national fire protection association report · aws d10.9, specification for qualification of...

55
First Revision No. 51-NFPA 750-2016 [ Global Input ] Replace every instance of "pressure container" AND "pressurized container" with "pressure vessel". Submitter Information Verification Submitter Full Name: Chelsea Tuttle Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Wed Oct 26 15:10:34 EDT 2016 Committee Statement Committee Statement: The TC has added the definition of pressure vessel for consistency across industry standards and other NFPA documents and is thereby changing the terms that are referenced to be consistent with the added definition. Response Message: National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... 1 of 48 1/9/2017 2:09 PM

Upload: donguyet

Post on 29-Jul-2018

221 views

Category:

Documents


1 download

TRANSCRIPT

First Revision No. 51-NFPA 750-2016 [ Global Input ]

Replace every instance of "pressure container" AND "pressurized container" with "pressure vessel".

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Oct 26 15:10:34 EDT 2016

Committee Statement

CommitteeStatement:

The TC has added the definition of pressure vessel for consistency across industry standards and other NFPA documents and is thereby changing the terms that are referenced to be consistent withthe added definition.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

1 of 48 1/9/2017 2:09 PM

First Revision No. 52-NFPA 750-2016 [ Global Input ]

Replace every instance of "safety device to release excess pressure" with "pressure relief device".

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Oct 26 15:16:00 EDT 2016

Committee Statement

Committee Statement: "Pressure relief device" is defined in Chapter 3 but was not previously used anywhere in the document. This global revision changes relevant terminology to keep consistency with the definition.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

2 of 48 1/9/2017 2:09 PM

First Revision No. 53-NFPA 750-2016 [ Detail ]

The TC voted to include to following text in 2.3.4 in response to PI No 55 and in relation to FR-17.

In the second paragraph following the words 'Revised Guidelines for Approval of Sprinkler Systems' the following text should be included:

and Resolution MSC.265(84) (adopted 9 May 2008) amendments equivalent to those referred to in SOLAS regulation II-2/12 (Resolution A.800(19))

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Oct 31 16:28:58 EDT 2016

Committee Statement

Committee Statement: Upon further inspection of the document referenced in PI No 55, the TC decided that this reference update was appropriate and applicable.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

3 of 48 1/9/2017 2:09 PM

First Revision No. 20-NFPA 750-2016 [ Section No. 2.2 ]

2.2 NFPA Publications.

National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471.

NFPA 13, Standard for the Installation of Sprinkler Systems, 2013 2019 edition.

NFPA 14 Standard for the Installation of Standpipe and Hose Systems, 2013 2016 edition.

NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection, 2013 2019 edition.

NFPA 22, Standard for Water Tanks for Private Fire Protection, 2013 2018 edition.

NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems, 2014 2017 edition.

NFPA 70®, National Electrical Code®, 2014 2017 edition.

NFPA 72®, National Fire Alarm and Signaling Code, 2013 2019 edition.

NFPA 170, Standard for Fire Safety and Emergency Symbols, 2012 2018 edition.

NFPA 220 Standard on Types of Building Construction, 2015 2018 edition.

NFPA 232 Standard for the Protection of Records, 2012 edition.

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Oct 26 09:26:57 EDT 2016

Committee Statement

Committee Statement: Updating NFPA references to most recent revisions

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

4 of 48 1/9/2017 2:09 PM

First Revision No. 21-NFPA 750-2016 [ Section No. 2.3.1 ]

2.3.1 ASME Publications.

American Society of Mechanical Engineers, Three Two Park Avenue, New York, NY 10016-5990.

ASME Boiler and Pressure Vessel Code , 2010.

ANSI/ASME B1.20.1, Pipe Threads, General Purpose (Inch), 2006 2013 .

ANSI/ ASME B16.18, Cast Copper Alloy Solder Joint Pressure Fittings, 2012.

ANSI/ASME B16.22, Wrought Copper and Copper Alloy Solder Joint Pressure Fittings, 2005 2013 .

ASME B31.1, Power Piping Code, 2010 2016 .

Boiler and Pressure Vessel Code , 2015.

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Oct 26 09:29:30 EDT 2016

Committee Statement

Committee Statement: In response to PI No 2. The TC updated the ASME references to the most recent versions and edited the address as written on the ASME standards.

Response Message:

Public Input No. 2-NFPA 750-2015 [Chapter 2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

5 of 48 1/9/2017 2:09 PM

First Revision No. 22-NFPA 750-2016 [ Section No. 2.3.2 ]

2.3.2 ASTM Publications.

ASTM International, 100 Barr Harbor Drive, P. O. Box C700, West Conshohocken, PA 19428-2959.

ASTM A 269 A269/A269M , Standard Specification for Seamless and Welded Austenitic Stainless Steel Tubing for General Service, 2010 2015A .

ASTM A 351/ASTM A 351M A351/A351M , Standard Specification for Castings, Austenitic, Austenitic-Ferritic (Duplex) for Pressure-Containing Parts, 2010 2016 .

ASTM A 403/ASTM A 403M A403/A403M , Standard Specification for Wrought Austenitic Stainless Steel Piping Fittings, 2011 2016 .

ASTM A 632 A632 , Standard Specification for Seamless and Welded Austenitic Stainless Steel Tubing (Small-Diameter) for General Service, 2009 2014 .

ASTM A 774/ASTM A 774M A774/A774M , Standard Specification for As-Welded Wrought Austenitic Stainless Steel Fittings for General Corrosive Service at Low and Moderate Temperatures, 2009 2014 .

ASTM A 778 A778/A778M , Standard Specification for Welded, Unannealed Austenitic Stainless Steel Tubular Products, 2009 2016 .

ASTM A 789/ASTM A 789M A789/A789M , Standard Specification for Seamless and Welded Ferritic/Austenitic Stainless Steel Tubing for General Service, 2010 2016A .

ASTM A 815/ASTM A 815M A815/A815M , Standard Specification for Wrought Ferritic, Ferritic/Austenitic, and Martensitic Stainless Steel Piping Fittings, 2010 2014 .

ASTM B 32 B32 , Standard Specification for Solder Metal, 2008 2014 .

ASTM B 42 B42 , Standard Specification for Seamless Copper Pipe, Standard Sizes, 2010 2015 .

ASTM B 75/B 75M B75/B75M , Standard Specification for Seamless Copper Tube, 2011.

ASTM B 88 B88 , Standard Specification for Seamless Copper Water Tube, 2009 2014 .

ASTM B 251 B251 , Standard Specification for General Requirements for Wrought Seamless Copper and Copper-Alloy Tube, 2010.

ASTM B 813 B813 , Standard Specification for Liquid and Paste Fluxes for Soldering Applications of Copper and Copper-Alloy Tube, 2010 2016 .

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Oct 26 09:32:52 EDT 2016

Committee Statement

Committee Statement: In response to PI No. 2. The TC updated the references to the most recent revisions.

Response Message:

Public Input No. 2-NFPA 750-2015 [Chapter 2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

6 of 48 1/9/2017 2:09 PM

First Revision No. 23-NFPA 750-2016 [ Section No. 2.3.3 ]

2.3.3 AWS Publications.

American Welding Society, 550 N 8669 N .W. LeJeune Road, Miami, FL 33126. 36 Street, #130, Miami, FL 33166-6672.

