Ser THl N21r 2 no. 167 c. 2 BLDG AbJdq~y NATIONAL RESEARCH COUNCIL CANADA DIVISION OF BUILDING RESEARCH A UNIQUE HOT - BOX COLD - ROOM FACILITY BY W. P. BROWN, K. R. SOLVASON AND A. G. WILSON REPRINTED WITH PERMISSION FROM THE TRANSACTIONS OF THE AMERICAN SOCIETY O F HEATING. REFRIGERATING AND AIR - CONDITIONING ENGINEERS. VOL. 67. 1961. P.561 - 577. RESEARCH PAPER NO. 167 OF THE DIVISION OF BUILDING RESEARCH OTTAWA SEPTEMBER 1962 PRICE 25 CENTS NRC 6887

Upload: others

Post on 16-Sep-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: N21r 2 no. 167 AbJdq~y~~~ c. 2 NATIONAL RESEARCHweb.mit.edu/parmstr/Public/NRCan/rp167.pdf1961. P.561 - 577. RESEARCH PAPER NO. 167 OF THE DIVISION OF BUILDING RESEARCH OTTAWA SEPTEMBER

Se r T H l

N21r 2 no. 167 c . 2

BLDG

A b J d q ~ y ~ ~ ~

NATIONAL RESEARCH COUNCIL CANADA

DIVISION O F BUILDING RESEARCH

A UNIQUE HOT - BOX COLD - ROOM FACILITY

BY

W. P. BROWN, K. R. SOLVASON AND A. G. WILSON

R E P R I N T E D WITH P E R M I S S I O N

FROM T H E

TRANSACTIONS O F THE AMERICAN SOCIETY O F HEATING. REFRIGERATING AND AIR - CONDITIONING ENGINEERS. VOL. 67. 1961. P.561 - 577.

R E S E A R C H PAPER NO. 167

O F THE

DIVISION OF BUILDING RESEARCH

OTTAWA

SEPTEMBER 1962 PRICE 25 C E N T S N R C 6887

Page 2: N21r 2 no. 167 AbJdq~y~~~ c. 2 NATIONAL RESEARCHweb.mit.edu/parmstr/Public/NRCan/rp167.pdf1961. P.561 - 577. RESEARCH PAPER NO. 167 OF THE DIVISION OF BUILDING RESEARCH OTTAWA SEPTEMBER
Page 3: N21r 2 no. 167 AbJdq~y~~~ c. 2 NATIONAL RESEARCHweb.mit.edu/parmstr/Public/NRCan/rp167.pdf1961. P.561 - 577. RESEARCH PAPER NO. 167 OF THE DIVISION OF BUILDING RESEARCH OTTAWA SEPTEMBER

No. 1764

A Unique Hot-Box Cold-Room Facility

W . P . BROWN K . R. SOLj'ASON A. G . WILSON hlember ASEIR.11': hfembrr ASHRrZE

A unique guarded hot box has been designed and built recently by the Division of Building Research of the -National Research Council to be used in conjunction with a large cold room (Fig. 1) for the measure- ment of the heat transmission co- efficients of building sections 4 ft wide and 8 ft high. A section to be tested is incon~orated as Dart

I L

of a partition which separates the cold room into two compartments. The smaller compartment, or warm room. tllen is heated electricallv to maintain a n y desired cons tan t warm side temperature from 65 to 75 F. The larger compartment is refrirerated to maintain the de-

c7

sired constant cold side tempera- ture from 40 to -60 F.

The guarded hot bos (Figs. 2 and 3 ) is positioned against the warm side of the builcline section " and is heated electrically to main- tain u constant temperature. The

W . P. Rro\vn. K . R. Solvnaon nnd A . G . Wilson are u i t h the Building Services Sect . I)iv o f Ruildinv Heuenrch, Nr~tionnl Kesenrch Council of Cnnn<la. This pnl)er wits ~rrennred for vres- entation i ~ t the ASHKAE 68th A n ~ ~ u n l Meeting. Denver. CoIo. June 26-28. 1961 .

heat transmission coefficient is cal- culated from the measured electri- cal i n p ~ ~ t and the temperatures.

The guarded hot box is similar in design to the warm b o x of the large-scale wall heat-flow measur- ing apparatus described in a pre- vious paper.' T h e design over- comes some of the limitations of other methods of detc..rrni!ling hcat transmission coefficients.

The test area of the box is large enough to meter the heat flow into the wllole of represerita- tive sections of building walls. Also building sectiorls mtlc i~ wider than 4 ft can 1)e installed in the cold r txm nartitior? and heat flows measured a t different positions. In this way the effect llpon heat tmns- mission coefficients of non-uniformi- ties in construction can b e studied.

Building sections tested are esposecl on both sides to condi- tions closely simulating those ~ i sed for design calculations. The scc- tion is exposed to controlled tem- perature surroundings as well as to air a t controlled temperature.

Page 4: N21r 2 no. 167 AbJdq~y~~~ c. 2 NATIONAL RESEARCHweb.mit.edu/parmstr/Public/NRCan/rp167.pdf1961. P.561 - 577. RESEARCH PAPER NO. 167 OF THE DIVISION OF BUILDING RESEARCH OTTAWA SEPTEMBER

562 ASHRAE TRANSACTIONS

Air motion on the cold side is rapid and the outside surface con- ductance is realistic. The box is large enough so that the surface conductance at the warm side of the test wall under natural convec- tion conditions approaches that occurring in practice.

The apparatus has been used successfully for the measurement of heat transmission coefficients of several metal skinned curtain walls. Additional tests on uniformlv con- structed walls were made to assess the performance of the apparatus. Studies were made of the inside surface conductance and of errors due to heat leakage through the box walls and at the edges. The apparatus and its operation now are described, together with re- sults of the tests.

