national fire protection association report - nfpa.org · pdf filepublic comment no. 4-nfpa...

33
Public Comment No. 20-NFPA 2001-2013 [ Section No. 4.1.3.2 ] 4.1.3.2* Storage containers shall be permitted to be located within : (a) outside the hazard or hazards they protect (b) within the hazard or hazards they protect . Statement of Problem and Substantiation for Public Comment The First Revision text inadvertently removed the requirement which allows for storage cylinders to be allowed to be located outside the hazard area as identified in the current edition of NFPA 2001. Submitter Information Verification Submitter Full Name: Robert Kasiski Organization: FM Global Affilliation: FM Global Street Address: City: State: Zip: Submittal Date: Fri Nov 15 17:00:31 EST 2013 Committee Statement Committee Action: Rejected but see related SR Resolution: SR-1-NFPA 2001-2014 Statement: The First Revision text inadvertently removed the requirement which allows for storage cylinders to be located outside the hazard area as identified in the current edition of NFPA 2001. National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... 1 of 32 6/13/2014 2:37 PM

Upload: truongnguyet

Post on 18-Feb-2018

216 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: National Fire Protection Association Report - nfpa.org · PDF filePublic Comment No. 4-NFPA 2001-2013 [ Section No. 4.1.4.4 ] 4.1.4.4 A means for determining pressure shall be provided

Public Comment No. 20-NFPA 2001-2013 [ Section No. 4.1.3.2 ]

4.1.3.2*

Storage containers shall be permitted to be located within :

(a) outside the hazard or hazards they protect

(b) within the hazard or hazards they protect .

Statement of Problem and Substantiation for Public Comment

The First Revision text inadvertently removed the requirement which allows for storage cylinders to be allowed to be located outside the hazard area as identified in the current edition of NFPA 2001.

Submitter Information Verification

Submitter Full Name: Robert Kasiski

Organization: FM Global

Affilliation: FM Global

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 15 17:00:31 EST 2013

Committee Statement

CommitteeAction:

Rejected but see related SR

Resolution: SR-1-NFPA 2001-2014

Statement: The First Revision text inadvertently removed the requirement which allows for storage cylinders to be located outside the hazardarea as identified in the current edition of NFPA 2001.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

1 of 32 6/13/2014 2:37 PM

Page 2: National Fire Protection Association Report - nfpa.org · PDF filePublic Comment No. 4-NFPA 2001-2013 [ Section No. 4.1.4.4 ] 4.1.4.4 A means for determining pressure shall be provided

Public Comment No. 4-NFPA 2001-2013 [ Section No. 4.1.4.4 ]

4.1.4.4

A means

for determining pressureshall be provided

for agent storage containersto determine the pressure in containers of inert gas agents .

Statement of Problem and Substantiation for Public Comment

The original statement is general and is followed by an exception in 4.1.4.5. Better to say what is required when and avoid saying what is not required when. A parallal statement is offered for superpressurized containers of liquid or liquified compressed gas agents.

Submitter Information Verification

Submitter Full Name: Joseph Senecal

Organization: UTC/Kidde-Fenwal, Inc.

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 13 21:26:45 EST 2013

Committee Statement

Committee Action: Rejected but see related SR

Resolution: SR-2-NFPA 2001-2014

Statement: Editorial clarification.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

2 of 32 6/13/2014 2:37 PM

Page 3: National Fire Protection Association Report - nfpa.org · PDF filePublic Comment No. 4-NFPA 2001-2013 [ Section No. 4.1.4.4 ] 4.1.4.4 A means for determining pressure shall be provided

Public Comment No. 5-NFPA 2001-2013 [ Section No. 4.1.4.5 ]

4.1.4.5

Liquefied halocarbon agents stored under their own vapor pressure shall not be required to comply with 4.1.4.4 . A means shall be providedto determine the pressure in containers of superpressurized liquid or liquefied compressed gas agents.

Statement of Problem and Substantiation for Public Comment

This comment follows a similar comment for 4.1.4.4 for inert gas agent containers. Together the proposed revisions to 4.1.4.4 and 4.1.4.5 state what is required in terms of providing means of pressure measurement for which types of agent containers. The 1st Draft exception statement is not needed.

Submitter Information Verification

Submitter Full Name: Joseph Senecal

Organization: UTC/Kidde-Fenwal, Inc.

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 13 21:31:25 EST 2013

Committee Statement

Committee Action: Rejected but see related SR

Resolution: SR-2-NFPA 2001-2014

Statement: Editorial clarification.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

3 of 32 6/13/2014 2:37 PM

Page 4: National Fire Protection Association Report - nfpa.org · PDF filePublic Comment No. 4-NFPA 2001-2013 [ Section No. 4.1.4.4 ] 4.1.4.4 A means for determining pressure shall be provided

Public Comment No. 10-NFPA 2001-2013 [ Section No. 4.3.1.1 ]

4.3.1.1 *

Detection, actuation, alarm, and control systems shall be installed, tested, and maintained in accordance with appropriate NFPA protectivesignaling systems standards. (See NFPA 70 and NFPA 72 . In Canada refer to CAN/ULC S524-06 and CAN/ULC S529-09.)

Statement of Problem and Substantiation for Public Comment

Adding * for new annex material

Submitter Information Verification

Submitter Full Name: John Spalding

Organization: Healey Fire Protection, Inc.

