onyxworks workstation

152
ONYXWorks ® Workstation Installation & Operation Manual Document 52342 06/01/07 Rev: D P/N: 52342:D ECN: 06-053

Upload: dota-ng

Post on 02-Jan-2016

107 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Onyxworks Workstation

ONYXWorks®

Workstation

Installation & Operation Manual

Document 5234206/01/07 Rev: D

P/N: 52342:D ECN: 06-053

Page 2: Onyxworks Workstation

Fire Alarm System LimitationsWhile a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!An automatic fire alarm system—typically made up of smoke detec-tors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel with remote notification capability—can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.

The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the recommenda-tions of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. These documents can be found at http://www.systemsensor.com/html/applicat.html.

A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not pro-vide timely or adequate warning, or simply may not function, for a variety of reasons:

Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire.

Particles of combustion or “smoke” from a developing fire may not reach the sensing chambers of smoke detectors because:

• Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.

• Smoke particles may become “cold,” stratify, and not reach the ceiling or upper walls where detectors are located.

• Smoke particles may be blown away from detectors by air outlets. • Smoke particles may be drawn into air returns before reaching the

detector.

The amount of “smoke” present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.

Smoke detectors, even when working properly, have sensing limita-tions. Detectors that have photo-electronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visi-ble smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detec-tor may not provide adequate warning of a fire.

Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in

bedrooms), smoking in bed, and violent explosions (caused by escap-ing gas, improper storage of flammable materials, etc.).

Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protect property, not life.

IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connec-tion of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire.

Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently con-sumed drugs, alcohol or medication. Please note that:

• Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.

• Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.

• In rare instances, the sounding of a warning device can cause tempo-rary or permanent hearing loss.

A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly main-tained and replaced regularly.

Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment listed for service with your control panel.

Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily dis-abled. For added protection against telephone line failure, backup radio transmission systems are recommended.

The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in excellent work-ing order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent mainte-nance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be sched-uled monthly or as required by National and/or local fire codes and should be performed by authorized professional fire alarm installers

2 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 3: Onyxworks Workstation

Installation PrecautionsAdherence to the following will aid in problem-free installation with long-term reliability:WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. The control unit and associated equipment may be dam-aged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.

CAUTION - System Reacceptance Test after Software Changes. To ensure proper system operation, this product must be tested in accor-dance with NFPA 72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any mod-ification, repair or adjustment to system hardware or wiring.

All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper sys-tem operation verified.

This system meets NFPA requirements for operation at 0°C to 49°C (32°F to 120°F) and at a relative humidity 93% ± 2% RH (non-con-densing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nominal room temperature of 15-27° C/60-80° F.

Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.

Like all solid state electronic devices this system may operate errati-cally or can be damaged when subjected to lightning-induced tran-sients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibil-ity. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services if any problems are anticipated or encountered.

Disconnect AC power and batteries prior to removing or inserting cir-cuit boards. Failure to do so can damage circuits.

Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.

Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.

Though designed to last many years, system components can fail at any time. This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static-sup-pressive packaging to protect electronic assemblies removed from the unit.

Follow the instructions in the installation, operating, and program-ming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel.

Acclimate Plus™, HARSH™, NOTI•FIRE•NET™, VeriFire™, NION™, NOTIFER Intergrated Systems™ and ONYXWorks™ are trademarks, andONYX®, FlashScan®, UniNet®, VIEW®, NOTIFIER® are registered trademarks of Honeywell. Simplex® is registered trademark of TycoInternational Ltd. Echelon® is a registered trademark and LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a registered trademark of DatapointCorporation. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. LEXAN® is a registered trademark of GE Plastics, a subsidiary ofGeneral Electric Company.

©2006 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.

FCC WarningWARNING: This equipment generates, uses, and can radi-ate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause inter-ference to radio communications. It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environ-ment. Operation of this equipment in a residential area is

likely to cause interference, in which case the user will be required to correct the interference at his own expense.

Canadian Requirements: This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communica-tions.

Le present appareil numerique n'emet pas de bruits radio-electriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement

3ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 4: Onyxworks Workstation

Documentation FeedbackYour feedback helps us keep our documentation up-to-date and accurate. If you have any comments, you can email us.

Please include the following information:

• Product name and version number (if applicable)• Manual page number• Your comment

Send email messages to:

[email protected]

Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.

4 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 5: Onyxworks Workstation

Table of ContentsSection 1 About This Manual...................................................................................................9

1.1: Manual Conventions ......................................................................................................................................91.1.1: Notes, Cautions, and Warnings ...........................................................................................................91.1.2: Procedures ...........................................................................................................................................91.1.3: Referencing Other Documents ............................................................................................................9

1.2: Agency Listings ...........................................................................................................................................101.2.1: Environmental Requirements ............................................................................................................10

1.3: Related Documentation ...............................................................................................................................111.4: Workstation Setup Overview Flow Diagram...............................................................................................12

Section 2 Hardware, Printer, and Power Connections ........................................................ 132.1: Installation Overview...................................................................................................................................142.2: Connect the Workstation Components ........................................................................................................15

2.2.1: Workstation Component Connections...............................................................................................152.3: Workstation AC Power Connection Preparation .........................................................................................162.4: Make Printer Connections ...........................................................................................................................18

2.4.1: About Connecting a Graphics Printer................................................................................................182.4.2: Local Event Printer Connection ........................................................................................................19

2.5: Uninterruptable Power Supply (UPS) Installation ......................................................................................202.5.1: Workstation’s UPS Supervision ........................................................................................................202.5.2: Printer’s UPS Supervision .................................................................................................................20

2.6: Workstation Hardware/Software Application Connections.........................................................................222.6.1: WSSUP Board Description ...............................................................................................................22

2.7: Workstation Network (LAN) Connection....................................................................................................232.8: Workstation Power-up .................................................................................................................................24

Section 3 Windows® Software Configuration...................................................................... 253.1: Windows Software Configuration Overview...............................................................................................253.2: Start the Workstation PC..............................................................................................................................263.3: Install Computer Software ...........................................................................................................................26

3.3.1: About the Windows XP Installation..................................................................................................263.3.2: About the Workstation Software Application Installation ................................................................263.3.3: About Anti-Virus Software Installations...........................................................................................26

3.4: Make Windows XP Settings ........................................................................................................................273.4.1: About Windows XP Settings.............................................................................................................273.4.2: About Changing the Windows Administrator Password...................................................................27

3.5: Add the Workstation to Your LAN Network ...............................................................................................283.5.1: About Naming the Workstation on Your Network ...........................................................................283.5.2: Workstation’s IP Address Configuration ..........................................................................................28

3.6: Workstation Software Application Start and Exit Methods.........................................................................303.6.1: About the Workstation Software Starting Mode ...............................................................................303.6.2: About the Workstation Software Exit Mode .....................................................................................30

Section 4 ONYXWorks® Workstation System Connections ............................................... 314.1: Workstation System Connections Overview ...............................................................................................314.2: Make ONYXWorks®System Connections ..................................................................................................324.3: Admin User Log In ......................................................................................................................................344.4: Add a Network Connection to the Workstation...........................................................................................35

4.4.1: About Adding an Existing Gateway..................................................................................................354.4.2: About Adding a New Network Connection ......................................................................................36

4.5: Auto-Create Gateway Point IDs ..................................................................................................................374.5.1: About Auto-Creating Gateway Point IDs..........................................................................................37

4.6: Workstation Database Modifications...........................................................................................................38

5ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 6: Onyxworks Workstation

Table of Contents

Section 5 Workstation Software Configuration ................................................................... 415.1: Workstation Software Application Configuration Overview.......................................................................415.2: Admin User Log In Configuration...............................................................................................................43

5.2.1: About the Factory Defined User Profiles and their Passwords .........................................................435.2.2: Admin User Password Change Procedure .........................................................................................43

5.3: Monitoring Profile Configuration ................................................................................................................445.3.1: About Monitoring Profiles.................................................................................................................445.3.2: Monitoring Profile Creation Procedure .............................................................................................455.3.3: Existing Monitoring Profile Management .........................................................................................46

5.4: Workstation Software Application Options Configuration..........................................................................475.4.1: Output Configuration.........................................................................................................................485.4.2: Local Event Printer Configuration.....................................................................................................505.4.3: Pager/Modem Configuration .............................................................................................................525.4.4: E-Mail Configuration.........................................................................................................................555.4.5: General Operation Configuration ......................................................................................................575.4.6: User Features Configuration..............................................................................................................60

5.5: Control Profiles Configuration ....................................................................................................................615.5.1: About Control Profiles.......................................................................................................................615.5.2: Control Profile Creation Procedure ...................................................................................................625.5.3: Existing Control Profile Management ...............................................................................................63

5.6: System Options Configuration.....................................................................................................................645.6.1: Icon Set ..............................................................................................................................................645.6.2: Operating Modes ...............................................................................................................................655.6.3: Time Server Settings..........................................................................................................................65

5.7: User Configuration.......................................................................................................................................665.7.1: About Users Definitions ....................................................................................................................665.7.2: About the User Database ...................................................................................................................665.7.3: About Point Controls .........................................................................................................................665.7.4: About User Security Options.............................................................................................................665.7.5: User Additions and Modifications.....................................................................................................695.7.6: About User Access to Workstation Keyboard Short-cuts .................................................................69

5.8: Macro Command Configuration ..................................................................................................................705.8.1: About Macro Commands...................................................................................................................705.8.2: Macro Creation and Management .....................................................................................................71

5.9: Color and Sound Configuration ...................................................................................................................735.9.1: About Color Configuration Settings ..................................................................................................735.9.2: About Sound Configuration Settings.................................................................................................74

5.10: Fan Monitor Configuration ........................................................................................................................745.10.1: About Fan Monitoring .....................................................................................................................745.10.2: Monitor Fan Setup ...........................................................................................................................74

5.11: Voice Paging Configuration (Optional Feature) ........................................................................................755.11.1: About the Voice Paging...................................................................................................................755.11.2: About a Public Address Amplifier ..................................................................................................765.11.3: Voice Paging Setup Procedure ........................................................................................................765.11.4: Voice Paging Activation Procedure.................................................................................................76

Section 6 Workstation Screen Graphical User Interface Management ............................. 776.1: Overview......................................................................................................................................................776.2: Auto-Creation of Workstation Screens, Nodes, and Points .........................................................................78

6.2.1: Description.........................................................................................................................................786.2.2: Manage the Auto-Creation Process ...................................................................................................79

6.3: Panel Programming......................................................................................................................................806.3.1: Panel Database Uploading .................................................................................................................816.3.2: Panel Application Downloading........................................................................................................826.3.3: Schedule Panel Uploads ....................................................................................................................83

6.4: Setup the Workstation Display Mode ..........................................................................................................846.4.1: View Workstation in Graphics Mode ................................................................................................84

6 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 7: Onyxworks Workstation

Table of Contents

6.4.2: View Workstation in Text Mode .......................................................................................................85

Section 7 ONYXWorks® Workstation Data Management .................................................... 877.1: Data Management Overview .......................................................................................................................877.2: About Database Management......................................................................................................................887.3: About History Manager ...............................................................................................................................90

7.3.1: History Manager Menu Descriptions ................................................................................................917.3.2: History Manager Right Click Menu Descriptions.............................................................................937.3.3: History Manager Filters.....................................................................................................................947.3.4: History Manager Configuration.........................................................................................................967.3.5: History Manager Reports...................................................................................................................97

7.4: System Explorer Searches ...........................................................................................................................997.4.1: Point Type, Text, and Off Normal Searches .....................................................................................99

7.5: Key Upgrade Utility ..................................................................................................................................1017.5.1: About the Key Upgrade Utility .......................................................................................................1017.5.2: Key Upgrade Procedure...................................................................................................................1017.5.3: Key Upgrade Utility Field Descriptions..........................................................................................101

Section 8 ONYXWorks® System Architecture Descriptions............................................. 1038.1: About the System Architecture..................................................................................................................1038.2: Fire Command Center (FCC) Mode Overview (PPU) ..............................................................................106

8.2.1: Architecture for FCC Mode.............................................................................................................1068.2.2: Event Handling Overview for FCC Mode.......................................................................................1068.2.3: FCC Mode Communications Requirements....................................................................................1078.2.4: FCC Mode Agency Approval..........................................................................................................1078.2.5: ONYXWorks® FCC Mode Ordering Information ..........................................................................1078.2.6: FCC Mode Example Life System Diagrams ...................................................................................108

8.3: Proprietary Supervising Station Mode Overview......................................................................................1108.3.1: Architecture For Supervising Station Mode....................................................................................1108.3.2: Overview of Event Handling in Supervising Station Mode ............................................................1108.3.3: Supervising Mode Communications Requirements ........................................................................1118.3.4: Supervising Mode Agency Approval ..............................................................................................1118.3.5: ONYXWorks® Supervising Mode Ordering Information...............................................................1118.3.6: Supervising Mode Example Life System Diagrams........................................................................112

8.4: Client Applications ....................................................................................................................................1148.5: Printers .......................................................................................................................................................1148.6: System Security .........................................................................................................................................115

8.6.1: Hardware Security ...........................................................................................................................1158.6.2: Software Security ............................................................................................................................115

8.7: Workstation Event Handling Basics ..........................................................................................................1168.8: Workstation Monitored Points ...................................................................................................................118

8.8.1: About Workstation Points ...............................................................................................................1188.8.2: Common Workstation Commands ..................................................................................................118

Appendix A: Glossary .......................................................................................................... 119Appendix B: Details about Event Data................................................................................ 123

B.1: Event Data.................................................................................................................................................123B.2: Event Priority ............................................................................................................................................123B.3: Printer Output Format ...............................................................................................................................127

Appendix C: ONYXWorks® Workstation User’s Guide...................................................... 129C.1: Workstation Display Descriptions.............................................................................................................129

C.1.1: Displayed User................................................................................................................................130C.1.2: Main Menu......................................................................................................................................130C.1.3: Toolbar Menu..................................................................................................................................130C.1.4: Taskbar Menu .................................................................................................................................130C.1.5: Overview.........................................................................................................................................130

7ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 8: Onyxworks Workstation

Table of Contents

C.1.6: Workstation Floorplan Area............................................................................................................131C.1.7: Graphic Elements Descriptions.......................................................................................................131C.1.8: Navigation Tree...............................................................................................................................132C.1.9: New Event.......................................................................................................................................133C.1.10: Acknowledged Events...................................................................................................................133C.1.11: Alarm Summary............................................................................................................................133C.1.12: Event Annunciator Icon ................................................................................................................134C.1.13: Other - Indicates input on, output on events. ................................................................................135

C.2: Daily Operation .........................................................................................................................................136C.2.1: Logging into the Workstation .........................................................................................................136C.2.2: Interpreting Events on the Workstation’s User Interface................................................................137C.2.3: Managing Events.............................................................................................................................140C.2.4: Acknowledge a New Event Procedures ..........................................................................................141

Appendix D: ONYXWorks® Workstation Software Installation Procedure...................... 143D.1: Windows Installation.................................................................................................................................143D.2: Required Windows Settings and Options..................................................................................................143

D.2.1: Windows Explorer Settings and Options Checklist........................................................................144D.3: ONYXWorks® Workstation Software Application Installation Procedure...............................................147

8 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 9: Onyxworks Workstation

Section 1 About This Manual

1.1 Manual Conventions

1.1.1 Notes, Cautions, and WarningsThis manual contains notes, cautions, and warnings to alert the reader as follows:

1.1.2 Procedures

Example Text: Main Menu select File >Print >Events.

The graphic above is represented in the Example Text. All selections, fields, buttons, and screen titles are spelled (upper/lower case) exactly as the appear on the display.

1.1.3 Referencing Other DocumentsExample: Refer to the ONYXWorks® Workstation manual.

italic text is used to reference a document by its specific name.

NOTE: In this document, unless expressly written otherwise, when the term ONYXWorks®

Workstation or Workstation is used those terms refer to the software application and the computer it is installed on as one.

NOTE: Supplemental information for a topic, such as tips and references.

! CAUTION: Summary in boldInformation about procedures that could cause programming errors, runtime errors, or equipment damage.

!WARNING: Summary in boldIndicates information about procedures that could cause irreversible equipment damage, irreversible loss of programming data or personal injury.

9ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 10: Onyxworks Workstation

About This Manual Agency Listings

1.2 Agency Listings

This product is intended to be installed in accordance with the Local Authority Having Jurisdiction (LAHJ) and has been investigated to, and found to be in compliance with the following standards and documents. Before proceeding, the installer should be familiar with them too.

Underwriters Laboratories U.S. Documents• UL-864: Control Units for Fire Protective Signaling Systems, Ninth Edition.• UL-1076: Proprietary Burglar Alarm Units and Systems, Fifth Edition.

Underwriters Laboratories Canada Documents• CAN/ULC-S527-99: Standard for Control Units for Fire Alarm Systems.

National Fire Protection Association Standards• NFPA 70: National Electrical Code.• NFPA 72: Installation, Maintenance, and Use of Protective Signaling Systems.

1.2.1 Environmental RequirementsThis product must be installed in the following environmental conditions:

• Temperature range of 0°C to 49°C (32°F - 120°F).• 93% humidity non-condensing at 30°C (86°F).

90.23 effective October 1, 2005

NOTE: ONYXWorks® systems work with products that have been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864 9th Edition, as well as products that have not received UL 864 9th Edition certification. Operation of a UL 864 9th Edition compliant system together with products not tested for UL 864 9th Edition has not been UL evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).

!WARNING: InstallationImproper installation, maintenance, and lack of routine testing could result in system malfunction.

NOTICE TO USERS, INSTALLERS, AUTHORIES HAVING JURISDICTION, AND OTHER INVOLVED PARITES

This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to

specific values or not used at all as indicated below.

Program feature or option Permited in UL 864 (Y/N) Possible Settings Settings permitted in UL 864

Remote resetting and silencing of a fire alarm control unit from other than the protected premises (ref: NFPA 72-2007 6.8.2.8)

No Security Levels• Administrator• User with Point Control• User with Client Control• Default User

10 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 11: Onyxworks Workstation

Related Documentation About This Manual

1.3 Related DocumentationThe following is a list of documentation resources related to the ONYXWorks® system.

• ONYXWorks® Echelon Gateway (P/N 52305)• ONYXWorks® NFN GW-2 Embedded (P/N 52656)• ONYXWorks® NFN GW PC (P/N 52307)• ONYXWorks® Receivers Gateway (P/N 52308)• ONYXWorks® NetLogic (P/N 52326)• ONYXWorks® Routers-Repeaters (P/N 52327)• ONYXWorks® Workstation Manual (P/N 52342)• ONYXWorks® Configuration Tool (P/N 53038)

NOTE: The contents of this manual are important and must be kept in close proximity of the Workstation. If building ownership is changed, this manual including all other testing and maintenance information must also be passed to the current owner of the facility. A copy of this manual was shipped with the equipment and is also available from the manufacturer.

11ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 12: Onyxworks Workstation

About This Manual Workstation Setup Overview Flow Diagram

1.4 Workstation Setup Overview Flow Diagram

The sequence in which these tasks are performed is determined by the Admin User performing them and this list is a suggested guideline to ensure that Workstation software application is configured correctly.

Figure 1.1 Workstation Setup Overview Flow Diagram

NOTE: The Workstation must be logged into before any of its settings can be configured. A User that has the Security Option to configure settings needs to login to change an existing setting. The factory defined User “Admin” has such a Security Option. Information in this document is written assuming that a User with the equivalent Security Option of the “Admin” User will be performing the procedures in this document.

“ONYXWorks® Workstation System Connections” on

page 31

“Hardware, Printer, and Power Connections” on page 13

“Windows® Software Configuration” on page 25

“Workstation Software Configuration” on page 41

“Workstation Screen Graphical User Interface Management” on

page 77

Start

Finished

12 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 13: Onyxworks Workstation

Section 2 Hardware, Printer, and Power Connections

NOTE: If you are not familiar with the Workstation’s graphical user interface, please refer to the Appendix C on page 129 for information.

!WARNING: Power SourcesRemove all power sources to equipment before connecting electrical components. The Workstation’s computers main power switch must be in the OFF position until installation of the entire ONYXWorks® system is complete and ready for testing.

! CAUTION: Life Safety System NotificationBefore performing any work on a fire alarm system:a) Notify the fire department and the central alarm receiving station if transmitting alarm conditions.b) Notify the people occupying the facility about the impending test, the expected time period of the

test, and to disregard any alarm during the test period.c) When appropriate, disable activation of alarm notification appliances and speakers to prevent

their sounding.d) Always physically disable releasing devices before system tests to prevent accidental discharge.

NOTE: The Workstation can only be installed in an environment that meets these conditions: - Temperature range of 0ºC – 49ºC (32ºF – 120ºF). - 93% humidity non-condensing.

NOTE: Ground faults are annunciated at zero value.

13ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 14: Onyxworks Workstation

Hardware, Printer, and Power Connections Installation Overview

2.1 Installation OverviewInstallation of a UL listed ONYXWorks® system must be performed by a factory-trained fire alarm technician. The ONYXWorks® Workstation computer is typically shipped with the required networking cards and the software application already installed.

The installer should perform the tasks listed here. Tasks sequence is determined by the installer and this list is a suggested guideline to ensure that the Workstation computer installed correctly.

Figure 2.1 Hardware, Printer, and Power Connections Flow Diagram

“ONYXWorks® Workstation System Connections” on

page 31

“Hardware, Printer, and Power Connections” on page 13

“Windows® Software Configuration” on page 25

“Workstation Software Configuration” on page 41

“Workstation Screen Graphical User Interface Management” on

page 77

Start

Finished

“Workstation Network (LAN) Connection” on page 23

“Connect the Workstation Components” on page 15

“Workstation AC Power Connection Preparation” on

page 16

“Make Printer Connections” on page 18

“Uninterruptable Power Supply (UPS) Installation” on page 20

“Workstation Hardware/Software Application

Connections” on page 22

“Workstation Power-up” on page 24

14 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 15: Onyxworks Workstation

Connect the Workstation Components Hardware, Printer, and Power Connections

2.2 Connect the Workstation ComponentsA UL listed Workstation’s computer is a rack-mount-capable Intel Pentium IV computer. The computer has a 2.0 GHz CPU, 1 GB of RAM, and a 40 GB hard drive.

All Workstations ship as a computer (PC), monitor, mouse, keyboard, network connection card, and a configured USB Hardlock Key. Workstations ordered and shipped with more than one gateway may have additional network cards installed.

The Workstation must be installed in accordance with local fire protection codes. The Workstation can be rack-mounted or placed on a desk or table with the monitor, keyboard, and mouse.

2.2.1 Workstation Component ConnectionsUse the following steps and figure as guidelines to complete connecting the Workstation’s components.

Step 1. Connect the factory supplied mouse/keyboard splitter cable to the KEY/MOUSE connector.

Step 2. Connect the mouse and keyboard to the mouse/keyboard splitter cable.Step 3. Connect the monitor cable to the VIDEO connector.Step 4. Connect the monitor sound cable to the Audio In Connector on the sound card.Step 5. Connect the USB Hardlock Key to one of the USB connectors.Step 6. If applicable, refer to “Make Printer Connections” on page 18.

Figure 2.2 Computer Component Connections

NOTE: The following figure is for information purposes, locate the appropriate connector using the labels attached to the Workstation’s computer rear panel.

1-256 34

15ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 16: Onyxworks Workstation

Hardware, Printer, and Power Connections Workstation AC Power Connection Preparation

2.3 Workstation AC Power Connection PreparationThe Workstation computer’s AC power cord must be connected in a permanent manner using the factory supplied Power Cord Locking Bracket (PCLB) and it must be connected to a regulated, UL 1481 listed, power limited Uninterruptible Power Supply (UPS).