Description of cold room-Cooling

in the cold room is provided by a diffuser containing the evaporator of the refrigeration system, past which air is circulated by a blower. The air is discharged horizontally near the ceiling through the supply grille. The grille has vertical ad- justable vanes which distribute the air evenly across the room. The air returns through an opening in the front of the diffuser near the floor.

In operating the cold room under given conditions, the refrig-. eration system is run continuously to provide an almost constant cool- ing effect, which is in excess of that required. Temperature control is achieved by reheating the air by electric heaters after it passes the evaporator. A resistance-element- type recorder and a three-action (proportional + reset + rate) con- troller regulate the amount of re- heat. The air temperature varia-

WARY ROOM

r"c"-T.1 rDI

-.. .

Fig. 1 Plan view of cold room

COLD RWY

C C I L I " I *,OH, - 10 r,.

I,'-,- *

Page 5: N21r 2 no. 167 AbJdq~y~~~ c. 2 NATIONAL RESEARCHweb.mit.edu/parmstr/Public/NRCan/rp167.pdf1961. P.561 - 577. RESEARCH PAPER NO. 167 OF THE DIVISION OF BUILDING RESEARCH OTTAWA SEPTEMBER

tion at any point in the cold room is less than _t 0.1 F. Floor-to-ceil- ing temperature gradients are less than 0.5 F. Air temperature can be controlled anywhere from -60 to 40 F on the cold side of a test wall.

For guarded hot box tests the warm room is heated by electric gravity baseboard convectors lo- cated along the wall opposite the test partition. The input voltage to the convector is regulated by a temperature controller. At the thermostat, air temperatures are controlled to k0.25 F. Air tem- perature gradients depend upon air circulation.

Description of guarded hot box apparatus - This apparatus is a large box mounted on wheels which can be rolled against the warm side of a test wall installed in the cold room partition. The measur- ing area of the box is 4 ft wide and 8 f t high. The depth of the box is 3 ft.

The inside of the box is lined

with aluminum panels (Fig. 4). The panels, which were developed for radiant heating and cooling applications, consist of aluminum extrusions with holders for copper tubing, through which water is circulated. A similar set of panels are installed outside of the inner panels and are separated from them by thermal insulation. When the outer panel is maintained at the same temperature as the inner panel, a guard is formed which prevents heat transfer across the walls of the box. The outside of the guard panel is insulated and sheathed with plywood. The con- tact edge of the box is 34 in. -wide and is formed by w d blm1cing between the inner pznel and an extension of the guard panel.

A water reservoir, pump, and pump motor for circulating water through the tubes of the inner panel are located inside the box. The pump is belt-driven by a series-wound dc motor. The energ./ input to the motor can -be varied from 25 watt (85 Btu/hr) to 3514

Fig. 2 View of guarded hot box in front of cold room

Page 6: N21r 2 no. 167 AbJdq~y~~~ c. 2 NATIONAL RESEARCHweb.mit.edu/parmstr/Public/NRCan/rp167.pdf1961. P.561 - 577. RESEARCH PAPER NO. 167 OF THE DIVISION OF BUILDING RESEARCH OTTAWA SEPTEMBER

564 ASHRAE TRANSACTIONS

watt (1200 Btu/hr) by regulating the voltage to the motor from 15 to 70 volt. The electrical input to the pump is normally sufficient to provide all of the wall transmis- sion; thus the energy i~nparted to the water by the pump serves to heat the panel ancl the energy loss from the motor and drive serves to heat the air directly.

Air heaters and water heaters are provided to supply an addi- tional 150 watt (500 Btu/hr) of energy and to vary the ratio of air heat to panel heat if so desired. The motor, pump, and air heaters which operate a t higher than panel temperature, are surroumtlcd by an additional set of panels through which water is circul;~tecl to pre- vent direct radiant exchange with the test wall surface.

A second reservoir and pump, located outside the box in the warm room, supply liquid (2/3 glycol 4- 1/3 water) to the guard panel. The liquid is continuously cooled by circulating part of it through a sec- tion of finned tubing mounted on the ceiling of the cold side. A hand valve regulates the flow of liquid though the tubing. The reservoir contains an electric heater to con- trol the temperature of the Iiquit~.

Instrumentation and control - The control system for the guarded hot box is shown in block form in Fig. 3. The dc input to the inner pancl pump motor and heaters is sup- pliecl by a 500-watt (100 volt and 5 amp) magnetic amplfier, the out- put pow(:r of which is regulated by a rcsistancc-element-tvne recorder

J L

and current adjusting controller

The controller produces an output signal of 0 to 5 milliamp ancl by manual switching all or part of the signal is applied to the control winding of the magnetic amplifier to regulate its output voltage from approximately 15.to 100 volt or 15 to 70 volt. This, together with re- sistance heaters which can b e con- nected in series with the pump motor, permits regulxtion of the maximum current to 5 amp and power regulation from 25 to 500 watt or 25 to 350 watt.

The rccorclcr has a 10 F span (65 to 75 F) and n sensitivity of 0.01 F or 1)ettcr. Operating records ]lave shown that the inner panel tcrnperature is controllecl to within 0.01 F of set value.

The input voltage ancl current to the inner panel are measured 13y a millivolt recorder connected across appropriate resistors. The

Fig. 3 Schematic cross sec- t ion of apparah~s

Page 7: N21r 2 no. 167 AbJdq~y~~~ c. 2 NATIONAL RESEARCHweb.mit.edu/parmstr/Public/NRCan/rp167.pdf1961. P.561 - 577. RESEARCH PAPER NO. 167 OF THE DIVISION OF BUILDING RESEARCH OTTAWA SEPTEMBER

maximum recorder error, with cali- bration, is Limited to less than k0 .25 per cent of scale span so that by sizing the resistors to g h e larger than half-scale deflection this error is always less than 0.5 per cent.

