novel mitigation and monitoring of ssr...
TRANSCRIPT
1 VISOR Workshop: UoM Research, 26/09/2017 Papiya Dattaray – Cigre NGN 20/02/2018
Novel Mitigation and Monitoring of SSR Oscillations
Papiya Dattaray, PhD student [email protected] Supervised by Prof. Vladimir Terzija
2 Papiya Dattaray – Cigre NGN 20/02/2018
Outline
Background Impact of Dynamic Loads on SSR
Using Dynamic Loads to damp SSR
What’s Next?
Conclusions
3 Papiya Dattaray – Cigre NGN 20/02/2018
Part 1
A Brief Background to
My Research
4 Papiya Dattaray – Cigre NGN 20/02/2018
Fixed Series Compensation Higher power transfers,
Enhanced transient stability limits,
Improved angular stability (reduced angular separation across corridors), and
Self-regulatory and instantaneous VAr support (steady state & dynamic voltage stability)
Tr
Line Source
G
MV
C
Bypass HV
HV_net
Capacitor in series with transmission line
5 Papiya Dattaray – Cigre NGN 20/02/2018
Facilitate increased power transfer at a lower cost
Great Britain increased flow of renewable
generation from Scotland to England (B6) to help meet goal of 15% renewable energy by 2020: Series capacitor banks have been installed at the Eccles, Moffat and Gretna substations (Scottish Power, 2015)
TCSC at the Hutton 400kV substation, near Kendal in Cumbria. Enhanced power transfer capacity by around 1 GW (National Grid, 2014)
Also installing HVDC in parallel to the AC network. (National Grid, 2018)
Fixed Series Compensation
6 Papiya Dattaray – Cigre NGN 20/02/2018
Facilitate increased power transfer at a lower cost
Great Britain increased flow of renewable
generation from Scotland to England (B6) to help meet goal of 15% renewable energy by 2020: Series capacitor banks have been installed at the Eccles, Moffat and Gretna substations (Scottish Power, 2015)
TCSC at the Hutton 400kV substation, near Kendal in Cumbria. Enhanced power transfer capacity by around 1 GW (National Grid, 2014)
Also installing HVDC in parallel to the AC network. (National Grid, 2018)
Fixed Series Compensation
7 Papiya Dattaray – Cigre NGN 20/02/2018
Subsynchronous Interactions: A Definition SSR is defined by IEEE as “the electrical power system condition where the electric network exchanges energy with a turbine generator at one or more of the natural frequencies of the combined system below the synchronous frequency of the system” [Source: IEEE SSR Working Group, “Proposed Terms and Definitions for Subsynchronous Resonance”, IEEE Symposium on Countermeasures for Subsynchronous Resonance, IEEE Pub. 81TH0086-9-PWR, 1981, p 92-97]
Shaft failure at Mohave (1970)
8 Papiya Dattaray – Cigre NGN 20/02/2018
SSR: The Physics
Natural frequencies occurring due to series capacitor compensation are below the nominal frequency of the network applied voltages
• w1 at the frequency of the driving voltage • w2 is dependant on the network parameters
Currents of frequency w2 are reflected onto the rotor as
• Sum, (w1+ w2) and difference (w1- w2) components
Difference or subsynchronous component of current induces subsynchronous frequency shaft torque
Torque oscillations mean torsional stress and fatigue
2
1 1 2 2( ) [ sin( ) sin( )]w t
i t K A w t Be w t
9 Papiya Dattaray – Cigre NGN 20/02/2018
Mode zero represents the condition where the masses all move in phase and the entire shaft system behaves as a solid mass (Classical generator rotor model) with a common mode of oscillation
Generator rotor as multi-mass
Any physical system composed of n masses
produces (n-1) oscillatory modes
10 Papiya Dattaray – Cigre NGN 20/02/2018
Part 2
Impact of dynamic loads on
torsional interactions
11 Papiya Dattaray – Cigre NGN 20/02/2018
Generation station modelled in detail
• turbines, generators, speed governors, excitation systems
Network is modelled in detail using algebraic and ordinary differential equations
But impact of LOADS is either neglected (IEEE Benchmark models) or assumed as constant Impedance (STATIC) models (throughout the years of SSR
research)
The impact of loads on system dynamics has been widely investigated for the classical stability studies but not for torsional interactions
Load modelling for assessment of SSR becomes critically important when the load center is in close electrical proximity to a generation center
In the absence of appropriate load models, simulations may over or underestimate the risk of SSR,
which may cause the protection or mitigation to be over/ under-designed
Load and SSR: EMT Studies
12 Papiya Dattaray – Cigre NGN 20/02/2018
……
Bulk power transmission network with dynamic models of
generators
Rectifier
DC Link
Inverter
M
DOL
M
Rectifier
DC Link
Inverter
M
DOL
M
Aggregated Static
Load
Aggregated Small and
Large Motor Load
Aggregated Static
Load
Aggregated Small and
Large Motor Load
Aggregation of loads at the transmission level
Load Type Description
Type 1 Loads neglected
Type 2 100% Const. Impedance
Type 3 50% DOL and 50% VFD based Motor loads
Type 4 100% DOL connected Motor load
Type 5
30% Const. Impedance 30% Const. Current 40% DOL connected Motor load
Type 6 50% Constant Impedance 50% DOL connected
Table I. List of load types considered
0 2 4 6 8 100.95
1
1.05
Time (sec)
Ptu
rb (
p.u
.)
