ManualPneumatic MPA-S
Valve terminal withMPA-S pneumaticstype:MPA-FB-...MPA-CPI-...MPA-MPM-... andMPA-ASI-...
Manual534 241en 0802c[688 821]
MPA-S valve terminal
Contents and general instructions
IFesto P.BE−MPA−EN en 0802c
Original de. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Edition en 0802c. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Designation P.BE−MPA−EN. . . . . . . . . . . . . . . . . . . . . . . . . . .
Order no. 534 241. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
© (Festo AG�&�Co. KG, D�73726 Esslingen, Germany, 2008)Internet: http://www.festo.comE−Mail: [email protected]
The reproduction, distribution and utilization of this docu−ment as well as the comunication of its contents to otherswithout express authorization is prohibited. Offenders willbe held liable for the payment of damages. All rights re−served in the event of the grant of a patent, utility moduleor design.
Contents and general instructions
II Festo P.BE−MPA−EN en 0802c
Contents and general instructions
IIIFesto P.BE−MPA−EN en 0802c
Contents
Designated use VII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Areas of application and approval by authorities VII . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Target group VIII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Service VIII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Note on the use of this manual IX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Important user instructions XII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1. Summary of components 1−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1 The MPA−S valve terminal 1−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1.1 Overview of variants 1−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1.2 Description of components 1−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1.3 Connecting and display elements 1−30 . . . . . . . . . . . . . . . . . . . . . . . . . . .
2. Fitting 2−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1 General instructions on fitting and dismantling 2−4 . . . . . . . . . . . . . . . . . . . . . . .
2.2 Fitting variants 2−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.1 Fitting onto/removing from a hat rail 2−6 . . . . . . . . . . . . . . . . . . . . . . . .
2.2.2 Fitting onto/removing from a hat rail 2−11 . . . . . . . . . . . . . . . . . . . . . . . .
2.3 Fitting/removing the inscription label holders 2−13 . . . . . . . . . . . . . . . . . . . . . . . .
2.4 Fitting/removing the manual override caps (optional) 2−15 . . . . . . . . . . . . . . . . .
Contents and general instructions
IV Festo P.BE−MPA−EN en 0802c
3. Installation 3−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 Preparing the compressed air 3−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1.1 Operation with non−lubricated compressed air 3−4 . . . . . . . . . . . . . . . .
3.1.2 Operation with lubricated compressed air 3−5 . . . . . . . . . . . . . . . . . . . .
3.2 General instructions on installation 3−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3 Laying the tubing 3−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4 Connecting the MPA−S valve terminal 3−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4.1 Pilot control of the valve solenoid coils (pilot air) 3−12 . . . . . . . . . . . . . .
3.4.2 MPA−S valve terminal with pressure zone separation 3−13 . . . . . . . . . . .
3.4.3 Operation of the MPA−S valve terminal with reversible pressure regulators 3−16 . . . . . . . . . . . . . . . . . . . . . . . . .
3.4.4 Setting the pressure regulator 3−16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4.5 Vacuum / low pressure operation 3−19 . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4.6 Connecting the pneumatic tubing 3−21 . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4.7 Connecting the electric cables 3−25 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.5 Address assignment of the valves 3−30 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.5.1 MPA−S valve terminal with CPX terminal 3−30 . . . . . . . . . . . . . . . . . . . . .
3.5.2 MPA−S valve terminal with CPI module or AS−Interface 3−32 . . . . . . . . . .
3.5.3 MPA−S valve terminal with multipin connection 3−32 . . . . . . . . . . . . . . .
4. Commissioning 4−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1 General instructions 4−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.1 Before commissioning 4−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.2 Pressure increase in the complete supply 4−4 . . . . . . . . . . . . . . . . . . . .
4.2 Manual override 4−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3 Checking the valves and the valve−actuator combination 4−8 . . . . . . . . . . . . . . .
4.4 LED display of the valves 4−13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.5 LED display of the proportional pressure regulator 4−16 . . . . . . . . . . . . . . . . . . . .
4.6 Commissioning instructions for the proportional pressure regulator 4−17 . . . . . .
4.7 Troubleshooting 4−19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.7.1 Impairment of function 4−19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.7.2 Operating states of the pneumatic system 4−21 . . . . . . . . . . . . . . . . . . .
Contents and general instructions
VFesto P.BE−MPA−EN en 0802c
5. Maintenance and conversion 5−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1 General precautionary measures 5−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2 Dismantling the MPA−S valve terminal 5−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3 Maintenance of the MPA−S valve terminal 5−6 . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.1 Cleaning the large surface−mounted silencer 5−6 . . . . . . . . . . . . . . . . .
5.3.2 Replace the large surface−mounted silencer or exhaust plate 5−7 . . . .
5.3.3 Replacing valves or cover plates 5−8 . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.4 Replace the proportional pressure regulator 5−11 . . . . . . . . . . . . . . . . .
5.3.5 Replacing electronic modules 5−12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.6 Replacing the sub−base, supply plate or MPA−S end plate 5−19 . . . . . . .
5.3.7 Replacing the manifold boards 5−22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4 Converting the MPA−S valve terminal 5−26 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.1 Conversion to internal or external pilot air 5−26 . . . . . . . . . . . . . . . . . . . .
5.4.2 Converting the MPA−S valve terminal to different pressure zones 5−31 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.3 Adding valve locations 5−35 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.4 Adding an electric supply plate 5−38 . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.5 Adding a pressure sensor plate 5−39 . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.6 Adding a proportional pressure regulator 5−40 . . . . . . . . . . . . . . . . . . . .
A. Technical appendix A−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.1 Technical specifications A−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.2 Festo accessories A−17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B. Supplementary component summary B−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B.1 Overview of valve location components B−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B.2 Separating the MPA−S valve terminal from the CPX terminal B−11 . . . . . . . . . . . .
C. Index C−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents and general instructions
VI Festo P.BE−MPA−EN en 0802c
Contents and general instructions
VIIFesto P.BE−MPA−EN en 0802c
Designated use
The MPA−S valve terminals described in this manual areintended for fitting into a machine or automated system. The user must at all times observe the safety regulationsspecified in this manual as well as the instructions concerningthe designated use of the relevant MPA−S valve terminal. TheMPA−S valve terminals may only be used as follows:
� as designated in industrial applications
� without any modifications by the user. Only the conversions or modifications described in thedocumentation accompanying the product are permitted.
� In perfect technical condition.
When used together with commercially available compo�nents, such as actuators, the specified limits for pressures,temperatures, electrical data, torques etc. must be observed.National and local safety regulations must also be observed.
Areas of application and approval by authorities
The product fulfils the requirements of the EU guidelines andis marked with the CE identification.
Standards and test values, which the product must observeand fulfil, can be found in the section �Technical specifica�tions". The product−relevant EU directive can be found in theconformity declaration.
Certain configurations of the product have been approved bythe Underwriters Laboratories Inc. (UL) for the USA andCanada. These configurations are marked as follows:
Contents and general instructions
VIII Festo P.BE−MPA−EN en 0802c
NoteObserve the following if the UL requirements are to becomplied with in your application:
� Rules for observing the UL certification can be found inthe separate UL−specific documentation. The relevanttechnical specifications listed there also apply here.
� The technical specifications in this documentation mayshow different values.
Target group
This manual is directed exclusively at technicians trained incontrol and automation technology.
Service
Please consult your local Festo repair service if you have anytechnical problems.
Contents and general instructions
IXFesto P.BE−MPA−EN en 0802c
Note on the use of this manual
This manual contains specific information on fitting, installing,commissioning, servicing and converting the MPA−S valveterminal. It includes only the description of the pneumaticcomponents and refers to the valve terminal variants listed inthe following table:
Variants of the MPA−...−VI valve terminal
MPA−S valve terminal with CPX terminalInformation on CPX modules can befound in the manual for the relevantmodule. An overview can be found inthe system manual for your CPXterminal, table �Manuals on theCPX�terminal").
MPA−S valve terminal with multipinconnectionInformation on the electric/electroniccomponents: see leaflet with product
Contents and general instructions
X Festo P.BE−MPA−EN en 0802c
Variants of the MPA−...−VI valve terminal
MPA−S with CPI moduleInformation on the electric/electroniccomponents: see leaflet with product
MPA−S valve terminal with AS−InterfaceInformation on the electric/electroniccomponents: see leaflet with product
Tab.�0/1: Connection variants of the MPA−S valve terminal
An overview of all user documentation on the CPX terminalcan be found in the relevant system manual.
Contents and general instructions
XIFesto P.BE−MPA−EN en 0802c
The MPA−S valve terminal consists of the following pneumaticand electric components: The most important componentsare shown in the following diagram:
12 3 4 5 67
8
13
9aJ
2 3
9 aJaJaA
1 Large surface−mounted silencer or exhaust plate
2 Cover plate
3 Valves
4 Pressure sensor plate
5 Electric supply plate
6 Proportional pressure regulator
7 Right−hand end plate
8 Pneumatic supply plate
9 Pressure regulator plate
aJ Sub−base
aA Multipin sub−base; AS−Interface,CPI�module or pneumatic interface
Fig.�0/1: Main components of the MPA−S valve terminal
Contents and general instructions
XII Festo P.BE−MPA−EN en 0802c
Important user instructions
Danger categories
This manual contains instructions on the possible dangerswhich may occur if the product is not used correctly. Theseinstructions are marked (Warning, Caution, etc.), printed on ashaded background and marked additionally with a picto�gram. A distinction is made between the following dangerwarnings:
WarningThis means that failure to observe this instruction mayresult in serious personal injury or damage to property.
CautionThis means that failure to observe this instruction mayresult in personal injury or damage to property.
NoteThis means that failure to observe this instruction mayresult in damage to property.
The following pictogram marks passages in the text whichdescribe activities with electrostatically sensitive compo�nents.
Electrostatically sensitive components may be damaged ifthey are not handled correctly.
Contents and general instructions
XIIIFesto P.BE−MPA−EN en 0802c
Marking special information
The following pictograms mark passages in the textcontaining special information.
Pictograms
Information:Recommendations, tips and references to other sources ofinformation.
Accessories:Information on necessary or sensible accessories for theFesto product.
Environment:Information on environment−friendly use of Festo products.
Text markings
· The bullet indicates activities which may be carried out inany order.
1. Figures denote activities which must be carried out in thenumerical order specified.
� Hyphens indicate general activities.
Contents and general instructions
XIV Festo P.BE−MPA−EN en 0802c
The following product−specific terms and abbreviations areused in this manual:
Term/abbreviation Meaning
Basic components Component (pneumatic interface, multipin sub−base, pneumaticsub−base or pneumatic supply plate) on which further components(exhaust plates, large surface−mounted silencers, pressure regulators,valves or cover plates) are fitted
Components Common term for pneumatic interface, multipin sub−base, exhaustplate, large surface−mounted silencer, pneumatic sub−base orpneumatic supply plate, electric supply plate, pressure sensor plate,proportional pressure regulator, end plate, pressure regulator plate,valve and cover plate
Connecting the tubing Connecting the pneumatic supply lines (tubing) to the MPA−S valveterminal
Cover plate Plate without valve function for sealing non−used valve locations onsub−bases
CPX module Common term for the various modules which can be incorporated in aCPX terminal
CPX terminal Modular electric terminal type 50 or type 53
Electric supply plate Plate for additional supply of the valves with load voltage
Electronic module Module in the sub−base with LED and valve coil management
End plate Extreme right−hand plate of the MPA−S valve terminal and extremeleft−hand plate of the CPX terminal with holes for fitting onto a wall
Exhaust plate Plate for ducted exhaust with connection 3/5
Sub−base Plate for 4 valve locations for single−solenoid, double−solenoid ormid−position valves, with work connections 2 and 4� size MPA1 (type MPAS...4) with 4 valve locations� size MPA2 (type MPAS...2) with 2 valve locations
I/O Input/Output modules
Isolating seal Special seals for forming pressure zones
Contents and general instructions
XVFesto P.BE−MPA−EN en 0802c
Term/abbreviation Meaning
Manual override Manual override
MPA1 or MPA2 Size of the valves: MPA1 = 10 mmMPA2 = 20 mm
MPA−S valve terminal Modular Performance Sub−base valve terminal (type 32) with multipinconnection or for CPX terminal
MPA−S valve terminalwith multipin connectiontype MPA...−MPM−...
Variant of the MPA−S valve terminal with sub−D plug. All valve solenoidcoils are connected centrally via the sub−D plug. The electric linking isconstructed on a modular basis, i.e. each sub−base has its own board.
Multipin connection Connection with modular electric linking type MPA....−MPM−...
Pneumatic interface The pneumatic interface is the interface between the modular electricalperiphery of the CPX terminal and the pneumatic MPA−S
Pneumatic module Module consisting of pneumatic sub−base, electronic module, valves orcover plates
Pneumatic supply plate Plate for additional supply of compressed air to the valves, e.g. withseveral pressure zones
Valve single−solenoid, double−solenoid or mid−position valves
Tab.�0/2: Product−specific terms and abbreviations
Contents and general instructions
XVI Festo P.BE−MPA−EN en 0802c
Summary of components
1−1Festo P.BE−MPA−EN en 0802c
Chapter 1
1. Summary of components
1−2 Festo P.BE−MPA−EN en 0802c
Contents
1. Summary of components 1−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1 The MPA−S valve terminal 1−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1.1 Overview of variants 1−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1.2 Description of components 1−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1.3 Connecting and display elements 1−30 . . . . . . . . . . . . . . . . . . . . . . . . . . .
1. Summary of components
1−3Festo P.BE−MPA−EN en 0802c
Contents of this chapter This chapter provides an overview of the following aspects ofthe MPA−S valve terminal:
� The connection variants and components of the valveterminal
� The maximum number of valve locations
� The identification code of the valves
� Connection, display and operating elements
Further information Instructions on connecting the electric multipin can be foundin the leaflet supplied with the product.
Information on the modules of the CPX terminal can be foundin the CPX system manual.
Information on the electronic module of the MPA−S valve ter�minal can be found in the leaflet supplied with the productand in the relevant electronics manual (see System Manualfor your CPX terminal, table �Manuals on the CPX terminal").
1. Summary of components
1−4 Festo P.BE−MPA−EN en 0802c
1.1 The MPA−S valve terminal
Festo supports your automation tasks at machine level withthe MPA−S valve terminal. The modular structure of theMPA−S valve terminal enables you to match this valveterminal optimally to your machine or system.
The valve terminal pneumatics provide the following:
� the common channels for supply and exhaust air
� the electric signals from all valve solenoid coils.
Work connections 2 and 4 are provided for each valve loca�tion on the individual pneumatic modules. The valves aresupplied with compressed air (operating pressure and pilotpressure) via the common channels and connections in thebasic components. The exhaust air (from the valves and thepilot exhaust air) is also exhausted via these common chan�nels. Further components for pressure supply are also avail�able, e.g. in order to supply pressure zones.
The MPA−S valve terminal is equipped with current reduction.The rated current of the valve solenoid coils is then reducedafter the high−current phase (switching procedure). The cur�rent reduction offers the following advantages:
� the MPA−S valve terminal has a lower energy consumption
� the power unit for the voltage supply to the MPA−S valveterminal can be designed more economically dependingon the individual case
� the valve solenoid coils have less leakage power andproduce less waste heat.
1. Summary of components
1−5Festo P.BE−MPA−EN en 0802c
1.1.1 Overview of variants
Sizes of the MPA−Svalve�terminal
The valve terminal is available in the following sizes:
� MPA1: valves of size 10 mm
� MPA2: valves of size 20 mm
MPA−S valve terminal with CPX terminal
This variant of the MPA−S valve terminal is available in thefollowing grades:
Load voltage supply for the valves via ... Valve positions 1)
MPA1 MPA2
... CPX terminal 2) 4, 8, 12 � 32 2, 4, 6 � 16
... CPX terminal and electric supply plate (MPA) 3) 4, 8, 12 � 64 2, 4, 6 � 32
1) Two solenoid coils can be controlled per valve location.2) Max. 64 valve coils can be supplied3) Max. 128 valve coils can be supplied
Tab.�1/1: Number of valve locations of the MPA−S valve terminal with CPX terminal
Fig.�1/1: MPA−S valve terminal with CPX terminal
1. Summary of components
1−6 Festo P.BE−MPA−EN en 0802c
MPA−S valve terminal with CPI module
This variant of the MPA−S valve terminal is available in thefollowing grades:
Load voltage supply for the valves via ... Valve positions 1)
MPA1 MPA2
... CPI module 2) 4, 8 � 12 2, 4, 6 � 12
... CPI terminal and electric supply plate (MPA) 3) 4, 8, 12 � 16 2, 4, 6 � 16
1) Two solenoid coils can be controlled per valve location.2) Max. 24 valve coils can be supplied3) Max. 32 valve coils can be supplied
Tab.�1/2: Number of valve locations of the MPA−S valve terminal with CPI module
Fig.�1/2: MPA−S valve terminal with CPI module
1. Summary of components
1−7Festo P.BE−MPA−EN en 0802c
MPA−S valve terminal with multipin connection
This variant of the MPA−S valve terminal is available in thefollowing grades:
Number of valve locations 1)
MPA1 MPA2
4, 8, 12 � 24 2, 4, 6, � 24
1) Max. 24 valve coils can be actuated. The valve coils are connected electrically at a central point via the multipin plug.
Tab.�1/3: Number of valve locations on the MPA−S valveterminal with multipin connection
Fig.�1/3: MPA−S valve terminal with multipin connection
1. Summary of components
1−8 Festo P.BE−MPA−EN en 0802c
MPA−S valve terminal with AS−Interface
This variant of the MPA−S valve terminal is available in thefollowing grades:
Variants of the MPA−S valve terminalwith AS Interface
Number of valve positions 1)
with AS−InterfaceMPA1 MPA2
VPMA−ASI−...−4E4A−Z 2) 4 2, 4
VPMA−ASI−...−8E8A−Z 3) 4, 8 2, 4, 6 � 8
1) The max. number of valve positions which can be controlled depends on the electronic module: � VMPA1−MPM−EMM−8 and VMPA2−MPM−EMM−4 occupy 2 addresses per valve position� VMPA1−MPM−EMM−4 and VMPA2−MPM−EMM−2 occupy 1 address per valve position
2) Max. 4 valve coils can be supplied3) Max. 8 valve coils can be supplied
Tab.�1/4: Number of valve locations on the MPA−S valve terminal with AS−Interface
Fig.�1/4: MPA−S valve terminal with AS−Interface
1. Summary of components
1−9Festo P.BE−MPA−EN en 0802c
1.1.2 Description of components
The MPA−S valve terminal with CPX terminal or CPI moduleconsists of the following pneumatic components:
1 2
567
3
8 4
1 Only with MPA−S valve terminal withCPX terminal: Pressure sensor plate(optional)
2 Only with MPA−S valve terminal withCPX terminal: Proportional pressureregulator (optional)
3 Right−hand end plate
4 Pneumatic supply plate (optional)
5 Identification labels with support(optional)
6 Sub−base with work connections andserial linking (bus)
7 Electric supply plate (optional)
8 Seal (optional isolating seal forseparating pressure zones)
Fig.�1/5: Pneumatic components of the MPA−S valve terminal with CPX terminal orCPI�module, 1st. level
1. Summary of components
1−10 Festo P.BE−MPA−EN en 0802c
1 2 3
1
4
34 2
1 Exhaust plate 3/5 or largesurface−mounted silencer
2 Electronic module with LEDs
3 Valve or cover plates
4 Pressure regulator plate (optional)
Fig.�1/6: Pneumatic components of the MPA−S valve terminal with CPX terminal orCPI�module, 2nd. level
1. Summary of components
1−11Festo P.BE−MPA−EN en 0802c
The MPA−S valve terminal with electric multipin orAS−Interface consists of the following pneumatic components:
25 34
1
4
1 Right−hand end plate
2 Pneumatic supply plate (optional)
3 Identification labels with support(optional)
4 Sub−base with work connections andelectric linking
5 Seal (optional isolating seal forforming pressure zones)
Fig.�1/7: Pneumatic components of the MPA−S valve terminal with electric multipin orAS−Interface, 1st. level
1. Summary of components
1−12 Festo P.BE−MPA−EN en 0802c
1 2
4
3 42
1
1 Exhaust plate 3/5 or largesurface−mounted silencer
2 Electronic module with LEDs
3 Valve or cover plates
4 Pressure regulator plate (optional)
Fig.�1/8: Pneumatic components of the MPA−S valve terminal with electric multipin orAS−Interface, 2nd. level
1. Summary of components
1−13Festo P.BE−MPA−EN en 0802c
A description of the electric components of the MPA−S valveterminal with CPI module or with AS−Interface can be found inthe leaflet supplied with the product.