AWS A5.8M/A5.8, Specification for Filler Metals for Brazing and Braze Welding, 2011.

AWS D10.9, Specification for Qualification of Welding Procedures and Welders for Piping and Tubing , 1980.

AWS B2.1/B2.1M, Specification for Welding Procedure and Performance Qualification , 2014. (Supersedes AWS D10.9)

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Oct 26 09:40:54 EDT 2016

Committee Statement

Committee Statement: In response to PI No 2. The TC corrected the address for AWS and updated the references to the most recent revisions.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

7 of 48 1/9/2017 2:09 PM

First Revision No. 17-NFPA 750-2016 [ Section No. 2.3.4 ]

Detail FR

2.3.4 IMO Publications.

International Maritime Organization, 4, Albert Embankment, London, SEI 7SR, United Kingdom.

IMO Assembly Resolution A.800(19), Revised Guidelines for Approval of Sprinkler Systems , and Resolution MSC.265(84) (adopted 9 May 2008) amendments equivalent to those referred to in SOLASregulation II-2/12 (Resolution A.800(19)).

IMOInternational Code for the Application of Fire Test Procedures , 19982010.

IMO MSC/Circ. 668, Alternative Arrangements for Halon Fire-Extinguishing Systems in Machinery Spaces and Pumprooms .

IMO MSC/Circ. 728, Revised Test Method for Equivalent Water-Based Fire-Extinguishing Systems for Machinery Spaces of Category A and Cargo Pump-Rooms Contained in MSC/Circ. 668 .

IMO MSC/. Circ. 9131165, Revised Guidelines for the Approval of Fixed Water-Based Local Application Fire-Fighting Systems for Use in Category AEquivalent Water-Based Fire-Extinguishing Systems forMachinery Spaces and Cargo Pump Rooms , 19992005.

MSC. Circ. 1387, Revised Guidelines for the Approval of Fixed Water-Based Local Application Fire-Fighting Systems for Use in Category A Machinery Spaces (MSC/CIRC.913), 2010.

SOLAS Regulation 11-2/12.4.1, Consolidated Edition, 20092014.

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Oct 25 18:12:50 EDT 2016

Committee Statement

CommitteeStatement:

IMO Standards referred in this section have been recently replaced by new versions. There is the need to revise NFPA 750 to refer to latest published standards.

A portion of the proposed text "and Resolution MSC.265(84) (adopted on 9 May 2008) amendments to the revised guidelines for Approval of Sprinkler Systems equivalent to that referred to in SOLASregulation II-2/12 (Resolution A.800(19))" was included as a ballotable detail (FR-53) in addition to this first revision.

ResponseMessage:

Public Input No. 55-NFPA 750-2016 [Section No. 2.3.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

8 of 48 1/9/2017 2:09 PM

First Revision No. 24-NFPA 750-2016 [ Section No. 2.3.5 ]

2.3.5 ISO Publications.

International Organization for Standardization, 1 rue de Varembé, Case postale 56, CH-1211 Geneve 20, ISO Central Secretariat BIBC II, 8, Chemin de Blandonnet, CP 401, 1214 Vernier, Geneva,Switzerland.

ISO 1219-1, Fluid power systems and components — Graphic symbols and circuit diagrams — Part 1: Graphic symbols for Conventional Use and Data-Processing Applications , 2006 2012 .

ISO 1219-2, Fluid power systems and components — Graphic symbols and circuit diagrams — Part 2: Circuit diagrams,1995 2012 .

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Oct 26 09:53:03 EDT 2016

Committee Statement

Committee Statement: In response to PI No. 2. The TC updated the address for ISO Publications and updated the references to the most recent revision.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

9 of 48 1/9/2017 2:09 PM

First Revision No. 16-NFPA 750-2016 [ Section No. 2.3.6 ]

2.3.6 ULC Publications.

Underwriters' Laboratories of Canada, 7 Underwriters Road, Toronto, Ontario ON M1R 3B4 3A9 , Canada.

CAN/ULC S524-06 S524-14 , Standard for the Installation of Fire Alarm Systems, 2006 2014 .

CAN/ULC S529-02 S529-16 , Standard for Smoke Detectors for Fire Alarm Systems, 2002 2016 .

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Oct 25 18:03:54 EDT 2016

Committee Statement

Committee Statement: This proposal updates the UL Standards to the current referenced edition.

Response Message:

Public Input No. 71-NFPA 750-2016 [Section No. 2.3.6]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

10 of 48 1/9/2017 2:09 PM

First Revision No. 25-NFPA 750-2016 [ Section No. 2.3.7 ]

2.3.7 U.S. Coast Guard Publications .

2100 Second Street, S.W., 2703 Martin Luther King Jr Ave SE, Stop 7509, Washington, DC 20593-0001 7509 .

NVIC 9-97 CH-1 , Guide to Structural Fire Protection, 2011.

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Oct 26 09:56:59 EDT 2016

Committee Statement

Committee Statement: The TC updated the address for the U.S. Coast Guard Publications and corrected the reference title.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

11 of 48 1/9/2017 2:09 PM

First Revision No. 26-NFPA 750-2016 [ Section No. 2.3.8 ]

2.3.8 U.S. Government Publications .

U.S. Government Printing Publishing Office, 732 North Capitol Street, NW, Washington, DC 20402 20401-0001 .

Title 46, Code of Federal Regulations, Parts 56.50 and 56.75, “Shipping.”

Title 49, Code of Federal Regulations, “Transportation.”

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Oct 26 09:59:36 EDT 2016

Committee Statement

Committee Statement: In response to PI No. 2. The TC updated the address for the US Government Publishing Office.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

12 of 48 1/9/2017 2:09 PM

First Revision No. 27-NFPA 750-2016 [ Section No. 2.3.9 ]

2.3.9 Other Publications.

BS EN-13480-3, Metallic Industrial Piping — Part 3: Code, Design and Calculation,2002 2012 .

Merriam-Webster's Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003.

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Oct 26 10:02:02 EDT 2016

Committee Statement

Committee Statement: In response to PI No. 2. The TC updated the title of the EN reference.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

13 of 48 1/9/2017 2:09 PM

First Revision No. 28-NFPA 750-2016 [ Section No. 2.4 ]

2.4 References for Extracts in Mandatory Sections.

NFPA 1, Fire Code, 2018 edition.

NFPA 13, Standard for the Installation of Sprinkler Systems, 2013 2016 edition.

NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection, 2013 2016 edition.

NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems, 2014 2017 edition.

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Oct 26 10:04:49 EDT 2016

Committee Statement

Committee Statement: The TC updated the references for the NFPA standards to the most recent revisions.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

14 of 48 1/9/2017 2:09 PM

First Revision No. 49-NFPA 750-2016 [ New Section after 3.3.9 ]

3.3.10 Gridded Water Mist System.

A water mist system in which parallel cross mains are connected by multiple branch lines, causing an operating nozzle to receive water from both ends of its branch line while other branch lines help transferwater between cross mains.

