    GENERAL ELECTRICITY

    COMPANY OF LIBYA (GECOL)

    ALIK ENERJSAN.TC.A

    POWER SYSTEMS E.P.C. GROUP

    KHOMS SCPP

    (525 MW POWER PLANT)

    Revision History

    A 28.04.2014 FOR APPROVAL AAB AAB JMO

    REV. DATE DESCRIPTION PREPARED CHECKED APPROVED

    DOCUMENT TITLE/SUBJECT:

    AUTOMATIC TRANSFER SYSTEM (ATS) OPERATION PHILOSOPHY

    PROJECT DOCUMENT NO:

    DetailedInformation

    Size A-4

    Project Unit SystemDisc

    Doc.

    Type

    Orig. Serial No Lang. Eng.

    KMS 15 VG_ ER IDM 004No. of

    Sheet30

    VENDOR DOCUMENT NO:

    ** if applicable

    Rev. No: A

  • 8/11/2019 MV ATS 3-12.pdf

    2/30

    AUTOMATIC TRANSFER

    SYSTEM (ATS)

    OPERATION

    PHILOSOPHY

    Doc. No. : KMS-15-VG_-ER_-IDM-004

    Page : 2 OF 30

    Date : 28.04.2014

    Revision : A

    This document is the property of ALIK Enerji Sanayi ve Ticaret A. and may not be copied, used, reprinted or distributed by others

    INDEX:

    1. GENERAL DESCRIPTION ............................................................................................................................... 3

    2. MV ATS ................................................................................................................................................................. 5

    2.1. MVATSINMANUAL/LOCALMODEOPERATION ............................................................................ 5

    2.2. MVATSINMANUAL/REMOTEMODEOPERATION ......................................................................... 7

    2.3. MVATSINDISABLEMODE ................................................................................................................... 11

    2.4. MVATSINAUTOMATCMODEOPERATION .................................................................................... 11

    3. LV ATS ................................................................................................................................................................ 15

    3.1. LVATSTYPEA ...................................................................................................................................... 15

    3.1.1 LV ATS type A in Local /Manual Mode Operation ............................................................................ 16

    3.1.2 LV ATS type A in Manual Mode and Remote mode Operation .......................................................... 18

    3.1.3 LV ATS type Ain Disable Mode .......................................................................................................... 21

    3.1.4 LV ATS type Ain Automatic Mode Operation ..................................................................................... 21

    3.2. LVATSTYPEB ...................................................................................................................................... 25

    3.2.1 LV ATS type B in Local /Manual Mode Operation ............................................................................ 25

    3.2.2 LV ATS type B in Manual Mode and Remote mode Operation .......................................................... 25

    3.2.3 LV ATS type Bin Disable Mode .......................................................................................................... 263.2.4 LV ATS type Bin Automatic Mode Operation ..................................................................................... 26

    4. DCS INTERCONNECTION SIGNAL LIST .................................................................................................. 29

  • 8/11/2019 MV ATS 3-12.pdf

    3/30

  • 8/11/2019 MV ATS 3-12.pdf

    4/30

    AUTOMATIC TRANSFER

    SYSTEM (ATS)

    OPERATION

    PHILOSOPHY

    Doc. No. : KMS-15-VG_-ER_-IDM-004

    Page : 4 OF 30

    Date : 28.04.2014

    Revision : A

    This document is the property of ALIK Enerji Sanayi ve Ticaret A. and may not be copied, used, reprinted or distributed by others

    Auto Mode:Being in this mode, ATS will sense the sources. Sensing that a source can

    be lost or is being lost, the ATS will transfer the load automatically without loosing

    the power in the bus bar. In this mode DCS may not operate neither incomers nor bus

    coupling.

    Manual operation modes could be selected Locallyor Remotely(from DCS). To select from

    where the ATS will be controlled, a L/R selector switch will be provided in the ATS panel.

    DCS ATS SWITCH GEAR Interfaces

    ATS panel for Local Operation

  • 8/11/2019 MV ATS 3-12.pdf

    5/30

    AUTOMATIC TRANSFER

    SYSTEM (ATS)

    OPERATION

    PHILOSOPHY

    Doc. No. : KMS-15-VG_-ER_-IDM-004

    Page : 5 OF 30

    Date : 28.04.2014

    Revision : A

    This document is the property of ALIK Enerji Sanayi ve Ticaret A. and may not be copied, used, reprinted or distributed by others

    2. MV ATS

    The MV ATS will controlling the following switchgears:

    10BBA01/02

    Each ATS manages three (3) circuit breakers:

    Circuit Breaker A (Incoming CB)

    Circuit Breaker B (Incoming CB)

    Circuit Breaker C (Tie Breaker)

    The parallel coupling of the two supply lines to the switchgear could be maintained for a short

    time, in order to avoid disturbance of load power during changing the supply.

    2.1. MV ATS IN MANUAL / LOCAL MODE OPERATION

    Manual mode and local mode could be selected in ATS panel

    The operator could transfer the load, from one selected incomer to the other one (or vice

    versa), through the ATS.

  • 8/11/2019 MV ATS 3-12.pdf

    6/30

    AUTOMATIC TRANSFER

    SYSTEM (ATS)

    OPERATION

    PHILOSOPHY

    Doc. No. : KMS-15-VG_-ER_-IDM-004

    Page : 6 OF 30

    Date : 28.04.2014

    Revision : A

    This document is the property of ALIK Enerji Sanayi ve Ticaret A. and may not be copied, used, reprinted or distributed by others

    All the possible scenarios are the followings:

    CASE 1: Transfer Signal by Operator.