The MPA−S valve terminal with CPX terminal consists of thefollowing electric components:
1 CPX bus node
2 Electric part ofthe pneumaticinterface
3 Further optionalCPX modules
4 Left−hand endplate (CPX)
0123
45678 DI
PSPL
SFM
RUNSTOP
ERRTP
1
2
3
4
Fig.�1/9: Electric components of the MPA−S valve terminal with CPX terminal
The MPA−S valve terminal with multipin connection sub−Dconsists of the following electric components:
1 Multipin socketwith cable
2 Electric part ofthe multipinsub−base withsub−D connection
1
2
Fig.�1/10: Electric components of the MPA−S valve terminal with multipin connection sub−D
1. Summary of components
1−14 Festo P.BE−MPA−EN en 0802c
Valves
The MPA−S valve terminal can be fitted with 2x3/2−way valves,5/2−way valves (single−solenoid and double−solenoid),5/3−way mid−position valves and proportional directionalcontrol valves.
All 5/2−way valves and 5/3−way mid−position valves can beused under all operating conditions:
� standard mode
� reversible mode
� low−pressure mode
� vacuum mode.
Identifying the valves The valves on the MPA−S valve terminal are marked byidentification codes. By means of this identification on thefront of the valve, you can ascertain the equipment fitted onyour MPA−S valve terminal.
Ident. code Valve
B 5/3−way valve, open in mid−position
D Two single−solenoid 2/2−way valves, normally closed
E 5/3−way valve, mid−position exhausted
G 5/3−way valve, mid−position closed
H Two single−solenoid 3/2−way valves, control side 12 in basic position open, controlside 14 normally closed
I Two 2/2−way valves, normally closed
with dual−pressure operation: operating pressure at connection 1 or connection 5
with vacuum operation: operating pressure at connection 1, vacuum at connection 5(e.g. for vacuum switching with reject pulse)
See also the instructions in the chapter 3.4.2 Pressure zone separation and 3.4.5Vacuum/low pressure operation as well as in appendix B1 Overview of the valveplates
J 5/2−way double solenoid valve
1. Summary of components
1−15Festo P.BE−MPA−EN en 0802c
Ident. code Valve
K Two single−solenoid 3/2−way valves, normally closed
M Single solenoid 5/2−way valve
N Two single−solenoid 3/2−way valves, basic position open
W Single−solenoid 3/2−way valve, open in basic position, external pressure supply via connection 2
X Single−solenoid 3/2−way valve, closed in basic position, external pressure supply via connection 4
Tab.�1/5: Ident. code of the valves
Further information on the valves can be found in appendix B.
Proportional pressure regulator
The VPPM−6TA−... proportional pressure regulator has beendesigned to regulate a pressure proportional to a specifiedsetpoint value. An integrated pressure sensor records thepressure at the work connection and compares this with thesetpoint value. If the actual value differs from the setpointvalue, the pressure regulator is actuated further until thesetpoint value is reached. For constant pressure supply, which is necessary for accuratecontrol quality, the proportional pressure regulator has anadditional supply connection.
Configure the proportional pressure regulator via the PLC orthe Festo Handheld (CPX−MMI). How to fit the proportional pressure regulator is described inthe mounting instructions VPPM−6TA−... Information on configuring the proportional pressureregulator can be found in the appropriate electronics manual(see also table �Manuals on the CPX terminal" in the relevantsystem manual).
1. Summary of components
1−16 Festo P.BE−MPA−EN en 0802c
Identifying the propor�tional pressure regulator
The proportional pressure regulators on the MPA−S valveterminal are marked by identification codes. With thisidentification you can ascertain the type of proportionalpressure regulator.
Ident. code Proportional pressure regulator, normally closed ...
2 % accuracy:
QA 0 � 2 bar output pressure
QB 0 � 6 bar output pressure
QC 0 � 10 bar output pressure
1 % accuracy:
QD 0 � 2 bar output pressure
QE 0 � 6 bar output pressure
QF 0 � 10 bar output pressure
Tab.�1/6: Identification code of the proportional pressure regulator
Pressure sensor plate
The pressure sensor plate serves for monitoring the followingdepending on the type:
� the operating pressure in channel 1 (type VMPA−FB−PS−1)
� an external processing pressure (type VMPA−FB−PS−P1)
� the pressure in the exhaust channels 3 and 5 (type VMPA−FB−PS−3/5).
By means of three LEDs the pressure sensor indicateswhether the pressure applied is less than, is equal to orexceeds the setpoint value. An additional LED shows commonfaults.
1. Summary of components
1−17Festo P.BE−MPA−EN en 0802c
The MPA−S valve terminal can be equipped with up to4�pressure sensor plates.
The limit values for pressure monitoring are set via theparametrizing. You can parametrize the pressure sensor platevia the PLC or the Festo Handheld (CPX−MMI).
How to fit the pressure sensor plate is described in themounting instructions VMPA−FB−PS−... Information on parametrizing the pressure sensor can befound in the Electronics Manual CPX−I/O modules from Festo.
Pneumatic supply plate
You can supply the valves with operating pressure separatelyvia the pneumatic supply plate. This is for example necessaryin the case of valve terminals equipped with several pressurezones or when a large number of valves on the valve terminalare switched simultaneously to flow.
How to fit the pneumatic supply plate is described in chapter�5under �Replace sub−base, supply plate or MPA−S end plate".
Electric supply plate
You can supply the valves with load voltage separately via theelectric supply plate.
How to fit the electric supply plate is described in the mount�ing instructions VMPA−FB−SP−...
1. Summary of components
1−18 Festo P.BE−MPA−EN en 0802c
Pressure zone separation
The MPA−S valve terminal can be equipped with pressurezones.
The pressure zones are formed either by special sub−bases orby special isolating seals.
Separation of the pilot channels 12 and 14 is not intended,as on the MPA−S valve terminal the air supply for the pilotcontrol of the valves is supplied centrally via the pneumaticinterface or the multipin sub−base.
Pressure zone separation with sub−bases
Sub−base for the propor�tional pressure regulator
The sub−base (type VMPA−...) for the proportional pressureregulator always has a pressure zone separation and this isnot therefore marked additionally on the exterior of the sub−base. Pressure zone separation takes place:
� for channel 1 on the left−hand side of the sub−base.
� for channels 3 and 5 on the left−hand and on the right−hand side of the sub−base.
If the proportional pressure regulator is to regulate the op�erating pressure for the valves on the MPA−S valve terminal,the valves must be positioned to the right of the propor�tional pressure regulator.
Sub−bases for the valves On the sub−bases with integrated pressure zone separationthe separation is made in the centre of the sub−base, i.e.on�the
� MPA1: after the second valve position
� MPA2: after the first valve position.
The sub−bases are available in the following designs:
� only supply channel (1) separate
� supply channel (1) and exhaust channels (3 and 5) separate.
1. Summary of components
1−19Festo P.BE−MPA−EN en 0802c
The sub−bases with integrated pressure zone separation aremarked with a notch. By means of the marking you can ascer�tain with which sub−base variant your valve terminal isequipped (see Tab.�1/7).
Sub−base design MPA1 MPA2
Sub−base with separate supplychannel 1
Type: VMPA−AP−4−1−T1 Type: VMPA−AP−2−2−T0
Sub−base with separate supplychannel 1 and separate exhaustchannels 3 and 5
Type: VMPA−AP−4−1−S1 Type: VMPA−AP−2−2−S0
Tab.�1/7: Variants of the sub−bases with pressure zone separation
1. Summary of components
1−20 Festo P.BE−MPA−EN en 0802c
Pressure zone separation with isolating seals
The following channels can be separated with the isolatingseals (see also Tab.�1/8):
� only the supply channel (1)
� the supply channel (1) and exhaust channels (3 and 5)
� only the exhaust channels (3 and 5)
You can recognize whether your MPA−S valve terminal isequipped with pressure zones, and if so how many either bythe marking on the sub−base (see Tab.�1/7) or by the markingon the seal (see Tab.�1/8).
1. Summary of components
1−21Festo P.BE−MPA−EN en 0802c
1
2 3 5
6
7
8
4
9aJ
MPA−S valve terminal with ...
1 Additional identification of the seals/isolating seals for the MPA−S valve terminal with exhaustplates
2 Position of the marking for isolating seals
... flat plate silencer ... exhaust plate
3 Without identification: Seal with openchannels 1, 3 and 5
7 Isolating seal, channels 3 and 5 blocked(Ident. code R)
4 Isolating seal, channels 3 and 5 blocked(Ident. code S)
8 Isolating seal, channel 1 bocked(Ident.�code I)
5 Isolating seal, channel 1 bocked(Ident.�code I)
9 Isolating seal, channels 1, 3 and 5 blocked(Ident. code S)
6 Isolating seal, channels 3 and 5 blocked(Ident. code R)
aJ Without identification: Seal with openchannels 1, 3 and 5
Tab.�1/8: Identification of the seal variants for the sub−bases
1. Summary of components
1−22 Festo P.BE−MPA−EN en 0802c
Vertical stacking
You can fit further pneumatic components in each locationbetween the manifold sub−base and the valve. These compo�nents will enable you to implement certain additional effectsas desired. The following components are available:
Component
Single−solenoid 5/2−way valves
Alternative:two 3/2−way valves or a5/2−way double−solenoid valveor a 5/3−way mid−position valve
Alternative:Cover plate, for sealing an unusedvalve location type MPA....
Pressure regulator plate type: VMPA....B8−R...C2−C−... (with or without pressure gauge).The Tab.�1/10 provides an overview of the available variants ofthe pressure regulator plates.The function of the most important pressure regulator plates is described in the following section.
Vertical stacking, optional components: 1)
Sub−base type MPA....−...−AP−... with electronic module typeVMPA�...−...−EM...
1) Notes on installing the vertical stacking components see chapter 3
Tab.�1/9: Components of the pneumatic module of the MPA−S valve terminal
1. Summary of components
1−23Festo P.BE−MPA−EN en 0802c
Pressure regulator plates
The pressure regulator plates of the vertical stacking aremarked on the MPA−S valve terminal with the Ident. code. Thecode is marked on the side of the component. With the aid ofthe following table you can identify the pressure regulatorplates.
Ident.code
Vertical stacking components MPA1 MPA2
PF Pressure regulator plate P for connection 1, input pressure 6 bar X X
PH Pressure regulator plate B for connection 2, input pressure 6�bar X X
PG Pressure regulator plate A for connection 4, input pressure 6 bar X X
PN Pressure regulator plate B for connection 2, input pressure 6�bar,reversible
−−− X
PM Pressure regulator plate A for connection 4, input pressure 6 bar,reversible
−−− X
PA Pressure regulator plate P for connection 1, input pressure 10�bar X X
PC Pressure regulator plate B for connection 2, input pressure 10�bar X X
PB Pressure regulator plate A for connection 4, input pressure 10 bar X X
PL Pressure regulator plate B for connection 2, input pressure 10�bar,reversible
−−− X
PK Pressure regulator plate A for connection 4, input pressure 10 bar,reversible
−−− X
T Pressure gauge for pressure regulator plate X X
Tab.�1/10: Identification of the pressure regulator plate in the type code
The switching times of the pressure regulator plate can befound in appendix B, Tab.�B/5.
1. Summary of components
1−24 Festo P.BE−MPA−EN en 0802c
Pressure regulator P (identification PF, PA)
Mode of operation:
PressurizingThe pressure regulator P regulates the pressure in front ofthe valve in channel 1 (P). The same regulated work airpressure will then be present in channels 2 and 4.
ExhaustingIn the valve exhausting takes place from channel 2 tochannel 3 and from channel 4 to channel 5.
Pressureregulator
Pressurizing Exhaustingregulator
regulated pressure of thework air
exhaust ducted via theintermediate plate
Pressure regulator P in channels 2 and 4 from channel 2 to channel 3 and from channel 4 to channel 5
Tab.�1/11: Pressure regulator P
The advantages of this pressure regulator are:
� The pressure regulator is not affected by venting, sincethe pressure is regulated before the valve.
� The pressure regulator can always be adjusted, since thepressure from the valve terminal is always present.
Application example:
� An equal working pressure is required at workingconnections 2 and 4.
� A lower working pressure (e.g. 3 bar) is required than theoperating pressure present at the valve terminal(e.g.�8�bar).
1. Summary of components
1−25Festo P.BE−MPA−EN en 0802c
Pressure regulator A or B (identifier PH, PG, PC, PB)
Mode of operation:
PressurizingThe pressure regulator A or B regulates the relevantpressure of the work air (see 1 in Tab.�1/12) when thepressure medium has flowed through the valve. The exhaustair is passed through the intermediate plate and is switchedto the relevant exhaust channel in the valve (see�2 inTab.�1/12).
ExhaustingDuring exhausting the air is passed unregulated through thevalve and the pressure regulator (see 3 in Tab.�1/12).
Pressureregulator
Pressurizing Exhaustingregulator
regulatedpressure ofthe work air1
exhaust vented via theintermediate plate 2
unregulated exhaustvented via the regulator 3
Pressureregulator A
in channel 4 from channel 2 to channel 3 from channel 4 to channel 5
Pressureregulator B
in channel 2 from channel 4 to channel 5 from channel 2 to channel 3
Tab.�1/12: Pressure regulator A or B
1. Summary of components
1−26 Festo P.BE−MPA−EN en 0802c
Fig.�1/11 shows the following switching position of the pressure regulator B: The work air is passed from channel 1 through the intermedi�ate plate and the valve to the pressure regulator plate, whereit is regulated and then passed to connection 2 of the sub−base. The exhaust is passed unregulated via channel 4through the intermediate plate to the valve, where it ispassed to channel 5 and vented.
1
2
3
4
1 Pressure regulator
2 Valve
3 Intermediate plate
4 Sub−base
Fig.�1/11: Pressure regulator B
Restrictions:
� The exhaust flow is restricted in the regulating directionby the pressure regulator.
� The pressure of the work air in channel 2 can only be setand read on the pressure gauge when the valve is in theswitch position (flow from 1 } �2).
1. Summary of components
1−27Festo P.BE−MPA−EN en 0802c
Application examples:
� If two different working pressures are required atconnections 2 and 4 instead of the operating pressure ofthe valve terminal:
� If it is not possible to use the reversible pressureregulator, e.g. when 2x3/2−way valves with ductedexhaust 82/84 are used.
Reversible pressureregulator A or B(identification PN, PM, PL, PK)
Operating method of the reversible pressure regulator:
PressurizingThe reversible pressure regulator splits up the supply air inchannel 1 and regulates the pressure in front of the valve inthe relevant channel (see 1 in Tab.�1/13), in the otherchannel (see 2 in Tab.�1/13) the unregulated pressure fromchannel 1 is present. The regulated air is then switched tothe relevant work channel. The valve is thus operated inreversible mode.
ExhaustingIn the valve the exhaust from the relevant work channel(see�3 in Tab.�1/13) is vented through channel 1 andpassed in the intermediate plate to the relevant exhaustchannel in the sub−base.
Reversiblepressure regulator
Pressurizing Exhaustingpressure�regulatorplate pressure of the
supply airregulated in frontof the valve 1
unregulated pressure of thesupply air 2
exhaust vented viathe intermediateplate 3
Reversible pressureregulator A
in channel 5 in channel 3 from channel 4 viachannel 1 to channel 5
Reversible pressureregulator B
in channel 3 in channel 5 from channel 2 viachannel 1 to channel 3
Tab.�1/13: Reversible pressure regulator A or B
1. Summary of components
1−28 Festo P.BE−MPA−EN en 0802c
Fig.�1/12 shows the following switching position of thereversible pressure regulator B. The supply air in channel 1 issplit up:
� The regulated pressure of the supply air is present inchannel 3. The pressure is regulated in front of the valve.
� The unregulated pressure of the supply air from channel 1is present in channel 5.
In the valve the regulated pressure is switched to channel 2.The unregulated exhaust is switched in the valve fromchannel 4 to channel 1 and then in the intermediate plate tochannel 3.
1
2
3
4
1 Pressure regulator
2 Valve
3 Intermediate plate
4 Sub−base
Fig.�1/12: Reversible pressure regulator B
1. Summary of components
1−29Festo P.BE−MPA−EN en 0802c
Advantages compared to the pressure regulator A or B:
� Faster cycle times
� 50 % higher exhaust flow rate, as air is not exhausted viathe pressure regulator. The load on the pressure regulatoris also reduced.
� No quick exhaust valves are required. The exhaust isducted completely via the valve terminal.
� The pressure regulator is always present at the pressureregulator, as the pressure is regulated before the valve,i.e. the regulator can always be adjusted. With pressureregulator A or B the valve must be switched for this.
Disadvantages compared to the pressure regulator A or B:
� Cannot be combined with 2x2/2−way valves with Ident.code D, I and 2x3/2−way valves with Ident. code N, K, H(non−reversible valves). These valves require operatingpressure in channel 1 for the pneumatic spring (seeswitching symbol in appendix B, Tab.�B/1 and Tab.�B/2).
Application examples:
� When two different pressures are required in ducts 2 and4 instead of the operating pressure of the valve terminal.
� When fast exhaust performance is required.
� When the pressure regulator must always be adjustable.
Instructions on installing these pressure regulator plates canbe found in the assembly instructions VMPA�...−B8−R...C2−C...
1. Summary of components
1−30 Festo P.BE−MPA−EN en 0802c
1.1.3 Connecting and display elements
You will find the following pneumatic connecting, display andoperating elements on the MPA−S valve terminal:
7
2
3
5
6
1
4
1
89aJ
6
3
4
aA
1 Manual override (per pilot solenoid,turning/locking or non−locking)
2 Manual override cover cap
3 Common exhaust connection (3/5)�Valves"
4 Work connections (2, 4) per valve
5 Connection �Pilot exhaust" (82/84)only with variant for ducted exhaust
6 Supply connections �Operatingpressure" (1)
7 Pressure output (2) of the proportionalpressure regulator
8 Exhaust (3) of the proportionalpressure regulator
9 Pressure input (1) of the proportionalpressure regulator
aJ External pressure input of pressuresensor type VMPA−FB−PS−P1
aA Pilot connection �External pilotsupply" (12/14)
Fig.�1/13: Pneumatic connecting and operating elements of the MPA−S valve terminal
1. Summary of components
1−31Festo P.BE−MPA−EN en 0802c
On the pressure regulator plates you will find the followingconnecting and operating elements:
21 4
3
3
2
1 Adjusting screw for pressureregulator�plate MPA1
2 Pressure gauge (optional)
3 Connection for pressure gauge (can be turned 90°)
4 Adjusting knob for pressure regulatorplate MPA2 with free−wheeling andsnap−in locking
Fig.�1/14: Operating and connecting elements of the pressure regulator plates
Information on the electric connecting and display elementsof the CPX bus node can be found in the relevant electronicsmanual (see System Manual for your CPX�terminal, table�Manuals on the CPX terminal"). Information on the electric connecting and display elementsof the CPI module can be found in the leaflet supplied withthe product.
1. Summary of components
1−32 Festo P.BE−MPA−EN en 0802c
You will find the following electric connecting and displayelements on the pneumatic components of the MPA−S valveterminal with CPX terminal or CPI module:
1
2 3 4
6
5
1
3
1 Identification fields
2 Only with MPA−S valve terminal withCPX�terminal: LEDs of the pressuresensor see Fig.�1/16
3 LEDs on the valve: on the MPA1 a dual colour LED/valve;on the MPA2 two LEDs/valve: yellow: signal status display of the
pilot solenoidsred: fault display
4 Green power LED (additional electric supply)
5 Only with MPA−S with CPX terminal:LEDs of the proportional pressureregulator see Fig.�1/17
6 Load voltage connection of thevalves (optional)
Fig.�1/15: Electric connecting and display elements of the MPA−S valve terminal withCPX�terminal or CPI module
1. Summary of components
1−33Festo P.BE−MPA−EN en 0802c
Further information on the LEDs of the electronic moduleVMPA�...−FB−EM...−D2−... can be found in the relevant elec�tronics manual (see System Manual for your CPX terminal,table �Manuals on the CPX terminal").
