1 © 2016 MITSUBISHI HEAVY INDUSTRIES, LTD. All Rights Reserved. © 2016 MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS , LTD. All Rights Reserved. 15 th Dec 2016 Optimal centrifugal chiller system for the middle east region considering the climate and the cooling load.

Upload: others

Post on 26-Aug-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Optimal centrifugal chiller system for the middle east ... · 2.3 GCC Region 3. Climate Condition and Characteristic of Cooling Load 3.1 Dry-bulb temp 3.2 Wet-bulb temp 3.3 Cooling

1© 2016 MITSUBISHI HEAVY INDUSTRIES, LTD. All Rights Reserved.© 2016 MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS , LTD. All Rights Reserved.

15th Dec 2016

Optimal centrifugal chiller system for the middle east region considering the climate and the cooling load.

Page 2: Optimal centrifugal chiller system for the middle east ... · 2.3 GCC Region 3. Climate Condition and Characteristic of Cooling Load 3.1 Dry-bulb temp 3.2 Wet-bulb temp 3.3 Cooling

2© 2016 MITSUBISHI HEAVY INDUSTRIES, LTD. All Rights Reserved.© 2016 MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD. All Rights Reserved. 2

1. Introduction

1.1 Trend of District Cooling Plant in GCC Region

1.2 Issue for DHC Plant in GCC Region

2. Experiences of District Heating and Cooling

2.1 Tokyo

2.2 South East Asia

2.3 GCC Region

3. Climate Condition and Characteristic of Cooling Load

3.1 Dry-bulb temp 3.2 Wet-bulb temp 3.3 Cooling water temp

3.4 Cooling Load

4. Basic design for DC plant in GCC

4.1 Chiller design for DC plant in GCC

4.2 Plant Specification

4.3 Optimal Control System

4.4 Annual Energy Consumption Results and Consideration

5. Conclusion

Contents

Page 3: Optimal centrifugal chiller system for the middle east ... · 2.3 GCC Region 3. Climate Condition and Characteristic of Cooling Load 3.1 Dry-bulb temp 3.2 Wet-bulb temp 3.3 Cooling

3© 2016 MITSUBISHI HEAVY INDUSTRIES, LTD. All Rights Reserved.© 2016 MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD. All Rights Reserved. 3

1. Introduction

Page 4: Optimal centrifugal chiller system for the middle east ... · 2.3 GCC Region 3. Climate Condition and Characteristic of Cooling Load 3.1 Dry-bulb temp 3.2 Wet-bulb temp 3.3 Cooling

4© 2016 MITSUBISHI HEAVY INDUSTRIES, LTD. All Rights Reserved.© 2016 MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD. All Rights Reserved. 4

1.1 Trend of District Cooling Plant in GCC Region

1. High DC plant demand in GCC1

Total capacity of DC plants in UAE, KSA and Qatar is 29% of the world in 2014.

2. Further growth of DC plant marketLarge capacity DC plants have been

constructed and under development in

GCC region. The DC plants in the region

will be 30 million RT until 20302.

3. Large capacity of DC plant.Scale of new DC plants is much larger than

conventional plants, like Madinah Hajj City

and Makkah.

1)UAE, Bahrain, Kuwait, Oman, Qatar, KSA.

The value includes the value of UAE, KSA, Qatar and Iran.

2) 4th Annual District Cooling Saudi Arabia Summit , Sep 2013.Fig1.Estimated cooling capacity of DC plant in GCC region

Page 5: Optimal centrifugal chiller system for the middle east ... · 2.3 GCC Region 3. Climate Condition and Characteristic of Cooling Load 3.1 Dry-bulb temp 3.2 Wet-bulb temp 3.3 Cooling

5© 2016 MITSUBISHI HEAVY INDUSTRIES, LTD. All Rights Reserved.© 2016 MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD. All Rights Reserved. 5

1.2 Issue for DC Plant in GCC Region

Design & method of operation for DC plant should be optimized to suit the climate

and the characteristic of cooling load in each region. The technologies would

reduce both capital and operating expenditure of the DC plants.

1. Optimal method for operating expenditureA operation method should be based on actual site condition in each region. Following

method would reduce the expenditure for DC plants.

1.1 Chiller number control: Operate chiller in efficient and high performance range

1.2 Control flow rate of chilled water variably

1.3 Control flow rate of cooling water variably

2. Optimal design for capital expenditureFollowing design for chiller and DC plant would reduce the expenditure.

2.1 Use large capacity chiller with 3,000 RT or more

2.2 Reduce footprint for large capacity chiller without cooling capacity

2.3 Reduce total chiller number installed in each DC plant

We have considered DC plant design and operation by using these methods in

Japan, Singapore and GCC region.

