optimization on indoor air diffusion of floor-standing type room air-conditioners

12
Optimization on indoor air diffusion of floor-standing type room air-conditioners Weiwei Liu, Zhiwei Lian * , Ye Yao Institute of Refrigeration and Cryogenics, Shanghai Jiao Tong University, Shanghai 200240, China Received 24 November 2006; received in revised form 25 December 2006; accepted 14 January 2007 Abstract The indoor air diffusion of a typical office equipped with a floor-standing type air-conditioner (FSAC) in summer was evaluated and optimized. Two existing evaluation indexes, the air diffusion performance index and the energy utilization coefficient, were modified for their more reasonable application in the evaluation on air diffusion performance of a FSAC. And also, a new index, fast cooling effect index, was presented to evaluate the fast-cooling effect. Based on the indoor airflow simulation using computational fluid dynamics, the three indexes were applied to evaluate the air diffusion performance of the FSAC. As a result, the optimal indoor air diffusion types with best thermal feelings, fine energy utilization efficiency and excellent fast-cooling effect were obtained, and also, a control scheme was suggested. # 2007 Elsevier B.V. All rights reserved. Keywords: Thermal comfort; Energy utilization efficiency; Air diffusion; Room air-conditioner; Computational fluid dynamics 1. Introduction Currently, more and more room air-conditioners are being used in residential apartments, offices and even some super- marts. They operate during several months of hot weather in a year. In this period, most of a person’s time is spent indoors. People, therefore, expect the indoor environment to be as comfortable as possible. Effective indoor air diffusion is essential to good thermal comfort as well as minimum energy use [1]. So far, a large amount of studies have been done for air diffusion and thermal comfort in occupied spaces [2–7]. However, among these studies, relatively little was devoted to room air-conditioners. Considering the wide using, it is significant to study air diffusion performance of room air-conditioners for a desirable indoor environment. In Ref. [7], for three positions of a window-type air-condi- tioner (one type of room air-conditioner), the performance of different air distribution types was determined and compared. A floor-standing type air-conditioner (FSAC) is also a main type of room air-conditioner, which is shown in Fig. 1. However, compared with a window-type air-conditioner, a FSAC has different configuration and operating characteristics. Therefore, the research conclusions on air diffusion of window-type air- conditioners cannot be applied to a FSAC. In the present work, air diffusion performance of a FSAC was studied. Different kinds of indoor air diffusion types can be obtained by changing directions of air outflow from the outlet (adjust the movable guide vanes in the outlet). That means different inclination angles of the vanes conduce different air diffusion types. Thus, the purpose of this study is to determine the optimal indoor air diffusion type with the maximum benefit in terms of indoor thermal comfort and energy utilization, by evaluating air diffusion performance of a FSAC. 2. Floor-standing type air-conditioner A FSAC consists of two units. One (outdoor unit) is installed outside the building, which mainly comprises a compressor, a condenser and a fan. Another (indoor unit) is placed in the occupied space. It contains an evaporator, a fan, an air outlet and one (or two) inlet. The two units are connected by copper tubes. www.elsevier.com/locate/enbuild Energy and Buildings 40 (2008) 59–70 Abbreviations: ADPI, air diffusion performance index; CFD, computa- tional fluid dynamics; EUC, energy utilization coefficient; FCEI, fast cooling effect index; FSAC, floor-standing type air-conditioner; SIMPLEC, semi- implicit method for pressure-linked equations consistent * Corresponding author. Tel.: +86 21 34204263; fax: +86 21 34206814. E-mail address: [email protected] (Z. Lian). 0378-7788/$ – see front matter # 2007 Elsevier B.V. All rights reserved. doi:10.1016/j.enbuild.2007.01.010

Upload: weiwei-liu

Post on 26-Jun-2016

225 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Optimization on indoor air diffusion of floor-standing type room air-conditioners

www.elsevier.com/locate/enbuild

Energy and Buildings 40 (2008) 59–70

Optimization on indoor air diffusion of floor-standing

type room air-conditioners

Weiwei Liu, Zhiwei Lian *, Ye Yao

Institute of Refrigeration and Cryogenics, Shanghai Jiao Tong University, Shanghai 200240, China

Received 24 November 2006; received in revised form 25 December 2006; accepted 14 January 2007

Abstract

The indoor air diffusion of a typical office equipped with a floor-standing type air-conditioner (FSAC) in summer was evaluated and optimized.

Two existing evaluation indexes, the air diffusion performance index and the energy utilization coefficient, were modified for their more reasonable

application in the evaluation on air diffusion performance of a FSAC. And also, a new index, fast cooling effect index, was presented to evaluate the

fast-cooling effect. Based on the indoor airflow simulation using computational fluid dynamics, the three indexes were applied to evaluate the air

diffusion performance of the FSAC. As a result, the optimal indoor air diffusion types with best thermal feelings, fine energy utilization efficiency

and excellent fast-cooling effect were obtained, and also, a control scheme was suggested.

# 2007 Elsevier B.V. All rights reserved.

Keywords: Thermal comfort; Energy utilization efficiency; Air diffusion; Room air-conditioner; Computational fluid dynamics

1. Introduction

Currently, more and more room air-conditioners are being

used in residential apartments, offices and even some super-

marts. They operate during several months of hot weather in a

year. In this period, most of a person’s time is spent indoors.

People, therefore, expect the indoor environment to be as

comfortable as possible.

Effective indoor air diffusion is essential to good thermal

comfort as well as minimum energy use [1]. So far, a large

amount of studies have been done for air diffusion and thermal

comfort in occupied spaces [2–7]. However, among these

studies, relatively little was devoted to room air-conditioners.

Considering the wide using, it is significant to study air

diffusion performance of room air-conditioners for a desirable

indoor environment.

