nfrc u-factor, shgc, vt, & condensation resistance...
TRANSCRIPT
NFRC U-FACTOR, SHGC, VT, &
CONDENSATION RESISTANCE
COMPUTER SIMULATION REPORT
Rendered to:
VALUE WINDOWS & DOORS
SERIES/MODEL:
Eurotek 70 Inswing/Outswing Door
Report Number:
Report Date:
H5300.01-301-45
09/20/17
2524 E. Jensen AvenueFresno, CA 93706
p. 559.233.8705f. 717.764.4129
www.archtest.com www.intertek.com/building
NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE
COMPUTER SIMULATION REPORT
Rendered to:
VALUE WINDOWS & DOORS
1830 Flower Avenue
Duarte, California 91010
Report Number:
Simulation Date:
Report Date:
Project Summary:
Standards:
Software:
Simulations Specimen Description:
Series/Model: Eurotek 70 Inswing/Outswing Door
Type: Swinging Door, Single Leaf Entrance Door
Frame Material: VA Head/Jambs: Vinyl w/All Members Reinforced
AV Sill: Aluminum/Vinyl Composite
Sash Material: VA Vinyl w/ All Members Reinforced
Standard Size: 960mm x 2090mm
Frame and Edge Modeling: THERM 7.4.4
Center-of-Glass Modeling: WINDOW 7.4.14
Total Product Calculations: WINDOW 7.4.14
*NFRC's Condensation Resistance rating is NOT equivalent to a Condensation Resistance
Factor (CRF) determined in accordance with AAMA 1503.
ANSI/NFRC 100-2017: Procedure for Determining Fenestration Product U-Factors
ANSI/NFRC 200-2017: Procedure for Determining Fenestration Product Solar Heat
Gain Coefficient and Visible Transmittance at Normal Incidence
NFRC 500-2017: Procedure for Determining Fenestration Product Condensation
Resistance Values
H5300.01-301-45
09/20/17
09/20/17
Architectural Testing, Inc., an Intertek Company (Intertek-ATI) was contracted to perform U-
Factor, Solar Heat Gain Coefficient, Visible Transmittance, and Condensation Resistance*
computer simulations in accordance with the National Fenestration Rating Council (NFRC).
The products were evaluated in full compliance with NFRC requirements to the standards listed
Spectral Data Library: IGDB 55.0
2524 E. Jensen AvenueFresno, CA 93706
p. 559.233.8705f. 717.764.4129
www.archtest.com www.intertek.com/building
H5300.01-301-45
Page 2 of 18
Modeling Assumptions/Technical Interpretations:
1) To prevent air infiltration, tape was applied to all interior sash crack locations.
2) Glazing beads vary based on overall insulated glass sizes per ANSI/NFRC 100-2017,
Section 4.2.1.D.
3) 0.188" x 0.625" and 0.188" x 0.750" grids do not need modeling per ANSI/NFRC
100-2017, Section 4.2.4.1.D.ii.a.
4) 0.250" x 0.625" and 0.313" x 1.000" grids do not need modeling in some options per
ANSI/NFRC 100-2017, Section 4.2.4.1.D.ii.a.
5) Inswing and Outswing doors are individual products within a product line per
ANSI/NFRC 100-2017, Section 5.2.2.F. and 4.2.1.I.iv.
Specialty Products Table:
SHGC = SHGC0 + SHGCc (SHGC1 - SHGC0)
VT = VT0 + VTc (VT1 - VT0)
Validation Matrix:
Outswing
No Dividers Dividers < 1 Dividers > 1
SHGC0 0.007275 0.010110 0.012732
SHGC1 0.608614 0.525075 0.447833
VT0 0.000000 0.000000 0.000000
VT1 0.601340 0.514964 0.435101
VT0 0.000000 0.000000 0.000000
VT1 0.604422 0.517843 0.437774
SHGC0 0.006910 0.009753 0.012381
SHGC1 0.611333 0.527595 0.450155
The specialty products method allow the manufacturer to determine the overall product SHGC
and VT for any glazing option. The center of glass SHGC and/or VT must be determined using
WINDOW 7.4.14. The method gives overall product SHGC and VT indexed on center of glass
properties. All values used in the calculations are truncated to six decimal place precision.
No Dividers Dividers < 1 Dividers > 1
Inswing
The following products are part of a validation matrix. Only one is required for validation
testing.
Product Line Report Number
None -
2524 E. Jensen AvenueFresno, CA 93706
p. 559.233.8705f. 717.764.4129
www.archtest.com www.intertek.com/building
H5300.01-301-45
Page 3 of 18
Spacer Option Description
Grid Option Description
Reinforcement Option Description
Gas Filling Technique Description
Edge-of-Glass Construction
Weatherstripping
Frame/Sash Materials Finish
Window ID Description
Grid Size Grid Type Grid Pattern
0.188" x 0.625" Aluminum Rectangular Grid (Painted) NFRC Standard
Spacer Type Primary Secondary Code
Quanex Super Spacer Standard Butyl Rubber OF-S
Sealant
Head and jambs Galvanized
Steel
Fill Type Method
90% Argon Single Prober Timed
0.313" x 1.000" Aluminum Contour Grid (Painted) NFRC Standard
Location Material
All members of the panel Galvanized
Steel
0.188" x 0.750" Aluminum Rectangular Grid (Painted) NFRC Standard
0.250" x 0.625" Aluminum Contour Grid (Painted) NFRC Standard
EPDM compression bulb gasket 1 row Bottom rail
Flexible vinyl sweep 1 row Bottom rail
EPDM compression bulb gasket 1 row Head and jambs
EPDM compression gasket 1 row All members of the panel
Interior Condition EPDM gasket between glass and glazing bead
Exterior Condition EPDM gasket between glass and glazing stop