Pressure sensor plate
The pressure sensor plate has the following display elements:
1 Pressuresensor plate
2 Red LED:pressureexceeded
3 Green LED:pressureobserved
4 Red LED:pressure too low
5 Red LED:common faultdisplay
1
23 4
5
Fig.�1/16: Display elements of the pressure sensor plate
1. Summary of components
1−34 Festo P.BE−MPA−EN en 0802c
Proportional pressure regulator
The proportional pressure regulator has the following displayelements:
1 Green power LED
2 Proportionalpressureregulator
3 Red fault LED
1
2
3
Fig.�1/17: Display elements of the proportional pressure regulator
1. Summary of components
1−35Festo P.BE−MPA−EN en 0802c
You will find the following electric connecting elements on themultipin connection of the MPA−S valve terminal:
1 Sub−D multipinplug with cable
2 Connection forfunctional earth
3 Sub−D connection
1
2
3
Fig.�1/18: Electric connecting elements of MPA−S valve terminal with multipin connection
1. Summary of components
1−36 Festo P.BE−MPA−EN en 0802c
You will find the following display elements on the pneumaticmodules of the MPA−S valve terminal with multipin connectionor AS−Interface:
1 MPA1: yellow LEDs:Signal statusdisplay of thepilot solenoids
2 MPA2: yellow LEDs:Signal statusdisplay of thepilot solenoids
3 Label supportswith inscriptionfield
1 2 3
Fig.�1/19: Electric display elements of MPA−S valve terminal with multipin connection orwith AS−Interface
Information on the electric connecting and display elementsof the AS−Interface can be found in the leaflet supplied withthe product.
Fitting
2−1Festo P.BE−MPA−EN en 0802c
Chapter 2
2. Fitting
2−2 Festo P.BE−MPA−EN en 0802c
Contents
2. Fitting 2−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1 General instructions on fitting and dismantling 2−4 . . . . . . . . . . . . . . . . . . . . . . .
2.2 Fitting variants 2−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2.1 Fitting onto/removing from a hat rail 2−6 . . . . . . . . . . . . . . . . . . . . . . . .
2.2.2 Fitting onto/removing from a hat rail 2−11 . . . . . . . . . . . . . . . . . . . . . . . .
2.3 Fitting/removing the inscription label holders 2−13 . . . . . . . . . . . . . . . . . . . . . . . .
2.4 Fitting/removing the manual override caps (optional) 2−15 . . . . . . . . . . . . . . . . .
2. Fitting
2−3Festo P.BE−MPA−EN en 0802c
Contents of this chapter The MPA−S valve terminal is already assembled when sup�plied from the factory. Accessories such as inscription labelsand manual override caps (optional) must be fitted on site.
This chapter describes how to fit and remove:
� The complete MPA−S valve terminal
� The inscription labels
� The manual override caps
Further information Special information on replacing or adding pneumaticcomponents can be found in chapter 5.
MPA−S valve terminal with CPX terminal:
� Information on fitting the MPA−S valve terminal withCPX�terminal can be found in the CPX system manual.
� Information on fitting and removing I/O modules can befound in the I/O module manual, table �Manuals on theCPX terminal").
� Information on fitting modules and components orderedat a later stage can be found in the leaflet supplied withthe product.
2. Fitting
2−4 Festo P.BE−MPA−EN en 0802c
2.1 General instructions on fitting and dismantling
WarningSudden unexpected movements of the connected actua�tors and uncontrolled movements of loose tubing cancause injury to human beings and/or damage to property.
Before carrying out installation and maintenance work,switch off the following:
� the compressed air supply
� the operating and load voltage supplies.
NoteHandle all modules and components of the MPA−S valveterminal with great care. Note especially the following:
� The specified torques must be observed.
� Electrostatically sensitive components. Do not therefore touch any contact surfaces.
2. Fitting
2−5Festo P.BE−MPA−EN en 0802c
2.2 Fitting variants
You can mount the MPA−S valve terminal in one of two ways:
Mountingmethod
Description
H−railmounting
The MPA−S valve terminal is suitable for fitting ontoa hat rail (support rail as per EN�60715). There is aguide groove on the back for hanging the valveterminal onto the hat rail.
Wall mounting The multipin sub−base or the pneumatic interfaceand the end plates contain holes for fitting theterminal onto a wall. With MPA−S valve terminalswhich are longer than 280 mm, additional fasteningbrackets on the supply plate are necessary (see instructions on vibration and shock inappendix A, Tab.�A/2).
Tab.�2/1: Mounting methods of the MPA−S valve terminal
NoteMount the MPA−S valve terminal so that there is sufficientspace for heat dissipation and ensure that the maximumlimits for temperatures are observed (see �Technicalspecifications").
2. Fitting
2−6 Festo P.BE−MPA−EN en 0802c
2.2.1 Fitting onto/removing from a hat rail
CautionHat rails with mounted valve terminals can break if theyare subjected to vibrations which exceed severity grade 1:
� 0.15 mm path at 15 � 58 Hz
� 2 g acceleration at 58 � 150 Hz
This can cause damage to the valve terminal or to yourmachine or system.
· In this case, use the wall fitting.
· Observe the permissible values for vibration and shockin appendix A �Technical specifications."
Caution� A hat rail fitting without a hat rail clamping unit is notpermitted.
In order to fit the valve terminal onto a hat rail you will requirethe following mounting kits:
� MPA−S valve terminal with multipin connection: CPA−BG−NRH. This kit contains 2 M4x10 screws and2�clamping elements
� for MPA−S valve terminals with CPX terminal: CPX−CPA−BG−NRH. This kit contains 3 clamping elementsand 3 M4x10 screws.
2. Fitting
2−7Festo P.BE−MPA−EN en 0802c
Variant Fastening points
1 1
MPA−S valve terminal with CPX terminal
2
Necessary fastening of the hatrail clamping units:� in the end plates:
each with an M4 screw 1� in the pneumatic interface:
with an M4 screw 2
1
MPA−S valve terminal with multipin connection
1
Necessary fastening of the hatrail clamping units:� In the right−hand end plate
and in the multipin sub−base:each with an M4 screw 1
Tab.�2/2: Necessary fastening points for the hat rail fitting
Fitting Proceed as follows:
1. Make sure that the fastening surface can support theweight of the MPA−S valve terminal (weights seeappendix�A, Tab.�A/1).
2. Fit the hat rail (support rail EN 60715 � 35x7.5; width 35 mm, height 7.5 mm). Make sure there issufficient space for connecting the supply cables andtubing.
3. Fasten the hat rail to the fastening surface at intervals ofapprox. every 100 mm.
2. Fitting
2−8 Festo P.BE−MPA−EN en 0802c
4. Fit the hat rail clamping unit to all necessary fasteningpoints (see Tab.�2/2).
5. Hang the MPA−S valve terminal onto the hat rail(see�Fig.�2/1, arrow A).
6. Swing the MPA−S valve terminal onto the hat rail(see�Fig.�2/1, arrow B). Make sure that the clampingelement lies horizontally to the hat rail.
1 H−rail
2 Locking screw ofthe hat railclamping unit
3 Clampingelement of thehat rail clampingunit
ÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔ
ÔÔÔÔÔÔÔÔ
(A)
(B)
1
2
3
Fig.�2/1: Fitting the MPA−S valve terminal onto a hat rail
7. Fasten the MPA−S valve terminal, as with the CPX terminal,against tilting or sliding by tightening the locking screwwith 1.3 Nm.
2. Fitting
2−9Festo P.BE−MPA−EN en 0802c
1 H−rail
2 Clamping elementof the hat railclamping unit 1
2
Fig.�2/2: Rear view: Fitting the CPX terminal as an example onto a hat rail
Information on fitting the MPA−S valve terminal withCPX�terminal can be found in the CPX system manual.
Dismantling Proceed as follows:
1. Loosen the locking screw of the hat rail clamping unit�(position of the screws see Tab.�2/2). Make sure that theclamping element lies horizontally to the hat rail.
2. Swing the MPA−S valve terminal forwards away from thehat rail (see Fig.�2/3).
3. Lift the MPA−S valve terminal away from the hat rail(see�Fig.�2/3).
2. Fitting
2−10 Festo P.BE−MPA−EN en 0802c
1 H−rail
2 Locking screw ofthe hat railclamping unit
3 Clamping elementof the hat railclamping unit
ÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔÔ
ÔÔÔÔÔÔÔÔ
1
A
B
2
3
Fig.�2/3: Dismantling the MPA−S valve terminal
2. Fitting
2−11Festo P.BE−MPA−EN en 0802c
2.2.2 Fitting onto/removing from a hat rail
The end plates, the MP sub−base and pneumatic interfacecontain holes for fitting the terminal onto a wall(see�Tab.�2/3).
CautionMPA−S valve terminals can become distorted and thereforedamaged if they are mounted on an uneven pliablesurface.
· Fit the MPA−S valve terminal only onto a flat fixedsurface.
Overstressing the fastening holes, bending the MPA−Svalve terminal with CPX terminal or internal vibrations cancause damage.
· Observe the instructions in appendix A, Tab.�A/2 foradditionally fastening the MPA−S valve terminals if theseare longer than 280 mm.
· In these cases use the additional fastenings for the CPXterminal (see instructions in the manual for the CPXsystem).
Fitting Proceed as follows:
1. Make sure that the fastening surface is flat and that it cansupport the MPA−S valve terminal (weights see appen�dix�A, Tab.�A/1).
Make sure there is sufficient space for connecting the supplycables and tubing.
2. Drill mounting holes in the fastening surface.
3. Fasten the MPA−S valve terminal with M4 or M6 screws ofsufficient length to the fastening surface as per Tab.�2/3).
2. Fitting
2−12 Festo P.BE−MPA−EN en 0802c
Variant Fastening points
1 1
22
1
1
2
1
MPA−S valve terminal with CPX terminal
1
2
3
Necessary fastening:
� End plates: two M4 1 or M6screws 2 each
� Pneumatic interface: two M4 screws 1
� Per fastening bracket to thepneumatic supply plate or theproportional pressure regula�tor (see also notes in appen�dix A, Tab.�A/2): one M6 screw 3
Note:If your MPA−S valve terminal isfitted with four or more CPXmanifold sub−bases, fasteningclips type CPX−BG−RW−... mustbe used as additional fastenings(see system manual for the CPXterminal)
1
1
1
1
2
2 2
2
MPA−S valve terminal with multipin connection
3
Necessary fastening:
� Multipin sub−base: two M4 1or M6 screws 2 each
� right−hand end plate: two M41 or M6 screws 2 each
� Per fastening bracket to thepneumatic supply plate (see also instructions in ap�pendix A, Tab.�A/2): one M6 screw 3
Tab.�2/3: Methods of fastening the MPA−S valve terminal
2. Fitting
2−13Festo P.BE−MPA−EN en 0802c
Dismantling Proceed as follows:
1. Prevent a hanging−mounted MPA−S valve terminal fromfalling down before you loosen it from the fasteningsurface.
2. Loosen the fastening screws (see Tab.�2/3).
3. Remove the MPA−S valve terminal from the fasteningsurface.
2.3 Fitting/removing the inscription label holders
An inscription label holder can be fitted onto each sub−baseto enable the valves or work connections to be distinguished.
Fitting Proceed as follows:
· Clip the inscription label holders into the grooves in thesub−bases (see diagram):
1 Support for labelholder on thesub−base
2 Inscription labelholder
1
2
Fig.�2/4: Fitting the inscription label holder
2. Fitting
2−14 Festo P.BE−MPA−EN en 0802c
Dismantling Proceed as follows:
1. Remove the 3rd. and 4th. valves from the relevant sub−base.
2. Unlock the inscription label holder by using a screwdriver(blade width max. 3.5 mm) to press down the snap hook(see diagram).
1 Holes forunlocking theinscription labelholder
2 Inscription labelholder
1
2
Fig.�2/5: Removing the inscription label holder
3. Pull the inscription label holder out of the recess in thesub−base.
2. Fitting
2−15Festo P.BE−MPA−EN en 0802c
2.4 Fitting/removing the manual override caps (optional)
The locking/non−locking function of the manual override canbe modified to only non−locking actuation if a cap is fitted inthe manual override.
Fitting Proceed as follows:
1. Make sure that the relevant manual overrides are in anon−actuated state. If necessary, set locking manualoverrides to the basic position (see chapter 4, Tab.�4/5).
2. Place the cap on the manual override so that the snaphooks of the cover can grip into the recess on the manualoverride.
3. Clip the manual override caps into the grooves in themanual overrides (see diagram):
1 Manual overridecover caps
2 Manual override 1
2
Fig.�2/6: Fitting the manual override cover caps
2. Fitting
2−16 Festo P.BE−MPA−EN en 0802c
NoteThe manual override cover caps serve for limiting the func�tion of the manual override and are constructed so thatthey can only be removed with a great deal of strength.During dismantling the snap hooks of the cover will bedamaged.
Dismantling Proceed as follows:
· Use a suitable screwdriver to lift the manual override capsout of the manual overrides (see figure):
Fig.�2/7: Removing the manual override cover caps
Installation
3−1Festo P.BE−MPA−EN en 0802c
Chapter 3
3. Installation
3−2 Festo P.BE−MPA−EN en 0802c
Contents
3. Installation 3−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 Preparing the compressed air 3−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1.1 Operation with non−lubricated compressed air 3−4 . . . . . . . . . . . . . . . .
3.1.2 Operation with lubricated compressed air 3−5 . . . . . . . . . . . . . . . . . . . .
3.2 General instructions on installation 3−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3 Laying the tubing 3−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4 Connecting the MPA−S valve terminal 3−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4.1 Pilot control of the valve solenoid coils (pilot air) 3−12 . . . . . . . . . . . . . .
3.4.2 MPA−S valve terminal with pressure zone separation 3−13 . . . . . . . . . . .
3.4.3 Operation of the MPA−S valve terminal with reversible pressure regulators 3−16 . . . . . . . . . . . . . . . . . . . . . . . . .
3.4.4 Setting the pressure regulator 3−16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4.5 Vacuum / low pressure operation 3−19 . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4.6 Connecting the pneumatic tubing 3−21 . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4.7 Connecting the electric cables 3−25 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.5 Address assignment of the valves 3−30 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.5.1 MPA−S valve terminal with CPX terminal 3−30 . . . . . . . . . . . . . . . . . . . . .
3.5.2 MPA−S valve terminal with CPI module or AS−Interface 3−32 . . . . . . . . . .
3.5.3 MPA−S valve terminal with multipin connection 3−32 . . . . . . . . . . . . . . .
3. Installation
3−3Festo P.BE−MPA−EN en 0802c
Contents of this chapter This chapter describes the tubing and cabling of the MPA−Svalve terminal. The following belong here:
� General instructions on preparing the compressed air andon connecting the tubing
� Instructions on pilot control of the valve solenoid coilswith internal or external pilot air
� Instructions on operating the MPA−S valve terminal withpressure zone separation
� Fitting the QS screw connectors
� Connecting the power supply
� Earthing the MPA−S valve terminal
� Address assignment of the valves
Further information Instructions on connecting the electric elements of the MPA−Svalve terminal with multipin connection can be found in theleaflet supplied with the product.
Requirements for observing the certified UL conditions if theproduct is operated in the USA or Canada can be found in theseparate special UL−specific documentation.
Instructions on connecting the operating voltage can befound in the system manual for your CPX terminal.
Detailed instructions on connecting the CPX modules (busnode, I/O modules etc.) can be found in the relevant manualsfor the CPX module (see system manual for your CPX terminal,table �Manuals on the CPX terminal").
Detailed instructions on addressing the pneumatic modulesof the MPA−S valve terminal with CPX terminal can be found inthe electronics manual for the module (see system manualforyour CPX terminal, table �Manuals on the CPX terminal").
3. Installation
3−4 Festo P.BE−MPA−EN en 0802c
3.1 Preparing the compressed air
CautionNon−filtered or incorrectly lubricated compressed air willreduce the service life of the valve terminal.
3.1.1 Operation with non−lubricated compressed air
CautionToo much residual oil in the compressed air will reduce theservice life of the valve terminal.
� If bio−oils are used (oils with synthetic ester or true esterbasis, e.g. rape oil methylester), the residual oil contentmust not exceed 0.1 mg/m3(see ISO 8573−1 class 2).
� If mineral oils are used (e.g. HLP oils as per DIN�51524parts 1 to 3) or corresponding oils on a polyalphaolefinebasis (PAO), the residual oil content must not exceed5�mg/m3 (see ISO 8573−1 class 4).
You will thereby avoid functional damage to the valves.
Excessive residual oil cannot be permitted irrespective of thecompressor oil, as otherwise the basic lubrication will bewashed out during the course of time.
3. Installation
3−5Festo P.BE−MPA−EN en 0802c
3.1.2 Operation with lubricated compressed air
Operate your system with non−lubricated compressed air ifpossible. This will prevent pollution of the environment. Festopneumatic valves and actuators have been designed so that,if used as intended, they will not require additional lubrica�tion and will still achieve a long service life.
CautionOperation with lubricated compressed air will cause theservice life lubrication, which is necessary for non−lubri�cated operation, to be �washed out".
Note the following instructions if lubricated compressed airmust be used. The compressed air prepared with the compressor mustcorrespond in quality to non−lubricated compressed air. Ifpossible, do not operate the complete system with lubricatedcompressed air. If possible, always install the lubricatorsdirectly in front of the consuming actuator.
CautionIncorrect additional oil and too much residual oil content inthe compressed air will reduce the service life of the valveterminal.
� Use Festo special oil OFSW−32 or the other oils listed inthe Festo catalogue (as per DIN 51524−HLP32, basicviscosity 32 CST at 40 °C).
� The additional lubrication must not exceed 25 mg/m3
(ISO 8573−1 class 5).
� Make sure that the lubricator setting is correct (see following section).
You will thereby avoid functional damage to the valves.
3. Installation
3−6 Festo P.BE−MPA−EN en 0802c
Setting the lubricator: with the machine running (typical operating status) 0.2 tomax. 1 drop/min. or 0.5 to 5 drops/1000 l air.
Checking the setting: the procedure described below can be used for checking thesetting of the lubricator.
Proceed as follows:
· Check the service units in respect of condensate andlubricator setting twice a week.
1. Ascertain the cylinder which is furthest from thelubricator.
2. Ascertain the valve terminal which controls this cylinder.
3. Remove the silencer, if fitted, from connection 3/5.
4. Hold a piece of white cardboard 10 cm in front of theexhaust port.
5. Let the system run for a short period.
� There must be only a slight yellow colouring on thecardboard. If oil drops out, this is an indication thattoo much oil has been used.
Another indication of over−lubrication is the colouring or thecondition of the exhaust air silencer. A distinctly yellowcolouring of the filter element or drops of oil on the silencerindicate that the lubricator setting is too high.
3. Installation
3−7Festo P.BE−MPA−EN en 0802c
3.2 General instructions on installation
WarningSudden unexpected movements of the connected actua�tors and uncontrolled movements of loose tubing cancause injury to human beings and/or damage to property.
Before carrying out installation and maintenance work,switch off the following:
� the compressed air supply
� the operating and load voltage supplies.
NoteObserve the following if the UL requirements are to becomplied with in your application:
� Rules for observing the UL certification can be found inthe separate UL−specific documentation. The relevanttechnical specifications listed there also apply here.
� The technical specifications in this documentation mayshow different values.
Pay particular attention to the following:The components of the valve terminal contain electrostaticallysensitive elements. The components will be damaged if youtouch the contact surfaces of the plug connectors or if you donot observe the regulations for handling electrostaticallysensitive components.
3. Installation
3−8 Festo P.BE−MPA−EN en 0802c
NoteWhen large−volume actuators are exhausted or if theexhaust performance is too low, back pressures can occurin the exhaust channels of the valve terminal. The backpressures can lead to other valves being pressurized,especially non−switched 3/2−way valves which are closedin the normal position.
Avoiding back pressures
� Optimize the exhaust peformance of the valve terminal,e.g by using additional pneumatic supply plates.
� If necessary, separate the exhaust channels with theisolating seals with Ident. code R (channels 3 and 5blocked, see Tab.�1/8).
3. Installation
3−9Festo P.BE−MPA−EN en 0802c
3.3 Laying the tubing
If elbow screw connectors or multiple distributors are used,the airflow will be reduced slightly.