Use the following steps and the following figure as guidelines to complete connecting the Workstation’s power connections.

Step 1. Verify that the Workstation computer’s Voltage Selection Switch in the correct position.

Step 2. Verify that the Workstation computer’s rear-panel power switch is set to the ON (|) position.

Step 3. Verify that the Workstation computer’s functional power switch, located behind the locking front door, is set to the OFF (O) position.

Step 4. Remove the Workstation computer’s three mounting screws (keep them for mounting the PCLB plate).

Step 5. Plug-in the factory supplied AC power cord to the Workstation computer’s AC power receptacle DO NOT CONNECT THE POWER CORD TO AN AC POWER SOURCE AT THIS TIME (Refer to “Workstation Power-up” on page 24.)

16 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 17: Onyxworks Workstation

Workstation AC Power Connection Preparation Hardware, Printer, and Power Connections

Step 6. Attach the PCLB Plate using the screws removed in the previous step.

Step 7. Connect an external power source the WSSUP PC board (verify location using labeling). Refer to “Workstation Hardware/Software Application Connections” on page 22.

Step 8. Connect the Workstation AC power cord to a supervised regulated, UL 1481 listed, power limited UPS that is rated to support the Workstation computer’s power requirements (115 VAC, 7 Amps, 60Hz). Refer to “Uninterruptable Power Supply (UPS) Installation” on page 20.

Step 9. Connect the network to the Workstation. Refer to “Workstation Network (LAN) Connection” on page 23.

! CAUTION: Possible Loss of Network CommunicationPower management options must be disabled in the CPU BIOS and on the monitor, or loss of network communication or alarm reporting may result.

17ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 18: Onyxworks Workstation

Hardware, Printer, and Power Connections Make Printer Connections

2.4 Make Printer ConnectionsThe following figure is for information purposes, locate the appropriate connector using the labels attached to the rear panel.

Figure 2.3 Computer Connectors and Ports

2.4.1 About Connecting a Graphics PrinterA graphics printer is a Windows compatible printer that prints what is currently displayed on the Workstation’s monitor. A graphics printer is connected to the Workstation’s LPT-1 connector or a USB connector.

Graphics Printer Configuration Windows operation apply when installing a printer’s driver, setting it up, and changing its printing preferences, consult Windows information. For printer connection information consult the printer’s manufacturers documentation.

COMM 1 and 2

LPT-1

USB

NOTE: When installing graphic printer drivers be sure to: - disable bidirectional support.*- set the graphics mode to raster.

*With any graphic printer always be sure to disable bidirectional communication. Never connect bidirectional points such as tape or disk drives to the Workstation PC’s LPT-1 port.

When using a HP® LaserJet 5, be sure that Advanced Functions are turned-off under the Parallel menu.

18 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 19: Onyxworks Workstation

Make Printer Connections Hardware, Printer, and Power Connections

2.4.2 Local Event Printer Connection

The Local Event Printer is a UL 864 listed Windows compatible dot-matrix printer that receives and prints all messages received/sent from the Workstation it is connected to. Refer to “About Local Event Printer Configuration” on page 50 for local event printer information.

A Workstation event printer must be able to be configured to and meet these requirements:

• Buffer Size: 32K• Baud Rate: 9600• 1 Stop Bit• Parity: None• Data Bits: 8 Bits.• Protocol – Robust XON/XOFF.

A event printer is connected to the Workstation’s COMM port. Use a serial cable that has been assembled according to the following figure.

Figure 2.4 Event Printer Cable

NOTE: The NOTIFIER® PRN-6 printer is a UL listed printer and can be used as a Local Event Printer.

Workstation COMM Port Pin Assignments Printer Cable Pin Assignments

19ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 20: Onyxworks Workstation

Hardware, Printer, and Power Connections Uninterruptable Power Supply (UPS) Installation

2.5 Uninterruptable Power Supply (UPS) InstallationFollow the manufacturers guidelines for UL regulated installations of UPS equipment.

The Workstation requires the use of a supervised 115VAC, regulated, UL 1481 listed, power limited Uninterruptible Power Supply (UPS). You can also supervise a Printer’s UPS. Refer to the following figures for wiring information to supervise the UPS and have the Workstation report an event when trouble occurs with your UPS.

2.5.1 Workstation’s UPS Supervision

Figure 2.5 Workstation UPS Supervision with a NFN Gateway PC and a FMM-1

2.5.2 Printer’s UPS Supervision

Figure 2.6 Printer’s UPS Supervision with a FDM-1

From Utility Failure connectors on UPS Inverter

Gateway PC-W/F (verify location)

From Low Current connectors on UPS Battery Charger

Workstation Computer

Normally ClosedComm

Outlet

From AC Load connector on UPS Inverter

UPS

FMM-1

From Utility Failure connectors on UPS Inverter

From Low Current connectors on UPS Battery Charger

Event Printer

Outlet

UPS

FDM-1

NC Comm

From AC Load connector on UPS Inverter

20 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 21: Onyxworks Workstation

Uninterruptable Power Supply (UPS) Installation Hardware, Printer, and Power Connections

UPS Supervision with a NION-2C8MA network bound NION-2C8M with supervised dry contact inputs can supervise a UPS. The NION must installed in a NION cabinet, be located within three feet of the UPS, and wiring must be in conduit. Refer to the following figure for wiring information.

Figure 2.7 UPS Supervision Using a NION-2C8M

To Utility Failure connector on UPS Inverter

To Low Current connector on UPS Battery Charger

NION-2C8M

NC

Com

m

21ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 22: Onyxworks Workstation

Hardware, Printer, and Power Connections Workstation Hardware/Software Application Connections

2.6 Workstation Hardware/Software Application Connections

2.6.1 WSSUP Board DescriptionPre-installed in your Workstation computer is the Workstation Supervisor PCI board (WSSUP Board) that is designed to monitor the computer and software application. The board is installed in the Workstation using an ISA slot and a standard mounting bracket. The board requires external power to activate it.

Figure 2.8 The WSSUP Board

1. Sounder emits a continuous audible noise if the CPU fails or the facilities monitoring software application stops functioning (not Exited).

2. Relay Output is used to enable annunciation by any external device, refer to "About the WSSUP Board Relay Output Connection":• That use power limited dry contacts.• Where a dedicated Workstation supervisor device is available that monitors its operation

through a direct connection with the motherboard’s bus.3. Power Connector, refer to "About the WSSUP Board Power Supply Connection".4. Acknowledge Button is used to silence the Sounder.5. Operation Alarm LED (3) - Used for visual confirmation that product is functioning.6. DIP switch The factory set pc board DIP switch settings are shown in Figure 2.8 (S2).

Switches S5 and S6 are not used. If the pc board is being retrofitted to a PC, be sure to use the defined default switch setting unless directed by a Technical Services Representative to do otherwise.

About the WSSUP Board Power Supply ConnectionPower to the board MUST be provided by an external +24VDC source, power limited, and regulated with battery backup which is UL/ULC listed (as appropriate for your area) for use with fire protective signalling units. Maximum power use is 35mA @ +24VDC.

About the WSSUP Board Relay Output ConnectionThe common relay output is a contact circuit that is not supervised and is rated for 2A @ +30VDC.

2

GND+24VDC

4

5

1

3

6

22 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 23: Onyxworks Workstation

Workstation Network (LAN) Connection Hardware, Printer, and Power Connections

2.7 Workstation Network (LAN) ConnectionAfter your LAN network (TCP/IP) is connected to the Workstation computer’s Ethernet connector (verify location using labeling); read and accomplish the steps in “Workstation Power-up” on page 24.

Figure 2.9 Workstation LAN (Ethernet) Connection

23ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 24: Onyxworks Workstation

Hardware, Printer, and Power Connections Workstation Power-up

2.8 Workstation Power-upPrerequisitesBefore powering-up the Workstation the following sections should have been read and the steps listed in them should have been accomplished, if you have not already done so.

• “Installation Overview” on page 14.• “Connect the Workstation Components” on page 15.• “Workstation AC Power Connection Preparation” on page 16.

ProcedureUse the following steps as guidelines to apply power to the Workstation.

Step 1. Connect the Workstation’s computer and monitor power cables to the UPS.Step 2. Apply power to the UPS.Step 3. Turn-on the Workstation monitor.Step 4. Turn-on the Workstation computer by setting the functional power switch located behind

the locking front door to the ON (|) position.When you first start up the Workstation:• Windows XP windows will start and display.• If you have the Workstation software application installed the PC Monitor’s splash

screen temporary flashes because PC Monitor is in the Windows Startup folder.• PC Monitor displays a prompting window for you to select a system.

Step 5. You are now ready to perform “Windows® Software Configuration” on page 25.

NOTE: This lists displays available ONYXWorks® system databases on the IP network. On a single Workstation system no IP addresses display, but on multiple Workstation system this list will be display all the IP addresses of other Workstations on the IP network.

NOTE: Do NOT select a system at this time if one is displayed in the list and if you are following the setup sequence of the “Workstation Setup Overview Flow Diagram” on page 12.

24 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 25: Onyxworks Workstation

Section 3 Windows® Software Configuration

3.1 Windows Software Configuration Overview

The sequence in which these tasks are performed is determined by the Admin User performing them and this list is a suggested guideline to ensure that Windows software is configured correctly.

Figure 3.1 Windows Software Configuration Flow Diagram

NOTE: The Workstation must be logged into before any of its settings can be configured. A User that has the Security Option to configure settings needs to login to change an existing setting. The factory defined User “Admin” has such a Security Option. Information in this document is written assuming that a User with the equivalent Security Option of the “Admin” User will be performing the procedures in this document.

“ONYXWorks® Workstation System Connections” on

page 31

“Hardware, Printer, and Power Connections” on page 13

“Windows® Software Configuration” on page 25

“Workstation Software Configuration” on page 41

“Workstation Screen Graphical User Interface Management” on

page 77

Start

Finished

“Install Computer Software” on page 26

“Make Windows XP Settings” on page 27

“Add the Workstation to Your LAN Network” on page 28

“Workstation Software Application Start and Exit

Methods” on page 30

25ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 26: Onyxworks Workstation

Windows® Software Configuration Start the Workstation PC

3.2 Start the Workstation PC

3.3 Install Computer Software

3.3.1 About the Windows XP InstallationThe Workstation’s computer ships with the Windows XP operating environment already installed; no installation tasks are required. Refer to “ONYXWorks® Workstation Software Installation Procedure” on page 143 for information about re-installing Windows and the ONYXWorks®

Workstation software application.

3.3.2 About the Workstation Software Application InstallationThe Workstation’s computer ships with the ordered software applications installed; no installation task are required.

Some of the software applications are configured to start automatically. What application programs that will accessible is determined by your USB Hardlock Key and the Workstation’s installed hardware. For example, PC Monitor was setup to start automatically and display in the Windows System Tray after power is applied to the Workstation and Microsoft Windows starts.

Refer to “Workstation Software Configuration” on page 41 for more information.

3.3.3 About Anti-Virus Software InstallationsIf it is absolutely necessary to use an anti-virus software application it must be MacAfee Enterprise.

NOTE: If you are following the setup sequence of the “Workstation Setup Overview Flow Diagram” on page 12 you should have already completed the steps in “Workstation Power-up” on page 24 before proceeding with these steps.

! CAUTION: Workstation Computer Software InstallationsDo NOT allow software that is NOT related to facilities monitoring, other than MacAfee® anti-virus software, to be installed on the Workstation’s computer.

!WARNING: Anti-Virus Automatic UpdatesDo NOT use a software update setting that will automatically restart the Workstation. The anti-virus software application must be manually updated.

26 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 27: Onyxworks Workstation

Make Windows XP Settings Windows® Software Configuration

3.4 Make Windows XP Settings

3.4.1 About Windows XP SettingsCritical Windows settings are set at the factory and the Workstation should function properly when powered on. For example; to ensure that the Workstation annunciates every message; all power management functions, like monitor sleep modes, are disabled. Only change Window settings with the approval of your Technical Services Representative.

3.4.2 About Changing the Windows Administrator PasswordThe factory setup for the Windows Administrator has no password set. It is recommended that the Admin User modify this password setting. Consult Windows information.

! CAUTION: Windows SettingsAll Windows settings are setup at the factory and must remain as they are for the Facilities Monitoring software application to function and display properly.

27ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 28: Onyxworks Workstation

Windows® Software Configuration Add the Workstation to Your LAN Network

3.5 Add the Workstation to Your LAN Network

3.5.1 About Naming the Workstation on Your NetworkThe Workstation should be given a name to differentiate it from its node name. To ensure an optimal computer name displays, it is recommended that computer names be no more than 16 characters in length.

This naming procedure is a standard Microsoft Windows® XP operation. Consult Windows® information.

3.5.2 Workstation’s IP Address ConfigurationThis configuration is a standard Microsoft Windows® XP operation. Consult Windows® information or use the following steps as guideline.

Step 1. Select Start >Settings >Network Settings. The Network Connections window displays.Step 2. Right-click on Local Area Connection, then select Properties from the list of choices. The

Local Area Connection Properties window displays

Figure 3.2 Select LAN Properties

NOTE: The LAN cable connection to your active network must have already been made. Refer to “Workstation Network (LAN) Connection” on page 23.

28 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 29: Onyxworks Workstation

Add the Workstation to Your LAN Network Windows® Software Configuration

Step 3. Select Internet Protocol (TCP/IP), then click Properties. The Internet Protocol (TCP/IP) Properties window displays.

Figure 3.3 Local Area Connection Properties Window

Step 4. Select “Use the following IP address:”, enter your IP address and Sub-net mask as it applies to your network, and then click OK.

Figure 3.4 Internet Protocol Window

29ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 30: Onyxworks Workstation

Windows® Software Configuration Workstation Software Application Start and Exit Methods

3.6 Workstation Software Application Start and Exit Methods

3.6.1 About the Workstation Software Starting ModeThe Admin User can configure the Workstation software application to automatically start when the computer is started. The Workstation software application is displayed as an always on top, full display window (no Windows Taskbar or System Tray will be visible).

If the desired startup operation is:

• Automatic; place a shortcut into a Windows® Startup folder.• Manual; select Start >Programs >Facilities Monitoring >Workstation.

3.6.2 About the Workstation Software Exit ModeAn Admin User is provided the Security Option (System Configuration) that would allow them to shutdown the Workstation software application or the Workstation computer and with that Security Option they can do the following:

Step 1. Exit the Workstation software application, Main Menu select File >Exit.Step 2. Shut down Windows, Start > Shutdown.

NOTE: The Workstation will not run without the USB Hardlock Key connected to the Workstation’s USB port. Please refer to “Connect the Workstation Components” on page 15 before starting to use Workstation software application, if you have not already done so.

! CAUTION: Workstation Shut DownFailure to exit the Workstation software application and Windows® properly could corrupt your software settings.

30 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 31: Onyxworks Workstation

Section 4 ONYXWorks® Workstation System Connections

4.1 Workstation System Connections Overview

The sequence in which these tasks are performed is determined by the Admin User performing them and this list is a suggested guideline to ensure that Workstation software application is configured correctly.

Figure 4.1 ONYXWorks® Workstation System Connections Flow Diagram

NOTE: The Workstation must be logged into before any of its settings can be configured. A User that has the Security Option to configure settings needs to login to change an existing setting. The factory defined User “Admin” has such a Security Option. Information in this document is written assuming that a User with the equivalent Security Option of the “Admin” User will be performing the procedures in this document.

“ONYXWorks® Workstation System Connections” on

page 31

“Hardware, Printer, and Power Connections” on page 13

“Windows® Software Configuration” on page 25

“Workstation Software Configuration” on page 41

“Workstation Screen Graphical User Interface Management” on

page 77

Start

Finished

“Make ONYXWorks®System Connections” on page 32

“Admin User Log In” on page 34

“Add a Network Connection to the Workstation” on page 35

“Auto-Create Gateway Point IDs” on page 37

31ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 32: Onyxworks Workstation

ONYXWorks® Workstation System Connections Make ONYXWorks®System Connections

4.2 Make ONYXWorks®System ConnectionsTheses figures illustrate example systems.

Figure 4.2 Basic NFN Gateway Network

Workstation

FACP FACP FACP

Workstation

NFN Network

TCP/IP Network

Gateway Embedded

32 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 33: Onyxworks Workstation

Make ONYXWorks®System Connections ONYXWorks® Workstation System Connections

Figure 4.3 Advanced NFN Gateway Network

FACP

Workstation/Gateway PC

FACPFACP FACP FACP FACP

Workstation

NFN Network NFN Network

TCP/IP Network

Workstation/Gateway PC Gateway Embedded

33ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 34: Onyxworks Workstation

ONYXWorks® Workstation System Connections Admin User Log In

4.3 Admin User Log InThe Workstation must be logged into before any of its networks can be chosen and connected. A User that has the Security Option to change a password needs to login to change an existing User’s password or to add a User and their password. The factory defined User “Admin” has such an Security Option.

The factory default Workstation software application Admin User’s password is admin. The factory defined Admin User profile can not be deleted.

Login ProcedureStep 1. From the Workstation PC’s Windows application, select Start >All Programs >Facilities

Monitoring >Workstation. The Workstation software applications starts.Step 2. From the Workstation Main Menu select File >Login. The User Login window displays.

Step 3. Click on “Admin” the User Name field.Step 4. Type in the password and then click on the OK button.

NOTE: You may also login by clicking the current user displayed in the upper right corner of the Workstation display. This will also open the User Login window.

34 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 35: Onyxworks Workstation

Add a Network Connection to the Workstation ONYXWorks® Workstation System Connections

4.4 Add a Network Connection to the WorkstationAs an Admin User you can use an automated method to establish a connection to your network if you are adding the Workstation to an existing ONYXWorks® system.

4.4.1 About Adding an Existing Gateway When you first start the Workstation you can automatically connect gateways that are physically connected or available through your ONYXWorks® system to the Workstation using PC Monitor operations.

Existing Network Connection ProcedureStep 1. Locate and right click on the PC Monitor icon in the Windows system tray and then select

Import System Data... from the list of choices. The Select System To Import From window displays.

Step 2. Select an entry from the list of choices and then click on the OK button.

Figure 4.4 Select System To Import From Window

35ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 36: Onyxworks Workstation

ONYXWorks® Workstation System Connections Add a Network Connection to the Workstation

4.4.2 About Adding a New Network ConnectionThe Admin User creates a Network name and then adds a gateway. Network Names and gateway connections are created using the Configuration Tool. The Configuration Tool is launched from Workstation’s main menu.

New Network Connection ProcedureStep 1. Start the Workstation software application (Start >All Programs >Facilities Monitoring

>Workstation). The Workstation software applications starts.Step 2. Login to the Workstation (Admin = admin).Step 3. Launch the Configuration Tool from the Workstation’s Main Menu (select Configure

>Launch Configuration Tool). The Network Configuration window displays.Step 4. Select Network >Add Network... The Network Properties window displays.Step 5. Type in the network’s name into the Alias field.Step 6. Select the Type down arrow and select the type of network from the list of choices.Step 7. Click on the Gateway Connection field’s Add Gateway icon (mouse over). The Gateway

Properties window displays.Step 8. Add the gateway using one of the following:

• Type in the Gateway’s IP Address.• Select a gateway from the list of Online Gateways.

The list of online gateways is filtered for the type of gateway selected in the Online Gateway field. For example, if you are adding an NFN gateway, you would select NFN as the type, then only the addresses of NFN gateways running on the system will be displayed in the list.

Step 9. Request nodes to added to Network.a. Expand the Navigation Tree to display the gateway’s IP address.b. Right click on the IP address and then select Request Nodes from the list of choices.

The Tree will populate and display all the nodes configured on that network.Step 10. Click on the OK button.Step 11. You must Exit the Configuration Tool and then respond to the Save Changes prompt with

the applicable button click to update the Workstation with the information created in this procedure.

36 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 37: Onyxworks Workstation

Auto-Create Gateway Point IDs ONYXWorks® Workstation System Connections

Network Right Click CommandsIn the Navigation Tree you can right click on a Network name and select these commands from the list of choices.

Add Node

Use this command to add a Node to your network. You will need to select the Node Type from a list of choices and type in the IP address of that node.

Import Database

Use this command to import a Verifire database. A Verifire database can be located and then selected, any nodes and points that are in the database will be auto-created on the Network.

Rename

Use this operation to type in a new name for the Network which is the equivalent of replacing the Network Alias on the Properties window.

Delete

Use this command to delete the Network, a confirmation prompt will display allowing you to cancel the command.

Properties

Use to add a redundant gateway to the Network, adding two gateways to one Network will set up gateway redundancy. You can also change the Network Alias name on this Network Properties window.

4.5 Auto-Create Gateway Point IDs

4.5.1 About Auto-Creating Gateway Point IDsA gateway’s nodes and the node’s points can be manually added and defined with the Configuration Tool, however it is highly recommended that the auto-creating method be used instead. The auto-creating method captures the node’s exact point ID. It is highly recommended that when initially configuring a facilities monitoring network that it be modified offline and not be modified while the Workstation is monitoring the gateway.

Network Node and Point ID Auto-Creation ProcedureUse this procedure as a guideline for creating your gateways icon for your gateway’s points.

Step 1. Make sure the connection between the respective networks and the monitoring Workstation is made.

Step 2. Start the monitoring Workstation software application.Step 3. If you have not already done so perform the steps in “Add a Network Connection to the

Workstation” on page 35.Step 4. Work with others to initiate troubles in the gateway devices (points) that will be reported

as off normal events to the monitoring Workstation.• The troubles in those points will automatically create an icon on the monitoring

Workstation screen (64 icons per screen before another screen is automatically added).• Those icons will have the exact point ID.• When points are auto-created a system backup should be performed using the

monitoring Workstation’s PC Monitor.Step 5. If applicable to your situation, you are now ready to “Workstation Database

Modifications” on page 38.

37ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 38: Onyxworks Workstation

ONYXWorks® Workstation System Connections Workstation Database Modifications

4.6 Workstation Database ModificationsUse this procedure as a guideline for creating and modifying a database. It it is recommended that you use a Configuration PC because of how it is defined. A Configuration PC is defined as a PC that has the Configuration Tool installed on it but is it not monitoring a life safety system.

Step I. Database Backup Creation ProcedureOn the monitoring Workstation use one of the following procedures to create a copy of the database.

Create a Copy of Database on the Workstation with PC Monitor

In this procedure you will create a backup copy of the database and then copy it to an external storage device.

Step 1. Right click on the monitoring Workstation’s PC Monitor and then select Backup System Data... The Browse For Folder window displays.

Step 2. Browse to a monitoring Workstation folder location and make a new folder (Create New Folder button) to copy the backup files to.

Step 3. Use Windows Explorer to copy the monitoring folders and files you created in Step 2 to an external storage device (USB flash-drive or CD-ROM).

Step 4. If necessary copy the folder and files to a read and write external storage device location.Step 5. Start the Configuration Tool. A Configuration Tool window displays.Step 6. Select the Locate Database to Edit icon. The Synchronize Data window displays.Step 7. Click on the Browse button to locate and then open the *.mdb database file in its location.Step 8. Click on the OK button. An import window will temporary display and then the

Configuration Tool main window will display.Step 9. Perform the “Step II. Database Modification Procedure” on page 39.

Create Database On the Configuration PC with the Configuration Tool

In this procedure you will connect the Configuration PC to the same IP network as a Workstation and then import its database.

Step 1. Connect the Configuration PC to the IP network the monitoring Workstation IP network.Step 2. Make the necessary IP settings to the Configuration PC.Step 3. Start the Configuration Tool. A Configuration Tool window displays.Step 4. Select the Locate Database to Edit icon. The Synchronize Data window displays.Step 5. Select a Workstation IP address in the Select System to Import field.Step 6. Click on the OK button. An import window will temporary display and then the

Configuration Tool main window will display.Step 7. Perform the “Step II. Database Modification Procedure” on page 39.