Type Quantity Location
EPDM gasket 1 row Sill and bottom rail of outswing profile
Interior Vinyl/Aluminum - Anodized
Exterior Vinyl/Aluminum - Anodized
Window Description Report ID Numbers
Inswing #1-16
Outswing #17-32
2524 E. Jensen AvenueFresno, CA 93706
p. 559.233.8705f. 717.764.4129
www.archtest.com www.intertek.com/building
H5300.01-301-45
Page 4 of 18
NFRC 100/200/500 Summary Sheet
Eurotek 70 Inswing/Outswing Door
ID
Pa
ne
Th
ick
nes
s 1
Ga
p W
idth
1
Pa
ne
Th
ick
nes
s 2
Ga
p W
idth
2
Pa
ne
Th
ick
nes
s 3
Ga
p W
idth
3
Pa
ne
Th
ick
nes
s 4
AIR CL OF-S N,G
Condensation
Resistance
1 Inswing: Clr / Air / Clr - 25.7mm (6mm-6mm)
0.224 0.563 0.224
Ga
p F
ill
Lo
w-e
(S
urf
ace
#)
Tin
t
Sp
ace
r
Gri
d T
yp
e
U-FactorSolar Heat Gain Coefficient (SHGC)
Grids (None / <1 / >=1)
Visible Transmittance (VT)
Grids (None / <1 / >=1)
ARG90 0.022(#2) CL OF-S N,G
CR 46
2 Inswing: E366 / Arg / Clr - 25.7mm (6mm-6mm)
0.225 0.563 0.224
U-Factor 0.40 SHGC (N / <1 / >1) 0.44 / 0.38 / 0.33 VT (N / <1 / >1) 0.48 / 0.41 / 0.35
AIR CL OF-S N,G
CR 61
3 Inswing: Clr / Air / Clr - 31.6mm (3mm-3mm)
0.118 1.000 0.118
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.27
AIR CL OF-S N,G
CR 46
Inswing: Clr / Air / Clr - 33.2mm (4mm-4mm)
0.154 1.000 0.154
U-Factor 0.40 SHGC (N / <1 / >1) 0.48 / 0.41 / 0.35 VT (N / <1 / >1) 0.50 / 0.43 / 0.36
AIR CL OF-S N,G
CR 46
Inswing: Clr / Air / Clr - 25.2mm (3mm-3mm)
0.118 0.750 0.118
U-Factor 0.40 SHGC (N / <1 / >1) 0.46 / 0.40 / 0.34 VT (N / <1 / >1) 0.49 / 0.42 / 0.36
AIR CL OF-S N,G
CR 46
Inswing: Clr / Air / Clr - 26.8mm (4mm-4mm)
0.154 0.750 0.154
U-Factor 0.40 SHGC (N / <1 / >1) 0.48 / 0.41 / 0.35 VT (N / <1 / >1) 0.50 / 0.43 / 0.36
AIR CL OF-S N,G
CR 46
Inswing: Clr / Air / Clr - 20.5mm (3mm-3mm)
0.118 0.563 0.118
U-Factor 0.40 SHGC (N / <1 / >1) 0.46 / 0.40 / 0.34 VT (N / <1 / >1) 0.49 / 0.42 / 0.36
AIR CL OF-S N,G
CR 46
Inswing: Clr / Air / Clr - 22.1mm (4mm-4mm)
0.154 0.563 0.154
U-Factor 0.40 SHGC (N / <1 / >1) 0.48 / 0.41 / 0.35 VT (N / <1 / >1) 0.50 / 0.43 / 0.36
ARG90 0.022(#2) CL OF-S N,G
CR 46
4 Inswing: E366 / Arg / Clr - 31.6mm (3mm-3mm)
0.117 1.000 0.118
U-Factor 0.40 SHGC (N / <1 / >1) 0.46 / 0.40 / 0.34 VT (N / <1 / >1) 0.49 / 0.42 / 0.36
ARG90 0.022(#2) CL OF-S N,G
CR 62
Inswing: E366 / Arg / Clr - 33.2mm (4mm-4mm)
0.153 1.000 0.154
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.39 / 0.34 / 0.28
CR 62U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.39 / 0.33 / 0.28
2524 E. Jensen AvenueFresno, CA 93706
p. 559.233.8705f. 717.764.4129
www.archtest.com www.intertek.com/building
H5300.01-301-45
Page 5 of 18
Gri
d T
yp
e
U-FactorSolar Heat Gain Coefficient (SHGC) Visible Transmittance (VT) Condensation
Grids (None / <1 / >=1) Grids (None / <1 / >=1) Resistance
Ga
p W
idth
3
Pa
ne
Th
ick
nes
s 4
Ga
p F
ill
Lo
w-e
(S
urf
ace
#)
Tin
t
Sp
ace
r
NFRC 100/200/500 Summary Sheet
Eurotek 70 Inswing/Outswing Door
ID
Pa
ne
Th
ick
nes
s 1
Ga
p W
idth
1
Pa
ne
Th
ick
nes
s 2
Ga
p W
idth
2
Pa
ne
Th
ick
nes
s 3
0.022(#2) CL OF-S N,G
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.28
Inswing: E366 / Arg / Clr-PVB-Clr - 35.26mm (3mm-Lami)
0.117 1.000 0.362 ARG90
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.27
ARG90 0.022(#2) CL OF-S N,G
CR 62
CR 62
Inswing: E366 / Arg / Clr-PVB-Clr - 36.06mm (4mm-Lami)
0.153 1.000 0.362
CR 62
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.39 / 0.34 / 0.28
ARG90 0.022(#2) CL OF-S N,G
CR 62
Inswing: E366 / Arg / Clr - 25.2mm (3mm-3mm)
0.117 0.750 0.118
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.39 / 0.33 / 0.28
ARG90 0.022(#2) CL OF-S N,G
Inswing: E366 / Arg / Clr - 26.8mm (4mm-4mm)
0.153 0.750 0.154
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.28
ARG90 0.022(#2) CL OF-S N,G
Inswing: E366 / Arg / Clr-PVB-Clr - 28.86mm (3mm-Lami)
0.117 0.750 0.362
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.27
ARG90 0.022(#2) CL OF-S N,G
CR 62
Inswing: E366 / Arg / Clr-PVB-Clr - 29.66mm (4mm-Lami)
0.153 0.750 0.362
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.39 / 0.34 / 0.28
ARG90 0.022(#2) CL OF-S N,G
CR 62
Inswing: E366 / Arg / Clr - 20.5mm (3mm-3mm)
0.117 0.563 0.118
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.39 / 0.33 / 0.28
ARG90 0.022(#2) CL OF-S N,G
CR 62
Inswing: E366 / Arg / Clr - 22.1mm (4mm-4mm)
0.153 0.563 0.154
U-Factor 0.40 SHGC (N / <1 / >1) 0.46 / 0.39 / 0.34 VT (N / <1 / >1) 0.49 / 0.42 / 0.35
AIR CL OF-S N,G
CR 62
5 Inswing: Clr / Air / Clr - 34.8mm (5mm-5mm)
0.185 1.000 0.185
U-Factor 0.40 SHGC (N / <1 / >1) 0.44 / 0.38 / 0.33 VT (N / <1 / >1) 0.48 / 0.41 / 0.35
AIR CL OF-S N,G
Inswing: Clr / Air / Clr - 36.8mm (6mm-6mm)
CR 47
0.224 1.000 0.224
CR 47
2524 E. Jensen AvenueFresno, CA 93706
p. 559.233.8705f. 717.764.4129
www.archtest.com www.intertek.com/building
H5300.01-301-45
Page 6 of 18