Connecting Proceed as follows:
1. Push the tubing as far as possible into or over the tubeconnection of the screw connector.
2. Pull the locking ring 1 over the tubing connection ortighten the locking screw 2.
3. For reasons of clarity, group the tubing together with: � tube straps or� multiple hose holders.
1
2
Fig.�3/1: Fitting the tubing
Disconnecting Proceed as follows:
WarningIf the pneumatic tubing is under pressure when connec�tions are loosened, it may perform sudden unexpectedmovements, thereby causing injury to human beings. Carry out the following steps before disconnecting thepneumatic tubing on the MPA−S valve terminal:
· Switch off the compressed air supply.
· Make sure that all pneumatic tubing is pressureless.
· Exhaust all actuators controlled by valves which areblocked in the rest or mid−positions.
3. Installation
3−10 Festo P.BE−MPA−EN en 0802c
1. Mark all pneumatic tubing.
2. Press down the locking ring of the screw connector 1e.g. with a screwdriver or the loosening tool QSO fromFesto or loosen the locking screw 2 of the screwconnector.
3. Remove the tubing from the screw connector.
4. Seal non−required screw connectors with blankingplugs�3.
1
2
3
Fig.�3/2: Disconnecting the tubing
3. Installation
3−11Festo P.BE−MPA−EN en 0802c
3.4 Connecting the MPA−S valve terminal
On sub−bases fitted with cover plates seal the work connec�tions (2 or 4) with blanking plates or threaded blanking plugs.This measure will protect the connections from dirt.
For the optimum performance of the valve terminal we recom�mend that the valves be supplied via more than one supplyand exhaust line when:
� more than 6 valves of size MPA1 or
� more than 3 valves of size MPA2
are switched simultaneously to flow.
Connections on the following components are available forsupplying the valve terminal:
on the MPA−S valve terminal with CPX terminal:
� on the pneumatic interface
� on the optional pneumatic supply plate, maximumbetween each sub−base
on the MPA−S valve terminal with multipin connection:
� on the multipin sub−base
� on the optional pneumatic supply plate, maximumbetween each sub−base.
3. Installation
3−12 Festo P.BE−MPA−EN en 0802c
3.4.1 Pilot control of the valve solenoid coils (pilot air)
Depending on the variant of the pneumatic interface or multi�pin sub−base, pilot control of the valve solenoid coils is car�ried out with internal or external pilot air. You can ascertainthe pilot control variant for which your MPA−S valve terminalis equipped, by the following features (see table).
Pilot control variants Pilot control connection 12/14 on the pneumaticinterface or multipin sub−base
Operation with external pilot air marked and open
Operation with internal pilot air not marked and closed
Tab.�3/1: Recogniton features of the pilot control variants
Internal pilot air supply If the operating pressure lies between 3 � 8 bar, you canoperate the pilot control of the valve solenoid coils with in�ternally branched pilot air. The auxiliary pilot air is branchedhere in the pneumatic interface or from supply channel 1 inthe multipin sub−base.
Note· Internal pilot air is branched centrally for all valve coilsfrom supply connection 1 in the pneumatic interface ormultipin sub−base. This also applies when the MPA−Svalve terminal is operated with several pressure zones(see Fig.�3/3).
External pilot air supply If the operating pressure lies below 3 bar or above 8 bar,pilot control of the valve solenoid coils must be operatedwith external pilot air. The pilot air is supplied via pilotconnection 12/14.
3. Installation
3−13Festo P.BE−MPA−EN en 0802c
Note· Use closed−loop regulated external pilot air (3 � 8 bar).Reliable faultless operation of the MPA−S valve terminalis then possible, e.g. even with fluctuating operatingpressure.
· The external pilot air for all valve solenoid coils issupplied centrally via pilot connection 12/14 dependingon the electric connection variant on the pneumaticinterface or on the multipin sub−base. This is the caseeven if the MPA−S valve terminal is operated withdifferent pressure zones.
· Set the external pilot air to correspond to theoperating pressure at which these valves are operated (see diagrams in appendix A Fig.�A/1 and Fig.�A/2).
3.4.2 MPA−S valve terminal with pressure zone separation
The pressure zones are formed either by special sub−bases orby special isolating seals.
You can ascertain whether your MPA−S valve terminal isequipped with pressure zones, and if so how many by themarking on the sub−base (see chapter 1, Tab.�1/7) or by themarking on the seal (see chapter 1, Tab.�1/8).
The sub−base (type VMPA−...) for the proportional pressureregulator always has a pressure zone separation and this isnot therefore marked additionally on the exterior of the sub−base. The pressure zone separation of channels 1, 3 and 5takes place on the left−hand side of the sub−base.
3. Installation
3−14 Festo P.BE−MPA−EN en 0802c
Note· Operate the valves with Ident. code I (2x2/2−way valve)in a separate pressure zone with separate exhaustchannnel 5 if the MPA−S valve terminal is also fitted withother valves.
Note the following in the case of the MPA−S valve terminalswhich are operated with internal pilot air and which haveseveral pressure zones:
· The pilot air supply is branched centrally for all valvecoils from supply connection 1 in the pneumatic inter�face or from the multipin sub−base (see Fig.�3/3).
· The pressure zone, which is supplied via the supplyconnection �1 of the pneumatic interface or the multipinsub−base, must be operated at a pressure between3���8 bar.
If the proportional pressure regulator is to regulate the oper�ating pressure for the valves on the MPA−S valve terminal, thevalves must be positioned to the right of the proportionalpressure regulator.
The following diagram shows as an example of an MPA−Svalve terminal with blocked channels 1, 3 and 5 the assign�ment of the supply and exhaust connections to the valves.
A pressure zone seal and a pneumatic supply plate isrequired for each pressure zone (see figure).
The connections 1 or 3/5 are:
� for the pressure zone on the outside left of the pneumaticinterface or multipin sub−base.
� for all other pressure zones on the pneumatic supplyplate which lies within the relevant pressure zones. The position of the supply plate in the pressure zone (left,centre or right) is optional, but two supply plates (e.g. ofneighbouring pressure zones) must not lie next to eachother.
3. Installation
3−15Festo P.BE−MPA−EN en 0802c
By fitting an additional pneumatic supply plaate within apressure zone you can provide additional supply air or extractexhaust air.
ÖÖÖÖÎÎÎÎÖÖÖÖÎÎÎÎ
ÖÖÖÖÎÎÎÎÖÖÖÖÖÎÎÎÎÎ
ÖÖÖÖÎÎÎÎÖÖÖÖÎÎÎÎ
12 3 4
5
67
12/14
1 1 1
3/5 3/53/5
1 Pneumatic interface or multipinsub−base with supply connection 1 for presssure zone 1 and pilotconnection 12/14 for the completevalve terminal
2 Pressure zone 1
3 Pressure zone 2
4 Pressure zone 3
5 Supply plate for pressure zone 3
6 Identification of the pressure zonedividing seal (projecting flag)
7 Supply plate for pressure zone 2
Fig.�3/3: Example of MPA−S valve terminal with 3 pressure zones
3. Installation
3−16 Festo P.BE−MPA−EN en 0802c
3.4.3 Operation of the MPA−S valve terminal with reversible pressureregulators
NoteOperation of the MPA−S valve terminal with reversiblepressure regulators (Ident. code PN, PM, PL, PK):
· Reversible pressure regulators must not be used onreversibly operated valve terminals.
· No 2x2/2−way valves with Ident. code D, I or 2x3/2−wayvalves with Ident. code N, K, H (non−reversible valves)may be operated with these pressure regulators.
3.4.4 Setting the pressure regulator
The pressure regulator plates can be set with the followingoperating elements:
� with size MPA1 via the adjusting screw
� with size MPA2 via the adjusting knob or the adjustingscrew.
Setting the pressure regulator (MPA2) via theadjusting knob
Proceed as follows:
1. Pull the adjusting knob 2 as far as possible out of thelocking level 1 into the setting level 3 (see Fig.�3/4).
2. Set the desired regulating variable at this level (see �Flowdiagrams of the pressure regulator plates" in appendix A)by turning the adjusting knob.
3. Installation
3−17Festo P.BE−MPA−EN en 0802c
3. Press the adjusting knob into the free running level 4. In this position you can turn the setting wheel withoutmodifying the regulating variable.
4. Turn the adjusting knob at right angles to the pressureregulator plate.
5. Press the adjusting knob in this position into the snap−inlocking of the locking level 1.
2
1
3 4
1. 2.
3.
4. 5.
1
1 Adjusting knob in the locking level
2 Adjusting knob
3 Adjusting knob in the setting level
4 Adjusting knob in the free−runninglevel
Fig.�3/4: Setting the pressure regulator plates (size MPA2) with the aid of the adjustingknob
3. Installation
3−18 Festo P.BE−MPA−EN en 0802c
Setting the pressure regulator via the adjustingscrew in the adjusting button (MPA2)
NoteIf the space around the adjusting knob is not sufficient forsetting the pressure regulator (size MPA2), use the sockethead screw in the adjusting knob.
Proceed as follows:
· Turn the adjusting screw (setting see Fig.�3/5) to set thedesired regulating variable (see �Flow diagrams of thepressure regulator plates" in appendix A).
1 Adjusting screw,socket head(A/F�2.0)
1
Fig.�3/5: Setting the pressure regulator plates (size MPA2) with the aid of the adjustingknob
3. Installation
3−19Festo P.BE−MPA−EN en 0802c
3.4.5 Vacuum / low pressure operation
NoteThe 2x2/2−way valves with Ident. code D, I and the2x3/2−way valves with Ident. code N, K, H are not suitablefor vacuum or low pressure operation if they are suppliedvia connection 1.
· Operate these valves in a separate pressure zone.
· The operating pressure for this pressure zone must beset in accordance with the diagram in Fig.�A/1.
If valves are used for switching vacuum, filters must beused in the suction line in order to avoid functionaldamage due to dirt.
The following conditions must be fulfilled before you canoperate your MPA−S valve terminal at supply connection 1with vacuum or low pressure between −0.9 � 3 bar:
� The pilot control of the valve solenoid coils is operatedwith external closed−loop regulated pilot air.
� The valve terminal is fitted with the following valve platesand, in some cases has further pressure zones.
Valve plates
Pressure zone withvacuum orlow−pressure supplyvia connection 1 1)
The pressure zone must be fitted only with the following valve plates:� 5/2−way valve, single−solenoid (Ident. code M)� 5/2−way valve, double−solenoid (Ident. code J)� 5/3−way valves (Ident. codes B, E and G)� 3/2−way valve (Ident. code W and X) see 2) and the following note
Pressure zone withover pressure supply 3)
via connection 1
The pressure zone can also be fitted with the following valve plates:� 2x3/2−way valves (Ident. code H, K and N)� 2x2/2−way valves (Ident. code D and I), see also the following note
1) The valve plates with Ident. code D, H, K, N and I are not suitable for vacuum or low−pressure operation if they are supplied via connection 1
2) in accordance with diagrams in appendix A, Fig.�A/23) in accordance with diagrams in appendix A, Fig.�A/1
Tab.�3/2: Valve plates
3. Installation
3−20 Festo P.BE−MPA−EN en 0802c
NoteValve with Ident. code I, 2x2/2−way valves:
� With this valve vacuum is supplied via connection 5. Thevacuum is switched to connection 4 with valve coil 14.
� The operating pressure at connection 1 can be used as areject pulse at connection 2. The operating pressure isswitched to connection 2 with valve coil 12.If the MPA−S valve terminal is also fitted with othervalves, operate this valve in a separate pressure zonewith separate exhaust channel 5.
Valve with Ident. code W and X, 3/2−way valve:
� These valves can be supplied individually and thereforeoperated in the pressure range −0.9 � 10 bar. They areindependent of supply connection 1 of the valveterminal. The connections via which these valves aresupplied with compressed air or vacuum and via whichexhaust air is removed are shown in Tab.�3/3.
The pilot air is supplied via the valve terminal.
3/2−way valve Compressed airor vacuum viaconnection
Exhaust viaconnection
Ident. code X 4 3
Ident. code W 2 5
Tab.�3/3: Connections to the valves with Ident. code X and W
3. Installation
3−21Festo P.BE−MPA−EN en 0802c
3.4.6 Connecting the pneumatic tubing
Note· Use blanking plugs to seal all connectionsnot requiredfor the functioning of the MPA−S valve terminal.
Position of the pneumatic connections
NoteIf the MPA−S valve terminals are fitted with large surfacemounted silencers, the exhaust from channels 3/5, and82/84 will be vented through the surface mountedsilencers.
NoteOn the MPA−S valve terminals with exhaust plates, the pilotexhaust is vented on at least one supply unit via connec�tion 82/84.
Fit the screw connector or the silencers according to the tablebelow. Then lay the tubing.
NoteMake sure that the proportional pressure regulator is sup�plied with a constant pressure. A constant supply pressureis necessary for good control quality. For a constant pres�sure supply use the separate supply connection on thesub−base of the proportional pressure regulator.
3. Installation
3−22 Festo P.BE−MPA−EN en 0802c
1
2
4
82/84
12/14
3/5
1
3/5
4
2
1
3P1
2
Fig.�3/6: Pneumatic connections of the MPA−S valve terminal
3. Installation
3−23Festo P.BE−MPA−EN en 0802c
Tubing Connection code(ISO 5599)
Connection size(ISO 228)
Connection 1)
Compressed air or vacuum
1 G¼" Screw connector in thepneumatic interface, in themultipin sub−base or in thepneumatic supply plate
Pilot air (external pilot air supply)
12/14 M7 Screw connector in thepneumatic interface or in themultipin sub−base
Ducted exhaust from the valves
3/5 QS10 Screw connector in exhaustplate 2)
Ducted exhaust from the pilot control
82/84 M7 Screw connector in thesupply plate�2)
Work air or vacuum 2 or 4 MPA1: M7MPA2: GÁ"
Screw connector in thesub−base
Connection for externalpressure
P1 M7 Screw connector in pressuresensor platetype�VMPA−FB−PS−P1
Pressure inputPressure outputExhaust of the VPPM−6TA
123
G ¼"G ¼"G ¼"
Screw connector in thesub−base of the proportionalpressure regulator
1) Depending on what you have ordered, the MPA−S valve terminal may already be fitted with QS�screw connectors.
2) Only with MPA−S valve terminals with exhaust plate or supply plate
Tab.�3/4: Assignment of the connections
Observe the following instructions on installing the pneu�matic components. Only then can you guarantee faultlessoperation.
3. Installation
3−24 Festo P.BE−MPA−EN en 0802c
NoteIn the case of several systems with centrally ductedexhaust air:
· Use non−return valves in the common exhaust lines 3/5or 82/84 in order to prevent functional impairment dueto back pressures.
1 First MPA−S valveterminal
2 Common 3/5
3 Central 82/84
4 Central 3/5
5 Second MPA−Svalve terminal
6 Common 82/84
1
2
3 4 5
6
6
2
2
Fig.�3/7: Common lines with non−return valves
3. Installation
3−25Festo P.BE−MPA−EN en 0802c
3.4.7 Connecting the electric cables
Warning· In order to provide the electric power supply, use onlyPELV circuits as per IEC/DIN EN 60204−1 (ProtectiveExtra−Low Voltage, PELV).Take into account also the general requirements forPELV circuits as per IEC/DIN EN 60204−1.
· Use only power packs which guarantee reliableelectrical isolation of the operating voltage as perIEC/DIN EN�60204−1.
By the use of PELV power units, protection against electricshock (protection against direct and indirect contact) isguaranteed in accordance with IEC/DIN EN 60204−1(electrical equipment of machines, general requirements).
NoteCheck within the framework of your EMERGENCY STOPcircuit, to ascertain the measures necessary for puttingyour machine/system into a safe state in the event of anEMERGENCY STOP (e.g. switching off the operating voltagefor the valves and output modules, switching off thecompressed air).
MPA−S valve terminal with CPX terminal: Instructions on connecting the operating voltage can befound in the system manual.
Detailed instructions on connecting CPX modules (bus node,I/O modules etc.) can be found in the relevant manuals forthe CPX modules (see system manual for your CPX terminal,table �Manuals on the CPX terminal").
MPA−S valve terminal with multipin connection: Instructions on connecting the electric elements of the MPA−Svalve terminal with multipin connection can be found in theleaflet supplied with the product.
3. Installation
3−26 Festo P.BE−MPA−EN en 0802c
Additional load voltage supply of the valves via anelectric supply plate
The electric supply plate type VMPA−FB−SP−...−V−... serves forsupplying the valves additionally with load voltage when, forexample, the valve terminal is to be operated with differentvoltage zones or when the necessary load voltage canot beprovided by the CPX terminal alone.
NoteDamage to components and functional damage
Please note:
� that with MPA−S valve terminals with more than8�sub−bases an electric supply plate is required forsupplying the load voltage.
� that only the electronic modules with electrical isolationtype VMPA�...−FB−EMG−... are permitted to the right of theelectric supply plate (see also section 5.3.5). If yourMPA−S valve terminal is to be equipped only withelectronic modules without electrical isolation(type�VMPA�...−FB−EMS−...), the pneumatic componentsmust be supplied exclusively via the manifold block withthe system supply (type CPX−GE−EV−S) of the CPXterminal.
� that the electric supply plate must not be installeddirectly to the left of a pneumatic supply plate(type�VMPA1−FB−SP−...).
� that you do not touch the electrostatically sensitivecontact surfaces of the plug connectors on the side ofthe electric supply plate.
Connect the relevant electric supply plate as described in thefollowing table.
3. Installation
3−27Festo P.BE−MPA−EN en 0802c
Plug M18 Pin assignment
2Pin 2 24 V DC valves
Pin 3 0 V DC valves
34 Pin 4 FE
Tab.�3/5: Pin assignment of the electric supply platetype�VMPA−FB−SP−V
Plug 7/8" (4−pin) Pin assignment
DCPin A n.c.
DCPin B 24 V DC valves
Pin C FE
AB Pin D 0 V DC valves
Tab.�3/6: Pin assignment of the electric supply platetype�VMPA−FB−SP−7/8−V−4POL
Plug 7/8" (5−pin) Pin assignment
2 1Pin 1 0 V DC valves (incoming)
2 1Pin 2 n.c.
3 Pin 3 FE (incoming)
54 Pin 4 n.c.54Pin 5 24 V DC valves
Tab.�3/7: Pin assignment of the electric supply platetype�VMPA−FB−SP−7/8−V−5POL
3. Installation
3−28 Festo P.BE−MPA−EN en 0802c
Earthing the MPA−S valve terminal
NoteEarth your MPA−S valve terminal.
· Connect the earth connection to the left−hand end plateor the multipin sub−base (see fig.) at low impedance(short cable with large cross−sectional area) with theearth potential.
· Please note the supplementary instructions on theMPA−S valve terminals with CPX terminal in the systemmanual of your CPX terminal.
You can thereby avoid faults due to electromagneticinfluences and ensure electromagnetic compatibility inaccordance with EMC guidelines.
3. Installation
3−29Festo P.BE−MPA−EN en 0802c
11
MPA−S valve terminal with multipin connectionMPA−S valve terminal with CPX terminal
MPA−S valve terminal with CPI module
1
MPA−S valve terminal with AS−Interface
1
1 Earth connection
Fig.�3/8: Earthing the MPA−S valve terminal
3. Installation
3−30 Festo P.BE−MPA−EN en 0802c
3.5 Address assignment of the valves
3.5.1 MPA−S valve terminal with CPX terminal
Maximum 16 MPA pneumatic modules are permitted on theMPA−S valve terminal with CPX terminal. The followingnumber of valve coils is therefore possible (if only valves ofthe same size are used):� MPA1: up to 128 valve solenoid coils
(max. 64 valve locations)� MPA2: up to 64 valve solenoid coils
(maximum 32 valve locations)
NoteNote with the addressing that an MPA2 pneumatic modulehas only 4 addresses compared to an MPA1 pneumaticmodule.
Assigning the addresses
� The assignment of the addresses is module−orientated.
� A pneumatic module occupies the following number ofaddresses:
� MPA1: 8 addresses
� MPA2: 4 addresses
� Counting begins on the valve terminal from left to right.
� Each valve location occupies 2 addresses, irrespective ofthe valve plate or blanking plate fitted. The following assignment applies:
� solenoid coil 14 occupies the less significant address
� solenoid coil 12 occupies the more significant address.