NOTE: It is highly recommended you create a folder because the Backup System Data operation will create several folders and files, so grouping them in that one folder is desirable.

38 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 39: Onyxworks Workstation

Workstation Database Modifications ONYXWorks® Workstation System Connections

Step II. Database Modification ProcedureIn this procedure you will edit and then save the database.

Step 1. On the Configuration Tool main window click on the Screen Objects icon. The Screen Object window displays.

Step 2. Edit the database (refer to the Configuration Tool manual for information about editing a database).

Step 3. Exit the Configuration Tool and then respond to the Save Changes prompt with a Yes button click to update the database.

Step 4. Perform the "Step III. Importing the Modified Database Procedure".

Step III. Importing the Modified Database ProcedureUse the applicable procedure to import your modified database back into the ONYXWorks® system.

Database Import from an External DeviceStep 1. On the Configuration PC right click on its PC Monitor and select Backup System Data...

The Browse For Folder window displays.Step 2. Browse to a Configuration PC folder location and make a new folder (Create New Folder

button) to copy the backup files to.Step 3. Use Windows Explorer to copy the folder on the Configuration PC to an external storage

device.Step 4. Exit all the ONYXWorks® system software applications that are running on the

monitoring Workstation except PC Monitor.Step 5. Right click on the monitoring Workstation’s PC Monitor icon and select Login.Step 6. Select a User and type in their password (Admin = admin).Step 7. Right click on the monitoring Workstation’s PC Monitor icon and then select Restore

System Data... from the list of choices. The Browse for Folder window displays.Step 8. Use the Browse for Folder window’s browse capability to locate the folder on the external

storage device that contains the backup files and select it.Step 9. Click on the OK button. The edited files are installed on the monitoring Workstation.Step 10. Restart monitoring Workstation and all of its relative the ONYXWorks® system software

applications.Step 11. Verify your modified database displays correctly.Step 12. You have completed "Workstation Database Modifications".

Database Import from a Configuration PCStep 1. Connect the Configuration PC to the IP network the monitoring Workstation IP network.Step 2. Start the Configuration PC’s version of the PC Monitor.Step 3. Right click on the PC Monitor icon and then select Export System Data to all Workstations

from the list of choices.Step 4. Go to a monitoring Workstation and verify your modified database display correctly.Step 5. You have completed "Workstation Database Modifications".

39ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 40: Onyxworks Workstation

ONYXWorks® Workstation System Connections Workstation Database Modifications

40 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 41: Onyxworks Workstation

Section 5 Workstation Software Configuration

5.1 Workstation Software Application Configuration Overview

NOTE: The Workstation must be logged into before any of its settings can be configured. A User that has the Security Option to configure settings needs to login to change an existing setting. The factory defined User “Admin” has such a Security Option. Information in this document is written assuming that a User with the equivalent Security Option of the “Admin” User will be performing the procedures in this document.

41ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 42: Onyxworks Workstation

Workstation Software Configuration Workstation Software Application Configuration Overview

The sequence in which these tasks are performed is determined by the Admin User performing them and this list is a suggested guideline to ensure that Workstation software application is configured correctly.

Figure 5.1 Workstation Software Configuration

“ONYXWorks® Workstation System Connections” on

page 31

“Hardware, Printer, and Power Connections” on page 13

“Windows® Software Configuration” on page 25

“Workstation Software Configuration” on page 41

“Workstation Screen Graphical User Interface Management” on

page 77

Start

Finished

“System Options Configuration” on page 64

“Workstation Software Application Configuration

Overview” on page 41

“Admin User Log In Configuration” on page 43

“Monitoring Profile Configuration” on page 44

“Workstation Software Application Options

Configuration” on page 47

“Control Profiles Configuration” on page 61

“Macro Command Configuration” on page 70

“Color and Sound Configuration” on page 73

“Fan Monitor Configuration” on page 74

“Voice Paging Configuration (Optional Feature)” on page 75

“User Configuration” on page 66

42 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 43: Onyxworks Workstation

Admin User Log In Configuration Workstation Software Configuration

5.2 Admin User Log In Configuration

5.2.1 About the Factory Defined User Profiles and their Passwords

The Workstation must be logged into before any of its settings can be configured. A User that has the Security Option to change a password needs to login to change an existing User’s password or to add a User and their password. The factory defined User “Admin” has such an Security Option.

The factory default Workstation software application Admin User’s password is admin. The factory defined Admin User profile can not be deleted.

5.2.2 Admin User Password Change ProcedureIt is highly recommended that the Admin User change the factory defined Admin User’s password to secure the Workstation. The steps to change any User’s password are the same. Refer to “User Additions Procedure” on page 69 for details about adding and deleting other Users.

Step 1. From the Workstation Main Menu select File >Login. The User Login window displays.

Step 2. Click on “Admin” the User Name field. Only the Password and Re-enter Password fields enable.

Step 3. Type the new password into the Password field.• Passwords are case-sensitive.• Alpha and numeric characters are supported.• 1 character minimum and 15 character maximum.

Step 4. Type the same new password into the Re-enter Password field.

Step 5. Click on the Apply button. The fields on the User Editor window disable.Step 6. Click on the Close button to complete the password change.

NOTE: You may also login by clicking the current user displayed in the upper right corner of the Workstation display. This will also open the User Login window.

NOTE: Please make note of the password because the new password can NOT be retrieved from the Workstation.

NOTE: The Security Option check boxes can not be changed for the Admin User.

43ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 44: Onyxworks Workstation

Workstation Software Configuration Monitoring Profile Configuration

5.3 Monitoring Profile Configuration

Figure 5.2 Monitoring Profiles Window

5.3.1 About Monitoring ProfilesMonitoring Profiles allows the Admin User to select what nodes will be monitored by a Workstation. The profile is defined for a specific network and or node on a network. That profile determines what events are displayed by the Workstation. By using Monitoring and Control Profiles (page 61), supervision of portions of the network is possible. Monitoring Profiles can be created and saved using the fields on the Monitoring Profiles window.

Monitoring Profiles are event annunciation filters that are setup to monitor or not to monitor an event location and its event type at the Workstation.

• The event’s location in the system is selected in the Network|Node Assignment area of the window.

• The event location’s event type (fire alarms, security, etc.) is selected in the Device Selection Status area of the window.

The factory defined Monitoring Profile Default is set to monitor all networks and nodes. The first Monitoring Profile created will be based on that Default profile. Therefore to not display any desired networks or nodes and their respective event types, the profile will need to be modified and then changes applied.

NOTE: Monitoring Profiles must be configured before "Local Event Printer Configuration", "Pager/Modem Configuration", or "E-Mail Configuration" can take place.

44 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 45: Onyxworks Workstation

Monitoring Profile Configuration Workstation Software Configuration

5.3.2 Monitoring Profile Creation ProcedureStep 1. From the Workstation Main Menu select Configure >Monitoring Profiles. The

Monitoring Profiles window displays.Step 2. Click on a profile listed in the Monitoring Profile column of the window. The Default

entry maybe the only one listed.Step 3. Click on the Add Profile button. A Monitoring Profile window with text already in the

field displays.Step 4. Replace the current text by typing in a unique name for the profile (duplicate profile

names cannot be created) and then click on the OK button. The profile is added to the list of profiles.

Step 5. Click on the newly added profile then:a. Click in the Network|Node Assignment’s Monitored column adjacent to desired entry

and set it to be monitor ( ) or not monitored (X).b. Click in the Device Status Selection’s Monitored column adjacent to desired entry and

set it to be monitor ( ) or not monitored (X).c. Repeat the previous steps until the desired level of monitoring is achieved.

Step 6. Click on the Apply button to apply the changes to profile.Step 7. Click on the Activate Profile button. This step makes the profile available for the printer,

pager, and email setup.Step 8. Click on the OK button to close the window.

NOTE: The Cancel button will not cancel changes if one of the other buttons has been previously clicked.

45ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 46: Onyxworks Workstation

Workstation Software Configuration Monitoring Profile Configuration

5.3.3 Existing Monitoring Profile ManagementEditingStep 1. In the list of profiles click on the profile to edit.Step 2. Modify Network|Node Assignment’s and or Device Status Selection.Step 3. Click on the Apply button.

DeletingStep 1. In the list of profiles click on the profile to delete.Step 2. Click on the Remove Profile button. A profile window prompt displays.Step 3. Select the Yes button.

• If the profile is NOT used in a printer, pager, modem, or email setup it will be deleted.• If the profile is used in a printer, pager, modem, or email setup a window prompt will

display indicating you can not delete it. You must revise the printer, pager, modem, or email setup to use another profile or delete that printer, pager, modem, or email profile that uses the profile you want to delete.

CopyingStep 1. In the list of profiles click on the profile to copyStep 2. Click on the Copy Profile button.Step 3. Name the profile.Step 4. Modify Network|Node Assignment’s and or Device Status Selection.Step 5. Click on the Activate Profile button. This step makes the profile available for the printer,

pager, and email setup.Step 6. Click on the Apply button.

46 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 47: Onyxworks Workstation

Workstation Software Application Options Configuration Workstation Software Configuration

5.4 Workstation Software Application Options ConfigurationThe Workstation Configure >Options command displays the Options window where these setup tasks are performed.

• “Output Configuration” on page 48• “Local Event Printer Configuration” on page 50• “Pager/Modem Configuration” on page 52• “E-Mail Configuration” on page 55• “General Operation Configuration” on page 57• “User Features Configuration” on page 60

47ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 48: Onyxworks Workstation

Workstation Software Configuration Workstation Software Application Options Configuration

5.4.1 Output Configuration

Figure 5.3 Options Window - Output Configuration

About the Output FormatsAn Output is the format of data that will be sent to a local event printer and individuals with a pager and or email. Once you have created and named an Output Format you will select it from the list of choices on the windows where you will setup the local event printer, pagers, and or email.

User Defined Messages

Although it can used with any Output format, it is highly recommended for a pager format you use the Available Fields’ User Defined selection. That selection allows you to enter brief descriptions for the User Defined Messages. Once User Defined is displayed in the Format Fields, the User Defined Messages area is activated. Click in field adjacent to the User Defined Messages’ name and type in a brief message that can be received on a pager.

NOTE: Monitoring Profiles must be configured before "Local Event Printer Configuration", "Pager/Modem Configuration", or "E-Mail Configuration" can take place.

48 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 49: Onyxworks Workstation

Workstation Software Application Options Configuration Workstation Software Configuration

Output Formats Configuration ProcedureStep 1. From the Workstation Main Menu select Configure >Options. The Option window

displays.Step 2. Click on the Output tab.Step 3. Click on the Add Format button. A window prompt with text already in the field displays.Step 4. Replace the current text by typing in a unique name (duplicate names cannot be created)

and then click on the OK button.Step 5. Select the types of information you want included in the Output Format from the list of

Available Fields. Once selected they will move and display in the Format Fields area of the window. Several methods of selecting can be used:• Double click on the entry.• Click on an entry and then click on the right arrow button.• Click on several; chose first, then last in list (press and hold the shift key) and then

click on the right arrow button. Press and hold the Ctrl key to select them.Step 6. Click on the Apply button when you have completed the choices. The Output Format is

now available for the printer, pager, and email setup.

Existing Output Format Management

Modify an Output FormatStep 1. Click on the Output Format field’s down arrow and select an existing name from the list of

choices. The previous choices for the Output Format display in the Format Fields area of the window.

Step 2. Select the types of information you want included or excluded in the Output Format from the list of Available Fields/Format Fields (refer to "Output Formats Configuration Procedure" for information about selecting, de-selecting is similar but done in reverse).

Step 3. Click on the Apply button when you have completed the choices.

Delete an Output FormatStep 1. Click on the Output Format field’s down arrow and select an existing name from the list of

choices. The previous choices for the Output Format display in the Format Fields area of the window.

Step 2. Click on the Delete Format button. An Output Format window prompt displays.Step 3. Select the Yes button.

• If the Output Format is NOT used in a printer, pager, modem, or email setup the selected Output Format will be deleted.

• If the Output Format is used in a printer, pager, modem, or email setup a window prompt will display indicating you can not delete the Output Format. You must revise the printer, pager, modem, or email setup to use another Output Format or delete that printer, pager, modem, or email profile that uses the Output Format you want to delete.

49ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 50: Onyxworks Workstation

Workstation Software Configuration Workstation Software Application Options Configuration

5.4.2 Local Event Printer Configuration

About Local Event Printer Configuration Windows procedures and operation apply when installing a printer’s driver and setting it up. Adding a printer and changing its printing preferences are standard Windows operation, consult Windows information.

A local event printer must have a buffer size of at least 32K and be able to set to these settings:

NOTE: “Monitoring Profile Configuration” on page 44 and “Output Configuration” on page 48 must be performed before this configuration can take place.

• Baud Rate: 9600 • Parity: None • Data Bits: 1 Stop Bit • Stop Bits: 8 Bits

NOTE: The NOTIFIER® PRN-6 printer is a UL listed printer and can be used as this Local Event Printer.

50 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 51: Onyxworks Workstation

Workstation Software Application Options Configuration Workstation Software Configuration

Local Event Printer Configuration Procedure

Step 1. Install the printer’s driver using Windows operations. You must name this Local Event Printer “Local Event Printer” using Windows operations. Consult Windows information for details about naming the printer.

Step 2. From the Workstation Main Menu select Configure >Options. The Option window displays.

Step 3. Click-on the Printer’s tab.Step 4. Make these settings:

• Select Local in the Location field.• Select Enable in the Enabled field.• Select a Monitoring Profile (refer to “Monitoring Profile Configuration” on page 44).• Select a Output Profile (refer to “Output Configuration” on page 48).

Figure 5.4 Options Window - Printer Configuration

Step 5. Click the Apply button. The Sample Output displays according the Output Profile selected.

Existing Printer Configuration ManagementAn existing local event printer configuration can be modified. Set the Location to None when the printer is physically disconnected from the Workstation. Change the Enable to Disable (stops printing), change Monitoring Profile or Output Profile settings. After any modification click the Apply button.

NOTE: A Local Event Printer can only be setup after it has been connected, refer to “Local Event Printer Connection” on page 19.

51ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 52: Onyxworks Workstation

Workstation Software Configuration Workstation Software Application Options Configuration

5.4.3 Pager/Modem Configuration

About Pager/Modem ConfigurationThe Pager/Modem functions provide the capability to send system information via a modem that is connected to a Workstations COMM port to a person’s pager. This configuration uses Monitoring Profiles and Output formats to determine the information that is sent. The modem needs to be connected and configured before a pager is added.

Pager Modem Configuration ProcedureStep 1. From the Workstation Main Menu select Configure >Options. The Options window

displays.Step 2. Click on the Pager/Modem tab.Step 3. Make Modem settings.

• Dialing Delay range: 10 to 30 seconds.• Retry Delay range: 10 to 30 seconds.• Number of Retries range: 0 to 3.• Time Out range: 45 to 300 seconds.• Group Time Window range: 0 to 30 seconds

Figure 5.5 Options Window - Modem Configuration

Step 4. Click the Apply button.

Pager Modem Configuration ProcedureStep 1. If you are using an external modem connect it to a Workstation COMM port.Step 2. From the Workstation Main Menu select Configure >Options. The Options window

displays.Step 3. Click on the Pager/Modem tab.Step 4. Make Modem settings.

• Type in the COMM port used on the Workstation.• Dialing Delay range: 10 to 30 seconds.• Retry Delay range: 10 to 30 seconds.• Number of Retries range: 0 to 3.• Time Out range: 45 to 300 seconds.

NOTE: “Monitoring Profile Configuration” on page 44 and “Output Configuration” on page 48 must be performed before this configuration can take place.

52 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 53: Onyxworks Workstation

Workstation Software Application Options Configuration Workstation Software Configuration

• Group Time Window range: 0 to 30 seconds

Figure 5.6 Options Window - Modem Configuration

Step 5. Click the Apply button.

53ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 54: Onyxworks Workstation

Workstation Software Configuration Workstation Software Application Options Configuration

Pager User Configuration ProcedureStep 1. From the Workstation Main Menu select Configure >Options. The Options window

displays.Step 2. Click on the Pager/Modem tab.Step 3. Click on the Add Pager button. A window prompt with text already in the field displays.Step 4. Replace the current text by typing in a unique name (duplicate names cannot be created)

and then click on the OK button.Step 5. Make these settings:

• Type in the pager phone number.• Type in the PIN.• Select Enable in the Enabled field.• Select Max C (Maximum Characters).• Select Monitoring times.

• If Yes is selected, the message will be sent when it occurs according to the parameters set in "Pager User Configuration Procedure".

• If No is selected, you will need to set the Start and Stop times. You can select a specific span of hours to send emails or pages by choosing a Start time and then a Stop time. Then emails or pages will only be sent for events that occur during that occur between the Start and Stop times.

• Select a Monitoring Profile (refer to “Monitoring Profile Configuration” on page 44).• Select a Output Profile (refer to “Output Configuration” on page 48)

Figure 5.7 Options Window - Pager Configuration

Step 6. Click the Apply button. The Sample Output displays according the Output Profile selected.

Existing Pager Configuration Management

Delete a PagerStep 1. Click on a name in the Pager field.Step 2. Click on the Delete Pager button.Step 3. Respond to the delete confirmation window prompt.

Modify a Pager

An existing pager configuration can be modified. Change any field using the steps in the "Pager User Configuration Procedure". Disable the pager to keep the pager listed but to stop sending pages to it.

54 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 55: Onyxworks Workstation

Workstation Software Application Options Configuration Workstation Software Configuration

5.4.4 E-Mail Configuration

About E-Mail ConfigurationThe E-Mail functions provide the capability to send system information via your email server to an email account. This configuration uses Monitoring Profiles and Output formats to determine the information that is sent. The server configuration should be done before an email account is added.

E-Mail Source Configuration ProcedureStep 1. Make sure you have an established connection between your email server and the

Workstation.Step 2. From the Workstation Main Menu select Configure >Options. The Options window

displays.Step 3. Click on the E-Mail tab.Step 4. Make E-Mail Source settings.

• Type in the your mail server address in the SMTP Server field.• Type in the return address you want displayed for the email receiver.• Type in a Site name.

Figure 5.8 Options Window - Modem Configuration

Step 5. Click the Apply button.

NOTE: “Monitoring Profile Configuration” on page 44 and “Output Configuration” on page 48 must be performed before this configuration can take place.

55ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 56: Onyxworks Workstation

Workstation Software Configuration Workstation Software Application Options Configuration

E-Mail User Configuration ProcedureStep 1. From the Workstation Main Menu select Configure >Options. The Options window

displays.Step 2. Click on the E-Mail tab.Step 3. Click on the Add E-Mail button. A window prompt with text already in the field displays.Step 4. Replace the current text by typing in a unique name (duplicate names cannot be created)

and then click on the OK button.Step 5. Make these settings:

• Type in the email address.• Select Enable in the Enabled field.• Select Monitoring times.

• If Yes is selected, the message will be sent at the time it occurs.• If No is selected, you will need to set the Start and Stop times.

• Select a Monitoring Profile (refer to “Monitoring Profile Configuration” on page 44).• Select a Output Profile (refer to “Output Configuration” on page 48)

Figure 5.9 Options Window - Pager Configuration

Step 6. Click the Apply button. The Sample Output displays according the Output Profile selected.

Existing E-Mail Configuration Management

Delete a E-MailStep 1. Click on a name in the Name field.Step 2. Click on the Delete E-Mail button.Step 3. Respond to the delete confirmation window prompt.

Modify a E-Mail

An existing email configuration can be modified. Change any field using the steps in the "E-Mail User Configuration Procedure". Disable the email name to keep the email account listed but to stop sending email to it.

56 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 57: Onyxworks Workstation

Workstation Software Application Options Configuration Workstation Software Configuration

5.4.5 General Operation ConfigurationThe functions provided on this “General” tab window allow the Admin User to configure overall settings for Workstation operations. This information is not written in procedural form because the sequence in which you choose to enable options is not necessary..

Figure 5.10 Option Window - General Configuration

57ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 58: Onyxworks Workstation

Workstation Software Configuration Workstation Software Application Options Configuration

.

Figure 5.11 Option Window - General Configuration

Event Label Buttons

Network Alias

Display the name assigned to the network using the Configuration Tool.

None

Doesn’t display the assigned name.

Node Label

Node Alias

Display the name assigned to the node using the Configuration Tool.

Node Number

Display the node number assigned to the node using the Configuration Tool.

None

Doesn’t display the assigned name or number.

Point Label

Point Alias

Display the name assigned to the point using the Configuration Tool.

Point Number

Display the point number assigned to the node using the Configuration Tool.

None

Doesn’t display the assigned number or name.

58 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 59: Onyxworks Workstation

Workstation Software Application Options Configuration Workstation Software Configuration

Icon Label FieldUse this selection to display the icon label. This selection is directly coupled to the choice made with the Event Label buttons.

Miscellaneous Check Boxes

Show Only Off Normal Devices

This selection will only display icons of points that are off normal (alarm, trouble, etc.). If there are no current events on the system there will be no points visible in the graphics display.

Autoactivate Next Event After Acknowledge

Use this select to auto-activate based on the acknowledge command. Once any events in the New Events window are acknowledged, the next event will autoactivate any linked files which are set to do so. This selection will also cause auto-navigation (if set). Not only will the next event display its' auto-activate linked media file will respond and the system will move to the Workstation floorplan area where that device is located.

By default, points with linked media files which are set to auto-activate for events will only do so when they are the first event to appear in an empty New Events window. If an event is annunciated for a point and any other events are currently in the New Events window, then any linked files will not be autoactivated.

Automatically Navigate on Event

Use this selection to have the Workstation software application automatically display the screen where an off-normal event is taking place. It is recommended that this setting be enabled to ensure the highest level of response to an event.

Extract Descriptions From Panel

Use this selection to assign point descriptions as they are reported from the panel instead of using the locally defined descriptions. This description is coupled with the Event Box Label and displays the point description or properties.

Most control and alarm panels contain a description that is sent over the network with panel messages. This option allows the Admin User to select whether these descriptions are used for each node or if the descriptions are entered at the Workstation when points are assigned for the panel. This feature applies only to nodes that have the capability to provide such a description.

History Backup FieldsNumber of days before performing history backup: Is used to periodically capture the local history file after the previous backup. The external backup file is named with the date: YYYYMMDD.HIS.

Number of days to keep history following backup: Is used to periodically empty the local history file of everything except a specified number of days’ data. The external backup file is named with the date: YYYYMMDD.HIS.

If this option is not checked and number of days set, the history database will continue to increase in size indefinitely, until it is backed up manually (refer to “About Database Management” on page 88).

59ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 60: Onyxworks Workstation

Workstation Software Configuration Workstation Software Application Options Configuration

5.4.6 User Features ConfigurationThis information is not written in procedural form because the sequence in which you choose to modify the fields is not necessary.

Figure 5.12 Options Window - User Feature Configuration

About Un-acked Event Alarm Configuration DescriptionsThese function manages how the Workstation software application supervises a User acknowledgement of new events. In security circles, this feature is commonly known as a “Dead Man.” When enabled, this function monitors the New Event window status and activity.

Unacked Event Timeout (3-60 Minutes)

When an event appears in the New Event window a timer is started and will run for a Admin User defined time (3 – 60 min.).