NFRC 100/200/500 Summary Sheet
Eurotek 70 Inswing/Outswing Door
ID
Pa
ne
Th
ick
nes
s 1
Ga
p W
idth
1
Pa
ne
Th
ick
nes
s 2
Ga
p W
idth
2
Pa
ne
Th
ick
nes
s 3
AIR
Gri
d T
yp
e
U-FactorSolar Heat Gain Coefficient (SHGC) Visible Transmittance (VT) Condensation
Grids (None / <1 / >=1) Grids (None / <1 / >=1) Resistance
Ga
p W
idth
3
Pa
ne
Th
ick
nes
s 4
Ga
p F
ill
Lo
w-e
(S
urf
ace
#)
Tin
t
Sp
ace
r
AIR CL OF-S N,G
CR 47
Inswing: Clr / Air / Clr - 30.4mm (6mm-6mm)
0.224 0.750 0.224
CL OF-S N,G
U-Factor 0.40 SHGC (N / <1 / >1) 0.46 / 0.39 / 0.34 VT (N / <1 / >1) 0.49 / 0.42 / 0.35
Inswing: Clr / Air / Clr - 28.4mm (5mm-5mm)
0.185 0.750 0.185
AIR CL OF-S N,G
CR 47
Inswing: Clr / Air / Clr - 23.7mm (5mm-5mm)
0.185 0.563 0.185
U-Factor 0.40 SHGC (N / <1 / >1) 0.44 / 0.38 / 0.33 VT (N / <1 / >1) 0.48 / 0.41 / 0.35
ARG90 0.022(#2) CL OF-S N,G
CR 47
6 Inswing: E366 / Arg / Clr - 34.8mm (5mm-5mm)
0.187 1.000 0.185
U-Factor 0.40 SHGC (N / <1 / >1) 0.46 / 0.39 / 0.34 VT (N / <1 / >1) 0.49 / 0.42 / 0.35
ARG90 0.022(#2) CL OF-S N,G
CR 62
Inswing: E366 / Arg / Clr - 36.8mm (6mm-6mm)
0.225 1.000 0.224
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.28
ARG90 0.022(#2) CL OF-S N,G
CR 62
Inswing: E366 / Arg / Clr-PVB-Clr - 36.86mm (5mm-Lami)
0.187 1.000 0.362
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.27
ARG90 0.022(#2) CL OF-S N,G
CR 62
Inswing: E366 / Arg / Clr-PVB-Clr - 37.86mm (6mm-Lami)
0.225 1.000 0.362
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27
ARG90 0.022(#2) CL OF-S N,G
CR 62
Inswing: E366 / Arg / Clr - 28.4mm (5mm-5mm)
0.187 0.750 0.185
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27
ARG90 0.022(#2) CL OF-S N,G
CR 62
Inswing: E366 / Arg / Clr - 30.4mm (6mm-6mm)
0.225 0.750 0.224
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.28
ARG90 0.022(#2) CL OF-S N,G
CR 62
Inswing: E366 / Arg / Clr-PVB-Clr - 30.46mm (5mm-Lami)
0.187 0.750 0.362
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.27
CR 62U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27
2524 E. Jensen AvenueFresno, CA 93706
p. 559.233.8705f. 717.764.4129
www.archtest.com www.intertek.com/building
H5300.01-301-45
Page 7 of 18
Gri
d T
yp
e
U-FactorSolar Heat Gain Coefficient (SHGC) Visible Transmittance (VT) Condensation
Grids (None / <1 / >=1) Grids (None / <1 / >=1) Resistance
Ga
p W
idth
3
Pa
ne
Th
ick
nes
s 4
Ga
p F
ill
Lo
w-e
(S
urf
ace
#)
Tin
t
Sp
ace
r
NFRC 100/200/500 Summary Sheet
Eurotek 70 Inswing/Outswing Door
ID
Pa
ne
Th
ick
nes
s 1
Ga
p W
idth
1
Pa
ne
Th
ick
nes
s 2
Ga
p W
idth
2
Pa
ne
Th
ick
nes
s 3
0.022(#2) CL OF-S N,G
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27
Inswing: E366 / Arg / Clr-PVB-Clr - 31.46mm (6mm-Lami)
0.225 0.750 0.362 ARG90
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.28
ARG90 0.022(#2) CL OF-S N,G
CR 49
CR 62
Inswing: E366 / Arg / Clr - 23.7mm (5mm-5mm)
0.187 0.563 0.185
CR 62
U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27
ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G
CR 49
7 Inswing: E366 / Arg / i89 - 34.8mm (5mm-5mm)
0.187 1.000 0.187
U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.37 / 0.32 / 0.27
ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G
Inswing: E366 / Arg / i89 - 36.8mm (6mm-6mm)
0.225 1.000 0.223
U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27
ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G
Inswing: E366 / Arg / i89 - 28.4mm (5mm-5mm)
0.187 0.750 0.187
U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.37 / 0.32 / 0.27
ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G
CR 49
Inswing: E366 / Arg / i89 - 30.4mm (6mm-6mm)
0.225 0.750 0.223
U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27
ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G
CR 49
Inswing: E366 / Arg / i89 - 23.7mm (5mm-5mm)
0.187 0.563 0.187
U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.37 / 0.32 / 0.27
ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G
CR 49
Inswing: E366 / Arg / i89 - 25.7mm (6mm-6mm)
0.225 0.563 0.223
U-Factor 0.22 SHGC (N / <1 / >1) 0.16 / 0.14 / 0.12 VT (N / <1 / >1) 0.36 / 0.31 / 0.26
ARG90 0.022(#2) CL OF-S N,G
CR 49
8 Inswing: E366 / Arg / Clr / Arg / Clr - 37.9mm (3mm-3mm-3mm)
0.117 0.563 0.118 0.563 0.118
U-Factor 0.22 SHGC (N / <1 / >1) 0.16 / 0.14 / 0.12 VT (N / <1 / >1) 0.35 / 0.30 / 0.26
ARG90 0.022(#2) CL OF-S N,G
Inswing: E366 / Arg / Clr / Arg / Clr - 40.3mm (4mm-4mm-4mm)
CR 72
0.153 0.563 0.154 0.563 0.154
CR 72
2524 E. Jensen AvenueFresno, CA 93706
p. 559.233.8705f. 717.764.4129
www.archtest.com www.intertek.com/building
H5300.01-301-45
Page 8 of 18
NFRC 100/200/500 Summary Sheet
Eurotek 70 Inswing/Outswing Door
ID
Pa
ne
Th
ick
nes
s 1
Ga
p W
idth
1
Pa
ne
Th
ick
nes
s 2
Ga
p W
idth
2
Pa
ne
Th
ick
nes
s 3
0.118 ARG90
Gri
d T
yp
e
U-FactorSolar Heat Gain Coefficient (SHGC) Visible Transmittance (VT) Condensation
