notice technique sirocco gb

Upload: marcos-amorim

Post on 04-Jun-2018

230 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/13/2019 Notice Technique SIROCCO GB

    1/28

    Installation instructions

    Air dehumidifier for indoor swimmingpools

    Rf.: N.D.005.A.EN - Ver. 02-2010

    SIROCCO 55-80-110

  • 8/13/2019 Notice Technique SIROCCO GB

    2/28

    1

    1. Installation ............................................................................................................... 2

    1.1 General ............................................................................................................................. 21.1.1 Precautions ................................................................................................................................ 21.1.2 General terms of delivery ........................................................................................................... 21.1.3 Storage and transport conditions ............................................................................................... 31.1.4 Field of application ..................................................................................................................... 31.1.5 Operating principle ..................................................................................................................... 3

    1.2 Description ........................................................................................................................ 31.2.1 Technical specifications ............................................................................................................. 31.2.2 Operating conditions .................................................................................................................. 3

    1.3 Installation ........................................................................................................................ 41.3.1 Electrical regulations for swimming pools .................................................................................. 41.3.2 Installation requirements ............................................................................................................ 51.3.3 Access to technical compartment .............................................................................................. 51.3.4 Connection to surrounding air .................................................................................................... 61.3.5 Inset connection ......................................................................................................................... 71.3.6 Connection of the condensation drainage ................................................................................. 81.3.7 Electric connections ................................................................................................................... 81.3.8 Connection of the options ........................................................................................................ 12

    1.4 Commissioning ............................................................................................................... 131.4.1 Starting the appliance .............................................................................................................. 131.4.2 Checks ..................................................................................................................................... 131.4.3 Commissioning the options ...................................................................................................... 13

    2. Troubleshooting.................................................................................................... 142.1 Status and faults in the ECP 600 settings ...................................................................... 142.2 Troubleshooting procedures ........................................................................................... 16

    3. Maintenance .......................................................................................................... 183.1 Maintenance instructions ................................................................................................ 18

    3.1.1 Monthly checks ........................................................................................................................ 183.1.2 Annual checks .......................................................................................................................... 18

    3.2 Spare parts ..................................................................................................................... 183.3 Recycling the product ..................................................................................................... 193.4 EC compliance certificate ............................................................................................... 19

    Available in the appendices at the end of the manual:- electric diagram- dimensions

  • 8/13/2019 Notice Technique SIROCCO GB

    3/28

    2

    1. Installation

    1.1 General

    Read this manual carefully before installing, maintaining or repairing th is appliance!

    The symbol indicates important information that must be taken into account in order toavoid the risk of injury and/or damage to the appliance.

    The symbol indicates useful information.

    1.1.1 Precautions

    1.1.2 General terms of delivery

    Any equipment, even CARRIAGE and PACKING FREE, travels at the recipients risk. The recipientmust indicate any reserves in writing on the carrier's delivery bill in the case of damage caused duringtransport (confirmation to be sent to the carrier within 48 hours by registered mail andAcknowledgement of Receipt).

    Contents:

    + + +

    Supplied parts:

    Hygro Control +anti-vibration studs x4 +dowel x 2long bolt x 2

    For Sirocco can be inset :

    sleeve x 2 +

    frame with cadre suction grid and filter x 1 +

    framewith blowing grid + frame fixture kit x 1

    The appliance must be transported upright on its pallet, in its orig inal packaging.If the appliance has been overturned make written reserves in writing to the transporter.

    Removing or shunting any of the safety or remote control parts will automaticallyvoid the guarantee; the same will apply for the replacement of parts by non-original parts.

    Do not discharge R407C fluid into the atmosphere: R407C is a fluorinatedgreenhouse effect gas, covered by the Kyoto Protocol, with a Global WarmingPotent ial (GWP) = 1653 - (Directive EC 842/2006).

    Before working on the appliance, ensure that it is disconnected from the powersupply.

    This device must be installed and serviced by certified professionals approved inthe electrical, hydraulic and cool ing domains.