    If, while normal operation (Picture 1), the operator wants to Transfer to Switchgear A,

    he should locally close the tie breaker C(before closing ATS shall check

    synchronization) and after that open the Circuit Breaker B (incoming to the Bus-bar B)

    .

    For that the steps to take are as follows in local panel:

    1.- ATS should be in manual / local mode

    2.- Select breaker of incomer to be closed in local panel

    3.- Push transfer command in local panel

    4.-After receiving the transfer command, ATS will check synchronization

    (synchrocheck or synchcheck relay electrically determines if the difference in voltage

    magnitude, frequency and phase angle falls within allowable limits) and then close the

    tie breaker (which was open) and open the incoming breaker that has not been

    selected.

    CASE 2: Transfer Signal by Operator.

    If, while normal operation (Picture 1), the operator wants to Transfer to Switchgear B,

    he should locally close the tie breaker C (before closing ATS shall check

    synchronization) and after that open the Circuit Breaker A (incoming to the Bus-bar A)

    .

    For that the steps to take are as follows in local panel:

    1.- ATS should be in manual / local mode

    2.- Select breaker of incomer to be closed in local panel

    3.- Push transfer command in local panel

    4.-After receiving the transfer command, ATS will check synchronization

    (synchrocheck or synchcheck relay electrically determines if the difference in voltage

  • 8/11/2019 MV ATS 3-12.pdf

    7/30

  • 8/11/2019 MV ATS 3-12.pdf

    8/30

    AUTOMATIC TRANSFER

    SYSTEM (ATS)

    OPERATION

    PHILOSOPHY

    Doc. No. : KMS-15-VG_-ER_-IDM-004

    Page : 8 OF 30

    Date : 28.04.2014

    Revision : A

    This document is the property of ALIK Enerji Sanayi ve Ticaret A. and may not be copied, used, reprinted or distributed by others

    ATS should be in manual mode

    All the possible scenarios are the followings:

    CASE 6: Transfer Signal by Operator.

    If, while normal operation (Picture 1), the operator wants to Transfer to Switchgear A,

    he should locally close the tie breaker C (before closing ATS shall check

    synchronization) and after that open the Circuit Breaker B (incoming to the Bus-bar B)

    .

    For that the steps to take are as follows:

    1.- ATS should be in manual / remote mode

    2.- ATS should be available

    3.- Select breaker of incomer to be closed in DCS

    4.- Push transfer command in DCS panel

    5.-After receiving the transfer command from DCS, ATS will check synchronization

    (synchrocheck or synchcheck relay electrically determines if the difference in voltage

    magnitude, frequency and phase angle falls within allowable limits) and then close the

    tie breaker (which was open) and open the incoming breaker that has not been

    selected.

    CASE 7: Transfer Signal by Operator.

    If, while normal operation (Picture 1), the operator wants to Transfer to Switchgear B,

    he should locally close the tie breaker C (before closing ATS shall check

  • 8/11/2019 MV ATS 3-12.pdf

    9/30

    AUTOMATIC TRANSFER

    SYSTEM (ATS)

    OPERATION

    PHILOSOPHY

    Doc. No. : KMS-15-VG_-ER_-IDM-004

    Page : 9 OF 30

    Date : 28.04.2014

    Revision : A

    This document is the property of ALIK Enerji Sanayi ve Ticaret A. and may not be copied, used, reprinted or distributed by others

    synchronization) and after that open the Circuit Breaker A (incoming to the Bus-bar

    B).

    For that the steps to take are as follows:

    1.- ATS should be in manual / remote mode

    2.- ATS should be available

    3.- Select breaker of incomer to be closed in DCS

    4.- Push transfer command in DCS panel

    5.-After receiving the transfer command from DCS, ATS will check synchronization

    (synchrocheck or synchcheck relay electrically determines if the difference in voltage

    magnitude, frequency and phase angle falls within allowable limits) and then close the

    tie breaker (which was open) and open the incoming breaker that has not been

    selected.

    CASE 8: Fault on Bus A.

    When while normal operation (Picture 1) a fault happens on Bus A, Circuit Breaker

    A (incoming to the Bus-bar A) will trip. ATS will be locked

    CASE 9: Pre-alarm on Unit Auxiliary Transformer A.

    If, while normal operation (Picture 1), there is a temperature prealarm or overloading

    on Transformer A, Operator in Control Room will notice an alarm.

    If there is any operators reaction, tie breaker C should be closed (before closing

    ATS shall check synchronization) and, after, the Circuit Breaker A (incoming to the

    Bus-bar A) should be opened.

    CASE 10: Undervoltage on Bus A.

    If, while normal operation (Picture 1), undervoltage is detected on Busbar A (V

  • 8/11/2019 MV ATS 3-12.pdf

    10/30

  • 8/11/2019 MV ATS 3-12.pdf

    11/30

    AUTOMATIC TRANSFER

    SYSTEM (ATS)

    OPERATION

    PHILOSOPHY

    Doc. No. : KMS-15-VG_-ER_-IDM-004

    Page : 11 OF 30

    Date : 28.04.2014

    Revision : A

    This document is the property of ALIK Enerji Sanayi ve Ticaret A. and may not be copied, used, reprinted or distributed by others

    - ATS shall check synchronization and then shall close Tie Breaker C

    - ATS shall open Circuit Breaker B.DCS shall change ATS mode from manual to disable

    CASE 16: Busbar A re-energization

    Busbar A re-energization shall be done in Remote/Manual mode. The Operator should

    close the Circuit Breaker A (incoming to the Bus-bar A) and open tie breaker C.

