national fire protection association - nfpa.org · pdf filesecond revision no. 3617-nfpa...

133
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 • Fax: 617-770-0700 • www.nfpa.org TO: NEC ® Code-Making Panel 13 FROM: Kimberly Shea, Administrator, Technical Projects DATE: January 25, 2016 SUBJECT: NFPA 70 Second Draft TC Ballot Final Results (A2016) ____________________________________________________________________________ According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. The attached report shows the number of affirmative, negative and abstaining votes as well as the explanation of the vote for each revision. To pass ballot, each revision requires: (1) a simple majority of those eligible to vote and (2) an affirmative vote of 2 /3 of ballots returned. See Sections 3.3.4.3 (c) and 4.3.10.1 of the Regulations Governing the Development of NFPA Standards. Page 1 of 133

Upload: hakhuong

Post on 12-Feb-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

National Fire Protection Association

1 Batterymarch Park, Quincy, MA 02169-7471

Phone: 617-770-3000 • Fax: 617-770-0700 • www.nfpa.org

TO: NEC® Code-Making Panel 13

FROM: Kimberly Shea, Administrator, Technical Projects

DATE: January 25, 2016

SUBJECT: NFPA 70 Second Draft TC Ballot Final Results (A2016)

____________________________________________________________________________

According to the final ballot results, all ballot items received the necessary affirmative votes to

pass ballot.

The attached report shows the number of affirmative, negative and abstaining votes as well as the

explanation of the vote for each revision.

To pass ballot, each revision requires: (1) a simple majority of those eligible to vote and (2) an

affirmative vote of 2/3 of ballots returned. See Sections 3.3.4.3 (c) and 4.3.10.1 of the

Regulations Governing the Development of NFPA Standards.

Page 1 of 133

Page 2: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ]

445.11 Marking.

Each generator shall be provided with a nameplate giving the manufacturer’s name, the rated frequency,the number of phases if of ac, the rating in kilowatts or kilovolt-amperes, the power factor, the normalvolts and amperes corresponding to the rating, and the rated ambient temperature or , and the ratedtemperature rise.

Nameplates or manufacturer's instructions shall provide the following information for all stationarygenerators and portable generators rated more than 15 kW: shall also give the power factor, thesubtransient and transient reactances, the maximum short-circuit current, and the insulation system class.Stationary and portable generators shall be marked to indicate if the generator is protected againstoverload by inherent design, an overcurrent protective relay, circuit breaker, or fuse.

(1) Subtransient, transient, synchronous, and zero sequence reactances

(2) Power rating category

(3) Insulation system class

(4) Indication if the generator is protected against overload by inherent design, an overcurrentprotective relay, circuit breaker, or fuse

(5) Maximum short-circuit current for inverter-based generators, in lieu of the synchronous,subtransient, and transient reactances

Marking shall be provided by the manufacturer to indicate whether or not the generator neutral is bondedto its frame. Where the bonding is modified in the field, additional marking shall be required to indicatewhether the neutral is bonded to the frame.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 15:00:30 PST 2015

Committee Statement

CommitteeStatement:

“Power factor” has been relocated to the first paragraph of section 445.11 since it is commonpractice to mark this information on generators of all sizes.

Changes were accepted in the second paragraph to allow certain gen-set information to be placedin the manufacturer’s instructions rather than the nameplate.

“Synchronous” and “zero sequence” have been added to reactances since this information is alsoneeded when modeling electrical systems.

The term “time-rating” was removed during the first draft stage but has been reinserted andrenamed to “power rating category”. This change is necessary to clarify if the gen-set is intendedfor Prime, Continuous, Limited Time Running, or Emergency Standby Power use.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

1 of 133 1/25/2016 1:23 PM

Page 2 of 133

Page 3: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

ResponseMessage:

Public Comment No. 252-NFPA 70-2015 [Section No. 445.11]

Public Comment No. 325-NFPA 70-2015 [Section No. 445.11]

Public Comment No. 508-NFPA 70-2015 [Section No. 445.11]

Public Comment No. 1215-NFPA 70-2015 [Section No. 445.11]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

18 Affirmative All

2 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

Affirmative with Comment

Currin, Jr., Richard D.

I am in agreement with this revision. The labeling requirements gives needed information to installers and AHJs

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

2 of 133 1/25/2016 1:23 PM

Page 3 of 133

Page 4: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

to insure a safe installation. Allowing the information to be in manufacturer's instructions will prevent nameplatesfrom becoming excessive in size.

Neeser, Daniel R.

Item 5 should include "zero" as in item 1. This should be considered for the 2020 NEC.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

3 of 133 1/25/2016 1:23 PM

Page 4 of 133

Page 5: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3618-NFPA 70-2015 [ Section No. 445.13(B) ]

(B) Overcurrent Protection Provided.

Where the generator set is equipped with a listed overcurrent protective device, including or acombination of a current transformer and overcurrent relay, conductors shall be permitted to be tappedfrom the load side of the protected terminals in accordance with 240.21(B).

Tapped conductors shall not be permitted for portable generators rated 15 kW or less where field wiringconnection terminals are not accessible.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 15:17:28 PST 2015

Committee Statement

CommitteeStatement:

Field wiring connection points are not typically provided on portable generators rated 15 kW orless. These products are typically cord- and plug-connected.

Editorial revisions are made for clarity.

ResponseMessage:

Public Comment No. 509-NFPA 70-2015 [Section No. 445.13(B)]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

19 Affirmative All

1 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

4 of 133 1/25/2016 1:23 PM

Page 5 of 133

Page 6: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

Affirmative with Comment

Currin, Jr., Richard D.

This revision clarifies the statement to better meet its intent.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

5 of 133 1/25/2016 1:23 PM

Page 6 of 133

Page 7: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3614-NFPA 70-2015 [ Section No. 445.14 ]

445.14 Protection of Live Parts.

Live parts of generators operated at more than 50 volts ac or 60 volts dc to ground shall not be exposedto accidental contact where accessible to unqualified persons.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 14:15:48 PST 2015

Committee Statement

CommitteeStatement:

In response to Public Comment 1063, changes were made to certain sections under Panel 13’spurview to correlate with the use of the terms 50 volts AC and 60 volts DC.

ResponseMessage:

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

19 Affirmative All

1 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Czarnecki, Neil A.

Degnan, James E.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

6 of 133 1/25/2016 1:23 PM

Page 7 of 133

Page 8: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

Affirmative with Comment

Currin, Jr., Richard D.

This was needed for correlation

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

7 of 133 1/25/2016 1:23 PM

Page 8 of 133

Page 9: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3619-NFPA 70-2015 [ Section No. 445.18(A) ]

(A) Disconnecting Means.

Generators other than cord- and plug-connected portable shall have one or more disconnecting meansthat . Each disconnecting means shall simultaneously disconnect all its associated ungroundedconductors. Each disconnecting means shall be lockable in the open position in accordance with 110.25.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 15:23:52 PST 2015

Committee Statement

CommitteeStatement:

445.18(A) has been revised to clarify that when multiple disconnects are installed on a gen-seteach disconnect is only required to open its own specific set of ungrounded conductors.Interlocking is not required.

ResponseMessage:

Public Comment No. 784-NFPA 70-2015 [Section No. 445.18(A)]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

19 Affirmative All

1 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

8 of 133 1/25/2016 1:23 PM

Page 9 of 133

Page 10: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

Affirmative with Comment

Currin, Jr., Richard D.

This revision clarifies the statement.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

9 of 133 1/25/2016 1:23 PM

Page 10 of 133

Page 11: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3620-NFPA 70-2015 [ Section No. 445.18(B) ]

(B) Shutdown of Prime Mover.

Generators shall have provisions to shut down the prime mover. The means of shutdown shall complywith all of the following :

(1) Be equipped with provisions to disable all prime mover start control circuits to render the primemover incapable of starting

(2) Initiate a shutdown mechanism that requires a mechanical reset

The provisions to shut down the prime mover shall be permitted to satisfy the requirements of 445.18(A)where it is capable of being locked in the open position in accordance with 110.25 .

Generators with greater than 15 kW rating shall be provided with an additional requirement to shut downthe prime mover. The This additional shutdown means shall be located outside the equipment room orgenerator weatherproof housing enclosure. enclosure and shall also meet The requirement in 445.18(B)shall be permitted to satisfy the requirements of 445.18(A) where it is capable of being locked in theopen position in accordance with 110.25 445.18(B)(1) and (B)(2) .

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 15:55:46 PST 2015

Committee Statement

CommitteeStatement:

This revision clarifies that the general provisions to shut down the prime mover may satisfy therequirements in 445.18(A) under the given conditions. The additional means located outside theequipment room is modified to meet the requirements of 445.18(B)(1) and (B)(2).

Not all generator enclosures are weatherproof so this portion of the requirement has beenremoved.

Editorial revisions were made for clarity.

ResponseMessage:

Public Comment No. 1200-NFPA 70-2015 [Section No. 445.18(B)]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

19 Affirmative All

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

10 of 133 1/25/2016 1:23 PM

Page 11 of 133

Page 12: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

1 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

Affirmative with Comment

Currin, Jr., Richard D.

This revision removed the term "weatherproof" since all generators are not weatherproof. It clarifies the requireddisconnect location.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

11 of 133 1/25/2016 1:23 PM

Page 12 of 133

Page 13: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3621-NFPA 70-2015 [ Section No. 445.20 ]

445.20 Ground-Fault Circuit-Interrupter Protection for Receptacles on 15-kW or Smaller PortableGenerators.

All 125-volt, single-phase, 15- and 20-ampere receptacle Receptacle outlets that are a part of a 15-kW orsmaller portable generator either shall have listed ground-fault circuit-interrupter protection (GFCI) forpersonnel integral to the generator or receptacle; or shall not be available for use when the 125/250-voltreceptacle is in use. If the generator does not have a 125/250-volt receptacle, the requirement to disablethe 125-volt, single-phase, 15- and 20-ampere receptacle outlets shall not apply. as indicated in either (A)or (B):

(A) Unbonded (Floating Neutral) Generators.

Unbonded generators with both 125-volt and 125/250-volt receptacle outlets shall have listed GFCIprotection for personnel integral to the generator or receptacle on all 125-volt and 15- and 20-amperereceptacle outlets.

Exception: GFCI protection shall not be required where the 125-volt receptacle outlets(s) is interlockedsuch that it is not available for use when any 125/250-volt receptacle(s) is in use.

(B) Bonded Neutral Generators.

Bonded generators shall be provided with GFCI protection on all 125-volt and 15- and 20-amperereceptacle outlets.

Informational Note: Refer to 590.6(A)(3) for GFCI requirements for 15-kW or smaller portablegenerators used for temporary electric power and lighting.

Exception to (A) and (B): If the generator was manufactured or remanufactured prior to January 1, 2015,listed cord sets or devices incorporating listed ground-fault circuit-interrupter GFCI protection forpersonnel identified for portable use shall be permitted.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 16:49:40 PST 2015

Committee Statement

CommitteeStatement:

It is necessary to separate the requirements for both bonded and unbonded generators. Therequirements are different. Clarity is provided in new first level subdivision (A) to clearly requireGFCI's at 125v, 15 and 20 amp only where both 125v and 125/250v receptacles exist on thegenerator. The exception for GFCI's at 125v is maintained for unbonded generators that areinterlocked to disable the 125v receptacles when the 125/250v receptacles are in use. Clarity isprovided in (B) to require that 125v, 15/20 amp receptacles outlets in bonded generators are alwaysrequired to be GFCI protected. The present text misses that and has been corrected. The newinformational note provides clarity by referring the code user to Article 590 for generators used intemporary power under the purview of Article 590. The exception is editorially modified to apply toboth first level subdivisions.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

12 of 133 1/25/2016 1:23 PM

Page 13 of 133

Page 14: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Public Comment No. 956-NFPA 70-2015 [Section No. 445.20]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

15 Affirmative All

3 Affirmative with Comments

2 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Caron, Daniel J.

Croushore, Timothy M.

Froemming, Steven F.

Keenan, Ronald A.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

Affirmative with Comment

Brandon, George M.

The word "and" needs to be removed from two sentences. The sentences are show below, first as they are in thestandard and then with the unneeded "and" removed. Original: Unbonded generators with both 125-volt and125/250-volt receptacle outlets shall have listed GFCI protection for personnel integral to the generator orreceptacle on all 125-volt and 15- and 20-ampere receptacle outlets. Updated: Unbonded generators with both125-volt and 125/250-volt receptacle outlets shall have listed GFCI protection for personnel integral to thegenerator or receptacle on all 125-volt 15- and 20-ampere receptacle outlets. Original Bonded generators shall beprovided with GFCI protection on all 125-volt and 15- and 20-ampere receptacle outlets. Updated Bondedgenerators shall be provided with GFCI protection on all 125-volt 15- and 20-ampere receptacle outlets.

Currin, Jr., Richard D.

This revision addresses the fact that GFCI protection is required for bonded 125/250v generators. It allows anexception for generators with interlocking that disables 125 v receptacles when the 125/250v receptacles are in

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

13 of 133 1/25/2016 1:23 PM

Page 14 of 133

Page 15: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

use.

Little, Linda J.

This revision is primarily editorial and provides significant clarity. The only substantive impact is that on bondedportable generators, the 125-volt receptacles must be GFCI protected. It is imperative to note that small unbondedgenerators that employ only 125-volt receptacles are not required to have GFCI protection. That has been theconcern of the generator manufacturers all along and SR 3621 does not impact those unbonded generators.Rejection of SR 3621 by CMP-13 would be an affirmation that bonded generators do not require GFCI protectionfor 125-volt, 15/20-amp receptacles, which would directly conflict with the requirements of section 210.8. CMP-13has no justification to specifically permit 125-volt, 15/20-amp receptacles to be applied without GFCI protection onbonded generators. Why would a manufacturer build a bonded generator and not provide GFCI protection,particularly when understanding that there is a path for fault current inherent to the generator and shock hazardsexist?

Negative with Comment

Czarnecki, Neil A.

The intent of the public inputs on 445.20 were intended to clarify the existing requirements of this section. ThePanel action to create SR 3621 goes well beyond clarification, and creates a new requirement that isunnecessarily restrictive and not technically substantiated.

Degnan, James E.

No substantiation was offered to justify the new text.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

14 of 133 1/25/2016 1:23 PM

Page 15 of 133

Page 16: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3628-NFPA 70-2015 [ Section No. 480.1 ]

480.1 Scope.

This article applies to all stationary installations of storage batteries.