    EN

  • 8/13/2019 Notice Technique SIROCCO GB

    4/28

    3

    1.1.3 Storage and transport conditions

    1.1.4 Field of appl ication

    1.1.5 Operating princip le

    1.2 Description

    1.2.1 Technical specifications

    Appl ianceDehumidifying

    capacity*Power

    consumed*Restored power atroom temperature*

    Nominal airflow

    without option L/h W W m/h

    Sirocco 55 2.3 L/h 990 W 2080 W 600 m3/h

    Sirocco 80 3.3 L/h 1100 W 2310 W 800 m3/h

    Sirocco 110 4.6 L/h 1340 W 2810 W 1000 m /h* under the following nominal conditions: air 30C - humidity 70%.

    unit protection class: Sirocco ambient: IP 44 ; Sirocco can be inset: IP 45

    class: I

    refrigerant gas: R407C

    refrigerant charge: see product information plate

    1.2.2 Operating condit ions

    operating range: 10C to 40C (temperature in the swimming pool hall)optimum operating conditions: between 25 C and 30 C

    Hygro Control on request

    Exclusive use: dehumidify ing swimming pool halls.Not to be used for any other purpose.Install in a dry, ventilated technical room, protected from frost and damp, and notused to store pool maintenance products.

    The appliance must be transported upright on its pallet.

    Condensation

    Ai r

    +35C40%HR

    Air

    +28C65%HR

    Compressor

    Expansion valve

  • 8/13/2019 Notice Technique SIROCCO GB

    5/28

    4

    1.3 Installation

    1.3.1 Electrical regulations for swimming pools

    Refer to the current regulations for your country.French standard C15.100 Section 702 - U.T.E:In volumes 0 and 1, only protection using Very Low Voltage (article 411.1) with a nominal voltage notexceeding 12 V AC or 30V DC is allowed. The protection must be installed outside volumes 0, 1 and 2(the appliance has a protection index of at least IP X5).

    In volume 2 (see figures 702A and 702B), the appliances must be:- either class II for lighting,- or class I protected by a 30 mA or less ground fault circuit breaker,- or powered by a separation transformer in compliance to paragraph 413.5.1The appliance has a protection index of at least IP X2.

    h: unknown variableV: volume

    EN

    Figure 702 A: volume sizes for in-groundpools and foot baths

    Figure 702 B: volume sizes forabove-ground pools

  • 8/13/2019 Notice Technique SIROCCO GB

    6/28

    5

    1.3.2 Installation requirements

    1.3.3 Access to technical compartment

    1) install the appliance on a level base, to avoid any overflows from the condensationtray (adjustment by two hexagonal screws, see figure 1.3.3),

    2) easy access to the appliance for maintenance and connections,

    3) place nothing in front of or on the blowing and suction g rates,

    4) anti-vibration studs(supplied) must be installedunder the base when the appliance

    is placed on the floor or on a support,

    5) for a swimming pool building wi th a high ceiling or visible roof frame:- destratification of the upper layers of the room = one or several fans with PVCblades oran air extractor with fresh air intake.

    Warning!230 V AC appliances = must be outside volume 1 (see 1.3.1),

    6) building requirements:swimming pool building = very damp roomDuring building make sure that:

    - the materials used are compatible with a swimming pool environment,- the walls are sufficiently waterproofed and insulated to avoid condensation forming inthe room when relative humidity reaches 60 to 70%.

    Light structure buildings (verandas, shelters...): there is no risk of deterioration of thestructure, even in case of dew as they are designed to support this (even with a relative

    humidity of 70%)

    7) risk of stratification:- height of the room < 4 to 5 meters: mechanical ventilator unit or extractor,- height of the room > 7 to 8 meters: ceiling fans with large blades,

    8) ventilation, renewal of air,- private pools: highly recommended- public pools: compulsory

    The air can be renewed by:- a simple mechanical ventilation unit,- a wall or roof extractor with fresh air intakes.

    This ventilation ensures the hygienic renewal of air, the removal of any chloraminespresent in the air, and the elimination of excessively hot air, whilst contributing to the

    dehumidification of the room.

    32

    Adjusting screw to level the appliance

    on each side

    1

    or

  • 8/13/2019 Notice Technique SIROCCO GB

    7/28

    6

    1.3.4 Connection to surrounding air

    1.3.4.1 Appliance on the ground (or on a support)

    1.3.4.2 Appliance fixed to the wallUsing the two anchoring points at the back of the appliance (with two bolt screws, washers and plugs(supplied) in a solid wall)

    Pool

    *minimum distance

    Sirocco 55-80-110

    suction gridblowing grid

    Hygro Control

    condensation drainage

    air renewal system (see 1.3.2)

    fresh air intake

    Pool

    * minimum distance** maximum distance

    Sirocco 55-80-110

    suction gridblowing grid

    Hygro Controlcondensation drainage

    air renewal system (see 1.3.2)

    fresh air intake

    EN

  • 8/13/2019 Notice Technique SIROCCO GB

    8/28

    7

    1.3.5 Inset connection

    Install the appliance in a technical room that is protected from freezing.

