Installation Instructions 818956-02 Level Electrodes NRG 6-5, NRG 7-5, NRG 9-5 GESTRA Steam Systems NRG 16-51 NRG 17-51 NRG 19-51 EN English

Upload: others

Post on 07-Aug-2020

18 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: NRG 17-51 English NRG 19-51 - Flowserve · Installation Instructions 818956-02 Level Electrodes NRG 6-5 , NRG 7-5 , NRG 9-5 GESTRA Steam Systems NRG 16-51 NRG 17-51 NRG 19-51 EN English

Installation Instructions 818956-02Level ElectrodesNRG �6-5�, NRG �7-5�, NRG �9-5�

GESTRA Steam Systems

NRG 16-51NRG 17-51NRG 19-51

ENEnglish

Page 2: NRG 17-51 English NRG 19-51 - Flowserve · Installation Instructions 818956-02 Level Electrodes NRG 6-5 , NRG 7-5 , NRG 9-5 GESTRA Steam Systems NRG 16-51 NRG 17-51 NRG 19-51 EN English

Contents

Usage for the intended purpose ..............................................................................................................4Function .................................................................................................................................................4

ApplicationPage

NRG �6-5�, NRG �7-5�, NRG �9-5�, step � ..........................................................................................�6NRG �6-5�, NRG �7-5�, NRG �9-5�, step � ..........................................................................................�6NRG �6-50F, NRG �7-50F, NRG �9-50, additional information ...............................................................�6 Tools .....................................................................................................................................................�7

NRG �6-5�, NRG �7-5�, NRG �9-5� .......................................................................................................6Corrosion resistance ...............................................................................................................................7Sizing .....................................................................................................................................................7Name plate/ marking ..............................................................................................................................8Dimensions NRG �6-5�, NRG �7-5� .......................................................................................................9Dimensions NRG �9-5� ........................................................................................................................�0

NRG �6-5�, NRG �7-5�, NRG �9-5� .....................................................................................................��NRG �6-5�, NRG �7-5�, NRG �9-5� with four-pole connector ...............................................................��NRG �6-5�F, NRG �7-5�F, NRG �9-5�F with aluminium terminal box ....................................................�3Key .......................................................................................................................................................�4

Functional Elements

Technical Data

Installation

Directives and Standards

Safety note ...........................................................................................................................................�5Scope of supply ....................................................................................................................................�5

Important Notes

Pressure Equipment Directive (PED) 97/�3/EC ........................................................................................5Functional Safety acc. to IEC 6�508 ........................................................................................................5VdTÜV Bulletin “Wasserstand �00” (= Water Level �00) ..........................................................................5ATEX (Atmosphère Explosible) .................................................................................................................5

Page 3: NRG 17-51 English NRG 19-51 - Flowserve · Installation Instructions 818956-02 Level Electrodes NRG 6-5 , NRG 7-5 , NRG 9-5 GESTRA Steam Systems NRG 16-51 NRG 17-51 NRG 19-51 EN English

3

NRG �6-5�, NRG �7-5�, NRG �9-5� .....................................................................................................�8Key .......................................................................................................................................................�9

Examples of Installation

Electrical Connection

Connection of level electrode ................................................................................................................�0NRG �6-5�, NRG �7-5�, NRG �9-5� with four-pole connector ...............................................................�0NRG �6-5�F, NRG �7-5�F, NRG �9-5�F with aluminium terminal box ....................................................�0Wiring diagram .....................................................................................................................................��Key .......................................................................................................................................................��Tools .....................................................................................................................................................��

Contents – continued –

Commissioning, Fault Indication and Remedy

Page

Disposal................................................................................................................................................��

Decommissioning

NRG �6-5�, NRG �7-5�, NRG �9-5� .....................................................................................................��

Page 4: NRG 17-51 English NRG 19-51 - Flowserve · Installation Instructions 818956-02 Level Electrodes NRG 6-5 , NRG 7-5 , NRG 9-5 GESTRA Steam Systems NRG 16-51 NRG 17-51 NRG 19-51 EN English

4

Application

Usage for the intended purpose

The level electrodes NRG �6-5�, NRG �7-5� and NRG �9-5� are used in conjunction with level switch NRS �-5� as high water level alarms for steam boiler plants and (pressurized) hot water installations. A high level alarm prevents the water level from exceeding the preset max. water level (HW) and for this purpose switches off e. g. the feedwater supply.

