11785 SW Highway 212 – Suite 305 Clackamas, OR 97015-9050 (503) 650-0088 WWW.DIRIGOLAB.COM
Non-CBI
Northwest Mfg. 600 Polk Ave Red Lake Falls, MN 56750
Qualification Testing EPA Method 28WHH Project # 033-HHP-039-1 Wood Master Mini Indoor Pellet Boiler
Contact: Mr. Bruce Gagner, President Email: [email protected] (800) 932-3629
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 1 Non CBI
This page intentionally left blank.
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 2 Non CBI
Contents Affidavit: ......................................................................................................................... 4
Introduction: .................................................................................................................. 5
Technician Notes: ......................................................................................................... 5
Test Procedures and Equipment: ............................................................................. 7 Sample Boxes ....................................................................................................................................... 8 HEX, Flow Meters, Thermopile ............................................................................................................. 9 Airflow Diagram ................................................................................................................................... 10
Statement of Estimated Uncertainty: ..................................................................... 10
Results: Hang Tag , Weighting and Data Summary: ............................................... 11
Process Operations: ................................................................................................... 13
Run Data: .................................................................................................................. 13
Test Fuel Properties: ............................................................................................... 14
Test Condition Summary: ....................................................................................... 16
Appliance Views: ......................................................................................................... 16 Front .................................................................................................................................................... 16 Left & Rear .......................................................................................................................................... 17 Right Side ............................................................................................................................................ 17 Front with Hopper and Burner Assembly ............................................................................................ 18
Sampling Locations: ................................................................................................ 19 Traverse and Sampling Points ............................................................................................................ 19
Sampling Methods: .................................................................................................. 20
System Schematic: .................................................................................................. 20
Sampling and Analytical Procedures: .................................................................... 20
Analytical Methods Description: ............................................................................ 21
Quality Control and Assurance Procedures and Results: ................................... 21
Appendices: ................................................................................................................. 22
Appendix A: Sampling and Analytical Procedures ............................................... 22
Appendix B: Alternate Procedures ........................................................................ 22
Appendix C: Complete Drawings, Manual, and Run Information: ....................... 22
Appendix D: Supporting Data ................................................................................ 22
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 3 Non CBI
Appendix E: Calibration ......................................................................................... 23
Appendix F: Dirigo Laboratories Accreditations ................................................. 34
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 4 Non CBI
Affidavit:
All testing and associated procedures were conducted at Dirigo Laboratories beginning 12/29/2014 and ending on 1/29/2015. Dirigo Laboratories is located at 11785 SE Highway 212 – Suite 305, Clackamas, OR 97015-9050. All EPA protocols from Methods 1, 2, 3, 4, 5, 28 WHH and ASTM 2618-13 were followed in the testing, sampling, analysis, and calibrations for these tests and all results are based on these methods. Particulate sampling was performed per EPA Method 5G sampling option 3 and ASTM E2515-11 Standard Test Method for Determination of Particulate Matter Emissions Collected in a Dilution Tunnel. Efficiency was calculated using EPA Method 28WHH and checked using CAN/CSA-B415.1-10 Performance Testing of Solid-Fuel Burning Heating Appliances.
The following people were associated with the testing, analysis and report writing associated with this project.
John Steinert
Gary Nelke
Ben Nelke
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 5 Non CBI
Introduction: Northwest Mfg contracted with Dirigo Laboratories, Inc. to perform EPA qualification testing on the Wood Master Mini model, indoor pellet fired hydronic heater per EPA Method 28WHH voluntary wood fired hydronic heater program. Efficiency testing was also performed per CSA B-415.1-10 “Performance Testing of Solid-Fuel Burning Heating Appliances”. All test results apply solely to the Wood Master Mini Boiler. This test report shall not be reproduced except in full, without the written approval of Dirigo Laboratories, Inc.
Technician Notes:
Unit arrived at Dirigo Laboratories on December 8, 2014.