Grids (None / <1 / >=1) Grids (None / <1 / >=1) Resistance
Ga
p W
idth
3
Pa
ne
Th
ick
nes
s 4
Ga
p F
ill
Lo
w-e
(S
urf
ace
#)
Tin
t
Sp
ace
r
ARG90 0.022(#2) / 0.022(#5) CL OF-S N,G
CR 72
Inswing: E366 / Arg / Clr) / Arg / E366(5) - 37.9mm (3mm-3mm-3mm)
0.117 0.563 0.118 0.563 0.117
0.022(#2) / 0.022(#4) CL OF-S N,G
U-Factor 0.18 SHGC (N / <1 / >1) 0.13 / 0.12 / 0.10 VT (N / <1 / >1) 0.28 / 0.24 / 0.20
9 Inswing: E366 / Arg / E366(4) / Arg / Clr - 37.9mm (3mm-3mm-3mm)
0.117 0.563 0.117 0.563
ARG90 0.022(#2) / 0.022(#4) CL OF-S N,G
CR 72
Inswing: E366 / Arg / E366(4) / Arg / Clr - 40.3mm (4mm-4mm-4mm)
0.153 0.563 0.153 0.563 0.154
U-Factor 0.18 SHGC (N / <1 / >1) 0.15 / 0.13 / 0.12 VT (N / <1 / >1) 0.28 / 0.24 / 0.20
ARG90 0.022(#2) / 0.022(#5) CL OF-S N,G
CR 72
Inswing: E366 / Arg / Clr) / Arg / E366(5) - 40.3mm (4mm-4mm-4mm)
0.153 0.563 0.154 0.563 0.153
U-Factor 0.18 SHGC (N / <1 / >1) 0.13 / 0.12 / 0.10 VT (N / <1 / >1) 0.28 / 0.24 / 0.20
ARG90 0.022(#2) / 0.022(#5) CL OF-S N
CR 72
10 Inswing: E366 / Arg / Clr-PVB-Clr / Arg / E366(5) - 38.96mm (3mm-Lami-3mm)
0.117 0.472 0.362 0.472 0.117
U-Factor 0.18 SHGC (N / <1 / >1) 0.15 / 0.13 / 0.12 VT (N / <1 / >1) 0.28 / 0.24 / 0.20
ARG90 0.022(#2) / 0.022(#4) CL OF-S N
CR 72
Inswing: E366 / Arg / E366(4) / Arg / Clr-PVB-Clr - 38.96mm (3mm-3mm-Lami)
0.117 0.472 0.117 0.472 0.362
U-Factor 0.19 SHGC (N) 0.15 VT (N) 0.27
ARG90 0.022(#2) / 0.022(#5) CL OF-S N
CR 72
Inswing: E366 / Arg / Clr-PVB-Clr / Arg / E366(5) - 40.56mm (4mm-Lami-4mm)
0.153 0.472 0.362 0.472 0.153
U-Factor 0.19 SHGC (N) 0.13 VT (N) 0.27
ARG90 0.022(#2) / 0.022(#4) CL OF-S N
CR 72
Inswing: E366 / Arg / E366(4) / Arg / Clr-PVB-Clr - 40.56mm (4mm-4mm-Lami)
0.153 0.472 0.153 0.472 0.362
U-Factor 0.19 SHGC (N) 0.15 VT (N) 0.27
ARG90 0.022(#2) / 0.022(#5) CL OF-S G
CR 72
11 Inswing: E366 / Arg / Clr-PVB-Clr / Arg / E366(5) - 38.96mm (3mm-Lami-3mm)
0.117 0.472 0.362 0.472 0.117
U-Factor 0.19 SHGC (N) 0.13 VT (N) 0.27
ARG90 0.022(#2) / 0.022(#4) CL OF-S G
CR 72
Inswing: E366 / Arg / E366(4) / Arg / Clr-PVB-Clr - 38.96mm (3mm-3mm-Lami)
0.117 0.472 0.117 0.472 0.362
U-Factor 0.19 SHGC (<1) 0.13 VT (<1) 0.23
CR 72U-Factor 0.19 SHGC (<1) 0.12 VT (<1) 0.23
2524 E. Jensen AvenueFresno, CA 93706
p. 559.233.8705f. 717.764.4129
www.archtest.com www.intertek.com/building
H5300.01-301-45
Page 9 of 18
Gri
d T
yp
e
U-FactorSolar Heat Gain Coefficient (SHGC) Visible Transmittance (VT) Condensation
Grids (None / <1 / >=1) Grids (None / <1 / >=1) Resistance
Ga
p W
idth
3
Pa
ne
Th
ick
nes
s 4
Ga
p F
ill
Lo
w-e
(S
urf
ace
#)
Tin
t
Sp
ace
r
NFRC 100/200/500 Summary Sheet
Eurotek 70 Inswing/Outswing Door
ID
Pa
ne
Th
ick
nes
s 1
Ga
p W
idth
1
Pa
ne
Th
ick
nes
s 2
Ga
p W
idth
2
Pa
ne
Th
ick
nes
s 3
0.022(#2) / 0.022(#5) CL OF-S G
U-Factor 0.19 SHGC (<1) 0.13 VT (<1) 0.23
Inswing: E366 / Arg / Clr-PVB-Clr / Arg / E366(5) - 40.56mm (4mm-Lami-4mm)
0.153 0.472 0.362 0.472 0.153 ARG90
U-Factor 0.19 SHGC (<1) 0.12 VT (<1) 0.23
ARG90 0.022(#2) / 0.022(#4) CL OF-S G
CR 72
CR 72
Inswing: E366 / Arg / E366(4) / Arg / Clr-PVB-Clr - 40.56mm (4mm-4mm-Lami)
0.153 0.472 0.153 0.472 0.362
CR 72
U-Factor 0.19 SHGC (>1) 0.11 VT (>1) 0.20
ARG90 0.022(#2) / 0.022(#5) CL OF-S G
CR 72
12 Inswing: E366 / Arg / Clr-PVB-Clr / Arg / E366(5) - 38.96mm (3mm-Lami-3mm)
0.117 0.472 0.362 0.472 0.117
U-Factor 0.19 SHGC (>1) 0.10 VT (>1) 0.20
ARG90 0.022(#2) / 0.022(#4) CL OF-S G
Inswing: E366 / Arg / E366(4) / Arg / Clr-PVB-Clr - 38.96mm (3mm-3mm-Lami)
0.117 0.472 0.117 0.472 0.362
U-Factor 0.19 SHGC (>1) 0.11 VT (>1) 0.20
ARG90 0.022(#2) / 0.022(#5) CL OF-S G
Inswing: E366 / Arg / Clr-PVB-Clr / Arg / E366(5) - 40.56mm (4mm-Lami-4mm)
0.153 0.472 0.362 0.472 0.153
U-Factor 0.19 SHGC (>1) 0.10 VT (>1) 0.20
ARG90 0.022(#2) / 0.022(#4) CL OF-S G
CR 72
Inswing: E366 / Arg / E366(4) / Arg / Clr-PVB-Clr - 40.56mm (4mm-4mm-Lami)
0.153 0.472 0.153 0.472 0.362
U-Factor 0.23 SHGC (N) 0.16 VT (N) 0.34
ARG90 0.022(#2) CL OF-S N
CR 72
13 Inswing: E366 / Arg / Clr-PVB-Clr / Arg / Clr-PVB-Clr - 40.62mm (3mm-Lami-Lami)
0.117 0.394 0.362 0.394 0.362
U-Factor 0.23 SHGC (<1) 0.14 VT (<1) 0.29
ARG90 0.022(#2) CL OF-S G
CR 71
14 Inswing: E366 / Arg / Clr-PVB-Clr / Arg / Clr-PVB-Clr - 40.62mm (3mm-Lami-Lami)
0.117 0.394 0.362 0.394 0.362
U-Factor 0.24 SHGC (>1) 0.12 VT (>1) 0.25
ARG90 0.022(#2) CL OF-S G
CR 70
15 Inswing: E366 / Arg / Clr-PVB-Clr / Arg / Clr-PVB-Clr - 40.62mm (3mm-Lami-Lami)
0.117 0.394 0.362 0.394 0.362
U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.28
ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G
16 Inswing: E366 / Arg / i89 - 31.6mm (3mm-3mm)
CR 70
0.117 1.000 0.117
CR 49
2524 E. Jensen AvenueFresno, CA 93706
p. 559.233.8705f. 717.764.4129
www.archtest.com www.intertek.com/building
H5300.01-301-45
Page 10 of 18
NFRC 100/200/500 Summary Sheet
