optimization of air-conditioning system operating strategies for hot and humid climates

12
Optimization of air-conditioning system operating strategies for hot and humid climates Jung-Ho Huh a , Michael J. Brandemuehl b, * a Architectural Engineering, University of Seoul, 90 Jeonnong-Dong Dongdaemoon-Gu, Seoul 130-743, Republic of Korea b Civil, Environmental, and Architectural Engineering, University of Colorado, 428 UCB, Room ECOT 441, Boulder, CO 80309 USA Received 16 August 2007; accepted 30 October 2007 Abstract This paper describes research into the optimal operation of building heating, ventilation, and air-conditioning (HVAC) systems focusing on both temperature and humidity control. While most previous work on HVAC optimization has been limited to evaluation of conventional temperature- based control systems, this study emphasizes the humidity control issue in meeting both sensible and latent building loads. The analysis is based on a combination of a realistic simulation of a direct expansion (DX) air-conditioning system and a direct-search numerical optimization technique. The simulation models have been validated through comparisons with field data. Optimization was performed on five different system control variables to minimize system power consumption while meeting building loads and maintaining comfort. Indoor temperature and humidity are also optimized within standard comfort constraints. Building loads were modeled using an extended bin method that allows consideration of the interactions between loads and indoor conditions. Results indicate that minimum energy use typically occurs at low airflow rates, with indoor humidity levels below the upper comfort limit. Results also show that coil air bypass and evaporator circuiting control are typically not necessary unless operation would otherwise result in overcooling. The optimization results also translate to relatively simple strategies for system control. Significant savings are demonstrated over conventional control strategies used in packaged DX equipment. # 2007 Elsevier B.V. All rights reserved. Keywords: Dehumidification; Energy consumption; Air-conditioning system; Simulation; Optimization 1. Introduction Humidity problems can be found in many applications including office buildings, supermarkets, art galleries, museums, libraries, electronics manufacturing facilities, pharmaceutical clean rooms, indoor swimming pools and other commercial facilities. In many HVAC applications, the cooling and dehumidification coil is unable to properly meet the dehumidification requirements of the building when the latent load is high, either due to large internal moisture generation or through communication with humid outdoor conditions. Depending on the application, the mismatch between building latent load and equipment latent capacity can degrade occupant comfort and productivity, cause damage from mold and condensate, and increase energy costs through reheating. These problems are exacerbated by the increased demand for outdoor air in buildings to address indoor air quality. In most commercial and residential applications, the humidity in the space is not directly controlled. In the process of meeting the sensible loads of the building, the air is forced below the dew-point temperature, coincidentally providing dehumidification as a result of the cooling process. The relative humidity in the space is controlled only indirectly and it floats up and down as a result of the changing match between the sensible and latent capacities of the equipment compared to the sensible and latent loads. In some commercial applications, most notably supermarkets, both temperature and humidity of the space are directly controlled. The most common method employed today to meet the coincident loads of a supermarket is to operate the constant-air-volume system at whatever compressor capacity is required to maintain both space temperature and humidity at or below the desired levels. If the system operation is dictated by space temperature, the space humidity is allowed to fall below the setpoint, causing increased energy use to remove more moisture than necessary. www.elsevier.com/locate/enbuild Available online at www.sciencedirect.com Energy and Buildings 40 (2008) 1202–1213 * Corresponding author. Tel.: +1 303 492 8594; fax: +1 303 492 7317. E-mail address: [email protected] (M.J. Brandemuehl). 0378-7788/$ – see front matter # 2007 Elsevier B.V. All rights reserved. doi:10.1016/j.enbuild.2007.10.018

Upload: jung-ho-huh

Post on 21-Jun-2016

214 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Optimization of air-conditioning system operating strategies for hot and humid climates

www.elsevier.com/locate/enbuild

Available online at www.sciencedirect.com

08) 1202–1213

Energy and Buildings 40 (20

Optimization of air-conditioning system operating strategies for hot

and humid climates

Jung-Ho Huh a, Michael J. Brandemuehl b,*a Architectural Engineering, University of Seoul, 90 Jeonnong-Dong Dongdaemoon-Gu, Seoul 130-743, Republic of Korea

b Civil, Environmental, and Architectural Engineering, University of Colorado, 428 UCB, Room ECOT 441, Boulder, CO 80309 USA

Received 16 August 2007; accepted 30 October 2007

Abstract

This paper describes research into the optimal operation of building heating, ventilation, and air-conditioning (HVAC) systems focusing on both

temperature and humidity control. While most previous work on HVAC optimization has been limited to evaluation of conventional temperature-

based control systems, this study emphasizes the humidity control issue in meeting both sensible and latent building loads. The analysis is based on

a combination of a realistic simulation of a direct expansion (DX) air-conditioning system and a direct-search numerical optimization technique.

The simulation models have been validated through comparisons with field data. Optimization was performed on five different system control

variables to minimize system power consumption while meeting building loads and maintaining comfort. Indoor temperature and humidity are also

optimized within standard comfort constraints. Building loads were modeled using an extended bin method that allows consideration of the

interactions between loads and indoor conditions. Results indicate that minimum energy use typically occurs at low airflow rates, with indoor

humidity levels below the upper comfort limit. Results also show that coil air bypass and evaporator circuiting control are typically not necessary

unless operation would otherwise result in overcooling. The optimization results also translate to relatively simple strategies for system control.

Significant savings are demonstrated over conventional control strategies used in packaged DX equipment.

# 2007 Elsevier B.V. All rights reserved.

Keywords: Dehumidification; Energy consumption; Air-conditioning system; Simulation; Optimization

1. Introduction

Humidity problems can be found in many applications

including office buildings, supermarkets, art galleries,

museums, libraries, electronics manufacturing facilities,

pharmaceutical clean rooms, indoor swimming pools and

other commercial facilities. In many HVAC applications, the

cooling and dehumidification coil is unable to properly meet the

dehumidification requirements of the building when the latent

load is high, either due to large internal moisture generation or

through communication with humid outdoor conditions.

Depending on the application, the mismatch between building

latent load and equipment latent capacity can degrade occupant

comfort and productivity, cause damage from mold and

condensate, and increase energy costs through reheating. These

* Corresponding author. Tel.: +1 303 492 8594; fax: +1 303 492 7317.