Function

When the level exceeds the max. water level, the level electrode enters the liquid and an alarm is triggered in the level switch NRS �-5�. The switchpoint “High level (HW) exceeded” is dictated by the length of the electrode rod. The self-monitoring function ensures that an alarm will also be triggered if the electrode insulation is contaminated or has developed a leak or if there is a malfunction in the electrical connection.The level electrode is installed inside steam boilers, vessels or inlet lines of hot-water systems. The protective tube mounted on site (see section Examples of Installation (pages �8, �9) ensures correct functioning.One level electrode NRG �...-5� can be installed together with one GESTRA water level limiting electrode in a single protection tube or external level pot. If the level electrode is installed in a level pot outside the boiler, make sure that the connecting lines are rinsed regularly. In addition, the logic unit SRL is required to monitor the purging times and the purging sequence.If the connecting lines for steam ≥ 40 mm and water ≥ �00 mm, the installation is considered to be internal. In this case the rinsing processes do not have to be monitored.

Page 5: NRG 17-51 English NRG 19-51 - Flowserve · Installation Instructions 818956-02 Level Electrodes NRG 6-5 , NRG 7-5 , NRG 9-5 GESTRA Steam Systems NRG 16-51 NRG 17-51 NRG 19-51 EN English

5

Directives and Standards

Pressure Equipment Directive (PED) 97/23/EC

The level electrode NRG �...-5� in conjunction with level switch NRS �-5� is EC type approved accord-ing to EN ��95�/EN ��953. These Directives state, among other things, the requirements made on limiting systems and equipment for steam boiler plants and (pressurised) hot-water installations.

ATEX (Atmosphère Explosible)

The level electrodes NRG �...-5�, NRG �...-�� are simple items of electrical equipment as specified in EN 60079-�� section 5.7. According to the European Directive 94/9/EC the equipment must be equipped with approved Zener barriers if used in potentially explosive areas. Applicable in Ex zones �, � (�999/9�/EC). The equipment does not bear an Ex marking. The suitability of the Zener barriers is certified in a separate document.Note that the requirements of the IEC 6�508 are not met if the NRG �...-5�, NRG �...-�� + Zener barriers + NRS �-5� are interconnected!

VdTÜV Bulletin “Wasserstand 100” (= Water Level 100)

The level electrodes NRG �-5�, NRG �...-�� in conjunction with the level switch NRS �-5� are type approved according to the VdTÜV Bulletin “Water Level �00”.The VdTÜV Bulletin “Wasserstand (=Water Level) �00” specifies the requirements made on water level control and limiting equipment for boilers.

Functional Safety acc. to IEC 61508

The level electrode NRG �...-5� is certified acc. to IEC 6�508 only if used in combination with level switch NRS �-5�. This standard describes the functional safety of safety-related electrical/electronic/programmable electronic systems.The equipment combination NRG �...-5� + NRS �-50 corresponds to a type B subsystem with Safety Integrity Level (SIL) 3.

Page 6: NRG 17-51 English NRG 19-51 - Flowserve · Installation Instructions 818956-02 Level Electrodes NRG 6-5 , NRG 7-5 , NRG 9-5 GESTRA Steam Systems NRG 16-51 NRG 17-51 NRG 19-51 EN English