Page 6: Optimal centrifugal chiller system for the middle east ... · 2.3 GCC Region 3. Climate Condition and Characteristic of Cooling Load 3.1 Dry-bulb temp 3.2 Wet-bulb temp 3.3 Cooling

6© 2016 MITSUBISHI HEAVY INDUSTRIES, LTD. All Rights Reserved.© 2016 MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD. All Rights Reserved. 6

2. Experiences

of District Heating and Cooling

Page 7: Optimal centrifugal chiller system for the middle east ... · 2.3 GCC Region 3. Climate Condition and Characteristic of Cooling Load 3.1 Dry-bulb temp 3.2 Wet-bulb temp 3.3 Cooling

7© 2016 MITSUBISHI HEAVY INDUSTRIES, LTD. All Rights Reserved.© 2016 MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD. All Rights Reserved. 7

2.1 Tokyo

1. Climate and operation

(1)Humid summer, cold winter

(2)Chilled water supply throughout the year, and

steam supply in winter for offices, hotels and so on

(3)Ice storage at night because of high electrical bills

($0.15 – 0.16/kWh)2

2. Commercial Operation: since April, 2003

3. Supply Capability

Chilled Water: 16,800 RT Steam: 71.3 t/h

4. Main Units

(1)Chilled Water Supply

Absorption Chiller: 2,500 RT×4, 850RT×2

Centrifugal Chiller: 900 RT×3

Ice Storage Bath : 5,700 RTH×3

(2) Steam Supply

Steam boiler: 15 t/h×3, 9.6 t/h×1

Exhaust heat boiler: 8.35 t/h×2

DHC Plant in Tokyo, Shinagawa Station-East Area1

1) http://www.jdhc.or.jp/article/%E5%93%81%E5%B7%9D%E9

%A7%85%E6%9D%B1%E5%8F%A3/

2) http://www.tepco.co.jp/ep/corporate/plan_h/plan06.html

Fig3.Appearance of Shinagawa Station-East Area

Our headquarters!

Page 8: Optimal centrifugal chiller system for the middle east ... · 2.3 GCC Region 3. Climate Condition and Characteristic of Cooling Load 3.1 Dry-bulb temp 3.2 Wet-bulb temp 3.3 Cooling

8© 2016 MITSUBISHI HEAVY INDUSTRIES, LTD. All Rights Reserved.© 2016 MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD. All Rights Reserved. 8

2.2 South East Asia

Marina Bay Sands, in Singapore

1. Climate and operation

(1)Humid summer throughout the year

(2)Chilled water supply for offices, hotels

and so on.

(3)Ice storage at night because

of High electrical bills ($0.08 – 0.13/kWh)2

2. Commercial Operation

since July, 2005

3. Supply Capability: 43,531 RT

4. Main Units

Centrifugal chiller: 3,697 RT×2 (ice storage)

2,844 RT×11(5, ice storage)

2,000 RT×2

853 RT×1

Fig4. Appearance of Marina Bay Sands1

1) http://www.mhi.co.jp/discover/graph/inquiry/no169.html

2) http://www.nna.jp/articles/show/20160401spd011A

Page 9: Optimal centrifugal chiller system for the middle east ... · 2.3 GCC Region 3. Climate Condition and Characteristic of Cooling Load 3.1 Dry-bulb temp 3.2 Wet-bulb temp 3.3 Cooling

9© 2016 MITSUBISHI HEAVY INDUSTRIES, LTD. All Rights Reserved.© 2016 MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD. All Rights Reserved. 9

2.3 GCC Region

Madinah Hajj City Project, in KSA

In this presentation, we have considered the optimal design and operation for the

three places (Tokyo, Singapore and Madinah Hajj), Makkah in KSA, Lusail in Qatar and

Dubai on the basis of the following conditions

(1) Target area: Tokyo, Singapore, Madinah Hajj, Makkah, Lusail, Dubai

(2) Climate condition: Outside air temperature of 3 hours on behalf every month

(3) Cooling capacity of DC plant: 30,000 RT

(4) Chiller select: 5,000 RT, PL unit.

Fig5. Appearance of Madinah Hajj City Project1

1. Climate and operation

(1)Hot summer and relative warm climate

throughout the year

(2)Chilled water supply for offices, hotels and so on.

