US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations Mitsubishi Heavy Industries, LTD. US-APWR Safety-Related Air Conditioning, Heating, Cooling, and Ventilation Systems Calculations Non-Proprietary Version March 2013 2013 Mitsubishi Heavy Industries, Ltd. All Rights Reserved

Upload: others

Post on 14-Jul-2020

6 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

US-APWR

Safety-Related Air Conditioning, Heating, Cooling, and Ventilation Systems Calculations

Non-Proprietary Version

March 2013

Ⓒ2013 Mitsubishi Heavy Industries, Ltd. All Rights Reserved

Page 2: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 1 of 37)

Revision Page

(Section) Description

0 (Nov-2010)

All Original issued

1 (Mar-2011) 7

7

7

7

7

7

7

9

11

14 Table 3-1: - Cooling Coil Capacity in C, D-Class 1E Electrical Room Air Handling Unit is changed from “2,250,000” to “2,290,000”.

21 Section 5.1.1, Outdoor Air Intake: - Replaced “Total required ventilation airflow is to be 1,637 cfm…” with “Total required ventilation airflow is to be 1,635 cfm…”.

22

Section 5.1.2.1, (3) Heat Gains: - Replaced “Heat gains for CRE including 15% margin are 238,000 Btu/h…” with “Heat gains for CRE including 15% margin are 242,000 Btu/h…”.

- Replaced “…one AHU is to be 119,000 Btu/h per unit.” with “…one AHU is to be 121,000 Btu/h per unit.”.

Page 3: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 2 of 37)

Revision Page

(Section) Description

1 (Mar-2011)

23 Section 5.1.2.1, (5) Additional Cooling Load (Additional margin): - Replaced “Additional cooling load (additional margin) is 13,000 Btu/h” with “Additional cooling load (additional margin) is 11,000 Btu/h”.

23

24

24

25 Section 5.1.2.2, (4) Heat Gains: - Replaced “...including 15% margin are 238,000 Btu/h...” with “...including 15% margin are 242,000 Btu/h...”

25 Section 5.1.2.2, (4) Heat Gains: - Replaced “The cooling load per one AHU is to be 119,000 Btu/h.” with “The cooling load per one AHU is to be 121,000 Btu/h.”.

25 Section 5.1.2.2, (6) Additional Cooling Load (Additional margin): - Replaced “Additional cooling load (additional margin) is 24,000 Btu/h” with “Additional cooling load (additional margin) is 22,000 Btu/h”.

26

26

26

27

27

Page 4: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 3 of 37)

Revision Page

(Section) Description

1

(Mar-2011)

27

27

28

29

Section 5.2.2.1, (1) Outdoor Air: - Replaced “...and 29.3 Btu/lb.” with “... and 29.5 Btu/lb.”. - Replaced “q = 60 × 0.075 × 2600 × (43.3 – 29.3) × 1.15 = 188,370 Btu/h, USE 189,000 Btu/h” with “q = 60 × 0.075 × 2600 × (43.3 – 29.5) × 1.15 = 185,679 Btu/h, USE 186,000 Btu/h”.

30 Section 5.2.2.1, (2.2) Return Air Fan Motor: - Editorial changed “= 83,332 Btu/h,” with “= 83,323 Btu/h,”.

30 Section 5.2.2.1, (3) Heat Gains: - Replaced “...15% margin are 929,000 Btu/h” with “...15% margin are 966,000 Btu/h”.

30 Section 5.2.2.1, (4) Additional Cooling Load (Additional margin): - Replaced “...(additional margin) is 127,000 Btu/h” with “...(additional margin) is 93,000 Btu/h”.

30

Page 5: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 4 of 37)

Revision Page

(Section) Description

1

(Mar-2011) 31

31

31

32

Section 5.2.2.2, (1) Outdoor Air: - Replaced “...and 30.1 Btu/lb.” with “...and 30.3 Btu/lb.”. - Replaced “q = 60 × 0.075 × 2600 × (43.3 – 30.1) × 1.15 = 177,606 Btu/h, USE 180,000 Btu/h” with “q = 60 × 0.075 × 2600 × (43.3 – 30.3) × 1.15 = 174,915 Btu/h, USE 175,000 Btu/h”.

32

Section 5.2.2.2, (3) Heat Gains: - Replaced “Heat gains including 15% margin are 1,422,000 Btu/h (Train C: 939,000 Btu/h (Table 5.2.1-2), Train D: 483,000 Btu/h (Table 5.2.1-1))” with “Heat gains including 15% margin are 1,465,000 Btu/h (Train C: 973,000 Btu/h (Table 5.2.1-2), Train D: 492,000 Btu/h (Table 5.2.1-1))”.

33 Section 5.2.2.2, (4) Additional Cooling Load (Additional margin): - Replaced “...(additional margin) is 119,000 Btu/h” with “...(additional margin) is 121,000 Btu/h”.

- Replaced “...= 2,250,000 Btu/h” with “...= 2,290,000 Btu/h”.

33

34

Page 6: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 5 of 37)

Revision Page

(Section) Description

1

(Mar-2011) 34

34

34

44 Section 5.5.2.2, Heat gains including 15% margin are changed from “23,000” to “21,000”.

45 Section 5.5.2.2, Additional cooling load is changed from “4,000” to “6,000”.

46

46

Page 7: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 6 of 37)

Revision Page

(Section) Description

1

(Mar-2011)

53

Section 5.6.1, Replaced “The required airflow to establish a -1/4 inch w.g. pressure in the penetration areas and the safeguard component areas within 180 seconds with respect to adjacent areas is calculated by equation 4.1-4.” with “The required airflow to establish a -0.4 inch w.g. pressure in the penetration areas and the safeguard component areas within 180 seconds with respect to adjacent areas is calculated by equation 4.1-4.”

54

Section 5.6.1: - Remove the “Volume decrease in the penetration areas (ΔV) is: ΔV = 3.14 x {(78.92 + 0.018)2 – 78.922} x 75.75 = 675.85, USE 675.9 ft3 CV expansion effect (ΔP) is: ΔP = 407 x {411,022 / (411,022-675.9) - 1 } = 0.67, USE 0.8 in. w.g.”.

55 Section 6: - Replaced “[2] “ASHRAE Handbook Fundamentals-1981,” ASHRAE” with “[2] “ASHRAE Handbook Fundamentals-2005,” ASHRAE”.

56

56

56

56

56

56

Page 8: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 7 of 37)

Revision Page

(Section) Description

1

(Mar-2011) 56

56

56

56

57

57

57

57

57

57

Page 9: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 8 of 37)

Revision Page

(Section) Description

1

(Mar-2011)

58

58

58

Page 10: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 9 of 37)

Revision Page

(Section) Description

1

(Mar-2011)

58

58

58

Page 11: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 10 of 37)

Revision Page

(Section) Description

1

(Mar-2011)

58

58

58

58

Page 12: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 11 of 37)

Revision Page

(Section) Description

1

(Mar-2011)

58

Page 13: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 12 of 37)

Revision Page

(Section) Description

1

(Mar-2011)

58

58

58

Page 14: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 13 of 37)

Revision Page

(Section) Description

1

(Mar-2011) 58

59

59

59

59

59

59

Page 15: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 14 of 37)

Revision Page

(Section) Description

1

(Mar-2011) 59

59

59

59

60

Page 16: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 15 of 37)

Revision Page

(Section) Description

1

(Mar-2011)

60

60

Page 17: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 16 of 37)

Revision Page

(Section) Description

1

(Mar-2011)

60

61

61

61

61

61

61

61

Page 18: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 17 of 37)

Revision Page

(Section) Description

1

(Mar-2011) 62

62

63

63

65

69

69

Page 19: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 18 of 37)

Revision Page

(Section) Description

1

(Mar-2011) 69

69

73

74

75

76

77

82

2

(Mar-2013) Abstract Add the new description at the last of paragraph.

1 Add the new description at the last of paragraph.

4 Table 2.2-1: - Add the Room of “Class 1E MOV Inverter Room” and “Cable Tray Area.”

6

6

6

6

Page 20: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 19 of 37)

Revision Page

(Section) Description

2

(Mar-2013) 6

6

6

6

6

6

6

6

7

7

10

12

12

Page 21: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 20 of 37)

Revision Page

(Section) Description

2

(Mar-2013) 13

Table 3-1: - System Component Capacity (Sheet 1 of 3) in Unit Airflow Capacity of Class 1E Electrical Room Air Handling Unit (train A, B) is changed from “40,000” to “42,000.”

- System Component Capacity (Sheet 1 of 3) in Unit Airflow Capacity of Class 1E Electrical Room Air Handling Unit (train C,D) is changed from “52,000” to “54,400.”

13

Table 3-1: - System Component Capacity (Sheet 1 of 3) in Cooling Coil Capacity of Class 1E Electrical Room Air Handling Unit (train A, B) is changed from “1,650,000” to “1,760,000.”

- System Component Capacity (Sheet 1 of 3) in Cooling Coil Capacity of Class 1E Electrical Room Air Handling Unit (train C, D) is changed from “2,290,000” to “2,400,000.”

13

Table 3-1: - System Component Capacity (Sheet 1 of 3) in Fan Airflow Capacity of Class 1E Battery Room Exhaust Fan is changed from “2,600” to “3,200.”

13

Table 3-1: - System Component Capacity (Sheet 1 of 3) in Fan Airflow Capacity of Class 1E Electrical Room Return Air Fan (train A, B) is changed from “37,400” to “39,100.”

- System Component Capacity (Sheet 1 of 3) in Fan Airflow Capacity of Class 1E Electrical Room Return Air Fan (train C, D) is changed from “49,400” to “51,200.”

14

Table 3-1: - System Component Capacity (Sheet 2 of 3) in Cooling Coil Capacity of EFW Pump (Motor-Driven) Area Air Handling Unit is changed from “110,000” to “115,000.”

14

Table 3-1: - System Component Capacity (Sheet 2 of 3) in Unit Airflow Capacity of EFW Pump (Turbine-Driven) Area Air Handling Unit is changed from “1,300” to “1,400.”

14

Table 3-1: - System Component Capacity (Sheet 2 of 3) in Cooling Coil Capacity of EFW Pump (Turbine-Driven) Area Air Handling Unit is changed from “62,000” to “65,000.”

20 Section 5.1.1.1, Outdoor Air Intake: - Added “A conservative value of 1,800 cfm is used.”

Page 22: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 21 of 37)

Revision Page

(Section) Description

2

(Mar-2013)

21

Section 5.1.2.1, (1) Outdoor Air: - Replaced “Outdoor air intake is 1,800 cfm and enthalpy of outdoor air and return air are 43.3 Btu/lb and 30.0 Btu/lb.”

With “The outdoor air intake is 1,800 cfm and the enthalpy of outdoor air and return air are 43.3 Btu/lb and 29.7 Btu/lb, respectively.”

- Replaced “q = 60 × 0.075 × 1800 × (43.3 –29.7) × 1.15 = 123,890 Btu/h” With“q = 60 × 0.075 × 1800 × (43.3 –29.7) × 1.15 = 126,684 Btu/h.”

- Replaced “During normal operation, two AHUs are in operation. Thus, the cooling load per one AHU is to be 61,945 Btu/h, USE 62,000 Btu/h per unit.”

with “During normal operation, two AHUs are in operation. Thus, the cooling load per one AHU is to be 63,342 Btu/h. A conservative value of 64,000 Btu/h is used.”

21

Section 5.1.2.1, (3) Heat Gains: - Replaced “Heat gains for CRE including 15% margin are 242,000 Btu/h obtained from Table 5.1.1-1

During normal plant operation, two AHUs are in operation. Thus, The cooling load per one AHU is to be 121,000 Btu/h per unit.”

With “Heat gains for the CRE including 15% margin are 228,000 Btu/h obtained from Table 5.1.1-1

During normal plant operation, two AHUs are in operation. Thus, the cooling load per one AHU is to be 114,000 Btu/h per unit.”

21

Section 5.1.2.1, (4) Humidification: - Replaced “When inside of Main Control Room is humidified from 51.9% RH as initial condition to 60% RH, Heat gain due to humidification is calculated by equation 4.2-3. Airflow rate is 20,000 cfm and enthalpy before humidification and after humidification are 28.3 Btu/h and 30.0 Btu/h.”

With “The Main Control Room heat gain due to humidification from an initial condition of 52.6% RH as initial condition to 60% RH, Heat gain due to humidification is calculated by equation 4.2-3. Airflow rate is 20,000 cfm and enthalpy before humidification and after humidification are 28.2 Btu/h and 29.7 Btu/h, respectively.”