Affilliation: Fire Suppression Systems Association

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 15 13:33:47 EST 2013

Committee Statement

CommitteeAction:

Rejected but see related SR

Resolution: SR-6-NFPA 2001-2014

Statement: Add new annex material. Information contained in the FSSA Guide will assist the designer in understanding the applicationtechiques involved with an automatic fire detection system.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

4 of 32 6/13/2014 2:37 PM

Page 5: National Fire Protection Association Report - nfpa.org · PDF filePublic Comment No. 4-NFPA 2001-2013 [ Section No. 4.1.4.4 ] 4.1.4.4 A means for determining pressure shall be provided

Public Comment No. 6-NFPA 2001-2013 [ Section No. 5.1.2.2 ]

5.1.2.2

Working plans shall be drawn to an indicated scale and shall show the following items that pertain to the design of the system:

(1) Name of owner and occupant

(2) Location, including street address

(3) Point of compass and symbol legend

(4) Location and construction of protected enclosure walls and partitions

(5) Location of fire walls

(6) Enclosure cross section, shown as a full-height or schematic diagram, including location and construction of building floor-ceilingassemblies above and below, raised access floor, and suspended ceiling

(7) Agent being used

(8) Extinguishing or inerting concentrations Agent concentration at the lowest temperature and the highest temperatures temperature forwhich the enclosure is protected

(9) Description of occupancies and hazards being protected, designating whether the enclosure is normally occupied

(10) For an enclosure protected by a clean agent fire extinguishing system, an estimate of the maximum positive pressure and the maximumnegative pressure, relative to ambient pressure, expected to be developed upon the discharge of agent

(11) Description of exposures surrounding the enclosure

(12) Description of the agent storage containers used, including internal volume, storage pressure, and nominal capacity expressed in units ofagent mass or volume at standard conditions of temperature and pressure

(13) Description of nozzle(s) used, including size, orifice port configuration, and equivalent orifice area

(14) Description of pipe and fittings used, including material specifications, grade, and pressure rating

(15) Description of wire or cable used, including classification, gauge [American Wire Gauge (AWG)], shielding, number of strands inconductor, conductor material, and color coding schedule;segregation requirements of various system conductors; required method ofmaking wire terminations.

(16) Description of the method of detector mounting

(17) Equipment schedule or bill of materials for each piece of equipment or device showing device name, manufacturer, model or partnumber, quantity, and description

(18) Plan view of protected area showing enclosure partitions (full and partial height); agent distribution system, including agent storagecontainers, piping, and nozzles; type of pipe hangers and rigid pipe supports; detection, alarm, and control system, including all devicesand schematic of wiring interconnection between them; end-of-line device locations; location of controlled devices such as dampers andshutters; and location of instructional signage

(19) Isometric view of agent distribution system showing the length and diameter of each pipe segment; node reference numbers relating tothe flow calculations; fittings, including reducers, strainers, and orientation of tees; and nozzles, including size, orifice port configuration,flow rate, and equivalent orifice area

(20) Scale drawing showing the layout of the annunciator panel graphics if required by the authority having jurisdiction

(21) Details of each unique rigid pipe support configuration showing method of securement to the pipe and to the building structure

(22) Details of the method of container securement showing method of securement to the container and to the building structure

(23) Complete step-by-step description of the system sequence of operations, including functioning of abort and maintenance switches, delaytimers, and emergency power shutdown

(24) Point-to-point wiring schematic diagrams showing all circuit connections to the system control panel and graphic annunciator panel

(25) Point-to-point wiring schematic diagrams showing all circuit connections to external or add-on relays

(26) Complete calculations to determine enclosure volume, quantity of clean agent, and size of backup batteries; method used to determinenumber and location of audible and visual indicating devices; and number and location of detectors

(27) Details of any special features

(28)

Statement of Problem and Substantiation for Public Comment

Extinguishing and inerting concentrations are not generally known as a function of temperature. All the that the system plans can say is what agent concentration will be achieved in the protected space for the given quantity of agent to be discharged.

Submitter Information Verification

Submitter Full Name: Joseph Senecal

Organization: UTC/Kidde-Fenwal, Inc.

Street Address:

City:

* Pressure relief vent area, or equivalent leakage area, for the protected enclosure to prevent development, during system discharge, ofa pressure difference across the enclosure boundaries that exceeds a specified enclosure pressure limit

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

5 of 32 6/13/2014 2:37 PM

Page 6: National Fire Protection Association Report - nfpa.org · PDF filePublic Comment No. 4-NFPA 2001-2013 [ Section No. 4.1.4.4 ] 4.1.4.4 A means for determining pressure shall be provided

State:

Zip:

Submittal Date: Wed Nov 13 21:37:58 EST 2013

Committee Statement

CommitteeAction:

Accepted

Resolution: SR-3-NFPA 2001-2014

Statement: Extinguishing and inerting concentrations are not generally known as a function of temperature. All that the system plans can say iswhat agent concentration will be achieved in the protected space for the given quantity of agent to be discharged.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

6 of 32 6/13/2014 2:37 PM

Page 7: National Fire Protection Association Report - nfpa.org · PDF filePublic Comment No. 4-NFPA 2001-2013 [ Section No. 4.1.4.4 ] 4.1.4.4 A means for determining pressure shall be provided

Public Comment No. 1-NFPA 2001-2013 [ Section No. 5.5.1.1 ]

5.5.1.1

The concentration of halocarbon clean agent that will be developed in the protected enclosure shall be calculated at both the minimum andmaximum design temperature using the following equation:

The equation as written is incoorrect. Correct equation is not correct. A minus sign was put in place of a dot "." which means multiplication. See attachment.