Electrical bills ($0.04 – 0.08/kWh)2

2. Commercial Operation: since 2018

3. Supply Capability: 200,000 RT

4.Main Units

Centrifugal Chiller: 2,500 RT,VSD×80

1) https://www.thebig5hub.com/news/2016/january/in-pictures-top-10-projects-in-makkah-and-madinah/ 2)http://www.nna.jp/articles/show/20160401spd011A

Page 10: Optimal centrifugal chiller system for the middle east ... · 2.3 GCC Region 3. Climate Condition and Characteristic of Cooling Load 3.1 Dry-bulb temp 3.2 Wet-bulb temp 3.3 Cooling

10© 2016 MITSUBISHI HEAVY INDUSTRIES, LTD. All Rights Reserved.© 2016 MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD. All Rights Reserved. 10

3. Climate Condition

and Characteristic of Cooling Load

Page 11: Optimal centrifugal chiller system for the middle east ... · 2.3 GCC Region 3. Climate Condition and Characteristic of Cooling Load 3.1 Dry-bulb temp 3.2 Wet-bulb temp 3.3 Cooling

11© 2016 MITSUBISHI HEAVY INDUSTRIES, LTD. All Rights Reserved.© 2016 MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD. All Rights Reserved. 11

3.1 Dry-Bulb Temperature

0

5

10

15

20

25

30

35

40

45

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Out

side

air t

empe

ratu

re(℃

)

Time(h)

JAN. FEB MAR APR MAY JUNJUL AUG SEP OCT NOV DEC

0

5

10

15

20

25

30

35

40

45

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Out

side

air t

empe

ratu

re(℃

)

Time(h)

JAN. FEB MAR APR MAY JUNJUL AUG SEP OCT NOV DEC

0

5

10

15

20

25

30

35

40

45

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Out

side

air t

empe

ratu

re(℃

)

Time(h)

JAN FEB MAR APR MAY JUNJUL AUG SEP OCT NOV DEC

Makkah

0

5

10

15

20

25

30

35

40

45

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Out

side

air t

empe

ratu

re(℃

)

Time(h)

JAN. FEB MAR APR MAY JUNJUL AUG SEP OCT NOV DEC

0

5

10

15

20

25

30

35

40

45

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Out

side

air t

empe

ratu

re(℃

)

Time(h)

JAN. FEB MAR APR MAY JUNJUL AUG SEP OCT NOV DEC

0

5

10

15

20

25

30

35

40

45

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Out

side

air t

empe

ratu

re(℃

)

Time(h)

JAN. FEB MAR APR MAY JUNJUL AUG SEP OCT NOV DEC

Tokyo

Singapore

Madinah

Lusail Dubai

※Weather data source : World Weather Online Using the Outside air temperature of 3 hours on behalf every month. Number of statistics: 8 per month×12=96

Although GCC countries are the highest temperature level that we have never

experienced in Japan . But the experience of Singapore must be useful, and the

temperature difference throughout the year in Tokyo is able to take advantage for the

design and method of operation

Fig.6 Dry - Bulb Temperature

Page 12: Optimal centrifugal chiller system for the middle east ... · 2.3 GCC Region 3. Climate Condition and Characteristic of Cooling Load 3.1 Dry-bulb temp 3.2 Wet-bulb temp 3.3 Cooling

12© 2016 MITSUBISHI HEAVY INDUSTRIES, LTD. All Rights Reserved.© 2016 MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD. All Rights Reserved. 12

3.2 Wet-Bulb Temperature

0

5

10

15

20

25

30

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Wet

bul

b te

mp(

℃)

Time(h)

JAN. FEB MAR APR MAY JUNJUL AUG SEP OCT NOV DEC

0

5

10

15

20

25

30

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Wet

bul

b te

mp(

℃)

Time(h)

JAN. FEB MAR APR MAY JUNJUL AUG SEP OCT NOV DEC

0

5

10

15

20

25

30

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Wet

bul

b te

mp(

℃)

Time(h)

JAN FEB MAR APR MAY JUNJUL AUG SEP OCT NOV DEC

0

5

10

15

20

25

30

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Wet

bul

b te

mp(

℃)

Time(h)

JAN. FEB MAR APR MAY JUNJUL AUG SEP OCT NOV DEC

0

5

10

15

20

25

30

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Wet

bul

b te

mp(

℃)

Time(h)

JAN. FEB MAR APR MAY JUNJUL AUG SEP OCT NOV DEC

※Weather data source : World Weather Online Using the Wet-bulb temperature of 3 hours on behalf every month. Number of statistics: 8 per month×12=96

0

5

10

15

20

25

30

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Wet

bul

b te

mp(

℃)

Time(h)

JAN. FEB MAR APR MAY JUNJUL AUG SEP OCT NOV DEC

Makkah

Tokyo

Singapore Madinah

Lusail Dubai

Fig.7 Wet-Bulb Temperature

Wet-bulb temperature of GCC countries is less than that of Singapore.

the fluctuation range is small enough.