Eurotek 70 Inswing/Outswing Door
ID
Pa
ne
Th
ick
nes
s 1
Ga
p W
idth
1
Pa
ne
Th
ick
nes
s 2
Ga
p W
idth
2
Pa
ne
Th
ick
nes
s 3
ARG90
Gri
d T
yp
e
U-FactorSolar Heat Gain Coefficient (SHGC) Visible Transmittance (VT) Condensation
Grids (None / <1 / >=1) Grids (None / <1 / >=1) Resistance
Ga
p W
idth
3
Pa
ne
Th
ick
nes
s 4
Ga
p F
ill
Lo
w-e
(S
urf
ace
#)
Tin
t
Sp
ace
r
ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G
CR 49
Inswing: E366 / Arg / i89 - 25.2mm (3mm-3mm)
0.117 0.750 0.117
0.022(#2) / 0.149(#4) CL OF-S N,G
U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.27
Inswing: E366 / Arg / i89 - 33.2mm (4mm-4mm)
0.153 1.000 0.160
ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G
CR 49
Inswing: E366 / Arg / i89 - 26.8mm (4mm-4mm)
0.153 0.750 0.160
U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.28
ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G
CR 49
Inswing: E366 / Arg / i89 - 20.5mm (3mm-3mm)
0.117 0.563 0.117
U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.27
ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G
CR 49
Inswing: E366 / Arg / i89 - 22.1mm (4mm-4mm)
0.153 0.563 0.160
U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.28
AIR CL OF-S N,G
CR 49
17 Outswing: Clr / Air / Clr - 25.7mm (6mm-6mm)
0.224 0.563 0.224
U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.27
ARG90 0.022(#2) CL OF-S N,G
CR 46
18 Outswing: E366 / Arg / Clr - 25.7mm (6mm-6mm)
0.225 0.563 0.224
U-Factor 0.40 SHGC (N / <1 / >1) 0.44 / 0.38 / 0.33 VT (N / <1 / >1) 0.48 / 0.41 / 0.35
AIR CL OF-S N,G
CR 61
19 Outswing: Clr / Air / Clr - 31.6mm (3mm-3mm)
0.118 1.000 0.118
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27
AIR CL OF-S N,G
CR 46
Outswing: Clr / Air / Clr - 33.2mm (4mm-4mm)
0.154 1.000 0.154
U-Factor 0.41 SHGC (N / <1 / >1) 0.48 / 0.41 / 0.35 VT (N / <1 / >1) 0.50 / 0.42 / 0.36
AIR CL OF-S N,G
CR 46
Outswing: Clr / Air / Clr - 25.2mm (3mm-3mm)
0.118 0.750 0.118
U-Factor 0.41 SHGC (N / <1 / >1) 0.46 / 0.40 / 0.34 VT (N / <1 / >1) 0.49 / 0.42 / 0.36
CR 46U-Factor 0.41 SHGC (N / <1 / >1) 0.48 / 0.41 / 0.35 VT (N / <1 / >1) 0.50 / 0.42 / 0.36
2524 E. Jensen AvenueFresno, CA 93706
p. 559.233.8705f. 717.764.4129
www.archtest.com www.intertek.com/building
H5300.01-301-45
Page 11 of 18
Gri
d T
yp
e
U-FactorSolar Heat Gain Coefficient (SHGC) Visible Transmittance (VT) Condensation
Grids (None / <1 / >=1) Grids (None / <1 / >=1) Resistance
Ga
p W
idth
3
Pa
ne
Th
ick
nes
s 4
Ga
p F
ill
Lo
w-e
(S
urf
ace
#)
Tin
t
Sp
ace
r
NFRC 100/200/500 Summary Sheet
Eurotek 70 Inswing/Outswing Door
ID
Pa
ne
Th
ick
nes
s 1
Ga
p W
idth
1
Pa
ne
Th
ick
nes
s 2
Ga
p W
idth
2
Pa
ne
Th
ick
nes
s 3
CL OF-S N,G
U-Factor 0.41 SHGC (N / <1 / >1) 0.46 / 0.40 / 0.34 VT (N / <1 / >1) 0.49 / 0.42 / 0.36
Outswing: Clr / Air / Clr - 26.8mm (4mm-4mm)
0.154 0.750 0.154 AIR
U-Factor 0.41 SHGC (N / <1 / >1) 0.48 / 0.41 / 0.35 VT (N / <1 / >1) 0.50 / 0.42 / 0.36
AIR CL OF-S N,G
CR 46
CR 46
Outswing: Clr / Air / Clr - 20.5mm (3mm-3mm)
0.118 0.563 0.118
CR 46
U-Factor 0.41 SHGC (N / <1 / >1) 0.46 / 0.40 / 0.34 VT (N / <1 / >1) 0.49 / 0.42 / 0.36
AIR CL OF-S N,G
CR 62
Outswing: Clr / Air / Clr - 22.1mm (4mm-4mm)
0.154 0.563 0.154
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.39 / 0.33 / 0.28
ARG90 0.022(#2) CL OF-S N,G
20 Outswing: E366 / Arg / Clr - 31.6mm (3mm-3mm)
0.117 1.000 0.118
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.39 / 0.33 / 0.28
ARG90 0.022(#2) CL OF-S N,G
Outswing: E366 / Arg / Clr - 33.2mm (4mm-4mm)
0.153 1.000 0.154
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27
ARG90 0.022(#2) CL OF-S N,G
CR 62
Outswing: E366 / Arg / Clr-PVB-Clr - 35.26mm (3mm-Lami)
0.117 1.000 0.362
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27
ARG90 0.022(#2) CL OF-S N,G
CR 62
Outswing: E366 / Arg / Clr-PVB-Clr - 36.06mm (4mm-Lami)
0.153 1.000 0.362
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.39 / 0.33 / 0.28
ARG90 0.022(#2) CL OF-S N,G
CR 62
Outswing: E366 / Arg / Clr - 25.2mm (3mm-3mm)
0.117 0.750 0.118
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.39 / 0.33 / 0.28
ARG90 0.022(#2) CL OF-S N,G
CR 62
Outswing: E366 / Arg / Clr - 26.8mm (4mm-4mm)
0.153 0.750 0.154
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27
ARG90 0.022(#2) CL OF-S N,G
Outswing: E366 / Arg / Clr-PVB-Clr - 28.86mm (3mm-Lami)
CR 62
0.117 0.750 0.362
CR 62
2524 E. Jensen AvenueFresno, CA 93706
p. 559.233.8705f. 717.764.4129
www.archtest.com www.intertek.com/building
H5300.01-301-45
Page 12 of 18
NFRC 100/200/500 Summary Sheet
Eurotek 70 Inswing/Outswing Door
ID
Pa
ne
Th
ick
nes
s 1
Ga
p W
idth
1
Pa
ne
Th
ick
nes
s 2
Ga
p W
idth
2
Pa
ne
Th
ick
nes
s 3
ARG90
Gri
d T
yp
e
U-FactorSolar Heat Gain Coefficient (SHGC) Visible Transmittance (VT) Condensation
Grids (None / <1 / >=1) Grids (None / <1 / >=1) Resistance
Ga
p W
idth
3
Pa
ne
Th