E-mail address: [email protected] (M.J. Brandemuehl).

0378-7788/$ – see front matter # 2007 Elsevier B.V. All rights reserved.

doi:10.1016/j.enbuild.2007.10.018

problems are exacerbated by the increased demand for outdoor

air in buildings to address indoor air quality.

In most commercial and residential applications, the

humidity in the space is not directly controlled. In the process

of meeting the sensible loads of the building, the air is forced

below the dew-point temperature, coincidentally providing

dehumidification as a result of the cooling process. The relative

humidity in the space is controlled only indirectly and it floats

up and down as a result of the changing match between the

sensible and latent capacities of the equipment compared to the

sensible and latent loads. In some commercial applications,

most notably supermarkets, both temperature and humidity of

the space are directly controlled. The most common method

employed today to meet the coincident loads of a supermarket

is to operate the constant-air-volume system at whatever

compressor capacity is required to maintain both space

temperature and humidity at or below the desired levels. If

the system operation is dictated by space temperature, the space

humidity is allowed to fall below the setpoint, causing

increased energy use to remove more moisture than necessary.

Page 2: Optimization of air-conditioning system operating strategies for hot and humid climates

J.-H. Huh, M.J. Brandemuehl / Energy and Buildings 40 (2008) 1202–1213 1203

If the system operation is dictated by space humidity, the space

temperature is allowed to drop only so far, typically to the

heating setpoint, before reheating is required to maintain

comfort conditions. If waste heat is not available, there is a cost

penalty for both overcooling the air and then reheating it.

The first step in addressing dehumidification needs involves

comprehensive system design. Design and selection of an

appropriate HVAC and dehumidification system requires that

the system meet both sensible and latent loads. However, since

design conditions typically occur at times of high sensible load,

off-design conditions often present situations of low sensible

load but high latent load. It is necessary to operate the system to

match the equipment performance with the building loads over

a broad range of off-design operating conditions, while

constrained to maintain temperature and humidity within a

desired range.

The ‘‘match’’ between the sensible and latent components of

the equipment capacities and building loads is represented by

the sensible heat ratio, SHR. The equipment capacity SHR is

defined as the ratio of the sensible capacity to total capacity, and

the load SHR is defined as the ratio of sensible load to total load,

where the total is the sum of the sensible and latent.

SHRcap ¼CAPsen

CAPsen þ CAPlat

(1)

SHRload ¼Qsen

Qsen þ Qlat

(2)

Low SHR implies a greater latent fraction and better

dehumidification. Under steady-state conditions, energy and

mass balances dictate that SHRcap = SHRload.

Given a particular system design, the goal of this research is

to develop optimal operational strategies for a direct expansion

(DX) HVAC system with respect to both energy consumption

and thermal comfort. The objective will be achieved by

applying numerical optimization techniques with a validated

simulation model.

Optimization techniques have not been widely used in the

study of HVAC system operation, and relatively little research

on optimal HVAC system operation has been reported in the

literature. Several HVAC systems have been previously studied

for optimal control in meeting temperature-cooling require-

ments only. To date there has been no comprehensive study on

the optimal set of HVAC operating parameters for the complete

thermal environment. In most applications both temperature

and humidity must be maintained, presenting a tougher

optimization problem than simple temperature control. Since

providing greater comfort is one of main objectives in today’s

HVAC industry, the need for efficient active humidity control

becomes more important.

Earlier optimization studies of HVAC systems mainly

focused on control of water-side equipment in a chilled water

plant, not air-side, and room air humidity was not controlled

directly. Even recent studies [1–3] investigated optimal control

of supply air temperature and/or airflow in air-handling unit

systems without considering humidity as a controlled variable.

Over the years, there have been many studies focusing on the

dehumidification performance of the air conditioners, including

issues of simulation, design, and operations. For example,

studies have been performed by Shirey [4], Brandemuehl and

Khattar [5], Kosar et al. [6], Mumma [7], Murphy [8], Khattar

[9], and Harriman and Judge [10]. There have also been many

studies of thermal comfort control involving optimal energy

use. Whitmer [11] minimized the energy requirements for a

simple system by determining the optimal combination of

environmental variables (air temperature, humidity, and air

velocity) with the thermal comfort constraint. Henderson et al.

[12] investigated the impact of controlling an HVAC system to

maintain constant comfort rather than fixed setpoint tempera-

ture under humid climate. More recently, Mazzei et al. [13]

conducted a critical review regarding the thermal comfort-

based HVAC dehumidification systems.

While there is a rich literature on all of the various aspects of

the problem, there has been no systematic effort to address

optimal off-design operation of an air-conditioning system to

satisfy both temperature and humidity constraints imposed by

the needs of occupant comfort and health. This evaluation will

be performed using validated simulation models of DX HVAC

equipment, simplified load models that include the effects of

changing indoor conditions on sensible and latent loads, and

constrained, direct-search optimization techniques.

2. Description of the analysis

2.1. System model

Fig. 1 shows a schematic diagram of a typical direct

expansion air-conditioning system focusing on air-side system

configuration considered in this study. Return air from the

building zone is mixed with outdoor air to provide mixed air to

the air handler. A reheat coil is included to provide reheat as

necessary to maintain a humidity setpoint.

A combined theoretical/empirical modeling strategy has been

adopted, which allows confidence in predicting performance over

a very wide range of operating conditions. The DX system model

is based on a set of physically based models for the components of

a DX system [14]. The components include compressors, dry-

surface heat exchangers (e.g., air-cooled condenser), wet-surface

heat exchangers (e.g., cooling coil), heat pipes, fans, and outdoor

air mixing chambers. The individual component models are then

combined into a complete system.

The compressor model is an empirically and statistically

based correlation for positive displacement compressors. The

model has polynomial fits for the cooling capacity, CAP, and

the power draw of the compressor, Pcomp. There are two

independent variables in each ten-term equation—the saturated

suction temperature, SST, and the saturated discharge

temperature, SDT.

CAP ¼ C1 þ C2SSTþ C3SDT þ C4SST2 þ C5ðSSTÞðSDTÞþ C6SDT2 þ C7SST3 þ C8ðSDTÞðSST2Þþ C9ðSSTÞðSDT2Þ þ C10SDT3 (3)

Page 3: Optimization of air-conditioning system operating strategies for hot and humid climates

of air-conditioning system.