    Reserve dimensions (+2 mm / -0 mm)

    mm

    Sirocco 55 618 x 165

    Sirocco 80 808 x 165

    Sirocco 110 998 x 165

    the sleeves are:- to be incorporated in the wall at the time of construction,

    - or for sliding into the previously made reservations in the wall, plan for a gasket between thewall and the outside surface of each sleeve of the technical room and swimming pool room side,

    present the base of the appliance (without the cover) to the wall, opposite the sleeves and markthe two inside anchoring points,

    install the fixing plugs into the solid wall using the marks,

    present the appliance again and from the inside screw in the bolt-screws + washers into each plug

    plan for an earth for the blowing and suction grid frame, following the electrical standards in forcein the country (in France: standard NFC 15100, see 1.3.1).

    At this moment, the frames fixed to the back of the appliance must easily slot into eachsleeve.

    The blocks of polystyrene must remain in the sleeves to protect them fromcrushing.

    Pool

    * minimum distance** maximum distanceSirocco 55-80-110suction gridblowing gridHygro Controlcondensation drainageair renewal system (see 1.3.2)fresh air intake

    Technical

    room

    Swimmingpoolhall

  • 8/13/2019 Notice Technique SIROCCO GB

    9/28

    8

    1.3.6 Connection of the condensation drainage

    Plan for an adequate slope to ensure a good flow. Drainage shall be via a siphon or a funnel(condensation drainage pipe 12/18). Outlet provided for at the left of the appliance (condition ex-works), with possibility of moving it to the right.Make sure the siphon is filled with water in such a way as not to create air suction by the condensationdrainage pipe.For placing the condensation drainage: see mark A 12/18 dimensions in the appendix.

    1.3.7 Electric connections1.3.7.1 Access to the electric box

    1.3.7.2 Voltage and protect ion

    The electrical supply must be provided through a protection and circuit breaking device (notsupplied) complying with the standards and regulations in force in the country where it is installed (inFrance standard NF C 15100).

    Electrical protection: 30 mA ground fault circuit breaker (at the head of the line).

    1.3.7.3 Cable sizes

    Supply cable size: for cables of a maximum length of 20 metres (calculation basis: 5A/mm), thismust be checked and adapted depending on installation conditions.

    Option VoltageNominalpower

    consumption

    Maximumpower

    consumptionCable size

    Unit A A mm

    Sirocco 55

    single-phase

    without option orhot water battery

    230V-50Hz- 4.45 5.9 3 x 2.5 3G2.5

    Extra heating 2kW

    230V-50Hz- 13.2 14.6 3 x 4 3G4

    Sirocco 80single-phase

    without option orhot water battery

    230V-50Hz- 5.05 8 3 x 2.5 3G2.5

    Extra heating 3kW

    230V-50Hz- 18 21 3 x 6 3G6

    Sirocco 110single-phase

    without option orhot water battery

    230V-50Hz- 6.35 9.8 3 x 2.5 3G2.5

    Extra heating 4.5kW

    230V-50Hz- 26 29.4 3 x 10 3G10

    Sirocco 110three-phase

    without option orhot water battery

    400V-50Hz- 2.8 3.8 5 x 2.5 5G2.5

    Extra heating 4.5

    kW 400V-50Hz- 9.3 10.3 5 x 2.5 5G2.5

    Acceptable voltage variation tolerance: 10% (during operation),

    Electric cables must be fixed.

    Prior to any operation, check that the voltage on the identification plate of theappliance corresponds to the mains voltage available on site.

    2

    On each side

    1 3

    EN

  • 8/13/2019 Notice Technique SIROCCO GB

    10/28

    9

    1.3.7.4 ConnectionsTerminal Sirocco single-phase 230V-1N-50Hz:

    Terminal Sirocco 110 three-phase 400V-3N-50HZ:

    1.3.7.5 Hygro Control connection

    - for installation location: see 1.3.3 and refer to 1.3.1,- correctly influenced by the swimming pool room air,- connect to terminals on the electric box.

    Hygro Control = digital display hygro-thermostat = display and setting of pool halltemperature* and humidity

    The appliance must be earthed.Risk of electrical shock inside the device. Only a qualified and experiencedtechnician must install the device cables.If the power cable is damaged it must be replaced by a qualified technician or by aZodiac Pool Care Europe service station.

