offshoredesignmanual (very important from ongc)

155
Offshore Design Manual http://www.infraline.com – Your Information Gateway to Indian Energy Sector 1 Offshore Design Manual FOREWORD It gives me great pleasure in presenting this manual on the designing aspects considered in the construction and commissioning of offshore facilities. This first time effort by the Offshore Design Section has efficiently covered the various design considerations that are essential in constructing offshore facilities. This design manual provides adequate data and references to carry out Basic Engineering of offshore facilities and may serve as a comprehensive guide to any new incumbent in the Offshore Design Section. The effort put in by the Offshore Design Section in the preparation of this manual is commendable. The Offshore Design Section shall on a regular basis, revise this manual and keep it up-to-date with the designing aspects actually being followed by the Offshore Design Section. (Mr. I. B. Raina) (ED – CES)

Upload: pokiri

Post on 07-May-2017

260 views

Category:

Documents


14 download

TRANSCRIPT

Page 1: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 1

Offshore Design Manual

FOREWORD

It gives me great pleasure in presenting this manual on the designing aspects considered in the construction and commissioning of offshore facilities.

This first time effort by the Offshore Design Section has efficiently covered the various design considerations that are essential in constructing offshore facilities. This design manual provides adequate data and references to carry out Basic Engineering of offshore facilities and may serve as a comprehensive guide to any new incumbent in the Offshore Design Section.

The effort put in by the Offshore Design Section in the preparation of this manual is commendable. The Offshore Design Section shall on a regular basis, revise this manual and keep it up-to-date with the designing aspects actually being followed by the Offshore Design Section.

(Mr. I. B. Raina)

(ED – CES)

Page 2: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 2

PREFACE

The Offshore Design Section is a division that provides in-house engineering to the Offshore Works Section in the design and construction of offshore facilities. It has been a constant endeavour of the Offshore Design Section to design minimum-facility offshore platforms in line with International standards and practices, to help exploit the offshore potential of oil and gas at optimum cost. The Offshore Design Section has realized these efforts by constantly reviewing and revising the Design Philosophy adopted in the design and development of offshore platforms.

This manual provides guidelines for Basic Engineering of offshore platforms and chronicles the various phases of development in the designing aspects, from the initial EIL-developed design criteria followed at the time of inception of the section, to the design criteria currently being adopted by the Offshore Design Section. This manual provides detailed descriptions of the essential design considerations followed by various disciplines of the Offshore Design Section and also covers safety considerations in designing offshore facilities.

This manual when used in conjunction with the Safety Manual, the ISO Manual and the Functional Specifications can provide all necessary inputs to make a functionally complete technical bid package for construction of offshore platforms and pipelines.

Advice and comments from the readers are welcome, and the same shall be taken care of in the future revisions of this document.

(Mr. R. K. Marya)

(Head – Offshore Design Section)

Page 3: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 3

1.0 INTRODUCTION:

This manual contains information on the Basic Engineering activities related to design of offshore platforms. This manual captures in one place all the design aspects considered in the design of offshore platforms. The intention of this manual is: • To provide guidelines for Basic Engineering (i.e. bid package preparation) of offshore

platforms • To provide guidelines on the essential considerations to be borne in mind while

generating design documents for offshore platforms This manual is to be used by the employees of Offshore Design Section, ONGC and other persons so authorized by the Chief Engineering Services. This manual shall be used as a reference document during Basic Engineering of offshore platforms together with the Safety Manual and ISO Manual prepared by the Offshore Design Section. This manual spans the changes that the Design Criteria has undergone from the time of inception of the erstwhile Engineering and Construction Division in 1992 to its evolution as Offshore Design Section in 2001. A brief description of the constituents of a bid package is covered in this manual. This is followed by detailed description of the essential design considerations of individual disciplines, including a description on safety considerations in designing offshore platforms. The codes & standards applicable in the design of offshore facilities have been covered appropriately in the design guidelines of various disciplines.

2.0 HISTORY OF THE OFFSHORE DESIGN SECTION (ODS):

In 1974, with the discovery of the Bombay High field, ONGC entered into a new era of exploration and exploitation of hydrocarbons. It called for creating an infrastructure and facilities for oil and gas field development. The Engineering & Construction (E&C) division was then set up to carryout engineering and construction activities of offshore projects. At the time of its inception, the E&C division primarily handled Project Management, with engineering activities being executed by reputed engineering consultants such as Lummus Crest Engineering, Snam Progetti and Engineers India Limited (EIL). Subsequently, a separate section called the Engineering & Planning (E&P) Division was created under the E&C division for conceptualization of schemes, preparation of Conceptual Study Report (CSR), review of basic engineering during bid package preparation and review during detailed engineering and for undertaking engineering studies. While E&P took care of the above-mentioned project related activities, other aspects of the project such as Basic Engineering, preparation of bid package, Detailed

Page 4: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 4

Engineering, Yard supervision, installation and commissioning were handled by E&C’s consultant, M/s EIL. During the year 1984-85, E&P took up engineering for conversion of Jack-up drilling rig “Sagar Vikas” into an Early Production System (EPS) Sagar Laxmi with back-up from CFP TOTAL. Subsequently, in 1990-91 when there was a spurt of development schemes requiring the establishment of 4 process platforms (SHG, NQP, NLP/NLW & SHW) and 13 well head platforms (L-ABCDE, I-MNTWPQS). M/s. EIL expressed their inability to provide consultancy for all these projects in the required time, owing to the enormity of the task. The E&P division was therefore required to undertake the engineering activities in addition to project management activities. This marked the beginning of E&P’s in-house consultancy service for design and construction of offshore platforms. During the initial stages of transformation of E&P as in-house consultants, the division engaged M/s TRIUNE Pvt. Ltd., New Delhi, as back-up consultants to assist the E&P division in its first engineering consultancy venture - the I-MNTW Project. The basic engineering documents for this project were adopted from the specifications prepared by M/s EIL for similar projects. From the time of its foray into in-house consultancy services, the E&P division has provided in-house engineering consultancy services for numerous project related to new platforms, modification of existing platforms, submarine pipelines and clamp-on projects as independent consultant, without any back-up. In 2001, E & P division for the first time took up the consultancy of a process platform project (MNW) – a single largest component of Mumbai High North Redevelopment Scheme. The MNW process platform project being the first platform project to be engineered by E&P, it was felt necessary to employ back-up consultants having adequate experience in engineering process platforms. M/s Worley, Australia were therefore engaged to assist in some of the critical specialty areas (viz. Common FGC Skid, Gas stripping based De-oxygenation system, Living Quarter & structural study, etc.) and to review the bid package for optimization of cost / schedule of MNW Project, participation in the pre-bid conference, review of techno-commercial bid, etc. In 2002, under the Corporate Rejuvenation Campaign (CRC), the E&P Division was renamed as Offshore Design Section and it continues to provide efficient in-house engineering consultancy.

3.0 EVOLUTION OF ENGINEERING BASIS: The foremost activity in the design of offshore platforms is identifying the quantum of work to be executed and finalizing the facilities to be erected and commissioned. These details are compiled to form a bid package which is then issued to prospective contractors. The bid package is prepared on the basis of the Feasibility Report on the project.

Page 5: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 5

Preparation of the bid package is done following approved ISO procedures (compiled by the Offshore Design Section in the form of an ISO Manual) together with inputs from this Design Manual, approved Safety Manual and various Functional Specifications, as well as suggestions / recommendations received from the Operations Group and recognized Engineering Consultants from time-to-time.

(Note: An extract of the Safety Manual and the ISO Manual is given in clause 5.1 and 6.0 respectively of this document) The bid package includes the Scope of Work of the project, the Design Criteria of various disciplines and the Functional Specifications of various equipment and systems envisaged on the platform. The Scope of Work describes the quantum and quality of work that is to be carried out. The Scope of Work is unique to every project and is the first document that is prepared when a project commences. (This manual does not cover the basis of finalization of scope of work of a project). The Design Criteria, which plays a pivotal role in the design and development of the offshore facilities, specifies the essential considerations in the design, procurement, fabrication, transportation, installation, pre-commissioning and commissioning of offshore platforms. It has been a constant endeavour of the Offshore Design Section to improve the design criteria by ensuring that the philosophy adopted reduces platform complexity and cost. (This manual covers in detail the design criteria adopted by various disciplines of the Offshore Design Section in the design of offshore facilities). The Functional Specifications describe the specific functional requirements of various equipment and systems envisaged under the Scope of Work of the project. (This manual does not include the design details covered in the Functional Specifications of different equipments and systems). The bid package documents, including the design criteria, used to be generated by EIL in the early 80’s and these were very elaborate and prescriptive. It advocated the use of exotic materials of construction and set higher safety limits, perhaps for achieving higher level of reliability. These additional reliability margins, however, considerably increased the cost, the execution time and the platform complexity. Owing to these, the necessity for optimization was increasingly felt. Therefore, in 1990, an effort was made towards optimization of cost and facilities, simplification and standardization of equipment / systems and deletion of supplementary equipment. These efforts resulted in a Phase-Wise Optimization process which has help achieve cost optimization by reducing structural tonnage, reducing size of equipment, deleting supplementary equipment and adopting new technology. The outcome of this

Page 6: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 6

optimization process has been the establishment of Minimum-Facility Offshore Platforms. Details of the Phase-Wise Optimization process has been covered in section 3.1 of this manual and the constituents of Minimum-Facility Offshore Platforms (both manned and unmanned) have been covered in section 3.2 of this manual.

3.1 PHASE WISE OPTIMIZATIONS:

As mentioned in section 3.0 above, the phase-wise optimization process was carried out to achieve cost optimization by reducing structural tonnage, reducing size of equipment, deleting supplementary equipment and adopting new technology. The details of the optimizations carried out (with respect to well-head platforms) are as follows:

• PHASE I:

During Phase I of the optimization process, certain items, which previously formed a part of well platforms, were deleted and the capacity of certain other items were reduced. Details of the same are as follows:

a) Deletion of items:

The following items were deleted:

Chemical Storage Tank and Chemical Injection Pumps U/V Sterilizers Potable Water Tank Salt Water Tank Bunk House Oxygen Scavengers and Bactericide Injection Pump Monorail

b) Reduction in Capacity:

Item Change in capacity

Crude Condensate Drum Sized for 7 days instead of 15 days

Instt Gas Drier Reduction in size

Test Separator Sized for 2500 BOPD instead of 5000 BOPD

Diesel Generator Set Reduced to 37 KW from 55 KW

Emergency Battery Reduced to 3000 AR from 4500 AR

LT Switch Gear Reduced to 100 A from 200 A

Page 7: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 7

• PHASE II:

Phase II of optimization activities began in December 1989 and a report on these activities was submitted in March 1990. This phase of optimization resulted in 250 m2 reduction of platform area and a reduction in structural steel tonnage of approximately 100 t. The total cost saving through this optimization process was approximately Rs. 31.5 million / platform.

The items deleted during this phase include:

Sump Caisson I/U Air Compressor in Platform (which is presently sweet) Space for Future Launcher / Receiver Nitrogen Back – up for instrument Air and Fire Water Pump Start – Up FQS in Gas Lift Instrumentation (flow Totalizer)

• PHASE III:

Phase III of optimization activities began in January 1990 and a report was submitted in May 1990. This resulted in a cost saving of Rs. 28 million / platform. The details of the reduction in capacity of items during phase III are as follows:

Item Change in capacity

Crude Condensate Drum Reduced to 2 m3 from 10 m3

Diesel Storage Tank Capacity reduced to 2 m3 from 10 m3.

Crude Condensate Pump Capacity reduced to 300 l/h

Instrumentation Number of RTU reduced to half

Fire Water Pump Capacity reduced to325 m3/h from 450 m3h.

Gas Detectors (HC & H2S) Number reduced to 13 and 12 from 25 each.

DG Set Capacity reduced to 10 KW from 37 KW.

Emergency Battery & Battery Charger

Capacity reduced to 1500 Ah from 3000Ah.

Gas Detection Battery, Battery Charger & Solar Panel

60% reduced for sweet fields, 30% reduced for sour fields.

Platform Lighting Load reduction in lighting to 7 KW, 8 KW from 17 KW, 18 KW.

LT Switch Gear Rating reduced to 25 A from 100 A.

Fire Wall in WH Area Replaced by steel isolating wall.

Page 8: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 8

Test Separator Capacity changed to 3000 BLPD.

• PHASE IV:

Phase IV of optimization activities were carried out in 1999 and involved the implementation of cost optimization recommended by M/s Worley, Australia in ZA Well Platform Project and MNW Process Platform Project.

a. Implementation of cost optimization recommended by M/s Worley in ZA

Well Platform Project:

Based on the recommendations of M/s Worley the ZA Well Platform design criteria were suitably modified to minimize electrical loads. This included optimization of RTU and Gas Detection Systems. Further, 2-phase test separator with water-cut meter was used in place of 3-phase separator.

b. Implementation of cost optimization recommended by M/s Worley in MNW

Process Platform Project:

As mentioned earlier, the MNW Process Platform Project under Mumbai High North Redevelopment Scheme, is the first process platform for which Offshore Design Section has taken up consultancy. The MNW Process Platform being a first time venture, it was felt necessary to have M/s. Worley, Australia, as back-up consultant to assist in some of the critical specialty areas (viz. Common FGC Skid, Gas stripping based De-oxygenation system, Living Quarter & structural study, etc.) during Detailed Engineering phase of this project. M/s Worley were also engaged to review the bid package of MNW Platform and suggest suitable cost and schedule optimization of the project. M/s Worley also participated in the pre-bid conference and reviewed the techno-commercial bid and has given valuable suggestions to improvise the bid documents. The suggestions have been incorporated in the MNW project. The Offshore Design Section shall also take care of these aspects during the design of future facilities.

• PHASE V:

Phase V of optimization activities began in 2001 and involved the adoption of CRINE (Cost Reduction Initiative for the New Era) Concept by the Offshore Design Section. The adoption of the CRINE Concept was aimed at cost effective development and application of new technology. The CRINE Concept primarily recommends the following:

Use of standard equipment Use Functional Specifications Determine documentation requirement based on criticality Simplify / Clarify contract language avoiding adversarial clauses Rationalize regulations on Certification

Page 9: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 9

Make quality qualifications more credible The Offshore Design Division has introduced the CRINE Concept in the N-11 & N-12 Well Platform Project in Mumbai High North field. The methodology for the implementation of the CRINE Concept in this project, reflected in the technical bid document, was as under:

Adoption of Functional Specification Flexibility in selection of material as per code and service, e.g. NACE piping,

etc. Rationalization of Documentation requirement

The benefits envisaged / derived through the introduction of Functional Specifications are:

Bidders have been given due flexibility to propose industry-proven

conceptual design and equipment for the well platform in line with the Company’s requirements. This would introduce the Company to new designs and layouts that would enable reduction in tonnage and hence in cost.

There has been a considerable reduction in volume of the Bid Package, owing to deletion of descriptive items in the bids.

3.2 DEVELOPMENT OF MINIMUM FACILITY OFFSHORE PLATFORMS

The continuous refinement of the Design Philosophy has helped realize minimum facility offshore platforms. A list of these typical facilities (on manned and unmanned platforms) is indicated below. The facilities mentioned are indicative only. The same may vary as per the specific requirements of the project.

3.2.1 Typical Facilities on Manned Platforms: Manned platforms may broadly be classified as Process Platforms and Water Injection Platforms. The manned platforms in general have the following facilities:

Six / Eight legged jacket complete with piles, Cathodic protection and monitoring system, barge bumpers, walk-ways, boat landing etc.

Two level deck structure (viz. cellar& main deck) including helideck and boat landing

facilities with walkways, stairways, ladders, railings etc.

Launchers/Receivers

Marine growth prevention system in jacket members and conductors up to an elevation of 30.00 m for still water level

Page 10: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 10

Complete system for sampling and on-line monitoring of Chlorination, Filtration, De-oxygenation, Biological treatment and Corrosion etc.

Deck drain system including a closed hydrocarbon drain system

Living accommodation to cater for the living, messing, recreational and other needs of

the personnel manning the platform offshore.

Utility Water System, Potable Water System, Sewage Treatment System

Fire/Gas Detection and Alarm system complete with detectors for hydrocarbon gas and hydrogen, Ultra Violet detectors, smoke detectors and thermal detectors

Fire Suppression System consisting of diesel engine driven fire water pump(s), fire

water distribution system and spray network, FM-200 extinguishing system, firewater and foam hose reels, portable CO2 extinguishers, dry chemical fire fighting systems etc.

Fuel Gas Conditioning System comprising of gas scrubber, filter, pre-heater, super heater etc.

Start-up Air System consisting of starting air compressor, air receivers etc

Material handling facilities comprising pedestal mounted diesel operated deck cranes,

electrically operated monorail hoists, pneumatically operated portable hoists, manually operated trolley mounted chain pulley blocks, hook mounted chain pulley blocks, drum racks, handling and storage space etc.

Switchgear Building Module comprising of Turbine Generator sets, transformers,

Switch gear, etc.

HVAC or AHU equipment

Helideck, suitable for landing and take-off of Russian MI- 8 Sikorsky S-61 and similar helicopters, to be installed on top of the LQ module, along with refueling facility

Radio room

Electrical Power Distribution System comprising H.T. & L.T. Switchgear,

Transformers and Distribution Boards, Control Stations, Junction boxes etc

Un-interrupted Power Supply System, Battery Banks and Battery Chargers

Multi-channel Radio System, Paging and Intercommunication System and Private Automatic-Exchange Telephone System

Closed circuit television (CCTV) System

Electrical Normal Lighting System and Emergency Lighting System

Navigation Aids and Aviation Marker Lighting Systems.

Page 11: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 11

Cathodic Protection with monitoring system

Grounding System

Heat tracing system

One Diesel Engine-driven Generator with complete control system

All Instrumentation and Safety System including Control Panels, Shut-down Panels,

Fire/Gas Panel, ESD/FSD System, RTU System, DCS etc

All materials related to interconnecting/piping, wiring, tubing, pipe supports, riser supports, pipeline supports, cable/trays supports etc

Life Support and Safety Systems comprising Survival Crafts, Life Rafts, Life Ring

Buoys, Life Preservers, Scramble nets and personnel baskets, First-Aid Kit etc.

Safety showers and Eye washers in chemical storage and handling area

All Process, Utility, Service and Miscellaneous piping systems comprising pipes, specialty items and fittings of different class, materials, specifications etc.

Fire Walls

3.2.1.1 Typical Facilities on Process Platforms:

In addition to the facilities listed in clause 3.2.1, the typical facilities provided on a Process platform are as follows:

Production Manifold

High Pressure Separators, Low Pressure Separators & Surge Tanks

Pumping facilities for transporting partially or fully stabilized oil through trunk

pipeline or through SBM tanker to shore

PGC module comprising of gas turbine driven process gas compressor with associated system

Gas dehydration system using T.E.G

Very low pressure gas venting system

HP and LP flare gas system

Hydrocarbon sump tank, sump pumps

Instrument and Utility Air System

Page 12: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 12

Produced Water Conditioning System

Power generation using Gas Turbine or Emergency generator using Diesel

Diesel Fuel System complete with diesel storage facilities, diesel filter coalesces, centrifuge separator, diesel transfer pumps etc.

3.2.1.2 Typical Facilities on Water Injection Platforms:

In addition to the facilities listed in clause 3.2.1, the typical facilities provided on a Water Injection platform are as follows:

Sea Water Chlorination System comprising electrolyte type Sodium Hypo-chlorite generators complete with filters, electrolytic cells, hydrogen removal system, air blowers, thyristor controlled power unit etc.

Skid mounted Fine Filters Package

Skid mounted De-oxygenation Tower Package comprising vacuum de-oxygenation

tower in two stage packed-bed design complete with electric motor driven vacuum pumps, ejectors etc.

Skid mounted Chemical Injection Package complete with storage and dosing system

for the chemicals

Skid mounted Solution Tank and mixers and pneumatically operated chemicals unloading pumps complete with drive motors, coagulant solution tanks, polyelectrolyte solution tank, mixers etc.

Skid mounted electric motor driven sea water lift, Booster Pumps, Main Injection

Pumps (only at Water injection facility)

3.2.2 Typical Facilities on Unmanned Platforms:

The typical facilities on unmanned offshore platforms are as follows:

Jacket (sub-structure) complete with piles, cathodic protection without monitoring system, well conductors, boat landing, barge bumpers, walkways, riser protector, pre-installed risers etc.

Super-structure comprising of main (drilling) deck, spider deck cellar deck, and

helideck with walkways, stairways, ladders, railings, rub strips etc.

Building module housing the switchgear, battery bank, telemetry, shelter room etc

Helideck suitable for use by Bell 212, Bell 412, Westland WG 30, Sikorsky 576A (Type-I and Type-II), Dauphin 2 SA 365N type helicopters etc

Production manifold with associated piping, instrumentation with two headers -

Production header and Test header

Page 13: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 13

Well testing facilities consisting of Three / Two-Phase Test Separator or multi-phase meter complete with shutdown panel, safety controls system etc.

Pipe Separator to supply gas (from prod. header) to OCI Storage Vessel and IUG

system.

Instrument Gas System utilizing the lift gas and complete with pressure reduction system, gas filter-separator, strap heater, instrument gas receiver and headers.

Utility Gas System (for gas driven OCI transfer pump and blow down of crude

condensate drum)

Chemical Injection System to inject Oil Corrosion Inhibitor in production manifold (prod. header and test header) and departing well fluid pipeline.

Crude / Condensate Storage and Transfer System based upon blow case design

Open Deck Drain (ODD) System and Closed Hydrocarbon Drain (CHD) System.

Low Pressure Gas Venting / Relief System comprising vent header, glycol seal

pot, flame arrester and vent boom.

Material Handling System including a pedestal mounted hydraulic deck crane (15 T), C. P. Blocks, hoists, monorails etc.

Fire Suppression System including firewater spray network, hose reels, portable

CO2 / dry chemical extinguishers etc.

Fire Fighting System comprising of Dry Chemical Powder (DCP) skid, hose reels etc.

Solar panels with back-up battery bank for catering to the continuous electrical

loads during normal unmanned operation.

Navigational Aids

Launchers / Receivers

Injection Water System

Lift Gas System

Safety devices for hydrocarbon service containing H2S e.g. first aid equipment, breathing apparatus etc.

Life rafts, life jackets, life rings / buoys and other life saving appliances and

portable medical units for eyewash.

Well / Fire Shutdown Panel

Page 14: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 14

Instrumentation and Shut-down Systems including ESD/FSD system, inter-connecting tubing/ cables etc.

Telemetry and Tele-communication System.

Mechanical Marine Growth Preventor (MGP) on jacket

Cathodic Protection System.

Gas Detection System including strobe light, fixed type HC detectors etc.

Portable H2S & HC gas detectors

3.3 The above deliberations show that from the EIL developed design criteria to the

Functional Specifications based Design Criteria, the Offshore Design Section has continuously strived to improve and standardize the design aspects of offshore facilities. The design criteria currently being used for manned and unmanned platforms broadly outlines the basic requirements for design, engineering, material selection, fabrication and testing of the facilities. This Design Criteria adequately covers various aspects of Equipment Layout, Personnel Safety and Safety of facility, pollution prevention, protection from corrosive environment, preventive maintenance, and platform design life to ensure a safe, pollution-free and reliable working condition. The design criteria / design document is generated by following certain established design guidelines and bearing in mind certain essential design considerations.

3.4 The Design Considerations to be followed while generating design documents are

elaborated in section 4.0 of this manual. 3.5 The Design Guidelines followed by the different disciplines of the Offshore Design

Section for the generation of design documents are detailed in section 5.0 of this manual. 4.0 DESIGN CONSIDERATIONS:

Design considerations are the parameters, which provide necessary guidelines for generating the design criteria so as to ensure a minimum facility platform that is cost effective, technically sound and safe for operation. These considerations may be categorized as General Design Considerations and Specific Design Considerations. These design consideration are listed below.

4.1 General Design Considerations: The general design considerations borne in mind while designing facilities for manned as well as unmanned offshore platforms are as follows:

Planning the facilities based on optimum requirements and arranging production

equipment on offshore structures for safe and efficient operation

Page 15: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 15

Provision of adequate space around equipment, headers etc. to permit easy access for

maintenance

Provision of crane and lifting points for safe handling of equipment and material

Proper lighting and ventilation of work areas with adequate provisions for communication between personnel

Design of all facilities in accordance with the latest standards and in compliance with

current government regulations

Proper routing of piping to minimize number of bends, corrosion and erosion and to provide easy access to functional parts of each piece of equipment

Safety Systems to ensure safety of personnel, environment & facility

Minimizing Capital costs, Operational costs and Maintenance cost by adopting a

design that is cost effective and technically efficient.

4.2 Specific Design Considerations:

The specific design considerations borne in mind while designing facilities for manned as well as unmanned offshore platforms are as follows:

Personnel, Environment & Facility Safety systems on Offshore Platforms:

The safety of operating personnel is the primary consideration in designing production facilities. Requirement for means of escape, personnel landings, guards, rails, life saving appliances etc. as specified in international codes and standards are followed. Design Criteria for Provision of Safety Systems (excluding Personnel Protective Equipments) on an offshore production platform is governed by standard API-RP-14C – Recommended Practice for Analysis, Design, Installation, and Testing of Basic Surface Safety Systems for Offshore Production Platforms. The Purpose of production platform safety system is to protect Personnel, the Environment and the Facilities from threats to safety caused by the production process. Details of the various safety considerations essential in the design of offshore platforms are given in clause 5.1 of this document. Also refer Safety Manual for further information on safety considerations in design of offshore platforms.

Utilities Assessment

Utilities on offshore structures may include potable water, utility water, seawater, electricity, gas, utility air, sewage treatment, garbage disposal, communication facilities etc. In planning / designing the utility systems, consideration is given to the number and type of wells, oil and gas processing facilities, remoteness from shore,

Page 16: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 16

anticipated production volumes, number of people to be accommodated on the structure, type of fire fighting system, type of control system and electric power source etc.

Flare and Emergency Relief Systems

Flare and emergency relief systems associated with process equipment are designed and located considering the amount of combustibles to be relieved, prevailing winds, location of other equipment, including rigs, personnel quarters, fresh air intake systems, helicopter approaches and other factor affecting the safe normal flaring or emergency relieving of the process fluids and gases.

Pollution Prevention

Designing of offshore production facilities include methods for containment and proper disposal of any type of contaminants which may include liquids or solids containing liquid hydrocarbons, relatively high concentrations of caustic or acidic chemicals, raw sewage, trash and inedible garbage etc.

Corrosion, Erosion and Preventive Maintenance

Preventive maintenance and the control of corrosion and erosion are an integral part of failure prevention, pollution control and safety. In addition, the conditions viz. space limitations, the salt air environment, and other special requirements are considered for offshore platform design and operation.

Communication

The Communication being vital to remotely located offshore sites there exists a scope for communication equipments in Process Platform technical bid specifications. To facilitate communication with base office, vessels, helicopter process platforms are provided with:

• Maritime Mobile Band communication equipment. • Aero Mobile Band communication equipment.

The Equipment for these facilities is installed in Display room / Radio room and are specified to be capable of remote operation from a distance of approximately 300 meters. Antennae of VHF Aero and VHF marine communication equipment are installed on the top deck of the living quarters.

Integrity Of Platform For Complete Design Life

The Design Criteria takes into account that the integrity of the platform is maintained for the complete design life of 25 years

Future Provisions

Page 17: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 17

Design considerations have to take into account the scope for future provisions like future Risers and Deck extensions.

Equipment Layout

Development of Equipment Layout primarily considers the following aspects:

• Safety • Accessibility • Operational convenience • Maintenance • Area optimization • Technical & Engineering requirements • Material handling from boat and also within the platform

Material of Construction

The material of construction of any item / instrument on an offshore platform is chosen considering its application. In general, the material is so chosen as to protect the item / instrument from the corrosive process conditions and the erosive environmental conditions that it is exposed to on the offshore platform. The materials of construction used for different applications on offshore platforms are as follows:

• Carbon steel (NACE & NON-NACE): For structural, pipelines and pipelines (Sour & Non- Sour services

• Stainless steel: Piping • Cupronickel: Fire water lines • Monel Piping and pipeline splash zone • Duplex and Super Duplex: Sour service piping (now replaced by CS-NACE)

Details regarding the selection of materials of construction for various offshore applications are covered in the design guidelines for different disciplines given under clause 5.0 of this document.

5.0 DESIGN GUIDELINES:

The design guidelines followed by various disciplines in the design of offshore platforms is detailed below. This includes design guidelines for: • Process • Instrumentation • Piping • Mechanical • Structural • Electrical and • Pipeline

Page 18: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 18

Safety of personnel and of the facility is one of the major concerns during the design of offshore platforms. These general safety considerations have also been described below.

5.1 GENERAL SAFETY:

As mentioned above, safety of personnel and of the facility is one of the major concerns during the design of offshore platforms. In an effort to compile at one place, all the safety aspects considered during the design of offshore platforms a Safety Manual” has been prepared by the Offshore Design Section. The Safety Manual is intended to serve as a comprehensive document on offshore safety considerations and is to be referred to during design of offshore platforms for ensuring platform and personnel safety. Few of the aspects covered in the Safety Manual are given below. The general safety features on offshore platforms include: ♦ Structural Protection:

The structural design ensures that all major load carrying structural elements such as supports, foundations, etc., which can be damaged by fire, are suitably protected. The structural design is carried out in such a manner that the effects of accidental loads (such as fire and explosion) and impact loads (such as collision loads or dropped objects) are reduced. The primary structure is designed to maintain its load bearing capacity during any fire for the period required for safe evacuation.

♦ Judicial layout of topside and field complex: The topside and field complex layout of offshore platforms is planned so that all areas are arranged in such a way that the consequences of fire and explosion are minimized. Hazardous equipment is segregated from the frequently manned areas on the platform. Generally the facilities on the platform are located in such a way that the higher risk areas are leeward to the prevailing wind direction. This provides maximum ventilation and also minimizes potential explosion overpressure. Adequate clearance and accessibility is provided around major items of equipment for carrying out maintenance.

♦ Pipeline and riser design:

Location of pipelines is designed so as to minimize the potential for dropped objects to impact the pipelines.

♦ Minimization of potential hydrocarbon release sources: The design of the production facilities minimizes the number of sources for hydrocarbon release as low as reasonably practicable. Minimization of potential hydrocarbon release sources can be achieved by: segregating inventories, isolating

Page 19: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 19

and blowing down hydrocarbon inventories to minimize the quantity that may be released and adequate isolation / venting / drainage to enable safe maintenance.

♦ Control of Ignition Sources:

The facility is designed so as to minimize the likelihood of ignition of released hydrocarbons as far as is reasonably practicable. This is achieved through hazardous area classification and developing equipment layouts in accordance with API RP 500, and using equipment suitable to the classified area. Providing maximum practical separation between flammable materials and known ignition sources also helps control fire.

♦ Identification of Fire Zones:

Fire zones are identified and designated in accordance with NFPA 72. Each fire zone is provided with fire detection and protection systems appropriate to the hazards present within the zone. These fire zones are generally defined by natural boundaries such as firewalls, solid decks or the extremities of the platform.

♦ Fire and Gas Detection Systems:

The Fire and Gas Detection system detects unwanted accumulation of hydrocarbon, H2S, H2 or fire and initiates appropriate control action such as initiation of active fire protection, initiation of shutdowns and / or initiation of alarms.

♦ Emergency Control Systems:

Emergency Control Systems are the safety critical systems that are required to operate and remain operable on detection of an emergency or an impending emergency. Such emergency control systems are designed to be fail-safe and have sufficient redundancy to prevent loss of the system. The Emergency Control Systems include: Emergency Shutdown Systems, Hydrocarbon Inventory Isolation, Hydrocarbon Inventory Blowdown, Pipeline and Riser Inventory Isolation, Navigation Aids and Emergency Lighting.

♦ Fire Control and Mitigation:

Fire Control and Mitigation is achieved by means of passive as well as active fire protection systems. Passive fire protection includes:

• Provision of fire divisions, walls and boundaries – penetrations through these are designed and constructed n order to maintain the fire rating of the division.

• Fire protection of vessels, equipment, shutdown valves, supports for vessels and of structural steel.

Active fire protection systems are used to contain / reduce the effects of smoke and radiation and extinguish fires as appropriate. Active fire protection systems include:

Page 20: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 20

• Water Deluge to cool areas and equipment that may be affected by radiated heat from a fire and prevent its escalation.

• Portable Water Monitors to support the fixed fire protection systems to cool process areas and equipment that may be affected by radiated heat from a fire.

• Foam to extinguish pool fires

♦ Explosion Control and Mitigation: The over pressure and subsequent consequences of a hydrocarbon gas explosion are controlled by a combination of maximized natural ventilation, optimized module aspect ratio and optimized equipment layout. Wherever possible, equipment containing hydrocarbon gas or condensate is located in naturally ventilated areas to aid dispersion of unburnt gases.

♦ Alarms and Communication Systems:

Alarms – both audio and visual – are provided on offshore platforms to intimate personnel about the existence of an emergency. An audible General Platform Alarm (GPA) is provided for annunciation in case of gas or confirmed fire detection. An audible Abandon Platform Alarm (APA) for annunciation when personnel are required to abandon the platform. In areas of high background noise, greater than 85 dBA, flashing beacons are used to supplement GPA and APA. Beacons are generally installed on a two loop system such that if one of the loops fail or is damaged, the beacons shall continue to function.

♦ Escape and Evacuation:

Escape and evacuation routes are provided to ensure the safe evacuation of personnel from the platform. The escape routes are designed in line with the NFPA requirements. At least two separate egress routes are provided from each area. The primary escape routes are generally located around the perimeter of each working area. All escape routes are clearly marked so that the personnel can readily follow them in an emergency. Escape ladders, scramble nets, life rafts, life jackets, lifebuoys, personnel baskets, and other personnel survival equipment such as smoke hoods, fireproof gloves, flashlights, etc. are provided to aid the personnel during evacuation.

♦ Protection against Occupational Hazards:

Protection against Occupational Hazards includes the following: • Fire fighting and rescue equipment • Breathing apparatus sets • Stretchers • Eye wash and safety showers • First aid kit • Limitation of noise and vibration • Protection against hot surface in accordance to API RP 14C

Page 21: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 21

5.2 PROCESS: 5.2.1 Unmanned Platforms:

In the Mumbai Region (MR), field development is based on mostly platform-completed wells though, very limited number of sub-sea wells have also been drilled and completed. These well platforms are normally ’unmanned’ and operators’ intervention is required normally once in a week or in a fortnight, for carrying out well testing and maintenance/checking of facilities i.e. utilities, safety system, material handling etc. Drilling & completion of wells and work-over operations of platform-based wells are carried out using mobile jack-up rigs as water depth is moderate. In general, unmanned well platform facilities are supported on 4 legged sub structures and have 6, 9 or 12 slots for drilling of wells, though monopod/tripod type structure & 16 slots platform have also been installed. The type of platform is planned depending on the suitability to support minimum facilities requirements. Generally, well testing, water injection & gas lift facilities are provided on these platforms. However, no processing facilities are provided on these platforms and oil/gas produced after manifolding is transported to process platform. Other facilities include utility/instrument air/gas system, fire & gas detection system with automatic shut down facilities, fire fighting, material handling, RTU etc. Though these platforms are unmanned, shelter room is also installed on these unmanned platforms for night stay of operators in case of any operational emergency. The well fluid pipelines are sized for a pressure range 300-500 psig (21-35 kg/cm²g) at well platform end. The arrival pressure at process platform end is considered to be 150 (10.5 kg/cm²g) psig or above. The well head lift gas injection pressure varies in the range of 1000–1150 psig (70-80 kg/cm²g) and water injection pressure as 1350-1500 psig (95-105.5 kg/cm²g). Accordingly, the sub-sea pipelines for lift gas and water injection are sized. All the wells are provided with Surface Safety valves (SSV) and Sub-Surface Safety Valves (SSSV) for automatic closing of wells. Shut down valves have also been installed on well fluid and gas lift pipelines for isolating the platform in case of abnormalities. Provision for automatic shut down of platforms has also been provided in case of any abnormality in operating conditions or if there are any fire or safety hazards.