J.-H. Huh, M.J. Brandemuehl / Energy and Buildings 40 (2008) 1202–12131204

2

Pcomp ¼ P1 þ P2SSTþ P3SDTþ P4SST þ P5ðSSTÞðSDTÞþ P6SDT2 þ P7SST3 þ P8ðSDTÞðSST2Þþ P9ðSSTÞðSDT2Þ þ P10SDT3 (4)

The rating procedure and the form of the equations are

specified by ARI Standard 540 [15]. While the results can be

corrected for different superheat and subcooling levels, our

analysis assumes fixed superheat of 11.1 8C and fixed

subcooling of 8.3 8C. The coefficients, Ci and Pi, are typically

available directly from the manufacturers.

The condenser is simulated using an air-to-liquid coil model

that accounts for heat transfer between air and a liquid through a

dry finned coil surface. The model is based on simple

effectiveness–NTU heat exchanger relationships, described in

most introductory heat transfer textbooks, and assumes that the

temperature of the refrigerant throughout the coil is fixed at the

SDT.

The evaporator is also modeled using effectiveness–NTU

relationships, modified to account for both the heat and mass

transfer of the cooling and dehumidifying coil [16,17]. In

particular, the cooling coil models accounts for both heat and

moisture transfer effects assuming a Lewis number of unity and

using a locally linear saturation curve. The model accounts for

both fully wet and partially wet coils by calculating coil surface

temperatures throughout the coil and comparing with local air

dew-point temperatures. The model also assumes that the

refrigerant temperature is constant at the SST through the coil.

The overall system is modeled by combining the compo-

nents. Computationally, the system performance is determined

by solving for the SST and SDT under a given set of operating

conditions. The required operating conditions are the airflow

Fig. 1. Schematic diagram

rate, air temperature, and humidity ratio entering each of the

coils.

The results of the model include the power consumption of

the compressor, indoor fan, and outdoor fan, as well as the

temperature and humidity of the air delivered to the building

and the average run-time fraction of the system.

The specific models of the individual components can be

calibrated with a combination of manufacturer’s data or

measured field performance. The compressor coefficients of

Eqs. (3) and (4) are generally available from the compressor

manufacturer. The air-cooled condenser model requires an

overall heat transfer coefficient to describe the physical size and

heat transfer performance of the condenser. The evaporator

model requires an overall heat transfer coefficient and the

fraction of this overall coefficient that is associated with the

external fin surfaces. These parameters can be back-calculated

knowing the condenser and evaporator heat transfer at a given

set of rating conditions.

Alternatively, the model parameters can be identified by

correlation to measured performance data. For this study, the

model has been calibrated to match the performance of a 30-

tonnes (105.6 kW) unit installed in a supermarket in Florida [5].

Compressor coefficients were obtained from the manufacturer

and overall heat transfer coefficients for the evaporator and

condenser were obtained through parameter identification

using measured data.

The DX system model has been validated through

comparisons with manufacturers’ published performance data

and field data at several sites in the southeastern U.S. Fig. 2

shows a comparison of measured and predicted compressor

power of the system for operation during a 2-month period in

summer. Similar comparisons are obtained for sensible and

Page 4: Optimization of air-conditioning system operating strategies for hot and humid climates

Fig. 2. Comparison of measured and simulated compressor power.

J.-H. Huh, M.J. Brandemuehl / Energy and Buildings 40 (2008) 1202–1213 1205

latent capacities, as well as suction and discharge pressures. In

each case, the comparisons have an R2 value of greater than

0.88.

2.2. System control strategies

Five different system control variables are considered in the

optimization process. Each control variable has an independent

effect on the efficiency of the refrigeration system and/or the

sensible versus latent capacity of the equipment as described by

the SHRcap. The first two control variables discussed here focus

on the compressor and condenser subsystem.

� C

ompressor capacity control. There are a variety of methods

to control compressor capacity, including variable speed

operation, on–off cycling, inlet guide vanes for centrifugal

compressors, slide valves for screw compressors, and

compressor unloading for reciprocating compressors. In

each case, the level of capacity control can be represented as a

fraction of full load capacity under the given operating

conditions. In this analysis, it is assumed that the compressor

capacity is continuously modulated.

� C

ondenser fan control. Air-cooled condensers typically have

multiple fans with provision for varying the number of

operating fans. Several manufacturers offer variable speed

operation on one fan to provide continuous airflow control.

Condenser airflow is typically controlled based on com-

pressor capacity, outdoor air temperature, and discharge

pressure. However, the airflow is actually an optimization

variable. At high airflow, condenser fan power increases

while the compressor power is reduced due to lower

discharge pressures. The optimal values also depend on

evaporator conditions and control. In this analysis, it is

assumed that the condenser fans and effective condenser area

are continuously staged. That is, as the condenser airflow is

reduced, it is assumed that the condenser area for heat transfer

is also proportionally reduced.

The following control variables have a direct effect on

the split between sensible and latent capacity of the system,

the SHRcap, by affecting the evaporator temperature and the

interactions of the evaporator with the moist air stream. In

general, a lower coil temperature dictates improved

dehumidification performance through reductions in the

SHRcap.

� S

upply airflow rate. Changes in the evaporator airflow rate

have a significant effect on system dehumidification

performance. Like the condenser, changes in evaporator

airflow cause trade-offs between compressor power and fan

power. Lower airflow yields lower fan power, but increased

compressor power because of lower suction pressure.

However, more importantly, changes in airflow rate have a

strong influence over the dehumidification performance of

the cooling coil. For DX systems, reduction in airflow lowers

the coil temperature and gives a closer approach of the

leaving air temperature to the coil temperature, both of which

reduce SHRcap. For this analysis, constraints are placed on the

control variables to ensure that the saturated suction

temperature is greater than �2.2 8C for freeze protection.

� B

ypass air around cooling coil. Practical considerations limit

the minimum supply airflow rate. In many cases, a minimum

flow or supply duct pressure is required to assure adequate air

circulation in the building. One common method to reduce

coil airflow without affecting the supply airflow is to bypass

part of the air stream around the coil through the use of a coil

face-bypass damper. While there are no additional savings

due to fan power reductions, the reduced coil airflow can save

energy by providing a better match between SHRcap and

SHRload.