• If a User acknowledges an event before the timer expires, no action is taken.• If any other events are outstanding in the New Event window, the timer is reset and starts

again; otherwise, it is canceled.• If the timer expires before an event is acknowledged, then a Admin User defined macro is

initialized. This macro either activates or deactivates an output on the network (also Admin User defined). When the User selects this macro it creates an event when the output is activated/deactivated. The output can be used to trip any external point (horn, strobe, pager etc.) provided by the installer. Once the User acknowledges all New Events, a second Admin User defined macro is performed and that macro contains the reverse commands of the first macro.

Macro Activated on Alarm Is used to select from Admin User defined macros. For more details on defining macros, refer to “Macro Command Configuration” on page 70.

User ResponsesTheses fields on this window allow the Admin User to modify the preset definitions that display for an event into custom responses. The text in these fields is text that will be displayed on a User response window as check-box options. When the Users makes a check-box selection it is recorded in the history data file.

60 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 61: Onyxworks Workstation

Control Profiles Configuration Workstation Software Configuration

5.5 Control Profiles Configuration

5.5.1 About Control ProfilesControl Profiles allows the Admin User to select what network and nodes will be controlled by a Workstation. Also Control Profiles allows the right-click menu options (enable, disable, arm, disarm etc.) on point icons or events in the events boxes. The profile is defined for a specific network and or node on a network. That profile determines when a message is sent to a node, or an event for a point type is acknowledged, that message or acknowledgment would only be received locally if the Workstation did not have control of that node. Sometimes a User does not always monitor or respond to events that may occur in other monitored locations in the system. By using Monitoring (page 44) and Control Profiles, supervision of portions of the network is possible. Control Profiles can be created and saved using the fields on the Control Profiles Configuration window.

Control Profiles can be configured to include or exclude any combination of nodes being monitored and controlled by the system. Control Profiles can be selected at the network and node levels in a network’s hierarchy.

In the Control Profile Select window under the PROFILES heading is the name of the Control Profile. Adjacent to the PROFILES heading is the hierarchy of networks and nodes on the network for that profile. There is a Controlled By field that displays the IP address of the Workstation that has control of that portion of the system or None if no Workstation has control.

If a Workstation does not have control of a node, all actions taken at a Workstation in regards to that node are local only. For example, an acknowledge command at the Workstation tallies on the Workstation, but the node doesn’t receive it. In addition, only one Workstation can have control of any node at any time. When control of a node is activated at a Workstation, it is deactivated at the other Workstation that previously had control.

It might be necessary to assume control of a profile or node from the current Workstation, in doing it is important to know that in doing so, only one Workstation can control any single profile or point at a given time.

The factory defined Control Profile Default is set to not control any networks and nodes. The first Control Profile created will be based on that Default profile. Therefore to control networks or nodes the profile will need to be modified and then changes applied.

61ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 62: Onyxworks Workstation

Workstation Software Configuration Control Profiles Configuration

5.5.2 Control Profile Creation ProcedureStep 1. From the Workstation Main Menu select Configure >Control Profiles. The Control

Profiles Configuration window displays.Step 2. Click on the Add Profile button. A window prompt with text already in the field displays.Step 3. Replace the current text by typing in a unique name (duplicate names cannot be created)

and then click on the OK button. The profile is added to the list of profiles.Step 4. In the Control Profiles column click on the newly added profile then modify it in the In

Profile column by:• Adding ( ).• Removing (X).

Step 5. When the desired level of control is achieved click on the Apply button to apply the changes to profile.

Step 6. Click on the Activate Profile button.Step 7. Click on the OK button to close the window.

NOTE: The Cancel button will not cancel changes if one of the other buttons has been previously clicked.

62 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 63: Onyxworks Workstation

Control Profiles Configuration Workstation Software Configuration

5.5.3 Existing Control Profile ManagementEditingStep 1. In the list of profiles click on the profile to edit.Step 2. Make In Profile changes.Step 3. Click on the Apply button.

DeletingStep 1. In the list of profiles click on the profile to delete.Step 2. Click on the Remove Profile button. A profile window prompt displays.Step 3. Select the Yes button.

CopyingStep 1. In the list of profiles click on the profile to copyStep 2. Click on the Copy Profile button.Step 3. Name the profile.Step 4. Make In Profile changes.Step 5. Click on the Activate Profile button.Step 6. Click on the Apply button.

63ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 64: Onyxworks Workstation

Workstation Software Configuration System Options Configuration

5.6 System Options Configuration

This Workstation System Options selection is made using the Configuration Tool which is launched from Workstation’s main menu; Configure >Launch Configuration Tool. Any selections made here is saved when you exit the Configuration Tool and then respond to the Save Changes prompt with the applicable button click.

5.6.1 Icon SetIcon Set SelectionStep 1. Check the Update Icons checkbox to activate the Icon Set field.Step 2. Click on the Icon Set field’s down arrow to display a list of icon choices.Step 3. Click on the OK button.Step 4. You must Exit the Configuration Tool and then respond to the Save Changes prompt with

the applicable button click to update the Workstation with the information created in this procedure.

Custom Icon Creation and SelectionIf you create and then load a custom icon set and it is missing required icons (i.e. smoke detector) then the points that require that type of icon will not be displayed. To avoid this undesirable behavior do the following.

Step 1. Create your custom icons with your graphic software application (256 x 256 PNG file formats highly recommended).

Step 2. Auto-create your points on the Workstation (refer to “Auto-Create Gateway Point IDs” on page 37).

Step 3. Copy and paste your custom icons into the appropriate C:\FacilitiesMonitoring\Data\System folder on the Workstation:Devices - for auto-created pointsButtons - for Macro ButtonsImages - for hazard, information icons, etc.

Step 4. Launch the Configuration Tool and then edit the data base (refer to “Workstation Database Modifications” on page 38).

Step 5. Use the Configuration Tool’s spread sheet operation to find and select the existing icon that will be replaced by your custom icon.

Step 6. Use the spread sheet’s Explorer function to locate and then select the custom icon from the folder you pasted it into.

Step 7. Replace one of the existing icon names with the custom icon name.Step 8. Copy the spread sheet cell and copy and paste it into the cells containing the name of the

existing icon.Step 9. Save the spread sheet and close the window.Step 10. You must Exit the Configuration Tool and then respond to the Save Changes prompt with

the applicable button click to update the Workstation with the information created in this procedure.

NOTE: All Workstations have a System Options selection preset according to the type of Workstation ordered.

NOTE: The previously selected Icon Set does not display in the Icon Set field. The default IconSet3D displayed as grayed out.

64 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 65: Onyxworks Workstation

System Options Configuration Workstation Software Configuration

5.6.2 Operating ModesSupervising Station

This selection is described “Proprietary Supervising Station Mode Overview” on page 110.

FCC and FCC+DCC

These selection is described in “Fire Command Center (FCC) Mode Overview (PPU)” on page 106.

5.6.3 Time Server SettingsThese time server settings will apply to all applications running on any PC on the system, Workstations, PC gateways, and pc monitors.

This field is used to type in the IP address of the server that will used to dictate time for the ONYXWorks® system time.

Figure 5.13 System Options Window

NOTE: You can only select the FCC and FCC+DCC modes if you only have one NFN gateway connected to the Workstation. Those modes are not available with multiple NFN gateways or if any other type of gateway is configured for your system.

NOTE: If the Workstation’s Windows time zones or daylight saving settings are changed, all the ONYXWorks® applications must be restarted.

Embedded Gateways

External SNTP Server

Workstation

Workstations

Embedded Gateways

Workstation

Workstations

Workstations

External SNTP Server

Embedded Gateways

65ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 66: Onyxworks Workstation

Workstation Software Configuration User Configuration

5.7 User Configuration

5.7.1 About Users DefinitionsThe Admin User manages system Users and their passwords by creating a profile for a User which includes a name, a password, and a Security Option. A Security Option check box selected on the User Editor window determines what operations are available to a User. For example, some system Users may have permission to respond to point events on the Workstation (Point Control).

5.7.2 About the User DatabaseThe User database contains information on personnel who have a defined profile on the system. The Admin User has the privileges to add, edit or delete the User database. After changes are made, Users are imported from the File >Import Users selection using the User Editor. A list of IP Addresses with User databases will be displayed. Select one and then click the Import button.

5.7.3 About Point ControlsOnly if User w/Point Control is checked on the Security Options tab can these Point Control tab options be selected. These choices are only displayed and therefore selectable when a User has been designated User w/ Point Control. They are all selected if a user has been designated Administrator on the Security Options tab.

• Field Acknowledge• Silence/Reset• Enable/Disable• Activate/Deactivate• Manual Evacuation• Lock/Unlock• Arm/Disarm

5.7.4 About User Security OptionsThe User Editor window’s Security Option tab and its check boxes determine what operations are available to a User The Security Options are defined in the terms of the action that the User is allowed to perform on menu selections and events. Menu selections are implied as available for all (for example File >Login).

Table 5.1 Security Option Descriptions

Security Option Description

Default User View>History

Right Click on Device>View Linked Video>View Linked Audio>View Linked Picture>View History Of Device

66 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 67: Onyxworks Workstation

User Configuration Workstation Software Configuration

Administrator File>Print>Events>Floorplan Area

>Exit

Actions>Reset (FCC Mode Only)>Off-Normal Nodes>All Nodes

>Signal Silence (FCC Mode Only)>Off-Normal Nodes>All Nodes

>Panel Programming>Open Verifire 1020 (FCC Mode Only)>Open Verifire Tools (FCC Mode Only)

View>History (Allow user to move columns in the event lists in text mode)>Activate View/Graphics Mode>System>Armed/Disarmed Points (Supervisory Mode Only)>Background Activations

Utilities>NUP Port Statistics (FCC Mode Only)>Network Statistics (FCC Mode Only)>Software Version Numbers (FCC Mode Only)>Walk Test (FCC Mode Only)

Configure>Launch Configuration Tool >Control Profiles>Monitoring Profiles>Users>Options>Backup History

Right Click on Device/Event>View Linked Video>View Linked Audio>View Linked Picture>View History Of Device >Enter Operator Response

Any Point Control tab options (refer to “About Point Controls” on page 66).

Client Ack

Table 5.1 Security Option Descriptions (Continued)

Security Option Description

67ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 68: Onyxworks Workstation

Workstation Software Configuration User Configuration

User w/ Point Control

File>Print>Events>Floorplan Area

View>History>Activate View/Graphics Mode>System>Armed/Disarmed Points>Background Activations

Action>Notify IP

Utilities>NUP Port Statistics (FCC Mode)>Network Statistics (FCC Mode)>Software Version Numbers (FCC Mode)>Walk Test (FCC Mode)

Configure>Backup History (Allow user to move columns in the event lists in text mode)

Right Click on Device/Event>View Linked Video>View Linked Audio>View Linked Picture>View History Of Device>Enter Operator Response

Any Point Control tab options (refer to “About Point Controls” on page 66).

Client Ack

User w/ Client Control

File>Print>Events>Floorplan Area

View>History>Activate View/Graphics Mode>System>Armed/Disarmed Points>Background Activations

Configure>Backup History (Allow user to move columns in the event lists in text mode)

Right Click on Device>View Linked Video>View Linked Audio>View Linked Picture>View History Of Device>Enter Operator Response

Client Ack

Table 5.1 Security Option Descriptions (Continued)

Security Option Description

68 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 69: Onyxworks Workstation

User Configuration Workstation Software Configuration

5.7.5 User Additions and ModificationsUser Additions ProcedureThis is the method used to add an individual’s name to the User Name listing, to set their password and Security Option. A User can only change this password if the Admin User has defined a Security Option that allows them to do so. When the Workstation starts "Logged Out" is displayed in the top right corner of the screen.

Step 1. Login as the Admin User.Step 2. Main Menu select Configure >Users. The User Editor window displays.Step 3. Click-on the Add button. The Add New User window displays.Step 4. Type in entries for the first, middle, and last name fields.Step 5. Type the new password into the Password field.

• Passwords are case-sensitive.• Alpha and numeric characters are supported.• 1 character minimum and 15 character maximum.

Step 6. Type the same new password into the Re-enter Password field.Step 7. Check the appropriate Security Option box.

• Use the definition in “About User Security Options” on page 66 determine which profile to use for a User.

• If User w/Point Control is checked the Point Control tab will be displayed.Step 8. Click on the Apply button to complete adding a User.Step 9. Click on the Close button to close the window.

About User ModificationsThe steps to modify a User’s name, password, and Security Option are similar to the "User Additions Procedure".

5.7.6 About User Access to Workstation Keyboard Short-cutsPC Monitor is an application installed with the ONYXWorks® Workstation software application. It will automatically start, like Windows, when the Workstation computer is started. Its primary function is to activate other applications as required, however it is also has a selection that used to deny access to some keyboard operations.

The PC Monitor choices are accessed by right clicking on its icon located in the Windows System Tray. The icon is an arrow pointed diagonally upward.

This toggle type choice is used by the Admin User to lockout PC keyboard key combinations that allow the User to access to Windows programs outside of the Workstation software application (Windows key), to shut-down or restart the PC (Alt - Ctrl - Delete), and Windows task switching (Alt - Tab). The capability to acknowledge events is not affected when this selection is made.

A prompt is displayed indicating that this selection (checked) requires a Workstation PC reboot in order for it to take affect. The Admin User changes this setting by logging in and selecting (uncheck) the choice.

69ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 70: Onyxworks Workstation

Workstation Software Configuration Macro Command Configuration

5.8 Macro Command Configuration

5.8.1 About Macro Commands

Macro commands have interdependent relationship that is established by the Admin User. Macro Commands are created using the Configuration Tool which is launched from Workstation’s main menu; Configure >Launch Configuration Tool. Any selections made here are saved when you exit the Configuration Tool and then respond to the Save Changes prompt with the applicable button click.

Macro are created and edited on the Screen Objects window (Screen Objects icon). You access the Marco Editor function in Tools menu; Tools >Macro Editor. A Macro command is created and defined, then it is activated in one of two ways.

• A macro icon may be created in the graphics display, when clicked on the associated macro will activate.

• The Workstation will display a Macros menu item when there are any configured macros on the system and a User logged in has the Security Option and Point Control.

The Admin User creates a Macro command by naming it and assigning it a Macro command. That Macro command’s Menu list of choices will be contingent on the gateway type, point, and node type that is selected.

NOTE: Creating these settings is optional and they do not need to be made for the Workstation to function properly.

NOTE: Macros can only be edited at a Workstation when another Workstation is not editing them.

70 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 71: Onyxworks Workstation

Macro Command Configuration Workstation Software Configuration

5.8.2 Macro Creation and ManagementThe Macro List and Macro Options areas have icons (with mouse over hints) that are used to create and or manage macros. Mouse over them to display the hint about which operation each performs.

Figure 5.14 Macro Editor Window

Figure 5.15 Macro Properties Windows

Macro Creation ProcedureStep 1. Click on the Add Macro icon (mouse over). The Macro Properties window displays.Step 2. Type in a name in the Name field.Step 3. Check the Confirmation field if applicable.

Step 4. Click on the OK button.Step 5. Click on to add new option (mouse over) icon. The Macro Option Properties window

displays.Step 6. Set up the Macro’s options

a. Select a Network.b. Select a Node.c. Select a Point.d. Select an Action.e. Click the OK button.

Step 7. Click on the Close button.

NOTE: This selection means a prompt will be displayed providing you the opportunity to cancel activating the macro.

71ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 72: Onyxworks Workstation

Workstation Software Configuration Macro Command Configuration

Macro Button ProcedureMacro Buttons are created using the Configuration Tool which is launched from Workstation’s main menu; Configure >Launch Configuration Tool.

Macro buttons are created and edited on the Screen Objects window (Screen Objects icon). You access the Marco Button function in Objects menu; Add >Macro Button.

Figure 5.16 Macro Button Window

Step 1. Type in the text you want displayed for the button in the Caption field.Step 2. Select a Macro to Execute from the list of macro previously defined using the field’s down

arrow.Step 3. Chose an icon to use for the Macro button.

a. Click on the Select Icon button. A Window Explorer window displays.b. Select the icon from the Buttons folder.c. Click on the Open button. The icon displays in the Icon area.

Step 4. Click on the OK button to complete the entry.Step 5. You must Exit the Configuration Tool and then respond to the Save Changes prompt with

the applicable button click to update the Workstation with the information created in this procedure.

72 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 73: Onyxworks Workstation

Color and Sound Configuration Workstation Software Configuration

5.9 Color and Sound Configuration

Custom colors and custom sounds for different event types are created using the Configuration Tool Tools >Color and Sound Configuration command which is launched from Workstation’s main menu; Configure >Launch Configuration Tool. Any selection made here are saved when you exit the Configuration Tool and then respond to the Save Changes prompt with the applicable button click.

5.9.1 About Color Configuration SettingsThe color configuration function allows the point icons, alarm summary icons, and alarm indicator in the navigation to display custom colors on all Workstation in the system not just the Workstation where the color change was defined. The color configuration settings also change Navicon and the History Manager too. Each event type may have a custom color assigned to it. The Workstation will display that color on the point icon, alarm summary icon, and the alarm indicator on the left of the Navigation Tree.

New Color for an Event Type SelectionStep 1. Double-click on the colored rectangle next to the event type. The Color window displays.Step 2. Click one of the pre-defined basic colors or click the Define Custom Colors button to

select a customized color.Step 3. Click OK when all colors choices have been made.Step 4. Click the Save button on the Color and Sound Configuration window to update the

Workstation with the new colorsStep 5. You must Exit the Configuration Tool and then respond to the Save Changes prompt with

the applicable button click to update the Workstation with the information created in this procedure.

Figure 5.17 Color Configuration

NOTE: Making these settings is optional and they do not need to be made for the Workstation to function properly.

NOTE: Multiple Workstation systems will require a color change be made to each Workstation if the desired color change is needed for every Workstation.

NOTE: To fully update the Workstation with the new color configuration, the Workstation software application must be exited and then restarted.

73ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 74: Onyxworks Workstation

Workstation Software Configuration Fan Monitor Configuration

5.9.2 About Sound Configuration SettingsEach event type may be configured to play a different sound and by default each event type will have a different factory defined sound already. For example a fire alarm sound may be configured so that it is distinctly different from the sound of a trouble event. The Color and Sound Configuration tab displays the currently configured sound in the Wave File window.

Sound Changes

Step 1. Click the inside the Wave File field An Open window will display.Step 2. Select the desired wave file and click the Open button. The name of the newly selected

file will be displayed in the Wave File window.Step 3. Click the Save button to update the Workstation software with the new sounds.

Figure 5.18 Choosing a Sound File

5.10 Fan Monitor Configuration

5.10.1 About Fan MonitoringPC Monitor is an application installed with the ONYXWorks® Workstation software application. It will automatically start, like Windows, when the Workstation computer is started. Its primary function is to activate other applications as required, however it can used to monitor the Workstation PC fan.

The PC Monitor choices are accessed by right clicking on its icon located in the Windows System Tray. The icon is an arrow pointed diagonally upward.

5.10.2 Monitor Fan SetupThis selection toggles between fan monitoring active (checked) or fan monitoring disabled (unchecked). When monitoring is enabled, the system keeps track of whether the computer’s fan is working or not. A check appears next to the option if it is active.

NOTE: To able to define a sound for an event; a sound file in a *.wav format must be placed into the Workstation’s ... \Applications\Configuration Tool\Sounds folder.

NOTE: Creating this settings is optional and it does not need to be made for the Workstation to function properly.

74 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 75: Onyxworks Workstation

Voice Paging Configuration (Optional Feature) Workstation Software Configuration

5.11 Voice Paging Configuration (Optional Feature)

5.11.1 About the Voice PagingThis function is intended to be used to send live voice messages during a non-fire facility emergency and general paging. Fire emergency and relocation messages should not be broadcast over this Voice Over IP function. Select Action >Notify IP to display the window.

Set up this function to allow the User to send live voice messages to remote sites on the network. The Voice Paging function allows the Admin User to individually select and activate paging destinations. Refer to the respective ONYXWorks® NFN Gateway manual (Embedded/PC) for additional voice paging information.

Figure 5.19 Voice Paging Window

Network Name - Previously defined as a connected gateway only.

Paging Zone - Name typed into Paging Label field on Audio Setup window.

Activate Paging - Check-box toggle for activation.

Paging Status - Idle, Audio Channel Open, and Access Denied can be displayed.

Start Paging - Sends a command to each Paging Zone that is selected in Audio Setup windows.

Stop Paging - Returns the paging status to Idle, five second delay before the audio channel is closed.

Add - Accesses the functionality to add a Paging Zone.

Delete - Accesses the functionality to delete a Paging Zone.

Edit - Accesses the functionality to edit an existing Paging Zone.

Cancel - Closes the current window without making changes to setup.

75ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 76: Onyxworks Workstation

Workstation Software Configuration Voice Paging Configuration (Optional Feature)

5.11.2 About a Public Address AmplifierRefer to the product’s manual for information about priority configuration.

• The Public Address Amplifier (PAA) and the Workstation must have a common AC power source (Refer to “Uninterruptable Power Supply (UPS) Installation” on page 20).

• The PAA can drive up to 250 ACT-2 audio coupling transformers. However, the strength and quality of the audio signal will diminished with increased wire length.

• Do NOT run cable adjacent to or in the same conduit as 120 VDC service, “noisy” electrical circuits that are powering mechanical bells and horns, audio circuits 25 volts RMS, motor control circuits, or SCR power circuits.

• NOITIFY-IP paging takes the lowest priority at the XPIQ.

5.11.3 Voice Paging Setup ProcedureThe Audio Setup window is used to create Paging Zones that can only be defined for previously defined NFN Gateways. Paging Zones cannot be programmed during an active page.

Step 1. Main Menu select Action >Voice Paging.Step 2. Click-on the name of the network under the Network Name column heading. The Audio

Setup window displays.Step 3. Type in a name to identify the Paging Zone in the Paging Label field.Step 4. Check the desired Paging Zones.Step 5. Click-on Edit to create the Paging Label.

5.11.4 Voice Paging Activation ProcedureStep 1. Main Menu select Action >Voice Paging.Step 2. Click-on Activate Voice Paging check-box (check mark showing).Step 3. Click-on Start Paging.Step 4. On the Workstation keyboard, press and hold both the Shift and Ctrl keys and speak into

the microphone.There is a five second delay in the voice page. If no sound is detected for 45 seconds, Paging Zones time-out and a trouble event is generated at the Paging Zone.

76 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 77: Onyxworks Workstation

Section 6 Workstation Screen Graphical User Interface Management

6.1 Overview

The sequence in which these tasks are performed is determined by the Admin User performing them and this list is a suggested guideline to ensure that Workstation software application is configured correctly.

Figure 6.1 Workstation Screen Graphical User Interface Management Flow Diagram

NOTE: If you are not familiar with the Workstation’s graphical user interface, please refer to the “ONYXWorks® Workstation User’s Guide” on page 129 for information.

NOTE: The Workstation must be logged into before any of its settings can be configured. A User that has the Security Option to configure settings needs to login to change an existing setting. The factory defined User “Admin” has such a Security Option. Information in this document is written assuming that a User with the equivalent Security Option of the “Admin” User will be performing the procedures in this document.

“ONYXWorks® Workstation System Connections” on

page 31

“Hardware, Printer, and Power Connections” on page 13

“Windows® Software Configuration” on page 25

“Workstation Software Configuration” on page 41

“Workstation Screen Graphical User Interface Management” on

page 77

Start

Finished

“Auto-Creation of Workstation Screens, Nodes, and Points” on

page 78

“Setup the Workstation Display Mode” on page 84

“Panel Programming” on page 80

77ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 78: Onyxworks Workstation

Workstation Screen Graphical User Interface Management Auto-Creation of Workstation Screens, Nodes, and Points

6.2 Auto-Creation of Workstation Screens, Nodes, and Points

6.2.1 DescriptionThe Admin User must determine how the system’s Navigation Tree (Tree) hierarchy will be organized and thus displayed after any auto-creation process takes place. The auto-creation process takes place each time a new point on the gateway is found through it reporting to Workstation with off-normal event. Refer to “Manage the Auto-Creation Process” on page 79 for information.

