1September 30th, 2008 2008 IBM Power and Cooling Symposium
Novel High Efficiency UPS SystemNovel High Efficiency UPS System
Yasuhiro OKUMAYasuhiro OKUMASenior General ManagerSenior General ManagerTechnology Planning DepartmentTechnology Planning DepartmentPower Electronics Development CenterPower Electronics Development CenterTechnology Development GroupTechnology Development GroupFuji Electric Systems Co., Ltd.Fuji Electric Systems Co., Ltd.
2September 30th, 2008 2008 IBM Power and Cooling Symposium
AgendaAgenda1. Background
2. Trend of Fuji UPS Technology
3. Series Parallel Processing Topology>Principal>Realization
4. New Products: 8000 Series ( Three-phase, Large Capacity )
5. New Products: GX Series ( Single-phase, Small Capacity )
6. Conclusion
3September 30th, 2008 2008 IBM Power and Cooling Symposium
AgendaAgenda1. Background
2. Trend of Fuji UPS Technology
3. Series Parallel Processing Topology>Principal>Realization
4. New Products: 8000 Series ( Three-phase, Large Capacity )
5. New Products: GX Series ( Single-phase, Small Capacity )
6. Conclusion
4September 30th, 2008 2008 IBM Power and Cooling Symposium
1997: Kyoto Protocol
1998: Promotion of the Measures to Copewith Global Warming
2008: Law Regarding the Rationalization of Energy Use2007: The Green Grid ( DCD, PUE )
Climate Savers Computing Initiative ( High Efficiency )
The function and the performance were important so far. Hereafter, efficiency becomes the most important.
Fuji Electric has worked on the developmentof high efficiency UPS since 2000.
BackgroundBackground
5September 30th, 2008 2008 IBM Power and Cooling Symposium
AgendaAgenda1. Background
2. Trend of Fuji UPS Technology
3. Series Parallel Processing Topology>Principal>Realization
4. New Products: 8000 Series ( Three-phase, Large Capacity )
5. New Products: GX Series ( Single-phase, Small Capacity )
6. Conclusion
6September 30th, 2008 2008 IBM Power and Cooling Symposium
Trend of Fuji UPS TechnologyTrend of Fuji UPS Technology
Capacitors, FW
Power Device
Topologies
ControllerControl Dev.Control Top.
Inverter
Interface
Rectifier
Compact,High efficiencyMore reliability
Low costHigh Efficiency(Energy Saving)
High ReliabilityUser FriendlyHigher Spec.Non-linear load
Compact in size
Low THDiHigher Spec(High Pf-in)
1st. Gen. LAN Applicable (network OS)
2nd. Gen. LAN (SNMP etc)
Contact
Analog Control Digital Control
1975 199019851980 1995 Requirement2000
Line Interactive
Items
Serial Port
Online Double conversion
Discrete IC, LSI Microprocessor, DSP, ASIC
6 Pulse, 12 Pulse Rectifier High Power Factor Rectifier
Multiplied Inverter Low Freq. PWM(Carrier F < 1kHz)
High Freq. PWM(Carrier F > 5kHz)
MOSFETIGBT IPM
Thyristors
[ Self arc-suppression, Rapid Switching, Low Loss, Low Drive Power ]
GTOPower Transistors
Catalytic Plug Valve Regulated Lead AcidStorageBatteries
Maintenance, LifetimeDownsizing
New Conversion
High Reliability
User Friendly
Auto Shutdown at Blackout
Scheduled Operation
Total Managing System
Environment, RoHS
= =
7September 30th, 2008 2008 IBM Power and Cooling Symposium
AgendaAgenda1. Background
2. Trend of UPS Technology
3. Series Parallel Processing Topology>Principal>Realization
4. New Products: 8000 Series ( Three-phase, Large Capacity )
5. New Products: GX Series ( Single-phase, Small Capacity )
6. Conclusion
8September 30th, 2008 2008 IBM Power and Cooling Symposium
Series Parallel Processing TopologySeries Parallel Processing TopologyWhat is Suitable Principal for High Efficiency?
Series Parallel Processing Topology
Voltage Stability Reduce Volume Efficiency Suitable for UPS
Double Conversion High Low Low High
Parallel Processing Low Mid High Mid
SMR+Inv. High High Low Mid
Direct Conversion High Mid High Low
Line Interactive Mid Low Mid Mid
Series Processing High High High Low
We need new Topology!!
9September 30th, 2008 2008 IBM Power and Cooling Symposium
Series Parallel Processing TopologySeries Parallel Processing TopologyWhy do we choose Series Parallel Processing Topology?
Double Conversion
Parallel Processing
Series Parallel Processingdc
acac
dc
dcac
dcac
acdc
Low Performance
High Efficiency
High Performance
Low Efficiency
High Performance
High Efficiency
Series Conv. Parallel Conv.