    Main supply(see 1.3.7.3)

    Regulation connection(see 1.3.7.5)

    Contact normallyopen control of heat source

    Main supply 230Vac-50Hzfor circulator

    (used with hot water battery, see 1.4.3.2)

    or

    Main supply(see 1.3.7.3)

    Regulationconnection

    (see 1.3.7.5)

    Circulator connection (C-C) or control of heatsource by contact NO(3-6) (see 1.4.3.2)

    Internal connectionterminals (do not modify

    the connections)

    Cable 5 x 1 mm,maximum length:30 meters

    on/off

    General Sirocco terminal

    Temperature* and humidity programmingor hygro-thermostat settings

    Value settings

  • 8/13/2019 Notice Technique SIROCCO GB

    11/28

    10

    Technical specifi cations

    Admissible room temperature C 0-55Admissible humidity level % 0-90Voltage V AC 12Maximum voltage V AC 24Protection index IP 20Dimensions: width / height / depth mm 120 x 70 x 28

    HysteresisHymidity % 4temperature C 1

    Display

    Hygro Control display Hygro-thermostat Hygrostat ThermostatOn standby

    Active

    Starting up and stopping the appliance

    Press for 5 seconds.

    Locking/unlock ing the keyboardTo lock and unlock the keyboard:

    - Hygro Control must be active,

    - press and simultaneously for 3 seconds,

    - the message is displayed or is removed.

    By default: display of the temperature and/or desired relative humidity.

    Display of the ambient temperature and/or humidity by pressing once, Cand/or

    %RHblink. To exit, press , or wait 10 seconds.

    *only if your appliance is fitted with the hot water battery option, or extra electricheating.

    - The numberingof the terminals must be respected,- Do not put these cables into the same duct as other 230 V or 400 V to avoid anyrisk of interference of the signals,- Obstructthe place where the cable emerges from the wall or seal it by using materialsother thansilicone and silicone-based materials, in order to avoid any arrival of airexterior to the room through the duct or dividing wall.

    Main supply 12Vac-50Hz- between terminals 4 and 5.

    Temperature display*Relative Humidity

    Degree Fahrenheit

    Degree Celsius

    Requestingdehumidification

    Requesting heating

    EN

  • 8/13/2019 Notice Technique SIROCCO GB

    12/28

    11

    Adjust ing the reference values- Hygro Control must be active,

    - press for 3 seconds, the modifiable value blinks,

    - use or to set the value,

    - press to validate,

    - and then to exit.

    Value range minimum maximum Comfort setting

    Humidity 55% 70% 65%Temperature 5 C 32 C 28C

    Test mode / Manual overrideTo force the appliance to operate for 30 minutes, even if the pool hall conditions do not trigger therequest:

    - Hygro Control must be active,

    - press on for 3 seconds, a value blinks,

    - press again for 10 seconds,

    - all the digits light , or and the appliance starts up.

    Parameter setting in hygro-thermostat or hygrostat mode

    - Hygro Control must be on standby,

    - press and for 3 seconds : (hygro-thermostat mode),

    - press or to select the function: (hygrostat mode),(thermostat mode)

    - validate by pressing .

    Hygro Control shipped with the setting for hygro-thermostat mode for appliances with theheating option for hygrostat mode for devices without the heating option.This setting must be changed if a heating option is added or removed.

    To quit this mode, press the button for 5 seconds.

    If the keyboard is not used for 30 seconds, the setting will be abandoned and the last(non validated) setting will not be taken into account.

  • 8/13/2019 Notice Technique SIROCCO GB

    13/28

    12

    1.3.8 Connection of the options

    1.3.8.1 Hot water battery

    Connections on 15-21, male fitting. Outlet must be obligatorily on the leftseen from the front.

    Power Water flow rate Water load loss

    Unit kW m/h mCE

    Primary 90/70C 45/40C 90/70C 45/40C 90/70C 45/40C

    Sirocco 55 6 2.1 0.25 0.35 0.41 0.77

    Sirocco 80 9 2.6 0.42 0.46 0.37 0.47

    Sirocco 110 12 3.3 0.53 0.58 0.65 0.83

    Water temperature input to the hot water battery: 45 C minimum, 90C maximum.Maximum pressure water battery circuit: 3 bars

    Power returned to the air at 27C input to the hot water battery.

    Connection to the primary circui t: before any valves or pumps.