In Ref. [7], for three positions of a window-type air-condi-

tioner (one type of room air-conditioner), the performance of

Abbreviations: ADPI, air diffusion performance index; CFD, computa-

tional fluid dynamics; EUC, energy utilization coefficient; FCEI, fast cooling

effect index; FSAC, floor-standing type air-conditioner; SIMPLEC, semi-

implicit method for pressure-linked equations consistent

* Corresponding author. Tel.: +86 21 34204263; fax: +86 21 34206814.

E-mail address: [email protected] (Z. Lian).

0378-7788/$ – see front matter # 2007 Elsevier B.V. All rights reserved.

doi:10.1016/j.enbuild.2007.01.010

different air distribution types was determined and compared. A

floor-standing type air-conditioner (FSAC) is also a main type

of room air-conditioner, which is shown in Fig. 1. However,

compared with a window-type air-conditioner, a FSAC has

different configuration and operating characteristics. Therefore,

the research conclusions on air diffusion of window-type air-

conditioners cannot be applied to a FSAC.

In the present work, air diffusion performance of a FSAC

was studied. Different kinds of indoor air diffusion types can be

obtained by changing directions of air outflow from the outlet

(adjust the movable guide vanes in the outlet). That means

different inclination angles of the vanes conduce different air

diffusion types. Thus, the purpose of this study is to determine

the optimal indoor air diffusion type with the maximum benefit

in terms of indoor thermal comfort and energy utilization, by

evaluating air diffusion performance of a FSAC.

2. Floor-standing type air-conditioner

A FSAC consists of two units. One (outdoor unit) is installed

outside the building, which mainly comprises a compressor, a

condenser and a fan. Another (indoor unit) is placed in the

occupied space. It contains an evaporator, a fan, an air outlet

and one (or two) inlet. The two units are connected by copper

tubes.

Page 2: Optimization on indoor air diffusion of floor-standing type room air-conditioners

Nomenclature

act actual time for cooling air (s)

c specific heat of air (kJ/kg K)

C1, C2, C3, cm empirical constants of turbulence equations

Ei,j mean strain rate (s-1)

Gb production item of turbulent kinetic energy due to

buoyancy (m2/s3)

Gk production item of turbulent kinetic energy due to

mean velocity gradients (m2/s3)

ict ideal time for cooling air (s)

k turbulence kinetic energy (m2/s2)

m total quality of air in a room (kg)

mi quality of a cell (kg)

M total quality of cells (kg)

p local static pressure (Pa)

pt pressure due to fluctuating velocity (Pa)

R2 correlation coefficient

S source item in energy equation

Si source item in momentum equations

t0 temperature of supply air (8C)

tc room control dry-bulb temperature (8C)

ti air temperature of a cell (8C)

tin outflow temperature of a floor-standing type air-

conditioner (8C)

tout inflow temperature of a floor-standing type air-

conditioner (8C)

tp local air-stream dry-bulb temperature (8C)

t̄ average air temperature (8C)

t̄iz average air temperature in occupied zone (8C)

t̄oz average air temperature out occupied zone (8C)

T mean temperature (K)

Ti indoor temperature (K)

Ts set temperature of an air-conditioner (K)

T0 fluctuating temperature (K)

ui, uj mean velocities along coordinate axes (m/s)

up local air-stream velocity (m/s)

u0i, u0j fluctuating velocities along coordinate axes (m/s)

x value of inclination angle

xi, xj distances along coordinate axes (m)

y fit value of evaluation indexes

W rated refrigerating effect (kW)

Dt range of temperature lowering (8C)

Dti�o temperature difference between inflow and

outflow of a floor-standing type air-conditioner

(8C)

Greek letters

r density of air (kg/m3)

t time (s)

h molecular viscosity of air (m2/s)

ht turbulent viscosity (m2/s)

G molecular diffusivity (kg/m/s)

Gt turbulent diffusivity (kg/m/s)

di,j Kronecker delta

e turbulence dissipation rate (m2/s3)

s turbulent Prandtl number

sk turbulent Prandtl number of k

se turbulent Prandtl number of en kinematic viscosity (m2/s)

u difference in effective draft temperature (K)

Subscripts

b buoyancy

i, j spatial coordinates

in inflow

iz in occupied zone

k turbulence kinetic energy

out outflow

oz out occupied zone

s set

t turbulence

e turbulence dissipation rate

W. Liu et al. / Energy and Buildings 40 (2008) 59–7060

As shown in Fig. 1, there are two inlets in the indoor unit of a

FSAC.

In summer, indoor air flows into the indoor unit via the two

inlets (inflow) and is cooled when passing through the

evaporator in the indoor unit. Afterwards, the cooled air is

supplied to the indoor space from the outlet (outflow). Because

of continuously cooling the indoor air, the required indoor

temperature is obtained. Therefore, the FSAC handles the

whole heat load. In an occupied space equipped with a FSAC,

gaps between doors (or windows) and walls are the sole areas

for air exchange between the indoors and outdoors. Usually, the

quantity of fresh air entering the room is small.

Fig. 1. The indoor unit of a floor-standing type air-conditioner.

Page 3: Optimization on indoor air diffusion of floor-standing type room air-conditioners

Table 1

Control mode of a floor-standing type air-conditioner

Control conditions Compressor Outdoor fan Indoor fan

Ti � Ts Off Off On

Ti > Ts + 1 On On On

W. Liu et al. / Energy and Buildings 40 (2008) 59–70 61

Under most circumstances, refrigerating capacity of a FSAC

is larger than the actual cooling load, so its operation has to be

intermittent, meaning that a FSAC will start when indoor

temperature is above a set temperature and stop when indoor

temperature is below the set value. The control mode of the

FSAC studied in this paper is depicted in Table 1, where Ti

stands for indoor temperature and Ts for set temperature.

Table 2 lists some technical parameters of the FSAC.

3. Evaluation method and indexes of air diffusion

performance

Up to now, almost no special methods were established to

evaluate the air diffusion performance of room air-conditioners.

Thus, an evaluation method was proposed in the present work.

3.1. Evaluation method

First, following aspects should be taken into account when

evaluating the air diffusion performance.