Type1
Type2
Type3
Type4
Type5
Type6
unstable for Type 1 and 2 stable for Types 3, 4, 5 and 6
Conservative results impact decisions •at the planning stage (regarding location and/or degree of compensation)
•during operation (setting improper thresholds for online alarms against dangerous interactions).
Loads and SSR Damping
13 Papiya Dattaray – Cigre NGN 20/02/2018
Subsynchronous Resonance Load Interactions
4 4.25 4.50
1
2
Ptu
rb(p
.u.)
Time (sec)
(a)
4 4.25 4.50.95
0.97
0.99
1.01
1.03
1.05
Te(
p.u
.)
Time (sec)
(b)
10 20 30 40 50 600
0.2
0.4
FF
Tm
ag(p
.u.)
Freq (Hz)
10 20 30 40 50 600
0.01
0.02
0.03
FF
Tm
ag(p
.u.)
Freq (Hz)
Te
Tm
In the presence of SSR – DOL and VFD loads exhibit sympathetic oscillations
4 4.1 4.2 4.3 4.4 4.50.99
1
1.01
g
en(p
.u.)
Time (sec)
(a)
4 4.1 4.2 4.3 4.4 4.50.5
1
1.5
Ptu
rb(p
.u.)
Time (sec)
(b)
4 4.1 4.2 4.3 4.4 4.5519.5
520
520.5
VD
C(k
V)
Time (sec)
(c)
4 4.1 4.2 4.3 4.4 4.521
21.05
21.1
To
rqu
e(k
Nm
)Time (sec)
(d)
10 20 30 40 50 600
2
4x 10
-3
FF
Tm
ag(p
.u.)
Freq (Hz)
10 20 30 40 50 600
0.1
0.2
FF
Tm
ag(p
.u.)
Freq (Hz)
10 20 30 40 50 600
0.02
0.04
0.06
FF
Tm
ag(k
V)
Freq (Hz)
10 20 30 40 50 600
0.005
0.01
0.015
FF
Tm
ag(k
Nm
)
Freq (Hz)
speede
speedh
speedi
speedla
speedlb
Te
Tm
(a) Generator-turbine shaft speed, (b) Turbine output power, (c) VFD dc link capacitor voltage and (d) Motor torque
DOL
VFD
Gen Series Capacitor
load
SSR
SSR – LI
Do Loads Interact with SSR?
14 Papiya Dattaray – Cigre NGN 20/02/2018
Part 3
Novel SSR Mitigation – Auxiliary damping
controller
15 Papiya Dattaray – Cigre NGN 20/02/2018
Protection Vs. Mitigation
Mitigation involves reducing the exposure of the system to the risk of SSR and thus allowing the vulnerable resources to continue operating, even when outages result in stronger electrical coupling between a generator and a series capacitor. In many cases, mitigation may also be able to completely eliminate the risk of SSR.
Protection involves forced tripping (removal of generator or series capacitor), which is disruptive for a system that is already in a weakened state due to outages and is generally recommended as a backup means of defence.
16 Papiya Dattaray – Cigre NGN 20/02/2018
It is essential to detect instability in the subsynchronous modes of vibration and to do this as fast as possible and evaluate the need to take proactive action.
Traditional means for Managing SSR
Relay schemes to disconnect generation
or transmission
TCSC Torsional Filters
Static Blocking Filter
Bypass Damping Filters
Supplementary Excitation Damping
Control (SEDC)
Bypass Filter
Latest solution installed by SPEN alongside their FSC – first of its kind installed anywhere in the world
Scope for a new
solution? Protection against the phenomenon
17 Papiya Dattaray – Cigre NGN 20/02/2018
Proposed Control Solution
The proposed ADC uses the existing auxiliary power plant 11 kV VFD interfaced induction motor loads (e.g FD/ID Fans and pump loads) that are available locally right at the generation centre
The ADC exploits their speed control systems with minor modifications to the control loop, which incurs little to no additional costs and ensures easy deployment
It uses the turbine output power as the control system input, which is a standard power plant control room signal and does not need additional communication or dedicated monitoring
18 Papiya Dattaray – Cigre NGN 20/02/2018
L
L
L
R
R
Rvn
va
vb
vc
ia
ib
ic
Ldc
Cdc
Standard motor drive control(slip compensation, voltage boost, current limiter
and other protection circuits not shown)
Wref Wref* fm
Vm
PIMotor/load
performance considerations
++
DWr
Auxiliary
Damping
Controller
W
Werror
Motor speed
feedback
+- VfPWM
Auxiliary speed signal
Three-phase controller diagram for the VFD_AD
Residue based ADC design
Linear Feedback Compensator
Input: Turbine Output Power
19 Papiya Dattaray – Cigre NGN 20/02/2018
The most important power plant auxiliary loads with variable frequency drives (VFDs) are Boiler Feed Water pumps (BFWs), Induced Draft (ID) fans and Forced Draft (FD) fans
3.6 % in fans and 7.2 % in pumps of the plant generation capacity
FD and ID fans, used in power plant combustion processes consume significant amounts of power with motor sizes approaching 14 to 18 MW in many large power plants.