• Conditioning occurred on 12/29/2014-(over 10 hours at a medium draw). • Prior to start of testing the dilution tunnel was cleaned with a 12” Steel chimney
brush. • Run #1 occurred on December 30, 2014 – Category 4 • Run #2 occurred on December 30, 2014 – Category 3 • Run #3 occurred on December 31, 2014 – Category 2 –(thrown out) • Run #4 occurred on December 31, 2014 – Category 1 –(thrown out) • Run #5 occurred on Janurary 27, 2015 – Category 1 • Run #6 occurred on Janurary 28, 2015 – Category 1 • Run #7 occurred on January 28, 2015 – Category 2 • Run #8 occurred on January 29, 2015 - Category 2
Per Method 28WHH, client opted to perform 2 additional category 1 runs (runs 5 & 6) and average those results to achieve the emissions and efficiency as stated in this report. Per Method 28WHH, client opted to perform 2 additional category 2 runs (runs 7&8) and average those results to achieve the emissions and efficiency as stated in this report.
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 6 Non CBI
Wood Heater Identification: • Appliance Tested: Wood Master Mini Boiler • Serial Number: MB30-0001 • Manufacturer: Northwest Manufacturing • Address: 600 Polk Ave SW • Phone: (800) 932-3629 • Contact: Bruce Gagner • Email: [email protected] • Catalyst: No • Heat exchange blower: N/A • Type: Hydronic Heater • Style: Indoor • Fuel: Pellet • Date Received: Monday, December 08, 2014 • Wood Heater Aging: 12/29/2014 • Testing Period – Start: Monday, December 29, 2014 Finish: Thursday,
January 29, 2015 • Test Location: Dirigo Laboratories, Inc. -11785 SE Highway 212 - Suite 305,
Clackamas, OR 97015 • Elevation: 30 Feet above sea level • Test Technician(s): Ben Nelke Gary Nelke • Test Observer(s): N/A
The Woodmaster Mini Boiler is manufactured by Northwest Manufacturing, Inc. of Red Lake Falls, MN. The unit is an automatic feed, wood pellet indoor hydronic heater and was tested to EPA Method 28 WHH protocol. All testing was conducted by Dirigo Laboratories, Inc. at 11785 SE Highway 212 – Suite 305, Clackamas, OR 97015.
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 7 Non CBI
Test Procedures and Equipment:
All test procedures used followed EPA Methods 1, 2, 3, 4, 5, 5g option 3, 28 WHH, ASTM 2515-11 and CSA B-415.1-10.
Equipment List:
1. Flow Meter - Omega FTB-1421, 0.6 – 3.0 GPM – Load side. 2. Flow Meter - Omega FTB-1424, 3.0 – 30.0 GPM – Load side. 3. Flow Meter - Omega FTB-1425, 5.0-50.0 GPM – Boiler Side. 4. Flow Meter – Omega FTB-602B-T, 0.3 – 9 LPM- Load Side 5. Analyzer -California Analytical ZRE CO2/CO/O2 IR ANALYZER. 6. Delmhorst J-2000 Wood Moisture Meter. 7. Dayton 4c121 Blower for dilution tunnel -Emissions Booth #2. 8. ScienTech Balance Scale. 9. 10 lb Calibration Weight. 10. DigiWeigh Bench Shipping Scale. 11. APEX XC-60 Digital Emissions Sampling Box A. 12. APEX XC-60 Digital Emissions Sampling Box B. 13. Gast MOA-P122-AA Vacuum Pump -Analyzer. 14. Rice Lake 4'x7' floor scale w/digital weight indicator. 15. APEX AK 6000 Ambient Sampling Box. 16. Delta T- 20 junction Thermopile.
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 8 Non CBI
Sample Boxes
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 9 Non CBI
HEX, Flow Meters, Thermopile
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 10 Non CBI
CBI
Airflow Diagram
Statement of Estimated Uncertainty: The combined estimated uncertainty of measurement is ± 10% for emissions results1 and ± 4% for efficiency .