(1) T

Tabl

Tech

Mod

KFR

hermal comfort due to the combined effect of air

temperature and velocity.

(2) E

nergy utilization efficiency of air diffusion.

(3) R

ate of indoor air temperature lowering to the set

temperature. This is hardly considered in a central air

conditioning system. However, for a room air-conditioner,

it can be used as an important index to reflect the fast-

cooling effect of indoor air diffusion.

Appropriate indexes are very important for exact evaluation

on air diffusion performance. Among the existing evaluation

indexes, the air diffusion performance index (ADPI) is

appropriate to assess thermal comfort level considering the

presence of draft [6–8], and the energy utilization coefficient

(EUC) can reflect the energy utilization efficiency of air

diffusion [8,9].

However, ADPI and EUC are initially proposed to assess air

diffusion of central air conditioning systems. Moreover,

calculations of the two indexes are usually based on

experimental values, not numerical simulation. (Here, the

evaluation on air diffusion performance of the FSAC was

performed based on results of indoor airflow simulation.)

e 2

nical parameters of a floor-standing type air-conditioner

el Rated refrigerating

effect (W)

Rate

pow

-72LW/DRUYB-Q2 7200 265

Therefore, for their more reasonable application in evaluating

the air diffusion performance of room air-conditioners,

appropriate modification is required.

In addition, none of the existing indexes can be used to

evaluate the fast-cooling effect of air diffusion. Thus, a new

index, fast cooling effect index (FCEI), was proposed.

As a whole, the modified indexes ADPI and EUC, together

with the index FCEI, were adopted in the evaluation method for

room air-conditioners.

3.2. Modification on air diffusion performance index

Considering quality of all calculation cells in airflow

simulation, here, ADPI is defined as the percentage of quality of

airflow meeting following specifications for effective draft

temperature and air velocity in the occupied zone, which is

given as

ADPI ¼

quality of air meeting � 1:5 K< u< 1:0 K

and up < 0:35 m=s

total air quality of indoor occupied zone� 100%

(1)

The difference in effective draft temperature u between any

point in the indoor environment and the control condition was

defined as [10,11]

u ¼ ðtp � tcÞ � 8:0ðup � 0:15Þ (2)

When the difference in effective draft temperature u is between

�1.5 and +1.0 K and the air velocity less than 0.35 m/s, a high

percentage of people feel comfortable.

By the modification, ADPI can reflect the size of airflow zone

where people feel comfortable in an air conditioning room.

3.3. Modification on energy utilization coefficient

Under most circumstances, for the FSAC, temperature of

exhaust air (inflow of the FSAC) is close to average temperature

of the air in the occupied zone, because the inlets of the FSAC

are in the occupied zone. Therefore, according to its definition

[8,9], EUC is always near the value of 1, which is not sensitive

enough to distinguish energy utilization efficiency of different

air diffusion.

Virtually, the energy utilization efficiency of air diffusion

can be indicated by the temperature difference between air in

and out the occupied zone. Thus, here the average temperature

of air out the occupied zone is used instead of the temperature

of exhaust air. By doing so, the modified EUC is written as,

EUC ¼ t̄oz � t0

t̄iz � t0

� 100% (3)

d

er (W)

Air circulation

rate (m3/h)

Dimension of indoor

unit (mm3)

0 1100 895 � 1735 � 335

Page 4: Optimization on indoor air diffusion of floor-standing type room air-conditioners

W. Liu et al. / Energy and Buildings 40 (2008) 59–7062

In summer, if the average temperature of air in the occupied

zone is lower than that out the occupied zone, EUC will be

bigger than 1.0, which indicates that most energy is used to cool

air in the occupied zone. That is people expected.

Considering the quality of cells, the average air temperature

can be calculated as,

t̄ ¼X�

timi

M

�(4)

3.4. Fast cooling effect index for fast-cooling effect

In this paper, a time ratio for fast cooling effect index, FCEI,

is proposed to evaluate the fast-cooling effect of air diffusion,

which is expressed as,

FCEI ¼ act

ict(5)

Where the act is the actual time consumed in the process of

average air temperature of the occupied zone dropping to a set

value, and the ict is an ideal time spent on cooling air of the

whole room to the same set temperature, provided that, in the

room considered, no heat and humidity load exist. According to

the definition of ict, it can be expressed as,

ict ¼ mcDt

W(6)

For a specific air-conditioner and a room, the value of ict

is a constant, if the range of temperature lowering, Dt, does

not change. Therefore, the value of FCEI depends on the size

of act. It is obvious that value of FCEI is always higher than

1.0.

The smaller the value of FCEI, the better the fast-cooling

effect of air diffusion is.

4. Modeling and experiment

As a reliable tool, computational fluid dynamics (CFD) was

increasingly employed to predict the indoor airflow in recent

years [12–15]. Here, the CFD software FLUENT 6.0 was used

to simulate airflow field in a typical office [16]. In order to

validate the simulation results, an experiment was performed to

measure the actual airflow field.

Fig. 2. Schematic representation of the office equip

For an exact airflow simulation, following factors were

considered in the model:

(1) u

ped

nsteady state of airflow because of the intermittent

operation of the FSAC;

(2) e

ffect of the movable guide vanes in the outlet of the FSAC

on direction of outflow;

(3) e

ffect of barriers (such as desks and computers) on indoor

airflow;

(4) b

uoyancy due to density difference between airflow with

different temperature.

4.1. Geometry and mesh generation

The office equipped with the FSAC is on the second floor of

an office building.

The office is 5.7 m long, 4.7 m wide, and 2.85 m high. As

shown in Fig. 2, it has one external wall, two external windows,

three internal walls, floor and ceiling.

The office and objects in it were created with the pre-processor

Gambit, version 2.0.4 [17]. In the office shown in Fig. 3, one can

identify one door, four tables, three computers, three beams and,

of course, the FSAC. This ambiance has been replicated as a full

3D geometric model. Among the various objects, the geometry of

the movable guide vanes in the outlet of the FSAC was

distinguished, which played a key role in air distribution.

