nal/nalf – for 12kv indoor switch-disconnector and switch ...f... · nal/nalf – for 12kv indoor...
TRANSCRIPT
— D IS TR I BUTI ON SOLUTI ONS
NAL/NALF – for 12kVIndoor switch-disconnector and switch-fuse combination
ABB offers its NAL switch-disconnector for 12kV, up to 1250A, and 1000 operations to support your panel building and CSS manufacturing business needs.
Maximizing your productivity• up to 15 years maintenance intervals (see details
in product manual)• 100 breaking operations at 630 A rated current • Easy replaceable with NAL/NALF-H version design
Optimize your investment• Reduced spare inventories• Recyclable materials• Modular design minimizes installation time
Safeguard your personnel and assets• Wide operating temperatures within -40/+55
Celsius degrees (higher values available based on agreement with manufacturer)
• high making capability up to 67 kA• Visible open insulation gap
NAL 12 kV 400/630 A is a general purpose switch. NAL 12 kV 1250 A is a limited purpose switch
Ensures safety and protection ofpersonnel and assets
Guarantees continuous and reliable operation of critical processes
Reduces maintenance and logistic efforts
2 N A L/N A LF – FO R 1 2 K V
—Technical data
—Switch disconnector type NAL–12 kV according to IEC 62271-103:2011
Rated voltage Ur kV 12
Rated current I A 400 630 1250
Rated continuous current Ir A 400 630 1150
Rated short-circuit making current Ima kA peak 67
Rated peak withstand current Ip kA peak 82
Rated short-time withstand current
1sIk kA r.m.s.
31.5 31.5 31.5
2s 25 25 25
Rated mainly active load-breaking current Iload A 400 630 1250
Rated closed-loop breaking current Iloop A 400 630 1250
Rated cable/line charging breaking capacity Icc/Ilc A 150 150
Rated earth fault breaking current Ief1 A 150 150
Rated cable-and line-charging breaking current under earth fault conditions
Ief2 A 90 90
Rated short-duration power-frequency withstand voltage
Common valueUd kV
281)
Across the isolating distance 321)
Rated lighting impulse withstand voltage
Common valueUp kV
75
Across the isolating distance 85
Rated frequency fr Hz 50
Pole distance mm 150; 170; 210
Max. operating torque on the spring mechanism shaft Nm 110
Opening time ms 40-60
Max. arcing time ms 10
Temperature class °C -40 +402)
Mechanical endurance class - M1
Electrical endurance class - E3 E3 E1
Capacitive switching class - C2 C2 -
Service condition class acc. IEC62271-304 Class 0 —Switch – Fuse combination type NALF–12 kV according to IEC 62271-105:2012
Rated voltage Ur kV 12
Rated normal current with fuses I A 1253)
Rated short-circuit breaking current I1 kA r.m.s. 63
Rated transfer current Irtransfer A 1600
Rated take-over current IIto A 1450
Making and breaking test at the rated short-circuit current Isc kA 158
Making and breaking test at the maximum breaking I2t Iwmax A 5170
Rated lighting impulse withstand voltage
Common valueUp kV
75
Across the isolating distance 85
Rated frequency fr Hz 50
Pole distance mm 150; 210
Max. operating torque on the spring mechanism shaft Nm 110
Opening time ms 40-60
Max. arcing time ms 10
Temperature class °C -40 +402)
Service condition class acc. IEC62271-304 Class 0
Above values are valid for CEF fuse-link produced by ABB. Other fuse-links can be used if IEC 62271-105 ed. 2.0 closure 6.105.3 is met.
IN D O O R S W ITCH - D ISCO N N EC TO R A N D S W ITC H - FUSE CO M B IN ATI O NN A L/N A LF – FO R 1 2 K V 3
—Earthing switch type E for NAL/NALF and stand alone type EB4) according to IEC 62271-102:2018
Rated voltage Ur kV 12
Rated frequency fr Hz 50
Rated peak withstand current Ip kA peak 825)
Rated short-time withstand current 1s Ik kA r.m.s. 31.5
Rated short-circuit making current Ima kA peak 675)
Rated power-frequency withstand voltage Ud kV 42
Rated lighting impulse withstand voltage Up kV 75
Pole distance mm 150; 170; 210
Mechanical endurance class - M0
Short-circuit making capability class - E2
Minimum and maximum ambient air temperature °C -40+402)
1) Higher value available based on agreement with manufacturer 2) For special application +55°C is available based on agreement with manufacturer. 3) 125 A valid for CEF 12 kV 125 A. For other fuses max rated current with fuses can be reduced according to standard requirements. 4) Mechanical interlocking can be fitted.5) When fed from moving contact side.
—Dimensions NAL-12 version (other configurations are available)
Type W[mm]
H[mm]
NAL 12-A/K P=150 mm 698 653
NAL 12-A/K P=170 mm 738 653
NAL 12-A/K P=210 mm 818 653
W
H
394
34
06
PL
160
5-W
1-en
. Ed
itio
n 0
8.2
018
—ABB Contact Centertel.: +48 22 22 37 [email protected]
ABB Sp. z o.o.Branch in Przasnysz59 Leszno St.06-300 Przasnysz, PolandPhone: +48 22 22 38 900 Fax: +48 22 22 38 950
—We reserve the right to make technical changes or modify the contents of this do-cument without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any re-sponsibility whatsoever for potential er-rors or possible lack of information in this document.
We reserve all rights in this document and in the subject matter and illustrations con-tained therein. Any reproduction, disclo-sure to third parties or utilization of its contents – in whole or in parts – is forbid-den without prior written consent of ABB.© Copyright 2018 ABB All rights reserved
—For additional information please contact your local ABB representative or visit web page.
www.abb.com
—Dimensions NALF-12 version (other configurations are available)
Type Fuse length[mm]
W[mm]
H[mm]
NALF 12-A/K P=150 mm
192 698 1064
292 698 1164
442 698 1314
NALF 12-A/K P=170 mm
192 738 1064
292 738 1164
442 738 1314
NALF 12-A/K P=210 mm
192 818 1064
292 818 1164
442 818 1314
W
H
394