5.2.2 Process Platforms:

The process platforms have facilities for processing of well fluid gathered from unmanned platforms. Well fluid is processed for separation of oil, gas and water. Partially stabilized oil is pumped to shore through trunk pipelines and fully stabilized oil is transported through tankers. Separated gas is compressed, dehydrated and transported to shore after utilizing for gas lift & other internal use such as fuel gas. The produced water after treatment is discharged into the sea after meeting mandatory discharge criteria. Important characteristics of Mumbai High oil are as follows:

API gravity - 38.40o Sp. Gravity - 0.833 Pour Point - 27oC

Page 22: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 22

Wax Content - 14 – 15% by wt. The specifications of stock tank oil for pumping to refinery (Custody Transfer) are:

Salt content – 22.8 mg/lit (8 P.T.B) Max. RVP at 100oF – 9 PSIA BS and W – 1.0% (Max.)

The process platforms have central control rooms, which are manned round the clock for monitoring process & safety parameters. Any abnormalities in platform operation if any, are noticed and alarmed immediately and remedial measures are taken, automatically, and if required, with manual intervention for safety of the platform and to save men & material. Radio & other communication between Helicopter and marine facilities i.e. MSV/OSV can be requisitioned as and when required and also in case of any emergency. The process platforms have living quarters having lodging & boarding facilities for operating personnel. The operating personnel operate on 14 days on/off pattern having shift of 12 hours duration for operation / maintenance of the platform. The process platform decks are generally supported on 6 or 8 legged sub structures with facilities for processing of well fluid i.e. oil, water & gas separation, gas compression, gas dehydration, oil pumping, produced water disposal, gas flaring etc. In a process complex, all the above facilities may not be installed on a single platform but on a number of platforms, which are bridge connected. This is because of limitation in size of the platform and also for the fact that the development of field takes place in stages and facilities are added as and when need arise. The processing scheme in general consist of gathering of well fluid from number of remotely located unmanned platforms which is manifolded and then heated wherever required, to the desired temperature in well fluid heaters before it is subjected for stage separation. The oil, gas and water are separated in 2 stages under “pressurized mode” of operation and in 3 stages under “stabilized mode” of operation of the platform. Under “pressurized mode” of operation, the separated and partially stabilized oil is pumped by Main Oil Line (MOL) pumps, through trunk pipeline, to shore terminal for further separation / processing of oil before sending it to refinery. The separated gas from both the stages is compressed in gas turbine driven compressors and then dehydrated by using suitable method to reduce the water content of gas to 7 lbs/5lbs per MMSCF. The dehydrated gas is then sent to shore by trunk pipeline after meeting gas lift requirement and other platform requirements like fuel gas etc. Under “stabilized mode” of operation, oil separation is carried out in 3 stages and the stabilized oil is pumped by crude transfer pumps to SBM for tanker loading or to other process platform for further transportation to shore through trunk pipeline. The 1st stage separator gas is compressed and dehydrated and low-pressure gas is flared. With the passage of time, reservoir pressure had declined, Reservoir Gas Oil Ratio (GOR) of well fluid decreased and water oil ratio has increased, which has resulted in lower flowing Tubing Head Pressure (THP). For maintaining / enhancing the production, the operating pressure of 1st Separator has been reduced to reduce the backpressure on well. A pipeline network has been evolved for inter platform transportation of 1st stage separator gas for compressing the excess gas, in case gas production of a platform complex exceeds gas compression capacity or due to non-availability of compressor

Page 23: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 23

because of shutdown, etc. This provides flexibility in gas compressor operations and also reduces the gas flaring from the field. Excess gas, which cannot be compressed or internally used for platform operations, is disposed off by flaring and cold venting in case of very low-pressure gas. Two types of flare headers i.e. high pressure and low-pressure flare headers are installed to collect the hydrocarbon gases and burnt-off in bridge connected or sub-sea pipe flares. Vent headers are also installed to collect very low-pressure gases for cold venting at safe locations. The produced water from different separators and vessels etc. are collected and treated in produced water conditioners to reduce the oil content in treated water to 48 mgm/lit. or 25 mgm/lit. before water is disposed off into the sea. TPI CPI Units were installed on the earlier platforms as produced water conditioners. Later on, Dissolved Gas Flotation/Induced Gas Floatation (DGF/IGF) Units were also installed beside CPI/TPI Units to reduce the oil content in treated water to 25 mgm/lit. Hydro-cyclone type produced water conditioning system was installed at NA/BHN platform complex by replacing old TPI units for treatment of produce water. The treated water is then disposed off into the sea through sump caisson or over board. The platforms have been provided with 2 types of deck drain system for collection of liquid for disposal. Closed drain system collects liquids from various vessels, piping, equipments and open deck drains system for taking care of rainwater, spillage and vessel drains etc. The open deck drain system has been further modified to collect rainwater and liquid hydrocarbons separately. The utilities and other facilities installed consist of gas turbine driven power generation system, emergency generators, utilities and instrumentation air system, gas and fire detection system, fire suppression system, waste heat recovery and hot oil system, water makers for making potable water, chlorinators, chemical injection system, central control room, work shop, switch gear room, HVAC system etc. Living quarters are also provided on the process platforms with boarding and lodging facilities for persons who operate and maintain process platforms and connected well platforms The Mumbai High oil is sweet oil i.e. no H2S content. However, there is possibility that due to water injection in the formation, it may turn sour in future. The well platforms, process platforms and well fluid pipelines etc. designed earlier, were based upon sweet oil, however, facilitates being designed now, from Infill Platforms onwards, are based on 230 ppm of H2S in well fluid. As such in a process complex like SH older platform SHP/SHQ, design was based on sweet oil where as design of new platform like SHG, which is bridge-connected, is based on 230 ppm in oil. Sub-sea pipelines were laid connecting well platforms with process platforms for transportation of well fluid from well platform to process platform and for supplying injection water and lift gas from WI process platforms and process platforms to well platform for carrying out Water Injection and gas lift respectively. The pipelines are provided with pig launchers and receivers for pigging the pipelines. These pipelines have been designed for maximum pressure to which it may be subjected i.e. Well fluid line to well shut in pressure and gas lift and W.I. pipelines for maximum pressure from the source. The pipelines are provided with anti-corrosion coating for protection against external corrosion and cement concrete coating for stability purpose. Most of the pipelines are not buried. For the protection against internal corrosion, OCI/GCI chemicals are injected into the pipelines. To avoid congealing of oil in the pipelines, pour

Page 24: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 24

point depressor is also injected. Pipelines connecting different process platforms are laid for transportation of stabilized oil from one platform to another for further transportation to shore. Low-pressure gas lines are also installed for transporting L.P. gas from one platform to another, for gas compression and dehydration if gas production exceeds gas compression capacity at a particular platform.

5.2.3 Water Injection Platforms:

Water Injection Process Platforms are also manned platforms where seawater is processed to make it suitable for the purpose of injecting into the reservoir. The treated seawater is pumped at high pressure for injecting into the reservoir through number of injectors wells. The other facilities installed on manned platforms are power generation, utility instrument air system, control room, fire and gas detection system, fire fighting facilities, material handling facilities, living quarters etc. The processing scheme consists of drawing the raw sea water from a depth of about 30 meters by sea water lift pumps. The raw water is then filtered in coarse filters where 98% of particles greater than 80-micron size are removed. The water is then subjected to 2nd stage filtration called ‘Fine Filters’ where suspended solids of size greater than 2-micron size are removed. The fine filters are vertical, pressure type dual media (Anthracite and Garnet), down-flow filters. Filter aids like polyelectrolyte and coagulants are added upstream of fine filters, which help in removing suspended particles from raw seawater. The fine filters require back washing every 2-3 days for maintaining the proper functioning. The filtered water is then fed to the De-Oxygenation (DO) tower to remove dissolved oxygen. The D.O. tower is 2 stage packed column having polypropylene pall ring packing and operating under vacuum. The vacuum is maintained by Vacuum pump (water ring type) in 1st stage and atmospheric air motivated ejector in 2nd stage. De-foamers are added in the water, up-stream of D.O. tower, to reduce foaming tendency. The D.O. tower is designed to achieve residual oxygen content in the de-oxygenated water to maximum 20 ppb. Oxygen scavenger is added in D.O. tower in case of poor performance of D.O. tower to achieve desired level of oxygen in the water. The de-oxygenated water pressure from D.O. tower is raised by booster and main injection pumps to the injection pressure. Chemicals like bactericides, scale inhibitor, corrosion inhibitor etc. are added, up stream of main injection pumps, before treated water is pumped by Main Injection pumps to various well platforms for water injection. All the water injection platforms in Bombay High are bridge connected to some process platforms. Attempts are made to make them hydrocarbon free and hence living quarters of a process complex are normally installed there. Power and utilities for WI Platforms and process platforms have been integrated for optimizing the design. The other major facilities installed on WI platforms are water makers, chlorinator, utility & instrument air compressors, fire water pump and diesel generators etc. for the operation at the platforms

Page 25: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 25

5.3 INSTRUMENTATION:

The purpose of the instrumentation on an offshore platform is to furnish the required information and data for monitoring and controlling the process and other systems and to obtain the desired information at the local control centers and Remote Telemetry interface Unit (RTU). The instrumentation design criteria broadly covers the minimum requirements of instrumentation on a platform. It also covers the design and engineering requirements of the control system for the platform. The philosophies applied in the design of platform Instrumentation and related control systems are enumerated in below.

5.3.1 INSTRUMENT PHILOSOPHY:

5.3.1.1 Field Instruments:

All field instruments connected with well monitoring and control, and all facilities that are not to be operated from a central control room, are pneumatic except those that are connected to RTU, which are electronic, SMART type. All instruments connected to control room and remote unit control panels of related utility systems are electronic. For remote control application, remote telemetry, telecontrol and data gathering, electronic instruments are used. All final actuation / control device, controlled from Central Control Room (CCR) are in general be pneumatic Control Valve.

Instrument ranges are selected such that the normal operating point is between 35% and 75% of the instrument total range.

Hand-held Intrinsically Safe calibration / configuration units are provided the platforms to enable online diagnostics, configuration or calibration of electronic instruments from any point in the loop.

5.3.1.2 Pneumatic Field Instruments:

The instrument air supply is designed to conform to ISA S7.3 “Quality Standard For Instrument Air”. For pneumatic instruments, dry instrument gas / air supply used is generally as follows:

5.5 Kg/cm2 (min.) 7.5 Kg/cm2 (nor.) 10.5 Kg/cm2 (max.)

For pneumatic analog control applications, the actuating signal range is in general 0.2 to 1 Kg/cm2. For pneumatic on-off applications, the actuating signal is in general 0 or 6.5 Kg/cm2.

Page 26: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 26

5.3.1.3 Electronic Field Instruments:

All electronic transmitters used are 24 V DC loop-powered type with 4 –20 mA Smart analog signal. Electronic Transmitters in general have integral LCD display. Where this is not possible, a separate local loop indicator is provided.

5.3.1.4 Control Room Instrumentation:

All signals to and from the Central Control Room are electronic. The standard analog signal is 4-20 mA using 2-wire system.

Instruments located on control panels and central control room (CCR) are microprocessor based.

On platforms with processing facilities, a Distributed Control System (DCS) is provided for monitoring and controlling the process, and for generating alarms in case of process upsets.

5.3.1.5 Safety Instrumentation System:

The new platforms are generally provided with the following safety systems: ♦ Emergency Shut Down (ESD) System: The ESD system is pneumatic and it initiates

process shutdown in case of abnormal process condition. ♦ Fire & Gas System: The F&G system initiates Fire Shut Down (FSD) upon detection

of hydrocarbon and/or H2S accumulation or fire. ♦ Manual ESD & FSD Stations: The ESD & FSD stations are provided at all strategic

locations on the platform for manual initiation of ESD and FSD.

All shutdown and alarm switches are “Fail Safe”. Shutdown is actuated by independent tripping devices with independent tapping points.

5.3.2 INSTRUMENT POWER SYSTEM PHILOSOPHY: 5.3.2.1 Pneumatic Supply:

For pneumatic instruments, dry instrument gas / air supply used is as follows:

5.5 Kg/cm2 (min.) 7.5 Kg/cm2 (nor.) 10.5 Kg/cm2 (max.)

5.3.2.2 Electric Power Supply:

Power supplies for all transmitters, controllers, signal converters, electric system and components in shutdown system are supplied from uninterruptible power supplies.

Power distribution to each consumer is through proper switch and fuse.

Page 27: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 27

In general, the following Power Supplies are used for instrumentation and Control:

i. For Process Platforms: 110V AC + 5%, 50HZ + 1% (UPS) for all instruments control. However, all components / instruments / system are made suitable for 110 V + 10% AC, 50 Hz + 3%

ii. For Process & Well Platforms: 24V DC + 5% Battery Negative earthed for

Platform interlock system, solenoid valves, Fire and Gas system and status lamp.

5.3.2.3 Instrument Earthing System Philosophy:

Three separate earthing systems are provided:

• Electrical Safety Earth – Bonded to the site structure and utilized for

electrical safety of metal enclosures and chassis on all instruments and electrical components.

• Instrument Clean Earth – Insulated from the site structure and other metal work, utilized for instrument cable screens and bonded to the main electrical earthing system at a single point.

• Intrinsically Safe Earth – Insulated from the site structure and other metal work, utilized for termination of IS zener barrier earth connections, and bonded to the main electrical earthing system at a single point.

5.3.3 EQUIPMENT PROTECTION PHILOSOPHY:

5.3.3.1 Environmental Protection:

All instruments / equipment and installation material are selected to be suitable for the overall climatic conditions, the position within the installation and the local environment, with particular attention to site ambient conditions. The conditions include exposure to Hydrocarbons, H2S (in case the process fluid is sour), moist salt laden atmosphere, sea spray, sunlight, monsoon rainfall, temperature, humidity, wind, fungal growth, vibration and shock, EMI and RFI. All equipment is designed to withstand these conditions during shipment, storage and installation prior to commissioning. Instrumentation is designed to withstand not only the quoted environmental conditions, but also the periodic testing of the Deluge or Fire Hose System. As all of the offshore sites are subject to seismic activity, all instrument / electrical frames, panel and racks are securely fixed in position.

In view of the highly corrosive ambient conditions, all internal and external parts which are not inherently corrosion resistant by choice of material are prepared and finished by plating or paint finish in accordance with the General Specification for protective coating, which forms a part of the bid document. Seals and purges are used as necessary, to ensure reliable instrument performance.

All field instruments are provided with necessary weathering and anti-corrosion protection. All field instruments are provided with plastic bags (min. 5 mm thick) to protect them during handling, installation and commissioning. The bags are kept in place at all times except during work on the devices. Drying agent (desiccant) with

Page 28: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 28

humidity indicator is put inside the bag and is replaced when color of the indicator changes from blue to pink Additional protection by other means such as canvas or leather blankets are provided to prevent damage caused by welding. Labels and tags that may be exposed to paint spray, are temporarily masked with a transparent material during construction activities, which are later removed at the time of hand over of the work. Plastic plugs are fitted to all instrument tubing and air, process and cable entry ports until final connections are made.

5.3.3.2 Ingress Protection:

All field instruments are designed to have ingress protection to NEMA 4X or IP 66. All instruments inside pressurized equipment / control rooms are designed to have ingress protection to IP 42 minimum.

5.3.3.3 Hermetic Sealing:

All relays and switches are hermetically sealed, and those utilized in 24 V DC control logic circuits have gold plated contacts rated 0.5 Amp at 24 V DC. Those interfacing with field equipment are rated 2 Amp 24 V DC. All switch contacts are SPDT minimum.

5.3.3.4 Hazardous Area Instrumentation: Hazardous areas are classified in accordance with API 500 and equipment is specified accordingly. All instruments mounted outside of normally pressurized control / equipment rooms require certification by bodies such as FM / UL / BASEEFA / CSA / DGMS for use in Class I, Division I, Group D, T3 hazardous area, even if the instrument’s location is classified as a normally non-hazardous area. Intrinsically safe protection using external barriers are provided for all process transmitter loops (closed as well as open). Isolating barriers used are of the plug-in type, mounted on modular back plane termination units. All other instrument loops are provided with explosion proof / flame proof protection. Solenoid valves, electric hand switches, signaling lamps and Intercom / Paging system are chosen Explosion proof / flame proof Ex d to NEMA 7.

5.3.3.5 R F Interference:

All equipment are designed to be unaffected by radio transmissions. Band-pass and / or band stop filers are fitted, as necessary to ensure immunity to RFI.

5.3.3.6 Sealing: Seal systems are used to isolate instrument from the process fluid encountered in the following services:

a) Wet gas, which may condense in the instrument lines. b) Process fluids that vaporize, condense or solidify under operating pressure and

ambient temperature. c) Process fluids that will subject the element to high temperature. d) Corrosive process conditions.

Page 29: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 29

e) Viscous liquids. Sealing is accomplished with diaphragm seals as well. All venting instrument and pilot valves are provided with bug screens fitted to atmospheric vents.

5.3.4 INSTRUMENT MATERIAL SELECTION PHILOSOPHY: All materials and equipment furnished are required to be new and unused, of current manufacture and the highest grade and quality available for the required service, and free of defects. Materials and equipment are adequately protected from construction damage, particularly damage due to sandblasting and painting.

Materials are selected with regard to the following criteria:

• Suitability for the specified process conditions, with SS 316 the minimum for use

outside pressurized rooms, except for salt-water service, which shall be Monel. • Suitability for the corrosive effects of the atmosphere. • Galvanic compatibility between dissimilar materials, with isolating bushes, plates,

used where necessary to prevent corrosion due to galvanic action. • The possibility of selective corrosion in certain alloys and stress corrosion cracking in

certain high strength materials when used in corrosive environments. Where H2S may be present in process streams, all wetted metallic parts of instruments, valves, tubing and fittings are required to comply with the requirements of NACE MR 0175, 2002.

• Company approval is mandatory for the use of Aluminium for any instrument component. Use of Aluminium is permissible only if no other suitable material is available from the manufacturer, and Aluminium is not used for any component in contact with the process fluid. If Aluminium is used for any housing or component it should be suitably coated and certified as copper free i.e. less than 0.4% copper by mass.

• Material for all junction boxes, and instrument electronics and termination housings is in general SS 316.

• All spindles, bushings, bolting, screws etc., are required to be manufactured from a suitable grade of stainless steel. All bolts and screws are required to have a flat 316 SS washer under the nut, and with the thread length such that there is complete full engagement of the nut, with a minimum of two threads protruding.

• All fittings, supports, panels, fasteners, brackets, grider clamps, angle, tube clips, saddles, channel, U-strut type channel, cable ladder, conduit, cable glands and the like are made of SS 316.

• All material for instrumentation, in contact with process fluid containing CO2 in excess of 2 Kg/cm2 psi partial pressure, are designed as follows:

Fluid Temperature Material to be used

< 71 oC ASTM A182-F316 (316SS) > 71 oC ASTM A182-F51 (2205 duplex steel)

• Moulded polyester parts are required to be anti-static for hazardous area locations,

and in general are constructed from UV-stabilized glass reinforced polyester. Surface resistance required is not less than 109 Ohms.

Page 30: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 30

5.3.5 INSTRUMENT INSTALLATION PHILOSOPHY:

The Instrument installation philosophy ensures quality craftsmanship and conformance to the best applicable engineering practices. All instruments are installed in a neat workmanlike manner for ease of operation and maintenance. The Contractor is required to prepare hook-up and installation details drawing for the Company’s approval, and all installation are carried out in accordance with these drawings. The instrument / equipment are installed only in the approved locations, with due consideration of the following:

No instrument with the exception of pressure gauges and temperature indicators,

shall be installed in such a way that it depends for support on the impulse piping or electrical connections to it.

Positioning of equipment shall not constitute a safety hazard. Where possible, instruments shall be mounted so that they are protected from the effects of rain and sun, while maintaining the requirements for access and visibility. Where this is not possible, the Contractor shall provide a fixed cover or hood to protect instruments, without impairing access or visibility

Visibility and accessibility for both maintenance and operations purpose Ease of access for lifting heavy items of equipment such as valves All instruments and valves shall be free from vibration. Instruments shall be mounted / connected so as not to stress vessel nozzles or pipe

tapping. Instruments shall be fitted so that they can be removed by a single person. All local process-connected instruments shall be located as close as possible to the

point of measurement while still being accessible from the deck, ladder or a platform. Instruments requiring frequent routine access (including hand-valves, manual resets,

manual switches, etc) shall be mounted approximately 1.4m above the deck or platform.

Instruments shall be properly supported on brackets or mounted on sub-plates, or placed on a suitable pedestal, pipe stand or structural support. Pipe or structural stands may be welded directly onto platform plate, with a suitable penetration in the grating, where applicable.

Instruments, tubing, cables and cable ladder shall not be fixed to gratings or handrails. Instruments shall not be mounted directly on process piping without the Company’s

written approval. Instruments or instrument lines shall not be supported on handrails unless approved

by the Company. Fittings such as instrument isolating valves and instrument air or gas regulators shall

be supported either on the instrument stand or close-coupled to the instrument in a manner that no undue stress is imposed o the tubing or instrument.

Instrument stands or panels are installed in accordance with the approved drawings, with consideration for:

Page 31: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 31

The most direct routes for tubing and piping to and from the stand, using common tubing runs and avoiding crossovers.

Ease of inter-connections between instruments Ease of access for on-site calibration and / or removal of instruments Minimum interference between tubing, piping and cabling to instruments

A 316 SS combination filter regulator with gauge is provided for each instrument requiring regulated gas or air supply.

5.3.6 INSTRUMENT INSPECTION & TESTING PHILOSOPHY:

General:

The Contractor has to submit a quality plan, which includes a comprehensive fully documented inspection and testing plan specific to the project. The procedures include inspection specifically for compliance with hazardous areas requirements, including current certificate, without which no circuit or loop is energized. All testing, calibration and pre-commissioning is done by the Contractor. The Contractor also provides assistance as required in the Company’s commissioning activities. The Contractor, in the presence of the Company Representative, verifies by inspection, calibration and loop testing that all instrumentation in field and control room including local and remote/central control panels is complete and operable. All testing and calibration are subject to approval of the Company. The Company Representative prior to shipment checks out panels, consoles, and packaged instrument assemblies.

In addition to yard calibration/testing loop checking and setting for safety devices like process switches, safety valves etc. and simulation testing of all interlock and shutdown systems, these activities are also carried out at offshore.

Flushing of Lines:

The Contractor is required to remove in line instruments like flow meter, control valves/safety valves if necessary and provide spool pieces/flanges prior to flushing of lines.

Instrument Supply Lines: Instrument air/gas piping and tubing are disconnected upstream of all filter/regulators and blown down to remove water, slag and mill scale from lines.

Instrument air/gas tubing and piping are hydrostatically tested. Instrument air supply lines are blown with instrument air prior to connecting to instruments. Instrument air/gas mains are isolated from the instrument and pressurized to 11/2 times maximum working pressure with instrument air. They are then isolated from the pressure source and the pressure reading on a test gauge is required not to fall by more than one psig in ten minutes.

Page 32: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 32

Instrument Signal Lines:

Instrument signal lines are blown with instrument air prior to connecting to instruments. All air/gas tubing are tested and inspected by one of the methods given in Instrument System & Automation Society (formerly known as Instrument Society of America) Recommended Practice RP 7.1 “Pneumatic control circuit pressure test”. Clean, oil free instrument air is used for the test. Impulse Lines: All process impulse lines are disconnected and flushed with potable water. Air lines are blown down with filtered air. Hydraulic lines are flushed with hydraulic oil.

After flushing, process impulse lines are isolated from the instrument and pressurized hydraulically to 11/2 times maximum working pressure corrected for ambient temperature. They are then isolated from the pressure source and the pressure reading on a test gauge is required not to fall at a rate exceeding one psig/hour.

Direct Mounted Instruments: For direct mounted instrument such as level gauges, level transmitters (displacer type), level switches etc, the installations are pressurized to maximum operating pressure slowly and steadily with the instruments. The installations are then isolated from main pressure source. The pressure is required not to fall at a rate exceeding one psig/hr.

Wiring: Wiring is checked to ensure that it is correctly connected and properly grounded. Insulation test is carried out on all wiring taking necessary precautions. Correct connections of all electric or pneumatic switches are also checked.

Calibration:

The Contractor’s instrument personnel calibrate the equipment. This calibration when possible is done with the instrument or system in place, otherwise calibration prior to installation or removal for calibration is done. The Contractor generally provides written results of all instrument calibration in prescribed format. Testing:

In general, all tests simulate, as closely as possible, design process conditions by use of manometers, potentiometers, deadweight testers, test pressure gauges, etc. utilizing hydraulic and pneumatic suppliers. Three (3) point calibration refers to the input signal to an instrument equivalent to 0, 25, 75 and 100 per cent of the instrument range upscale (rising) and 75, 25 and 0 percent of the instrument range downscale (falling). All instruments are generally calibrated in upscale and downscale directions and, if necessary, adjusted until their accuracies conform to those limits stated by the

Page 33: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 33

manufacturer. Upon completion of these tests, the instruments are drained, the components removed and the shipping stops replaced.

Reporting:

The Contractor is required to provide written results of all above tests and if required by the Company, provide reasonable evidence of the satisfactory condition of test equipment.

All errors of faulty workmanship discovered during this testing are to be corrected to the satisfaction of the Company

5.3.7 INSTRUMENT SPARES PHILOSOPHY:

For all major equipment, normal commissioning spares are included as a part of the equipment. The Contractor also furnishes separately, list of recommended spares for two year’s trouble free operation along with the prices for purchaser’s review.

5.3.8 PHILOSOPHY FOR FUTURE FACILITIES:

Provision is made in all control systems such as control room instrumentation, pneumatic shutdown panels and local panels etc to operate and control future facilities shown in P&ID. All panel / cabinet mounted instruments and accessories required for this purpose are also supplied and installed by the Contractor.

5.3.9 LIST OF CODES & STANDARDS FOLLOWED BY INSTRUMENTATION:

The Codes & Standards followed by the Instrumentation discipline in generating design documents are as follows:

American Gas Association (AGA)

AGA Report No. 3 Orifice Metering of Natural Gas

AGA Report No. 8 Compressibility and Supercomressibility for Natural Gas and other Hydrocarbons.

AGA Report No. 9 Measurement of Gas by Multipath Ultrasonic Meters

American National Standards Institute (ANSI)

ANSI B 2.1 Pipe Threads

ANSI B 16.5 Steel Pipe Flanges, Flanged Valves and Fittings

B 16.10 Face to Face and End to End Dimensions of Ferrous Valves

B 16.34 Hydrostatic body and leak testing of isolation valves.

B 16.37 Hydrostatic Testing of Control Valves

B 16.104 Control Valve Leakage

Page 34: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 34

FCI 70.2 Leak Testing of Control Valves

ANSI C 96.1 Temperature Measurement Thermocouples

ANSI B 1.20.1 Pipe Threads, General Purpose

MC 96.1 Temperature Measurement Thermocouples

American Petroleum Institute (API)

API 6D Specification for pipeline valves

API 6FA Fire Test for Valves

API RP 14C RP for Analysis, Design, Installation and Testing of Basic Surface Safety Systems on Offshore Production Platforms.

API RP 14F RP for Design and Installation of Electrical Systems for Offshore Production Platforms

API RP 14G RP for Fire Prevention and Control on Open Type Offshore Production Platforms

API RP 500 Classification of Locations for Electrical Installations at Petroleum Facilities Classified as Class 1, Division 1 and Division 2

API RP 520 Sizing, Selection and Installation of Pressure Relieving Devices in Refineries, Part I and Part II

API RP 521 Guide for Pressure Relief and Depressing Systems

API RP 526 Flanged Steel Safety Relief Valves

API RP 527 Commercial Seat Tightness of Safety Relief valves with Metal to Metal Seats

API RP 550 Manual on Installation of Refinery Instruments and Control Systems (out of print)

API RP 551 Process Measurement Instrumentation

API RP 552 Transmission Systems

API RP 554 Process Instruments and Control

API RP 555 Process Analyzers

API 598 Valve Inspection and Testing

API Standard 2000 Venting Atmospheric and Low Pressure Storage Tanks: Non-refrigerated and Refrigerated.

API 1101 Measurement of Petroleum Liquid Hydrocarbons by Positive Displacement Meter

Page 35: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 35

API RP 2001 Fire Protection in Refineries

API 2534 Measurement of Liquid Hydrocarbons by Turbine Meter Systems

API Manual of Petroleum Measurement Standards – Measurement of Crude Oil by Coriolis Meter

American society of Mechanical Engineers (ASME)

ASME PTC 19.3 Performance Test Code Temperature Measurement

American Society for Testing and Materials (ASTM)

ASTM A269 Stainless Steel Tube

ASTM A276.316L Stainless Steel Fittings

ASTM 370 Standard Test methods and definitions for Mechanical Testing of steel products

ASTM 450 General Requirements for Carbon, Ferritic Alloy, and Austenitic Alloy Steel Tubes

British Standards

BS 1904 Specification for industrial platinum resistance thermometer sensors

BS 4937 International Thermocouple Reference Tables

BS 5501 Electrical Apparatus for Potentially Explosive Atmospheres

BS EN 60529 Specification for degrees of protection provided by enclosures (IP) codes

International Electrotechnical Commission (IEC)

IEC STD 801 Part 3 – EMI and RFI Immunity

IEC 60092-373 Shipboard flexible coaxial cables

IEC 60092-359 Specification for insulation and sheath of electric cables

IEC 60227 Polyvinyl chloride insulated cables of rated voltages up to and including 440/750 V

IEC 60331 Fire resisting characteristics of electric cables

IEC 60332-1 Tests on electric cables under fire conditions Part I: Tests on single vertical insulated wire or cable

IEC 60332-3 Tests on electric cables under fire conditions Part II: Tests on single small vertical insulated copper wire or cable

IEC 61508-1-7 Functional safety on electrical / electronic / programmable electronic safety-related systems

Page 36: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 36

IEC 61000-4-2 Electromagnetic Compatibility (EMC) – Part 4: Testing and Measurement Techniques – Section 2: Electrostatic Discharge Immunity Test

IEC 61000-4-3 Electromagnetic Compatibility (EMC) – Part 4: Testing and Measurement Techniques – Section 3: Radiated, Radio-Frequency, Electromagnetic Field Immunity Test

IEC 61131-3 1993 Programmable Controllers – Part 3: Programming languages

Institute of Electrical and Electronic Engineers (IEEE)

IEEE STD.472 Surge Withstand Capabilities

IEEE C37.90.1 Standard Surge Withstand Capability (SWC) Tests for Protective Relays and Relay Systems

IEEE 730 Standard for Software Quality Assurance Plans Revision of IEEE Std 730-84 and Redesignation of IEEE 730.1-89; IEEE Computer Society Document

IEEE 828 Standard for Software Configuration of Management Plans

IEEE 1042 Guide to Software Configuration management IEEE Computer Society Document

Instrumentation Systems and Automation Society (ISA)

ISA 5.1 Instrumentation Symbols and Identification

S 7.0.01 Quality Standard for Instrument Air

ISA/ANSI-S 84.01 Application of Safety Instrumented Systems for the Process Industry

ISA 912.13 Part I: Performance Requirements, Combustible Gas Detectors Part II: Installation, Operation and Maintenance of Combustible Gas Detectors

ISA S 71.01 Environmental Conditions for Process Measurement and Control Systems: Temperature and Humidity

ISA S 71.04 Environmental Conditions for Process Measurement and Control Systems: Airborne contaminants

ISA S 75.01.01 Flow equations for sizing control valves

S 75.03 Face to Face Dimensions for Flanged Globe Style Control valves

International Organization for Standardization (ISO)

ISO 5167 Measurement of Fluid Flow by means of Orifice Plates

Page 37: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 37

National Association of Corrosion Engineers (NACE)

NACE MR 0175 Sulfide Stress Cracking resistant metallic materials for oilfield equipment

National Electrical Manufacturers Association (NEMA)

NEMA 250 Enclosures for electrical Equipment (1000 Volts maximum)

National Electric Code (NEC)

National Fire Protection Association (NFPA)

NFPA 70 National Electrical Code

NFPA 1 Fire Protection Code

NFPA 72 E Automatic Fire Detectors

NFPA 496 Standard for Purged and Pressurized Enclosures for Electrical Equipment

Other Bodies

Report EE170E.98 ER & E Version 1.0, Alarm Management Guidelines

Engineering Equipment Materials Users Association (EEMUA) publication No. 191, Alarm Systems – a Guide to Design Management and Procurement

5.4 PIPING:

GENERAL: This refers to the basic requirements of material selection, corrosion philosophy, piping design parameters to be considered during fabrication, hook-up & pre-commissioning activities and safety, health & environmental aspects. International codes governing design are given in clause 6.0 of the manual.