Within the current pre-processor both structured and

unstructured meshes can be created. The unstructured meshes

are ideally suited for the discretization of complicated geo-

metrical domains. Considering the internal structure of the

office was complex, the tetrahedron was applied.

For the outlet of the FSAC, it’s a cube, so a hexahedral

(structure) mesh was used. Compared with the whole office, the

size of the outlet and the movable guide vanes was very small.

Therefore, a smaller mesh size was adopted.

The tables and the computers were meshed by means of

hexahedron. The beams used a tetrahedral grid.

The mesh was formed by approx. 900,000.

4.2. Turbulence model

In real situation the indoor flow field changes with time.

Thus, the simulations are carried for an unsteady indoor

with a floor-standing type air-conditioner.

Page 5: Optimization on indoor air diffusion of floor-standing type room air-conditioners

Fig. 3. Geometry of the office equipped with a floor-standing type air-condi-

tioner.

W. Liu et al. / Energy and Buildings 40 (2008) 59–70 63

environment. The governing equations for an unsteady buoyant

airflow consist of the Reynolds-averaging equations, expressed

as follows [18]:

Continuity :@r

@tþ @

@xiðruiÞ ¼ 0 (7)

Momentum :@

@tðruiÞ þ

@

@x jðruiu jÞ

¼ � @ p

@xiþ @

@x j

�h

@ui

@x j� ru0iu

0j

�þ Si (8)

Energy :@

@tðrTÞ þ @

@x jðru jTÞ ¼

@

@x j

�G

@T

@x j� ru0jT

0�þ S

(9)

In the momentum equations, (�ru0iu0j) are the Reynolds

stresses. Introducing the Boussinesq assumption, the items can

be given as:

�ru0iu0j ¼ � ptdi; j þ ht

�@ui

@x jþ @u j

@xi

�� 2

3htdi; j (10)

In the energy equations, item �ru0jT0 can be expressed as:

�ru0jT0 ¼ G t

@T

@x j(11)

The turbulent viscosity (ht) and the turbulent diffusivity (Gt)

are not physical property parameters of the air, which lie on the

turbulence properties. Researches indicated that, generally, the

Table 3

Boundary conditions for inlet/outlet

Location Type

Air outlet of the floor-standing type air-conditioner Mass-flow-inlet

Air inlet of the floor-standing type air-conditioner Pressure-outlet

ratio of ht to Gt can be approximatively treated as a constant:

s ¼ ht

G t

(12)

Thus, the key to calculate turbulent is to determine ht. Here, the

Realizable k � e turbulence model is employed [13,18]. In this

model, the turbulence kinetic energy (k) and its dissipation rate

(e) are determined from the following transport equations:

@

@tðrkÞ þ @

@xiðruikÞ ¼

@

@x j

��hþ ht

sk

�@k

@x j

�þ Gk þ Gb � re

(13)

@

@tðreÞ þ @

@xiðruieÞ

¼ @

@x j

��hþ ht

se

�@e@x j

�þ rC1ð2Ei; jEi; jÞ1=2e

� rC2

e2

k þffiffiffiffiffivep þ C1

ek

C3Gb (14)

ht can be obtained as:

ht ¼cmrk2

e(15)

where C1, C2, C3, cm, sk and se are constants.

For the calculation of near-wall airflow, the standard wall

functions were employed.

The airflow equations were solved using the well-known

SIMPLEC pressures–velocity coupling algorithm. Conver-

gence was reached when the normalized residual measured

less than 10�3. It is noted that temperature reaches 10�6 of

convergence.

A computer with 1 GB memory and an Intel PIII 1.8 GHz

processor was used for computations. Usually, for an unsteady

calculation, it takes about 72 h to complete.

4.3. Boundary conditions, discretization scheme and

materials

The airflow model is solved with the conditions for air outlet,

inlet and solid boundaries. These boundary conditions are

depicted in Tables 3 and 4, respectively.

The discretization scheme affects the precision of the

simulation. Table 5 illustrates the discretization scheme

adopted in this simulation.

Materials used in the simulation are listed in Table 6.

Number Dimensions

(mm2)

Hydraulic

diameter

Turbulence

intensity (%)

1 424.7 � 248.0 0.1566 4

2 600.0 � 64.0 0.0578 3

Page 6: Optimization on indoor air diffusion of floor-standing type room air-conditioners

Table 4

Boundary conditions for solid walls

Internal wall External wall Floor Ceiling Window Door

Number 3 1 1 1 2 1

Thickness (mm) 280 280 145 125 45 45

Thermal conditions Convection Temperature Convection Convection Temperature Convection

Convection coefficient (W/m2 K) 8.72 – 8.72 8.72 – 8.72

Table 5

Discretization scheme

Pressure Momentum Turbulence dissipation

rate

Turbulence kinetic

energy

Energy Unsteady

formulation

Diffusion

term

Standard 2nd-order upwind 2nd-order upwind 2nd-order upwind 2nd-order upwind 1st-order implicit 2nd-order central-

difference

Table 6

Materials properties

Type Density

(kg/m3)

Specific heat

(J/(kg K))

Viscosity

(kg/(m s))

Thermal conductivity

(W/(m K))

Air Fluid Piecewise-linear 1006.43 1.7894e�5 0.0242

Beam Solid 2500 840 – 1.63

Internal wall Solid 1800 880 – 0.828

External wall Solid 1800 880 – 0.813

Floor Solid 2500 840 – 0.70

Ceiling Solid 2500 840 – 1.404

Window Solid 2500 840 – 0.68

Desk Solid 700 2310 – 0.173

Computer Solid 1170 1465 – 0.167

W. Liu et al. / Energy and Buildings 40 (2008) 59–7064

4.4. Airflow measure experiment

4.4.1. Air inlet/outlet temperature measurement

For determination on the temperature difference between

the inflow and outflow of the FSAC, temperature of outflow

and inflow of the FSAC were tested, respectively. In this

measurement, two copper–constantan thermocouples were

used, one of which was placed in the center of the outlet of

the FSAC for the outflow temperature, and the other in a

location close to the fan behind one inlet for the inflow

temperature. Both were linked to a multi-channel data collector

(KEITHLEY 2700, Keithley Instruments, USA), and tempera-

tures were recorded at 0.2 s intervals.

