nari pcs-985g generator relay
DESCRIPTION
NARI PCS-985G Generator RelayTRANSCRIPT
-
PCS-985G
Generator Relay
Instruction Manual
NR Electric Co., Ltd.
-
Preface
PCS-985G Generator Relay i
Date: 2013-6-23
Preface
Introduction
This guide and the relevant operating or service manual documentation for the equipment provide
full information on safe handling, commissioning and testing of this equipment.
Documentation for equipment ordered from NR is dispatched separately from manufactured goods
and may not be received at the same time. Therefore, this guide is provided to ensure that printed
information normally present on equipment is fully understood by the recipient.
Before carrying out any work on the equipment, the user should be familiar with the contents of
this manual, and read relevant chapter carefully.
This chapter describes the safety precautions recommended when using the equipment. Before
installing and using the equipment, this chapter must be thoroughly read and understood.
Health and Safety
The information in this chapter of the equipment documentation is intended to ensure that
equipment is properly installed and handled in order to maintain it in a safe condition.
When electrical equipment is in operation, dangerous voltages will be present in certain parts of
the equipment. Failure to observe warning notices, incorrect use, or improper use may endanger
personnel and equipment and cause personal injury or physical damage.
Before working in the terminal strip area, the equipment must be isolated.
Proper and safe operation of the equipment depends on appropriate shipping and handling,
proper storage, installation and commissioning, and on careful operation, maintenance and
servicing. For this reason, only qualified personnel may work on or operate the equipment.
Qualified personnel are individuals who:
Are familiar with the installation, commissioning, and operation of the equipment and of the
system to which it is being connected;
Are able to safely perform switching operations in accordance with accepted safety
engineering practices and are authorized to energize and de-energize equipment and to
isolate, ground, and label it;
Are trained in the care and use of safety apparatus in accordance with safety engineering
practices;
Are trained in emergency procedures (first aid).
Instructions and Warnings
The following indicators and standard definitions are used:
-
Preface
PCS-985G Generator Relay ii Date: 2013-6-23
DANGER!
It means that death, severe personal injury, or considerable equipment damage will occur if safety
precautions are disregarded.
WARNING!
It means that death, severe personal, or considerable equipment damage could occur if safety
precautions are disregarded.
CAUTION!
It means that light personal injury or equipment damage may occur if safety precautions are
disregarded. This particularly applies to damage to the device and to resulting damage of the
protected equipment.
WARNING!
The firmware may be upgraded to add new features or enhance/modify existing features, please
make sure that the version of this manual is compatible with the product in your hand.
WARNING!
During operation of electrical equipment, certain parts of these devices are under high voltage.
Severe personal injury or significant equipment damage could result from improper behavior.
Only qualified personnel should work on this equipment or in the vicinity of this equipment. These
personnel must be familiar with all warnings and service procedures described in this manual, as
well as safety regulations.
In particular, the general facility and safety regulations for work with high-voltage equipment must
be observed. Noncompliance may result in death, injury, or significant equipment damage.
DANGER!
Never allow the current transformer (CT) secondary circuit connected to this equipment to be
opened while the primary system is live. Opening the CT circuit will produce a dangerously high
voltage.
WARNING!
Exposed terminals
Do not touch the exposed terminals of this equipment while the power is on, as the high voltage
generated is dangerous.
-
Preface
PCS-985G Generator Relay iii
Date: 2013-6-23
Residual voltage
Hazardous voltage can be present in the DC circuit just after switching off the DC power supply. It
takes a few seconds for the voltage to discharge.
CAUTION!
Earth
The earthing terminal of the equipment must be securely earthed.
Operating environment
The equipment must only be used within the range of ambient environment detailed in the
specification and in an environment free of abnormal vibration.
Ratings
Before applying AC voltage and current or the DC power supply to the equipment, check that they
conform to the equipment ratings.
Printed circuit board
Do not attach and remove printed circuit boards when DC power to the equipment is on, as this
may cause the equipment to malfunction.
External circuit
When connecting the output contacts of the equipment to an external circuit, carefully check the
supply voltage used in order to prevent the connected circuit from overheating.
Connection cable
Carefully handle the connection cable without applying excessive force.
Copyright
Version: R1.00
P/N: EN_YJBH2641.0086.0001
Copyright NR 2013. All rights reserved
NR ELECTRIC CO., LTD.
69 Suyuan Avenue. Jiangning, Nanjing 211102, China
Tel: +86-25-87178185, Fax: +86-25-87178208
Website: www.nrelect.com, www.nari-relays.com
Email: [email protected]
We reserve all rights to this document and to the information contained herein. Improper use in particular reproduction and dissemination
to third parties is strictly forbidden except where expressly authorized.
The information in this manual is carefully checked periodically, and necessary corrections will be included in future editions. If
nevertheless any errors are detected, suggestions for correction or improvement are greatly appreciated.
We reserve the rights to make technical improvements without notice.
-
Preface
PCS-985G Generator Relay iv Date: 2013-6-23
Documentation Structure
The manual provides a functional and technical description of this relay and a comprehensive set
of instructions for the relays use and application.
All contents provided by this manual are summarized as below:
1 Introduction
Briefly introduce the application, functions and features about this relay.
2 Technical Data
Introduce the technical data about this relay, such as electrical specifications, mechanical
specifications, ambient temperature and humidity range, communication port parameters, type
tests, setting ranges and accuracy limits and the certifications that our products have passed.
3 Operation Theory
Introduce a comprehensive and detailed functional description of all protective elements.
4 Supervision
Introduce the automatic self-supervision function of this relay.
5 Management
Introduce the displayed measurement and recording in the relay.
6 Hardware
Introduce the main function carried out by each plug-in module of this relay and providing the
definition of pins of each plug-in module.
7 Settings
List all the settings and some notes about the setting application.
8 Human Machine Interface
Introduce the hardware of the human machine interface (HMI) module and a detailed guide for the
user how to use this relay through HMI. It also lists all the information which can be view through
HMI, such as settings, measurements, all kinds of reports etc.
9 Communication
Introduce the communication port and protocol which this relay can support, IEC60970-5-103,
IEC61850 and DNP3.0 protocols are introduced in details.
10 Installation
Introduce the recommendations on unpacking, handling, inspection and storage of this relay. A
guide to the mechanical and electrical installation of this relay is also provided, incorporating
earthing recommendations. A typical wiring connection to this relay is indicated.
-
Preface
PCS-985G Generator Relay v
Date: 2013-6-23
11 Commissioning
Introduce how to commission this relay, comprising checks on the calibration and functionality of
this relay.
12 Maintenance
A general maintenance policy for this relay is outlined.
13 Decommissioning and Disposal
A general decommissioning and disposal policy for this relay is outlined.
14 Manual Version History
List the instruction manual version and the modification history records.
Typographic and Graphical Conventions
Deviations may be permitted in drawings and tables when the type of designator can be obviously
derived from the illustration.
The following symbols are used in drawings:
&
AND gate
1
OR gate
Comparator
BI
Binary signal via opto-coupler
SET I>
Input signal from comparator with setting
EN
Input signal of logic setting for function enabling
SIG
Input of binary signal except those signals via opto-coupler
OTH
Input of other signal
XXX
Output signal
-
Preface
PCS-985G Generator Relay vi Date: 2013-6-23
t
t
Timer
Timer (optional definite-time or inverse-time characteristic)
10ms 0ms
Timer [delay pickup (10ms), delay dropoff (0ms), non-settable]
[t1] 0ms
Timer (t1: delay pickup, settable)
0ms [t2]
Timer (t2: delay dropoff, settable)
[t1] [t2]
Timer (t1: delay pickup, t2: delay dropoff, settable)
IDMT
Timer (inverse-time characteristic)
*
*
Instrument current transformer
Instrument voltage transformer
Symbol Corresponding Relationship
Basic Example
A, B, C L1, L2, L3 Ia, Ib, Ic, I0 IL1, IL2, IL3, IN
AN, BN, CN L1N, L2N, L3N Ua, Ub, Uc VL1, VL2, VL3
ABC L123 Uab, Ubc, Uca VL12, VL23, VL31
U (voltage) V U0, U1, U2 VN, V1, V2
-
1 Introduction
PCS-985G Generator Relay 1-a
Date: 2013-06-23
1 Introduction
Table of Contents
1 Introduction ..................................................................................... 1-a
1.1 Application ....................................................................................................... 1-1
1.2 Function ........................................................................................................... 1-1
1.3 Features ........................................................................................................... 1-3
1.4 Order Information............................................................................................ 1-7
List of Tables
Table 1.2-1 Function configuration of generator ..................................................................... 1-1
Table 1.2-2 Function configuration of excitation transformer/exciter ................................... 1-2
Table 1.2-3 Mechanical function configuration ........................................................................ 1-2
-
1 Introduction
PCS-985G Generator Relay 1-1
Date: 2013-06-23
1.1 Application
PCS-985G can be applied for large-scale turbo-dynamo, gas-turbine generator and nuclear power
generator with different connection modes.