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Oct 26 14:55:37 EDT 2016

Committee Statement

Committee Statement: "Gridded water mist systems" is used in the document so the TC is defining it in Chapter 3.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

15 of 48 1/9/2017 2:09 PM

First Revision No. 50-NFPA 750-2016 [ New Section after 3.3.15 ]

3.3.17 Pressure Vessel.

A container, process vessel, or other component designed in accordance with the ASME Boiler and Pressure Vessel Code , DOT, or other approved standards. [ 1, 2018]

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Oct 26 15:01:55 EDT 2016

Committee Statement

CommitteeStatement:

The TC is changing "pressure container" to "pressure vessel" to establish consistency throughout the industry and other NFPA standards. The term is being defined here because it is used widelythroughout the document.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

16 of 48 1/9/2017 2:09 PM

First Revision No. 1-NFPA 750-2016 [ Section No. 3.3.24.1 ]

3.3.26.1 Deluge Water Mist System.

A water mist system utilizing nonautomatic mist nozzles (open) attached to a piping network connected to the fluid supply(ies) directly or through a valve controlled by an independent detection systeminstalled in the same area as the mist nozzles.

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Oct 25 09:52:43 EDT 2016

Committee Statement

Committee Statement: There are listed solutions that do not require a valve to be installed between nozzles and water supply. By adding “directly” we will allow the use of these listed solutions under this definition.

Response Message:

Public Input No. 59-NFPA 750-2016 [Section No. 3.3.24.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

17 of 48 1/9/2017 2:09 PM

First Revision No. 54-NFPA 750-2016 [ Section No. 6.4.2.10 ]

6.4.2.10

Welding shall be performed in accordance with AWS D10.9 B2.1/B2.1M , Specification for Qualification of Welding Procedures and Welders for Piping and Tubing Specification for Welding Procedure andPerformance Qualification , Level AR-3.

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 21 15:57:20 EST 2016

Committee Statement

Committee Statement: AWS B2.1/B2.1M supercedes AWS D10.9.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

18 of 48 1/9/2017 2:09 PM

First Revision No. 7-NFPA 750-2016 [ Section No. 7.4.3 ]

7.4.3 Preaction Systems.

7.4.3.1

Preaction systems shall employ automatic nozzles attached to a piping network containing a pressurized gas with a supplemental, independent detection system installed in the same area as the nozzles.

7.4.3.2

Preaction systems shall be one of the following types:

(1) A non-interlock system, which admits water to the water mist system on operation of the detection devices or automatic water mist nozzles

(2) A single interlock system, which admits water to the water mist system piping on actuation of detection devices

(3) A double interlock system, which admits water to the water mist system piping on operation of both detection devices and automatic nozzles

7.4.3.3

Preaction systems shall be designed and installed in accordance with the specifications developed for their listing in accordance with 9.4.5 .

7.4.3.4

Preaction systems shall not use a gridded piping configuration.

7.4.3.5

The preaction system size shall be designed to deliver water mist to the most remote nozzle at no more than the maximum water mist delivery time from the listing for the application, starting at the normal airpressure on the system, with the detection system activated and the inspection test connection located for the most remote automatic nozzle fully opened simultaneously.

7.4.3.6

System operation tests shall be conducted to verify the actual water mist delivery time in accordance with 14.2.6 .

7.4.3.7

The pressurized piping in all preaction systems shall be supervised to ensure system integrity.

7.4.3.8

Operation of the detection system shall actuate a listed tripping device that opens the valve, pressurizing the pipe network with water to the automatic nozzles.

7.4.3.8.1

The listed tripping device shall be provided with hydraulic, pneumatic, or mechanical manual means for operation that is independent of detection devices and of the automatic water mist nozzles.

7.4.3.9

The automatic detection for the preaction system shall be provided in accordance with 6.10.2 .

7.4.3.9

The pressurized piping in all preaction systems shall be supervised to ensure system integrity.

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Oct 25 13:57:43 EDT 2016

Committee Statement

Committee Statement: Additional guidance is needed to properly design and install preaction water mist systems.

Response Message:

Public Input No. 72-NFPA 750-2016 [Section No. 7.4.3]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

19 of 48 1/9/2017 2:09 PM

First Revision No. 8-NFPA 750-2016 [ Section No. 7.5 ]

7.5* Media System Types.

Water mist systems shall be classified by two media system types:

(1) Single fluid

(2) Twin fluid

(a) Comprising water and atomizing media

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Oct 25 14:44:45 EDT 2016

Committee Statement

Committee Statement: This modification further supports the definition of twin-fluid system in section 3.3.20

Response Message:

Public Input No. 68-NFPA 750-2016 [New Section after 7.1]

Public Input No. 67-NFPA 750-2016 [Section No. 7.5]

Public Input No. 70-NFPA 750-2016 [New Section after A.6.10.4.3.1]

Public Input No. 69-NFPA 750-2016 [Section No. A.7.5]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

20 of 48 1/9/2017 2:09 PM

First Revision No. 19-NFPA 750-2016 [ Section No. 8.1.1 ]

8.1.1* Listing.

Listed materials and devices shall be installed in accordance with their listing.

Supplemental Information

File Name Description

Annex_8.1.1.docx New annex material for 8.1.1

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Oct 26 09:17:49 EDT 2016

Committee Statement

Committee Statement: The addition of this annex material explains that end users should not mix different listed components/systems into one system that was never designed or tested together.

Response Message:

Public Input No. 78-NFPA 750-2016 [Section No. 9.2.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

21 of 48 1/9/2017 2:09 PM

A.8.1.1.

Designs based on individually listed components should be permitted to

utilize compatible listed components from different manufacturers

provided their use is within the scope of their individual listings.

Products listed as complete systems should utilize only those

components included in the listing in accordance with the limitations of

the listing and installation instructions. Use of components outside the

scope of the listing may void the listing.

First Revision No. 18-NFPA 750-2016 [ Section No. 8.5.5.3.2 ]

8.5.5.3.2*

When any cylinder is removed for maintenance, automatic means shall be provided to prevent leakage from the manifold if the system is operated.

Supplemental Information

File Name Description

Annex_8.5.5.3.2.docx Annex material for FR-18

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Oct 26 08:55:16 EDT 2016

Committee Statement

Committee Statement: This annex addition provides clarification on the possible devices to be used as automatic means.

Response Message:

Public Input No. 77-NFPA 750-2016 [Section No. 8.5.5.3.2]

Public Input No. 62-NFPA 750-2016 [Section No. 8.5.5.3.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

22 of 48 1/9/2017 2:09 PM

A.8.5.5.3.2

As an example, automatic means may comprise of check valves installed in between the manifold and

the cylinder. This automatic means provides personnel safety in a recurring maintenance activity while

allowing the system to remain in service.

First Revision No. 5-NFPA 750-2016 [ New Section after 9.4 ]

9.4.5 Preaction Systems.

The listing requirements for a preaction water mist system shall be based upon the following:

(1) Type of preaction system

(2) Maximum water mist delivery time from the fire test(s) for the listing of the specific hazard or occupancy but not to exceed 60 seconds

9.4.5.1

If a calculation method is used to determine water mist delivery time, it shall be tested and validated as part of the listing program.