- Replaced “q = 60 × 0.075 × 20000 × (30.0 - 28.3) × 1.15 = 175,950 Btu/h” with “q = 60 × 0.075 × 20000 × (29.7 - 28.2) × 1.15 = 155,250 Btu/h.”

21

Section 5.1.2.1, (4) Humidification: - Replaced “Thus, the cooling load per one AHU is to be 88,000 Btu/h per unit.” with “Thus, the cooling load per one AHU is to be 78,000 Btu/h per unit.”

Page 23: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 22 of 37)

Revision Page

(Section) Description

2

(Mar-2013)

22 Section 5.1.2.1, (5) Additional Cooling Load (Additional margin): - Replaced “Additional cooling load (additional margin) is 11,000 Btu/h” with “Additional cooling load (additional margin) is 26,000 Btu/h.”

22

23

23

Page 24: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 23 of 37)

Revision Page

(Section) Description

2

(Mar-2013)

23

23

Section 5.1.2.2, (1) Outdoor Air: - Replaced “Outdoor air intake is 1,200 cfm, enthalpy of outdoor air and return air are 43.3 Btu/lb and 28.2 Btu/lb”

with “Outdoor air intake is 1,200 cfm, while the enthalpy of outdoor air and return air are 43.3 Btu/lb and 28.1 Btu/lb.”

- Replaced “q = 60 × 0.075 × 1200 × (43.3 – 28.2) × 1.15 = 93,771 Btu/h” with “q = 60 × 0.075 × 1200 × (43.3 –28.1) × 1.15 = 94,392 Btu/h.”

- Replaced “Thus, the cooling load per one AHU is to be 46,886 Btu/h, USE 47,000 Btu/h per unit” with “Thus, the cooling load per one AHU is to be 47,196 Btu/h. A conservative value of 48,000 Btu/h is used.”

24

Section 5.1.2.2, (4) Heat Gains: - Replaced “Heat gains for CRE including 15% margin are 242,000 Btu/h obtained from Table 5.1.1-1.” with “Heat gains for CRE including 15% margin are 228,000 Btu/h obtained from Table 5.1.1-1.”

- Replaced “During emergency pressurization mode operation, two AHUs are in operation. Thus, The cooling load per one AHU is to be 121,000 Btu/h.” with “During emergency pressurization mode operation, two AHUs are in operation. Thus, the cooling load per one AHU is to be 114,000 Btu/h.”

24 Section 5.1.2.2, (6) Additional Cooling Load (Additional margin): - Replaced “Additional cooling load (additional margin) is 22,000 Btu/h” with “Additional cooling load (additional margin) is 28,000 Btu/h.”

Page 25: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 24 of 37)

Revision Page

(Section) Description

2

(Mar-2013) 25

26

26

26

26

Page 26: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 25 of 37)

Revision Page

(Section) Description

2

(Mar-2013)

27

27

Section 5.2.1, Outdoor Air Intake Requirement: - Replaced “Outdoor air intake requirement is to be approximately 2,600 cfm obtained from CERVS calculation sheet. Therefore, the Class 1E battery room exhaust fan capacity is to be determined as 2,600 cfm”

with “Outdoor air intake requirement is to be approximately 3,200 cfm obtained from the CERVS calculation sheet. Therefore, the Class 1E battery room exhaust fan capacity is to be determined as 3,200 cfm.”

28

Section 5.2.1, Class 1E Electrical Room AHU Airflow Requirements: - Replaced “Therefore, airflow capacity for train A&B AHUs is 40,000 cfm, and for train C&D AHUs is 52,000 cfm”

with “Therefore, airflow capacity for train A&B AHUs is 42,300 cfm, and for train C&D AHUs is 54,400 cfm.”

28

Section 5.2.1, Class 1E Electrical Room Return Air Fan Capacity: - Replaced “Therefore, A,B-Class 1E Electrical Room return air fan capacity is to be 37,400 cfm, and C,D-Class 1E Electrical Room return air fan capacity is to be 49,400 cfm”

with “Therefore, A,B-Class 1E Electrical Room return air fan capacity is to be 39,100 cfm, and C,D-Class 1E Electrical Room return air fan capacity is to be 51,200 cfm.”

Page 27: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 26 of 37)

Revision Page

(Section) Description

2

(Mar-2013)

28

Section 5.2.2.1 (1) Outdoor Air: - Replaced “Outdoor air intake is 2,600 cfm and enthalpy of outdoor air and return air are 43.3 Btu/lb and 29.5 Btu/lb”

with “Outdoor air intake is 3,200 cfm and enthalpy of outdoor air and return air are 43.3 Btu/lb and 29.3 Btu/lb, respectively.”

- Replaced “q = 60 × 0.075 × 2600 × (43.3 – 29.5) × 1.15 = 185,679 Btu/h, USE 186,000 Btu/h”

with “q = 60 × 0.075 × 2600 3,200 × (43.3 –29.3) × 1.15 = 231,840 Btu/h. A conservative value of 232,000 Btu/h is used.”

28

Section 5.2.2.1 (2.1) AHU Fan Motor: - Replaced “Airflow rate requirement is 40,000 cfm” with “Airflow rate requirement is 42,300 cfm.”

- Replaced “q = 2545 × 0.000157 × 11 × 40000 / (0.7 × 0.9) × 1.15 = 320,920 Btu/h, USE 321,000 Btu/h”

with “q = 2545 × 0.000157 × 11 × 42,300 / (0.7 × 0.9) × 1.15 = 339,373 Btu/h. A conservative value of 340,000 Btu/h is used.”

29

Section 5.2.2.1 (2.2) Return Air Fan Motor: - Replaced “Airflow rate requirement is 37,400 cfm” with “Airflow rate requirement is 39,100 cfm.”

- Replaced “q = 2545 × 0.000157 × 2.4 × 37400 / (0.55 × 0.9) × 1.15 = 83,323 Btu/h, USE 84,000 Btu/h”

with “q = 2545 × 0.000157 × 2.4 ×39,100 / (0.55 × 0.9) × 1.15 = 87,110 Btu/h. A conservative value of 88,000 Btu/h is used.”

- Replaced “Therefore, total cooling load of fan motors is 405,000 Btu/h” with “Therefore, total cooling load of fan motors is 428,000 Btu/h.”

29

Section 5.2.2.1 (3) Heat Gains: - Replaced “Heat gains including 15% margin are 966,000 Btu/h obtained from Table 5.2.1-1” with “Heat gains including 15% margin are 992,000 Btu/h obtained from Table 5.2.1-1.”

29 Section 5.2.2.1 (4) Additional Cooling Load (Additional margin): - Replaced “Additional cooling load (additional margin) is 93,000 Btu/h” with “Additional cooling load (additional margin) is 108,000 Btu/h.”

- Replaced “Total cooling load = (1)+(2)+(3)+(4) = 1,650,000 Btu/h” with “Total cooling load = (1)+(2)+(3)+(4)= 1,760,000 Btu/h.”

29

Page 28: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 27 of 37)

Revision Page

(Section) Description

2

(Mar-2013)

30

30

30

31

Section 5.2.2.2 (1) Outdoor Air: - Replaced “Outdoor air intake is 2,600 cfm. Enthalpy of outdoor air and return air are 43.3 Btu/lb and 30.3 Btu/lb” with “Outdoor air intake is 3,200 cfm. Enthalpy of outdoor air and return air are 43.3 Btu/lb and 30.1 Btu/lb, respectively.”

- Replaced “q = 60 × 0.075 × 2600 × (43.3 – 30.3) × 1.15 = 174,915 Btu/h, USE 175,000 Btu/h” with “q = 60 × 0.075 ×3,200 × (43.3 –30.1) × 1.15 = 218,592 Btu/h. A conservative value of 219,000 Btu/h is used.”

Page 29: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 28 of 37)

Revision Page

(Section) Description

2

(Mar-2013) 31

Section 5.2.2.2 (2.1) AHU Fan Motor: - Replaced “Airflow rate requirement is 52,000 cfm” with “Airflow rate requirement is 54,400 cfm.”

- Replaced “q = 2545 × 0.000157 × 11 × 52000 / (0.7 × 0.9) × 1.15 = 417,197 Btu/h, USE 418,000 Btu/h” with “q = 2545 × 0.000157 × 11 × 54,400 / (0.7 × 0.9) × 1.15 = 436,452 Btu/h. A conservative value of 437,000 Btu/h is used.”

31

Section 5.2.2.2 (2.2) Return Air Fan: - Replaced “Airflow rate requirement is 49,400 cfm” with “Airflow rate requirement is 51,200 cfm.”

- Replaced “q = 2545 × 0.000157 × 2.4 × 49400 / (0.55 × 0.9) × 1.15 =110,057 Btu/h, USE 111,000 BTU/h” with “q = 2545 × 0.000157 × 2.4 × 51,200 / (0.55 × 0.9) × 1.15 =114,067 Btu/h. A conservative value of 115,000 Btu/h is used.”

- Replaced “Therefore, total cooling load of fan motors is 529,000 Btu/h” with “Therefore, total cooling load of fan motors is 552,000 Btu/h.”

31

Section 5.2.2.2 (3) Heat Gains: - Replaced “Heat gains including 15% margin are 1,465,000 Btu/h” with “Heat gains including 15% margin are 1,492,000 Btu/h.”

- Replaced “(Train C: 973,000 Btu/h (Table 5.2.1-2), Train D: 492,000 Btu/h (Table 5.2.1-1))” with “(Train C: 465,000 Btu/h (Table 5.2.1-1), Train D: 1,027,000 Btu/h (Table 5.2.1-2)).”

32 Section 5.2.2.2 (3) Heat Gains: - Replaced “Additional cooling load (additional margin) is 121,000 Btu/h” with “Additional cooling load (additional margin) is 137,000 Btu/h.”

- Replaced “Total cooling load = (1)+(2)+(3)+(4) = 2,290,000 Btu/h” with “Total cooling load = (1)+(2)+(3)+(4)= 2,400,000 Btu/h.”

32

32

Page 30: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 29 of 37)

Revision Page

(Section) Description

2

(Mar-2013)

33

33

33

34

Section 5.3.2 (1) Fan Motors: - Replaced “q = 2545 × 0.000157 × 5 × 5000 / (0.7 × 0.9) × 1.15 = 18,234 Btu/h, USE 19,000 Btu/h” with “q = 2545 × 0.000157 × 5 × 5000 / (0.7 × 0.9) × 1.15 = 18,234 Btu/h. A conservative value of 19,000 Btu/h is used.”

34

Section 5.3.2 (2) Internal Heat Gain (Except for Fan Motors): - Replaced “Heat gain from equipment, piping, lighting, and structure is 109,498 Btu/h obtained from Table 5.3.1-1. USE 126,000 Btu/h added the 15% margin (16,502 Btu/h)” with “Heat gain from equipment, piping, lighting, and structure is 109,322 Btu/h obtained from Table 5.3.1-1. A conservative value of 126,000 Btu/h including the 15% margin (16,678 Btu/h).”

Page 31: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 30 of 37)

Revision Page

(Section) Description

2

(Mar-2013) 36

37 Section 5.4 Emergency Feedwater Pump Area HVAC System (EFWPAVS):

- Replaced “Table 5.4-1” with “Table 5.4.1-1.”

37

Section 5.4.1 Outdoor Air Intake: - Replaced “Total required ventilation airflow is to be 85 cfm per EFW pump (turbine-driven) area Table 5.4-1” with “Total required ventilation airflow is to be 87 cfm per EFW pump (turbine-driven) area Table 5.4.1-1.”

37 Section 5.4.1 Cooling Airflow Requirements: - Replaced “Table 5.4-1” with “Table 5.4.1-1.”

37

Section 5.4.1 AHU Airflow Requirements: - Replaced “Total cooling airflow for motor-driven and turbine-driven area is 2,100 cfm and 1,300 cfm (See Table 5.4-1)” with “Total cooling airflow for motor-driven and turbine-driven area is 2,100 cfm and 1,400 cfm (See Table 5.4.1-1).”

38

Section 5.4.2.1 (2) Internal Heat Gains: - Replaced “Heat gain from pumps, piping and supports, lighting and concrete walls, including 15% margin, is 105,000 Btu/h obtained from Table 5.4-1.” with “Heat gain from pumps, piping and supports, lighting and concrete walls, including 15% margin, is 109,000 Btu/h obtained from Table 5.4.1-1.”