Informational Note: The following standards are frequently referenced for the installation ofstationary batteries:

(1) IEEE 484-2008 IEEE 484 , Recommended Practice for Installation Design and Installation ofVented Lead-Acid Batteries for Stationary Applications

(2) IEEE 485-1997 IEEE 485 , Recommended Practice for Sizing Vented Lead-Acid StorageBatteries for Stationary Applications

(3) IEEE 1145-2007 IEEE 1145 , Recommended Practice for Installation and Maintenance ofNickel-Cadmium Batteries for Photovoltaic (PV) Systems

(4) IEEE 1187-2002 IEEE 1187 , Recommended Practice for Installation Design, and Installationof Valve-Regulated Lead-Acid Batteries for Stationary Applications

(5) IEEE 1375-1996 (Rev. 2003) IEEE 1375 , IEEE Guide for the Protection of Stationary BatterySystems

(6) IEEE 1578-2007 IEEE 1578 , Recommended Practice for Stationary Battery Electrolyte SpillContainment and Management

(7) IEEE 1635/ASHRAE 21-2012 IEEE 1635/ASHRAE 21 , Guide for the Ventilation and ThermalManagement of Batteries for Stationary Battery Installations Applications

(8) UL 1973, Standard for Batteries for Use in Light Electric Rail (LER) Applications andStationary Applications

(9) UL Subject 2436, Outline of Investigation for Spill Containment for Stationary Lead AcidBattery Systems

(10) UL 1989, Standard for Standby Batteries

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Nov 10 15:30:29 PST 2015

Committee Statement

CommitteeStatement:

The documents referenced within the informational note provide common resources for stationarybattery systems. The document titles were corrected and the inclusion of a particular edition orpublication date for these documents is removed since the applicability of this information isdetermined by the user.

ResponseMessage:

Public Comment No. 167-NFPA 70-2015 [Section No. 480.1]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

15 of 133 1/25/2016 1:23 PM

Page 16 of 133

Page 17: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

17 Affirmative All

1 Affirmative with Comments

2 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

Affirmative with Comment

Currin, Jr., Richard D.

This corrects and correlates with the documents while removing a specific edition.

Negative with Comment

Croushore, Timothy M.

Removal of the dates of the referenced documents within Second Revision 3628 is inconsistent with NFPARegulations Governing the Development of NFPA Standards, Section 3.3.6.2 Reference to Other NFPA Standardsor Other Publications. In addition, this action is inconsistent with the action on SR #3643 where the dates are leftin place on similar referenced standards.

Savage, Sr., Michael L.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

16 of 133 1/25/2016 1:23 PM

Page 17 of 133

Page 18: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3629-NFPA 70-2015 [ New Section after 480.2 ]

480.3 Equipment.

Storage batteries and battery management equipment shall be listed. This requirement shall not applyto lead-acid batteries.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Nov 10 16:36:25 PST 2015

Committee Statement

CommitteeStatement:

This revision recognizes the need for third party evaluation of storage batteries and batterymanagement equipment. This is necessary to provide the installer, maintainer, and AHJ withnecessary information and instructions for safe application of storage batteries.

ResponseMessage:

Public Comment No. 1490-NFPA 70-2015 [New Definition after Definition: Terminal.]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

17 Affirmative All

2 Affirmative with Comments

1 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Degnan, James E.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

18 of 133 1/25/2016 1:23 PM

Page 18 of 133

Page 19: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Froemming, Steven F.

Keenan, Ronald A.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

Affirmative with Comment

Currin, Jr., Richard D.

Agree because listing is needed to insure products are safe. This provides AHJs and installers assurance that thebatteries installed are suitable for the application.

Little, Linda J.

This new requirement is necessary to ensure safe operation. Recent failures in the Boeing 747 Dreamliner andhover-boards have shown that thermal runaway is a serious fire hazard. The expansion of energy storage intofacilities with occupants mandates that these new battery technologies be tested and certified before installation inaccordance with the NEC.

Negative with Comment

Czarnecki, Neil A.

The current ANSI standard for storage batteries is battery chemistry independent, and as such, does not take thedifferences in chemistry into consideration in the safety design process. The addition of a listing requirement willtherefore provide limited benefit to the battery consumer and potentially restricts the implementation of newtechnologies and solutions into the electrical industry.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

19 of 133 1/25/2016 1:23 PM

Page 19 of 133

Page 20: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3615-NFPA 70-2015 [ Section No. 480.5 ]

480.6 Overcurrent Protection for Prime Movers.

Overcurrent protection shall not be required for conductors from a battery with a nominal voltage of 50 60volts dc or less if the battery provides power for starting, ignition, or control of prime movers. Section300.3 shall not apply to these conductors.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 14:16:54 PST 2015

Committee Statement

CommitteeStatement:

In response to Public Comment 1063, changes were made to certain sections under Panel 13’spurview to correlate with the use of the terms 50 volts AC and 60 volts DC.

ResponseMessage:

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

19 Affirmative All

1 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Czarnecki, Neil A.

Degnan, James E.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

20 of 133 1/25/2016 1:23 PM

Page 20 of 133

Page 21: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

Affirmative with Comment

Currin, Jr., Richard D.

This makes the distinction from power batteries and batteries used to start prime movers.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

21 of 133 1/25/2016 1:23 PM

Page 21 of 133

Page 22: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3616-NFPA 70-2015 [ Section No. 480.6(A) ]

(A) Disconnecting Means.

A disconnecting means shall be provided for all ungrounded conductors derived from a stationary batterysystem with a nominal voltage over 50 60 volts dc . A disconnecting means shall be readily accessibleand located within sight of the battery system.

Informational Note: See 240.21(H) for information on the location of the overcurrent device forbattery conductors.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 14:17:56 PST 2015

Committee Statement

CommitteeStatement:

In response to Public Comment 1063, changes were made to certain sections under Panel 13’spurview to correlate with the use of the terms 50 volts AC and 60 volts DC.

ResponseMessage:

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

19 Affirmative All

1 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

22 of 133 1/25/2016 1:23 PM

Page 22 of 133

Page 23: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

Affirmative with Comment

Currin, Jr., Richard D.

Agree, this is a change to correlate with the new 60 volt DC level.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

23 of 133 1/25/2016 1:23 PM

Page 23 of 133

Page 24: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3630-NFPA 70-2015 [ Section No. 480.6(D) ]

(D) Notification.

The disconnecting means shall be legibly marked in the field. A label with the marking shall be placed in aconspicuous location near the battery if a disconnecting means is not provided. The marking shall be ofsufficient durability to withstand the environment involved and shall include the following:

(1) Nominal battery voltage

(2) Maximum available fault short-circuit current derived from the stationary battery system

(3) Date the fault short-circuit current calculation was performed

(4) The battery disconnecting means shall be marked in accordance with 110.16.

Informational Note No. 1: Battery equipment suppliers can provide information about short-circuitcurrent on any particular battery model.

Informational Note No. 2: The available fault-current marking(s) addressed in 480.7(D)(2) is relatedto required short-circuit current ratings of equipment. NFPA 70E-2015, Standard for ElectricalSafety in the Workplace, provides assistance in determining the severity of potential exposure,planning safe work practices, and selecting personal protective equipment.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Nov 10 16:42:44 PST 2015

Committee Statement

Committee Statement: CMP 13 agrees that the term short-circuit current is appropriate.

Response Message:

Public Comment No. 1421-NFPA 70-2015 [Section No. 480.6(D)]

Public Comment No. 1476-NFPA 70-2015 [Section No. 480.6(D)]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

18 Affirmative All

2 Affirmative with Comments

0 Negative with Comments

0 Abstention

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

24 of 133 1/25/2016 1:23 PM

Page 24 of 133

Page 25: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

Affirmative with Comment

Currin, Jr., Richard D.

Agree this change is appropriate.

Neeser, Daniel R.

An editorial change by the Correlating Committee or NFPA Staff is suggested. The term “fault-current” inInformational Note No. 2 should be changed to “short-circuit current” as this term is used in 480.7(D)(2). FR 3643changed “short-circuit current” to “fault-current” in 480.7(D)(2) and added Informational Note No. 2, so there wascorrelation with the term. However, SR 3630 changed 480.7(D)(2) from “fault-current” back to “short-circuitcurrent” which is the 2014 NEC term used in this section. However, the SR did not correspondingly change theterm in Informational Note No. 2 to “short-circuit current.” Since this is an Informational Note editorial change, itshould be permissible.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

25 of 133 1/25/2016 1:23 PM

Page 25 of 133

Page 26: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3622-NFPA 70-2015 [ Section No. 695.4(B)(3) ]

(3) Disconnecting Means.

All disconnecting devices that are unique to the fire pump loads shall comply with items (a) through (e).

(a) Features and Location — Normal Power Source. The disconnecting means for the normal powersource shall comply with all of the following: [20:9.2.3.1]

(1) Be identified as suitable for use as service equipment.

(2) Be lockable in the closed position. The provision for locking or adding a lock to the disconnectingmeans shall be installed on or at the switch or circuit breaker used as the disconnecting means andshall remain in place with or without the lock installed.

(3) Not be located within the same enclosure, panelboard, switchboard, switchgear, or motor controlcenter, with or without common bus, that supplies loads other than the fire pump.

(4) Be located sufficiently remote from other building or other fire pump source disconnecting meanssuch that inadvertent operation at the same time would be unlikely.

Exception to 695.4(B)(3)(a): For a multibuilding campus-style complex(s) installed under theprovisions of 695.3(C), only the requirements in 695.4(B)(3)(a)(2) shall apply for normal powersource disconnects.

(b) Features and Location — On-Site Standby Generator. The disconnecting means for an on-sitestandby generator(s) used as the alternate power source shall be installed in accordance with700.10(B)(5) for emergency circuits and shall be lockable in the closed position. The provision for lockingor adding a lock to the disconnecting means shall be installed on or at the switch or circuit breaker usedas the disconnecting means and shall remain in place with or without the lock installed.

(c) Disconnect Marking. The disconnecting means shall be marked “Fire Pump DisconnectingMeans.” The letters shall be at least 25 mm (1 in.) in height, and they shall be visible without openingenclosure doors or covers. [20:9.2.3.1(5)]

(d) Controller Marking. A placard shall be placed adjacent to the fire pump controller, stating thelocation of this disconnecting means and the location of the key (if the disconnecting means is locked).[20:9.2.3.2]

(e) Supervision. The disconnecting means shall be supervised in the closed position by one of thefollowing methods:

(1) Central station, proprietary, or remote station signal device

(2) Local signaling service that causes the sounding of an audible signal at a constantly attended point

(3) Locking the disconnecting means in the closed position

(f) Sealing of disconnecting means and approved weekly recorded inspections when thedisconnecting means are located within fenced enclosures or in buildings under the control of the owner[20:9.2.3.3]

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Nov 10 08:12:45 PST 2015

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

26 of 133 1/25/2016 1:23 PM

Page 26 of 133

Page 27: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Committee Statement

CommitteeStatement:

This revision clarifies that the exception applies to all of 695.4(B)(3)(a) and not just to695.4(B)(3)(a)(4).

Response Message:

Public Comment No. 210-NFPA 70-2015 [Section No. 695.4(B)(3)]

Public Comment No. 963-NFPA 70-2015 [Section No. 695.4(B)(3)]

Public Comment No. 1863-NFPA 70-2015 [Section No. 695.4(B)]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

19 Affirmative All

1 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

27 of 133 1/25/2016 1:23 PM

Page 27 of 133

Page 28: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Affirmative with Comment

Currin, Jr., Richard D.

This revision provides clarification.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

28 of 133 1/25/2016 1:23 PM

Page 28 of 133

Page 29: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3623-NFPA 70-2015 [ Section No. 695.6(A)(2) ]

(2) Feeders.

Fire pump supply conductors on the load side of the final disconnecting means and overcurrent device(s)permitted by 695.4(B) , or conductors that connect directly to an on-site standby generator, shall complywith all of the following:

(a) Independent Routing. The conductors shall be kept entirely independent of all other wiring.

(b) Associated Fire Pump Loads. The conductors shall supply only loads that are directly associatedwith the fire pump system.

(c) Protection from Potential Damage. The conductors shall be protected from potential damage byfire, structural failure, or operational accident.

(d) Inside of a Building. Where routed through a building, the conductors shall be protected from firefor 2 hours using one of the following methods:

(1) The cable or raceway is encased in a minimum 50 mm (2 in.) of concrete.

(2) Is The cable or raceway is a listed fire- resistive cable system.

Informational Note 1: Fire- resistive cables are tested to ANSI/UL 2196, Tests for FireResistive Cables.

Informational Note 2: The listing organization provides information for fire- resistive cablesystems on proper installation requirements to maintain the fire rating.

(3) Be The cable or raceway is a listed electrical circuit protective system.

Informational Note 1: Electrical circuit protective systems could include, but are not be limitedto, thermal barriers or a protective shaft and are tested to in accordance with UL 1724, FireTests for Electrical Circuit Protection Systems.

Informational Note 2: The listing organization provides information for electrical circuitprotective systems on proper installation requirements to maintain the fire rating.

Exception to (A)(2)(d): The supply conductors located in the electrical equipment room where theyoriginate and in the fire pump room shall not be required to have the minimum 2-hour fireseparation or fire- resistance rating, unless otherwise required by 700.10(D) of this Code.

Supplemental Information

File Name Description

695.6_A_2_SR3623_LM.docx Staff use only

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Nov 10 08:19:09 PST 2015

Committee Statement

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

29 of 133 1/25/2016 1:23 PM

Page 29 of 133

Page 30: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

CommitteeStatement:

The permission to use 2 inches of concrete was deleted in the first revision stage and is addedback in this revision. The absence of a dimension for the depth of concrete would cause seriousconfusion in practical applications.

Public Comment No. 838-NFPA 70-2015 [Section No. 695.6(A)(2)]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

19 Affirmative All

0 Affirmative with Comments

1 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

Negative with Comment

Currin, Jr., Richard D.

There is no evidence to support that 2" of concrete provides a 2 hour rating. In fact there is evidence that impliesthe contrary and that it would require 4" or more of concrete encasement to provide a 2 hour fire rating. I wouldagree with this revision if it were limited to the application of slab on grade (SOG) cases. Since it is not specific to

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

30 of 133 1/25/2016 1:23 PM

Page 30 of 133

Page 31: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

SOG that then ceilings and walls would be allowed as protection for conductors. This is an area that needs labtest to be performed to determine temperatures that conductors are exposed too under various levels of concretethicknesses as well as different concrete mixes. The test should include conductors installed on grade, walls, andceiling/floors.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

31 of 133 1/25/2016 1:23 PM

Page 31 of 133

Page 32: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3624-NFPA 70-2015 [ Section No. 695.6(G) ]

(G) Ground-Fault Protection of Equipment.