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Oct 25 12:55:37 EDT 2016

Committee Statement

CommitteeStatement:

Additonal guidance is needed to properly design a preaction water mist system. The specifications to be used for a preaction water mist system need to developed from testing as part of the listingprocess. This Public Input identifies the critical parameters that need to be evaluated for those specifications.

ResponseMessage:

Public Input No. 73-NFPA 750-2016 [New Section after 9.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

23 of 48 1/9/2017 2:09 PM

First Revision No. 9-NFPA 750-2016 [ Section No. 12.5.4.6 ]

12.5.4.6*

A reliable means shall be provided to indicate the pressure and level in all storage containers that will be pressurized.

Supplemental Information

File Name Description

Annex_12.5.4.6.docx New annex material for 12.5.4.6 in response to PI 80

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Oct 25 16:43:23 EDT 2016

Committee Statement

CommitteeStatement:

This addition will clarify that manufacturers with a common manifold system can use just one pressure indicating device to accomplish the intent of section 12.5.4.6 across all pressurized storagecontainers provided they are not isolated from one another or from the manifold.

ResponseMessage:

Public Input No. 80-NFPA 750-2016 [Section No. 12.5.4.6]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

24 of 48 1/9/2017 2:09 PM

A.12.5.4.6

Applications with multiple pressure containers may include a common manifold, provided it is not

possible to isolate an individual container from the pressure indicator or isolate the containers from one

another.

First Revision No. 44-NFPA 750-2016 [ New Section after 12.5.5.2 ]

12.5.5.3

The fire department connection shall comply with the strainer or filter requirements of 12.5.1.5 .

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Oct 26 12:28:36 EDT 2016

Committee Statement

Committee Statement: The TC added this section to identify the importance of having a strainer or filter after the FDC to prevent debris/contaminants from entering the water mist system and affecting its performance.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

25 of 48 1/9/2017 2:09 PM

First Revision No. 43-NFPA 750-2016 [ Section No. 12.5.5.3 ]

12.5.5.4

For water mist systems with system design pressures less than or equal to 12 bar (175 psi), the connection of the fire department connection to the system shall be made on the upstream downstream(supply discharge ) side of the system strainer or filter pressure source component .

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Oct 26 12:06:36 EDT 2016

Committee Statement

Committee Statement: The TC edited the language to clarify the proper placement of the FDC on a low pressure water mist system.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

26 of 48 1/9/2017 2:09 PM

First Revision No. 45-NFPA 750-2016 [ Section No. 12.5.5.4 ]

12.5.5.5

For water mist systems with system design pressures in excess of 12 bar (175 psi), the connection of the fire department connection to the system shall be made on the upstream (suction) suction side of thepressure source components.

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Oct 26 12:31:05 EDT 2016

Committee Statement

Committee Statement: The TC added minor language to keep consistency with section 12.5.5.4 above it.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

27 of 48 1/9/2017 2:09 PM

First Revision No. 6-NFPA 750-2016 [ New Section after 14.2.6.5 ]

14.2.6.6

It shall be verified for preaction water mist systems that the actual water mist delivery time is in accordance with the design of the water mist system.

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Oct 25 13:18:29 EDT 2016

Committee Statement

Committee Statement: Preaction water mist systems need to be validated for proper installation to their design specification as part of their listing in order to ensure proper performance for fire suppression.

Response Message:

Public Input No. 74-NFPA 750-2016 [New Section after 14.2.6.5]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

28 of 48 1/9/2017 2:09 PM

First Revision No. 55-NFPA 750-2016 [ Section No. 16.1.2.2 ]

16.1.2.2

Flammable liquid hazard systems shall comply with fire suppression and components manufacturing tests contained in IMO MSC/Circ. 1165, 668, Alternative Arrangements for Halon Fire-ExtinguishingSystems in Machinery Spaces and Pumprooms , as amended by IMO MSC/Circ. 728, Revised Test Method for Guidelines for the Approval of Equivalent Water-Based Fire-Extinguishing Systems forMachinery Spaces of Category A and Cargo Pump-Rooms Contained in MSC/Circ. 668 .

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: National Fire Protection Assoc

Street Address:

City:

State:

Zip:

Submittal Date: Tue Nov 22 15:32:48 EST 2016

Committee Statement

Committee Statement: MSC/Circ. 1165 replaced MSC/Circ. 668 and 728. This was updated in Chapter 2, Referenced Publications, so this was changed for consistency.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

29 of 48 1/9/2017 2:09 PM

First Revision No. 42-NFPA 750-2016 [ Section No. 16.2.11.5 ]

16.2.11.5*

For light hazard public and accommodation spaces, the design area shall be the deck area of the most hydraulically demanding compartment up to a maximum of 140 m2 (1500 ft2).

Supplemental Information

File Name Description

Annex_16.2.11.5.docx Annex material for FR-42

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Oct 26 11:45:13 EDT 2016

Committee Statement

Committee Statement: Annex material was added to provide guidance for the users of NFPA 750. It notifies the readers that the SOLAS design criteria may be different.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

30 of 48 1/9/2017 2:09 PM

A.16.2.11.5

The design criteria for light hazard public and accommodation spaces for SOLAS certificated

vessels may be different than that listed in 16.2.11.5. See IMO Assembly Resolution A.800(19).

First Revision No. 10-NFPA 750-2016 [ Section No. 16.3.9.1 ]

16.3.9.1

Systems for machinery spaces shall be capable of fire extinguishment without the necessity of engine shutdown, personnel evacuation, shutdown of forced ventilation fans, or the sealing of the space asdemonstrated by fire testing in accordance with IMO MSC / Circ. 913 1387 , Revised Guidelines for the Approval of Fixed Water-Based Local Application Fire-Fighting Systems for Use in Category AMachinery Spaces (MSC/CIRC.913) .

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Oct 25 17:27:26 EDT 2016

Committee Statement

Committee Statement: IMO Standards referred in this section have been recently replaced by new versions. There is the need to revise NFPA 750 to refer to latest published standards.

Response Message:

Public Input No. 60-NFPA 750-2016 [Section No. 16.3.9.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

31 of 48 1/9/2017 2:09 PM

First Revision No. 11-NFPA 750-2016 [ Section No. 16.3.9.2 ]

16.3.9.2

Component testing shall be in accordance with the following provisions of Appendix A of IMO MSC/Circ. 728 1165 , Revised Test Method Guidelines for the Approval of Equivalent Water-BasedFire-Extinguishing Systems for Machinery Spaces of Category A and Cargo Pump Rooms: Contained in MSC/Circ. 668 .

(1) MSC/Circ. 668 1165 , Section 3.4, “Water Flow and Distribution”

(2) MSC/Circ. 668 1165 , Section 3.6, “Strength of Body”

(3) MSC/Circ. 668 1165 , Section 3.11, “Corrosion”

(4) MSC/Circ. 668 1165 , Section 3.15, “Resistance to Heat”

(5) MSC/Circ. 668 1165 , Section 3.16, “Resistance to Vibration (Plus Functional Test in 3.5.2 Only)”

(6) MSC/Circ. 668 1165 , Section 3.17, “Impact”

(7) MSC/Circ. 668 1165 , Section 3.22, “Clogging”

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Oct 25 17:32:02 EDT 2016

Committee Statement

Committee Statement: IMO Standards referred to in this section have been recently replaced by new versions. There is the need to revise NFPA 750 to refer to latest published standards.