    Before closing circuit breaker A, ATS will check synchronism.

    CASE 17: Busbar B re-energization

    Busbar B re-energization shall be done in Remote/Manual mode. The Operator should

    close the Circuit Breaker B (incoming to the Bus-bar B) and open tie breaker C.

    Before closing circuit breaker A, ATS will check synchronism.

    2.3. MV ATS IN DISABLE MODE

    This option shall be chosen mainly for maintenance purposes when it is required to isolate one

    of the supply lines or one of the Bus-bars.

    In this situation the system works as it did not exist automatic changeover system, and the

    orders of opening and closing of any circuit breaker will not cause any reaction in other

    circuit breakers.

    2.4. MV ATS IN AUTOMATC MODE OPERATION

    Automatic position could be selected or locally if ATS in Local mode or remotely if ATS in

    remote mode.

    Above statements mean that opening/closing commands are controlled by the ATS.

  • 8/11/2019 MV ATS 3-12.pdf

    12/30

    AUTOMATIC TRANSFER

    SYSTEM (ATS)

    OPERATION

    PHILOSOPHY

    Doc. No. : KMS-15-VG_-ER_-IDM-004

    Page : 12 OF 30

    Date : 28.04.2014

    Revision : A

    This document is the property of ALIK Enerji Sanayi ve Ticaret A. and may not be copied, used, reprinted or distributed by others

    CASE 18: Fault on Bus A.

    When while normal operation (Picture 1) a fault happens on Bus A, Circuit BreakerA (incoming to the Bus-bar B) will trip. ATS will be locked

    CASE 19: Unit Auxiliary Transformer A tripped or Undervoltage on Bus A.

    If, while normal operation (Picture 1), there is a trip on Transformer A or

    Undervoltage on Busbar A (V

  • 8/11/2019 MV ATS 3-12.pdf

    13/30

    AUTOMATIC TRANSFER

    SYSTEM (ATS)

    OPERATION

    PHILOSOPHY

    Doc. No. : KMS-15-VG_-ER_-IDM-004

    Page : 13 OF 30

    Date : 28.04.2014

    Revision : A

    This document is the property of ALIK Enerji Sanayi ve Ticaret A. and may not be copied, used, reprinted or distributed by others.

    OPERATIONAL TABLE MV ATS

    A C

    !"#AL $ $ %

    T"AS&E" SI'AL () !*E"AT!" L!+ALL) $ $

    $ $

    !"#AL $ $ %

    T"AS&E" SI'AL () !*E"AT!" L!+ALL) $ $

    % $

    !"#AL $ $ %

    &A/LT ! (/S A % %

    !"#AL $ $ %

    &A/LT ! (/S ( $ %

    T"AS&E" &"!# A $ $ $

    T"AS&E" SI'AL () !*E"AT!" L!+ALL) $ $

    !"#AL $ %T"AS&E" &"!# ( $ % $

    T"AS&E" SI'AL () !*E"AT!" L!+ALL) $ $

    !"#AL $ %

    !"#AL $ $ %

    T"AS&E" SI'AL () 1+S $ $

    $ $

    !"#AL $ $ %

    T"AS&E" SI'AL () 1+S $ $

    % $

    !"#AL $ $ %

    &A/LT ! (/S A % %

    !"#AL $ $ %

    T"AS&!"#E" A *"EALA"# $ %

    $ $

    2 % $

    !"#AL $ $ %

    /1E"3!LTA'E ! (/S A ALA"# $ %

    $ $

    2 % $

    !"#AL $ $ %

    &A/LT ! (/S ( $ %

    &au0t on (us A "E#!TE ; #A/AL

    +ASE &au0t on (us A L!+AL

    +ASE 2 &au0t on (us ( L!+AL

    +ASE 7aTransfer Si

  • 8/11/2019 MV ATS 3-12.pdf

    14/30

    AUTOMATIC TRANSFER

    SYSTEM (ATS)

    OPERATION

    PHILOSOPHY

    Doc. No. : KMS-15-VG_-ER_-IDM-004

    Page : 14 OF 30

    Date : 28.04.2014

    Revision : A

    This document is the property of ALIK Enerji Sanayi ve Ticaret A. and may not be copied, used, reprinted or distributed by others

    A C

    !"#AL $ $ %T"AS&!"#E" ( *"EALA"# $ %

    $ $

    2 $ $

    !"#AL $ $ %

    /1E"3!LTA'E ! (/S ( ALA"# $ %

    $ $

    2 $ $

    !"#AL $ $ %

    T"AS&E" SI'AL () 1+S $ $

    % $

    !"#AL $ $ %

    T"AS&E" SI'AL () 1+S $ $

    $ $

    /1E"3!LTA'E ! (/S A $ % $

    "E>EE"'IATI! (/S(A" A $ $

    $ %

    /1E"3!LTA'E ! (/S ( $ $ $

    "E>EE"'IATI! (/S(A" ( $ $

    $ %

    !"#AL $ $ %

    &A/LT ! (/S A % %

    !"#AL $ $ %

    $ $

    % $

    !"#AL $ $ %

    &A/LT ! (/S ( $ %

    !"#AL $ $ %

    $ $

    $ $

    1ISA(LE ATS 1ISA(LE

    L!+AL 1+S (L!+KE1

    #A/AL

    A/T!

