Novec 1230™
SYSTEM DESIGN
3M™ Novec 1230™ Fire Protection Fluid
![Page 2: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/2.jpg)
Design Concepts
•Total Flooding Fire Protection System– Must have an enclosure
– Agent mixes with atmosphere to protect
entire volume– No local application
– Agent mixing performed by nozzles
![Page 3: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/3.jpg)
Design Concepts
•Enclosure Integrity
– Air leaks effectively sealed
– Door fan test is used to determine
whether or not integrity exists
– Procedure in Appendix C of NFPA 2001
– Must be performed on all new installations
![Page 4: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/4.jpg)
Design Concepts
•Duration of Protection– “...(Extinguishing concentration) shall be
maintained for the specified period of time
to allow effective emergency action by
trained personnel.” -NFPA 2001, Section 5.6
– Hold time is typically 10 minutes, but not
standard– Refer to local AHJ
![Page 5: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/5.jpg)
Design Concepts
•Discharge Time– Must be 10 seconds or less
– Rapid extinguishment reduces production of
by-products (HF)
– Per NFPA 2001 5.7.1.2.1
– Software will issue a warning for less
than 6 seconds
![Page 6: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/6.jpg)
HAZARD SURVEY AND ANALYSIS
![Page 7: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/7.jpg)
Perform Hazard Survey
•Define Hazard:
– Enclosure boundaries
– Enclosure integrity exists?
– Fuels
– Hazard type (Class A, B, C or D)
– MSDS for chemicals present
![Page 8: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/8.jpg)
Required Data
– Dimensions
– Ambient Temperature Range
– Min. and Max.
– Occupancy Requirements
– Normally occupied?
![Page 9: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/9.jpg)
Determine Novec 1230 Suitability
•Novec 1230 is suitable for:
– Class A: Fires in ordinary combustibles
– Class B: Flammable Liquid Fires
– Class C: Fires involving energized
electrical equipment
![Page 10: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/10.jpg)
Determine Novec 1230 Suitability
•Novec 1230 is NOT suitable for use with:– Deep seated fire hazards
– Metal fires per NFPA 2001, par. 1.4.2.2
– Certain chemicals capable of rapid oxidation in
the absence of air: gunpowder,
– Reactive metals: sodium, magnesium, etc.
– Metal hydrides
– Chemicals capable of undergoing autothermal
decomposition
![Page 11: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/11.jpg)
Determine Novec 1230 Suitability
•Operating temperature range for Novec 1230 equipment is 32°F to 130°F
![Page 12: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/12.jpg)
AGENT QUANTITY
![Page 13: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/13.jpg)
Extinguishing Concentration
•NFPA 2001 5.4.2
– Class A extinguishing concentration
determined as part of witness testing
– UL 2166
– Class B extinguishing concentrations
determined by cup burner test
– Appendix B
![Page 14: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/14.jpg)
Minimum Design Concentration
•NFPA 2001 5.4.2– Class A design concentration
– EC x 1.2
– Class B design concentration– MCB x 1.3
– Class C design concentration must be at least
that for Class A
– Manual-Only systems design concentration– EC x 1.3
![Page 15: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/15.jpg)
Minimum Design Concentration
•Determined by Hazard Analysis:
– Class A Hazard: 4.2% (Minimum)
– Class C Hazard: At least that of Class A:
4.2%
– Manual-Only systems: 4.6%
![Page 16: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/16.jpg)
Minimum Design Concentration
•Determined by Hazard Analysis:
– Class B Hazard:
– Reference list in manual or
call Kidde
![Page 17: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/17.jpg)
Minimum Design Concentration•Class B Reference list
![Page 18: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/18.jpg)
Minimum Design Concentration
•If multiple fuels and/or classifications are present, highest applicable concentration is used
![Page 19: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/19.jpg)
Minimum Design Quantity (MDQ)
Equation
-or-
Table
![Page 20: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/20.jpg)
•Dimensions taken during hazard analysis
•OK to subtract permanent volume reductions– Columns– Platforms
•Do NOT subtract for equipment and moveable objects!