The auto-creation process of the ONYXWorks® Workstation software application does the following.

• A parent screen is created for the gateway, a child screen for the node, a child screen under that for the points for that node.

• It will place 64 point icons on a Workstation screen before it creates the next screen.

The Tree entries for a Workstation screen will be created, added, and named as follows:

GW003 NFN Screen 1

where:– G003 is the alias name that was assigned to the gateway during its configuration.– NFN is the type of gateway (i.e. ECH, NFN, RCV).– Screen 1 is one of the enumerated screens for this gateway.

Figure 6.2 Example of Navigation Tree with Auto-Creation Process

Each auto-created Tree entry, by default, will be placed in the Tree at random levels. An asterisk next to a entry’s name indicates that the auto-creation process has created the Tree entry and its name. It also indicates its position in the Tree has not been redefined by the Admin User.

In the example shown in the Figure 6.2 on page 78 the G003 NFN Screen 2 can be created due to the result of G001 NFN Screen 1 having over 64 point icons created on it. In other words Screen 1 became too full and Screen 2 was auto-created with additional addressable points.

The Admin User can organize the Navigation Tree in such a manner it will aid the User with locating a specific event in a campus (site) or building. The Navigation Tree can be arranged in a parent-child hierarchical-relationship so a User can, in a logical progression, “drill-down” from a

NOTE: Every Addressable Device must be represented on a Workstation screen as a point icon. If ONYXWorks® Workstation software application auto-create function has been disabled, meaning the check box that controls the operation has been uncheck, or if a Addressable Device has been deleted, then the first time the Addressable Device reports an event an Addressable Device will be assigned to the default Workstation screen. Device icons generated in that manner should be edited to ensure all information is complete and relocated to an appropriate Workstation screen.

78 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 79: Onyxworks Workstation

Auto-Creation of Workstation Screens, Nodes, and Points Workstation Screen Graphical User Interface Management

site view to the floor plan of a building on that site. The Tree also shows at what level of the hierarchy an event is occurring. For an event colored-highlighted boxes appear at the left side of the Tree and correspond to the highest priority event.

Figure 6.3 Sample Navigation Tree Hierarchy

6.2.2 Manage the Auto-Creation ProcessRestructure the Navigation Tree After the Auto-Creation ProcessAuto-created Workstation screens can:

• Be renamed.• Be cut and copied below another Tree entry.• Be reordered, refer to “Reordering Workstation Screens” on page 79.• NOT be deleted if there are point icons on the screen. Cut and copy the point icons onto

another screen or just delete the points on the screen.

A Workstation screen may be recreated if the system finds a point that is not currently in the screen database and a new addressable point needs to be auto-created.

Reordering Workstation Screens

The Configuration Tool is used to reorder screens. When the Configuration Tool is open you can use a right-click on the screen in the Navigation Tree, then it can drag and drop screens to adjust the hierarchical level (i.e. “promote” a screen from child to peer, or demote the screen from peer to child). Dropping between screen levels will place the screen between those levels. After screens are moved. Navicons maintain their link to the screen.

Reordering Workstation Screen Methods• Drag and drop a Workstation screen from/to any position in the list.• Use the Tab key to move a given screen down one level, and Shift >Tab to move the selected

screen up one level.• Right-click on a screen in the Navigation Tree and options display as in the following figure.

NOTE: Any and all screens can have a child screen but four (4) is the maximum of child screens allowed directly under any one screen.

79ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 80: Onyxworks Workstation

Workstation Screen Graphical User Interface Management Panel Programming

6.3 Panel ProgrammingThe Panel Programming function is used to setup an upload or download the database from a node, and to perform application downloads for those nodes that support using this function. Options are available to initiate uploads and downloads, schedule uploads, and abort any current actions. Information about the node number, status indication and progress indication will be displayed by the upload / download. Select Action >Panel Programming to display the window.

Figure 6.4 Upload/Download Main Window: Status of Current Actions

All upload / download messages that affect the operation are stored in the history window and current event window. This includes initiating the upload / download process, aborting the process, or any errors that will prohibit the process from completing successfully. A message will also be stored in these windows if the upload / download has successfully completed.

80 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 81: Onyxworks Workstation

Panel Programming Workstation Screen Graphical User Interface Management

6.3.1 Panel Database UploadingBefore a Database upload is initiated, the Workstation will query the User for a database file in which to store the received information. All uploaded information, including the database version, is saved to the UPDL database. The Workstation will also update the run-time database with the new information. Select Action >Panel Programming to display the window.

This function can not be used to upload a panel databases from one panel to another unless the panels are of the same model number.

Step 1. On the Panel Programming tab select the Network’s number to connect to in the Network Select field.

Step 2. Click on the Database radio button.Step 3. Click on Receive From Nodes radio button.Step 4. Select the Node’s name from the list of choices in the Select Node field.Step 5. Click on the Classic Panels or Panels’ ... button to display the Select Database File

window and then type in name or select a database from the list of choices displayed in the C:\FacilitiesMonitoring\NFNGateway\NFNUtility\UPDL folder.

Step 6. Click the Start button to start the upload. The progress prompt will display.

Figure 6.5 Uploading & Downloading Nodes

The Workstation will query the User for a database to download. It will open the database specified, and check the version. If the database specified is an older version, the upload will not proceed. There will be no option to continue the download. Use VeriFire® Tools to convert an older database format to the current format.

This function can not be used to download panel application information from one panel to another unless the panels are of the same model number.

12

3

4

5

5

81ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 82: Onyxworks Workstation

Workstation Screen Graphical User Interface Management Panel Programming

6.3.2 Panel Application DownloadingApplications files, which contain a panel’s operating firmware, can be downloaded using this screen to those network nodes that support downloading. Select Action >Panel Programming to display the window.

Step 1. On the Panel Programming tab select the Network’s number to connect to in the Network Select field.

Step 2. Click on the Application radio button.Step 3. Click on the Application Code ... button to display the Select Database File window and

then type in a name or select a application from the list of choices displayed in the UPDL folder.

Step 4. Select the Node’s name from the list of choices in the Download to Nodes field. Only nodes that support downloading will display in the field.

Step 5. Check All Nodes of the Same Type selected if you want all similar nodes selected in the Select Node field downloaded.

Step 6. Select the desired Application Code Type from the list of choices.Step 7. Select the desired language from the list of choices.Step 8. Click the Start button to start the download. The progress prompt will display..

Figure 6.6 Application Download

12

3

4

6

7

5

8

! CAUTION:You must be certain to download the correct version of the application. Otherwise, an older version of the application may overlay a newer version.

82 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 83: Onyxworks Workstation

Panel Programming Workstation Screen Graphical User Interface Management

6.3.3 Schedule Panel UploadsThe Workstation provides you with the ability to schedule database uploads once or on a monthly basis. All scheduling options, including dates, times, and nodes selected, are saved to the database. Select Action >Panel Programming to display the window.

Step 1. On the Schedule tab select the Network’s number to connect to in the Network Select field.

Step 2. Schedule the Upload:a. Select one of the Schedule Upload Settings radio buttons.• Only Once – Uploads the database at the entered time on the entered starting date.• Monthly – Uploads the database at the entered time on the entered starting date on that

day of the month.b. Select a Starting Date from the list of choices.c. Select a Time to begin the upload on the Starting Date.

Step 3. Click on the Classic Panels or Panels’ ... button to display the Select Database File window and then type in name or select a database a database from the list of choices displayed in the UPDL folder.

Step 4. Select the Node’s name from the list of choices in the Upload to Nodes field.Step 5. Check All Nodes selected if you want all similar nodes selected in the Select Node field

uploaded.Step 6. Click Apply to complete entries for your scheduled upload. The upload will start on the

using the parameters set above and if a existing file is present it will be overwritten.

Figure 6.7 Scheduled Uploads Screen

12

3

4

5

6

83ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 84: Onyxworks Workstation

Workstation Screen Graphical User Interface Management Setup the Workstation Display Mode

6.4 Setup the Workstation Display ModeTransition from Graphics Mode to Text Mode and vice-versa is accomplished by accessing the View menu. When the Workstation is in Graphics Mode, the View menu will display “Text Mode”. When the Workstation is in Text Mode, the View menu will display “Graphics Mode”.

6.4.1 View Workstation in Graphics ModeIn Graphics Mode the Workstation displays an ONYXWorks® system as floor plans, point icons, and event information in tabular/list form.

The Admin User designs and implements the “Floorplan Area” concept in the Workstation and used when the Workstation is in Graphic Setup mode.

• A “Floorplan Area” is a drawing or imported file that is background layer of the Workstation screen.

• A “Floorplan Area” will serve as the primary source for visual feedback the location of an off-normal event in an ONYXWorks® system, it serves as a visual representation of a point’s location in a building.

The points types can include fire panels, fire protection points, security points, cameras, and other equipment.

84 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 85: Onyxworks Workstation

Setup the Workstation Display Mode Workstation Screen Graphical User Interface Management

6.4.2 View Workstation in Text ModeThe Text Mode view provides the functionality to expand the Workstation’s New Events and Acknowledged Events areas across the entire Workstation screen. When in Text Mode events will be dynamically updated as they occur. The Panel Ack column will be displayed with check-boxes to indicate the event is known to be acknowledged at the panel.

Figure 6.8 Text Mode Displayed on the Workstation

The same color-coding used to reflect status is used in both modes. The factory default colors will correspond to status class:

• White: Normal• Green: Return To Normal• Red: Alarm• Yellow: Trouble• Blue: Security

In Graphic Mode gray shading will indicate whether an event is known to be acknowledged at the panel.

85ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 86: Onyxworks Workstation

Workstation Screen Graphical User Interface Management Setup the Workstation Display Mode

86 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 87: Onyxworks Workstation

Section 7 ONYXWorks® Workstation Data Management

7.1 Data Management Overview

The sequence in which these tasks are performed is determined by the Admin User performing them and this list is a suggested guideline to ensure that Workstation software application is configured correctly.

• “About Database Management” on page 88.• “About History Manager” on page 90.• “System Explorer Searches” on page 99.• “Key Upgrade Utility” on page 101.

NOTE: The Workstation must be logged into before any of its settings can be configured. A User that has the Security Option to configure settings needs to login to change an existing setting. The factory defined User “Admin” has such a Security Option. Information in this document is written assuming that a User with the equivalent Security Option of the “Admin” User will be performing the procedures in this document.

87ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 88: Onyxworks Workstation

ONYXWorks® Workstation Data Management About Database Management

7.2 About Database ManagementWorkstation data management is accomplished using these PC Monitor choices and choices made under the Workstation Configure >Options menu.

Compact and Repair System DataThis command is selected from the PC Monitor’s right click list of choices.

Compact System Data

When an entry is deleted from a database in the Workstation it is flagged as being deleted. If the next database entry to be added will fit in the deleted entry’s location, it will be stored in that location. Like most databases the Workstation database can grow larger in size over time because of unused space.

The Workstation will rebuild its index file and remove the dead space in the file. This command is typically performed automatically each day, but it is recommended that a database be compacted manually any time a large portion of that database is deleted. Compacting does not delete or modify any actual data, so periodic compacting of the database is a good idea for optimal system performance.

Repair System Data

This command provides the option to repair databases. Damage to the database is caused by software or hardware level corruption of the database file. If some portion of the file index becomes damaged, the file will be unreadable. If this corruption does not affect the actual entries, or only a portion, the database is repairable. The repair functions reconstruct the index file, and un-reference any damaged entries. Use this functions if a database file will not open properly or its information seems damaged.

Backup System DataThis Workstation command provides the Admin User the options to back up all the systems databases. The operation prompts for you create a folder in which to store the system data. It is recommended you use a folder name with the current date (for example MySystemDataBackup03-07-07).

Any time Workstation editing is completed, it is recommended a back up the databases is performed. Backing up after each time databases are edited insures that there is a backup copy of the latest database file stored on the computer. In addition, if any changes are made that need to be undone, the backup copy can be restored.

It is recommended that you store system data created in the folder you create during a system backup on an external storage device, such as a CD-ROM or server. The Workstation has a CD-RW type drive and you can use CD-R or CD-RW media in it.

NOTE: Please contact Technical Services before you attempt to repair your systems data.

88 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 89: Onyxworks Workstation

About Database Management ONYXWorks® Workstation Data Management

Restore System DataThis Workstation command provides the Admin User the options to restore a database created with the Backup System Data command. The operation prompts for you to choose the location and folder the system data is stored in.

Import System DataThis Workstation command is used when you want changes that are made on a local Workstation to be made to other Workstations on the system that you will individually select from the list of IP addresses on the system.

Export System Data To All WorkstationsThis Workstation command is used when you want changes that are made on a local Workstation to be made to all other Workstations on the system.

89ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 90: Onyxworks Workstation

ONYXWorks® Workstation Data Management About History Manager

7.3 About History ManagerThe History Manager is a application program interface for viewing all of the events that are currently stored in the history database of a network client application. It serves as a viewer that can organize all events that pass through the Workstation software application.

The History Manager allows a set of filters to be applied to the events in order to view specific event types, points, and events for specific dates. It can be accessed from the View...History menu item within a network client (such as the Workstation), or it can be started stand-alone (called from outside the application environment) from the Start >Programs >Facilities Monitoring >Utilities >History Manager.

Figure 7.1 History Manager Main Window

The information bar at the bottom of the window displays the number of entries in the database, which events are being shown, the date and current time. At the top of the window are the File and Tools menu selections.

The lists of events:

• Are displayed according to any applied filters.• Can be the current history file or an archived history file.• Displayed depends on what specific application provided the database.

90 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 91: Onyxworks Workstation

About History Manager ONYXWorks® Workstation Data Management

d

e

7.3.1 History Manager Menu DescriptionsFile Menu

Open Database

Clicking this icon allows the Admin User to open a previously saved event history database. Selecting File >Open Database performs the same function.

FilterOpen Saved Filter This command (or icon) displays the Open or Delete Filter window which allows the Admin User to choose a filter that was previously saved using the "Save Filter As" command. To select a filter click on the arrow adjacent to the filter name and then the Open button.

Save Filter As This command (or icon) displays the Save Current Filter window which allows the Admin User to name, describe, and then save the filters that are currently being used to view the History Manager window.

ReportsOpen Saved Report... This command (or icon) displays Select a Report to Print window which allows the Admin User to select a report that was previously saved using the "Save Current Layout As Report" command. The report can be deleted or the modified and then printed to the Workstation’s Windows printer. Refer to “History Manager Reports” on page 97.

Save Current Layout As Report This command (or icon) displays Save Current Layout as Report window which allows the Admin User to customize a report layout then it can be named, described, and saved. The report can be opened then be printed. Refer to “History Manager Reports” on page 97.

PrintDisplayed Events This command (or icon) prints the current event in History Manager window. The printout is sent to the printer setup using the "Printer Setup" command.

Printer Options This command displays the Printer Configuration window which allows the Admin User to determine how the information displayed in the History manager window will be printed in the context of font type, font size, page orientation, and options (show/hide grids/color) to the printer set up using the "Printer Setup" command.

Printer Setup This command displays Windows Print Setup window which allows the Admin User to set up a Windows printer connected to the Workstation. Consult Windows information for setup information.

! CAUTION: Event Report PrintoutsWhen you click the printer icon, a complete event report will be printed out. If no filters have been applieto narrow the parameters for the report, this printout may be lengthy. To halt printing, right-click the printer icon that appears in the bottom right of the PC desktop, then select Cancel Print Job, or go to thprinter and manually cancel the print job.

91ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 92: Onyxworks Workstation

ONYXWorks® Workstation Data Management About History Manager

Tools MenuSet Filter This command is used to display the Select Filter Criteria window which allows the Admin User to define and apply filters to the History Manager window. Refer to “History Manager Filters” on page 94.

View Current Filters This command is used to display the View Current Filters window which allows the Admin User to display and manage what filters are to be used when you are viewing the History Manager window. Refer to “History Manager Filters” on page 94.

Clear All Filters This command is used to return History Manager’s view to its factory default state. Unless the current filter view was saved using the "Save Filter As" command then the "Open Saved Filter" command can not be used to return the History Manager window to current filter view.

Show Columns This command is used to display the Select Columns to Show window which allows the Admin User to select a check box that correspond the columns that they want to display or not to display in the History Manager window.

Options This command is used to display Options window. Refer to “History Manager Configuration” on page 96 for details.

92 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 93: Onyxworks Workstation

About History Manager ONYXWorks® Workstation Data Management

7.3.2 History Manager Right Click Menu DescriptionsThe commands displayed depend on which column the right-click is performed. List of choices menus will display providing the option to sort and filter various events and/or columns. One of two right click menus can be displayed; the "Filter Right-Click Options" or the "Header Right-Click Options".

Filter Right-Click OptionsThe Filter list of choices can be accessed by right-clicking any row in the main body of the History Manager window. The list of choices are:

Filter By Selection this command allows the Admin User to display all records according to the event and column that was right-clicked on.

Filter Excluding Selection this command allows the Admin User to exclude displaying all records according to the event and the column that was right-clicked on.

Filter For This command displays a History Manager window which allows the Admin User to filter for a specific word or phrase using keywords and or wildcard characters.

Figure 7.2 Keyword/Wildcard Filter Window

Clear All Filters This command allows the Admin User to return the History Manager window to the factory default filters. Once this option has been chosen, all filters are lost unless they where saved using the "Save Filter As" command.

Show If Greater Than Or Equal To This command allows the Admin User to filter by Received Time. The filtering is based on the event’s time and forward.

Show If Less Than Or Equal To This command allows the Admin User to filter by Received Time. The filtering is based on the event’s time and backwards.

Header Right-Click OptionsThe Header list of choices can be accessed by right-clicking on any column header. This list of choices applies to a column rather than specific row entries. The options are used to perform commands that will organize the database columns for search clarity. The list of choices are:

Hide Column This command allows the Admin User to temporarily hide the selected data column. The column itself is not deleted, only hidden.

Show Column This command allows the Admin User to select hidden data columns and set them back to be displayed.

Show All Columns This command allows the Admin User to remove all data column filters which were previously applied.

Sort ASCending This command allows the Admin User to sort the data column in ascending order (numeric or alphabetical).

Sort DESCending This command allows the Admin User to sort the data column in descending order (numeric or alphabetical).

93ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 94: Onyxworks Workstation

ONYXWorks® Workstation Data Management About History Manager

7.3.3 History Manager FiltersFilters are search settings that are used to define and apply search criteria to the Workstation’s event database displayed in the History Manager window. The Select Filter Criteria window is used for defining and applying the filter search settings.

Figure 7.3 Select Filter Criteria Window

About Filter Field SelectionThe Set Filter command is used to display the window where you make filter selections. It is accessed by selecting Tools >Set Filter. The window that displays contains fields, each devoted to a specific column found within the window. The information in the window is dynamic and will display up to five filters per page and may contain multiple pages depending on which client history file is being accessed.

• A filter is used if its check box displays a check inside the box and then what has been selected in field adjacent to it defines the filter.

• A filter may be defined as time. Select from a calendar month (large arrow), date (up/down arrows), and type in time of day (begin through the end).

• Multiple items in a filter’s list of choices can be selected after its list of choices is displayed. Press and hold the SHIFT key to select a range of choices. Press and hold the CTRL key and then click on an entry to add individual choices.

94 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 95: Onyxworks Workstation

About History Manager ONYXWorks® Workstation Data Management

About Filter BuildingAfter a filter field selection is made and you click on the Apply New Filter button:

• The filter is applied to History Manager’s current view.• It has been added to a list that defines which filters are being used for current view. The list is

accessed through the Tools >View Current Filters (Figure 7.4).• You can save the current view so you can open it to apply it again and or modify it.

Figure 7.4 View Current Filters Window

About Filter SavingWith History Manager you can save the set of currently selected filters for use later. To save a set of filters select File >Filters >Save Filter As. A filter may be added to a previous arrangement or created as a new set of filters.

The Save Current Filter window is used to enter a name for the filter and a brief description. All queries and filters are defined using SQL statements. The SQL field displays the query statement for the filter. That statement may be edited to refine the filter beyond the scope of the Select Filter Criteria window but it is strongly recommended to leave the settings as they are unless you have a through understanding of SQL. Once the fields have been filled out, then click OK to save the filter.

Figure 7.5 Save Filter Window

95ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 96: Onyxworks Workstation

ONYXWorks® Workstation Data Management About History Manager

About Filter Opening And DeletingTo open a previously saved filter select File >Filters >Open Saved Filter. Use the Open or Delete Filter window to select any of the saved filters by selecting the arrow to the left of the filter name. Then use the Open or Delete button to perform your task.

Figure 7.6 Open Or Delete Filter Window

7.3.4 History Manager ConfigurationSelect Tools >Options to display the Options window which allows a drop down item limit settings to be made to History Manager view.

The Enter the Drop-Down Item Limit field lists the field used to enter drop-down limit. The value entered will determine whether or not the drop-down list on the Set Filters dialog loads possible selections. If the number of possible selections is greater than the drop-down items limit, then the drop-downs will not load the selections. The default number of drop-down limit is 1000 selections.

Figure 7.7 History Manager Options Window

96 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 97: Onyxworks Workstation

About History Manager ONYXWorks® Workstation Data Management

7.3.5 History Manager ReportsIn History Manager reports saved as database layouts may be printed in hard copy. A saved report can be opened for viewing and printing; select File >Reports >Open Saved Report... to open a previously saved event report.

To create a report, select File >Save Current Layout as Report. The Save Current Layout as Report window will display and the fields and choices can be used to customize the report’s layout. A report may be set up to display events in any specific order. A Title and a brief description for the report is required.

Figure 7.8 Save Current Layout as Report Window

Save Current Layout as Report Button and Field Descriptions

Select Time Period

The set up of the Select Time Period buttons and fields determines how much of the history.mdb is included in the printed report.

All All records from every recorded day are added to the report.

Month to Date This set reports all records from the beginning of the current month up to and including the current date.

Year to Date This set reports all records from the beginning of the current year up to and including the current date.

Today When this option is selected, times must be entered into the Starting field and Ending field. This option saves a specific time frame during one day's worth of events to be saved into the report.

Yesterday The Yesterday option is identical to the Today option, yet rather than saving events of today, it saves the events from yesterday.

To Today This option calls for the report to save XXX number of days up to but exclusive of today, where XXX is any three digit number typed into the Days field.

Through Today This option is similar to the To Today feature, but includes the current day in the report.

97ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 98: Onyxworks Workstation

ONYXWorks® Workstation Data Management About History Manager

Based On: After the time period has been selected the report must be based on actual event time or the received event time. Either option may be selected from the Based On menu.

Scheduled Report Printing

The setup of the Scheduled Report Printing buttons and fields determines when to print the saved report.

Enabled Select to Scheduled Report Printing to the report.

Weekly Prints a copy of the specified report weekly.

Monthly Same as above, yet prints a copy of the report monthly.

Custom Prints a report every XXX days where XXX is what the Admin User enters into the field.

Starting: Is used to select a date for the Scheduled Report Printing.

NOTE: The History Manager must be running in order for Scheduled Reports Printing to operate. History Manager may be left running as a background application, or it can be launched automatically using Windows scheduling accessories.

98 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 99: Onyxworks Workstation

System Explorer Searches ONYXWorks® Workstation Data Management

7.4 System Explorer Searches

7.4.1 Point Type, Text, and Off Normal SearchesThe ONYXWorks® system can be searched for a point type, text, and off normal event.