ick
nes
s 4
Ga
p F
ill
Lo
w-e
(S
urf
ace
#)
Tin
t
Sp
ace
r
ARG90 0.022(#2) CL OF-S N,G
CR 62
Outswing: E366 / Arg / Clr - 20.5mm (3mm-3mm)
0.117 0.563 0.118
0.022(#2) CL OF-S N,G
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27
Outswing: E366 / Arg / Clr-PVB-Clr - 29.66mm (4mm-Lami)
0.153 0.750 0.362
ARG90 0.022(#2) CL OF-S N,G
CR 62
Outswing: E366 / Arg / Clr - 22.1mm (4mm-4mm)
0.153 0.563 0.154
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.39 / 0.33 / 0.28
AIR CL OF-S N,G
CR 62
21 Outswing: Clr / Air / Clr - 34.8mm (5mm-5mm)
0.185 1.000 0.185
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.39 / 0.33 / 0.28
AIR CL OF-S N,G
CR 46
Outswing: Clr / Air / Clr - 36.8mm (6mm-6mm)
0.224 1.000 0.224
U-Factor 0.40 SHGC (N / <1 / >1) 0.45 / 0.39 / 0.34 VT (N / <1 / >1) 0.49 / 0.42 / 0.35
AIR CL OF-S N,G
CR 46
Outswing: Clr / Air / Clr - 28.4mm (5mm-5mm)
0.185 0.750 0.185
U-Factor 0.40 SHGC (N / <1 / >1) 0.44 / 0.38 / 0.33 VT (N / <1 / >1) 0.48 / 0.41 / 0.35
AIR CL OF-S N,G
CR 46
Outswing: Clr / Air / Clr - 30.4mm (6mm-6mm)
0.224 0.750 0.224
U-Factor 0.40 SHGC (N / <1 / >1) 0.45 / 0.39 / 0.34 VT (N / <1 / >1) 0.49 / 0.42 / 0.35
AIR CL OF-S N,G
CR 46
Outswing: Clr / Air / Clr - 23.7mm (5mm-5mm)
0.185 0.563 0.185
U-Factor 0.40 SHGC (N / <1 / >1) 0.44 / 0.38 / 0.33 VT (N / <1 / >1) 0.48 / 0.41 / 0.35
ARG90 0.022(#2) CL OF-S N,G
CR 46
22 Outswing: E366 / Arg / Clr - 34.8mm (5mm-5mm)
0.187 1.000 0.185
U-Factor 0.40 SHGC (N / <1 / >1) 0.45 / 0.39 / 0.34 VT (N / <1 / >1) 0.49 / 0.42 / 0.35
ARG90 0.022(#2) CL OF-S N,G
CR 62
Outswing: E366 / Arg / Clr - 36.8mm (6mm-6mm)
0.225 1.000 0.224
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.28
CR 62U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27
2524 E. Jensen AvenueFresno, CA 93706
p. 559.233.8705f. 717.764.4129
www.archtest.com www.intertek.com/building
H5300.01-301-45
Page 13 of 18
Gri
d T
yp
e
U-FactorSolar Heat Gain Coefficient (SHGC) Visible Transmittance (VT) Condensation
Grids (None / <1 / >=1) Grids (None / <1 / >=1) Resistance
Ga
p W
idth
3
Pa
ne
Th
ick
nes
s 4
Ga
p F
ill
Lo
w-e
(S
urf
ace
#)
Tin
t
Sp
ace
r
NFRC 100/200/500 Summary Sheet
Eurotek 70 Inswing/Outswing Door
ID
Pa
ne
Th
ick
nes
s 1
Ga
p W
idth
1
Pa
ne
Th
ick
nes
s 2
Ga
p W
idth
2
Pa
ne
Th
ick
nes
s 3
0.022(#2) CL OF-S N,G
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27
Outswing: E366 / Arg / Clr-PVB-Clr - 36.86mm (5mm-Lami)
0.187 1.000 0.362 ARG90
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.37 / 0.32 / 0.27
ARG90 0.022(#2) CL OF-S N,G
CR 62
CR 62
Outswing: E366 / Arg / Clr-PVB-Clr - 37.86mm (6mm-Lami)
0.225 1.000 0.362
CR 62
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.28
ARG90 0.022(#2) CL OF-S N,G
CR 62
Outswing: E366 / Arg / Clr - 28.4mm (5mm-5mm)
0.187 0.750 0.185
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27
ARG90 0.022(#2) CL OF-S N,G
Outswing: E366 / Arg / Clr - 30.4mm (6mm-6mm)
0.225 0.750 0.224
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27
ARG90 0.022(#2) CL OF-S N,G
Outswing: E366 / Arg / Clr-PVB-Clr - 30.46mm (5mm-Lami)
0.187 0.750 0.362
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.37 / 0.32 / 0.27
ARG90 0.022(#2) CL OF-S N,G
CR 62
Outswing: E366 / Arg / Clr-PVB-Clr - 31.46mm (6mm-Lami)
0.225 0.750 0.362
U-Factor 0.27 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.28
ARG90 0.022(#2) CL OF-S N,G
CR 62
Outswing: E366 / Arg / Clr - 23.7mm (5mm-5mm)
0.187 0.563 0.185
U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.37 / 0.32 / 0.27
ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G
CR 62
23 Outswing: E366 / Arg / i89 - 34.8mm (5mm-5mm)
0.187 1.000 0.187
U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.37 / 0.32 / 0.27
ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G
CR 49
Outswing: E366 / Arg / i89 - 36.8mm (6mm-6mm)
0.225 1.000 0.223
U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.37 / 0.32 / 0.27
ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G
Outswing: E366 / Arg / i89 - 28.4mm (5mm-5mm)
CR 49
0.187 0.750 0.187
CR 49
2524 E. Jensen AvenueFresno, CA 93706
p. 559.233.8705f. 717.764.4129
www.archtest.com www.intertek.com/building
H5300.01-301-45
Page 14 of 18
NFRC 100/200/500 Summary Sheet
Eurotek 70 Inswing/Outswing Door
ID
Pa
ne
Th
ick
nes
s 1
Ga
p W
idth
1
Pa
ne
Th
ick
nes
s 2
Ga
p W
idth
2
Pa
ne
Th
ick
nes
s 3
ARG90
Gri
d T
yp
e
U-FactorSolar Heat Gain Coefficient (SHGC) Visible Transmittance (VT) Condensation
Grids (None / <1 / >=1) Grids (None / <1 / >=1) Resistance
Ga
p W
idth
3
Pa
ne
Th
ick
nes
s 4
Ga
p F
ill
Lo
w-e
(S
urf
ace
#)
Tin
t
Sp
ace
r
ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G
CR 49
Outswing: E366 / Arg / i89 - 23.7mm (5mm-5mm)
0.187 0.563 0.187
0.022(#2) / 0.149(#4) CL OF-S N,G
U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.37 / 0.32 / 0.27