Response Message:

Public Input No. 61-NFPA 750-2016 [Section No. 16.3.9.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

32 of 48 1/9/2017 2:09 PM

First Revision No. 32-NFPA 750-2016 [ Section No. A.1.6 ]

A.1.6

For additional conversions and information, see ASTM E 380 SI10 , American National Standard Practice for Use of the International System of Units (SI): (the Modernized Metric System) The Modern MetricSystem , and in Canada, refer to CSA CAN3-A234.1 CAN/CSA-Z234.1-00 , Canadian Metric Practice Guide.

The abbreviation “gal” in Table 1.6.3 indicates the U.S. gallon measure.

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Oct 26 10:27:22 EDT 2016

Committee Statement

Committee Statement: The ASTM and CSA references were replaced with the most recent versions.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

33 of 48 1/9/2017 2:09 PM

First Revision No. 12-NFPA 750-2016 [ Section No. A.4.1 ]

A.4.1

A water mist system is a water-based fire protection system using very fine water sprays (i.e., water mist). The very small water droplets allow t./he the water mist to control or extinguish fires by cooling of theflame and fire plume, oxygen displacement by water vapor, radiant heat attenuation, and prevention of fire spread by pre-wetting of combustibles.

Water mist systems have proved effective in controlling, suppressing, or extinguishing many types of fires. Potential applications include the following:

(1) Gas jet fires

(2) Flammable and combustible liquids, including storage

(3) Hazardous solids, including fires involving plastic foam furnishings

(4) Protection of aircraft occupants from an external pool fire long enough to provide time to escape

(5) Ordinary (Class A) combustible fires such as paper, wood, and textiles

(6) Occupancy classifications in accordance with Chapter 5

(7) Electrical hazards, such as transformers, switches, circuit breakers, and rotating equipment rotating equipment, and cable tunnels

(8) Electronic equipment, including telecommunications equipment

(9) Highway and railway tunnels (see NFPA 502) , Standard for Road Tunnels, Bridges, and Other Limited Access Highways )

(10) Fighter aircraft hangars, light aircraft hangars, and helicopter hangars

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Oct 25 17:35:14 EDT 2016

Committee Statement

Committee Statement: The TC added further examples of where water mist systems have been demonstrated successfully.

Response Message:

Public Input No. 81-NFPA 750-2016 [Section No. A.4.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

34 of 48 1/9/2017 2:09 PM

First Revision No. 13-NFPA 750-2016 [ Section No. C.1.2 ]

C.1.2

Table C.1.2 identifies several organizations with wide international recognition that currently develop or administer test protocols for water mist fire suppression systems. The following sections provide briefdescriptions of the scope of application and the acceptance criteria of the test protocols that are the basis for the 1998 listings for water mist systems. The testing laboratories can add or subtract certain firetests, at their discretion, based on their interpretation of the system performance limits. The reader should refer to the original test protocols for complete test details.

Table C.1.2 Internationally Recognized Agencies with Published Fire Test Protocols for Water Mist Fire Protection Systems

Agency Water Mist Fire Test Protocol

1. International Maritime Organization,

London, EnglandIMO MSC/Circ. 668, Alternative Arrangements for Halon Fire-Extinguishing Systems in Machinery Spaces and Pump-Rooms.

(a) Appendix A, “Component Manufacturing Standards of Equivalent Water-Based Fire Extinguishing Systems,” 1994.

(b) Appendix B, “Interim Test Method for Fire Testing Equivalent Water-Based Fire-Extinguishing Systems for Machinery Spaces of Category A andCargo Pump-Rooms,” 1994.

As amended in MSC/Circ. 728, Amendments to the Test Method for Equivalent Water-Based Fire-Extinguishing Systems for Machinery Spaces ofCategory A and Cargo Pump-Rooms Contained in MSC/Circ. 668, Appendix B, June 1996.

IMO Res. A.800 (19), Revised Guidelines for Approval of Sprinkler Systems, Equivalent to that That Referred referred to in SOLAS RegulationII-2/12 .

(a) Appendix 1, “Component Manufacturing Standards for Water Mist Nozzles.”

(b) Appendix 2, “Fire Test Procedures for Equivalent Sprinkler Systems in Accommodation, Public Space and Service Areas on Passenger Ships,”December 1995.

2. FM Approvals, 1151 Boston-Providence Turnpike, P.O.Box 9102, Norwood, MA, 02062.

ANSI/FM Approvals 5560, American National Standard for Water Mist Systems, December 2007.FM Approvals 5560, Approval Standard for WaterMist Systems , March 2009.

(a) Fire Tests for Water Mists Systems for the Protection of Combustion Turbines with Volumes up to, and including, 2825 ft3 (80 m3)

(b) Fire Tests for Water Mists Systems for the Protection of Combustion Turbines with Volumes up to, and including, 9175 ft3 (260 m3)

(c) Fire Tests for Water Mists Systems for the Protection of Combustion Turbines with Volumes Exceeding 9175 ft3 (260 m3)

(d) Fire Tests for Water Mists Systems for the Protection of Wet Benches and Other Similar Processing Equipment

(e) Fire Tests for Water Mists Systems for the Protection of Local Applications

(f) Fire Tests for Water Mists Systems for the Protection of Industrial Oil Cookers

(g) Fire Tests for Water Mists Systems for the Protection of Computer Room Sub Floors

(h) General Requirements

(i) Performance Requirements (Water Mist Nozzles and System Components)

(j) Operations Requirements

FM Approvals Class Number 5560, Approval Standard for Water Mist Systems, April 2016

(a) Fire Tests for Water Mists Systems for the Protection of Machinery in Enclosures with Volumes not Exceeding 2825 ft3 (80 m3)

(b) Fire Tests for Water Mists Systems for the Protection of Combustion Turbines in Enclosures with Volumes not Exceeding 2825 ft3 (80 m3)

(c) Fire Tests for Water Mists Systems for the Protection of Machinery in Enclosures with Volumes not Exceeding 9175 ft3 (260 m3)

(d) Fire Tests for Water Mists Systems for the Protection of Combustion Turbines in Enclosures with Volumes not Exceeding 9175 ft3 (260 m3)

(e) Fire Tests for Water Mists Systems for the Protection of Machinery in Enclosures with Volumes Exceeding 9175 ft3 (260 m3)

(f) Fire Tests for Water Mists Systems for the Protection of Combustion Turbines in Enclosures with Volumes Exceeding 9175 ft3 (260 m3)

(g) Fire Tests for Water Mists Systems for the Protection of Light Hazard Occupancies

(h) Fire Tests for Water Mists Systems for the Protection of Wet Benches and Other Similar Processing Equipment

(i) Fire Tests for Water Mists Systems for the Protection of Local Applications

(j) Fire Tests for Water Mists Systems for the Protection of Industrial Oil Cookers