38 Section 5.4.2.1 (3) Additional Cooling Load (Additional margin): - Replaced “Additional cooling load (additional margin) is 1,900 Btu/h” with “Additional cooling load (additional margin) is 2,900 Btu/h”.

- Replaced “Total cooling load = (1)+(2)+(3) = 110,000 Btu/h” with “Total cooling load = (1)+(2)+(3) = 115,000 Btu/h.”

38

39

Page 32: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 31 of 37)

Revision Page

(Section) Description

2

(Mar-2013)

39

39

Section 5.4.2.2 (1) Outdoor Air: - Replaced “Heat gain from outdoor is calculated by equation 4.2-1. Outdoor air intake is 100 cfm, enthalpy of outdoor air and return air are 43.3 Btu/lb and 35.6 Btu/lb” with “Heat gain from outdoor air is calculated by equation 4.2-1. Outdoor air intake is 100 cfm, enthalpy of outdoor air and return air are 43.3 Btu/lb and 35.3 Btu/lb.”

- Replaced “q = 60 × 0.075 × 100 × (43.3 – 35.6) × 1.15 = 3,985 Btu/h” with “q = 60 × 0.075 × 100 × (43.3 –35.3) × 1.15 = 4,140 Btu/h.”

- Replaced “Thus, the cooling load per one AHU is to be 4,000 Btu/h.” with “Thus, the cooling load per one AHU is to be 5,000 Btu/h.”

39

Section 5.4.2.2 (2) Fan Motors: - Replaced “Airflow rate requirement is 1,300 cfm” with “Airflow rate requirement is 1,400 cfm”.

- Replaced “q = 2545 × 0.000157 × 2 × 1300 / (0.7 × 0.9) × 1.15 = 1,896 Btu/h” with “q = 2545 × 0.000157 × 2 × 1400 / (0.7 × 0.9) × 1.15

= 2,042 Btu/h”. - Replaced “Thus, cooling load of fan motor is 2,000 Btu/h” with “Thus, cooling load of the fan motor is 3,000 Btu/h.”

39

Section 5.4.2.2 (3) Internal Heat Gains: - Replaced “Heat gain from pumps, piping and supports, lighting and concrete walls, including 15% margin, is 54,000 Btu/h obtained from Table 5.4-1”

with “Heat gain from pumps, piping and supports, lighting and concrete walls, including 15% margin, is 57,000 Btu/h obtained from Table 5.4.1-1.”

Page 33: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 32 of 37)

Revision Page

(Section) Description

2

(Mar-2013)

40 Section 5.4.2.2 (4) Additional Cooling Load (Additional margin): - Replaced “Additional cooling load (additional margin) is 2,000 Btu/h” with “Additional cooling load (additional margin) is 0 Btu/h.”

- Replaced “Total cooling load = (1)+(2)+(3)+(4) = 62,000 Btu/h” with “Total cooling load = (1)+(2)+(3)+(4) = 65,000 Btu/h.”

40

40

41

41

41

41 Section 5.5 Safety Related Component Area HVAC System (SRCAVS): - Replaced “Table 5.5-1” with “Table 5.5.1-1.”

Page 34: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 33 of 37)

Revision Page

(Section) Description

2

(Mar-2013) 41

Section 5.5.1 Cooling Airflow Requirements: - Replaced “Table 5.5-1” with “Table 5.5.1-1.”

41 Section 5.5.1 AHU Airflow Requirements: - Replaced “Table 5.5-1” with “Table 5.5.1-1.”

42 Section 5.5.2.1 (2) Heat Gains: - Replaced “Table 5.5-1” with “Table 5.5.1-1.”

43

44 Section 5.5.2.2 (2) Heat Gains: - Replaced “Heat gains including 15% margin are 21,000 Btu/h obtained from Table 5.5-2” with “Heat gains including 15% margin are 23,000 Btu/h obtained from Table 5.5.1-2.”

44

45

45

46

47

Section 5.5.2.4 (2) Heat Gains: - Replaced “Heat gains including 15% margin are 285,000 Btu/h obtained from Table 5.5-4” with “Heat gains including 15% margin are 281,000 Btu/h obtained from Table 5.5.1-4.”

Page 35: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 34 of 37)

Revision Page

(Section) Description

2

(Mar-2013) 47 New paragraph is added in 5.5.2.4.

47 Section 5.5.2.4 (4) Additional Cooling Load (Additional margin): - Replaced “Additional cooling load (additional margin) is 26,000 BTU/h” with “Additional cooling load (additional margin) is 18,000 BTU/h.”

- Replaced “Total cooling load = (1)+(2)+(3) = 330,000 Btu/h” with “Total cooling load = (1)+(2)+(3)+(4) = 330,000 Btu/h.”

47

48

48

48

48

Page 36: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 35 of 37)

Revision Page

(Section) Description

2

(Mar-2013)

49

49 Section 5.5.2.5 (2) Heat Gains: - Replaced “Table 5.5-5” with “Table 5.5.1-5.”

50

51 Section 5.5.2.6 (2) Heat Gains: - Replaced “Table 5.5-6” with “Table 5.5.1-6.”

52

52

Section 5.6.1: - Replaced “V: Volume in the penetration area 411,022 ft3” with “V: Volume in the penetration area 409,249 ft3.”

- Replaced “ΔP = 407 x {411,022 / (411,022-675.9) - 1 } = 0.67, USE 0.8 in. w.g” with “ΔP = 407 x {409,249 / (409,249-675.9) - 1 } = 0.67. A conservative value of 0.8 in. w.g. is used.”

- Added “A conservative value of 675.9 ft3 is used.” after “∆V = =3.14 x {(78.92 + 0.018)2 – 78.922} x 75.75 = 675.85.”

- Added “A conservative value of 0.018 ft is used.” after “∆R = 68 x 76.752 / (4,769 x 103 x 4.33) x (1 – 0.17/2) = 0.0177.”

- Replaced “ ( )( ) 1,500

13018040740.80.460Q +

−⋅⋅+⋅

=022,11 = 2954.23”

with “ ( )

( ) 1,500130180407409,2490.80.460Q +

−⋅⋅+⋅

= = 2947.96.”

- Replaced “V: Volume of safeguard component areas, 312,426 ft3” with “V: Volume of safeguard component areas, 311,819 ft3”.

- Replaced “ ( )( ) 1,500

130180407312,42600.460Q +−⋅⋅+⋅

= = 1868.46”

with “ ( )

( ) 1,500130180407

311,81900.460Q +−⋅⋅+⋅

= = 1867.74.”

Page 37: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 36 of 37)

Revision Page

(Section) Description

2

(Mar-2013) 56

57

57

58

59

60

61

62

63

64

65

66

67

68

68

69

70

71

Page 38: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Revision History (Sheet 37 of 37)

Revision Page

(Section) Description

2

(Mar-2013) 71

72

73

74

75

76

77

79

80

82

84

All pages The descriptions in this technical report are revised to provide readability without technical changes.

Page 39: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Ⓒ 2013 MITSUBISHI HEAVY INDUSTRIES, LTD.

All Rights Reserved

This document has been prepared by Mitsubishi Heavy Industries, Ltd. (“MHI”) in connection with the U.S. Nuclear Regulatory Commission’s (“NRC”) licensing review of MHI’s US-APWR nuclear power plant design. No right to disclose, use or copy any of the information in this document, other that by the NRC and its contractors in support of the licensing review of the US-APWR, is authorized without the express written permission of MHI.

This document contains technology information and intellectual property relating to the US-APWR and it is delivered to the NRC on the express condition that it not be disclosed, copied or reproduced in whole or in part, or used for the benefit of anyone other than MHI without the express written permission of MHI, except as set forth in the previous paragraph.

This document is protected by the laws of Japan, U.S. copyright law, international treaties and conventions, and the applicable laws of any country where it is being used.

Mitsubishi Heavy Industries, Ltd. 16-5, Konan 2-chome, Minato-ku

Tokyo 108-8215 Japan

Page 40: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

Abstract

The purpose of this technical report is to present calculations on the heating, cooling and airflow requirements of the safety-related air conditioning, heating, cooling, and ventilation systems of US-APWR. The safety-related air conditioning, heating, cooling, and ventilation systems of US-APWR include the Main Control Room Heating, Ventilation and Air Conditioning (HVAC) System (MCRVS), the Class 1E Electrical Room HVAC System (CERVS), the Safeguard Component Area HVAC System (SCAVS), the Emergency Feedwater Pump Area HVAC System (EFWPAVS), the Safety Related Component Area HVAC System (SRCAVS) and the Annulus Emergency Exhaust System (AEES). This report provides the calculations of the cooling and airflow requirements for the operating mode of each of these air conditioning, heating, cooling, and ventilation system. Some design information such as heat gain from equipment and components will be updated as the design progresses and includes design enhancements outside the scope of standard US-APWR design. This technical report will also be updated when the HVAC system specifications are revised due to heat gain changes identified during the design progression.

Page 41: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. i

Table of Contents List of Tables ........................................................................................................................... iii List of Figures .......................................................................................................................... iv List of Acronyms ...................................................................................................................... v 1. INTRODUCTION ............................................................................................................... 1 2. DESIGN CONDITION........................................................................................................ 2 2.1 Outdoor Air Condition ...................................................................................................... 2 2.2 Room Air Condition ......................................................................................................... 2 2.3 Ventilation Requirement .................................................................................................. 2 2.4 Internal Heat Gains ......................................................................................................... 2

2.4.1 Electrical Boards ....................................................................................................... 2 2.4.2 Lighting ..................................................................................................................... 2 2.4.3 People ...................................................................................................................... 2 2.4.4 Components ............................................................................................................. 2 2.4.5 Piping and Supports ................................................................................................. 2

2.5 Surface Temperature of Exterior Roofs and Walls ........................................................... 2 2.6 Heat Gain or Loss through Roofs, Walls and Floors ........................................................ 3 2.7 Supply Air Temperature ................................................................................................... 3 2.8 Fan Total Pressure .......................................................................................................... 3 2.9 Other Design Consideration ............................................................................................ 3

2.9.1 Safeguard Component Area HVAC System .............................................................. 3 2.9.2 Annulus Emergency Exhaust System ....................................................................... 3

3. SUMMARY OF COMPONENT CAPACITY ..................................................................... 13 4. EQUATION ..................................................................................................................... 16 4.1 Airflow Rate Requirements ............................................................................................ 16

4.1.1 Cooling Airflow Requirements ................................................................................. 16 4.1.2 Ventilation Requirements for Removal of Hydrogen ............................................... 16 4.1.3 Airflow Requirements for AEES .............................................................................. 16

4.2 Heat Gains .................................................................................................................... 17 4.2.1 Outdoor Air or Infiltration Air ................................................................................... 18 4.2.2 Fan in case of Motor in Airstream ........................................................................... 18 4.2.3 Humidification ......................................................................................................... 18

4.3 Air Temperature Rise across Fans and Electrical Heaters ............................................. 18 4.4 Cooling Capacity ........................................................................................................... 19 5. CALCULATIONS ............................................................................................................. 20 5.1 Main Control Room HVAC System (MCRVS) ................................................................ 20

5.1.1 Airflow Requirement ............................................................................................... 20 5.1.2 Cooling Coil Requirement ....................................................................................... 20

5.1.2.1 Normal Operation Mode .................................................................................. 21 5.1.2.2 Emergency Pressurization Mode ..................................................................... 23

5.2 Class 1E Electrical Room HVAC System (CERVS) ....................................................... 27 5.2.1 Airflow Requirement ............................................................................................... 27 5.2.2 Cooling Coil Requirement ...................................................................................... 28

5.2.2.1 A,B-Class 1E Electrical Room Air Handling Unit .............................................. 28 5.2.2.2 C,D-Class 1E Electrical Room Air Handling Unit ............................................. 31

5.3 Safeguard Component Area HVAC System (SCAVS) ................................................... 33 5.3.1 Airflow Requirement ............................................................................................... 33

Page 42: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. ii

5.3.2 Cooling Coil Requirement ....................................................................................... 34 5.4 Emergency Feedwater Pump Area HVAC System (EFWPAVS) .................................... 37

5.4.1 Airflow Requirement ............................................................................................... 37 5.4.2 Cooling Coil Requirement ....................................................................................... 37

5.4.2.1 Motor-Driven Pump Area Air Handling Unit ..................................................... 37 5.4.2.2 Turbine-Driven Pump Area Air Handling Unit .................................................. 39

