Page 1: MV circuit breaker for outdoor installation GI-E Range · A new path for achieving your electrical installations A comprehensive offer The GI-E range is part of a comprehensive offer

MV circuit breaker for outdoor installation

GI-E Range

Catalogue

2008

Page 2: MV circuit breaker for outdoor installation GI-E Range · A new path for achieving your electrical installations A comprehensive offer The GI-E range is part of a comprehensive offer

A new path for achieving your electrical installations

A comprehensive offer

The GI-E range is part of a comprehensive offer of products that are perfectly coordinated to meet all medium and low voltage electrical distribution requirements. All of these products have been designed to work together: electrical, mechanical and communication compatibility.The electrical installation is thus both optimised and has improved performance:b better service continuity,b increased personnel and equipment safety,b guaranteed upgradeability,b efficient monitoring and control.You therefore have all the advantages at hand in terms of know-how and creativity for achieving optimised, safe, upgradeable and compliant installations.

Tools for facilitating the design and installation

With Schneider Electric, you have a complete range of tools to help you get to know and install the products whilst complying with current standards and good working practices. These tools, technical sheets and guides, design software, training courses, etc. are regularly updated.

For a real partnership with you

A universal solution doesn’t exist because each electrical installation is specific. The variety of combinations on offer allows you to truly customise the technical solutions.You are able to express your creativity and put your know-how to best advantage when designing, manufacturing and exploiting an electrical installation.

Schneider Electric is associating itself with your know-how and your creativity to produce optimised, safe, upgradeable and compliant installations

Page 3: MV circuit breaker for outdoor installation GI-E Range · A new path for achieving your electrical installations A comprehensive offer The GI-E range is part of a comprehensive offer

1

Contents

pagesGeneral presentation 2

Application 2Description 2Sulphur hexafluoride gas (SF6) properties 2Advantages 3Tests 4Safety 4Reliability/Service continuity 5Quality assurance 5Standards 5

Rating 6Principle of interruption and pole sectional view 7Operating mechanism 8Sepam 10

Metering and protection unit 10Selection table 11

Current and voltage transformers 12General presentation 12

Wiring diagram 14Accessories and ratings of auxiliaries 16Overall dimensions 18

Outdoor circuit breaker GI-E type “A” 18Outdoor circuit breaker GI-E type “B” 19

Packing 20Installation and commissioning 21Order form 22Environment 23

Preserving the environment 23

PE

6023

3

GI-E Range

Page 4: MV circuit breaker for outdoor installation GI-E Range · A new path for achieving your electrical installations A comprehensive offer The GI-E range is part of a comprehensive offer

2

DE

6032

9General presentation

ApplicationThe SF6 outdoor circuit breakers GI-E range are particularly suitable for the followingapplications:b protection of distribution system up to 40.5 kVb protection of transformersb switching of capacitor banksb protection of distribution network characterized by severe conditions of Transient Recovery Voltage, largely exceeding the IEC requirements.

Descriptionb SF6 gas (Sulphur Exafluoride Gas) is utilized in the oudoor circuit breakers GI-E range, for the switching and for the insulation purpose.b The interrupting system using SF6 gas as medium of interruption is the “puffer type”; it is the same system utilized in all the extra high voltage circuit breakers benefiting of the large experience accumulated by our group, in this field, since years 60’s.b The breaking chambers of the three poles SF6 gas circuit breakers, GI-E range, are mounted inside porcelain insulators. They have long creepage distance which gets the circuit breaker suitable for installation in areas with high degree of environmental pollution too.b Every pole is filled with SF6 gas at the rated pressure of 400 kPa gauge, referred to 20° C.The monitoring of the pressure of SF6 gas is achieved by using pressure switches mounted in the lower part of the poles. The pressure switches are complete with contacts and in case of low pressure, they are suitable to initiate:v An alarm circuit (first pressure switch contact).v The electrical block circuit of both closing and opening operations or the block of any further electrical operations after the automatic opening of the circuit breaker (second pressure switch contact).b The three poles are mounted on a base frame hot dip galvanised and operated by a common three pole spring motorcharged operating mechanism which is housed in a box having very high degree of protection.b Option for integrated measuring protection facilities and/or instrument transformers.

Sulphur hexafluoride gas (SF6) propertiesb Sulphur hezafluoride gas has been used in the medium voltage and high voltage electrical switchgears for more than 30 years for its excellent properties and even more for its remarkable characteristics as a medium of interruption of an electric arc.This gas combines the following main properties:v high and rapid heat evacuation capacity by convection of the heat originated by the switching of the arc;v high radial thermal conductivity near zero current which allows the cooling of the arc;v high electron captation capacity as the very high electronegativity of the fluorine atoms, at the passage through zero current, captures the free electrons which are responsible for the electrical conduction.b Several millions of different types of units using the SF6 gas as a medium of insulation and interruption are estimated to be currently in service troughout the world.They are operating with full end-users satisfaction.v Techniques of interruption using SF6 gas usually do not originate any switching overvoltages and restrikes of the electric arc, assuring the blow out at the first zero current.b SF6 is an insulating gas offering at low pressure too, very high dielectric strength. At atmospheric pressure its dielectric strength is 2.5 times higher than air.b SF6 is an inert gas, non toxic, very stable and flame proof.b The possible presence of humidity in SF6 gas and the minimum quantity of decomposition products originated by the arc are absorbed by molecular sieves.v The general properties of new SF6 are described in IEC 60376 section 2, while safety aspects, basic information and guidelines for working with SF6 are covered by IEC 61634.For additional information about SF6 gas characteristics, end-users can refer to the above mentioned standards.