Calculate Volume
![Page 21: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/21.jpg)
Design Temperature
•To calculate agent quantity, use minimum expected ambient temperature
•Agent concentration is proportional to air temperature– Same quantity of agent will result in a low
concentration at low temperatures and a high concentration at high temperatures
![Page 22: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/22.jpg)
MDQ Calculation Example
•Enclosure is 10 ft. W x 10 ft. L x 10 ft. H
•Min Ambient Temperature = 70°F
•Class A Surface Fire Hazard
![Page 23: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/23.jpg)
MDQ Calculation Example
Volume = 1000 ft.3
s = 0.9856 + (0.002441 x 70°F) = 1.1565
W = (1000 ft.3 / 1.1565 ) x (4.2% / 100% - 4.2%) = 37.9 lb.
- or -Flooding Factor(4.2%, 70°F) = 0.0379 lb./ft.3
W = 1000 ft.3 x 0.0379 lb./ft. 3 = 37.9 lb.
![Page 24: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/24.jpg)
EXAMPLE PROBLEMS
![Page 25: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/25.jpg)
Correct For Pressure Differentials
•Must correct if ±11% or more from normal
barometric pressure at sea level– Approximately ± 3000 feet from sea level
•Reference Table 5.5.3.3 in NFPA 2001
(also in manual)– Atmospheric correction
– Highly pressurized; keep dust out
– Highly depressurized; keep particles in
![Page 26: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/26.jpg)
EXAMPLE PROBLEMS
![Page 27: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/27.jpg)
Minimum Design Concentration
vs. Adjusted Design Concentration•Minimum Design Concentration is the
minimum required per NFPA 2001
•Adjusted Design Concentration is the concentration used to calculate the quantity of agent in the cylinder– ADC >= MDC
![Page 28: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/28.jpg)
AGENT STORAGE CONTAINER LOCATION
![Page 29: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/29.jpg)
KIDDE
Agent Storage Container Location
•As close as possible to or within the protected enclosure– Per NFPA 2001
![Page 30: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/30.jpg)
KIDDE
Agent Storage Container Location
•Floor loading
– Container weight plus
agent weight
![Page 31: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/31.jpg)
KIDDE
Agent Storage Container Location
•Space requirements
– Single/Multiple cylinders
– Space for riser and attached controls
![Page 32: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/32.jpg)
KIDDE
Agent Storage Container Location
•Accessibility– Cylinder(s) accessible
for maintenance
![Page 33: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/33.jpg)
KIDDE
Agent Storage Container Location
•Storage temperature– Balanced or Single Hazard
Systems
= 32°F to130°F
– Unbalanced, Multi-Hazard
Systems
= 60°F to 80°F
![Page 34: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/34.jpg)
KIDDE
Agent Storage Container Location
•Storage temperature– If necessary, build an enclosure
and control temperature
– Does not reflect hazard
temperature(s)
![Page 35: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/35.jpg)
KIDDE
Agent Storage Container Location
•Classified areas– Explosion-proof equipment
needed/available?
![Page 36: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/36.jpg)
Novec 1230™SERIES SYSTEMS
![Page 37: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/37.jpg)
NOVEC 1230 Nozzles
•Two nozzle types– 180° Nozzle– 360° Nozzle
•Nozzle sizes– 3/8” through 2”– 1/4” offered - Non UL and FM
•All nozzles must be pendant (hanging down)
![Page 38: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/38.jpg)
Wid
th (
W)
Length (L)
1/3 L 1/3 L 1/3 L
1/3 W
1/3 W
1/3 W
Acceptable 180 degree nozzle location
NOVEC 1230 Nozzles
•180° Nozzle– Placed 6” ± 2” from a wall
– Orifices aimed away from the wall
– 6 - 19” ± 2” from ceiling to orifices
– As close to center of the wall as possible– At least 1/3
– No corner placement
![Page 39: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/39.jpg)
Wid
th (
W)
Length (L)
1/3 L 1/3 L 1/3 L
1/3 W
1/3 W
1/3 W
Acceptable 360 degree nozzle location
NOVEC 1230 Nozzles
•360° Nozzle– Discharges agent in a
360° pattern
– Placed as close to center
of hazard as possible
– 6” to 19” from ceiling to
orifices
![Page 40: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/40.jpg)
Novec 1230 Discharge
•Discharged as both liquid and vapor
•When near obstructions, liquid will “splash”
– Will effect the mixing of agent in the space due to reduced momentum in discharge.
