The integrated Web Visualization of netSCADA Modbus sets the path of graphical Web Browser based HMI for low
cost control of automated machines and industrial manufacturing systems. The device links to the targeted system
with simple Modbus RTU protocol over a serial RS-232, RS-485 or RS-485 connection. The two Ethernet ports with
integrated 2-port switch functionality are connecting the unit economically with the existing network at no need for
additional Ethernet Switches.
The Web Visualization is managing the pages without plugins such as ActiveX®, Flash®, Java® or Silverlight™ and
can be executed by all leading Web Browsers. Visualizations can be displayed and accessed on any Windows®/
Linux PC based system as well as such on tablets and smartphones with browser support. The simultaneous access
of multiple browsers at a time is also supported.
Although native Web Technology is being used there is no HTML code programming necessary. Front end creation
as well as the dynamizations of the visualizing elements are easily and quickly configured with a few mouse clicks.
Color change, movement, scaling, user rights, the support of all common graphic formats and multilingualism are
standard. Next to monitoring online data, Alarming and Acknowledgment and Data Trending are supported. For best
visual effects a large catalogue of high-quality graphics from the industrial sector is optionally available as library.
Upgrades a simple Modbus-enabled network into
a fully featured Visualization and Control System
Visualizes thanks Web Technique platform-neutral
and free of charge with standard Web Browsers
Saves additional installation costs using existing
and company‘s wide spread Ethernet IT structures
Guarantees fast output at minimum effort
due to intuitive Point and Click Engineering Tool
netSCADA ModbusModbus Node with integrated Web Visualization
Visualizing most flexible und economically over Web BrowsersVisualizing most flexible und economically over Web BrowsersVisualizing most flexible und economically over Web Browsers
Technical Data / Product Overview
HeadquartersGermanyHilscher Gesellschaft für Systemautomation mbHRheinstrasse 1565795 HattersheimPhone: +49 (0) 6190 9907-0 Fax: +49 (0) 6190 9907-50E-Mail: [email protected] Web: www.hilscher.com
JapanHilscher Japan KKTokyo, 160-0022Phone: +81 (0) 3-5362-0521E-Mail: [email protected] KoreaHilscher Korea Inc. Seongnam, Gyeonggi, 463-400Phone: +82 (0) 31-789-3715E-Mail: [email protected]
SwitzerlandHilscher Swiss GmbH 4500 SolothurnPhone: +41 (0) 32 623 6633E-Mail: [email protected] USAHilscher North America, Inc. Lisle, IL 60532Phone: +1 630-505-5301E-Mail: [email protected]
IndiaHilscher India Pvt. Ltd.New Delhi 110 002Phone: +91- 8888 750 777E-Mail: [email protected] ItalyHilscher Italia S.r.l.20090 Vimodrone (MI)Phone: +39 02 25007068E-Mail: [email protected]
SubsidiariesChinaHilscher Systemautomation(Shanghai) Co. Ltd.200010 ShanghaiPhone: +86 (0) 21-6355-5161E-Mail: [email protected] FranceHilscher France S.a.r.l.69500 BronPhone: +33 (0) 4 72 37 98 40E-Mail: [email protected]
Distributors More information at www.hilscher.com
Note: All technical data may be changed without further notice.
05/2
014
GB
NSCD-T52-RS/ATVISE/MBR 1800.100/ATVISE/MBR netSCADA Modbus, Modbus Node with integrated Web Visualization atvise
ATVISE ELEMENTS 1701.432 Vector Graphics Library with over 4000 images of the Industrial Sector
Ove
rvie
w
Article Article Number Article Description
Parameter Value
Processor netX 52
Power Supply 18 … 30 V / ca. 60 mA @ 24 V
Supply Connection COMBICON MC 1,5/5 5-pin, light gray
Ethernet Connection 2 x RJ45 with integrated switch
Ethernet 10/100 Base-TX Ethernet
Modbus Connection COMBICON MSTB 2,5/5 5-pin, green
Modbus Interface RS-232, RS-485, RS-422 each non isolated
LED Indicators SYSTEM,CONFIG,MODBUS,ACTIVE,LOAD
Operating Temperature 0 … 50 °C
Dimensions (L x W x H) 88 mm x 22,5 mm x 78 mm
Weight approx. 84 g
Protection Class IP20
Mounting DIN EN 60715
EC Conformity Directive 2004/108/EG
Real-Time Clock Hardware supported, precision 20ppm
Real-Time Clock buffering 7 days min., maintenance-free by SuperCap
Clock Synchronization Manual / cyclic over SNTP protocol
Web Application Memory 6 MByte, non-volatile FLASH memory
Trending Memory 8 Mbyte, non-volatile FLASH memory
Parameter Value
Modbus-RTU Slave / Master to 16 Slaves
Function Codes FC1,FC2,FC3,FC4,FC5,FC15,FC16
Baud Rate 1,2 kBaud ... 115,2 kBaud
SNTP Client RFC 2030, Port 123, Time Synchronization
FTP Server RFC 959, Port 21, Passive Mode
HTTP Server RFC 2616, Port 80, HTTP/1.1
Supported Browsers Internet Explorer 8/9/10, Mozilla
Firefox 24; Safari 5.1.7, Chrome 31,
Opera 16.0, Blackberry 6 or 10
with at least 3 simultaneous connections
Web Visualization atvise® (webMI) with Hilscher Plugin
Engineering Tool atvise builder, Multi-User License
Variables/Data Points Unlimited
Web Memory Consumption 200kByte per page typically
Standard Functions Alarm, Trend and User Management
Adaptability Entirely customizable using Java Scripting
Multilingualism Yes, german / english as standard
Trend Variables 32 max., Sampl. Rate 200msec to 24hrs.
Recording Time 8 Variables @60 seconds Rate = 45 days
18 Variables @1 hour Rate = 1200 days
Tec
hn
ical
Dat
a
ATVISE SUPPORT SERVICE 0027.002 Half-day atvise Phone Support / Adaption / Programming / Personal Training @Hattersheim
atvise® is a registered trademark of CERTEC GmbH.