GI-E Range

Page 5: MV circuit breaker for outdoor installation GI-E Range · A new path for achieving your electrical installations A comprehensive offer The GI-E range is part of a comprehensive offer

3

Advantagesb The breaking techniqueThe range of the GI-E circuit breakers consists of modern switchgears in which the well proven experience with the sulphur hezafluoride puffer type technology has allowed the design of breaking chambers characterized by optimised injection of gas SF6.

b No overvoltagesThe intrinsic properties of the SF6 gas associated with the own characteristics of the “puffer type” breaking technique do not originate re-strikes and harmful overvoltages.

b Steady monitoring of the “dielectric”SF6 gas pressure monitoring device on each pole (pressure switch with contacts) allow the steady remote control of the insulating medium.

b Insensitiveness to the environmentThe GI-E pole-unit provides a completely sealed system. It consists of an hermetically sealed gas tight enclosure filled with SF6 gas. Therefore the live parts of the circuit breaker are completely unaffected by any external environmental condition.

b Easy installationThe modular design of simple and modern conception allows to perform on site and within few hours the installation, the general verification foreseen after the assembly and the commissioning test.

b Long electrical lifeThe limited energy originated by the electrical arc, (its own characteristic of the puffer type technique of interruption) combined with the negligible deterioration of the chemical properties of the SF6 gas allows to limit the wear of the main contacts, getting the circuit breaker suitable for a service life over 20 years.

b Long mechanical lifeThe spring motorcharged operating mechanism serie GMh, utilized in the circuit breakers GI-E range, is characterized by a very high mechanical strenght and is suitable to assure more than 10.000 operations.

b Low maintenanceUnder normal conditions of service the GI-E range circuit breakers are able to switch off all the charge and short circuit currents. During their expected electrical life the live parts of the breaking chambers do not require any maintenance even in the case of frequent operations. Simple greasing of some mechanical components of the operating mechanism only, is recommended to be periodically performed every 3000 operations.

Page 6: MV circuit breaker for outdoor installation GI-E Range · A new path for achieving your electrical installations A comprehensive offer The GI-E range is part of a comprehensive offer

4

General presentation

Testsb The SF6 gas circuit breakers GI-E range have been fully type tested in accordance with IEC Standards.

b The type tests have been carried out at laboratories which enjoy high international reputation as follows:v CESI (ITALY)v KEMA (HOLLAND)v SVEPPI (ITALY)v LUIGI MAGRINI TEST LABORATORY (ITALY)

Type test evidence and reports are available on customer request.

b All the SF6 gas circuit breakers GI-E range are tested in our workshop before delivering in accordance with the Routine test list and procedure, as stated in the IEC Standards. The routine tests carried out on GI-E range circuit breakers are as follows:v Power frequency withstand voltage test on the main circuit.

v Dielectric test on auxiliary and control circuit.

v Measurement of the resistance of the main circuit.

v Mechanical operations test, which includes:a) measurement of resistance of the operation coils and of the heating resistors;b) measurement of closing and opening times. Check of simultaneous operation ofthe three phases;c) recording of closing and opening speed;d) check of antipumping device operation;e) check of all the electrical and mechanical locks and of the signalling devices;f) check of the auxiliary contacts.

v SF6 gas tightness test.v SF6 gas humidity test.v Conformity checks.

The routine test reports are filled in and issued by our quality control department and they can be available on customer request.

Safetyb The design of the SF6 gas circuit breakers GI-E range has been made in order to guarantee and to ensure the maximum safety to the installation and operational personnel.b SF6 gas monitoring deviceThe pre-arrangement in every pole of a SF6 gas pressure monitoring system, by means of pressure switches is able to give remote electrical alarm signals.b The SF6 gasThe utilization of SF6 gas (very stable and fireproof) as a medium of interruption makes impossible any fire hazard.b The electrical clearanceAppropriate clearance distances between phases and between the line terminals to ground have been provided allowing to assure insulation levels higher than what foreseen in the Standard IEC.b Degree of protectionThe spring motorcharged operating mechanism is housed in a box having degreeof protection IP 55, with door closed and degree of protection IP 20, with door open. The design of the operating mechanism box has been performed in order to safely allow the accessibility to the devices of operation and to the auxiliary switches.b InterlocksThe pre-arrangement of a simple and reliable selector switch provided with mechanical lock prevents any dangerous operations from the remote control room when the personnel are performing on the circuit breakers local operations.b InstructionsComplete and exhaustive instruction manual book relevant to the storage, unpacking, installation, commissioning and ordinary maintenance of the circuit breaker, is available inside every operating mechanism box.

GI-E Range

Page 7: MV circuit breaker for outdoor installation GI-E Range · A new path for achieving your electrical installations A comprehensive offer The GI-E range is part of a comprehensive offer

5

Reliability/Service continuityb The design of the SF6 gas circuit breaker GI-E range has been developped in order to assure high reliability during the whole expected service life.The reliability of the equipment is not only derived from the experience of the service, as it is planned at the time of design of all components by means of severe mechanical endurance tests and by the application of severe quality control procedures.

b The circuit breakers GI-E range assure long continuity of service because of the following features:v long proven experience with the technique of interruption of the electric arc by thev system of self-compression and selfregulation of the SF6 gas pressure,v high guarantee of gas tight enclosures assured by the reliability of the design ofv the sealing system and by severe tests performed in our work-shop before delivering to sites,v simple maintenance usually confined to quick periodical checks,v easy and fast replacement of the main components,v steady remote control of the condition of the insulating medium,v suitability for installation in any environment with temperatures ranging from -25°C up to +40°C. For higher performances, please consult our technical department.