[5.5.1.1]

where:

C = agent concentration [vol%]

W = installed quantity of agent [lb (kg)]

s = specific volume of the gaseous agent at the minimum/maximum design temperature of the hazard [ft3/lb (m3/kg)]

V = volume of the as-built enclosure [ft3 (m3)]

Additional Proposed Changes

File Name Description Approved

Comment-NFPA_2001-5.5.1.1.docx Corrected equation for 5.5.1.1

Statement of Problem and Substantiation for Public Comment

Correction of equation to that intended by submitter.

Submitter Information Verification

Submitter Full Name: Joseph Senecal

Organization: UTC/Kidde-Fenwal, Inc.

Street Address:

City:

State:

Zip:

Submittal Date: Fri Sep 27 13:03:48 EDT 2013

Committee Statement

Committee Action: Rejected but see related SR

Resolution: SR-4-NFPA 2001-2014

Statement: Equation is incorrect. Replace the minus signs in the equation with multiplication.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

7 of 32 6/13/2014 2:37 PM

Page 8: National Fire Protection Association Report - nfpa.org · PDF filePublic Comment No. 4-NFPA 2001-2013 [ Section No. 4.1.4.4 ] 4.1.4.4 A means for determining pressure shall be provided

NFPA 2001 Section 5.5.1.1 The concentration of halocarbon clean agent that will be developed in the protected enclosure shall be

calculated using the following equation

Equation 5.5.1.1

based on the following parameters:

(a) volume of the as-built enclosure;

(b) installed quantity of agent;

(c) minimum design temperature of the protected space;

(d) maximum design temperature of the protected space

where

C = agent concentration [vol%]

W = quantity of agent [lb (kg)]

V = volume of the hazard [ft3 (m3)]

s = specific volume of the gaseous agent at the temperature of the hazard [ft3/lb (m3/kg)]

Editorial note: In the equation as shown above, a dot between symbols (“”), as used above, means multiplication. Submitted by Joseph Senecal 9-27-13

1

100

V

sW

V

sW

C

Page 9: National Fire Protection Association Report - nfpa.org · PDF filePublic Comment No. 4-NFPA 2001-2013 [ Section No. 4.1.4.4 ] 4.1.4.4 A means for determining pressure shall be provided

Public Comment No. 13-NFPA 2001-2013 [ Section No. 5.6 [Excluding any Sub-Sections] ]

Make modifications to paragraph 5.6 as follows:

5.6 Duration of Protection. A minimum concentration of 85 percent of the adjusted minimum design concentration shall be held at thehighest level height of hazard content combustibles for a period of 10 minutes or for a time period sufficient to allow for response bytrained personnel.

Statement of Problem and Substantiation for Public Comment

Combustibles as stated could be anything in the room, including structure. The hazard content combustibles are what are being protected by a clean agent system. Structural or building combustible are typically protected by code required automatic sprinklers.

Submitter Information Verification

Submitter Full Name: Paul Rivers

Organization: 3M Company

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 15 14:08:28 EST 2013

Committee Statement

CommitteeAction:

Rejected but see related SR

Resolution: SR-5-NFPA 2001-2014

Statement: Combustibles as stated could be anything in the room, including structure. The hazard content combustibles are what are beingprotected by a clean agent system. Structural or building combustible are typically protected by code required automatic sprinklers.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

8 of 32 6/13/2014 2:37 PM

Page 10: National Fire Protection Association Report - nfpa.org · PDF filePublic Comment No. 4-NFPA 2001-2013 [ Section No. 4.1.4.4 ] 4.1.4.4 A means for determining pressure shall be provided

Public Comment No. 19-NFPA 2001-2013 [ Section No. 5.6 [Excluding any Sub-Sections] ]

A minimum concentration of 85 percent of the adjusted minimum design concentration shall be held at the highest level of combustibles for aperiod of 10 minutes or for a time period sufficient to allow for response by trained personnel, whichever is greater .

Statement of Problem and Substantiation for Public Comment

Adequate protection from clean agent systems should be provided for a minimum time period of 10 minutes. The First Draft Revision allows for protection to be designed and provided for a shorter period replying on the human element to intervene, defeating the purpose of fixed protection. If the response time from trained personnel is extended or trained personnel no longer are available from the original design time period at a later date, there may be inadequate protection provided to the occupancy. In addition this revision will effect the listings with FM Approval as the Class 5600 have a 600 second time limit for extinguishment in the Class A fire tests. Fires may not be extinguished if the minimum time period is removed.

Submitter Information Verification

Submitter Full Name: Robert Kasiski

Organization: FM Global

Affilliation: FM Global

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 15 16:47:52 EST 2013

Committee Statement

Committee Action: Rejected

Resolution: Ten minutes is a sufficient retention time when trained personnel cannot respond sooner.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

9 of 32 6/13/2014 2:37 PM

Page 11: National Fire Protection Association Report - nfpa.org · PDF filePublic Comment No. 4-NFPA 2001-2013 [ Section No. 4.1.4.4 ] 4.1.4.4 A means for determining pressure shall be provided

Public Comment No. 7-NFPA 2001-2013 [ Section No. 5.6 [Excluding any Sub-Sections] ]

A minimum concentration of 85 percent of the adjusted minimum design concentration shall be held at the highest level of combustibles for aminimum period of 10 minutes or for a time period sufficient to allow for response by trained personnel.