Outswing: E366 / Arg / i89 - 30.4mm (6mm-6mm)
0.225 0.750 0.223
ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G
CR 49
Outswing: E366 / Arg / i89 - 25.7mm (6mm-6mm)
0.225 0.563 0.223
U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.37 / 0.32 / 0.27
ARG90 0.022(#2) CL OF-S N,G
CR 49
24 Outswing: E366 / Arg / Clr / Arg / Clr - 37.9mm (3mm-3mm-3mm)
0.117 0.563 0.118 0.563 0.118
U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.37 / 0.32 / 0.27
ARG90 0.022(#2) CL OF-S N,G
CR 71
Outswing: E366 / Arg / Clr / Arg / Clr - 40.3mm (4mm-4mm-4mm)
0.153 0.563 0.154 0.563 0.154
U-Factor 0.23 SHGC (N / <1 / >1) 0.16 / 0.14 / 0.12 VT (N / <1 / >1) 0.36 / 0.30 / 0.26
ARG90 0.022(#2) / 0.022(#4) CL OF-S N,G
CR 71
25 Outswing: E366 / Arg / E366(4) / Arg / Clr - 37.9mm (3mm-3mm-3mm)
0.117 0.563 0.117 0.563 0.118
U-Factor 0.23 SHGC (N / <1 / >1) 0.16 / 0.14 / 0.12 VT (N / <1 / >1) 0.35 / 0.30 / 0.25
ARG90 0.022(#2) / 0.022(#5) CL OF-S N,G
CR 72
Outswing: E366 / Arg / Clr) / Arg / E366(5) - 37.9mm (3mm-3mm-3mm)
0.117 0.563 0.118 0.563 0.117
U-Factor 0.19 SHGC (N / <1 / >1) 0.13 / 0.12 / 0.10 VT (N / <1 / >1) 0.28 / 0.24 / 0.20
ARG90 0.022(#2) / 0.022(#4) CL OF-S N,G
CR 72
Outswing: E366 / Arg / E366(4) / Arg / Clr - 40.3mm (4mm-4mm-4mm)
0.153 0.563 0.153 0.563 0.154
U-Factor 0.19 SHGC (N / <1 / >1) 0.15 / 0.13 / 0.12 VT (N / <1 / >1) 0.28 / 0.24 / 0.20
ARG90 0.022(#2) / 0.022(#5) CL OF-S N,G
CR 72
Outswing: E366 / Arg / Clr) / Arg / E366(5) - 40.3mm (4mm-4mm-4mm)
0.153 0.563 0.154 0.563 0.153
U-Factor 0.19 SHGC (N / <1 / >1) 0.13 / 0.12 / 0.10 VT (N / <1 / >1) 0.28 / 0.24 / 0.20
ARG90 0.022(#2) / 0.022(#5) CL OF-S N
CR 72
26 Outswing: E366 / Arg / Clr-PVB-Clr / Arg / E366(5) - 38.96mm (3mm-Lami-3mm)
0.117 0.472 0.362 0.472 0.117
U-Factor 0.19 SHGC (N / <1 / >1) 0.15 / 0.13 / 0.11 VT (N / <1 / >1) 0.28 / 0.24 / 0.20
CR 71U-Factor 0.19 SHGC (N) 0.15 VT (N) 0.27
2524 E. Jensen AvenueFresno, CA 93706
p. 559.233.8705f. 717.764.4129
www.archtest.com www.intertek.com/building
H5300.01-301-45
Page 15 of 18
Gri
d T
yp
e
U-FactorSolar Heat Gain Coefficient (SHGC) Visible Transmittance (VT) Condensation
Grids (None / <1 / >=1) Grids (None / <1 / >=1) Resistance
Ga
p W
idth
3
Pa
ne
Th
ick
nes
s 4
Ga
p F
ill
Lo
w-e
(S
urf
ace
#)
Tin
t
Sp
ace
r
NFRC 100/200/500 Summary Sheet
Eurotek 70 Inswing/Outswing Door
ID
Pa
ne
Th
ick
nes
s 1
Ga
p W
idth
1
Pa
ne
Th
ick
nes
s 2
Ga
p W
idth
2
Pa
ne
Th
ick
nes
s 3
0.022(#2) / 0.022(#4) CL OF-S N
U-Factor 0.19 SHGC (N) 0.13 VT (N) 0.27
Outswing: E366 / Arg / E366(4) / Arg / Clr-PVB-Clr - 38.96mm (3mm-3mm-Lami)
0.117 0.472 0.117 0.472 0.362 ARG90
U-Factor 0.19 SHGC (N) 0.15 VT (N) 0.27
ARG90 0.022(#2) / 0.022(#5) CL OF-S N
CR 71
CR 71
Outswing: E366 / Arg / Clr-PVB-Clr / Arg / E366(5) - 40.56mm (4mm-Lami-4mm)
0.153 0.472 0.362 0.472 0.153
CR 71
U-Factor 0.19 SHGC (N) 0.13 VT (N) 0.27
ARG90 0.022(#2) / 0.022(#4) CL OF-S N
CR 71
Outswing: E366 / Arg / E366(4) / Arg / Clr-PVB-Clr - 40.56mm (4mm-4mm-Lami)
0.153 0.472 0.153 0.472 0.362
U-Factor 0.19 SHGC (<1) 0.13 VT (<1) 0.23
ARG90 0.022(#2) / 0.022(#5) CL OF-S G
27 Outswing: E366 / Arg / Clr-PVB-Clr / Arg / E366(5) - 38.96mm (3mm-Lami-3mm)
0.117 0.472 0.362 0.472 0.117
U-Factor 0.19 SHGC (<1) 0.12 VT (<1) 0.23
ARG90 0.022(#2) / 0.022(#4) CL OF-S G
Outswing: E366 / Arg / E366(4) / Arg / Clr-PVB-Clr - 38.96mm (3mm-3mm-Lami)
0.117 0.472 0.117 0.472 0.362
U-Factor 0.19 SHGC (<1) 0.13 VT (<1) 0.23
ARG90 0.022(#2) / 0.022(#5) CL OF-S G
CR 71
Outswing: E366 / Arg / Clr-PVB-Clr / Arg / E366(5) - 40.56mm (4mm-Lami-4mm)
0.153 0.472 0.362 0.472 0.153
U-Factor 0.19 SHGC (<1) 0.12 VT (<1) 0.23
ARG90 0.022(#2) / 0.022(#4) CL OF-S G
CR 71
Outswing: E366 / Arg / E366(4) / Arg / Clr-PVB-Clr - 40.56mm (4mm-4mm-Lami)
0.153 0.472 0.153 0.472 0.362
U-Factor 0.19 SHGC (>1) 0.11 VT (>1) 0.20
ARG90 0.022(#2) / 0.022(#5) CL OF-S G
CR 71
28 Outswing: E366 / Arg / Clr-PVB-Clr / Arg / E366(5) - 38.96mm (3mm-Lami-3mm)
0.117 0.472 0.362 0.472 0.117
U-Factor 0.19 SHGC (>1) 0.10 VT (>1) 0.20
ARG90 0.022(#2) / 0.022(#4) CL OF-S G
CR 71
Outswing: E366 / Arg / E366(4) / Arg / Clr-PVB-Clr - 38.96mm (3mm-3mm-Lami)
0.117 0.472 0.117 0.472 0.362
U-Factor 0.19 SHGC (>1) 0.11 VT (>1) 0.20
ARG90 0.022(#2) / 0.022(#5) CL OF-S G
Outswing: E366 / Arg / Clr-PVB-Clr / Arg / E366(5) - 40.56mm (4mm-Lami-4mm)
CR 71
0.153 0.472 0.362 0.472 0.153
CR 71
2524 E. Jensen AvenueFresno, CA 93706
p. 559.233.8705f. 717.764.4129
www.archtest.com www.intertek.com/building
H5300.01-301-45
Page 16 of 18
NFRC 100/200/500 Summary Sheet
Eurotek 70 Inswing/Outswing Door
ID
Pa
ne
Th
ick
nes
s 1
Ga
p W
idth
1
Pa
ne
Th
ick
nes
s 2
Ga
p W
idth
2
Pa
ne
Th
ick
nes
s 3
0.362 ARG90
Gri
d T
yp
e
U-FactorSolar Heat Gain Coefficient (SHGC) Visible Transmittance (VT) Condensation
Grids (None / <1 / >=1) Grids (None / <1 / >=1) Resistance
Ga
p W
idth
3
Pa
ne
Th
ick