Quality assuranceHigh technology product like the GI-E range calls for the application of a quality assurance program which goes beyond the usual acceptance test.b The design of the SF6 gas circuit breaker GI-E range has been strictly made in accordance with the high quality level ISO 9001 which concernes all the process of design, manufacturing up to the after sale service management.b Quality assurance organisation in force since 1975 and control procedures applied to all the activities, from work shop to office work, guarantees the high “degree of quality conformity”.b The certificate of compliance with the standard EN 29001 (ISO 9001) achieved by the quality assurance system in force in our company is the evidence of our steady commitment towards the quality. Schneider Electric has been qualified by CSQ, the official independent certification body in the electric field in Italy.

Standardsb The SF6 gas circuit breakers GI-E range for outdoor installation comply with the following standards:- International standards IEC 60056 (1987) and IEC 62271-100 (2001) “High voltage alternating current circuit breakers”.

Page 8: MV circuit breaker for outdoor installation GI-E Range · A new path for achieving your electrical installations A comprehensive offer The GI-E range is part of a comprehensive offer

6

Rating

All ratings listed below are in compliance with IEC Standards

Rated voltage (50 and 60Hz) kV 24-36-40,5 24-36-40,5Rated insulation level withstand voltage at power frequency impulse (1,2/50ms)

kVkV

80 (3)

200 (2)

80 (3)

200 (2)

Type “A” Type “B”Rated normal current (1) 630A b b b b

1250A b b b b

1600A b b b b

2000A b b b b

3150A b b b b

Rated short time withstand current for 3 s. kA 16 20 25 16 20 25 31,5Rated short-circuit breaking current kA 16 20 25 16 20 25 31,5Rated short-circuit making current kA 40 50 63 40 50 63 80Capacitor bank breaking current A 630 1250Rated cable-charging breaking current A 31,5 - 50 (***) 31,5 - 50 (***)Operating times (*) Opening * ms 33/50 30/43

Arcing (max) ms 15 15Break (*) (max) ms 48/65 45/58Closing (*) ms 60/83 57/80

Rated operating sequenceO-0,3s-CO-3min-CO b b

O-0,3s-CO-15s-CO b b

Rated SF6 gas pressure kPa gauge 400 400Rated line-charging breaking current A 10 10Rated small inductive breaking current (**) A 500-1600 (shunt reactor switching) 500-1600 (shunt reactor switching) Magnetizing breaking current (**) A 3-6-12 (no load transformer switching) 3-6-12 (no load transformer switching)

* with operating circuits energized at the rated voltage and circuit breaker at rated gas pressure

** at present these figures have not been defined by IEC standars -see IEC 61233.

*** for rated voltage 36kV and 40,5kV, rated cable charging breaking current is 50A

(1): The current carrying capacities are referred to an ambient temperature of 40°C as called for by IEC standards, as follows- maximum value +40°C- 24 hours average: maximum value +35°C

(2): The insulation capacity values are in accordance with IEC standard requirements. For higher rated insulation level withstand voltages, consult our technical department.

(3): Power frequency voltage withstand dry test: 100kV x 1’.

GI-E Range

Page 9: MV circuit breaker for outdoor installation GI-E Range · A new path for achieving your electrical installations A comprehensive offer The GI-E range is part of a comprehensive offer

7

E28

673

E28

670

fig.1 fig.2

E28

671

E28

672

fig.3 fig.4

DE

6033

0

Principle of interruption and pole sectional view

Principle of interruption (the puffer type technology)The principle of interruption of the circuit breaker GI-E range is based on the puffer type technology.Gas compression is self-generated in the puffer cylinder by contact motion during theopening operation. The SF6 gas pressure necessary to extinguish the arc is self-regulated as the arc core restricts the gas blow and causes the increase of the gas pressure up to the arc extinguishing value. The pressure of SF6 gas blown towards the arc is proportional to the value of the current to be interrupted.b The main contacts and the arcing contacts are initially closed and the opening spring is charged (fig. 1).b Thanks to the energy released by the spring, the moving contact is dragged to the open position.During the opening operation the following phases take place subsequently:

Precompression:At the beginning of the opening motion, the piston causes a slight compression of the SF6, filling the compression cylinder before the arcing contacts are open.

Arc quenching and cooling:v Separation of the main contacts and transfer of all current on the arcing contacts circuit (fig. 2).v Separation of the arcing contacts and priming, between the arcing contacts, of the electrical arc (fig. 3).v Cooling of the arc thanks to the pressurised blow of SF6 gas which is generated in the compression chamber. The blow of SF6 gas is driven towards the arc through appropriate insulated nozzle.v Arc quenching at the crossing of the zero current.v Completion of the opening stroke of the moving contact, increasing the gap between the contacts and sweeping away any arc product (fig. 4).b The SF6 gas decomposed by the electric arc recombines itself restoring stable molecules.The SF6 gas by product is easily absorbed by the molecular sieves which are contained in an adequate quantity in the breaker pole.

Pole sectional viewb The components of a pole of a circuit breaker GI-E range, namely the main and arcing contacts and the blow nozzle, are the same as adopted for the indoor circuit breakers.b They are highly reliable and time proven since these breakers have been working successfully for many years.b The switching of the rated normal current and of the rated short-circuit current takes place inside the “puffer type” breaking chambers.b In accordance with standard IEC 694 (96) 6.8.3, the poles of the circuit breaker GI-E range provide a sealed pressure system, for which no further gas processing is required during its expected operating life.b The poles are filled with SF6 gas at the pressure of 400 kPa gauge referred to 20°C.b Steady control of the SF6 gas pressure inside the pole is achieved by means of pressure switch with two monitoring contacts.b Thanks to the excellent SF6 gas chemical characteristics and to the excellent quality of the components utilised, the poles do not lose their own insulating properties during their service life, even after many switching operations.b The breaker poles contain molecular sieves which maintain the purity of the SF6 gas without any renewal, even after a large number of interruptions.