Step 1. Select View >System. The System Explorer window displays.Step 2. Check the box that is appropriate for your search.Step 3. Define the search:

• Search For Point Type - use the down arrow and select from the list of choices.• Search For Text - type the text to search for.• Search For Off Normals - use the down arrow and select from the list of choices.

Step 4. Click on the Search button. The results are displayed adjacent to the selection area.Step 5. Select OK to close the window and end the searching.

Point Type Search

Figure 7.9 Search For Point Type

Text Search

Figure 7.10 Text Search

99ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 100: Onyxworks Workstation

ONYXWorks® Workstation Data Management System Explorer Searches

Locate Off Normal Events

Figure 7.11 Off Normals Search

100 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 101: Onyxworks Workstation

Key Upgrade Utility ONYXWorks® Workstation Data Management

7.5 Key Upgrade Utility

7.5.1 About the Key Upgrade UtilityEvery Workstation is shipped with a USB Hardlock Key. This key is programmed to allow features of the network monitoring system to function on that Workstation.

A Hardlock Key upgrade is required when a new feature is desired. You must have acquire a Upgrade Code from Technical Services to update the key.

7.5.2 Key Upgrade ProcedureThe USB Hardlock Key currently plugged into the Workstation is upgraded with this procedure.

Step 1. Shut down the Workstation software application.Step 2. Select Start >Facilities Monitoring >Key Upgrade Utility. The Key Upgrade Utility

window displays.

Figure 7.12 Key Upgrade Window

Step 3. Type the code into the Upgrade Code field.Step 4. Click on the Perform Upgrade button. Fields on the window update to reflect the Upgrade

Code. Step 5. Click on the Done button to complete the upgrade and close the window.

7.5.3 Key Upgrade Utility Field DescriptionsInstallation Name This is typically a factory defined site name. It is not recommended but the name can be changed by typing into a new entry into field.

Registered This is typically a factory defined site name. It is not recommended but the name can be changed by typing into a new entry into field.

Node License Shows how many node licenses are included with the current key configuration.

Serial # Displays the serial number of the Hardlock Key (different from the Authorization Code).

101ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 102: Onyxworks Workstation

ONYXWorks® Workstation Data Management Key Upgrade Utility

102 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 103: Onyxworks Workstation

Section 8 ONYXWorks® System Architecture Descriptions

8.1 About the System ArchitectureThe ONYXWorks® system is designed to provide clear and precise annunciation of life safety and other building system events. The preciseness of that annunciation enables the responding personnel to identify the location of a life safety event quickly and accurately. The status of the emergency equipment or fire safety functions that might affect the safety of the occupants is also easily identifiable.

An ONYXWorks® Workstations (Workstation) and gateways communicate over an Ethernet (TCP/IP) network. Gateways also communicate with other panels and networks of fire alarm and protective equipment. Each gateway relays Ethernet protocol messages from the monitored equipment using the equipment’s native protocol to the Workstation. An ONYXWorks® system supports 99 gateway connections. The minimum ONYXWorks® system is one Workstation and one gateway.

Several types of gateways are available, such as ONYXWorks® Echelon Gateway, ONYXWorks® NFN Gateway PC and Embedded. An ONYXWorks® NFN Gateway exists as a node on a NFN network.

The Workstation can be installed on a dedicated TCP/IP network, or part of a shared TCP/IP network such as the Internet. It can be part of a customer’s enterprise (or corporate) TCP/IP network. Canada installations require a dedicated TCP/IP network. Shared bandwidth TCP/IP connectivity allows the ONYXWorks® system design to be versatile and flexible for various system requirements. Workstations, gateways, and other clients can be located in close proximity to each other or separated by many miles. ONYXWorks® system nodes can be controlled from any Workstation located on the contiguous property being monitored. Clients that have monitoring capabilities to non-contiguous properties may not control that property without the approval of Authority Having Jurisdiction (AHJ).

103ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 104: Onyxworks Workstation

ONYXWorks® System Architecture Descriptions About the System Architecture

Example SystemsIn simple systems, Workstations and gateways can co-exist on one computer. For larger systems, multiple computers can be networked together over the TCP/IP network running up to 99 gateways. The following figure shows a sample network diagram on which ONYXWorks® Gateways resides.

Figure 8.1 Basic NFN Gateway Network

Workstation

FACP FACP FACP

Workstation

NFN Network

TCP/IP Network

Gateway Embedded

104 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 105: Onyxworks Workstation

About the System Architecture ONYXWorks® System Architecture Descriptions

Figure 8.2 Advanced NFN Gateway Network

FACP

Workstation/Gateway PC

FACPFACP FACP FACP FACP

Workstation

NFN Network NFN Network

TCP/IP Network

Workstation/Gateway PC Gateway Embedded

105ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 106: Onyxworks Workstation

ONYXWorks® System Architecture Descriptions Fire Command Center (FCC) Mode Overview (PPU)

8.2 Fire Command Center (FCC) Mode Overview (PPU)

8.2.1 Architecture for FCC ModeAn ONYXWorks® system is an ideal solution for facility monitoring and control. The ONYXWorks® Workstation software application provides extensive control and monitoring functions for fire, security, and building automation of local and remote sites. The software application can be customized to adapt to a wide variety of monitoring and control situations. The software application allows a User with the appropriate Security Option to allow/disallow access to the application by adding other Users and creating security profiles for them. Those other Users typically, when they are logged in, will be monitoring a portion of local and remote sites.

Workstation software applications in FCC mode comply with the requirements for UL and NFPA for Protected Premises Units (PPU). The Workstation was designed to warn building monitoring personnel of potential life safety situations so that they can take the necessary actions to evacuate the premises.

In FCC mode, there is always one Workstation and one NFN gateway. The NFN gateway can be installed on the same PC that is running the Workstation software application or an optionally installed embedded NFN gateway. The choice of which gateway to use will be dependent on the system layout.

8.2.2 Event Handling Overview for FCC ModeThe following features are provided by the Workstation when FCC mode is running.

• Block Acknowledge of troubles, supervisory, and security events.• Always requires an individual acknowledgement of Fire Alarm and Hold-up events.• Display and Command Center (DCC).• Performance:

• Annunciation of alarm signals at the Workstation in FCC mode (PPU) occurs within 10 seconds after the activation of an initiating point (device).

• Trouble signals and their restoration to normal shall be indicated within 200 seconds.

NOTE: FCC mode is NOT supported when a gateway other than the NFN gateway is used and if there are more than one gateway in the ONYXWorks® system.

NOTE: Running this Workstation in FCC mode (PPU) ULC requires it be operated by trained personnel.

NOTE: If multiple gateways are present or required, the Workstation software application must run in Supervising Station mode.

NOTE: FCC mode is to be used on a dedicated fire protective signalling network only.

106 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 107: Onyxworks Workstation

Fire Command Center (FCC) Mode Overview (PPU) ONYXWorks® System Architecture Descriptions

8.2.3 FCC Mode Communications Requirements• In FCC in which the fire system is sharing bandwidth on an TCP/IP network with other

systems, a UL listed barrier gateway, integral with or attached to each control unit or group of control units, as appropriate, shall be provided to prevent the other systems from interfering with or controlling the fire alarm system. A barrier gateway is required on dedicated TCP/IP networks.

• All signal control and transport equipment (such as routers, servers) used with the ONYXWorks® system in FCC mode shall be listed for fire alarm service. For example: Contemporary Control Systems Inc. (www.ctrlink.com) has several UL864 recognized switching hubs that will meet the requirements of a barrier gateway.

8.2.4 FCC Mode Agency ApprovalIn FCC Mode, ONYXWorks® systems are classified as a Protected Premises Fire Alarm System Unit and meet all the regulatory agency’s requirements for a protected premises unit.

The ONYXWorks® Workstation software application is approved, in compliance with the NFPA, for the remote resetting and silencing of a fire alarm control unit from other than the protected premises provided the authority having jurisdiction approves it.

8.2.5 ONYXWorks® FCC Mode Ordering InformationUse the following table to verify your life safety application needs.

NOTE: For ULC applications, the Internet cannot be used for either primary or ancillary functionality. ULC does not allow operation over an Internet connection.

Table 8.1 FCC Mode Ordering Information

Part Number Description

ONYXWORKS • FCC Mode Workstation by default• ONYXWorks® PC with Workstation GUI software• FCC Mode: Order NFN-GW-PC-W/F or NFN-GW-EM only.• Supervising Station Mode: Order up to 99 gateways (see below) • Change To Supervising Station via option in Workstation

ONYXWORKS-NW • FCC Mode Workstation by default• ONYXWorks® PC with Workstation GUI software• Includes NFN-GW-PC-W network card and NFN Gateway software.• Change To Supervising Station via option in Workstation

ONYXWORKS-NF • FCC Mode Workstation by default• ONYXWorks® PC with Workstation GUI software• Includes NFN-GW-PC-F network card and NFN Gateway software.• Change To Supervising Station via option in Workstation

Gateways Description

NFN-GW-EM • Embedded NFN Gateway.• Additional required parts ordered separately

– ONYXWORKS, ONYXWORKS-NW, ONYXWORKS-NF– Cabinet for NFN Gateway

• NCM-W/F for connections to NFN network

NFN-GW-PC-W • NFN Gateway PC card (wire connections)

NFN-GW-PC-F • NFN Gateway PC card (fiber connections)

107ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 108: Onyxworks Workstation

ONYXWorks® System Architecture Descriptions Fire Command Center (FCC) Mode Overview (PPU)

8.2.6 FCC Mode Example Life System Diagrams

Figure 8.3 ONYXWorks® FCC Mode Example 1

Protected Premises Unit

NFN/ArcNet Network

Workstation

*Ethernet Hub (TCP/IP)UL 864 Listed Switch

Gateway Embedded

Other TechnologiesLAN/WAN/Internet/Intranet

(Dedicated Only)

Ethernet Hub (TCP/IP)UL 864 Listed Switch (Not required on dedicated Network)

NFN/ArcNet Network

108 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 109: Onyxworks Workstation

Fire Command Center (FCC) Mode Overview (PPU) ONYXWorks® System Architecture Descriptions

Figure 8.4 ONYXWorks® FCC Mode Example 2

Protected Premises Unit

Workstation

NFN Network

109ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 110: Onyxworks Workstation

ONYXWorks® System Architecture Descriptions Proprietary Supervising Station Mode Overview

8.3 Proprietary Supervising Station Mode Overview

8.3.1 Architecture For Supervising Station ModeProprietary supervising station fire alarm systems monitor the life safety systems of the protected premises that is under the same ownership. The supervising station can be located at the protected premises or at multiple protected properties. Properties may consist of a single building, such as a high-rise building, or several buildings, such as a campus where multiple separate buildings report to a proprietary supervising station owned and operated by the campus. The property may be contiguous or non-contiguous. If it is non-contiguous, it may consist of protected properties at remote locations. Codes do not limit the geographic distance that may exist between non-contiguous properties. This permits an owner to oversee protection features at geographically diverse locations from a single proprietary supervising station.

The ONYXWorks® system is a Proprietary Supervising Station Fire Alarm System and may serve contiguous and non-contiguous properties, under one ownership. Monitoring is typically performed from a proprietary supervising station located at the protected property, or at one of multiple non-contiguous protected properties, at which trained, competent personnel are in constant attendance. Monitoring may include, but is not limited to, the proprietary supervising station; power supplies, signal-initiating points, initiating point circuits, signal notification appliances, equipment for the automatic, permanent visual recording of signals; and equipment for initiating the operation of emergency building control services. ONYXWorks® systems are permitted to be interconnected with other systems intended to make the premises safer.

In Supervising Station mode, the ONYXWorks® system supports up to 99 gateways. Multiple NFN gateways, Echelon gateways, and Receiver gateways are supported simultaneously and can be constantly supervised and communicating with the same Workstation. An NFN gateway and an Echelon gateway can both be installed in the same Workstation if required. They can also span the TCP/IP network and exist on multiple Workstations or embedded hardware. The choice of which gateways to use and where they should be located is application specific and should be analyzed by a trained individual.

8.3.2 Overview of Event Handling in Supervising Station ModeONYXWorks® Workstation, in Supervising Station mode complies with NFPA-72 2002 and UL for Supervising Stations.

The following features are provided by the Workstation software application when Supervising Mode is running.

• Each change of state must be individually acknowledged.• Performance:

• The maximum duration between the initiation of an alarm signal at the protected premises, transmission of the signal, and subsequent display and recording of the alarm signal at the Workstation shall not exceed 90 seconds.

• Display rate of subsequent alarms at the Workstation shall be at a rate no slower than one complete signal every 10 seconds.

• Trouble signals and their restoration to normal shall be indicated within 200 seconds.

110 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 111: Onyxworks Workstation

Proprietary Supervising Station Mode Overview ONYXWorks® System Architecture Descriptions

8.3.3 Supervising Mode Communications Requirements• If the Workstation or gateway is sharing on-premises communications equipment, the shared

equipment shall be “listed for the purpose”. If on-premises communications equipment is not listed for the purpose, the fire alarm transmitter shall be installed ahead of the unlisted communications equipment.“Listed for the purpose” has been formally interpreted by NFPA (Formal Interpretation 72-99-1) for equipment on packet switched networks as being listed to the requirements applicable to general purpose communications network equipment.

8.3.4 Supervising Mode Agency ApprovalIn Supervising Station mode, Workstations are classified as a Proprietary Supervising Station and meets all the agency requirements for a supervising station fire alarm system. ONYXWorks®

Workstation software application is approved, in compliance with NFPA, for the remote resetting and silencing of a fire alarm control unit from other than the protected premises provided the authority having jurisdiction approves it.

8.3.5 ONYXWorks® Supervising Mode Ordering InformationUse the following information to verify your life safety application needs.

NOTE: For ULC applications, the Internet cannot be used for either primary or ancillary functionality.

Table 8.2 Supervising Mode Configuration Information

Part Number Description

ONYXWORKS • FCC Mode Workstation by default• ONYXWorks® PC with Workstation GUI software• FCC Mode: Order NFN-GW-PC-W/F or NFN-GW-EM only.• Supervising Station Mode: Order up to 99 gateways (see below) • Change To Supervising Station via option in Workstation

ONYXWORKS-EW • Supervising Station Mode Workstation• ONYXWorks® PC with Workstation GUI Software.• Includes PCLTA-20 ECH-GW-PC-W Echelon network card and Echelon

Gateway software application.• Will communicate with other gateways (i.e. Echelon, NFN, Receivers)• Order up to 99 gateways (see below) separately• Change To FCC mode via option in Workstation. Only 1 NFN gateway can be

used with an FCC Workstation. Echelon gateways do not support FCC mode Workstations.

Gateways Description

NFN-GW-EM • Embedded NFN Gateway.• Additional required parts ordered separately

– ONYXWORKS, ONYXWORKS-NW, ONYXWORKS-NF– Cabinet for NFN Gateway

• NCM-W/F for connections to NFN

NFN-GW-PC-W • NFN Gateway PC card (wire connections)

NFN-GW-PC-F • NFN Gateway PC card (fiber connections)

ECH-GW-PC-W • Echelon Gateway PC card (wire connections)

111ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 112: Onyxworks Workstation

ONYXWorks® System Architecture Descriptions Proprietary Supervising Station Mode Overview

8.3.6 Supervising Mode Example Life System Diagrams

Figure 8.5 ONYXWorks® Supervising Station Mode Example 1

DACR-GW • Digital Alarm Communicator Receiver Gateway

Table 8.2 Supervising Mode Configuration Information

Supervising Station Transmission and Communications Path

Protected Premises Unit

NFN Network

Echelon Network

Workstation/ Gateway PC

Workstation

Workstation

Workstation/ Echelon Gateway

Gateway Embedded

NFN NetworkOther Technologies

LAN/WAN/Internet/Intranet (Shared or Dedicated)

NION

NION

NION

Workstation/ Gateway PC

112 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 113: Onyxworks Workstation

Proprietary Supervising Station Mode Overview ONYXWorks® System Architecture Descriptions

Figure 8.6 ONYXWorks® Supervising Station Mode Example 2

Supervising Station Transmission and Communications Path Protected Premises Unit

Workstation/NFN Gateway PC/Echelon Gateway/Receiver Gateway

Digital Alarm Communicator Receiver

Echelon Network

NION

NION

NION

NFN Network

RS-232

113ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 114: Onyxworks Workstation

ONYXWorks® System Architecture Descriptions Client Applications

8.4 Client ApplicationsThe main client application in an ONYXWorks® system is the ONYXWorks® Workstation software application which provides:

• An interface for the entire ONYXWorks® system.• The functions that are necessary to create the visual look of the ONYXWorks® system.• The controls to respond to off-normal events from the ONYXWorks® system.• The functions to create security, monitoring, and control profiles, and complete history

tracking.• The capability to expand life safety system with the expansion of the protected premises.• The support for a NFN network’s full Control-By-Event functionality as a node capable of

configuring and controlling formulas for system-wide automated response.

8.5 PrintersONYXWorks® Workstation software application supports graphics printing and event printing. Windows®-compatible printers are required.

• To print screens, floor plans, history reports, etc., connect a graphics printer (laserjet) directly to the LPT port or a USB port on the Workstation PC.

• To print a record of every annunciated Workstation event an event printer (dot matrix) directly to the COM port on the Workstation PC.Refer to “Make Printer Connections” on page 18 and “Local Event Printer Configuration” on page 50 for more printer information.

114 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 115: Onyxworks Workstation

System Security ONYXWorks® System Architecture Descriptions

8.6 System SecurityThe Workstation software application uses security controls to ensure that computer is not disabled by unauthorized personnel. Hardware protections and software protections are both used.

8.6.1 Hardware SecurityThe Workstation’s power connection must be secured with special hardware and the computer’s power switch disabled. The Workstation must be protected from power failures with proper line current surge protection and a regulated, UL 1481 listed, power limited Uninterruptible Power Supply (UPS).

Refer to the following for more information:

• “Workstation AC Power Connection Preparation” on page 16.• “Uninterruptable Power Supply (UPS) Installation” on page 20.

8.6.2 Software Security

The methods of Workstation software security are:

• Control/Command Key LockoutsThis type of lockout disables the Workstation’s keyboard keys that are used to access Windows programs that are not part of the Workstation software applications. For example, keyboard key combinations can be used to shut-down or restart the Workstation and for switching between software applications. The PC Monitor’s Secure Windows selection disables those types of operations.

• User Security OptionsUser accounts can be created with differing levels of access to the ONYXWorks® system. The User’s Security Option choice determines which functions are visible or selectable. For example, some User accounts may not have permission to exit the Workstation software application. Refer to “User Configuration” on page 66 for information.

NOTE: The Workstation must be logged into before any of its settings can be configured. A User that has the Security Option to configure settings needs to login to change an existing setting. The factory defined User “Admin” has such a Security Option. Information in this document is written assuming that a User with the equivalent Security Option of the “Admin” User will be performing the procedures in this document.

115ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 116: Onyxworks Workstation

ONYXWorks® System Architecture Descriptions Workstation Event Handling Basics

8.7 Workstation Event Handling BasicsTrouble in the life safety system is detected by Workstation software application and reported as off-normal events. When off-normal events that are received from a fire alarm panel and points are reported to the Workstation and if the Workstation is in Graphics Mode these display changes will take place if Autonavigate has been selected (refer to “Automatically Navigate on Event” on page 59).

1. When an event(s) occur(s) the Workstation navigates to the location of the event(s) in the system and displays the highest-priority unacknowledged event by a flashing its respective icon in the Workstation screen.If there are multiple events and all unacknowledged events are taking place in the same ONYXWorks® system location, all unacknowledged event icons will be flashing on the Workstation screen.

2. There could be multiple highest-priority unacknowledged events and the following will reveal them for acknowledging.

a. Read the list of events in the New Events window.b. The Navigation area will display colored boxes next to the affected Navigation Tree

entry.To determine multiple highest-priority unacknowledged events use with the following colors if they have not been changed from the factory default settings.Red: alarm.Yellow: trouble and supervisory.Blue: disable and security.

c. Read the incremental list in the Alarm Summary window.d. The corresponding event icon(s) will display in the Event Annunciator Icon window.e. When an event is acknowledged the icon stops flashing but displays the off normal

color.

Figure 8.7 Troubles Reported

1

2

2a

2c

2d

116 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 117: Onyxworks Workstation

Workstation Event Handling Basics ONYXWorks® System Architecture Descriptions

FCC Mode or Supervising Mode Event Handling Comparison

Events are displayed the same way whether the Workstation is running in Fire Control Center (FCC) mode or Supervising Station mode. Such as:

• If the event is acknowledged at the panel “Acked” will be displayed prefixing the event in the New Events list.

• If the Workstation has node control of the point a colored box will display to the left of the event in the Navigation Tree.

• If the event is unreliable (meaning it was reported while a gateway or node was in fault) an * will be displayed prefixing the event in the New Events list.

However the Workstation handles return-to-normal conditions and acknowledgements in a significantly different way, depending on operating mode.

For more information, refer to Appendix B, “Details about Event Data”, on page 123.

Table 8.3 FCC Mode and Supervising Mode Comparison

Action FCC Mode

Supervising Mode

If an event is acknowledged at the Fire Alarm Control Panel (FACP) it is acknowledged at the Workstation

YES NO

If an event is acknowledged at the Workstation it is acknowledged at the Fire Alarm Control Panel (FACP)

YES*

* If the logged in User has the Security Profile to do so.

YES*

When an event returns to a normal state it is removed from the New Event listing

YES NO

When an event returns to a normal state it is acknowledged at the FACP YES NO

117ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 118: Onyxworks Workstation

ONYXWorks® System Architecture Descriptions Workstation Monitored Points

8.8 Workstation Monitored Points

8.8.1 About Workstation PointsCommands may be sent from the Workstation through the gateway to nodes and their points on a network. Command choices vary by node/point types. There are common commands but not all common commands are relative to all nodes/points. The common commands are displayed when you right click on a node/point icon that is on the Workstation’s screen.

8.8.2 Common Workstation CommandsThe Workstation monitors a node (panel) and can be used to perform control commands for that node’s points. When a right click is performed on a node/point’s icon a list of commands is displayed. Those commands are sent from the Workstation to or through the nodes to the node’s points.

These right click commands are common to all nodes and points.

Enter User Response This Workstation command allows you to select a choice from a list of factory default or User created responses. These choices provide the logged in User the means to report various conditions and operations related to a node/point.

• Dispatched Personnel To Investigate• Response Personnel on Scene• Device Undergoing Test• Device Testing Completed• Contacted System Contractor• Faulty Device• Replaced Device• Preventative Maintenance

History Of Device This Workstation command only displays the history information in the History Manager window for the selected node/point.

Linked Media This Workstation command will access any media that has been created and then assigned to the node/point. Several types of media files may be linked to the node/point. One of each type can be used.

• A text file to give specific information or instructions to the User (.TXT).• A raster image type graphic can be linked (.BMP).• A sound file may be linked giving audible information or instructions (.WAV).• A video file may be linked (.AVI).

118 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 119: Onyxworks Workstation

Appendix A: GlossaryAAbsolute Address The absolute address is the actual physical address of an addressable device on the network. An absolute address is a 14 character string that consists of a three digit node ID, a three digit sub-node ID, and an 8 character (alphanumeric) point ID.

Alias ID A 14 character name for a addressable device that is custom defined by the Admin User. Alias IDs can be used in place of Absolute IDs to make identification of the device easier for the User. Alias ID is also referred to as the Display ID.

B Bitmap (.BMP) Graphic file format. Basic image data is stored in the form of a grid of pixels, each with a certain color. Bitmaps are the standard method of importing and transporting image type information. Bitmap files each have a specific size in pixels. Because of this, they may degrade in quality if they are zoomed or re-sized. Files are identified with the extension *.BMP.