![Page 41: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/41.jpg)
Min 6' Min 6'
Min 6'
Min 6'
Min 6'
Min 6'
Min 6'
NOVEC 1230 Nozzle Locations
•Proximity of nozzles to significant obstructions– 6 ft. of clearance between
nozzle and wall
(or significant obstruction)
– Additional agent can be
discharged to
compensate for “losses”
on obstructions
![Page 42: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/42.jpg)
Min 10'
Min 10' Min 10'
Min 10'
NOVEC 1230 Nozzle Locations
•Proximity of multiple nozzles– At least 10 ft. of clearance between
nozzles
![Page 43: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/43.jpg)
2' (Min 1')
Imaginary boundary
NOVEC 1230 Nozzle Locations
•Back-to-Back 180° Nozzles– 1 ft. to 2 ft. apart– Must face away from each other– Nozzles discharge equal quantities
![Page 44: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/44.jpg)
NOVEC 1230 Nozzle Locations
•For smaller enclosures
– Recommend using 180 nozzles in order
to meet 6 ft. clearance
– Recommend placing 180 nozzles along
longest wall to allow maximum
clearance in all directions
![Page 45: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/45.jpg)
d
d
NOVEC 1230 Nozzle Coverage
•Tested 35.6 ft. x 35.6 ft. Rectangle– (10.9 m x 10.9m)
•Actual coverage area defined as rectangle with diagonal, d
• 180°-d = 39.8 ft.(12.1m) 360°–d = 25.2 ft.(7.7 m)
![Page 46: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/46.jpg)
NOVEC 1230 Nozzle Height
•Maximum height for single nozzle is 16 ft.
•Minimum height– 1 ft. for UL Listed systems
![Page 47: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/47.jpg)
Max 16’
Max 16’
Nozzle Tiering
•Use two rows of nozzles to protect enclosures greater than 16 ft. high (note max elevation difference limit)
![Page 48: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/48.jpg)
Quantity of Nozzles
•Not always dictated by coverage area
•Coverage volume 35.6 ft. x 35.6 ft. x 12
ft. requires 574 lb. of Novec 1230– Will not discharge out of a single nozzle
within 10 seconds!
•Rule of Thumb:– Approximately 200 lb. per nozzle
![Page 49: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/49.jpg)
Novec 1230™Engineered System Limits
![Page 50: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/50.jpg)
NOVEC 1230 Engineered Systems
•Hydraulic flow calculations used as basis of design– Allows for unbalanced systems
– Allows designer to use smaller pipe
– Use computer software to run flow
calculations
![Page 51: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/51.jpg)
NOVEC 1230 Piping Network: Tees
•Tee Parameters:
– Tee Orientation
– Flow Splits
– Bull Tees
– Side Tees
– “10 Pipe Diameters”
![Page 52: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/52.jpg)
NOVEC 1230 Piping Network: Tees
•Orientation
– 1 inlet
– May be horizontal or vertical (bull head tee
only)
– 2 outlets
– Both must be horizontal
![Page 53: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/53.jpg)
IN
OUT OUT
NOVEC 1230 Piping Network: Tees
•Bull tee flow split
– Minimum imbalance: 50/50
– Maximum imbalance: 75/25
![Page 54: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/54.jpg)
SIDE OUTLET(10 - 35)
INRUN OUTLET
(90 - 65)
NOVEC 1230 Piping Network: Tees
•Side tee flow split– Minimum imbalance: 65/35
– Maximum imbalance: 90/10
![Page 55: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/55.jpg)
NOVEC 1230 Piping Network: Tees
•“10 Pipe Diameters” Rule:– Length of pipe between a tee and a
change in direction must be equal to 10 times the nominal diameter of the pipe– A change in direction is defined as either
an elbow or another tee
– Must be adhered to before and after the tee
– Only necessary if the tee feeds agent to
separate hazards
![Page 56: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/56.jpg)
KIDDE KIDDE KIDDE
NOVEC 1230 Piping Network: Layout
•Keep network as simple, balancedand short as possible
•Consider structural members for hanging/bracing
•Avoid obstructions
![Page 57: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/57.jpg)
Max 20’
NOVEC 1230 Piping Network: Layout
•Maximum allowable elevation difference in system piping (outlet and furthest horizontal pipe run/nozzle, or nozzles) is 20 ft.