Additional pumps/fans available as backup or two pumps/fans operating in parallel at 50 % of their capacity
VFD based auxiliary power plant loads
High availability and redundancy
Significant Capacity
20 Papiya Dattaray – Cigre NGN 20/02/2018
Performance Evaluation: Test Systems
• VFD with ADC control added to two test systems
• Lines removed in 68 bus system to leave generator radial to SC
• The ADC stabilised the SSR
IEEE First Benchmark
IEEE 68 Bus System
21 Papiya Dattaray – Cigre NGN 20/02/2018
10 20 30 400
0.005
0.01
0.015
0.02
Pt A
mp
litu
de
10 20 30 400
0.005
0.01
0.015
0.02
IEEE FBM
10 20 30 400
0.005
0.01
0.015
0.02
10 20 30 400
0.005
0.01
0.015
0.02
IEEE 68 Bus
Frequency (Hz)10 20 30 40
0
0.005
0.01
0.015
0.02
10 20 30 400
0.005
0.01
0.015
0.02
None
with VFD
with VFD-AD
0.1 - 1.6 s
7.5 - 9 s
7.5 - 9 s 13 -
14.5 s
13 -
14.5 s
Performance Evaluation: FFT Analysis
ADC Stabilises SSR
22 Papiya Dattaray – Cigre NGN 20/02/2018
(a) turbine output power (b) unstable SSR in turbine shaft section speeds (c) turbine shaft section speeds in the presence of VFD motor (d) stable shaft speed oscillations with ADC (e) Frequency spectrum seen in turbine output
power with VFD-AD (f) FFT amplitude spectrum for Pt from 13-14.5 sec for No VFD and with VFD-AD
Unstable 25 Hz mode
60 % compensation for the unstable 25 Hz mode
Testing for different modes: 25 and 32 Hz ADC Stabilises turbine output
power
Stable shaft section speeds
Unstable SSR replaced with low level control
interaction
23 Papiya Dattaray – Cigre NGN 20/02/2018
(a) turbine output power (b) unstable SSR in turbine shaft section speeds (c) turbine shaft section speeds in the presence of VFD motor (d) stable shaft speed oscillations with ADC (e) Frequency spectrum seen in turbine output
power with VFD-AD (f) FFT amplitude spectrum for Pt from 13-14.5 sec for No VFD and with VFD-AD
40 % compensation for the critically unstable 32 Hz mode
Unstable 32 Hz mode Unstable 25 Hz mode
Testing for different modes: 25 and 32 Hz
60 % compensation for the unstable 25 Hz mode
24 Papiya Dattaray – Cigre NGN 20/02/2018
Cases
Fault
clearing
times
Pt Wh
a a
No ADC
5ms 0.984 0.026 0.02 0.026
10ms 1.072 0.024 0.022 0.024
20ms 0.864 0.026 0.017 0.026
40ms 0.454 0.026 0.009 0.026
50ms 0.661 0.027 0.013 0.027
83.3ms 0.13 0.023 0.002 0.023
With
ADC
5ms 1.712 -0.21 0.035 -0.208
10ms 1.922 -0.217 0.037 -0.214
20ms 1.574 -0.222 0.032 -0.219
40ms 0.821 -0.215 0.016 -0.211
50ms 1.198 -0.216 0.024 -0.213
83.3ms 0.243 -0.217 0.004 -0.204
SSR-LI shown through motor electrical
torque versus speed plot
ADC performance for TA • ADC effective against Torque
Amplification • Three phase short circuit in IEEE FBM • Tested for a range of fault times
Dual protection for both the generator and
vital auxiliaries
25 Papiya Dattaray – Cigre NGN 20/02/2018
The effectiveness of the ADC and participation of the VFD based motor load in SSR damping would depend on its loading at the time of the disturbance
When the VFD is operating at, or close to, its full load capacity the proposed ADC will not be able to provide satisfactory damping
Simplistic control method adopted by the proposed ADC must be tuned for a specific shaft mode
Future work will involve looking at robust control designs that may damp multiple torsional modes simultaneously.
Challenges identified …..
26 Papiya Dattaray – Cigre NGN 20/02/2018
The ADC performance is evaluated for both TI and TA types of SSR interactions in the IEEE FBM and IEEE 68 bus networks and is shown to provide effective positive damping and mitigate SSR under a range of operating conditions
The solution is novel and practical and it incurs minimum additional costs by virtue of exploiting existing resources and provides an effective means for SSR mitigation right at the point of vulnerability (generation centre)
A rather simplistic control architecture has been adopted here to provide a proof of concept.
Conclusions and Future Work
27 VISOR Workshop: UoM Research, 26/09/2017 Papiya Dattaray – Cigre NGN 20/02/2018
Thank you, any questions?
Papiya Dattaray, PhD student [email protected] Supervised by Prof. Vladimir Terzija