    Swimmingpool hall Technicalroom

    Swimmingpool hall

    Technicalroom

    Circulator mainsupply cable

    Circulator mainsupply cable

    Sirocco ambient

    Suction

    Blowing

    Sirocco can be inset

    Suction

    Blowing

    EN

    Automatic purge

    Circulator

    Check valve orsolendoid valve

    Check valve or solendoid

    Automatic purge

    Circulator

    Check valve orsolendoid valve

    Check valve orsolendoid valve

  • 8/13/2019 Notice Technique SIROCCO GB

    14/28

    13

    1.4 Commissioning

    1.4.1 Starting the appliance

    power on the appliance (by switching on the general terminal board),

    only for three-phased Sirocco: when the dehumidifier is switched on, check the status of the phasecontroller (KA4). If it is off, cut off the power supply and invert two phases directlyon the applianceconnection terminal board.

    This operation must be only be carried out by a qualified professional.

    set the humidity and temperature on the Hygro Control so that it triggers dehumidifying and / or airheating (optional), see 1.3.7.5.

    1.4.2 Checks

    In the Hygro Control comfort model (see 1.3.7.5)

    check that hot air is coming out of the blower grates,

    check that the appliance is draining condensation,

    1.4.3 Commissioning the options

    The heating options are operational from 4C surrounding air temperature.

    1.4.3.1 Extra heating

    starting up Hygro Control and adjust the thermostat to between 26 and 28C (maximum 30C), ingeneral choose an air temperature 1 to 2C higher than the pool water temperature,

    check that with the VI/VP switch on VI, and no dehumidification or defrosting cycles in progress:- the fan stops operating, after post-ventilation of 3 minutes when the reference room temperatureon the pool room thermostat is lowered,- in the event of abnormal overheating, the appliance shuts down the heating option automatically,by shutting off the heating elements and keeping the ventilation operational (for as long as aheating request is active).

    This safety device has two levels of triggering:1) by THS safety thermostat if the TC is > 65C (it is automaticallyreset),2) if the temperature continues to increase, the second positive

    THSM safety thermostatputs the appliance into safety mode.=> reset it manually (with power off), after having checked that theappliance air flow is correct (with the VI/VP switch on VP), thatthe grates are not obstructed, that the filter is not clogged, and thefan is not defective.

    1.4.3.2 Hot water battery

    supply the battery with hot water at 45 C minimum from the heat source (boiler, heat pump,

    geothermal energy, solar heating), installation must be carried out by a qualified technician, using acirculator (not supplied) which will be powered by terminals C-C on the electrical terminal board.

    Insulate the hot water battery hot water pipes between the heat source and the appliance(for the purpose of limiting calorie loss).

    if your pool has a cover (shutter or bubble sheet type, etc.), you can lower the roomtemperature when it is in place (by adjusting the thermostat to about 20C) and raise thepool hall temperature before removing the cover.

    When the ECP 600 regulator is switched on ventilation is active for 5 minutes.This also occurs if the appliance is powered on and the on/off switch o f theHygro Control delivered with the appliance is used.

    This phase order controller protects the compressor.Its forbidden toinverted phases:- on the power contactor (KM2)- on the compressor

    If the indicator remains switched off after this operation check for the presence of thethree phases on the phase order controller KA4.

    EN

  • 8/13/2019 Notice Technique SIROCCO GB

    15/28

    14

    connection to a ZPCE double circuit gas boiler: connect the terminals 3-6 of the terminal board, toterminals 3-6 of the boiler terminal board,

    adjust the thermostat between to 26 and 28C (maximum 30C), in general set the air temperature1 to 2C higher than the pool water temperature,

    a post-ventilation runs for 3 minutes when the reference temperature is reduced on the thermostatlocated in the pool hall (with the VI/VP switch on VI, without any dehumidification or defrostingcycles in progress): check that the circulator stops.