    89: Times indicated are orientab0e. Time of /ndervo0ta

  • 8/11/2019 MV ATS 3-12.pdf

    15/30

    AUTOMATIC TRANSFER

    SYSTEM (ATS)

    OPERATION

    PHILOSOPHY

    Doc. No. : KMS-15-VG_-ER_-IDM-004

    Page : 15 OF 30

    Date : 28.04.2014

    Revision : A

    This document is the property of ALIK Enerji Sanayi ve Ticaret A. and may not be copied, used, reprinted or distributed by others.

    3. LV ATS

    The LV automatic changeover systems (ACO) to be considered are the following ones:

    LV ATS Type A: Connection between 2 Normal LV Switchgears.

    LV ATS Type B: Connection between 2 Essential LV Switchgears and 1

    Emergency Diesel Group.

    The following General considerations have to be taken into account in order to guarantee the

    proper working of the Automatic Change Over System:

    At least two CBs must be closed.

    All the circuit breakers must be not tripped.

    No fault in any Busbar.

    All Circuit Breakers shall be in Remote Mode.

    All Circuit Breakers shall be available in DCS (grouped signals: Remote Mode, No

    test mode, CB inserted ):

    3.1. LV ATS TYPE A

    Controlling the switchgears:

    11BFB01/02

    12BFB01/02

    10BFA01/02

    Each ATS manages three (3) circuit breakers:

    Circuit Breaker A (Incoming CB)

    Circuit Breaker B (Incoming CB)

    Circuit Breaker C (Tie Breaker)

  • 8/11/2019 MV ATS 3-12.pdf

    16/30

    AUTOMATIC TRANSFER

    SYSTEM (ATS)

    OPERATION

    PHILOSOPHY

    Doc. No. : KMS-15-VG_-ER_-IDM-004

    Page : 16 OF 30

    Date : 28.04.2014

    Revision : A

    This document is the property of ALIK Enerji Sanayi ve Ticaret A. and may not be copied, used, reprinted or distributed by others

    The parallel coupling of the two supply lines to the switchgear could be maintained for a short

    time, in order to avoid disturbance of load power during changing the supply.

    3.1.1 LV ATS type A in Local /Manual Mode Operation

    Manual mode and local mode could be selected in ATS panel

    The operator could transfer the load, from one selected incomer to the other one (or vice

    versa), through the ATS.

    All the possible scenarios are the followings:

    CASE 1: Transfer Signal by Operator.

    If, while normal operation, the operator wants to Transfer to Switchgear A, he should

    locally close the tie breaker C(before closing ATS shall check synchronization) and

    after that open the Circuit Breaker B (incoming to the Bus-bar B) .

    For that the steps to take are as follows in local panel:

    1.- ATS should be in manual / local mode

    2.- Select breaker of incomer to be closed in local panel

    3.- Push transfer command in local panel

    4.-After receiving the transfer command, ATS will check synchronization

    (synchrocheck or synchcheck relay electrically determines if the difference in voltagemagnitude, frequency and phase angle falls within allowable limits) and then close the

    tie breaker (which was open) and open the incoming breaker that has not been

    selected.

    CASE 2: Transfer Signal by Operator.

    If, while normal operation, the operator wants to Transfer to Switchgear B, he should

    locally close the tie breaker C (before closing ATS shall check synchronization) and

    after that open the Circuit Breaker A (incoming to the Bus-bar A) .

  • 8/11/2019 MV ATS 3-12.pdf

    17/30

    AUTOMATIC TRANSFER

    SYSTEM (ATS)

    OPERATION

    PHILOSOPHY

    Doc. No. : KMS-15-VG_-ER_-IDM-004

    Page : 17 OF 30

    Date : 28.04.2014

    Revision : A

    This document is the property of ALIK Enerji Sanayi ve Ticaret A. and may not be copied, used, reprinted or distributed by others

    For that the steps to take are as follows in local panel:1.- ATS should be in manual / local mode

    2.- Select breaker of incomer to be closed in local panel

    3.- Push transfer command in local panel

    4.-After receiving the transfer command, ATS will check synchronization

    (synchrocheck or synchcheck relay electrically determines if the difference in voltage

    magnitude, frequency and phase angle falls within allowable limits) and then close the

    tie breaker (which was open) and open the incoming breaker that has not been

    selected.

    CASE 3: Fault on Bus A.

    When while normal operation, a fault happens on Bus A, Circuit Breaker A

    (incoming to the Bus-bar A) will trip. ATS will be locked.

    CASE 4: Fault on Bus B.

    When while normal operation a fault happens on Bus B, Circuit Breaker B

    (incoming to the Bus-bar B) will trip. ATS will be locked.

    CASE 5: Transfer Signal by Operator to come to normal operation.

    If, the operator wants to go to normal operation fromTransfer A or B busbar, he should

    locally close Circuit breaker of the incomer A or B, that was opened (before closing

    ATS shall check synchronization) and after that open the tie Breaker C.