5.5 Safety Related Component Area HVAC System (SRCAVS) .......................................... 41 5.5.1 Airflow Requirement ............................................................................................... 41 5.5.2 Cooling Coil Requirement ....................................................................................... 42

5.5.2.1 Essential Chiller Unit Area AHU Cooling Coil .................................................. 42 5.5.2.2 CCW Pump Area AHU Cooling Coil ................................................................ 43 5.5.2.3 Charging Pump Area AHU Cooling Coil .......................................................... 45 5.5.2.4 Penetration Area AHU Cooling Coil ................................................................. 47 5.5.2.5 Annulus Emergency Exhaust Filtration Unit Area AHU Cooling Coil ................ 49 5.5.2.6 Spent Pump Pit Area AHU Cooling Coil .......................................................... 51

5.6 Annulus Emergency Filtration System (AEES) .............................................................. 52 5.6.1 Airflow Requirement for Penetration Areas ............................................................. 52 5.6.2 Airflow Requirement for Safeguard Component Areas ........................................... 53 5.6.3 Annulus Emergency Exhaust Fan EFU Airflow Requirements ................................ 54

6. REFERENCE .................................................................................................................. 55

Page 43: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. iii

List of Tables

Table 2.2-1 Conditioned Air Design Values 4 Table 2.3-1 Ventilation Requirements 5 Table 2.4.1-1 Heat Gain from Electrical Boards 6 Table 2.4.2-1 Heat Gain from Lighting 7 Table 2.4.4-1 Heat Gain from Components 8 Table 2.4.5-1 Heat Gain from Piping and Supports 9 Table 2.5-1 Surface Temperature of Exterior Roofs and Walls 9 Table 2.6-1 Thermal Insulation Properties 10 Table 2.7-1 Supply Air Temperature 10 Table 2.8-1 Fan Total Pressure 11 Table 2.9-1 Specific Design Conditions of SCAVS 11 Table 2.9-2 Specific Design Conditions of AEES 12 Table 3-1 System Component Capacity 13 Table 5.1.1-1 MCRVS Calculation Sheet 56 Table 5.1.2-1 MCRVS Return Air Temperature Condition (Normal Operation

Mode) 57

Table 5.1.2-2 MCRVS Return Air Temperature Condition (Emergency Pressurization Mode)

57

Table 5.2.1-1 CERVS Calculation Sheet 58 Table 5.2.1-2 Cooling and Heating Loads in Non-Safety Related Portion of

CERVS Train-D following Accident Condition 59

Table 5.2.2-1 CERVS Return Air Temperature 60 Table 5.3.1-1 SCAVS Cooling and Heating Loads 61 Table 5.3.1-2 SCAVS Calculation Sheet (During Normal Operation Severed by

AUXVS) 62

Table 5.3.1-3 SCAVS Calculation Sheet (During Abnormal Plant Operation) 63 Table 5.3.1-4 SCAVS Airflow Ratio of Normal to Abnormal Operation 64 Table 5.3.2-1 SCAVS Return Air Temperature Condition 65 Table 5.4.1-1 EFWPAVS Calculation Sheet 66 Table 5.4.2-1 EFWPAVS Return Air Temperature Condition 67 Table 5.5.1-1 SRCAVS (Essential Chiller Unit Area) Calculation Sheet 68 Table 5.5.1-2 SRCAVS (CCW Pump Area) Calculation Sheet 68 Table 5.5.1-3 SRCAVS (Charging Pump Area) Calculation Sheet 69 Table 5.5.1-4 SRCAVS (Annulus Area) Calculation Sheet 70 Table 5.5.1-5 SRCAVS (Annulus Emergency Exhaust Filtration Unit Area)

Calculation Sheet 71

Table 5.5.1-6 SRCAVS (Spent Fuel Pit Pump Area) Calculation Sheet 71 Table 5.5.2-1 SRCAVS Return Air Temperature Condition 72

Page 44: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. iv

List of Figures

Figure 5.1-1 MCRVS Psychometric Chart (Normal Operation Mode) 73 Figure 5.1-2 MCRVS Psychometric Chart (Emergency Pressurization Mode) 74 Figure 5.1-3 MCRVS Airflow Distribution Sketch (Emergency Pressurization

Mode) 75

Figure 5.2-1 CERVS Train A&B Psychometric Chart 76 Figure 5.2-2 CERVS Train C&D Psychometric Chart 77 Figure 5.3-1 SCAVS Psychometric Chart 78 Figure 5.4-1 EFWPAVS (Motor-Driven Pump Area) Psychometric Chart 79 Figure 5.4-2 EFWPAVS (Turbine-Driven Pump Area) Psychometric Chart 80 Figure 5.5-1 SRCAVS (Essential Chiller Unit Area) Psychometric Chart 81 Figure 5.5-2 SRCAVS (CCW Pump Area) Psychometric Chart 82 Figure 5.5-3 SRCAVS (Charging Pump Area) Psychometric Chart 83 Figure 5.5-4 SRCAVS (Penetration Area) Psychometric Chart 84 Figure 5.5-5 SRCAVS (Annulus Emergency Exhaust Filtration Unit Area)

Psychometric Chart 85

Figure 5.5-6 SRCAVS (Spent Fuel Pit Pump Area) Psychometric Chart 86

Page 45: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. v

List of Acronyms

The following list defines the acronyms used in this document. AAC Alternate AC ACH Air Change per Hour AEES Annulus Emergency Exhaust System AHU Air Handling Unit ASHARE American Society of Heating, Refrigerating and Air-Conditioning Engineers AUXVS Auxiliary Building HVAC System CCW Component Cooling Water CERVS Class 1E Electrical Room HVAC System CLTD Cooling Load Temperature Differential CRDM Control Rod Drive Mechanism CRE Control Room Envelope CS Containment Spray DB Dry Bulb EFU Emergency Filtration Unit EFW Emergency Feedwater EFWPAVS Emergency Feedwater Pump Area HVAC System ESF Engineered Safety Features FU Filtration Unit HVAC Heating, Ventilation and Air Conditioning System I&C Instrumentation and Control LOCA Loss of Coolant Accident LOOP Loss of Offsite Power LRT Leakage Rate Testing MCR Main Control Room MCRVS Main Control Room HVAC System M-G Motor-Generator R/B Reactor Building RH Relative Humidity RHR Residual Heat Removal RSC Remote Shutdown Console SCAVS Safeguard Component Area HVAC System SFP Spent Fuel Pit SI Safety Injection SRCAVS Safety Related Component Area HVAC System UPS Uninterruptible Power Supply WB Wet Bulb WG Water Gauge

Page 46: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 1

1. INTRODUCTION

This document contains calculations on the cooling and airflow requirement of the safety-related HVAC systems. The safety-related HVAC systems are as follows:

Main Control Room HVAC System (MCRVS)

Class 1E Electrical Room HVAC System (CERVS)

Safeguard Component Area HVAC System (SCAVS)

Emergency Feedwater Pump Area HVAC System (EFWPAVS)

Safety Related Component Area HVAC System (SRCAVS)

Annulus Emergency Exhaust System (AEES)

The information presented in this technical report will be updated in the future as the design progresses; including design enhancements outside the scope of standard US-APWR design. This technical report will also be updated when the HVAC system specifications are changed due to heat gain changes identified during the design progression.

Page 47: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 2

2. DESIGN CONDITION

This chapter summarizes the design conditions for calculating the cooling and airflow requirements of the safety-related HVAC systems.

2.1 Outdoor Air Condition

The safety-related HVAC systems are designed with zero (0) percent exceedance values to accommodate all environmental conditions. The 0% exceedance temperatures are used in the following calculation. 0% exceedance maximum : 115oF (DB) / 80oF (WB)

2.2 Room Air Condition

The conditioned air design values for rooms served by the safety-related HVAC systems are specified in Table 2.2-1.

2.3 Ventilation Requirement

The air ventilation requirements for rooms served by the safety-related HVAC systems are specified in Table 2.3-1. The class 1E battery room exhaust system is designed to maintain the hydrogen concentration below 1% by volume in accordance with Regulatory Guide 1.128 (Reference 1).

2.4 Internal Heat Gains

The internal heat gains from electrical boards, lights, people, and components that can contribute the majority of the cooling load in the building are shown in following sections.

2.4.1 Electrical Boards

The heat gain from the electrical boards in each room is specified in Table 2.4.1-1.

2.4.2 Lighting

The heat gain from lighting for each room is specified in Table 2.4.2-1.

2.4.3 People

The heat gain from people in the control room envelope (CRE) is specified as 350 Btu/h per person.

2.4.4 Components

The heat gain from the components in each room (e.g., thermal heat exchangers and pumps etc.) is shown in Table 2.4.4-1.

2.4.5 Piping and Supports

The heat gain from the piping and its supports in each room is specified in Table 2.4.5-1.

2.5 Surface Temperature of Exterior Roofs and Walls

Page 48: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 3

The values used for determining the conductive heat gain through exterior walls and roofs are specified in Table 2.5-1. The values are based on the Cooling Load Temperature Differential (CLTD) method in the ASHRAE Fundamentals Handbook-1981 (Reference 2), Chapter 26.

2.6 Heat Gain or Loss through Roofs, Walls and Floors

Roofs and walls exposed to outside air are provided with thermal insulation to minimize heat loss from air-conditioned areas. The thermal insulation properties are specified in Table 2.6-1. The effect of the thermal insulation is ignored when the heat gains through roofs and walls are calculated.

2.7 Supply Air Temperature

The supply air temperature provided to each area served by the HVAC systems are specified in Table 2.7-1.

2.8 Fan Total Pressure

The total design pressure of each air handling unit supply fan is specified in Table 2.8-1. This value is used to estimate the air temperature rise across the fan.

2.9 Other Design Consideration

The SCAVS and the AEES are designed to account for these specific design considerations:

The SCAVS connects to the Auxiliary Building HVAC system (AUXVS) supply and exhaust ducts. During normal operation, the AUXVS serves the safeguard component areas via the SCAVS distribution ductwork. During a design basis accident or Loss of Offsite Power (LOOP), the safeguard component areas are cooled by individual safeguard component area air handling units.

The AEES is designed to establish a - 1/4 inch water gauge (WG) pressure in the penetration areas and the safeguard component areas within 240 seconds to mitigate potential leakage to the environment of fission products from the containment following a Loss of Coolant Accident (LOCA).

2.9.1 Safeguard Component Area HVAC System

The following specific design considerations are applied to SCAVS calculations and the specific design values associated with these considerations are summarized in Table 2.9-1.

・ Water leakage from Engineered Safety Features (ESF) components during accident condition

・ Infiltration from surrounding areas during accident condition

・ Use of common distribution ductwork

2.9.2 Annulus Emergency Exhaust System

Specific design conditions applied to the AEES are summarized in Table 2.9-2.

Page 49: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 4

Table 2.2-1 Conditioned Air Design Values

HVAC System Rooms Air Condition

MCRVS Main Control Room (Including sub-room) 73 - 78oF 25 - 60% RH

CERVS

Class 1E I&C Room 68 - 79oF

Remote Shutdown Console Room 73 - 78oF

Class 1E Battery Room 65 - 77oF

MCR/Class 1E Electrical HVAC Equipment Room MCR Emergency Supply Filtration Unit & Fan Room 50 - 130oF

Class 1E Electrical Room Class 1E Battery Charger Room Class 1E UPS Room AAC Selector Circuit Panel Room Reactor Trip Breaker Room M-G Set Room M-G Set Control Panel Room CRDM Cabinet Room LRT Room Class 1E MOV Inverter Room Cable Tray Area

50 - 95oF

SCAVS

SI Pump Room CS/RHR Pump Room CS/RHR Heat Exchanger Room Safeguard Component Area AHU Room R/B Sump Tank Room

50 - 130oF (50 - 105oF) (Note)

EFWPAVS EFW Pump Area 50 - 105oF

SRCAVS

CCW Pump Area Charging Pump Room Penetration Area Annulus Emergency Exhaust Filtration Unit Area Spent Fuel Pit Pump Area

50 - 130oF

Essential Chiller Unit Area 50 - 105oF

Note : During normal plant operation, the safeguards component areas are maintained within this temperature range by the AUXVS through the distribution ductwork of the SCAVS.