5.4.1 CORROSION PHYLOSOPHY:

Corrosion implications for process components consist of the five process stream components contributing to the corrosiveness of the fluid are water, carbon dioxide, hydrogen sulphide, chlorides and organic acids in crude oil. The opposing components are oil films and any inhibitor additions or scaling chemicals contributed from the produced water. The Contractor carries out such calculations to demonstrate that the design life will be achieved. Free Water: In piping and vessels filled with liquids, the metal surfaces may be protected by scales from corrosion products or formation deposits, oil films or deliberately added inhibitor. Use of carbon steel may be acceptable provided that the combination of corrosion allowance and inhibited corrosion rate can deliver the design life and that downstream

Page 38: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 38

contamination by corrosion products is not a concern. In a gas stream after water separation or after compression, corrosion will only occur if there is produced water carryover or the gas stream is condensing and there is no other control measure such as addition of a misting inhibitor. Standard calculations provide the dew point temperature for given conditions although the dew point temperature predictions are most accurate on smooth surfaces such as pipes. In crevices or in locations with deposits, condensation may occur a few degrees below the dew point. The difference in corrosivity between wetting with potentially scaling produced water and condensation of CO2 saturated water are to be considered to assess the possible benefits of scaling on corrosion rates. Carbon dioxide: CO2 corrosion only occurs when the susceptible metal is wet and is the result of the CO2 reacting with water to form carbonic acid. CO2 corrosion is prevalent as pitting and mesa type corrosion where water condenses out of the gas phase. CO2 is also prevalent as general corrosion (often severe) where water gathers or flows even if it is beneath liquid hydrocarbons. The corrosion mechanism may be self mitigated to some degree due to the formation of a FeCO3 layer but in the presence of chlorides in the formation/produced water, the FeCO3 layer will become unstable and will not satisfactorily slow the corrosion rate. Hence, the severity of CO2 corrosion will depend both on the temperature and pressure but will also depend on whether the water is condensed or is formation water that frequently contains scale-forming components, which reduces the corrosion rate. Hydrogen sulphide: Process streams containing hydrogen sulphide may cause sulphide stress cracking of susceptible materials. The phenomenon is affected by a complex interaction of parameters including metal chemical composition and hardness, heat treatment, and microstructure as well as factors such as ph, hydrogen sulphide concentration, stress and temperature. Material used to contain process stream containing hydrogensulphide are selected to accommodate these parameter. The Mumbai high oil is sweet oil i.e. no H2s content. However, there is possibility that due to water injection in the formation, it may turn sour in future. The well platform, process platforms and well fluid pipeline etc. designed earlier, were based upon sweet oil, however, facilitates being designed now, from Infill Platforms onwards are based on 230ppm of H2S in well fluids. As such in a process complex like SH older platform SHP/SHQ, design was based on sweet oil where as design of new platform like SHG, which is bridge-connected, is based on 230 ppm H2S in oil. Chlorides: Any austenitic stainless steel vessel or pipe work that is internally heated so its external temperature is above 550C and exposed to the atmosphere is at risk from stress corrosion cracking unless it is painted or otherwise shielded to prevent chloride concentration on surface that may be used or carbon steel components that are internally clad with 316L stainless steel. However, the latter requires additional expertise in welding and fabrication. Organic acids:

Page 39: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 39

No Total Acid Number (TAN) data has been is reported although problems usually arise at more elevated temperatures than those to which the process stream is heated on this platform. Nevertheless, this corrosion mechanism requires consideration if carbon steel is used in contact with water and high TAN oils. Corrosion Inhibition and Monitoring: Any inhibitor program is designed around the delivery points and techniques. A water-soluble inhibitor is selected from candidate materials by use of laboratory tests. The timing of the dosing is selected by persistency trials reinforced by monitoring. In area, which suffer from condensation but are not adequately wetted with inhibited water, corrosion can be controlled by mist spraying of inhibitor. The only caveat is that mists do not travel well around bends unless the flow is sufficiently turbulent. The inhibitor evaluation includes possible environmental effects of any inhibitor dosing that is discharged with the extracted water. The design of the corrosion monitoring includes the three timelines philosophy, i.e. short, medium and long term monitoring. The routing process monitoring, which is carried out automatically (with operator overview) provides the first level of monitoring to ensure that temperatures, pressure and pressure drops, flow pH and conductivity are within expected limits. If they are not then the process is to have an incremental response depending on the consequences of the deviation and its magnitude. This requires sufficient automated instrumentation and management software/firmware for proper analysis of the data. The second tier is the regular testing programs where process samples are procured and analyzed at set intervals. Corrosion coupons or, more probably electrical resistance probes, are measured regularly. The final tier is the scheduled measurements of residual wall thickness and general inspection possibly including internal surfaces of vessels although the risks of process contamination inherent in opening vessels obviously limit internal inspections. Note that there has to be external inspection programs that will run in parallel with the monitoring of the process side.

5.4.2 Utilities and Support Systems: These include non-corrosive air, possibly corrosion inhibiting and biocide chemicals, oil treatment chemicals and seawater for fire or deluge control. Heat exchangers are air-cooled. Heating oil and the like are not critical as far as internal corrosion is concerned.

5.4.3 Chemical Delivery: Such systems generally cannot be inhibited and cannot tolerate corrosion products so they may be assembled from stainless steel. The fluids may include potable water or any of the emulsion controlling, inhibiting or other chemicals, which are aggressive to carbon steel. As indicated previously small diameter stainless steel tube may require external coatings in the tropical marine environment to prevent staining, pitting and possibly stress corrosion cracking. Whilst it is superficially attractive to specify an improved surface finish (<0.5umRa) with its enhanced corrosion resistance the probability of damage during the design life virtually dictates that an external coating is a more conservative option.

Page 40: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 40

5.4.4 Sea Water:

If seawater is used for the firewater system then the material choice depends to some extent on the operating philosophy, i.e. is it recalculating, left dry, left stagnant, etc. Typically seawater is sterilized by oxidizing compounds and then is held stagnant for some time. Oxidizing treatments will tend to increase corrosion rates in seawater. The design must consider whether carbon steel (possibly with an internal coating) or even 316L is adequate or the preferred option of the more resistant materials such as CuNi or glass reinforced polymer with fire resistant treatments. The 10-year design life is addressed with plans to control the possible defects arising from fabrication or subsequent operation.

5.4.5 Bolting: It is generally not acceptable to use unprotected high strength carbon steel bolts in a corrosive environment (such a marine exposure) because of the risk of corrosion causing hydrogen embrittlement. Heavy galvanizing has proven satisfactorily in tropical marine environments. The use of stainless steel fasteners has its own difficulties especially if the fasteners are required to be removed. Austenitic fasteners tend to gall or cold weld, which often leads to fracture of the fastener. The problem occurs if the mating surfaces are close in hardness (difference <50HB) and is worse for surfaces outside the surface roughness range of 0.25 to 1.5um or if the contact stress is high. It can be reduced if different materials are used, e.g. duplex nuts and austenitic stainless steel bolts. A second best procedure is to use material for nut and bolt with the addition of an anti-seize lubricant.

5.4.6 Fire Water And Deluge System:

Injection water are specified for the firewater and deluge system. The system will be dosed with biocide and will remain stagnant except for the monthly tests required by NFPA20. The seawater will be oxygenated on ingestion but may steadily deoxygenate and rise to ambient temperatures in the pipes Cathodic protection provided by the bronze components.

5.4.7 Material Selection Philosophy: This covers the minimum requirements for materials selection for offshore manned & unmanned Platform. This refers the assessment of material requirements for various services on offshore platforms for deck piping &, vessels in sweet, sour conditions & offshore environment. The material selection logic has been based on a design life of 25 years, reservoir data, and environmental data, process simulation information that provides pressure, Temp & fluid composition for various piping systems. The material of construction is very critical to designing of oil & gas facility due to varying environment & handling requirement. During initial stage of development well platforms in offshore were provided with exotic materials viz. Incoloy, DSS & CS with cladding etc were also

Page 41: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 41

provided as extra measures of safety with due considerations of H2S & CO2 etc in oil/ gas fluid. Therefore these platforms provided relatively costly due to use of such materials. Cost optimization exercise & gain in experience in exploitation less costly materials. Carbon steel materials are suitable for the majority of the piping system on production platforms as per API-RP-E.Presence of process streams viz.water, carbondioxide hydrogen sulphide, Chloride and organic acid as given in 8.3.1 influence material selection. However, for hydrocarbon service, material selection is based on the following considerations:

When the H2S exceeds the limits as prescribed in NACE-MR-0175, CS (Nace) is selected.

At high temperature, high partial pressure of H2S and CO2, SS(Nace) is selected. At high temperature, further higher partial pressure and in the presence of chlorides,

more catastrophic stress corrosion cracking can occur. In such cases application of high alloy stainless steel and nickel alloy as such as Duplex – S.S. are selected.

For seawater services the material selection is based on the following consideration: For Raw Sea water, Cu-Ni is a suitable material due to high corrosion resistance. For treated seawater, C.S. is widely used.

Further the material recommendation for various services are presented in the form of table. This specification will present information on most commonly used metallurgy for process piping, firewater, sewage water, drain water, chemical injection services & other services.

5.4.8 Material Recommendations: Material Recommendations for various services for piping systems are listed below as table 4.0 (A) & table 4.0 (B):

TABLE 4.0 (A)

SERVICE Min CA in mm PIPES FITTINGS FLANGES

Gas Lift

6.0 CS (NACE) CS (NACE) CS (NACE)

Well Fluid 6.0 CS (NACE) CS (NACE)

CS (NACE)

Injection Water 3.0 CS CS CS

Produce Water 0.0 GRE (Glass

reinforced Epoxy) GRE GRE

Instrument Gas 1.5 SS316L SS316L SS316L

Closed Drain 6.0 CS (NACE) CS (NACE) CS (NACE)

Page 42: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 42

Open Drain 3.0 CS CS CS

Sea/Saltwater 0.5 90-10 CU-NI 90-10 CU-NI 90-10 CU-NI

Chemical 1.5 SS316L SS316L SS316L

Potable Water (Drinking) 0.0 CU CU CU

Sodium Hypo Chlorite 0.0 CPVC CPVC CPVC

Sewage 0.0 GRE GRE GRE

Acidisation 3.0 CS CS CS

TABLE 4.O (B)

VALVES

SERVICE BODY TRIM Gas Lift CS (NACE) ASTM A 182 GRADE F 316L

Well Fluid CS (NACE) ASTM A 182 GRADE F 316L

Injection Water CS ASTM A 182 GRADE F 316L

Produce Water CS WITH GRE LINING ASTM A 182 GRADE F 316L

Instrument Gas SS316L SS316L

Closed Drain CS (NACE) ASTM A 182 GRADE F 316L

Open Drain CS ASTM A 182 GRADE F 316L

Sea/Saltwater Al-Ni bronze MONEL

Chemical SS316L SS316L

Potable Water

(Drinking) Bronze Bronze

Sodium Hypo

Chlorite CPVC CPVC

Sewage CS WITH GRE LINING ASTM A 182 GRADE F 316L

Acidisation CS ASTM A 182 GRADE F 316L

5.4.9 SOUR SERVICE REQUIREMENTS:

All sour service materials conform to NACE Standard MR0175 and so the materials selected are restricted to those complying with the Standard. Sour gas service materials are in accordance with NACE Standard MR-01-75. All sour service material meet the special testing viz. HIC (as per NACE MR O1 77) and inclusion count check (as per ASTM A45) and as specified below:

Page 43: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 43

Plate: ASTM A-516 Grade 70 Forgings: ASTM A-105 Pipe: ASTM A-106 Grade B Fittings: ASTM A-234 Grade WPB Flanges: ASTM A-234 Grade WPB Valves: Body- ASTM A-234 Grade WPB & Trim- 13% Cr alloy Bolts: ASTM A-193 Grade B7M (22 HRC max. hardness) Nuts: ASTM A-194 Grade 2M (22 HRC max. hardness) Copper-based materials are prohibited from use in sour gas service. Stress relieving of rolled plates, formed heads and pipe fittings is in accordance with NACE Standard MR0175. Threaded connections are not permitted on sour gas service.

5.4.10 DESIGN REQUIREMENTS: All materials conform to project Specification and the identified API, ASME, ASTM, BS and NACE codes and Standards. All materials are new & unused. Materials older than one year from the date of manufacturing are not be accepted. Design and fabrication conform to this Specification and ASME B31.3, API RP14E & other applicable codes. Thickness and material for piping including piping components & specialties items from reducer of barrel to hanger flange are same as that of riser in splash zone to maintain constant ID to permit smooth pigging operations. All cupro-nickel piping are supplied in 20-bar system. Velocity in Cu-Ni piping does not exceed 1.6 m/sec for 2” NB and below and 3.3 m/sec. for 3” NB and above. Design of Cu-Ni piping system is to be such as to avoid excessive turbulence in the system. Monel is used at locations such as bends, reducers, downstream of restriction orifices, downstream of control valves, downstream of check valves, etc. wherever there may be a possibility of flow velocities exceeding the limits given above, impingement of flow stream on piping, or excessive turbulence. In all cases where Monel is used, it is in the form of spool pieces with electrical isolation with Cu-Ni material for minimizing galvanic corrosion of Cu-Ni piping.

Wherever dissimilar materials are in contact, sacrificial spool piece of 600 mm or insulating material is provided to avoid galvanic corrosion. Pipe work, its supports and anchors, are designed to withstand the results of the following combinations of loads and forces within the limits of stress set by ASME B31.3:

Hydro-test Condition (The empty weight plus weight of water to fill the piping).

Page 44: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 44

Operating and Design Conditions (The empty weight plus the weight of operating fluid)

Wind loading condition Dynamic Loading Condition Periodic Site Test Condition Any other condition that would affect the safety of the pipe work, e.g. cyclic loading

and slug forces, when identified on the Data Sheet Piping general arrangement drawings/isometrics/support drawings etc. are prepared using good engineering practices and as per guidelines furnished in project Specifications. As good engineering practices, piping in safe area carrying hydrocarbon and toxic/hazardous chemicals are of continuous lengths with welded joints such that valves, regulators, flanges etc. are not located in the safe area. Thermal Insulation are provided wherever required as per P& IDs, and Bid-insulation Specification. Acoustic insulation, wherever is necessary to limit the piping emitted noise to the permissible values, follow API standards, and materials used are as per piping specifications. Piping schedule/thickness are calculated for each size, service & piping class including corrosion allowance indicated in material of construction of piping specification as per ASME B-31.3 for various services based on piping class conditions upto class 900 & actual design conditions for 1500 class of the system. All the piping on the bridge between two platforms are designed taking into account the differential movement of the two structures under extreme (100 years) storm conditions. Flexibility analysis of the piping system is carried out wherever required by the design conditions/platform movements and provide necessary loops/supporting arrangement. The piping connected to equipment is analyzed by the Contractor for flexibility and maximum stresses developed, along with nozzle reaction on equipment, will not exceed the permissible limits/values as specified in relevant codes & standards. Vendor data for maximum permissible nozzle loadings is obtained while analyzing piping for flexibility analysis. The above permissible limits are not exceeded in any case. Piping is suitably supported, as necessary, to prevent sagging, mechanical stresses and vibrations. In general, piping is fastened to pipe racks with appropriate sizes cadmium plated U bolts (3/8” min.) and is double nutted. The layout of equipment and piping is based on following principles.

To locate all equipments identified on equipment list. To comply with standards, regulations, codes, piping specifications and sound

engineering industrial practices. To maximize safety of personnel, equipment and facilities. To ensure operatibility & maintainability of equipment. To provide means of escape & access for fire fighting. To satisfy all requirements indicated in process documents (P&ID’s) To minimize shutdown duration. To provide neat and economical layout, allowing for easy supporting and adequate

flexibility to meet equipment allowable nozzle load.

Page 45: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 45

5.4.11 DESIGN OF SPECIFIC COMPONENTS:

Pipes: The pipes are designed as per applicable codes & standards. Piping thickness calculations are performed as per ASME B 31.3. Pipe dimensions are in accordance with ASME B36,10 for carbon steel pipe and ASME B36.19 for stainless steel pipe and BS2871 Part 2 for 90/10 Cu-Ni pipe work up to DN 500 (20”). Nominal pipe sizes DN 30 (1¼”), DN65 (2½”), DN85 (3½”) and DN 125 (5”) are not used except where they are required for connections to equipment of standard design or where specific velocities are to be maintained. When these sizes are used on equipment, the connecting piping is increased or decreased to standard sizes as close to the equipment as is practical. The minimum nominal pipe size is DN20 (¾”) except for air, instrument air, water and manufacturers’ standard equipment piping. All nipples are made from pipe as specified in each piping specification. Carbon steel pipe DN40 (1½”) and smaller used for process lines and other lines carrying flammable or toxic fluids will have wall thickness at least Schedule 80. Fittings: Fittings are used as per the requirement of various fittings like elbows, tees, reducers, sockolet, weldolets, nipple, swage, couplings, caps, plugs etc. The class of fittings like ANSI 6000, 3000, 9000 are selected as per ASME B 31.3. The thickness of fittings are same as that of connected piping. All unions DN25 (1”) and larger comply with BS 3799. No straight elbows or threaded bushings are used in piping. Hexagonal bushings (but no flush bushings) only are used with tubing fittings for connection to instruments, or as otherwise specifically approved by the Company. The thickness or reducing fittings match with the wall thickness of the higher schedule pipe wall. The fitting wall thickness is tapered on a 1:4 gradient to ensure that the pipefitting wall thickness matches the lower schedule pipe wall. Seamless fittings are generally used. The only acceptable alternatives are specified in the Piping Material Specification. Wrought fittings made from block forging and machined to the required dimensions can be used only with specific approval from the Company. All 90º-weld elbows are long radius, unless restricted by available space. If short radius weld elbows are used, they are de-rated to 80% of the calculated allowable working pressure if subject to pulsations.

Page 46: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 46

Fittings are at least the same nominal wall thickness as the pipe to which they attach. Short radius elbows, which have been de-rated as specified above, may require a wall thickness greater than that of the connecting pipe. Welded fittings materials are compatible with the piping material. Fittings DN40 (1-½”) and smaller are screwed or socket weld except as dictated by individual material specification classes. Fittings DN50 (2”) and larger are butt welded except where specified in an individual pipe class Data Sheet. Mitred joints are not used. Flanges: Flanges are in accordance with ASME B16.5 for DN50 to DN600 and with ASME b16.47 Series B for flanges DN650 and larger. They are raised face unless otherwise shown on the individual vessel data sheets and/or drawings. Non-standard size flanges are calculated in accordance with ASME Code Rules. Flanges on 90/10 Cu-Ni pipe work are drilled to ASME B16.5, Class 150#, but be otherwise compliant with BS4504 Part 2. API ring joint 5000-psi flanges comply with API 6A. ASME ring joint (RTJ) flanges have octagonal grooves conforming to ASME B16.5. API ring joint flanges conform to API specification 6A. Flanges for orifice plates or spectacle blinds and all RTJ flange assemblies (DN100 (4”) and larger) are provided with jackscrews (two, 180º apart) in one of each pair of flanges. The bolt hole pitch circle diameter for orifice flanges DN50, DN80 and DN100 are 1.6 mm smaller than specified in ASME B16.5. Flat-face steel flanges are used in cases where piping flanges will mate with valves or equipment, which have cast or ductile flat face flanges and full-face gaskets used. Flanges in the piping are kept to a minimum. Flanges are installed only to facilitate construction, maintenance and inspection and in cases where process conditions dictate. Spectacle blinds rather than spade blinds are provided where required. Thickness of blinds is calculated in accordance with ASME B31.3. Pairs of spacers and blinds are used instead of spectacle blinds of size DN 350 and larger. Valves: Valve bodies, seals, etc., are in accordance with the design pressure and design temperature of the applicable Piping System Specification. Valves may be supplied with higher design pressure or design temperature trims in order to meet the service requirements.

Page 47: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 47

Each valve is supplied with a stainless steel tag, attached to the gland bolting, or hand wheel, with stainless steel wire, bearing the applicable valve identification, Tag Number and Purchase Order number. Ball valves comply with API 6D or BS 5351. All ball valves in hydrocarbon service are fire-safe in accordance with the requirements of either API 6FA (for trunnion ball valves) or API 607 (for floating ball valves). Ball valve body patterns are long pattern to ASME B16.10 Carbon steel, stainless, and alloy ball valves, DN20 (¾”) and larger, are quarter-turn design. Soft seals and seats for ball valves are suitable for the maximum applied differential pressure, the service fluid and the specified pressure and temperature ratings. Check valves comply with BS1868 and BS5352. Swing type check valves have bolted bonnets. Where check valves are placed in vertical runs, valves are equipped with flapper stops. The stops are not connected to bonnet taps in any way. Gate valves comply with API 600, 602 or 603 as applicable. Gate and butterfly valves are used in “clean” non-hydrocarbon services only. Globe valves comply with BS1873 and BS5352. Plug valves comply with BS1873 and BS5353. Steel and alloy valves are designed and tested in accordance with the following: -

ASME 150# - Designed and examined in accordance with ASME B16.34 and tested in accordance with API 598.

ASME 300# through ASME 2500# - Designed and tested in accordance with API 6D. API 2000# through API 5000# - Designed and tested in accordance with API 6A.

All valves with non-metallic seats and seals are fire-safe, tested in accordance with API 607 or API 6FA and certified by an accepted third-party agency. Valves specified with removable bonnets are of the bolted construction with a minimum of four (4) bolts. Gate, globe, angle, ball and check valves are supplied with replacement seats. Where replaceable seats are not available, the valve seat is stellited and welded into the valve body. “LO” (Locked Open) or “LC” (Locked Closed) on drawings is provided with locking devices. Valves are furnished with the locking tab hardware installed. Open-ended valves are equipped with threaded plugs or blind flanges. Full port (as opposed to regular port), ball valves are used where ever specified on the drawings. Every block valve is provided with a lever, handle, or hand wheel as necessary to operate the valve.

Page 48: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 48

Gear operators are heavy-duty lubricated type and are completely housed in a weatherproof enclosure. Socket-weld valves are bolted body or top entry design, allowing removal of seats/seals for heat protection, prior to welding, without loss of assembly orientation. Single piece valve bodies, or valves bodies assembled by screwed-together components, are not used with socket-weld ends. Valve body thickness, wherever the minimum is not specified the relevant valve standard, is in accordance with ASME B16.34. All fittings are seamless. Steel castings for valves are radiographed in accordance with ASME B16.34 Annexure B, to the following extents:- Carbon Steel: ASME 150#, DN600 or smaller 10% ASME 150#, DN650 or larger 100% ASME 300#, DN400 or smaller 10% ASME 300#, DN450 or larger 100% ASME 600# and higher 100% Carbon steel to NACE requirements 100% Stainless and high alloy steel 100% Other alloys 100% Socket-weld-end valves with non-metallic seats or seals are provided with 80mm long nipples having materials and thickness equivalent to those specified in the relevant pipe set specifications. These nipples are welded to the valves on both ends before the packing, seats and seals are fitted. Welded nipples are subject to 100% radiography. Stem protection is required for all carbon steel gate and globe valves where 13% Chromium trims are specified. The stems are totally enclosed in sleeves, which are packed with grease. (Note: Details of Actuator selection for Valves are covered by the Instrumentation discipline in Functional Specification No.3700) Bolting: Flange bolting are full threaded alloy steel stud bolts, each with two heavy hexagonal nuts. Stud bolts have full continuous threads and have lengths in accordance with B16.5 with the provision that a minimum of one (1) thread and a maximum of three (3) threads outside each nut. Stud bolts are used for all piping closures except where tapped wafer valves dictate the use of machine bolts. Branch Connections: The branch tables are listed. The lists show requirements for branches at 90º angles to the header. Branch angles less than 90º, but not less than 45º, are allowed, and provided the

Page 49: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 49

connections are reinforced through the use of circular reinforcing pads or integrally reinforced branch fittings.

5.4.12 PIPING SYSTEM DESIGN:

Design calculations for pressure/temperature, wall thickness requirements, acoustics, vibrations, thermal expansion and contraction, pipe weights and flexibility are carried out in accordance with ASME B31.3 and ASME VIII and API-RP-14E and submitted to the Company for acceptance. Piping components are located where they can safely be operated (where necessary) and maintained. Access is provided to such components, which are located out of reach from the platform deck. The use of extended hand wheel stems or chain wheels are avoided. Dead ends on distribution and collection headers are generally be blind flanged but where sour or toxic fluids are being carried, spectacle blinds are provided. Where erosive fluids are being carried, targeted tees are provided. Long radius bends are generally used, but for pigged lines, 5D bends are required. Short radius bends are avoided unless essential for clearances. Cold-formed bends are not permitted. Fabricated mitre bends can only be used on gas turbine exhausts.

5.4.13 PIPE ROUTING:

Piping are routed so as to have the short runs and minimize pipe supports whilst providing sufficient flexibility for thermal expansion and contraction and mechanical movement. Expansion and swivel joints are avoided. Large bore piping are designed to minimize pressure drops. Smaller bore piping are routed in groups where practical along main pipe racks. Piping are kept within the deck boundaries. The number of flanges and unions are minimized. Pipe work carrying hydrocarbons or other hazardous materials through safe areas do not incorporate flanged connections, except for those at the associated equipment connections. Piping are routed to avoid trip and overhead hazards. Consecutive elbows in different planes are avoided. Pipe routing allows sufficient space for bolting up flanges or for line-up clamps to be used for field welds. Refer to 10.5 “Piping Clearances”. Piping routing to ensure that clear head clearance of 2.3 meter is available on decks. Piping passing through firewalls are sealed with fire-retarding sleeves. Primary process and gas connections on piping are DN25 (1”) or larger through the first block valve. Primary utility (air, steam and water) connections on piping are DN20 (¾”) or larger through the first block valve.

Page 50: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 50

All instrument air and fuel gas connections are from the top of the associated headers. The angle between any branch and its header is less than 45º. Scraper tees are provided for lines which are to be pigged wherever branches are larger than DN50 (2”). Dimensional rules for piping design are as follows: Minimum pipe diameter for thermo-well connection on straight run pipe DN 100. Minimum pipe diameter for thermo-well connection on 90º elbow DN 80 Pipe racks to be sized to allow for the future equipment +20%. Minimum run size of piping in racks DN 50 Spacing of instrument air take-offs along pipe rack headers >3000 mm in process areas. Minimum slope of HP and LP flare headers 1:100 Minimum slope of open drain header 1:100 Minimum slope of closed drain header 1:100 Minimum slope of pump suction lines where vapour may be present 1:50

5.4.14 PIPE SUPPORTS;

Piping are suitably supported to prevent sagging, mechanical stresses vibrations and consequent fatigue, while allowing for thermal and structural movement. Piping are adequately supported for the weight of piping filled with water, with attached components unsupported, subject to wind, seismic, insulation and any other applicable loads. The supports prevent excessive stresses in the piping and in the nozzles of the equipment to which it is connected. Small bore instrument tubing and piping are adequately supported and protected from impact damage. Bracing is provided for small bore branches in piping adjacent to vibrating machinery.

5.4.15 PIPE WAYS: The piping is routed in either platform north/south or east/west in established pipe ways. All lines running platform north/south are on different elevation from lines running platform east/west, as far as practical. A minimum of 600 mm or more clearance between pipes at the time of changes in elevation of pipe runs in pipe ways to be ensured.

5.4.16 PIPING CLEARANCE:

Page 51: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 51

The minimum access clearance for maintenance access shall be 750 mm. The following design constraints shall also apply. Minimum height from underside of pipe or insulation to high point of deck level or platform: 200 mm. Piping routing to ensure head clearance of 2.3 metres is available on deck. Control valve arrangement: Preferred bottom of pipe (BOP) of control valve above deck level or platform: 400 mm For meter runs, the minimum clearance between BOP and deck is 760 mm Pipe spacing: Minimum space between pipes without flanges (after allowing for insulation and lateral movement): 100 mm Minimum space between pipes with flanges (largest 100 mm flange to pipe) (after allowing for insulation and lateral movement) Minimum distance from pipe to face of steel work (after allowing for insulation): 50 mm Minimum distance from flange to face of steel work, 50 mm etc. Valve installations and access: Preferred height of hand wheel from deck or platform: Horizontally mounted valves 1000/1350 mm Vertically mounted valves 1100/1300 mm Maximum height from local deck or platform level to center line of horizontal hand wheel without platform (or chain wheel) Vertically mounted valves (DN100 and larger) 2000 mm (DN 80 and smaller) 2250 mm Maintenance or isolation 3000 mm (Except where temporary platforms can be used and at pipe racks) Use of chain wheels and extension stems shall be kept to a minimum. Chain shall clear operating level by: 1000 mm

5.4.17 FLANGED CONNECTIONS:

Flanged connections are minimized, being used only where frequent dismantling is required, where specific flanged spools are needed, where needed to provide clearances for equipment removal, or for piping class or material changes.

5.4.18 THREADED PIPE WORK:

Page 52: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 52

Threaded piping is not used to carry hydrocarbons. Ping DN40 (1½”) and smaller, when used for services upto 1900 kPag (275 psig), may be threaded. Screwed fittings are rated at least 20.7 Mpa (3000 psi). Bushings, close nipples and street elbows are not used. Pipe threads conform to ASME B1.20.1. Cu-Ni pipe work are not threaded. Adapters can be used at valves or equipment.

5.4.19 CHANGES IN MATERIALS:

Where dissimilar piping metals connect, sacrificial pipe spools are provided. These are of anodic material and at least 600 mm or 3 times the relevant nominal pipe size long, whichever is greater. Where this is not practical, electrical insulation joints are provided to prevent galvanic corrosion.

5.4.20 VENTS, DRAINS AND BLEEDS:

High points on all lines are provided with DN20 (¾”) minimum plugged or flanged connections for venting during hydrostatic tests. For lines carrying hydrocarbons or other toxic fluids, the vents are be piped to the nearest vent header. Low points in lines are provided with drain connections of nominal sizes as follows:-

Line Size Drain Size DN15 (½”) DN15 (½”) DN20 (¾”0 TO dn100 (4”) DN20 (¾”) DN150 (6”) to DN250 (10”) DN25 (1”) Dn300 (12”) and larger DN25 (1”) to DN 40 (1½”)

Drains on lines other than fire water are provided with valves and plugged. Fire water drains do not need valves. All hydro-test vents and drains in hydrocarbon service are DN 20 with valves and steel plugs unless noted otherwise. A hydrostatic vent and drain philosophy are developed during detail design and shown on the isometrics.

5.4.21 CORROSION INHIBITION AND MONITORING PIPE WORK:

Page 53: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 53

Corrosion monitoring fittings are located as close as practical to the pipe work being monitored, where servicing access is easy and away from sources of vibration. Clearance is provided for the removal of the injection quills and monitoring probes motoring probes, suiting each nozzle orientation and the length of the associated probe. Corrosion probe nozzles are mounted on the underside of the pipes.

5.4.22 RELIEF VALVES:

Relief valve assemblies are installed in the vertical position, as close to the pressure source as possible, and are provided with permanent platform access. Relief valves are bolted directly to vessel and equipment nozzles. Relief valve piping are designed to withstand reaction forces and moments caused by the valve discharging. Piping from relief valves to closed systems slope toward the headers and enter them from above, or, where that is not practical, have DN20 (¾”) drains in safe areas. Headers have at least 1:100 slopes toward downstream.

5.4.23 CONTROL VALVES:

Control valves are preferably installed in horizontal lines, with the actuator in the vertical position. Each valve is located as close as possible to the item of plant under control and is easily accessible from the deck or permanent platform. Where control valves are less than line size, reducing spools are made long enough to permit bolt removal. Consideration is made for removal or withdrawal of valves or part of valves for maintenance.

5.4.24 ISOLATIONS:

Piping is designed, so that the connections to equipment and vessels can be isolated for safe maintenance. This may be accomplished by providing for the insertion of blind flanges at strategic points or removable spools if blinding is not practical due to line size. All vessels containing hydrocarbons or other hazardous fluids and which involve personnel entry during maintenance require such blinds. Blinds are located so that insertion can be made from the deck or permanent platforms or access ways. Permanent hook eyes are provided above blinds, which weigh more than 25 kg. Where blinds are not required for isolation, valves are provided for safe isolation. Double block and bleed isolations are provided where shown on the P & IDs.

5.4.25 CUPRO-NICKEL PIPEWORK:

Cupro-Nickel or Copper-Nickel (Cu-Ni) piping are used for fire water deluge systems. Fluid velocities in Cu-Ni piping are not to exceed 1.6 m/sec. For DN50 (2”) and smaller and 3.3 m/sec for DN80 (3”) and larger piping. The piping is designed to minimize

Page 54: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 54

turbulence. Monel is used where turbulence or impingement are likely – at bends, reducers and downstream of restriction orifices, control valves, check valves, etc. Monel piping are in spool pieces and these are electrically isolated from Cu-Ni spools. Supports for Cu-Ni piping are lined with soft packing pads, neoprene or similar, which are free of ammonia compounds.

5.4.26 COPPER PIPING:

Copper (Cu) piping are used for potable and other clean water systems. Fluid velocities in copper piping are not to exceed 1.5 m/sec.

5.4.27 GRE PIPING SYSTEMS:

Glass-Reinforced Epoxy (GRE) or Fibre glass-Reinforced Plastic (FRP) piping are used for water services where there is little risk of physical impact, typically for overboard lines. When a GRE pipe penetrates a fire rated wall or floor, the GRE is substituted by a flanged metallic spool piece, fabricated from a material suitable for the proposed service.

5.4.28 PIPING ON THE BRIDGE:

The design of the piping on the bridge takes into account the differential movement between the two structures under extreme (100 years) storm conditions and thermal expansion and contraction. Flexibility analysis of the piping systems is carried out.

5.4.29 PIPING AT THE EQUIPMENT:

Piping at equipment are arranged so the equipment can be removed without the need to dismantle the equipment, adjacent equipment or piping. Equipment is not used to anchor piping. Forces transmitted to equipment at tie-in points is within the Equipment Contractor’s recommended limits. Piping connected to rotating equipment are designed and supported to minimize the transmission of vibrations from the machines. The Contractor carries out flexibility analysis of this pipe work to prevent exceeding allowable nozzle loads as defined by Contractors of the equipment.

5.4.30 PIPING AT HEAT EXCHANGERS:

Cooling water piping to shell & tube exchangers are arranged so that water does not drain from the outlet when water supply fails. Exchanger piping is arranged so that the exchanger can be removed as one unit and so that the tube bundle can be pulled after disconnecting channel piping. Piping connections to exchangers are designed and properly aligned to allow for hot & cold service and to limit the stress on exchanger nozzles to within allowable levels. Filters are provided in lines to cooling fluid inlets.

Page 55: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 55

5.4.31 PIPING AT PUMPS:

Piping at pumps are designed and supported so that equipment can be dismantled or removed with a minimum number of temporary supports and without dismantling valves and piping other than the spool that connects to the pump. Clearances permit installation of blind flanges against block valves when the service is hazardous and the removal of pump rotating elements. Pump suction lines end with at least four diameters of straight pipe with the same nominal size as the suction flanges. If reducers are required on suction lines, they are to be eccentric and installed flat side up. Recycle lines are provided to allow minimum flows required for pumps. Pressure relief lines are to be provided for positive displacement pumps. Valves are located as close as possible to the pump nozzles as practical. Isolation valves on pump suction lines are full-bore ball type. Isolation valves on discharge lines are located downstream of check valves. Pump suction lines in which vapour may be present are inclined downward towards the pumps with slopes of at least 1:50. Strainers are provided in all pump suction lines. Permanent Y-type or basket strainers are provided for reciprocating and rotary pumps. The open area of strainer is at least 300% (HOLD) of the cross-sectional area of the pipe. The piping is arranged so that the filter or strainer element can be removed from the flanged joints without altering the piping, supports or pump alignment.

5.4.32 PIPING AT TURBINES:

Air Inlet and Exhaust duct termination are positioned away from hazardous areas, and areas frequented by personnel or any open ended or filtered inlet ducts. Fuel gas piping within the turbine enclosure is subject to strict control with respect to the number and type of flanged joints, fully welded being preferred. Flanged joints are provided only for connection to the equipment and for isolation and shut down valves.

5.4.33 PIPING AT DIESEL ENGINES:

All piping connected to diesel engines are arranged in such a manner that adequate flexibility is maintained so as to effectively isolate the piping from any engine vibration. Piping is not routed directly over diesel engines. Fuel lines are not run over exhaust piping or any location where leaks would cause fuel to impinge on to hot surfaces. Fuel lines incorporate local isolation valves. The fuel oil header is not dead-ended. Silencers, where installed in suction and discharge piping, are located as close as possible to the engine.

Page 56: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 56

Air intake openings are located away from any hazardous area, face toward the prevailing wind direction and be in such a position as to limit the ingress of dust (e.g. salt crystals) and moisture.

5.4.34 PROTECTIVE COATINGS:

Painting, protective coatings and the procedures used for the preparation of surfaces as per protective coating specification given in the bid document. Flanges are painted on the flange edges, inside boltholes, and up to the gasket surface. Piping are insulated where indicated on drawings. The piping to be insulated is grit blasted and given one coat of primer, only then insulation applied as per relevant Bid-Specification.

5.5 MECHANICAL:

Mechanical design broadly covers the following areas: ♦ General design requirements ♦ Material handling ♦ Pumps ♦ Personnel protection equipments ♦ Fire fighting equipments ♦ Process gas compressor ♦ Emergency generator ♦ Gas turbine ♦ HVAC Package ♦ Instrument / Utility air compressor The detail design requirements are as follows

5.5.1 GENERAL MECHANICAL DESIGN REQUIREMENTS

Unless otherwise stated all equipment shall be designed for location on outdoor area and must be able to operate in highly saline corrosive atmosphere in condition of high relative humidity.

All equipment shall be designed to meet the area classification defined in the job specification.

Maintenance and operational access requirements on all four sides and also over head / underneath shall be examined while engineering the platform facilities.

