MAXIMUMLENGTH OF SLOPEDSURFACE IS 12" (305 MM)

Outsulation® Plus MD System®

OUTSULATION PLUSMD SYSTEM

BY OTHERS

©

The architecture, engineering, and design of the project using theDryvit products is the responsibility of the project's designprofessional. All systems must comply with local building codes andstandards. This detail is for general information and guidance onlyand Dryvit specifically disclaims any liability for the use of this detailand for the architecture, design, engineering or workmanship of anyproject. The project design professional determines, in its solediscretion, whether this detail or a functionally equivalent detail isbest suited for the project. Use of a functionally equivalent detail doesnot violate Dryvit's warranty. This detail is subject to change withoutnotice. Contact Dryvit to ensure you have the most recent version.