Fig. 4. Temperature difference between the inflow and outflow of the floor-

standing type air-conditioner.

The measurement was carried out at a summer night. Air in

the office was cooled from 26 8C to 23 8C by the FSAC. Fig. 4

shows the real-time test results.

In Fig. 4, the temperature-lowering phase means the process

of cooling indoor air from an initial temperature to an air

conditioning set value, and the temperature-preserving phase

the process of keeping the indoor air temperature at the set

value (fluctuation less than 1 8C).

4.4.2. Airflow field measurement

In order to provide experimental data for validation of the

airflow simulation, measurements of airflow temperature and

velocity at some locations in the office were needed. Because

the office was not a full-scale test room (here the experimental

results were only used for validation of the simulation), 20

measurement points were arranged in the office, as shown in

Fig. 5. At these measurement points, the velocity of airflow was

measured by an anemoscope (TSI Compuflow 8585, E & E

Process Instrumentation, Canada). Table 7 gives the locations

of the 20 measurement points. The temperatures of airflow were

tested using copper–constantan thermocouples, which were

collected by the multi-channel data collector at 1-s intervals.

The measuring instruments were listed in Table 8. Before the

measurement, all the thermocouples were calibrated in a water

bath against a standard mercury thermometer with precision of

0.1 8C (Shanghai Huo er Co., China).

Page 7: Optimization on indoor air diffusion of floor-standing type room air-conditioners

Fig. 5. Schematic representation of locations of the measurement points.

Table 7

Locations of 20 measurement points

Number and locations

No. 1 2 3 4 5 6 7 8 9 10

X (m) 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2 4.2

Y (m) 1.5 3.2 1.5 3.2 1.5 3.2 1.5 3.2 1.5 3.2

Z (m) 0.1 0.1 0.6 0.6 1.4 1.4 1.8 1.8 2.2 2.2

No. 11 12 13 14 15 16 17 18 19 20

X (m) 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0

Y (m) 1.5 3.2 1.5 3.2 1.5 3.2 1.5 3.2 1.5 3.2

Z (m) 0.1 0.1 0.6 0.6 1.4 1.4 1.8 1.8 2.2 2.2

W. Liu et al. / Energy and Buildings 40 (2008) 59–70 65

The accuracy of the instruments meets the requirements in

ASHRAE Standard 55-1992 and ISO 7726 [19,20].

4.5. Validation of airflow numerical simulation

4.5.1. Calculation conditions

The unsteady simulation was done on the airflow field in the

office, due to 08 angle (horizontal) of the guide vanes in the

outlet of the FSAC.

In the simulation, as to the inlet boundary condition of the

office, temperature of the outflow of the FSAC can be obtained

as

tin ¼ tout � Dti�o (16)

Table 8

Instruments used in the experiment

Instrument Model

Thermocouple Copper–constantan

Standard mercury thermometer –

Anemoscope TSI Compuflow 8585

Multi-channel data collector KEITHLEY 2700

The temperature of the inflow of the FSAC, tout, was given

by the simulation. The temperature difference between the

inflow and outflow, Dti�o, was obtained by the inlet and outlet

temperature measurement depicted in Section 4.4.1.

Table 9 illustrates the fit result of Dti�o based on the test data.

The thermal boundary temperatures of walls (air tempera-

tures out the office) were measured using copper–constantan

thermocouples, which are listed in Table 10. The lower

boundary temperatures of internal wall 3 and ceiling were the

air conditioning temperature of the next offices, respectively.

During the measurement, the temperatures almost kept

steady.

The windows and the door closed during the experiment,

therefore, the office can be treated as air-tightness. Before the

FSAC worked, the indoor air did not move, and the initial air

velocity was taken as 0 m/s. The initial air temperature in the

office was 27 8C and the set value of the FSAC 20 8C. Mass

flow rate of outflow was 0.386 kg/s. The time step size was set

as 1 s. Height of the occupied zone was 1.8 m.

In addition, there was no solar radiation entering the office

through the windows, and no computers worked, meaning that

there were no internal heat sources.

4.5.2. Comparison between simulation and experimental

results

Considering that the optimization was done based on the

steady air diffusion of the temperature-preserving phase, Fig. 6

shows the comparison between the simulated and experimental

values of the 20 indoor measurement points during this phase.

The experimental data were the average value in 1 min, and so

did the simulated data.

From Fig. 6(a), it was noted that an excellent agreement was

achieved between the measured and simulated value of air

temperature. The maximum absolute error of temperature was

1.39 K (at measurement point 15), with the maximum relative

error 0.47%.

According to Fig. 6(b), the simulated air velocity distribu-

tion (relative magnitude of velocity) at the whole measured

points yielded a good match with the measured results, though

the maximum relative error at point 13 reached 67.03%. The air

velocity was usually very low (the lowest value was 0.085 m/s

at point 13) and always fluctuated, which induced that the

accurate measurement of velocity was almost impossible. Thus,

the well-matched velocity distribution is more important and

creditable to verify the simulation, compared to the relative

error at a single point.

Consequently, the simulated results can well reflect the

actual airflow field in the office equipped with the FSAC, which

Precision Purpose

0.2 8C Measuring temperature

0.1 8C Calibration

�3% of reading Measuring velocity

– Collecting data from thermocouples

Page 8: Optimization on indoor air diffusion of floor-standing type room air-conditioners

Table 10

Boundary temperatures of walls (8C)

Internal wall 1 Internal wall 2 Internal wall 3 External wall Ceiling Floor Windows Door

29 29 26.5 31 23 29 31 29

Table 9

Fit results of temperature difference between inflow and outflow (8C)

Temperature-lowering phase Temperature-preserving phase

Phase t � 53 s t > 53 s I II

Compressor off Compressor on

Fit values 0.0002t3 � 0.023t2 + 0.8658t � 0.5086 0.0094t + 10.5207 4.66 13.38

W. Liu et al. / Energy and Buildings 40 (2008) 59–7066

shows that the airflow simulation model was reasonable and

applicable.