Ground-fault protection of equipment shall not be permitted for fire pumps. installed in any fire pumppower circuit. [ 20: 9.1.8.1]

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Nov 10 08:41:40 PST 2015

Committee Statement

CommitteeStatement:

This revision will clarify that ground-fault protection of equipment is not permitted for the firepump power circuit.

This revision is limited to the fire pump power circuit as 695.6 is titled “Power Wiring”.

This change is necessary to clarify that multi building campus style distribution systems mayinclude upstream ground fault protection.

See NFPA 20: 9.1.8.1 for the NFPA 20 requirement.

ResponseMessage:

Public Comment No. 211-NFPA 70-2015 [Section No. 695.6(G)]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

19 Affirmative All

1 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

32 of 133 1/25/2016 1:23 PM

Page 32 of 133

Page 33: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

Affirmative with Comment

Currin, Jr., Richard D.

I agree with this although it does raise some concern over possible coordination issues.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

33 of 133 1/25/2016 1:23 PM

Page 33 of 133

Page 34: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3625-NFPA 70-2015 [ Section No. 695.14(E) ]

(E) Electric Fire Pump Control Wiring Methods.

All electric motor–driven fire pump control wiring shall be in rigid metal conduit, intermediate metalconduit, liquidtight flexible metal conduit, electrical metallic tubing, liquidtight flexible nonmetallic conduit,listed Type MC cable with an impervious covering, or Type MI cable.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Nov 10 08:51:47 PST 2015

Committee Statement

CommitteeStatement:

This revision correctly adds electrical metallic tubing in the list of approved wire methodsbased on actions taken in the First Draft stage.

ResponseMessage:

Public Comment No. 658-NFPA 70-2015 [Section No. 695.14(E)]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

19 Affirmative All

1 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Czarnecki, Neil A.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

34 of 133 1/25/2016 1:23 PM

Page 34 of 133

Page 35: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

Affirmative with Comment

Currin, Jr., Richard D.

I agree with this revision as it adds EMT as an approved means for fire pump control wiring.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

35 of 133 1/25/2016 1:23 PM

Page 35 of 133

Page 36: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3626-NFPA 70-2015 [ Section No. 695.14(F) ]

(F) Generator Control Wiring Methods.

Control conductors installed between the fire pump power transfer switch and the standby generatorsupplying the fire pump during normal power loss shall be kept entirely independent of all other wiring.Breakage, disconnecting, shorting of the wires, or loss of power to the remote start circuits controlconductors shall cause immediate starting and continuous running of the generator and shall not preventthe starting of the generator(s) due to causes other than failure of these external control circuits Theintegrity of the generator control wiring shall be continuously monitored. Loss of integrity of the remotestart circuit(s) shall initiate visual and audible annunciation of generator malfunction at the generator localand remote annunciator(s) and start the generator(s) .

Informational Note: See NFPA 20-2013, Standard for the Installation of Stationary Pumps for FireProtection, Section 3.3.7.2, for more information on fault-tolerant external control circuits.

The control conductors shall be protected to resist potential damage by fire or structural failure. They shallbe permitted to be routed through a building(s) using one of the following methods:

(1) Be encased in a minimum 50 mm (2 in.) of concrete.

(2) Be protected by a fire-rated assembly listed to achieve a minimum fire rating of 2 hours anddedicated to the fire pump circuits.

(3) Be a listed electrical circuit protective system with a minimum 2-hour fire rating. The installation shallcomply with any restrictions provided in the listing of the electrical circuit protective system used.

Informational Note: The listing organization provides information for electrical circuit protectivesystems on proper installation requirements to maintain the fire rating.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Nov 10 08:55:37 PST 2015

Committee Statement

CommitteeStatement:

The revised text provides necessary clarity. A generator cannot start if the control conductors losepower due to failed batteries. A new last sentence is added to require visual and audibleannunciation where a loss of power prevent the starting of the generator.

ResponseMessage:

Public Comment No. 1201-NFPA 70-2015 [Section No. 695.14(F)]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

36 of 133 1/25/2016 1:23 PM

Page 36 of 133

Page 37: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

19 Affirmative All

1 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

Affirmative with Comment

Currin, Jr., Richard D.

The new statement is clearer and more concise.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

37 of 133 1/25/2016 1:23 PM

Page 37 of 133

Page 38: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3601-NFPA 70-2015 [ Definition: Luminaire, Directly Controlled. ]

Luminaire, Directly Controlled.

An emergency lighting luminaire that operates on constant power and has a control input for an integraldimming or switching function that is used to drive drives the luminaire to full brightness illumination uponloss of normal power.

Informational Note: See ANSI/UL 924, Emergency Lighting and Power Equipment, for informationcovering directly controlled luminaires.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 08:31:32 PST 2015

Committee Statement

CommitteeStatement:

The panel recognizes that directly controlled luminaires may not always be powered in normaloperation and revises the definition. Additional editorial revisions are made for clarity.

The panel reaffirms that “directly controlled luminaires” return to full illumination upon loss ofnormal power.

ResponseMessage:

Public Comment No. 666-NFPA 70-2015 [Definition: Luminaire, Directly Controlled.]

Public Comment No. 1171-NFPA 70-2015 [Definition: Luminaire, Directly Controlled.]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

19 Affirmative All

1 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

38 of 133 1/25/2016 1:23 PM

Page 38 of 133

Page 39: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

Affirmative with Comment

Currin, Jr., Richard D.

Statement now includes luminaires that are not powered during normal operation.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

39 of 133 1/25/2016 1:23 PM

Page 39 of 133

Page 40: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3602-NFPA 70-2015 [ Section No. 700.3(F) ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

40 of 133 1/25/2016 1:23 PM

Page 40 of 133

Page 41: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

(F) Temporary Source of Power for Maintenance or Repair of the Alternate Source of Power.

If the emergency system relies on a single alternate source of power, which that must will be disabled formaintenance or repair, the emergency system shall include permanent switching means to connect aportable or temporary alternate source of power, which shall be available for the duration of themaintenance or repair. The permanent switching means to connect a portable or temporary alternatesource of power shall comply with the following:

(1) Connection of to the portable or temporary alternate source of power shall not require disabling ofthe emergency system’s normal modification of the permanent system wiring .

(2) It shall be permissible to utilize manual switching to switch from the permanent source of power ordisconnection of the emergency system’s to the portable or temporary alternate source of power,other than by the switching means .

(3) Any transfer Transfer of power between the normal power source and the emergency power sourceshall be in accordance with 700.12. It shall be permissible to utilize manual switching.

(4) The connection point for the portable or temporary alternate source shall be marked with the phaserotation and system bonding requirements.

(5) Mechanical or electrical interlocking shall prevent inadvertent interconnection of power sources.

(6) The switching means shall include an “emergency source disabled” contact for connection to acontact point which shall annunciate at a generator remote annunciator or another facility alarmdata collection point monitoring system to indicate that the permanent emergency source isdisconnected from the emergency system .

It shall be permissible to utilize the switching means for connection of a load bank.

Informational Note: There are many possible methods to achieve the requirements of 700.3(F) .See Figure 700.3(F) for one example.

Figure 700.3(F)

Exception: A The permanent switching means to temporarily connect an a portable or temporaryalternate source of power, for the duration of the maintenance or repair, shall not be required whereone any of the following conditions exists:

(1) All processes that rely on the emergency system source are capable of being disabled duringmaintenance or repair of the emergency source of power.

(2) The building or structure is unoccupied and fire suppression systems are fully functional and do notrequire an alternate power source.

(3) Other temporary means can be substituted for the emergency system.

(4) A permanent alternate emergency source, such as, but not limited to, a second on-site standbygenerator or separate electric utility service connection, capable of supporting the emergencysystem, exists .

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

41 of 133 1/25/2016 1:23 PM

Page 41 of 133

Page 42: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Supplemental Information

File Name Description

700.3_F_SR_3602_LM.pdf

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 09:06:42 PST 2015

Committee Statement

CommitteeStatement:

The deletion of the last sentence in 700.4(B) in first revision 3617 inadvertently removed therequirement for portable or temporary alternate sources to be available whenever the emergencygenerator is out of service for maintenance or repair.

This requirement is now added into the parent text of first level subdivision 700.3(F) to require aportable or temporary alternate source to be available whenever the emergency generator is out ofservice for maintenance or repair.

The previous requirement was incorrectly located in 700.4(B) Capacity, which limited application tostandby generators used in emergency systems that were also used for selective load pickup, loadshedding, and peak load shaving. The committee expands the requirement to all emergencygenerators where “maintenance or repair” is to be performed. Where an emergency system isrequired, provisions for supplementing the emergency standby generator during maintenance orrepair are necessary.

Editorial revisions are made throughout the requirement to increase clarity and usability.

ResponseMessage:

Public Comment No. 318-NFPA 70-2015 [Section No. 700.4(B)]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

19 Affirmative All

1 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

42 of 133 1/25/2016 1:23 PM

Page 42 of 133

Page 43: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

Affirmative with Comment

Currin, Jr., Richard D.

This is needed for safety as facilities such as healthcare must have an emergency power source available at alltimes.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

43 of 133 1/25/2016 1:23 PM

Page 43 of 133

Page 44: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3603-NFPA 70-2015 [ Section No. 700.10(A) ]

(A) Identification.

Emergency circuits shall be permanently marked as components of an emergency circuit or system sothey will be readily identified by the following methods:

(1) All boxes and enclosures (including transfer switches, generators, and power panels) for emergencycircuits shall be permanently marked so they will be readily as a component of an emergency circuitor system .

(2) Where boxes or enclosures are not encountered, exposed cable or raceway systems shall bepermanently marked to be identified as a components of an emergency circuit or system atintervals not to exceed 25 ft

Receptacles supplied from the emergency system shall have a distinctive color or marking on thereceptacle cover plates or the receptacles themselves.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 10:22:32 PST 2015

Committee Statement

CommitteeStatement:

The requirement for identifying emergency circuits is modified to address circuits that may notinclude junction boxes. The intent of 700.10(A) is to provide installers, maintainers and the AHJ withthe ability to identify components of an emergency circuit or system. There are many circuitsincluding but not limited to metal clad cable installations in lighting fixtures that use duplexconnectors without junction boxes. These circuits are required to be identified. It is not intended thatthe entire length of raceways and cable assemblies be identified and a maximum distance betweenmarkings of 25 feet is added for clarity.

ResponseMessage:

Public Comment No. 1129-NFPA 70-2015 [Section No. 700.10(A)]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

19 Affirmative All

1 Affirmative with Comments

0 Negative with Comments

0 Abstention

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

44 of 133 1/25/2016 1:23 PM

Page 44 of 133

Page 45: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

Affirmative with Comment

Currin, Jr., Richard D.

This revision will help inspectors.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

45 of 133 1/25/2016 1:23 PM

Page 45 of 133

Page 46: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3612-NFPA 70-2015 [ Section No. 700.10(D) [Excluding any

Sub-Sections] ]

Emergency systems shall meet the additional requirements in (D)(1) through (D)(3) in the followingoccupancies:

(1) assembly Assembly occupancies for not less than 1000 persons or in

(2) buildings Buildings above 23 m (75 ft) in height.

(3) Health care occupancies where persons are not capable of self preservation

(4) Educational occupancies with more than 300 occupants

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 13:46:01 PST 2015

Committee Statement

CommitteeStatement:

Fire protection of emergency systems is necessary in many venues in addition to high-rise buildingsand those buildings or portions of buildings with large occupancy loads. Schools (K-12) andInstitutional venues housing people who are incapable of self-preservation must also be included.Many schools and large hospitals are not high-rise buildings or classed as assembly occupancies,yet should require emergency systems that are protected from fire for a minimum of 2-hours.

ResponseMessage:

Public Comment No. 395-NFPA 70-2015 [Section No. 700.10(D) [Excluding any Sub-Sections]]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

16 Affirmative All

2 Affirmative with Comments

2 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

46 of 133 1/25/2016 1:23 PM

Page 46 of 133

Page 47: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Czarnecki, Neil A.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Rodriguez, Arnoldo L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

Affirmative with Comment

Currin, Jr., Richard D.

I agree with the addition of educational facilities with over 300 occupants being added to 700.10(D) as thesefacilities may house occupants that require more egress time than similar sized facilities with a differentoccupancy.

Paulsen, Shawn

The numbering layout is a bit confusing when reading the entire Rule. The Rule states that (D)(1)through (D)(3)isto be followed and directly underneath there are 4 requirements. I realize these are not the requirements to befollowed and suggest these 4 additional requirements possibly be lettered in place of numbering.

Negative with Comment

Degnan, James E.

Defining the extent of emergency system construction by building occupancy type should not be within NFPA 70,instead it should be in the appropriate building code. Building codes consider multiple aspects of life safety whichcannot be accounted for by an electrical code. Listing these items in NFPA 70 has the potential to lead to conflictswith building codes, leaving AHJs in quandary. Instead of expanded, this paragraph should be removed, otherwiseit will subsequently need to add other occupancy types to the list, with all of their corresponding building codedetails.

Savage, Sr., Michael L.

After much consideration and research I have not been able to locate where the absence of this requirement hasresulted in undo hardship or injury to the building or inhabitants. The provision for automatic fire sprinklers isalready mandated in these structures as noted in the building and life safety codes, which will provide not only lifesafety protection but property protection as well. The archived materials and fire reports I have read state thesprinkler systems engaged fires within their respective design times. I recently interviewed a Institutional UseConstruction Manager/Inspector, in preparation for the voting on this revision, and I was informed they prepare forand practice fire evacuations for their facility and were against the added cost this proposal would add toadditional buildings in their campus style installation. After researching the NFPA archives for additional fire data Ifeel I need to vote negative without any quantitative or empirical technical substantiation.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

47 of 133 1/25/2016 1:23 PM

Page 47 of 133

Page 48: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3604-NFPA 70-2015 [ Section No. 700.10(D)(1) ]

(1) Feeder-Circuit Wiring.

Feeder-circuit wiring shall be protected from fire for 2 hours using meet one of the followingmethods conditions :

(1) The cable or raceway is installed in spaces or areas that are fully protected by an approvedautomatic fire suppression system.

(2) The cable or raceway is protected by a listed electrical circuit protective system with a minimum2-hour fire rating.

Informational Note No. 1: Electrical circuit protective systems could include but not be limitedto thermal barriers, or a protective shaft and are tested to UL 1724, Fire Tests for ElectricalCircuit Protection Systems.