All package units shall be furnished as skid mounted equipments totally assembled, piped, wired and tested on a structural steel base frame. Drip pan with suitably connected drains shall be provided to avoid spillage of fluids on deck.

Structural design of the base shall allow for:

Static and dynamic equipment loads

Page 57: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 57

The design wind load Seismic loads Hydrostatic test loads Lifting, shipping and installation loads.

The quality assurance programme of the vendor (BS EN ISO9001) shall be submitted to company for approval to ensure that all work is performed in conformity with specifications & good engineering practices. The equipment shall be designed and selected for continuous duty unless otherwise specified.

Fly wheels, sheaves, shafts, coupling and similar hazards shall have removable safety guards which shall be sufficiently rigid to prevent deflection and shall be constructed from non sparking material.

Surfaces operating in excess of 60ºC and located within a distance of 2 m above floor shall be insulated.

Unless otherwise specified the offered equipment or equipment of similar design shall have been type tested and shall have been in continuous satisfactory service on offshore for a minimum period of 2 years.

The Design of various Mechanical / Rotary equipments shall conform to the principles described herein.

5.5.2 MATERIAL HANDLING FACILITIES

Adequate facilities shall be provided on the platform for the following:

Handling and transfer of equipment / sub-assemblies during routine maintenance

Handling and transfer of consumables like chemicals drum etc., between barges and respective consumption areas shall be in the most convenient matter requiring minimum time.

Movement of operating personnel through personnel basket

Material handling facilities are broadly categorized as follows:

A. Deck crane B. Electric operated monorail hoists. C. Chain pulley blocks.

A. DECK CRANE

The deck crane is utilized for handling of equipment, materials, drums and personnel baskets from offshore platform to barges & supply vessels and vice versa. The capacity of the crane is decided based on the design of the platform in the concerned project. The equipment shall be designed as per API 2C as evidenced by the placement of API medallion on the crane.

Page 58: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 58

The offered equipment model shall have been type tested and shall have been in continuous satisfactory service on offshore for a minimum period of 2 years. The crane shall be suitable for operation under the wind and ocean condition for the given project.

Codes & Standards The applicable codes & standards are as follows:

API SPEC 2C Specification for Offshore Cranes.

API RP 9E Recommended practice on Application, Care & Use of

wire rope for Oil Field Service.

API RP 2D Recommended practice for Maintenance & Operation of Offshore Cranes.

NEC National Electric Code.

IEC International Electro Technical Commission.

NEMA National Electrical Manufacturers Association.

ISO 3046 Reciprocating I.C. Engine.

EEMUA 107 Engineering Equipment & Materials User Association.

OSHA Occupational Safety & Health Act.

AGMA American Gear Manufacturers Association.

Boom

Boom shall be constructed of structural steel of ASTM A-36 or A 500 Grade B.

Boom shall be of lattice construction and be of sufficient length to reach the areas of platform which required lifting of equipment / material for maintenance purposes.

Boom rest shall be so provided so that the boom tip is easily accessible for maintenance of hoist pulleys.

A cat ladder shall be provided to enable reaching the tip from boom base.

Hoist & Ropes

• The crane shall have main hoist, and boom hoist winches driven by

hydraulic motors and fitted with automatic braking system. • Hoist shall employ power load lowering counter balance valve and shall not

lower against brakes. • Each hoist shall be equipped with brake of fail-safe type.

Page 59: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 59

• Wire rope for main and auxiliary hoist shall be non twisting type. • Wire ropes shall be suitable for use in marine environment. Swing

• The crane shall be capable of rotating 360º. • Adjustable stop switches shall be provided to enable limiting of crane

rotation, if required. • A lever operated parking brake shall be provided in the cabin, the same shall

be held off hydraulically during swing motion.

Mounting

• The crane shall be mounted on a pedestal support designed and furnished by the contractor as per requirement of API 2H.

• Crane cabin shall be approachable from the deck / intermediate working platform at all angles of crane position. A swing platform with ladder approach shall be provided all around the crane pedestal at a height such that it is 5 Ft below the swing mechanism for ease of maintenance and approachability of crane from platform in any direction.

Cab

• The cab shall be fully enclosed and equipped with shatter proof glass

windows and shall be mounted in such position so as to provide operator with full view of boom at all times.

• Stainless Steel load charts (one dynamic and other static) based on vendors ratings shall be placed inside the cabin.

Prime Mover • The primary power shall be supplied by a heavy duty preferably naturally

aspirated industrial type diesel engine for driving the hydraulic pump. • Flame trap in air intake and exhaust to be provided. • There shall be two starting systems Air and Hydraulic. • The hydraulic staring system shall include a manual hydraulic pump in

addition to the engine shaft driven hydraulic pump and accumulator. • The site rating of the engine shall be worked out considering de-rating in

accordance with ISO 3046. • For process platform where utilities are available, multiswivel connection for

power (paging and intercom), fuel and water shall be provided.

Electrical

All the equipment shall be selected in accordance with the area classification requirements.

The lighting system shall include two 400 W swivel type flood lights on the boom along with a red aircraft warning blinker light on tip of the boom and another on top of the crane frame.

Controls

Page 60: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 60

All controls shall operate in a fail safe mode. Brakes shall engage automatically when any control is placed in the neutral position and also in the event of engine power failure, loss of hydraulic pressure or control failure.

Provision shall be made of a hydraulic emergency stop to stop all functions of the crane without stopping the engine.

Control shall be designed so that one operator can conveniently perform all maneuvers and speed control.

An automatic safe load indicator shall be provided to give the crane operator a clear and continuous warning when the load being carried exceeds a figure not less than 90% of the safe working load of the crane at that radius.

Testing

• Operability test of crane at yard and at offshore after completion of

installation. • Rated lifting load operational test with boom at minimum and maximum

working radius. Both main hoist and auxiliary hoist shall be so tested. • All protective equipment and devices shall be tested.

B. MONORAIL ELECTRIC HOIST

Monorail Electric Hoists are utilized for removal of heavy equipment sub-assemblies such as rotors for Emergency Generator, Gas turbine, Process Gas compressor, Main Injection Pumps, etc. for overhaul / maintenance purpose.

The equipment supplied shall include monorail hoist with drive motors, flexible power supply cable with support rail, Pendant type push button control panel, limit switches, brakes etc.,

Codes and Standards Applicable Codes & Standards are as follows:

IS 3938 Monorail Electric Hoist BS 4465 Electric Hoist NEC National Electric Code NEMA National Electric Manufacturers Association

Testing

Load test shall be carried out at vendors work, fabrication yard and at offshore. Load test at 125% of safe working load shall be carried out in presence of the company / its authorized representative or certifying agency.

Page 61: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 61

C. CHAIN PULLEY BLOCK

Chain pulley block are widely used on process / well platforms to meet the material handling / maintenance requirements.

Codes and Standards The applicable codes and standards are as follows:

IS 3832 Chain Pulley Block BS 3243 Chain Pulley Block

For chain pulley blocks operating in hazardous area. The material of rubbing parts shall be of non-sparking type. Material for load hook shall be forged brass or aluminum bronze. Load chain shall be of alloy steel duly galvanized.

Testing

Load test shall be carried out at vendor’s works, fabrication yard and at offshore.

5.5.3 PUMPS

5.5.3.1 CENTRIFUGAL PUMPS :

Centrifugal pumps are the most commonly used equipments on offshore platform and cover a wide range of applications such as main injection pumps, Booster pumps, Sea Water Lift pump, Utility water pump, etc. The pumps shall be designed to latest edition of API 610. The vendor shall have produced at least 2 pumps of comparable type, rating and design from the proposed manufacturing plant and shall provide evidence of satisfactory operation of at least 8000 hrs when operating in similar conditions.

Codes & Standards

The applicable codes and standards are as follows:

API 610 Centrifugal pumps for petroleum, heavy duty for the chemical and gas

industry service. API RP500 Recommended practice for classification of location of Electrical

Installations at Petroleum facilities. API 670 Non contacting vibration and axial position monitoring system API 682 Shaft sealing systems NEC National Electrical Code API 671 Special purpose coupling for refinery service API 614 Lubrication, shaft sealing and control oil systems for special purpose

applications ASTM American Society for Testing & Materials ISO 1940 Balance Quality of Rotating rigid bodies ISO 518 Hydraulic performance standard ASME B 16.20 Metallic Gaskets

General

Page 62: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 62

• The equipment shall be designed and constructed for a minimum service life of 25

years and for an uninterrupted period of 5 years. • Balancing of axial thrust shall be achieved by means of individually balanced

impellers, opposed impeller arrangement or the use of balance pistons, however balance pistons shall not be used for applications involving the pumping of liquids containing abrasives.

• Net Positive Suction head available shall exceed the Net Positive Section head required by at least 1 m across the entire operating range, from minimum continuous flow to 125% of the rated capacity.

• Suction side of all pumps handling hydrocarbons shall be designed for full discharge pressure unless otherwise specified.

• The flexible coupling shall be designed for the maximum driver power and maximum speed and torque.

MAIN INJECTION PUMP

• Pumps shall be designed to meet the operating conditions of the water injection

service of the platform with the pumps operating in parallel and any one of the pumps as a standby pump.

• Pumps shall be HT motor driven and shall normally take suction from Booster pumps.

• Bearings of the pump shall be hydrodynamic type with force feed oil lubrication. • Lube oil system shall be common to driver and pump in accordance with API 614. • Main lube oil pump shall be shaft driven or separate AC motor driven. The

auxiliary lube oil pump shall be of same capacity and shall be AC motor driven. • An emergency D.C motor driven pump shall also be provided. • Lube oil shall be cooled with air fin type cooler. • All shutdown/interlocking, sequential start/stop shall be relay/PLC based and

shall be located in the unit control panel in the central control room. • Vendor shall provide all the alarms and shutdowns such as high vibration, high

bearing temperature, high motor amperage, low lube oil pressure, etc. required for safe operation of the pump.

• The key process parameters and machine parameters shall be made available on the DCS normally envisaged for the process platform

Testing

Performance & NPSH test shall be carried out with parameters recorded at rated flow, two intermediate points, minimum continuous stable flow and shut off (Performance only).

Full load mechanical test shall be carried out for the complete module including all contract equipment for at least 4 hours.

Sound level test. A continuous 72-hour run test at site shall be conducted for each pump.

BOOSTER PUMP

Booster pump shall supply water to main injection pump to provide adequate NPSH

required by MIP’s.

Page 63: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 63

Pumps shall be designed to meet the operating conditions as specified on the bid package with pumps operating in parallel.

The pump casing shall be axially split design for ease of maintenance. Pump shall be fitted with mechanical seals. Vendor shall provide High Vibration (Motor & Pump), High bearing temperature and

High motor winding temperature alarms and shutdowns for safe operation of the unit. Various operating parameters including alarms and shutdown shall be available at the

DCS normally envisaged for the process platform

Testing

♦ Each pump shall be tested for performance & NPSH test with parameters recorded at rated flow, minimum continuous stable flow. Two intermediate points, shutoff head.

♦ Full load Mechanical run test of the complete package shall be conducted using all contract equipment, auxiliaries and controls at rated flow for a minimum period of four hours.

♦ Sound level test shall be carried out

SEA WATER LIFT PUMP

Seawater lift pumps shall be motor driven vertical shaft type pumps for pumping raw seawater into de-oxygenation towers through filter.

Pumps shall be designed to operate in parallel with any pump being kept as standby, standby pump shall start automatically when any of the operating pump fails.

Non-reverse ratchet shall be provided to prevent reverse rotation of pump. Line shaft bearing shall be self-lubricating type, bearing material shall be suitable for

dry running during startup. Pump assembly shall be such that it can be lifted/dismantled for repair/maintenance

in the space available over mounting floor. Vendor shall provide alarm and shutdown signals for High vibration (Motor &

pump), High temperature (Motor bearing & Motor winding) and high motor amperage.

Testing

Each pump shall be tested for performance at rated speed preferably with full column

length assembly. Mechanical run test of the entire package shall be carried out with all contracted

equipments

FIRE WATER PUMP

Firewater pump installed on Offshore Platforms are Diesel Engine Driven vertical shaft type. The packager shall have engineered, manufactured, packaged, installed & commissioned at least two packages of similar or higher sizes for fire water services for offshore platforms and same shall have been operated successfully/satisfactory for a period of at least 3 years with out any major overhaul. The offered pump and diesel engine model shall be one from existing regular production range of the vendor. The major codes & standards applicable are as follows:

NFPA 20 National Fire Protection Association.

Page 64: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 64

API 610 Centrifugal Pump for General Refinery Service ISO 3046 Reciprocating Internal Combustion Engine. EEMUA Engineering Equipment & Material Users Association (Publication

No. 107) NEC National Electrical Code NEMA National Electrical Manufacturers Association. API RP 14C Analysis, Design, Installation and Testing of Basic Surface Safety

Systems on Offshore Platform. AGMA American Gear Manufacturers Association.

Complete package shall be designed and manufactured for continuous duty operation even though operation of the pump is intermittent.

Pump

♦ Pump assembly shall be such that it can be lifted and dismantled for

repair/maintenance in the space available over the mounting floor. ♦ Pump column shall be furnished in flanged section. ♦ Pump shall be installed in a caisson pipe. ♦ Thrust bearing shall be provided in the gearbox to withstand thrust load caused by

the pump. ♦ Line shaft bearing shall be self lubricated type and shall be suitable for dry running

during pump startup.

Right Angle Gear Box

♦ Gear Box shall be furnished with heavy-duty thrust bearing. ♦ Non-reverse racket arrangement shall be provided in gearbox to prevent reverse

rotation of pump.

Engine

♦ Diesel Engine Driver shall be in accordance with NFPA 20 & ISO 3046 ♦ The engine site rating should be at least 10% higher than the maximum power

required by the pump. ♦ The capacity of engine fuel tank should be sufficient for 24 hours continuous

operation at full load. ♦ Engine shall have two starting systems air and hydraulic starting.

Controls

♦ Pump control system shall be designed for single push button start of the auxiliaries,

driver and pump in proper sequence from a locally mounted push button station, remote control panel and console of DCS.

♦ Control system shall also include automatic starting by any of the following situations:

o Activation of low-pressure switch in the firewater header. o Melting of fusible plug in the pneumatic loop or activation of manual FSD

Station served by pressure switch mounted on vendors local control panel.

Page 65: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 65

o On receipt of signal from Fire and Gas Detection System, if the primary fire water pump fails to start after six cranking of the diesel engine or the primary pump is under maintenance an automatic signal shall start the first standby fire water pump if available on a bridge connected platform.

o Vendor shall furnish an Automatic type controller as per NFPA 20. o The Local Control Panel shall conform to NEMA 4 & 7.

Testing

♦ The performance test and mechanical running test for pump, gear and engine shall

be carried out as per the respective codes. ♦ Sound level test at equipment manufacturers shop shall be carried out for each

equipment to verify the estimated noise level. Sound level test of the package shall be carried out during package test.

♦ A package test shall be conducted using the contract equipment, auxiliaries and control for a minimum of 4 hours.

5.5.3.2 ROTARY GEAR PUMP

Rotary Gear Pumps are used for varied application on Offshore Platforms. Rotary Gear Pumps are used as diesel transfer pump, chemical transfer pump for oil corrosion inhibitor, gas corrosion inhibitor, demulsifier, pour point depressant and for any other similar use in accordance with data sheets.

Codes and Standards

API 676 Positive Displacement Pump – Rotary NEC National Electric Code NEMA National Electrical Manufacturer’s Association IEC International Electro Technical Commission

Design Requirements

♦ Pump shall be designed, manufactured and tested in accordance with API 676. (latest

edition) ♦ Integral Pressure relief valve shall be provided with each pump. ♦ Vendor to provide pulsation dampeners, if required.

Test Requirement Besides the test mentioned in API 676 following tests are carried out: ♦ Relief Valve Set Test ♦ Performance Test

5.5.3.3 CONTROLLED VOLUME RECIPROCATING PUMP

The pumps covered under this specification shall be used to inject chemical corrosion inhibitors in well heads to outgoing flow line. Codes and Standards

Page 66: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 66

The following codes (latest edition) are made part of pump specification.

API 675 Positive Displacement Pumps – Controlled Volume NEMA National Electric Manufacturer’s Association NEC National Electric Code IEC International Electro Technical Commission.

Design Requirements

Pump is to be designed, manufactured and tested as per latest edition API 675 and to suit saliferous environment.

All electrical equipment selected for hazardous area shall be certified by BASEEFA, UL or equivalent international testing agency. The pump shall be lightweight, compact and containing minimum number of working parts for maintenance. In case of gas driven pump the exhaust gas from pump driver shall be collected and taken to common header. All parts of the pump/pump driver coming in contact with utility gas shall meet the requirements of NACE as per MR-01-75. Also all valves, piping, fitting and instrument on the utility gas line shall meet NACE MR-01-75. Pulsation Dampener shall be designed as per ASME Section VIII Part VI. Pump to be provided with manual capacity control.

Test Requirement In addition to all tests as under API 675 the following tests have to be carried out.

Flow repeatability and linearity test Noise and vibration Relief Valve Test

PERSONNEL PROTECTIVE EQUIPMENT

As the safety hazard cannot be fully eliminated controlled or isolated by engineering means in the offshore environment, the use of personal protective equipments is enforced through various equipments described below ; all life saving equipment need approval by Statutory Authority & a certificate has to be submitted to company for approval.

Codes and Standard Following codes and standards (latest edition) are followed for all life saving equipments.

Specifications to the international convention on safety of life at sea (SOLAS) and its

amendments.

Page 67: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 67

USCG-CG-320 “ Rules and Regulations for Artificial Island and fixed structure on the outer continental shelf.

SURVIVAL CRAFT Survival Craft forms an essential part of the safety equipment on Offshore Process Platform and provides a safe means of personnel evacuation from platform in case of emergency. The survival craft shall be of totally enclosed type. Codes and Standards The applicable codes and standards are as follows:

SOLAS International Convention of Safety of Life at Sea NEC National Electrical Code NEMA National Electrical Manufacturers Association

Equipment Design

Survival Craft shall be constructed from fire retardant fiber glass reinforced plastic.

Craft shall be sea worthy for 100 years storms condition.

The survival craft shall be powered by suitably sized diesel engine of marine duty.

Diesel engine shall be provided with:

Hydraulic powered starting system with manual pump override

Manual starting with hand cracking

Complete radio system shall be supplied.

Launch platform shall consist of cantilever type structure to hold and support the

craft.

The winch shall be electric motor driven. The system shall be so designed to control the descent without the aid of electric power.

The equipment furnished shall have approval of statutory authority.

Vendor shall give an on site demonstration of the craft including launching and

recovery operation correspondence to full capacity.

Survival craft shall have approval of a Statutory Authority. INFLATABLE LIFE RAFTS

Each life raft shall be self-inflatable type installed in self launching mode

(inclined at 45º).

It shall confirm to SOLAS specification Chapter III.

Page 68: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 68

Material used for life raft shall be suitable for saline and corrosive atmosphere.

At least one life raft is provided on each cellar and main deck.

Inflatable Life Raft should not inflate in air.

Inflatable life raft shall have approval of Statutory Authority.

LIFE PRESERVERS (LIFE JACKET) AND MARINE WORK VEST

Life preserver shall provide 16 kgs (38 pounds) buoyancy in fresh water for 24 hours.

The buoyancy shall not be decreased by more than 5% after 24 hours of sub-mergence in fresh water. It shall be bright orange in colour.

Each life jacket shall comply with regulation of Chapter III of SOLAS.

Marine work vest shall comply with regulations of chapter IV of SOLAS – Marking

and labeling shall be screen-printed in water resistant, vinyl ink.

Life preserves and marine work vest shall be approved by Statutory Authority.

LIFE RING BUOYS

Life Buoy shall be capable of floating in fresh water for 24 hours, with a weight of 16 kg iron suspended from it.

It should be capable of withstanding a drop test into water from a height of at least 38

metres.

Life buoy shall have self igniting light.

Life ring buoy shall also meet the requirement of SOLAS regulation , Chapter III.

Life Buoy shall have approval of Statutory Authority.

FIRST AID KIT The contents of kit shall include the following item as minimum.

a) Triangular Bandages 90 cm (wide) x 127 cm (base) 08 nos. b) First Aid Dressing 06 nos. c) Burn Dressing 03 Nos. d) Roller Bandages 04 Nos. e) Water Proof Adhesive Tape 01 Roll f) Pre-medicated Adhesive Dressing Strips 10 nos. g) Cotton Wool (Sterilized) 03 nos. h) Ophthalmic Pads 2 nos. i) Antiseptic & Burn Ointment 1 j) Mouth to Mouth Resuscitation consisting of a short oral

airway with NRV 1 nos.

Page 69: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 69

The container shall be weatherproof box. Personnel Basket and Scramble Net

Each personnel basket shall be suitable for a minimum of six (6) men. Scramble net shall support a minimum of twenty four (24) men simultaneously.

Miscellaneous Items

Eye goggles – cup type, rubber framed Self contained open circuit compressed portable air breathing pack. H2S & Safety Information Chart Portable eye wash bottles.

5.5.5 FIRE FIGHTING EQUIPMENT

DCP SKID Dry chemical fire extinguishing system is means of applying dry chemical powder that can be automatically or manually activated to discharge through a distribution system onto the protected hazard. Dry chemical powder is composed of very small particles usually sodium bicarbonate, potassium bicarbonate based with added particulate material suspended by special treatment to provide resistance to packing, resistance to moisture absorption (baking) and proper flow capabilities. Codes and Standards

NFPA National Fire Protection Association. Standard No. 17 – Dry Chemical

Extinguishing System. ASME Boiler and Pressure Vessel Code. Section-VIII, Div. I

The offered DCP skid or DCP skid of similar design manufactured by the same supplier shall have been type tested and UL listed and shall have been in continuous satisfactory service on offshore for a minimum period of 2 years. General The type of hazard and equipment that can be protected using dry chemical extinguishing system consists of flammable liquid/gases/solids and electrical hazards. Dry Chemical Skid consists of following minimum equipment:

Nitrogen system Chemical Storage vessel Actuator system Hose Reel assembly

Design Requirement

A dual actuation (Manual/pneumatic) control system is provided for the DCP skid.

Page 70: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 70

DCP system to have capability of nitrogen cylinders and cartridges being replenished on the platform from indigenous source.

The amount of dry chemical in the system shall be at least sufficient for the largest

size Hazard protected, or for the group of hazard that are to be protected simultaneously.

The capacity of nitrogen cylinder is such that its adequate for the full time of discharge

of powder at required pressure.

The hose shall be non-collapsible type with all weather neoprene covering, conforming to NFPA requirements. Hose to be UL listed for their intended use.

Corrosion allowance for the dry chemical container shall be minimum 3 mm.

The nozzle shall be push lever type with pull pin designed for dry chemical service.

The nozzle should have an effective range of not less than 8 meters.

Number of DCP skid on process platform is finalized during detailed engineering based on equipment layout and safety norms. On well platform a DCP skid is placed on each cellar deck, main deck and helideck.

Tests

Operational test of each skid is conducted at fabrication yard and at offshore. FIRE BLANKET AND FIREMAN’S OUTFIT, STRETCHER

Fire blanket shall be processed with fire proofing chemical. Complete set of fireman’s

outfit shall be furnished in accordance with SOLAS.

Stretcher shall be rigid, in which injured person can be securely and comfortably strapped and hoisted. It shall be of bright orange type.

Fire blanket and Fireman’s outfit and stretcher shall have approval of Statutory

Authority.

Helicopter Rescue Kit Helicopter rescue kit shall contain:

a) Crow bar - 2 b) Fire Axes - 2 c) Bolt Cutter - 1 d) Fire Blanket - 2 e) Hand Safety Lamp - 2 f) Protective Clothing - 2 sets g) Hack saw - 2 h) Rescue Knives - 2

PORTABLE FIRE EXTINGUISHERS

Page 71: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 71

• All fire fighting equipment shall be designed according to following codes/standards.

NFPA National Fire Protection Agency API RP 14G Recommended Practice for fire prevention and control on

offshore production platform. API RP 2G Recommended practice for production facilities on offshore

structures. ISI Indian Standards Institution standards

♦ All extinguisher have to be ISI stamped. ♦ Extinguisher shall be suitable for Class B,C & E fire as per IS:2190. ♦ Dry Chemical shall be potassium bicarbonate based with properties confirming

to IS:4308. ♦ CO2 extinguisher shall be as per IS 2878 ♦ Fire extinguisher used on offshore platform are generally:

10 kg dry chemical extinguisher 4.5 kg CO2 extinguisher 3 kg CO2 extinguisher

• All extinguishers shall be portable type with a carrying handle and wall hook or bracket for

mounting when not in use. Each extinguisher to be installed in weather proof box. PROCESS GAS COMPRESSOR

The centrifugal compressor is used to compress associated gas or free gas produced in offshore platform for transmission to onshore terminals. The compressor design is based on API-617 and the codes referred therein. The basic input data relating to the design of a compressor are obtained from the project conceptual report. Codes & Standards The major codes & standards associated with Process Gas Compressor are as follows:

API 617 Centrifugal Compressors for General Refinery Service.

API 616 Combustion Gas Turbine for refinery service.

API 614 Lubrication, Shaft Sealing & Control Oil System for special

purpose application.

API 670 Vibration & Axial position & Bearing Temperature Monitoring Systems.

API 671 Special purpose coupling for refinery service.

API 661 Air cooled heat exchangers for refinery service.

API 613 Special purpose gear unit for refinery service.

Page 72: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 72

API RP 14C Analysis, Installation & Testing of surface safety systems on offshore production platform.

API 676 Positive displacement pump rotary.

ASME PTC 10 Test code for compressors and exhausters.

ASME SEC VIII DIV. 1

Pressure vessel code.

ANSI American National Standard Institute.

ISO 1940 Balance Quality of Rotating rigid bodies

Compressor & Module Design:

• P&ID furnished in the bid are the preliminary estimates based on ideal gas. This is

indicative of the compressor module vendor’s scope at the battery limits. • Based on the above parameters the compressor manufacturer shall carry out the process

design based on real gas, preferably using the BWRs relations.

• Performance Guarantee shall be provided at the rated conditions as provided in the specification.

• Vendor data requirements, including performance curves for different sections and also

composite curves, shall be as per the API 617 code.

Vendor is required to furnish a single lift compressor module capable of fitting in the space allocated for module in tentative layout drawing of the platform. Safety requirement for module design are as per API-RP-14C, 14G and 14F and OSHA. Structural analysis shall be as per API 617 and codes referred therein shall be complied. Fire detection system based on UV and thermal detectors and a fire suppression facility consisting of CO2, water sprinklers and clean agent system (control room) shall be provided.

Sealing System Compressor sealing system may be gas seals or liquid seals as specified in the bid specifications. Seal oil system shall be designed as per API 614. For oil shaft seal provision shall be made for an overhead tank having sufficient capacity to last for total period of run down and isolation of compressor train. Seal oil chosen shall have a life of over 12 months.

Knock out Drum (KOD)

Page 73: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 73

The KOD shall be ASME coded vessel. The sizing follows from the inter stage pressures and volumes arrived from the process design by the vendor.

Coolers • Design shall be based on 14 deg. C approach to maximum ambient site temperature

specified in the project specifications • The mechanical design shall be based upon ASME code. • Air cooled design shall be employed unless specified otherwise. • The material of cooler shall be selected to provide for a cooler life of 25 years.

Piping All gas piping shall be of 316L. The vendor shall ensure low pressure drops by adequate sizing as per good engineering practice.

Instrumentation System The control system is designed for automatic remote control start up and shut down. The compressor train shall be provided with suitable antisurge protection and load sharing system (if required)

Gas Turbine Driver

• Gas turbine driver shall be simple cycle , preferably heavy duty industrial type, having adequate track record in offshore experience as specified in the bid package.

• The site rating shall be base continuous with 105% margin over the power required at site ambient temperature specified for the project. Fuel System Gas turbine shall be equipped with dedicated fuel gas treatment system capable of handling saturated gas as a measure of protection against failure of gas turbines. The complete fuel conditioning system construction shall be of SS316L. Inlet Air system The air filtration system shall be 3 stage marine type having filters of washable/disposable type. The minimum design life of filter elements shall be 6 months for the condition prevailing at site. The construction of inlet system shall be of stainless steel. Lube oil system A combined lube oil system based on API 614 for compressor, turbine and gearbox (if any) shall be provided. Exhaust System

Page 74: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 74

The exhaust stack shall be preferably straight up type . the material shall be selected to ensure the design life of the platform. Testing Requirements

For the major components the following are the tests:

Performance Test of Compressor as per ASME PTC 10 Mechanical Run Test of Compressor as per API 617 Performance and Mechanical Test of Gas Turbine based on ASME PTC22 and

API 616 respectively. Gear unit test for load

Full Module Tests:

Full Load Full Speed String Test of the module

This test shall be conducted for 4 hours. This test is conducted with all auxiliary contract equipment.

72 hour site commissioning test

This is the final test before handing over the unit in the platform and is a non stop 72 hour test to establish the equipment performance in actual conditions

EMERGENCY GENERATOR Emergency Generator is a diesel engine driven generator used for emergency power generation and supplies power to motors, communication equipments, lighting and utility loads on the platform during periods when the main generating sets are shutdown and during platform start-up. It takes emergency and critical load of platform and is also used in Black Start of platform. Codes and Standards

ISO 3046/ BS-5514 Reciprocating IC engines ANSI American National Standard Institute ASTM American Society of Testing of Materials NEC National Electric Code NEMA National Electrical Manufacturer’s Association IEEE Institute of Electrical and Electronic Engineer’s IEC International Electro-technical Commission EEMUA Engineering, Equipment and Material User’s Association

(Publication No. 107) “Recommendation for the protection of diesel engines operating in hazardous area”.

API RP 14C Analysis, design, installation and testing of basic surface, safety system in offshore production platform.

Prime Mover

Page 75: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 75

Prime mover is diesel fuel operated, water cooled, naturally aspirated or turbo charged engine.

Diesel engine is designed for continuous duty indoor location on an offshore platform. The offered diesel engine shall be one of regular production models of the manufacture for offshore industrial application and already type tested. In case the proposed engine model has not been type tested, vendor to furnish a reference list of its existing installation and atleast two of these engines should have completed 8000 hrs (each) of continuous running on offshore installation. The engine is rated to continuously develop net electrical power equal to the specified generator continuous rating (in addition to the electrical power requirement for emergency generator auxiliaries) under the worst site condition as indicated in generator data sheet. The engine shall also be capable of providing an overload power of 110% of the continuous rating at the same crank shaft speed for one-hour with or without interruption, within a period of 12 hours of operation. De-rating of engine to be done in accordance with ISO-3046 / BS-5514. The engine shall have positive displacement, gear type lubrication oil pump for supplying oil under pressure. The engine shall be equipped with an air motor starting system. Diesel engine driven compressor along with suitably sized air receiver for black start condition. Additionally, the engine has hydraulic start system with provision of priming by engine or hand.

Generator

Generator rating indicated in the data sheet shall be the net output of the set after accounting for all auxiliaries for the prime mover and generator. Generator voltage to be 415 v.

Generator shall be suitable for operating in parallel with normal power supply of the platform. Generator to operate satisfactorily under sudden load rejection and sudden load application. In case or sudden application of full load at rated power factor, the voltage drop shall not exceed 15% of the rated voltage. The rated voltage shall be restored within 0.5 to 0.8 secs. The voltage regulation of the machine shall be within ±2% of the nominal voltage. The generator shall be suitable for continuous operation at rated load for a frequency variation of ±3% of rated value. The generator shall be capable of withstanding 10% overload for one hour and 50% overload for one minute. The control of emergency generator shall operate in fail safe mode. The generator set shall function as per one of the following scheme:-

Auto main failure scheme (AMF)

Page 76: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 76

Manual start in service mode Manual test mode

Testing of Emergency Generator

String Test

String test is carried out on complete diesel engine generator as per electrical specification.

Site Test The complete emergency generator set shall be tested at site in accordance with IEC-46.

Shop Test Engine to be tested separately at engines manufacturer’s shop as per diesel engine data sheet and ISO 3046. The engine generator set shall be run at synchronous speed non-stop for two(2) hours, at it rated capacity.

GAS TURBINE

The Combustion Turbine employed in Offshore projects is a simple gas cycle machine to be designed in accordance with API 616 (latest edition). The turbine may be Industrial or Aero-derivative type. Turbine Driver for Mechanical drive requirements e.g. Process gas compressor are two shaft machines whereas turbine for Power generation requirements may be single or two shaft designs. The turbine shall be capable of supplying the power requirement with the specified power margin on a continuous duty basis based on the stated site and environmental conditions specified in the bid package. The power ratings shall include all site and operating allowances such as inlet and exhaust losses (including losses discharging through the Waste Heat Recovery Unit if specified for the project). As the process facilities are designed for a life of 25 years the gas turbine shall be designed and constructed for a period of 25 years. The gas turbine and auxiliary equipment shall be suitable for at least three years of uninterrupted continuous full load duty. Codes and Standards Some of the major codes and standards associated with the Gas Turbine are as follows:

API 616 Gas Turbine for refinery service API 614 Lubrication, Shaft sealing and control oil systems for special Purpose applications API 613 Special purpose gear units for refinery services API 671 Special purpose coupling for refinery services API 670 Vibration and Axial position and Bearing Temperature API 661 Air cooled Head exchangers for General Refinery Services

Page 77: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 77

ASME PTC22 Performance Test Code for Turbine ASME B31.3 Codes for Chemical Plant & Petroleum Refinery Piping API RP500 Classification of areas for Electrical Installations ISO 1940 Balance Quality of Rotating rigid bodies

The other project specifications for Instrumentation, Piping fabrication & Installation, Insulation, Pressure Vessel, Specification for welding, etc. are made a part of specification for Gas Turbine. Gas Turbine Selection The Gas Turbine catalogue ratings are at ISO conditions which are :

Ambient Temperature - 15 deg.C Attitude - 0’ Relative Humidity - 60% Ambient pressure - 101.3 kpa Driver Catalogue rating = Driver Site rating + Power loss due to environmental conditions Driver Site rating = Driven equipment power requirement + Drive loss in gearbox & coupling + Power margin While making power calculations various losses are considered on following account: Gearbox loss – around 2% Electrical Generator loss – around 2% Inlet and exhaust loss – around 1% Loss on account of humidity as per standard curve Loss on account of elevation as per standard curve Loss on account of suction air temperature as per standard curve Based on the power calculations with losses on above basis, the gas turbines with proven offshore track record may be selected. As per existing criteria turbine models having completed satisfactorily at least 8000 hrs. of continuous operation on the offshore installation under similar operating conditions are considered. The following Performance guarantee are taken from the vendor with no negative tolerance:

Gas Turbine site rated power output (MW) Gas Turbine heat rate at rated output (KJ/KW-hr)

Gas Turbine enclosure

The Gas turbine shall be enclosed in a weather proof and noise attenuating housing. The auxiliary system like lube oil system requiring routine maintenance shall be housed outside the enclosure. Enclosure ventilation shall be provided with electric driven fans with 100% standby capacity.

Page 78: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 78

For power generation application the enclosure shall be maintained at a pressure of at least 5mm of water less than atmospheric and for Process gas Compressor at a positive pressure of at least 5mm of water by operation of only one ventilation fan. An interlock shall be provided such that in the event any enclosure door of the turbine is not properly closed/gets opened due to any reason the turbine should automatically shutdown/its start blocked.