Page 13: Optimal centrifugal chiller system for the middle east ... · 2.3 GCC Region 3. Climate Condition and Characteristic of Cooling Load 3.1 Dry-bulb temp 3.2 Wet-bulb temp 3.3 Cooling

13© 2016 MITSUBISHI HEAVY INDUSTRIES, LTD. All Rights Reserved.© 2016 MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD. All Rights Reserved. 13

3.3 Cooling Water Temperature

0

5

10

15

20

25

30

35

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Coo

ling

wat

er in

let

tem

pera

ture

(℃)

Time(h)

JAN FEB MAR APR MAY JUNJUL AUG SEP OCT NOV DEC

0

5

10

15

20

25

30

35

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Coo

ling

wat

er in

let

tem

pera

ture

(℃)

Time(h)

JAN. FEB MAR APR MAY JUNJUL AUG SEP OCT NOV DEC

0

5

10

15

20

25

30

35

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Coo

ling

wat

er in

let

tem

pera

ture

(℃)

Time(h)

JAN. FEB MAR APR MAY JUNJUL AUG SEP OCT NOV DEC

0

5

10

15

20

25

30

35

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Coo

ling

wat

er in

let

tem

pera

ture

(℃)

Time(h)

JAN. FEB MAR APR MAY JUNJUL AUG SEP OCT NOV DEC

0

5

10

15

20

25

30

35

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Coo

ling

wat

er in

let

tem

pera

ture

(℃)

Time(h)

JAN. FEB MAR APR MAY JUNJUL AUG SEP OCT NOV DEC

※Weather data source : World Weather Online Using the Cooling water inlet temperature of 3 hours on behalf every month. Number of statistics: 8 per month×12=96

0

5

10

15

20

25

30

35

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Coo

ling

wat

er in

let

tem

pera

ture

(℃)

Time(h)

JAN. FEB MAR APR MAY JUNJUL AUG SEP OCT NOV DEC

Makkah

Tokyo Singapore Madinah

Lusail Dubai

Fig.8 Cooling Water Temperature

Cooling water temperature changes widely in Japan through a year.

In Singapore it is almost constant.

In Madinah, Makkah, Lusail and Dubai it is narrow.

Page 14: Optimal centrifugal chiller system for the middle east ... · 2.3 GCC Region 3. Climate Condition and Characteristic of Cooling Load 3.1 Dry-bulb temp 3.2 Wet-bulb temp 3.3 Cooling

14© 2016 MITSUBISHI HEAVY INDUSTRIES, LTD. All Rights Reserved.© 2016 MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD. All Rights Reserved. 14

3.4 Cooling Load

※Using the Cooling load of 3 hours on behalf every month. Peak load:30,000USRt

0

5000

10000

15000

20000

25000

30000

35000

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Cap

acity(

USR

t)

Time(h)

JAN FEB MAR APR MAY JUNJUL AUG SEP OCT NOV DEC

0

5000

10000

15000

20000

25000

30000

35000

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Cap

acity(

USR

t)

Time(h)

JAN FEB MAR APR MAY JUNJUL AUG SEP OCT NOV DEC

0

5000

10000

15000

20000

25000

30000

35000

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Cap

acity(

USR

t)

Time(h)

JAN FEB MAR APR MAY JUNJUL AUG SEP OCT NOV DEC

0

5000

10000

15000

20000

25000

30000

35000

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Cap

acity(

USR

t)

Time(h)

JAN FEB MAR APR MAY JUNJUL AUG SEP OCT NOV DEC

0

5000

10000

15000

20000

25000

30000

35000

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Cap

acity(

USR

t)

Time(h)

JAN FEB MAR APR MAY JUNJUL AUG SEP OCT NOV DEC

0

5000

10000

15000

20000

25000

30000

35000

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Cap

acity(

USR

t)

Time(h)

JAN FEB MAR APR MAY JUNJUL AUG SEP OCT NOV DEC

Makkah

Tokyo Singapore Madinah

Lusail Dubai

Fig.9 Cooling Load (24h×12month)

In Japan, Load fluctuation is a large at daytime and small at night time.