    2. Troubleshooting

    2.1 Status and faults in the ECP 600 settings

    Terminals Description

    N - R mains-supply 230Vac-50Hz to the ECP600 regulator20 - 21 output from compressor supply 230 Vac -50Hz30 - 31 230Vac-50Hz output (not used) and protected by the ECP600 fuse22 - 23 ventilator 230Vac-50Hz output25 - 24 output for circulator hot water battery option 230Vac-50Hz26 - 27 output alarm report 230Vac-50Hz28 - 29 output contact NO (without polarity) control of heat source hot water battery option

    11 12 - 13 Input control sensor type PTC (inlet or defrost)

    4 - 5 power supply 12Vac-50Hz

    7input 6Vac-50Hz given by the hygrostat function (request active if 6Vac-50Hzbetween 7 and 4)

    2input 6Vac-50Hz given by the thermostat function (request active if 6Vac-50Hzbetween 2 and 4)

    8input 12Vac-50Hz fan heat fault (shunted not active) (fault active if 0Vac-50Hzbetween 8 and 4, dfaut thermique ventilateur led lit up)

    9input 12Vac-50Hz faults BP and/or HP, and/or phase order (Sirocco three-phase)(fault active if 0Vac-50Hz between 9 and 4, dfaut pressostat HP ou BP led lit up)

    10input 12Vac-50Hz compressor heat fault (shunted not active) (fault active if 0Vac-50Hz between 10 and 4, dfaut thermique compresseur led lit up)

    Led lit continuously Meaning

    compresseur= compressor

    the compressor is operational (blinking = temporisation in process)

    EPROM ECP600 regulator out of order

    Warning - low temperature: if the dehumidifier hot water battery is not supplied by aboiler, but by an aero-thermal or a geothermal system, the heating circuit water will be ata maximum temperature of 45-40C. The power of the battery will then be considerablylower (3 to 4 times less) than the nominal power given for water at 90-70C. If the powerof the battery is lower than the heating needs of the room, plan for additional heating byradiator, heated floor or fan convector.

    If your pool has a cover (shutter or bubble sheet type, etc.), you can lower the room

    temperature (by adjusting the thermostat to about 20C) when it is in place and raise thepool hall temperature before removing the cover.

    Terminals 3-6 can also ensure a heat source control function (see 1.3.7.4)

    EN

  • 8/13/2019 Notice Technique SIROCCO GB

    16/28

    15

    Led lit continuously Meaning

    dfaut thermiqueventilateur

    = fan heat faultNot used on Sirocco

    dfaut pressostatHP ou BP

    = high or low

    pressure switch fault

    triggering HP and/or LP switch and/or phase order relay KA4 (only onSirocco three-phase)

    - HP : check that the ventilator is operational, that the air filter is clean andthe belt is tight enough,

    - LP: insufficient gas, call a specialist,- KA4: check for the presence of the 3 phases, if so, see 1.4.2.

    dfaut thermiquecompresseur

    = compressor heatfault

    Not used on Sirocco

    dclenchementalarme

    = Triggering of thealarm

    - HP and/or LP switch triggered more than 3 times in one hour- order phase relay KA4 triggered (only on Sirocco three-phase)

    dfaut horstemprature

    = temperature rangefault

    - temperature < than 10C or > than 40C (compressor stopped),- restart sensor is out of order.- In all cases, if the ventilator is active before the triggering of this fault, it ismaintained for 3 minutes before stopping.- If the returns to within its operating range:- there is a 30 seconds delay before the fault is cleared,- there is a 3 minute delay before restarting the compressor and the fan (if adehumidification request is still active)

    cycle de dgivrage= defrosting cycle

    - cooling circuit temperature < than -5C or > than 40C,-a defrosting cycle is in progress (temperature is >-5C). The compressor isstopped and ventilation is maintained,- the defrosting sensor is out of order.The defrosting cycle stops when the temperature of the sensor goes over2.2C. If the sensor is out of range (40C) during the activedefrosting cycle, this LED remains on for 3 minutes with the ventilationoperating, before it stops.In all cases, if the ventilator is active before the triggering of this fault,ventilation is maintained for 3 minutes before stopping.If the sensor returns within its operating range:- there is a delay of 30 seconds before the fault is cleared,- there is a 3 minute delay before the compressor and fan restart (if adehumidification request is still active)

    Others Description

    VI/VP switchintermittent ventilation (standard setting)or permanent ventilation (to permanently circulate the pool hall air)Using VI, a post-ventilation is active for 3 minutes.The ventilation is active when:

    - dehumidification is triggered,- a defrosting cycle is started,- pool hall air heating is triggered,- active for at least 5 minutes in one hour without any of thesetriggers.

    On VP, the compressor starts after a delay of 3 minutes.Connecteur module

    de prog.= programming

    module connector

    ECP 600 programming connector or implementation of a diagnosis moduleby the technical support department

    ECP 600 250Vac T=10A 6,3x32 fuse

  • 8/13/2019 Notice Technique SIROCCO GB

    17/28

    16

    2.2 Troubleshooting procedures

    Checks to make before any operation:- correct electrical supply (voltage and cable size)- all cables are correctly connected- Hygro Control operational- appliance has triggered dehumidification but not heating

    Check the fuse of theECP 600 and the

    electrical box (if present)?