Page 50: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 5

Table 2.3-1 Ventilation Requirements

Page 51: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 6

Table 2.4.1-1 Heat Gain from Electrical Boards

Page 52: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 7

Table 2.4.2-1 Heat Gain from Lighting

Page 53: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 8

Table 2.4.4-1 Heat Gain from Components

Page 54: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 9

Table 2.4.5-1 Heat Gain from Piping and Supports

Table 2.5-1 Surface Temperature of Exterior Roofs and Walls

Page 55: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 10

Table 2.6-1 Thermal Insulation Properties

Table 2.7-1 Supply Air Temperature

Page 56: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 11

Table 2.8-1 Fan Total Pressure

Table 2.9-1 Specific Design Conditions of SCAVS

Page 57: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 12

Table 2.9-2 Specific Design Conditions of AEES

Page 58: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 13

3. SUMMARY OF COMPONENT CAPACITY

The safety-related HVAC system component capacity is summarized in Table 3-1.

Table 3-1 System Component Capacity (Sheet 1 of 3)

Main Control Room Air Handling Unit

Unit Airflow Capacity, cfm 10,000 per unit

Cooling Coil Capacity, Btu/h 341,000 per unit

Main Control Room Toilet/Kitchen Exhaust Fan

Fan Airflow Capacity, cfm 1,800 per unit

Main Control Room Smoke Purge Fan

Fan Airflow Capacity, cfm 20,000 per unit

Class 1E Electrical Room Air Handling Unit

Unit Airflow Capacity, cfm 42,300 per unit - train A, B 54,400 per unit - train C, D

Cooling Coil Capacity, Btu/h 1,760,000 per unit - train A, B 2,400,000 per unit - train C, D

Class 1E Battery Room Exhaust Fan

Fan Airflow Capacity, cfm 3,200 per unit

Class 1E Electrical Room Return Air Fan

Fan Airflow Capacity, cfm 39,100 per unit - train A, B 51,200 per unit - train C, D

Safeguard Component Area Air Handling Unit

Unit Airflow Capacity, cfm 5,000 per unit

Cooling Coil Capacity, Btu/h 180,000 per unit

Page 59: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 14

Table 3-1 System Component Capacity (Sheet 2 of 3)

EFW Pump (Motor-Driven) Area Air Handling Unit

Unit Airflow Capacity, cfm 2,100 per unit

Cooling Coil Capacity, Btu/h 115,000 per unit

EFW Pump (Turbine-Driven) Area Air Handling Unit

Unit Airflow Capacity, cfm 1,400 per unit

Cooling Coil Capacity, Btu/h 65,000 per unit

Essential Chiller Unit Area Air Handling Unit

Unit Airflow Capacity, cfm 1,000 per unit

Cooling Coil Capacity, Btu/h 30,000 per unit

CCW Pump Area Air Handling Unit

Unit Airflow Capacity, cfm 1,000 per unit

Cooling Coil Capacity, Btu/h 30,000 per unit

Charging Pump Area Air Handling Unit

Unit Airflow Capacity, cfm 1,000 per unit

Cooling Coil Capacity, Btu/h 10,000 per unit

Penetration Area Air Handling Unit

Unit Airflow Capacity, cfm 5,000 per unit

Cooling Coil Capacity, Btu/h 330,000 per unit

Annulus Emergency Exhaust Filtration Unit Area Air Handling Unit

Unit Airflow Capacity, cfm 1,000 per unit

Cooling Coil Capacity, Btu/h 10,000 per unit

Page 60: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 15

Table 3-1 System Component Capacity (Sheet 3 of 3)

Spent Fuel Pit Pump Area Air Handling Unit

Unit Airflow Capacity, cfm 1,500 per unit

Cooling Coil Capacity, Btu/h 100,000 per unit

Annulus Emergency Exhaust Filtration Unit & Fan

Design flow rate, cfm 5,600 per unit

Page 61: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 16

4. EQUATION

The equations applied to calculate the following requirements are as follows.

4.1 Airflow Rate Requirements

4.1.1 Cooling Airflow Requirements

Cooling airflow requirements are calculated by following equations. These equations are generally used to estimate the airflow rate for cooling.

Q = q / (60 × ρ × Cp × (ti - to)) × α : equation 4.1-1

where, Q : Airflow rate requirements , cfm q : Heat Loads , Btu/h Cp : Specific heat , 0.24 Btu/lb-oF ρ : Density , 0.075 lb/ft3 ti : Design room temperature , oF to : Supply air temperature , oF α : Margin , 1.15

4.1.2 Ventilation Requirements for Removal of Hydrogen

Adequate Class 1E battery room ventilation is required to prevent the accumulation of hydrogen. The required airflow through the battery room is in accordance with BS EN50272-2 (Reference 3). The required ventilation airflow rate is calculated by the following equation:

Q = v × g × s × n × Igas × Cn × 10-3 : equation 4.1-2

where, Q : Airflow rate requirements , cfm v : Necessary dilution of hydrogen g : Hydrogen gas evolution rate , cfm/cell-A s : General safety factor n : Number of cells Igas : Current producing gas in mA per Ah , Amp/Ah ( = Iboost× fg × fs) Iboost : Typical boost charge current , Amp/Ah fg : Gas emission factor fs : Gas emission safety factor Cn : Capacity for lead acid cells , Ah

4.1.3 Airflow Requirements for AEES

The AEES exhaust airflow rate to establish required negative pressure in the penetration areas and the safeguard component areas within the required drawn-down time with respect to adjacent areas is calculated by the following equation.

Page 62: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 17

( )( ) in

f0Q

TTPVΔPP60Q +

−⋅⋅+⋅

= : equation 4.1-4

where, Q : Required airflow , cfm P : Establishing negative pressure , in. w.g. P 0 : Surrounding area ambient pressure (Standard air) , in. w.g. ∆P : CV expansion effect , in. w.g. V : Free volume of penetration and safeguard component areas , ft3

T : Time of establishing the design negative pressure , sec. Tf : Time of reaching fan design airflow rate , sec. Qin : Infiltration to the penetration area and safeguard component area , cfm

CV expansion effect (∆P) is calculated by the following equation.

∆P=P x {V / (V - ∆V) - 1} : equation 4.1-5

where, ∆P : Effect of the expansion of CV , in. w.g. P : Initial pressure , in. w.g. V : Volume in the penetration area , ft3 ∆V : Volume decrease in the penetration area , ft3

Volume decrease (DV) in the penetration areas is calculated by the following equation.

∆V=3.14 x {(Rcvo + DR)2 – Rcvo2} x h : equation 4.1-6

where, ∆V : Volume decrease in the penetration area , ft3 Rcvo : Outside radius of CV , ft ∆R : Radial expansion of CV , ft h : Height of the penetration area , ft

Radial expansion of CV (DR) is calculated by the following equation.

∆R = P x R2 / (E x t) (1 - ν/2) : equation 4.1-7

where, ∆R : Radial expansion of CV , ft P : Internal pressure of CV , psig R : Average radius of CV , ft t : Thickness of CV , ft E : Modulus of elasticity for concrete , ksi ν : Poisson’s ratio

4.2 Heat Gains

This section calculates the heat load from the outdoor intake, infiltration air, fan operation, and humidification.

Page 63: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 18

4.2.1 Outdoor Air or Infiltration Air

Heat gain from outdoor air and infiltration is calculated by the following equation.

q = 60 × ρ × Q × (hi -ho) × α : equation 4.2-1

where, q : Heat gain from outdoor , Btu/h ρ : Density , 0.075 lb/ft3

Q : Outdoor air intake or infiltration air , cfm hi : Enthalpy of outdoor air or infiltration air , Btu/lb ho : Enthalpy of return air or room air , Btu/lb α : Margin , 1.15

4.2.2 Fan in case of Motor in Airstream

Heat gain from the fan motor and drive inside the airstream is calculated by the following equation.

q = 2545 × 0.000157 × H × Q / (hf × ηm) × α : equation 4.2-2

where, q : Fan motor load , Btu/h H : Fan total pressure , in. w.g. Q : Airflow rate requirement , cfm hf : Fan efficiency(Note1) hm : Motor efficiency(Note2) α : Margin , 1.15

Note: 1. Typical centrifugal fan and axial fan efficiency use 0.7 and 0.55. 2. A typical motor efficiency use 0.9.

4.2.3 Humidification

Heat gain due to humidification is calculated by the following equation.

q = 60 × ρ × Q (ho - hi) × α : equation 4.2-3

where, q : Cooling load , Btu/h ρ : Density , 0.075 lb/ft3 Q : Airflow rate , cfm hi : Enthalpy before humidification , Btu/h ho : Enthalpy after humidification , Btu/h α : Margin , 1.15

4.3 Air Temperature Rise across Fans and Electrical Heaters

Page 64: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 19

The outlet air temperature from fan associated with electrical heaters increases when the entering air passes through the electrical heaters. The equations to determine the temperature rise of the entering air temperature is discussed in the following sections.

(a) Temperature Rise across fan

The air temperature rise across fan is calculated by the following equation.

∆t = 2545 × 0.000157 × H / (1.08 x ηf × ηm) : equation 4.3-1

where, ∆t : Temperature rise across fan , oF H : Fan total pressure , in. w.g. ηf : Fan efficiency (Note1) ηm : Motor efficiency (Note2)

Note: 1. Values for typical centrifugal fan and axial fan efficiency of 0.7 and 0.55 are used respectively. 2. A typical value for motor efficiency of 0.9 is used.

(b) Temperature Rise across electrical heaters

The air temperature rise across the electric heater is calculated by the following equation.

to = q / (60 x Q× ρ × Cp) + ti : equation 4.3-2

where, to : Exiting air temperature , oF q : Heat gain from electric heating coil , Btu/h Q : Airflow rate , cfm Cp : Specific heat , 0.24 Btu/lb-oF ρ : Density , 0.075 lb/ft3 ti : Inlet air temperature , oF

4.4 Cooling Capacity

The cooling capacity is calculated by the following equation.

q = 60 × ρ × Q × (hi - ho) ×α : equation 4.4-1

where, q : Cooling requirement , Btu/h ρ : Density , 0.075 lb/ft3 Q : AHU airflow , cfm hi : Enthalpy of cooling coil inlet , Btu/lb ho : Enthalpy of cooling coil outlet , Btu/lb α : Margin , 1.15

Page 65: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 20

5. CALCULATIONS

This chapter contains the calculations for each safety-related HVAC System including the AEES.

5.1 Main Control Room HVAC System (MCRVS)

Table 5.1.1-1 summarizes the MCRVS airflow requirements based on cooling requirements.

5.1.1 Airflow Requirement

Outdoor Air Intake

Outdoor air intake flow is determined in accordance with the requirements shown in Table 2.3-1. Total required ventilation airflow is to be 1,635 cfm shown in Table 5.1.1-1. A conservative value of 1,800 cfm is used.

Exhaust Fan Flow

The toilet/kitchen exhaust fans discharge air from the CRE through the toilet/kitchen area. The exhaust fan is designed to be capable of extracting fresh air equivalent to makeup airflow requirements from the outdoor environment. Therefore, the capacity of the exhaust fan is 1,800 cfm.

Cooling Airflow Requirements

Cooling airflow requirements are calculated by equation 4.1-1. Required cooling airflow for each area is shown in Table 5.1.1-1.

AHU Airflow Requirements

According to the MCRVS calculation sheet (Table 5.1.1-1), total cooling airflow is approximately 20,000 cfm. The MCR supply system consists of 4 units (50% x 4 ). Thus, one AHU airflow capacity is to be 10,000 cfm.

Smoke Purge Fan Airflow Requirement

The MCR HVAC system is designed so that the outside air quantity will be increased to 100 percent of system supply air flow rate during smoke purge operation in accordance with URD (Reference 5). Thus the smoke purge fan is designed to be capable of exhausting a maximum 20,000 cfm purging air from the MCR. The capacity of the main control room smoke purge fan is to be 20,000 cfm.

5.1.2 Cooling Coil Requirement

The conditioned air requirement of the cooling coils is determined for both normal operation mode and the emergency pressurization mode. During emergency pressurization mode operation, the emergency filtration unit electrical heating coils are energized to reduce relative humidity below 70% RH to ensure charcoal adsorber efficiency. Psychrometric charts containing air properties during normal operation and emergency operation are shown in

Page 66: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 21

Figure 5.1-1 and 5.1-2, respectively. The air properties at the cooling coil for normal operation mode is discussed in Subsection 5.1.2.1. The air properties at the cooling coil for Emergency Pressurization Mode is discussed in Subsection 5.1.2.2. The specification of cooling coil capacity is determined by incorporating sufficient margins.

5.1.2.1 Normal Operation Mode

The cooling coil capacity is calculated by summing up the following cooling loads.