6

NRG 16-51, NRG 17-51, NRG 19-51

Technical Data

Service pressure NRG �6-5�: PN 40, 3� bar at �38 °C NRG �7-5�: PN 63, 46 bar at �60 °C NRG �9-5�: PN �60, �00 bar at 3�� °CMechanical connection Screwed ¾" to EN ISO ��8-�Materials Sheath �.430� X5 CrNi�8-�0 Screw-in body �.457�, X6CrNiMoTi�7-��-� Measuring electrode �.457� X6CrNiMoTi�7-��-�Electrode rod �.440� X5CrNiMo�7-��-� Electrode insulation PEEK NRG �...-5�: Four-pole connector: polyamid (PA) NRG �...-5�F: Terminal box 3.��6� G AlSi8Cu3Lengths available 500 mm, �000 mm, �500 mmElectrical connection NRG �...-5�: Four-pole connector, cable glands M �6 NRG �...-50F: Terminal box made from aluminium, cable gland M �0Protection IP 65 to EN 605�9Max. admissible ambient temperature 70 °CWeight Approx. �.� kg (without extension) (NRG �6-5�, NRG �7-5�, NRG �9-5�) Approx. �.� kg (without extension) (NRG �6-5�F, NRG �7-5�F, NRG �9-5�F)

Approvals EC Prototype approval PED Pressure Equipment Directive 97/�3/EC, EN ��95�-��, EN ��953-09: Requirements made on limiting equipment for boilers.Functional Safety SIL 3 IEC 6�508: Functional safety of safety-related electrical/electronic/programmable electronic systems TÜV type approval VdTÜV Bulletin “Wasserstand �00” (= Water Level �00): Requirements made on water level limiting & control equipment. Type approval no. TÜV · SHWS · XX-4�3 (see name plate)

Gylon® is a registered trademark of Garlock Sealing Technologies, Palmyra NY, USA

Page 7: NRG 17-51 English NRG 19-51 - Flowserve · Installation Instructions 818956-02 Level Electrodes NRG 6-5 , NRG 7-5 , NRG 9-5 GESTRA Steam Systems NRG 16-51 NRG 17-51 NRG 19-51 EN English

7

Corrosion resistance

If the equipment is used for the intended purpose, its safety is not impaired by corrosion.

Sizing

The body is not designed for pulsating loads. Welds and flanges are designed to withstand dynamic loading (bending and alternative stress). The dimensional allowances and anti-corrosive additives reflect the latest state of the technical art.

Technical Data – continued –

Page 8: NRG 17-51 English NRG 19-51 - Flowserve · Installation Instructions 818956-02 Level Electrodes NRG 6-5 , NRG 7-5 , NRG 9-5 GESTRA Steam Systems NRG 16-51 NRG 17-51 NRG 19-51 EN English

8

Technical Data – continued –

Name plate/marking

Fig. 1

Fig. 2

Equipment designation Safety note

Disposal note

CE marking

Pressure rating, thread type, material number, type approval number

Manufacturer Serial number

Equipment designation, pressure rating

Pressure/temperature rating

CE Marking, type approval

Screwed connection, material number, protection

Safety note

Disposal note

Manufacturer

Serial number

Page 9: NRG 17-51 English NRG 19-51 - Flowserve · Installation Instructions 818956-02 Level Electrodes NRG 6-5 , NRG 7-5 , NRG 9-5 GESTRA Steam Systems NRG 16-51 NRG 17-51 NRG 19-51 EN English

9

Technical Data – continued –

Dimensions NRG 16-51, NRG 17-51

Fig. 3NRG �6-5�, NRG �7-5� with four-pole connector

≤�5

0090

�7�

¾", DIN EN ISO ��8-�

Fig. 4NRG �6-5�F, NRG �7-5�F with aluminium terminal box

9033

8≤

�50

0

�75

�40

b = 70

Page 10: NRG 17-51 English NRG 19-51 - Flowserve · Installation Instructions 818956-02 Level Electrodes NRG 6-5 , NRG 7-5 , NRG 9-5 GESTRA Steam Systems NRG 16-51 NRG 17-51 NRG 19-51 EN English

�0

GESTRA Steam Systems

GESTRA

Technical Data – continued –

Dimensions NRG 19-51

Fig. 5NRG �9-5�

b = 70

�40

�75

≤ �

500

Fig. 6NRG �9-5�F

350

�40

≤ �

500

�84

�", DIN EN ISO ��8-��", DIN EN ISO ��8-�

�40

Page 11: NRG 17-51 English NRG 19-51 - Flowserve · Installation Instructions 818956-02 Level Electrodes NRG 6-5 , NRG 7-5 , NRG 9-5 GESTRA Steam Systems NRG 16-51 NRG 17-51 NRG 19-51 EN English