Informational Note No. 2: The listing organization provides information for electrical circuitprotective systems on proper installation requirements to maintain the fire rating.

(3) Be The cable or raceway is a listed fire fire- resistive cable system.

Informational Note No. 1: Fire- resistive cables are tested to ANSI/UL 2196, Tests for FireResistive Cables.

Informational Note No. 2: The listing organization provides information for fire-resistive cablesystems on proper installation requirements to maintain the fire rating.

(4) The cable or raceway is protected by a listed fire-rated assembly that has a minimum fire rating of 2hours and contains only emergency circuits

(5) The cable or raceway is encased in a minimum of 50 mm (2 in.) of concrete.

Supplemental Information

File Name Description

700.10_D_1_SR_3604_LM.docx Staff use only

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 10:53:05 PST 2015

Committee Statement

CommitteeStatement:

List item (4), for listed fire-rated assemblies with a minimum fire rating of 2 hours and containsonly emergency circuits was deleted during the FR cycle and is added in this second revision. Thismeans to achieve a 2-hour fire rating for emergency systems is time tested, and commonly used.

The permission to use 2-inches of concrete was also deleted in the first revision stage and isadded back in this revision. The absence of a dimension for the depth of concrete would causeserious confusion in practical application.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

48 of 133 1/25/2016 1:23 PM

Page 48 of 133

Page 49: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Public Comment No. 603-NFPA 70-2015 [Section No. 700.10(D)(1)]

Public Comment No. 786-NFPA 70-2015 [Section No. 700.10(D)(1)]

Public Comment No. 840-NFPA 70-2015 [Section No. 700.10(D)(1)]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

18 Affirmative All

0 Affirmative with Comments

2 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

Negative with Comment

Currin, Jr., Richard D.

There is no evidence to support that 2" of concrete provides a 2 hour rating. In fact there is evidence that impliesthe contrary and that it would require 4" or more of concrete encasement to provide a 2 hour fire rating. I wouldagree with this revision if it were limited to the application of slab on grade (SOG) cases. Since it is not specific toSOG that then ceilings and walls would be allowed as protection for conductors. This is an area that needs labtesting to be performed to determine temperatures that conductors are exposed too under various levels of

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

49 of 133 1/25/2016 1:23 PM

Page 49 of 133

Page 50: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

concrete thicknesses as well as different concrete mixes. The testing should include conductors installed ongrade, walls, and ceiling/floors.

Paulsen, Shawn

The term "not capable of self preservation" needs to be defined. An individual could enter a health careoccupancy being capable and for a portion of the stay not being capable of self preservation. For example would aDentist office be considered. As written I believe this term will lead to inconsistent application of the Rule.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

50 of 133 1/25/2016 1:23 PM

Page 50 of 133

Page 51: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3611-NFPA 70-2015 [ Section No. 700.10(D)(3) ]

(3) Generator Control Wiring.

Control conductors installed between the transfer equipment and the emergency generator shall be keptentirely independent of all other wiring and shall meet the conditions of 700.10(D)(1). Breakage,disconnecting, shorting of the wires, or loss of power to the remote start circuits control conductors shallcause immediate starting and continuous running of the generator and shall not prevent the starting of thegenerator(s) due to causes other than failure of these external control circuits. The integrity of thegenerator control wiring shall be continuously monitored. Loss of integrity of the remote start circuit(s)shall initiate visual and audible annunciation of generator malfunction at the generator local and remoteannunciator(s) and start the generator(s).

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 13:34:09 PST 2015

Committee Statement

CommitteeStatement:

The revised text provides necessary clarity. A generator cannot start if the control conductors losepower due to failed batteries. A new last sentence is added to require visual and audibleannunciation where a loss of power prevent the starting of the generator.

ResponseMessage:

Public Comment No. 1203-NFPA 70-2015 [Section No. 700.10(D)(3)]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

19 Affirmative All

1 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

51 of 133 1/25/2016 1:23 PM

Page 51 of 133

Page 52: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

Affirmative with Comment

Currin, Jr., Richard D.

I agree this change will enhance safety at a minimal cost by requiring generator controls to fail in the start mode.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

52 of 133 1/25/2016 1:23 PM

Page 52 of 133

Page 53: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3613-NFPA 70-2015 [ Section No. 700.12 [Excluding any

Sub-Sections] ]

Current supply shall be such that, in the event of failure of the normal supply to, or within, the building orgroup of buildings concerned, emergency lighting, emergency power, or both shall be available within thetime required for the application but not to exceed 10 seconds. The supply system for emergencypurposes, in addition to the normal services to the building and meeting the general requirements of thissection, shall be one or more of the types of systems described in 700.12(A) through (E). Unit equipmentin accordance with 700.12(F) shall satisfy the applicable requirements of this article.

In selecting an emergency source of power, consideration shall be given to the occupancy and the type ofservice to be rendered, whether of minimum duration, as for evacuation of a theater, or longer duration, asfor supplying emergency power and lighting due to an indefinite period of current failure from trouble eitherinside or outside the building.

Equipment shall be designed and located so as to minimize the hazards that might cause complete failuredue to flooding, fires, icing, and vandalism.

Equipment for sources of power as described in 700.12(A) through (E) shall be installed either in spacesfully protected by approved automatic fire suppression systems (sprinklers, carbon dioxide systems, andso forth) or in spaces with a 1-hour fire rating where located within the following:

(1) assembly Assembly occupancies for greater more than 1000 persons or in

(2) buildings Buildings above 23 m (75 ft) in height with any of the following occupancy classes —assembly, educational, residential, detention and correctional, business, and mercantile — shall beinstalled either in spaces fully protected by approved automatic fire suppression systems (sprinklers,carbon dioxide systems, and so forth) or in spaces with a 1-hour fire rating.

(3) Health care occupancies where persons are not capable of self-preservation

(4) Educational occupancies with more than 300 occupants

Informational Note No. 1: For the definition of Occupancy Classification, see Section 6.1 of NFPA101-2015, Life Safety Code.

Informational Note No. 2: For further information, see ANSI/IEEE 493-2007, RecommendedPractice for the Design of Reliable Industrial and Commercial Power Systems.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 13:55:34 PST 2015

Committee Statement

CommitteeStatement:

The action taken by the committee on the Second Revision to 700.10(D) to expand the fireprotection requirements in 700.10(D) requires that correlation occur in section 700.12.

This revision adds “health care occupancies where persons are not capable of self preservationand educational occupancies with more than 300 occupants” to correlate with the revisions in700.10(D).

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

53 of 133 1/25/2016 1:23 PM

Page 53 of 133

Page 54: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

This revision does not represent new material. Public input 1246 sought the revisions seen in theFR to modify 700.10(D). In the first revision stage public input 1246 was resolved. If a first revisionhad occurred in 700.10(D) as suggested in public comment 1246, a first revision to correlate in700.12 would have been necessary.

ResponseMessage:

Public Comment No. 563-NFPA 70-2015 [Section No. 700.12 [Excluding any Sub-Sections]]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

17 Affirmative All

2 Affirmative with Comments

1 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Rodriguez, Arnoldo L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

Affirmative with Comment

Currin, Jr., Richard D.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

54 of 133 1/25/2016 1:23 PM

Page 54 of 133

Page 55: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

I agree with the addition of educational facilities with over 300 occupants being added to 700.10(D) as thesefacilities may house occupants that require more egress time than similar sized facilities with a differentoccupancy.

Savage, Sr., Michael L.

I could support this proposal as it does reference the inclusion/exception for a sprinkler system, which should bean automatic sprinkler system.

Negative with Comment

Paulsen, Shawn

The term "not capable of self preservation" needs to be defined. An individual could enter a health careoccupancy being capable and for a portion of the stay not being capable of self preservation. For example would aDentist office be considered. As written I believe this term will lead to inconsistent application of the Rule.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

55 of 133 1/25/2016 1:23 PM

Page 55 of 133

Page 56: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3606-NFPA 70-2015 [ Section No. 700.12(A) ]

(A) Storage Battery.

Storage batteries shall be of suitable rating and capacity to supply and maintain the total load for aminimum period of 11⁄2 hours, without the voltage applied to the load falling below the load equipmentmanufacturer's minimum operating value 87 1 ⁄2 percent of normal . Automotive-type batteries shall not beused.

An automatic battery charging means shall be provided.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 11:11:48 PST 2015

Committee Statement

CommitteeStatement:

The 87.5% minimum battery retention threshold is reinstated. The minimum voltage requirementallows the power source and the load equipment to be independently certified and then mated inthe field without the need for field testing for compatibility. The related product standard (UL 924) isbenchmarked to this 87.5% threshold.

ResponseMessage:

Public Comment No. 431-NFPA 70-2015 [Section No. 700.12(A)]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

18 Affirmative All

1 Affirmative with Comments

1 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

56 of 133 1/25/2016 1:23 PM

Page 56 of 133

Page 57: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Caron, Daniel J.

Croushore, Timothy M.

Czarnecki, Neil A.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

Affirmative with Comment

Currin, Jr., Richard D.

This provides standardization of battery requirements.

Negative with Comment

Degnan, James E.

See my statement on SR 3612

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

57 of 133 1/25/2016 1:23 PM

Page 57 of 133

Page 58: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3607-NFPA 70-2015 [ Section No. 700.12(F)(2) ]

(2) Installation of Unit Equipment.

Unit equipment shall be installed in accordance with 700.12(F)(2)(1) through (6).

(1) The batteries shall be of suitable rating and capacity to supply and maintain the total lamp loadassociated with the unit in accordance with (a) or (b):.

(a) For a period of at least 11⁄2 hours without the voltage falling below the equipmentmanufacturer’s minimum operating voltage value 87 1 ⁄2 percent of normal battery voltage

(b) The unit equipment shall supply and maintain not less than 60 percent of the initialemergency illumination for a period of at least 11⁄2 hours

(2) Unit equipment shall be permanently fixed in place (i.e., not portable) in place and shall have allwiring to each unit installed in accordance with the requirements of any of the wiring methods inChapter 3. Flexible cord-and-plug connection shall be permitted, provided that the cord does notexceed 900 mm (3 ft) in length.

(3) The branch circuit feeding the unit equipment shall be the same branch circuit as that serving thenormal lighting in the area and connected ahead of any local switches.

Exception: In a separate and uninterrupted area supplied by a minimum of three normal lightingcircuits that are not part of a multiwire branch circuit, a separate branch circuit for unit equipmentshall be permitted if it originates from the same panelboard as that of the normal lighting circuitsand is provided with a lock-on feature.

(4) The branch circuit that feeds unit equipment shall be clearly identified at the distribution panel.

(5) Emergency luminaires that obtain power from a unit equipment and are not part of the unitequipment shall be wired to the unit equipment as required by 700.10 and by one of the wiringmethods of Chapter 3.

(6) Remote heads providing lighting for the exterior of an exit door shall be permitted to be supplied bythe unit equipment serving the area immediately inside the exit door.

Supplemental Information

File Name Description

700.12_F_2_SR_3607_LM.docx Staff use only

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 11:15:32 PST 2015

Committee Statement

CommitteeStatement:

The 87.5% minimum battery retention threshold is reinstated. The minimum voltage requirementallows the power source and the load equipment to be independently certified and then mated inthe field without the need for field testing for compatibility. The related product standard (UL 924) is

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

58 of 133 1/25/2016 1:23 PM

Page 58 of 133

Page 59: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

benchmarked to this 87.5% threshold.

Public Comment No. 433-NFPA 70-2015 [Section No. 700.12(F)(2)]

Public Comment No. 434-NFPA 70-2015 [Section No. 700.12(F)(2)]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

19 Affirmative All

1 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

Affirmative with Comment

Currin, Jr., Richard D.

This provides standardization of battery requirements.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

59 of 133 1/25/2016 1:23 PM

Page 59 of 133

Page 60: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3608-NFPA 70-2015 [ Section No. 701.6(D) ]

(D) Ground Fault.

To indicate a ground fault in solidly grounded wye, legally required standby systems of more than 150volts to ground and circuit-protective devices rated 1000 amperes or more. The sensor for the ground-faultsignal devices shall be located at, or ahead of, the main system disconnecting means for the legallyrequired standby source, and the maximum setting of the signal devices shall be for a ground-fault currentof 1200 amperes. Instructions on the course of action to be taken in event of indicated ground fault shallbe located at or near the sensor location.

For systems with multiple emergency sources connected to a paralleling bus, the ground fault sensorshall be permitted at an alternate location.

Informational Note: For signals for generator sets, see NFPA 110-2013, Standard for Emergencyand Standby Power Systems.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 11:26:01 PST 2015

Committee Statement

CommitteeStatement:

First level subdivision 701.6(D) is revised to correlate with the revision made in section700.6.

Response Message:

Public Comment No. 257-NFPA 70-2015 [Section No. 701.6(D)]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

19 Affirmative All

1 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

60 of 133 1/25/2016 1:23 PM

Page 60 of 133

Page 61: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

Affirmative with Comment

Currin, Jr., Richard D.

This is needed to correlate 700.6

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

61 of 133 1/25/2016 1:23 PM

Page 61 of 133

Page 62: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3609-NFPA 70-2015 [ Section No. 701.12(A) ]

(A) Storage Battery.

Storage batteries shall be of suitable rating and capacity to supply and maintain the total load for aminimum period of 11⁄2 hours without the voltage applied to the load falling below the load equipmentmanufacturer's minimum operating value 87 1 ⁄2 percent of normal . Automotive-type batteries shall not beused.

An automatic battery charging means shall be provided.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 11:27:45 PST 2015

Committee Statement

CommitteeStatement:

The 87.5% minimum battery retention threshold is reinstated. The minimum voltage requirementallows the power source and the load equipment to be independently certified and then mated inthe field without the need for field testing for compatibility. The related product standard (UL 924) isbenchmarked to this 87.5% threshold.

ResponseMessage:

Public Comment No. 432-NFPA 70-2015 [Section No. 701.12(A)]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

19 Affirmative All

1 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

62 of 133 1/25/2016 1:23 PM

Page 62 of 133

Page 63: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Caron, Daniel J.

Croushore, Timothy M.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

Affirmative with Comment

Currin, Jr., Richard D.

This provides standardization of battery requirements.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

63 of 133 1/25/2016 1:23 PM

Page 63 of 133

Page 64: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3610-NFPA 70-2015 [ Section No. 701.12(G) ]

(G) Unit Equipment.