Statement of Problem and Substantiation for Public Comment

I believe that it is important to retain the minimum hold time of 10 minutes. If the word minimum is removed is gives users of this standard the ability to have hold times less than 10 minutes.

Submitter Information Verification

Submitter Full Name: Brad Stilwell

Organization: Fike Corporation

Street Address:

City:

State:

Zip:

Submittal Date: Thu Nov 14 15:47:10 EST 2013

Committee Statement

Committee Action: Rejected

Resolution: Ten minutes is a sufficient retention time when trained personnel cannot respond sooner.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

10 of 32 6/13/2014 2:37 PM

Page 12: National Fire Protection Association Report - nfpa.org · PDF filePublic Comment No. 4-NFPA 2001-2013 [ Section No. 4.1.4.4 ] 4.1.4.4 A means for determining pressure shall be provided

Public Comment No. 15-NFPA 2001-2013 [ Section No. 6.4.3.1 ]

6.4.3.1

The discharge time shall be increased to compensate for any hazard condition that would require a longer cooling period or mechanicalrundown time associated with ventilation equipment present to prevent re-ignition.

Statement of Problem and Substantiation for Public Comment

This proposed change consolidates conditions that may require an increased discharge time to prevent re-ignition, thus, eliminating an unneeded paragraph.

Submitter Information Verification

Submitter Full Name: Paul Rivers

Organization: 3M Company

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 15 14:39:49 EST 2013

Committee Statement

Committee Action: Rejected but see related SR

Resolution: SR-8-NFPA 2001-2014

Statement: Editorial revision.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

11 of 32 6/13/2014 2:37 PM

Page 13: National Fire Protection Association Report - nfpa.org · PDF filePublic Comment No. 4-NFPA 2001-2013 [ Section No. 4.1.4.4 ] 4.1.4.4 A means for determining pressure shall be provided

Public Comment No. 14-NFPA 2001-2013 [ Section No. 6.4.3.4 ]

6.4.3.4

The discharge time shall be increased to compensate for any mechanical rundown time associated with ventilation equipment present.

Statement of Problem and Substantiation for Public Comment

In the interest of brevity, this proposed change and recommending to include in paragraph 6.4.3.1 reference to mechanical rundown time associated with ventilation equipment consolidates conditions that may require an increased discharge time to prevent re-ignition, thus, eliminating an unneeded paragraph.

Submitter Information Verification

Submitter Full Name: Paul Rivers

Organization: 3M Company

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 15 14:24:48 EST 2013

Committee Statement

Committee Action: Rejected but see related SR

Resolution: SR-8-NFPA 2001-2014

Statement: Editorial revision.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

12 of 32 6/13/2014 2:37 PM

Page 14: National Fire Protection Association Report - nfpa.org · PDF filePublic Comment No. 4-NFPA 2001-2013 [ Section No. 4.1.4.4 ] 4.1.4.4 A means for determining pressure shall be provided

Public Comment No. 3-NFPA 2001-2013 [ New Section after 7.1.3.3 ]

TITLE OF NEW CONTENT

Owners Inspection.

On a monthly basis, inspection shall be conducted in accordance with the manufacturer’s listed installation and maintenance manual orowner’s manual.

As a minimum, this “quick check” or inspection shall include verification of the following:

(1) Release panel is in service.

(2) Manual actuators are unobstructed

(3) Maintenance Tag is in place.

(4) System shows no physical damage or condition that might prevent operation.

(5) Pressure gauges if provided are in required operational range.

(6) Protected equipment and or hazard has not been changed and or modified.

(7) Noted deficiencies have been corrected.

If any deficiencies are found, appropriate corrective action shall be taken immediately.

Where the corrective action involves maintenance, it shall be conducted by a service technician

Personnel making inspections shall keep records for those extinguishing systems that were found to require corrective actions.

At least monthly, the date the inspection is performed and the initials of the person performing the inspection shall be recorded. The recordsshall be retained until the next semiannual maintenance.

A service technician who performs maintenance on an extinguishing system shall be trained and shall have passed a written or online testthat is acceptable to the authority having jurisdiction.

Statement of Problem and Substantiation for Public Comment

Provide documentation by owners representative that due dilligence is being performed checking that systems are being maintained in service.

Submitter Information Verification

Submitter Full Name: BEN SMITH

Organization: GLOBAL RISK CONSULTANTS

Affilliation: Member

Street Address:

City:

State:

Zip:

Submittal Date: Tue Nov 05 13:28:45 EST 2013

Committee Statement

CommitteeAction:

Rejected but held

Resolution: The committee agrees that this concept should be included in the standard. However, it constitutes new material at this time and isbeing held for further consideration at the next revision cycle.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

13 of 32 6/13/2014 2:37 PM

Page 15: National Fire Protection Association Report - nfpa.org · PDF filePublic Comment No. 4-NFPA 2001-2013 [ Section No. 4.1.4.4 ] 4.1.4.4 A means for determining pressure shall be provided

Public Comment No. 16-NFPA 2001-2013 [ Section No. A.1.6 ]

A.1.6

Many factors impact the environmental acceptability of a fire suppression agent. Uncontrolled fires pose significant impact by themselves. Allextinguishing agents should be used in ways that eliminate or minimize the potential environmental impact [see Table A.1.6]. Generalguidelines to be followed to minimize this impact include the following:

(1) Not performing unnecessary discharge testing

(2) Considering the ozone depletion and global warming impact of the agent under consideration and weighing those impacts against thefire safety concerns

(3) Recycling all agents where possible

(4) Consulting the most recent environmental regulations on each agent

The unnecessary emission of clean extinguishing agents with the ODP, the GWP, or both should be avoided. All phases of design,installation, testing, and maintenance of systems using these agents should be performed with the goal of no emission into the environment.