![Page 58: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/58.jpg)
NOVEC 1230 Piping Network: Layout
•Percent of Agent in Pipe
– Percentage of the available agent that is
required to fill the pipe network
– Maximum 100%
– Affected by agent quantity, pipe lengths
and pipe diameters
![Page 59: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/59.jpg)
NOVEC 1230 Piping Network: Layout
•Percent of Agent Before 1st Tee is 2%
– Percentage of the available agent that is
required to fill the pipe network between
the cylinder outlet and the first tee
![Page 60: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/60.jpg)
NOVEC 1230 Piping Network: Layout
•Arrival Time Imbalance– Difference in time between when the agent
reaches the first nozzle and when it reaches the last nozzle
– Max 1.0 seconds (Subject to change)
•Runout Time Imbalance– Similar to Arrival Time Imbalance, but refers to
when agent runs out at each nozzle
– Max 3.2 seconds (Subject to change)
![Page 61: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/61.jpg)
NOVEC 1230 Piping Network: Pipe Sizes
•Pipe sizes are estimated by the software based on quantity of agent designated to each nozzle– Flow rate = lb. of Novec 1230 in branch /
10 seconds– Pipe estimating table in DIOM manual
(Table 3-6)
•Some manual changes may be required
![Page 62: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/62.jpg)
NOVEC 1230 Piping Network: Pipe Sizes
•Pipe sizes 1/2” through 6” are listed/approved– Largest Nozzle Size is 2”
•Smaller than 1/2” is available in software, but not listed/approved– Smallest Nozzle Size is 3/8”
– 1/4” nozzle is available (Unapproved
systems only)
![Page 63: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/63.jpg)
NOVEC 1230 Piping Network: Nozzles
•Minimum Nozzle Pressure– 91 psig (per UL 2166 Requalification)
![Page 64: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/64.jpg)
NOVEC 1230 Piping Network: Hydraulic Calculation
•Enter:– Enclosure info– Agent quantity– Agent Source– Pipe network
•Run Main Calculations
•Verify system acceptance
![Page 65: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/65.jpg)
Hints, Tips and Other Considerations
![Page 66: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/66.jpg)
Multiple Systems / Single Hazard
•If enclosure is large, consider using:– Multiple, modular NOVEC 1230 systems,
which will discharge simultaneously,
located throughout the hazard
– However - With 100% Agent in Pipe limit
- Novec flows well in complex pipe
networks.
![Page 67: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/67.jpg)
Single System / Multiple Hazards
•If protecting more than four enclosures that are not connected, consider:
– Separate NOVEC 1230 systems
![Page 68: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/68.jpg)
Agent Migration
• If protecting a single space with multiple nozzles, each nozzle should discharge the quantity of agent required by the nozzle’s design coverage area
– Maximum of 5% of the required agent may be discharged by a nozzle protecting an adjacent area
![Page 69: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/69.jpg)
Designing for Multiple Hazards
•For more than one hazard, design with an adjusted concentration of 4.2% or higher
– Extra agent will make flow splits a lot
easier
– NOTE: Still use 4.2% as minimum
![Page 70: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/70.jpg)
Tee Design Factor
•NFPA 2001 5-5.3.1– Starting from each hazard, count:
– Every tee within the hazard that splits to a
separate hazard
– Each tee between entry point to hazard and
the agent source (not including tees in a
manifold)– Reference Table 5-5.3.1 in NFPA 2001
for additional agent required
![Page 71: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/71.jpg)
Tee Design Factor Example
![Page 72: Novec 1230 ™ SYSTEM DESIGN 3M™ Novec 1230™ Fire Protection Fluid](https://reader033.vdocuments.site/reader033/viewer/2022061322/56649e3c5503460f94b2e664/html5/thumbnails/72.jpg)
Tee Design Factor Example
– Maximum tee count is 6
– From NFPA 2001, Table 5-5.3.1, a tee
count of 6 requires a 0.02 (2%) safety
factor