NFPA 54 National Fuel Gas
Code
BoilerManufacture
r
ANSI Standards
LocalCodes
Vent Manufacture
r
![Page 3: NFPA 54 National Fuel Gas Code Boiler Manufacturer ANSI Standards Local Codes Vent Manufacturer](https://reader035.vdocuments.site/reader035/viewer/2022081503/56649e175503460f94b01f7e/html5/thumbnails/3.jpg)
Understanding ANSI StandardsUnderstanding ANSI StandardsUnderstanding ANSI StandardsUnderstanding ANSI Standards
Negative Positive
Non-condensing
Condensing
VENTINGVENTING
II
IIII
IVStatic Pressure in Vent
Above Dew Point
Below Dew Point
![Page 4: NFPA 54 National Fuel Gas Code Boiler Manufacturer ANSI Standards Local Codes Vent Manufacturer](https://reader035.vdocuments.site/reader035/viewer/2022081503/56649e175503460f94b01f7e/html5/thumbnails/4.jpg)
Understanding ANSI StandardsUnderstanding ANSI StandardsUnderstanding ANSI StandardsUnderstanding ANSI Standards
Negative Positive
Non-condensing
Condensing
VENTINGVENTING
II
IIII
IV
NFGC Airtight
AirtightCorrosion Resistant
Corrosion Resistant
![Page 5: NFPA 54 National Fuel Gas Code Boiler Manufacturer ANSI Standards Local Codes Vent Manufacturer](https://reader035.vdocuments.site/reader035/viewer/2022081503/56649e175503460f94b01f7e/html5/thumbnails/5.jpg)
Make sure the
equipment and venting
system match.
![Page 6: NFPA 54 National Fuel Gas Code Boiler Manufacturer ANSI Standards Local Codes Vent Manufacturer](https://reader035.vdocuments.site/reader035/viewer/2022081503/56649e175503460f94b01f7e/html5/thumbnails/6.jpg)
Determine the type of equipment installed (Category I, II, III, or IV).
![Page 7: NFPA 54 National Fuel Gas Code Boiler Manufacturer ANSI Standards Local Codes Vent Manufacturer](https://reader035.vdocuments.site/reader035/viewer/2022081503/56649e175503460f94b01f7e/html5/thumbnails/7.jpg)
Vent category specifies whether the vent system operates under a negative pressure or a positive pressure, and if the products of combustion condense into a liquid in the flue.
(ANSI) Vent System Categories
(ANSI) Vent System Categories
![Page 8: NFPA 54 National Fuel Gas Code Boiler Manufacturer ANSI Standards Local Codes Vent Manufacturer](https://reader035.vdocuments.site/reader035/viewer/2022081503/56649e175503460f94b01f7e/html5/thumbnails/8.jpg)
IV
III
II
I
Appliance Designation
•AtmosphericDraft Diverter
•Fan Assisted
Negative Positive
Non-Condensing
Condensing
•Forced Draft
•Fan Assisted•Fan Assisted
•Fan Assisted
![Page 9: NFPA 54 National Fuel Gas Code Boiler Manufacturer ANSI Standards Local Codes Vent Manufacturer](https://reader035.vdocuments.site/reader035/viewer/2022081503/56649e175503460f94b01f7e/html5/thumbnails/9.jpg)
Check that the proper venting material is used (B-vent, pressure stack, AL29-4C etc.).
![Page 10: NFPA 54 National Fuel Gas Code Boiler Manufacturer ANSI Standards Local Codes Vent Manufacturer](https://reader035.vdocuments.site/reader035/viewer/2022081503/56649e175503460f94b01f7e/html5/thumbnails/10.jpg)
IV
III
II
I
•Forced DraftUL103 P-Stack
Welded Steel
•AtmosphericB-Vent
Masonry
•Fan AssistedB-Vent
Masonry (interior)
Acceptable Vent Material
AL29-4C double wall
•Fan Assisted
(86 – 90 % efficiency)
•Condensing
(90+ efficiency)
AL29-4C single wall
CPVC (tested with appliance)
(85 – 90 % efficiency)
AL29-4C double wall
•Direct VentAL29-4C double wall
![Page 11: NFPA 54 National Fuel Gas Code Boiler Manufacturer ANSI Standards Local Codes Vent Manufacturer](https://reader035.vdocuments.site/reader035/viewer/2022081503/56649e175503460f94b01f7e/html5/thumbnails/11.jpg)
Check appliance draft requirements. Codes require that the draft must meet the
manufacturers specifications.