GWP is a measure of how much a given mass of greenhouse gas is estimated to contribute to global warming. It is a relative scale thatcompares the gas in question to the same mass of carbon dioxide whose GWP is by convention equal to 1.

It is important to understand that the impact of a gas on climate change is a function of both the GWP of the gas and the amount of the gasemitted. The U.S. EPA employed its vintaging model (U.S. EPA, Inventory of U.S. Greenhouse Gas Emissions and Sinks: 1990–2007) toestimate the emissions of greenhouse gases (GHGs) from various sources. This model indicated that fire protection emissions accounted for0.6 percent of total GHG emissions. For current U.S. emissions data, refer to the HFC Emissions Estimating Program (HEEP).

Table A.1.6 Potential Environmental Impacts

AgentGWP

(IPCC 2007)ODP

FIC-13I1 0.4 0*

FK-5-1-12 1 0

HCFC Blend A 1550 0.048

HFC Blend B 1540 0

HCFC-124 609 0.022

HFC-125 3500 0

HFC-227ea 3220 0

HFC-23 14800 0

HFC-236fa 9810 0

IG-01 0 0

IG-100 0 0

IG-541 0 0

IG-55 0 0

*Agent might have a nonzero ODP if released at altitudes high above ground level.

GWP is reported over a 100-year integrated time horizon.

Statement of Problem and Substantiation for Public Comment

ODP and GWP for the agents are listed in the table. It is important to have independent references with the most current data on which to rely. Environmental data maintained and regularly updated by the Montreal Protocol and the IPCC are the most reliable sources to which one can refer internationally.

Submitter Information Verification

Submitter Full Name: Paul Rivers

Organization: 3M Company

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 15 14:57:27 EST 2013

Committee Statement

CommitteeAction:

Rejected but see related SR

Resolution: SR-11-NFPA 2001-2014

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

14 of 32 6/13/2014 2:37 PM

Page 16: National Fire Protection Association Report - nfpa.org · PDF filePublic Comment No. 4-NFPA 2001-2013 [ Section No. 4.1.4.4 ] 4.1.4.4 A means for determining pressure shall be provided

Statement: ODP and GWP for the agents are listed in the table. It is important to have independent references with the most current data on whichto rely. Environmental data maintained and regularly updated by the Montreal Protocol and the IPCC are available sources. The valuesreported in Table A.1.6 were updated to reflect the most recent data.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

15 of 32 6/13/2014 2:37 PM

Page 17: National Fire Protection Association Report - nfpa.org · PDF filePublic Comment No. 4-NFPA 2001-2013 [ Section No. 4.1.4.4 ] 4.1.4.4 A means for determining pressure shall be provided

Public Comment No. 8-NFPA 2001-2013 [ Section No. A.1.6 ]

A.1.6

Many factors impact the environmental acceptability of a fire suppression agent. Uncontrolled fires pose significant impact by themselves. Allextinguishing agents should be used in ways that eliminate or minimize the potential environmental impact [see Table A.1.6 ]. Generalguidelines to be followed to minimize this impact include the following:

(1) Not performing unnecessary discharge testing

(2) Considering the ozone depletion and global warming impact of the agent under consideration and weighing those impacts against thefire safety concerns

(3) Recycling all agents where possible

(4) Consulting the most recent environmental regulations on each agent

The unnecessary emission of clean extinguishing agents

with the ODP, the GWP, or both

with non-zero ODPs or non-zero-GWPs should be avoided. All phases of design, installation, testing, and maintenance of systems usingthese agents should be performed with the goal of no emission into the environment.

GWP is a measure of how much a given mass of greenhouse gas is estimated to contribute to global warming. It is a relative scale thatcompares the gas in question to the same mass of carbon dioxide whose GWP is by convention equal to 1.

It is important to understand that the impact of a gas on climate change is a function of both the GWP of the gas and the amount of the gasemitted. The U.S. EPA employed its vintaging model (U.S. EPA, Inventory of U.S. Greenhouse Gas Emissions and Sinks:

1990–2007

1990–2011 ) to estimate the

emissions

impact on climate change of greenhouse gases (GHGs) from various sources. This model indicated that fire protection emissions of HFCsaccounted for 0.

6 percent

01 percent of the total impact on climate change of all GHG emissions. For current U.S. emissions data, refer to the HFC EmissionsEstimating Program (HEEP).

Table A.1.6 Potential Environmental Impacts

AgentGWP

(IPCC 2007)ODP

FIC-13I1 0.4 0*

FK-5-1-12 1 0

HCFC Blend A 1550 0.048

HFC Blend B 1540 0

HCFC-124 609 0.022

HFC-125 3500 0

HFC-227ea 3220 0

HFC-23 14800 0

HFC-236fa 9810 0

IG-01 0 0

IG-100 0 0

IG-541 0 0

IG-55 0 0

*Agent might have a nonzero ODP if released at altitudes high above ground level.