PCS-985G provides complete electric quantity protection of a generator and an exciter or
excitation transformer. It also supports ECT/EVT and meets the requirements of power plant
automation.
For a large-scale generator, two sets of PCS-985G can be used and then main protection,
abnormal operation condition protection and backup protection can be duplicated. Control circuit
and mechanical protection are installed on a separate panel. Two sets of PCS-985G use different
CT groups and main and backup protection in one PCS-985G share one CT group. The outputs
correspond to various trip coils.
1.2 Function
PCS-985G takes fully into account maximum configuration of large-scale generator, and suits the
generator with capacity of 100MW or above.
1.2.1 Protection Function
PCS-985G can select to configure the following protection functions, and means that it is an
abnormality alarm function.
Table 1.2-1 Function configuration of generator
No. Function Stage Delay ANSI
1 Differential protection 87G
2 DPFC differential protection 87G
3 Transverse differential protection 2 87G
4 Longitudinal residual overvoltage protection for inter-turn fault 1 1 59N/60
5 DPFC directional protection for inter-turn fault 1 1 67
6 Calculated longitudinal residual overvoltage protection for inter-turn
fault 1 1
7 Voltage controlled overcurrent protection 2 1 50
8 Phase-to-phase impedance protection 2 1 21G
9 Fundamental residual voltage protection for stator earth fault 2 1 64S
10 Third harmonic overvoltage ratio protection for stator earth fault 1 1 64S
11 Third harmonic overvoltage differential protection for stator earth fault 1 1 64S
12 stator earth-fault protection with voltage injection 2 1 64R
13 Rotor one-point earth-fault protection 2 1 64R1
14 Rotor two-point earth-fault protection 1 1 64R2
15 Definite-time stator overload protection 2 1 50S
16 Inverse-time stator overload protection 51S
17 Definite-time negative-sequence overload protection 2 1 50Q
18 Inverse-time negative-sequence overload protection 51Q
-
1 Introduction
PCS-985G Generator Relay 1-2 Date: 2013-06-23
19 Loss-of-excitation protection 3 1 40
20 Out-of-step protection 2 1 78
21 Overvoltage protection 2 1 59
22 Undervoltage protection 1 1
23 Definite-time over-excitation protection 2 1 24
24 Inverse-time over-excitation protection 24
25 Reverse-power protection 2 1 32R
26 Low-power protection 1 1 37G
27 Sequential tripping reverse-power protection 1 1 32R
28 Underfrequency protection 3 1 81U
29 Overfrequency protection 2 1 81O
30 Startup/shutdown protection of differential current 1 1
31 Startup/shutdown protection of residual voltage 1 1
32 Low-frequency overcurrent protection 1 1 50
33 Inadvertent energization protection 1 1 50/27
34 Breaker failure protection 1 2 50BF
35 Voltage balance function 60
36 VT circuit supervision VTS
37 CT circuit supervision CTS
Note!
Rotor earth-fault protection can select voltage switchover principle or external voltage
injection principle.
Table 1.2-2 Function configuration of excitation transformer/exciter
No. Function Stage Delay ANSI
1 Differential protection 87ET
2 Overcurrent protection 2 1 50
3 Definite-time overload protection 1 1 50
4 Inverse-time overload protection 51
Table 1.2-3 Mechanical function configuration
No. Function Stage Delay ANSI
1 Mechanical protection 1 1 1
2 Mechanical protection 2 1 1
3 Mechanical protection 3 1 1
4 Mechanical protection 4 1 1
5 Mechanical protection 5 1 1
6 Mechanical protection 6 1 1
7 Mechanical protection 7 1 1
8 Mechanical protection 8 1 1
-
1 Introduction
PCS-985G Generator Relay 1-3
Date: 2013-06-23
Note!
The name of mechanical protection 1~8 can be modified.
1.2.2 Configuration Explanation
1.2.2.1 Differential Protection
1. For generator with the capacity of 300MW or above, panel A and B are both equipped with
generator differential protection.
2. For generator differential protection, there are two kinds of percentage differential protection:
variable slope percentage differential protection and DPFC percentage differential protection.
1.2.2.2 Backup Protection
1. Panel A and B are equipped with complete set of backup protection of generator and
excitation transformer/exciter. Different CTs are used for them.
2. As to rotor earth-fault protection, two sets of such protection cannot work simultaneously
otherwise influence between them will appear. Only one set of rotor earth-fault protection can
be enabled during operation. If other set will be put into operation sometimes, this set shall be
quitted firstly.
1.2.2.3 Current Transformer
1. Panels A and B adopt different CT.
2. Main protection and backup protection share one group of CT.
3. Generator reverse power protection can share one group of generator terminal CT with
generator differential protection, or adopt independent measurement CT.
1.2.2.4 Voltage Transformer
1. Panel A and B shall adopt different VT or its different windings if possible.
2. For generator inter-turn protection, in order to prevent undesired operation due to VT circuit
failure at HV side used dedicatedly for this protection, one set of protection shall adopt two
groups of VT. However, if it is considered to adopt only independent VT windings, too much
VT will be installed at generator terminal and it is not reasonable. So it is recommended to
equip three windings of VT there, namely VT1, VT2 and VT3. Panel A adopts voltage from
VT1 and VT3 while panel B VT2 and VT3. During normal operation, panel A adopts VT1 and
panel B adopts VT2 while VT3 is backup to both of them. If circuit of VT1 or VT2 fails, VT3 will
be switched on automatically by software.
3. For residual voltage, there are two windings adopted by two sets of protection equipments
simultaneously in general.
1.3 Features
High-performance general-purpose hardware and real-time calculations
-
1 Introduction
PCS-985G Generator Relay 1-4 Date: 2013-06-23
Hardware structure of 32-bit microprocessorsdual DSP is adopted. A number of processors
operate in parallel. 32-bit microprocessors provide functions of HMI, communication, and printing,
etc. The two DSPs provide protection operations and output logic. High performance hardware
ensures real-time calculation for all relays in each sampling interval of this relay. This relay adopts
32-bit high performance CPUs and DSPs, internal high-speed bus, and intelligent I/O. Both
hardware and software adopt modular design, which can be flexibly configured. Features include
versatility, easy expansion, and easy maintenance.
Independent fault detector elements
The output mode of fault detector AND protection operation eliminates the possibility of
malfunction and misjudgment caused by hardware fault of the device.
Strong EM compatibility
Integral panel and fully enclosed chassis are adopted. Strong electricity and weak electricity are
strictly separated. Traditional rear board wiring mode is not used. At the same time, measures
against interference are taken in software design, greatly improving the immunity to disturbances.
EM radiation to outside satisfies relevant standards.
Modular programs
Modular programs allow flexible protection configuration and easy functional adjustment.
Variable slope percentage differential protection
Variable slope percentage characteristic is adopted for differential protection. Pickup slope and
maximum slope should be reasonably set, so that high sensitivity can be gained during internal
fault and transient unbalance current can be avoided during external fault. In order to prevent
undesired operation of differential protection due to CT saturation, measures to discriminate CT
saturation are provided for phase current at each side.
DPFC percentage differential protection
DPFC percentage differential protection reflects only deviation components of differential current
and restraint current and is not effected by load current. It can detect light fault within generator.
Besides, it is insensitive to CT saturation since its restraint coefficient is set comparatively high.
Detect CT Saturation by asynchronous method
According to relation between DPFC restraint current and DPFC differential current of differential
protection, external or internal fault can be discriminated correctly. For external fault, waveform
discrimination of phase current and differential current is adopted. Undesired operation will not
occur if CT correct transfer time from primary to secondary side is not less than 5ms. As to internal
fault, the device will operate quickly.