    For that the steps to take are as follows in local panel:

    1.- ATS should be in manual / local mode

    2.- Select INC-1/INC-2 in local panel

    3.- Push transfer command in local panel

    4.-After receiving the transfer command, ATS will check synchronization

    (synchrocheck or synchcheck relay electrically determines if the difference in voltage

  • 8/11/2019 MV ATS 3-12.pdf

    18/30

    AUTOMATIC TRANSFER

    SYSTEM (ATS)

    OPERATION

    PHILOSOPHY

    Doc. No. : KMS-15-VG_-ER_-IDM-004

    Page : 18 OF 30

    Date : 28.04.2014

    Revision : A

    This document is the property of ALIK Enerji Sanayi ve Ticaret A. and may not be copied, used, reprinted or distributed by others

    magnitude, frequency and phase angle falls within allowable limits) and then close the

    breaker (which was open) and open the tie breaker.

    3.1.2 LV ATS type A in Manual Mode and Remote mode Operation

    Being the ATS in manual mode (this operation mode could be selected remotely if ATS in

    remote mode), the operator could transfer the load, from one selected incomer to the other (or

    vice versa), through the ATS.

    ATS should be in manual mode

    All the possible scenarios are the followings:

    CASE 6: Transfer Signal by Operator.

    If, while normal operation, the operator wants to Transfer to Switchgear A, he should

    locally close the tie breaker C (before closing ATS shall check synchronization) and

    after that open the Circuit Breaker B (incoming to the Bus-bar B) .

    For that the steps to take are as follows:

    1.- ATS should be in manual / remote mode

    2.- ATS should be available

    3.- Select breaker of incomer to be closed in DCS

    4.- Push transfer command in DCS panel5.-After receiving the transfer command from DCS, ATS will check synchronization

    (synchrocheck or synchcheck relay electrically determines if the difference in voltage

    magnitude, frequency and phase angle falls within allowable limits) and then close the

    tie breaker (which was open) and open the incoming breaker that has not been

    selected.

    CASE 7: Transfer Signal by Operator.

  • 8/11/2019 MV ATS 3-12.pdf

    19/30

    AUTOMATIC TRANSFER

    SYSTEM (ATS)

    OPERATION

    PHILOSOPHY

    Doc. No. : KMS-15-VG_-ER_-IDM-004

    Page : 19 OF 30

    Date : 28.04.2014

    Revision : A

    This document is the property of ALIK Enerji Sanayi ve Ticaret A. and may not be copied, used, reprinted or distributed by others

    If, while normal operation , the operator wants to Transfer to Switchgear B, he should

    locally close the tie breaker C (before closing ATS shall check synchronization) andafter that open the Circuit Breaker A (incoming to the Bus-bar B) .

    For that the steps to take are as follows:

    1.- ATS should be in manual / remote mode

    2.- ATS should be available

    3.- Select breaker of incomer to be closed in DCS

    4.- Push transfer command in DCS panel

    5.-After receiving the transfer command from DCS, ATS will check synchronization

    (synchrocheck or synchcheck relay electrically determines if the difference in voltage

    magnitude, frequency and phase angle falls within allowable limits) and then close the

    tie breaker (which was open) and open the incoming breaker that has not been

    selected.

    CASE 8: Fault on Bus A.

    When while normal operation a fault happens on Bus A, Circuit Breaker A

    (incoming to the Bus-bar A) will trip. ATS will be locked

    CASE 9: Pre-alarm on MV/LV Transformer A.

    If, while normal operation , there is a temperature prealarm or overloading on

    Transformer A, Operator in Control Room will notice an alarm.

    If there is any operators reaction, tie breaker C should be closed (before closing

    ATS shall check synchronization) and, after, the Circuit Breaker A (incoming to the

    Bus-bar A) should be opened.

    CASE 10: Undervoltage on Bus A.

    If, while normal operation , undervoltage is detected on Busbar A (V

  • 8/11/2019 MV ATS 3-12.pdf

    20/30

    AUTOMATIC TRANSFER

    SYSTEM (ATS)

    OPERATION

    PHILOSOPHY

    Doc. No. : KMS-15-VG_-ER_-IDM-004

    Page : 20 OF 30

    Date : 28.04.2014

    Revision : A

    This document is the property of ALIK Enerji Sanayi ve Ticaret A. and may not be copied, used, reprinted or distributed by others

    If there is any operators reaction, tie breaker C should be closed (before closing

    ATS shall check synchronization) and, after, the Circuit Breaker A (incoming to theBus-bar A) should be opened.

    CASE 11: Fault on Bus B.

    When while normal operation a fault happens on Bus B, Circuit Breaker B

    (incoming to the Bus-bar B) will trip. ATS will be locked

    CASE 12: Pre-alarm on MV/LV Transformer B.

    If, while normal operation , there is a temperature prealarm or overloading on

    Transformer B, Operator in Control Room will notice an alarm.

    If there is any operators reaction, tie breaker C should be closed (before closing

    ATS shall check synchronization) and, after, the Circuit Breaker B (incoming to the

    Bus-bar B) should be opened.

    CASE 13: Undervoltage on Bus B.