� C

ooling coil face-split circuit control. It is common,

especially in multiple compressor systems, to disable part

of the evaporator surface at part-load conditions. For

example, a rooftop unit might have two equal compressors,

each with 50% cylinder unloading, for effective capacity

staging. It is common to provide two separate evaporator

coils, one for each compressor, stacked on top of each other in

the air stream. More generally, it is possible to design the

system with variable evaporator area available for refrigerant

flow. For the purposes of this analysis, it is assumed that the

evaporator refrigerant flow is controlled in a ‘‘face-split’’

arrangement, using the full depth of the coil. With this

circuiting arrangement, reducing the evaporator area lowers

the suction temperature and lowers the SHRcap.

It should be noted that the mixed air conditions entering the

air handler have a significant effect of DX system performance.

Since the mixed air is comprised of outdoor and return air, the

outdoor air fraction is an important control variable. For this

analysis, it is assumed that the outdoor airflow rate is fixed at

15% of the design airflow rate to meet indoor air quality

concerns. In particular, as the supply airflow rate is decreased,

the outdoor air fraction increases.

2.3. Building load models

In evaluating optimal control strategies for temperature and

humidity control, one major constraint on system operation is

that the sensible and latent loads be met. Alternatively, the

indoor temperature and humidity must be maintained within

Page 5: Optimization of air-conditioning system operating strategies for hot and humid climates

Fig. 3. Simplified load model from detailed computer simulation.

J.-H. Huh, M.J. Brandemuehl / Energy and Buildings 40 (2008) 1202–12131206

desired ranges. As discussed in the next section, the analysis

includes evaluation of optimization to maintain a desired

comfort level in which indoor temperature and humidity can

vary as long as overall comfort is maintained. Unfortunately,

since a portion of the building load derives from the difference

between indoor and outdoor conditions, changes in indoor

temperature and humidity cause changes in the loads. Since

changes in the loads have a dramatic effect on energy

consumption, evaluation of optimal control strategies requires

consideration of the interactions between loads and indoor

conditions.

A detailed dynamic hourly analysis of these interactions

would require dynamic optimization to account for heat and

moisture storage in the building, which would involve daunting

computational difficulties. Instead, the interactions between

loads and indoor conditions are estimated using an extension of

the modified bin method [18]. The building loads have been

simplified to represent the sensible cooling load as a function of

the difference between outdoor air temperature and indoor air

temperature. Latent cooling loads are represented as a function

of the difference between outdoor and indoor humidity ratios.

Separate load relationships can be used at night and during the

day to account for the difference in solar effects, lighting levels

and occupancy.

The following relationships describe the loads as functions

of indoor and outdoor conditions.

Qsen ¼ KsenðToa � Tz þ DTgainÞ (5)

Qlat ¼ K latðwoa � wz þ DwgainÞ (6)

DTgain ¼Gsen

Ksen

(7)

Dwgain ¼Glat

K lat

(8)

where

Qsen = zone sensible load (W),

Ksen = linear load coefficient for sensible loads (W/8C),

Gsen = effective sensible internal gain (W),

Toa = outdoor temperature (8C),

Tz = building zone temperature (8C),

DTgain = temperature difference associated with internal

heat gains (8C),

Qlat = zone latent load (W),

Klat = linear load coefficient for latent loads (W),

Glat = effective latent internal gain (W),

woa = outdoor humidity ratio,

wz = building zone humidity ratio,

Dwgain = humidity ratio difference associated with internal

moisture gains.

Fig. 3 shows a comparison of the simplified sensible loads

for the retail store as obtained from hourly simulation [14]. The

fluctuations are largely due to the simplified accounting of

solar gains and to fluctuations in occupancy and infiltration.

Notice that there is a net positive cooling load at very low

outdoor temperatures, indicating that the internal heat gains

dominate the envelope heat gains in determining the cooling

requirements.

The simplified relationships were developed using the

results of hourly load simulations of a retail store in Miami [14].

Ksen ¼ 986:4 W=�C Gsen ¼ 32; 192:5 W

K lat ¼ 1:172� 106 W Glat ¼ 1; 490:5 W

The load models used here appear very simple. However, it

can be argued that they are also very appropriate to the task of

comparing dehumidification alternatives. While the simple bin

models do not explicitly account for solar effects or dynamic

variations in load due to thermal storage in the building, the

regressions for sensible load have been developed from a model

that does explicitly handle these effects. While the results of the

detailed model show variations in sensible load at a given

outdoor temperature, the averaging of these variations can be

appropriate for comparisons of annual energy consumption.

Most significantly, the moisture transport and latent load model

of the most common hourly building simulation programs are

identical to the latent load model employed here. That is, the

latent load is a function only of the scheduled internal moisture

gains and the difference between indoor and outdoor humidity

ratio. In an effort to account for the effects of indoor humidity

on latent load and equipment performance, the simplified

model used here represents less of a compromise than typically

required in other bin analyses.

3. Optimization method

3.1. Objective function and constraints

The objective function and constraints for this HVAC system

optimization problem derive directly from the desire to

minimize energy use while satisfying building loads and

maintaining indoor conditions within desired ranges. There

could be two approaches to devise the objective function

depending on whether the comfort constraints are handled as

part of the objective function or constraint functions. While

both techniques have been evaluated, the discussions here will

focus on the simpler objective function. The objective function

Page 6: Optimization of air-conditioning system operating strategies for hot and humid climates

J.-H. Huh, M.J. Brandemuehl / Energy and Buildings 40 (2008) 1202–1213 1207

will then be confined to the power consumption of the

compressor, condenser fans, and air handler fans. Since the

analysis will be performed assuming quasi-steady-state

operation, minimizing power is synonymous with minimizing

energy use.

Jðu; fÞ ¼ Pcomp þ Pcond þ Pahu (9)

where

J = the objective function and the,

u = vector of controlled variables,

f = vector of uncontrolled variables,

Pi = power consumption of component i.

As noted above, the power use of the HVAC system is a

function of the sensible and latent loads, the outdoor

environmental conditions, the indoor environmental condi-

tions, and the system control variables. The vector of

uncontrolled variables, f, includes the sensible and latent

loads and the outdoor temperature and humidity. In this case,

with the loads a function of outdoor and indoor conditions, the

outdoor conditions are effectively the only uncontrolled

variables.