Fire and Gas Detection

The enclosure shall be designed with gas (Hydrocarbon & H2S) detection, fire detection and fire suppression system. The detectors shall provide a two step alarm (20% and 60% LEL, 10ppm & 50ppm of H2S) of rising concentration of gases before the hazard level (100% LEL/100ppm H2S) is reached. The coincident detection of the 60% LEL of gas or 50ppm H2S shall ensure shutdown with cut off of fuel gas supply. The manifestation of fire is sensed by either Ultraviolet light detectors or Fixed temperature thermal detectors. Fire extinguishing in the enclosure is by CO2 or clean agent fire extinguishing type. Fire suppression system shall be so designed that it can be activated automatically by receiving a signal from coincidental UV detection or thermal detection or can also be manually activated by an operator.

Lubrication system

The lubrications system of turbine and it’s driven system shall confirm to API-614. Lube oil may be cooled with air fin fan type of coolers with standby fan sized for 100% capacity. The main and standby lube oil pumps shall be powered by AC motor if main lube oil pump is not shaft driven as per vendors standard. An emergency pump powered by a DC motor to provide lube oil for coast down and cooling period. A common portable lube oil purifier and a trolley mounted lube oil pump for filling/draining out from reservoir are also included in turbine system.

Coupling and Gear Box

The couplings shall be flexible non lubricated type as per API 671 with a non sparking guard. The gearbox if required between the gas turbine and driven equipment shall conform to API 613. Performance test shall also be conducted on gearbox at full speed and full load in accordance with API 613. Fuel Gas System

Page 79: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 79

The fuel gas treatment system for the gas turbines shall be designed for ISO rating of the gas turbine or shall meet the turbine starting acceleration requirements whichever is higher. It shall consist of twin knockout pots for removal of condensate with level indication and auto drain taps, fuel strainers/filters with differential pressure indicator and alarm and fuel gas super heater. All liquid/gas fuel piping and valves shall be in 316L stainless steel or higher grade as required.

Air intake and exhaust system

The intake air system including ducting, intake filter frames, plenum and hardware shall be manufactured from SS316L material suitable for withstanding the corrosive marine environment. The filter system shall be designed to meet the mandatory filteration standards prescribed by the turbine manufacturer but as a minimum shall meet the following requirement:

Removal of 99% particles greater than 5 micron Removal of sodium or potassium chloride concentrations greater than 0.01ppm Average synthetic dust weight arrestor as per BS6540.

The air filter shall be 3-stage marine type described as under:

1st stage: Washable type Pre filter for maximum solids/salt removal and water

coalescence. It should be possible to remove the 1st stage filter cartridge during turbine operation for maintenance.

2nd stage: High efficiency type filter to remove smaller particles passing through 1st

stage. 3rd stage: Inertial vane separator bank to remove water particles retained in the air

flow.

• Filter elements shall be washable type and minimum expected life shall be 5 years. The Air intake filter shall be oriented in such a way that no exhausts/vents are re circulated in the gas turbine intake system.

• The exhaust system shall be so designed so as to preclude the possibility of heating of other equipments, causing hinderance in Helicopter flight paths and crane operations.

• HC gas detectors shall be provided inside the air intake system.

General Mechanical Requirements a.

Noise level of any point of package including ducts shall be such as to restrict the noise level to within 88 dBA at any point located 1m away from surface.

Surface temperature of any exposed part likely to come in contact with humans shall not exceed 60 deg.C.

Page 80: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 80

Vendor shall include a crank detergent/water wash cleaning system including one set of common portable washing equipment.

Access to the turbine and associated auxiliary equipment on the skids for operation and maintenance is of utmost importance. The contractor shall include all lifting points, monorail electric hoists, overhead cranes, etc. necessary for handling maintenance lifts till the designated material handling area on the deck.

Controls

All the turbine controls shall operate in a fail safe mode. The control system shall be designed for local and remote startup and shutdown. The control system shall be distributed microprocessor based consisting of redundant microcomputer section with video display and membrane keyboard for operator interface. The system shall be provided with sufficient level of redundancy such as processor and power supply so that a single failure would not cause total shutdown. The system shall have self diagnostic feature to card/module level so that in case of failure of the concerned card/module can be removed, repaired and returned to service without interrupting operation of unit. The system shall have non volatile memory or shall have battery backup. A programming unit shall be provided for the system to enter/alter program. The critical parameters of the machine shall be duplicated in the DCS ( Distributed Digital Control System normally envisaged for the process platform ) operators monitoring, event/alarm logging, trending and periodic logging through serial digital communication interface. The local control panel and local gauge panel shall be mounted locally on the skid whereas the UCP shall be in the CCR.

Startup and shutdown

The turbine drivers shall be equipped with AC motor driven starting system. The system shall be designed to provide reliable programmed starting, acceleration and full load operation of the unit along with shutdown of the system . Vendor shall provide suitable alarms and shutdowns such as over speed, high temperature, high vibration etc for safe operation of the unit. Testing

The turbine shall be subjected to a mechanical running and performance test (ASME PTC 22) to confirm its performance, power generation, fuel consumption, vibration levels etc.

Page 81: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 81

A mechanical string test (full load, full speed) for not less than four continuous hours shall be carried out with all contractor supplied driven equipment including gearbox, lube oil system, control system, etc. specific to the project. The test shall include but may not be limited to verifying the performance of such system as :

Run down without AC power Package control & instrumentation system Package safety systems such as shutdowns, alarms, sensors and monitors.

Noise test shall also be carried out on the gas turbine during testing.

Tools and spare parts The contractor shall provide a recommended spare part list to cover the commissioning and one year operations. The contractor shall provide special tools for the erection, operation and maintenance of the gas turbines including boroscopic tools with camera. HVAC PACKAGE

The HVAC system shall be used to maintain desired environmental conditions inside the living quarter module, switchgear module, TG control room, etc. on the offshore process platform. The system shall comprise of two components namely: A. Chilled water type centralized air conditioning system comprising broadly:

♦ Compressors with drivers ♦ Condensers ♦ Chillers ♦ Air Handling Units (AHU’s) ♦ Chilled Water Pump ♦ Network of Refrigerant Piping, ductwork and controls.

B. Ventilation system comprising:

♦ Supply air fans with drivers ♦ Exhaust fans ♦ Duct work with dampers ♦ Associated instruments & controls.

The offered equipments or equipment of similar design manufactured by the same supplier shall have been type tested and shall have been in continuous satisfactory service on offshore for a period of 2 years. Codes & Standards The major codes and standards to which the equipment shall comply are as follows:

ASHRAE American Society of Heating, Refrigeration & Air Conditioning

Engineers

Page 82: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 82

NEMA National Electric manufacturers Association. NEC National Electric Code. SMACNA Sheet Metal & Air Conditioning Contractors. AMCA Air Moving & Conditioning Association. ARI American Refrigeration Institute. NFPA National fire Protection Association. ASTM American Society for Testing and Materials.

Air Conditioning System

♦ A centralized air conditioning plant working on chilled water system or Direct

Expansion (DX) shall be provided. ♦ Outside air for air conditioning, ventilation and pressurization shall be taken from a

safe area as classified in the area classification drawing. The exhaust of ventilated areas shall be let into safe area.

♦ Areas to be air conditioned shall include as a minimum the following:

Living quarter accommodation (except those requiring spot cooling) Switchgear Room Control Room RTU Room Recreation room Lounge/Library Conference Room Radio Room All workshops including Machine shop, Electronic/Electrical shops, stores

♦ Areas to be spot cooled are as follows:

o Kitchen / Tea Room o Laundry & Wash Room o Toilets & Shower Room

♦ Areas to be ventilated shall include:

o Battery Room o Emergency Generator Room o Transformer Room

♦ No return air is to be taken from laboratories, dining hall and infirmary. ♦ All areas which are air conditioned shall provide guaranteed inside conditions as

specified in the project conditions and all equipment shall be suitable for meeting the worst outside ambient conditions as specified for the project.

Chilled Water Package • Chiller package shall comprise of compressors, driver, chiller, air cooled condenser,

associated hookup piping and fittings. • There shall be 100% standby for chilled water packages. • Separate chilled water pump set shall be provided with each chiller package

(working or standby).

Page 83: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 83

• The system shall provide adequate interchangeability so as to operate any chiller package with any chiller pump of the system under consideration.

• Refrigent utilized for chilled water package shall be environment friendly (non zone depleting).

Air Handling Unit (AHU)

• Air handling unit shall comprise air filters, dampers, chilled water coils, electric

heaters, centrifugal fans etc. • Each AHU shall be equipped with two nos of centrifugal blowers each of 100%

capacity. • In the event of failure of air conditioning system the blowers would continue to run

to maintain the specified positive pressure.

Pressurization

• Positive pressurization of around 5mm of water gauge shall be maintained at all times in the areas specified in the project.

• A purge cycle shall occur upon startup and upon a loss of pressurization. • Humidity and temperature control are not necessarily maintained during purge

cycle. • Non-explosion proof electrical equipments shall be energized only after the purge

cycle is complete. Ventilation

• The areas shall be ventilated at the rate of 12 air changes/hour or based on maximum

room temperature rise of 5ºC whichever gives higher air change/hr. • For emergency generator actual dissipated heat rejection of generator at full load to

be considered for ventilation requirement of emergency generator room. • Ventilation for battery room and emergency generator shall be by means of forced

filtered air supply and forced air exhaust system.

Control System

• The control system should incorporate basic controls in the control panel to maintain constant room temperature, humidity and positive pressure as specified in the project specifications.

• Room conditions shall be controlled with the help of room mounted thermostats and humidistat.

• Control circuit and interlocking shall be provided so that compressor shall not start unless:

o The AHU fan motors are switched on o The condenser fan motors are switched on o The chilled water pump motors are started

Testing

Page 84: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 84

• All the equipment shall be performance tested at the manufacturers works as per the relevant code and standards. The chilled water piping shall be checked for proper insulation and leakage.

• Dry & wet bulb temperature of the various constituents of the system shall be checked.

• The building pressurization (5 mm of water column ) shall be checked.

I/U AIR COMPRESSOR The instrument & utility air requirement of the process platform are met through the Instrument & Utility Air Compressor cum Air Drier Package. The compressor can be reciprocating type complying with API 618 or screw type designed in accordance with API 619. The system broadly comprises of Electric Motor Driven Compressors, Air Inlet Filter & Silencers, Moister Separators, Intercoolers & After Coolers, Twin Tower Heatless type absorption air driers, Control System etc. Codes & Standards

API 618 Reciprocating Compressors for General Refinery Service. API 619 Rotary type positive displacement compressors for petroleum,

chemical & gas industry service. API RP 500 Recommended practice for classification of locations for Electrical

Installation at Petroleum facilities. API 661 Air cooled heat exchangers ASME SEC. VIII Pressure vessel and boiler code ASME 31.3 Process piping NEMA National Electrical Manufacturer Association ASTM American Society of Testing Material NEC National Electrical Code

Compressor Design Requirement

• The compressor package capacity shall be selected after taking into account the losses

due to air drier purging and leakage losses. • Reciprocating type compressors shall be Non-lubricated, heavy duty industrial,

water cooled type with closed circuit cooling tower. • For screw compressors each compressor shall be fitted with an oil separator for

provision of oil free air of a maximum contamination of 5 ppm. • Each compressor shall be fitted with a relief valve (for each stage) that can not be

isolated, sized for full compressor (stage) capacity. • The package shall be provided with an automatic capacity control system which shall

function by suction throttling (screw compressor).

Air Dryer

• A dual air drier set shall be installed downstream of utility air receiver. • The air drier assembly shall be a heatless, solid desiccant type with twin tower each

sized to supply dry air continuously and meet the rated capacity of package. • Regeneration shall be by means of compressed air.

Page 85: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 85

• The unit shall be arranged for automatic change over such that one tower is always under drying and the other under regeneration. Visual indication shall be provided on local panel to indicate the state of each vessel (drying / regeneration).

• The desiccant shall be activated alumina or equivalent. • Adequate openings shall be provided on each dryer vessel to enable the loading /

unloading of desiccant without dismantling the vessels or pipe work. • Sampling provision for air dew point measurement shall be provided.

Vessels

ASME code stamp shall be provided on all pressure vessels. Corrosion allowance of 3 mm shall be applied for C.S. parts of vessels.

Filters

• Upstream and downstream of the dryer assembly shall be a set of pre-filters and after

filters respectively. • Both filter assembly shall consist of two 100% capacity units each arranged in parallel

& provided with an automatic drainer. Controls

• Local panel shall have alarm and shutdown devices for high vibration, high

condensate level, low lube oil pressure, high discharge temperature etc. for safe operation of the unit.

• Various process and machine parameters shall be available at the platform DCS.

Testing

• Compressor shall be performance tested at manufacturers works at their rated speed, capacity and pressure in accordance with the relevant codes.

• All pressure containing parts shall be hydrostatically tested to 1.5 times their respective design pressure.

5.6 STRUCTURAL:

The concept and design of offshore structures are based largely to suit process requirements, design service life, space and weight of equipments and utilities, water depth, environmental parameters and geo-technical parameters etc. and the cost of the structural system is significantly governed by the cost of fabrication, transportation and installation. At present in our country in offshore operational areas, fixed offshore platforms are being constructed for the water depth ranging between 40m & 90m.These fixed platforms, consists of a large multilevel deck structure supported on template, usually called a Jacket, is three dimensional welded frame of tubular members and is rigidly connected to sea bed by means of the piles. The decks provide necessary facilities on wellhead platforms and for support buildings, compressors, generator, storage tank, equipment module and related facilities.

Page 86: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 86

In order to establish the design criteria, the following codes and standards (latest amendments) are adhered and are globally acceptable:

API RP 2A Recommended practice for planning, designing and constructing fixed

offshore platforms- Working stress design of American Petroleum Institute.

AWS D1.1 Structural Welding code of the American Welding Society (AWS) provides the design guidance for structural welding of tubular members & joints.

AISC, 9TH Edition Manual of steel construction, Allowable stress design of American Institute of Steel Construction.

On the basis of operational philosophy, the platforms are classified into two broad categories: The unmanned platforms are those platforms where operator’s intervention is required normally occasionally for carrying out well testing and maintenance/checking of facilities. These platforms are of smaller sizes and a conventional platform is having four-legged jacket sub structure, two major decks (cellar and main) with defined well head area and building module below the helideck. The manned platforms are basically process platforms with facilities for processing of oil/gas gathered from number of well platforms. As such, the process platforms of multiple facility providers cover large space and heavy structural loads of different modules installed over decks .In general, these platforms of multilevel deck structure installed on 6-8 legged jacket structures. Structural Design Philosophy

The In service analysis consists of In place and fatigue analysis and is performed in order to find the structural response of the structure during operating life of the platform. The In-place analysis covers the environment loads response due to extreme loading & operating loading conditions applied to check the soundness of the structure along with self, live loads and accidental loads. Loads acting on an offshore structure are added up in different logical combinations to arrive at the maximum possible loads, which are likely to occur during the service life. The Fatigue analysis of jacket tubular joints subjected to repetition of stress due to the cyclic nature of wave loading is analyzed for fatigue endurance. The deterministic fatigue analysis as outlined in API RP 2A is performed for the platforms. The Pre service analysis covers the following activities, which are required from fabrication yard till the installation is completed. Load out analysis, (Either by skidding or by trailers). The structure shall be checked for adequacy for the proposed load-out operation and for the effects of the localized loadings.

Transportation analysis: The jacket and topsides are checked w.r.t transportation loads exerted during towing from fabrication yard to the installation site. A dynamic motion response analysis of barge/ structure system is carried out to determine the maximum loads imposed on the structure and the sea fastening members during the course of voyage from fabrication yard to off shore side.

Page 87: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 87

Lifting analysis: The topside is analyzed for installing by direct lifting from cargo barge. Jacket will also be analyzed for lift condition during various upending stages for final installation.

Launching analysis: Monitors the jacket behavior and to check the structural integrity while launching.

Floatation and upending analysis: Flotation analysis of jacket is carried out using static interactive approach to calculate the stable equilibrium position of natural floating. Calculation of individual sling loads, hook loads and ballasting requirements at successive stages to raise the jacket from its free floating position to an upright position till the jacket finally set into the sea bed

On bottom stability analysis: For checking the jacket stability and mud mat for structural integrity, when it is seated prior to piling and during initial piling on defined Environmental parameters and installation conditions.

Pile drivability analysis: The analysis consists of three definite steps. First, the driving resistances that can be overcome by a particular hammer- pile –soil system determination, second the pile wall thickness is adequate & Third, the sectionalistion of the pile (add-on lengths) from dynamic and static stress considerations.

BASIC LOAD CASES AND LOAD COMBINATIONS:

Load parameters: The design loads for the analysis are considered in the following categories.

o Dead loads: All permanent structured modeled as well as non-modeled

structural items of permanent nature come under this category. o Live loads: The design live loads for local beam/plate design and global

design (truss/framing) are defined in terms of uniform distributed loads over the areas.

o Equipment and piping loads: The dry, operating and hydro test weights of equipments, piping including pipe supports, electrical cables and trays, and other machines are covered in this category.

o Operating loads: Covers vessels designed with full of liquids/water, vessels for gas, gas lines, and liquid lines in full conditions.

o Environmental loads complies the following parameters, which are applied on all structural components during detailed Engineering.

o Wave and Current forces: The design wave is treated as a regular wave ‘STOKE’ fifth order theory and is used to compute water particle kinematics, using apparent wave period computed as per API RP 2A.

o Wind forces: The wind forces are calculated taking into consideration shielding shape coefficients and variation of wind velocity with height as specified in API RP 2A.Wind are assumed to act simultaneously and collinearly with wave and current forces. Sustained wind and gust of appropriate duration are used as per API RP 2A for different global and local analysis of platform components.

o Earthquake loading: The earthquake loading on the platform structure shall be calculated using response spectrum method in accordance with the provisions of API RP 2A. The response spectrum data for this analysis follows the guidelines of Zone IV earthquake as given in Indian Standard IS-1893.

Page 88: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 88

On the basis of environmental parameters, the wave, astronomical tide, current profile and wind velocities are taken into consideration for design. Defined contingencies are allowed for any weight variation or inaccuracy in load data during early stages of detailed engineering. The In place integral-structural analysis of the idealized deck- substructure (jacket)- soil system is performed on different load combinations for substructure, deck and building modules.

The major loads which are taken into account for combinations are Environmental loads (Extreme storm wind, wave & current, Operating storm wind, wave & current), Structural dead loads, Equipment & piping weights, open / UDL live loads, crane dead and operating loads, riser dead loads, and reaction from modules.

A typical load combination for substructure analysis is as under:

Load combination no. 1 Extreme storm condition with operating loads Load combination no. 2 Operating storm condition with operating loads Load combination no. 3 Extreme storm condition with empty equipment to check the

capacity of the piling under the max. Uplift force. Load combination no. 4 Earthquake with operating load. Load combination no. 5 Modular rig load with extreme & operating storm

A typical load combination for deck structural and Building frame analysis is as under:

Load combination no. 1 & 2

Extreme storm condition with operating loads

Load combination no. 3 & 4

Operating storm condition with operating loads

Load combination no. 5 Normal operating loads plus crane operating load. Load combination no. 6 Earthquake with operating loads. Load combination no. 7 Modular rig load with extreme & operating storm

Individual panels of jackets and decks are separately analyzed as required to check their integrity. Stresses and deflections up to Allowable limits are permissible in confirmation to those allowed in API RP 2A or AISC. The structures are designed safe for all stages of in service, and pre service stages (viz. load out, transportation, floatation and upending, on bottom stability, pile drivability) and fabrication. Seabed Features: The Jackets are designed for seabed slope and to meet the installation tolerances. If the seabed slope is such as to tilt the Jacket by an angle exceeding 25 minutes, the slope is considered in design. Design of the Jackets also considers mudslide, if any. If the slope in seabed is such as to tilt the structure by an angle exceeding 1 in 100, the detail design takes into account the slope in seabed in the form of adjustment in framing and/or mudmat elevations. Platform Configuration:

Page 89: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 89

The platform is sized and designed in accordance with the approved equipment layout and arrangement. The equipment weights, sizes, clearances, and space requirements for personnel movement and maintenance purposes, are considered for the determination of platform size and equipment arrangement, and necessary provision is kept in the layout. The consideration in HAZOP study is incorporated. Installation Philosophy: Generally, the Jacket and Topside modules are installed offshore by derrick barge. Such type of lift installation is highly economical. Water Depth: For the design of substructure appurtenances, a provision for the variation of ±1.0m in the actual water depth is usually allowed. Marine Growth: All the framing braces between the jacket level and the first horizontal level are fitted with an ocean powered marine growth prevention system. The design of platforms generally includes full allowance for marine growth on all members of the jackets and appurtenances including risers, caissons etc. Geometrical Considerations: The top horizontal framing of the substructure is designed to be at a minimum elevation above chart datum level, so as not to be in wave splash zone. Minimum air gap requirement as per API RP 2A is also considered. Structural Analysis: All structural analysis is performed using a suitable structural analysis computer programme. The datum for the axes is the Platform Datum. The modeling techniques used are chosen appropriate for the structure, the analysis being undertaken and normal industry practice. All analyses utilize the same base model. That is, the in-place model forms the basis for all the other analyses to be performed. The in-place analyses includes a combined Jacket and Topsides model to ensure the correct soil pile-structure stiffness interaction. Non-linear pile foundations to the Jacket are considered for the analysis and design of the jacket. The Jacket model considers the effect of environmental loads on the appurtenances including anodes, boat landing, barge bumpers, conductors, risers and riser guard etc. All structural analyses are performed using a suite of programs applicable to the design of offshore structures. The analyses demonstrate the adequacy of the structures under all envisaged phases and anticipated loading. Analyses generally include, but are not limited to:

IN-SERVICE CONDITION

Page 90: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 90

• In-place operating and extreme storm • Foundation Design- Pile Analysis & Design • Fatigue • Seismic • Accidental loads (The scope is of which is generally determined by the Contractor

and approved by the Company following the Platform Safety studies)

PRE-SERVICE CONDITION • Fabrication • Loadout • Trsnportation • Installation

a. Jacket structures (launch, flotation and up-ending, OR lift) b. On Bottom stability c. Piles (stick-up, drivability)

• Topsides Lift

Seismic Data: The earthquake loading on the combined jacket and topsides structure is calculated using the response spectrum method and in accordance with the provision of API RP 2A. The response spectrum data for this analysis generally follows the guidelines for Zone-IV earthquake area as given in Indian Standard IS-1893. Corrosion Protection: All structures are designed to resist corrosion in different zones. As per API RP 2A, additional material thickness as corrosion allowance for structural members and other components in the splash zone are provided as follows:

Item Corrosion Allowance Thickness (mm) Submerged Zone 0.0 Splash Zone Barge Bumper

Boat Landing Other

6.0 6.0

13.01 Atmospheric Zone 0.0.

Note: All structure, caissons, pump casings, etc. the corrosion allowance shall apply over the entire component.

All steel surfaces in the submerged zone are protected against corrosion by a sacrificial anode system. The design is as per specification for cathodic protection. All pipelines and risers shall be properly insulated from CP System. All steel surfaces in the splash zone and atmospheric zone are painted in accordance with the respective project specification. All equipment, stairways and appurtenances such as barge bumpers, boat landings, riser protectors etc. including their stabbing guides are painted irrespective of the applicable zone.

Page 91: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 91

Areas and joints, which are inaccessible for maintenance and thereby susceptible to corrosion, are suitably sealed by methods such as boxing with plates etc. Design Loads: The design loads generally applicable to Jacket and Topsides are as follows:

1. Structure Dead Loads

The structure dead loads include the weight of all deck plate, grating, and secondary steel, deck beams, girders and trusses.

2. Equipment Loads Equipment loads include the weight of all equipment, bulks, piping. These loads are to be developed based on equipment layouts. Two basic load conditions are considered for global design. These are: • Equipment & Piping Dead Weight • Equipment & Piping Operating Contents Weight • For local design, hydrostatic test weights shall be considered where

applicable.

3. Crane Loads On the basis of the Crane requirement and the data provided by the crane manufacturer, the static and dynamic crane loads are determined. The dynamic crane load cases generally consider a range or boom direction to ensure all possible lifting scenarios are adequately checked. A minimum of eight boom directions are considered.

4. Live Load for Local and Global Design: Local and global live loads are used in the in-service analysis. The magnitudes of local and global live loads to be used vary from project-to-project, and these are specified in the bid package of every new platform.

5. Open Area Live Load: The Open Area Live Loads are applied to all clear unoccupied areas of deck and internal areas of the Utility and Equipment rooms. The Open Area live loads are used in conjunction with equipment and crane loads for the design of primary and major secondary steelwork. Open Area Live Loads are generally combined with equipment weight data, from the weight control report and/or when provided by the Suppliers.

6. Wind Loads: Wind loads are calculated according to the requirements of API RP 2A. The wind areas for global design of the Topsides are calculated assuming that the area between the decks is fully enclosed. Wind areas are also included for

Page 92: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 92

equipment items on all decks. The following are considered in the calculation of wind loads:

a) A minimum of eight storm directions is considered for each load case for the

extreme storm and operating storm conditions. b) Wind is assumed to act simultaneously and collinearly with wave and

current forces. c) Wind speeds are adjusted for elevation and gust duration, in accordance

with API RP 2A

7. Wave & Current Loads: Environmental parameters, specific to a location are applied to maximize loading on all structural components. Analysis is performed for wave approach along grid directions and selected diagonal directions. For each direction of approach, the more severe of the environmental parameters of directions adjacent to it are selected. A minimum of eight storm directions is considered for each load case for the extreme storm and operating storm conditions. Waves and current shall be considered concurrent with wind.

The design wave is treated as a regular wave. 'Stokes' Fifth Order theory’ is used to compute water particle kinematics, using apparent wave period computed as per API RP 2A. Wave kinematics factor, as given for each project, is used to account for wave directional spreading or irregularity in wave profile shape.

The current speed in the vicinity of the platform is reduced by the current blockage factors. The wave particle kinematics multiplied by the wave kinematics factor and the current velocities, adjusted for blockage, are added vectorially to obtain total velocity vector at any point. The given current profile is treated as applicable to water depth equal to still water level. For any other water level at different points along the wave, the velocities are calculated based on linear stretching of the current profile. Morison's equation applied to only the normal components of velocity and acceleration is used to compute normal wave forces on the individual members. The coefficients of drag and mass (inertia), Cd and Cm values are considered as per API RP 2A.

8. Fabrication Loads:

All structures are checked for the loads applied during fabrication. Details of such loads and the structure support points are generally determined during the fabrication. Consideration is given to the support points used for weighing and load out. Wind loads are included with this load condition, appropriate for the site location.

9. Load-out Loads:

All structures are checked for the loads applied during load-out. The proposed method of load out is generally skidded, trolleyed or lifted. The following is, however, considered:

Page 93: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 93

a) Dry loads are only used, together with weights for all preinstalled lifting gear, sea-fastenings, loose ship items, etc. The loads are based on the Weight Control Report.

b) For lifted Load out, Lift Installation Loads as described below are used. c) For skidded or trolleyed load out:

• A minimum horizontal racking load of 15% of the total load on one

skid rail is applied. • Total loss of vertical support at one support location with the structure

being supported by the remaining support locations only. The vertical deflection at the un-supported leg need not be more than 25 mm

• Wind loads for a return period of 1 year are included appropriate for the site location.

Structures are loaded out onto the transportation barge by means of launch ways, continuous or discrete skids or wheeled dollies. The structures are checked for adequacy for the proposed load out operation and for the effects of the localized loadings resulting from change in slope of launch ways / tracks and the change in draft of the transportation barge as the structure moves on to it. For substructure structures loaded out on launch cradle this analysis covers the front end of launch cradle unsupported for various distances (barge moves downward), and two ends of the launch trusses supported (barge moves upward). For structures loaded out on discrete skids or wheeled dollies, the analysis covers cases due to loss of support of one or more supports, including three point support conditions. For other means of load out the analysis is based on the support conditions likely to be experienced. If the support conditions envisaged during weighting of the deck/module are different from those considered for loadout analysis, a separate analysis is performed with appropriate support conditions to ensure adequacy of the structure during weighing operations.

10. Transportation Loads:

Preliminary transportation Analysis: All structures are checked for the inertia loads applied during sea transportation. Consideration is given to the support points used for sea fastening. The following points are also considered: • Dry loads only, are used, together with weights for all preinstalled lifting

gear, sea fastening, loose ship items etc. The loads are based on the Weight Control Report.

• For the preliminary transportation condition, in lieu of a detailed transportation and barge motions analysis, the following inertia loads are used:

Page 94: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 94

Barge Type Single Amplitude (in 10 Sec. Period) Roll Pitch Heave Small cargo barge (76 m LOA or 23m beam)

25º 15º 1.0g +/- 0.2g

Large barges 20º 12.5º 1.0g +/- 0.2g

• The center of rotation is assumed to be 60% above barge keel at longitudinal midship of the transport barge.

• The transportation inertia loads are combined as roll ± heave and pitch ± heave. Quartering seas are generally not considered.

• Wind loads for a return period of 10 years (1 minute mean) are included with this load condition.

Detailed Transportation Analysis The design of all structures is done so as to accommodate the forces imposed during transportation. The computer analysis is performed in accordance with the ABS or any other International Certifying agency rules along with the provisions given therein.

The final transportation analysis consists of the following:

Static Stability of barge/structure system: a) Intact condition b) Damaged condition with at least any one compartment of barge flooded.

Sustained wind speeds of 148 kmph and 93 kmph are considered for calculating the wind forces on the barge freeboard and cargo’s surface area for Intact and Damaged conditions respectively. Wind forces are calculated as per ABS Rules.

Dynamic motion response analysis for barge/structure system:

In order to determine the maximum loads imposed on the structure and sea fastenings during the course of voyage from fabrication yard to offshore site an analysis of the dynamic motion response for the structure/barge system is performed. This analysis generally includes the following phases:

The following are considered for the route specific dynamic motion analysis: a) Wave direction: Beam, Head and Quartering Seas. b) The maximum sea state to be considered depends upon route of tow and

season of tow. c) The environmental conditions to be considered are based on an average

recurrence period of not less than ten years for the season of year when the tow will take place.

d) In order to obtain the maximum acceleration response, at least three sets of periods are chosen for the maximum sea state for each direction of approach depending upon the dynamic characteristics of the barge/structure system and the towing speed of barge.

e) A reduced wave height (less than the maximum)/period combination, if that is likely to result in near resonant response conditions.

Page 95: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 95

After obtaining the maximum response for various sea states, the structure is analyzed for the corresponding maximum inertia/gravity forces.

Based on the above analysis, the Contractor carries out the design of sea fastening and the preparation of detailed sea fastening drawings.

11. Lift Installation Loads:

All structures are checked for the loads applied during lift installation off the barge and into position in accordance with API RP 2A. The following points are also considered:

Dry loads are only used, together with weights for all preinstalled lifting gear,

sea-fastenings, loose ship items, etc. The loads are based on the Weight Control Report.

A dynamic factor of 2.0 is applied to the lift weight of the item for the design of lifting frames, pad eyes and adjacent members.

A dynamic factor of 1.35 is applied to the lift weight for all other members transmitting lifting forces.

Where a four sling arrangement is used to lift the item, the analysis is carried out in two cases, one assuming all slings equally effective i.e. each diagonal carries 50% of the static lift weight and another with one diagonal sling carry 75% and the other diagonal sling carry 25% of the static lift weight.

Rigging is designed to limit the swing of the lifted objects to within 2 degrees from horizontal about any axis. Static equilibrium during the lifting operation is ensured.

Structural deflections are limited for deflection sensitive equipment, buildings and other items.

A complete three-dimensional idealized mathematical model of the structure is analyzed for the stresses developed during lifting operation to comply with the provisions of API RP-2A.

During Detail Engineering the contractor performs a lift study to establish that the modules as conceived are liftable with the proposed barge crane. This study includes adverse combinations of variation in centre of gravity and weight. The lifting scheme including requirements of spreader frame is finalized based on this study. The weight control report generated forms the basis of the study. A three-dimensional space frame lift analysis is also performed for all structures to be lifted. The lifting analysis is carried out as per provisions of API RP 2A. The load combination includes appropriate skew load distribution between the two diagonal pair of slings to account for sling length variation.

If the subsequent weight control reports / actual weighing of the module indicate a weight increase of more than 5% and / or a shift in centre of gravity of more than 2% of the corresponding linear dimension, a revised lift analysis is carried out to ensure that the permissible stress are not exceeded due to the revised weight / centre of gravity. The analysis is also repeated if the framing

Page 96: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 96

arrangement of lifting scheme, spreader frame arrangement or components to be lifted is revised to an extent to affect the stress distribution in the structure. Deflections are to be limited for structures with deflection sensitive appurtenances.

12. Other Installation Loads: All structures and structural components are checked for all of the loads likely to be imposed during all phases of the installation. The imposed loads are considered appropriate to the method of installation.

Jacket Launch: Three dimensional launch trajectory analyses consider the following variation in basic parameters:

Launch Weight -3% to + 5% of the weight defined in the Weight Control report

Longitudinal Centre of Gravity is offset to 1% of length of jacket towards top of jacket

Barge Trim is –50% to +50% of the selected trim Coefficient of Friction for skid rails is (+) 25% of estimated value Higher values of variation in the above parameters may be studied if so

required Sufficient combinations of the above basic parameters are analyzed to produce

the worst-case launch scenario. A minimum mudline clearance of 10.0m at both top and bottom of the jacket

shall be ensured during the entire launch operation. The Jacket member and joint stresses are checked for code compliance during all phases of the launch Members with longitudinal axis, which enter the water within 15 degrees of horizontal, are checked for slam effects using predicted velocities from the launch analysis.

Jacket Flotation and Upending: Flotation and Upending analyses are performed to investigate the stability, bottom clearance, derrick vessel hook loads and buoyancy requirements at successive stages of the Jacket installation. A minimum bottom clearance of 3.0 m is maintained throughout the upending operation. A minimum reserve buoyancy of 12% over the estimated weight is ensured in the design. With any one buoyancy component fully flooded, the reserve buoyancy is designed to be a minimum of 6%.

Jacket on Bottom Stability: A rigid body stability analysis is performed for the Jacket to ensure stability before pile installation. Both still water and installation environmental conditions are considered. The Still Water Level is considered as LAT + 50% of Astronomical Tide. For the on-bottom weight the jacket is considered in all its applicable set down ballast and stabbed hanging pile configurations. The steel mudmats are sized to provide bearing and sliding resistance. Any slope in the seabed is taken into account. The ultimate bearing capacity of the mudmats under combined vertical and horizontal loading is calculated using the methods in API RP 2A. Pile sleeve extensions or skirts, where applicable may be used to enhance the mudmat capacity. Critical wave heights are determined and checked against installation environmental

Page 97: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 97

conditions for jacket. API safety factors of 2.0 for bearing failure and 1.5 for sliding failure are applied.

13. Stab-in Guides and Installation Aids:

All stab-in guides and bumpers are designed for the following loads, as a minimum: • Horizontal impact force = 10% of the static weight of the item. • Vertical impact force = 50% of the static weight of the item.

14. Earthquake Loads: The earthquake loading on the combined Jacket and deck structure is calculated using the response spectrum method and in accordance with the provisions of API RP 2A. The response spectrum data for this analysis follows the guidelines for Zone-IV earthquake area as given in Indian Standards IS-1893. The importance factor is taken as 2.0 and the coefficient to account for the soil foundation system is taken as 1.2. Contribution of the marine growth in the added mass is also considered in the analysis. For building / equipment / modules, an equivalent static analysis is carried out with a horizontal seismic coefficient of 0.12.