A filter network on the outnut of the magnetic amplifier li&its ripple voltage to less than 0.75 volt. I t can be shown that the error due to the ac component is negligible for all power inputs. The total error in power measurement is less than 1 . 0 I ~ e r cent.

I

A servo voltage multiplier is being procured so that input power can be recorded directly. This will

Fig. 4 Details of guarded hot box walls and edge

improve the accuracy of measure- ment and will facilitate the deter- mination of average power input.

A differential thermocouple signal is a m p a e d and used to actuate a three-action controller to control guard panel temperature. The controller regulates an elec- tric heater. Heating can be sup- plied continuously on, continuously off or pulsed on-off by the con- troller. The sensitivity of the amplifier-controller arrangement is such that guard panel liquid tem- perature is controlled t o within t 0.05 F or less of inner panel liq- uid temperature a t the respective panel headers.

The rates of circulation are such that the temperature drops through the two panels are very small, less than 0.1 F. Also, the panel to water temperature dif- ference and the temperature varia- tion over the panel surface is less than 0.1 F. It is unlikely, there- fore, that the average temperature difference between the inner and guard panels exceeds 0.05 F.

Temperature measurements are made with 30-gauge copper- constantan thermocouples and an electronic self-balancing tempera- ture indicator. With calibration of the apparatus, temperature differ- ence measurements are accurate to t 0.2 F. This corresponds to an error of + 0.67 per cent a t an over- all temperature difference of 30 F.

Heat leakage - There are two sources of heat leakage in the guarded hot \,ox. Panel heat leak- age, leakage of heat between the guard and inner panels, is caused,

Page 8: N21r 2 no. 167 AbJdq~y~~~ c. 2 NATIONAL RESEARCHweb.mit.edu/parmstr/Public/NRCan/rp167.pdf1961. P.561 - 577. RESEARCH PAPER NO. 167 OF THE DIVISION OF BUILDING RESEARCH OTTAWA SEPTEMBER

566 ASHRAE TRANSACTIONS

by temperature differences between the two panels. Edge heat leakage is lateral heat flow at the junction of the hot box edge construction and test wall which results in an error in metered heat into the test area.

Panel heat leakage-The insul a t' ion between the inner and guard pan- els provides a calculated thermal conductance of 0.18 Btu/hr/sq ft/ (F temperature difference) or a total heat flow of 19 Btu/hr/(F temperature difference). Tests were carried out on a wall of uniform thermal conductance to determine the actual panel heat leakage for a number of guard panel/inner panel temperature differences. The results are shown on Fig. 5. The variation in thermal conductance of 6 per cent per F temperature difference for the test wall denotes a panel heat leakage of 22 Btu/hr/ ( F temperahire difference). With the panel temperatures balanced to i 0 . 0 5 F the actual panel heat leakage is 1.1 Btu/hr as com- pared with the estimated heat leak- age of t 0.9 Btu/hr.

, r ition Edge heat leakage-The p.1 t framework in the cold room is constructed to nccommodate test walls 8 ft ligll with an allowance of 1 in. for clearance a t the top and the bottom. Movable vertical posts can be positioned for various test wall widths.

It is possible to install walls from 4 to 13 ft in width. IVhich width is prcfcrable depends upon thc thermal characteristics of the tcst wall and upon practic'il con- sidcrntions of wall fi1bric:ltion.

With walls having modules other than 12, 16 or 24 in. for example, it may be desirable to have a test wall wider than 4 ft and to make tests a t more than one position, in order to determine the effect of joints or other discontinuities on the thermal coefficients.

Fig. 6 shows the two edge ar- rangements that have been used for guarded hot box tests to date. Arrangement A is used at the top and bottom of all test walls and at the sides of test walls which are 4 ft wide. The test wall is sepa- rated from the surrounding parti- tion hy a l-in. thickness of rigid insulation. The wall is held in place in the partition by compres- sion. All possiblc sources of mass transfer into or out of the box are sealed with either caulking coin- pound or tape. Arrangement B is ~ i s ed at the vertical cdgcs of walls wider than 4 ft. Strips of rigid in- sulation 1 in. thick are caulked and taped in place vertically on the test wall. In both arrangements the contact edge of the box is

Fig. 5 Variation of meas- ured thermal conductance with inner panel-guard panel temperature difference

0 1 1 0 I -2[0 -10 0 110 . 2 0 .10

I I I - - G U A R D '1UCl C O L O E I W l l O PANEL W A l l Y T R - ~ - C

I N N E R PnUEL - G V A R O ?..EL T E L P L R A T U I I E D V r l P f U C E - F

Page 9: N21r 2 no. 167 AbJdq~y~~~ c. 2 NATIONAL RESEARCHweb.mit.edu/parmstr/Public/NRCan/rp167.pdf1961. P.561 - 577. RESEARCH PAPER NO. 167 OF THE DIVISION OF BUILDING RESEARCH OTTAWA SEPTEMBER

clamped against the protruding air temperature at the top edge is edge of the insulation. The box is about 2.5 F higher than that at the sealed to the edge of the insulation bottom edge, with a warm side/ with tape. cold side temperature difference of

whichever edge anangement 70 F. The air temperature gradi- is Llsed, tile edge heat leakage ent in the warm room around the error is a function of the average eclge of the guarded hot I)'" is air temprature difrerence across similiar to that in the hot box. the edge. In Fig. 7 measured This is achieved despite the thermal conductance is plotted confining effect of the hot box edge against warm room air/guarded construction hy providing gentle hot box air temperature difference forced circulation with a propellor for several test walls. The box air fan, which is directed to supple- temperature is the average air tern- ment the n;ituraI air motion in the perature 3 in. from the test w:ill warm room induced hy the 1)asc-

and the warn, room ;lir lmard convector on the wall oppo- temperature is the average air tern- site the test specimen. perahre surrounding the guarded ~ 1 1 test walls sl,c,w a hot box edge, measured with thrr- measllred mocouples. thermal conductance with air tem-