    No LED lit up on ECP 600

    yesno

    Reconnect orchange the fuse

    At the level of the terminalboard: disconnect the wiresfrom the Hygro Control and

    make a shunt betweenterminals 1-5-7 and check thevoltage between 4-5 (12V~)?

    Replace the ECP 600

    no

    yes

    Replace the Hygro Control

    See faultstable2.1

    The appliance does not work.

    No fault displayed on theECP 600, green light on

    The compressor is workingbut not the ventilation

    No LED lit up on ECP 600

    Display of a fault on

    ECP 600

    The ventilation is workingbut not the compressor

    EN

    no

    Replace C1

    The compressor is working but not the ventilation

    Voltage between terminals 22-23 on ECP 600?

    yes

    Capacitor C1?no

    Connection between the

    ventilator and the ECP 600?

    Replace theECP 600

    yes

    yes

    Replace the ventilator motorRe-connect

    no

  • 8/13/2019 Notice Technique SIROCCO GB

    18/28

    17

    The ventilation is working but not the compressor

    yes Siroccothree-phase

    yesSirocco

    single-phase

    EN

    yes

    Redo the connectionsbetween the contactorand the compressor

    yes

    yes

    Is the compressor indicatoron the ECP 600 lit?

    Set the VI/VP switch

    on the ECP 600 toVI

    Voltage between 20-21on ECP 600? (230V~)

    ReplaceECP 600

    no

    no

    Is the appliance beingventilated all the time?

    Voltage on thecompressor terminals(230V~ or 400V~)?

    yes

    Replace thecontactor

    no

    no

    Re-connect the Hygro

    Control and check thatit is operational

    Wait for theend of the

    cycle

    Voltage between A1and A2 oncompressor

    contactor (230V~)?

    no

    yes

    Call a certified ZPCEstation to check the

    compressor

    no

    Is the appliance in a defrost cycle(indicator lit on ECP 600)?

    Re-connectterminals 20-21 and

    A1-A2

    Voltage on contactorpower terminals

    (230V~ or400V~)?

    no

    yes

    Is the contactorprimed?

    yes

    no

  • 8/13/2019 Notice Technique SIROCCO GB

    19/28

    18

    3. Maintenance

    3.1 Maintenance instruct ions

    3.1.1 Monthly checks

    check for clogging in the filter:

    - wash the filter with warm soapy water,- rinse it abundantly and dry it,- replace it if necessary.

    check visually that the condensation is drained.

    3.1.2 Annual checks

    check that the electric cable connections, contactors are correctly tightened,Loose cables may cause overheating of terminals,

    check that each command relay, power switch and electronic protection device is operational,

    check the adjustment and operation of the Hygro Control if necessary clean the dust inside it usinga jet of air,

    clean the whole unit with a slightly damp cloth,

    check the cleanliness of the condensation drainage tray and tube,

    to improve the operation of the appliance, it is possible to make a visual check of the fouling of thebatteries (evaporator / condenser and hot water) by removing the cover from the appliance(switched off). Depending on the condition, clean with a silk brush and a vacuum cleaner.

    3.2 Spare parts

    Naming Item number Representation

    Hygro Control sensor WCE03431

    Filter:Sirocco 55 can be inset

    WSD01911

    Sirocco 80 can be inset WSD01912

    Sirocco 110 can be inset

    Sirocco 55 ambient

    WSD01913

    Sirocco 80 ambient WSD01914

    Sirocco 110 ambient WSD01915

    Be aware of the following:On the three-phase Sirocco, via the phase controller (KA4), any modification of the orderof phases on the distribution network or on the existing electrical installation is detected.The appliance then goes into fault mode (alarm triggered led lit), see 2.1.

    The appliance must have a filter fitted when operating.

    Appl iance powered off and decommissioned!

    A general servicing of the appliance is strongly recommended to check the properoperation of the appliance, maintain its performance, to avoid certain faults and preservethe building in good condition.

    EN

  • 8/13/2019 Notice Technique SIROCCO GB

    20/28

    19

    3.3 Recycling the product

    Your appliance has reached the end of its working life. You would like to dispose of it or replace it.Please do not throw it into your dustbin or into your local selective sorting containers.