Earthquake Forces wherever applicable are taken as occurring in both the direction and 50% in the vertical direction. Equipment Support & Services All equipment supports, pipe supports and other services support steelwork are designed to withstand the operating and hydrotest loads specified on the Supplier documents. For the transportation condition, in lieu of a detailed analysis, the following inertia loads are used as a minimum design case:

Horizontal acceleration = 0.7 g Vertical acceleration= 1.0 g +/- 0.20g

Barge Bumpers The Barge Bumpers and their associated connections to the Jacket are designed for the following loading:

a) Vessel impact directly in the middle 1/3 height of post. Energy to be

absorbed in the system is 30.4 tonne-metre. b) Vessel impact lateral in the middle 1/3 height of post. Energy to be absorbed

in the system is 11.0 tonne-metre.

Boat Landing The Boat landing and its associated connections and local framing are designed for the following load combinations:

Page 98: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 98

i. Dead load + Live Load of 5.0 kPa on each landing

ii. Dead Load + Boat impact load at different points on the berthing face iii. Dead Load + Extreme environmental load. iv. Installation Loads.

The energy to be absorbed in the system from vessel impact is 3.0 tonne-metre.

Wave Slam: Horizontal members in the wave zone are designed for wave slam forces in accordance with API RP 2A. Bending stresses due to both horizontal and vertical slam forces are investigated. One-third increase in permissible stress is allowed. However, the current velocity components are not included in the wave kinematics when calculating wave slam loading. For X-braces, members are assumed to span the full length. Member lengths are reduced to account for Jacket leg ratio. Permissible Stresses & Factors of Safety The permissible stresses and factors of safety are generally as recommended in API RP 2A. Load Contingencies, Mill Tolerance & Weld Metal It is required to accurately calculate the pre-service and in-service design loads consisting of dead loads, piping and equipment loads (empty and operating), topside modules, utilities and any other loads to which the system will be subjected during fabrication, transportation, installation and operation etc. A minimum of 3% weight allowance to account for mill tolerance and weld metal is applied for all analyses. This allowance is added to the estimated substructure and superstructure dead weight.

In the preliminary analysis stage and till the accurate estimation of loads is arrived, the platform in-service and pre-service design loads, applied either globally or locally, includes contingencies estimated over and above the estimated loads.

Jacket Fatigue Design The tubular joints of the Jackets are analyzed for fatigue endurance in accordance with API RP 2A. A deterministic fatigue analysis using Palmgren-Miner’s Rule is used to predict the fatigue lives of structural connection. Dynamic analysis is carried out to predict the fundamental periods of the platforms in order to confirm the sensitivity of the structure to wave induced excitation. The fundamental sway periods are used to derive the dynamic amplification for the in-place analysis loading conditions.

Page 99: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 99

Fatigue analysis is performed for the Jacket structures using methods appropriate to the sensitivity to dynamic loading. A deterministic approach is deemed adequate for platforms with fundamental period less than 3 seconds. Fatigue Life: The in-service fatigue design life of the joints is designed to be at least two times the service life of the platform. Analysis Procedure: The fatigue analysis is performed for all joints, which determine the safety and reliability of all the steel work of the structure. Particular attention is paid to joints in the top one-third of the substructure structure including deck legs and the bottom horizontal brace level. For each joint and type of failure under consideration the stress range spectra is computed at a minimum of 8 positions around the joint periphery to ensure that the point of maximum damage and hence lowest fatigue life is considered. For computation of fatigue damage, the stress range versus wave height diagram for each wave approach direction is divided into (a minimum of 10) blocks (of 15 cm) and the damage computed for each block and summed up. For each circular tubular joint two types of failure are considered, using the appropriate stress concentration factors - Brace to weld failure and chord to weld failure. For joints other than those between tubular members, individual detailed consideration is given with due regard being paid to publish, reliable experimental data.

Stress Concentration Factors (SCF): The hot spot stresses ranges at the joints on the brace and chord side of the weld, used to estimate the fatigue lives, are determined from.

Hot spot stress range = Fra, SCFa + FRi.SCFi + FRo.SCFo

Where, FRa, FRi and FRo are the brace nominal axial, in-plane bending and out-of-plane being stress ranges and SCFa, SCFi and SCFo are the corresponding stress concentration factors for axial, in-plane bending and out-of-plane bending stresses for the chord side or the brace side.

The fatigue life on both the brace and chord side of the weld is calculated with one of the following methods for obtaining the stress concentration factor applied to the brace nominal stresses:

For K Joints: Formula proposed by J.G. Kuang et al “Stress Concentration in Tubular Joints” (Society of Petroleum Engg. Aug. 1977).

For T, Y and X Joints: Formula proposed by A.C. Wordsworth and G.P. Smedley

“Stress concentration in Unstiffened Tubular Joints” select seminar on European Offshore steel Research, November 1978.

S.N. Curves: The basic S-N curves to be used in the evaluation of fatigue life are the API X-prime curve. The thickness correction effect as specified in API RP 2A is applicable. The use of X-curve, with corresponding joint preparation as per API RP 2A is acceptable for joints that do not have a computed fatigue life greater than half the required fatigue life when the X-prime curve is used. Marking of Joints: The joints are to be identified with the computed in-service fatigue life less than four times the service life of the platform. These joints are marked with neoprene based Cupro-Nickel embedded sheets for future inspection purposes.

Page 100: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 100

Identification marking is designed to be easily accessible for divers and a minimum gap of 250mm is maintained between the identified joint and the marking. MISCELLANEOUS DESIGN Structural design generally conforms to the relevant codes in particular API RP 2A and AISC. Structural design is based on working stress methods. Where code checks are not applicable, allowable stresses are computed using rational procedures and appropriate factors of safety. Major rolled shapes are designed as compact sections as defined by AISC. The minimum thickness of structural plates and flange/web thickness of sections are generally 6mm. All deck plate is chequer type with a raised pattern surface and the minimum thickness is 8mm. The minimum thickness of Jacket tubulars is 10mm except in the splash zone where 25mm is used. The minimum thickness of deck truss tubulars is 8mm. Clear span of plating and grating is designed not to exceed 1200mm. Vibration is considered for any structure supporting major rotating machinery. The structure is designed so that the natural frequency of the supporting structure is less than 70% or greater than 140% of the equipment operating frequency. Member stresses due to aspects which are not specifically covered in the computer structural analysis are investigated by manual calculations and results combined with computer results to ensure that the stress and deflection limitations are not exceeded. All major structural members are designed to meet the following guidelines: a. Member slenderness ratio: K1/r <100. The buckling coefficient K, is chosen for each

member in accordance with API RP 2A recommendations. b. Tubular member diameter to thickness ratio: 20 < D/t <60. c. Pile diameter to thickness ratio: D/t <60. d. Use of sections back-to-back, battened and lattice type built up sections is not

permitted, in order to avoid areas difficult for maintenance. Connections: All connections are designed as welded joints. The joints required for removable type structural members are generally considered as bolted joints.

Tubular Joints: Tubular joint design and detailing for both pre-service and in-service conditions are in accordance with API RP 2A and are designed and detailed as simple joints. Where overlap cannot be avoided, the minimum overlap is determined as per API RP 2A. Non-Tubular Joints: Hybrid joints, combining rolled wide flange sections with tubular sections as used in module trusses, plate girder or wide flange joints are designed in accordance with AISC using rational engineering methods. Truss brace to chord joints are designed for transfer of axial loads from one brace to another across the truss chord in shear. The web stiffeners are designed to carry in compression the permissible axial tensile load of the brace.

Ring Stiffened Joints: Appropriate closed ring solutions are used to design launch leg ring stiffeners at deck leg/girder intersections as per the provisions of API RP 2A. Cross joints, Launch leg joints and other joints in which the load is transferred across the chord are designed assuming an effective width of the chord equal to 1.25 times chord diameter, on each side from the centerline of the extreme incoming braces, or length of the can whichever is less.

Page 101: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 101

Deflections: Deflections are limited to criteria, based on equipment operating requirements, specified by equipment suppliers or the following, whichever is less:

• Deflections are checked for the actual equipment live loads and casual area live loads

Pattern loading shall be considered. • Deflection of members supporting deflection sensitive equipment is not greater than

1/500 for beams and L./250 for cantilevers. • Deflection of other structural members are designed not to be greater than L/360 for

beams and L/180 for cantilevers, where “L” is the effective span of the member.

Design Philosophy: The Jacket and Topside are designed to withstand the extreme storm and operating storms that occur in the Mumbai High South area of the Arabian Sea. Structure Analysis and design is generally in accordance with the requirements of API RP 2A and/or AISC using working stress design methods. Primary and major secondary steelwork for the Topsides modules and Jacket (including foundation) are proportioned to ensure adequate strength and serviceability throughout all facets of installation and in service conditions.

Primary steel includes: Topsides – All truss members, deck girders, crane pedestal (if specified) and deck legs. Jacket – All legs, vertical / inclined bracing, horizontal bracing, launch truss (if required) and piles.

Topsides secondary steel includes deck plate, grating, deck beams/stringers, equipment support beams, walkways, stairs, and hand railing. Jacket secondary steel includes cathodic protection, boat landing, barge bumpers, walkways, casings and caissons, appurtenances and their supports and mud mats. Deck Plate and Grating Design: The local design of deck plating and grating is based on the applicable loads. Spans of plate and grating shall not exceed 1200mm. Plates are reinforced if concentrated loads are directly placed on plating. Grating Design is for a maximum deflection restriction of L/200 or 6 mm whichever is less. Bearing member is minimum 30 mm X 5 mm serrated type spreader at 30 mm center to center. Steel cross bar is minimum 8 mm diameter high strength deformed bar spaced at 75 mm center to center. Each bearing member is serrated by making a hole of 10 mm dia. at 15 mm center to center at top end and depth of hole shall be 8 mm to match with 8 mm dia. bar top. Gratings are galvanized as per project protective coating specification.

Beam and Plate Girder Design: The local design of beams and plate girders is based on the applicable loads defined for the project. These are designed in accordance with AISC’s specification and incorporate the following guidelines.

All plate girders are compact sections as defined by AISC. Web, Top and bottom flanges at a given section are of the same grade of steel and

symmetric about the beam’s axes. These are also checked for loading due to hydro test conditions. Deflection is limited to the criteria listed above.

Handrails, Walkways, Stairways and Ladders: Handrails, walkways, stairways and ladders are designed as specified below:

Page 102: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 102

Handrails are provided around the perimeter of all open decks and on both sides of

stairways. Handrails around the perimeter of laydown areas, loading and unloading areas are

removable type. The top rail of the handrail is supported at maximum 1500 mm intervals. Handrails are designed to withstand 100 kg concentrated load acting vertically or

horizontally at any point. Handrails in the wave zone are designed to withstand extreme storm maximum wave

loading. Walkways, stairways and landings are designed for the following load combinations.

i. Dead load + live loads ii. Dead load + extreme storm three second wind gusts and/or extreme storm

maximum wave whichever is applicable Stairways are made of structural steel, double runner with serrated bar grating treads

and handrails. The minimum clear width of stairways and walkways is 1000 mm. Walkway and stair tread grating are designed to be replaceable.

Handrails: Handrails of height 1100 mm height with three horizontal tubular and one 100 mm X 6 mm kick plate are provided around the perimeter of each deck (except the helideck), both sides of stairways, sides of walk ways in Jacket level and side of helideck walk ways. Handrails around loading/unloading areas are made removable to allow loads on hoists to pass.

The preferable types of handrails are as follows:

SL. NO TYPE Detail of hand rail type 1. Type - I HR below Cellar deck (wave zone) fixed type. 2. Type – II HR on and above Cellar deck fixed type. 3. Type – III HR on and above Cellar deck removable type. 4. Type - IV HR with safety chain.

The preferable member size for different handrail are as follows:

MEMBER INDIAN STANDARD

INTERNATIONAL STANDARD

Type –I vertical post and top horizontal member

---

60.32 X 5.54 , 80s ASTM A316L

Type –I other horizontal member ---

48.26 X 5.08 , 80s ASTM A316L

Type –II, III, IV vertical post and horizontal member

48.3Φ X 5.08 1.9” X 0.2” XS

Type – III Socket, Collar 60.3Φ X 3.91 2.5” X 0.154” Std Kick plate 100 X 6 100 X 6 Coaming angle 100 X 100 X 8 100 X 100 X 8 Safety Chain 6 mm 6 mm

Page 103: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 103

Removable type handrail is fitted with Socket/Collar. The Socket/Collar is fitted with Kick plate. Fixed handrail is fitted with kick plate at lower level. Kick plate 100 x 6 mm ASTM A316L is provided at lower level for handrail Type –I.

Walkways, Stairways and Landings: Stairways are designed with adequate width to maneuver a stretcher up and down the stairs. Preferable riser height is between 200 mm to 230 mm and width of trade is 230 mm. Trade is generally of 30 mm thick grating. All stairs extending to the substructure walkway level are adjustable in length to suit site conditions. Handrails are provided on both sides of the top of the substructure walkways Handrails, kick plates, walkways, stairways, and landings and grating for the Boat Landing and Sea Deck Walkway are of ANSI 316L stainless steel. This includes gratings for treads and handrails of staircase from Boat Landing to Spider/Sea Deck and Spider/Sea Deck to Cellar Deck. These are fastened to the structure by a bolting system carefully designed for the salt-water corrosive environment and not welded. Stainless steel bolts are not used for this duty. Rough edges on the stainless steel grating are removed to avoid hazards to personnel. Access Platforms: Access platforms are provided, where required to allow personnel easy and safe access in elevated locations. Access platforms are designed for live loads and any piping or other imposed loads.

Cranes: Based on the scope of work, the crane pedestals and the supporting structure are designed in accordance with API RP 2A and API SPEC 2C except that the impact factors conform to design requirements for the cranes. The supporting structure is defined as the pedestal and all members directly connected to the pedestal. The deflection of the top of pedestal from the supporting deck is limited to H/200 under design loads, where H is the height above the deck. The material for pedestal is selected to meet or exceed the requirements of API Spec 2H Gr.50 steel

Fire Walls: Firewalls for Utility Room walls, ceilings and floors shall be determined following the platform safety case/risk assessment studies. The fire protection system for firewalls is designed to comply with the specification Passive Fire Protection for Structural steelwork on offshore platforms. Skid Shoe Design: The skid shoes are designed such that the module reaction forces are spread evenly onto the skid rail. The skid shoes are designed to meet the dimensional requirements of the skid rails in the construction yard. At the tugging points, a safety factor of 2.0 is applied to the attachment points and the structure local to the attachment point. Consideration is given to the effects of any eccentrically applied loads. For design, the friction breakout coefficient for the shoe wearing timber on a steel skid rail is assumed to be 0.5 and the coefficient or sliding friction is 0.25. No increase in basic allowable member stresses is permitted.

Sea fastenings: The design of sea fastenings accommodates the anticipated loads during Transportation.

Hydrostatic Collapse: All buoyant member including buoyancy tanks are checked for hydrostatic collapse during the pre service conditions for higher of the two following cases:

Maximum water depth reached during pre service operations, with a factor of safety of 2.0

Page 104: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 104

Accidental complete submergence condition i.e. hydrostatic pressure at mud level with a factor of safety of 1.5

Tubular members are checked for in-service condition for hydrostat pressure and in service stress interaction as per API RP 2A. The factor of safety for axial compression case is taken as 1.5 and 2.0 for extreme and operating environmental conditions respectively. For earthquake condition the factor of safety for axial compression case is taken as 1.2

Jacket & Topsides Installation Aids: Installation aids are designed to suit the proposed method of installation for the anticipated function and leads and the requirements of API RP 2A

Substructure Installation Aid: Flooding System Flooding system is made suitable and reliable for the jacket legs or buoyancy chamber for controlled flooding of the jacket during upending and placing on bottom.

Grouting System Pressure grouting system or Single stage grouting system with packers/grout seals is used. The system is designed as a fail-safe system to cater for all possible contingencies/eventualities such as failure of any of the components. Each of the grouting systems adopted has provision for alternate means of grouting in case of failure of the planned system. In case substructure leg extensions are provided in design, the grout inlet is taken below mudline just above the packer and the grout line is designed to have a protective casing upto mudline. Only inflatable grouting packers of proven design are acceptable. Properly sized air supply lines extend from each of the grout seals to the substructure top level. All inflatable packers are provided with a rupture disc installed above the inflating connections to prevent premature inflation of the packer by hydrostatic pressure in the event of inflation line getting damaged during substructure installation. Passive Grout Seals of proven design are also sometimes used as an alternative to inflatable grout packers. Two seals are provided at each location. Suitable arrangement is provided for collection of return grout from the annulus, in case the pressure grouting system is not utilized.

Buoyancy Tanks: Buoyancy tank’s supports are designed to withstand the effect of maximum hydrostatic pressures and slamming forces during dive.

Skirt Pile guides: Skirt Pile guides are designed for the loads imposed during the installation of the skirt piles. As a minimum, following criteria are considered for the design of the skirt pile guide and the supporting framework: a) Top Level:

1.5 times the weight of the lead pile section. The total weight of all pile add-on sections supported at this level during piling operation. 0.25 times the weight of the lead section applied lateral to the plane of the supporting frame.

b) Second Level: The weight of the pile, which will initially pass this level.

Page 105: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 105

c) Subsequent Level: 0.5 times the weight of the pile, which will initially pass these levels.

d) Pile Stabbing Guides: Stabbing guides are designed to facilitate centering and alignment and to provide effective support to pile add-on sections.

e) Chaser Pile and Pile Connections: Adequate pile connectors are used to assemble chaser pile segments and ensure a sound connection of the chaser with the skirt pile. Positive type of connectors is used to drive skirt piles.

f) Upending Pad eyes: Upending pad eyes are designed for the maximum sling load computed during the upending operation. A lateral load of 5% of the static sling load is applied in addition to the lateral load computed during the upending operation. This load is applied at the edge of the outer check plate. A load factor of 2.0 is considered for all the above loads. The orientation of the lower set of padeyes is fixed by taking into account the variation of the angle of sling with rotation of the substructure during successive stages of upending operation.

g) Lifting Padeyes: Lifting Padeyes are designed as per API RP 2A. The substructure legs are designed to have ring stiffeners at these locations to prevent ovalising of the tubular.

Design of Installation Aids for superstructure: All installation aids are designed to suit the method of installation for the anticipated function and loads. Applicable requirements of API RP 2A are followed. Lifting Eyes / Trunnions: Trunnions are used for lifting points with a static sling load of over 600 tonnes. Lifting eyes are designed as per requirements of API RP 2A. The design sling load is computed based on an assumed tilt of 2º in the most adverse direction. The lifting eye / trunnions design includes sufficient reserve strength to allow for future weight growth, load distribution changes and final selection of rigging.

Spreader Frames: Spreader frames are generally connected to the modules by slings. If rigid legs are provided, then they are adequately braced to carry sway forces.

Bumper Guides: Bumper guides are provided on superstructure to arrest the sway of the module being installed over it and to position the module accurately. The guide system configuration and design are such that the guide system elements fail prior to any damage to the module or the support structure, and the connections to the support are stronger than the guide elements. The guide system is designed for a Normal load of 10 percent of the module weight in the direction of guide support and a friction force of 3 percent of the module weight in the lateral direction acting simultaneously. Basic AISC permissible stresses are used in the design.

Boat Landing: Boat landing is provided in minimum three steps with minimum stepping of one-meter between high and low tide variation with suitable ladder. Boat landings associated connections, and local framing are designed for boat impact loads, environmental loads, uniform live loads and dead loads. For structural design the load is treated as a concentrated load. Mooring bollards are provided near each end of the boat landings for supply vessel mooring. Two swing ropes are provided near the mid point of each landing, one at the face of the landing and the other 1 metre seawards of the landing face and about 1 meter apart horizontally. Swing ropes are supported from the lower deck structure. Proper arrangements for replacing the swing ropes are provided. The boat landing is detailed such that there is no interference with other items of substructure such as risers, barge bumper etc. during installation of operation. In case of boat landing

Page 106: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 106

designed to be field installed, it is designed to allow a +/- 1 .0 m elevation adjustment to compensate for variation in the installed height of the jacket. The boat landing is designed as removable and readily replaceable. Members are allowed to form plastic hinges under design impact forces.

Barge Bumper: For structural design the load is treated as a concentrated load. Local denting of the vertical post is neglected. Members are allowed to form plastic hinges under the design impacts forces. The barge bumpers are designed as removable and readily replaceable. It is permissible to integrate the design of Boat landing and barge bumper systems into a single unit. Analysis of jacket framing members is carried out for the boat impact loads on Barge bumper for this purpose the force equal to the rated load of the shock cell is applied at the shock cell support points. No one-third increase in permissible stress is allowed in Jacket framing member for this analysis. However, one-third increase is allowed for a vertical member supporting the barge bumpers / shock cells.

Riser Protector/Conductor Protector: All riser / conductor protectors are designed to absorb a concentrated impact energy of 100 tonne metres (TM) applied any where on face at any point. Plastic collapse analysis may be performed for this purpose. Any point on the deflected structure is at least 300 mm clear from any present or future riser / conductor. Vertical member is grout filled. The support of the riser / conductor protector, which are welded to the jacket is designed elastically. No increase in basic permissible stresses is considered.

Conductor Guide Framing: The support for Curved Conductor is designed for elastic bending forces in combination with extreme storm design environmental conditions. The designs of Conductor guide framing also consider the load imposed during and after the installation of Conductors. As a minimum the following criteria are considered for the design of Conductor guide framing:

iii. Top Level: Weight of all the Conductors (Straight and Curved) installed in the substructure prior to drilling of 1.5 time the weight of the Conductor which will initially pass this level, whichever is applicable.

iv. Second Level: 1.5 times the weight of the Conductor, which will initially pass this level.

v. Subsequent Level: 0.5 times the weight of the Conductor, which will initially pass this level

Conductors: Curved Conductor is generally pre-installed in the substructure before the substructure load out. Curvature of curved conductors is taken 3° per 30.5m of arc length. The minimum clearance between any two Conductors is not less than 600 mm below mudline and 150 mm above mudline. ARCHITECTURAL DESIGN CRITERIA The Architectural Design Criteria is to specify requirement to size the Building module. The requirement are stated below:

Occupancy Type of living room required Provision of kitchen, dining, frizer, chiller, dry-storage-food lay down area

Page 107: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 107

Requirement of entertainment room like TV / DVD room, recreation room, games room, gymnasium room

Infirmary Provision of number of office, conference room, library, document room Radio room, battery room, control room, switchgear room Water heater-HVAC / AHU, chiller Laboratory Any other requirement of room varying from project to project.

The safety requirement aspect is also specified in the Architectural Design Criteria like provision life boat, life raft, fire extinguisher, smoke detector, fire hose reel, dry chemical fire extinguisher etc. It also specifies the requirement like type of flooring required for different type of room, wall paneling, false ceiling, requirement of fire integrity of wall etc.

CLAMP-ON STRUCTURES In clamp-on structure 3 additional wells for drilling are installed on the existing well platform. Main and Cellar Decks with well conductor guides are extended towards north side of existing well platforms by welding structural members. Since welding below water is difficult, therefore, well conductor guides are attached with a tubular frame and this frame is fixed to the existing jacket horizontal members with the help of clamps. Vertical and curved conductors are installed after installation of well conductor guides. To protect the well conductors, conductor protector is also installed at water level. Following codes as followed in platform structure are also followed for establishing design criteria for clamp-on structure: API RP 2A AWS D1.1 AISC, 9th. Edition DNV RP B401/NACE RP-01-76 Structural Design Philosophy for Clamp-On Structures The in service design analysis consist of in place analysis which determines the sizes of structural members. The extreme and operational environmental loads combined with dead weight and elastic bending forces of curved conductors are analysed for determination of design loads for each structural member. Structural analysis and design as followed for platform structure is also followed for clamp-on structure except analysis for load out, transportation, seismic/earthquake loads. Since piles are not involved, therefore, pile drivability analysis and grouting are not done in clamp-on structure. Basic Load Cases and Load Combinations Like platform structure basic load cases with contingencies for variation of dead load with following load combinations are considered for in-place analysis:

Load Combination -1 Dead Load + Live Load + Extreme Storm + Elastic Bending Force

Page 108: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 108

Load Combination -2 Dead Load + Live Load + Operational Storm + Elastic Bending Force Load Combination -3 Dead Load + Installation Wave Load + Elastic Bending Force +

Installation Load Load Combination -4 Dead Load + Installation Wave Load + Elastic Bending Force +

Installation Load Load Combination -5 Dead Load + Installation Wave Load + Elastic Bending Force +

Installation Load Conductors for Clamp-On Structures:

Vertical and curved conductors are installed after completion of installation of guides, main deck and cellar deck installation.

5.7 ELECTRICAL:

The offshore platforms are having their own generating source of electrical power to meet the requirements of process utilities and other electric drives, living quarters, platform illumination system, communication and annunciation system, fire and gas alarm system, etc. The Electrical Design Criteria broadly outlines the minimum requirements for the design, selection, sizing and installation of the electrical equipment and associated system on the platform. The philosophy being followed for the above is described in the following sections.

5.7.1 SALIENT FEATURES OF ELECTRICAL DESIGN PHILOSOPHY:

The electrical system on an offshore platform is designed to provide

Safety to personnel, equipments and marine life Reliability of service Minimal fire risk Ease of maintenance and convenience of operation Automatic protection of all electrical equipments through selective relaying system Adequate provisions for future expansion and modification Maximum interchangeability of equipments Fail safe features Hook-up provisions with existing facilities, wherever required

5.7.2 CODES AND STANDARDS:

The specification of design documents, material and system performance is based upon the requirements of the latest versions of all applicable International Standards, Codes, Regulations and Code of practice being followed by the Industries world-wide. Some of them are listed below - IEC - International Electro Technical Council NEMA - National Electrical Manufactures Association (USA) ASTM - American Society for Testing of Material (USA) NFPA - National Fire Protection Agency (USA) IALA - International Association of Light House Authority

Page 109: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 109

BIS - British Standard Institute ANSI - American National Standards Institute API - American Petroleum Institute (USA) NEC - National Electric Code (USA) RIIS - Research Institute of Industrial Safety, Japan SOLAS - Safety of life at sea NESC - National Electric Safety Code DNV - Det Norske Veritas NACE - National Association of Corrosion Engineers In the event of conflict between codes being used, the most stringent one is followed. The electrical design documents are generally drafted on the basis of International Standards or equivalent Indian Standards. However, Indian Standard is used only

Where required by regulation or Indian law and Where they are more stringent than international Standards or Where there is no suitable international Standard

If Indian standards are legally required, but are less stringent than the corresponding International Standards, the international standard is followed. The definition of most stringent is that approved by Company.

5.7.3 GENERAL REQUIREMENTS:

Site Conditions All electrical equipment and accessories / material are suitable for installation and operation under extremely saline, humid, corrosive and hostile marine environment with specified degree of hazards. General Safety The electrical system employs safety margins to ensure that platform is safe under all operating conditions, including those associated with the start up and shutdown of equipment and throughout intervening shutdown periods. The emphasis in equipment specification is on operability, prevention of accident / fault and functionality for the intended design life. All insulating materials specified for the equipment are non toxic. Fire Integrity All cable penetrations through firewalls, switchgear room walls and between safe and hazardous area are sealed using multi cable transits to maintain fire integrity and prevent gas migration. Evacuation All services required for safe evacuation of the facility are designed to operate for sufficient time after loss of both main and emergency power at the platform. The support duration is in line with the risk assessment study. Material, workmanship & suitability

Page 110: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 110

All material used in the construction of electrical equipment, cables, mounting and fastening devices, etc., are to be of latest specifications, new and in manufacturer’s current production. Material scheduled for modification are not be used, unless approved by Company. Should any material proves unsatisfactory it is to be rejected notwithstanding any previous satisfactory examination on test of similar material or of equipment.

5.7.4 ELECTRICAL LOADS:

Definitions The following definitions are applied in the preparation of load schedule. Brake Power ( KW ) – Power transmitted along the shaft to the mechanical equipment Nominal power – Name plate rating of motors or load absorbed by non- motor load.

Efficiency ( % ) - As per vendor data the ratio of output power to input power complying with IEC Std

Load classifications

Electrical loads are classified as Normal, Emergency or Critical.

Normal - Loads in service for full production application Critical - Load required for life support and occupancy purpose Emergency - Loads required for personnel safety/safe shutdown and abandonment purpose

Utilization Category

Load are divided into following three classes according to use. Continuous load - which draws power at continuous rate Intermittent load - which draws power as per duty cycle for small time Stand-by load - which are connected with power supply and ready to act as and when required.

Load assessment

All Electrical loads are developed by contractor based on estimated load identified in

mechanical equipment list. The data sheet is issued to specify maximum power requirement. In evaluating load summary, utilisation category is applied as follows -

Total Load i) Continuously operating equipment - 100% of operating load ii) Intermittent load - 50% of the total intermittent load or the largest intermittent load whichever is greater iii) Stand-by equipment - 10% of total ‘standby’ load or largest stand by load, whichever is greater iv) Margin for future load growth - 10% of estimated load

Page 111: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 111

The total load shall be sum of i), ii), iii) and iv).

5.7.5 GENERATION AND UTILIZATION VOLTAGE LEVELS:

Generation Voltage

The generation voltage on a process platform is usually 6.6 KV and in some cases 11 KV.

Utilization Voltage ( Nominal )

i) 6.6 / 11 KV AC, 3 Ø, 50 Hz - For motors rated 160 KW and above ii) 415 V AC, 3 Ø, 50 Hz - For motors rated at 0.37 KW upto 160 KW,

Battery chargers, UPS, Platform Illumination system ( Normal Lighting ), HVAC, Bulk AC loads (

like Process heaters ), etc. iii) 240 V AC, 1 Ø, 50 Hz - For motors rated below 0.37 KW, Platform communication system, Radio Equipment, Anti- condensation space heaters,Convenience oulets, Level gauge illumination, etc. iv) 110 V DC, 2 wire - Critical lighting, Switchgear & Generator

controls, DC motors for Emergency lub oil pumps, etc.

v) 24 V DC, 2 wire, - Instrument supply, Fire & Gas detection system, CP monitoring panel, etc. vi) 12 V DC, 2 wire - Navigational Aids system vii) 110 V AC, UPS - Distributed Control System viii) 240 V AC, UPS - Telephone Exchange, CCTV system,

Radio system, Paging & Intercom system, Telemetry, telecom and computer system

5.7.6 CALCULATION METHODS:

Fault levels As part of detailed engineering, initial fault current calculation is carried out based on

typical vendor data for machines parameter with specified design tolerance. The calculations identify the maximum expected values of switch gear making and breaking fault currents, including motor contribution. Calculations are to be done as per IEC 60909. Switch gears are to be designed such that actual fault levels are at least 20% below the switch gear ratings, considering transient, fault break, fault make and peak fault levels.

Cable Sizing During detailed engineering all power and control cables are identified and sized according to the requirement of Indian and International standards. The sizing calculation takes into account following factors –

• Connected load • Current carrying capacity

Page 112: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 112

• Voltage drop • Short circuit temperature rise • Laying conditions

Wherever possible, power cables and control cables are to be run separately or with adequate spacing to minimize the effects of de- rating. Motor cables are generally selected from a standard 415/600V AC Motor Cable Selection chart. For branch circuits and feeders, conductor current rating is to be established on the basis of 125% of design load current at an ambient temperature of 40ºC and de-rated for grouping and method of installation. Final sub-circuits are sized from standard 240 V AC cables selection charts based on circuit breaker rating and voltage drop limit. The voltage rating of cables is as follows – High Voltage cables - 6.6 / 11 KV Power & Control cables - 600 / 1000 V Instrumentation cables - 250 V DC cables - 150 V DC Voltage drop

• The maximum allowable voltage drop in any feeder under steady state condition is to be maintained as follows –

Motors - 3% Switch Boards / Distribution Boards, Lighting / Power Panels - 1% Lighting Points - 2% DC System - 3%

• The voltage drop at the worst affected pre- loaded bus is not to be exceeded 15%

of nominal voltage during start –up of the largest motor. • The voltage available at motor terminals during start- up is to be sufficient to

ensure positive starting and acceleration to full speed by the motor ( even in motor fully loaded condition, if required ) without causing any damage to the motor. However, under no circumstances, the voltage at motor terminals during starting is allowed to fall below 80% of the nominal voltage.

5.7.7 SPECIFIC REQUIREMENTS FOR EQUIPMENT & ASSOCIATED COMPONENTS:

Environment Electrical equipment, installation material, wiring and cabling etc. are suitable for overall climatic condition, their position within the installation and the local environment. The conditions are likely to encompass exposure to moisture and salt laden atmosphere, sea spray, sunlight, extremes of temperature and humidity, fungal growth, abnormal vibration and shock. In general, all outdoor electrical equipment are to be designed for 40°C temperature and maximum 90%RH while the indoor equipment are to be designed for 45°C temperature and maximum relative humidity of 90%.

Page 113: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 113

Corrosion For out door locations, corrosion resistant material are considered for electrical equipment. As a minimum material / equipment requirements are as follows – Cable ladders and trays are fiberglass reinforced plastic and UV protected. Associated accessories are SS -316. Explosion- proof junction boxes, light fittings, control stations, etc., are to be

manufactured from cast stainless steel or copper -free aluminum with an epoxy finish. Cable glands are nickel plated brass or equivalent.

Proof of material suitability is required to ensure that the chosen material is suitable for the intended design life of the equipment/ facility. Degree of Protection The degree of protection against dust and water ingress, necessary for individual electrical items is determined by the equipment duty, its environment, its location and the hazardous area classification. The equipment located outside or subject to deluge from fire water system are to be specified weather proof construction and protected against the most adverse conditions that are anticipated. These enclosures are to be classified to IP-56 as a minimum degree of protection, increased as necessary where the location/situation demands. Indoor equipment will be a minimum of IP-42 protection and accessible equipment within enclosures will be a minimum of IP-22 degree of protection. Where indoor has specific ventilation requirements lower ingress protection rating will be considered subject to evaluation. Hazardous area Requirements The hazardous area classification is carried out in accordance with API-RP-500.The hazardous area classification drawings form the basis for layout of electrical equipment for various locations. All equipment selected for use in hazardous areas are to be certified by internationally recognized certification agency. Equipment shall have certification of CENELEC, BASEEFA, UL or FM or equivalent international testing agency for the area and service in which they could be used. All outdoor electrical equipment on the platform handling oil and gas are , at least, suitable for Class -I , Division - II , Gas Group - D area unless otherwise specified. However, equipment / items installed in battery room are suitable for Class –I, Division -1, Gas Group - B area. Lighting Normal lighting circuits are rated at 230 V, 50 Hz AC supply. The power for lighting is made available through a lighting transformer installed in switch gear room and is fed from 3 phase ,440 V , 50 Hz feeder coming from emergency switch board. Lighting system has provision of dimmerstste to vary the illumination level from zero to 100%. Normal lighting fixtures normally constitute 70 % of total luminaires and remaining 30 % fixtures are of emergency lighting. The external area of platform are fitted with fluorescent luminaires rated for Class -I, Div.-I hazardous area and have an ingress protection of not less than IP -56. Out door emergency lighting fixtures are self contained battery / inverter fluorescent lighting fixtures having duration of 90 minutes

Page 114: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 114

and are to be certified for Class – I, Division - I hazardous area. The temporary escape emergency lighting fixtures are strategically located along stairways and walkways, escape routes, switch gear room, battery rooms and boat landing area to provide adequate illumination for personnel to evacuate in the event of emergency. Emergency light fittings are designed in accordance with IEC60598 -2-22, thus the specified battery autonomy of 90 minutes must be met after 4 years of continuous operation. Battery for Navigational Aids have autonomy time of 7 days which is to be met after 25 years of operation.