nes
s 4
Ga
p F
ill
Lo
w-e
(S
urf
ace
#)
Tin
t
Sp
ace
r
ARG90 0.022(#2) CL OF-S N
CR 71
29 Outswing: E366 / Arg / Clr-PVB-Clr / Arg / Clr-PVB-Clr - 40.62mm (3mm-Lami-Lami)
0.117 0.394 0.362 0.394 0.362
0.022(#2) / 0.022(#4) CL OF-S G
U-Factor 0.19 SHGC (>1) 0.10 VT (>1) 0.20
Outswing: E366 / Arg / E366(4) / Arg / Clr-PVB-Clr - 40.56mm (4mm-4mm-Lami)
0.153 0.472 0.153 0.472
ARG90 0.022(#2) CL OF-S G
CR 70
30 Outswing: E366 / Arg / Clr-PVB-Clr / Arg / Clr-PVB-Clr - 40.62mm (3mm-Lami-Lami)
0.117 0.394 0.362 0.394 0.362
U-Factor 0.23 SHGC (N) 0.16 VT (N) 0.34
ARG90 0.022(#2) CL OF-S G
CR 70
31 Outswing: E366 / Arg / Clr-PVB-Clr / Arg / Clr-PVB-Clr - 40.62mm (3mm-Lami-Lami)
0.117 0.394 0.362 0.394 0.362
U-Factor 0.23 SHGC (<1) 0.14 VT (<1) 0.29
ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G
CR 70
32 Outswing: E366 / Arg / i89 - 31.6mm (3mm-3mm)
0.117 1.000 0.117
U-Factor 0.24 SHGC (>1) 0.12 VT (>1) 0.24
ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G
CR 49
Outswing: E366 / Arg / i89 - 33.2mm (4mm-4mm)
0.153 1.000 0.160
U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.28
ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G
CR 49
Outswing: E366 / Arg / i89 - 25.2mm (3mm-3mm)
0.117 0.750 0.117
U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27
ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G
CR 49
Outswing: E366 / Arg / i89 - 26.8mm (4mm-4mm)
0.153 0.750 0.160
U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.28
ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G
CR 49
Outswing: E366 / Arg / i89 - 20.5mm (3mm-3mm)
0.117 0.563 0.117
U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27
ARG90 0.022(#2) / 0.149(#4) CL OF-S N,G
CR 49
Outswing: E366 / Arg / i89 - 22.1mm (4mm-4mm)
0.153 0.563 0.160
U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.33 / 0.28
CR 49U-Factor 0.24 SHGC (N / <1 / >1) 0.17 / 0.15 / 0.13 VT (N / <1 / >1) 0.38 / 0.32 / 0.27
2524 E. Jensen AvenueFresno, CA 93706
p. 559.233.8705f. 717.764.4129
www.archtest.com www.intertek.com/building
H5300.01-301-45
Page 17 of 18
SIMULATED BY: REVIEWED BY:
Elizabeth A. Moser Kenny C. White
Simulation Technician Laboratory Manager
Simulator-In-Responsible-Charge
EAM:eam
H5300.01-301-45
Attachments (pages): This report is complete only when all attachments listed are included.
Results obtained are simulated values and were secured by using the designated test methods.
This report does not constitute certification of this product nor an opinion or endorsement by
this laboratory. It is the exclusive property of the client so named herein and relates only to the
product simulated. This report may not be reproduced, except in full, without the written
approval of Intertek-ATI
For INTERTEK-ATI:
Appendix A: Drawings and Bills of Material (23)
The Condensation Resistance results obtained from this procedure are for controlled laboratory
conditions and do not include the effects of air movement through the specimen, solar radiation,
and the thermal bridging that may occur due to the specific design and construction of the
fenestration system opening.
Ratings values included in this report are for submittals to an NFRC-licensed IA and are not
meant to be used directly for labeling purposes. Only those values identified on a valid
Certification Authorization Report (CAR) by an NFRC accredited Inspection Agency (IA) are
to be used for labeling purposes. The ratings values were rounded in accordance to NFRC 601,
NFRC Unit and Measurement Policy.
Intertek-ATI is an NFRC accredited simulation laboratory and all simulations were conducted
in full compliance with NFRC approved procedures and specifications. The values included in
this report are not considered in compliance with ANSI/NFRC 100, ANSI/NFRC 200, and/or
NFRC 500 unless the associated validation test requirements have been satisfied, as applicable.
Intertek-ATI will service this report for the entire test record retention period. Test records that
are retained such as detailed drawings, datasheets, representative samples of test specimens, or
other pertinent project documentation will be retained by Intertek-ATI for the entire test record
retention period. The test record retention end date for this report is September 20, 2022.
2524 E. Jensen AvenueFresno, CA 93706
p. 559.233.8705f. 717.764.4129
www.archtest.com www.intertek.com/building
H5300.01-301-45
Page 18 of 18
Revision Log
Rev. # Date Page(s) Revision(s)
This report produced from controlled document template ATI 00037, Revised 10/2/2012.
.01R0 09/20/17 All Original Report Issue. Work Requested by
Mr. Shawn Wan of Value Windows &
Doors.
2524 E. Jensen AvenueFresno, CA 93706
p. 559.233.8705f. 717.764.4129
www.archtest.com www.intertek.com/building
All drawings and Bills of Material used to simulate this product are enclosed in this Appendix