(k) Fire Tests for Water Mists Systems for the Protection of Computer Room Sub Floors. Continuous Wood Board Presses

(l) Fire Tests for Water Mists Systems for the Protection of Continuous Wood Board Presses Chemical Fume Hoods

(m) General Requirements Fire Tests for Water Mists Systems for the Protection of Data Processing Equipment Rooms/Halls – Above Raised Floor

(n) Performance Requirements (Water Mist Nozzles and System Components) Fire Tests for Water Mists Systems for the Protection of DataProcessing Equipment Rooms/Halls – Below Raised Floor

(o) Operations Requirements Scaling Methodology: Fire Tests for the Protection of Machinery and Combustion Turbines in Enclosures in ½-Scale

3. Underwriters Laboratories Inc.,

Northbrook, IL, USAANSI/UL 2167, Standard for Water Mist Nozzles for Fire Protection Service [contents can be read from the standard]

4.CEN, EuropeCEN/TS 14972, Fixed firefighting systems — watermist Watermist systems — design Design and installation [contents can be read from thestandard]

5. IMO International Code for Application of Fire Test Procedures, 2012

Supplemental Information

File Name Description

PI_No_64.docx Annex table changes for PI No 64. For staff use

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Oct 25 17:44:02 EDT 2016

Committee Statement

Committee Statement: Updating references to FM Approvals Standard Class 5560, Water Mist Systems, to be in line with current published version of the document.

Public Input No. 64-NFPA 750-2016 [Section No. C.1.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

35 of 48 1/9/2017 2:09 PM

Table C.1.2 Internationally Recognized Agencies with Published Fire Test Protocols for Water Mist Fire Protection Systems

Agency Water Mist Fire Test Protocol

1. International Maritime Organization,London, England

IMO MSC/Circ. 668, Alternative Arrangements for Halon Fire-Extinguishing Systems in Machinery Spaces and Pump-Rooms. (a) Appendix A, “Component Manufacturing Standards of EquivalentWater-Based Fire Extinguishing Systems,” 1994.(b) Appendix B, “Interim Test Method for Fire Testing Equivalent Water-BasedFire-Extinguishing Systems for Machinery Spaces of Category A and CargoPump-Rooms,” 1994.As amended in MSC/Circ. 728, Amendments to the Test Method for EquivalentWater-Based Fire-Extinguishing Systems for Machinery Spaces of Category A and Cargo Pump-Rooms Contained in MSC/Circ. 668, Appendix B, June 1996.

IMO Res. A.800 (19), Revised Guidelines for Approval of Sprinkler Systems, Equivalent to that referred to in SOLAS Regulations II-2/12. (a) Appendix 1, “Component Manufacturing Standards for Water Mist Nozzles.”(b) Appendix 2, “Fire Test Procedures for Equivalent Sprinkler Systems inAccommodation, Public Space and Service Areas on Passenger Ships,” December1995.

2. FM Approvals, 1151 Boston-ProvidenceTurnpike, P.O. Box 9102, Norwood, MA,02062.

ANSI/FM Approvals 5560, American National Standard for Water Mist Systems, December 2007. FM Approvals 5560, Approval Standard for Water Mist Systems, March 2009. (a) Fire Tests for Water Mists Systems for the Protection of Combustion Turbines withVolumes up to, and including, 2825 ft3 (80 m3)(b) Fire Tests for Water Mists Systems for the Protection of Combustion Turbines withVolumes up to, and including, 9175 ft3 (260 m3)(c) Fire Tests for Water Mists Systems for the Protection of Combustion Turbines withVolumes Exceeding 9175 ft3 (260 m3)(d) Fire Tests for Water Mists Systems for the Protection of Wet Benches and OtherSimilar Processing Equipment(e) Fire Tests for Water Mists Systems for the Protection of Local Applications(f) Fire Tests for Water Mists Systems for the Protection of Industrial Oil Cookers(g) Fire Tests for Water Mists Systems for the Protection of Computer Room SubFloors(h) General Requirements(i) Performance Requirements (Water Mist Nozzles and System Components)(j) Operations Requirements

FM Approvals Class Number 5560, Approval Standard for Water Mist Systems, April 2016 (a) Fire Tests for Water Mists Systems for the Protection of Machinery in Enclosureswith Volumes not Exceeding 2825 ft3 (80 m3)(b) Fire Tests for Water Mists Systems for the Protection of Combustion Turbines inEnclosures with Volumes not Exceeding 2825 ft3 (80 m3)(c) Fire Tests for Water Mists Systems for the Protection of Machinery in Enclosureswith Volumes not Exceeding 9175 ft3 (260 m3)(d) Fire Tests for Water Mists Systems for the Protection of Combustion Turbines inEnclosures with Volumes not Exceeding 9175 ft3 (260 m3)(e) Fire Tests for Water Mists Systems for the Protection of Machinery in Enclosureswith Volumes Exceeding 9175 ft3 (260 m3)(f) Fire Tests for Water Mists Systems for the Protection of Combustion Turbines inEnclosures with Volumes Exceeding 9175 ft3 (260 m3)(g) Fire Tests for Water Mists Systems for the Protection of Light Hazard Occupancies(h) Fire Tests for Water Mists Systems for the Protection of Wet Benches and OtherSimilar Processing Equipment(i) Fire Tests for Water Mists Systems for the Protection of Local Applications(j) Fire Tests for Water Mists Systems for the Protection of Industrial Oil Cookers(k) Fire Tests for Water Mists Systems for the Protection of Computer Room SubFloors Continuous Wood Board Presses

2015 Edition

ANNEX C 750–67

Table C.1.2 Continued

Agency Water Mist Fire Test Protocol

(l) Fire Tests for Water Mists Systems for the Protection of Continuous Wood Board Presses Chemical Fume Hoods (m) General Requirements Fire Tests for Water Mists Systems for the Protection of Data

Processing Equipment Rooms/Halls – Above Raised Floor (n) Performance Requirements (Water Mist Nozzles and System Components) Fire Tests for

Water Mists Systems for the Protection of Data Processing Equipment Rooms/Halls – Below Raised Floor

(o) Operations Requirements Scaling Methodology: Fire Tests for the Protection of Machinery and Combustion Turbines in Enclosures in ½-Scale

3. Underwriters Laboratories Inc., Northbrook, IL, USA

ANSI/UL 2167, Standard for Water Mist Nozzles for Fire Protection Service [contents can be read from the standard]

4. CEN, Europe CEN/TS 14972, Fixed firefighting systems — watermist systems — design and installation [contents can be read from the standard]

5. IMO International Code for Application of Fire Test Procedures, 2012

First Revision No. 14-NFPA 750-2016 [ Sections C.3.12, C.3.13 ]

C.3.12 Computer Room Subfloors.