High-sensitive transverse differential protection
By adopting frequency tracking, digital filter and Fourier transformation, the filtration ratio of third
harmonic component can reach more than 100. These entire countermeasure guarantees the
reliability of the protection in all occasions as mentioned as below:
-
1 Introduction
PCS-985G Generator Relay 1-5
Date: 2013-06-23
The transverse differential protection can get reliable restraint effect because the faulty phase
current increases greatly while transverse differential current increases less in external fault
situation.
The protection has very high operation sensitivity because transverse differential current
increases comparatively large whereas phase current change not too observably in slightly
inter-turn fault situation.
The high-setting stage of transverse differential protection will operate quickly and reliably when
severe inter-turn fault occurs in stator winding.
In case of phase-to-phase fault of stator winding, not only transverse differential current but also
phase current increase greatly, therefore just low percentage restraint by phase current
guarantees the reliable operation of transverse differential protection against the fault.
As for unbalanced transverse differential current increasing during normal operation condition,
transverse differential protection uses float threshold to avoid undesired operation.
Percentage restraint inter-turn protection
By adopting frequency tracking, digital filter and Fourier transformation, the filtration ratio of third
harmonic component can reach more than 100. Calculated longitudinal residual overvoltage
protection is adopted in PCS-985G, which is the new criteria of generator inter-turn protection and
does not need the special VT for the protection.
Stator earth-fault protection
By adopting frequency tracking, digital filter and Fourier transformation, the filtration ratio of third
harmonic component can reach more than 100.
The sensitive stage of fundamental residual voltage protection operates and issues trip command
only if the dual criterias of residual voltages of generator terminal and neutral point are met at the
same time.
The ratio settings of third harmonic of generator terminal to that of neutral point used in third
harmonic ratio criteria will automatically suit to the change of ratio fore-and-aft incorporating in
power network third harmonic voltage of the plant unit. This automation adjustment function
ensures the correctness of signals generated and issued by the third harmonic voltage criteria
even during incorporation or isolation course of generator.
The ratio and phase-angle difference of third harmonic voltage of generator terminal to that of
neutral point keeps almost stable when the generator is in normal operation condition; also it is a
slow developing course. Through real time adjustment of coefficient of amplitude value and phase,
PCS-985 makes differential voltage between generator terminal and neutral point as zero in
normal operation condition. When stator earth fault occurs, the criteria tend to operate reliably and
sensitively.
Stator earth-fault protection with external voltage injection principle
The protection adopts digital technology to calculate earth fault resistance accurately.
-
1 Introduction
PCS-985G Generator Relay 1-6 Date: 2013-06-23
Settings configured two stage are provided. One stage operates to alarm, and the other stage
operates to trip.
The residual current protection is free from impact of 20Hz power, which provides mainly
protection for comparatively severe stator earth fault.
The protection is adaptive for various operation conditions, such as stillness, no-load, shutdown,
startup and connected to power grid.
Sampling-switch type rotor earth-fault protection
DC current is input by high-performance isolated amplifier. Via switching two different electronic
switches, PCS-985 solves four different ground-loop equations to compute rotor winding voltage,
rotor ground resistance and earthing position on real time and display these information on LCD.
Rotor earth-fault with external voltage injection principle
Injecting a low-frequency square wave between positive terminal and negative terminal of rotor
windings or between one terminal of rotor windings and axis, the device acquires leakage current
of rotor, and calculates insulation resistance between rotor windings and ground in real-time. The
injected square wave voltage is generated by the device. The protection reflects the insulation
reduction between rotor windings and axis.
The calculation to rotor earth resistance is unrelated to fault location, and no dead zone.
The calculation accuracy of rotor earth resistance is high and is not affected by the capacitance
between rotor windings and ground.
The calculation to rotor earth resistance is unrelated to excitation voltage. It can still supervise
insulation situation of rotor windings when no excitation voltage is supplied.
It can be adaptive to various lead-out modes of rotor windings, and both single-end injection and
double-ends injection can be selected. The fault location can be measured if selecting
double-ends injection.
Loss-of-excitation protection
Loss-of-excitation protection adopts optimizing protection scheme in which stator impedance
criteria, reactive power criteria, rotor voltage criteria and busbar voltage criteria, could be
optionally combined to meet various demands of different generator units.
Out-of-step protection
Out-of-step protection adopts three-impedance element (gains from positive-sequence current
and positive sequence voltage of generator) to distinguish out-of-step from steady oscillation.
More than that, the protection can accurately locate the position of oscillation center and record
oscillation slid numbers of external and internal oscillation respectively in real-time.
VT circuit failure supervision
Two groups of VT inputs are equipped at generator terminal. If one group fails, the device will
issue alarm and switch over to the healthy one automatically. It doesnt need to block protection
-
1 Introduction
PCS-985G Generator Relay 1-7
Date: 2013-06-23
element relevant to voltage. Based on percentage restraint characteristic, it can discriminate that
neutral point of VT circuit fails.
CT circuit failure supervision
Reliable blocking function when CT circuit failure can prevent the device from undesired operation
due to CT circuit failure or AC sampled circuit failure.
Powerful communication function
Flexible communication mode is provided. 2 independent Ethernet interfaces and 2 independent
RS-485 communication interfaces are provided. Power industry communication standard
IEC60870-5-103, Modbus protocol and new generation substation communication standard
IEC61850 are supported.
Complete event recording function
64 faults and operation sequence, 64 fault waveforms, results of 256 self-supervision reports, and
1024 binary signal change reports can be recorded.
Auxiliary PC software
PC software allows easy application of this device.
1.4 Order Information
CT secondary rated value: 1A or 5A
DC power supply for device: 110/125V, 220/250V
DC power supply for binary input: 110/125V, 220V
-
1 Introduction
PCS-985G Generator Relay 1-8 Date: 2013-06-23
-
2 Technical Data
PCS-985G Generator Relay 2-a
Date: 2013-06-24
2 Technical Data
Table of Contents
2 Technical Data ................................................................................. 2-a
2.1 Electrical Specifications ................................................................................. 2-1
2.1.1 AC Current Input .................................................................................................................. 2-1
2.1.2 AC Voltage Input .................................................................................................................. 2-1
2.1.3 Power Supply ....................................................................................................................... 2-1
2.1.4 Binary Input .......................................................................................................................... 2-1
2.1.5 Binary Output ....................................................................................................................... 2-2
2.2 Mechanical Specifications ............................................................................. 2-2
2.3 Ambient Temperature and Humidity Range .................................................. 2-2
2.4 Communication Port ....................................................................................... 2-3
2.4.1 EIA-485 Port ........................................................................................................................ 2-3
2.4.2 Ethernet Port ........................................................................................................................ 2-3
2.4.3 Optical Fibre Port ................................................................................................................. 2-3
2.4.4 Print Port .............................................................................................................................. 2-4
2.4.5 Clock Synchronization Port ................................................................................................. 2-4
2.5 Type Tests ........................................................................................................ 2-4
2.5.1 Environmental Tests ............................................................................................................ 2-4
2.5.2 Mechanical Tests ................................................................................................................. 2-4
2.5.3 Electrical Tests ..................................................................................................................... 2-5
2.5.4 Electromagnetic Compatibility ............................................................................................. 2-5