LEGEND:1 Cover2 Molecular sieves3 Upper terminal4 Upper insulator5 Fixed main contact6 Fixed arcing contact7 Blast nozzle8 Moving main contact9 Moving arcing contact10 Compression chamber11 Lower terminal12 Lower insulator13 Insulating rod14 SF6 gas15 SF6 gas filling valve16 Operating shaft17 Crank gear box18 Pressure switch

GI-E Range

Page 10: MV circuit breaker for outdoor installation GI-E Range · A new path for achieving your electrical installations A comprehensive offer The GI-E range is part of a comprehensive offer

8

PE

6023

4Operating mechanism

b The SF6 gas circuit breaker GI-E range is equipped with a well proven stored energy type operating mechanism, series GMh, suitable for three-pole reclosing.This type of operating mechanism has been used for many years in the indoor circuit breakers too and it is proven by a long service experience. The spring motorcharged operating mechanism has been designed in order to assure a long mechanical life.

b The operating mechanism is stored energy type.v The closing springs are charged by a motoreducer that can be operated either by d.c.or by a.c.operating voltages; v after every closing operation the motoreducer automatically recharges the closing spring.(Charging time is less than 15 seconds) The opening springs get charged with the energy stored by the closing spring during the circuit breaker closing operation;v in case of emergency the springs can be manually charged by means of hand charging lever. This device is removable type, located on the front of the operating mechanism;v the stored energy is capable to carry out the O-C-O cycle without recharging.

b Opening and closing operations have a speed independent from the operator one.

b The opening and closing operations of the circuit breaker can be performed either electrically by means of electrical push buttons, operating opening and closing coils, or manually, by means of mechanical push buttons.v The mechanical and electrical push buttons are provided on the front of the operating mechanism.

b The electrical closing and opening operations can be performed either locally or remotely.v The operating mechanism is equipped with a 3 positions selector switch, (local/zero/remote positions with withdrawble key in zero and remote positions and with N°1 aux.contact available in order to remotely signalize the local and zero positions).

The spring motorcharged operating mechanism complete of all its operating and control devices is housed in an hot dip galvanised box.

GI-E Range

Page 11: MV circuit breaker for outdoor installation GI-E Range · A new path for achieving your electrical installations A comprehensive offer The GI-E range is part of a comprehensive offer

9

PE

6023

5

b All the exposed ferrous parts of the operating mechanism box (and of the supporting structure too) are hot dip galvanised (600 g/m2) in accordance with Standard UNI 5744 which substantially corresponds to Standard BS 729, ASTM 123-153 and DIN 50976.

b The operating mechanism box has been designed in order to prevent the entry of water and the deterioration of the mechanism due to the condensation that could be originated by the humidity.v In accordance with standard IEC 529, the operating mechanism box has a degree of protection IP 55; v the operating mechanism box is complete with two heaters, one of which is permanently on, while the other one is controlled by a thermostat.

b The accessibility to the operating and control devices of the spring motorcharged operating mechanism and the watertightness of the operating mechanism box is provided by means of a door, hinged on the left side and by a proper gasket.

b A facility for the locking of the door by padlock device mounted on the door, is provided.

b The mechanical position indicators as well as the operation counter, which are mounted inside the operating mechanism box, are visible from the outside through inspection windows located on the front door of the box.

b The indication of the circuit breaker position (open-closed) is achieved by means of a mechanical position indicator. The indication is stressed as follows:v open position: with a black letter “O” engraved on a green backgroundv closed position: with a white letter “I” engraved on a red background.

b A gland plate for the cable entry is provided in the bottom of the operating mechanism box.v The gland plate must be purposely drilled on site.v The available surface is 200x400 mm.v The cable glands are usually provided by the contractors.

b All the electrical auxiliary equipments requiring connection to external control and operating apparatus are wired to the terminal board in accordance with the wiring diagram stated in the catalogue.v The wiring consists of homopolar PVC insulated, copper flexible black cable, type N07V-K, having degree of insulation up to 750V and section of 1,5 mm2.v The cables are anti-flame propagation type in accordance with IEC 60332-3 standard.v In order to connect the outside aux.cables, the terminal board is provided with terminal blocks suitable for screw tightening and for cables up to 4 mm2.v The terminal blocks are grey-coloured having 6 mm width; they are 6.6/6 polyamide insulated, with anti-fire additive, V0 class in accordance with UL 94.Additional short circuiting terminal blocks for connection of the secondary of the current transformers can be provided, on specific request.

Page 12: MV circuit breaker for outdoor installation GI-E Range · A new path for achieving your electrical installations A comprehensive offer The GI-E range is part of a comprehensive offer

10

Sepam Metering and protection unit

Optional Sepam 1000+ unit can be installed inside the operating mechanism box, visible from the outside through inspection windows located on the front door of the box.

Metering functions:Currentsb RMS measurement of the circuit’s 3 phase currents.b Residual current measurement.

Average currents and peak demand currentsMeasurement of the average current on each of the 3 phases.Measurement of the greatest average current on each of the 3 phases.The peak demand currents give the current consumed at the time of peak loads.The average current is calculated over a period that may be parameterized from 5 to 60 mn. The “clear” key is used to reset the peak demand currents to zero when they are on the display.

Tripping currentsStorage of the greatest average value of the 3 phase currents and earth current at the time Sepam gave the last tripping order, to provide the fault breaking current (fault analysis).These values are stored until the next trip order is given.

Diagnosis measurements:Cumulative breaking currentThe displayed value may be used to evaluate the state of the circuit breaker poles.

Operating time, charging timeMeasures the device operating time. These data may be used to evaluate the stateof the pole and operating mechanism.

Number of operationsCumulative number of breaker opening operations.

Running hours counter / operating timeCumulative time during which the protected equipment is on load (I > 0.1 Ib).The cumulative value is displayed in hours (0 to 65535 h) and saved every 4 hours.