The reasons to the errors between the simulation and the

experiment are as follows:

(1) t

Fig.

poin

he physical model of the office was simplified based on the

actual structure;

(2) t

he numerical model had some errors, such as round-off

error and discretization error;

(3) t

here were small differences between the calculation

conditions and the actual conditions.

4.5.3. Variety in average air temperature during the

temperature-lowering phase

In fact, the operation of the compressor is controlled

according to the inflow temperature of the FSAC. Therefore,

specifically, the temperature-lowering phase is defined as the

process of the inflow temperature dropping from an initial value

to a set value.

Fig. 7 depicts the variety in the average air temperature of

the occupied zone and the inflow temperature during the whole

6. Comparison between the simulated and the measured values of the test

ts.

temperature-lowering phase based on the airflow simulated

result.

As shown in Fig. 7, the average air temperature had a faster

decreasing trend than that of the inflow during the whole

temperature-lowering phase. Therefore, when the inflow tempe-

rature dropped to 20 8C (the set value), the average temperature

was about 0.6 8C lower than the set value, which meant the latter

reached the set value of the FSAC more rapidly. In this

simulation, the actual time consumed in the process of average

air temperature of the occupied zone dropping to the set value

was 1942 s, while the temperature-lowering phase lasted 2270 s.

5. Determination of optimal air diffusion of the FSAC

Theverified airflow simulation model was used to calculate air

diffusion of the office conduced by different inclination angles of

the vanes in the outlet of the FSAC. Based on the simulated

results, performance of these air diffusion types in the occupied

zone were evaluated employing the three indexes, ADPI, EUC

and FCEI, respectively. By comparing and analyzing the

evaluated results, the optimal air diffusion type can be obtained.

In the simulation, the calculation conditions were the same

as those in Section 4.5, except for the initial temperature of the

office and the set value of the FSAC. Here, the two values were

separately 30 8C and 26 8C.

5.1. Inclination angle of the vanes

Theoretically, the vanes in the outlet of the FSAC can rotate

1808 (from +908 to �908), as shown in Fig. 8.

Fig. 7. Variety in the average air temperature of the occupied zone and the

inflow temperature during the temperature-lowering phase.

Page 9: Optimization on indoor air diffusion of floor-standing type room air-conditioners

Fig. 8. Range of inclination angles and corresponding values of Pia.

Fig. 9. Variation of ADPI and EUC with time in the temperature-preserving

phase.

Fig. 10. ADPI of air diffusion for different inclination angles.

W. Liu et al. / Energy and Buildings 40 (2008) 59–70 67

Here, a dimensionless parameter is used to denote an

inclination angle of a vane, defined as,

Pia ¼ � inclination angle ð�Þ90�

(19)

where ‘‘+’’ means up-inclination, ‘‘�’’ down-inclination and 0

a horizontal angle.

Correspondingly, the value of Pia can change from +1.0

(+908) to �1.0 (�908).

5.2. Values of ADPI and EUC

As mentioned before, the indoor airflow is unsteady because

of the intermittent operation of the FSAC. As a result, the values

of ADPI and EUC change with time. However, considering

variation of the airflow field was small in the temperature-

preserving phase, both values can achieve stabilization (vary

slightly) at one time. Here, this time is titled as ‘‘stabilization

time’’.

For a better evaluation on air diffusion, the stable value of

ADPI and EUC should be applied. Thus, first the stabilization

time was determined.

5.2.1. Stabilization time

Fig. 9 gives the variation of ADPI and EUC during the early

10 min of the temperature-preserving phase for four inclination

angles.

In the calculation of ADPI, the indoor control temperature

(thermal comfort temperature) in Eq. (2) was taken as 26 8C in

summer [21,22].

In Fig. 9, 0 means the initial time of the temperature-

preserving phase when the inflow temperature of the FSAC

reached the set temperature for the fist time. According to the

trend shown in Fig. 9, it revealed clearly that the 8th min was

the stabilization time in this study.

5.2.2. Value of air diffusion performance index

For 10 inclination angles, values of ADPI and EUC were

calculated and compared based on the airflow simulation,

respectively. The 10 angles were�408,�108, 08, 108, 208, 308,358, 408, 458 and 608. The corresponding values of Pia can be

found in Fig. 8.

Fig. 10 shows the values of ADPI at the 8th min in the

temperature-preserving phase (the stabilization time). Figs. 11–

13 show the air temperature distribution on a middle section of

the office (Y = 2.72 m) when the inclination angle is �408, 208and 608, separately.

As illustrated in Fig. 10, when the inclination angle was

�408 or 608, the ADPI had a smaller value. As the angle was

between 20 and 458, it had a bigger value. In detail, for the

calculated 10 inclination angles, the ADPI reached its

maximum value of 0.69 at the angles of 208 and 358, and

minimum value of 0.4 at the angle of 608.It can be noted that values of ADPI for up-inclination

(except 608) were higher than those for down-inclination. This

was explained as follows.

The simulated results indicated that the average temperature

of the occupied zone (25.3–25.7 8C) was lower than the thermal

comfort temperature (26 8C) for any inclination angle, which

meant that air temperatures at most locations were smaller

than 26 8C. Thus, for these locations, the effective draft

temperature difference has the possibility of meeting the

Page 10: Optimization on indoor air diffusion of floor-standing type room air-conditioners

Fig. 11. Air temperature distribution (K) on the section Y = 2.72 m when the

inclination angle is �408.

Fig. 12. Air temperature distribution (K) on the section Y = 2.72 m when the

inclination angle is 208.