There is a vertical air tcm- perature diffcrencc between hot A

perature gradient in thc hot 1 ~ ) s box and warm room. The degree dependent on the heat flow through of variation del3ends on test wall the test wall. For walls of thermal constr~~ction and on thc ?pe of conductance about 0.15 Btu/hr/sq edge arrangement that is used. f t / (F temperature difference), tlln \Valls 1 and 3 of Fig. 7 are almost

Fig. 6 Typical guarded hot box- test wall edge contact arrangements

1 K 6 RIGID MSUIATIOH

; :

ARRANGEMENT A TEST WALL WIDTH = 4 FT

- T E S T WALL

RIGID IHSlLATlOH

CAULKING COMPOUND

- INSULATION TAPED

INSULATION

ARRANGEMENT B

T E S T WALL WIDTH > 4 F T

Page 10: N21r 2 no. 167 AbJdq~y~~~ c. 2 NATIONAL RESEARCHweb.mit.edu/parmstr/Public/NRCan/rp167.pdf1961. P.561 - 577. RESEARCH PAPER NO. 167 OF THE DIVISION OF BUILDING RESEARCH OTTAWA SEPTEMBER

568 ASHRAE TRANSACTIONS

identical curtain walls. Wall 1 was 4 ft wide and edge arrangement A was used at the vertical edges. Wall 2 was 8 ft wide and edqe arrangement R was used at the vertical edges. The metal skin pro- vided a highly conductive heat transfer path across edge arrange- ment B. Consequently, the lateral heat transfer or edge heat leakage across edge arrangement R was greater than the lateral heat trans- fer across edge arrangement A for a given air temperature difference.

Wall 3 of Fig. 7 is an 8- by

8-ft test wall of uniform thennal conductance. At position 1, edge arrangement A was used at one vertical edge and edge arrange- ment B at the other. At position 2, edge arrangement B was used at both vertical edges. The edge heat leakage a t position 2 was greater than the edge heat leakage a t position 1 for the same air tem- perature difference, since the re- sistance to lateral heat flow through the plywood surface in edge ar- rangement B was less than through the perimeter insulation in edge

Fig. 7 Variation of measured thermal conductance with room air-box air temperature difference

0 . 2 0 0 ' I OUTER SHEET, IS 16 GA ALUMINUM

LL - /-. + LL

INNER SHEET IS 18 G GALVANIZED S T E E L g 0 ' 1 8 0 -

V - I

WALL 1 , 4 F T WlDE COLD ROOM TEMP, D'F

V

m

0.150

W U

z u

0 . 1 4 0 - 0

o U

A

a 0 I 3 0

W I +

0. I 2 0

- C ROOM COLDER ROOM WARMER -+

ROOM AIR -BOX AIR T E M P E R A T U R E DIFFERENCE - O F

- \ \ \ \

'\,\\,

\

\ \ \ , \ '

\ \, -

-

WALL 2, 8 F T WlDE COLD ROOM TEMP, +5'F

2" INSULATION

\ \ \, WALL 3 \ COLD ROOM

\ + 3 0 F

\ \ TEMPERATURE I/?' PLYWOOD

\ O F

\\ - 3 0 F

- P O S I T I O N I ARRANGEMENTS A 8 8

---- V E R T I C A L EOGES

I 10 0 + 10

Page 11: N21r 2 no. 167 AbJdq~y~~~ c. 2 NATIONAL RESEARCHweb.mit.edu/parmstr/Public/NRCan/rp167.pdf1961. P.561 - 577. RESEARCH PAPER NO. 167 OF THE DIVISION OF BUILDING RESEARCH OTTAWA SEPTEMBER

arrangement A. the surface temperature 5 in. from With the warm room air tern- the edge was unaffected by the

perature substantially higher than edge heat exchange. The distortion the box air temperature, the edge of the surface temperature pattern heat leakage results in a decreax from this point to the edge at in metered heat flow into the test equal warm room and hot box area and vice versa. It would be temperatures was quite small, ex- desirable if there were no lateral cept at the junction of the speci- heat flow at the edges of the test men and perimeter insulation; edge section with hot box and warm heat leakage resulted in an increase room at the same temperature. The in heat flow at the inner surface surface temperature Pattern at the in both edge arrangements. Similar edge would then be unaffected by measurements indicated a corn- the Presence of the box and con- parable increase in heat flow at the ditions would be ideal for measur- top edge and perhaps a small de- ing a correct value of thermal con- crease in heat flow at the b t t o m ductance. edge with equal average warm

Fig, room and hot box air temperatures. tures measured a t the vertical edges To assess the error due to edge of wall 3 with different warm room heat leakage a relaxation calcula- air temperatures for both edge ar- tion2 was carried out for a homo- rangements A and B. At geneous wall with edge arrange- values of hot box/wam room air merit A. section studied is temperature difference to F, shown in Fig. 9 a,ong with the

temp~rature distribution obtained. The calculation has been made for

Fig. 8 Edge surface tern- equal air temperature in warm perntures room and hot box and equal sur-

face conductances. This latter as- sumption can be shown to be rea- sonably valid for the air and sur- face temperature conditions shown for edge arrangement B in Fig. 8 and therefore also for edge ar- rangement A. I t has also been assumed that the surface of the

EDGE ARR~NGEMENT A edge insulation in contact with the r -z.RIGID IHSULIlTlOH

r2-T% 3 J ' 7 , pLywoDD hot ~ H ) X is at hot box temperature. I I

t I 1 , i There is distortion of the iso- - x therms a t the edge of the specimen

primarily as a result of two factors.