Phase overcurrent (ANSI 50/51)Three-phase protection against overloads and phase-to-phase short-circuits.The protection comprises four units:b IDMT or definite time,b instantaneous or time-delayed.Sepam 1000+ offers a number of tripping curves:b definite time (DT),b IDMT.The IDMT curves also include a reset time which is used for:b detection of restriking faults,b coordination with electromechanical relays.

Earth fault (ANSI 50/51N or 50/51G)Connection and equipment earth fault protection.Earth faults may be detected by three phase currents (3I sum).The protection comprises four units:b IDMT or definite time,b instantaneous or time-delayed.The characteristic curves are the same as those for the phase current overcurrentprotection.Each set point has a reset time setting (by an adjustable timer hold with definite time characteristic) that allows restriking faults to be detected.Each set point has a 2nd harmonic restraint in order to ensure stability during transformer energizing.

Negative sequence / unbalance (ANSI 46)Protection against phase unbalance.Sensitive protection against 2-phase faults on long feeders.Protection of equipment against temperature build-up caused by an unbalanced supply or wrong phase rotation or the loss of a phase and protection against low levels of phase-to-phase overcurrent.IDMT or definite time characteristics.

Recloser (ANSI 79)Automation device used to reclose the circuit breaker after tripping triggered by a transient fault on a line (the function includes 4 parameterizable reclosing cycles).

PE

4062

5GI-E Range

Page 13: MV circuit breaker for outdoor installation GI-E Range · A new path for achieving your electrical installations A comprehensive offer The GI-E range is part of a comprehensive offer

11

Sepam Selection table

Sepam 1000+

functions type of Sepamprotections ANSI code S20 T20phase overcurrent (1) 50/51 4 4

earth fault (or neutral) (1) 50N/51N 4 4

unbalance / negative sequence 46 1 1

thermal oveload 49 RMS 2

rate of change of frequency 81R

recloser (4cycles) 79 v

thermostat / Buchholz v

temperature monitoring (2) 38/49T v

metering

phase current I1, I2, I3 RMS b b

residual current Io b b

average current I1, I2, I3 b b

peak demand phase current IM1, IM2, IM3 b b

temperature measurement (2) v

network diagnosis

tripping current I1, I2, I3, Io b b

unbalance ratio / negative sequence current li b b

running hours counter / operating time b

thermal capacity used b

remaining operating time before overload tripping b

waiting time after overload tripping) b

disturbance recording b b

switchgear diagnosis

cumulative breaking current (2) b b

trip circuit supervision v v

number of operations v v

operating times v v

self-diagnosis

watchdog b b

output realy test (3) v v

control and monitoring

circuit breaker / contractor control (4) v v

logic discrimination v v

4 addressable logic outputs b b

additional modules

MET 148 module - 8 temperature sensor inputs v

MSA 141 module - 1 low level analog output v v

MES 108 module - (4I/4S) or MES 114 module - (10I/4O) v v

ACE 949-2 module - (2-wire) or ACE 959 (4-wire) RS485 interface v v

Detailed brochure of Sepam unit is available on request.

g standardc according to parameter setting and MES 108 or MES 114 input/output module options.

(1) 4 relays with the exclusive possibility of logic discrimination or switching from one 2-relay group of settings to another 2-relay group.(2) with MET 148 sensor option, 2 set points per sensor.(3) with advanced UMI option only.(4) for shunt trip unit or undervoltage release coil according to parameter setting.

GI-E Range

Page 14: MV circuit breaker for outdoor installation GI-E Range · A new path for achieving your electrical installations A comprehensive offer The GI-E range is part of a comprehensive offer

12

DE

6033

1

Optional configuration with CT.

Current and voltage transformers General presentation

Main charcteristics of optional instrument transformers

The range of Merlin Gerin Instrument transformers has been designed for 7,2kV to 36kV voltage and rated currents from 5 to 2500A. In order to comply with higher short circuit levels in the systems, the current transformers have been designed to withstand 60kA x 1 second short circuit currents.

All our devices are up to the new and stricter provisions of the IEC regulations (partial discharge testing is performed after the induced voltage withstand test).

Current transformers can be in accordance with:b the accuracy classes “TPS-TPX-TPY-TPZ” defined by IEC 60044-6 standard and referring to transformer behaviour during short circuit transient phases.

Compliance with standardsAll Merlin Gerin Instrument Transformers are in compliance with IEC 60044-1 and IEC 60044-2 standards.Transformers compliant with other countries’ regulations can also be supplied (AS 1675- AS 1243, IEEE C57.13, BS7626 - BS7625, NFC 45502 - NFC 42501, VDE 0414 ...).

SpecificationsThe working parts (windings and magnetic cores) are entirely enclosed in an epoxy resin bloc casting, whose twofold function is to:b guarantee electric insulation inside the device,b ensure the highest strength.

The external surface of device is covered with silicon RAL 7035 color, whose function is to:b guarantee electric insulation outside the device,b ensure the highest strength

Product quality over time is guarantee not only by thirty years’ experience in the field of resin insulated instrument transformer manufacturing but also by:b the use of silica-loaded epoxy resin resulting inv high dielectric strength including at high temperatures (18kV/mm at 180°C for 20.000 hours),v insulation class B according to IEC 44-1 provisions.b extremely good ageing behaviour both to heat mass ageing according to IEC216 (over 20 years at 120°C) and to surface ageing obtained in salty mist.b In case of fire, no toxic substances are released in accordance with standards CEI 20-37, CEI 20-22 and ASTM D3286.b Extremely effective behaviour in tropical climates.b High strength even at the highest working temperatures (Martens point exceeding 105°C).b Accurate production process resulting in:v no blisters or blowholes in the resin thanks to vacuum casting;v low constant partial discharge figure also thanks to the high quality of the other insulating materials used (SF6 injection in voltage transformer windings);v high strength and very good electric conductivity in primary and secondary terminals even at the temperatures reached during a short circuit, thanks to mechanical seaming;process parameters remaining unchanged over time thanks to computer control used to manage and monitor the whole production line.