Individual unit equipment for legally required standby illumination shall consist of the following:

(1) A rechargeable battery

(2) A battery charging means

(3) Provisions for one or more lamps mounted on the equipment and shall be permitted to haveterminals for remote lamps

(4) A relaying device arranged to energize the lamps automatically upon failure of the supply to the unitequipment

The batteries shall be of suitable rating and capacity to supply and maintain the total lamp load associatedwith the unit for not less than (a) or (b):

(a) For a period of 11⁄2 hours, without the voltage falling below the equipment manufacturer’sminimum operating voltage value 87 1 ⁄2 percent of normal voltage

(b) The unit equipment shall supply and maintain not less than 60 percent of the initial emergencyillumination for a period of at least 11⁄2 hours.

Unit equipment shall be permanently fixed in place (i.e., not portable) and shall have all wiring to each unitinstalled in accordance with the requirements of any of the wiring methods in Chapter 3. Flexiblecord-and-plug connection shall be permitted, provided that the cord does not exceed 900 mm (3 ft) inlength. The branch circuit feeding the unit equipment shall be the same branch circuit as that serving thenormal lighting in the area and connected ahead of any local switches. Legally required standbyluminaires that obtain power from a unit equipment and are not part of the unit equipment shall be wired tothe unit equipment by one of the wiring methods of Chapter 3.

Exception: In a separate and uninterrupted area supplied by a minimum of three normal lighting circuits,a separate branch circuit for unit equipment shall be permitted if it originates from the same panelboardas that of the normal lighting circuits and is provided with a lock-on feature.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 11:29:50 PST 2015

Committee Statement

CommitteeStatement:

The 87.5% minimum battery retention threshold is reinstated. The minimum voltage requirementallows the power source and the load equipment to be independently certified and then mated inthe field without the need for field testing for compatibility. The related product standard (UL 924) isbenchmarked to this 87.5% threshold.

ResponseMessage:

Public Comment No. 435-NFPA 70-2015 [Section No. 701.12(G)]

Public Comment No. 436-NFPA 70-2015 [Section No. 701.12(G)]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

64 of 133 1/25/2016 1:23 PM

Page 64 of 133

Page 65: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

19 Affirmative All

1 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

Affirmative with Comment

Currin, Jr., Richard D.

This provides standardization of battery requirements. Also the 87.5% value matches UL standard 94.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

65 of 133 1/25/2016 1:23 PM

Page 65 of 133

Page 66: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3643-NFPA 70-2015 [ Section No. 706.1 ]

706.1 Scope.

This article applies to all permanently installed energy storage systems (ESS) operating at over 50 voltsac or 60 volts dc that may be stand-alone or interactive with other electric power production sources.

Informational Note: The following standards are frequently referenced for the installation of energystorage systems:

(1) NFPA 111-2013, Standard on Stored Electrical Energy Emergency and Standby Systems

(2) IEEE 484-2008, Recommended Practice for Installation Design and Installation of VentedLead-Acid Batteries for Stationary Applications

(3) IEEE 485-1997, Recommended Practice for Sizing Vented Lead-Acid Storage Batteries forStationary Applications

(4) IEEE 1145-2007, Recommended Practice for Installation and Maintenance of Nickel-CadmiumBatteries for Photovoltaic (PV) Systems

(5) IEEE 1187-2002, Recommended Practice for Installation Design, and Installation of Valve-Regulated Lead-Acid Batteries for Stationary Applications

(6) IEEE 1578-2007, Recommended Practice for Stationary Battery Electrolyte Spill Containmentand Management

(7) IEEE 1635/ASHRAE 21-2012, Guide for the Ventilation and Thermal Management ofStationary Battery Installations Batteries for Stationary Applications

(8) UL 810A, Electrochemical Capacitors

(9) UL 1973, Batteries for Use in Light Electric Rail (LER) Applications and StationaryApplications

(10) UL 1989, Standard for Standby Batteries

(11) UL Subject 2436, Spill Containment For Stationary Lead Acid Battery Systems

(12) UL Subject 9540, Safety of Energy Storage Systems and Equipment

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 11 12:33:04 PST 2015

Committee Statement

CommitteeStatement:

The scope of Article 706 is modified to specifically limit application to systems over 50 volts ACor 60 volts DC to correlate with existing NEC requirements.

ResponseMessage:

Ballot Results

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

66 of 133 1/25/2016 1:23 PM

Page 66 of 133

Page 67: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

This item has passed ballot

21 Eligible Voters

1 Not Returned

18 Affirmative All

2 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

Affirmative with Comment

Croushore, Timothy M.

The dates (editions) are included with the referenced material of Second Revision 3643 which is consistent withthe requirements of the NFPA Regulations and Procedures-Regulations Governing the Development of NFPAStandards-3.3.6.2 Reference to Other NFPA Standards or Other Publications. Please see my negative commenton SR 3628.

Currin, Jr., Richard D.

The change is needed to correlate with the new 60 volts DC level that is throughout the code.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

67 of 133 1/25/2016 1:23 PM

Page 67 of 133

Page 68: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3633-NFPA 70-2015 [ Definition: Battery Terminal. ]

Battery Terminal.

That part of a cell, container, or battery to which an external connection is made (commonly identified asa post, pillar, pole, or terminal post).

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 11 08:38:01 PST 2015

Committee Statement

CommitteeStatement:

Deleting "Battery" from the title aligns this definition with the definition of "terminal" inArticle 480.

Response Message:

Public Comment No. 1712-NFPA 70-2015 [Definition: Battery Terminal.]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

19 Affirmative All

1 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Czarnecki, Neil A.

Degnan, James E.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

68 of 133 1/25/2016 1:23 PM

Page 68 of 133

Page 69: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

Affirmative with Comment

Currin, Jr., Richard D.

This allows for clarity and allows the definition to match article 480.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

69 of 133 1/25/2016 1:23 PM

Page 69 of 133

Page 70: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3634-NFPA 70-2015 [ Definition: Electrochemical Battery. ]

Electrochemical Battery.

A battery comprised of one or more rechargeable cells of the lead-acid, nickel-cadmium, or otherrechargeable electrochemical types.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 11 08:42:09 PST 2015

Committee Statement

Committee Statement: Batteries can be electrochemical or other types depending on the technology.

Response Message:

Public Comment No. 1478-NFPA 70-2015 [Definition: Electrochemical Battery.]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

19 Affirmative All

1 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

70 of 133 1/25/2016 1:23 PM

Page 70 of 133

Page 71: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

Affirmative with Comment

Currin, Jr., Richard D.

I agree with removing this definition as it was not needed.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

71 of 133 1/25/2016 1:23 PM

Page 71 of 133

Page 72: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3635-NFPA 70-2015 [ Definition: Energy Storage System,

Pre-engineered of Matche... ]

Energy Storage System, Pre-engineered Engineered of Matched Components.

Energy storage systems that are not self-contained systems but instead are provided as separatecomponents of pre-engineered and field-assembled using separate components supplied as a system bya singular entity that are matched and intended to be assembled as an energy storage system at thesystem installation site.

Informational Note: Pre-engineered systems of matched components for field assembly as asystem will generally be designed by a single entity and comprised of components that are testedand listed separately or as an assembly to safety standards relevant to the component and readilyassembled on site as a system and connected on site to the electrical system .

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 11 08:45:01 PST 2015

Committee Statement

CommitteeStatement:

This revision eliminates redundant text and provides necessary clarity by inserting“pre-engineered” and “field-assembled”.

ResponseMessage:

Public Comment No. 1258-NFPA 70-2015 [Definition: Energy Storage System, Pre-engineered of Matche...]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

20 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

72 of 133 1/25/2016 1:23 PM

Page 72 of 133

Page 73: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Currin, Jr., Richard D.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

73 of 133 1/25/2016 1:23 PM

Page 73 of 133

Page 74: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3658-NFPA 70-2015 [ Definition: Energy Storage System,

Self-contained. ]

Energy Storage System, Self-contained Contained .

Energy storage systems where the energy storage devices components such as cells, batteries, ormodules and any necessary controls, ventilation, illumination, fire suppression, or alarm systems areassembled, installed, and packaged into a singular energy storage container or unit.

Informational Note: Self-contained systems will generally be manufactured by a single entity, testedand listed to safety standards relevant to the system, and readily connected on site to the electricalsystem and in the case of multiple systems to each other.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 11 16:34:34 PST 2015

Committee Statement

CommitteeStatement:

This action revises multiple definitions to delete the undefined term “energy storage device”.For correlation purposes, similar changes were made throughout Article 706.

ResponseMessage:

Public Comment No. 1116-NFPA 70-2015 [Definitions (706.2): Electrolyte... to Energy Stor...]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

20 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

74 of 133 1/25/2016 1:23 PM

Page 74 of 133

Page 75: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Currin, Jr., Richard D.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

75 of 133 1/25/2016 1:23 PM

Page 75 of 133

Page 76: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3659-NFPA 70-2015 [ Definition: Flow Battery. ]

Flow Battery.

An energy storage device component similar to a fuel cell that stores its active materials in the form of twoelectrolytes external to the reactor interface. When in use, the electrolytes are transferred between reactorand storage tanks.

Informational Note: Two commercially available flow battery technologies are zinc bromine andvanadium redox, sometimes referred to as pumped electrolyte ESS.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 11 16:36:20 PST 2015

Committee Statement

CommitteeStatement:

This action revises multiple definitions to delete the undefined term “energy storage device”.For correlation purposes, similar changes were made throughout Article 706.

ResponseMessage:

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

20 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

76 of 133 1/25/2016 1:23 PM

Page 76 of 133

Page 77: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Currin, Jr., Richard D.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

77 of 133 1/25/2016 1:23 PM

Page 77 of 133

Page 78: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3636-NFPA 70-2015 [ Definition: Intertier Connector. ]

Intertier Connector.

In an electrochemical a battery system, an electrical conductor used to connect two cells on different tiersof the same rack or different shelves of the same rack.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 11 08:50:42 PST 2015

Committee Statement

CommitteeStatement:

This revision provides necessary clarity to this definition, which addresses a “connector” notthe battery.

Response Message:

Public Comment No. 1094-NFPA 70-2015 [Definition: Intertier Connector.]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

20 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Currin, Jr., Richard D.

Czarnecki, Neil A.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

78 of 133 1/25/2016 1:23 PM

Page 78 of 133

Page 79: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

79 of 133 1/25/2016 1:23 PM

Page 79 of 133

Page 80: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3639-NFPA 70-2015 [ Section No. 706.3 ]

706.3 Other Articles.

Wherever the requirements of other articles of this Code and Article 706 differ, the requirements of Article706 shall apply. If the ESS is capable of being operated in parallel with a primary source(s) of electricity,the requirements in 705.6, 705.14, 705.16, 705.32, and 705.100, 705.143, and Part IV of Article 705shall apply.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 11 09:08:13 PST 2015

Committee Statement

CommitteeStatement:

The references to other articles are editorially revised and supplemented for correlationthroughout the NEC. The panel notes that action taken by Panel 4 to revise Part IV of Article 705may affect the reference added in this revision.

ResponseMessage:

Public Comment No. 1682-NFPA 70-2015 [Section No. 706.3]

Public Comment No. 1480-NFPA 70-2015 [Section No. 706.3]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

19 Affirmative All

1 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

80 of 133 1/25/2016 1:23 PM

Page 80 of 133

Page 81: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Caron, Daniel J.

Currin, Jr., Richard D.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

Affirmative with Comment

Croushore, Timothy M.

I am in agreement with the additional sections and Part IV of Article 705 referenced in the text of 706.3 OtherArticles. However, the action on Second Revision 3939 needs to be correlated with the action on Second Revision3645 and have 705.40 added to the list of referenced sections in 706.3 Other Articles. Section 706.3 shouldappear as follows: 706.3 Other Articles. Whenever the requirements of other articles of this Code and Article 706differ, the requirements of Article 706 shall apply. If the ESS is capable of being operated in parallel with a primarysource(s) of electricity, the requirements in 705.6, 705.14, 705.16, 705.32, 705.40, 705.100, 705.143, and Part IVof Article 705 shall apply.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

81 of 133 1/25/2016 1:23 PM

Page 81 of 133

Page 82: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3640-NFPA 70-2015 [ Section No. 706.4 ]

706.4 System Classification.

ESS shall be classified as one of the types described as follows:

(1) ESS, Self self -contained ESS

Informational Note: Some self-contained systems may be listed.

(2) ESS, Pre pre -engineered of matched components ESS intended for field assembly as a system

(3) Energy storage system ESS , other

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 11 09:31:15 PST 2015

Committee Statement

Committee Statement: This revision aligns the terms with definitions in 706.2.

Response Message:

Public Comment No. 1115-NFPA 70-2015 [Section No. 706.4]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

20 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

82 of 133 1/25/2016 1:23 PM

Page 82 of 133

Page 83: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Croushore, Timothy M.

Currin, Jr., Richard D.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

83 of 133 1/25/2016 1:23 PM

Page 83 of 133

Page 84: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3641-NFPA 70-2015 [ Section No. 706.5 ]

706.5 Equipment.

Monitors and , controls, switches, fuses, and circuit breakers, power conversion systems, inverters andtransformers, energy storage devices components , and other components of the energy storage systemother than lead-acid batteries, shall be listed for the intended application as a part of an energy storagesystem and labeled . Alternatively, prepackaged self-contained systems ESS shall be permitted to belisted for the intended application listed and labeled as a complete energy storage system. Only inverterslisted and identified as interactive shall be permitted on interactive systems.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 11 10:39:50 PST 2015

Committee Statement

CommitteeStatement:

This revision removes listing requirements for “lead-acid batteries” to correlate with the SecondRevision in Article 480. Multiple editorial revisions are made for clarity and usability. This revisionclarifies that self contained ESS are required to be listed.

ResponseMessage:

Public Comment No. 1557-NFPA 70-2015 [Section No. 706.5]

Public Comment No. 1637-NFPA 70-2015 [Section No. 706.5]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

20 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

84 of 133 1/25/2016 1:23 PM

Page 84 of 133

Page 85: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Currin, Jr., Richard D.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

85 of 133 1/25/2016 1:23 PM

Page 85 of 133

Page 86: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3642-NFPA 70-2015 [ Section No. 706.7(D) ]

(D) Notification.

The disconnecting means shall be legibly marked in the field. A label with the The marking shall beplaced in a conspicuous location near the ESS if a disconnecting means is not provided. The markingshall be of sufficient durability to withstand the environment involved meet the requirements of 110.21(B)and shall include the following:

(1) Nominal ESS voltage

(2) Maximum available fault short-circuit current derived from the ESS

(3) Arc flash risk assessment at the disconnecting means and a hazard warning meeting therequirements of 110.16 .