2.6 Certifications ................................................................................................... 2-6
2.7 Protective Functions ....................................................................................... 2-6
2.7.1 Generator/ Excitor Differential Protection ............................................................................ 2-6
2.7.2 Excitation Transformer Differential Protection ..................................................................... 2-7
2.7.3 Generator Transverse Differential Protection ...................................................................... 2-7
-
2 Technical Data
PCS-985G Generator Relay 2-b
Date: 2013-06-24
2.7.4 Generator Longitudinal Residual Overvoltage Protection ................................................... 2-7
2.7.5 Generator Stator Earth-fault Protection ............................................................................... 2-7
2.7.6 Stator Earth-fault Protection with External Inject Principle .................................................. 2-8
2.7.7 Generator Rotor Earth-fault Protection ............................................................................... 2-8
2.7.8 Generator Stator Overload Protection ................................................................................. 2-8
2.7.9 Generator Negative-sequence Overload Protection ........................................................... 2-8
2.7.10 Excitation Windings Overload Protection .......................................................................... 2-9
2.7.11 Generator Loss-of-excitation Protection ............................................................................ 2-9
2.7.12 Generator Out-of-step Protection ...................................................................................... 2-9
2.7.13 Generator Voltage Abnormality Protection ........................................................................ 2-9
2.7.14 Generator Over-excitation Protection .............................................................................. 2-10
2.7.15 Generator Power Protection ............................................................................................ 2-10
2.7.16 Generator Frequency Protection ..................................................................................... 2-10
2.7.17 Generator Inadvertent Energization Protection ............................................................... 2-10
2.7.18 Generator Startup/shutdown Protection ........................................................................... 2-11
2.7.19 Low-impedance Protection ............................................................................................... 2-11
2.7.20 Voltage Controlled Overcurrent Protection ....................................................................... 2-11
2.7.21 Mechanical Protection ...................................................................................................... 2-11
2.7.22 Breaker Failure Protection at Generator Terminal............................................................ 2-11
2.8 Metering Scope and Accuracy ..................................................................... 2-12
2.9 Management Functions ................................................................................ 2-12
2.9.1 Clock Performance ............................................................................................................ 2-12
2.9.2 Fault and Disturbance Recording ...................................................................................... 2-12
2.9.3 Binary Input Signal............................................................................................................. 2-12
-
2 Technical Data
PCS-985G Generator Relay 2-1
Date: 2013-06-24
2.1 Electrical Specifications
2.1.1 AC Current Input
Standard IEC 60255-27:2005
Phase rotation ABC
Nominal frequency (fn) 505Hz, 605Hz
Rated Current (In) 1A 5A
Linear to 0.05In~40In
Thermal withstand
-continuously
-for 10s
-for 1s
-for half a cycle
4In
30In
100In
250In
Burden < 0.15VA/phase @In < 0.25VA/phase @In
Accuracy 0.5%In
2.1.2 AC Voltage Input
Standard IEC 60255-6, IEC60288
Phase rotation ABC
Nominal frequency (fn) 505Hz, 605Hz
Rated Voltage (Un) 50~120V 100~220Vbroken-delta voltage
Linear to 1~170V 2V~233V
Thermal withstand
-continuously
-10s
-1s
200V
260V
300V
220V
380V
420V
Burden at rated < 0.20VA/phase @Un < 0.80VA/phase @Un
Accuracy 0.5%Un
2.1.3 Power Supply
Standard IEC 60255-11:2008
Rated Voltage 110Vdc/125Vdc, 220Vdc/250Vdc
Operating Range 80%~120% of rated voltage
Permissible AC ripple voltage 15% of the nominal auxiliary voltage
Burden
Quiescent condition
Operating condition
-
2 Technical Data
PCS-985G Generator Relay 2-2
Date: 2013-06-24
Dropoff voltage
-
2 Technical Data
PCS-985G Generator Relay 2-3
Date: 2013-06-24
Pollution degree 2
Altitude
-
2 Technical Data
PCS-985G Generator Relay 2-4
Date: 2013-06-24
2.4.3.3 For Pilot Channel
Characteristic Glass optical fiber
Connector type FC
Fibre type Single mode
Transmission distance
-
2 Technical Data
PCS-985G Generator Relay 2-5
Date: 2013-06-24
2.5.3 Electrical Tests
Standard IEC 60255-27:2005
Dielectric tests Test voltage 2kV, 50Hz, 1min
Standard IEC 60255-5:2000
Impulse voltage tests Test voltage 5kV
Overvoltage category
Insulation resistance
measurements Isolation resistance >100M@500VDC
2.5.4 Electromagnetic Compatibility
1MHz burst disturbance test
IEC 60255-22-1:2007
Common mode: class III 2.5kV
Differential mode: class III 1.0kV
Electrostatic discharge test
IEC60255-22-2:2008 class IV
For contact discharge: 8kV
For air discharge: 15kV
Radio frequency interference tests
IEC 60255-22-3:2007 class III
Frequency sweep
Radiated amplitude-modulated
10V/m (rms), f=80~1000MHz
Spot frequency
Radiated amplitude-modulated
10V/m (rms), f=80MHz/160MHz/450MHz/900MHz
Radiated pulse-modulated
10V/m (rms), f=900MHz
Fast transient disturbance tests
IEC 60255-22-4:2008
Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns
Communication terminals: class IV, 2kV, 5kHz, 5/50ns
Surge immunity test
IEC 60255-22-5:2008
Power supply, AC input, I/O port: class IV, 1.2/50us
Common mode: 4kV
Differential mode: 2kV
Conducted RF Electromagnetic
Disturbance
IEC 60255-22-6:2001
Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150
kHz~80MHz
Power Frequency Magnetic Field
Immunity
IEC 61000-4-8:2001
class V, 100A/m for 1min, 1000A/m for 3s
Pulse Magnetic Field Immunity IEC 61000-4-9:2001
class V, 6.4/16s, 1000A/m for 3s
Damped oscillatory magnetic field
immunity
IEC 61000-4-10:2001
class V, 100kHz & 1MHz100A/m
-
2 Technical Data
PCS-985G Generator Relay 2-6
Date: 2013-06-24
Auxiliary power supply performance
- Voltage dips
-Voltage short interruptions
IEC60255-11: 2008
Up to 500ms for dips to 40% of rated voltage without reset
100ms for interruption without rebooting
2.6 Certifications
ISO9001:2008
ISO14001:2004
OHSAS18001:2007
ISO10012:2003
CMMI L4
EMC: 2004/108/EC, EN50263:1999
Products safety(PS): 2006/95/EC, EN61010-1:2001
2.7 Protective Functions
Note!
Ie is secondary rated current of generator
In is secondary rated current of CT
Un is secondary rated voltage of VT
Pn is rated active power of generator
2.7.1 Generator/ Exciter Differential Protection
Pickup setting range of percentage differential
element 0.1Ie~1.5Ie
Setting accuracy 5% or 0.01In whichever is greater
Setting range of unrestrained instantaneous
differential element 2Ie~14Ie
Setting accuracy 2.5%
Setting range of first slope of percentage differential
element 0~0.50
Setting range of maximum slope of percentage
differential element 0.30~0.80
Operation time of percentage differential protection 25ms (2 times pickup current settings)
Operation time of unrestrained instantaneous
differential protection 20ms (1.5 times pickup current settings)
-
2 Technical Data
PCS-985G Generator Relay 2-7
Date: 2013-06-24
2.7.2 Excitation Transformer Differential Protection
Pickup setting range of percentage differential
element 0.1Ie~1.5Ie
Setting accuracy 5% or 0.01In whichever is greater
Setting range of unrestrained instantaneous
differential element 2Ie~14Ie
Setting accuracy 2.5%
Setting range of first slope of percentage differential
element 0~0.50
Setting range of maximum slope of percentage
differential element 0.50~0.80
Secondary harmonic restraint coefficient 0.10~0.35
Operation time of percentage differential protection 35ms(2 times pickup current settings)
Operation time of unrestrained instantaneous
differential protection 25ms(1.5 times pickup current settings)
2.7.3 Generator Transverse Differential Protection
Setting range of transverse differential element 0.1ln~10ln
High setting range of transverse differential element 0.1ln~10ln
Setting accuracy 2.5% or 0.01In whichever is greater
Time delay of transverse differential element
(one-point earth) 0.1~10s
Operating time 35ms (1.5 times pickup current settings)
2.7.4 Generator Longitudinal Residual Overvoltage Protection
Setting range of longitudinal residual voltage element 1~10V
Setting accuracy 2.5% or 0.05V whichever is greater
Setting accuracy of calculated longitudinal residual
voltage element 2.5% or 0.05V whichever is greater
Time delay of longitudinal residual voltage element 0.1~10s
Setting accuracy 1%Setting + 40ms
2.7.5 Generator Stator Earth-fault Protection
Setting range of residual voltage blocking element 1~100V
Setting range of residual voltage element 0.1~50V
High setting range of residual voltage element 0.1~50V
Setting accuracy 2.5% or 0.05V whichever is greater
Setting range of third harmonic voltage ratio element 0.5~10
Setting range of third harmonic voltage differential
element 0.05~2.0
Setting accuracy 5%
Time delay 0.1~10s
-
2 Technical Data
PCS-985G Generator Relay 2-8
Date: 2013-06-24
Setting accuracy 1%Setting + 40ms
2.7.6 Stator Earth-fault Protection with External Inject Principle
Resistance setting range 0.1~30k
Setting accuracy 5%
Residual current setting range 0.02~1.50A
Setting accuracy 5% or 0.001A whichever is greater
Time delay 0.1~10s