EAL 7 3 0 ~*-4-07 6 f o T ~ First, the temperature gradient in LOGE 6 r T 71 6 6 4 6 1 6 1 0 6 3 9 6 4 0 X I 2 bu BOTTOY 6 8 6 _ 6 2 6 6 l 4 1 6 4 0 ! 5.0; 1 0 6 1 the adjacent construction is differ-

E W E A R R ~ G E M E N T B ent from that in the specimen

r r \ ln TLYPERATLRES x SURFACE TLYPLRATURLS

result of the greater thickness and

Page 12: N21r 2 no. 167 AbJdq~y~~~ c. 2 NATIONAL RESEARCHweb.mit.edu/parmstr/Public/NRCan/rp167.pdf1961. P.561 - 577. RESEARCH PAPER NO. 167 OF THE DIVISION OF BUILDING RESEARCH OTTAWA SEPTEMBER

570 ASHRAE TRANSACTIONS

thermal resistance of the former. Consequently, all p i n t s through the depth of the specimen tend to he at a slightly higher temperature at the edge than at similar loca- tions removed from the edge with a resulting tendency for lateral heat flow into the test section. Counteracting this is the effect of the projection of the edge insula- tion on the warm side which tends to lower temneratures at the ad- jacent inner s'urface of the speci- men. The net effect is a small in- crease in metered heat flow from the hot box into the test area of the spe~imen.

The increased heat flow at the ctlge of the specimen for arrange- ~nent A, as determined from the assumed inside surface conduct- ance and the calculated surface temptratures in Fig. 9 represents 0.3 per cent of the total heat flow

into the test area. p n the other hand, the heat floy from the hot 11ox into the edge,insulation is 2.7 per cent of the tfial heat flow into the test area. The calculation thus indicates that with the hot box and the warm room air tempera- tures balanced, the error in meas- ured thermal conductance due to edge heat leakage is + 3 per cent. This is confirmed by the calculated value of thermal conductance f m the test wall, based on measured values of conductivity for the insu- lation and published values of thermal conductance for plywood, which is 3 to 4 per cent lower than the value obtained in the guarded hot h x .

N o rel'isation calculation has heen made of the eclge heat leak- age error for edge arrangcment 13. The isotherm pattern, which can he visualized hy reference to that

Fig. 9 Temperature distribution at edge arrangement A

Page 13: N21r 2 no. 167 AbJdq~y~~~ c. 2 NATIONAL RESEARCHweb.mit.edu/parmstr/Public/NRCan/rp167.pdf1961. P.561 - 577. RESEARCH PAPER NO. 167 OF THE DIVISION OF BUILDING RESEARCH OTTAWA SEPTEMBER

for arrangement A in Fig. 9, will be affected only by the l-in. square strip of edge insulation and will be symmetrical about it. The dis- tortion of the isotherms at the inner surface of the specimen ad- jacent to the edge will be similar to that in Fig. 9 but slightly more pronounced, since there will not be the counteracting effect of the thicker edge construction. Thus. < 2

for thin walls at least, the error due to edge heat leakage with warm room and hot box air temperatures 1,alanced is likely to be slightly greater. This is confirmed by the results in Fig. 7, which for wall 3 shows slightly higher values of thermal conductance at balance with arrangement B at both verti- - cal edges.

The error due to edge heat leakage can he minimized by rv- ducing the projection of the edge insulation from the inner surface of thc test specimen. Ideally, this shoultl approximate the inside sur- face cvnductance of the spPcimen, which would be achieved with about 54 -in. thickness. The project- ing insulation acts as a gxsket to overcome irregularities in the

c 7

planencss of the wall specimen. Thc l-in. proj(>ction w a chosen to facilitate. sc; i l in~ of the box with

0

tam. Altcmative methtds of seal- ing the 1)ox to the spt~imc,n \vhich will permit ;i smaller projection of the edge insulation arc being con- sidcrtd. This is c ~ s r x ~ t c ~ d to rcducc errors diic to edge licat Icakagc. to negligi1,le proportions ;it cclual hot hos and warm room air tcn11x.r:l-

I

turcs. Flirthcr invc.stigations of trlgcb brat Icakagc arc plannctl rt.l;itive to tllc cffcvt of diffvrcnt

surface conductances and air tem- peratures with various wall con- structions and edge arrangements. It is thought that the resistance " paper analog might be adapted for this study. I t will be recognized that edge heat leakage is equally a problem with the traditional guarded hot box."

WARM SURFACE HEAT EXCHANGE

H e a t t r a n s f e r character is t ics of wall cons t ruct ions usually a r e specified 01.

compared on the basis of t h e thermal t ransmit tance coefficients o r U values, which include the su r f ace conduct- ances. S ince the surface conductance is a function of surrounding condi- t ions, i t i s necessary to u s e s tandard values. I n the A S H R A E GUIDE in- s ide surface conductances are based on natul ,al convection, w i th a i r ant1 surroundings a t t h e s a m e tempera- ture. I n the tradit ional guarded hot box, forced convection is proritieti, so t h a t the inside surface conductances a r e usual ly much h ighe r than those f o r na tu ra l convection. I t is neces- s a ry , therefore , to base t h e thermal conductance of the wall on measured surface tem[!eratures and t o compute t he U value , in corpora tin^ the stantl- a r d inside surface conductance.

T h e inside surface tempera ture dis- tr ibution and therefore t h e thermal conductance of non-uniform walls i s affected by the inside s u r f a c e conduct- ance. T h u s the t he rma l conductance obtained wi th forced convection on t h e inside m a y differ somewha t from t h a t f o r na tu ra l convection. Fu r th r rmore . i t i s somet imes dificult to establish a n app ropr i a t e average surface-to-sur- f ace tempera ture difference by direct measurement fo r t h e determin;ition of t he rma l conductance of non-unifomm walls because of t h e variations in su r - f ace tempera ture .