Typical occupancies within the scope of this application are defined in FM Global Property Loss Prevention Data Sheet Numbers 4-2, Water Mist Systems , and 5-32, Electronic Data Processing Systems .System installations are limited to computer room subfloor areas and heights not exceeding those tested. Additionally, the equivalent opening area of the subfloor cannot exceed those tested. The agentsupply should be capable of supplying agent to all nozzles at the maximum rated operating pressure for a minimum of twice the longest time to extinguish the test fires or 10 minutes, whichever is greater.This protocol evaluates only the fire extinguishment capabilities of the water mist system. An evaluation of the smoke-cleansing capabilities is not made. Consultation with FM Global Property LossPrevention Data Sheet Numbers 4-2, Water Mist Systems , and 5-32, Electronic Data Processing Systems , is required for installation of these systems.

C.3.12 Continuous Wood Board Presses.

This application is further defined in FM Global Property Loss Prevention Data Sheet Number 7-10, Wood Processing and Woodworking Facilities. Application of the water mist system is limited to theprotection of the continuous wood board press only and does not include the protection of other equipment unless tested for other applications. All hazards included under the scope of this application are to beprotected for a minimum of twice the longest time to extinguish the test fires or 30 minutes, whichever is greater. Consultation with FM Global Property Loss Prevention Data Sheet Numbers 4-2, Water MistSystems, and 7-10, Wood Processing and Woodworking Facilities, is required for installation of these systems.

C.3.13 Data Centers and Related Facilities.

This application includes protection of data center processing equipment rooms/halls, which include control rooms, process control rooms, diagnostic equipment, and critical systems and equipmentassociated with data centers. This application is further defined in FM Global Property Loss Prevention Datasheet 5-32, Data Centers and Related Facilities . Forced ventilation is included in the evaluationto a maximum nominal upward velocity of 1 m/s (3.3 ft/s) through perforated floor openings and a maximum 1.2 m/s (4 ft/sec) horizontal airflow from server cabinets. Preaction systems are limited to singleinterlock configurations with a maximum 30-second water delivery time delay.

For above raised floor protection, the water supply should be capable of supplying 60 minutes of water to the hydraulically most remote nozzles. The design area of the water mist system should be 6 nozzlesor 1.5 times the number of operated nozzles during fire performance testing, whichever is greater. For below raised floor protection, the water supply should be capable of supplying 60 minutes of water tothe hydraulically most remote nozzles. The design area of the water mist system should be a minimum of 6 nozzles for an area of coverage design and a minimum of 4 nozzles for a local application design.For an installation that includes both above and below raised floor protection, the design area of the water mist system should be based on the most hydraulically demanding protection.

The systems are for the protection of data and power cables with a maximum fire propagating index (FPI) of 26 in the metric unit when tested in accordance with FM Approvals 3972, Test Standard forCable Fire Propagation . Alternative cables with a higher FPI can be used based on the manufacturer’s intended applications for protection, and approval will be limited to cables with FPIs less than or equalto the tested cable. The systems are not intended to protect data processing equipment with packaging awaiting installation. Packaged equipment is to be located in storage and staging areas separate fromdata processing equipment rooms (i.e., where fire involving the storage will not expose critical equipment). Where storage and staging areas are not available, limit in-process packaged equipment in dataprocessing equipment rooms to a temporary basis with regular removal of the packaging during the installation.

The systems are tested and listed to provide primary protection of the occupancy. The systems have been proven to extinguish fire involving cables but are not intended to provide equipment protection.

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Oct 25 17:49:05 EDT 2016

Committee Statement

Committee Statement: Updated FM Approvals fire test protocols to match those published in the current published revision of FM Approvals Standard Class 5560, Water Mist Systems, April 2016.

Response Message:

Public Input No. 65-NFPA 750-2016 [Sections C.3.12, C.3.13]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

36 of 48 1/9/2017 2:09 PM

First Revision No. 29-NFPA 750-2016 [ Section No. E.1.1 ]

E.1.1 NFPA Publications.

National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471.

NFPA 4, Standard for Integrated Fire Protection and Life Safety System Testing, 2015 2018 edition.

NFPA 13, Standard for the Installation of Sprinkler Systems, 2013 2019 edition.

NFPA 14, Standard for the Installation of Standpipe and Hose Systems, 2013 edition.

NFPA 15, Standard for Water Spray Fixed Systems for Fire Protection, 2012 2017 edition.

NFPA 20, Standard for the Installation of Stationary Pumps for Fire Protection, 2013 2019 edition.

NFPA 70®, National Electrical Code®, 2014 2017 edition.

NFPA 232, Standard for the Protection of Records, 2012 2017 edition.

NFPA 502, Standard for Road Tunnels, Bridges, and Other Limited Access Highways, 2014 2017 edition.

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Oct 26 10:08:11 EDT 2016

Committee Statement

Committee Statement: The TC updated the NFPA publications to the most recent revisions.

NFPA 14 removed because no longer referenced in the Annex chapters.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

37 of 48 1/9/2017 2:09 PM

First Revision No. 30-NFPA 750-2016 [ Section No. E.1.2.2 ]

E.1.2.2 ASME Publications.

American Society of Mechanical Engineers, Three Two Park Avenue, New York, NY 10016-5990 .

ANSI/ASME B31.1, Power Piping Code, 1998 2016 .

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Oct 26 10:11:10 EDT 2016

Committee Statement

Committee Statement: In response to PI No. 3. The TC updated the address for ASME and updated the reference to the most recent revision.

Response Message:

Public Input No. 3-NFPA 750-2015 [Chapter E]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

38 of 48 1/9/2017 2:09 PM

First Revision No. 31-NFPA 750-2016 [ Section No. E.1.2.3 ]

E.1.2.3 ASTM Publications.

ASTM International, 100 Barr Harbor Drive, P. O. Box C700, West Conshohocken, PA 19428-2959.

ASTM E 380, Standard Practice for Use of the International System of Units (SI) (the Modernized Metric System) , 1993.

ASTM E799, Standard Practice for Determining Data Criteria and Processing for Liquid Drop Size Analysis, 1992 2003 (reapproved 2015) .

ASTM F1547, Standard Guide Listing Relevant Standards and Publications for Commercial Shipbuilding, 1994. (Withdrawn)

ASTM SI10, American National Standard for Use of the International System of Units (SI): The Modern Metric System , 2010.

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Oct 26 10:12:49 EDT 2016

Committee Statement

Committee Statement: In response to PI No. 3. The TC updated the references to the most recent revisions, including the addition of ASTM SI10 which replaced ASTM E380.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

39 of 48 1/9/2017 2:09 PM

First Revision No. 33-NFPA 750-2016 [ Section No. E.1.2.5 ]

E.1.2.5 CSA Publications.

Canadian Standards Association, 5060 Spectrum Way, Mississauga, Ontario, L4W 5N6, Canada. CSA Group, 178 Rexdale Blvd., Toronto, ON Canada M9W 1R3.

CAN3-A234.1, CAN/CSA-Z234.1-00 Canadian Metric Practice Guide, 1979 2011. (Withdrawn) .

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Oct 26 10:31:28 EDT 2016

Committee Statement

Committee Statement: In response to PI No. 3. The TC updated the reference title and date to the most recent revision.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

40 of 48 1/9/2017 2:09 PM

First Revision No. 15-NFPA 750-2016 [ Section No. E.1.2.6 ]

E.1.2.6 FM Approvals Publications LLC .

FM Approvals, 1151 Boston-Providence Turnpike, P.O. Box 9102, Norwood, MA, 02062.