Boolean A boolean is a binary value that is either on or off. Examples include check-boxes and other options that require one of the two settings.

C Child Screen Refer to Parent Screen.

Command Buttons Up to eight Taskbar buttons can be Admin User configured to perform common system operations. Defined through the Configuration menu. (Separate from the Macro Buttons that appear on a specified Workstation screen.)

Control Profiles Control profiles determine what addressable devices the Workstation is currently supervising. If a Workstation does not have control of a device, commands and actions relating to that device will affect only the device on that Workstation, not in the network. In order to affect a device on the network, the User must have control of that addressable device.

DDigital Alarm Receiver An addressable device connected to a network in a ONYXWorks® system; the receiver routes incoming calls from dialers connected to remote panels and directs resulting messages to the ONYXWorks® Workstation.

Discrete Devices Discrete addressable devices are monitored nodes, points, and panels with defined (discrete) states or conditions. These conditions are annunciated at the Workstation. For example, a pull-station either reports a normal state, an alarm state, or a trouble state. Normal state indicates normal operation,

Alarm state shows that the pull-station has been activated, and a Trouble state indicates a functional problem with the device.

Display ID Refer to Alias ID.

EEchelon Gateway The Echelon Gateway translates information on the LonWorks network into information that can be used by a ONYXWorks® Workstation in the ONYXWorks® system.

Echelon Network LonWorks Technologies open architecture standard used for communication between devices and the Echelon Gateway on the ONYXWorks® system.

Ethernet Network communication standard using the TCP/IP protocol. Connects gateways in the ONYXWorks® system.

Event An Event is any change in the status of an addressable device or a transfer of information between a device and either the Workstation or another device. Some of these events are considered background and housekeeping events, and are not seen by the User. The events that are of primary concern to the User are those identified as off-normal events.

Event Printer An event printer is a dot matrix printer that connects to ONYXWorks® Workstation and prints all events that are annunciated at the Workstation.

FFire Alarm Event Event issued by fire protection devices such as pull-stations, smoke detectors, and sprinkler systems.

Floorplan Area The Floorplan Area provides the primary source of the Workstation visual feedback and interaction with the ONYXWorks® system.

Functional Buttons Refer to Macro Buttons.

119ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 120: Onyxworks Workstation

Glossary

GGateway Gateways connect the ONYXWorks®

Workstation to a specific fire alarm network, and to other ONYXWorks® Workstation all of which make up an ONYXWorks® system. A Gateway may be installed in the Workstation or an independent wall-mounted unit.

Graphics Printer The graphics printer is attached to the Workstation using the parallel port and is configured through the standard Windows® printer interface. A Graphics printer can be used to print various reports, floor plans, and lists from the Workstation.

Guidance Text Guidance text is linked text associated with a specific Workstation screen. Usually this material relates to special procedures or precautions. Guidance text provides text explanations to Users about what to do in special emergency situations, such as instructions for calling facility managers in case of a fire alarm.

HHardlock Key The Hardlock Key attaches to the USB port of a Workstation and provides authorization and feature information to the Workstation. A Hardlock Key is needed for each Workstation running the software. History Database Maintains a record of all events and actions that take place in the ONYXWorks® system. The history database can become the largest of all the database files.

HVAC Heating, Ventilation, and Air Conditioning.

IInformation Labels An information label hyperlinks to text, pictures, video, and/or sound, to provide details about locations monitored by the ONYXWorks® system. These are not physical devices; they are clicked-on to display important information for the User or for emergency responders. Suggested pop-ups are pictures of hazardous materials storage areas; special warnings and instructions for hazardous materials; construction area designations; and locations of emergency exits.

IP Address An IP address is a unique identifier that represents a connection of a TCP/IP network. IP addresses are used to address individual workstations and servers on the ONYXWorks® system.

LLinked Information Any addressable device or information label on the floor plan can have linked information. Linked information can be text, video, bitmaps, and sound. To access the linked information on a device (either addressable or an information label), right-click-on the icon to display the pop-up menu and then make the appropriate selection.

MMacro Macros are used to define custom commands for communication with particular devices on the network. Macros can be defined to perform a variety of different commands (dependent on the point type), to one or more specified devices.

Macro Buttons Macro Buttons are added to the Workstation screen to perform macro functions that have been previously defined by the Admin User. These are sometimes referred to as Functional Buttons. They can be customized more than the Command Buttons that appear on the ONYXWorks® Workstation Taskbar.

Member database Refer to User Database.

Monitoring Profiles Monitoring profiles allow the User to select exactly what events are seen by the Workstation, organized based on selecting specific nodes, sub-nodes and devices. Monitoring assignments are the job of the Admin User, who creates a number of profiles that can be selected by the User. Usually these profiles are created around a physical or operational structure, such as by building or by work shift.

Mouse-over Window A window that pops-up a window with additional information about something on the Workstation screen when the mouse pointer is position over it.

NNavicons User-defined icons on the Workstation’s screen that provides a shortcut to another Workstation screen. Function is similar to hyperlinks on a web page.

Navigational Buttons Refer to Navicons

NION Network Input Output Node. A device with the necessary protocol to provide communication dialog between the addressable devices on a network with the Workstation.

Node Number A node number is the ID for any given node on a network.

OOff-Normal Event An off-normal event is an event which indicates activity or change in a condition that requires the attention and/or response of an User.

Overview The Overview provides either an overview of the currently displayed Workstation screen (without devices, buttons, or other objects).

120 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 121: Onyxworks Workstation

Glossary

PPaired Event Events which, after acknowledgment, still require another event to return the associated device to its original state. This second event may be initiated by the User (as in the case of sending a reset to a device or panel), or the original device itself (such as an alarm server which originally went off-line and is coming back on-line). Devices can send more than one off-normal event before the related return state event is sent, for example a fire panel may have more than one alarm state, and these will not clear until all events have cleared and the panel reports an all clear state.

Panel A panel is a central gateway that connects a number of related devices together. For example, a fire panel might have smoke detectors, pull-stations, sprinkler systems, and sirens all connected at the panel. This also allows the Workstation to communicate directly with the panel instead of the individual device.

Parent Screen In the Navigation Tree’s outline view, the highest level is the Title Screen. The Gateways, nodes, and devices that branch off of it are its Child Screens. A parent screen can have zero or many child screens. The highest level is the Title Screen; it cannot be a child.

Plug-In A Plug-In can be in one of two forms, either an *.EXE application or a *.CFG configuration file. Plug-In Applets are independently operating software applications. They interface with the Workstation at the local level. Configuration files act to create new menu options by defining ‘macro’ commands or sequences of information for communicating with specific devices. Configuration files may or may not launch independent applications.

Point Icons An Admin User defined graphic element on a Workstation screen. Each represents a physical addressable device on the network.

Point ID The point identification (ID) is the eight character alphanumeric address suffix for the monitored point reported by the node. The Point ID for each device must match the point ID reported by the node. The point ID makes up the last 8 characters of a device’s absolute address.

Pop-Up Menu Pop-Up Menus provide the User with device specific information and controls. The device pop-up menu is activated by right-clicking-on any addressable device. The menu that appears depends on the point type, situation, and the access permissions of the User. Some options are common to all addressable devices, while others have functions that are point type specific.

Pull-station A pull-station is a fire related device which, when activated (generally by pulling a lever or switch) triggers an alarm at the panel, activating audible alarms and other pre-configured devices.

RReceivers Gateway Acts as a bridge between the supported digital alarm receivers and the ONYXWorks® system.

SScreen Screens are the fundamental visual interface between gateways and the User. Screens are displayed in the Floor Plan Area of the main display. Each system can contain numerous screens, and screens can contain floor plans, graphics, and/or devices.

Screen Database The Screen Database holds information for the backgrounds, devices, buttons, etc. for all of the Workstation screens and gateways on the ONYXWorks® system.

Security Alarm Event An event issued by security related devices such as motion detectors, glass break detectors, and door contacts.

Security Options User functionality and activity are controlled by the assignment of security profiles. Each User and Admin User is assigned a security profile with their system member record. Security profiles contain a list of all Workstation functions to which anyone assigned to that profile is allowed access.

Single Ended Event An event that, once it is received, leaves the sending device in the same condition that it was in originally.

Site A site is the physical location being protected by an ONYXWorks® system installation, i.e. the building itself. (Refer to the Gateway definition for the building’s virtual organization within the network.)

Site Annunciation Icons Site Annunciation icons are special point icons that represent the overall condition of a site monitored on the network. Site Annunciation icons have two states: normal and off-normal. The state of a Site annunciation icon is dependent on the condition of the devices at the site it represents. If all devices at the represented site are in normal condition, then the site annunciation icon displays a normal condition. If any device at the site reports an off-normal condition, then the site annunciation icon is changed to be displayed in an off-normal condition.

Supervisory Alarm Event A Supervisory alarm is a special alarm to indicate action that has functionally disabled a key device (for either fire protection or security). An example of this is the event generated if the water valve is shut off for a sprinkler system.

121ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 122: Onyxworks Workstation

Glossary

TTaskbar This area of the Workstation screen displays Admin User configured command buttons and open-window tabs. The Taskbar is located between the Navigation Tree and the Workstation’s Toolbar.

TCP/IP The protocol used by the Workstation level of the ONYXWorks® network that provides communication among workstations, and gateways.

Title Screen Refer to Parent Screen.

Toolbar The area of the Workstation screen directly below the Main Menu, providing icons for commonly used functions.

Trouble Event A Trouble Event indicates a functional problem with a addressable device on the network. Examples of trouble events include a device or Workstation going off-line, a battery low or no power event, a dirty head on a smoke detector, etc.

UUPS Uninterrupted Power Supply. A UPS is used between the building’s power source and the Workstation and provides battery backup. A UPS will allow the Workstation to continue to operate as usual for a period of time determined by the UPS’s rating.

User Database The User Database holds all of the information pertaining to members of the ONYXWorks® system. This includes Users and Admin Users with access to the monitored gateways.

VVector Graphics Vector Graphics are based on lines, boxes, curves, and fills between discrete points in two dimensional space. Because all objects are described as sets of points, lines, curves, and fills that can be recreated at any scale, vector drawings are freely scalable over an unlimited range with no loss of resolution. This makes vector drawings ideal for floor plan layouts and detailed design work.

W Windows® MetaFile (.WMF) Graphic files that hold vector drawing information, discrete points, lines, and curves. *.WMF files are used in the Workstation predominately for importing floor plans. Because the *.WMF format is vector-based, the information in WMF files can be re-sized without loss of resolution and quality. When dealing with floor plans in the Workstation, this is very important as it allows the floor plan to be zoomed in without degrading resolution of the lines. Files are identified with the extension *.WMF.

Workstation Workstation is the standard name for a computer running the ONYXWorks® Workstation software application. It is possible for a Workstation PC to also run Gateway software if the appropriate network card is also installed.

122 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 123: Onyxworks Workstation

Appendix B: Details about Event Data

B.1 Event Data

Each event within the ONYXWorks® system has its own unique properties. These properties include normal and off-normal conditions, abbreviations for the event, color codes, and the priority of the event. Included in this index are tables that provide the information in a simplified format.

B.2 Event PriorityPriority is the most important of the event specific information because it affects which events are annunciated by the Workstation first. Knowing the priority of events provides an understanding about the severity of various events, and how events interrelate.

Priority is ordered in groups as defined by UL/ULC. Each event within a group has equal priority. These groups are (highest to lowest) Fire Alarm and Process Alarm, Supervisory and Fire Trouble Signals, Holdup and Burglar Alarms, and Other Signals.

Each event within the ONYXWorks® system has a corresponding color. This color coding is used when displaying the event on-screen, when viewing events in history manager, and various other applications throughout the software.

Table B.2, “Event Color Coding” shows each event type and its corresponding color. Keep in mind that this lists off-normal events only. Each off-normal event has a corresponding normal event. Every Normal discrete event within the Workstation is displayed with the color gray when in Graphic Mode.

NOTE: All data is current as of publication however, new events may be added in the future.

NOTE: Workstation default color codes are discussed here. Admin Users can customize these color choices if required by their Authority Having Jurisdiction. Always document custom color schemes for future reference.

Table B.1 Events By Priority (Highest Priority First)

UL Category Off-Normal Condition Normal Condition

Fire Alarms and Process Alarms

Alarm Alarm Restored

Fire Alarm Fire Alarm Restored

Fire Alarm (Non-latching) Fire Alarm Restored

123ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 124: Onyxworks Workstation

Details about Event Data Event Priority

Supervisory and Fire Trouble Signals Audibles Silenced Audibles Re-activated

Supervisory Alarm Supervisory Normal

Pre-Alarm Pre-Alarm Restored

Verifying for Fire Alarm No Longer Verifying

Alert Condition Alert Condition Restored

Fault Condition Fault Condition Resolved

Zone Trouble Zone Trouble Restored

Trouble Trouble Restored

Off-Normal Condition Returned to Normal

Loop Trouble Loop Trouble Restored

Bad Address Bad Address Resolved

Device Non-monitoring Device Returned to Monitoring

Security Alarm Security Alarm Restored

Tamper Switch Activated Tamper Switch Restored

Holdup and Burglar Alarms(Not UL Listed)

Door Ajar Door Ajar Restored

Forced Entry Forced Entry Restored

Panic Alarm Panic Alarm Restored

Other Signals Agent Release Agent Release Off

Agent Release Abort Agent Release Abort Off

Recent Alarm N/A

Point Inactive Point Active

Temperature Alarm Temperature Normal

Ground Fault Ground Fault Restored

AC Power Failure AC Power Restored

Extremely Low Value N/A

Extremely High Value N/A

Very Low Value N/A

Very High Value N/A

High Value N/A

Table B.1 Events By Priority (Highest Priority First) (Continued)

UL Category Off-Normal Condition Normal Condition

124 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 125: Onyxworks Workstation

Event Priority Details about Event Data

Other Signals (continued) Low Value N/A

Cover Open Cover Replaced

Out of Paper Paper Restored

Offline Offline Restored

Transmission Trouble Transmission Normal

Fuse Failure Fuse Failure Restored

Short Circuit Circuit Restored

Open Circuit Circuit Restored

Position Alarm Position OK

Video Signal Loss Video Signal Restored

Device Disabled Device Re-enabled

Unlock Locked

Addressable Input On Addressable Input Off

Armed N/A

Disarmed N/A

Armed Away Mode N/A

Armed Stay Mode N/A

Program Entry N/A

Program Exit N/A

Armed Instant N/A

Armed Maximum N/A

Test Mode Activated Test Mode Terminated

Restart N/A

Manual Disable Manual Enable

Schedule Disable Schedule Enable

Manual Output On Manual Output Off

Schedule Output On Schedule Output Off

Reset N/A

Panel Normal N/A

Table B.1 Events By Priority (Highest Priority First) (Continued)

UL Category Off-Normal Condition Normal Condition

125ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 126: Onyxworks Workstation

Details about Event Data Event Priority

Table B.2 Event Color Coding

Off-Normal

Off-Normal Event Off-Normal Color

Off-Normal Event

Yellow • Pre-Alarm• Verifying for Fire Alarm• Alert Condition• Soft Anti-Passback Warning• Point Inactive• Fault Condition• Temperature Alarm• Zone Trouble• Ground Fault• AC Power Failure• Trouble• Loop Trouble• Very Low Value• Very High Value• High Value• Low Value• Cover Open• Out of Paper• Transmission Trouble• Fuse Failure• Short Circuit• Open Circuit• Position Alarm• Video Signal Loss• Unlock• Program Entry• Program Exit

Red • Fire Alarm (Non Latching)• Alarm• Agent Release• Tamper Switch Activated• Agent Release Abort• Door Ajar• Forced Entry• Recent Alarm• Panic Alarm• Supervisory Alarm• Extremely Low Value• Extremely High Value• Addressable Input On• Restart

Blue • Security Alarm• Audibles Silenced• Off-Normal Condition• Bad Address• Device Disabled• Addressable Output On• Device Non-Monitoring• Armed• Disarmed• Armed Away Mode• Armed Stay Mode• Armed Instant• Armed Maximum• Test Mode Activated• Manual Disable• Schedule Disable• Manual Output On• Schedule Output On

Gray • Offline

126 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 127: Onyxworks Workstation

Printer Output Format Details about Event Data

B.3 Printer Output FormatThe event printer port of the Workstation outputs each event as it is annunciated at the Workstation. Event printer output format is determined by the output format configured in Workstation >Options. Your event printer output could be different than the one shown below.

This example annunciation output is five lines per event. There are four lines containing device information and status. The lines are not padded with spaces at the end, but are padded internally for columnar separation. The fifth line is a separation bar comprised of 79 asterisks. A format description and an example printer output is provided below.

Figure B.1 Printer Output Format Example1. Time of Alarm – The time that the alarm occurred. On a local area network, this will be the

same as the reported time. On a wide area network, this time is the time the alarm occurred and was received at the remote communications device (but not the time it was reported to the Workstation). (40 characters padded with spaces).

2. Time Alarm Was Reported – This field reports the time at which the event was annunciated at the Workstation. On a local area network, this time will usually be the same as the Time of Alarm field. (40 characters not padded with spaces).

3. Gateway – This field is the Gateway ID of the gateway with the off-normal device. (20 characters padded with spaces).

4. Device – This field is the point ID of the off-normal event. The format for this entry is node, sub-node, point ID in the following format:

<NNNSSSDDDDDDDD>, where “NNN” is the three digit node ID, “SSS” is the three digit sub-node ID, and “DDDDDDDD” represents the point ID. If the point ID is less than 8 characters in length, it is padded with spaces in front of the ID and after the sub-node. For example: <003001 Smk01>. (20 characters padded with spaces).

5. Point Type – This field reports one of the standard point types. This field is 30 characters in length. (40 characters not padded with spaces).

6. Status Name – This field reports a standard device status. For information on each different device status. (30 characters padded with spaces).

7. Value – What this field reports according to the type of device. For example, a discrete input will report to this field with a “Value” the appropriate current condition. An analog input will list the value and units for the analog input. (50 characters not padded with spaces).

8. Device Description – This is the description of the device as defined within the Workstation. This description is normally comprised of a 40 character device description and a 40 character zone description that is extracted from the panel when a device reports. (80 characters not padded with spaces).

1 2

3

45

6

7

8

127ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 128: Onyxworks Workstation

Details about Event Data Printer Output Format

128 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 129: Onyxworks Workstation

Appendix C: ONYXWorks® Workstation User’s GuideThe Admin User should print this information and have the copy near the Workstation so the person who typically monitors the Workstation can refer to it.

C.1 Workstation Display DescriptionsOperating the Workstation in Text Mode displays the graphical user interface in tabular form. Typically a Admin User does not use the Text Mode view as your monitoring interface. For more information refer to “About Text Mode View” on page 135.1. “Displayed User” on page 130.2. “Main Menu” on page 130.3. “Toolbar Menu” on page 130.4. “Taskbar Menu” on page 130.5. “Overview” on page 1306. “Workstation Floorplan Area” on page 1317. “Graphic Elements Descriptions” on page 1318. “Navigation Tree” on page 132.9. “New Event” on page 13310. “Acknowledged Events” on page 13311. “Alarm Summary” on page 13312. “Event Annunciator Icon” on page 134

Figure C.1 Workstation Display

543

9

11

12

8

10

6

7

12

129ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 130: Onyxworks Workstation

ONYXWorks® Workstation User’s Guide Workstation Display Descriptions

C.1.1 Displayed UserThe Admin User sets Security Options for you which determines your level of access to the Workstation. For example, some accounts may not have permission to exit the Workstation or some Main Menu selections maybe grayed out.

C.1.2 Main MenuThe Workstation software application’s Main Menu when selected displays drop-down a list of choices. If after the choice a ... (dot dot dot) is present, then the choice will display another window where additional action is required if you are to continue.

C.1.3 Toolbar MenuYou can identify these icons by placing the mouse’s cursor over the icon and reading the hint that is displayed. The icons are used to perform the following common functions.

• Previous Screen - Displays floorplan that was viewed before the current displayed floorplan.• Next Screen - Displays the next floorplan below the current floorplan in the Navigation Tree

hierarchy.• Up one level - Displays the next floorplan above the current floorplan in the Navigation Tree

hierarchy.• Print Current Screen – Prints the floorplan display to the currently selected printer.• Zoom In One Level - Increases the zoom of the floor plan display by 50% (ranges from 100%

to 3700%)• Zoom Out One Level – Decreases the zoom of the floor plan display by 50% (ranges from

100% to 3700%).• Zoom Full Image - Display current displayed floorplan at 100%• Show Floorplan – Toggles floorplan on and off.

C.1.4 Taskbar MenuThe Taskbar displays custom command icons and or an icon that corresponds to an open Workstation software application window. The Admin User defines these custom command buttons. Taskbar buttons display from left to right.

C.1.5 OverviewThe Overview window allows you to determine their location on the currently displayed Workstation floorplan area. It displays and indicates where on the Workstation floorplan area the you are viewing by encompassing that viewed area in a red rectangle. The red rectangle is clicked and dragged for repositioning the viewing area, helpful when a zoom in scale is selected for the Workstation floorplan area. The Overview window does not display the graphic elements within it.

130 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 131: Onyxworks Workstation

Workstation Display Descriptions ONYXWorks® Workstation User’s Guide

C.1.6 Workstation Floorplan AreaThe Workstation floorplan area title identifies which area of an ONYXWorks® system that is currently being displayed on the Workstation’s display. The Workstation floorplan area usually has a building floor plan that is background layer and serves as the primary source for visual feedback the location of an off-normal event in an ONYXWorks® system which corresponds to the point’s (device) location in a building. The point types can be a fire alarm control panel, fire protection devices, security devices, and cameras.

C.1.7 Graphic Elements DescriptionsPoint IconsThese graphic elements represent a physical addressable device on the system. Examples of point icons are fire panels, and fire protection devices, and NION interfaces. A name of the point displays above the icon and at times its status is displayed below it. If the point’s status becomes off-normal, its icon will flash and information about its status will be displayed below it.

Clicking on an icon displays a box with detailed information across the bottom of the Workstation screen. The information reflects the current state of the associated icon.

NaviconsThese graphic elements represent a method to navigate between Workstation floorplan areas to find points or an event. They are used exclusively to find an event if in the Autonavigate feature has not been set to autonavigate to an off-normal event.

Each Workstation floorplan area (parent) has one Navicon that hyper-links to each of its respective subordinate (child screen) Workstation floorplan areas (refer to the Navigation Tree hierarchy). Navicons change color to match the off-normal event that is reported to the Workstation. They are used to locate an event on parent or child screen; follow the same colored Navicon to find an event.

Information LabelsThese graphic elements represent important information for the you during monitoring. That information can be a photograph, a text document, a video, or a sound clip. Information Labels use an asterisk to identify them as such. One suggested use is to provide firefighters with an image of hazardous materials stored on-site.

Factory defined and Admin User assigned control commands are available for all point icons, navicons, and information labels. Those commands are accessed with right-clicks-on its Navigation Tree entry or right-clicks-on its icon.

NOTE: Control commands are available only when you have a node control and security profile that allows it.

NOTE: Only one Workstation can control any single system device at a given time. Taking control of a device removes control from the previous supervisor of that device.

131ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 132: Onyxworks Workstation

ONYXWorks® Workstation User’s Guide Workstation Display Descriptions

C.1.8 Navigation TreeThe Navigation Tree:

• Has an user interface similar to Microsoft’s Windows® Explorer.• Displays the ONYXWorks® system in a structured hierarchy form.

Navigation Tree Descriptions1. Device screen name that is currently displayed.2. “–” used to collapse Navigation Tree (Tree) and hide child screens.3. Node on a Workstation floorplan area; double-click-on the name of a device to display the

node and the Workstation floorplan area it is located on.4. “+” used to expand Tree and view child screens.5. Pane boundary; click and hold, then drag on the boundary point to change the pane’s size (refer

to , "Window Pane View Changes").