3. Installation
3−31Festo P.BE−MPA−EN en 0802c
0
1
2
3
4
1 0 3 2
6
75
12 3
45
6
7
1 2
6
7
1) non−occupied addresses
1)
1)
1) 1)
1 Valve plates with two solenoid coils
2 Valve plates with one solenoid coil
3 Cover plate
4 Pneumatic modules (MPA2)
5 Pneumatic modules (MPA1)
6 Addresses of valve coils 14
7 Addresses of valve coils 12
Fig.�3/9: Example: Address assignment of an MPA−S valve terminal with CPX terminaland 6 valve locations (top view)
Further instructions on addressing the pneumatic modules ofthe MPA−S valve terminal with CPX terminal can be found inthe electronics manual for the module (see system manualforyour CPX terminal, table �Manuals on the CPX terminal").
3. Installation
3−32 Festo P.BE−MPA−EN en 0802c
3.5.2 MPA−S valve terminal with CPI module or AS−Interface
Instructions on addressing the pneumatic modules can befound in the leaflet supplied with the product.
3.5.3 MPA−S valve terminal with multipin connection
� Assign the addresses in ascending order without gaps(see example).
� Addess assignment does not depend on whether blankingplates or valve plates are fitted.
� Depending on the electronic module, a valve locationoccupies the following number of addresses:
Number ofdd
Electronic moduleaddresses MPA1 MPA2
one address VMPA1−MPM−EMM−4 VMPA2−MPM−EMM−2
two addresses VMPA1−MPM−EMM−8 VMPA2−MPM−EMM−4
Tab.�3/8: Electronic modules for multipin connection
� If a valve location occupies 2 addresses, the followingapplies:
� pilot solenoid 14 occupies the lower−value address
� pilot solenoid 12 occupies the higher−value address.
3. Installation
3−33Festo P.BE−MPA−EN en 0802c
Example of address assignment
CautionNote that addresses may be shifted if the valve terminal isextended at a later stage.
In the following example an MPA−S valve terminal typeMPA−MPM−PI with the folllowing components is addressed:
Component MPA1 MPA2
Sub−bases 2 (8 valve positions) 2 (4 valve positions)
Electronicmodule
1 VMPA1−MPM−EMM−81 VMPA1−MPM−EMM−4
1 VMPA2−MPM−EMM−41 VMPA2−MPM−EMM−2
Tab.�3/9: Example: Electronic modules for multipinconnection
3. Installation
3−34 Festo P.BE−MPA−EN en 0802c
For controlling the valves, each valve coil is assigned to acertain pin of the multipin plug.
Pin Address Valvelocationnumber
Solenoidcoil
Electronic module
12
01
0 1412
VMPA1−MPM−EMM−8(for 4 MPA1 valveseach with two coils)
34
23
1 1412
each with two coils)
56
45
2 1412
78
67
3 1412
9 8 4 14 VMPA2−MPM−EMM−2(for 2 MPA2 valves
10 9 5 14(for 2 MPA2 valveseach with one coil)
11 10 6 14 VMPA1−MPM−EMM−4(for 4 MPA1 valves
12 11 7 14(for 4 MPA1 valveseach with one coil)
13 12 8 14
)
14 13 9 14
1516
1415
10 1412
VMPA2−MPM−EMM−4(for 2 MPA2 valveseach with two coils)
1718
1617
11 1412
each with two coils)
... ... ... ... ...
25 0 V 1)
1) Connect 0 V with positive−switching control signals, 24 V with negative−switching control signals; mixed operation is not permitted.
Tab.�3/10: Example: Address assignment of the MPA−Svalve terminal with multipin connection and12valve locations
3. Installation
3−35Festo P.BE−MPA−EN en 0802c
Example of address assignment (seen from above):
2
15 14 17
1 2 3 4
7
4
9 8
35
6
1 5
2
1
0
1 3
4
5
6
7 8 9
10 11 12 13
16
1
aJ
1 Addresses of valve coils 14 (manual override 14)
2 Addresses of valve coils 12 (manual override 12)
3 LED solenoid coil 12
4 LED solenoid coil 14
5 Unused valve location
6 Sub−base with electronic moduleVMPA2−MPM−EMM−4 occupies twoaddresses per valve location
7 Supply plate for additional pressuresupply
8 Sub−base with electronic moduleVMPA1−MPM−EMM−4 occupies oneaddress per valve location
9 Sub−base with electronic moduleVMPA2−MPM−EMM−2 occupies oneaddress per valve location
aJ Sub−base with electronic moduleVMPA1−MPM−EMM−8 occupies twoaddresses per valve location
Fig.�3/10: Example: Address assignment of the MPA−S valve terminal with multipinconnection and 12 valve locations, type MPA...−MPM−... (top view)
3. Installation
3−36 Festo P.BE−MPA−EN en 0802c
Commissioning
4−1Festo P.BE−MPA−EN en 0802c
Chapter 4
4. Commissioning
4−2 Festo P.BE−MPA−EN en 0802c
Contents
4. Commissioning 4−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1 General instructions 4−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.1 Before commissioning 4−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.2 Pressure increase in the complete supply 4−4 . . . . . . . . . . . . . . . . . . . .
4.2 Manual override 4−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3 Checking the valves and the valve−actuator combination 4−8 . . . . . . . . . . . . . . .
4.4 LED display of the valves 4−13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.5 LED display of the proportional pressure regulator 4−16 . . . . . . . . . . . . . . . . . . . .
4.6 Commissioning instructions for the proportional pressure regulator 4−17 . . . . . .
4.7 Troubleshooting 4−19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.7.1 Impairment of function 4−19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.7.2 Operating states of the pneumatic system 4−21 . . . . . . . . . . . . . . . . . . .
4. Commissioning
4−3Festo P.BE−MPA−EN en 0802c
Contents of this chapter This chapter describes the commissioning of the MPA−S valveterminal. The following belong here:
� Instructions on building up pressure in the completesupply
� Operating the manual overrides
� Checking the valves and the valve−actuator combination
� The assignment of LEDs and manual overrides to the valvesolenoid coils
� Function impairments
� Operating states of the pneumatic system
Further information The commissioning of the CPX terminal is described in therelevant manual for the CPX bus node (see system manual foryour CPX terminal, table �Manuals on the CPX terminal").
4. Commissioning
4−4 Festo P.BE−MPA−EN en 0802c
4.1 General instructions
4.1.1 Before commissioning
· Switch off the power supply before connecting ordisconnecting plugs (otherwise this could lead tofunctional damage).
· Commission only a valve terminal which has been fittedand wired completely.
· Make sure that there is a sufficient supply of fresh air(cooling) for the following operating conditions: � when the maximum number of valves are fitted� when the maximum operating voltage is applied� when the valve coils are constantly under stress.
· Please observe the following instructions on building uppressure in the complete supply.
4.1.2 Pressure increase in the complete supply
WarningIf the build−up in pressure of the auxiliary pilot air is tooslow or delayed, this may cause the actuators to performsudden unexpected movements under the followingconditions:
� when the compressed air is switched on with a safetystart−up valve (slow build up of pressure) and
� if there are electric signals (e.g. after EMERGENCY STOP).
This can cause damage to the machine or system and eveninjury to human beings.
· Operate the valve terminal with external pilot air(3���8�bar). Branch the pilot air in front of the safetystart−up valve (see diagram).
4. Commissioning
4−5Festo P.BE−MPA−EN en 0802c
The pilot air must reach a pressure of 3 � 8 bar as soon as itis switched on, Otherwise, there is no guarantee that thevalve will switch directly (see diagram). If the pressure is less than 3 bar, there may be a delay beforethe valve is switched, in spite of an electric signal being pres�ent. The slow increase in pressure of the complete supplydoes not then affect the actuator. The actuator would reactsuddenly (e.g. a cylinder would extend or retract suddenly,depending on the valve function).
1
4 2
5 3
14 12
1
2
1
12/14
12/14
3
82/84
2
1 Externally supplied pilot air (3 to 8 bar), branched infront of the safety start−up valve
2 Safety start−up valve (slow build up of pressure ofcomplete supply)
Fig.�4/1: Example of valve−cylinder combination with slowincrease in pressure of the complete supply
4. Commissioning
4−6 Festo P.BE−MPA−EN en 0802c
The table below shows the effects of slow start−up pressuriza�tion when there are electric signals.
External pilotair supply
Pressure in�crease in com�plete supply
Pressureincrease in thepilot air (12/14)
Time pointwhen a valveswitches
Movement ofthe actuator
branched after thesafety start−upvalve
slow slow after pressureincrease at (1)
fast
branched in frontof the safetystart−up valve
slow fast before pressureincrease at (1)
slow
Tab.�4/1: Effects of slow start−up pressurization
4.2 Manual override
You should use the manual override especially when commis�sioning the pneumatic system, in order to check the functionand operation of the valve or the valve−actuator combination.
By actuating the manual override, you can switch the valvewithout an electric signal. You only need to switch on thecompressed air supply.
The manual override has been designed to be used asfollows:
Control type Method of operation
pushing (non−detenting) After actuation the manual overrideis reset automatically by a spring.
turning, locking The manual override remainsactuated until it is reset by hand.
Tab.�4/2: Actuation methods of the manual override
4. Commissioning
4−7Festo P.BE−MPA−EN en 0802c
The locking/non−locking function of the manual override canbe modified to only non−locking actuation if a cap is fitted.
The assignment of the manual override actuations to thevalve solenoid coils is as follows:
1
2
12 12 12 12
14 14 14 14 14 14 14 14
12 14 14
1
2
2
34
1 Manual override for valve solenoid coils 12
2 Manual override for valve solenoid coils 14
3 Valve size MPA2
4 Valve size MPA1
Fig.�4/2: Position of the manual overrides (top view)
4. Commissioning
4−8 Festo P.BE−MPA−EN en 0802c
4.3 Checking the valves and the valve−actuator combination
NoteBefore commissioning the MPA−S valve terminal, note thespecifications concerning the medium, see section�Installation", section �Pilot control of the valve solenoidcoils (pilot air)".
The MPA−S valve terminal should be commissioned asfollows:
Commissioning variants Activity
Preliminary test of thepneumatic tubing
Test the valve−actuator combinationby means of the manual override
Complete commissioning ofthe complete system
Installing and connecting thecomplete systemProgram control via PLC/industrial PC
Tab.�4/3: Commissioning variants
Commissioning the pneumatic components by means of themanual override is described below.
The commissioning of the CPX terminal is described in therelevant manual for the CPX bus node (see system manual foryour CPX terminal, table �Manuals on the CPX terminal").
4. Commissioning
4−9Festo P.BE−MPA−EN en 0802c
WarningBefore actuating the manual override:
Uncontrolled actuation of the valve coils can cause theactuators to perform sudden unexpected movementswhich may cause injury to human beings and damage toproperty.
· Disconnect the power supply for the valve solenoid coilsat the relevant connections on the MPA−S valve terminal.
You will thereby avoid undesired actuation of the valvecoils.
Before switching on the power supply:
During commissioning, manual override functions whichare in the switched state can cause actuators to performsudden unexpected movements. These movements cancause injury to human beings and damage to property.
· Make sure that all manual override actuations are resetto their basic positions.
You will thereby avoid undefined switching states of thevalves.
Proceed as follows:
WarningBefore testing the valve−actuator combination:
� make sure that nobody is in the danger zone.
NoteA valve which has been switched by an electric signal,cannot be reset by the manual override. The electric signalis dominant in this case.
· Reset the electric signal before actuating the manualoverride.
4. Commissioning
4−10 Festo P.BE−MPA−EN en 0802c
1. Switch on the compressed air supply.
2. Check the functioning and operation of each individualvalve−actuator combination by actuating the manualoverride as shown in the following diagrams.
NoteIncorrect actuation of the non−locking manual override canlead to malfunctioning or damage to the manual override.
· Use a screwdriver (blade width max. 3 mm) for actuatingthe manual override.
· Actuate the manual override with only max. 25 N.
3. With the locking function of the manual override: After testing the valves, make sure that all manualoverride actuations are in their basic positions again.
CautionValves with manual overrides in switch position can moveactuators unintentionally during commissioning. This cancause injury to people and damage to property.
· Before commissioning, reset all manual overrides totheir basic positions again.
If the manual override is in the actuated state, it is notpossible to reset the valve to its basic position with anelectric signal. The manual override is dominant in thiscase.
4. Switch off the compressed air supply after testing thevalves.
4. Commissioning
4−11Festo P.BE−MPA−EN en 0802c
Before actuating the manual override (automatic reset)
Operation Valve response
· Use a screwdriver (max. bladewidth 3 mm) to press down theplunger of the manual overrideuntil the valve switches.
Note:In the case of manual overrideswithout a cap, do not turn thepressed−down plunger as otherwisethe manual override will lock.
The valve:� moves to the switching position
Keep the plunger of the manualoverride pressed down.
� remains in the switching position
· Release the plunger (the springresets the plunger of the manualoverride to the basic position).
� moves back to the basic position(not with double−solenoid valve,Ident. code J�)
Tab.�4/4: Non−locking actuation of the manual override
4. Commissioning
4−12 Festo P.BE−MPA−EN en 0802c
NoteThe locking actuation of the manual override is onlypossible if a manual override cap is not fitted.
Locking actuation of the manual override (manual reset)
Operation Valve response
· Use a screwdriver (max. bladewidth 3 mm) to press down theplunger of the manual overrideuntil the valve switches.
· Then turn the plunger in a clock�wise direction as far as possible.
The valve:� moves to the switching position
· Leave the plunger in position. � remains in the switching position
· Then turn the plunger in ananti−clockwise direction as far aspossible.
· Then release the plunger.
� moves back to the basic position(not with double−solenoid valve,Ident. code J�)
Tab.�4/5: Turning/locking actuation of the manual override
4. Commissioning
4−13Festo P.BE−MPA−EN en 0802c
4.4 LED display of the valves
There is a yellow LED and a manual override for each valvesolenoid coil. The diagram below shows the position of theLEDs and the manual overrides for the relevant valve solenoidcoil.
21
2
1
2 1
34
12 12 12 12
14 14 14 14 14 14 14 14
12 14 14
1 LED and manual override for valve solenoid coil 12
2 LED and manual override for valve solenoid coil 14
3 Valve size MPA2
4 Valve size MPA1
Fig.�4/3: The assignment of LEDs and manual overrides to the valve solenoid coils
4. Commissioning
4−14 Festo P.BE−MPA−EN en 0802c
MPA−S valve terminal with CPX terminal orCPI�module
The two−colour LEDs on th evalves have a double function.
� When yellow the LEDs indicate the switching status of thevalve solenoid coils.
� When red the LEDs indicate a fault in the electronicmodule.
LED Switching position of thevalve
Meaning
out Basic position Logical 0 (no signal)
yellow alight � Switch positionor
� Basic position
Logical 1 (signal present)
Logical 1 but:� compressed air supply not OK
or� pilot exhaust blocked
or� servicing required
lights up red � In the starting phase for approx. 2 seconds
� During operation
� test phase when power supply has been switched on voltage
� see Electronics manual for the MPA pneumatic module
Tab.�4/6: Meaning of the LED display (MPA−S valve terminal with CPX terminal orCPI�module)
Further instructions on commissioning and diagnosing theMPA pneumatic modules can be found in the electronics man�ual for the electronics manual for these modules (see systemmanual for your CPX terminal, table �Manuals on the CPXterminal").
4. Commissioning
4−15Festo P.BE−MPA−EN en 0802c
MPA−S valve terminal with multipin connection orAS−Interface
The LEDs on the valves show the switching statusof the valvesolenoid coils.
LED Switching positionof the valve
Meaning
out Basic position Logical 0 (no signal)
yellow alight � Switch positionor
� Basic position
Logical 1 (signal present)
Logical 1 but:� load voltage of the valves lies below the permitted
tolerance range (18 � 30 V DC)� compressed air supply not OK
or� pilot exhaust blocked
or� servicing required
Tab.�4/7: Meaning of the LED display (MPA−S valve terminal with multipin connection orAS−Interface)
4. Commissioning
4−16 Festo P.BE−MPA−EN en 0802c
4.5 LED display of the proportional pressure regulator
The two LEDs on the proportional pressure regulator showthe operating status of the valve.
Status of the LED display Cause
Power LED(green)
Fault LED(red)
lights up out � Normal operating status
lights up lights up � Non−permitted nominal value� Non−permitted parameter� There is a hardware fault� Internal temperature too high
lights up flashes � There is a hardware fault� Overvoltage (> 30 V) or undervoltage of the load voltage supply� Internal temperature too high
out out � Undervoltage in the load and logic voltage supply
Tab.�4/8: Meaning of the LED display on the proportional pressure regulator
4. Commissioning
4−17Festo P.BE−MPA−EN en 0802c
4.6 Commissioning instructions for the proportional pressure regulator
Note� Place the proportional pressure regulator as near aspossible to the consuming device. This will lead to bettercontrol accuracy and shorter response times.
� Make sure there is sufficient space for the connectingelements. In this way you will prevent the connectingcable from being bent.
� Long signal cables reduce the immunity to interference.Make sure that the signal cables are not longer than10�m.
� Make sure that the proportional pressure regulator isnot subjected to high−frequency irradiation (e.g. by radiosets, mobile telephones or other devices which causeinterference). In this way you will avoid increased toler�ances in the output pressure (compare specifications onEMC in appendix A).
� The proportional pressure regulator interprets nominalvalues which are smaller than 1 % full scale as zero pointswitching off, i.e. the valve is force−ventilated and there�fore assumes a defined position.
� Pressurise the proportional pressure regulator with aninput pressure at least 1 bar higher than the maximumrequired output pressure. A proportional output pres�sure P2 sets itself as the nominal value. Tab.�4/9 showsthe output pressure which is assigned to the end ranges(1 % FS or 100 % FS) of the nominal value.
� When switching off the proportional pressure regulator,make sure that first the supply pressure, then the supplyvoltage is switched off.
4. Commissioning
4−18 Festo P.BE−MPA−EN en 0802c
VPPM−6TA−... Output pressure withsignal 1 % FS 1) 2)
Output pressure withsignal 100 % FS 1) 2)
2 bar type 0.02 bar 2 bar
6 bar type 0.06 bar 6 bar
10 bar type 0.1 bar 10 bar
1) FS = Full scale (1 % FS = 0.1 V / 100 % FS = 10 V)2) 0 V = 0 bar
Tab.�4/9: Output signal of the proportional pressure regulator
Further important Information on commissioning theproportional pressure regulator, e.g. the parametrizing, canbe found in the relevant electronics manual for the module(see�the system manual for your CPX terminal, table�Manuals on the CPX terminal").
4. Commissioning
4−19Festo P.BE−MPA−EN en 0802c
4.7 Troubleshooting
4.7.1 Impairment of function
After switching on the compressed air supply or whensubsequently testing the individual valves, you can learn thefollowing about the operating status of the pneumaticsystem:
Operating status of thepneumatic system
Fault treatment when the compressed air supplyhas been switched off
Air escapes from ...� common line or work line
connections· Check the tubing fitting
The valve or the pneumatic system ...� does not react as expected
� does not react
· Check the tubing· Check the electric cables
· Bring the locking manual override into the basic position�· After switching on again check the operating pressure
(if necessary for each pressure zone) Set operatingpressure in accordance with instructions in chapter 3.
· Servicing required
With valve terminals which must be operated withclosed−loop regulated external pilot air:· After switching on again, check the pilot pressure
(if necessary, set as a factor of the operating pressure,see�chapter 3)
Tab.�4/10: Function impairment of the pneumatic system
4. Commissioning
4−20 Festo P.BE−MPA−EN en 0802c
Operating status of theproportional pressureregulator
Possible cause Remedy
Proportional pressureregulator does not react
Supply voltage not applied,POWER LED does not light up
Check the 24 V DC supplyvoltage
No supply pressure Switch on supply pressure
Nominal value reached Modify nominal value
Proportional pressure regulatordefective
Send the device to Festo forrepairs
Flow too low Restriction of the flow crosssection due to connection design(swivel fitting connectors)
Use different type of connection
Pressure increase too slow Large cylinder volume and longtubing
Select different parameterrecord
Pressure constant despitemodified setpoint valuespecification
Supply pressure p1 too low Increase supply pressure
Tab.�4/11: Functional impairment of the proportional pressure regulator
4. Commissioning
4−21Festo P.BE−MPA−EN en 0802c
4.7.2 Operating states of the pneumatic system
The following conditions should be fulfilled, in order that thedesired pneumatic operating states listed below can beachieved:
Desired pneum.operating status
Requirement Comment
Free of leakage � Tubing connected with care� Regulated pilot air supply
Fast reaction Sufficient pressure supply by meansof pressure supply modules
Exhaust the MPA−S valve terminal viaall the exhaust plates or via the largesurface−mounted silencer
Faultless Non−return valves in commonexhaust line
This applies when several systemswith centrally ducted exhaust areused
Two or morepressure zones
� Limiting the pressure zones bymeans of isolating seals withblocked channels
� Appropriate number of pneumaticsupply plates for the variouspressure zones.