In Singapore, Medina, Mecca, Lusail and Dubai, these load characteristics

are similar

Page 15: Optimal centrifugal chiller system for the middle east ... · 2.3 GCC Region 3. Climate Condition and Characteristic of Cooling Load 3.1 Dry-bulb temp 3.2 Wet-bulb temp 3.3 Cooling

15© 2016 MITSUBISHI HEAVY INDUSTRIES, LTD. All Rights Reserved.© 2016 MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD. All Rights Reserved. 15

4. Basic design for DC plant in GCC

Page 16: Optimal centrifugal chiller system for the middle east ... · 2.3 GCC Region 3. Climate Condition and Characteristic of Cooling Load 3.1 Dry-bulb temp 3.2 Wet-bulb temp 3.3 Cooling

16© 2016 MITSUBISHI HEAVY INDUSTRIES, LTD. All Rights Reserved.© 2016 MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD. All Rights Reserved. 16

4.1 Chiller design for DC plant in GCC

1.We suggest 3 concepts of chiller design for DC plant in GCC to reduce capital expenditure.

(1). Large capacity, more than 3,000 RT

(2). Small footprint with the large capacity chiller

(3). High performance chiller even under the GCC condition

2.We suggest 3 solutions in order to meet the above concepts.

(1). Big capacity compressor apply for the chiller

(2). Dabble compressors on one chiller, Parallel unit.

(3). Series-Counter flow configuration by one Parallel unit or two units.

Larger capacity chillers and the smaller footprint should be selected to be less the plant

building cost.

3. Optimal control system

The optimal operation system controls the number of chiller, chilled water flow and cooling

water flow to reduce the operation expenditure in accordance with the cooling water

temperature and the cooling load. Reduction of the operation cost will be huge by using the

optimal operation.

Page 17: Optimal centrifugal chiller system for the middle east ... · 2.3 GCC Region 3. Climate Condition and Characteristic of Cooling Load 3.1 Dry-bulb temp 3.2 Wet-bulb temp 3.3 Cooling

17© 2016 MITSUBISHI HEAVY INDUSTRIES, LTD. All Rights Reserved.© 2016 MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD. All Rights Reserved. 17

4.2 Plant specification

Page 18: Optimal centrifugal chiller system for the middle east ... · 2.3 GCC Region 3. Climate Condition and Characteristic of Cooling Load 3.1 Dry-bulb temp 3.2 Wet-bulb temp 3.3 Cooling

18© 2016 MITSUBISHI HEAVY INDUSTRIES, LTD. All Rights Reserved.© 2016 MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD. All Rights Reserved. 18

FSD VSD

30,000 30,000

5,000 5,0006 6

3,498 3,4985.0 5.0

13/4.4 13/4.4

1,655 1,655

53.4 53.413.0 13.090 90

35/43.5 35/43.5

2,107.8 2,107.8

31.0 31.020.0 20.0200 200

DC plant capacity(USRt)

Capacity(USRt)

Cooling water pump power(kW)

Model No.

Unit nuber

Power Input(kW)

Pump head(mAq)

Rated COP

Evaporator pressure drop(kPa)

Chilled water pump power(kW)

Condenser pressure drop(kPa)

Chilled water(℃)

Cold water flow rate(m3/h)

Cooling water(℃)

Cooling water flow rate(m3/h)

Pump head(mAq)

※1 FSD:Fixed Speed Drive chiller, VSD:Variable Speed Drive chiller

※2 Chilled water pump head=Head loss of straight pipe+Piping fittings,

valves and others+Strainer(3mAq)+Control valve(3mAq)+Head loss and flow rate of Evaporator

※3 Cooling water pump head=Head loss of straight pipe+Piping fittings,

valves and others+Strainer(3mAq)+Control valve(3mAq)+Open-type cooling tower(10mAq)+Head loss and flow rate of Condenser

※1 ※1

※2 ※2

※3 ※3

Following table shows specifications of chillers with FSD and VSD

4.2.1 Chiller Specifications for 30kRT Plant

Table.1 Specifications of chiller

Low pressure drop

Low pressure drop

Large capacity

Large temperature

difference

High performance

Page 19: Optimal centrifugal chiller system for the middle east ... · 2.3 GCC Region 3. Climate Condition and Characteristic of Cooling Load 3.1 Dry-bulb temp 3.2 Wet-bulb temp 3.3 Cooling

19© 2016 MITSUBISHI HEAVY INDUSTRIES, LTD. All Rights Reserved.© 2016 MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD. All Rights Reserved. 19

4.2.2 Part Load Performances

0

2

4

6

8

10

12

14

16

18

0 20 40 60 80 100 120

CO

P(-

)

Cooling Capacity(%)

Estimated Part Load Performance Curve

35℃

31℃

27℃23℃

19℃

15℃

12℃

0

2

4

6

8

10

12

14

16

18

0 20 40 60 80 100 120

CO

P(-

)