10September 30th, 2008 2008 IBM Power and Cooling Symposium
Series Parallel Processing TopologySeries Parallel Processing TopologyPrincipal
Series Processing
Parallel Processing
Series Parallel Processing
dcac
acdc
dcac
dcac
Voltage Compensator
Active Filter
Series Conv. Parallel Conv.
Series Conv. : Voltage Compensator Function
Parallel Conv. : Active Filter & Parallel Inverter Function
11September 30th, 2008 2008 IBM Power and Cooling Symposium
Series Parallel Processing TopologySeries Parallel Processing TopologyRealization: Three-Phase System
How did we achieve smooth changing operation?
P-Con.S-Con.
VI
VI
Th1
Th2
V
Th1
Th2
Alternate Switching
Active filter & PFC
AVR
<Normal Mode>
12September 30th, 2008 2008 IBM Power and Cooling Symposium
Series Parallel Processing TopologySeries Parallel Processing TopologyRealization: Three-Phase System
P-Con.S-Con.
V
Th1
Th2
Inv.
AVR
<Back-Up Mode>Non Interruption!
Transition Period: High Gain AVR operation
P-Con.S-Con.
V
Th1
Th2
Inv.
13September 30th, 2008 2008 IBM Power and Cooling Symposium
Series Parallel Processing TopologySeries Parallel Processing TopologyRealization: Single-Phase System
Easy to Compose the Series Converter with a Transformer.However, the miniaturization of the device of small capacity disturbed by the Transformer.
How did we achieve without using the transformer?
S-Con. S-Con.
?
Series Converter
AVR
Furthermore we needDC Power Source.
14September 30th, 2008 2008 IBM Power and Cooling Symposium
Series Parallel Processing TopologySeries Parallel Processing TopologyRealization: Single-Phase System
Parallel Converter
Parallel Converter
Series Converter
Series Converter
15September 30th, 2008 2008 IBM Power and Cooling Symposium
AgendaAgenda1. Background
2. Trend of Fuji UPS Technology
3. Series Parallel Processing Topology>Principal>Realization
4. New Products: 8000 Series ( Three-phase, Large Capacity )
5. New Products: GX Series ( Single-phase, Small Capacity )
6. Conclusion
16September 30th, 2008 2008 IBM Power and Cooling Symposium
New Products: 8000 SeriesNew Products: 8000 Series
1. High Efficiency : 98%2. Non Interruption3. High reliability : (N+1) Redundant systems
Features
System / Circuit configurations
~
O
●
X● ● ● ●
●
●
X
● ● O
OO
Maintenance Bypass Circuit
Through Circuit
SeriesConverter
ParallelConverter
Battery
UPS 8000D
●
ac Switch
Loa
ds
Load Voltage
Input Voltage
Operation Waveforms
17September 30th, 2008 2008 IBM Power and Cooling Symposium
New Products: 8000 SeriesNew Products: 8000 SeriesSpecifications
Dual processing method (Standby redundancy operation possible)
Rated output capacity (kVA) 100 150 200 250 300 400 500 600 750 1000 1500 2000
Switching time on serv ice interruption No short break
AC input Number of phases Three-phase, three-wire
Voltage
Frequency 50/60Hz (+/-1 to +/-5% selectable f or setting)
Power f actor 0.98 or more (At the rating)
Number of phases Three-phase, three-wire
Voltage Same as the AC output v oltage
AC output Voltage 200V or 415V, 3-phase
Frequency Same as the input, except f or +/-0.01% when operated on battery .
Load power f actor 0.8 (lag) to 1.0 (Rated at 1.0).
Voltage accuracy (When set) In AVR mode: +/-2% or less
In ECO mode: +/-5% or less (Selectable f or setting)
Transient v oltage f luctuation +/-5% or less (Load 0 <=> 100%)
Voltage waveform distortion factor 5% or less
Ov erload capacity In normal condition: 125% for 10 minutes, 200% for one minute, 1000% for one cycle.
During serv ice interruption: 150% f or one minute.
Direct transmissioninput
200 V +/-15%
415 V +/-15%
UPS Sy stem
18September 30th, 2008 2008 IBM Power and Cooling Symposium
New Products: 8000 SeriesNew Products: 8000 SeriesExample of Parallel Operation System
Maintenance Bypass Circuit
No 2 UPS
Maintenance Bypass Circuit
No 1 UPS
Direct Transmission
Battery
Output Input
P-Con.S-Con.