    If, while normal operation , undervoltage is detected on Busbar B (V

  • 8/11/2019 MV ATS 3-12.pdf

    21/30

    AUTOMATIC TRANSFER

    SYSTEM (ATS)

    OPERATION

    PHILOSOPHY

    Doc. No. : KMS-15-VG_-ER_-IDM-004

    Page : 21 OF 30

    Date : 28.04.2014

    Revision : A

    This document is the property of ALIK Enerji Sanayi ve Ticaret A. and may not be copied, used, reprinted or distributed by others

    CASE 15: MV/LV TRANSFORMER B in maintenance:

    If while Normal Operation, with ATS in Remote Mode it is decided to make amaintenance to MV/LV Transformer B, Distributed Control System (DCS) will

    send the transfer order to ATS:

    - ATS shall check synchronization and then shall close Tie Breaker C

    - ATS shall open Circuit Breaker B.

    DCS shall change ATS mode from manual to disable

    CASE 16: Busbar A re-energization

    Busbar A re-energization shall be done in Remote/Manual mode. The Operator should

    close the Circuit Breaker A (incoming to the Bus-bar A) and open tie breaker C.

    Before closing circuit breaker A, ATS will check synchronism.

    CASE 17: Busbar B re-energization

    Busbar B re-energization shall be done in Remote/Manual mode. The Operator should

    close the Circuit Breaker B (incoming to the Bus-bar B) and open tie breaker C.

    Before closing circuit breaker A, ATS will check synchronism.

    3.1.3 LV ATS type Ain Disable Mode

    This option shall be chosen mainly for maintenance purposes when it is required to isolate one

    of the supply lines or one of the Bus-bars.

    In this situation the system works as it did not exist automatic changeover system, and the

    orders of opening and closing of any circuit breaker will not cause any reaction in other

    circuit breakers.

    3.1.4 LV ATS type Ain Automatic Mode Operation

    Automatic position could be selected or locally if ATS in Local mode or remotely if ATS in

    remote mode.

  • 8/11/2019 MV ATS 3-12.pdf

    22/30

    AUTOMATIC TRANSFER

    SYSTEM (ATS)

    OPERATION

    PHILOSOPHY

    Doc. No. : KMS-15-VG_-ER_-IDM-004

    Page : 22 OF 30

    Date : 28.04.2014

    Revision : A

    This document is the property of ALIK Enerji Sanayi ve Ticaret A. and may not be copied, used, reprinted or distributed by others

    Above statements mean that opening/closing commands are controlled by the ATS.

    In Operational Table LV ATS type A all the scenarios have been explained as follows:

    CASE 18: Fault on Bus A.

    When while normal operation (Picture 1) a fault happens on Bus A, Circuit Breaker

    A (incoming to the Bus-bar B) will trip. ATS will be locked

    CASE 19: MV/LV Transformer A tripped or Undervoltage on Bus A.

    If, while normal operation (Picture 1), there is a trip on Transformer A or

    Undervoltage on Busbar A (V

  • 8/11/2019 MV ATS 3-12.pdf

    23/30

    AUTOMATIC TRANSFER

    SYSTEM (ATS)

    OPERATION

    PHILOSOPHY

    Doc. No. : KMS-15-VG_-ER_-IDM-004

    Page : 23 OF 30

    Date : 28.04.2014

    Revision : A

    This document is the property of ALIK Enerji Sanayi ve Ticaret A. and may not be copied, used, reprinted or distributed by others.

    OPERATIONAL TABLE LV ATS TYPE A

    A C !"#AL $ $ %

    T"AS&E" SI'AL () !*E"AT!" L!+ALL) $ $

    $ $

    !"#AL $ $ %

    T"AS&E" SI'AL () !*E"AT!" L!+ALL) $ $

    % $

    !"#AL $ $ %

    &A/LT ! (/S A % %

    !"#AL $ $ %

    &A/LT ! (/S ( $ %

    T"AS&E" &"!# A $ $ $

    T"AS&E" SI'AL () !*E"AT!" L!+ALL) $ $

    !"#AL $ %

    T"AS&E" &"!# ( $ % $

    T"AS&E" SI'AL () !*E"AT!" L!+ALL) $ $

    !"#AL $ %

    !"#AL $ $ %

    T"AS&E" SI'AL () 1+S $ $

    $ $

    !"#AL $ $ %

    T"AS&E" SI'AL () 1+S $ $

    % $

    !"#AL $ $ %

    &A/LT ! (/S A % %

    !"#AL $ $ %

    T"AS&!"#E" A *"EALA"# $ %

    $ $

    2 % $

    !"#AL $ $ %

    /1E"3!LTA'E ! (/S A ALA"# $ % $ $

    2 % $

    !"#AL $ $ %

    &A/LT ! (/S ( $ %

    +ASE B Transfer Si

  • 8/11/2019 MV ATS 3-12.pdf

    24/30

    AUTOMATIC TRANSFER

    SYSTEM (ATS)

    OPERATION

    PHILOSOPHY

    Doc. No. : KMS-15-VG_-ER_-IDM-004

    Page : 24 OF 30

    Date : 28.04.2014

    Revision : A

    This document is the property of ALIK Enerji Sanayi ve Ticaret A. and may not be copied, used, reprinted or distributed by others