The vector of controlled variables, u, includes the five

equipment variables described above in the section on system

control variables. Specifically, the vector includes the following

variables:

ucomp = fraction of compressor capacity at given operating

conditions,

ucond = fraction of design condenser airflow,

uahu = fraction of design air handler airflow rate,

ubyp = coil air bypass fraction,

uevap = fraction of evaporator coil with refrigerant flow, face

split.

For this analysis, the indoor conditions are also considered to

be controlled variables. That is, we desire to identify the

optimal values of the indoor temperature and humidity that

minimize energy use while maintaining comfort. Since comfort

is subjective and a function of both temperature and humidity, it

is possible to find alternative pairs of temperature and humidity

that provide the same comfort, but that require different energy

consumption from the HVAC system. Constraints are subse-

quently required to ensure that the indoor environment is

comfortable.

In this study, there are two groups of the constraints:

building sensible and latent loads, and thermal comfort. The

building loads represent inequality constraint functions,

specifying that (1) the sensible capacity of the equipment is

greater than or equal to the sensible load of the building and (2)

the latent capacity of the equipment is greater than or equal to

the latent load of the building. If overcooling of the building is

required to meet the latent loads, reheat is required to maintain

comfort.

Constraints on the indoor conditions are applied in three

different forms:

1. C

onstant setpoint for indoor temperature and maximum

setpoint for humidity. That is, the temperature is maintained

precisely, using reheat if necessary, but the humidity is

allowed to float down below the setpoint.

2. S

et minimum and maximum values for the temperature and

humidity ratio. That is, comfort is defined in terms of a

rectangular section of the psychrometric chart.

3. S

et minimum and maximum values for the predicted mean

vote (PMV).

The PMV is a single index of comfort that includes the

effects of air temperature, air humidity, radiant temperature, air

velocity, clothing level, and activity level [19]. Numerical

values have been assigned to the responses according to the 7-

point thermal sensation scale that runs from cold (�3) to hot

(+3). It has further been determined that 90% of people will be

express satisfactory thermal comfort within the range

�0.5 � PMV � +0.5.

For this analysis, only temperature and humidity have

been varied in the comfort calculations. Metabolic rate was

1.2 mets and no external work are assumed, corresponding to

standing, but relaxed, activity. Light summer clothing is fixed

as 0.5 clo. Relative air velocity is fixed at 0.2 m/s. Room air

temperature and mean radiant temperature are assumed to be

identical.

3.2. The complex search method

Essentially, the simplex method is a rudimentary steep

ascent procedure, in which a sequence of experimental designs,

each in the form of a regular simplex, is used. (The convex hull

of n + 1 points is called an n-dimensional simplex.) The

direction of steepest ascent is estimated from observations at

the vertices of a regular simplex and proceeds from the center of

the simplex out through that face which is opposite to (does not

contain) the point corresponding to the lowest observation.

Thus, the optimization procedure is to continually move into

the adjacent regular simplex obtained by discarding the point of

the current simplex corresponding to the lowest observation and

replacing it by its mirror image in the plane (hyperplane) of the

remaining points.

The original complex method has the advantage of easy

handling capability for implicit inequality constraints, and of

not requiring computation of any derivative such as in the

gradient method. It has, however, the disadvantage of

relatively slow convergence to an optimum point and requires

many iterative computations. Therefore, improvement of the

convergence rate of the method has been attempted by

modifying it without introducing many complexities. The

improved algorithm, the golden complex search method, is

based on the Box’s Complex Method [20] and was developed

by Hughes [21] and extended by Malik [22] in the form of the

general-purpose subroutine. This algorithm has subtle

improvements for handling infeasible points, for avoiding

Page 7: Optimization of air-conditioning system operating strategies for hot and humid climates

J.-H. Huh, M.J. Brandemuehl / Energy and Buildings 40 (2008) 1202–12131208

local minima, and for accelerating convergence by weighted

centroid calculations.

4. Results and discussion

An optimization analysis has been performed for a retail

building using a direct expansion air-conditioning system, as

described previously. The building has a design-cooling load

of 105.6 kW. The air-conditioning system has a rated COP of

3.0 and SHR of 0.7. The air handler delivers a design airflow

rate of 5663 or 53.6 L/s kW with a fan power at design flow of

8.5 kW.

The analysis uses the extended bin analysis, which

characterizes sensible and latent cooling loads as functions

of indoor and outdoor temperatures and humidities. The

analysis has been performed with the building located in

Miami, which exhibits humid weather conditions during the

summer. Weather data for Miami were obtained from typical

meteorological year (TMY) data.

The analysis is based on coincident sensible and latent loads,

which requires bin weather data for coincident temperature and

humidity. Fig. 4 shows coincident temperature and humidity

data for Miami, FL. For the purpose of this analysis, the hourly

dry-bulb temperature is organized in bins of 2.0 8C and

humidity ratio in bins of 0.002. The analysis is performed for

the months of May through September. Bins with less than 15 h

were excluded from the analysis, giving a total of 3335 h with

temperatures between 23 8C and 33 8C.

The analysis is performed at each outdoor temperature and

humidity bin, corresponding to a specific set of uncontrolled

variables, f. The optimization has been performed under several

different sets of operating conditions and constraints on indoor

Fig. 4. Coincident outdoor temperature

conditions. The following sections describe results of these

scenarios.

4.1. Base case

The base case represents typical operations in retail

buildings using rooftop air-conditioning systems. The indoor

temperature is set to 25.6 8C and the indoor relative humidity is

limited to a maximum of 55% (0.0113 humidity ratio). Supply

airflow is constant at design flow with no coil bypass. The air-

conditioning equipment operates with modulated capacity

control using 100% of the evaporator coil. As with typical

system operation, the compressor capacity fraction, ucomp, is

determined to meet the loads and the condenser fan fraction,

ucond, tracks the compressor capacity fraction. As such, there is

no optimization involved in the base case.

The results of the base case analysis are given in Fig. 5. Total

cooling energy consumption was calculated to be 122,132 kWh

for the 3335 h of the analysis. The figure also displays results

for the individual outdoor temperature and humidity bins,

showing the power and compressor fraction at each bin. As

shown in the figure, compressor power to meet the loads in each

bin increases with increasing temperature and humidity. The

figure of compressor fraction shows similar trends, ranging

between values of 0.44 and 1.0.