Cooling Capacity ( % )

Estimated Part Load Performance Curve

19℃

15℃

31℃

12℃

35℃

27℃

23℃

High performance characteristic in actual operation range

Fig.10 Part load performance curve

FSD VSD

Page 20: Optimal centrifugal chiller system for the middle east ... · 2.3 GCC Region 3. Climate Condition and Characteristic of Cooling Load 3.1 Dry-bulb temp 3.2 Wet-bulb temp 3.3 Cooling

20© 2016 MITSUBISHI HEAVY INDUSTRIES, LTD. All Rights Reserved.© 2016 MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD. All Rights Reserved. 20

4.2.3 Optimal control for PL type

35 4.72 4.90 5.03 5.14 5.20 5.23 5.23 5.20 5.14 5.08 4.9934 4.81 4.99 5.13 5.24 5.31 5.34 5.33 5.31 5.25 5.18 5.1032 5.15 5.23 5.34 5.46 5.53 5.56 5.56 5.54 5.49 5.42 5.3330 5.56 5.63 5.67 5.69 5.76 5.80 5.81 5.78 5.74 5.67 5.5828 6.02 6.09 6.12 6.13 6.12 6.10 6.07 6.05 6.00 5.93 5.8726 6.57 6.62 6.64 6.63 6.61 6.58 6.54 6.49 6.43 6.36 6.2824 7.20 7.24 7.24 7.23 7.19 7.15 7.09 7.02 6.94 6.85 6.7522 7.96 7.98 7.96 7.93 7.87 7.81 7.73 7.63 7.53 7.42 7.2920 8.88 8.87 8.83 8.77 8.69 8.59 8.48 8.36 8.22 8.07 7.9118 10.01 9.97 9.89 9.80 9.68 9.54 9.39 9.22 9.04 8.84 8.6316 11.45 11.36 11.23 11.07 10.90 10.70 10.48 10.25 10.00 9.73 9.45

50 55 60 65 70 75 80 85 90 95 100

Coolin

g w

ate

r in

let te

mp

.(℃

)

Higher COP value is shown at each condition, cooling load and cooling water

temperature in Fig.11, comparing with performance between FSD and VSD.

VSD is better performance in low cooling water temperature.

FSD is better performance in high cooling water temperature and high

cooling load

※1 FSD:Fixed Speed Drive chiller, VSD:Variable Speed Drive chiller

Fig.11 COP Comparison between VSD and FSD

Tokyo

Singapore

Madinah Dubai, Makkah, Lusail

FSD / VSD

Cooling load.(%)

Page 21: Optimal centrifugal chiller system for the middle east ... · 2.3 GCC Region 3. Climate Condition and Characteristic of Cooling Load 3.1 Dry-bulb temp 3.2 Wet-bulb temp 3.3 Cooling

21© 2016 MITSUBISHI HEAVY INDUSTRIES, LTD. All Rights Reserved.© 2016 MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD. All Rights Reserved. 21

4.2.4 Comparison of the Unit Layout

Footprint of 2 single units is about the same of a parallel unit in the case of our chillers.

Fig.13 Installation Area 117m2

10.3m

11.5

m

19.5m

5.0

m

Fig.12 Installation Area 118m2

Series counter flow by 2 single units

5000RT

Series counter flow by a parallel unit

5000RT

Page 22: Optimal centrifugal chiller system for the middle east ... · 2.3 GCC Region 3. Climate Condition and Characteristic of Cooling Load 3.1 Dry-bulb temp 3.2 Wet-bulb temp 3.3 Cooling

22© 2016 MITSUBISHI HEAVY INDUSTRIES, LTD. All Rights Reserved.© 2016 MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD. All Rights Reserved. 22

4.2.5 Plant Layout

30.4m

19.3

m

Chiller water inlet Chiller water outlet

Cooling water outlet Cooling water inlet

5,000RT

The layout shows the minimum area for 30kRT plant

with 6 parallel centrifugal chillers.

Tube

cleaning area

Fig.14 Plant Layout

Tube

cleaning area

Tube

cleaning area

Fig.15 Outline of 5kRT chiller

Page 23: Optimal centrifugal chiller system for the middle east ... · 2.3 GCC Region 3. Climate Condition and Characteristic of Cooling Load 3.1 Dry-bulb temp 3.2 Wet-bulb temp 3.3 Cooling

23© 2016 MITSUBISHI HEAVY INDUSTRIES, LTD. All Rights Reserved.© 2016 MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD. All Rights Reserved. 23

4.3 Optimal control system

Page 24: Optimal centrifugal chiller system for the middle east ... · 2.3 GCC Region 3. Climate Condition and Characteristic of Cooling Load 3.1 Dry-bulb temp 3.2 Wet-bulb temp 3.3 Cooling

24© 2016 MITSUBISHI HEAVY INDUSTRIES, LTD. All Rights Reserved.© 2016 MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD. All Rights Reserved. 24

・・・・・

4.3.1 Outline of control items

The optimal control system is able to control six items of following (1) –(6) in Fig.16

show the system diagram.