FM Approvals 3972, Test Standard for Cable Fire Propagation , 2009.

ANSI/FM Approvals 5560, American National Standard for Water Mist Systems, December 2007.

FM Approvals 5560, Approval Standard for Water Mist Systems, March 2009 April 2016 .

Property Loss Prevention Data Sheet Number 3-26, Fire Protection Water Demand for Nonstorage Sprinklered Properties.

Property Loss Prevention Data Sheet Number 4-2, Water Mist Systems .

Property Loss Prevention Data Sheet Number 5-32, Data Centers and Related Facilities .

Property Loss Prevention Data Sheet Number 7-7, Semiconductor Fabrication Facilities .

Property Loss Prevention Data Sheet Number 7-10, Wood Processing and Woodworking Facilities .

Property Loss Prevention Data Sheet Number 7-20, Oil Cookers .

Property Loss Prevention Data Sheet Number 7-78, Industrial Exhaust Systems .

Property Loss Prevention Data Sheet Number 7-79, Fire Protection for Combustion Turbine Installations .

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Oct 25 17:51:41 EDT 2016

Committee Statement

Committee Statement: Updating reference to FM Approvals Standard Class 5560, Water Mist Systems, to the current revision date of April 2016.

Response Message:

Public Input No. 66-NFPA 750-2016 [Section No. E.1.2.6]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

41 of 48 1/9/2017 2:09 PM

First Revision No. 34-NFPA 750-2016 [ Section No. E.1.2.7 ]

E.1.2.7 FSSA Publications.

Fire Suppression Systems Association, 5024-R Campbell Blvd. (FSSA), 3601 East Joppa Road , Baltimore, MD 21236-5974 21234 .

Pipe Design Handbook for Use with Special Hazards Fire Suppression Systems, 2003.

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Oct 26 10:38:52 EDT 2016

Committee Statement

Committee Statement: In response to PI No. 3. The TC updated the address for FSSA. Also added year for publication.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

42 of 48 1/9/2017 2:09 PM

First Revision No. 35-NFPA 750-2016 [ Section No. E.1.2.8 ]

E.1.2.8 IMO Publications.

International Maritime Organization, 4, Albert Embankment, London, SEI 7SR, United Kingdom.

IMO IC844E, International Code for Application of Fire Test Procedures, 2012.

IMO MSC/Circ. 668, Alternative Arrangements for Halon Fire-Extinguishing Systems in Machinery Spaces and Pump-Rooms.

IMO MSC/Circ. 728, Amendments to the Test Method for Equivalent Water-Based Fire Extinguishing Systems for Machinery Spaces of Category A and Cargo Pump-Rooms Contained in MSC/Circ. 668 .

IMO MSC/Circ. 913, Guidelines for the Approval of Fixed Water-Based Local Application Fire-Fighting Systems for Use in Category A Machinery Spaces .

IMO MSC/Circ 1165, Revised Guidelines for Approval of Equivalent Water-Based Fire Extinguishing Systems for Machinery Spaces and Cargo Pump Rooms.

IMO Resolution A.800(19), Revised Guidelines for Approval of Sprinkler Systems.

SOLAS Regulation II-2/12.4.1, Consolidated Edition, 2014.

SOLAS Resolution 10, Fixed Pressure Water Spray Systems.

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Oct 26 10:45:54 EDT 2016

Committee Statement

Committee Statement: The TC updated the references according to the latest revisions and what is used in the Annex.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

43 of 48 1/9/2017 2:09 PM

First Revision No. 36-NFPA 750-2016 [ Section No. E.1.2.9 ]

E.1.2.9 ISA Publications.

Instrumentation, Systems, and Automation Society, 67 Alexander International Society of Automation, 67 T.W. Alexander Drive, P.O. Box 12277, Research Triangle Park, NC 27709.

ISA-S84.01, Application of Safety Instrumentation to the Process Industries , 1996.

ISA 84.00.01 P1, Functional Safety: Safety Instrumented Systems for the Process Industry Sector — Part 1: Framework, Definitions, System, Hardware and Software Requirements , 2004. (Supersedes ISAS84.01)

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Oct 26 10:55:52 EDT 2016

Committee Statement

Committee Statement: In response to PI No. 3. The TC updated the organization name and the latest revision of the reference.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

44 of 48 1/9/2017 2:09 PM

First Revision No. 38-NFPA 750-2016 [ Section No. E.1.2.11 ]

E.1.2.11 U.S. Coast Guard Publications .

2100 Second Street, S.W. 2703 Martin Luther King Jr Ave SE, Stop 7509 , Washington, DC 20593-0001 7509 .

NVIC 9-97 CH-1 , Guide to Structural Fire Protection,1997 2011 .

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Oct 26 11:02:41 EDT 2016

Committee Statement

Committee Statement: The TC updated the Coast Guard address and the most recent revision of the reference.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

45 of 48 1/9/2017 2:09 PM

First Revision No. 39-NFPA 750-2016 [ Section No. E.1.2.12 ]

E.1.2.12 VDS VdS Publications .

VDS, Pasteurstrasse 17A, Koln 50735, Germany. VdS, Amsterdamer Str. 172-174, 50735 Cologne, Germany.

VDS VdS 2498, Guidelines for Water Extinguishing Systems Requirements and Test Methods for Fine Spray Nozzles, 1996 edition.

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Oct 26 11:08:54 EDT 2016

Committee Statement

Committee Statement: The TC updated the address for VdS. Note: the title of VdS does not have a capital D.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

46 of 48 1/9/2017 2:09 PM

First Revision No. 40-NFPA 750-2016 [ Section No. E.2 ]

E.2 Informational References.

The following documents or portions thereof are listed here as informational resources only. They are not a part of the requirements of this document.

Cote, A. E., and P. A. Powell, eds. “Water Mist Suppression Systems,” Fire Protection Handbook, 20th edition.

IMO/FSS Code, International Code for Fire Safety Systems , 2015.

IMO Standard for Shipboard Corridors, Cabins, and Public Spaces, May 2008.

IMO Standard for Shipboard Machinery Spaces, June 2008.

NFPA 14, Standard for the Installation of Standpipe and Hose Systems , 2016 edition.

VdS 3188en Guidelines for Water Mist Sprinkler Systems and Water Mist Extinguishing Systems (High Pressure Systems)—Planning and Installation , 2015

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Oct 26 11:31:12 EDT 2016

Committee Statement

Committee Statement: The TC added two informational references to assist the end user. These references contain many of the smaller references used throughout the standard.

NFPA 14 moved to this section since it is no longer referred to in the Annex chapters.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

47 of 48 1/9/2017 2:09 PM

First Revision No. 41-NFPA 750-2016 [ Section No. E.3 ]

E.3 References for Extracts in Informational Sections.

NFPA 13, Standard for the Installation of Sprinkler Systems, 2013 2016 edition.

Submitter Information Verification

Submitter Full Name: Chelsea Tuttle

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Oct 26 11:38:03 EDT 2016

Committee Statement

Committee Statement: The TC updated the reference to the most recent revision.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

48 of 48 1/9/2017 2:09 PM