(4) Date the calculation was performed

Informational Note: Battery equipment suppliers can provide information about short-circuitcurrent on any particular battery model.NFPA 70E-2015 , Standard for Electrical Safety inthe Workplace , provides requirements for arc flash risk assessment.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 11 11:15:55 PST 2015

Committee Statement

CommitteeStatement:

The second sentence was deleted as there is no exception in 706.7 (A) to allow the disconnect tobe omitted. “Fault current” was changed to “short circuit current” for proper terminology. Arc flashrisk assessment was expanded to include marking requirements in 110.16.

ResponseMessage:

Public Comment No. 1102-NFPA 70-2015 [Section No. 706.7(D)]

Public Comment No. 1137-NFPA 70-2015 [Section No. 706.7(D)]

Public Comment No. 1184-NFPA 70-2015 [Section No. 706.7(D)]

Public Comment No. 1596-NFPA 70-2015 [Section No. 706.7(D)]

Public Comment No. 1714-NFPA 70-2015 [Section No. 706.7(D)]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

19 Affirmative All

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

86 of 133 1/25/2016 1:23 PM

Page 86 of 133

Page 87: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

0 Affirmative with Comments

1 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Currin, Jr., Richard D.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

Negative with Comment

Paulsen, Shawn

706.7(D)(3) makes reference to the label including Arc flash risk assessment information at the disconnectingmeans meeting the requirements of 110.16. In reviewing the proposed revisions to 110.16(B) it appear thatinformation related to the arc flash risk assessment such as: available incident energy, arc rating of clothing andsite specific PPE is being removed. If this proposed change is accepted for 110.16(B) then 706.7(D)(3) will need tobe revised.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

87 of 133 1/25/2016 1:23 PM

Page 87 of 133

Page 88: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3644-NFPA 70-2015 [ Section No. 706.7(E) ]

(E) Partitions and Distance.

Where energy storage device system input and output terminals are more than 1.5 m (5 ft) fromconnected equipment, or where the circuits from these terminals pass through a wall or partition, theinstallation shall comply with the following:

(1) A disconnecting means and overcurrent protection shall be provided at the energy storagedevice system end of the circuit. Fused disconnecting means or circuit breakers shall be permitted tobe used.

(2) A second disconnecting means located at the connected equipment shall be installed where thedisconnecting means required by 706.7(E)(1) is not within sight of the connected equipment.

Informational Note No. 1: For remote disconnect controls in information technologyequipment rooms, see 645.10 .

Note: For overcurrent protection of batteries, see 240.21(H) .

(3) Where fused disconnecting means are used, the line terminals of the disconnecting means shall beconnected toward the energy storage device system terminals.

(4) Overcurrent devices or disconnecting Disconnecting means shall not be permitted to be installed inenergy storage device system enclosures where explosive atmospheres can exist if listed forhazardous locations .

(4) A second disconnecting means located at the connected equipment shall be installed where thedisconnecting means required by 706.7(E) (1) is not within sight of the connected equipment.

(5) Where the energy storage device disconnecting means in (1) is not within sight of the ESSdisconnecting means in (2) , placards or directories shall be installed at the locations of alldisconnecting means indicating the location of all other disconnecting means.

Supplemental Information

File Name Description

706.7_E_SR_3644_LM.docx Staff use only

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 11 13:16:59 PST 2015

Committee Statement

CommitteeStatement:

List items are editorially revised for clarity.

References to overcurrent protection and overcurrent devices are deleted as this sectionaddresses only disconnecting means.

New list item (4) is modified for clarity to reference hazardous locations.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

88 of 133 1/25/2016 1:23 PM

Page 88 of 133

Page 89: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

New informational notes are added to aid the Code user.

Additional editorial corrections are made for clarity.

ResponseMessage:

Public Comment No. 1119-NFPA 70-2015 [Section No. 706.7(E)]

Public Comment No. 1186-NFPA 70-2015 [Section No. 706.7(E)]

Public Comment No. 1117-NFPA 70-2015 [Section No. 706.7(E)]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

20 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Currin, Jr., Richard D.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

89 of 133 1/25/2016 1:23 PM

Page 89 of 133

Page 90: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Windey, Timothy P.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

90 of 133 1/25/2016 1:23 PM

Page 90 of 133

Page 91: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3647-NFPA 70-2015 [ Section No. 706.8(B) ]

(B) Identified Interactive Equipment.

Only inverters and ac modules listed and labeled or identified as interactive shall be permitted oninteractive systems.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 11 14:15:09 PST 2015

Committee Statement

CommitteeStatement:

“Listed and labeled, or identified” is the correct terminology. Stated in this manner therequirement provides a choice for compliance.

ResponseMessage:

Public Comment No. 1646-NFPA 70-2015 [Section No. 706.8(B)]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

20 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Currin, Jr., Richard D.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

91 of 133 1/25/2016 1:23 PM

Page 91 of 133

Page 92: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

92 of 133 1/25/2016 1:23 PM

Page 92 of 133

Page 93: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3645-NFPA 70-2015 [ Section No. 706.8(C) ]

(C) Loss of Interactive System Power.

An inverter in an interactive energy storage system shall automatically de-energize its output to theconnected electrical production and distribution network upon loss of voltage in that system and shallremain in that state until the electrical production and distribution network voltage has been restored. Anormally interactive energy storage system shall be permitted to operate as a stand-alone system tosupply loads that have been disconnected from electrical production and distribution networksources. Upon loss of primary source, an ESS with a utility interactive inverter shall comply with therequirements of 705.40 .

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 11 13:29:02 PST 2015

Committee Statement

Committee Statement: This revision references 705.40 directly instead of rephrasing language.

Response Message:

Public Comment No. 1273-NFPA 70-2015 [Section No. 706.8(C)]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

19 Affirmative All

1 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

93 of 133 1/25/2016 1:23 PM

Page 93 of 133

Page 94: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Currin, Jr., Richard D.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

Affirmative with Comment

Croushore, Timothy M.

I am in agreement with the deletion of the text of 706.8(C) describing the requirements for Loss of InteractiveSystem Power and including the reference to 705.40. However, this action needs to be correlated with the actionon Second Revision 3639 and added to the list of referenced sections in 706.3 Other Articles.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

94 of 133 1/25/2016 1:23 PM

Page 94 of 133

Page 95: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3646-NFPA 70-2015 [ Section No. 706.20(A) ]

(A) Maximum Rated Current for a Specific Circuit.

The maximum current for the specific circuit shall be calculated in accordance with 706.20(A)(1) through(A)(5).

(1) Nameplate- Rated Circuit Current.

The nameplate(s)- rated circuit current shall be the rated current indicated on the ESS nameplate(s) orsystem listing for pre-engineered or self-contained systems of matched components intended for fieldassembly as a system.

(2) Inverter Output Circuit Current.

The maximum current shall be the inverter continuous output current rating.

(3) Inverter Input Circuit Current.

The maximum current shall be the continuous inverter input current rating when the inverter is producingrated power at the lowest input voltage.

(4) Inverter Utilization Output Circuit Current.

The maximum current shall be the continuous inverter output current rating when the inverter is producingrated power at the lowest input voltage.

(5) DC to DC Converter Output Current.

The maximum current shall be the dc-to-dc converter continuous output current rating.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 11 13:53:32 PST 2015

Committee Statement

Committee Statement: A first level subdivision title is added as required by the NEC Style Manual.

Response Message:

Public Comment No. 1139-NFPA 70-2015 [Section No. 706.20(A)]

Public Comment No. 1715-NFPA 70-2015 [Section No. 706.20(A)]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

20 Affirmative All

0 Affirmative with Comments

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

95 of 133 1/25/2016 1:23 PM

Page 95 of 133

Page 96: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Currin, Jr., Richard D.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

96 of 133 1/25/2016 1:23 PM

Page 96 of 133

Page 97: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3648-NFPA 70-2015 [ Section No. 706.21 ]

706.21 Overcurrent Protection.

(A) Circuits and Equipment.

Energy storage ESS circuit conductors shall be protected in accordance with the requirements of Article240. Protection devices for ESS circuits shall be in accordance with the requirements of706.21(B)706.21(B)706.11(B) through (F). Circuits shall be protected at the source from overcurrent.

(B) Overcurrent Device Ampere Ratings.

Overcurrent protective devices, where required, shall be rated in accordance with Article 240 and therating provided on systems serving the ESS and shall be not less than 125 percent of the maximumcurrents calculated in 706.20(A)706.10(A) .

(C) Direct Current Rating.

Overcurrent protective devices, either fuses or circuit breakers, used in any dc portion of an ESS shall belisted and labeled for dc and shall have the appropriate voltage, current, and interrupting ratings for theapplication .

(D) Prime Movers.

Overcurrent protection shall not be required for conductors from an ESS with a nominal voltage of 50volts or less if these conductors provide power for starting, ignition, or control of prime movers. Section300.3 shall not apply to these conductors.

(D) Current Limiting.

A listed, and labeled current-limiting, overcurrent protective device shall be installed in adjacent to theESS for each dc output circuit adjacent to the ESS .

Exception: Where current-limiting overcurrent protection is provided for the dc output circuits of a listedand labeled ESS, additional current-limiting overcurrent devices shall not be required.

(E) Fuses.

Means shall be provided to disconnect any fuses associated with ESS equipment and components whenthe fuse is energized from both directions and is accessible to other than qualified persons. Switches,pullouts, or similar devices that are rated for the application shall be permitted to serve as a means todisconnect fuses from all sources of supply.

(F) Location.

Where ESS input and output terminals are more than 1.5 m (5 ft) from connected equipment, or wherethe circuits from these terminals pass through a wall or partition, overcurrent protection shall beprovided at the ESS.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 11 14:38:20 PST 2015

Committee Statement

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

97 of 133 1/25/2016 1:23 PM

Page 97 of 133

Page 98: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

CommitteeStatement:

This revision editorially revises first level subdivisions (A)(B), and (C). First level subdivision (D) isdeleted as it is presently covered in Article 480. First level subdivision (E) (now (D)) is revised forclarity and a new exception is added to address situations where current limiting overcurrentprotection is provided for the dc output circuits of a listed and labeled ESS. A new first levelsubdivision (F) is added to clarify the location of the required OCPD where conductors pass througha wall or partition.

ResponseMessage:

Public Comment No. 1112-NFPA 70-2015 [Section No. 706.21(A)]

Public Comment No. 1121-NFPA 70-2015 [Section No. 706.21]

Public Comment No. 1193-NFPA 70-2015 [Section No. 706.21(A)]

Public Comment No. 1194-NFPA 70-2015 [Section No. 706.21(B)]

Public Comment No. 1196-NFPA 70-2015 [Section No. 706.21(E)]

Public Comment No. 1280-NFPA 70-2015 [Section No. 706.21(E)]

Public Comment No. 1393-NFPA 70-2015 [Section No. 706.21(E)]

Public Comment No. 1605-NFPA 70-2015 [Sections 706.21(A), 706.21(B), 706.21(C)]

Public Comment No. 1629-NFPA 70-2015 [Section No. 706.21(C)]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

20 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Currin, Jr., Richard D.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

98 of 133 1/25/2016 1:23 PM

Page 98 of 133

Page 99: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

99 of 133 1/25/2016 1:23 PM

Page 99 of 133

Page 100: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3649-NFPA 70-2015 [ Section No. 706.22 ]

706.22 Wiring from and Equipment Supplied by Energy Storage Systems.

Wiring and equipment supplied from ESS(s) and system components shall be subject to the applicableprovisions of this Code applying to wiring and equipment operating at the same voltage, unlessotherwise permitted by this article.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 11 14:50:09 PST 2015

Committee Statement

CommitteeStatement:

Section 706.22 is deleted because it did not contain a requirement, only references to otherareas of the NEC.

Response Message:

Public Comment No. 1281-NFPA 70-2015 [Section No. 706.22]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

20 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Currin, Jr., Richard D.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

100 of 133 1/25/2016 1:23 PM

Page 100 of 133

Page 101: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

101 of 133 1/25/2016 1:23 PM

Page 101 of 133

Page 102: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3650-NFPA 70-2015 [ Section No. 706.23(C) ]

(C) Charge controllers and DC-to-DC converters.

When charge controllers and other dc-to-dc power converters that increase or decrease the outputcurrent or output voltage with respect to the input current or input voltage are installed, requirements shallcomply with all of the following:

(1) the The ampacity of the conductors in output circuits shall be based on the maximum ratedcontinuous output current of the charge controller or converter for the selected output voltage range,and .

(2) the The voltage rating of the output circuits shall be based on the maximum voltage output of thecharge controller or converter for the selected output voltage range.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 11 15:10:29 PST 2015

Committee Statement

CommitteeStatement:

The requirement is split into list items for clarity and “dc power converters” is changed to“DC-DC power converters”.

ResponseMessage:

Public Comment No. 1140-NFPA 70-2015 [Section No. 706.23(C)]

Public Comment No. 1720-NFPA 70-2015 [Section No. 706.23(C)]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

20 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

102 of 133 1/25/2016 1:23 PM

Page 102 of 133

Page 103: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Currin, Jr., Richard D.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

103 of 133 1/25/2016 1:23 PM

Page 103 of 133

Page 104: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3651-NFPA 70-2015 [ Section No. 706.30 ]

706.30 Installation of Batteries.

Storage batteries associated with an ESS shall be installed in accordance with the provisions thisarticle.

(A) Dwelling Units.

ESSs An ESS for dwellings shall be configured so as to operate at a voltage of 100 volts or less dwellingunits shall not exceed 100 volts between conductors or to ground .

Exception: Where live parts are not accessible during routine ESS maintenance, an ESS voltagegreater than exceeding 100 volts shall be permitted.

(B) Storage System Nonconductive Cases and Conductive Racks.

Flooded, vented lead-acid batteries where operating at more than 100 volts shall not use conductivecases or shall not be installed in conductive cases. Conductive racks used to support nonconductivecases shall be permitted where no rack material is located within 150 mm (6 in.) of the tops of thenonconductive cases.

Exception: This requirement shall not apply to any type of valve-regulated lead-acid (VRLA) batteryor other types of sealed batteries that may require steel cases for proper operation.

Note: Parts VI and VII of Article 250 address exposed metal parts.

(B) Disconnection of Series Battery Circuits.

Battery circuits subject to field servicing, where operating at more than 100 volts exceeding 240 voltsnominal between conductors or to ground , shall have provisions to disconnect the series-connectedstrings into segments of 100 volts or less not exceeding 240 volts nominal for maintenance by qualifiedpersons. Non–load-break bolted or plug-in disconnects shall be permitted.