��

Fig. 10

N 8

N�0

Fig. 7

Fig. 8

¾", DIN EN ISO ��8-�

∅ 33

Functional Elements

1

2

3

4

6

5

7

8

NRG 16-51, NRG 17-51, NRG 19-51

Fig. 9NRG �6-50NRG �7-50 NRG �9-50

0.5

Page 12: NRG 17-51 English NRG 19-51 - Flowserve · Installation Instructions 818956-02 Level Electrodes NRG 6-5 , NRG 7-5 , NRG 9-5 GESTRA Steam Systems NRG 16-51 NRG 17-51 NRG 19-51 EN English

��

Fig. 11

f

e

c

b

9

0

a

d

Functional Elements – continued –

NRG 16-51, NRG 17-51, NRG 19-51 with four-pole connector

Page 13: NRG 17-51 English NRG 19-51 - Flowserve · Installation Instructions 818956-02 Level Electrodes NRG 6-5 , NRG 7-5 , NRG 9-5 GESTRA Steam Systems NRG 16-51 NRG 17-51 NRG 19-51 EN English

�3

Functional Elements – continued –

Fig. 13

NRG 16-51F, NRG 17-51F, NRG 19-51F with aluminium terminal box

Fig. 12

ig h

k

j

Page 14: NRG 17-51 English NRG 19-51 - Flowserve · Installation Instructions 818956-02 Level Electrodes NRG 6-5 , NRG 7-5 , NRG 9-5 GESTRA Steam Systems NRG 16-51 NRG 17-51 NRG 19-51 EN English

�4

1 Measuring electrode

2 Bore

3 Spring

4 Electrode tip

5 NRG �...-5�: Joint ring �7 x 3�, form D, DIN 7603, �.430�, bright annealed

6 Seating surface

7 Electrode thread

8 Thermal insulation, provided on site, d = �0 mm (outside of thermal insulation of steam boiler)

9 Screw M 4

0 Cover

a Upper part of the terminal box

b Connecting plate

c Insulating plate

d Contact plate of level electrode

e Cable strain relief

f Cable gland M �6 (PG 9)

g Housing screws M 4

h Cable gland M �0 x �.5

i Housing cover

j Nut

k Terminal strip

Functional Elements – continued –

Key

Page 15: NRG 17-51 English NRG 19-51 - Flowserve · Installation Instructions 818956-02 Level Electrodes NRG 6-5 , NRG 7-5 , NRG 9-5 GESTRA Steam Systems NRG 16-51 NRG 17-51 NRG 19-51 EN English

�5

Important Notes

Safety note

Danger

When loosening the electrode steam or hot water might escape!This presents the risk of severe scalding all over the body!It is therefore essential not to dismantle the electrode unless the boiler pressure is verified to be 0 bar.The electrode becomes hot during operation.Risk of severe burns to hands and arms.Before carrying out installation and maintenance work make sure that the steam trap is cold.

High water level alarms are safety devices and must only be installed, wired and commissioned by qualified and competent staff.Retrofitting and maintenance work must only be performed by qualified staff who – through adequate training – have achieved a recognised level of competence.

Attention

The name plate specifies the technical features of the equipment. Do not commission or operate any item of equipment that does not bear its specific name plate.

Scope of supply

NRG 16-51 � Level electrode NRG �6-50, PN 40 � Joint ring �7 x 3�, Form D, DIN 7603, �.430�, bright annealed � Installation manualNRG 17-51 � Level electrode NRG �7-50, PN 63 � Joint ring �7 x 3�, Form D, DIN 7603, �.430�, bright annealed � Installation manual

NRG 19-51 � Level electrode NRG �9-50, PN �60 � Joint ring �7 x 3�, Form D, DIN 7603, �.430�, bright annealed � Installation manual

Note

For outdoor installations please use level electrode NRG �...-5� F. Level electrodes with this suffix (F) feature a terminal box made from aluminium.