4.2. Variable indoor conditions within specified bounds

A zone thermostat is the most common device that controls

the operation of a commercial rooftop DX system. If humidity

is directly controlled, as in a supermarket, the control signal is

typically a dew-point sensor in the zone. If setpoints are to be

and humidity data for Miami, FL.

Page 8: Optimization of air-conditioning system operating strategies for hot and humid climates

Fig. 5. Base case results (conventional operation).

Table 1 (Continued )

Humidity Temperature (8C)

24 26 28 30 32

0.0160 1.00 1.00 1.00 1.00 1.00

0.0180 1.00 1.00 1.00 1.00 1.00

Optimal setpoint temperature

0.0100 78.00 78.00 78.00 78.00 78.00

0.0120 78.00 78.00 78.00 78.00 78.00

0.0140 78.00 78.00 78.00 78.00 78.00

0.0160 78.00 78.00 78.00 78.00 78.00

0.0180 78.00 78.00 78.00 78.00 78.00

PMV

0.0100 �0.03 �0.05 �0.06 �0.07 �0.08

0.0120 �0.02 �0.03 �0.04 �0.06 �0.07

0.0140 0.00 �0.02 �0.03 �0.04 �0.05

0.0160 0.01 0.0160 �0.01 �0.03 �0.03

0.0180 0.03 0.01 �0.01 �0.02 �0.02

Optimal compressor fraction

0.0100 0.31 0.37 0.45 0.54 0.60

0.0120 0.35 0.42 0.51 0.60 0.68

0.0140 0.48 0.48 0.57 0.66 0.77

0.0160 0.46 0.54 0.64 0.73 0.82

0.0180 0.50 0.60 0.71 0.82 0.93

Optimal bypass air fraction

0.0100 0.01 0.00 0.00 0.00 0.00

0.0120 0.00 0.00 0.00 0.00 0.00

0.0140 0.00 0.00 0.00 0.00 0.00

0.0160 0.00 0.00 0.00 0.00 0.00

0.0180 0.00 0.00 0.00 0.00 0.00

Optimal condenser fraction

0.0100 0.78 0.94 0.92 0.86 1.00

0.0120 1.00 1.00 0.94 0.90 1.00

0.0140 1.00 1.00 1.00 1.00 1.00

0.0160 1.00 1.00 1.00 1.00 1.00

0.0180 1.11 1.00 1.00 1.00 1.00

Optimal setpoint humidity ratio

0.0100 0.0092 0.0088 0.0085 0.0081 0.0077

0.0120 0.0097 0.0093 0.0090 0.0086 0.0082

0.0140 0.0101 0.0097 0.0094 0.0090 0.0086

0.0160 0.0105 0.0101 0.0098 0.0095 0.0093

J.-H. Huh, M.J. Brandemuehl / Energy and Buildings 40 (2008) 1202–1213 1209

changed, the most natural bounds for indoor conditions are dry-

bulb temperature and dew-point temperature, or humidity ratio.

The results of this section are generated by allowing the indoor

temperature to range between 22 and 26 8C and by allowing the

indoor humidity ratio to increase up to 0.012. The actual indoor

temperature and humidity are determined through optimiza-

tion, which seeks the optimal indoor conditions in conjunction

with optimal values of the five system control variables to

minimize system power consumption at each set of outdoor

temperature and humidity.

Table 1

Results for variable indoor conditions, bound temperature and humidity

Humidity Temperature (8C)

24 26 28 30 32

Relative power consumption ratio vs. Base case

0.0100 0.57 0.58 0.60 0.61 0.59

0.0120 0.60 0.61 0.63 0.65 0.65

0.0140 0.60 0.64 0.66 0.68 0.70

0.0160 0.60 0.66 0.69 0.72 0.75

0.0180 0.62 0.66 0.71 0.76 0.80

Optimal supply airflow fraction

0.0100 0.50 0.50 0.50 0.50 0.49

0.0120 0.50 0.50 0.50 0.50 0.50

0.0140 0.50 0.50 0.50 0.50 0.50

0.0160 0.50 0.50 0.50 0.51 0.55

0.0180 0.50 0.50 0.50 0.51 0.53

Optimal evaporator fraction

0.0100 1.00 1.00 1.00 1.00 1.00

0.0120 1.00 1.00 1.00 1.00 1.00

0.0140 1.00 1.00 1.00 1.00 1.00

0.0180 0.0109 0.0105 0.0102 0.0098 0.0096

Ventilation airflow: 850 L/s (15% OA design); minimum supply airflow rate:

50% of design airflow; location: Miami, FL; building type: retail store.

Total cooling energy consumption (kWh): 85,381. Saving: 30.1%.

Note: (1) 3335 h were analyzed during the cooling season (May through

September: total 3672 h)—OA conditions of low frequency occurrence (below

15 h) were excluded in this analysis.

(2) Bound of setpoint temperature: 22–26 8C.

(3) Bound of setpoint humidity ratio: 0.0044–0.0120.

Table 1 shows results for the analysis. As a seasonal

summary, total cooling energy consumption is 85,381 kWh.

This optimal operating strategy consumes 30% less energy

than the conventional operation. Comparing the power

consumption in each bin with the corresponding values in

Table 1, it can be seen the optimization reduces power

consumption at every set of outdoor conditions. The table also

shows a set of subtables that give the optimal values of each of

the seven optimized variables, which help to explain the causes

of the energy savings at each bin. Following trends are

observed:

Page 9: Optimization of air-conditioning system operating strategies for hot and humid climates

J.-H. Huh, M.J. Brandemuehl / Energy and Buildings 40 (2008) 1202–12131210

compressor fraction: increases steadily with increases in

outdoor temperature and humidity, reflecting increases in

loads.

Supply airflow fraction: stays at minimum allowable value,

giving lowest fan power and improved dehumidification,

except at highest outdoor temperatures. Notice, though, that

the airflow fraction is greater than the compressor fraction

for the lower temperatures and humidities, indicating that

the airflow per unit compressor capacity is greater than at

design conditions.

Coil bypass fraction: stays closed for all bins. It is always

more cost effective to reduce air handler supply airflow than

to bypass coil. It is uneconomical to further lower indoor

humidity by opening the bypass damper without air handler

fan savings.

Evaporator surface fraction: uses full coil surface for all

bins. It is always more cost effective to reduce air handler

supply airflow than to eliminate coil surface area.