Setting accuracy 1%Setting + 40ms
2.7.7 Generator Rotor Earth-fault Protection
Resistance setting range of one-point earth 0.1~100k
Setting accuracy 10% or 0.5k whichever is greater
negative-sequence voltage setting range of 2nd
harmonic 0.1~10V
Setting range of switchover cycle 0.5~10s
Time delay 0.1~10s
Setting accuracy 1%Setting + 1s
2.7.8 Generator Stator Overload Protection
Definite-time current setting range 0.1In~10In
Setting accuracy 2.5% or 0.01In whichever is greater
Inverse-time pickup current setting range 0.1In~20In
Setting accuracy 2.5% or 0.01In whichever is greater
Time delay 0.1 ~10s
Setting accuracy 1%Seting + 40ms
Setting range of thermal capacity of stator windings 1~100
Setting range of heat emission factor 1.02~2.0
2.7.9 Generator Negative-sequence Overload Protection
Definite-time negative-sequence current setting range 0.1In~4In
Setting accuracy 2.5% or 0.01In whichever is greater
Time delay 0.1~10s
Setting accuracy 1%Setting + 40ms
Inverse-time negative-sequence pickup current
setting range 0.05In~1In
Setting accuracy 2.5% or 0.01In whichever is greater
Setting range of rotor heat constant 1~100
Setting range of continuous tolerable
negative-sequence current 0.05ln~1ln
-
2 Technical Data
PCS-985G Generator Relay 2-9
Date: 2013-06-24
2.7.10 Excitation Windings Overload Protection
Definite-time current setting range 0.1ln~20ln
Inverse-time pickup current setting range 0.05ln~10ln
Setting accuracy 2.5% or 0.01In whichever is greater
Time delay 0.1~25s
Setting accuracy 1%Setting + 40ms
Setting range of thermal capacity factor 1~100
Setting range of reference current 0.1ln~10ln
2.7.11 Generator Loss-of-excitation Protection
Impedance setting range (Z1) 0.1 ~ 200
Impedance setting range (Z2) 0.1 ~ 200
Setting accuracy 2.5% or 0.1 whichever is greater
Reverse reactive power setting range 0 ~ 50.00%Pn
Setting accuracy 1% or 0.002Pn whichever is greater
Low-voltage setting range of rotor 1 ~ 500V
No-load voltage setting range of rotor 1 ~ 500V
Low-voltage setting range of bus or generator terminal 0.1 ~ 100V
Setting accuracy 2.5% or 0.05V whichever is greater
Setting range of rotor low-voltage factor 0 ~ 10
Time delay of stage 1 and stage 2 0.1 ~ 10s
Time delay of stage 3 0.1 ~ 3000s
Setting accuracy 1%Setting + 40ms
2.7.12 Generator Out-of-step Protection
Impedance setting A range 0 ~ 100
Impedance setting B range 0 ~ 100
Impedance setting C range 0 ~ 100
Setting accuracy 2.5% or 0.1whichever is greater
Setting range of sensitive angle 0 ~ 90
Setting range of lens inner angle lens 0 ~ 150
Setting accuracy 3
Setting range of pole slipping number 1 ~ 1000
Setting range of permitted tripping current 0.1ln ~ 20ln
Setting accuracy 2.5% or 0.01In whichever is greater
2.7.13 Generator Voltage Abnormality Protection
Vero-voltage setting range 0.1 ~ 200V
Under-voltage setting range 0.1 ~ 100V
Setting accuracy 2.5% or 0.05V whichever is greater
Time delay 0 ~ 10s
Setting accuracy 1%Setting + 40ms
-
2 Technical Data
PCS-985G Generator Relay 2-10
Date: 2013-06-24
2.7.14 Generator Over-excitation Protection
Definite time V/F setting range 1.0 ~ 2.0 pu
Setting accuracy 2.5% or 0.01 whichever is greater
Definite time delay for tripping 0.1 ~ 3000.0s
Definite time delay for alarm 0.1 ~ 25s
Setting accuracy 1%Setting + 40ms
Inverse time V/F setting range 1.0 ~ 2.0 pu
Inverse time delay for tripping 0.1 ~ 3000.0s
2.7.15 Generator Power Protection
Setting range of reverse power element 0.5 ~ 50%Pn
Setting range of reverse power sequential tripping
element 0.5 ~ 10%Pn
Setting range of under-power element 0.5 ~ 10%Pn
Setting accuracy 10% or 0.002Pn whichever is greater
Time delay of reverse power element 0.1 ~ 3000s
Time delay of reverse power sequential tripping
element 0.01~10s
Time delay of under-power element 0.01~10s
Setting accuracy 1%Setting + 40ms
2.7.16 Generator Frequency Protection
Setting range of underfrequency protection (stage
1~3) 0.90~1.02fn
Setting range of overfrequency protection (stage 1-2) 1.00~1.20fn
Setting accuracy 0.02Hz
Time delay of underfrequency protection (stage 1~2) 0.1 ~ 300min
Time delay of underfrequency protection (stage 3) 0.1 ~ 100s
Time delay of overfrequency protection (stage 1) 0.1 ~ 100min
Time delay of overfrequency protection (stage 2) 0.1 ~ 100s
Setting accuracy 1%Setting + 40ms
2.7.17 Generator Inadvertent Energization Protection
Current setting range of inadvertent energization
protection 0.1ln ~ 10ln
Setting accuracy 2.5% or 0.01In whichever is greater
Undervoltage setting range of inadvertent
energization protection 6~80V
Setting accuracy 2.5% or 0.05V whichever is greater
Blocking frequency setting range 0.80~1.00fn
Time delay of inadvertent energization protection 0.01 ~ 1.0s
Setting accuracy 1%Setting + 40ms
-
2 Technical Data
PCS-985G Generator Relay 2-11
Date: 2013-06-24
2.7.18 Generator Startup/shutdown Protection
Blocking frequency setting range 0.80~1.00fn
Differential current setting range 0.2le~10Ie
Setting accuracy 5% or 0.02In whichever is greater
Overcurrent setting range under low-frequency
condition 0.1ln ~ 20ln
Setting accuracy 5% or 0.02In whichever is greater
Residual voltage setting range 5 ~ 25V
Setting accuracy 5% or 0.02Un whichever is greater
Time delay 0 ~ 10s
Setting accuracy 1%Setting + 40ms
setting range
2.7.19 Low-impedance Protection
Forward impedance setting range 0.1 ~ 100
Reverse impedance setting range 0.1 ~ 100
Setting accuracy 2.5% or 0.1 whichever is greater
Time delay 0.1 ~ 10s
Setting accuracy 1%Setting + 40ms
2.7.20 Voltage Controlled Overcurrent Protection
Negative-sequence voltage setting range 1 ~ 20V
Low voltage setting range 10 ~ 100V
Setting accuracy 2.5% or 0.05V whichever is greater
Current setting range 0.1ln ~ 20ln
Setting accuracy 2.5% or 0.01In whichever is greater
Time delay 0 ~ 10s
Setting accuracy 1%Setting + 40ms
2.7.21 Mechanical Protection
Time delay 0.1 ~ 10s
Setting accuracy 1%Setting + 40ms
2.7.22 Breaker Failure Protection at Generator Terminal
Phase current setting range 0.1ln ~ 4ln
Negative-sequence current setting range 0.1ln ~ 4ln
Setting accuracy 2.5% or 0.01In whichever is greater
Time delay 0.1~ 10s
Setting accuracy 1% + 40ms
-
2 Technical Data
PCS-985G Generator Relay 2-12
Date: 2013-06-24
2.8 Metering Scope and Accuracy
Metering Item Range Accuracy
Phase range 0 ~ 360 0.5% or 1
Frequency 35.00Hz ~ 70.00Hz 0.02Hz
Currents from dedicated metering current transformers
Current 0.05 ~ 1.40In 0.2% of rating
Active power (W) 0.05 ~ 1.20Un, 0.05 ~ 1.40In 1.0% of rating at unity power factor
Currents from protection measurement current transformers
Current 0.05 ~ 1.40In 2.0% of rating
Voltage 0.05 ~ 1.20Un 1.0% of rating
Active power (W) 0.05 ~ 1.20Un, 0.05 ~ 1.40In 3.0% of rating at unity power factor
2.9 Management Functions
2.9.1 Clock Performance
Real time clock accuracy 3s/day
Accuracy of GPS synchronization 1ms
External time synchronization IRIG-B (200-98), PPS, IEEE1588 or SNTP protocol
2.9.2 Fault and Disturbance Recording
Magnitude and relative phases 2.5% of applied quantities
Maximum duration 2048 sampled points (24 sampled points per cycle)
Recording position 3 cycles before pickup of trigger element
2.9.3 Binary Input Signal
Resolution of binary input signal 1ms
Binary input mode Potential-free contact
Resolution of SOE 2ms
-
3 Operation Theory
PCS-985G Generator Relay 3-a
Date: 2013-06-28
3 Operation Theory
Table of Contents
3 Operation Theory ............................................................................ 3-a
3.1 Overview .......................................................................................................... 3-1
3.2 Fault Detector (FD) .......................................................................................... 3-1
3.2.1 Differential Protection of Generator ..................................................................................... 3-2
3.2.2 Inter-turn Protection of Generator ....................................................................................... 3-2
3.2.3 Stator Earth-fault Protection of Generator ........................................................................... 3-2
3.2.4 Stator Earth-fault Protection with Voltage Injection of Generator ........................................ 3-2
3.2.5 Rotor Earth-fault Protection of Generator ........................................................................... 3-2
3.2.6 Stator Overload Protection of Generator ............................................................................. 3-3
3.2.7 Negative-sequence Overload Protection of Generator ....................................................... 3-3
3.2.8 Loss-of-excitation Protection of Generator .......................................................................... 3-3
3.2.9 Out-of-step Protection of Generator .................................................................................... 3-3
3.2.10 Voltage Protection of Generator ........................................................................................ 3-3
3.2.11 Over-excitation Protection of Generator ............................................................................ 3-3
3.2.12 Power Protection of Generator .......................................................................................... 3-4
3.2.13 Frequency Protection of Generator ................................................................................... 3-4
3.2.14 Inadvertent Energization Protection of Generator ............................................................. 3-4
3.2.15 Startup/shutdown Protection of Generator ........................................................................ 3-4
3.2.16 Differential Protection of Excitation Transformer/Exciter ................................................... 3-4
3.2.17 Overcurrent Protection/Overload Protection of Excitation Transformer/Exciter................ 3-5
3.2.18 Breaker Failure Protection at Generator Terminal............................................................. 3-5
3.2.19 Mechanical Protection ....................................................................................................... 3-5