![Page 12: NFPA 54 National Fuel Gas Code Boiler Manufacturer ANSI Standards Local Codes Vent Manufacturer](https://reader035.vdocuments.site/reader035/viewer/2022081503/56649e175503460f94b01f7e/html5/thumbnails/12.jpg)
-0.05” -0.06” -0.08”
-0.02” -0.03” -0.03”
0.00” -0.01” -0.01”
-0.14” -0.17” -0.20”
20’
6’10’
50’
1,000 MBH
Fan Assist Cat. I (10” B-Vent) 95°F 60°F 25°F
Chimney Pressures - Steady StateChimney Pressures - Steady State
![Page 13: NFPA 54 National Fuel Gas Code Boiler Manufacturer ANSI Standards Local Codes Vent Manufacturer](https://reader035.vdocuments.site/reader035/viewer/2022081503/56649e175503460f94b01f7e/html5/thumbnails/13.jpg)
Vertical Venting with a Metal Chimney System and Inside Air
Futera II
Category I
![Page 14: NFPA 54 National Fuel Gas Code Boiler Manufacturer ANSI Standards Local Codes Vent Manufacturer](https://reader035.vdocuments.site/reader035/viewer/2022081503/56649e175503460f94b01f7e/html5/thumbnails/14.jpg)
Futera III
Category II
![Page 15: NFPA 54 National Fuel Gas Code Boiler Manufacturer ANSI Standards Local Codes Vent Manufacturer](https://reader035.vdocuments.site/reader035/viewer/2022081503/56649e175503460f94b01f7e/html5/thumbnails/15.jpg)
Modulating Boiler SystemModulating Boiler SystemModulating Boiler SystemModulating Boiler System
-0.13
-0.12
-0.11
-0.1
-0.09
-0.08
-0.07
-0.06
-0.05
-0.04
-0.03
-0.02
-0.01
0
0.01
0.02
Ap
plian
ce
Ou
tlet
Pre
ssu
re (
in.
W.C
.)
Blr
1 s
tart
s
Blr
2 s
tart
s
Blr
3 s
tart
s
Blr
4 s
tart
s
Blr
2 s
top
s
Blr
3 s
top
s
Blr
4 s
top
s
Vent = 30’ vert./10’ horiz., 18” diam.
4 Fan-assisted Cat I boilers with 1,000 MBH input each
Constant ambient of 60°F
Draft variations in a modulating boiler system
![Page 16: NFPA 54 National Fuel Gas Code Boiler Manufacturer ANSI Standards Local Codes Vent Manufacturer](https://reader035.vdocuments.site/reader035/viewer/2022081503/56649e175503460f94b01f7e/html5/thumbnails/16.jpg)
Barometric DampersBarometric Dampers
• Draft Hoods and Barometric Dampers will maintain
the boiler’s operating efficiency, but now excess air
will be needed to be pulled into the equipment room.
– Consider automatic dampers, or a– Modulating exhaust system, or– Modulating dampers
![Page 17: NFPA 54 National Fuel Gas Code Boiler Manufacturer ANSI Standards Local Codes Vent Manufacturer](https://reader035.vdocuments.site/reader035/viewer/2022081503/56649e175503460f94b01f7e/html5/thumbnails/17.jpg)
Horizontal Vent using Inside Air
Futera II
Category I
![Page 18: NFPA 54 National Fuel Gas Code Boiler Manufacturer ANSI Standards Local Codes Vent Manufacturer](https://reader035.vdocuments.site/reader035/viewer/2022081503/56649e175503460f94b01f7e/html5/thumbnails/18.jpg)
Side Wall Venting using Inside Air
Futera II
Category III
![Page 19: NFPA 54 National Fuel Gas Code Boiler Manufacturer ANSI Standards Local Codes Vent Manufacturer](https://reader035.vdocuments.site/reader035/viewer/2022081503/56649e175503460f94b01f7e/html5/thumbnails/19.jpg)
Z223.1-51-2002 (Venting of Equipment)10.3.4.6 Mechanical Draft Systems.