I t is therefore d e s i r a t ~ l e in heat flow measurements t o provide surfrtccl conductances closely app rox ima t in s s t anda rd \.slues used f o r c;~lculatinr: U values and to know t h e surf;ice h e a t c schange characterist ics of the al)- p a r a t u s ~ ~ r e c i s c ~ l y , in o rde r to facili- t a t e t h c tieteimination of thermal conduckinc.e.

Page 14: N21r 2 no. 167 AbJdq~y~~~ c. 2 NATIONAL RESEARCHweb.mit.edu/parmstr/Public/NRCan/rp167.pdf1961. P.561 - 577. RESEARCH PAPER NO. 167 OF THE DIVISION OF BUILDING RESEARCH OTTAWA SEPTEMBER

572 ASHRAE TRANSACTIONS

The total heat exchange between a test wall surface and the guarded hot box is the sum of the convection ex- change between the surface and the box air and the radiation exchange between the surface and the box inner panel surface.

qt = qr f qc (1) In a grey enclosure, such a s the

guarded hot box, the radiation ex- change' is:

qr F,, , (Tt - Tx4) (2) For one source (guarded hot box) and one sink surface (test wall) and no interconnecting surfaces, i t can be shown tha t

1

The radiation component can also be accounted for by the following:

q r = h r (t,-t,) where

(4)

guarded hot box tests, the error in using equation (6) is less than 0.05 per cent.

The heat transfer between the a i r in the guarded hot box and test wall surface is by natural convection. The convective movements are brought about solely by differences of density caused by differences of temperature. Natural convection can be expressed in dimensionless terms by relating the Nusselt, Grashof and Prandtl numbers a s follows'

Nu = x (Gr Pr ) '

The constants x and y are evaluated from experimental data . The equa- tion can be applied to all tests in the guarded hot box provided that the

(T: - TW4) geometry of the system remains the h , = F , , o (5)

same and (Gr P r ) lies within the

(TP-Tw) range of conditions used in the orig- inal evaluation of the constants.

Equation (5) can be approximated by The bulk temperature of the fluid, the following: well away from t h e surface, is used in

h, = 4 F,, a (T,)' the determination of t h e temperature (6) difference (t. - t,). The values of

For the range of conditions in the the physical constants C,, p, k, and P

Fig. 10 Heat exchange in guarded hot box by natural convection

I : I l l ! ;

rr 4 1 8 F T WALL

2 6 - 8 I 8 F T WALL

Page 15: N21r 2 no. 167 AbJdq~y~~~ c. 2 NATIONAL RESEARCHweb.mit.edu/parmstr/Public/NRCan/rp167.pdf1961. P.561 - 577. RESEARCH PAPER NO. 167 OF THE DIVISION OF BUILDING RESEARCH OTTAWA SEPTEMBER

are taken a t the arithmetic mean tem- perature of surface and bulk fluid. The height of the wall surface is taken a s the characteristic linear dimension, L.

Because the temperature range in the guarded hot box tests is small, the physical properties of a i r may .be regarded a s constants. Equation (7 j can therefore be simplified to:

h. = x' (t . - t,-)" (8) where

The heat flow rate due to convec- tion is:

q c = h, (t. - t,,) (10) The total heat flow rate from equa- tions ( I ) , (4) and (10) is

Combining h, and h, to form the usual surface conductance f~ and defining a n equivalent temperature t ~ , equation (11) becomes:

q1 = f , (tl - t , ) (12) The equivalent temperature, tl, is the temperature of a i r and panel surface which would produce the same total heat flow ra te a s t, and t, and is cal- culated from equations (11) and (12)'.

hr t, + hc t, t l = (13)

hr + h,

For a test on a wall of uniform con- ductance where it is possible to meas- ure the average surface tempel-ature, t,., accurately, q, can be readily cal- culated from equation (2) . knowing the emissivities and interchange fac- tor. Since q, is accurately measured, q, and hence I?, can be determined from equations (1 ) and (10). A num- ber of values of h, can be obtained from tests a t a number of different total heat flow rates. The dimen- sionless groups from equation ( 7 ) can then be evaluated for each of the tests and the constants x and y de- termined by correlation.

The following three series of tests were carried out with the guarded hot

box to evaluate the convection con- stants: 1. Tests a t different total heat flow

rates on a uniform 4- b y 8-ft wall painted flat white (e, = e, = 0.87)

2. Tests a t different total heat flow rates on same wall a s above but covered with aluminum foil (e, = 0.87, e, = 0.05)

3. Tests a t different total heat flow rates on a uniform 8- by 8-ft wall painted flat white (e, = e, = 0.87)

The total hemispherical emissivities quoted were estimated f rom the meas- ured-otal normal emissivities. F o r this purpose the total hemispherical emissivity was taken a s 0.95 and 1.15 of the total normal emissivity for non- conductive and conductive surfaces, re- spectively'. The over-all interchange factors were calculated f rom equation (3). F o r all tests A, = 32 sq f t , A, = 137 sq f t for series 1 and 2 and 153 sq f t fo r series 3. The change in box surface area was due to extensive modifications carried ou t between series 2 and 3 tests. Average air and surface temperatures were measured with thermocouples. The temperature of the inner panel circu!ating fluid was taken as the average tempera- ture of the inner surface of the guard- ed hot box. All a i r properties were taken from reference 8.