Condenser fan fraction: always greater than the compressor

fraction, indicating that, for this system, increases in

condenser fan power are compensated by improvements

in compressor efficiency.

Fig. 6. Results for bound indoor conditi

Indoor temperature: always at the maximum allowable

temperature, giving reduced sensible load.

Indoor humidity: not always at the maximum allowable

humidity. Optimal humidity level decreases as outdoor

temperature increases, and increases as outdoor humidity

increases.

Logically, it might be expected that the optimal indoor

conditions occur at the upper bounds of space temperature and

humidity ratio, which minimize the sensible and latent loads,

respectively. However, the optimization results indicate that the

performance of the HVAC equipment can dictate lower indoor

humidity levels. In this case, the optimal humidity setpoint is

largely determined by the airflow rate. Low airflow rate reduces

SHRcap, giving a lower indoor humidity. The lower humidity

also serves to reduce the compressor efficiency and to increase

the load on the compressor. However, since supply duct

pressure is not typically controlled in packaged rooftop

equipment, decreasing the airflow rate reduces the indoor

fan energy to the cubic power. The net effect of these competing

factors gives minimum energy at the reduced airflow, which in

turn, dictates the lower indoor humidity.

ons, reduced minimum airflow rate.

Page 10: Optimization of air-conditioning system operating strategies for hot and humid climates

J.-H. Huh, M.J. Brandemuehl / Energy and Buildings 40 (2008) 1202–1213 1211

4.3. Variable indoor conditions with PMV constraint

The results of Table 1 show that the optimal indoor

conditions result in excellent comfort, giving comfort in the

range of �0.09 � PMV � 0.03. It might be argued that such

conditions are ‘‘too comfortable’’ when additional cost

savings could be achieved by relaxing the comfort

requirements.

A similar analysis has been performed in which the PMV

was bound between �0.5 � PMV � 0.5. As expected, the

optimal indoor conditions at all bins of outdoor conditions were

found to be at the upper limit of PMV = 0.5. In all cases, the

resulting indoor temperatures were approximately 1.1 8Cwarmer than those in Table 1. Optimal indoor humidities were

also slightly higher, giving almost identical SHRload to those of

Table 1. Detailed results are not presented here, since all trends

in control variables were similar. However, it is noted that the

increases in indoor temperature and humidity resulted in total

energy savings of 40% compared to the base case.

Fig. 7. Results for supermarket lo

4.4. Low minimum supply airflow

The results of Table 1 suggest that the supply airflow is the

single most important variable in determining the SHRcap and

the resulting match between equipment performance and the

sensible and latent loads of the building. However, the

constraints of that analysis limit the supply airflow to 50%

of the design airflow. Fig. 6 shows results of the analysis if the

constraint is relaxed to allow lower values of supply airflow.

Depending on outdoor conditions, the results show that the

optimal airflow fraction could be as low as 36% of design

airflow. It is further noted that the supply airflow fraction is

always less than the compressor fraction, indicating that the

airflow per unit compressor capacity is lower than the design

values.

The lower airflow rates cause a lower SHRcap, which gives a

lower indoor humidity level and increased latent load. While

the lower airflow saves fan energy, it is offset by the additional

latent load, and the net energy savings are only slightly more

ads, bound indoor conditions.

Page 11: Optimization of air-conditioning system operating strategies for hot and humid climates

J.-H. Huh, M.J. Brandemuehl / Energy and Buildings 40 (2008) 1202–12131212

than the case in which the supply airflow is constrained to be no

less than 50% of the design airflow. The minor increase in

savings indicates that the optimum is relatively ‘‘flat’’ with

respect to airflow rate in this region and suggests that a fixed

airflow rate of 50% design flow is nearly optimal.

4.5. Supermarket loads

The previous results are all based on a single load

relationship that represents sensible and latent loads for a

typical retail store. In general, retail store loads are

characterized as dominated by internal loads associated with

lights and occupancy. As shown in Fig. 4, there is a large

sensible load even when the outdoor temperature is below the

indoor temperature. As a result, the SHRload is relatively high

due to the large sensible component. By comparison, super-

market loads have much lower SHRload because of the cooling

effects of the refrigerated cases. It is not uncommon for a

supermarket to require dehumidification without a need for

cooling.

Fig. 7 shows the results of an optimization analysis for the

supermarket load characteristics. The analysis has been

performed with bounded indoor conditions having a slightly

tighter humidity control requirement. Like the retail store

analysis, the temperature is bound between 22 and 26 8C, but

the zone humidity ratio is limited to be lower than 0.0102.

(Zone humidity levels are often controlled to levels as low as

40% RH to save energy on the refrigeration system.) The

supply airflow rate has also been limited to no less than 50% of

the design airflow.

The most significant difference between the retail and

supermarket results is that, when the outdoor temperature is

below 29.4 8C, the HVAC equipment is unable to meet the latent

load without overcooling the zone air. The zone air temperature

drops to as low as 22.4 8C and the optimal humidity ratio is fixed

at the upper allowable value. Under these conditions, there is also

an incentive to exercise control over the coil bypass and the

evaporator coil area fraction. In the most extreme case of outdoor

conditions of 23.9 8C and 0.012 humidity ratio, the compressor is

operating at a part-load ratio of 14%, the supply fan airflow is

fixed at 50% of design airflow to ensure adequate circulation, and

74% of the supply air is bypassed around the cooling coil. Notice,

though, that the combination of the control actions results in

about 13% of the design airflow over the coil to accompany the

14% compressor part-load operation.

5. Summary and conclusions

This paper describes the methods and results of an

optimization of HVAC system controls to minimize energy

use while maintaining comfort, with a special emphasis on the

control of humidity in commercial buildings. The analysis has

been based on realistic modeling of a DX air-conditioning

system coupled with techniques for constrained direct-search

optimization. Loads have been linked to indoor and outdoor

conditions through an extended bin method. Results have been

presented for a range of outdoor conditions and load features,

and with a variety of constraints on comfort conditions and

system operation.

The results of the analysis indicate that significant energy

savings are available through optimization. The most sig-

nificant factors affecting operation are the interactions between

the compressor capacity control and the air handler fan control.

Coil bypass and evaporator circuiting control are only

appropriate to avoid overcooling. For the particular systems

considered, it was generally advantageous to operate with high

condenser fan fraction.