Fig. 14. A fit curve of ADPI.

W. Liu et al. / Energy and Buildings 40 (2008) 59–7068

comfort specifications, only if the air velocity is low enough,

according to its definition in Section 3.2. When the vanes

inclined down, the outflow from the outlet of the FSAC was

fully developed in the occupied zone, as shown in Fig. 11,

which led to higher air velocity at most locations. Conse-

quently, the value of ADPI was lower. Compared with down-

inclination, as depicted in Fig. 12, only part of the outflow

entered the occupied zone when up-inclination, resulting in

lower air velocity at most locations, so higher value of ADPI.

Fig. 13. Air temperature distribution (K) on the section Y = 2.72 m when the

inclination angle is 608.

As to the inclination angle of 608, the main reason to the

minimum value of ADPI is that the ceiling and the beam

restricted the development of the outflow in the office, which

led to the bad performance of the air diffusion. This can be seen

in Fig. 13.

In order to obtain the air diffusion having the highest value

of ADPI, a polynomials fit on the data provided by Fig. 10 is

needed. It is known the value of ADPI is higher as the vanes

incline up. Taking into account this, here the fit was done on the

up-inclination (Pia � 0), result of which is shown in Fig. 14.

According to Fig. 14, at the Pia of 0.37 (338), the air

diffusion had a maximum ADPI of 0.69. In fact, when the

inclination angle varied between 208 and 458, the value of ADPI

changed slightly (0.68–0.69).

5.2.3. Value of energy utilization coefficient

Fig. 15 gives the values of EUC at the stabilization time.

Fig. 15 reveals the following facts.

(1) V

Fig.

alues of EUC were always higher than 1.0. This is

reasonable considering that the cooler air goes down due to

the buoyant flow, which induces a lower average air tempe-

rature in the occupied zone than out the occupied zone.

(2) T

he value of EUC had a decreasing trend with the value of

Pia increasing from �0.11 to 0.67, because only part of the

cooler outflow entered the occupied zone when the vanes

incline upwards, and the bigger the up-inclination angle, the

less the outflow entered the occupied zone.

(3) U

nexpectedly, the value of EUC was not the biggest when

the Pia had a value of �0.44. It can be seen in Fig. 11 that

the outflow directly flowed to the floor, which meant more

cold was consumed in removing the heat flux from the floor.

Therefore, the average temperature difference between the

occupied zone and the non-occupied zone was not the

maximum, so did the value of EUC.

15. EUC of air diffusion for different inclination angles and its fit curve.

Page 11: Optimization on indoor air diffusion of floor-standing type room air-conditioners

Fig. 16. FCEI of air diffusion for different inclination angles and its fit curve.

Table 11

Comparison of air diffusion performance between two installation locations

Location 08 208

ADPI EUC FCEI ADPI EUC FCEI

Middle 0.61 1.195 18.34 0.69 1.105 19.26

Corner 0.38 1.201 16.70 0.54 1.080 20.14

W. Liu et al. / Energy and Buildings 40 (2008) 59–70 69

A polynomials fit on the calculated data of EUC is also

described in Fig. 15. The fit result indicated when the

inclination angle is �208 (Pia is �0.22), the corresponding air

diffusion had a maximum EUC of 1.241.

5.3. Values of fast-cooling effect index

The index FCEI was used to evaluate the fast-cooling effect

of air diffusion. Here, the value of ict was 50 s. Seven

inclination angles were chosen for comparing the values of

FCEI. The result is plotted in Fig. 16.

When the value of Pia was 0, the FCEI reached the smallest

value of 18.34. When the vanes inclined upwards, part of the

cooler outflow, not the whole, entered the occupied zone to cool

the air, so the values of FCEI were bigger. When the vanes

inclined downwards, more cold of the outflow was consumed in

removing the heat flux from the floor and the desks, resulting in

the bigger values of FCEI, too.

A polynomials fit on the calculated results of the FCEI is

given. According to the fit curve, the air diffusion due to the

inclination angle of 48 (Pia is 0.03) had a minimum FCEI of

18.33, which means the least value of act was 916 s.

5.4. Comparison between two installation locations

Besides the installation location of the FSAC in the previous

simulation (shown in Fig. 3), a corner of the office is also a

familiar installation location, which is plotted in Fig. 17.

Here, for two inclination angles of 08 and 208, the

comparison between both locations was done. The results

Fig. 17. Geometry of the office as the floor-standing type air-conditioner in the

corner.

are illustrated in Table 11. For ADPI, the air diffusion had a

larger value when the FSAC was in the middle. However, the

values of EUC were almost the same. As to the FCEI, when the

inclination angle was 08, this value for the middle location was

more than that for the corner location, whereas when the

inclination angle was 208, the result was inverse.

5.5. Discussion

Among the three evaluation indexes in the present study,

ADPI and EUC are applied for the temperature-preserving

phase, and FCEI for the temperature-lowering phase.

Here, ADPI is prior to EUC when evaluating the

performance of the air diffusion. There are two reasons. On

one hand, thermal comfort is the emphasis of this study. On the

other hand, the value of EUC was higher than 1 for any

inclination angle of the FSAC, which indicates a fine energy

utilization efficiency.

Based on the results in Sections 5.2–5.4, it is preferable to

install the FSAC in the middle close to one internal wall of the

office (as shown in Fig. 3), and the inclination angles of the

vanes corresponding to the optimal air diffusion are given in

Table 12.

According to Table 12, a control scheme of the FSAC was

suggested. When the FSAC starts, regulate the inclination angle

of the vanes to 48 for fast cooling. After about 916 s, set the

vanes to incline up 338 for best thermal feelings and good

energy utilization efficiency.

In this work, the office can be regarded as a typical room

equipped with a FSAC, with its size matching the rated

refrigerating effect of the FSAC. In addition, the indoor air

diffusion mainly depends on the airflow from the outlet of the

FSAC, and the effect of outdoor conditions was less. Therefore,

for most instances, the optimization results are applicable.