The exit terminals of mechanical draft systems shall be not less than 7ft above grade where located adjacent to public walkways.
PublicWalkway
Not less
than 7’
Side wall ventingSide wall venting
![Page 20: NFPA 54 National Fuel Gas Code Boiler Manufacturer ANSI Standards Local Codes Vent Manufacturer](https://reader035.vdocuments.site/reader035/viewer/2022081503/56649e175503460f94b01f7e/html5/thumbnails/20.jpg)
Z223.1-56 (Venting of Equipment)7.8 Venting System Location.
(a) A Venting system shall terminate at least 3 ft (0.9 m) above any forced air inlet located within 10 ft (3.1 m).
Exception No. 1: This provision shall not apply to the combustion air intake of a direct-vent appliance.
Exception No. 2: This provision shall not apply to the separation of circulating air inlet and flue gas discharge of listed outdoor appliances.
Forced AirInlet
If Lessthan 10’
3’ Min.
Side wall ventingSide wall venting
Alexander Conca
![Page 21: NFPA 54 National Fuel Gas Code Boiler Manufacturer ANSI Standards Local Codes Vent Manufacturer](https://reader035.vdocuments.site/reader035/viewer/2022081503/56649e175503460f94b01f7e/html5/thumbnails/21.jpg)
Z223.1-56 (Venting of Equipment)7.8 Venting System Location.
(b) The venting system of other than a direct-vent appliance shall terminate at least 4 ft (1.2 m) below, 4 ft (1.2 m) horizontally from, or 1 ft (30 cm) above any door, window, or gravity air inlet into any building. The bottom of the vent terminal shall be located at least 12 in. (30 cm) above grade.
Gravity Air Inlet
Gravity Air Inlet
GravityAirInlet
4’Min.
12”Min.
4’Min.
Side wall ventingSide wall venting
![Page 22: NFPA 54 National Fuel Gas Code Boiler Manufacturer ANSI Standards Local Codes Vent Manufacturer](https://reader035.vdocuments.site/reader035/viewer/2022081503/56649e175503460f94b01f7e/html5/thumbnails/22.jpg)
Z223.1-56 (Venting of Equipment)
As required for Clearance to Combustibles or Snow Load.
As required forClearance toCombustibles
ParapetRoof
Rooftop ventingRooftop ventingRooftop ventingRooftop venting
2 feet above anything within 10 feet & no less than 3 feet above roof
![Page 23: NFPA 54 National Fuel Gas Code Boiler Manufacturer ANSI Standards Local Codes Vent Manufacturer](https://reader035.vdocuments.site/reader035/viewer/2022081503/56649e175503460f94b01f7e/html5/thumbnails/23.jpg)
Common Code ViolationsCommon Code ViolationsNFPA 54 c99 Sec. 7.6.1(d)NFPA 54 c99 Sec. 7.6.1(d)
The total horizontal distance of a vent plus the The total horizontal distance of a vent plus the horizontal vent connector serving Category 1 horizontal vent connector serving Category 1 appliancesappliances Shall Not Be Greater Than 75%Shall Not Be Greater Than 75% of the of the vertical height of the vent.vertical height of the vent.
![Page 24: NFPA 54 National Fuel Gas Code Boiler Manufacturer ANSI Standards Local Codes Vent Manufacturer](https://reader035.vdocuments.site/reader035/viewer/2022081503/56649e175503460f94b01f7e/html5/thumbnails/24.jpg)
Common Code ViolationsCommon Code ViolationsNFPA 54 c99 Sec. 10.2.2,4,5NFPA 54 c99 Sec. 10.2.2,4,5
The length of the common vent connector, offset, The length of the common vent connector, offset, and breechingand breeching Shall Not Exceed 1 1/2 ft. (18”)Shall Not Exceed 1 1/2 ft. (18”) for for each inch of common vent diameter.each inch of common vent diameter.