(1) Outdoor Air

Heat gain from the outdoor air is calculated by equation 4.2-1. The outdoor air intake is 1,800 cfm and the enthalpy of outdoor air and return air are 43.3 Btu/lb and 29.7 Btu/lb, respectively.

q = 60 × 0.075 × 1800 × (43.3 – 29.7) × 1.15 = 126,684 Btu/h

During normal operation, two AHUs are in operation. Thus, the cooling load per one AHU is to be 63,342 Btu/h. A conservative value of 64,000 Btu/h is used. .

(2) AHU Fan Motors

Heat gain from fan motors is calculated by equation 4.2-2. The airflow rate requirement is 10,000 cfm (Section 5.1.1). Fan total pressure is 8.0 in. w.g. as given in Table 2.8-1. Fan efficiency and motor efficiency used are 0.7 and 0.9, respectively.

q = 2545 × 0.000157 × 8.0 × 10000 / (0.7 × 0.9) × 1.15 = 58,350 Btu/h

Thus, the cooling load of fan motor is 59,000 Btu/h per unit

(3) Heat Gains

Heat gains for the CRE including 15% margin are 228,000 Btu/h obtained from Table 5.1.1-1

During normal plant operation, two AHUs are in operation. Thus, the cooling load per one AHU is to be 114,000 Btu/h per unit.

(4) Humidification

The Main Control Room heat gain due to humidification from an initial condition of 52.6% RH to 60% RH, is calculated by equation 4.2-3. Airflow rate is 20,000 cfm and enthalpy before humidification and after humidification are 28.2 Btu/h and 29.7 Btu/h, respectively.

q = 60 × 0.075 × 20000 × (29.7 - 28.2) × 1.15 = 155,250 Btu/h

During normal operation, two AHUs are in operation. Thus, the cooling load per one AHU is 78,000 Btu/h per unit.

Page 67: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 22

(5) Additional Cooling Load (Additional margin)

Additional cooling load (additional margin) is 26,000 Btu/h

Total cooling load = (1)+(2)+(3)+(4)+ (5) = 341,000 Btu/h

Page 68: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 23

5.1.2.2 Emergency Pressurization Mode

The cooling coil capacity is calculated by summing up the following cooling loads.

(1) Outdoor Air

The heat gain from outdoor is calculated by equation 4.2-1. Outdoor air intake is 1,200 cfm, while the enthalpy of outdoor and return air are 43.3 Btu/lb and 28.1 Btu/lb.

q = 60 × 0.075 × 1200 × (43.3 – 28.1) × 1.15 = 94,392 Btu/h

During emergency pressurization mode operation, two AHUs are in operation. Thus, the cooling load per one AHU is to be 47,196 Btu/h. A conservative value of 48,000 Btu/h is used.

Page 69: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 24

(2) Fan Motors

(2.1) AHU Fan

Heat gain from fan motors is calculated by equation 4.2-2. Airflow rate requirement is 10,600 cfm. Fan total pressure is 8.0 in. w.g. as given in Table 2.8-1. Fan and motor efficiencies of 0.7 and 0.9 are used.

q = 2545 × 0.000157 × 8 × 10600 / (0.7 × 0.9) × 1.15 = 61,851 Btu/h

Thus, cooling load of fan motor is 62,000 Btu/h per unit.

(2.2) EFU Fan

Heat gain from fan motors is calculated by equation 4.2-2. The airflow rate requirement is 3,600 cfm. Fan total pressure is 7.3 in. w.g. as given in Table 2.8-1. Fan efficiency used is 0.7.

q = 2545 × 0.000157 ×7.3 × 3600 / 0.7 × 1.15 = 17,251 Btu/h

Thus, cooling load of fan motor is 18,000 Btu/h per unit.

(3) Electric Heating Coil

Heat gain from MCR EFU electric heating coil is 18kw (61,500 Btu/h). Thus, cooling load of heating coil is 71,000 Btu/h in consideration of 15% margins.

(4) Heat Gains

Heat gains for CRE including 15% margin are 228,000 Btu/h obtained from Table 5.1.1-1.

During emergency pressurization mode operation, two AHUs are in operation. Thus, the cooling load per one AHU is to be 114,000 Btu/h.

(5) Humidification

Not considered (Humidifier is not operated during emergency pressurization mode operation)

(6) Additional Cooling Load (Additional margin)

Additional cooling load (additional margin) is 28,000 Btu/h.

Total cooling load = (1)+(2)+ (3)+(4)+(5)+(6) = 341,000 Btu/h

Page 70: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 25

Page 71: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 26

Page 72: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 27

5.2 Class 1E Electrical Room HVAC System (CERVS)

Table 5.2-1 summarizes the CERVS airflow requirements based on cooling requirements.

5.2.1 Airflow Requirement

Class 1E Battery Room Exhaust Fan Airflow Requirement

1) Ventilation Requirements for Removal of Hydrogen

Required ventilation airflow rate is calculated by equation 4.1-2. Calculation condition is as follows.

Necessary dilution of hydrogen v = 99 Hydrogen gas evolution rate g = 0.000269 cfm/cell-A(Note) General safety factor s = 5 Number of cells n = 120(60 × 2) Current producing gas in mA per Ah Igas = 20 Amp/Ah ( = Iboost fg × fs) Typical boost charge current Iboost = 4 Amp/Ah Gas emission factor fg = 1 Gas emission safety factor fs = 5

Capacity for lead acid cells Cn = 2,552 Ah

Note: Hydrogen gas evolution rate is found in IEEE Std.484TM-2002 (Reference 4).

accordingly,

Q = 99 × 0.000269 × 5 × 120 × 20 × 2552 × 10-3 = 815.5 cfm

Thus, ventilation requirement for removal hydrogen is to be minimum 900 cfm.

Outdoor Air Intake Requirement

Outdoor air intake requirement is to be approximately 3,200 cfm obtained from the CERVS

Page 73: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 28

calculation sheet. Therefore, the Class 1E battery room exhaust fan capacity is 3,200 cfm.

Cooling Airflow Requirements

Cooling airflow requirements are calculated by equation 4.1-1. Required cooling airflow for each area is shown in Table 5.2.1-1.

Class 1E Electrical Room AHU Airflow Requirements

The CERVS consists of four trains, each is sized to satisfy 100% of the cooling and heating demand of two trains, i.e., train A or B can provide cooling and heating for both trains A & B, and train C or D can provide cooling and heating for both train C & D. Therefore, airflow capacity for train A&B AHUs is 42,300 cfm, and for train C&D AHUs is 54,400 cfm ( See Table 5.2.1-1).

Class 1E Electrical Room Return Air Fan Capacity

Class 1E Electrical Room return air fan capacity is based on AHUs airflow capacity and exhaust fan capacity. Therefore, A,B-Class 1E Electrical Room return air fan capacity is to be 39,100 cfm, and C,D-Class 1E Electrical Room return air fan capacity is to be 51,200 cfm.

5.2.2 Cooling Coil Requirement

5.2.2.1 A,B-Class 1E Electrical Room Air Handling Unit

The cooling coil capacity is calculated by summing up the following cooling loads.

(1) Outdoor Air

Heat gain from outdoor air is calculated by equation 4.2-1. Outdoor air intake is 3,200 cfm and enthalpy of outdoor air and return air are 43.3 Btu/lb and 29.3 Btu/lb, respectively.

q = 60 × 0.075 × 3,200 × (43.3 – 29.3) × 1.15 = 231,840 Btu/h. A conservative value of 232,000 Btu/h is used.

(2) Fan Motors

(2.1) AHU Fan Motor

Heat gain from AHU fan motors is calculated by equation 4.2-2. Airflow rate requirement is 42,300 cfm. Fan total pressure is 11.0 in. w.g. as given in Table 2.8-1. Fan efficiency and motor efficiency used are 0.7 and 0.9, respectively.

q = 2545 × 0.000157 × 11 × 42,300 / (0.7 × 0.9) × 1.15 = 339,373 Btu/h. A conservative value of 340,000 Btu/h is used.

(2.2) Return Air Fan Motor

Heat gain from the return air fan motors is calculated by equation 4.2-2. Airflow rate requirement is 39,100 cfm. Fan total pressure is 2.4 in. w.g. as given in Table 2.8-1. Fan

Page 74: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 29

efficiency and motor efficiency used are 0.55 and 0.9, respectively.

q = 2545 × 0.000157 × 2.4 × 39,100 / (0.55 × 0.9) × 1.15 = 87,110 Btu/h. A conservative value of 88,000 Btu/h is used.

Therefore, total cooling load of fan motors is 428,000 Btu/h

(3) Heat Gains

Heat gains including 15% margin are 992,000 Btu/h obtained from Table 5.2.1-1.

(4) Additional Cooling Load (Additional margin)

Additional cooling load (additional margin) is 108,000 Btu/h

Total cooling load = (1)+(2)+(3)+(4) = 1,760,000 Btu/h

Page 75: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 30

Page 76: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 31

5.2.2.2 C,D-Class 1E Electrical Room Air Handling Unit

The cooling coil capacity is calculated by summing up the following cooling loads.

(1) Outdoor Air

Heat gain from outdoor air is calculated by equation 4.2-1. Outdoor air intake is 3,200 cfm. Enthalpy of outdoor air and return air are 43.3 Btu/lb and 30.1 Btu/lb, respectively.

q = 60 × 0.075 × 3,200 × (43.3 – 30.1) × 1.15 = 218,592 Btu/h. A conservative value of 219,000 Btu/h is used.

(2) Fan Motors

(2.1) AHU Fan Motor

Heat gain from fan motors is calculated by equation 4.2-2. Airflow rate requirement is 54,400 cfm. Fan total pressure is 11.0 in. w.g. as given in Table 2.8-1. Fan efficiency and motor efficiency used are 0.7 and 0.9, respectively.

q = 2545 × 0.000157 × 11 × 54,400 / (0.7 × 0.9) × 1.15 = 436,452 Btu/h. A conservative value of 437,000 Btu/h is used.

(2.2) Return Air Fan

Heat gain from fan motors is calculated by equation 4.2-2. Airflow rate requirement is 51,200 cfm. Fan total pressure is 2.4 in. w.g. as given in Table 2.8-1. Fan efficiency and motor efficiency used are 0.55 and 0.9, respectively.

q = 2545 × 0.000157 × 2.4 × 51,200 / (0.55 × 0.9) × 1.15 =114,067 Btu/h. A conservative value of 115,000 Btu/h is used.

Therefore, total cooling load of fan motors is 552,000 Btu/h.

(3) Heat Gains

Heat gains including 15% margin are 1,492,000 Btu/h (Train C: 465,000 Btu/h (Table 5.2.1-1), Train D: 1,027,000 Btu/h (Table 5.2.1-2))

Note: Heat load and loss through structures (concrete walls, floors, and ceilings, etc.) in the Non-Class 1E electrical rooms are calculated by using 1% exceedance values to determine the required airflow rate of tempered air required during normal plant operation. However, if the non-safety portion provides tempered air without system isolation, and the exhaust air returns to the Class 1E electrical room AHUs during accident condition, then the heat load and loss through structures should be calculated using 0% exceedance values. In the calculation for cooling coil demand, the outside air temperature condition for the non-safety portion uses 0% exccedance values. Table 5.2.1-1 summarized the cooling load and heat loss of

Page 77: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 32

non-safety related rooms served by CERVS during abnormal conditions.

(4) Additional Cooling Load (Additional margin)

Additional cooling load (additional margin) is 137,000 Btu/h

Total cooling load = (1)+(2)+(3)+(4) = 2,400,000 Btu/h

Page 78: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 33

5.3 Safeguard Component Area HVAC System (SCAVS)

Table 5.3.1-2 summarizes the SCAVS airflow requirements based on cooling requirement during normal operation. Table 5.3.1-3 summarizes the SCAVS airflow requirements based on cooling requirement during abnormal operation.

5.3.1 Airflow Requirement

Page 79: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 34

Cooling Airflow Requirements

Cooling airflow requirements are calculated by equation 4.1-1. Required cooling airflow for each area during normal plant operation and abnormal plant operation are shown in Table 5.3.1-2 and Table 5.3.1-3. During normal operation, the safeguard component areas are ventilated by the AUXVS. During abnormal operation condition, these areas are served by the SCAVS.

Airflow Ratio of Normal to Abnormal Operation Condition

Required airflow is the difference between normal operation condition and abnormal operation condition. Each required airflow should be determined so that the airflow ratio of normal to abnormal operation condition is around “1.4” because active balancing dampers (Variable Air Volume System) are not provided in the safety related portion of the system. Table 5.3.1-4 shows the airflow ratio.