And, the evaluation method presented in this paper can almost

be used for various air diffusion conduced by room air-

conditioners.

Table 12

Optimal inclination angles of the vanes for the floor-standing type air-condi-

tioner

Location of the

floor-standing type

air-conditioner

Temperature-lowering

phase

Temperature-preserving

phase

Inclination

angle (8)FCEI/

act (s)

Inclination

angle (8)ADPI EUC

Middle close to

an internal wall

4 18.33/916 33 0.69 1.075

Page 12: Optimization on indoor air diffusion of floor-standing type room air-conditioners

W. Liu et al. / Energy and Buildings 40 (2008) 59–7070

6. Conclusions

The performance of indoor air diffusion of the FSAC was

evaluated and optimized, based on the results of airflow

simulation. Following conclusions can be obtained.

The simulated results can well reflect the actual airflow field

in the office equipped with the FSAC. The airflow simulation

model built in the paper is reasonable and applicable.

Traditional evaluation indexes, such as air diffusion perfor-

mance index and energy utilization coefficient, should be

modified before employing to the air diffusion of room air-

conditioners. By appropriate modification, both indexes can be

used to obtain more reasonable results in the evaluation on air

diffusion performance of room air-conditioners.

In the temperature-lowering phase, the optimal air diffusion

is due to the inclination angle of 48 (the best value I), which has

a minimum value of fast cooling effect index.

In the temperature-preserving phase, the optimal air diffu-

sion is induced by the inclination angle of 338 (the best value

II), which has a maximum value of air diffusion performance

index and fine energy utilization coefficient.

It is suggested that when the FSAC starts, regulate the

inclination angle of the vanes to the best value I for fast

cooling. After the average air temperature of the occupied

zone reaches the set value, set the inclination angle to the best

value II for best thermal feelings and good energy utilization

efficiency.

It is preferable to install the FSAC in the middle close to one

internal wall of the office for higher thermal comfort level.

Acknowledgements

The project was financially supported by National Natural

Science Foundation of China (no. 50478018). The authors

wish to acknowledge Zhijian Hou and Zhengping Zhou for

their assistance during the experiment. And also, the authors

want to express thanks to Ms. A.L. Lian for her translation of

the paper.

References

[1] ASHRAE, ASHRAE Standard 62. Ventilation for Acceptable Indoor Air

Quality, American Society of Heating, Refrigeration and Air-Condition-

ing Engineers, Atlanta, GA, USA, 1989.

[2] Z. Lin, T.T. Chow, K.F. Fong, et al., Comparison of performances of

displacement and mixing ventilations. Part I. Thermal comfort, Interna-

tional Journal of Refrigeration 28 (2005) 276–287.

[3] S.C. Sekhar, C.S. Ching, Indoor air quality and thermal comfort studies of

an under-floor air-conditioning system in the tropics, Energy and Build-

ings 34 (2002) 431–444.

[4] T. Imanari, T. Omori, K. Bogaki, Thermal comfort and energy consump-

tion of the radiant ceiling panel system. Comparison with the conventional

all-air system, Energy and Buildings 30 (1999) 167–175.

[5] C.-S. Pan, H.-C. Chiang, M.-C. Yen, et al., Thermal comfort and energy

saving of a personalized PFCU air-conditioning system, Energy and

Buildings 37 (2005) 443–449.

[6] K.C. Chung, C.Y. Lee, Predicting air flow and thermal comfort in an

indoor environment under different air diffusion models, Building and

Environment 31 (1996) 21–26.

[7] M. Bojic, F. Yik, T.Y. Lo, Locating air-conditioners and furniture inside

residential flats to obtain good thermal comfort, Energy and Buildings 34

(2002) 745–751.

[8] R. Zhao, C. Fan, D. Xue, et al., Air Conditioning, China Architecture

Industry Press, Beijing, 1994.

[9] G. Gan, Evaluation of room air distribution systems using computational

fluid dynamics, Energy and Buildings 23 (1995) 83–93.

[10] J. Rydberg, P. Norback, Air distribution and draft, ASHVE Transactions

55 (1949) 225–240.

[11] A. Koestel, G.L. Tuve, Performance and evaluation of room air distribu-

tion systems, ASHRAE Transactions 61 (1955) 533–550.

[12] J. Abanto, D. Barrero, M. Reggio, et al., Airflow modeling in a computer

room, Building and Environment 39 (2004) 1393–1402.

[13] C. Teodosiu, R. Hohota, G. Rusaouen, et al., Numerical prediction of

indoor air humidity and its effect on indoor environment, Building and

Environment 38 (2003) 655–664.

[14] H. Hangan, F. McKenty, L. Gravel, et al., Case study: numerical simula-

tions for comfort assessment and optimization of the ventilation design for

complex atriums, Journal of Wind Engineering and Industrial Aerody-

namics 89 (2001) 1031–1045.

[15] P.V. Nielsen, Computational fluid dynamics and room air movement,

Indoor Air 14 (2004) 134–143.

[16] Fluent Inc., Fluent 6.0. user’s guide, Fluent Inc., 2001.

[17] Fluent Inc., Gambit 2.0 user’s guide, Fluent Inc., 2001.

[18] W. Tao, Numerical Heat Transfer, second ed., Xi’an Jiaotong University

Press, Xi’an, 2001.

[19] ASHRAE. ANSI/ASHRAE Standard 55-1992, Thermal Environmental

Conditions for Human Occupancy, Atlanta, GA, 1992.

[20] ISO, International Standard 7730, Moderate thermal environments—

determination of the PMV and PPD indices and the specification of

conditions for thermal comfort, second ed., International Standards

Organization, Geneva, 1994.

[21] ASHRAE. ASHRAE Applications Handbook (SI). HOTELS, MOTELS,

AND DORMITORIES. Atlanta, GA, 2003.

[22] The tenth design and research institute of China mechanical industry

department, Air Conditioning Design Handbook, China Architecture

Industry Publishing Company, Beijing, 1983.