    When this symbol appears on a new appliance, it means that the equipment must notbe thrown away and that it wi ll be collected selectively so that it can be reused,

    recycled or recovered. Any substances it may contain which are potentially dangerousto the environment will be eliminated or neutralised.

    You can give it to a community association which will be able to repair it and put it back into circulation.If you buy a new appliance, you can take the old one back to the reseller or ask the transporter to take it

    back.This is known as a One-for-One exchange.

    Otherwise please take it to a waste collection centre, if your local council has set up a selectivecollection system for these products.

    3.4 EC compliance certificate

    Z.P.C.E. declares that the products or ranges below:

    SPECIAL POOL DEHUMIDIFIERSSirocco 55-80-110 ambient and can be inset

    are in compliance with the provisions of the:

    ELECTROMAGNETIC COMPATIBILITY di rective 89/336/EEC.

    LOW VOLTAGE directive 73/23/EEC, as amended by 93/068/EEC.

    The following harmonised standards have been applied:

    EN 60335.2.40

    In the context of ongoing improvement, our products are subject to change without not ice.Version 02/2010

    Give the applianceto a community

    association. Take the used device back

    to the reseller whenmaking a new purchase.

    Take the useddevice to a wastecollection centre.

  • 8/13/2019 Notice Technique SIROCCO GB

    21/28

    N

    o

    t

    e

    s

    -

    N

    o

    t

    e

    n

    -

    A

    a

    nt

    e

    k

    e

    n

    i

    n

    g

    -

    N

    o

    t

    a

    s

    -

    N

    o

    t

    a

  • 8/13/2019 Notice Technique SIROCCO GB

    22/28

    1

    Electric diagram

    Sirocco 55-80-110 single-phase

  • 8/13/2019 Notice Technique SIROCCO GB

    23/28

    2

    Sirocco 110 three-phase

    *

  • 8/13/2019 Notice Technique SIROCCO GB

    24/28

    3

    English

    U-N single phase main supply 230Vac-1N-50Hz

    U-V-W-N three phase main supply 400Vac-3N-50Hz

    PE Earth

    N black

    B blue

    M brown

    B1 command logic controller ECP 600

    SD1 air inlet sensor (black sheath)

    SD2 defrost sensor (grey sheath)

    5-7-2-4-1 connection of Hygro Control (sie 1.3.7.4)

    26-27 supply (230 V AC -50 Hz) for remote fault warning light or relaying

    3-6 control of heating for PSA type boiler or an existing heating system

    C-Csupply (230Vac-50Hz) for battery circulator or used for electric logic of the heating optionby electric backing

    E1 high pressure switch

    E2 low pressure switch

    OAE back up heating option

    R heating resistor

    THS high limit thermostat (automatic reset)THSM positive high limit thermostat (manual reset)

    M1 ventilator motor (230Vac/50Hz)

    M2 compressor motor (230Vac/50Hz)

    KM1 power contactor of back up heating resistor

    KM2 compressor power contactor

    KA4 starting relay or phase order relay on Sirocco three phase

    F2 Compressor internal thermal protection

    C1 ventilator capacitor

    C2 compressor capacitor

    C3 filtering capacitor

    C4 starting relay capacitor

  • 8/13/2019 Notice Technique SIROCCO GB

    25/28

    4

    Dimensions

    weight without option A B C

    Kg mm

    Sirocco 55 65 1030 620 653

    Sirocco 80 75 1220 810 843

    Sirocco 110 85 1410 1000 1033

    *

  • 8/13/2019 Notice Technique SIROCCO GB

    26/28

    N

    o

    t

    e

    s

    -

    N

    o

    t

    e

    n

    -

    A

    a

    nt

    e

    k

    e

    n

    i

    n

    g

    -

    N

    o

    t

    a

    s

    -

    N

    o

    t

    a

  • 8/13/2019 Notice Technique SIROCCO GB

    27/28

    N

    o

    t

    e

    s

    -

    N

    o

    t

    e

    n

    -

    A

    a

    nt

    e

    k

    e

    n

    i

    n

    g

    -

    N

    o

    t

    a

    s

    -

    N

    o

    t

    a

  • 8/13/2019 Notice Technique SIROCCO GB

    28/28

    Chauffage et dshumidif ication de pisc ines Heating and dehumidification of pools

    Zodiac Pool Care Europe Boulevard de la Romanerie BP 90023

    49180 Saint Barthlmy dAnjou cedex France

    www.zodiac-poolcare.com

    Votre installateur Your installer

    Plaque signaltique Product name plate