The In this presentation, COP and system COP were calculated in consideration of

(1) Multiple chiller control, (2) Chilled water variable flow control and (3) Cooling water variable

flow control.

Cooling Tower

Cooling Water Pump

Chiller

Chilled Water Pump

Cooling Water Inlet

Cooling Water Outlet

Chilled Water Outlet

Chilled Water Inlet

(1) Multiple chiller control

(2) Chilled water

variable flow control

Water supply Header

(3) Cooling water

variable flow control

(5) Cooling water

bypass valve control

(6) Chilled water bypass valve control

(4) Cooling tower

operation control

The parallel

series counter flow

chillers, chilled

water pumps and

cooling water

pumps are installed

on same floor.

Cooling towers

are on the top

Fig.16 Diagram of the DC plant

Page 25: Optimal centrifugal chiller system for the middle east ... · 2.3 GCC Region 3. Climate Condition and Characteristic of Cooling Load 3.1 Dry-bulb temp 3.2 Wet-bulb temp 3.3 Cooling

25© 2016 MITSUBISHI HEAVY INDUSTRIES, LTD. All Rights Reserved.© 2016 MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD. All Rights Reserved. 25

4.3.2 Multiple Chiller Control

Optimal load area

FSD VSD Inlet temp of cooling water

Optimal load area

Fig.17 Optimal load range of FSD and VSD

(1) An Optimal load range is unique to each cooling water temperature in case of VSD, and to each chiller. The range is able to be calculated and transmitted to the control system via the operating box of the chiller. An Optimal range is around maximum load for FSD.

冷却水流量

Co

olin

g W

ate

r F

low

ra

te

Rated

Min

Chiller Operation Load

a

■Cooling Tower

■Cooling Water Pump

■ChillerEnerg

y c

onsum

ption

Value of Cooling Water Flow (%)

b

Optimal flow rate for

cooling water pump

Fig.18 Cooling water variable flow control

(2)Adequate chilled water flow minimizes (6) bypass flow between the inlet and outlet header.(3)An Optimal flow range of cooling water is decided by the cooling load in Fig.18-a, and ,minimize the

energy consumption (Fig.18-b)

Inlet temp of cooling

water

Cooling Load (%) Cooling Load (%)

Page 26: Optimal centrifugal chiller system for the middle east ... · 2.3 GCC Region 3. Climate Condition and Characteristic of Cooling Load 3.1 Dry-bulb temp 3.2 Wet-bulb temp 3.3 Cooling

26© 2016 MITSUBISHI HEAVY INDUSTRIES, LTD. All Rights Reserved.© 2016 MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD. All Rights Reserved. 26

4.4 Annual energy consumption

and consideration

Page 27: Optimal centrifugal chiller system for the middle east ... · 2.3 GCC Region 3. Climate Condition and Characteristic of Cooling Load 3.1 Dry-bulb temp 3.2 Wet-bulb temp 3.3 Cooling

27© 2016 MITSUBISHI HEAVY INDUSTRIES, LTD. All Rights Reserved.© 2016 MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD. All Rights Reserved. 27

4.0

4.2

4.4

4.6

4.8

5.0

5.2

5.4

5.6

5.8

0 20 40 60 80 100 120

Cooling load (%)

FSD VSD

2

4

6

8

10

12

14

0 20 40 60 80 100 120Cooling load (%)

FSD VSD

130.3133.8 132.2

137.5

4.3

4.62.7

2.69.5

10.3

7.1

7.0

120

125

130

135

140

145

150

155

FSD VSD FSD VSDConventional Control Optimal Control

44.9 40.646.6 43.4

2.12.4

0.90.8

4.65.3

2.22.1

0

10

20

30

40

50

60

FSD VSD FSD VSDConventional Control Optimal Control

4.4.1 Tokyo and Singapore

Cooling Water PumpChilled Water PumpChiller

Fig19-(a)Annual energy consumption in Tokyo

VSD:7.91FSD:6.08

Fig19-(b) COPsys through the year in Tokyo

The VSD is better than the FSD by more than 6% in Tokyo at the view of Annual energy consumption. The Optimal control system has a reliable advantage in spite of the drive unit. Both VSD and Optimal control system are useful in the region has fluctuation of cooling water temp and cooling load.

