Oncor West Texas Dynamic Line Rating (DLR) Project ERCOT RPG Overview March 26 th , 2013

Upload: others

Post on 21-Sep-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Oncor West Texas Dynamic Line Rating (DLR) Project · Line Ratings Terminology Static Rating – based on prescribed ambient conditions, i.e., full sun mid-day, 104°F, 2 foot per

OncorWest Texas Dynamic Line Rating

(DLR) Project

ERCOT RPG Overview

March 26th, 2013

Page 2: Oncor West Texas Dynamic Line Rating (DLR) Project · Line Ratings Terminology Static Rating – based on prescribed ambient conditions, i.e., full sun mid-day, 104°F, 2 foot per

Transmission Line Ratings are governed by:

– Current flowing in the conductor

– Conductor size and resistance

– Conductor clearance to ground

– Ambient weather conditions:

• Temperature

• Wind speed and direction

• Solar radiation

Dynamic Line Rating

Ambient Temperature:3.6o F, 2oC change +/- 2%

Solar Radiation:Cloud shadowing +/- a few

Wind increase 3.2 ft/sec (2.2 mph): 45 angle + 35%90 angle + 44%

Page 3: Oncor West Texas Dynamic Line Rating (DLR) Project · Line Ratings Terminology Static Rating – based on prescribed ambient conditions, i.e., full sun mid-day, 104°F, 2 foot per

Line Ratings Terminology

Static Rating – based on prescribed ambient conditions, i.e., full sun mid-day, 104°F, 2 foot per second wind

Ambient Adjusted Rating (AAR) – adjusted for ambient temperature other than Static Rating base temperature

Dynamic Line Rating (DLR) – adjusted rating based on actual measured ambient conditions

Page 4: Oncor West Texas Dynamic Line Rating (DLR) Project · Line Ratings Terminology Static Rating – based on prescribed ambient conditions, i.e., full sun mid-day, 104°F, 2 foot per

Integrated DLR System

SCADA/EMS Master

Existing SCADA protocolover substation RTU channel(RS232/485)

License freeSpread Spectrum Radio

IntelliCATTM

for WindowsICCP or MODBUS protocol

CAT-1™ and line load data from EMS

Substation

Control Center

Transmission Line

Operator’s Console’

CATMasterTM

Base Station

Line capacity and temperature to EMS

TGM & ERCOT Operations Telemetry

Page 5: Oncor West Texas Dynamic Line Rating (DLR) Project · Line Ratings Terminology Static Rating – based on prescribed ambient conditions, i.e., full sun mid-day, 104°F, 2 foot per

DOE DLR Project Description

Page 6: Oncor West Texas Dynamic Line Rating (DLR) Project · Line Ratings Terminology Static Rating – based on prescribed ambient conditions, i.e., full sun mid-day, 104°F, 2 foot per

LOCATION OF INSTRUMENTED CIRCUITS• Study Area in Critical Congestion Zone

– 42 Loadcell Tension Monitors– 8 Master Locations Feeding into SCADA

Page 7: Oncor West Texas Dynamic Line Rating (DLR) Project · Line Ratings Terminology Static Rating – based on prescribed ambient conditions, i.e., full sun mid-day, 104°F, 2 foot per

1400

1900

2400

2900

3400

3900

4400

25-A

ug

25-A

ug

26-A

ug

27-A

ug

Ratin

g (A

mps

)

Time of Day

Dynamic Line Ratings and Ambient Adjusted RatingsTradinghouse-Temple Pecan Creek, August, 2011

Time Series

Ambient Adjusted Rating Dynamic Line Rating Static Rating

Example of Capacity ChartStatic, Ambient-Adjusted & DLR Ratings

Page 8: Oncor West Texas Dynamic Line Rating (DLR) Project · Line Ratings Terminology Static Rating – based on prescribed ambient conditions, i.e., full sun mid-day, 104°F, 2 foot per

Example of Capacity ChartStatic, Ambient-Adjusted & DLR Ratings

1400

1900

2400

2900

3400

3900

4400

25-A

ug

26-A

ug

27-A

ug

Ratin

g (A

mps

)

