Ambient temperature
Degree of Protection
Conformity
+5°C to +25°C
IP20
BSEN 60.598-2-22
YOUR AUTHORITY IN SELF-TESTING EMERGENCY LIGHTING
Operating Instructions - ExiLED Surface Mounted
Gerneral Description
The ExiLED Surface Mounted are fully automatic self testing emergency
lighting luminaires and does not require a key switch testing facility.
1. Luminaires should only be installed by suitably
qualified personnel
2. Installation should be carried out in accordance with the requirements of
BS7671 and BS5266 Pts 1 and 8 as well as BS EN 1838.
3. Before installing, connecting or servicing these luminaires, isolate the
mains supply to which they are to be connected.
P4 Limited
1 Wymans Way, Fakenham, Norfolk NR21 8NT
T: 01328-850555
F: 01328-850559
www.p4fastel.co.uk
Details correct at time of publication P4 reserve the right to change specification at any time.
Testing regime
Luminaires incorporate fully automatic selt testing and will regularly test for
correct lamp (LEDs) functioning and for battery functioning in accordance with
a predefined test programme that exceeds the requirements of BSEN50172 /
BS5266 Pt.8: 2004.
See separate FASTEL test regime description.
Remote control and monitoring (SRM units only)
All SRM version luminaires incorporate remote control and monitoring
capability. Luminaires may be connected, either via CB100 Collector boxes or if
less than 125 luminaires are to be monitored, directly to a M-web unit to a LAN
or internet connection and remotely controlled and monitored. All SRM
luminaires are assigned individual addresses before leaving the factory and
should be installed in accordance with the installation plans. Details of the
remote control and monitoring operation may be found in separate sheet.
© 2016 copyright all rights reserved
Technical Specification
Supply Voltage
Mode of Operation
Duration
Light sources
Battery
Recharge period
Weight
Non Maintained or Maintained
24 hours for full duration
(14 hours for 1 hour)
3 hours
2.8V 1200mAh High Temperature NiMh
230V +10% -10%, 50/60Hz
680-1022 Issue 1. July 2016
High Efficiency white LEDs
Drawn By T. Skevington - Approved By A. Daniels
EXIR/SC/M3 - 2.3kg
Installation and Operating Instructions for
ExiLED Surface Mounted Exit Sign
Product Codes
EXIR/SC/S/M3 & EXIR/SC/SRM/M3
Self-Testing emergency lighting unit
with integrated LED converter for LED lighting
LECJ SRM 350/2SC/180
2.4
V 1
.6
Ah
Pa
rt n
o: 1
4-1
52
P
Co
de
: 4
7-1
0
Se
ria
l N
o: 1
59
17
Cell T
ype: S
AF
T V
NT
Cs
KR
MT
3
3/6
2
BATT
Power
LED
LED
RE
DR
ED
LED 350mA max 11V
Operating time 3h
Batt. NiCd 2.4V / 1.5-1.8Ah
Mains 220-230V +/- 10% / 50-60Hz
LED voltage - SELV - max. 25V
BUS
+ -
+
-
+ -
+
-
C1 C2
N LLSW
C1 C2
NL LSW
6
6
0
-
0
1
0
Self-Testing emergency lighting unit
with integrated LED converter for LED lighting
LECJ SRM 350/2SC/180
2.4
V 1
.6
Ah
Pa
rt n
o: 1
4-1
52
P
Co
de
: 4
7-1
0
Se
ria
l N
o: 1
59
17
Cell T
ype: S
AF
T V
NT
Cs
KR
MT
3
3/6
2
DO
N
OT
S
HO
RT
C
IR
CU
IT
Ni-C
d
Cd
EN 60598-2-22/ EN 61347-2-13/ EN 62034
L'
L
N
8mm
wire preparation:
0.5-1.5
Tc= 65°C
BATT
Power
LED
LED
RE
DR
ED
LED 350mA max 11V
Operating time 3h
Batt. NiCd 2.4V / 1.5-1.8Ah
Mains 220-230V +/- 10% / 50-60Hz
LED voltage - SELV - max. 25V
13
0
°F
5
4
°
C
BUS
Removing Mounting Plate
5. Plug the battery (Red and Black Cables) into the converter, ensuring
polarity is correct. Stow the Cables in a safe place inside the fitting to avoid
damage during re-fitting of the shroud.
1. Remove the Surface
Mounted ExiLED from it
protective box and remove
the mounting plate from the
Shroud by unscrewing the
x2No. M3 screws on the
front of the fitting.
Place the shroud and the
fixing screws in a safe
place for re-fitting later on.
1
Fitting Mounting Plate to Ceiling
2
Wiring Detail
4
Wire Key
= Live
= Switch Live
= Nutural
= =Earth
= Coms 1
= Coms 2
Battery Connection
5
fig 2a.
fig 2b.
3. Wire the connector block as per
the label guides. In case of
maintained operation the switched
live must be connected to the LSW
terminal. Note the switched live
and the unswitched live must
originate from the same phase.
Shroud Re-Fitting
6
6. Take the shroud and plug the
corresponding connectors blocks
together using the label guides.
Once complete re-fit the shroud to
the mounting plate by repeating
Step 1 in reverse.
2. The ExiLED Surface Mounting Plate has been
design to work with either surface or recessed
BESA Boxes. (See fig 2a.)
Locate the BESA box and position the Mounting
plate so the fitting is pointing in the required
direction.Then using suitable fixing screws secure
the Mounting Plate to the BESA box. (See fig 2b.)
Non Maintained
Maintained
N
L
N
L
Lsw
7. Apply mains supply to test the luminaire. The indicator LED will show
flashing green and the LEDs will illuminate if the Switched Live supply is
connected and switched on.
Applying Mains Supply
7
NOTE: It is the fitters responsibility to
find suitable fixing screws. Fixings
screws are not supplied with this fitting.
A special Conduit Skirt is available for
surface mounted BESA boxes as an
optional extra.
Wiring Detail
3
4. Take the Legend Panel out
of the protective packaging and
insert into the legend slot on
the ExiLED fitting. See Fig 4a.
The grub screws come ready
fitted into the Legend Panel.
Line up the grub screws with
the holes on either side of the
heatsink. See Fig 4b.
When in line unscrew the grub
screws by 2mm until it is
securely resting on the heatsink
mounting holes. See Fig 4c.
Fig 4a.
Fig 4c.Fig 4b.
N
L
Lsw
8. To test, briefly fail the
supply to illuminate sign from
the internal battery. The
indicator LED will be
extinguished.
Test Emergency Supply
8
Reconnect Mains Supply
9. Reconnect the unswitched supply to restart battery charging, indicated
by the flashing green indicator LED. Reconnection of the Switched Live
will re-illuminate the LEDs from the mains supply if connected for
maintained operation.
9
Image same as Step 7.