The results of the optimization also indicated that it is often

desirable to operate at indoor humidity levels that are below the

maximum allowed for comfort. While the lower indoor

humidity increases the load on the HVAC system, the design

of the equipment dictates that there would be a greater penalty

in fan power to operate the system at the higher SHRcap. In

contrast, the results indicate that it is almost always optimal to

operate at the highest allowable indoor temperature within

comfort constraints. The only exception is if the equipment

cannot meet the latent load without overcooling.

The results of the analysis suggest the following guidelines

for near-optimal operation of DX HVAC equipment to meet

both sensible and latent loads in hot and humid climates.

� C

ompressor capacity fraction is the primary control variable

for meeting loads over a wide range of outdoor conditions.

� F

or this system in which the condenser fan power is

proportional to the airflow fraction, the condenser fan airflow

fraction is optimal at about twice the compressor capacity

fraction. Optimal condenser airflow increases with reductions

in air handler airflow.

� O

ptimal airflow rates are generally between 33.5 and 46.9 L/s

kW. However, the minimum is relatively flat.

� C

oil air bypass is only appropriate if overcooling would

otherwise result because the HVAC system could not meet the

latent load at minimum air handler airflow. It is always more

economical to reduce airflow, if possible.

� T

here is no advantage to explicitly controlling indoor

humidity to a specific setpoint. Rather, allow humidity to

float below a maximum, dictated by the equipment

performance at the controlled air handler airflow.

As with most research, the results also ask additional

questions. The results were generated for two building types in a

single location with a single HVAC system, with a particular set

of compressor, condenser, and evaporator, and a particular set of

compressor and fan power characteristics. However, a packaged

rooftop DX system is commodity HVAC equipment and there is

considerable similarity in the performance among systems,

especially at typical efficiency levels. The relationship between

the building application, load details, and location climate will

clearly have an impact on the specific results. However, results at

selected additional locations in the hot and humid regions of the

southeastern US show similar trends in optimal operating

strategies. In locations with more temperate or dry climates, it is

not clear that the same strategies for supply airflow operation will

be optimal. Ideally, it would be possible to perform the

Page 12: Optimization of air-conditioning system operating strategies for hot and humid climates

J.-H. Huh, M.J. Brandemuehl / Energy and Buildings 40 (2008) 1202–1213 1213

optimization on-line with a data-driven inverse model that

characterizes the installed performance of the specific system.

Perhaps the most significant restriction is that the work was

performed for a DX system. It is not clear that similar trends

will be observed with chilled water systems.

References

[1] Y.P. Ke, S.A. Mumma, Optimized supply-air temperature (SAT) in vari-

able-air-volume (VAV) systems, Energy 22 (6) (1997) 601–614.

[2] F. Engdahl, D. Johansson, Optimal supply air temperature with respect to

energy use in a variable air volume system, Energy and Buildings 36 (3)

(2004) 205–218.

[3] L. Song, M. Liu, Optimal outside airflow control of an integrated air-

handling unit system for large office buildings, Journal of Solar Energy

Engineering 126 (2004) 614–619.

[4] D.B. Shirey III, Demonstration of efficient humidity control techniques at

an art museum, ASHRAE Transactions 99 (1) (1993) 93–102.

[5] M.J. Brandemuehl, M. Khattar, Dehumidification performance of air-

conditioning systems in supermarkets, EPRI Report TR-106065, Palo

Alto, CA, Electric Power Research Institute, 1996.

[6] D.R. Kosar, et al., Dehumidification issues of standard 62-1989, ASHRAE

Journal 40 (3) (1998) 71–75.

[7] S.A. Mumma, Designing dedicated outdoor air systems, ASHRAE Journal

43 (5) (2001) 28–31.

[8] J. Murphy, Dehumidification performance of HVAC systems, ASHRAE

Journal 44 (3) (2002) 23–28.

[9] M.K. Khattar, Seperating the V in HVAC: a dual-path approach, ASHRAE

Journal 44 (5) (2002) 37–42.

[10] L.G. Harriman III, J. Judge, Dehumidification equipment advances,

ASHRAE Journal 44 (8) (2002) 22–29.

[11] L.R. Whitmer, Minimizing space energy requirements subject to

thermal comfort conditions, ASHRAE Journal 18 (6) (1976) 48–

51.

[12] H.I. Henderson Jr., K. Rengarajan, D.B. Shirey III, The impact of comfort

control on air conditoner energy use in humid climates, ASHRAE

Transactions 98 (2) (1992) 104–113.

[13] P. Mazzei, F. Minichiello, D. Palma, HVAC dehumidification systems for

thermal comfort: a critical review, Applied Thermal Engineering 25

(2005) 677–707.

[14] J.H. Huh, Optimal air-conditioning system operating strategies for com-

bined temperature and humidity control in buildings, Ph.D. Thesis,

University of Colorado at Boulder, 1995.

[15] ARI, ARI Standard 540-1999 Positive Displacement Refrigerant Com-

pressors and Compressor Equipment, Arlington, VA, Air-Conditioning &

Refrigeration Institute, 1999.

[16] T.H. Kuehn, J.W. Ramsey, J.L. Threlked, Thermal Environmental

Engineering, third ed., Prentice-Hall Inc., 1998.

[17] M.J. Brandemuehl, S. Gabel, I. Andresen, HVAC 2 Toolkit: Algorithms

and Subroutines for Secondary HVAC System Energy Calculations,

American Society of Heating, Refrigerating, and Air-Conditioning Engi-

neers, Inc., Atlanta, 1993.

[18] D. Knebel, Simplified Energy Analysis Using the Modified Bin Method,

American Society of Heating, Refrigerating, and Air-Conditioning Engi-

neers, Inc., Atlanta, 1985.

[19] ASHRAE, ASHRAE Handbook—Fundamentals, American Society of

Heating, Refrigerating, and Air-Conditioning Engineers, Inc., Atlanta,

2005.

[20] M.J. Box, A new method of constrained optimization and comparison with

other methods, Computer Journal 8 (1965) 42–52.

[21] R.R. Hughes, Mathematical models for process design optimization,

AIChE Today Series Notes (1972).

[22] R.K. Malik, Optimal design of flexible chemical processes, Ph.D. Thesis,

University of Wisconsin at Madison, 1979.