(GW

h/Y

ear) 51.6 48.3 49.7 46.3

5.84

System

COP

6.07 6.516.25

The VSD is worse than the FSD by about 3% due to electrical loss. High performance FSD chillers should be applied for Singapore site.

Fig20-(a)Annual energy consumption in Singapore Fig20-(b) COPsys through the year in Singapore

(GW

h/Y

ear)

Cooling Water PumpChilled Water PumpChiller

5.04 5.11 4.944.89

144 149 142 147

System

COP

Tokyo

Singapore

Tokyo Tokyo

Singapore Singapore

Page 28: Optimal centrifugal chiller system for the middle east ... · 2.3 GCC Region 3. Climate Condition and Characteristic of Cooling Load 3.1 Dry-bulb temp 3.2 Wet-bulb temp 3.3 Cooling

28© 2016 MITSUBISHI HEAVY INDUSTRIES, LTD. All Rights Reserved.© 2016 MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD. All Rights Reserved. 28

88.478.1

91.5 83.9

4.34.7

2.42.2

9.510.4

4.84.7

0

20

40

60

80

100

120

FSD VSD FSD VSDConventional Control Optimal Control

97.1 96.4 99.395.9 94.3

99.294.6 93.8 96.793.3 91.6

96.6

0

20

40

60

80

100

120

FSD(Conventional Control) VSD(Conventional Control)FSD(Optimal Control) VSD(Optimal Control)

Makkah Lusail Dubai

GWh/Year

4.4.2 GCC region

Fig22-(a) Annual energy consumptions of GCC region

Makkah Lusail Dubai

Fig22-(b) COPsys through the year in GCC region

4.0

4.5

5.0

5.5

6.0

6.5

7.0

7.5

8.0

0 20 40 60 80 100 120

Cooling load (%)

FSD VSD

Dubai

5.43 5.50 5.58 5.65 5.47 5.60 5.62 5.76 5.31 5.32 5.45 5.46

Cooling Water PumpChilled Water PumpChiller

(GW

h/Y

ear)

102 93.2 98.7 90.8

6.84 7.08 7.687.50

6.0

7.0

8.0

9.0

10.0

11.0

0 20 40 60 80 100 120

Cooling load (%)

FSD VSD

Madinah

4.0

4.5

5.0

5.5

6.0

6.5

7.0

7.5

8.0

0 20 40 60 80 100 120

Cooling load (%)

FSD VSD

Lusail

Fig20 Annual energy consumption in

4.0

4.5

5.0

5.5

6.0

6.5

7.0

7.5

8.0

0 20 40 60 80 100 120

Cooling load (%)

FSD VSD

Makkah

High performance FSD chiller, are suitable for typical GCC region, Makkah Dubai and Lusail. The Series counter flow parallel unit is one of best ways for DC plant in GCC region.

Madinah

In Madinah, the VSD is better than the FSD by about 9% at the view of annual energy consumption due to low cooling water temperature. The Optimal control system reduces additionally about 3% energy consumption.

The combination FSD & Optimal control system is better suited to typical GCC region, Makkah Dubai and Lusail, due to high cooling water temperature.

System

COP

Page 29: Optimal centrifugal chiller system for the middle east ... · 2.3 GCC Region 3. Climate Condition and Characteristic of Cooling Load 3.1 Dry-bulb temp 3.2 Wet-bulb temp 3.3 Cooling

29© 2016 MITSUBISHI HEAVY INDUSTRIES, LTD. All Rights Reserved.© 2016 MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD. All Rights Reserved. 29

5. Conclusion

Page 30: Optimal centrifugal chiller system for the middle east ... · 2.3 GCC Region 3. Climate Condition and Characteristic of Cooling Load 3.1 Dry-bulb temp 3.2 Wet-bulb temp 3.3 Cooling

30© 2016 MITSUBISHI HEAVY INDUSTRIES, LTD. All Rights Reserved.© 2016 MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD. All Rights Reserved. 30

5. Conclusion

1. High performance FSD centrifugal chiller is suited to DC plant

in GCC region, due to high temperature cooling water.

2. The Optimal control system is reduce the energy consumption

of the DC plant by approx. 3% in any case.

3. If temperature difference through a year is large, the

combination VSD chillers and Optimal control system is best.

It improves the performance of the DC plant by 10%

4. The series counter flow parallel unit with double

compressors is ideally suited to DC plant in GCC region, due

to large capacity, high performance and small footprint.