1ASTM E2515 – 11 Standard Test Method for Determination of Particulate Matter Emissions Collected by a Dilution Tunnel. Section X1.3.5
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 11 Non CBI
Results: Hang Tag , Weighting and Data Summary:
Data Summary Part Aθ Wfuel MCave Qin Qout
Wood Run Load% Actual Actual Test Weight Wood Heat Heat
Category No Capacity Load Load Duration as-fired Moisture Input Output% of
Btu/hr max hrs lb % DB Btu Btu≤ 15% of
I 5&6 max ≤ 15,300 12,585 12.34 4.00 10.5 3.87 86,936 50,34016-24%
II 7&8 of max 16,320 to 24,480 21,097 20.68 4.43 16.9 3.87 139,511 93,35425-50%
III 2 of max 25,500 to 51,000 40,964 40.16 4.00 28.0 3.87 231,828 163,856Max
IV 1 capacity 101,577 99.59 4.00 65.0 3.87 538,173 406,308
Target Load
Btu/hr
102,000
Data Summary Part B
T2 Min E E Eg/hr Eg/kg ηdel ηSLM
Min StackRun Load% Return PM Output PM Output PM PM Delivered Loss
Category No Capacity H2O Temp Based Based Rate Factor Efficiency Efficiencylbs/MMBtu
°F Output g/MJ g/hr g/kg % %≤ 15% of
I 5&6 max 144.07 0.1007 0.0433 0.59 0.50 58.07 69.9516-24%
II 7&8 of max 142.67 0.1220 0.0525 1.17 0.70 66.90 83.9025-50%
III 2 of max 138.71 0.1276 0.0549 2.37 0.78 70.68 82.50Max
IV 1 capacity 131.00 0.0758 0.0326 3.49 0.49 75.50 86.2013.98
9.49
5.18
Emissions
g
2.33
ET
Total PM
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 12 Non CBI
The Wood Master Mini Boiler meets the Phase 2 emission level of 0.32lbs/MMBtu heat output weighted average and the 18.0 g/hr cap limit using Table 2, EPA Method 28 WHH.
Hang Tag Information:
Manufacturer: Northwest Mfg
Model Number: Wood Master Mini
102,000 Btu/hr
8-Hour Output Rating: Qout-8hr 101,577 Btu/hr8-Hour Average
Efficiency: ηavg-8hr 76% (Using higher heating value)
81% (Using lower heating value)
Annual Efficiency Rating: ηavg 65% (Using higher heating value)
69% (Using lower heating value)
Particle Emissions: Eavg 1.36 Grams/hr (average)
0.11 Lbs/Million Btu Output
Manufacturer Maximum Rated Output
Year Round Use Weighting:
Weighting
Category Run No. Factor (Fi) ηdel,i x Fi ηdel-LHV,i x Fi Eg/MJ,i x Fi Eg/kg,i x Fi Elb/MMBtu,i x Fi Eg/hr,i x Fi
I 5&6 0.437 25.37659 27.32124 0.0189221 0.2192866 0.0440059 0.25783II 7&8 0.238 15.9222 17.14314 0.012495 0.167195 0.029036 0.27846III 2 0.275 19.437 20.92475 0.0150975 0.2145 0.03509 0.65175IV 1 0.050 3.775 4.064 0.00163 0.0245 0.00379 0.1745
Totals: 1.000 64.5 69.5 0.0481 0.63 0.11 1.36
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 13 Non CBI
Process Operations:
The appliance was operated according to procedures as described in the Operations Manual. Manufacturer settings were used in the operation of the pellet boiler to achieve the required burn rates. No adjustments were made.
All exterior draft measurements around the unit for all runs were less than 1 ft3 per minute.
Run Data: All corresponding run data can be found in their respective folders supplied with this report.
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 14 Non CBI
Test Fuel Properties: All fuel consisted of premium grade hard wood pellets manufactured by Indeck Energy, Inc. Fuel moisture content was 3.87% Dry Basis. Fuel analysis was performed by Twin Ports Testing of Superior, WI. See below.