GWP is reported over a 100-year integrated time horizon.

Statement of Problem and Substantiation for Public Comment

Section 1.6 of NFPA 2001indicates that "the effects of the agent on the environment shall be considered" and that furthermore agent selection shall include consideration of "potential environmental impacts." The current text in Section A.1.6 fails to provide relevant and current third party information related to the impact of HFC clean agents on climate change.

The proposed version of Section A.1.6 correctly points out that the impact of a gas on climate change is afunction of BOTH the GWP value and the amount of emissions, but then cites only emissions data - this does not address the concern of Section 1.6 which emphasizes that the effect or impact is the item to be considered. The proposed text provides the necessary data, from a third party independent source (the US EPA) related to the concern of Section 1.6 - the IMPACT of emissions.

Submitter Information Verification

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

16 of 32 6/13/2014 2:37 PM

Page 18: National Fire Protection Association Report - nfpa.org · PDF filePublic Comment No. 4-NFPA 2001-2013 [ Section No. 4.1.4.4 ] 4.1.4.4 A means for determining pressure shall be provided

Submitter Full Name: Mark Robin

Organization: DuPont Fluoroproducts

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 15 11:46:23 EST 2013

Committee Statement

Committee Action: Rejected

Resolution: The paragraph being revised by the submitter was deleted because of the regional nature of the content. See SR 11.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

17 of 32 6/13/2014 2:37 PM

Page 19: National Fire Protection Association Report - nfpa.org · PDF filePublic Comment No. 4-NFPA 2001-2013 [ Section No. 4.1.4.4 ] 4.1.4.4 A means for determining pressure shall be provided

Public Comment No. 17-NFPA 2001-2013 [ Section No. A.4.1.4.1 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

18 of 32 6/13/2014 2:37 PM

Page 20: National Fire Protection Association Report - nfpa.org · PDF filePublic Comment No. 4-NFPA 2001-2013 [ Section No. 4.1.4.4 ] 4.1.4.4 A means for determining pressure shall be provided

A.4.1.4.1

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

19 of 32 6/13/2014 2:37 PM

Page 21: National Fire Protection Association Report - nfpa.org · PDF filePublic Comment No. 4-NFPA 2001-2013 [ Section No. 4.1.4.4 ] 4.1.4.4 A means for determining pressure shall be provided

Containers used for agent storage should be fit for the purpose. Materials of construction of the container, closures, gaskets, and othercomponents should be compatible with the agent and designed for the anticipated pressures. Each container is equipped with a pressurerelief device to protect against excessive pressure conditions.

The variations in vapor pressure with temperature for the various clean agents are shown in Figure A.4.1.4.1(a) through Figure A.4.1.4.1(m).

For halocarbon clean agents, the pressure in the container is significantly affected by fill density and temperature. At elevated temperatures,the rate of increase in pressure is very sensitive to fill density. If the maximum fill density is exceeded, the pressure will increase rapidly withtemperature increase and present a hazard to personnel and property. Therefore, it is important that the maximum fill density limit specifiedfor each liquefied clean agent not be exceeded. Adherence to the limits for fill density and pressurization levels specified in Table A.4.1.4.1should prevent excessively high pressures from occurring if the agent container is exposed to elevated temperatures. Adherence to the limitswill also minimize the possibility of an inadvertent discharge of agent through the pressure relief device. The manufacturer should beconsulted for superpressurization levels other than those shown in Table A.4.1.4.1.

Figure A.4.1.4.1(a) Isometric Diagram of FIC-13I1.

Figure A.4.1.4.1(b) Isometric Diagram of FK-5-1-12.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

20 of 32 6/13/2014 2:37 PM

Page 22: National Fire Protection Association Report - nfpa.org · PDF filePublic Comment No. 4-NFPA 2001-2013 [ Section No. 4.1.4.4 ] 4.1.4.4 A means for determining pressure shall be provided

Figure A.4.1.4.1(c) Isometric Diagram of HCFC Blend A.

Figure A.4.1.4.1(d) Isometric Diagram of HCFC-124 Pressurized with Nitrogen.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

21 of 32 6/13/2014 2:37 PM

Page 23: National Fire Protection Association Report - nfpa.org · PDF filePublic Comment No. 4-NFPA 2001-2013 [ Section No. 4.1.4.4 ] 4.1.4.4 A means for determining pressure shall be provided

Figure A.4.1.4.1(e) Isometric Diagram of HCFC-125 Pressurized with Nitrogen.

Figure A.4.1.4.1(f) Isometric Diagram of HCFC-227ea Pressurized with Nitrogen.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

22 of 32 6/13/2014 2:37 PM

Page 24: National Fire Protection Association Report - nfpa.org · PDF filePublic Comment No. 4-NFPA 2001-2013 [ Section No. 4.1.4.4 ] 4.1.4.4 A means for determining pressure shall be provided

Figure A.4.1.4.1(g) Isometric Design of HFC-23.

Figure A.4.1.4.1(h) Isometric Diagram of HCFC-236fa Pressurized with Nitrogen.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

23 of 32 6/13/2014 2:37 PM

Page 25: National Fire Protection Association Report - nfpa.org · PDF filePublic Comment No. 4-NFPA 2001-2013 [ Section No. 4.1.4.4 ] 4.1.4.4 A means for determining pressure shall be provided

Figure A.4.1.4.1(i) Isometric Diagram of IG-01.