Subsequent conversion possible(see�chapter 5)
Vacuum or low−pressure operation
Externally supplied regulated pilotair (3 � 8 bar)
Vacuum/low−pressure operation notwith 3/2−way valves
EMERGENCY STOP ofpressure zones
Guaranteeing the controller functionfor the pilot air despite the completesupply being switched off
The controller regulates the pilot airsupply to all the valve plates on anMPA−S valve terminal
Slow start−up afterEMERGENCY STOP
If there are control signals, the pilotair must have a pressure of 3 � 8 barimmediately after being switched on
Tab.�4/12: Pneumatic operating states
4. Commissioning
4−22 Festo P.BE−MPA−EN en 0802c
Maintenance and conversion
5−1Festo P.BE−MPA−EN en 0802c
Chapter 5
5. Maintenance and conversion
5−2 Festo P.BE−MPA−EN en 0802c
Contents
5. Maintenance and conversion 5−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1 General precautionary measures 5−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2 Dismantling the MPA−S valve terminal 5−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3 Maintenance of the MPA−S valve terminal 5−6 . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.1 Cleaning the large surface−mounted silencer 5−6 . . . . . . . . . . . . . . . . .
5.3.2 Replace the large surface−mounted silencer or exhaust plate 5−7 . . . .
5.3.3 Replacing valves or cover plates 5−8 . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.4 Replace the proportional pressure regulator 5−11 . . . . . . . . . . . . . . . . .
5.3.5 Replacing electronic modules 5−12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.6 Replacing the sub−base, supply plate or MPA−S end plate 5−19 . . . . . . .
5.3.7 Replacing the manifold boards 5−22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4 Converting the MPA−S valve terminal 5−26 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.1 Conversion to internal or external pilot air 5−26 . . . . . . . . . . . . . . . . . . . .
5.4.2 Converting the MPA−S valve terminal to different pressure zones 5−31 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.3 Adding valve locations 5−35 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.4 Adding an electric supply plate 5−38 . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.5 Adding a pressure sensor plate 5−39 . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4.6 Adding a proportional pressure regulator 5−40 . . . . . . . . . . . . . . . . . . . .
5. Maintenance and conversion
5−3Festo P.BE−MPA−EN en 0802c
Contents of this chapter This chapter explains how to fit and remove the followingcomponents for maintenance work and conversion:
� Valve or cover plate
� Electronic module
� Exhaust plate or large surface−mounted silencer
� Sub−base, supply plate and end plate
The following activities are also described:
� Adding pressure zones
� Converting the valve terminal to internal or externalpilot�air
Further information MPA−S valve terminal with CPX terminal: Information on fitting /removing components and on theelectrical connections can be found in the CPX systemmanual.
MPA−S valve terminal with multipin connection: Instructions on connecting the electric components can befound in the leaflet supplied with the product.
5. Maintenance and conversion
5−4 Festo P.BE−MPA−EN en 0802c
5.1 General precautionary measures
WarningSudden unexpected movements of the connected actua�tors and uncontrolled movements of loose tubing cancause injury to human beings and/or damage to property.
Before carrying out installation and maintenance work,switch off the following:
· the compressed air supply
· the operating and load voltage supplies.
NoteHandle all modules and components of the MPA−S valveterminal with great care. Note especially the followingwhen fitting components:
· Screws must be fitted accurately (otherwise threads willbe damaged).
· Screws must be fastened at first only by hand. Screwsmust be placed so that the self−cutting threads can beused.
· The specified torques must be observed.
· Screw connections must be fitted free of offset andmechanical tension.
· Check the seals for damage (IP65).
· The contact surfaces must be dry and clean (sealing effect, avoid leakage and contact faults).
5. Maintenance and conversion
5−5Festo P.BE−MPA−EN en 0802c
5.2 Dismantling the MPA−S valve terminal
Providing the MPA−S valve terminal is easily accessible, itneed not be dismantled when the following components arereplaced or removed:
� valves or cover plates
� electronic module
� exhaust plates or large surface−mounted silencer.
Loosen the electrical connections
Connecting variants Procedure
CPX terminal · Instructions on loosening the electrical connections can be found inthe CPX system manual.
Multipin connection · Loosen the fastening screws and remove the Sub−D multipin plug.
Tab.�5/1: Loosen the electrical connections
Loosen the pneumatic connections
Loosening the penumatic connections is described inchapter�3.
Dismantling the MPA−S valve terminal
The procedure for dismantling the MPA−S valve terminal isdescribed in chapter 2.
5. Maintenance and conversion
5−6 Festo P.BE−MPA−EN en 0802c
5.3 Maintenance of the MPA−S valve terminal
5.3.1 Cleaning the large surface−mounted silencer
CautionDirt in the large surface−mounted silencer can cause anincrease in pressure in exhaust channels 3 and 5.
· Clean the silencer insert if it is yellow/black or a darkcolour, or replace it by a new insert.
· Do not use TRI for cleaning, but benzine or paraffin.
· Observe the safety regulations for handling easilyinflammable cleaning agents.
In this way you can ensure that the large surface−mountedsilencer functions correctly and that the valves operatecorrectly.
Proceed as follows:
1. Loosen the 6 fastening screws of the surface mountedsilencer and remove it from the basis components.
2. Clean the surface mounted silencer with benzine orparaffin.
3. Check the seal between the basis component and thesurface mounted silencer for damage. Replace the seal ifit is damaged.
4. Fasten the silencer only with the original screws. Tighten the screws in diagonally opposite sequence0.90����1.10 Nm.
5. Maintenance and conversion
5−7Festo P.BE−MPA−EN en 0802c
5.3.2 Replace the large surface−mounted silencer or exhaust plate
Proceed as follows:
1. Loosen the 6 fastening screws of the large surface−mounted silencer or exhaust plate and remove it from thebasis component.
2. Check the seal between the basis component and thesurface−mounted silencer or exhaust plate for damage.Replace the seal if it is damaged.
3. Make sure that the seal is seated correctly. The seating isdetermined by guides in the large surface−mountedsilencer or exhaust plate.
4. Fasten the large surface−mounted silencer or exhaustplate only with the original screws. Tighten the screws indiagonally opposite sequence wuth 0.59 � 0.71 Nm(exhaust plate) or 0.90 � 1.10 Nm (large surface−mountedsilencer).
5. Maintenance and conversion
5−8 Festo P.BE−MPA−EN en 0802c
5.3.3 Replacing valves or cover plates
NoteThe sub−bases of the MPA−S valve terminal with multipinconnection support the control of one or two solenoid coilsper valve location depending on the MPA electronicmodule fitted (see Tab.�5/4).
Dismantling Proceed as follows:
· Use a screwdriver with a narrow blade to loosen thefastening screws and remove the components from thesub−bases (see diagram).
Fig.�5/1: Removing valves or blanking plates
5. Maintenance and conversion
5−9Festo P.BE−MPA−EN en 0802c
Fitting Proceed as follows:
1. Make sure the seal is not damaged.
2. Replace seals if they are damaged.
3. Make sure that the cord seal is seated correctly betweenthe sub−base and the components. The cord seal must liein the recess for the components.
1 Fastening screwsof the valve or thecover plate
2 Valve or coverplate
3 Cord seal
4 Electronic module
5 Sub−base
1
2
3
4
5
Fig.�5/2: Fitting valves or blanking plates (MPA1)
5. Maintenance and conversion
5−10 Festo P.BE−MPA−EN en 0802c
2
1
2
3
4
5
1 Fastening screws of the component
2 Valve or cover plate
3 Cord seal
4 Sub−base
5 Electronic module
Fig.�5/3: Fitting valve plates or blanking plates (MPA2)
4. Place the component on the sub−base.
5. Screw the component at first only slightly and thentighten with the following torque:
� MPA1: 0.20 � 0.30 Nm
� MPA2: 0.59 � 0.71 Nm
5. Maintenance and conversion
5−11Festo P.BE−MPA−EN en 0802c
5.3.4 Replace the proportional pressure regulator
How to fit the proportional pressure regulator is described inthe mounting instructions VMPA−6TA−...
1 Proportionalpressure regulator
2 Fastening screwsof theproportionalpressure regulator(tightening torque1.80���2.20 Nm)
3 Sub−base
4 Fastening screwsof the electronicmodule(tightening torque0.32 � 0.48 Nm)
5 Electronic module
12
3
4
5
Fig.�5/4: Fitting the proportional pressure regulator and the electronic module
5. Maintenance and conversion
5−12 Festo P.BE−MPA−EN en 0802c
5.3.5 Replacing electronic modules
How to fit the proportional pressure regulator is described inthe mounting instructions VMPA−6TA−...
The MPA−S valve terminal is fitted with one electronic moduleper sub−base. It provides the following number of contactsbetween the electrical linking and the solenoid coils, depend�ing on the size of the sub−bases.
� for size MPA1 contacts for 4 valve locations
� for size MPA2 contacts for 2 valve locations.
The LEDs (function see chapter 4) and further electroniccomponents are integral parts of the electronic module.
CautionThe electronic modules may be damaged if they are nothandled correctly.
· Switch off the power supply before removing theelectronic modules.
· Do not touch any contact surfaces.
· Observe the handling specifications for electrostaticallysensitive components.
· Discharge yourself before installing or removingsub−assemblies to protect the sub−assemblies fromstatic discharges.
CautionReplace an electronic module only by an electronic moduleof the same type.
5. Maintenance and conversion
5−13Festo P.BE−MPA−EN en 0802c
Before fitting the electronic module
There are different designs of electronic modules dependingon the connection variant.
Electronic modules for the MPA−S valve terminal withCPX�terminal
CautionDamage to components and functional damage
It is not permitted to supply voltage to MPA pneumaticmodules with electronic modules without electrical isola�tion via a manifold sub−base type CPX−GE−EV−V... (valvesupply) or CPX−GE−EV−S−7/8−5POL (5−pin system supply).
· If your MPA pneumatics are fitted with electronicmodules of type VMPA1−FB−EMS−... orVMPA2−FB−EMS−..., you must supply the MPA pneumatcsexclusuvely via a 4−pin system supply module typeCPX−GE−EV−S or CPX−GE−EV−S−7/8−4POL.
Note the overview in Tab.�5/2.
Note that MPA electronic modules may only be supplied withpower via the following supply modules:
MPA electronic module Permitted supply modules
... without electrical isolation� VMPA1−FB−EMS−...� VMPA2−FB−EMS−...
� System supply (M18, 4−pin): type CPX−GE−EV−S� System supply (7/8", 4−pin): type CPX−GE−EV−S−7/8−4POL
... with electrical isolation� VMPA1−FB−EMG−...� VMPA2−FB−EMG−...
� Valve supplies (M18 or 7/8"): type CPX−GE−EV−V...� Electric supply plate MPA�: type VMPA−FB−SP−...−V−...� System supplies (M18 or 7/8"): 1) type CPX−GE−EV−S...
1) If a 4−pin system supply is used, there will be no electrical isolation.
Tab.�5/2: Permitted supply modules for MPA electronic modules
5. Maintenance and conversion
5−14 Festo P.BE−MPA−EN en 0802c
In the case of MPA electronic modules with electrical isolationtype VMPA1−FB−EMG−... or VMPA2−FB−EMG−..., VEL/SEN andVVAL are completely electrically isolated. In conjunction withthe following voltage supply modules, it is therefore possibleto switch off the valve supply voltage at all poles:
� manifold sub−base with valve supply (M18 or 7/8"): type�CPX−GE−EV−V...
� system supply (7/8", 5−pin): type�CPX−GE−EV−S−7/8−5POL
� electric supply plate MPA: type�VMPA−FB−SP−...−V−...
NoteThe electrical function of an MPA pneumatic module isdetermined by the electronic module used, e.g.:
� electromagnetic compatibility (EMC)
� switching off the valve power supply at all poles.
You must observe the instructions in the manual for theCPX I/O modules if you wish to fit an electronic module ofa different type.
Recommendation:Replace only with electronic modules of the same type.
The electronic modules type VMPA�...−FB−... support thecontrol of two valve solenoid coils per valve location.
5. Maintenance and conversion
5−15Festo P.BE−MPA−EN en 0802c
The following electronic modules are available:
Type Description of the electronic module
VMPA1−FB−EMG−8 � 4 valve locations / 8 outputs� with electrical isolation
VMPA1−FB−EMG−D2−8 � 4 valve locations / 8 outputs� with electrical isolation� with diagnostic functions D2
VMPA1−FB−... VMPA1−FB−EMS−8 � 4 valve locations / 8 outputs� without electrical isolation
VMPA1−FB−EMS−D2−8 � 4 valve locations / 8 outputs� without electrical isolation� with diagnostic functions D2
VMPA2−FB−EMG−4 � 2 valve locations / 4 outputs� with electrical isolation
VMPA2−FB−EMG−D2−4 � 2 valve locations / 4 outputs� with electrical isolation� with diagnostic functions D2
VMPA2−FB−... VMPA2−FB−EMS−4 � 2 valve locations / 4 outputs� without electrical isolation
VMPA2−FB−EMS−D2−4 � 2 valve locations / 4 outputs� without electrical isolation� with diagnostic functions D2
Outputs correspond to valve solenoid coils
Tab.�5/3: Electronic modules for MPA−S valve terminal with CPX terminal
Further Information on the MPA electronic modules can befound in the leaflet supplied with the product and in the rel�evant electronics manual for the module (see System Manualfor your CPX terminal, table �Manuals on the CPX terminal").
5. Maintenance and conversion
5−16 Festo P.BE−MPA−EN en 0802c
MPA−S valve terminal with multipin connection orAS−Interface
The following types are available:
Type Description of the electronic module
VMPA1−MPM−EMM−8 4 valve locations / 8 outputs 1)
VMPA1−...
VMPA1−MPM−EMM−4 4 valve locations / 4 outputs 2)
VMPA2−MPM−EMM−4 2 valve locations / 4 outputs 1)
VMPA2−...
VMPA2−MPM−EMM−2 2 valve locations / 2 outputs 2)
Outputs correspond to valve solenoid coils1) Control of two valve coils is supported per valve location.2) Control of one valve coil is supported per valve location.
Tab.�5/4: Electronic modules for the MPA−S valve terminal with multipin connection(type MPA...−MPM−...)
Removing/fitting the electronic module
Dismantling Proceed as follows:
Before removing the electronic module, you must first removeall valve plates or blanking plates on the relevant electronicmodule (see section �Removing valve plates or blankingplates").
1. Loosen the screws with which the electronic module isfastened to the sub−base.
2. Pull the electronic module upwards out of the body of thesub−base.
5. Maintenance and conversion
5−17Festo P.BE−MPA−EN en 0802c
1 Fastening screws ofthe valve plate orblanking plate
2 Valve or cover plates
3 Cord seal
4 Electronic module
5 Sub−base
6 Inscription labelholder
7 Seal of the electronicmodule
8 Fastening screws ofthe electronic module
9 2 conical ring sealsper valve plate orblanking plate
1
2
3
4
5
6
9
8
7
Fig.�5/5: Dismantling and fitting the electronic module (example MPA1)
5. Maintenance and conversion
5−18 Festo P.BE−MPA−EN en 0802c
Fitting Proceed as follows:
CautionReplace an electronic module only by an electronic moduleof the same type.
� You can then avoid problems in controlling the valvesolenoid coils and damage to the electrical contacts.
NoteBefore fitting, check the condition and position of thefollowing seals:
� seal of the electronic module
� the ring seal of the electrical contacts
� the cord seal of the valve plates or blanking plates.
1. Place the electronic module in the sub−base and fasten it(tightening torque of the screws 0.32 � 0.48 Nm).
2. Then fit the valve plates or blanking plates (see section�Fitting valve plates or blanking plates").
5. Maintenance and conversion
5−19Festo P.BE−MPA−EN en 0802c
5.3.6 Replacing the sub−base, supply plate or MPA−S end plate
Dismantling Proceed as follows:
1. Loosen the electric and pneumatic connections andremove the MPA−S valve terminal from its fasteningsurface (see section 5.2).
2. Place the MPA−S valve terminal on a flat working surface.
3. Loosen the screws of the component (sub−base, supplyplate or end plate) which you wish to remove in thesequence 3, 2, 1, (see diagram).
4. Then remove the screws. The sub−bases are now heldtogether only by the electrical linking or by the bus.
ÖÖÖÖ
ÖÖÖÖÖÖ
1
2
3
Fig.�5/6: Position of the screw connectors of sub−bases andthe right−hand end plate
5. Pull the relevant component away from the neighbouringcomponent.
5. Maintenance and conversion
5−20 Festo P.BE−MPA−EN en 0802c
Fitting Proceed as follows:
1. Make sure the seals are not damaged. Replace the seals ifthey are damaged.
2. Place the sheet metal seal onto the guide pins of thesub−base or supply plate.
1 Guide pins
2 Seal (optionalisolating seal forseparatingpressure zones)
2
1
1
Fig.�5/7: Fitting the sub−bases
5. Maintenance and conversion
5−21Festo P.BE−MPA−EN en 0802c
3. Screw the sub−bases together. Tighten the screws in thesequence 1, 2, 3 as shown in the diagram by hand.Then tighten the screws with a torque of 1.62 � 1.98 Nm.
1
2
2
1
3
Fig.�5/8: Screw connectors of the sub−bases
4. Fit the MPA−S valve terminal onto the fastening surface(see chapter 2 �Fitting onto a wall" or �Fitting onto a hatrail").
5. Then fit the pneumatic and electrical connections(see�chapter 3 �Installation, connecting the MPA−S valveterminal").
5. Maintenance and conversion
5−22 Festo P.BE−MPA−EN en 0802c
5.3.7 Replacing the manifold boards
MPA−S valve terminal with multipin connection orAS−Interface
With the multipin connection the electrical manifold sub−baseis constructed on a modular basis. Each sub−base has its ownboard. The following manifold boards are available for theMPA−S valve terminal with multipin connection:
Manifold boards for ... Version
one sub−base one sub−base and a supplyplate
Type: VMPA1−MPM−EV−AB−8 Type: VMPA1−MPM−EV−ABV−8 Only for size MPA1:Board for controlling a total of8�valve coils per sub−base.
Type: VMPA1−MPM−EV−AB−4 Type: VMPA1−MPM−EV−ABV−4 For sizes MPA1 and MPA2:Board for controlling a total of4�valve coils per sub−base.
Type: VMPA2−MPM−EV−AB−2 Type: VMPA2−MPM−EV−ABV−2 Only for size MPA2:Board for controlling a total of2�valve coils per sub−base.
Tab.�5/5: Manifold boards type VMPA−MPM−...
5. Maintenance and conversion
5−23Festo P.BE−MPA−EN en 0802c
Dismantling Proceed as follows:
1. Loosen all valve plates and blanking plates on the sub−base from which you wish to remove the manifold board(see section 5.3.3).
2. Remove the electronic module from the sub−base(see�section 5.3.5).
3. Loosen the sub−base from the neighbouring components(see section 5.3.6).
4. If you wish to remove the last manifold board in front ofthe right−hand MPA end plate, you must remove the endpiece type MPA from this manifold board.
1 End piecetype�MPA
1
Fig.�5/9: Removing the end piece from the last manifold board
5. Loosen the relevant manifold board from above byunlocking the locking clips (e.�g with a small screwdriver).Then pull the manifold board to the right out of thesub−base.
5. Maintenance and conversion
5−24 Festo P.BE−MPA−EN en 0802c
1 Locking clip
1
Fig.�5/10: Unlocking the manifold board
Fitting Proceed as follows:
1. Push the manifold board to be fitted into the sub−basefrom the right until it clips into position.
Fig.�5/11: Fitting the manifold board
2. If the fitted manifold board is the last one in front of thefright−hand MPA end plate, you must insert the end piecetype MPA into this manifold board.