Airflow Requirements for Normal Plant Operation

During normal plant operation, the AUXVS provides ventilation air of 27,700 cfm to the safeguard component areas (See Table 5.3.1-2).

AHU Airflow Requirements

Total cooling airflow is 5,000 cfm per one unit (See Table 5.3.1-3). .

5.3.2 Cooling Coil Requirement

The cooling coil capacity is calculated by summing up the following cooling loads.

(1) Fan Motors

Heat gain from fan motors is calculated by equation 4.2-2. Airflow rate requirement is 5,000 cfm, fan total pressure is 5.0 in. w.g. given in Table 2.8-1. Fan efficiency and motor efficiency used are 0.7 and 0.9, respectively.

q = 2545 × 0.000157 × 5 × 5000 / (0.7 × 0.9) × 1.15 = 18,234 Btu/h. A conservative value of 19,000 Btu/h is used.

Thus, cooling load of fan motor is 19,000 Btu/h.

(2) Internal Heat Gain (Except for Fan Motors)

Heat gain from equipment, piping, lighting, and structure is 109,322 Btu/h obtained from Table 5.3.1-1. A conservative value of 126,000 Btu/h including the 15% margin (16,678 Btu/h).

(3) Infiltration

Heat load of infiltration is calculated by equation 4.2-1. Infiltration flow is 375 cfm, enthalpy of infiltration air and room air are 47.0 Btu/lb(Note) and 36.4 Btu/lb.

Page 80: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 35

q = 60 × 0.075 × 375 × (47.0 – 36.4) × 1.15 = 20,571 Btu/h

Thus, the cooling load per one AHU is to be 21,000 Btu/h

Note: For the assumed infiltration air condition of 130oF and 0.0141lb/lb' during LOCA events, the enthalpy is 47.0 Btu/lb.

(4) Leakage from ESF Components

When leakage is occurred inside safeguard component areas, the area is humidified by leakage water. Heat gain due to humidification is calculated by equation 4.2-3. Circulation airflow rate is 5,000 cfm. Enthalpy before and after the leakage are 37.5 Btu/lb and 37.2 Btu/lb, respectively.

q = 60 × 0.075 × 5000 × (37.5 – 37.2) × 1.15 = 7,763 Btu/h

Thus, the cooling load per one AHU is to be 8,000 Btu/h

(5) Additional Cooling Load (Additional margin)

Additional cooling load (additional margin) is 6,000 Btu/h

Total cooling load = (1)+(2)+(3)+(4)+ (5) = 180,000 Btu/h

Page 81: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 36

Page 82: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 37

5.4 Emergency Feedwater Pump Area HVAC System (EFWPAVS)

Table 5.4.1-1 summarizes the airflow requirement based on cooling requirements and ventilation requirements.

5.4.1 Airflow Requirement

Outdoor Air Intake

EFW pump (turbine-driven) area is ventilated by dedicated ventilation system that provides fresh air. Outdoor air intake flow is determined in accordance with the ventilation requirements in Table 2.3-1. Total required ventilation airflow is to be 87 cfm per EFW pump (turbine-driven) area Table 5.4.1-1. Thus, EFW pump (turbine-driven) pump area HVAC system provides 100 cfm of fresh air to EFW pump areas.

Cooling Airflow Requirements

Cooling airflow requirements are calculated by equation 4.1-1. Required cooling airflow for each area is shown in Table 5.4.1-1.

AHU Airflow Requirements

Total cooling airflow for motor-driven and turbine-driven area is 2,100 cfm and 1,400 cfm (See Table 5.4.1-1).

5.4.2 Cooling Coil Requirement

5.4.2.1 Motor-Driven Pump Area Air Handling Unit

The cooling coil capacity is calculated by summing up the following cooling loads.

(1) Fan Motors

Heat gain from fan motors is calculated by equation 4.2-2. Airflow rate requirement is 2,100 cfm. Fan total pressure is 2.0 in. w.g. as given in Table 2.8-1. Fan efficiency and motor efficiency used are 0.7 and 0.9, respectively.

q = 2545 × 0.000157 × 2 × 2100 / (0.7 × 0.9) × 1.15 = 3,063 Btu/h

Thus, cooling load of fan motor is 3,100 Btu/h.

Page 83: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 38

(2) Internal Heat Gains

Heat gain from pumps, piping and supports, lighting and concrete walls, including 15% margin, is 109,000 Btu/h obtained from Table 5.4.1-1.

(3) Additional Cooling Load (Additional margin)

Additional cooling load (additional margin) is 2,900 Btu/h.

Total cooling load = (1)+(2)+(3) = 115,000 Btu/h

Page 84: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 39

5.4.2.2 Turbine-Driven Pump Area Air Handling Unit

The cooling coil capacity is calculated by summing up the following cooling loads.

(1) Outdoor Air

Heat gain from outdoor air is calculated by equation 4.2-1. Outdoor air intake is 100 cfm, enthalpy of outdoor air and return air are 43.3 Btu/lb and 35.3 Btu/lb.

q = 60 × 0.075 × 100 × (43.3 – 35.3) × 1.15 = 4,140 Btu/h

Thus, the cooling load per one AHU is to be 5,000 Btu/h.

(2) Fan Motors

Heat gain from fan motors is calculated by equation 4.2-2. Airflow rate requirement is 1,400 cfm. Fan total pressure is 2.0 in. w.g. as given in Table 2.8-1. Fan efficiency and motor efficiency used are 0.7 and 0.9, respectively.

q = 2545 × 0.000157 × 2 × 1400 / (0.7 × 0.9) × 1.15 = 2,042 Btu/h

Thus, cooling load of the fan motor is 3,000 Btu/h.

(3) Internal Heat Gains

Heat gain from pumps, piping and supports, lighting and concrete walls, including 15% margin, is 57,000 Btu/h obtained from Table 5.4.1-1.

Page 85: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 40

(4) Additional Cooling Load (Additional margin)

Additional cooling load (additional margin) is 0 Btu/h.

Total cooling load = (1)+(2)+(3)+(4) = 65,000 Btu/h

Page 86: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 41

5.5 Safety Related Component Area HVAC System (SRCAVS)

Table 5.5.1-1 through 5.5-6 summarizes the SRCAVS airflow requirements based on cooling requirements.

5.5.1 Airflow Requirement

Cooling Airflow Requirements

Cooling airflow requirements are calculated by equation 4.1-1. Required cooling airflow for each area is shown in Table 5.5.1-1 through 5.5-6.

AHU Airflow Requirements

Cooling airflow requirements of each safety related component area AHU is obtained from Table 5.5.1-1 through 5.5-6. Each AHU airflow rate is shown below.

Essential Chiller Unit AHU : 1,000 cfm CCW Pump Area AHU : 1,000 cfm Charging Pump Area AHU : 1,000 cfm Penetration Area AHU : 5,000 cfm Annulus Emergency Exhaust Filtration Unit Area AHU : 1,000 cfm Spent Fuel Pit Pump Area AHU : 1,500 cfm

Page 87: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 42

5.5.2 Cooling Coil Requirement

5.5.2.1 Essential Chiller Unit Area AHU Cooling Coil

The cooling coil capacity is calculated by summing up the following cooling loads.

(1) Fan Motors

Heat gain from fan motors is calculated by equation 4.2-2. Airflow rate requirement is 1,000 cfm. Fan total pressure is 3.0 in. w.g. as given in Table 2.8-1. Fan efficiency and motor efficiency used are 0.7 and 0.9, respectively.

q = 2545 × 0.000157 × 3 × 1000 / (0.7 × 0.9) × 1.15 = 2,188 BTU/h

Thus, cooling load of fan motor is 3,000 Btu/h.

(2) Heat Gains

Heat gain including 15% margin are 22,000 Btu/h obtained from Table 5.5.1-1

(3) Additional Cooling Load (Additional margin)

Additional cooling load (additional margin) is 5,000 BTU/h.

Total cooling load = (1)+(2)+(3) = 30,000 Btu/h

Page 88: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 43

.

5.5.2.2 CCW Pump Area AHU Cooling Coil

The cooling coil capacity is calculated by summing up the following cooling loads.

(1) Fan Motors

Heat gain from fan motors is calculated by equation 4.2-2. Airflow rate requirement is 1,000 cfm. Fan total pressure is 3.0 in. w.g. as given in Table 2.8-1. Fan efficiency and motor efficiency used are 0.7 and 0.9, respectively.

q = 2545 × 0.000157 × 3 × 1000 / (0.7 × 0.9) × 1.15 = 2,188 BTU/h

Thus, cooling load of fan motor is 3,000 Btu/h.

Page 89: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 44

(2) Heat Gains

Heat gains including 15% margin are 23,000 Btu/h obtained from Table 5.5.1-2.

(3) Additional Cooling Load (Additional margin)

Additional cooling load (additional margin) is 4,000 BTU/h

Total cooling load = (1)+(2)+(3) = 30,000 Btu/h

Page 90: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 45

5.5.2.3 Charging Pump Area AHU Cooling Coil

The cooling coil capacity is calculated by summing up the following cooling loads.

(1) Fan Motors

Heat gain from fan motors is calculated by equation 4.2-2. Airflow rate requirement is 1,000 cfm. Fan total pressure is 3.0 in. w.g. as given in Table 2.8-1. Fan efficiency and motor efficiency used are 0.7 and 0.9, respectively.

q = 2545 × 0.000157 × 3 × 1000 / (0.7 × 0.9) × 1.15 = 2,188 BTU/h

Thus, the cooling load of fan motor is 3,000 Btu/h.

(2) Heat Gains

Heat gain including 15% margin are 3,000 Btu/h obtained from Table 5.5-3

(3) Additional Cooling Load (Additional margin)

Additional cooling load (additional margin) is 4,000 BTU/h.

Total cooling load = (1)+(2)+(3) = 10,000 Btu/h

Page 91: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 46

Page 92: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 47

5.5.2.4 Penetration Area AHU Cooling Coil

The cooling coil capacity is calculated by summing up the following cooling loads.

(1) Fan Motors

Heat gain from fan motors is calculated by equation 4.2-2. Airflow rate requirement is 5,000 cfm, fan total pressure is 5.0 in. w.g. as given in Table 2.8-1. Fan efficiency and motor efficiency used are 0.7 and 0.9, respectively.

q = 2545 × 0.000157 × 5 × 5000 / (0.7 × 0.9) × 1.15 = 18,234 BTU/h

Thus, cooling load of fan motor is 19,000 Btu/h.

(2) Heat Gains

Heat gains including 15% margin are 281,000 Btu/h obtained from Table 5.5.1-4.

(3) Infiltration

Heat load of infiltration is calculated by equation 4.2-1. Infiltration flow is 375 cfm, and enthalpy of infiltration air and room air are 47.0 Btu/lb(Note) and 41.1 Btu/lb, respectively.

q = 60 × 0.075 × 375 × (47.0 – 41.1) × 1.15 = 11,450 Btu/h

Thus, the cooling load per one AHU is to be 12,000 Btu/h.

Note: In case that the infiltration air condition is 130oF and 0.0141lb/lb' during LOCA events, the enthalpy is to be 47.0 Btu/lb.

(4) Additional Cooling Load (Additional margin)

Additional cooling load (additional margin) is 18,000 BTU/h.

Total cooling load = (1)+(2)+(3)+(4) = 330,000 Btu/h

Page 93: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 48

Page 94: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 49

5.5.2.5 Annulus Emergency Exhaust Filtration Unit Area AHU Cooling Coil

The cooling coil capacity is calculated by summing up the following cooling loads.

(1) Fan Motors

Heat gain from fan motors is calculated by equation 4.2-2. Airflow rate requirement is 1,000 cfm, fan total pressure is 3.0 in. w.g. as given in Table 2.8-1. Fan efficiency and motor efficiency used are 0.7 and 0.9, respectively.

q = 2545 × 0.000157 × 3 × 1000 / (0.7 × 0.9) × 1.15 = 2,188 BTU/h

Thus, the cooling load of fan motor is 3,000 Btu/h.

(2) Heat Gains

Heat gain through the structure including 15% margin are 2,000 Btu/h obtained from Table 5.5.1-5.

(3) Additional Cooling Load (Additional margin)

Additional cooling load (additional margin) is 5,000 BTU/h.