Page 16: NRG 17-51 English NRG 19-51 - Flowserve · Installation Instructions 818956-02 Level Electrodes NRG 6-5 , NRG 7-5 , NRG 9-5 GESTRA Steam Systems NRG 16-51 NRG 17-51 NRG 19-51 EN English

�6

Installation

NRG 16-51, NRG 17-51, NRG 19-51, step 1

�. Screw electrode tip 4 into measuring electrode 1. Fig. 7�. Carefully determine required measuring length of electrode. 3. Mark length of electrode tip 4.4. Unscrew electrode tip 4 from measuring electrode 1 and cut tip.5. After visual inspection screw electrode tip 4 into measuring electrode 1. Slide spring 3 along

electrode tip 4 so that its end completely enters the small hole 2.

NRG 16-51, NRG 17-51, NRG 19-51, step 2

6. Check seating surfaces. Fig. 107. Place joint ring 5 onto seating surface 6 of the electrode. Fig. 88. Apply a light smear of silicone grease (e. g. WINIX® ��50) to electrode thread 7.9. Screw level electrode into threads or flange provided on vessel and tighten with a 4� mm

open-end spanner. The torque required when cold is 160 Nm.

NRG 16-50F, NRG 17-50F, NRG 19-50, additional information

One level electrode NRG �...-5� F can be installed together with one GESTRA level electrode (with aluminium terminal box) in a single protection tube or external level pot. Please proceed as follows: �. Mount level electrode NRG �...-5�F as first device as described in items 6 – 9.When installing level electrode NRG �...-5� F, please observe the following instructions: �. Unscrew screws g and remove housing cover i . Fig. 12. The arrow on the name plate points

towards this cover.�. Loosen nut j with a �9 mm spanner, but do not remove! Fig. 133. Turn terminal box into desired position (+/– �80°).The terminal box can now be turned through +/– 180° .4. Tighten nut j with a torque of 25 Nm.5. Mount housing cover i and tighten screws g.

Note

n One level electrode NRG �...-5� can be installed together with one GESTRA water level limiting electrode in a single protection tube or external level pot (inside diameter �00 mm). Fig. 16.

Page 17: NRG 17-51 English NRG 19-51 - Flowserve · Installation Instructions 818956-02 Level Electrodes NRG 6-5 , NRG 7-5 , NRG 9-5 GESTRA Steam Systems NRG 16-51 NRG 17-51 NRG 19-51 EN English

�7

Note

n For the approval of the boiler standpipe the relevant regulations must be considered.n Refer to pages �8 for typical installation examples.n The angle of inclination of the electrode must not exceed 45°, with the length of the

electrode rod being limited to �000 mm. Fig. 15n For outdoor installations please use level electrode NRG �...-5� F. Level electrodes with

this suffix (F) feature a terminal box made from aluminium.

n The seating surfaces of the standpipe or the flange provided on the vessel must be accurately machined, see Fig. 10

n Do not bend electrode tip when mounting.n Use only the joint rings supplied with the electrode.

NRG �6-5�, NRG �7-5�, NRG �9-5�: �7 x 3�, form D, DIN 7603, �.430�n Do not lag electrode body above the hexgonal section.n Do not insulate electrode thread with hemp or PTFE tape!n Do not apply conductive paste or grease to the electrode thread!n Make sure that the air distance between the electrode rod and earth (flange, vessel

wall) is not less than �4 mm. Fig. 14 – 17n Observe the minimum distances for the installation of the electrode!

Attention

Tools

n Open-end spanner A. F. �3, DIN 3��0, ISO 33�8n Open-end spanner A. F. �9, DIN 3��0, ISO 33�8n Open-end spanner A. F. 4�, DIN 3��0, ISO 33�8n Scribern Hacksawn Flat file, medium cut, DIN 7�6�, form A

Installation – continued –

Page 18: NRG 17-51 English NRG 19-51 - Flowserve · Installation Instructions 818956-02 Level Electrodes NRG 6-5 , NRG 7-5 , NRG 9-5 GESTRA Steam Systems NRG 16-51 NRG 17-51 NRG 19-51 EN English

�8

4

Examples of Installation

DN �00

�0

�0

≥ DN �0

�4.5 �4.5

�0 ∅�0

DN 50

¾"

¾"

¾"

≤�0

≤ 30

00

∅ �0

≤ 90°

∅ �0

¾"

≤ 90°

Cent

re d

ista

nce

≥�4

≥ DN �0

≥ DN �0

lm

no

p

max. �

000

�0

≥�4

≥�4

45°

lm

p

on

o

l

n

p

≥ �0

NRG 16-51, NRG 17-51, NRG 19-51

s

q

t

u

t

r

s

t

u

Fig. 15 Inclined installation, e. g. in ascending inlet lines of hot-water installations or vessels

Fig. 14 Protection tube (provided on site) if electrode is used as internal high level alarm.