3.3 Differential Protection of Excitation Transformer/Exciter............................ 3-5
3.3.1 Operation Characteristic ...................................................................................................... 3-5
3.3.2 Inrush Current Detection Element ....................................................................................... 3-7
-
3 Operation Theory
PCS-985G Generator Relay 3-b
Date: 2013-06-28
3.3.3 CT Saturation Detection Element ........................................................................................ 3-8
3.3.4 High-setting Percentage Differential Protection Element (HSDP) ...................................... 3-8
3.3.5 Unrestrained Instantaneous Differential Protection Element (UIDP) .................................. 3-9
3.3.6 Differential Current Abnormality Alarm and CT Circuit Failure Blocking ............................. 3-9
3.3.7 Overexcitation Detection Element ..................................................................................... 3-10
3.3.8 Logic Scheme ..................................................................................................................... 3-11
3.4 Differential Protection of Generator ............................................................ 3-12
3.4.1 Percentage Differential Protection (SPDP) ....................................................................... 3-12
3.4.2 High Performance Blocking Technique in Case of CT Saturation .................................... 3-13
3.4.3 High-setting Percentage Differential Protection (HSDP) ................................................... 3-14
3.4.4 Unrestrained Instantaneous Differential Protection (UIDP) .............................................. 3-14
3.4.5 Differential Current Abnormality Alarm and CT Circuit Failure Blocking ........................... 3-14
3.4.6 Logic Scheme .................................................................................................................... 3-15
3.5 DPFC Differential Protection ........................................................................ 3-15
3.5.1 Operation Characteristic .................................................................................................... 3-16
3.5.2 Differential Current Abnormality Alarm and CT Circuit Failure Blocking ........................... 3-17
3.5.3 Logic Scheme .................................................................................................................... 3-17
3.6 Generator Inter-turn Protection ................................................................... 3-18
3.6.1 High-sensitive Transverse Differential Protection ............................................................. 3-18
3.6.2 Longitudinal Residual Voltage Protection .......................................................................... 3-20
3.6.3 VT2 Circuit Failure Alarm and Blocking ............................................................................. 3-20
3.6.4 DPFC Inter-turn Protection ................................................................................................ 3-21
3.6.5 Calculated Longitudinal Residual Voltage Protection ....................................................... 3-21
3.6.6 VT1 Circuit Failure Alarm and Blocking ............................................................................. 3-23
3.7 Phase-to-phase Backup Protection of Generator ...................................... 3-23
3.7.1 Voltage Controlled Overcurrent Protection ........................................................................ 3-23
3.7.2 Impedance Protection ........................................................................................................ 3-25
3.8 Stator Earth-fault Protection ........................................................................ 3-27
3.8.1 Fundamental Residual Overvoltage Protection ................................................................. 3-27
3.8.2 Third Harmonic Voltage Ratio Protection .......................................................................... 3-28
-
3 Operation Theory
PCS-985G Generator Relay 3-c
Date: 2013-06-28
3.8.3 Third Harmonic Voltage Differential Protection ................................................................. 3-29
3.8.4 VT Circuit Failure Blocking ................................................................................................ 3-29
3.8.5 Logic Scheme .................................................................................................................... 3-30
3.9 Stator Earth-fault Protection with Voltage Injection ................................... 3-32
3.9.1 Earthing Resistance Criterion ............................................................................................ 3-32
3.9.2 Earthing Current Criterion .................................................................................................. 3-33
3.9.3 External Voltage Circuit Monitoring ................................................................................... 3-33
3.9.4 Logic Scheme .................................................................................................................... 3-34
3.10 Rotor Earth-fault Protection with Ping-pang Type ................................... 3-34
3.10.1 One-point Earth-fault Protection ...................................................................................... 3-34
3.10.2 Two-points Earth fault Protection .................................................................................... 3-35
3.11 Rotor Earth-fault Protection with Voltage Injection .................................. 3-36
3.11.1 One-point Earth-fault Protection ...................................................................................... 3-36
3.11.2 Two-point Earth-fault Protection ...................................................................................... 3-37
3.12 Stator Overload Protection ......................................................................... 3-38
3.12.1 Definite-time Stator Overload Protection ......................................................................... 3-38
3.12.2 Inverse-time Stator Overload Protection ......................................................................... 3-39
3.13 Negative-sequence Overload Protection .................................................. 3-40
3.13.1 Definite-time Negative-sequence Overload Protection ................................................... 3-40
3.13.2 Inverse-time Negative-sequence Overload Protection ................................................... 3-41
3.14 Loss-of-excitation Protection ..................................................................... 3-42
3.14.1 Undervoltage Criterion ..................................................................................................... 3-42
3.14.2 Stator-side Impedance Criterion ...................................................................................... 3-43
3.14.3 Rotor-side Criterion ......................................................................................................... 3-44
3.14.4 Logic Scheme .................................................................................................................. 3-45
3.15 Out-of-step Protection ................................................................................ 3-46
3.16 Generator Voltage Protection ..................................................................... 3-48
3.16.1 Overvoltage Protection .................................................................................................... 3-48
3.16.2 Undervoltage Protection .................................................................................................. 3-49
3.17 Over-excitation Protection ......................................................................... 3-50
-
3 Operation Theory
PCS-985G Generator Relay 3-d
Date: 2013-06-28
3.17.1 Definite-time Over-excitation Protection .......................................................................... 3-50
3.17.2 Inverse-time Over-excitation Protection .......................................................................... 3-50
3.18 Power Protection......................................................................................... 3-51
3.18.1 Reverse Power Protection ............................................................................................... 3-51
3.18.2 Sequence Tripping Reverse Power Protection ............................................................... 3-52
3.18.3 Low Power Protection ...................................................................................................... 3-53
3.19 Frequency Protection ................................................................................. 3-53
3.19.1 Underfrequency Protection .............................................................................................. 3-53
3.19.2 Overfrequency Protection ................................................................................................ 3-53
3.19.3 Logic Scheme .................................................................................................................. 3-54
3.20 Inadvertent Energization Protection .......................................................... 3-54
3.21 Startup and Shutdown Protection ............................................................. 3-56
3.22 Overload Protection of Excitation Windings ............................................ 3-57
3.22.1 Definite-time Excitation Winding Overload Protection .................................................... 3-57
3.22.2 Inverse-time Excitation Winding Overload Protection ..................................................... 3-58
3.23 Excitation Transformer /Exciter Overcurrent Protection ......................... 3-59
3.24 Breaker Failure Protection at Generator Terminal ................................... 3-59