Total cooling load = (1)+(2)+(3) = 10,000 Btu/h

Page 95: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 50

Page 96: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 51

5.5.2.6 Spent Pump Pit Area AHU Cooling Coil

The cooling coil capacity is calculated by summing up the following cooling loads.

(1) Fan Motors

Heat gain from fan motors is calculated by equation 4.2-2. Airflow rate requirement is 1,500 cfm, and fan total pressure is 3.0 in. w.g. as given in Table 2.8-1. Fan efficiency and motor efficiency used are 0.7 and 0.9, respectively.

q = 2545 × 0.000157 × 3 × 1500 / (0.7 × 0.9) × 1.15 = 3,282 BTU/h

Thus, the cooling load of fan motor is 4,000 Btu/h.

(2) Heat Gains

Heat gains including 15% margin are 88,000 Btu/h obtained from Table 5.5.1-6.

(3) Additional Cooling Load (Additional margin)

Additional cooling load (additional margin) is 8,000 BTU/h.

Total cooling load = (1)+(2)+(3) = 100,000 Btu/h

Page 97: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 52

5.6 Annulus Emergency Filtration System (AEES)

5.6.1 Airflow Requirement for Penetration Areas

The required airflow to establish a -0.4 inch w.g. pressure in the penetration areas and the safeguard component areas within 180 seconds with respect to adjacent areas is calculated by equation 4.1-4. The input values are as follows:

P : Establishing negative pressure , 0.4 in. w.g. Po : Surrounding area ambient pressure (Standard air) , 407 in. w.g. ∆P : CV expansion effect , 0.8 in. w.g. T : Time of establishing a 1/4 inch w.g. , 180 sec. Tf : Time of reaching fan design airflow rate , 130 sec. V : Volume in the penetration area , 409,249 ft3 Qin : Infiltration to the penetration areas , 1,500 cfm

where, CV expansion effect (∆P) stated above is calculated by equation 4.1-5 input following

Page 98: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 53

conditions.

P : Initial pressure , 407 in. w.g. V : Volume in the penetration area , 409,249 ft3 ∆V : Volume decrease in the penetration area , 675.9 ft3

Therefore,

∆P = 407 x {409,249 / (409,249-675.9) - 1 } = 0.67. A conservative value of 0.8 in. w.g. is used.

where, Volume decrease in the penetration areas (∆V) stated above is calculated by equation 4.1-6 with the following input conditions.

Rcvo : Outside Radius of CV , 78.92 ft ∆R : Radial expansion of CV , 0.018 ft H : Height of the Penetration Area , 75.75 ft

Therefore,

∆V = =3.14 x {(78.92 + 0.018)2 – 78.922} x 75.75 = 675.85. A conservative value of 675.9 ft3 is used.

where, Radial expansion of CV (∆R) stated above is calculated by equation 4.1-7 with the following input conditions.

P : Internal Pressure of CV , 68 psig R : Average Radius of CV , 76.75 ft t : Thickness of CV , 4.33 ft E : Modulus of Elasticity for Concrete , 4,769 ksi n : Poisson’s Ratio , 0.17

Thus, Radial expansion of CV (∆R) is:

∆R = 68 x 76.752 / (4,769 x 103 x 4.33) x (1 – 0.17/2) = 0.0177. A conservative value of 0.018 ft is used.

Therefore, the required airflow (Q) is:

( )( ) 1,500

130180407409,2490.80.460Q +−⋅⋅+⋅

= = 2947.96

Approximately 15% margin is added in this value. Thus, required airflow for penetration areas, including a margin is 3,500 cfm.

5.6.2 Airflow Requirement for Safeguard Component Areas

Page 99: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 54

The required airflow to establish a -1/4 inch w.g. pressure in the safeguard component areas within 180 seconds with respect to adjacent areas is calculated by equation 4.1-4. The input values are as follows:

P : Establishing negative pressure , 0.4 in. w.g. Po : Surrounding area ambient pressure (Standard air) , 407 in. w.g. ∆P : CV expansion effect , 0 (Not applicable) T : Time of establishing a 1/4 inch w.g. , 180 sec. Tf : Time of reaching fan design airflow rate , 130 sec. V : Volume of safeguard component areas , 311,819 ft3 Qin : Infiltration to the penetration areas , 1,500 cfm Therefore,

( )( ) 1,500

130180407311,81900.460Q +−⋅⋅+⋅

= = 1867.74

Note: CV expansion effect (DP) is zero (0)

Approximately 10% margin is added in this value. Thus, required airflow for safeguard component areas, including a margin is 2,100 cfm.

5.6.3 Annulus Emergency Exhaust Fan EFU Airflow Requirements

According to the airflow requirement discussed in Section 5.6.2 and 5.6.3, the annulus emergency exhaust filtration unit and fan is determined by summing up the airflow requirement for penetration and safeguard component areas. Thus, the annulus emergency exhaust fan capacity is to be 5,600 cfm.

Page 100: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 55

6. REFERENCE

1. “Installsation Design and Installation of Vented Lead-Aicd Storage Batteries for Nuclear Power Plants,” Regulatory Guide 1.128, Revision 2

2. “ASHRAE Handbook Fundamentals-2005,” ASHRAE

3. “Safety requirements for secondary batteries and battery installations – Part 2: Stationary batteries,” BS EN50272-2:2001

4. “IEEE Recommended Practice for Installation Design and Installation of Vented Lead-Acid Batteries for Stationary Applications,” IEEE Std 484TM-2002

5. EPRI Advanced Light Water Reactor Utility Requirements Document Volume II

Page 101: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD.

56

Table 5.1.1-1 MCRVS Calculation Sheet

Page 102: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 57

Table 5.1.2-1 MCRVS Return Air Temperature Condition (Normal Operation Mode)

Table 5.1.2-2 MCRVS Return Air Temperature Condition

(Emergency Pressurization Mode)

Page 103: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 58

Table 5.2.1-1 CERVS Calculation Sheet

Page 104: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APW

R Safety-R

elated Air Conditioning, H

eating MU

AP-10020-NP (R

2) C

ooling, and Ventilation Systems C

alculations

Mitsubishi H

eavy Industries, LTD. 59

Table 5.2.1-2 Cooling and Heating Loads in Non-Safety Related Portion of CERVS Train-D following Accident Condition

Page 105: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 60

Table 5.2.2-1 CERVS Return Air Temperature

Page 106: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 61

Table 5.3.1-1 SCAVS Cooling and Heating Loads

Page 107: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 62

Table 5.3.1-2 SCAVS Calculation Sheet (During Normal Operation Severed by AUXVS)

Page 108: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 63

Table 5.3.1-3 SCAVS Calculation Sheet (During Abnormal Plant Operation)

Page 109: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 64

Table 5.3.1-4 SCAVS Airflow Ratio of Normal to Abnormal Operation

Page 110: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 65

Table 5.3.2-1 SCAVS Return Air Temperature Condition

Page 111: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 66

Table 5.4.1-1 EFWPAVS Calculation Sheet

Page 112: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 67

Table 5.4.2-1 EFWPAVS Return Air Temperature Condition

Page 113: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 68

Table 5.5.1-1 SRCAVS (Essential Chiller Unit Area) Calculation Sheet

Table 5.5.1-2 SRCAVS (CCW Pump Area) Calculation Sheet

Page 114: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 69

Table 5.5.1-3 SRCAVS (Charging Pump Area) Calculation Sheet

Page 115: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 70

Table 5.5.1-4 SRCAVS (Annulus Area) Calculation Sheet

Page 116: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 71

Table 5.5.1-5 SRCAVS (Annulus Filtration Unit Area) Calculation Sheet

Table 5.5.1-6 SRCAVS (Spent Fuel Pit Pump Area) Calculation Sheet

Page 117: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APWR Safety-Related Air Conditioning, Heating MUAP-10020-NP (R2) Cooling, and Ventilation Systems Calculations

Mitsubishi Heavy Industries, LTD. 72

Table 5.5.2-1 SRCAVS Return Air Temperature Condition

Page 118: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APW

R Safety-R

elated Air Conditioning, H

eating MU

AP-10020-NP (R

2) C

ooling, and Ventilation Systems C

alculations

Mitsubishi H

eavy Industries, LTD. 73

Figure 5.1-1 Psychrometric Chart (Normal Operation Mode) (MCRVS)

Page 119: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APW

R Safety-R

elated Air Conditioning, H

eating MU

AP-10020-NP (R

2) C

ooling, and Ventilation Systems C

alculations

Mitsubishi H

eavy Industries, LTD. 74

Figure 5.1-2 Psychrometric Chart (Emergency Pressurization Mode) (MCRVS)

Page 120: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APW

R Safety-R

elated Air Conditioning, H

eating MU

AP-10020-NP (R

2) C

ooling, and Ventilation Systems C

alculations

Mitsubishi H

eavy Industries, LTD. 75

Figure 5.1-3 MCRVS Airflow Distribution Sketch (Emergency Pressurization Mode)

Page 121: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APW

R Safety-R

elated Air Conditioning, H

eating MU

AP-10020-NP (R

2) C

ooling, and Ventilation Systems C

alculations

Mitsubishi H

eavy Industries, LTD. 76

Figure 5.2-1 Psychrometric Chart (Train A&B) (CERVS)

Page 122: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APW

R Safety-R

elated Air Conditioning, H

eating MU

AP-10020-NP (R

2) C

ooling, and Ventilation Systems C

alculations

Mitsubishi H

eavy Industries, LTD. 77

Figure 5.2-2 Psychrometric Chart (Train C&D) (CERVS)

Page 123: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APW

R Safety-R

elated Air Conditioning, H

eating MU

AP-10020-NP (R

2) C

ooling, and Ventilation Systems C

alculations

Mitsubishi H

eavy Industries, LTD. 78

Figure 5.3-1 SCAVS Psychrometric Chart

Page 124: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APW

R Safety-R

elated Air Conditioning, H

eating MU

AP-10020-NP (R

2) C

ooling, and Ventilation Systems C

alculations

Mitsubishi H

eavy Industries, LTD. 79

Figure 5.4-1 EFWPAVS (Motor-Driven Pump Area) Psychrometric Chart

Page 125: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APW

R Safety-R

elated Air Conditioning, H

eating MU

AP-10020-NP (R

2) C

ooling, and Ventilation Systems C

alculations

Mitsubishi H

eavy Industries, LTD. 80

Figure 5.4-2 EFWPAVS (Turbine-Driven Pump Area) Psychrometric Chart

Page 126: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APW

R Safety-R

elated Air Conditioning, H

eating MU

AP-10020-NP (R

2) C

ooling, and Ventilation Systems C

alculations

Mitsubishi H

eavy Industries, LTD. 81

Figure 5.5-1 SRCAVS (Essential Chiller Unit Area) Psychrometric Chart

Page 127: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APW

R Safety-R

elated Air Conditioning, H

eating MU

AP-10020-NP (R

2) C

ooling, and Ventilation Systems C

alculations

Mitsubishi H

eavy Industries, LTD. 82

Figure 5.5-2 SRCAVS (CCW Pump Area) Psychrometric Chart

Page 128: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APW

R Safety-R

elated Air Conditioning, H

eating MU

AP-10020-NP (R

2) C

ooling, and Ventilation Systems C

alculations

Mitsubishi H

eavy Industries, LTD. 83

Figure 5.5-3 SRCAVS (Charging Pump Area) Psychrometric Chart

Page 129: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APW

R Safety-R

elated Air Conditioning, H

eating MU

AP-10020-NP (R

2) C

ooling, and Ventilation Systems C

alculations

Mitsubishi H

eavy Industries, LTD. 84

Figure 5.5-4 SRCAVS (Penetration Area) Psychrometric Chart

Page 130: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APW

R Safety-R

elated Air Conditioning, H

eating MU

AP-10020-NP (R

2) C

ooling, and Ventilation Systems C

alculations

Mitsubishi H

eavy Industries, LTD. 85

Figure 5.5-5 SRCAVS (Annulus Emergency Exhaust Filtration Unit Area) Psychrometric Chart

Page 131: MUAP-10020-NP (R2), 'US-APWR Safety-Related Air Conditioning, Heating… · 2013-04-26 · US-APWR Safety-Related Air Conditioning, Heating, MUAP-10020-NP (R2) Cooling, and Ventilation

US-APW

R Safety-R

elated Air Conditioning, H

eating MU

AP-10020-NP (R

2) C

ooling, and Ventilation Systems C

alculations

Mitsubishi H

eavy Industries, LTD. 86

Figure 5.5-6 SRCAVS (Spent Fuel Pit Pump Area) Psychrometric Chart