Fig. 16 Protection tube (provided on site) if electrode is used as internal water level-limter combined with water level control or high water level alarm

Fig. 17 Level pot if electrode is used as external high level alarm.

�0

�0

Page 19: NRG 17-51 English NRG 19-51 - Flowserve · Installation Instructions 818956-02 Level Electrodes NRG 6-5 , NRG 7-5 , NRG 9-5 GESTRA Steam Systems NRG 16-51 NRG 17-51 NRG 19-51 EN English

�9

l Flange PN 40, PN 63, PN �60, DN 50, DIN �50�-� (for one electrode)

Flange PN 40, PN 63, PN �60, DN �00, DIN �50�-� (for two electrodes)

m For the approval of the boiler standpipe with connecting flange the relevant

regulations must be considered.

n Vent hole Provide vent hole as close to the boiler wall as possible!

o High water HW

p Electrode rod d = 8 mm

q Protection tube DN 80 (in France according to AFAQ ≥ DN �00)

r Protection tube DN �00

s Electrode distance ≥ �4 mm (air gap and creepage distance)

t Low water LW

u Reducer DIN �6�6-�, K-88.9 x 3.�- 4�.4 x �.6 W

Examples of Installation – continued –

Key

Page 20: NRG 17-51 English NRG 19-51 - Flowserve · Installation Instructions 818956-02 Level Electrodes NRG 6-5 , NRG 7-5 , NRG 9-5 GESTRA Steam Systems NRG 16-51 NRG 17-51 NRG 19-51 EN English

�0

Connection of level electrode

To connect the level electrode use screened multi-core control cable with a min. conductor size 0.5 mm�, e.g. LiYCY 4 x 0.5 mm� . Max. length �00 m with an electrical conductivity of the boiler water > �0 μS/cm at �5 °C. Max. length 30 m with an electrical conductivity of the boiler water < �0 μS/cm at �5 °C.Wire terminal strip in accordance with the wiring diagram. Fig. 18 Connect screens only to terminal 5 of the level switch NRS �-5�.

Electrical Connection

�. Undo screw 9. Fig. 12 �. Remove upper part a of the terminal box from the level electrode but leave insulating plate c on

contact plate d. 3. Remove cover 0. 4. Press connecting plate b out of upper part of the terminal box a. The upper part of the terminal box can be turned in steps of 90°. 5. Detach cable gland f and cable clamp e from upper part of the terminal box a. 6. Run cable through cable gland f and upper part of the terminal box a and wire terminals of the

connecting plate b in accordance with wiring diagram. Fig. 19 7. Press connecting plate b into the upper part of the terminal box and align cable. 8. Fix cable with cable clamp e and cable gland f. 9. Re-attach cover 0 and insert screw 9.�0. Put upper part of the terminal box onto the level electrode and fix it with screw 9.

NRG 16-51F, NRG 17-51F, NRG 19-51F with aluminium terminal box

NRG 16-51, NRG 17-51, NRG 19-51 with four-pole connector

�. Unscrew screws g and remove housing cover i. Fig. 12�. Undo cable gland h. Pull cable through cable entry.3. Remove terminal strip k from circuit board.4. Connect terminal strip according to the wiring diagram. Fig. 205. Attach terminal strip.6. Tighten the cable gland in order to seal the cable entry. 7. Mount housing cover i and tighten screws g.