The test results a re shown plotttd in Fig. 10. Curves f rom Fishenden and Saunders also a re given. There is substantial disagreement betweer: the results for the high and low emis- sivity surfaces. F o r t!lis reason t?le results f o r each were correlated sepa- rately by the method of least squares. The analysis indicated t h a t convec- tion to the test wall surfaces may be represented by the following equa- tions:

For e, = e, = 0.87

For e, = 0.05, e, - 0.87 Nu = 0.42 (Gr Pr)'.= (15)

Considering air properties as belng constant the equations can be simpli- fied to t h e form of equation (8) as follows:

F o r e, = e, = 0.87

h, 0.29 (L - t,.)O.'" (16)

Page 16: N21r 2 no. 167 AbJdq~y~~~ c. 2 NATIONAL RESEARCHweb.mit.edu/parmstr/Public/NRCan/rp167.pdf1961. P.561 - 577. RESEARCH PAPER NO. 167 OF THE DIVISION OF BUILDING RESEARCH OTTAWA SEPTEMBER

574 ASHRAE TRANSACTIONS

The difference in the ra te of convec- tion heat exchange for the high and low emissivity surfaces can be ex- plained by reference to the various heat exchanges taking place in the guarded hot box, shown in Fig. 11. A summation of the heat exchanges gives:

hence

Test results show that the panel sur- face t o a i r temperature difference (t, - t.) is quite small. Furthermore, a t equal a i r to wall surface tempera- ture difference ( t - t ,) , the differ- ence between (b - t ) f o r the high and low emissivity wall surface is negligible. I t can be seen from equa- tion (19), therefore, that the differ- ence in the convection exchange, q,, a t equal values of (Gr P r ) fo r the high and low emissivity wall surfaces is due to differences in the motor loss ql. Since the motor loss increases with increasing total heat input, q, In- creases proportionately. The increased radiation exchange to the high emis- sivity surface requires a larger total heat input. The convection heat rate, q,, is therefore larger for the high emissivity surface.

The equation to be used for the cal- culation of the convective component of the surface conductance therefore depends upon test wall emissivity. The two equations determined here correspond to the extremes of surface emissivity likely to be encountered in guarded hot box tests.

The convection equations compare favorably with the recommended equation for turbulent flow on vertical free plates (curve A Fig. 10). This is expected since turbulence is known to set in a t (Gr P r ) about 10' although a t values of 1 0 9 0 10" it is still fully developed only a t the upper parts of the surface. I t is thought that the over-all effect of the boundaries is to reduce the convection heat transfer below that expected on a free plate of the same dimensions. This is offset, however, by the presence of the pump motor, which increases the convection heat transfer by increasing circula- tion.

Equations ( 6 ) , (16) and (17) are used in calculating surface contluct- ances fo r guarded hot box tests.

Where the wall surface emissivity falls between values f o r which the convection equations a r e valid, the surface can usually be painted to provide an emissivity approximately equal to 0.87. These equations can also be used to determine an average surface temperature f o r non-uniform walls from which a wall thermal con- ductance can be calculated. Rear- ranging equation (11) gives

from which t, can be obtained by trial and error.

The surface conductances provided in the hot box tests compare favor- ably with those recommended by t h e ASHRAE GUIDED f o r purposes of computation. F o r a surface of emis- sivity 0.90 and temperature 70 F fat- ing surroundings having a n emissivity of 0.90 and a t the same temperature a s the ambient air, the GUIDE recom- mends a combined surface conduct- ance of 1.46 based on a surface-air temperature difference of 10 F. F o r the same conditions the surface con- ductance with the guarded hot box is 1.45.

Fig. 11 H e a t exchange in guarded hot box

TEST WALL

- C q ~ = q , + 9 c

Page 17: N21r 2 no. 167 AbJdq~y~~~ c. 2 NATIONAL RESEARCHweb.mit.edu/parmstr/Public/NRCan/rp167.pdf1961. P.561 - 577. RESEARCH PAPER NO. 167 OF THE DIVISION OF BUILDING RESEARCH OTTAWA SEPTEMBER

COLD SURFACE HEAT transmittance coefficient for such EXCHANGE walls is therefore between + 0.2,

Forced convection is provided in the per cent and + 5.8 per cent. Alter- cold room by a i r movement inducetl native of sealing the box by the diffuser fans. Each fan motor has three s p e d settings and the total to the wall specimen which will a i r discharge ra te can be varied fronl largely eliminate edge heat leak- 2800 to 11,400 cfm in six steps. The discharge rate decreases slightly with error are being considered. frost build-up on the evaporator coils. The total percentage error will de- Tests on smooth-surface uniform crease as the temperature difference walls with emissivity equal to 0.9 have shown that outside surface con- between hot and ductance, f,, varies between 3 a n d 4 increases or as the thermal con- with the main diffuser f a n operating ductance of the wall increases. a t high speed.

The variation in surface conduct- The error in measuring ther- ance with heat flow, temperature level mal conductance depends on the and wall emissivity is rather small reliability with which an appro- since the heat transfer is mainly by forced convection. Calculations f o r a P i a t e average surface temperature typical wall show that the radiant can be measured or estimated. component of the surface heat ex- Operation indicates that heat trans- change may vary from 0.4 to 0.75 for a wall of 0.9 emissivity and from 0.1 m i ~ ~ i 0 n coefficients Can be repro- to 0.2 for a wall of 0.25 emissivity as duced within 1.0 per cent. the cold room temperature varies from The temperature of the inside - 4 0 to 40 F. surface of the hot box is under

CONCLUSION

It has been shown that heat flo\v through any 4- by 8-ft section of test walls up to 12, ft in length can be metered reliably with the guarded hot-box cold -room ar- rangement described in this paper. The total error in determination of thermal transmittance coefficients depends upon test conditions and on wall thermal conductance. For a wall of U value 0.1 Btu/hr/sq ft/ F at a temperature difference of 30 F the total of panel heat leak- age, control and measurement errors, if additive, is + 2.8 per cent. The edge heat leakage error de- pends upon wall construction and edge arrangement. For thin wall sections with the edge configura- tion used to date it is about + D per cent.