5. Maintenance and conversion
5−25Festo P.BE−MPA−EN en 0802c
1 End piecetype�MPA
1
Fig.�5/12: Fitting the end piece into the last manifold board
3. Fit the sub−base to the neighbouring components(see�section 5.3.6).
4. Fit the electronic module into the sub−base (see section 5.3.5).
5. Fit all the valves and blanking plates again onto thesub−base (see section 5.3.3).
5. Maintenance and conversion
5−26 Festo P.BE−MPA−EN en 0802c
5.4 Converting the MPA−S valve terminal
The MPA−S valve terminal can be extended/converted at alater stage. Information on permitted possibilities of combin�ing MPA−S components can be found in the Festo Catalogue(see www.festo.com\catalogue).
The following conversion work can be undertaken on theMPA−S valve terminal:
� Conversion of the MPA−S valve terminal to internal orexternal pilot air
� Conversion of the MPA−S valve terminal to different pressurezones
� Adding valve locations (sub−bases)
5.4.1 Conversion to internal or external pilot air
Pilot control of the valve coils can be undertaken with internalor external pilot air depending on the pneumatic interface orthe multipin sub−base.
NoteMixed operation of the MPA−S valve terminal with internaland external pilot air is not intended. Irrespective of theavailable pressure zones, all valve coils of the MPA−S valveterminal are supplied with the same pilot air.
5. Maintenance and conversion
5−27Festo P.BE−MPA−EN en 0802c
You can ascertain the pilot control variant for which yourMPA−S is equipped by the following features listed inchapter�3, Tab.�3/1.
The following pneumatic interfaces or multipin sub−bases areavailable for pilot control of the MPA−S valve terminal:
Variant Pneumaticinterface
Multipinsub−bases
Recognition features
� Operation withinternal pilot air
� Ducted exhaust air
VMPA�...−FB−EPL−G MPA1−MP−EPL−G /VMPA1−MPM−EPL−G
� Sealed connection 12/14� Exhaust plate
� Operation withinternal pilot air
� Exhausting via largesurface−mountedsilencer
VMPA�...−FB−EPL−GU MPA1−MP−EPL−GU /VMPA1−MPM−EPL−GU
� Sealed connection 12/14� Large surface−mounted
silencer
� Operation withexternal pilot air
� Ducted exhaust air
VMPA�...−FB−EPL−E MPA1−MP−EPL−E /VMPA1−MPM−EPL−E
� Open connection 12/14� Exhaust plate
� Operation withexternal pilot air
� Exhausting via largesurface−mountedsilencer
VMPA�...−FB−EPL−EU MPA1−MP−EPL−EU /VMPA1−MPM−EPL−EU
� Open connection 12/14� Large surface−mounted
silencer
Tab.�5/6: Variants of the pneumatic interface and multipin sub−bases
MPA−S valve terminal with CPX terminal
Removing the CPX pneumatic interface:� from the sub−base of the MPA−S valve terminal is
described in appendix B. � from the CPX terminal is described in the system manual
for the CPX terminal.
5. Maintenance and conversion
5−28 Festo P.BE−MPA−EN en 0802c
MPA−S valve terminal with multipin connection
Dismantling Proceed as follows:
1. Loosen the electrical and pneumatic connections andremove the MPA−S valve terminal from its fasteningsurface (see this chapter �Dismantling the MPA−S valveterminal").
2. Place the MPA−S valve terminal on a flat working surface.
3. Loosen the fastening screws between the multipinsub−base and the pneumatic sub−bases in the sequence3, 2, 1 (see following diagram).
4. Then loosen and remove the fastening screws.
1
2 3
Fig.�5/13: Position of the screw connectors on the sub−base
5. Pull the multipin sub−base away from the pneumaticsub−bases.
5. Maintenance and conversion
5−29Festo P.BE−MPA−EN en 0802c
Fitting Proceed as follows:
1. Make sure the seals are not damaged. Replace the seals ifthey are damaged.
2. Place the seal onto the guide pins of the multipinsub−base.
1 Multipinsub−base
2 Guide pins
3 Seal
4 Pneumaticsub−base
21
2 3 4
Fig.�5/14: Fitting the multipin sub−base
3. Pull the multipin sub−base away from the pneumaticsub−bases. Make sure that the seal and the componentsare correctly positioned.
5. Maintenance and conversion
5−30 Festo P.BE−MPA−EN en 0802c
4. Screw the multipin sub−base to the pneumatic sub−bases.Tighten the screws in the sequence 1, 2, 3 as shown inthe diagram at first slightly and then with 1.3 Nm.
2
1
3
Fig.�5/15: Screw connectors of the sub−bases
5. Fit the MPA−S valve terminal onto the fastening surface(see chapter 2 �Fitting onto a wall" or �Fitting onto ahat�rail").
6. Then fit the pneumatic and electrical connections(see�chapter 3 �Installation, connecting the MPA−S valveterminal").
5. Maintenance and conversion
5−31Festo P.BE−MPA−EN en 0802c
5.4.2 Converting the MPA−S valve terminal to different pressure zones
The MPA−S valve terminal can be fitted with the followingnumber of pressure zones depending on the connectionvariant:
Electrical connection variant MPA−S valve terminal with ...
CPX terminal multipin connection
Pressure zones 1 � 8 1) or 1 � 16 2) 1 � 12
1) Electric supply of the valves via the CPX terminal2) Electric supply of the valves via the electric supply plate
Tab.�5/7: Number of pressure zones
The pressure zones are formed either by special sub−bases orby special isolating seals (see chapter 1, section �Pressurezone separation").
The formation of pressure zones with the aid of isolating sealsis described below.
NoteNote the following if the MPA−S valve terminal is extendedor converted at a later stage:
The isolating seals for forming pressure zones are dividedinto two groups (see chapter 1, Tab.�1/8):
� Isolating seals for MPA−S valve terminals fitted with largesurface−mounted silencers.
� Isolating seals for MPA−S valve terminals fitted withexhaust plates.
5. Maintenance and conversion
5−32 Festo P.BE−MPA−EN en 0802c
For converting the valve terminal, you will require the follow�ing components for each pressure zone:
� Isolating seal with pressure zone separationVMPA�...−DP−...
� If not already provided, one of the following supply unitswith exhaust plate or large surface−mounted silencer:
MPA−S valve terminal with ...
CPX terminal multipin sub−base
VMPA�...−FB−SP or VMPA�...−FB−SPU
VMPA−FB−SP orVMPA−FB−SPN
Tab.�5/8: Pneumatic supply plates
� When adding a pneumatic supply plate:
� MPA−S valve terminal with multipin connection: an appropriately lengthened manifold board (see section �Overview of the manifold boards").
� MPA−S valve terminal with CPX terminal: for the pneumatic supply unit the appropriatemanifold board type: MPA1−FB−EV−V.
Dismantling Proceed as follows:
1. Loosen the electrical and pneumatic connections andremove the MPA−S valve terminal from its fasteningsurface (see this chapter section �Dismantling the MPA−Svalve terminal").
2. Place the MPA−S valve terminal on a flat working surface.
3. Loosen the sub−base at the point where you wish to insertthe iisolating seal for the pressure zone separation (see section �Dismantling the sub−bases").
5. Maintenance and conversion
5−33Festo P.BE−MPA−EN en 0802c
Fitting Proceed as follows:
1. Insert the isolating seal for the pressure zone separation.
2. If not already provided, fit the following for pressurezones 2 � 8: an appropriate pneumatic supply unit foreach pressure zone (see section 5.3.6).
3. MPA−S valve terminal with multipin connection: In order to bridge the pneumatic supply plate, replace theshort manifold board in the sub−base which follows thepneumatic supply plate by a longer version (see section5.3.7 Replacing manifold boards).
4. Fit the sub−base (see section 5.3.6).
5. Fit the MPA−S valve terminal onto the fastening surface(see chapter 2 �Fitting onto a wall" or �Fitting onto ahat�rail").
6. Then fit the pneumatic and electrical connections (see chapter 3 �Installation, connecting the MPA−S valveterminal").
5. Maintenance and conversion
5−34 Festo P.BE−MPA−EN en 0802c
The following diagram shows the structure of pressure zonesusing as an example an MPA−S valve terminal with CPXterminal.
1 2 3
4567 5
1 Valve plates of the 1st. pressure zone
2 Valve plates of the 2nd. pressure zone
3 Valve plates of the 3rd. pressure zone
4 Supply plate with connection 1 for supplying compressed air to the 3rd.pressure zone
5 Marking the isolating seal with pressure zone separation
6 Supply plate with connection 1 for supplying compressed air to the 2nd.pressure zone
7 Pneumatic interface with connection 1 for supplying compressed air to the 1st.pressure zone
Fig.�5/16: Example of MPA−S valve terminal with CPX terminal and 3 pressure zones
5. Maintenance and conversion
5−35Festo P.BE−MPA−EN en 0802c
5.4.3 Adding valve locations
You can easily adapt the MPA−S valve terminal to the require�ments of your machine or system by adding valve locations.The smallest extension unit is a sub−base with 4 valve loca�tions (MPA1) or 2 valve locations (MPA2).
MPA−S valve terminal with multipin connection
The valve terminals can be configured with as many sub−bases as there are addresses available (see table). With thesevalve terminals, the maximum number of solenoid coils whichcan be actuated by the multipin connection is limited to24�addresses.
If control is carried out with size MPA 1 or MPA 2 and valveswith the same number of solenoid coils, this will result in thefollowing maximum number of sub−bases:
MPA−S valve terminal Valve locations persub−base (n1)
Valve coils per valve location (n2)
max. 1)
MPA1 4 1 6
2 3
MPA2 2 1 12
2 6
1) Maximum number of sub−bases when fitted exclusively with one size and with valves with the same number of solenoid coils
Tab.�5/9: Maximum number of sub−bases
With 24 controllable solenoid coils the maximum number ofsub−bases (Xmax) can be calculated as follows:
Xmax � 24�n1� n2�
5. Maintenance and conversion
5−36 Festo P.BE−MPA−EN en 0802c
MPA−S valve terminal with CPX terminal
NoteMaximum 16 MPA sub−bases are permitted on the MPA−Svalve terminal with CPX terminal and electric supply plate.Without the electric supply plate 8 MPA sub−bases arepermitted.
Necessary components
For extension you will require:
Components MPA−S valve terminal with ...
CPX terminal multipin connection
One sub−base per:� MPA1: 4 valve positions� MPA2: 2 valve positions
VMPA1−FB−AP−...VMPA2−FB−AP−...
One electronic module per sub−base VMPA�...−FB−EM−... VMPA�...−MPM−EMM−...
Valve or cover plates:� MPA1: 4 per sub−base� MPA2: 2 per sub−base
VMPA�...−M1H−...VMPA�...−M1H−...
If necessary, additional pneumatic supply plate:� with exhaust plate� with large−surface silencer
VMPA�...−FB−SPVMPA�...−FB−SPU
If necessary, additional electric supply plate:� with M18 plug� with 7/8" (4−pin) plug� with 7/8" (5−pin) plug
VMPA−FB−SP−VVMPA−FB−SP−7/8−V−4POLVMPA−FB−SP−7/8−V−5POL
For each sub−base or pneumatic supply plateadded the appropriate manifold boards:� Manifold boards for sub−base
� Manifold boards for pneumatic supply plate
VMPA1−FB−EV−AB
VMPA1−FB−EV−V
See this chapter,Tab.�5/5
5. Maintenance and conversion
5−37Festo P.BE−MPA−EN en 0802c
Components MPA−S valve terminal with ...
CPX terminal multipin connection
For each sub−base or pneumatic supply plateadded the appropriate seal or isolating seal:� Seal
� Isolating seal
MPA−DPU or MPA−DP
Channel 1 separate: MPA−DPU−P or MPA−DP−PChannels 3 and 5 separate: MPA−DPU−RS or
MPA−DP−RSChannels 1, 3 and 5 separate: MPA−DPU−PRS or
MPA−DP−PRS
Tab.�5/10: Valve location extension
Dismantling Proceed as follows:
1. Loosen the MPA−S valve terminal from the fasteningsurface (see section �Dismantling the MPA−S valveterminal").
2. Remove the sub−base or supply plate at the point whereyou wish to extend the valve terminal (see section 5.3.6).
3. Only MPA−S valve terminal with multipin connection: If you wish to fit a further sub−base on the last sub−basebefore the right−hand MPA end plate, you must removethe end piece type MPA from the last manifold board.
1 End piecetype�MPA
1
Fig.�5/17: Removing/fitting the end piece of the last manifold board
5. Maintenance and conversion
5−38 Festo P.BE−MPA−EN en 0802c
Fitting Proceed as follows:
1. Fit the new sub−base and, if necessary, another pneumaticsupply plate (see section 5.3.6).
2. Only MPA−S valve terminal with multipin connection: If the new sub−base added is the last one in front of theright−hand MPA end plate, you must insert the end piecetype MPA into the last manifold board (see Fig.�5/17).
3. Fit the valve plates or blanking plates onto the emptyvalve locations (see section 5.3.3).
4. Mount the MPA−S valve terminal on the fastening surface(see chapter 2 �Fitting onto a wall" or �Fitting onto ahat�rail").
5. Then fit the pneumatic and electrical connections(see�chapter 3 �Installation, connecting the MPA−S valveterminal").
NoteIf a sub−base is inserted between existing sub−bases, theaddress assignment of all the valves to the right of theinserted sub−base will be shifted.
5.4.4 Adding an electric supply plate
The electric supply plate is intended for the intermediatesupply of load voltage for the valves.
5. Maintenance and conversion
5−39Festo P.BE−MPA−EN en 0802c
Necessary components
For extension you will require:
Components Type
One of the following electric MPA supply plates:� with M18 plug, (3−pin)� with 7/8" plug, (4−pin)� with 7/8" plug, (5−pin)
VMPA−FB−SP−VVMPA−FB−SP−7/8−V−4POLVMPA−FB−SP−7/8−V−5POL
Also a seal without channel separation or an isolating seal with channel separation See Tab.�1/8
Tab.�5/11: Electric supply plates
Fitting Proceed as follows:
1. Loosen the electric and pneumatic connections andremove the MPA−S valve terminal from its fasteningsurface (see section 5.2).
2. Fit the electric supply plate in accordance with the specifi�cations in the mounting instructions VMPA−FB−SP−...−...
5.4.5 Adding a pressure sensor plate
Necessary components
For extension you will require:
Components Type
One of the following pressure sensor plates:� For displaying the operating pressure in channel 1� For displaying the pressure in exhaust channels 3 and 5� For displaying an external pressure (P1)
VMPA−FB−PS−1VMPA−FB−PS−3/5VMPA−FB−PS−P1
Also a seal without channel separat. or an isolating seal with channel separation See Tab.�1/8
Tab.�5/12: Pressure sensor plates
5. Maintenance and conversion
5−40 Festo P.BE−MPA−EN en 0802c
Fitting Proceed as follows:
1. Loosen the electric and pneumatic connections andremove the MPA−S valve terminal from its fasteningsurface (see section 5.2).
2. How to fit the pressure sensor plate is described in themounting instructions VMPA−FB−PS−...
5.4.6 Adding a proportional pressure regulator
Necessary components
For extension you will require:
Components Type
Proportional pressure regulator VPPM−6TA−L−1−0L�...
Electronic moduleSub−baseAlso a seal without channel separat. or an isolating seal with channel separation
VMPA−Z−FB−EMS−P1VMPA−FB−AP−P1See Tab.�1/8
Tab.�5/13: Components of the proportional pressure regulator
Fitting Proceed as follows:
1. Loosen the electric and pneumatic connections andremove the MPA−S valve terminal from its fasteningsurface (see section 5.2).
2. How to fit the proportional pressure regulator isdescribed in the mounting instructions VMPA−6TA−...
Technical appendix
A−1Festo P.BE−MPA−EN en 0802c
Appendix A
A. Technical appendix
A−2 Festo P.BE−MPA−EN en 0802c
Contents
A. Technical appendix A−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.1 Technical specifications A−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.2 Festo accessories A−17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A. Technical appendix
A−3Festo P.BE−MPA−EN en 0802c
A.1 Technical specifications
NoteThe valves can be used at temperatures down to −5 °C. In order to prevent the condensate and the humidity fromfreezing, we recommend that you fit a dryer with whichcondensate and humidity can be removed.
General information
Permitted temperature range� Long−time storage� Operation� Medium
−20 � +40 °C−5 � +50 °C−5 � +50 °C
Protection class as per EN 60529 IP65 (with cable from Festoaccessories)
Relative humidity 90 % at 40 °C
Protection against corrosion KBK1 (as per FN 940070)
Assembly position as desired, with hat rail fitting onlyhorizontal
Tightening torques (MA)� Electronic modules on sub−bases� Proportional pressure regulator on sub−base� Exhaust plates on pneumatic supply plate, multipin
sub−base or pneumatic interface� Large surface−mounted silencer on pneumatic supply
plate, multipin sub−base or pneumatic interface� Fastenin gof sub−bases or electric supply plates (linking)� Board in multipin sub−base� Multipin connection� Support bracket on sub−bases or supply plates� Locking screw of the hat−rail clamping unit
0.32 � 0.48 Nm1.80 � 2.20 Nm0.59 � 0.71 Nm
0.90 � 1.10 Nm
1.62 � 1.98 Nm0.90 � 1.10 Nm0.59 � 0.71 Nm1.62 � 1.98 Nm1.30 Nm
MPA1 MPA2
� Components on sub−bases (valve, cover plate andvertical stacking)
0.20 � 0.30 Nm 0.59 � 0.71 Nm
A. Technical appendix
A−4 Festo P.BE−MPA−EN en 0802c
General information
Materials� Valve, sub−bases, supply plates and end plates� Electronic module� Multipin connection� Seals� Cover of the proportional pressure regulator
AlPOM/polycarbonatePolyamide 6Elastomer, NBRPAXMD6−GF50/gr−P; PA6−GB20, GF10/gr−P
Weights� Pneumatic interface or multipin sub−base
(with exhaust plate / large surface−mountedsilencer)
� CPI sub−base (with exhaust plate / large surface−mounted silenecer)
� AS−Interface (with exhaust plate / large surface−mounted silenecer)
� Per sub−base (with seal, electronic module,electric linking, label supports, screws)
� Per pneumatic supply plate (with seal, electriclinking, screws, exhaust plate / large surface−mounted silencer)
� Per electric supply plate (with seal, electriclinking, screws)
� Per pressure sensor plate� Per proportional pressure regulator with
sub−base and electronic module)� Per complete CPX module� Left−hand end plate (CPX terminal)� Right−hand end plate (MPA−S)
324 g / 315 g
427 g / 418 g
396 g / 360 g
185 g (4 valve locations)
120 g / 111 g
200 g
200 gapprox. 575 g
approx. 210 gapprox. 80 g55 g
MPA1 MPA2
� Per valve� Per cover plate� Per pressure regulator plate
approx. 56 g24 g100 g
approx. 100 g44 g180 g
Tab.�A/1: General technical data
A. Technical appendix
A−5Festo P.BE−MPA−EN en 0802c
NoteMPA−S valve terminal with multipin connection:
� The maximum number of sub−bases which can beconfigured corresponds to the number of addressesavailable. The maximum number of solenoid coils whichcan be actuated is limited by the multipin connection to24 addresses.
MPA−S valve terminal with CPX terminal:
� Maximum 16 sub−bases (MPA−S with electric supplyplate) or 8 sub−bases (MPA−S without electric supplyplate) are permitted.
MPA−S valve terminal with CPX terminal or multipinconnection:
� If the terminal is fitted on a wall and has 7 or moresub−bases, additional fastenings (wall backets) must befitted after every 2 to max. 4 sub−bases.
A. Technical appendix
A−6 Festo P.BE−MPA−EN en 0802c
General information
Vibration and shock 1) 2) 4)
� Vibration
� Shock
� Continuous shock
tested as per DIN/IEC 68 / EN 60068 part 2−6;with horizontal hat rail fitting: Severity level 1;with wall fitting: 2) 3)
tested as per DIN/IEC 68 / EN 60068 part 2−27;with horizontal hat rail fitting: Severity level 1;with wall fitting: 2) 3)
tested as per DIN/IEC 68 / EN 60068 part 2−29;with wall and hat rail fitting: Severity level 1
1) Specifications on vibration and shock of the CPX terminal can be found in the manual for the CPX�system.