GI-E Range

Page 15: MV circuit breaker for outdoor installation GI-E Range · A new path for achieving your electrical installations A comprehensive offer The GI-E range is part of a comprehensive offer

13

PE

6023

7

current transformer type OAM3

PE

6023

8

current transformer type OAM7

Current Transformers type OAM3/N1 - OAM7

Characteristics:Standard reference: IEC 60044-1Rated highest voltage: 7,2 - 12 - 17,5 - 24 - 36KVRated continous thermal current: 1,2 x InFrequency: 50 or 60 HzRated secondary current standard: 5 or 1AFor primary current <800A: Double primary ratio through primary coupling.For primary current >800A: Double primary ratio through secondary reconnection.

Voltage Transformers type OVF2n - OVF3n

DescriptionVoltage transformer for phase-ground connection

Characteristics:Standard reference: IEC 60044-2Standard primary voltage Up: 30 - 33 - 35 kVRated insulation level: 36 kVRated secondary voltage Us: 100: √3 100 : 3 110: √3 110 : 3 VFrequency: 50 or 60 HzRated voltage factor: 1,9 for 8 hoursThermal burden: 450 VA

Nota : Detailed burden/class characteristics as per detailed brochure available on request.

PE

6023

9

voltage transformer type OVF2

Page 16: MV circuit breaker for outdoor installation GI-E Range · A new path for achieving your electrical installations A comprehensive offer The GI-E range is part of a comprehensive offer

14

DE

6033

2

Optional

DE

6033

Wiring diagram GI-E Range

Page 17: MV circuit breaker for outdoor installation GI-E Range · A new path for achieving your electrical installations A comprehensive offer The GI-E range is part of a comprehensive offer

15

CIRCUITS(1) closing(2) opening and SF6 gas monitoring(3) closing springs charging motor(4) a.c. auxiliaries: heaters, current socket, lightning(5) undervoltage opening release(6) available aux. contacts(7) ammetrical connection for Sepam(8) auxiliary connection for Sepam(9) Sepam’s aux. contacts(10) Sepam’s available aux. contacts

LEGEND:EC anticondensation resistorEL lightning lampET heating resistorF1 SepamKN antipumping relayKP pressure switches aux. relay (locking)M spring charging gear motorQC MCCB for the protection of the closing circuitQE MCCB for the protection of the heating and anticondensation resistorsQL lightning lamp switchQM MCCB for the protection of the spring charging motor circuitQO MCCB for the protection of the opening circuitRUM varistor (resistor voltage dependent)RYU resistor for the YU circuitSC closing push bottonSM1-2 end limit switches of the springs charging gear motorSO opening push bottonSOO consent contact to close the circuit breakerSPA1-2-3 pressure switches alarm contactsSPB1-2-3pressure switches locking contactsSQ1-2 circuit breaker aux. contactsSS selector switch D-0-L (remote - zero - local)ST thermostatXC terminal block to sectionalize the closing circuitXE terminal block to sectionalize the anticondensation and heating resistors circuitsXE1 bivalent socketXE2 bivalent socketXM terminal block to sectionalize the spring charging gear motor circuitXO terminal block to sectionalize the opening circuitXU terminal block to sectionalize the under voltage release circuitYC closing releaseYU under voltage releaseY01 opening releaseY02 additional opening release GI-E Range

The diagram refers to open circuit breaker, deenergized circuits, released closing springs, SF6 gas at rated pressure and alive undervoltage release.The circuits surrounded by the sketched line areavailable on specific request

Page 18: MV circuit breaker for outdoor installation GI-E Range · A new path for achieving your electrical installations A comprehensive offer The GI-E range is part of a comprehensive offer

16

Accessories and ratings of auxiliaries

Standard accessoriesb Closing springs gear motor (M) complete with end limit switches (SM1-SM2)b Electric contacts indicating that closing springs are charged (SM1)b Closing release (YC)b Opening release (Y01)b Antipumping relay (KN)b Pressure switch with 2 contacts (SPA-SPB) (one pressure switch for each pole)b Aux.pressure switches relay (KP)b Local/zero/remote selector switch (SS)b Terminal block to sectionalize the closing spring gear motor circuit (XM)b Terminal block to sectionalize the anticondensation and heating resistors circuit (XE)b Terminal block to sectionalize the opening circuit (XO)b Terminal block to sectionalize the closing circuit (XC)b Mechanical position indicator of circuit breaker position (open-closed)b Mechanical indicator of springs condition (charged-released)b Mechanical operated operation counterb 11NA+9NC free aux.contactsb Mechanical close-opening push buttonsb Electrical close-opening push botton (SO-SC)b Anticondensation resistor (EC)b Heating resistor and thermostat (ET+ST)b Operating mechanism box with degree of protection IP 55b Operating mechanism box hot dip galvanised (600g/m2 average coating value)b Hot dip galvanized supporting structureb Poles lifting facilitiesb Grounding facilities (holes)b Fixing anchor boltsb Spring charging leverb Packing: wooden structure covered with plywood panelsb Nota: the porcelain insulators of the poles are brown coloured, RAL 8016.