(C) Storage System Maintenance Disconnecting Means.

ESS greater than exceeding 100 volts between conductors or to ground shall have a disconnectingmeans, accessible only to qualified persons, that disconnects the ungrounded and grounded circuitconductor(s) in the electrical storage system for maintenance. This disconnecting means shall notdisconnect the grounded circuit conductor(s) for the remainder of any other electrical system. A non–load-break-rated switch shall be permitted to be used as a disconnecting means.

(D) Storage Systems of More Than 100 Volts.

On electrochemical ESS operating at more than exceeding 100 volts between the conductors or toground , the system battery circuits shall be permitted to operate with ungrounded conductors, provided aground-fault detector and indicator is installed to monitor for ground faults within the storage system.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 11 15:47:27 PST 2015

Committee Statement

Committee Statement: The parent text to 706.30 has been removed for clarity.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

104 of 133 1/25/2016 1:23 PM

Page 104 of 133

Page 105: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

This revision editorially revises first level subdivision (A) and the associated exception.

First level subdivision (B) is deleted as this requirement presently exists in Article 480.

First level subdivisions (C), (D), and (E) (now (B), (C), and (D)) are editorially revised.

The 100 volt threshold in (C) (now (D)) is modified to address current practice.

Response Message:

Public Comment No. 1257-NFPA 70-2015 [Section No. 706.30(E)]

Public Comment No. 1485-NFPA 70-2015 [Section No. 706.30(E)]

Public Comment No. 1507-NFPA 70-2015 [Section No. 706.30(B)]

Public Comment No. 1512-NFPA 70-2015 [Section No. 706.30(D)]

Public Comment No. 1526-NFPA 70-2015 [Section No. 706.30]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

20 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Currin, Jr., Richard D.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

105 of 133 1/25/2016 1:23 PM

Page 105 of 133

Page 106: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

106 of 133 1/25/2016 1:23 PM

Page 106 of 133

Page 107: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3652-NFPA 70-2015 [ Section No. 706.34 [Excluding any

Sub-Sections] ]

Electrochemical battery Battery locations shall conform to 706.34(A) , (B), and (C).

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 11 15:56:03 PST 2015

Committee Statement

Committee Statement: This revision deletes electrochemical for clarity and correlation throughout Article 706.

Response Message:

Public Comment No. 1487-NFPA 70-2015 [Section No. 706.34 [Excluding any Sub-Sections]]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

20 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Currin, Jr., Richard D.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

107 of 133 1/25/2016 1:23 PM

Page 107 of 133

Page 108: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

108 of 133 1/25/2016 1:23 PM

Page 108 of 133

Page 109: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3653-NFPA 70-2015 [ Section No. 706.34(B) ]

(B) Top Terminal Batteries.

Where top terminal electrochemical energy storage devices batteries are installed on tiered racks or onshelves of battery cabinets, working space in accordance with the storage equipment manufacturer’sinstructions shall be provided between the highest point on a storage system component and the row,shelf, or ceiling above that point.

Informational Note No. 1: The installation instructions of the system component manufacturertypically define how much top working space is necessary for a particular system component.

Informational Note: IEEE 1187 provides guidance for top clearance of VRLA batteries, which arethe most commonly used battery in cabinets.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 11 16:03:38 PST 2015

Committee Statement

CommitteeStatement:

Informational Note 1 is removed to correlate with Article 480. The language in first levelsubdivision (B) is revised for clarity.

ResponseMessage:

Public Comment No. 1493-NFPA 70-2015 [Section No. 706.34(B)]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

20 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

109 of 133 1/25/2016 1:23 PM

Page 109 of 133

Page 110: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Currin, Jr., Richard D.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

110 of 133 1/25/2016 1:23 PM

Page 110 of 133

Page 111: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3654-NFPA 70-2015 [ Section No. 706.34(C) ]

(C) Gas Piping.

Gas piping shall not be permitted in dedicated battery rooms or spaces dedicated to electrochemicalESS .

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 11 16:07:39 PST 2015

Committee Statement

Committee Statement: First level subdivision (C) is editorially revised as 706.34 addresses battery locations only.

Response Message:

Public Comment No. 1498-NFPA 70-2015 [Section No. 706.34(C)]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

20 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Currin, Jr., Richard D.

Czarnecki, Neil A.

Degnan, James E.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

111 of 133 1/25/2016 1:23 PM

Page 111 of 133

Page 112: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

112 of 133 1/25/2016 1:23 PM

Page 112 of 133

Page 113: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3655-NFPA 70-2015 [ Section No. 706.35 ]

706.35 Vents.

(A) Vented Cells.

Each vented cell shall be equipped with a flame arrester.

Informational Note: A flame arrested is designed to prevent destruction of the cell due to ignitionof gases within the cell by an external spark or flame under normal operating conditions.

(B) Sealed Cells.

Sealed battery or cells shall be permitted to be equipped with a pressure-release vent to preventexcessive accumulation of gas pressure.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 11 16:10:11 PST 2015

Committee Statement

Committee Statement: The material covered by 706.35 is presently covered adequately in Article 480.

Response Message:

Public Comment No. 1539-NFPA 70-2015 [Section No. 706.35]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

20 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

113 of 133 1/25/2016 1:23 PM

Page 113 of 133

Page 114: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Caron, Daniel J.

Croushore, Timothy M.

Currin, Jr., Richard D.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

114 of 133 1/25/2016 1:23 PM

Page 114 of 133

Page 115: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3656-NFPA 70-2015 [ Section No. 706.42 ]

706.42 Electrolyte Containment.

Flow battery systems shall be provided with a means for electrolyte containment to prevent spills ofelectrolyte from the system. An alarm system is to shall be provided to signal an electrolyte leaks fromthe system. Electrical wiring and connections shall be located and routed in a manner that mitigates thepotential for exposure to electrolytes.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 11 16:17:12 PST 2015

Committee Statement

CommitteeStatement:

This revision changes “leaks” to “leak” and modifies the second paragraph for compliancewith the NEC Style Manual.

ResponseMessage:

Public Comment No. 1197-NFPA 70-2015 [Section No. 706.42]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

20 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

115 of 133 1/25/2016 1:23 PM

Page 115 of 133

Page 116: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Currin, Jr., Richard D.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

116 of 133 1/25/2016 1:23 PM

Page 116 of 133

Page 117: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3657-NFPA 70-2015 [ Section No. 706.43 ]

706.43 Flow Controls.

Controls shall be provided to safely shut down the system in the event of electrolyte blockage such as amalfunctioning electrolyte pump or valve .

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 11 16:19:12 PST 2015

Committee Statement

Committee Statement: This revision editorially modifies the requirement for clarity.

Response Message:

Public Comment No. 1554-NFPA 70-2015 [Section No. 706.43]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

20 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Currin, Jr., Richard D.

Czarnecki, Neil A.

Degnan, James E.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

117 of 133 1/25/2016 1:23 PM

Page 117 of 133

Page 118: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

118 of 133 1/25/2016 1:23 PM

Page 118 of 133

Page 119: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3605-NFPA 70-2015 [ Section No. 708.10(C)(2) ]

(2) Fire Protection for Feeders.

Feeders shall be protected for 2 hours using meet one of the following methods conditions :

(1) The cable or raceway is protected by a listed electrical circuit protective system with a minimum2-hour fire rating .

Informational Note: The listing organization provides information for electrical circuit protectionsystems on proper installation requirements to maintain the fire rating.

(2) Be The cable or raceway is a listed fire-resistive cable system with a minimum 2-hour fire rating.

Informational Note No. 1: Fire-resistive cables are tested to ANSI/UL 2196, Tests for FireResistive Cables.

Informational Note No. 2: The listing organization provides information for fire-resistive cablesystems on proper installation requirements to maintain the fire rating.

(3) The cable or raceway is protected by a listed fire-rated assembly that has a minimum fire rating of 2hours.

(4) The cable or raceway is encased in a minimum of 50 mm (2 in.) of concrete.

Supplemental Information

File Name Description

708.10_C_2_SR_3605_LM.docx Staff use only

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Nov 09 10:56:46 PST 2015

Committee Statement

CommitteeStatement:

The permission to use 2-inches of concrete was deleted in the first revision stage and is addedback in this revision. The absence of a dimension for the depth of concrete would cause seriousconfusion in practical application.

Listed fire-rated assemblies with a minimum fire rating of 2 hours was deleted in the first revisionstage and is added in this second revision. This means to achieve a 2 hour fire rating for COPSsystems is time tested and commonly used.

Editorial revisions were made to the parent text and the list items to clarify the 2-hour requirement.

Public Comment No. 842-NFPA 70-2015 [Section No. 708.10(C)(2)]

Ballot Results

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

119 of 133 1/25/2016 1:23 PM

Page 119 of 133

Page 120: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

This item has passed ballot

21 Eligible Voters

1 Not Returned

19 Affirmative All

0 Affirmative with Comments

1 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

Negative with Comment

Currin, Jr., Richard D.

There is no evidence to support that 2" of concrete provides a 2 hour rating. In fact there is evidence that impliesthe contrary and that it would require 4" or more of concrete encasement to provide a 2 hour fire rating. I wouldagree with this revision if it were limited to the application of slab on grade (SOG) cases. Since it is not specific toSOG that then ceilings and walls would be allowed as protection for conductors. This is an area that needs labtesting to be performed to determine temperatures that conductors are exposed too under various levels ofconcrete thicknesses as well as different concrete mixes. The testing should include conductors installed ongrade, walls, and ceiling/floors.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

120 of 133 1/25/2016 1:23 PM

Page 120 of 133

Page 121: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3627-NFPA 70-2015 [ Article 712 ]

Article 712 Direct Current Microgrids

Part I. General

712.1 Scope.

This article applies to direct current microgrids.

712.2 Definitions.

Direct Current Microgrid (DC Microgrid).

A direct current microgrid is a power distribution system consisting of one or more than oneinterconnected dc power sources , supplying dc-dc converters (s) , dc loads (s) , and/or ac loads (s)powered by dc-ac inverters (s) . A dc microgrid is typically not directly connected to an ac primary sourceof electricity, but some dc microgrids interconnect via one or more dc-ac bidirectional converters or dc–acinverters.

Informational Note: Direct current power sources include ac-dc converters (rectifiers), bidirectionaldc-ac inverters/converters, photovoltaic systems, wind generators, energy storage systems(including batteries), and fuel cells.

Grounded Two-Wire DC System

A two-wire dc power system that has a direct solid connection or reference-ground between one of thecurrent carrying conductors and the equipment grounding system.

Grounded Three-Wire DC System.

A dc power system with a solid connection or reference-ground between the center point of a bipolar dcpower source and the equipment grounding system.

Nominal Voltage.

A nominal value assigned to a circuit or system for the purpose of conveniently designating its dc voltageclass (e.g., 24 volts dc, 190/380 volts dc, 380 volts dc) .

Informational Note: The actual voltage at which a circuit operates can vary from the nominalvoltage within a range that permits satisfactory operation of equipment.

Reference-Grounded DC System.

A microgrid system that is not solidly grounded but has a low-impedance resistance electrical referencethat maintains voltage to ground in normal operation. In the faulted-state, the system becomesungrounded or high-impedance grounded in order to limit fault current.

Resistively Grounded.

A dc power system with a high-impedance resistance connection between the current carryingconductors and the equipment grounding system.

Primary DC Source.

A dc power source that supplies the majority of the dc load in a dc microgrid.

Ungrounded DC System.

A dc power system that has no direct or resistive connection between the current carrying conductors andthe equipment grounding system.

712.3 Other Articles.

Wherever the requirements of other articles of this Code and Article 712 differ, the requirements of Article712 shall apply. DC microgrids interconnected through an inverter or bi-directional converter with acelectric power production sources shall comply with Article 705.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

121 of 133 1/25/2016 1:23 PM

Page 121 of 133

Page 122: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

712.4 Labeling and Listing and Labeling .

Any direct-current equipment used in the dc circuits of a direct-current micro grid shall be listed or andlabeled for dc use.

712.10 Directory.

A permanent directory denoting all dc electric power sources operating to supply the dc microgrid shall beinstalled at each source location capable of acting as the primary dc source.

Part II. Circuit Requirements

712.25 Identification of Circuit Conductors

(A)

Ungrounded circuit conductors in dc microgrids shall be identified according to the requirements of210.5(C)(2) for branch circuits and 215.12(C)(2) for feeders.

(B)

Ungrounded conductors of 6 AWG or smaller shall be permitted to be identified by polarity at alltermination, connection, and splice points by marking tape, tagging, or other approved means.

712.30 System Voltage.

The system voltage of a dc microgrid shall be defined as follows determined by one of the followingmethods :

(1) The nominal voltage to ground for solidly grounded systems

(2) The nominal voltage to ground for reference-grounded systems where all conductors aredisconnected from power sources when the reference ground is in the high-impedance, faulted state

(3) The highest nominal voltage between conductors for resistively grounded dc systems andungrounded dc systems.

Informational Note: Examples of nominal dc system voltages include but are not limited to 24, 48,125, 190/380, or 380 volts.

Part III. Disconnecting Means

712.34 DC Source Disconnecting Means.

The output of each dc source shall have a readily accessible, lockable disconnecting means that islockable in the open position . Disconnecting means shall be located in accordance with 690.13(A) forphotovoltaic systems and adjacent to the source for other systems .

712.35 Disconnection of Ungrounded Conductors.

In solidly grounded two- and three-wire systems, the disconnecting means shall simultaneously open allungrounded conductors. In ungrounded, resistively grounded and reference-grounded systems, suchdevices shall open all current-carrying conductors.

712.37 Directional Current Devices.

Disconnecting means and protective and overcurrent devices that are designed shall be listed, be markedfor use in a single current direction, shall and only be used in the designated current direction.

Informational Note: Examples of directional current devices are magnetically quenched contactorsand semiconductor switches in overcurrent devices.

712.38 Loss of Direct Current Source.

Upon loss of primary dc source, all dc electric power sources shall be automatically disconnected fromall ungrounded conductors of the dc primary source and shall not be reconnected until the primary dcsource is restored. Individual premises dc sources shall be permitted to reconfigure and operate as theprimary dc source in a stand-alone system(s) to supply loads that have been disconnected.

Part IV. Wiring Methods

712.40 Identification for Branch Circuits and Feeder Circuits.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

122 of 133 1/25/2016 1:23 PM

Page 122 of 133

Page 123: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

(A)

Wiring methods for dc microgrids shall comply with the requirements of 210.5 for branch circuits and215.12 for feeders.