Exit lighting fixtures are provided on each door of equipment housing. Flood lights are provided where illumination for large and open area is required, such as the main deck, boat landing, etc. All light fittings are to be secured and fastened using SS - 316 fasteners and accessories.The highest point on the platform is fitted with omni directional red obstruction light. The required maintenance intervals for all light fittings in continuous operation are not to be less than 3- 4 years.

Transformer for Normal Lighting. Two nos. of lighting transformers are normally provided in switch gear room. Each transformer is sized for 120% of the predicted distribution design load so that either transformer can supply 100% of load. The transformer is to be sized , using natural air cooling with the ambient condition of switch gear room. The transformers are natural air cooled , cast epoxy resin dry type , suitable for indoor installation. For stepless variation of lighting voltage, the motorised controlled dimmerstate are to be provided to vary the illumination level of lighting system Switchgears Feeders for 400 ampere rating or more are provided with ACB. Feeders for more than 63 ampere rating and up to 400 ampere rating have MCCB. Feeders of up to 63 ampere rating have MCB. However, all motor feeders have MCCBs regardless of ampere rating. Bus bar and isolating devices are rated at 125% of design load. Bus bars are generally identified as R, Y & B with phase coloured as red, yellow and blue. All the switch gears are industrial grade equipment installed in free standing sheet metal cubicles of modular design. All the switch gears are to be installed in a closed naturally ventilated room . Air Circuit Breaker ACB Incomer feeders are withdrawable air break type with charging motor , spring release and close mechanism. Breaker close /trip solenoid are fed through 110 Volt DC . Motor Starters / Contactor feeders, MCCB / MCB Feeders Each starter unit have component designed for Type- 2 co-ordination as per IEC. Switchboard and MCC have front access and the switch gear and starter components are ‘withdrawable’ type as per IEC - 60947 . Compartments are capable of withdrawing to a test position. This test position isolates the motor power cables to allow the live commissioning of control circuit. The LV switch boards are provided with a minimum of 20 % fitted spare motor starters and feeder modules.

Page 115: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 115

Motor starters invariably have MCCB for short circuit protection regardless of ampere rating. Protection Equipment The equipment defined provides adequate safeguards against the effect of any fault occurring on the system or component parts. All protective devices , including relays and current transformers ( CTs ) etc. are to be adequately rated to withstand the prospective short circuit current, which can flow or be induced. Where ever applicable, unrestricted over current relays provided have IDMT characteristics of the standardised type. Where ever applicable, the relay protection devices are such that a clear indication is given of fault which caused a trip. Circuit breakers are not able to re-close without first resetting the appropriate master trip relay. Motor Protection Contactor units used as LV ( 600 volt) motor starters incorporate the following protective devices –

• MCCB for Short circuit. • Single phasing prevention relay for motors. • Earth fault protection for motors above 37.5 kw. • Overload relay.

AC Incomer & Outgoing Feeder Protection ACBs used for 600 V Incomer & Outgoing feeders are to be provided with short circuit and overload protection, as minimum. DC Feeders ( 110V DC, 24V DC, 12 V ) Protection MCBBs / MCBs used for DC incomer feeders and DC distribution feeders are to be provided with short circuit and overload protection, as a minimum.

Transformer Protection As a minimum the following protection shall be provided for transformers over current with instantaneous trip. Back up Protection Time and time- current grading of up stream protective devices provide back up protection. There are no specific back up protection for failure of primary protection to clear faults. The design features are such as to clear a fault in a total clearance time of 0.5 seconds if the primary protection fails to clear a fault for any reason.

Bus tie Protection There are no special protection and tie-breaker acts like a switching device.

Page 116: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 116

Socket outlets Socket outlet are provided on the platform as 415 V, ,50 Hz, 3 wire plus earth 63 amp, 4 pin and 240 V, 50 Hz, 2 wire plus earth , 15 A, 3 pin certified for use in Class - I Division - I. Sufficient socket outlets are specified to enable normal operation, maintenance, testing and inspection of installation. Socket outlets are provided with earth leakage protection, 30 mA for 240 V, outlets and 300 mA for 415 V, welding outlets via dedicated distribution board. Junction Boxes Junction boxes for use in outdoors are to be certified for use in Class – I, Division - I, Hazardous area and fabricated from the following material - SS –316, Epoxy coated copper- free aluminum suitable for 25 years of service life. MOTOR START / STOP CONTROL STATION ( PUSH BUTTON STATIONS ) The push button stations are suitable for Class - I, Division - I hazardous area. They are to be fabricated from copper- free aluminum alloy. The cable entry glands are nickel plated brass material and of double compression type with EX(d) protection. ELECTRIC MOTORS. All the motors required by mechanical packages ( excepting those for Main Injection Pump, Sea Water Lift Pump, Booster Pump, wherever applicable ) are designed for 415 V, 3 phase, 50 Hz. and meet the requirement of relevant international standards. Also, all electric motors meet the requirements for the hazardous area classification indicated on the respective data sheets. All motors are totally enclosed fan cooled (TEFC) type with Class - F insulation, temperature rise limited to class - B. All hazardous area motors are suitable for Class - I, Division -I , Temperature Class T-3 and Gas group - D hazards. Hazardous area protection technique is Ex(d). Any motor rated at 75 kw or above, are fitted with positive temperature co -efficient thermistors. Motors rated 3.7 KW or above are to be fitted with anti- condensation space heaters. Motors for large equipment such as Main Water Injection Pump, Fuel Gas Compressor, etc., if installed on the platform, are normally provided with variable frequency drive ( VFD starters ) in order to limit the stating inrush current, transient torques and starting step load on supply source i.e. Turbine Generator. All motors, as a minimum , are designed to have power rating at least equal to 110% of the maximum shaft demand of the driven equipment for any of the specified operating conditions. NAVIGATIONAL AIDS The navigational aids along with associated DC supply and battery is to be provided on the platform.

CABLES

Page 117: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 117

Cable are heat and oil resistant, flame retardant (HOFR) type suitable for service in environmental conditions described for the platform. All ( normal and emergency ) cables have flame retardant characteristics to IEC 60332-3 category A. Cables for DC system including critical lighting system, navigational aids, etc.,are to be fire resistant type to the requirement of IEC 60331. Cable joints via cast resin kit or other type are not permitted on the offshore installations. Special care is taken to the routing and separation of cables to minimize the effect of fire on emergency and essential supplies and production operations. All cables are identified with SS - 316 Tags. In addition the minimum distance between power/control wiring and electronic signal wiring on prolonged cable route will be as follows –

Power / Control cable

Minimum distance from electronic/ signal cable

Up to 125 V 150mm Up to 300 V 150mm Up to 1000 V 300mm Above 1000V 450mm

Earth Conductor Earth cable has 6 mm2, 16 mm2 , 70 mm2 or 240 mm2 stranded copper conductor with CSP or EVA insulated and green / yellow insulation sheath. Cable support System The cable system comprises cable installed on cable tray or ladder with 25% spare capacity for future extension. Intrinsically safe circuit cables run in separate trays. Cable straps or ties are SS - 316. Cable tray /Ladder Two primary cable tray / ladder system are installed on the platform.

Low voltage power and control cable ( normal and emergency ) Instrumentation, control and ESD.

The cable trays / ladders are heavy duty type capable of being loaded to 120 Kg/m with 6 m support spans to NEMA 20B. Cable ladders /trays are to be manufactured from FRP material with UV protection features. Cable ladders are fitted with removable , ventilated covers where there is exposure to chemical spillage, falling object or direct sunlight. The covers are suitable for cyclone / monsoon conditions. Cable trays are installed in accordance with manufacturer’s recommendations and specifically supported at each elbow. The overhead cable trays are installed a minimum of 2.5 meter above deck. Cable Glands and Multi CableTransit ( MCT ) Frames

Page 118: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 118

Suitable size double compression type glands are supplied for all cables. For entries into Ex(d) enclosures, barrier type ( or compound filled) gland are provided. All cable glands and adaptors are made up of nickel plated brass and are fitted with soft sealing nylon washer. Fibre washers are not to be used.Lock nuts are used for entry into sheet steel boxes enclosures. Industrial cable glands are not used on offshore platforms. All cable glands are to be type tested and certified for use in specified hazardous area.

Cable transit frames are to be fitted where cables pass through -

Decks and walls to open air, Fire walls, From safe to hazardous area.

Such cable transit frames are designed to include 25% spare capacity for future use. Cable transit frames are to be supplied with test certificates from an accredited independent test authority to confirm a fire rating adequate for deck or wall in which they are to be installed. Cathodic Protection Cathodic Protection for Rigid Structures and Submarine Pipelines is to be carried out in accordance with respective Equipment specifications.

5.7.8 ELECTRICAL EQUIPMENT/PRODUCT / MATERIAL SELECTION PHILOSOPHY:

All electrical equipment / product / material ( viz. motors, transformers, switch gears, distribution system, cables etc.) offered by the vendor are to be as per relevant standards, specifications, new and unused, of current manufacture and the highest grade and quality available for the required service, and free of defects. The equipment is to be protected from construction damage and damage in transportation. and damage due to sandblasting and painting.

The selection of electrical equipment / product / material is generally based on the following factors -

Functional specifications and electrical design criteria in respect of each

individual equipment Applicable Standards , Codes & Recommended Practice Reliable & trouble free performance for 25 years of design life Safety General Operating / Site conditions Hazardous area classification Suitability for the specified requirement for use in outside pressurised rooms

and inside pressurised rooms Suitability for the corrosive effects of the saline and humid marine atmosphere,

galvanic action, etc.

Page 119: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 119

5.7.9 VENDOR PRE-QUALIFICATION:

All offered electrical product or equipment or equipment with similar designs and construction features, manufactured by the same vendor -

• Shall have been type tested by an authority approved by ONGC • Shall have been in continuous satisfactory service on offshore installation for a

minimum period of two ( 2 ) years and should be under manufacture at least for the last three ( 3 ) years, unless otherwise specified

• Shall have a current certification /approval /listing by UL or FM or by an

agency approved by ONGC. 5.7.10 ELECTRICAL EQUIPMENT CALCULATIONS:

Certified calculations, as listed below, for electrical equipments of process platform in respect of size / rating / power / capacity, etc., are to be provided by the contractor for approval of ONGC during Detailed Engineering –

Turbine Generators Transformers Electric Motors Switch gear and control gear Power and control cable MCTs Area lighting fixtures Cable trays Battery & Battery Chargers for various system Earthing cable/conductor Lighting transformer Cathodic protection system

These calculations form part of the relevant Purchase Specification to be submitted during detailed engineering.

5.7.11 REVIEW AND APPROVAL:

All Purchase Specifications along with list of deviations, calculation sheets, offers of the vendor and all relevant documents are to be furnished for ONGC’s approval during detailed engineering. Contractor is advised not to place order for purchase of any item without obtaining prior approval from ONGC in writing. Contractor prepares and furnishes the list of all drawings / documents enlisted in the bid document for ONGC’s review. The category of drawings / documents ( i.e. whether to be reviewed / approved by ONGC is generally decided in consultation with contractor and ONGC’s consultant after award of Contract. All vendors drawing are to be submitted for ONGC’s, review after the contractor’s engineering consultant approves them.

5.7.12 TAGGING AND NAMEPLATES:

Page 120: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 120

All equipment ( Motors, push buttons, motor control centers , push button stations, pull boxes etc. ) are provided with SS tag or nameplate of a permanent type with identification number and service description. The Contractor assigns individual tag numbers in accordance with ONGC’s established system to all electrical equipment. The tag number that pertains to a electrical equipment appears invariably on all drawings and documents. Nameplates and identification tags are to be provided to properly identify each equipment and / or their component.

All panel electrical equipment nameplates are to be made up of white laminated plastic plates with black engraved lettering and securely fastened with SS -316 screws. All front panel mounted equipment are to be identified with a metal or plastic nameplate attached to the rear of the device and easily visible via the rear access doors. All wiring, power and control cables, junction boxes and auxiliary equipment are to be suitably identified as per applicable codes and practices. Plastic adhesive tapes are not used for identification. All wirings are to be tagged with slip- on or clip-on wire marker at both ends with the wire number specified on the drawing.

5.7.13 ELECTRICAL EQUIPMENT INSPECTION & TESTING PHILOSOPHY:

The Contractor’s quality plan includes a comprehensive fully documented inspection and testing plan specific to the project and it is to be submitted to ONGC for review and approval. The inspection procedures includes inspection specifically for compliance with hazardous areas requirements.The Contractor is also required to provide suitable workshop, equipment and all necessary tests for electrical equipment. ONGC reserves the right to reject any or all test work, if found unsatisfactory / not upto the mark.

In addition to yard testing of loop checking and setting for safety devices like overload relays etc. and simulation testing of all interlock and shutdown systems,they are required to be carried out in offshore also.

Insulation tests are to be carried out on all cabling by using a megger of 500 volt DC. The IR value is required to be more than 10 M ohm for acceptance.

Correct connections of all electric equipment are to be checked.

All testing and pre-commissioning activities are required to be done by the Contractor. The Contractor is also required to provide assistance for ONGC’s commissioning activities.

The Contractor is required to provide written results of all above tests, if so required by ONGC. Also, the contractor is required to furnish reasonable evidence of the satisfactory condition of test equipments.

5.7.14 ELECTRICAL EQUIPMENT SPARES PHILOSOPHY:

Page 121: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 121

For all major equipment, the Contractor is required to include normal commissioning spares as a part of the equipment. The Contractor is also required to furnish separately, list of recommended spares for two year’s trouble free operation along with the prices for purchaser’s review. The spares requirement of individual systems shall be as per the relevant functional specification.

5.7.15 TRANSPORT AND SHIPMENT:

All electrical equipment, cables and trays etc. are required to be securely anchored to the skid. All equipments that could be damaged in shipment shall be removed, tagged and crated in a weatherproof box. Weather proof box shall protect the equipment from dynamic forces.

All openings, flange thread connections and cables exposed as a result of cable removal are required to be protected in a manner to prevent damage during shipment.

5.7.16 WARRANTY:

Contractor is required to warrant that his equipments will satisfy the requirement of intended use and it is free from latent defect.

The contractor is also required to assume responsibility for obtaining manufacturer’s

performance warranty for all equipment purchased by him. Contractor will then assume this warranty in his guarantee to the company.

Contractor is required to agree to repair or replace any equipment which proves to defective within 12 months after being placed in operation but not exceeding 18 months from date of shipment.

5.8 PIPELINE: 5.8.1 DESIGN PARAMETERS:

Design Life: 25 Years (a) Rigid Pipelines:

The design of pipelines, risers, tie-ins, pipeline crossings and free span corrections follows the guidelines of Det Norske Veritas Rules for submarine pipeline system 1981 (DNV). The design and loading conditions and design criteria are as defined in Section 3 & 4 of the above rules. Constants and coefficients to be used for the design calculations are taken from these rules except as specified below:

i) Maximum allowable steel : 85% SMYS stresses during installation. loading condition “b” (SMYS- Specified Minimum Yield Strength). During Hydrotest: : 90% SMYS ii) Zone-1

Page 122: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 122

Maximum allowable steel stress during operation Pipeline, load condition 'a' : 72% SMYS Pipeline, load condition 'b' : 85% SMYS iii) Zone-2 (upto a distance of 12.2M from bottom end of the riser bend) Load Condition 'a' : 50% SMYS Load Condition 'b' : 67% SMYS Von Mises Stress Hypothesis is to be used for determination of combined stresses in the riser/pipeline

(b) Flexible Pipelines

The design of flexible pipelines and riser system, pipeline crossing, and tie-ins shall follow the guidelines of API RP 17B “Recommended practice for Flexible Pipe” and Specification for flexible pipe material as per Spec. 2020E Rev. 2.

Flexible pipeline is to be designed for hydrostatic collapse for a breached outer sheath with the pipeline in empty condition. The different layers & sub layers in each layer and thickness of layers required in the structure is finalized during detailed engineering.

Environmental Parameters are defined on the basis of Glenn’s Report. Pipeline sizes, design temperature/pressure, material (for rigid pipeline) etc. are decided after basic engineering.

The geotechnical data is collected during pre engineering survey as per Spec. 2011 Rev. 1. The soil data collected should be enough to determine strength and index properties required for engineering, areas prone to scour and instability.

5.8.2 APPLICABLE CODES AND STANDARDS: DNV 1981 - Rules for Submarine Pipeline System(For rigid pipelines) ANSI B31.4 - Liquid Petroleum Transportation Piping Systems. IP Part 6 - Institute of Petroleum, Model code of safe Practice. ANSI B31.8 - Gas Transmission and Distribution Piping Systems. API Std.1104 - Standard for Welding Pipelines and Related Facilities. API RP 1110 - RP for the Pressure Testing of Liquid Petroleum Lines. API RP 1111 - Recommended practice for design, construction, operation and

maintenance of offshore hydrocarbon pipeline. United States - Minimum Federal Safety Standards for Gas Lines. Part 191,192 - Minimum Federal Safety Standards for Liquid Pipelines. Part 195 SIS 05-5900 - Swedish Standards Institution for Surface Preparation.

Page 123: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 123

DNV RPB-401 - Cathodic Protection System NACE RP-06-75 - Recommended Practices: Control of Corrosion on Offshore Steel

Pipelines. API RP 5L1 - Recommended practice for Rail – Road Transportation of Line

pipe. API RP 2A - Recommended practice for planning, designing, construction of

fixed offshore platforms. API RP 5L5 - Recommended practice for marine transportation of line pipe. DNV OS-F101 - Submarine pipeline systems API RP 17B - Recommended Practice for Flexible Pipe DNV TNA 503 - Technical notes for flexible pipes and hoses for submarine

pipelines system. 5.8.3 STABILITY ANALYSIS:

The stability requirement is evaluated by lateral and vertical stability analysis of the pipeline during installation, testing and operation. The lateral stability analysis includes all environmental forces such as drag, inertia and lift as well as frictional resistance. The vertical stability analysis includes pipe buoyancy, an assessment of soil liquefaction potential, trenching depth and backfill material requirements. The following design cases are considered:

- Pipe resting on the seabed - Pipe in a Trench (if applicable) - Pipe resting on seabed and stabilized by other means such as placing additional

restraints e.g. grout bags, blocks, etc. - Pipe crossing with pipe resting on supports.

The stability requirement is primarily met by increasing the submerged weight of the pipe. The required submerged weight of the pipe for the stability analysis is determined for the following design conditions:

- Pipe empty during installation - Pipe filled with product during operation.

5.8.4 STRESS ANALYSIS AND UNSUPPORTED SPAN:

The criterion for pipe stress analysis is to maintain all stresses during installation, testing and operation within the allowable limits set by Section 1.0.

To keep pipeline stresses within the allowable limits, the unsupported spans shall not exceed certain maximum values. The static allowable spans are calculated for the following three pipeline conditions:

Pipe empty after installation Pipe flooded during hydrostatic testing Pipe filled with product during operation.

Page 124: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 124

In addition, the pipeline is designed to avoid excessive vibrations due to vortex shedding by limiting span lengths so that resonance does not occur. If this is not feasible, safety against fatigue failure is analyzed. For each of the three pipeline conditions mentioned above the shortest calculated span length is used as the maximum allowable span length.

5.8.5 COLLAPSE AND BUCKLING ANALYSIS: Wall thickness is checked against collapse in addition to hoop stress. Local buckling due to external over pressure, bending and propagation buckling due to external over-pressure are also analyzed.

5.8.6 CORROSION PROTECTION:

Pipeline external corrosion protection is provided by corrosion protection coating. This coating shall be a double coat and wrap as per the specification 2012 Rev. 1 for rigid pipelines.

5.8.7 CATHODIC PROTECTION:

The cathodic protection of pipelines is provided in accordance with the Specification No. FS 4020B Rev 0.

5.8.8 ROUTE AND PROFILE:

Utilizing the survey information the pipeline alignment is finalized. The pipeline route shall be selected such that the pipeline follows a smooth seabed profile, and avoid, wherever possible, coral reefs, and soft or liquefied soils. Where it is not practical to avoid seabed irregularities, capable of causing significant stresses in the pipeline, stress levels shall be checked against the allowable stresses. In the event that the stress levels exceed the allowable limit, the pipeline profile shall be modified such that the stress levels are within the allowable limits. Unsupported pipeline spans shall not exceed the allowable limits calculated.

5.8.9 OFFSHORE PIPELINE CROSSINGS:

The crossings is designed, such that the existing or proposed pipeline shall not be over-stressed, either during installation or operation, according to criteria mentioned in Section 1.0 and the resulting spans shall not exceed their allowable limits. The stability analysis of the pipeline and supports at the crossing is based on maximum wave heights/significant wave height at operating conditions. Separators are provided to maintain physical separation of 350mm or more between the existing pipeline and the proposed pipeline for the life span of the proposed pipeline.

5.8.10 PIPELAY ANALYSIS:

Page 125: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 125

The laying analysis is performed using the details of the proposed barge/laying method to confirm that pipelines can be laid with proposed barge and the design thickness without exceeding allowable stresses.

5.8.11 RISER DESIGN:

The design of riser is carried out in compliance with the requirements of Section 5.8.1 and code & standards specified in Section 5.8.2 above.

5.8.11.1 Riser Location:

Riser location is finalized after pre-engineering riser face survey during detail engineering. Flexible pipeline riser is enclosed in I Tube/ J Tube.

5.8.11.2 Stress Control (Rigid Pipelines):

The criterion for the riser stress analysis is to provide a safe and functional riser design. Stresses during installation, operation and testing shall not exceed the allowable limits as per Section 1.0. Expansion of pipelines and movement of jacket due to operational and environmental load is also to be considered in the riser design. For stress analysis of riser, the temperature decay along the pipeline is to be considered for thermal expansion of the pipeline.

It shall be endeavored to absorb in the riser any expansion/contraction in the pipeline or deflection of the platform caused by environmental and functional forces without the use of expansion loop by locating the first riser clamp as high as possible from the seabed or increasing the submerged weight of the pipe-line near the riser end, thus ensuring that the stresses in the riser are below the allowable limits and the loads transferred from the risers to the jacket are minimized. Flexibility analysis of the riser is carried out.

5.8.11.3 Clamps and Location:

Riser is supported by hanger flange and Riser (in case of rigid pipelines)/ I Tube- J Tube (in case of flexible pipelines) is guided by non-frictional riser clamps attached to the platform. The clamp spacing shall be such that the risers are safely supported and that calculated allowable spans are not exceeded. Number of clamps and their location shall be selected to prevent the riser from becoming over-stressed during design storm conditions while the pipeline remains in full operation. Spacing of riser clamps shall be based on risers withstanding storm conditions, temperature stresses and vortex shedding criteria given in Appendix-A to DNV rules for submarine pipeline system. Clamps shall be internally padded with 12mm thick neoprene bonded to the clamps steel surface by adhesion. Where adjustable clamps are provided, electrical continuity for cathodic protection of clamps shall be provided between jacket and clamps. All bolting on the riser clamps shall utilize fully tightened double nuts on each end of the struts. All nuts and bolts used for clamping the risers shall be XYLAN coated.

Page 126: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 126

5.8.11.4 Coating of Risers and Bends (Rigid Pipelines):

All risers, including bends, are to be coated and wrapped with the corrosion protective coating as described in the specification attached, from the sea bed upto the splash zone. All risers are to be coated with a concrete weight coating upto splash zone. The minimum thickness of concrete coating on risers shall be 30 mm. The field joint coating at the riser to pipeline connection and on risers shall follow the guidelines set for pipeline field joints. Risers extending above the splash zone are to be painted in accordance with general specification 2005 Rev.0 "Protective Coating". "Monel Jacket" is to be applied on portion extending from (-) 2.0m w.r.t. Chart Datum upto hanger flange or upto splash zone whichever is higher. A 5mm thick Monel sheet is to be welded to the riser pipe at top and bottom to form a tight jacket, which should have facilities for future testing for tightness. At onshore yard, the Monel jacket is checked for tightness by an air pressure test to 1.5 kg/cm2.

Monel Sheathing shall meet the requirements of Clause 8.13 of Spec. No. 2015 Rev.1. All the welds shall be coated with epoxy/resin to prevent corrosion.

5.8.11.5 Riser Bend:

Prefabricated shop pipe bends as described in the specification no. 2017 are to be used at the bottom (only in case of rigid pipelines) and at the top of risers. Bends radius shall be at least 5 times the outside diameter of pipe and should be suitable for pigging with a fault detection/intelligent pig. Transition from one pipe wall thickness to another shall be by internal bevel not exceeding 1 to 4 taper. Diagonal bracing shall be attached to the bottom riser bends by clamps during fabrication. These bracing shall be removed or a 600 mm section cut out of the brace after riser installation is completed and clamps are tightened. The brace shall not be welded to the pipeline. The clamps shall be padded with 12 mm thick neoprene padding as per Clause 8.10 of specification No. 2015 Rev.1.

5.8.11.6 Cathodic Protection of Risers:

Cathodic protection of risers is to be provided in conformance to Spec. No. FS 4020B Rev.0 and Electrical design criteria.

5.8.11.7 Hanger Flanges:

All pipelines shall be provided with suitable hanger flanges for supporting the risers. The riser hanger flanges shall be designed, manufactured and installed as per relevant Codes and Standards.

Page 127: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 127

Flexibility analysis for all risers and connected deck piping is carried out to determine the design loads.

5.8.11.8 I-Tubes/J-Tubes (in case of Flexible Pipelines):

I-Tubes/J-Tube along with other related appurtenances like bell mouth/seals, clamp etc. is designed for all flexible risers. In case of alternative arrangement also, the same shall be applicable.

The I-tube/J-tube assembly is designed as per structural design criteria and provided with external Monel sheathing in the splash zone portion i.e. between elevation – 2.0 m and upto the bottom of hanger clamp or +5.5 m elevation, whichever is higher as per Spec. No. 2015, Rev. 1.

5.8.12 DESIGN REVIEW:

Following reports are prepared during detail engineering:

Pipeline Design Criteria Report Pipeline Design Report Riser Design Report Installation/Testing Method Report Specifications Cathodic Protection System design report

a) Pipeline Design Criteria Report includes:

Appraisal of Data (environmental, bathymetry, soils, etc.) Selection of the Pipeline Route and pipeline length Pre-engineering, pre-construction and post-installation survey reports

b) The Pipeline Design Report includes:

Pipeline wall thickness analysis Pipeline Stability Analysis Pipeline Stress Analysis. Pipe lay analysis Pipeline Buckle & Collapse Analysis Pipeline Unsupported Span Analysis Pipeline Crossing Stability and Stress Analysis Pipeline Expansion analysis. Pipe Cathodic Protection Analysis

c) The Riser Design report includes:

Riser Flexibility Analysis (in case of rigid pipelines) Riser Stress Analysis (in case of rigid pipelines) Clamp Loads Vortex shedding analysis Clamps and clamps spacing/allowable spans

Page 128: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 128

d) The Installation Methods Report shall include :

Pipeline Risers Hydrotest Pull-in Analysis (in case of flexible pipelines)

e) Specification for:

Rigid Pipelines Pipe Pipe Bends Pipe Fittings & Flanges, if any Corrosion Protection Coating Concrete weight coating Field Joint Coating Splash Zone Materials Pipeline Crossings Tie-in fittings Cathodic Protection System Trenching and burial, if required

Flexible pipelines

Pipelines, End Connectors/ Fittings Corrosion Protection Coating for I-tube/J-tube assembly, end connector/

fittings Cathodic Protection of flexible pipe, I-tube/J-tube assembly, end

connectors/fittings Splash Zone Materials Pipeline Crossings Trenching and burial, if required

5.8.13 DRAWINGS:

The following drawings are prepared during detail engineering:

Area Maps Pipeline Alignment Drawings Anode Installation drawings Pipeline Approach to and Departure from platforms Pipeline Crossings. Riser Elevation and Clamps spacing, riser makeup Clamps details

5.8.14 PIPELINE INSTALLATION:

All works related to pipeline installation is performed in accordance with the specifications 2015 Rev. 1 and 2015A Rev. 1. Both, S-lay or Reel-lay methods for laying of rigid pipelines are acceptable based on overall cost economics.

Page 129: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 129

In S Lay method the pipeline is tensioned at the lay barge and supported on stinger having a positive buoyancy to compensate for the weight of the pipeline so as to avoid generation of higher stresses in the over bend and sag bend region. The following laying parameters are obtained through stress analysis:

Tension in the pipeline Length, shape and buoyancy of stinger

In REEL LAY method the pipes are welded together at the shore based yard. Also, corrosion coating has is applied at the onshore yard. Next, welded pipes are spooled on to the pipe laying vessel’s reel (normally a D.P. vessel). To initiate pipe lay, the end of pipe stalk is anchored, and the pipe laying vessel then move along the pipeline route, unreeling pipes as it advance. In this method, concrete weight coating cannot be applied, and hence on bottom stability may be achieved by increasing the wall thickness of the pipe, if required. For submarine pipeline to be laid by Reel Lay Method, pipe material & procedures, etc. shall comply to the requirements of Section 7H of DNV OS-F101 Offshore Standard for Submarine Pipeline Systems 2000 edition.

5.8.15 HYDROSTATIC TESTING OF PIPELINE SYSTEM:

Testing of pipeline & riser system is carried out as per the specification no. 2022 Rev. 0 completion of all installation works of pipelines, risers, crossing, operations and remedial works, if any. Before hydrostatic testing, the pipeline & riser shall be cleaned with a mechanical pig. Hydrostatic test is carried out for a minimum continuous period of 24 hours after stabilization, to a test pressure of 1.25 times the design pressure.

5.8.16 POST – CONSTRUCTION SURVEY:

Survey of the installed pipeline system, with all necessary equipment, such as sub-bottom profiler, side scan sonar, echo sounder etc. for determining the extent of unsupported spans, damage etc. is carried out.

5.8.17 AS BUILT PIPELINE SYSTEM REPORT:

On completion of hydrostatic testing, As built Drawings/Reports for all pipeline system is prepared. Alignment details shall be obtained from plotted data taken during construction and post-construction surveys. All pertinent data such as pipeline appurtenances, fittings, crossings, unsupported spans, burial details, location of anodes, elevation of riser clamps, Monel sheath and hanger flange etc. are accurately located on the "As Built Drawings".

6.0 ISO GUIDELINES FOR BID PACKAGE PREPARATION:

Preparation of the bid package during the basic engineering of a project is done in line with approved ISO procedures and the documents are prepared as per approved ISO formats. These procedures and formats form a part of the ISO Manual issued by the Offshore Design Section.

Page 130: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 130

The ISO Manual provides guidelines that would enable the Offshore Design Section to provide services at par with international standards of excellence to the satisfaction of the customers in the area of Design and Development of offshore facilities. The ISO Manual consists of three broad sections: • Quality Manual • Quality Procedure Manual • Formats The Quality Manual defines the policy and objectives of the Offshore Design Section; resources available with the section and the functional policies of the section. The Quality Procedure Manual defines the various procedures for different activities of the Offshore Design Section. The Procedure Manual also identifies the person responsible for execution of a particular procedure. The Formats section of the ISO Manual contains forms and checklists used by the Offshore Design Section. The documents that form a part of the bid package are generally prepared as per format no.: ODS / SOF / 004 of the ISO Manual. It is essential to have a good understanding of the requirements listed in the ISO Manual and prepare the bid package in line with the laid procedures and in the approved formats, so as to generate a quality bid package that would ensure successful development of the offshore field and efficient operation of the facility, while maintaining safety of platform and personnel.

7.0 QUALITY ASSURANCE:

As mentioned in its Quality Manual, the Offshore Design Section is committed to provide services at par with international standards of excellence to the satisfaction of the customer. This is ensured not only by generating comprehensive design documents, but also by ensuring that the products / instruments received are of good quality and can perform the intended function, while remaining functional for the laid down design life. This is in turn ensured by accepting products only from established suppliers and laying stringent inspection and testing requirements for all items / equipments.

7.1 The items / equipment used in the setting up of offshore facilities are always procured from established suppliers through the turn-key contractor executing the project. In case, an item is to be procured from a new supplier, the supplier and his product is approved only after the required pre-qualification documents are submitted and found satisfactory. These pre-qualification documents include:

• Past track record of similar item for similar service in offshore application along

with details of clients, type of product, make, size, service, year of completion, and copies of any feedback information received from clients regarding

Page 131: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 131

functioning of equipment / material supplied. This is necessary to ensure that the product offered is not a prototype. Only such items / equipments which are of proven design that have been in continuous satisfactory service on offshore installation for a minimum period of two (2) years are accepted for use on the offshore platforms.

• Leaflets / catalogues / drawings / sketches of the particular product being supplied – This is necessary to ensure that the offered product can meet the necessary technical specifications.

• Details of their Indian Vendors (in case of foreign vendors) and sub-suppliers, viz. the name(s) of Manufacturer etc. for easy correspondence and after-sales requirements

• Quality assurance Manual for review by Offshore Design Section, to analyze the schemes for product quality assurance, storage and traceability of products, quality assurance and quality control procedures.

• The Supplier’s Company profile with details of organogram & facilities to assess the capability of the personnel to assist in testing and commissioning activities.

7.2 All items that are procured by the turn-key contractor for use / installation on offshore

platforms are subjected to inspection and testing by the Offshore Design Section / Certifying Agency (CA) appointed by the Offshore Design Section / the turn-key Contractor and / or a Third Party Inspection Agency (TPIA) appointed by the turn-key Contractor & authorized by the Offshore Design Section. According to the type of inspection carried out on the product, the product is classified as Category A, Category B or Category C.

• Category A Item: Items under this category are inspected by the Certifying Agency (appointed by the Offshore Design Section) either stage-wise or at the final stage. The result of this inspection is submitted to the Offshore Design Section for review. This inspection is in addition to the inspection carried out by the turn-key Contractor / the TPIA.

• Category B Item: Items under this category are inspected by the turn-key Contractor / the TPIA during the intermediate and / or final stages. The inspection report is then submitted to the Offshore Design Section / the CA at the fabrication yard to obtain clearance for usage of the material / equipment.

• Category C Item: The material test certificates / compliance reports for items under this category are submitted to the turn-key Contractor for review. If these documents are found in order, the turn-key Contractor endorses them as “Reviewed & Accepted”. These duly endorsed documents are then submitted to the Offshore Design Section / the CA at the fabrication yard to obtain clearance for usage of the material / equipment.