The error in measured thermal

direct control. This makes it pos- sible to operate the box under con- ditions of natural convection with- out excessive vertical air tempera- ture gradients and to exercise some control over the relationship be- tween box surface and air tem- perature. With energy supplied only to the pump motor the air temperature has been generally within ?h F of the box surface tem- perature in tests on typical walls.

Relationships describing the radiant and convective components of the inside surface conductance, applicable to most walls, have been determined for the box. These relationships can also be used to determine an average inside sur- face temperature for non-uniform walls from which a wall thermal conductance can be calculated. The inside surface conductances provided 1)y the box are similar to

Page 18: N21r 2 no. 167 AbJdq~y~~~ c. 2 NATIONAL RESEARCHweb.mit.edu/parmstr/Public/NRCan/rp167.pdf1961. P.561 - 577. RESEARCH PAPER NO. 167 OF THE DIVISION OF BUILDING RESEARCH OTTAWA SEPTEMBER

576 ASHRAE TRANSACTIONS

those that occur in practice under natural convection conditions. Real- istic outside surface conductances can be provided in the cold room.

ACKNOWLEDGMENTS

The authors wish to thank Dr. D. G. Stephenson for his advice in connec- tion with the relaxation calculation. The contributions of Dr. N. B. Hutch- eon, Assistant Director of the Div of Building Research, in the planning of the facility a r e gratefully acknowl- edged. This is a contribution from the Div of Building Research, Na- tional Research Council, Canada, and is published with the approval of the Director of the Div.

NOMENCLATURE

A = area of a surface, sq f t A,,, inside surface of guarded hot box .4,, surface of test wall

C = thermal conductance, Btu per ( h r ) ( sq f t ) ( F temp diff)

C,= specific heat of a i r a t con- s tant pressure, Btu per (Ib) ( F )

e = total hemispherical emissiv- ity of a surface, dimension- less e,, inside surface of guarded hot box e , ~ , surface of test wall

f = combined surface film con- ductance, Btu per ( h r ) (sq f t ) ( F temp diff) f , , warm surface; f,, cold surface

F., = over-all interchange factor for radiation from test wall to guarded hot box, dimen- sionless

g = local acceleration of gravity, f t per (sec')

Gr = Grashof number, /3 g p' L' (t. - t,)/p2, dimensionless

h = surface conductance, Btu per ( h r ) (sq f t ) ( F temp diff) h... convection; h,, radiation

k = thermal conductivity of air, I3tu per ( h r ) (sq f t ) ( F pcr f t of thickness)

K = thermal conductivity, Btu per ( h r ) (sq Tt) ( F per in. of thickness)

L = characteristic linear dimen- sion for convection, f t

Nu = Nusselt number, h, L/k, di- mensionless

P r = Prandtl number, p C,/k, di- mensionless

q = heat flow rate, Btu per ( h r ) (sq f t ) q,, convection heat exchange

between box air and test wall surface

q',, convection heat exchange between box inner panel surface and box a i r

q ~ , convection heat exchange between box motor and box a i r

q,, radiation hea t exchange between box inner panel surface and test wall sur - face

q,, total heat exchange be- tween box and test wall, also equal to total heat input to box

T = absolute temperature, X (deg) T., average a i r temperature

in guarded hot box T,, average temperature of

inner panel surface of guarded hot box

T,, average temperature of test wall surface

T,, mean temperature be- tween inner panel surface and test wall surface

t - temperature, F (deg) t., average a i r temperature

in guarded hot box t , , temperature equivalent tu

t, and t. t,., average a i r temperature

in cold room t,, average temperature of

inner panel surface of guarded hot box

t., , average temperature of test wall surface

U = thermal transmittance, Btu per ( h r ) (sq f t ) ( F tern11 diff)

x, x', y = constants

Page 19: N21r 2 no. 167 AbJdq~y~~~ c. 2 NATIONAL RESEARCHweb.mit.edu/parmstr/Public/NRCan/rp167.pdf1961. P.561 - 577. RESEARCH PAPER NO. 167 OF THE DIVISION OF BUILDING RESEARCH OTTAWA SEPTEMBER

Greek Le t t e r s p - coefficient of thermal expan-

sion of a i r , l/T, p e r R a = Stefan-Boltzmann constant

0.1712 X 10.' Btu pe r ( h r ) ( s q f t ) (R) '

p = dynamic viscosity of a i r , Ib p e r ( h r ) ( f t )

p = m a s s dens i ty of a i r , s l ugs pe r ( f t ) '

BIBLIOGRAPHY ' Lt~rpe-Scxle Wall Heat-Flow Measuring AD- ptlmtus. I(. R. Solvason. (ASHHAE Transac- tions. Val. 65. 1969. p. 5.11-560).

Relaxation Methods, D. Allan. (McGra\v-Hill, New York. 1954). ' Method of Tes t for Thermal Conductance ant1 T r a n s n i i t t a n c ~ nf Built-url Sections 1.y Means oE the Guarded Hot Box. ASTM Designation C236- K A T

' Heat Transmission. W. H. McAdams. (Mc- Graw-Hill. New York. 1954. 1,. 7 2 ) . 6 H e a t T r a n s f e r , M. ?ishenden and 0. A. Saunders. (Oxford U n ~ v e r s i t y Press . London, 1950, D. 89) . ' Method of Test for Normal Tota l Emittance >f Surfaces of Materials 0.01 in. or less i n rhickness a t Approximately Room T e r n ~ ~ r i ~ t u r e . ASTM Designation C415-59T. ' Measurement of Angular Emissivity, A. Umur , G. V. Parrnelee and L. F. Schutrum (ASHAE Transactions. Val. 61. 1955, D. 111). 8 Tables of Thermal Pronert ies of (;aspa (Na- tional Bureau of Standards, C ~ r ~ u l a r 561; 1955). O A S H R A E GUIDE. 1960, D. 108.