(B)

DC microgrids operating at voltages greater than 300 volts dc shall be reference-grounded dc systemsor resistively grounded dc systems.

712.52 System Grounding.

(A) General.

Direct-current microgrids shall be grounded in accordance with 250.162.

(B) Over 300 Volts.

DC microgrids operating at voltages greater than 300 volts dc shall be reference-grounded dc systems orresistively grounded dc systems.

712.55 Ground Fault Protection of Detection Equipment.

Ungrounded, reference grounded, or resistively grounded DC dc microgrids operating at greater than 60volts dc shall have ground fault protection detection that does all of the following: Detects the faultIndicates indicates that a fault has occurred. For solidly grounded and reference-grounded systems,disconnects power from the faulted equipment Ground The ground fault equipment shall comply bemarked in accordance with 250.167(C).

(A)

DC microgrids operating at greater than 60 volts dc shall have ground fault protection that does all of thefollowing:

(0) Detects the fault

(0) Indicates that a fault has occurred

(0) For solidly grounded and reference-grounded systems, disconnects power from the faultedequipment

(A)

Ground fault equipment shall comply with 250.167.

712.57 Arc Fault Protection.

Where required elsewhere in this Code , specific systems within the DC microgrids with a systemvoltage of greater than 60 volts shall be required to have arc fault protection. for utilization circuits.Arc The arc fault protection equipment shall be identified and listed for the purpose .

Informational Note: Section 90.4 applies when suitable equipment for arc fault protection is notavailable.

Part V. Marking

712.62 Panelboards Distribution Equipment and Conductors .

Panelboards in dc microgrid systems shall be marked in accordance with 408.3 Distribution equipmentand conductors shall be marked as required elsewhere in this Code .

712.65 Panelboards.

Panelboards in dc microgrid systems shall be marked in accordance with 408.3 .

712.65 Available DC Fault Short-Circuit Current.

(A) Field Marking.

Maximum The maximum available dc short-circuit current on the dc microgrid shall be field marked at thedc source(s) . The field marking(s) shall include the date the fault- short-circuit current calculation wasperformed and be of sufficient durability to withstand the environment involved.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

123 of 133 1/25/2016 1:23 PM

Page 123 of 133

Page 124: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

(B) Modifications.

When modifications to the electrical installation occur that affect the maximum available fault short-circuitcurrent at the dc source, the maximum available fault short-circuit current shall be verified or recalculatedas necessary to ensure the equipment ratings are sufficient for the maximum available fault short-circuitcurrent at the line terminals of the equipment. The required field marking(s) in 712.65(A) shall beadjusted to reflect indicate the new level of maximum available fault short-circuit current and date .

Part VI. Systems with Multiple Sources Protection

712.70 Overcurrent Protection.

Equipment and conductors connected to more than one electrical source shall have overcurrentprotective devices located so as to provide protection from all sources.

712.72 Interrupting and Short-Circuit Current Ratings .

Consideration shall be given to the contribution of fault short-circuit currents from all interconnected powersources for the interrupting ratings and short-circuit current ratings of equipment in the dc microgridsystems (s) . Overcurrent protective devices and equipment used within a dc microgrid shall have aninterrupting rating at nominal circuit voltage or a short-circuit current rating sufficient for the availablefault short-circuit current at the line terminals of the equipment.

Part VII. Systems over 1000 Volts

712.80 General.

Systems with a maximum voltage between conductors of over 1000 volts dc shall comply with Article 490and other requirements in this Code applicable to installations rated over 1000 volts.

Supplemental Information

File Name Description

712_SR3627_LM.docx Staff use only

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Nov 10 15:28:23 PST 2015

Committee Statement

CommitteeStatement:

The defined terms “Grounded Two-Wire DC System”, “Grounded Three-Wire DC System,”“Nominal Voltage”, “Reference-Grounded DC System”, “Resistively Grounded”, “Primary DCSource”, “Ungrounded DC System” are editorially modified for clarity, usability and compliance withthe NEC style manual.

The definition of “Direct Current Microgrid” is modified to clarify that more than one interconnectedsource is required.

The last sentence in the defined term, “Reference-Grounded DC System” is deleted because it is arequirement.

712.4 is modified for clarity.

Editorial corrections are made and an Informational Note is added to 712.30 for clarity and usability.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

124 of 133 1/25/2016 1:23 PM

Page 124 of 133

Page 125: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

712.34 is modified for clarity. The reference to 690.13(A) is deleted as there are many potentialsources.

712.37 is modified for clarity. The listing and marking requirement is added to ensure that directionalcurrent devices are approved for the intended use.

Section 712.38 was deleted. The requirements in this section were intended to mirror theanti-islanding requirements for interconnected ac systems, in that distributed sources should notback-feed a de-energized utility grid. As there are presently no dc utility services, 712.38 only addsconfusion and is unlikely to be relevant for many years until dc utility distribution systems are againimplemented.

712.40 is deleted. First level subdivision (A) was just a reference to identification of DC conductorsand the requirements in 210 and 215 apply as per section 90.3. First level subdivision (B) is deletedbecause it is referenced in 712.52.

712.52 is editorially revised to add first level subdivision titles.

In section 712.55, the term “ground fault protection” was changed to “ground fault detection.” Theremainder of the section was editorially revised.

712.57 for arc fault protection of systems was modified to reference other requirements for arc faultprotection in the NEC.

Part numbers were editorially revised.

Section 712.62 was modified from panelboards to distribution equipment and conductors.

Section 712.65, Panelboards, is deleted because it was duplicated.

Section 712.65, Available DC Fault Current, is modified for clarity and to specifically address “shortcircuit current” and to include the date of the marking.

The title of Part VII (now Part VI) is revised to “Protection” for clarity.

Section 712.70 is revised for clarity and usability.

Section 712.72 is modified for clarity to specifically address “short circuit current”.

Section 712.80 is revised for clarity and usability.

ResponseMessage:

Public Comment No. 1016-NFPA 70-2015 [Section No. 712.4]

Public Comment No. 1017-NFPA 70-2015 [Section No. 712.34]

Public Comment No. 1019-NFPA 70-2015 [Section No. 712.37]

Public Comment No. 1021-NFPA 70-2015 [Section No. 712.40]

Public Comment No. 1174-NFPA 70-2015 [Article 712]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

18 Affirmative All

1 Affirmative with Comments

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

125 of 133 1/25/2016 1:23 PM

Page 125 of 133

Page 126: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

1 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Currin, Jr., Richard D.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

Affirmative with Comment

Little, Linda J.

We are voting affirmative on SR 3627 with the following comment: It is imperative that the title of this Article isreconsidered, and if changed, editorial revisions made throughout. The use of the term “microgrid” may causeserious confusion in the industry. The term “microgrid” infers utility owned conductors and equipment. Thesystems addressed in this Article should be addressed by a term that more appropriately captures the systemitself. This Article could be retitled as “Interconnected Direct Current (DC) Distribution Systems.” The NECCorrelating Committee (CC) is well aware of previous issues created in 90.2 with references to the NESC ininformational notes, and the CC formed a task group to resolve those issues. The CC must understand thesignificance of this issue and the serious concerns presented by the electrical utilities represented in this revisionstage with respect to the use of the term “microgrid.” We, the NEC community, would take serious exception if theNational Electrical Safety Code (NESC) would begin to use and apply the term “premises wiring” to utility ownedconductors and systems. This Article and the work within are important and should be in the 2017 NEC, which iswhy we are voting affirmative. The NEC CC should seriously consider removal of the term “microgrid.”

Negative with Comment

Croushore, Timothy M.

The term “Microgrid” is a jargon and non-specific term. The NEC process consistently encourages usingterminology that provides clarity. The term “Interconnected Direct Current (DC) Distribution System” provides thisclarity. To ensure that we maintain fundamental separation between utility wiring and premises wiring, we need to

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

126 of 133 1/25/2016 1:23 PM

Page 126 of 133

Page 127: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

use terminology that provides clear separation between the two systems (NEC and NESC). The electric utility typemicrogrid systems are still in the R&D phase and still in development in other standards committees outside theNFPA. Therefore, as this technology continues to emerge, we need to ensure that the lines do not become blurredbetween the two systems. We are mixing two different systems, therefore keeping different terms in the NEC willbest serve the industry. To move forward with the technology of an interconnected DC system and revise thejargon out of this new Article 712 to a specific term, the 14 following changes to Article 712 needs to be made.Identifiable portion of the ballot. 1. Revise the title to Article 712 Interconnected Direct Current (DC) DistributionSystems. 2. In 712.2 Definitions, remove the title, the definition and Information Note for Direct Current Microgrid(DC Microgrid) and replace it with the following: Interconnected Direct Current (DC) Distribution System. Aninterconnected direct current (DC) distribution system is a power distribution system consisting of more than oneparallel connected dc power source, supplying dc-dc converter(s), dc load(s)s, and/or ac load(s) powered by dc-acinverter(s). Informational Note: Direct current power sources include ac-dc converters (rectifiers), bidirectionaldc-ac inverters/converters, photovoltaic systems, wind generators, energy storage systems (including batteries),and fuel cells. Interconnected Direct Current Distribution Systems are sometimes called DC microgrids. 3. In 712.Definitions, revise the definition of Primary DC Source as follows: Primary DC Source. A source that supplies themajority of the dc load in an interconnected dc distribution system. 4. In 712.3 Other Articles, remove the secondsentence and replace it with the following: DC distribution systems that are interconnected through an inverter orbi-directional converter with ac electric power sources shall comply with Article 705. 5. In 712.4, remove thefollowing text “direct-current micro grid” and replace it with “interconnected direct current (DC) distribution system”.6. In 712.10, remove the term “dc microgrid” and replace it with “interconnected direct current (DC) distributionsystem”. 7. In 712.25, remove the term “dc microgrid” and replace it with “interconnected direct current (DC)distribution system”. 8. In 712.30, remove the term “dc microgrid” and replace it with “interconnected direct current(DC) distribution system”. 9. In 712.52(A), remove the term “Direct-current microgrids” and replace it with“interconnected direct current (DC) distribution systems”. 10. In 712.52(B), remove the term “DC microgrids” andreplace it with “interconnected direct current (DC) distribution systems”. 11. In 712.55, remove the term “dcmicrogrids” and replace it with “interconnected direct current (DC) distribution systems”. 12. In 712.57, remove theterm “DC microgrid” and replace it with “interconnected direct current (DC) distribution system”. 13. In 712.65(A),remove the term “dc microgrid” and replace it with “interconnected direct current (DC) distribution system”. 14. In712.72, remove the term “dc microgrid system(s)” in the first sentence and replace it with “interconnected directcurrent (DC) distribution system(s)” and remove the term “dc microgrid” in the second sentence and replace it with“interconnected direct current (DC) distribution system”.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

127 of 133 1/25/2016 1:23 PM

Page 127 of 133

Page 128: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3638-NFPA 70-2015 [ Definition: Energy Storage System (ESS).

[Excluding any Sub... ]

A device One or more than one device components assembled together capable of storing energy for useat a future time. ESS(s) includes can include but is not limited to electrochemical storage devices (e.g.,batteries) , flow batteries, capacitors, and kinetic energy devices (e.g., flywheels and compressed air).These systems can have ac or dc output for utilization and can include inverters and converters to changestored energy into electrical energy.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 11 09:00:45 PST 2015

Committee Statement

CommitteeStatement:

The definition is editorially revised for clarity and correlation within Article 706 andcompliance with the NEC Style Manual.

ResponseMessage:

Public Comment No. 1049-NFPA 70-2015 [Definition: Energy Storage System (ESS). [Excluding any Sub...]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

20 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

128 of 133 1/25/2016 1:23 PM

Page 128 of 133

Page 129: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Croushore, Timothy M.

Currin, Jr., Richard D.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

129 of 133 1/25/2016 1:23 PM

Page 129 of 133

Page 130: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3631-NFPA 70-2015 [ Part III. ]

Part III. Electrochemical Energy Storage Systems

Part III of this article applies to ESSs that are comprised of sealed and non-sealed cells or batteries orsystem modules that are comprised of multiple sealed cells or batteries that are not components within alisted product .

Informational Note: An energy storage component, such as batteries, that are integrated into alarger piece of listed equipment, such as an uninterruptible power supply (UPS), are examples ofcomponents within a listed product.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 11 08:28:37 PST 2015

Committee Statement

Committee Statement: This revision provides necessary clarity for the application of Part III in Article 706.

Response Message:

Public Comment No. 1187-NFPA 70-2015 [Part III.]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

20 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

130 of 133 1/25/2016 1:23 PM

Page 130 of 133

Page 131: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Currin, Jr., Richard D.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

131 of 133 1/25/2016 1:23 PM

Page 131 of 133

Page 132: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Second Revision No. 3632-NFPA 70-2015 [ Part III. ]

Part IV. Flow Battery Energy Storage Systems

The provisions Part IV apply applies to ESSs composed of or containing flow batteries.

Submitter Information Verification

Submitter Full Name: CMP 13

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Wed Nov 11 08:33:40 PST 2015

Committee Statement

CommitteeStatement:

Editorial comment to correct the title from "Part III" to "Part IV".

In addition to the correction of the Part number, the extraneous text “provisions” has beenremoved.

Response Message:

Public Comment No. 1195-NFPA 70-2015 [Part III.]

Public Comment No. 1504-NFPA 70-2015 [Part III.]

Ballot Results

This item has passed ballot

21 Eligible Voters

1 Not Returned

20 Affirmative All

0 Affirmative with Comments

0 Negative with Comments

0 Abstention

Not Returned

Tobias, Jr., David

Affirmative All

Adams, Martin D.

Brandon, George M.

Caron, Daniel J.

Croushore, Timothy M.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

132 of 133 1/25/2016 1:23 PM

Page 132 of 133

Page 133: National Fire Protection Association - nfpa.org · PDF fileSecond Revision No. 3617-NFPA 70-2015 [ Section No. 445.11 ] 445.11 Marking. Each generator shall be provided with a nameplate

Currin, Jr., Richard D.

Czarnecki, Neil A.

Degnan, James E.

Froemming, Steven F.

Keenan, Ronald A.

Little, Linda J.

Neeser, Daniel R.

Ode, Mark C.

Paulsen, Shawn

Rodriguez, Arnoldo L.

Savage, Sr., Michael L.

Spina, Mario C.

Waterman, Kendall M.

White, James R.

Whittall, Herbert V.

Windey, Timothy P.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

133 of 133 1/25/2016 1:23 PM

Page 133 of 133