3.25 CT Circuit Supervision ............................................................................... 3-60
3.25.1 Three-phase Current Circuit Failure Alarm ..................................................................... 3-60
3.25.2 Differential Current Alarm in Differential Protection Circuit ............................................. 3-60
3.25.3 Alarm or Blocking to Differential Protection by CT Circuit Failure ................................... 3-61
3.26 VT Circuit Supervision ................................................................................ 3-61
3.26.1 VT Circuit of Any Side Failure Alarm ............................................................................... 3-61
3.26.2 Voltage Valance on Generator Terminals ........................................................................ 3-62
3.26.3 Three-phase Voltage Circuit Failure Supervision ............................................................ 3-62
3.27 Mechanical protection ................................................................................ 3-62
List of Figures
Figure 3.1-1 Hardware structure ................................................................................................ 3-1
Figure 3.3-1 Operation characteristic of differential protection............................................. 3-6
-
3 Operation Theory
PCS-985G Generator Relay 3-e
Date: 2013-06-28
Figure 3.3-2 Operation characteristic of HSDP ........................................................................ 3-9
Figure 3.3-3 Logic diagram of differential protection ............................................................ 3-11
Figure 3.4-1 Operation characteristic of percentage differential protection ...................... 3-12
Figure 3.4-2 Logic diagram of differential protection ............................................................ 3-15
Figure 3.5-1 Operating characteristic of DPFC percentage differential protection ........... 3-17
Figure 3.5-2 Logic diagram of DPFC percentage differential protection ............................ 3-17
Figure 3.6-1 Logic diagram of high-setting stage transverse differential protection ........ 3-19
Figure 3.6-2 Logic diagram of sensitive stage transverse differential protection ............. 3-19
Figure 3.6-3 Logic diagram of longitudinal residual voltage protection ............................. 3-20
Figure 3.6-4 Logic diagram of calculated longitudinal residual voltage protection .......... 3-22
Figure 3.7-1 Logic diagram of overcurrent protection .......................................................... 3-25
Figure 3.7-2 Operation characteristic of impedance protection .......................................... 3-26
Figure 3.7-3 Logic diagram of impedance protection ........................................................... 3-27
Figure 3.8-1 Logic diagram of stator earth-fault protection ................................................. 3-31
Figure 3.9-1 Circuit design of stator earth-fault protection with voltage injection ............ 3-32
Figure 3.9-2 Logic diagram of stator earth-fault protection with voltage injection ........... 3-34
Figure 3.10-1 Schematic diagram of measurement principle ............................................... 3-35
Figure 3.10-2 Logic diagram of one-point earth fault protection ......................................... 3-35
Figure 3.10-3 Logic diagram of two-points earth fault protection ....................................... 3-36
Figure 3.11-1 Measuring scheme of voltage injection into the rotor winding at single-end
.............................................................................................................................................. 3-36
Figure 3.11-2 Measuring scheme of voltage injection into the rotor winding at double-ends
.............................................................................................................................................. 3-37
Figure 3.11-3 Logic diagram of one-point earth-fault protection ......................................... 3-37
Figure 3.11-4 Logic diagram of two-points earth-fault protection ....................................... 3-38
Figure 3.12-1 Logic diagram of definite-time stator overload protection ........................... 3-39
Figure 3.12-2 Operation curve of inverse-time stator overload protection ........................ 3-39
Figure 3.12-3 Logic diagram of inverse-time stator overload protection ........................... 3-40
Figure 3.13-1 Logic diagram of definite-time negative-sequence overload protection .... 3-41
Figure 3.13-2 Operation curve of inverse-time negative-sequence overload protection .. 3-41
-
3 Operation Theory
PCS-985G Generator Relay 3-f
Date: 2013-06-28
Figure 3.13-3 Logic diagram of inverse-time negative-sequence overload protection ..... 3-42
Figure 3.14-1 Operation characteristic of steady-state stabilization impedance circle .... 3-43
Figure 3.14-2 Operation characteristic of asynchronous impedance circle ...................... 3-44
Figure 3.14-3 Logic diagram of loss-of-excitation protection (stage 1) .............................. 3-45
Figure 3.14-4 Logic diagram of loss-of-excitation protection (stage 2) .............................. 3-46
Figure 3.14-5 Logic diagram of loss-of-excitation protection (stage 3) .............................. 3-46
Figure 3.15-1 Operation characteristic of out-of-step protection ........................................ 3-47
Figure 3.15-2 Logic diagram of out-of-step protection ......................................................... 3-48
Figure 3.16-1 Logic diagram of overvoltage protection ........................................................ 3-49
Figure 3.16-2 Logic diagram of undervoltage protection ..................................................... 3-49
Figure 3.17-1 Logic diagram of definite-time over-excitation protection ............................ 3-50
Figure 3.17-2 Inverse-time characteristics ............................................................................. 3-51
Figure 3.17-3 Logic diagram of inverse-time over-excitation protection ............................ 3-51
Figure 3.18-1 Logic diagram of reverse power protection ................................................... 3-52
Figure 3.18-2 Logic diagram of sequence tripping reverse power protection ................... 3-52
Figure 3.18-3 Logic diagram of low power protection .......................................................... 3-53
Figure 3.19-1 Logic diagram of underfrequency protection ................................................. 3-54
Figure 3.19-2 Logic diagram of overfrequency protection ................................................... 3-54
Figure 3.20-1 Logic diagram of inadvertent energization protection (standard version) . 3-55
Figure 3.20-2 Logic diagram of inadvertent energization protection (special version) .... 3-56
Figure 3.21-1 Logic diagram of generator startup and shutdown protection .................... 3-57
Figure 3.22-1 Logic diagram of definite time excitation winding overload protection ...... 3-57
Figure 3.22-2 Operation characteristic of inverse-time excitation winding overload
protection ............................................................................................................................ 3-58
Figure 3.22-3 Logic diagram of inverse-time excitation winding overload protection ...... 3-59
Figure 3.23-1 Logic diagram of excitation transformer or exciter overcurrent protection 3-59
Figure 3.24-1 Logic diagram of breaker failure protection ................................................... 3-60
-
3 Operation Theory
PCS-985G Generator Relay 3-1
Date: 2013-06-28
3.1 Overview
The device has 2 plug-in modules (i.e. protection DSP module and fault detector DSP module),
and the logic relation between them is AND. They have independent sample circuit and output
circuit. AC current and voltage is converted into small voltage signal and sent to protection
calculation module (also called DSP module 1) and fault detector calculation module (also called
DSP module 2) respectively. Protection DSP module is responsible for protection calculation and
fault detector DSP module is responsible for fault detector. Fault detectors on fault detector DSP
module picks up to connect positive pole of power supply of output relays. Real-time data
exchange between protection DSP module and fault detector DSP module is performed. Based on
strict mutual check and self-check, any of them fails will lead to block the device and issue alarm
signal. The device will not mal-operate due to hardware error.
AC
Signal LPF A/D DSP
CPU
External BI
Output
RelayProtection DSP module
LPF A/D DSP
Fault detector DSP module
+E
Opto-
coupler
QDJ
Ethernet
Clock Synchronization
Serial port
Print
Figure 3.1-1 Hardware structure
3.2 Fault Detector (FD)
Each fault detector element will be enabled when the corresponding protection element is enabled.
After the fault detector element operates, the positive power supply will be provided to output relay
and pickup signal will keep 500ms even the fault detector element drops off. Tripping output is only
enabled if both corresponding fault detector element on fault detector DSP module and
corresponding protection element on protection DSP module operate, otherwise the device will
issue alarm signal. The fault detector element with the prefix of FD_ will delay drop-off with a
time delay of 500ms, and the fault detector element with the prefix of St_ will dropoff with no
time delay. The principle of each fault detector element is given below:
-
3 Operation Theory
PCS-985G Generator Relay 3-2
Date: 2013-06-28
3.2.1 Differential Protection of Generator
When the differential current of generator is greater than the setting [I_Pkp_PcntDiff_Gen], the
fault detector element of generator differential protection [FD_Diff_Gen] and [St1_DiffProt_Gen]
will operate.
When the fundamental variation of differential current is greater than the threshold value, the fault
detector element of generator differential protection [FD_Diff_Gen] and [St2_DiffProt_Gen] will
operate.