Time of Day

Dynamic Line Ratings and Ambient Adjusted RatingsTradinghouse-Temple Pecan Creek, August, 2012

Time Series

Ambient Adjusted Rating Dynamic Line Rating Static Rating

Page 9: Oncor West Texas Dynamic Line Rating (DLR) Project · Line Ratings Terminology Static Rating – based on prescribed ambient conditions, i.e., full sun mid-day, 104°F, 2 foot per

Percent Time Above Static

0.000%

10.000%

20.000%

30.000%

40.000%

50.000%

60.000%

70.000%

80.000%

90.000%

100.000%

110.000%

Aug

ust-1

1

Sep

tem

ber-1

1

Oct

ober

-11

Nov

embe

r-11

Dec

embe

r-11

Janu

ary-

12

Febr

uary

-12

Mar

ch-1

2

Apr

il-12

May

-12

June

-12

July

-12

Aug

ust-1

2

Sep

tem

ber-1

2

Oct

ober

-12

Nov

embe

r-12

Perc

ent

of T

ime

Lake Creek -Temple 345 kVDLR & AAR Percent of Time Above Static

DLR above static AAR above static

Page 10: Oncor West Texas Dynamic Line Rating (DLR) Project · Line Ratings Terminology Static Rating – based on prescribed ambient conditions, i.e., full sun mid-day, 104°F, 2 foot per

Annual Probability Distribution

1400

1600

1800

2000

2200

2400

2600

2800

3000

3200

3400

0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%

Ratin

g (A

mps

)

% of Time

Cumulative Probability DistributionAugust 2012 - December 2012

DLR AAR Static Rating No wind

Static Rating 1794 amps -DLR provided 99.2% of time

DLR exceeded AAR rating90% of time

Page 11: Oncor West Texas Dynamic Line Rating (DLR) Project · Line Ratings Terminology Static Rating – based on prescribed ambient conditions, i.e., full sun mid-day, 104°F, 2 foot per

DLR Congestion Mitigation

• Target Lines – can significantly mitigate congestion toward $0; with +5 to +10% DLR;

• Peripheral Lines – radiate from one of the target endpoint substations – see additional relief

• Ripple effect – some additional congestion impacts distant from target lines– Some mitigation– Some increases – Grid flexibility – System awareness increased

Page 12: Oncor West Texas Dynamic Line Rating (DLR) Project · Line Ratings Terminology Static Rating – based on prescribed ambient conditions, i.e., full sun mid-day, 104°F, 2 foot per

West Texas DLR Project

DLR Applied to 5 Target Lines:Odessa – Odessa North 138 kV (4)

Moss – Amoco Cowden North – Holt 138 kV (3)

Holt – Emma Tap 69 kV (1)

Moss – Odessa Southwest – Odessa EHV 138 kV (3)

Midland East – Winwood 138 kV (1)

() Number of DLR units on target line

Page 13: Oncor West Texas Dynamic Line Rating (DLR) Project · Line Ratings Terminology Static Rating – based on prescribed ambient conditions, i.e., full sun mid-day, 104°F, 2 foot per

West Texas DLR Project

Page 14: Oncor West Texas Dynamic Line Rating (DLR) Project · Line Ratings Terminology Static Rating – based on prescribed ambient conditions, i.e., full sun mid-day, 104°F, 2 foot per

West Texas DLR ProjectDLR Application in ERCOT Nodal System

• Ratings polled from Oncor server by ERCOT every 10 secs

• DLR Ratings updated every 10 minutes (remember time constant of conductor)

• Oncor posts DLR rating (if passes quality and availability check)

orAAR rating (default if DLR is not available)

• SCED operates on posted ratings every 5 minutes

Page 15: Oncor West Texas Dynamic Line Rating (DLR) Project · Line Ratings Terminology Static Rating – based on prescribed ambient conditions, i.e., full sun mid-day, 104°F, 2 foot per

West Texas DLR Project

DLR Installation Milestones

• Schedule line outages to install DLR loadcells starting March 18th

• Calibrate DLR ratings completed May 17th

• Post DLR ratings to ERCOTcompleted May 31st