Optional accessoriesb Additional opening release (Y02)b Under voltage release (YU)b MCCB complete of aux.contact for protection of the circuit of the spring charging gear motor (QM)b MCCB complete of aux.contact for protection of the circuit of the anticondensation and heating resistors (QE)b MCCB complete of aux.contact for protection of the opening circuit (QO)b MCCB complete of aux.contact for protection of the closing circuit (QC)b Mechanical interlock Ronis type;with key removed, the circuit breaker is mechanically locked in “open” positionb Key padlock device mounted on the door of the operating mechanism boxb Portable lightning lamp (EL)b 2 poles + earth bivalent outlet socket 10-16A/250V a.c.(XE1+XE2)b Hot dip galvanized supporting structure suitable to fit outdoor current transformersb Earthing clampb Cables clampb Flexible connection between C.B. and C.Ts.b SF6 gas filling deviceb SF6 gas (bottles by 5 kg or 20 kg each)b RAL 7035 grey colour porcelain insulators

b Digital control and protection unit Sepam (see pages 10-11)

b Current transformer (see pages 12-13)

Additional short circuiting terminal blocks for the connection of the secondaries of the C.Ts

Page 19: MV circuit breaker for outdoor installation GI-E Range · A new path for achieving your electrical installations A comprehensive offer The GI-E range is part of a comprehensive offer

17

Ratings of the auxiliariesb Standard rated supply voltagesd.c.: 24-48-110-125-220 (V )a.c.: 110-127-220 (V)-(50/60 Hz)b Voltage variation rangeThe electric auxiliary equipment can operate satisfactorily within the range of the following voltage variation table:v spring charging gear motor85% - 110% of Vn - (a.c.)85% - 110% of Vn - (d.c.)v shunt opening release70% - 110% of Vn - (d.c.)85% - 110% of Vn - (a.c.)v shunt closing release85% - 110% of Vn - (d.c.)85% - 110% of Vn - (a.c.)v under-voltage releaseIt operates to open the switching device when the voltage at the terminals of the release falls below 35% of its rated voltage.The closing of the switching device can be achieved when the voltage at the terminals of the release is equal to, or higher than 85% of its rated voltage.b Maximum power consumptionb spring charging gear motor500 VA - a.c.400 W - d.c.v shunt opening release200 VA - a.c.150 W - d.c.v shunt closing release150 VA - a.c.100 W - d.c.v heating resistor150 Wv anticondensation resistor60 Wv under-voltage release75 VA - a.c.15 W - d.c.b Ratings of auxiliary contactsRated normal current: 10ARated voltage: 250V a.c.Breaking current capacity:v 0,5A at 220V d.c.-L/R< 40msv 3A at 220V d.c.-L/R< 10ms10A at 220V a.c.- power factor >0,3

GI-E Range

Page 20: MV circuit breaker for outdoor installation GI-E Range · A new path for achieving your electrical installations A comprehensive offer The GI-E range is part of a comprehensive offer

18

DE

6033

4Overall dimensions outdoor circuit breaker GI-E type “A”

Rated current 24 GI-E 16 24 GI-E 20 24 GI-E 25 24 GI-E 31 36 GI-E 16 36 GI-E 20630A Dim.type “A” Dim.type “A” Dim.type “A” Dim.type “A” Dim.type “A”

1250A Dim.type “A” Dim.type “A” Dim.type “A” Dim.type “A” Dim.type “A”

1600A Dim.type “A” Dim.type “A” Dim.type “A” Dim.type “A” Dim.type “A”

2000A Dim.type “B” Dim.type “B”

3150A Dim.type “B” Dim.type “B”

Page 21: MV circuit breaker for outdoor installation GI-E Range · A new path for achieving your electrical installations A comprehensive offer The GI-E range is part of a comprehensive offer

19

DE

6033

5

Overall dimensionsoutdoor circuit breaker GI-E type “B”

Rated current 36 GI-E 25 36 GI-E 31 40 GI-E 16 40 GI-E 20 40 GI-E 25 40 GI-E 31630A Dim.type “A” Dim.type “A” Dim.type “A” Dim.type “A”

1250A Dim.type “A” Dim.type “A” Dim.type “A” Dim.type “A”

1600A Dim.type “A” Dim.type “A” Dim.type “A” Dim.type “A”

2000A Dim.type “B” Dim.type “B” Dim.type “B” Dim.type “B”

3150A Dim.type “B” Dim.type “B” Dim.type “B” Dim.type “B”

GI-E Range

Page 22: MV circuit breaker for outdoor installation GI-E Range · A new path for achieving your electrical installations A comprehensive offer The GI-E range is part of a comprehensive offer

20

Packing

b The packing has been designed in order to guarantee the correct protection of the equipment during transportation and during the short time of storage before assembly and commissioning in the substation take place.v In addition, on specific customer request, the operating mechanism box can be protected by means of a thermic-weld barrier bag, complete of sufficient quantity of dehydrated salt suitable to keep the internal humidity below 35% referred to 20°C, for a maximum period of 12 months.

b Every circuit breaker is shipped in a standard case having the following dimensions:v length: 2800 mmv depth: 1100 mmv height: 1750 mm

b Every crate includes the three sets of poles, the operating mechanism box and the loose elements of the supporting structure.The gross weight of the case including the equipment is as follows:v roughly 900 kg for circuit breaker with dimensions “type A”v roughly 950 kg for circuit breaker with dimensions “type B”v If are requested, the SF6 gas bottles for the first filling and the refilling devices are delivered in separate cases.

b The cases are suitable for indoor storage.v On specific customer request different kind of packing can be provided.If CT’s are requested they are delivered in separate cases.