DiameterDiameter
Not Greater than 1.5 Ft. per Not Greater than 1.5 Ft. per Every Inch of DiameterEvery Inch of Diameter
![Page 25: NFPA 54 National Fuel Gas Code Boiler Manufacturer ANSI Standards Local Codes Vent Manufacturer](https://reader035.vdocuments.site/reader035/viewer/2022081503/56649e175503460f94b01f7e/html5/thumbnails/25.jpg)
Common Code ViolationsCommon Code ViolationsNFPA 54 c99 Sec. 10.2.8, 15NFPA 54 c99 Sec. 10.2.8, 15
The flow area of the vertical ventThe flow area of the vertical vent Shall Not Exceed Shall Not Exceed Seven (7) TimesSeven (7) Times the flow area of the smallest listed the flow area of the smallest listed appliance.appliance.
Not Greater than 7 times Not Greater than 7 times the smallest Outlet Cross the smallest Outlet Cross Sectional AreaSectional Area
Smallest DiameterSmallest Diameter
![Page 26: NFPA 54 National Fuel Gas Code Boiler Manufacturer ANSI Standards Local Codes Vent Manufacturer](https://reader035.vdocuments.site/reader035/viewer/2022081503/56649e175503460f94b01f7e/html5/thumbnails/26.jpg)
Common Code ViolationsCommon Code ViolationsNFPA 54 Z223.1NFPA 54 Z223.1
Connector Rise Not Adequate for Breeching DiameterConnector Rise Not Adequate for Breeching Diameter
RiserRiser
3 Ft. Minimum Vertical Rise on 8900 Units3 Ft. Minimum Vertical Rise on 8900 Units
5 Ft. Minimum Vertical Rise on 8800 Units5 Ft. Minimum Vertical Rise on 8800 Units
![Page 27: NFPA 54 National Fuel Gas Code Boiler Manufacturer ANSI Standards Local Codes Vent Manufacturer](https://reader035.vdocuments.site/reader035/viewer/2022081503/56649e175503460f94b01f7e/html5/thumbnails/27.jpg)
Common Code ViolationsCommon Code ViolationsNFPA 54 v99 Sec. 7.10.4(b)NFPA 54 v99 Sec. 7.10.4(b)
Vent Connectors serving equipment vented by Vent Connectors serving equipment vented by natural draftnatural draft Shall Not Be Connected Into Any Shall Not Be Connected Into Any PortionPortion of mechanical draft systems under positive of mechanical draft systems under positive pressure.pressure.
![Page 28: NFPA 54 National Fuel Gas Code Boiler Manufacturer ANSI Standards Local Codes Vent Manufacturer](https://reader035.vdocuments.site/reader035/viewer/2022081503/56649e175503460f94b01f7e/html5/thumbnails/28.jpg)
Common Code ViolationsCommon Code ViolationsNFPA 54 c99 Sec. 7.3.4(b)NFPA 54 c99 Sec. 7.3.4(b)
Forced draft systems and all portions of induced Forced draft systems and all portions of induced draft systems under positive pressure shall be draft systems under positive pressure shall be designed and installed so as to prevent leakage designed and installed so as to prevent leakage of flue gasses into the building.of flue gasses into the building.
![Page 29: NFPA 54 National Fuel Gas Code Boiler Manufacturer ANSI Standards Local Codes Vent Manufacturer](https://reader035.vdocuments.site/reader035/viewer/2022081503/56649e175503460f94b01f7e/html5/thumbnails/29.jpg)
Combustion AirCombustion Air
Make sure the proper amount of combustion air is available.
![Page 30: NFPA 54 National Fuel Gas Code Boiler Manufacturer ANSI Standards Local Codes Vent Manufacturer](https://reader035.vdocuments.site/reader035/viewer/2022081503/56649e175503460f94b01f7e/html5/thumbnails/30.jpg)
Air from Outside or Inside the BuildingNFPA 54 - National Fuel Gas Code, Outside Air for Combustion National Fire Protection Association, NFPA Gas fuels:
Minimum No. openings required 2
Indoor opening, sq. in./Btu h 1/1000
Outdoor opening, sq. in./Btu h 1/4000
Vertical ducts, sq. in./Btu h 1/4000
Horizontal ducts, sq. in./Btu h 1/2000
Ducts same as opening yes
Louver & grill free area opening
CFM per 1000 BTU’s (atmospheric) .50
CFM per 1000 BTU’s (fan assist)without barometric .27
with barometric .35
- Single Outdoor opening: 1/3000