Page 132: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 132

ANNEXURE – I

LIST OF COMMONLY USED BARGES

S. No. BARGE

YEAR OF

CONSTN

CRANE TYPE

CAPACITY TOTAL

BOOM LENGT

H

CAPACITY AT BOOM LENGTH

1 DLB

REGINA 250

1978

CLYDE 4063

250 MT

57.9 M

250 T AT 18M

2 GAL CONSTR.

1978

4100 VICON WITH RINGER

300 T

61 M

150 T AT 45’

3 DLB/DB NAVAJO -

AMERICAN-REVOLVER

356 -

180’ 150 ST AT60’

4 WB 80 1980

MANITOWAC-4000 CRAWLER

150 T

140’

33.5MT

AT 12.2M

5 JWB 250 1969

MANITOWAC-4100 CRAWLER 73MT

AT 12M

6 SARMAX UTAMA

1981

AMERICAN HOIST 9310 CRAWLER

225 ST

150’ -

7 SARMAX 2000

1991

AMERICAN HOIST 9320 CRAWLER

250 ST

170’ -

8 JAVA CONSTR.

1982

PADASTAL MOUNTED AMERICAN

HOIST

200 ST

200’

200ST(180M) AT 80’

9 WB 97 1983 AMERICAN HOIST

280 T 150’ -

10 SARKU

SAMUDRA

1983 AMERICAN HOIST-11760

280 T 150’ 127 ST AT

28’

11 SEABULK OFFSHOR

E

1973

MANITOWAC-4000W

CRAWLER - -

33.5MT AT 12.2M

RADIUS

12 SEABULK MAIMTAI-

NER

1966 -DO- - - -

13 SUBTEC-1 1977 MANITOWAC-4100 - - 82MT AT

8.5M

14 SCANLAY-1

1982

DETAILS NOT

SUBMITTED - - -

Page 133: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 133

ANNEXURE – II LIST OF FUNCTIONAL SPECIFICATIONS USED BY OFFSHORE DESIGN SECTION

Discipline S. No Spec. No. Description

1 2011 Submarine pipeline route surveys

2 2012 Coal tar Enamel coating of submarine pipelines

3 2013 Concrete weight coating of submarine pipelines

4 2014 Field Joint coating of submarine pipelines

5 2015 Installation of submarine pipeline and related facilities

6 2015 A Installation of submarine flexible pipes

7 2016 Anodes for cathodic protection

8 2017 Anode Installation of submarine pipeline

9 2018 Long radius bends submarine pipelines

10 2019 welding

11 2020 A Carbon steel seamless line pipe for submarine pipelines

12 2020 B Carbon steel seamless line pipe for submarine pipelines (sour service)

13 2020 E Flexible pipes

14 2021 Trenching & backfilling of submarine pipelines

15 2022 Hydrostatic testing of submarine pipelines

16 2024 A Fittings & flanges for submarine pipelines

17 2024 B Fittings & flanges for submarine pipelines( sour service)

18 2025 A Sub sea ball valves

19 2025 B Sub sea ball valves ( sour service)

20 2028 A Sub sea Flow tees

21 2028 B Sub sea Flow tees ( sour service)

22 2029 A Sub sea Pig signalers

PIPE

LIN

E

23 2072 B Sub sea butterfly valves for SPM( sour service)

1 5001 Centrifugal Pump

MEC

HA

NIC

AL

2 5002 Equipment Noise Limit

Page 134: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 134

Discipline S. No Spec. No. Description

3 5003 Heat Exchanger

4 5004 Equipment Vibration

5 5005 Reciprocating Pump

6 5009 Reciprocating Compressor

7 5011 Skid Mounted Separator

8 5012 HVAC

9 5014 Shell & Tube Head Exchanger

10 5015 Air Cooled Exchanger

11 5018 Gas Turbine

12 5052F Deck Crane

13 5055F OCI Transfer Pump

14. 5055C Reciprocating Pump – Controlled Volume

15 5056F Rotary Gear Pump

16 5100W Packaged Equipment for well platforms

17 5100P Packaged equipment for Process platform

18 5101 Safety Studies

19 5102 Safety specifications

20 5103W Commissioning procedure for well platform

21. 5103P Commissioning Procedure for process platform

22 5104 HSE Requirement

23 5105 FGC

1. 3100 Level Gauge

2. 3101 Level Switch (Pneumatic)

3. 3102 Level Switch (Electrical)

INST

RU

MEN

TATI

ON

4. 3103 Level Transmitter

Page 135: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 135

Discipline S. No Spec. No. Description

5. 3200 Flow Switch

6. 3201 Flow Totalizer

7. 3202 Electronic Flow Transmitter

8. 3203 Orifice Plate

9. 3204 Restriction Orifice Assembly

10. 3205 Senior Orifice Assembly

11. 3206 Rotameter

12. 3207 Turbine Flow Meter

13. 3208 Coriolis Meter

14. 3209 MPFM

15. 3210 Gas Flow Computer

16. 3211 Liquid Flow Computer

17. 3300 Temperature Gauge

18. 3301 Temperature Switch (Electrical)

19. 3302 Temperature Transmitter (Electronic)

20. 3400 Differential Pressure Gauge

21. 3401 Pressure Gauge

22. 3402 Pressure Switch (Electrical)

23. 3403 Pressure Transmitter (Electronic)

24. 3500 Fire & Gas Detection System

25. 3501 Shut Down Panel (Pneumatic)

26. 3502 Telemetry Interface Cabinet

27. 3503 Instrumentation for Equipment Package

28. 3600 Hi-Lo Pilot Switch

29. 3601 Pressure Indicating Controller

ISN

TRU

MEN

TATI

ON

(C

ontd

.)

30. 3602 P / I Converter

Page 136: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 136

Discipline S. No Spec. No. Description

31. 3603 Recorder (Electronic)

32. 3604 Recorder (Pneumatic)

33. 3605 Portable Calibrator

34. 3607 Filter Regulator

35. 3700 Control Valve

36. 3701 Safety Relief Valve

37. 3702 Self Actuated Pressure Control Valve

38. 3703 Deluge Valve

39. 3800 Chlorine Analyzer

40. 3801 Corrosion Analyzer

41. 3802 Dissolved Oxygen Analyzer

42. C100 Distributed Control System

43. C101 Programmable Logic Controller

1 2004-A Specification for piping design

2 2004-B Specification for piping fabrication & installation

3 2004-C Specification for unfired pressure vessels

4 2004-D Specification for piping specialties

5 2004-E Specification for flexible piping

PIPI

NG

6 2006 Specification for insulation of piping & Equipment

1. 4011-P Emergency Generator & Accessories

2. 4012-P L.V. Switchgear

3. 4013-P Battery & Battery Charger

4. 4014-P Navigational Aids

5. 4016-P Lighting & Power Distribution Panel

6. 4017-P Medium & High Voltage Cables & Accessories

7. 4018-P FRP Cable Trays

ELEC

TRIC

AL

8. 4019-P Aviation Marker Lights

Page 137: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 137

Discipline S. No Spec. No. Description

9. 4020-B Cathodic Protection System for structures with Monitoring System

10. 4021 Light fittings & Junction boxes

11. 4022 Explosion proof Plugs & Sockets

12. 4023 Industrial type Plugs & Sockets

13. 4024 Explosion proof Control / Local Push Button Stations

14. 4025 Industrial type Control / Local Push Button Stations

15. 4026 Div-2 Explosion proof light fittings and junction boxes

16. 4027 Self contained Emergency Luminaries

17. 4028 Neutral Grounding Resistors

18. 4029 Heaters & Controls

19. 4030 Communication cables

20. 4031 Paging & Intercom System

21. 4032 Radio system

22. 4033 Automatic telephone exchange

23. 4034 Close circuit TV (CCTV) system for process area monitoring

24. 4035 Uninterrupted power supply (UPS) system

25. 4036 Motorized actuator for valves (MOVs)

26. 4037 Generator relay control, synchronizing & load shedding panel

27. 4038 Fixed type Alok Chauduri & DC Distribution Boards

28. 4039 HV metal clad switchgear

29. 4040 Synchronous Generator & Accessories

30. 4042 Power distribution transformer (Cast Resin type)

31. 4001 Electrical work

32. 4002 Electrical work of skid mounted equipment

33. 4003 Electrical Heat Tracing

34. 4004 HV Motors

35. 4005 MV Motors

Page 138: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 138

Discipline S. No Spec. No. Description

36. FS-4001 Cathodic protection of offshore structures

37. FS-4002 Cathodic protection of submarine pipeline

38. FS-4003 Navigational aids

39. FS-4003-SPM Navigational aids for SPM

40. FS-4004 Lighting and power distribution board

41. FS-4005 FRP cable trays

42. FS-4006 Light fitting and junction box

43. FS-4007 Solar power system

44. FS-4008 MV Motors

45. FS-4009 Lighting Transformer

46. FS-4010 Emergency Light

47. FS-4011 Electrical Cable

48. FS-4012 Explosion proof control station

49. FS-4013 LV Switchgear

50. FS-4014 Motorized actuator for valve

51. FS-4016 Electrical Heat Tracing

52. FS-4017 Electrical equipment with packaged plant

53. FS-4018 Boost charging at well platform

54. FS-4019 Intrinsically safe walkie talkie set technical specification

1 6001 General Specification for material fabrication & installation of structure

STR

UC

TUR

AL

2 2005 General Specification for protective coating

Page 139: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 139

ANNEXURE III – SUGGESTED LIST OF SUPPLIERS

Discipline S. No Equipment / Material Supplier

1. Deck Crane a) Weatherford, USA b) Favelle Favco, Australia c) Manitowak, USA d) Seaking, USA e) Nautilus, USA f) Raina Engineers,Mumbai g) American Aero, USA

2. Pneumatic Pumps a) Haskal Energy, UK b) Nikkiso, Japan

3. Vessels a) L&T, Hazira/Powai b) R.D.Engineers, Mumbai (India) c) Kilburn, Mumbai (India) d) BHEL, Trichy e) MIS, Sharjah

4. Test Separator a) Deutche Babcock, AbuDhabi

b) MIS, Sharjah c) IMS, Italy d) L&T, Hazira (India)

5. Inst./Utility Gas

System a) Dodwell, Japan b) Tide Air Inc. USA c) McNeill & Magor, Mumbai (India) d) Howmar e) Nigata, Japan f) Kilburn,Mumbai

MEC

HA

NIC

AL

6. Chain Pulley Block a) Ingersoll Rand, USA b) Beebe International Inc. USA c) Dresser, USA d) Ajmeera, India e) Kito, Japan f) Air Dyne

Page 140: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 140

Discipline S. No Equipment / Material Supplier

7. Heat Exchangers a) BHPV, India b) EBM-Hudson, Italy c) IMB (Industrie Meccaniche Di Bagnolo spa)

Italy d) Nuovo Pignone SPA, Italy e) OLMI SPA, Italy f) HHI, KOREA g) Belleli Energy srl, Italy h) L&T, India i) Kavery, India

8 Produced Water Conditioning System

a) Skimovex dv. Netherland b) Wemco, USA c) Pertolite d) Technomirk with Snam e) Axsia Serck Baker, f) Petreco, UK

MEC

HA

NIC

AL

(Con

td.)

9. Fire Water Pump a) Weir Pumps, UK b) Pompes Guinard, France c) Fluid Power, USA d) Peerless Pumps, USA/Australia e) Ingeroll Rand UK, USA f) Worthington Pumps, UK g) Thompson Pumps h) KSB Pumps, Germany i) Ebara Corporation, Japan j) SPP, UK

Page 141: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 141

Discipline S. No Equipment / Material Supplier

10. Utility Generator A.GENERATOR a) AVON – KAICK b) KATO c) ALSTHOM

B.ENGINE a) Fuji Electric, Japan b) Cooper Energy Services c) MAN AND B&W Engine, Germany d) OT-Waltsila e) Suizer Brothers Ltd. f) Societe Alsacienne Deconstr Mecan g).Compagnia Genesale Tractore SDA h) FIN Cantieri Div.Grandi Motor i) MAN-UNTERREHMNSBERI CH. Diesel Motoren A.G.

C. ENGINE SUPPLIER AND PACKAGER

a) Steward & Stevenson, USA b) Geveke Motoren, Netherlands c) Caterpillar, USA d) KATO, USA e) Ruston Diesel, USA f) Wankesha Pearce Ind.Inc, USA g) Cummins, USA h) Detroit Diesel, USA

i) Regon Equpt.Co.USA 11. Instrument Air

Compressors a) Tide Air b) Atlas Capco c) Worthington Turbodyne d) Bellies Morcom e) Norwalk, USA f) Compare, UK g) Ingersoll Rand, USA/India

MEC

HA

NIC

AL

(Con

td.)

12. Chlorinators a) Electro Catalytic b) Engel Hard, UK c) Diaki Engineering Co. Ltd, Japan d) Mistsubishi Heavy Ind.Japan e) Petreco International, UK

Page 142: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 142

Discipline S. No Equipment / Material Supplier

13 Sea Water Lift Pumps a) Weir Pumps, UK b) Pompes Guinard, France c) KSB, Germany d) Ebara Corporation, Japan e) Worthington Pumps, Italy f) Thompson Kelly & Lewis g) DMW, Japan h) UPC, USA i) SPP, UK j) BPCL, India

14 Fuel Gas Conditioning And Compressors

a) Petreco, UK With Peter Brother b) Paladon, UK c) Ingersoll Rand, USA d) Cenatco, UK e) IHI, Japan f) Axsia Serck Baker g) Alien Process Ltd, UK

MEC

HA

NIC

AL

(Con

td.)

15.

Process gas compressor module (Vendors to meet Bid Evaluation Criteria and other Bid Specification)

A) PROCESS GAS COMPRESSOR

a) M/s KHI, Japan

b) M/s IHI, Japan

c) M/s Dresser Rand, USA

d) M/s Copper Energy Services, USA

e) M/s MAN Turbo, Germany

f) Elliott (now owned by Ebara, Japan)

g) M/s Solar Turbines Inc, USA

h) M/s Demag – De Laval (Siemens

AG, Germany)

B) GAS TURBINES

a) M/s General Electric, USA

b) M/s Rolls – Royce, UK

c) M/s Alstom (M/s EGT), UK

d) M/s Solar Turbines, USA

Page 143: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 143

Discipline S. No Equipment / Material Supplier

16.

TURBINE GENERATOR SET (Vendors to meet Bid Evaluation Criteria and other Bid Specification)

A) GAS TURBINES

a) M/s General Electric, USA b) M/s Rolls – Royce, UK c) M/s Alstom (M/s EGT), UK d) M/s Solar Turbines, USA

B) ALTERNATORS a) M/s Brush Electric, USA b) M/s General Electric, USA c) M/s Siemens, Germany d) M/s Alstom, UK e) M/s Fuji Electric, Japan

1 Dry Chemical Skid a) Ansul Fire Protection, USA b) Safety & Health, USA c) Wormald, USA d) Fire Boss, USA

2. Portable Fire Extinguishers

a) Kooverji Devshi & Co. Pvt. Ltd. Mumbai b) Wormald Fire Engg. USA c) Houston Fire Safety Eqpt. Co., USA d) Doopley Fire System Inc., USA e) Zenith Fire Services, Mumbai (India)

3. Life Preservers (Life

Jackets) Life ring Buoys), Inflatable Life Rafts, First Aid Kits, Fire Blanket, Fireman’s Outlet, Breathing Equipment Stretcher, Personnel Baskets Scramble nets

a) Ahmed. S. Moloobhoy & Sons. Mumbai b) Meridian Inflatable Pvt. Ltd., Mumbai c) Aero marine Industries Pvt. Ltd., Madras d) Wormald Fire Engg. USA e) Houston Fire & Safety Eqpt. Co. USA f) Alexander Industrial INC. Houston g) Keegan Speciality, USA h) Billy Pugh Co. Inc,USA i) Eastern Stores,Mumbai j) Galvianiser,Mumbai k) Mercantile & Marine Services ( I ) Pvt. Ltd.

Mumbai, India

4. Eye Wash & Safety Shower

a) Unicare Emergency Equipment, M’bai b) Offshore Clothing and Suppliers Ltd.UK c) Nippon Encon. Mfg. Co. Ltd. Japan

SAFE

TY IT

EMS

5. Helicopter Rescue Kit a) Bristol Uniform Ltd., Bristol, UK. b) Wormald Fire Engg. USA c) Houston Fire Safety Eqpt. Co., USA d) Doopley Fire Systems Inc. USA e) Joseph Lesilic & Co., Mumbai, (Inida) f) AMCO, USA

Page 144: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 144

Discipline S. No Equipment / Material Supplier

6. Personnel Protection Eqpt. From H2S Exposure

a) Wormald Fire Engg. USA b) Dooley Fire Systems Inc., USA c) Nohmi Fire Safety Eqpt. Co. USA d) Houston Fire Safety Eqpt. Co. USA e) Drager Aktiengesell Schaft, Germany Joseph

Lesilic & Sons, Mumbai (India) f) AMCO, USA

1. Telemetry Interface Cabinet

a) Marine Electricals, Mumbai (India) b) Fabricon, Mumbai c) Switch Gears & Control, Mumbai (India) d) Elec. Mech. Corporation, Mumbai (India) e) Marine Delight, Calcutta (India) f) YEW, Japan g) Backer-CAC, USA h) Yokogawa Blue Star, India

2. Well Fire Shutdown Panel & Test Separator Shutdown Panel

a) Backer CAC, USA b) Haven Automation, Singapore c) Brisco Engineering, UK d) Autocon, USA e) Petrotech, USA f) Bousted Services,Singapore g) Wormald,UK

3. Pneumatic Pr.Switch/HI-LO Pilots (Indicating dial type)

a) BACKER CAC, USA b) WKM, USA c) Axelson, USA d) Petrotech, USA e) Helliburton Energy

4. Pr. Switches (Explosion Proof)

a) SOR, USA b) Danfoss, India c) ITT Neo Dyn., USA d) Aschroft, USA e) YEW, Japan f) Delta Controls, USA g) Backer CAC, USA h) Dag Process (I)

INST

RU

MEN

TATI

ON

5. Pr. Relief Valves a) IMI Bailey Birkit, UK b) Sapag – Alshom, France c) Anderson Greenwood, USA d) Fukui, Japan e) Crosby, UK f) Teledyne Farris Engineering, USA g) Moorco (India) only for NON-ASME Service h) Triangle, UK i) AUDCO India Ltd.

Page 145: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 145

Discipline S. No Equipment / Material Supplier

6. Pr. Indicating Controllers

a) Yokagawa, Japan b) Fisher, UK c) ITT Barton, USA d) Foxboro, USA e) Taylor, India/USA f) ABB-Kent, UK

7. A) Large Case Field Recorders

a) Taylor, India b) Fox Boro, USA c) ITT Barton, USA

d) Yokagawa, Japan

B) Field Pneumatic Integrators

a) Taylor, India b) Yokagawa, Japan

8. Gauge Glass & Cocks a) Daniels, USA b) Nihon Klinger, Japan c) Patrole Services, France d) Jerguson Gauge & Valve Company, USA e) Chemtrols, Mumbai (India) f) Protolina, Mumbai (India) g) Samil, Korea h) Penburty, USA i) Technomatic, India

9. Level Instruments (Pneumatic (Level-controls & Level Switches)

a) MSW Controls, UK b) Fisher Controls, UK c) Magnetrol, Belgium (only Level Switches) d) Masoneilan, France (only Level controls) e) Eckardt, Germany (only Level-controls) f) S.O.R.USA (only Level Switches) g) Backer CAC, USA (only Level-switches0

h) Chemtrols (I) (only Level-switches)

ISN

TRU

MEN

TATI

ON

(Con

td.)

10. Level Switches (Explosion Proof)

a) SOR, USA b) Petrol Service, France c) MSW Controls, UK d) Tokyo Keiso, Japan e) Magnetrol Intl, Belgium f) Dag Process (I) g) Chemtrol (I)

Page 146: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 146

Discipline S. No Equipment / Material Supplier

11. Pressure Gauges a) Gauges Bourden, UK b) Bundenberg Gauges, UK c) Aschroft, USA d) ITT Barton, USA e) Ametek, USA f) Manometer India g) WIKA, Germany h) General Instruments

12. Differential Pr. Gauges/Indicators

a) Burdon, France b) Gauges Bourdon, UK c) ITT Barton, USA d) WIKA, Germany e) Meriam Inst., USA f) Aschcroft, USA g) Barton Inst. UK

13. Pr. Transmitters/P to I Convertors

a) Gould, USA b) Instrumentation Ltd. Kota (India) c) Rosemount, Mumbai (India) d) Taylor, Faridabad, India e) Rosemount, Singapore f) YEW, Japan g) Honeywell,USA h) ABB-Kent, UK i) Youogawa Blue Star,India j) Fisher Controls,UK k) Amerson Process

14. Solenoid Valves a) SCO, USA

b) Blackborough,UK c) Maxseal, UK d) Skinner, USA

ISN

TRU

MEN

TATI

ON

(Con

td.)

15. Turbine Flow Meter a) Daniels, USA b) Bopp & Reuther, Germany c) Flow Tech. USA d) Moorco, India e) Smith, USA f) Brooks Inst. USA g) ITT Barton, UK h) FMC Sammar

ISN

TRU

MEN

TATI

ON

(Con

td.) 16. Temperature

Transmitters a) Rosemount, Singapore b) Yokagawa, Japan c) Schlumberger d) ABB- Kent. UK

e) Honeywell, USA

Page 147: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 147

Discipline S. No Equipment / Material Supplier

17. Temp. Gauges a) Ascroft, USA b) Gauges Bourdon, UK c) Nagano Keili, Japan d) General Inst.Mumbai (India) e) A.N. Instruments (I) f) WIKA, Germany

18. ESD & FSD Valves a) Baker CAC, USA b) Sigma USA c) Protection system & Devices, India d) Versa, Neitherland

19. Temp. Switches a) Delta Controls, UK b) ASCO, USA c) KDG Instruments, UK d) Nagano - Keiki, Japan e) SOR, USA f) ITT-Snider

g) Aschcroft – Dresser, USA 20. Fusible Plugs a) Baker CAC, USA

b) Sigma, USA c) Ruelco, USA (M/s Nisson Consultant,Mumbai)

21. Flame Arrestors a) Petrols Service, France b) Groth Equipment Corporation USA c) GPE Controls, USA d) Braunsch Weigr, Germany e) Whersoe, S.A France f) Shand & Jurs, USA g) Marvac, UK h) Safety System, UK

22. Orifice Plates & Flanges and Restriction Orifices

a) Perry Equipt. Corpn, USA b) Daniels, USA c) Taylor, India d) Micro Precision, Faridabad (India) e) General instrument consortium (Mumbai)

23. Senior, Junior Simplex

Orifice Fittings a) Daniel, USA b) Perry Equipment Corpn., USA

24. Filter regulators a) Shavo Norgen, Madras (India) b) Fisher Controls, UK c) Masoneilon, France d) Taylor, India

ISN

TRU

MEN

TATI

ON

(C

ontd

.)

25. Flow Switches Pneumatic & Electric)

a) MSW, UK b) Magnetrol, Belgium c) Tokyo Keiso, Japan d) Link, USA e) Yokogawa Blue Star, India

f) ITT Barton

Page 148: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 148

Discipline S. No Equipment / Material Supplier

A) Control Valves a) Fisher Controls, UK b) Masoeneilon, France c) Blake Borugh, UK d) Motoyama Engineering Works, Japan e) KOSON, Singapore f) ABB-Kent, UK g) Weir valves & controls, UK ltd

26.

B) Self Actuated Pressure Control Valves

a) Fisher Controls, UK b) Masoeneilon, France c) ESME, UK d) Weir valves & controls, UK ltd

27. Gas Detection Systems a) Seiger, UK b) General Monitors, UK c) Haven Automation, Singapore d) Detronics, USA e) Delphian, USA

28. Deluge Valve with Test Facility

a) George Kent, Singapore b) Wormald, Hong Kong/Singapore c) Cla-Val, USA d) MIL Ltd.

29 Water Cut Meter a) Emerson process

30 Rota Meter a) AL Flow Glass Equipment, India b) Tyco Kiesco Co. Ltd. Japan

31 Distributed Control System

a) Foxboro, USA b) Baily Controls, USA c) Toshiba, Japan

d) Honeywell, USA e) Yokogawa, Japan

f) Fisher Rosemount, UK g) Yokogawa Blue Star, India

32 Fire and Gas Detection System

a) Nohmi Bosai, Japan b) G.P.Elliot, UK c) Safety Systems, UK d) ICS, UK e) Seiger, UK

f) Yokogawa Indl.Safety System,Malaysia 33 Dew point analyzer a) M/S Panametrics,USA

ISN

TRU

MEN

TATI

ON

(C

ontd

.)

34 Data logger a) M/S Econ instruments b) Flueke

PIPI

NG

1. Pipe (Duplex SS) a) Sumitomo Corporation, Japan b) Kawasaki, Japan c) NSC, Japan d) Sandvik, Sweden e) Avesta, Sweden f) Mannesmam, Germany g) NKK, Japan

Page 149: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 149

Discipline S. No Equipment / Material Supplier

2. Fittings (Duplex SS) a) Sumitomo, Japan b) Sandvik, Sweden c) Shmoda Iron Works Co.Ltd.,Japan d) Coprosider Spa, Italy e) Mannesmann Rohren, Germany f) NKK, Japan

3. Flanges (Duplex SS) a) Sumitomo, Japan b) Sandvik, Sweden c) Nicola Galperti & Figlio, Italy d) Coprosider Spa. Italy e) Mannesmann, Germany f) Melesi,Italt (for sub-sea flanges)

4. Ball Vales (D.S.S)

a) KTM, Japan b) Kitz, Japan c) Deutsch Audco. Germany d) Argus, Germany e) Grove Italia Spa. Italy f) T.K.Valves(Abu Dhabi) |Ltd. g) Petrol Valves,Italy

5. Shutdown Valves DSS a) KTM, Japan b) Kitz, Japan c) Deutsch Audco. Germany d) Argus, Germany e) Grove Italia Spa. Italy f) T.K.Valves (Abu Dhabi) |Ltd.

g) Petrol Valves, Italy

6. Other Valves (Gate Globe, Check) D.S.S.

a) Kitz. Japan b) KTM, Japan c) Rona Valves, Belgium d) Petrol Valves, Italy e) T.K. Valve (Abu Dhabi) Ltd. f) Valvinox, Italy

PIPI

NG

(Con

td.)

7. Pipe (NACE C.S.) a) Sumitomo, Japan b) NKK, Japan c) Nippon Steel Corporation, Japan d) Mannesmann, West Germany e) Misubishi Corporation, Japan f) Dalmine Spa. Italy g) Mitsui & Co. Kawasaki h) Raccordi Forgiati, Italy (NACE Pipes-

A106GB NACE pipe API 44 x 52) i) Kawasaki, Japan j) OMR Officine Meccaniche,Italy k) Schulz Export EMBH, Germany l) Engineering Supply EST

Page 150: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 150

Discipline S. No Equipment / Material Supplier

8. Fittings (NACE C.S) a) Sumitomo, Japan b) Mega Spa. Italy c) Gam Recordie, Italy d) Raccordie Forgiati, Italy e) Fittinox Sri Italy (A 105) f) OMR Officine Meccaniche, Italy g) Schulz Export EMBH, Germany

(NACE Fittings MSS-SP-75 WPHY 52 NACE Fitting A234 WPB Seamless)

9. Flanges (NACE C.S) a) Sumitomo, Japan b) Coprosider Spa. Italy c) Nicoa Galpeti Figtio, Italy d) Trouvay & Cauvin. France e) Melesi, Italy f) Ambrocio Melesi & C Sri, Italy (A 105 &

A694 F 52) g) Galpeti (A 694 & A 105) h) MGL,France i) Schulz Export EMBH, Germany

PIPI

NG

(Con

td.)

10. Valves (NACE C.S) a) Cameron Iron Works, USA b) Grove Italia, Spa c) KTM, Japan d) Deutach Audeo, Germany e) Argus, Germany f) Kitz, Japan g) Serck Audco Valves International UK h) Flow Control Technology, France i) Crane, USA j) Orbit Valve, UK k) T.K.Valve (Abu Dhabi) l) Omb Spa, Spain (Upto 1.5” size) m) Petrol Valve, Italy n) Valvinox, Italy o) Universal Sri. Italy NACE Ball Valve (4” &

Below) Caslid NACE Gate, Globe, Check Valve (above 2”) Forged NACE Gate, Globe, Check & Needle valve (2” & below)

p) LCM Italia SRL, Italy q) SACCAP S.A. France

(Gate,Globe,Check&Needle Valves)

Page 151: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 151

Discipline S. No Equipment / Material Supplier

11. Shutdown Valves NACE C.S

a) Grove Italia, Italy b) KTM, Japan c) Argus, Germany d) Cameron Iron Works, USA e) KITJ, Japan f) Flow Control Technology, France g) Crane, USA h) Orbit Valves, UK

i) T.K. Valves, Abu Dhabi A) Pipe (Carbon Steel) a) BHEL, Trichy (Acceptable upto4”)

b) Indian Seamless, Ahmed Nagar c) Jindal Pipes, New Delhi d) Saw Pipes, Delhi e) NSC,Japan f) Mitsubhishi,Japan g) MGL,France

B) Pipe (Stainless Steel) a) Choksi Tubes, Ahmedabad b) Kalindi, Delhi c) NFC, Hyderabad

12.

C) Pipes (Cu-Ni) a) Alcabex Metals, Jodhpur b) Cubex Tubing, Hyderabad

c) Lebronze Industrial,France 13. Pipe Fittings in CS

(Both Seamless & Block Forged)(All Indian Vendors)

a) Eby Industries, Mumbai (India) b) Shivananda Pipe Fittings, Madras (only

seamless) c) Commercial Supplying Agencies, Mumbai

(India) 14. Forged Flanges in C.S

(All Indian Vendors) a) Echjay Industries, Mumbai /Rajkot b) Paramount Forge, Mumbai (India)

15. Valves in C.S (Both Cast & Forged) (All Indian Vendors)

a) BHEL, Trichy b) AUDCO, India c) Vergo Engineers, India

16. Needle Valves (All Indian Vendors) C.S

a) Sakhi Engrs. Mumbai/Baroda b) Chemvalves Industries, Mumbai (India)

17. A) Ball Valves

(Fire Safe) C.S

a) L&T/Audco, India b) Pertrol Valves, Italy

B) Ball Valves

(Non Fire Safe) C.S

• L&T/Audco, India

18. Cu-Ni Pipes & Fittings a) Yorkshire Imperial Metal, UK b) Le Brone Industrial, France c) Dia Yung Metal Industrial Co-Busan, Korea d) V.D.M., Germany

PIPI

NG

(Con

td.)

19. Gasket a) Madras Industrial Product, Madras b) IGP, Madras

Page 152: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 152

Discipline S. No Equipment / Material Supplier

20 Scrapper Tees a) TD Williamson, USA b) Pipeline Engineering Supply, UK c) Schulz Export EMBH, Germany d) GD Engineering, UK

21. Hinged Closures a) Perry Equipment Corporation, USA b) TD Williamson, USA

c) Pipeline Engineering Supply, UK 22 Corrosion Probes a) Casasco Division, USA

b) Rehrback Cosasco, USA c) Mc Murray, USA d) Caproco Intl. Canada e) Atel, Italy f) Corrocean, Italy

23. Pig Detector a) Pipeline Engineering & Supply Co.UK b) TD Williamson, USA

24. FWFM Reels & Utility

Hose Reels a) Marine Hydraulic, Mumbai (India) b) Royal India Corporation, Mumbai (India) c) Gayatri, Mumbai (India)

25. Strainers a) Armstorng, USA

b) Multitex Engineers, New Delhi c) Greaves Cotton, Delhi

26. Spray Nozzles a) Marine Hydraulics, Mumbai (India)

b) Wormald Fire system, UK

27. Continuous Drainers a) Armstrong, USA b) Greaves Cotton, Mumbai (India)

28. 5D Bends a) Fabricom, Belgium b) Sungjin Korea c) Igawara, Signapore d) PSL,Kandla (India) e) Induction Bending

29. Chemical & Utility Hoses and Hose Connection

a) Marine Hydraulics, Mumbai (India) b) Gaytri Industries Corporation, Mumbai

(India) c) Royal India Corporation, Mumbai (India)

PIPI

NG

(Con

td.)

30. Choke Valves a) Modveld, USA b) Petrol Valves, Italy c) Valvinox, Italy

Page 153: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 153

Discipline S. No Equipment / Material Supplier

31. Hand Control Valves Mansoneilan, France Mokveld, USA Fisher Controls,USA Koson Process Controls, Singapore Kent Process Control Ltd.,UK Control Component Inc.,USA Hoppkinsons Blackborough,Dubai

32. Sample Bomb a) Harsh Engineering, Mumbai (India)

33. Launcher/Receiver a) Pipeline Engineering,UK b) T D Williamson,USA c) L&T, India

1. Transformers (Cast Resin Type)

a) Westing House, USA b) General Electric, USA c) Fuji, Japan d) Mat & Christie e)Traftech f)Toshiba, Japan g)Maidensha h)Merlin Gerlin i)GEC, UK j)Toshiba, Japan

k)Kirloskar Power, India 2. UPS System a)SAB-NIEF, Sweeden

b)Stand By Power, USA c)Chloride System, UK d)Fuji, Japan e)GUTOR, Switzerland f)Emerson, USA

ELEC

TRIC

AL

3. LT Switch Gear a)Westing House, USA b)General Electric Co., UK c)Hitachi, Japan d)Toshiba, Japan e)Fuji, Japan f)L.K.Nes, Singapore g)Nuovo Magnini, Italy h)Aplerre i)IME-Quadri j)Abbott Power, USA k)Merlin – Gerlin, USA l)Martelli Electo Technical m)Pan Electirc n)Helco, Korea o)Terasaki, Japan

p)L&T, India

Page 154: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 154

Discipline S. No Equipment / Material Supplier

4. HT Switch Gear a) Westing House, USA b) Hitachi, Japan

c) General Electric Co., UK/USA d) SACE, Italy e) ABB, Norway f)Merlin Gerlin, USA g)Siemens, Germany/Indonesia h) Fuji, Japan

5. Battery & Battery Charger

a) SAB-NIFE b)Stand By Power, USA c)Chloride System, UK d)Yuasa, Japan e)Fuji, Japan f)Gutor, Switzerland g)Emerson, USA h)HBL NIFE, Hydrabad (India)

6. Cathodic Protection System

a) Impalloy, Singapore/UK b) Alico Industries,UAE c) Aluminium Pechinary, France d) Nippon Corrosion, Japan e) Nakagawa Corrosion, UK f) Willson, India g) PSL, India h) Emirates-Techno Casting LLC, Dubai,UAE

7. Fluorescent/Incandescent Class `B’LTG Fixtures

a) Heyes Lighting,UK b) Crouse Hinds, USA c) Appleton, USA d) ITO-Denki, Japan

8. Navigational Aids System (NAVAID)

a) Automatic Power Inc, USA b) Tideland Singnal Corp, USA c) TATA BP, India d) SOLAPAK, UK e) BP SOLAR, Australia

9. Lead Acid Batteries (Solar Power System)

a) VARTA BATTERIES, Germany b) Heagen Batteries, Germany c) Chloride Batteries, UK d) Amaraja Batteries, India e) Yuasa, Japan

10. Multi Cable Transit (MCT)

a) A.B. Lykab, Sweeden b) Engtek Pte Singapore Ltd, Singapore c) S.V.T.International, Germany

ELEC

TRIC

AL

(Con

td.)

11. Div.2 Aviation Marker Ltg. Fixtures

a) GEC Electrical Project Ltd, UK b) Transberg A/S, Sweeden c) DTS, France d) Tide Land Signal, USA

Page 155: OffshoreDesignManual (Very Important From ONGC)

Offshore Design Manual

http://www.infraline.com – Your Information Gateway to Indian Energy Sector 155

Discipline S. No Equipment / Material Supplier

12. Lighting & Power Distribution Panel

a) Morarji Dorman, Mumbai b) Indo Asian Switch Gear, Jullundhar, India c) Versatrip Circuit Breaker Mfg.(P) Ltd.,

Mumbai, India d) Bhartiya Cutler Hammer, Faridabad, India e) Reunion Engg. Co, Mumbai f) Fabricons, Mumbai g) Siemans, Germany / India h) Willson & Co, India

13. Solar Power System a) Central Electronics Ltd, Faridabad, India b) BHEL, India c) Tata BP Solar, India d) BP Solar, Australia e) Solapak, UK

14. FRLS Cables a) Universal Cables, Satna, India b) Nicco Cables Co. Ltd, Kolkata, India c) Cable Corporation Of India, India

15. Fire Survival Cables a) Universal Cables, Satna, India b) INCAB, India

c) Cable Corporation Of India, India

ELEC

TRIC

AL

(Con

td.)

16. Fiber Glass Cable Trays a)Super Reinforced Plastics Associated Engg.Corp., Mumbai, India b)Grip India, Mumbai c)SSB Industries, Bangalore, India d)Ercon Composites, Jodhpur, India