GI-E RangeP

E60

240

PE

6024

1

Page 23: MV circuit breaker for outdoor installation GI-E Range · A new path for achieving your electrical installations A comprehensive offer The GI-E range is part of a comprehensive offer

21

Installation and commissioning 0

b Detailed instruction manual book (including all the information concerning the installation procedure to be followed on site) is available inside the operating mechanism box.v A careful reading of it, before starting any operation, is recommended.b The installation of the supporting structure on the suitable concrete is very easy and fast; the supporting structure is fixed to the floor by means of anchor bolts.b The installation operation goes on with the lifting of the preassembled three poles set and of the operating mechanism on the supporting structure and then with the connection of the operating linkage between the poles and the operating mechanism.b A very simple mechanical setting of the operating linkage shall have to be performed on site in accordance with the exhaustive instruction stated in the manual book.b In order to simplify on site the lifting operation of the three poles set, theavailability of a lifting device is recommended.The assembly operations do not require futher special tools, in addition to the standard spanners.

Points to noteDuring the installation procedure, warning shall have to be taken in order to assembly the operating mechanism and the three pole set having the same serial number.b In accordance with the safety transport regulation in force, the poles are shipped with an internal pressure lower than the rated one (about 50 kPa gauge).When the installation of the equipment has been completed, the poles shall have to be filled with SF6 gas up to the rated pressure.v As the SF6 gas bottles for the first filling as well the refilling device are supplied if requested.b After the circuit breaker has been installed and all the connections to the auxiliaries and to the line have been completed, the end user may personally conduct the commissioning test, in order to check that no damages have occurred during transportation and storage.b The series of test shall have to be carried out in accordance with manufacturerís instructions about kind of test to be performed and limits of the acceptable values.In this regard the IEC 62271-100 (2001) recommendations will govern too.

GI-E RangeP

E60

242

Page 24: MV circuit breaker for outdoor installation GI-E Range · A new path for achieving your electrical installations A comprehensive offer The GI-E range is part of a comprehensive offer

22

Order form Outdoor GI-E

Only one of the boxes (ticked X or filled by the needed value) have to beconsidered between each horizontal line.Blue box X corresponds to none priced functions.

Basic circuit breaker Quantity

Rated voltage Ur (kV)

Breaking current Isc (kA)

Rated current Ir (A)Electrical motor - M

24 Vdc 110 Vdc 110 Vac (50 Hz) 110 Vac (60 Hz)48 Vdc 125 Vdc 127 Vac (50 Hz) 127 Vac (60 Hz)60 Vdc 220 Vdc 220 Vac (50 Hz) 220 Vac (60 Hz)

Closing shunt release - YC24 Vdc 110 Vdc 110 Vac (50 Hz) 110 Vac (60 Hz)48 Vdc 125 Vdc 127 Vac (50 Hz) 127 Vac (60 Hz)60 Vdc 220 Vdc 220 Vac (50 Hz) 220 Vac (60 Hz)

1st opening shunt release - Y0124 Vdc 110 Vdc 110 Vac (50 Hz) 110 Vac (60 Hz)48 Vdc 125 Vdc 127 Vac (50 Hz) 127 Vac (60 Hz)60 Vdc 220 Vdc 220 Vac (50 Hz) 220 Vac (60 Hz)

Heating resistors - ET+EC110 V (50-60 Hz) 127 V (50-60 Hz) 240 V (50-60 Hz)

220 V (50-60 Hz) 260 V (50-60 Hz)Leaflets language

French Italian English Spanich

Options2nd opening shunt release - Y02

24 Vdc 110 Vdc 110 Vac (50 Hz) 110 Vac (60 Hz)48 Vdc 125 Vdc 127 Vac (50 Hz) 127 Vac (60 Hz)60 Vdc 220 Vdc 220 Vac (50 Hz) 220 Vac (60 Hz)

Undervoltage release - YU24 Vdc 110 Vdc 110 Vac (50 Hz) 110 Vac (60 Hz)48 Vdc 125 Vdc 127 Vac (50 Hz) 127 Vac (60 Hz)60 Vdc 220 Vdc 220 Vac (50 Hz) 220 Vac (60 Hz)

AccessoriesFirst filing device quantity

SF6 gas for first filing (each CB needs 2 kg)

5 kg cylinder quantity

20 kg cylinder quantity

40 kg cylinder quantity

GI-E Range

Calculation zone

Page 25: MV circuit breaker for outdoor installation GI-E Range · A new path for achieving your electrical installations A comprehensive offer The GI-E range is part of a comprehensive offer

23

Environment Preserving the environment

The Schneider recycling procedure

PE

6024

3

Within the framework of the group’s environmental policy, Schneider services has made an operational procedure available, enabling medium voltage switchgear to be processed while eliminating any release of SF6 into the atmosphere.To help you to protect the environment, and to take care of your storage or dismantling concerns, Schneider services offers to recover any of your equipment that is reaching the end of its service life.The GI-E has been designed with environmental protection in mind:b the insulating and conducting materials that are used are identified, easy to separate, and recyclable,SF6 can be recovered at the end of its life, and reused after treatment.

GI-E RangeP

E60

244

PE

6024

5

The Schneider recycling procedure for SF6 based products is subject to rigorous management, and allows each device to be traced through to its final destruction.

Page 26: MV circuit breaker for outdoor installation GI-E Range · A new path for achieving your electrical installations A comprehensive offer The GI-E range is part of a comprehensive offer

24

Page 27: MV circuit breaker for outdoor installation GI-E Range · A new path for achieving your electrical installations A comprehensive offer The GI-E range is part of a comprehensive offer
Page 28: MV circuit breaker for outdoor installation GI-E Range · A new path for achieving your electrical installations A comprehensive offer The GI-E range is part of a comprehensive offer

Ref

. AM

TE

D30

0042

EN

© 2

008

- Sch

neid

er E

lect

ric -

All

right

s re

serv

ed

As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.

Production: Schneider Electric SASPrinting: Imprimerie du pont de claix

Schneider Electric Industries SAS

ART96558 04/2008

89, boulevard franklin-Roosevelt92506 Rueil-Malmaison Cedex FRANCETél. : 0 810 012 999http://www.schneider-electric.com