Figure A.4.1.4.1(j) Isometric Diagram of IG-100.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

24 of 32 6/13/2014 2:37 PM

Page 26: National Fire Protection Association Report - nfpa.org · PDF filePublic Comment No. 4-NFPA 2001-2013 [ Section No. 4.1.4.4 ] 4.1.4.4 A means for determining pressure shall be provided

Figure A.4.1.4.1(k) Isometric Diagram of IG-541.

Figure A.4.1.4.1(l) Isometric Diagram of IG-55.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

25 of 32 6/13/2014 2:37 PM

Page 27: National Fire Protection Association Report - nfpa.org · PDF filePublic Comment No. 4-NFPA 2001-2013 [ Section No. 4.1.4.4 ] 4.1.4.4 A means for determining pressure shall be provided

Figure A.4.1.4.1(m) Isometric Diagram of HFC Blend B.

With the exception of inert gas–type systems, all the other clean agents are classified as liquefied compressed gases at 70°F (21°C). Forthese agents, the pressure in the container is significantly affected by fill density and temperature. At elevated temperatures, the rate ofincrease in pressure is very sensitive to fill density. If the maximum fill density is exceeded, the pressure will increase rapidly withtemperature increase and present a hazard to personnel and property. Therefore, it is important that the maximum fill density limit specifiedfor each liquefied clean agent not be exceeded. Adherence to the limits for fill density and pressurization levels specified in Table A.4.1.4.1should prevent excessively high pressures from occurring if the agent container is exposed to elevated temperatures. Adherence to the limitswill also minimize the possibility of an inadvertent discharge of agent through the pressure relief device. The manufacturer should beconsulted for superpressurization levels other than those shown in Table A.4.1.4.1.

Table A.4.1.4.1 Storage Container Characteristics

Extinguishing

Agent

Maximum Fill Density for Conditions

Listed (lb/ft3)

Minimum Container Design Level WorkingPressure (Gauge)

(psi)

Total Gauge Pressure Level at70°F (psi)

FK-5-1-12 90 500 360

HCFC Blend A 56.2 500 360

HCFC-124 71 240 195

HFC-125 58 320 166.4a

HFC-227ea 72 500 360

HFC-23 54 1800 608.9a

FIC-13I1 104.7 500 360

IG-01 N/A 2120 2370

IG-100 (300) N/A 3600 4061

IG-100 (240) N/A 2879 3236

IG-100 (180) N/A 2161 2404

IG-541 N/A 2015+ 2175

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

26 of 32 6/13/2014 2:37 PM

Page 28: National Fire Protection Association Report - nfpa.org · PDF filePublic Comment No. 4-NFPA 2001-2013 [ Section No. 4.1.4.4 ] 4.1.4.4 A means for determining pressure shall be provided

Extinguishing

Agent

Maximum Fill Density for Conditions

Listed (lb/ft3)

Minimum Container Design Level WorkingPressure (Gauge)

(psi)

Total Gauge Pressure Level at70°F (psi)

IG-541 (200) N/A 2746 2900

IG-55 (222) N/A 2057+ 2222b

IG-55 (2962) N/A 2743+ 2962c

IG-55 (4443) N/A 4114+ 4443d

HFC Blend B 58 400 195e

For SI units, 1 lb/ft3 = 16.018 kg/m3; 1 psi = 6895 Pa; °C = (°F – 32)/1.8.

Notes:

(1) The maximum fill density requirement is not applicable for IG-541. Cylinders for IG-541 are DOT 3A or 3AAand are stamped 2015+ orgreater.

(2) Total pressure level at 70°F (21°C) is calculated from the following filling conditions:

 IG-100 (300): 4351 psi (30.0 MPa) and 95°F (35°C)

 IG-100 (240): 3460 psi (23.9 MPa) and 95°F (35°C)

 IG-100 (180): 2560 psi (17.7 MPa) and 95°F (35°C)

 IG-55 (2222): 2175 psi (15 MPa) and 59°F (15°C)

 IG-55 (2962): 2901 psi (20 MPa) and 59°F (15°C)

 IG-55 (4443): 4352 psi (30 MPa) and 59°F (15°C)

a Vapor pressure for HFC-23 and HFC-125.

b Cylinders for IG-55 are stamped 2060+.

c Cylinders for IG-55 are DOT 3A or 3AA stamped 2750+ or greater.

d Cylinders for IG-55 are DOT 3A or 3AA stamped 4120+ or greater.

e Vapor pressure of agent.

Statement of Problem and Substantiation for Public Comment

Editorial.

Submitter Information Verification

Submitter Full Name: Paul Rivers

Organization: 3M Company

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 15 15:02:48 EST 2013

Committee Statement

Committee Action: Rejected

Resolution: Submitter did not provide recommended text.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

27 of 32 6/13/2014 2:37 PM

Page 29: National Fire Protection Association Report - nfpa.org · PDF filePublic Comment No. 4-NFPA 2001-2013 [ Section No. 4.1.4.4 ] 4.1.4.4 A means for determining pressure shall be provided

Public Comment No. 11-NFPA 2001-2013 [ New Section after A.4.2.5.5 ]

TITLE OF NEW CONTENT

Type your content here ...