Page 21: NRG 17-51 English NRG 19-51 - Flowserve · Installation Instructions 818956-02 Level Electrodes NRG 6-5 , NRG 7-5 , NRG 9-5 GESTRA Steam Systems NRG 16-51 NRG 17-51 NRG 19-51 EN English

��

Electrical Connection – continued –

Wiring diagram

Fig. 20 Wiring of level electrode with aluminium terminal box

Fig. 19 Wiring of level electrode with four-pole connector

wFig. 18

Terminal strip NRS �-5�

+ -v

Page 22: NRG 17-51 English NRG 19-51 - Flowserve · Installation Instructions 818956-02 Level Electrodes NRG 6-5 , NRG 7-5 , NRG 9-5 GESTRA Steam Systems NRG 16-51 NRG 17-51 NRG 19-51 EN English

��

Electrical Connection – continued –

Key

v Stand-by input �, �4 V DC, for connecting the logic unit SRL

w Level electrode NRG �...-5�, NRG �...-��

Commissioning, Fault Indication and Remedy

For additional information on commissiong procedures and troubleshooting refer to the installation manual of the level switch NRS �-5�.

Tools

n Screwdriver for cross head screws, size �n Screwdriver for slotted screws, size �.5, completely insulated according to DIN VDE 0680-�n Open-end spanner A.F. �8 (�9) mm

Disposal

Danger

Risk of severe burns and scalds to the whole body! Before removing the level electrode make sure that the vessel or the external pot are depressurised (0 bar) and cooled down to room temperature (�0 °C).

Decommissioning

Dismantle the level electrode and separate the waste materials, using the specifications in the table “Materials” as a reference.For the disposal of the equipment observe the pertinent legal regulations concerning waste disposal.

If faults occur that are not listed above or cannot be corrected, please contact our service centre or authorized agency in your country.

Page 23: NRG 17-51 English NRG 19-51 - Flowserve · Installation Instructions 818956-02 Level Electrodes NRG 6-5 , NRG 7-5 , NRG 9-5 GESTRA Steam Systems NRG 16-51 NRG 17-51 NRG 19-51 EN English

�3

For your Notes

Page 24: NRG 17-51 English NRG 19-51 - Flowserve · Installation Instructions 818956-02 Level Electrodes NRG 6-5 , NRG 7-5 , NRG 9-5 GESTRA Steam Systems NRG 16-51 NRG 17-51 NRG 19-51 EN English

�48�8956-0�/05-�0�0cm (8088�3-0�) · GESTRA AG · Bremen · Printed in Germany

Agencies all over the world:

www.gestra.de

GESTRA AGP. O. Box�0 54 60, D-�8054 Bremen Münchener Str. 77 , D-�8��5 BremenTelephone 0049 (0) 4�� / 35 03 - 0 Fax 0049 (0) 4�� / 35 03 - 393E mail [email protected] Internet www.gestra.de

GESTRA

Great Britain

Flowserve GB LimitedAbex RoadNewbury, Berkshire RG�4 5EYTel. 0044 �6 35 / 46 99 90Fax 0044 �6 35 / 3 60 34E-mail: [email protected]

Italia

Flowserve S.p.A.Flow Control DivisionVia Prealpi, 30l-�003� Cormano (MI)Tel. 0039 0� / 66 3� 5�Fax 0039 0� / 66 3� 55 60E-mail: [email protected]

GESTRA ESPAÑOLA S.A.Luis Cabrera, 86-88E-�800� MadridTel. 0034 9� / 5 �5 �0 3�Fax 0034 9� / 4 �3 67 47; 5 �5 �0 36E-mail: [email protected]

España

Flowserve GESTRA U.S.�34� Ampere DriveLouisville, KY 40�99Tel. 00� 50� / �67-��05Fax 00� 50� / �66-5397E-mail: [email protected]

USA

Portugal

Flowserve Portuguesa, Lda.Av. Dr. Antunes Guimarães, ��59Porto 4�00-08�Tel. 0035� �� / 6 �9 87 70Fax 0035� �� / 6 �0 75 75E-mail: [email protected]

Polska

GESTRA POLONIA Spolka z.o.o.Ul. Schuberta �04PL - 80-�7� GdanskTel. 0048 58 / 3 06 �0 - 0� 0048 58 / 3 06 �0 - �0Fax 0048 58 / 3 06 33 00E-mail: [email protected]