    A C !"#AL $ $ %

    T"AS&!"#E" ( *"EALA"# $ %

    $ $

    2 $ $

    !"#AL $ $ %

    /1E"3!LTA'E ! (/S ( ALA"# $ %

    $ $

    2 $ $

    !"#AL $ $ %

    T"AS&E" SI'AL () 1+S $ $

    % $

    !"#AL $ $ %

    T"AS&E" SI'AL () 1+S $ $

    $ $

    /1E"3!LTA'E ! (/S A $ % $

    "E>EE"'IATI! (/S(A" A $ $

    $ %

    /1E"3!LTA'E ! (/S ( $ $ $"E>EE"'IATI! (/S(A" ( $ $

    $ %

    !"#AL $ $ %

    &A/LT ! (/S A % %

    !"#AL $ $ %

    $ $

    % $

    !"#AL $ $ %

    &A/LT ! (/S ( $ %

    !"#AL $ $ %

    $ $

    $ $

    1ISA(LE ATS 1ISA(LE

    L!+AL 1+S (L!+KE1

    #A/AL

    A/T!

    T"AS&!"#E" A T"I*

    /1E"3!LTA'E ! (/S A

    T"AS&!"#E" ( T"I*

    /1E"3!LTA'E ! (/S (

    +ASE $C &au0t on (us A "E#!TE ; A/T!

    +ASE $=#3L3 Transformer @A tripped or

    /ndervo0taener

  • 8/11/2019 MV ATS 3-12.pdf

    25/30

    AUTOMATIC TRANSFER

    SYSTEM (ATS)

    OPERATION

    PHILOSOPHY

    Doc. No. : KMS-15-VG_-ER_-IDM-004

    Page : 25 OF 30

    Date : 28.04.2014

    Revision : A

    This document is the property of ALIK Enerji Sanayi ve Ticaret A. and may not be copied, used, reprinted or distributed by others.

    3.2. LV ATS TYPE B

    Controlling the switchgears:

    10BMA01/02

    This ATS manages three (3) circuit breakers:

    Circuit Breaker A (Incoming CB)

    Circuit Breaker B (Incoming CB) Circuit Breaker C (Tie Breaker)

    The parallel coupling of the two supply lines to the switchgear could be maintained for a short

    time, in order to avoid disturbance of load power during changing the supply.

    3.2.1 LV ATS type B in Local /Manual Mode Operation

    LV ATS Type B shall work as LV ATS Type A

    3.2.2 LV ATS type B in Manual Mode and Remote mode Operation

    LV ATS Type B shall work as LV ATS Type A with the following exceptions:

  • 8/11/2019 MV ATS 3-12.pdf

    26/30

    AUTOMATIC TRANSFER

    SYSTEM (ATS)

    OPERATION

    PHILOSOPHY

    Doc. No. : KMS-15-VG_-ER_-IDM-004

    Page : 26 OF 30

    Date : 28.04.2014

    Revision : A

    This document is the property of ALIK Enerji Sanayi ve Ticaret A. and may not be copied, used, reprinted or distributed by others

    cases related to MV/LV Transformers have also been modified or eliminated, becauseincomers of busbar A or B are from BFA busbar

    in case of no power supply in Bus-bars B after the transfer done, EDG will start

    automatically to feed the essential loads according to document EGDs philosophy.

    3.2.3 LV ATS type Bin Disable Mode

    LV ATS Type B shall work as LV ATS Type A

    3.2.4 LV ATS type Bin Automatic Mode Operation

    LV ATS Type B shall work as LV ATS Type A with the following exceptions:

    cases related to MV/LV Transformers have also been modified or eliminated, because

    incomers of busbar A or B are from BFA busbar

    in case of no power supply in Bus-bars B after the transfer done, EDG will start

    automatically to feed the essential loads according to document EGDs philosophy.

  • 8/11/2019 MV ATS 3-12.pdf

    27/30

    AUTOMATIC TRANSFER

    SYSTEM (ATS)

    OPERATION

    PHILOSOPHY

    Doc. No. : KMS-15-VG_-ER_-IDM-004

    Page : 27 OF 30

    Date : 28.04.2014

    Revision : A

    This document is the property of ALIK Enerji Sanayi ve Ticaret A. and may not be copied, used, reprinted or distributed by others.

    OPERATIONAL TABLE LV ATS TYPE B

    A C !"#AL $ $ %

    T"AS&E" SI'AL () !*E"AT!" L!+ALL) $ $

    $ $

    !"#AL $ $ %

    T"AS&E" SI'AL () !*E"AT!" L!+ALL) $ $

    % $

    !"#AL $ $ %

    &A/LT ! (/S A % %

    !"#AL $ $ %

    &A/LT ! (/S ( $ %

    T"AS&E" &"!# A $ $ $

    T"AS&E" SI'AL () !*E"AT!" L!+ALL) $ $

    !"#AL $ %

    T"AS&E" &"!# ( $ % $

    T"AS&E" SI'AL () !*E"AT!" L!+ALL) $ $

    !"#AL $ %

    !"#AL $ $ %

    T"AS&E" SI'AL () 1+S $ $

    $ $

    !"#AL $ $ %

    T"AS&E" SI'AL () 1+S $ $

    % $

    !"#AL $ $ %

    &A/LT ! (/S A % %

    +ASE = *re>a0arm on #3L3 Transformer @A

    !"#AL $ $ %

    /1E"3!LTA'E ! (/S A ALA"# $ %

    $ $

    2 % $

    !"#AL $ $ %&A/LT ! (/S ( $ %

    A

    if there i s an operatorDs reaction

    +ASE B Transfer Si

  • 8/11/2019 MV ATS 3-12.pdf

    28/30

    AUTOMATIC TRANSFER

    SYSTEM (ATS)