No 3 UPS
Max 8-Parallel / Redundancy
19September 30th, 2008 2008 IBM Power and Cooling Symposium
New Products: 8000 SeriesNew Products: 8000 SeriesExample of Parallel Operation WaveformsBreakdown Mode
Out-Put
Voltage
Out-Put
Current
No 1
No 2
No 3
WarningNo 1 MC3
3-Parallel Operation 2-Parallel Operation
No 1-Fuse Blown No 1-MC3 Opened
Loads
No 1
No 2
No 3
MC3
Loads
No 1
No 2
No 3
MC3
Breakdown
20September 30th, 2008 2008 IBM Power and Cooling Symposium
New Products: 8000 SeriesNew Products: 8000 SeriesComparison in Efficiency and Loss ( Example at 80kW )
Series Output ( kW ) Efficiency ( % ) Loss ( kW ) Power Consumption ofAir-Conditioning Unit ( kW )
Conventional UPS 80 88 10.9 3.9
8000 Series 80 98 1.6 0.45
Comparison in Electric Charge ( Example at 100kVA )
*When operated continuously all year around under 100% load.
Item Result Remarks
Difference in UPS loss 9.3kW =10.9kW-1.6kW
Difference in air-conditioning power consumption 3.45kW =3.9kW-0.45kW
Electric power improved 12.75kW =9.3kW+3.45kW
Annual electric energy reduced 111,690kWh =12.75kW x 24h x 365days
Electric charge saved (Annual) 1.68 million yen / year Electricity rate of 15 yen/kWh
Amount of CO2 cut back 41.4t CO2 emission rate of 0.371kg-amount of CO2/kWh
The 8000 Series leads to a substantial cutback of running cost and reduction of CO2 emissions.It can therefore be termed environment-friendly and suitable Green-IDC systems.
21September 30th, 2008 2008 IBM Power and Cooling Symposium
AgendaAgenda1. Background
2. Trend of Fuji UPS Technology
3. Series Parallel Processing Topology>Principal>Realization
4. New Products: 8000 Series ( Three-phase, Large Capacity )
5. New Products: GX Series ( Single-phase, Small Capacity )
6. Conclusion
22September 30th, 2008 2008 IBM Power and Cooling Symposium
New Products: GX SeriesNew Products: GX Series
1. High Efficiency : 96.7% ( 3000VA )
2. Non Interruption
Features
System / Circuit configurations Operation Waveforms
GX200 GX100
Input voltage
Output voltage
Change from 165V to 235V Change from 235V to165V
Input voltage
Output voltage
Input voltage
Output voltage
Change from 165V to 235V Change from 235V to165V
23September 30th, 2008 2008 IBM Power and Cooling Symposium
New Products: GX SeriesNew Products: GX SeriesSpecifications
Series GX200 GX100Capacity ( kVA ) 0.7, 1.4, 3.0, 5.0, 7.5, 10 1, 1.5, 2.0, 3.0, 5.0, 7.5, 10
Phase Single-Phase / 2-Wire Single-Phase / 2-Wire
Voltage ( V ) 200 ( +20%, -20% )220 / 230 ( +25%, -25% )
240 ( +20%, -20% )
85 - 138 ( Wide Range )
Phase Single-Phase / 2-Wire Single-Phase / 2-WireVoltage ( V ) 200, 220 / 230, 240 ( +3%, -3% ) 100, 105, 110, 115, 120
( +2%, -2% )Selectable on Dip Switches
Backup Time 5 - minutes 6 - minutes
Output
Input
24September 30th, 2008 2008 IBM Power and Cooling Symposium
New Products: GX SeriesNew Products: GX SeriesComparison in Efficiency and Loss
Series Voltage ( % ) Efficiency ( % ) Loss ( W ) Conversion Loss ( W )
75 92.8 187 139
100 96.7 83 36
125 94.9 129 81
85 85.1 426 251
100 87.1 361 190
115 88.5 316 156
75 90.4 47 35
100 96.6 16 4
125 92.8 35 23
85 84.3 151 100
100 86.6 126 77
115 88.3 108 63
ConventionalJ:1000VA
GX:700VA
ConventionalJ:3000VA
GX: 3000VA
The GX Series is a high efficiency UPS. It means a substantial cutback of running cost and environment-friendly and suitable Server systems.
25September 30th, 2008 2008 IBM Power and Cooling Symposium
AgendaAgenda1. Background
2. Trend of Fuji UPS Technology
3. Series Parallel Processing Topology>Principal>Realization
4. New Products: 8000 Series ( Three-phase, Large Capacity )
5. New Products: GX Series ( Single-phase, Small Capacity )
6. Conclusion
26September 30th, 2008 2008 IBM Power and Cooling Symposium
ConclusionConclusion
Fuji Electric has worked on the development ofhigh efficiency UPS since 2000.
New Topology: Series Parallel Processing Topology
8000 Series: Large Capacity ( 100kVA - 2,000kVA )High Efficiency and High PerformanceSuitable Green-IDC
GX Series : Small Capacity ( 0.7kVA - 10kVA ) High Efficiency, For Server
Fuji Electric Systems works on strategic development of newcircuit topology and further, high efficiency UPS System aimingat the achievement of the Sustainable Society.