3.2.2 Inter-turn Protection of Generator
When the transverse differential current of generator is greater than the setting
[I_SensTrvDiff_Gen], the fault detector element of generator transverse differential protection
[FD_IntTurn_Gen] and [St_TrvDiffProt_Gen] will operate.
When the longitudinal residual voltage is greater than the setting [V_SensROV_Longl_Gen], the
fault detector element of longitudinal residual voltage protection [FD_IntTurn_Gen] and
[St_ROV_Longl_Gen] will operate.
When the fundamental variation of negative-sequence voltage, current and power are greater than
their threshold values, the fault detector element of DPFC inter-turn protection [FD_IntTurn_Gen]
and [St_DPFC_IntTurn_Gen] will operate.
When the calculated longitudinal residual voltage is greater than the setting
[V_SensROV_Longl_Gen], the fault detector element of longitudinal residual voltage protection
[FD_IntTurn_Gen] and [St_ROV_Longl2_Gen] will operate.
3.2.3 Stator Earth-fault Protection of Generator
When residual voltage of generator terminal and neutral point are greater than the setting
[V_SensROV_Sta], the fault detector element of residual voltage protection [FD_StaEF_Gen] and
[St_ROVProt_Sta] will operate.
When third harmonic voltage ratio is greater than the setting [k_V3rdHRatio_PreSync_Sta] or
[k_V3rdHRatio_PostSync_Sta], the fault detector element of third harmonic voltage ratio
protection [FD_StaEF_Gen] and [St_V3rdHRatio_Sta] will operate.
3.2.4 Stator Earth-fault Protection with Voltage Injection of Generator
When the calculated earth resistance is lower than the resistance setting [R_Trp_Inj_EF_Sta], the
fault detector element [FD_InjStaEF_Gen] and [St_InjR_Sta] will operate.
When earthing current of stator without being subjected to digital filter is greater than the current
setting [I_ROC_Inj_EF_Sta], the fault detector element [FD_InjStaEF_Gen] and [St_InjI0_Sta] will
operate.
3.2.5 Rotor Earth-fault Protection of Generator
When grounded resistance of rotor windings is smaller than its setting [R_1PEF_RotWdg], the
fault detector element of rotor one-point earth-fault protection [FD_EF_RotWdg] and
-
3 Operation Theory
PCS-985G Generator Relay 3-3
Date: 2013-06-28
[St_1PEF_RotWdg] will operate.
When the change of rotor grounding location is greater than its internally fixed setting, the fault
detector element of rotor two-points earth-fault protection will [FD_EF_RotWdg] and
[St_2PEF_RotWdg] operate.
3.2.6 Stator Overload Protection of Generator
When maximum value of three phase currents is greater than the setting [I_OvLd_Sta], the fault
detector element of definite-time overload protection [FD_StaOvLd_Gen] and [St_OvLd_Sta] will
operate.
When the inverse time accumulated value is greater than the setting [I_InvOvLd_Sta], the fault
detector element of inverse-time overload protection [FD_StaOvLd_Gen] and [St_InvOvLd_Sta]
will operate.
3.2.7 Negative-sequence Overload Protection of Generator
When maximum value of negative sequence current is greater than the setting [I_NegOC_Gen],
the fault detector element of definite-time negative-sequence overload protection
[FD_NegOC_Gen] and [St_NegOC_Sta] will operate.
When the inverse time accumulated value is greater than the setting [I_InvNegOC_Gen], the fault
detector element of inverse-time negative-sequence overload protection [FD_NegOC_Gen] and
[St_InvNegOC_Sta] will operate.
3.2.8 Loss-of-excitation Protection of Generator
When the locus of calculated impedance enters into impedance circle, the fault detector of
loss-of-excitation protection [FD_LossExc_Gen] and [St_LossExcn_Gen] (n can be 1, 2 or 3) will
operate.
3.2.9 Out-of-step Protection of Generator
When the locus of calculated impedance leaves boundary of impedance operation zone, the fault
detector of out-of-step protection [FD_OOS_Gen] and [St_x_OOS_Gen] (x can be Ext or Int) will
operate.
3.2.10 Voltage Protection of Generator
When maximum value of three phase-to-phase voltage is greater than the setting [V_OVn_Gen],
the fault detector element of overvoltage protection [FD_VoltProt_Gen] and [St_OVn_Gen] will
operate (n can be 1 or 2).
When maximum value of three phase-to-phase voltage is greater than the setting [V_UV_Gen],
the fault detector element of overvoltage protection [FD_VoltProt_Gen] and [St_UV_Gen] will
operate.
3.2.11 Over-excitation Protection of Generator
When the measured U/F is greater than the setting [k_OvExc1_Gen], the fault detector element of
-
3 Operation Theory
PCS-985G Generator Relay 3-4
Date: 2013-06-28
definite-time over-excitation protection [FD_OvExc_Gen] and [St_OvExc1_Gen] will operate.
When the accumulated value is greater than the setting [k0_InvOvExc_Gen], the fault detector
element of inverse-time over-excitation protection [FD_OvExc_Gen] and [St_OvExc2_Gen] will
operate.
3.2.12 Power Protection of Generator
When reverse power is greater than setting [P_RevP_Gen], the fault detector of reverse power
protection [FD_PwrProt_Gen] and [St_RevP_Gen] will operate.
When reverse power is greater than setting [P_SeqTrpRevP_Gen], the fault detector of reverse
power protection [FD_PwrProt_Gen] and [St_SeqTrpRevP_Gen] will operate.
When power is lower than setting [P_UP_Gen] and the binary input [BI_NotUrgBrake] is energized,
the fault detector of low power protection [FD_PwrProt_Gen] and [St_UP_Gen] will operate.
3.2.13 Frequency Protection of Generator
When the frequency is smaller than the setting value for a specified time interval, the fault detector
element of low-frequency protection [FD_Freq_Gen] and [St_UFn_Gen] (n can be 1, 2 or 3) will
operate.
When the frequency is greater than the setting value for a specified time interval, the fault detector
element of over-frequency protection [FD_Freq_Gen] and [St_OFx_Gen] (x can be 1 or 2) will
operate.
3.2.14 Inadvertent Energization Protection of Generator
When the maximum value of three phase currents of generator is greater than the setting
[I_OC_AccEnerg_Gen], the fault detector element of generator inadvertent energization protection
[FD_AccEnerg_Gen] and [St_AccEnerg_Gen] will operate.
3.2.15 Startup/shutdown Protection of Generator
When the differential current of generator is greater than the setting [I_GenDiff_StShut_Gen], the
fault detector element of generator startup/shutdown protection [FD_StShut_Gen] and
[St_GenDiff_StShut_Gen] will operate.
When the residual voltage of generator is greater than the setting [V_StaROV_StShut_Gen], the
fault detector element of generator startup/shutdown protection [FD_StShut_Gen] and
[St_StaROV_StShut_Gen] will operate.
When the low-frequency current of generator neutral point is greater than the setting
[I_OC_StShut_Gen], the fault detector element of generator startup/shutdown protection
[FD_StShut_Gen] and [St_OC_StShut_Gen] will operate.
3.2.16 Differential Protection of Excitation Transformer/Exciter
When the maximum value of three phase differential currents is greater than the setting
[I_Pkp_PcntDiff_Exc], the fault detector element of differential protection [FD_Diff_Exc] and
[St_DiffProt_Exc] will operate.
-
3 Operation Theory
PCS-985G Generator Relay 3-5
Date: 2013-06-28
3.2.17 Overcurrent Protection/Overload Protection of Excitation
Transformer/Exciter
When the maximum value of three phase currents is greater than the setting [I_OCn_Exc] (n can
be 1 or 2), the fault detector element of overcurrent protection [FD_Bak_Exc] and [St_OCn_Exc]
will operate.
3.2.18 Breaker Failure Protection at Generator Terminal
When the binary input [BI_ExtTrpCtrl] is energized, and phase current or negative-sequence
current is greater than the setting value, the fault detector element of breaker failure protection
[FD_BFPGCBProt] and [St_BFPGCBProt] will operate.
3.2.19 Mechanical Protection
When the operation duration of mechanical protection is greater than its time delay, the fault
detector element of mechanical protection [FD_MechRly] and [St_MechRlyn] (n can be 1, 2, 3, 4,
5, 6, 7 or 8) will operate.
Note!
These setting values of above fault detector elements are formed automatically by the
device, it needs not to set manually.
3.3 Differential Protection of Excitation Transformer/Exciter
3.3.1 Operation Characteristic
Operation cr