    OPERATION

    PHILOSOPHY

    Doc. No. : KMS-15-VG_-ER_-IDM-004

    Page : 28 OF 30

    Date : 28.04.2014

    Revision : A

    This document is the property of ALIK Enerji Sanayi ve Ticaret A. and may not be copied, used, reprinted or distributed by others

    A C +ASE $ *re>a0arm on #3L3 Transformer @(

    !"#AL $ $ %

    /1E"3!LTA'E ! (/S ( ALA"# $ %

    $ $

    2 $ $

    +ASE $2 T"AS&!"#E" A I #AITEA+E

    +ASE $7 T"AS&!"#E" ( I #AITEA+E

    /1E"3!LTA'E ! (/S A $ % $

    "E>EE"'IATI! (/S(A" A $ $

    $ %

    /1E"3!LTA'E ! (/S ( $ $ $

    "E>EE"'IATI! (/S(A" ( $ $

    $ %

    !"#AL $ $ %

    &A/LT ! (/S A % %

    !"#AL $ $ %

    $ $

    % $!"#AL $ $ %

    &A/LT ! (/S ( $ %

    !"#AL $ $ %

    $ $

    $ $

    1ISA(LE ATS 1ISA(LE

    L!+AL 1+S (L!+KE1

    #A/AL

    A/T!

    +ASE $ /ndervo0taenerener

  • 8/11/2019 MV ATS 3-12.pdf

    29/30

    AUTOMATIC TRANSFER

    SYSTEM (ATS)

    OPERATION

    PHILOSOPHY

    Doc. No. : KMS-15-VG_-ER_-IDM-004

    Page : 29 OF 30

    Date : 28.04.2014

    Revision : A

    This document is the property of ALIK Enerji Sanayi ve Ticaret A. and may not be copied, used, reprinted or distributed by others.

    4. DCS INTERCONNECTION SIGNAL LIST

    As per this operation philosophy there will be the following signals exchange between ATS

    and DCS:

    SIGNALSIGNAL TYPE (in

    DCS)

    SIGNAL

    VOLTAGE

    LEVEL

    DESCRIPTION

    1isab0e #ode 1!

    #aintained type

    2 3dc

    8A+!:

    1isab0e mode se0ection from 1+S J#I

    #anua0 #ode 1!

    #aintained type

    2 3dc

    8A+!:

    #anua0 mode se0ection from 1+S J#I

    Auto #ode 1!

    #aintained type

    2 3dc

    8A+!:

    Auto mode se0ection from 1+S J#I

    Incomer> $ Se0ected 1!

    #aintained type

    2 3dc

    8A+!:

    Incomer $ se0ected from 1+S J#I

    Incomer> Se0ected 1!

    #aintained type

    2 3dc

    8A+!:

    Incomer se0ected from 1+S J#I

    I+>$I+>

    Se0ected

    1!

    #aintained type

    2 3dc

    8A+!:

    I+>$I+> se0ected from 1+S J#I. To

    come to norma0 situation

    Transfer +ommand 1!

    *u0se type

    87 sec:

    2 3dc

    8A+!:

    +ommand from 1+S to reuire ATS to

    rea0iGe a manua0 transfer accordin< to

    the se0ection done.

    Avai0ab0e 1I

    #aintained type

    2 3dc

    81+S:

    ATS is ready for operation no a0arm,

    poFer supp0y o-, etc.

    1isab0e

    1I

    #aintained type

    2 3dc

    81+S:

    ATS is out of order. In this situation

    1+S can open and c0ose incomers and

    bus coup0er but never can c0ose a00 of

    them at the same time.

    #anua0 #ode1I

    #aintained type

    2 3dc

    81+S:

    ATS is in #anua0 #ode. In this situation

    1+S cannot operate incomers or bus

    coup0er. ATS Fi00 operate them

    Auto #ode1I

    #aintained type2 3dc81+S:

    ATS is in Auto #ode. In this situation

    1+S cannot operate incomers or bus

    coup0er. ATS Fi00 operate them

    "emote #ode1I

    #aintained type

    2 3dc

    81+S:

    ATS is in "emote #ode. 1+S can

    se0ectcontro0 ATS operation modes

    disab0e, manua0 or auto mode

    Loca0 #ode1I

    #aintained type

    2 3dc

    81+S:

    ATS is in Loca0 #ode. Loca00y operator

    can se0ectcontro0 ATS operation

    modes disab0e, manua0 or auto mode

    Transfer 1one 1I

    *u0se type

    87 sec:

    2 3dc

    81+S:

    ATS feedbac-. Transfer correct0y done.

  • 8/11/2019 MV ATS 3-12.pdf

    30/30

    AUTOMATIC TRANSFER

    SYSTEM (ATS)

    OPERATION

    PHILOSOPHY

    Doc. No. : KMS-15-VG_-ER_-IDM-004

    Page : 30 OF 30

    Date : 28.04.2014

    Revision : A

    SIGNALSIGNAL TYPE (in

    DCS)

    SIGNAL

    VOLTAGE

    LEVEL

    DESCRIPTION

    A0arm 1I

    #aintained type2 3dc

    81+S:

    ATS has