Figure C.2 Navigation Tree Overview

2

3

1

4

5

132 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 133: Onyxworks Workstation

Workstation Display Descriptions ONYXWorks® Workstation User’s Guide

Window Pane View Changes1. The Navigation, New Events, and Acknowledged Events areas can be expanded or collapsed

by clicking and holding-on and then dragging the boundaries between sections.2. The Overview and Alarm Summary window can be expanded and collapsed with a click-on

the arrows in its title bar.

Figure C.3 Expanding Event Areas for Viewing

C.1.9 New EventWhen an event is reported to a Workstation, the Workstation will display the event information in the “New Events” area and sound an audible alarm at the station. The Workstation will auto-navigate to the Workstation floorplan area that has the highest priority event.

New Events are events that have been reported to and received by the Workstation but not yet acknowledged by you. Once you acknowledge an event, the event moves to the Acknowledged Events list.

New Events are displayed in this manner:

• If the event is acknowledged at the panel “Acked” will be displayed prefixing the event in the New Events list.

• If the Workstation has node control of the point a colored box will display to the left of the event in the Navigation Tree.

• If the event is unreliable (meaning it was reported while a gateway or node was in fault) an * will be displayed prefixing the event in the New Events list.

C.1.10 Acknowledged EventsOnce you acknowledges an event, the event is added to the Acknowledged Events listing. The Acknowledged Events listing only displays events that have been received by the Workstation and have been acknowledged by you.

C.1.11 Alarm SummaryThe Alarm Summary window will display a list that is a running total of new and acknowledged events by type; they are listed in order of priority. The Alarm Summary window by default is hidden and is revealed by clicking-on the arrows adjacent to the Alarm Summary title. Clicking on the alarm summary icons displays a list of all the points currently in that state.

1

2

133ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 134: Onyxworks Workstation

ONYXWorks® Workstation User’s Guide Workstation Display Descriptions

C.1.12 Event Annunciator IconEvent Annunciation Icons display in a highlighted priority related-color when an event is reported to the Workstation. They are always visible and remain in a highlighted priority related-color until all off-normal conditions have been resolved.

You can identify these icons by placing the mouse’s cursor over the icon and reading the hint that is displayed. The following describes the types of events that are reported.

• Fire - Events issued by fire protection related devices such as pull-stations, smoke detectors, and sprinkler systems.

• PreAlarm - Events that indicate that a point is close to declaring an alarm, giving the facility manager opportunity to address the problem before an emergency develops.

• Security - Events issued by security related devices such as motion detectors, glass break detectors, and door contacts.

• Supervisory - Alarms that are special alarms to indicate action that has functionally disabled a key device (for either fire protection or security) . An example of this is the event generated if the water valve is shut off for a sprinkler system.

• Troubles - Events that indicate a functional problem with a device on the network. Examples of trouble events include a device or Workstation going off-line, a battery low or no power event, a dirty head on a smoke detector, etc.

• Advise - A condition that is an administrative event, internal to the ONYXWorks® system. This is not a life-safety or security event, but an internal warning of a condition that may need someone’s attention—such as the history file reaching 100,000 entries.

• Disabled - Indicates all disabled points on the system.

134 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 135: Onyxworks Workstation

Workstation Display Descriptions ONYXWorks® Workstation User’s Guide

C.1.13 Other - Indicates input on, output on events.•

Workstation Display OptionsThe Admin User setups how the Workstation graphical user interface usually is displayed. Typically you do not require the feature of toggling between Graphics Mode and Text Mode. The Admin User may have not allowed you access to this Main Menu choice.

About Graphics Mode ViewIn Graphics Mode the Workstation displays an ONYXWorks® system as floor plans, point icons, and the system’s event information in window pane form.

About Text Mode ViewThe Text Mode view expands the Workstation’s New Events and Acknowledged Events information in tabular form across the entire Workstation display. The Detailed Events/IM/IRM are displayed. Just like in Graphics mode, when in Text Mode events will be dynamically updated as they occur. The Panel Ack column will be displayed with check-boxes to indicate the event is known to be acknowledged at the panel.

Figure C.4 Text Mode Displayed on the Workstation

Transition from Graphics Mode to Text Mode and vice-versa is accomplished by accessing the View menu. When the Workstation is in Graphics Mode, the View menu will display “Text Mode”. When the Workstation is in Text Mode, the View menu will display “Graphics Mode”. In addition there is a Disabled icon.

The same color-coding used to reflect status is used in both modes. The colors will correspond to status class:

• Green: Return To Normal• Red: Alarm• Yellow: Trouble

135ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 136: Onyxworks Workstation

ONYXWorks® Workstation User’s Guide Daily Operation

• Blue: Security

In Graphic Mode gray shading will indicate whether an event is known to be acknowledged at the panel.

C.2 Daily Operation

C.2.1 Logging into the WorkstationThe Admin User must have created your profile that will allow you to log into the Workstation. When you log in, the Workstation software automatically logs out the previous User.

User Login ProcedureStep 1. On the Workstation software application’s Main Menu select File >Login. The User

Login window displays.Step 2. Click-on to highlight the desired User name in the list of Available Users.Step 3. Type the User’s password.Step 4. Click-on OK button. The name of the current User appears at the top right of the

Workstation floorplan area.

User Log Out Procedure Step 1. On the Workstation software application’s Main Menu select File >Login.Step 2. On the User Login window, click-on the <current User’s name> in the list of Available

Users.Step 3. Click-on Logout button. The Workstation will login the internal logged out account which

has no permissions other than allowing someone to log in. This login change ensures the ONYXWorks® system will continue to be monitored.

136 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 137: Onyxworks Workstation

Daily Operation ONYXWorks® Workstation User’s Guide

C.2.2 Interpreting Events on the Workstation’s User InterfaceWhat Happens When a New Event OccursWhen an event occurs in the ONYXWorks® system a Workstation receives information about the event and the following occurs at the Workstation:

1. In the New Events window, the event is added to a list.2. In the Navigation Tree, a colored box will display adjacent to the level(s) with the event(s).

Priority of the event(s) is displayed by color (red for fire, yellow for trouble, etc.).3. The auto-navigate feature will display the Workstation floorplan area and the addressable

device’s icon experiencing the event and display it as a priority color. The software will attempt to center the point icon in the window.

4. In the Alarm Summary window the alarm will be added to its list.5. The corresponding Alarm Summary Icon will be displayed as a priority color.6. A sound is emitted indicating the event(s).

Figure C.5 Event Windows

About Point Icon SelectionClicking a point’s icon will display a window across the bottom of the screen display that has details about the point. The window’s title bar will be colored coded based on the current state of the associated icon.

3

5

4

1

2

137ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 138: Onyxworks Workstation

ONYXWorks® Workstation User’s Guide Daily Operation

What Happens When New Events are AcknowledgedWhen a paired event is acknowledged at the Workstation the following occurs:

• Fire Control Center Mode: In the New Events window, the acknowledged event moves to the list in the Acknowledged Events window.If and when a new event is acknowledged at the FACP, the FACP acknowledged event will automatically move from list to list at the Workstation.

• Supervisor Station Mode: In the New Events window, the acknowledged event moves to the list in the Acknowledged Events window.

• On the Workstation floorplan area, the point icon will stop flashing but remain in its appropriate off-normal priority color.

• The sound indicating the new event will stop playing, but only if there are no other new events in the New Events box. Sound continues to be emitted until all events in the New Events box have been acknowledged at the Workstation.

NOTE: If an event is acknowledged at a FACP and the Workstation is in Activate Graphics Mode as a Supervising Station, the event will remain in the New Events window but the status field of that event will turn from white to gray indicating an acknowledgement at the FACP. The event will still need to be acknowledged at the Workstation. Once acknowledged at the Workstation the acknowledged event will move from the New Events window to the Acknowledged Events window and remain there until it returns to normal. The status field will still be gray.

138 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 139: Onyxworks Workstation

Daily Operation ONYXWorks® Workstation User’s Guide

What Happens When Acknowledged New Events Return to NormalWhen the event returns to normal the following occurs on the Workstation.

• Fire Control Mode only: In the New Events window, The off normal event vanishes from the list.

• Supervisor Station Mode: In the New Events window, the return to normal event remains in the list.

• In the Workstation floorplan area, the point icon returns to its normal condition color.• In the Alarm Summary window, the Alarm Counter list will decrement.• The corresponding Alarm Summary Icon returns to its normal condition color, provided there

are no other off-normal events of that type on the system.• In the Navigation Tree, the adjacent colored box will vanish, provided there are no other off-

normal conditions on those Workstation floorplan areas.• The sound should not be sounding from the Workstation. If a sound is still being emitted then

more events are present in the system.

FCC Mode or Supervising Mode Event Handling ComparisonEvents are displayed the same way whether the Workstation is running in Fire Control Center (FCC) mode or Supervising Station mode. Such as:

• If the event is acknowledged at the panel “Acked” will be displayed prefixing the event in the New Events list.

• If the Workstation has node control of the point a colored box will display to the left of the event in the Navigation Tree.

• If the event is unreliable (meaning it was reported while a gateway or node was in fault) an * will be displayed prefixing the event in the New Events list.

However the Workstation handles return-to-normal conditions and acknowledgements in a significantly different way, depending on operating mode.

Table C.1 FCC Mode and Supervising Mode Comparison

Action FCC Mode

Supervising Mode

If an event is acknowledged at the Fire Alarm Control Panel (FACP) it is acknowledged at the Workstation

YES NO

If an event is acknowledged at the Workstation it is acknowledged at the Fire Alarm Control Panel (FACP)

YES*

* If the logged in User has the Security Profile to do so.

YES*

When an event returns to a normal state it is removed from the New Event listing

YES NO

When an event returns to a normal state it is acknowledged at the FACP YES NO

139ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 140: Onyxworks Workstation

ONYXWorks® Workstation User’s Guide Daily Operation

C.2.3 Managing EventsAn event is defined as any change in the status of a device or a transfer of information between a device and the Workstation or between two devices. Some of these events are considered background and housekeeping events and are not seen by you on the Workstation’s display. Those background and housekeeping events can be viewed with the View >Background Activation command. The View >Armed/Disarmed Points command may be used to view events also.

The events that are of primary concern to you are off-normal events. An off-normal event indicates activity or change that requires your attention and/or response. Refer to Appendix B, “Details about Event Data”, on page 123 for information about events.

About New Events Priority RatingIn the New Events window, new events are listed according to the date and time that they occurred and they are further defined by the highest to lowest priority of the event.

For example:

• A” fire alarm event” with the same time and date as a “trouble event” will display higher in the list.

• A “fire alarm event” with the more recent date and time will be listed above a “fire alarm event” with older date and time.

About Off-Normal Events• A change in condition or activation of a monitoring device (Motion Detectors, Smoke Alarms,

etc.).• A door is ajar.• A node becomes disconnected from the network.• A Monitoring device is disconnected from its monitoring node.

Single Off-Normal Events

A single event that, once it is received, leaves the sending device in the same condition that it was in originally. Single events do not represent a lasting change of condition. A single event is removed from the Acknowledged Events list after it is acknowledged.

Paired Off-Normal Events

If a single event is paired with another event, one event can move to the Acknowledged Events list after it is acknowledged, but it remains in the Acknowledged Events list until its paired event is acknowledged. Once an acknowledge to the related pair events is performed, both events are removed from New Events and added to the Acknowledged Events list.

Fire alarms actually latch a FACP and require that the panel be reset. Therefore, alarm states will remain in the New Event list until the fire alarm control panel (FACP) associated with the alarm states it is reset. Alarm-off states that have been acknowledged will clear once the panel is reset and all the panel’s devices have returned to a normal condition.

140 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 141: Onyxworks Workstation

Daily Operation ONYXWorks® Workstation User’s Guide

C.2.4 Acknowledge a New Event ProceduresAcknowledge an Event in the New Events

To acknowledge events, highlight the event in the Navigation Tree and then click-on the appropriate New Events icon (i.e. ( ).

Block Acknowledge Events (FCC Control Mode Only)

To acknowledge multiple events, highlight the events in the Navigation Tree and then click-on the appropriate New Events icon (i.e. ( ).

Troubles, supervisory, and security events can be block-acknowledged through a NFN Gateway. Fire Alarm and Hold-up events require individual acknowledgement.

Point Right Click Choices to Respond to Events

Addressable Device’s have right-click menus that provide you with a list of choices that are device specific information and used to control a device. The choices that appear in menu depends on the type of device, the situation, and your Security Option permissions. The following descriptions are provided for an overview of some right-click menus options:

• <Point Description> – Selecting the top line Device Description displays window which shows the device’s provided description. This description may have been entered by the Admin User or the description was read from a panel on the system.

• Enter User Response – This choice displays a window with predefined User responses for reporting various conditions and operations related to the device. There is also a custom field for text-entry if a unique situation occurs. The selected response is logged to the history file.

• History of Device – Opens the History Manager window that displays the history information relating to the selected device.

• View or Play: Text, Bitmap, Video, Audio – Only if the device has an asterisk displayed adjacent to a choice, it has linked media and an choice will also display in the list of choices.

• Zoom – This choice allow the selection of various zoom levels and a return to the previous zoom level choice. When a zoom is selected, the zoom will center on the current mouse pointer location.

An asterisk next to a choice indicates that another Workstation has control of the device; a Workstation must have control of a device to perform a command for the device.

Send a Voice Page

You can send a voice page to sites on the network.

Step 1. Main Menu select Action >Voice PagingStep 2. Click-on Activate Voice Paging check-box (check mark showing).Step 3. Click-on Start Paging.Step 4. On the Workstation keyboard, press and hold both the Shift and Ctrl keys and speak into

the microphone.There is a five second delay in the voice page. If no sound is detected for 45 seconds, Paging Zones time-out and a trouble event is generated at the Paging Zone.

NOTE: Supervision Station Mode Only. When an event is acknowledged at a Workstation the event is only acknowledged locally. That acknowledgement does not affect the event status or device on other Workstations on the network unless the acknowledging Workstation has control of that device.

141ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 142: Onyxworks Workstation

ONYXWorks® Workstation User’s Guide Daily Operation

142 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 143: Onyxworks Workstation

Appendix D: ONYXWorks® Workstation Software Installation Procedure

D.1 Windows InstallationA Windows CD-ROM was shipped with the Workstation and it should be used to install Windows.

Step 1. Insert the CD-ROM in the Workstation computer’s CD-ROM drive.Step 2. Follow the on screen prompts.Step 3. Perform the "Required Windows Settings and Options".

D.2 Required Windows Settings and Options

NOTE: These Windows options must be configured if for some reason you had to re-install the Windows operating environment.

NOTE: If you are prompted by Windows to reboot the PC after making any of these settings, you should and then return to the place in the required Windows options procedures and continue.

143ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 144: Onyxworks Workstation

ONYXWorks® Workstation Software Installation Procedure Required Windows Settings and Options

D.2.1 Windows Explorer Settings and Options Checklist

User Accounts• Administrator account only• No password for Administrator account• Login to Administrator account automatically – no login prompt at startup

Windows Services• Automatic Updates service disabled• Automatic Updates applet turned off• Themes service disabled• Time service disabled

Hard Drive• Folders – only folders present should be • Documents and Settings• Program Files• Windows (WinNT)• Hidden System Folders• Disk Cleanup• Recycle Bin empty• No Temporary Internet Files• No Temporary Files

Networking• Computer Name – set to “Workstation”• Workgroup – set to “WORKGROUP”• IP Address – set to 192.168.1.100• Subnet Mask – set to 255.255.255.0

Display Properties

Themes Tab• Theme = Windows Classic

Desktop Tab

Background = none

Screen Saver Tab

Screen Saver = none

Screen Saver Tab - Power Options• Turn Off Monitor = never• Turn Off Hard Disks = never

Appearance Tab• Windows and Buttons = Windows Classic Style• Color Scheme = Windows Standard• Font Size = normal

NOTE: These Windows Explorer options must be configured if for some reason you had to re-install the Windows operating environment.

144 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 145: Onyxworks Workstation

Required Windows Settings and Options ONYXWorks® Workstation Software Installation Procedure

Settings Tab• 1024x768 resolution• 32 Bit Color

Settings Tab - Advanced Options

DPI Setting = large (120 DPI)

Desktop• Taskbar Set To Auto-Hide• Only Desktop Icons – My Computer, My Network Places, Recycle Bin• No Taskbar Shortcuts

Windows Registry - HKEYLOCALMACHINE\SOFTWARE\Microsoft\Windows\CurrentVersion• Run Key is empty• RunOnce Key is empty• RunOnceEx Key is empty

Windows Messenger options• Disable “Run Windows Messenger when Windows starts”• Disable “Allow Messenger to run in the background”

Miscellaneous Options• Performance Options = Adjust For Best Performance• Enable Classic Start Menu

Audio Driver• Verify Proper Driver For CMI8738 Audio Device

Step 1. Open Windows Control Panel – Start \ Settings \ Control Panel.Step 2. Open System applet, select Hardware Tab, click Device Manager button.

Step 3. Select CMI8738 Audio Device and view properties.

NOTE: Correct driver is available on Matrix install CD under Drivers\Comark_Sound_Card

145ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 146: Onyxworks Workstation

ONYXWorks® Workstation Software Installation Procedure Required Windows Settings and Options

Step 4. Select Driver tab.

Step 5. Verify settings• Title = CMI8738/8768 Audio Device• Driver Provider = Dogbert• Driver Date = 6/30/2007• Driver Version = 1.1.3.0

Step 6. You are now ready to perform “ONYXWorks® Workstation Software Application Installation Procedure” on page 147.

146 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 147: Onyxworks Workstation

ONYXWorks® Workstation Software Application Installation Procedure ONYXWorks® Workstation Software Installation

D.3 ONYXWorks® Workstation Software Application Installation Procedure

A ONYXWorks® Workstation CD-ROM was shipped with the Workstation and it must be used to install the software application.

Step 1. Connect the ONYXWorks® USB Software Key to an appropriate connector on the PC.Step 2. Insert the ONYXWorks® Software CD-ROM.

Step 3. Follow the on screen prompts.

Step 4. After HASP installation is finished, the software application displays another prompt window, select the Next button.You can NOT specify a location for the installation.

Step 5. Click the Finish button to restart the computer and then remove the CD-ROM.Step 6. You are now ready to perform additional system setup. Refer to your ONYXWorks®

manuals for further information.

...setup.exe

147ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 148: Onyxworks Workstation

ONYXWorks® Workstation Software Installation Procedure ONYXWorks® Workstation Software Application Installation

148 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 149: Onyxworks Workstation

IndexAAbout 74About Events 117Acknowledged Events 133

How to 141Add Node 37Admin 12, 25, 31, 41, 77, 87, 115Advise Events 134Alarm Summary 133Automatically Backup History 59

CChange

admin password 43color-coding 135Configuration PC 38Control Profiles

Defining, 44Filtering, 45

Control profiles, see Node control profilesCurrent Operator Button 34, 43Custom 73

DDatabase Management 88Delete 37

EEnter Operator Response 118, 141Event Annunciator Icon 134Event Data 123Event Handling 117Event Monitoring Profiles 44Event Priority 123Event Types 117

Advise Events 134Fire Alarms 117, 134PreAlarm 134Security Alarms 117, 134Supervisory Alarms 117, 134Trouble Alarms 134

EventsPaired 140Single 140

Events By Priority 123Events Priority Rating 140Exit Workstation 30Extract Descriptions From Panel 59

FFire Alarm 134

Ggateway

redundant 37Graphic Elements 131Graphics Mode 116, 135Guidance Text 118

HHardware Security 115History Backup 59History Manager 90History of Device 118, 141

IIcon Label 59Import Database 37Information Labels 131Installation

Environmental Conditions 10IP Address 28

LLogin 34, 43Logout 136

MMacro Activated on Alarm 60Main Screen 129

NNavicons 131Navigation 132New Event 133NFN Gateway

Advanced System Architecture 33, 105Node control profiles 61

OOnline Gateways 36Overview window 130

PPaired Events 140Password

Admin 43

149ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 150: Onyxworks Workstation

Index

Play Audio 141Play Text 141Point Description 141Point Icons 131Point Label 58PreAlarm 134Printer Output Format 127Printer Setup 18, 50

Event, 19Connections, 19

Screen/Report, 18, 19, 50Windows®, 19

Properties 37

Rredundant gateway 37Rename 37Reordering Device Screens 79Request Nodes 36

SSecurity 134Security Options 130

Software Security 115Single Events 140Software Security 115Supervisory 134

TTerminology 119, 120, 121Text Mode 85, 129, 135Troubles 134

UUnacked Event Supervision Configuration 60Unacked Event Timeout 60Unacknowledging Events 116Uninterrupted Power Supply 20UPS Supervision 20User Login 34, 43, 136User Response 60

VView

Graphics Mode 135Text Mode 135

View Bitmap 141View Graphics Mode 84View Video 141

WWorkstation Screen 131

ZZoom 141

150 ONYXWorks® Workstation Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 151: Onyxworks Workstation

Limited WarrantyHoneywell International Inc. warrants products manufactured byit to be free from defects in materials and workmanship foreighteen (18) months from the date of manufacture, under normaluse and service. Products are date stamped at time ofmanufacture. The sole and exclusive obligation of HoneywellInternational Inc. is to repair or replace, at its option, free of chargefor parts and labor, any part that is defective in materials orworkmanship under normal use and service. All returns for creditare subject to inspection and testing at the factory before actualdetermination is made to allow credit. Honeywell InternationalInc. does not warrant products not manufactured by it, but assignsto the purchaser any warranty extended by the manufacturer ofsuch products. This warranty is void if the product is altered orrepaired by anyone other than Honeywell International Inc. or asexpressly authorized by Honeywell International Inc. in writing, oris serviced by anyone other than Honeywell International Inc. orits authorized distributors. This warranty is also void if there is afailure to maintain the products and systems in which they operatein a proper and workable manner. In case of defect, secure aReturn Material Authorization form from our Return AuthorizationDepartment.

This writing constitutes the only warranty made by HoneywellInternational Inc., with respect to its products. HoneywellInternational Inc., does not represent that its products will preventany loss by fire or otherwise, or that its products will in all casesprovide the protection for which they are installed or intended.Buyer acknowledges that Honeywell International Inc., is not aninsurer and assumes no risk for loss or damages or the cost of anyinconvenience, transportation damage, misuse, abuse, accident orsimilar incident.

HONEYWELL INTERNATIONAL INC. GIVES NO WARRANTY,EXPRESS OR IMPLIED, OF MERCHANTABILITY, FITNESS FORANY PARTICULAR PURPOSE, OR OTHERWISE WHICHEXTENDS BEYOND THE DESCRIPTION ON THE FACEHEREOF. UNDER NO CIRCUMSTANCES SHALL HONEYWELLINTERNATIONAL INC. BE LIABLE FOR ANY LOSS OF ORDAMAGE TO PROPERTY, DIRECT, INCIDENTAL ORCONSEQUENTIAL, ARISING OUT OF THE USE OF, ORINABILITY TO USE HONEYWELL INTERNATIONAL INC.’SPRODUCTS. FURTHERMORE, HONEYWELL INTERNATIONALINC. SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY ORDEATH WHICH MAY ARISE IN THE COURSE OF, OR AS ARESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USEOF ITS PRODUCTS.

151ONYXWorks® Workstation - Installation & Operation Manual - P/N: 52342:Rev: D 06/01/07

Page 152: Onyxworks Workstation

World Headquarters12 Clintonville Road

Northford, CT 06472-1610 USA203-484-7161

fax 203-484-7118

www.notifier.com