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 15 Non CBI
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 16 Non CBI
Test Condition Summary:
Testing conditions for runs 1,2,3,4,5,6,7,& 8 fell within allowable specifications of Method 28WHH. Details of all run conditions can be found in corresponding run folders.
Appliance Views:
Front
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 17 Non CBI
Left & Rear
Right Side
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 18 Non CBI
Front with Hopper and Burner Assembly
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 19 Non CBI
Sampling Locations: Sample ports are located 16.5 feet downstream from any disturbances and 4 feet upstream from any disturbances. Flow rate traverse data was collected 12 feet downstream from any disturbances and 5.5 feet upstream from any disturbances.
Traverse and Sampling Points
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 20 Non CBI
Sampling Methods: A dual filter dry sampling train system (ASTM 2515-11 / 5G sample option 3) was used in collecting particulate samples. The dilution tunnel is 12 inches in diameter. All particulate sampling conditions per ASTM 2515-11 and method 5G option 3 were followed.
System Schematic:
Sampling and Analytical Procedures: All sampling and analytical procedures used followed EPA Methods 1, 2, 3, 4, 5, 5g and 28WHH, ASTM E2618-13, ASTM E2515-11, and CSA B-415.1-10.
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 21 Non CBI
Analytical Methods Description: All sample recovery and analysis procedures followed EPA Method 5g3 procedures. At the end of each test run, filters were removed from their housings, dessicated for 24 hours, and then weighed to a constant weight per Method 5 section 11.0.
Quality Control and Assurance Procedures and Results:
Calibration procedures and results were conducted per ASTM 2515-11, EPA Method 1 through 5, 5g and Method 28WHH. Calibration certificates and results can be found in Appendix E.
Test method quality control procedures (leak checks, volume meter checks, stratification checks, proportionality results) followed the procedures outlined in Method 5.
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 22 Non CBI
Appendices:
Appendix A: Sampling and Analytical Procedures All sampling and analytical procedures were performed by Gary Nelke, Ben Nelke. All procedures used were directly from ASTM 2515-11, EPA Methods 1, 2, 3, 4, 5, 5g and 28WHH. Stack loss efficiency testing was performed to CSA B-415.1-10.
Appendix B: Alternate Procedures
No alternate procedures were used.
Appendix C: Complete Drawings, Manual, and Run Information:
All drawings, manuals and run information have been submitted in separate digital folders .
Appendix D: Supporting Data
Supporting data has been submitted in separate digital folders with the report.
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 23 Non CBI
Appendix E: Calibration
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 24 Non CBI
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 25 Non CBI
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 26 Non CBI
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 27 Non CBI
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 28 Non CBI
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 29 Non CBI
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 30 Non CBI
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 31 Non CBI
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 32 Non CBI
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 33 Non CBI
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 34 Non CBI
Appendix F: Dirigo Laboratories Accreditations
Dirigo Laboratories is accredited by the U.S. Environmental Protection Agency for the certification of wood heaters pursuant to subpart AAA of 40 CFR Part 60, New Source Performance Standards For Residential Wood Heaters- Methods 28, 28A, 28WHH, 5G, 5H. Certificate Numbers 9 and 9M (mobile).
Dirigo Laboratories is accredited by the American Association Of Laboratory Accreditation to the following ISO Standards:
• ISO 17020: 2012 Criteria for Bodies for Perfoming Inspections • ISO 17025: 2005 Requirements for Testing Laboratories: Mechanical Testing • ISO 17065: 2012 Requirements for Bodies Operating Inspection Bodies.
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 35 Non CBI
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 36 Non CBI
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 37 Non CBI
Northwest Mfg. Wood Master Mini Boiler EPA Qualification Testing Project # 033-HHP-039-1
Prepared by Dirigo Laboratories, Inc.
Page | 38 Non CBI