A.4.3.1 The "FSSA Application Guide Detection & Control for Fire Suppression Systems" offers the designer information of the various typesof detection and control equipment.

Additional Proposed Changes

File Name Description Approved

FSSA_Detection_Suppression_Guide_for_NFPA.pdf FSSA Application Guide Det & Control

Statement of Problem and Substantiation for Public Comment

Information contained in the FSSA Guide will assist the designer in understanding the application techiques involved with an automatic fire detection system.

Submitter Information Verification

Submitter Full Name: John Spalding

Organization: Healey Fire Protection, Inc.

Affilliation: Fire Suppression Systems Association

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 15 13:37:00 EST 2013

Committee Statement

CommitteeAction:

Rejected but see related SR

Resolution: SR-6-NFPA 2001-2014

Statement: Add new annex material. Information contained in the FSSA Guide will assist the designer in understanding the applicationtechiques involved with an automatic fire detection system.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

28 of 32 6/13/2014 2:37 PM

Page 30: National Fire Protection Association Report - nfpa.org · PDF filePublic Comment No. 4-NFPA 2001-2013 [ Section No. 4.1.4.4 ] 4.1.4.4 A means for determining pressure shall be provided

Public Comment No. 9-NFPA 2001-2013 [ Section No. A.7.7.2.1 ]

A.7.7.2.1

A sample test report is provided in Figure A.7.7.2.1. An alternate form which includes the review of mechanical components, 7.7.2.2(7.7.2.2.1 - 7.7.2.2.13) and the review of electrical components 7.7.2.4 (7.7.2.4.1 - 7.7.2.4.14) to the satisfaction of the authority havingjurisdiction may be used.

Figure A.7.7.2.1 Sample Acceptance Test Report.

Statement of Problem and Substantiation for Public Comment

The added text allows the installing contractor to utilize their standard or modified forms to document the specific installed system.

Submitter Information Verification

Submitter Full Name: John Spalding

Organization: Healey Fire Protection, Inc.

Affilliation: Fire Suppression Systems Association

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 15 13:08:47 EST 2013

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

29 of 32 6/13/2014 2:37 PM

Page 31: National Fire Protection Association Report - nfpa.org · PDF filePublic Comment No. 4-NFPA 2001-2013 [ Section No. 4.1.4.4 ] 4.1.4.4 A means for determining pressure shall be provided

Committee Statement

Committee Action: Rejected but see related SR

Resolution: SR-9-NFPA 2001-2014

Statement: The added text allows the use of standard or modified forms to document the specific installed system.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

30 of 32 6/13/2014 2:37 PM

Page 32: National Fire Protection Association Report - nfpa.org · PDF filePublic Comment No. 4-NFPA 2001-2013 [ Section No. 4.1.4.4 ] 4.1.4.4 A means for determining pressure shall be provided

Public Comment No. 18-NFPA 2001-2013 [ Section No. B.4.2.11 ]

B.4.2.11 Pre-Burn Time.

Period between ignition of fuel and start of agent flow. The pre-burn time should be 80 be 95 seconds ± 20 ± 5 seconds.8

Statement of Problem and Substantiation for Public Comment

The target range proposed is too wide, and there is no reason why one cannot achieve a target cup burner pre-burn time within +/- 5 seconds. It is recommended to the previous language.

Submitter Information Verification

Submitter Full Name: Paul Rivers

Organization: 3M Company

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 15 15:07:42 EST 2013

Committee Statement

CommitteeAction:

Rejected

Resolution: The pre-burn time specification is being retained to harmonize with international standards. Test data has shown that the widetolerance does not affect accuracy of the test.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

31 of 32 6/13/2014 2:37 PM

Page 33: National Fire Protection Association Report - nfpa.org · PDF filePublic Comment No. 4-NFPA 2001-2013 [ Section No. 4.1.4.4 ] 4.1.4.4 A means for determining pressure shall be provided

Public Comment No. 12-NFPA 2001-2013 [ Section No. E.1.2.6 ]

E.1.2.6 FSSA Publications.

Fire Suppression Systems Association, 5024-R Campbell Boulevard, Baltimore, MD 21236-5974 (www.faaa.net).

FSSA Application Guide to Estimating Enclosure Pressure Relief Vent Area for Use with Clean Agent Fire Extinguishing Systems, 2nd edition,rev. 1, January 2013.

FSSA Design Guide for Use with Fire Protection Systems Inspection Forms, January 2012.

FSSA Pipe Design Guide for Use with Special Hazard Fire Suppression Systems,2nd ed., 2011.

FSSA Test Guide for Use with Special Hazard Fire Suppression Systems Containers, 3rd edition, January 2012.

FSSA Application Guide Detection & Control for Fire Suppression Systems, November, 2010.

Statement of Problem and Substantiation for Public Comment

Add the document to the reference list for the FSSA, assuming the annex material is adopted.

Submitter Information Verification

Submitter Full Name: John Spalding

Organization: Healey Fire Protection, Inc.

Affilliation: Fire Suppression Systems Association

Street Address:

City:

State:

Zip:

Submittal Date: Fri Nov 15 13:46:14 EST 2013

Committee Statement

Committee Action: Rejected but see related SR

Resolution: SR-7-NFPA 2001-2014

Statement: Add new reference. Correct the publisher's address.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

32 of 32 6/13/2014 2:37 PM