2) MPA−S valve terminal with CPX terminal:� up to a length of 280 mm between the pneumatic interface and the right−hand end plate, without additional fastening: Severity level 2
� up to a length of 280 mm between the pneumatic interface and the right−hand end plate, with additional fastening on the pneumatic supply plates: Severity level 2
3) MPA−S valve terminal with CPI, with AS−Interface or with multipin connection: � up to a length of 280 mm of the valve terminal without additional fastening Severity level 2� as from a length of 280 mm of the valve terminal with at least one additional fastening in the centre of the valve terminal to the pneumatic supply plate: Severity level 2
4) Explanations on the severity classes see following table.
Tab.�A/2: Vibration and shock
Severitylevel
Vibration Shock Continuous shock
1 0.15 mm travel at 10 � 58 Hz,2 g acceleration at 58 � 150 Hz
±15 g at 11 ms duration,5 shocks per direction
±15 g at 6�ms duration;1000 shocks per direction
2 0.35 mm travel at 10 � 60 Hz,5 g acceleration at 60 � 150 Hz
±30 g at 11 ms duration,5 shocks per direction
−−−−−
Tab.�A/3: Values for vibration and shock as per DIN/IEC 68
A. Technical appendix
A−7Festo P.BE−MPA−EN en 0802c
Pneumatics
Medium Compressed air, filtered (< 40 m), lubricated (oil: VG 32) ornon−lubricated/vacuum, inert gases
Design Valve sub−bases with spool valves
Operating pressure/pilot controlPressure sensor
Valves:� With internal pilot air supply
(branched from connectrion 1)
� Operation with external pilot air
Pressure range0 � 10 bar
Valve location Ident. code B, D, E, G, H, I, J, K, M, N, W and X) at connection1: 3 � 8 bar
Valve location Ident. code B, E, G, J and M at connection 1: −0.9 � 10 barValve location Ident. code W at connection 2: −0.9 � 10 barValve location Ident. code X at connection 4: −0.9 � 10 barValve location Ident. code D, H, I, K and N at connection 1: 3 � 10 bar
All valve plates:at connection 12/14: see relevant diagrams
Proportional pressure regulator 2 bar type 6 bar type 10 bar type
� Input pressure 1)
� Regulating range� Control accuracy
� Standard (2 %)� Class S1 (1 %)
max. 4 bar0.02 � 2
0.045 bar0.025 bar
max. 8 bar0.06 � 6
0.135 bar0.075 bar
max. 11 bar0.1 � 10
0.225 bar0.125 bar
Rated size of proportionalpressure regulator� Pressurization� Exhaust
6 mm4.5 mm
Manual override Locking or non−locking
1) The input pressure p! must be at least 1 bar over output pressure p2.
Tab.�A/4: Medium and pressure range
A. Technical appendix
A−8 Festo P.BE−MPA−EN en 0802c
1 Pressure of theexternal pilot air(connection12/14), [bar]
2 Work range forvalves withexternal pilot air
3 Operatingpressure atconnection 1[bar]
0 1 2 3 4 5 6 7 8 9 100
1
2
3
4
5
6
7
8
9
1
2
3
Fig.�A/1: Diagram: Required pilot pressure related to the operating pressure with external pilot air supply and use of valve plates with Ident. code D, H, I, K and N
1 Pressure of theexternal pilot airsupply at pilotconnection 12/14[bar]
2 Work range forvalves withexternal pilot air
3 Operatingpressure atconnection 1[bar]
0 1 2 3 4 5 6 7 8 9 10
12
3
4
5
6
7
8
9
−10
1
2
3
Fig.�A/2: Diagram: Required pilot pressure related to the operating pressure with external pilot air and use of valve plates with Ident. code B, E, G, J, M, W and X
A. Technical appendix
A−9Festo P.BE−MPA−EN en 0802c
NoteThe screw connectors of the pneumatic connections causea reduction in the flow rate of the valves.
Pneumatics MPA1
I.C. 1) Valve Standard rated flows [l/min],measured with screw connector QS−M7−6−I
1 }% 2 or 1 } 4 2)
2 } 3/5 or 4 } 3/5 2)
DINKHX, WM, JBGE
2 x 2/2−way2 x 2/2−way2 x 3/2−way2 x 3/2−way2 x 3/2−way1 x 3/2 way5/2−way5/3−way, pressurised5/3−way, closed5/3−way, exhausted
230260300230300255360
300 (220) 3)
320240
230260300310305295360270320
240 (200) 3)
Valve switching times in [ms](Measuring method 0 � 10 % as per FN 942032)
On/changeover Off
D, IN, K, HX, WMJB, G, E
2 x 2/2−way2 x 3/2−way1 x 3/2 way5/2−way, single solenoid5/2−way, double−solenoid5/3−way valves
10101010
10/1510
20202020−−−35
1) I.C. = Identification Code of the valve plate2) Flow direction 1 } 4 or 4 } 3/5 not with valves with Ident. code I, W and X.3) Values for the mid−position are quoted in brackets
Tab.�A/5: Rated flows and valve switching times for MPA1
A. Technical appendix
A−10 Festo P.BE−MPA−EN en 0802c
Pneumatics MPA2
I.C. 1) Valve Standard rated flows [I/min] measured:
without fitting with screw connectorQS G1/8−8−I
1 }% 2 or1 } 4 2)
2 } 3/5 or 4 } 3/5 2)
1 }% 2 or1 } 4 2)
2 } 3/5 or 4 } 3/5 2)
D, INKHX, WM, JBGE
2 x 2/2−way2 x 3/2−way2 x 3/2−way2 x 3/2−way1 x 3/2 way5/2−way5/3−way, pressurised5/3−way, closed5/3−way, exhausted
680560500560500700520630610
−−−−490560490590700
650 (350) 3)
630440 (350) 3)
650550500550470670510610590
−−−−480540480560670
600 (350) 3)
610420 (350) 3)
Valve switching times in [ms](Measuring method 0 � 10 % as per FN 942032)
On/changeover Off
D, IN, K, HX, WMJBGE
2 x 2/2−way2 x 3/2−way1 x 3/2 way5/2−way, single solenoid5/2−way, double−solenoid5/3−way, pressurised5/3−way, closed5/3−way, exhausted
781315
9 /2211 / 2310 / 2111 / 23
25282228−−−464047
1) I.C. = Identification Code of the valve plate2) Flow direction 1 } 4 or 4 } 3/5 not with valves with Ident. code I, W and X.3) Values for the mid−position are quoted in brackets
Tab.�A/6: Rated flows and valve switching times for MPA2
A. Technical appendix
A−11Festo P.BE−MPA−EN en 0802c
Flow rate diagrams of the pressure regulator plates
Pressure regulator P
1 Output pressure
2 Flow rate
1
2
Fig.�A/3: Diagram: Flow as a factor of the output pressure for the proportional pressure regulator P, size MPA2 (Ident. code: PF and PA)
Pressure regulator B
1 Output pressure
2 Flow rate
1
2
Fig.�A/4: Diagram: Flow as a factor of the output pressure for the pressure regulator B,size MPA2 (Ident. code: PH and PC)
A. Technical appendix
A−12 Festo P.BE−MPA−EN en 0802c
Pressure regulator A
1 Output pressure
2 Flow rate
1
2
Fig.�A/5: Diagram: Flow as a factor of the output pressure for the pressure regulator A,size MPA2 (Ident. code: PG and PB)
Reversible pressure regulator B
1 Output pressure
2 Flow rate
1
2
Fig.�A/6: Diagram: Flow as a factor of the output pressure for the reversible pressure regulator B, size MPA2 (Ident. code PN and PL)
A. Technical appendix
A−13Festo P.BE−MPA−EN en 0802c
Reversible pressure regulator A
1 Output pressure
2 Flow rate
1
2
Fig.�A/7: Diagram: Flow as a factor of the output pressure for the reversible pressure regulator A, size MPA2 (Ident. code: PM and PK)
A. Technical appendix
A−14 Festo P.BE−MPA−EN en 0802c
Flow curves for type VPPM−6TA−L−1−...
2 bar valve variant:type VPPM−6TA−L−1−OL2H−...
6 bar valve variant:type VPPM−6TA−L−1−OL2H−...
10 bar valve variant:type VPPM−6TA−L−1−OL2H−...
Tab.�A/7: Flow curves of the proportional pressure regulator
A. Technical appendix
A−15Festo P.BE−MPA−EN en 0802c
Electric components, general
Electromagnetic compatibility (EMC)� Interference emission 1)
� Immunity to interference 2)see declaration of conformity è www.festo.com
Protection against electric shock(protection against direct and indirect contact as perIEC/DIN EN 60204−1)
by means of a PELV circuit (Protected Extra−Low Voltage)
1) The MPA valve terminal is intended for industrial usage.2) The maximum signal cable length with MPA−S valve terminals with multipin connection is 10 m
Tab.�A/8: Technical specifications for the electric components, general
Electrics, MPA−S valve terminal with multipin connection or AS−Interface
Voltage supply� Nominal voltage� Residual ripple
24 V DC ±25 %4 Vpp
Current consumption at the sub−D multipin connectionper pin (for each valve solenoid coil) at 24 V
MPA1 MPA2
� Rated pick−up current/duration� Nominal current with current reduction
80 mA / 25 ms25 mA after 25 ms
100 mA / 50 ms20 mA after 50 ms
Tab.�A/9: Technical specifications on electric components, MPA−S valve terminal withmultipin connection
Technical specifications on the electric components of theMPA−S valve terminal with multipin connection or AS−Interfacecan be found on the leaflet supplied with the product.
A. Technical appendix
A−16 Festo P.BE−MPA−EN en 0802c
Electric components, MPA−S valve terminal with CPX terminal or CPI module
Electronic module VMPA...−FB−...Operating voltage supply for electroniccomponents (VEL/SEN):� Nominal voltage� Max. intrinsic current consumption at 24 V
(internal electronics, all outputs 0 signal)
24 V DC ±25 %8 mA
VMPA...−FB−EMG−... VMPA...−FB−EMS−...
Load voltage supply valves (VVAL)� Nominal voltage� Max. intrinsic current consumption at 24 V
(internal electronics, without valves)� Diagnostic message undervoltage VVAL,
load voltage outside function range
24 V DC ±25 %typ. 23 mA
� 17.5 � 15.5 V
24 V DC ±25 %typ. 3 mA
� 17.5 � 15.5 V
Maximum current consumption per solenoidcoil out of load voltage VVAL at 24 V
MPA1 MPA2
� Nominal pull current/duration� Nominal current with current reduction
58 mA / 20 ms9 mA after 20 ms
99 mA / 20 ms18 mA after 20 ms
Pressure sensor plate� Accuracy� Display step width
< ±2.5 % FS (full scale)20 mbar
Proportional−Druckregelventil�VMPA−6TA−...
Operating voltage supply� Nominal voltage� Current consumption
24 V DC (permitted residual ripple max. ±10 %)max. 300 mA
Example of current calulationCurrent consumption with two solenoid coils MPA2 switched in parallel and one electronics modulewithout electrical isolation:� IEL/SEN = 20 mA� Rated pick−up current: IVAL = 8 mA + 2 x 90 mA = 188 mA� Rated current with current reduction: IVAL = 8 mA + 2 x 18 mA = 44 mA
Tab.�A/10: Technical specifications on electric components, MPA−S valve terminal withCPX terminal or CPI module
A. Technical appendix
A−17Festo P.BE−MPA−EN en 0802c
Technical specifications on the electronic module of theMPA−S valve terminal with CPX terminal or CPI module canbe found in electronics manual for the module (see systemmanual for your CPX terminal, table �Manuals on the CPXterminal").
A.2 Festo accessories
In the following table only some of the accessories for theMPA−S valve terminal are listed. The complete range of accessories can be found in the Festocatalogue (see www.festo.com\catalogue).
Accessories Type designation
General information� Blanking plug type M7� Blanking plug type G1/4� Manual override cover (manual override not accessible)� Manual override cap (manual override can only be operated in
non−locking mode)� Inscription label holder� Additional fastening bracket for wall fitting
B−M7B−1/4VMPA1−HBVVMPA1−HBT
VMPA1−ST−1−4VMPA−BG−RW
MPA−S valve terminal with multipin connection� Ready−to−use multipin cable with socket:
� for terminals with 4 valve locations� for terminals with 4 valve locations, suitable as drag chain� for terminals with 8 � 24 valve locations� for terminals with 8 � 24 valve locations, suitable as drag chain
� Multipin plug without cable� Hat rail mounting kit
VMPA−KMS1−8−...VMPA−KMS2−8−...−PURVMPA−KMS1−24−...VMPA−KMS2−24−...−PURVMPA−KMS−HCPA−BG−NRH
MPA−S valve terminal with CPX terminalHat rail mounting kit CPX−CPA−BG−NRH
Tab.�A/11: Accessories for the MPA−S valve terminal
A. Technical appendix
A−18 Festo P.BE−MPA−EN en 0802c
Supplementary component summary
B−1Festo P.BE−MPA−EN en 0802c
Appendix B
B. Supplementary component summary
B−2 Festo P.BE−MPA−EN en 0802c
Contents
B. Supplementary component summary B−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B.1 Overview of valve location components B−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B.2 Separating the MPA−S valve terminal from the CPX terminal B−11 . . . . . . . . . . . .
B. Supplementary component summary
B−3Festo P.BE−MPA−EN en 0802c
B.1 Overview of valve location components
The numbers on the following switching symbols are thedesignations of the connections, coils and manual overrides;e.g. designation 14 stands for manual override 14 or coil 14.They are not logic designations.
NoteAddress assignment of the MPA−S valve terminal withmultipin connection and modular linking (MPA−MPM−...):The number of addresses that a module occupiesdepends�on:
� the relevant electronic module (see chapter 3, Tab.�3/8)
� the relevant manifold board (see chapter 5, Tab.�5/5).
B. Supplementary component summary
B−4 Festo P.BE−MPA−EN en 0802c
2/2−way valves
82/84
12/14 1
4 2
1214
Ident. code DFunction:� Two single−solenoid 2/2−way valves,
normally closed� Spring return
82/84
12/14 1
4 2
1214
5
Ident. code IFunction: 1)
� Two single−solenoid 2/2−way valves, bothvalves normally closed, valve on controlside�14 reversible
� Spring return� With dual−pressure operation:
� supply operating pressure via connection 1� separate operating pressure can be supplied via connection 3/5
� with valve coil 14 operating pressure is switched from connection 5 to connection 4
� with valve coil 12 operating pressure is switched from connection 1 to connection 2
� With vacuum operation:� supply operating pressure via connection 1� supply vacuum via connection 5 � with valve coil 14 vacuum is switched to connection 4
� at connection 4 or in tubing 4 a filter is intended so that no dirt can enter the valve.
� with valve coil 12 operating pressure is switched to connection 2 (e.g. for reject pulse with vacuum operation)
� for reject pulses between connections 2, 4 and the vacuum generator, create connection via T−piece
1) Note: If this 2/2−way valve (Ident. code I) is also operated with other valves on the MPA−S valve terminal, this 2/2−way valve must be operated in a separate pressure zone with separate exhaust channel 5.
Tab.�B/1: 2/2−way valves
B. Supplementary component summary
B−5Festo P.BE−MPA−EN en 0802c
3/2−way valves
82/84
12/14 5 31
4 2
1214
Ident. code HFunction:� On control side 14 a single−solenoid 3/2−way
valve (normally closed)� On control side 12 a single−solenoid 3/2−way
valve (normally open)� Spring return
82/84
12/14 53
1
4 2
1214
Ident. code KFunction:� Two single solenoid 3/2−way valves� Normally closed� Spring return
82/84
12/14 53
1
4 2
1214
Ident. code NFunction:� Two single solenoid 3/2−way valves� Normally open� Spring return
82/84
12/14 32
4
14
Ident. code WFunction:� One 3/2−way valve, single−solenoid, normally
open, external pressure supply� Spring return
82/84
12/14 3
2
4
14
Ident. code XFunction:� One 3/2−way valve, single−solenoid, normally
closed, external pressure supply� Spring return
Tab.�B/2: 3/2−way valves
B. Supplementary component summary
B−6 Festo P.BE−MPA−EN en 0802c
5/2−way valves
82/84
12/145 31
4 2
1214
Ident. code JFunction:� One 5/2−way double−solenoid valve� Double solenoid
82/84
12/145 31
4 2
14
Ident. code MFunction:� One single−solenoid 5/2−way valve� Spring return
Tab.�B/3: 5/2−way valves
B. Supplementary component summary
B−7Festo P.BE−MPA−EN en 0802c
Note� In a currentless state 5/3−way valves assume themid−position by means of spring force.
� If both valve coils on 5/3−way valves are energizedsimultaneously, the valve remains in the switch position.
5/3−way valves
82/84
12/145 31
4 2
1214
Ident. code BFunction:� 5/3−way valve� Open in mid−position
82/84
12/145 3
1
4 2
1214
Ident. code EFunction:� 5/3−way valve� Mid−position exhausted
82/84
12/14 5 31
4 2
1214
Ident. code GFunction:� 5/3−way valve� Closed in mid−position
Tab.�B/4: 5/3−way valves
B. Supplementary component summary
B−8 Festo P.BE−MPA−EN en 0802c
Pressure regulator plates
24
14 5 1 3 12
Pressure regulator plate for connection 1(pressure regulator P)Ident. code: PF or PAFunction:� Regulates the operating pressure in channel 1
in front of the directional control valve
24
14 5 1 3 12
Pressure regulator plate for connection 2(pressure regulator B)Ident. code: PH or PCFunction:� Regulates the operating pressure in channel 2
after the directional control valve.
24
14 5 1 3 12
Pressure regulator plate for connection 4(pressure regulator A)Ident. code: PG or PBFunction:� Regulates the operating pressure in channel 4
after the directional control valve.
B. Supplementary component summary
B−9Festo P.BE−MPA−EN en 0802c
Pressure regulator plates
24
14 5 1 3 12
Pressure regulator plate for connection 2,reversible (pressure regulator B)Ident. code: PN or PLFunction:� Conducts the operating pressure from channel
1 to channels 3 and 5 in front of the directionalcontrol valve.
� Regulates the pressure in chanel 3 in front ofthe directional control valve.
� Conducts the exhaust from channel 1 tochannel 3 after the directional control valve.
Note:Cannot be combined with 2x2/2−way valves(Ident. code D and I) and 2x3/2−way valves(Ident. code H, K and N).
24
14 5 1 3 12
Pressure regulator plate for connection 4,reversible (pressure regulator A)Ident. code: PM or PKFunction:� Conducts the operating pressure from
channel�1 to channels 3 and 5 in front of thedirectional control valve.
� Regulates the pressure in chanel 5 in front ofthe directional control valve.
� Conducts the exhaust from channel 1 tochannel 5 after the directional control valve.
Note:Cannot be combined with 2x2/2−way valves(Ident. code D and I) and 2x3/2−way valves(Ident. code H, K and N).
Tab.�B/5: Pressure regulator plates for regulating outputs 1, 2 and 4
B. Supplementary component summary
B−10 Festo P.BE−MPA−EN en 0802c
Proportional pressure regulator VPPM−6TA−...
+w
−w
3
1
2
xIdent. code: QA, QB, QC, QD, QE, QFFunction:� Regulates the pressure proportional to a
specified nominal value
Tab.�B/6: Proportional pressure regulator
B. Supplementary component summary
B−11Festo P.BE−MPA−EN en 0802c
B.2 Separating the MPA−S valve terminal from the CPX terminal
The MPA−S valve terminal is connected to the CPX terminal bymeans of a pneumatic interface (see following figure).
1 CPX terminal
2 Pneumaticinterface
3 MPA−S valveterminal
1 2 3
Fig.�B/1: Pneumatic interface
Dismantling Proceed as follows:
1. Loosen the electrical and pneumatic connections andremove the MPA−S valve terminal from its fasteningsurface (see chapter 5, �Dismantling the MPA−S valveterminal").
2. Loosen the fastening screws between the pneumaticinterface and the MPA sub−base in the sequence 3, 2,1 (see Fig.�B/2).
3. Then loosen the fastening screws.
B. Supplementary component summary
B−12 Festo P.BE−MPA−EN en 0802c
2
1
3
Fig.�B/2: Removing the MPA−S valve terminal from thepneumatic interface
Information on replacing the pneumatic interface can befound in the CPX system manual.
B. Supplementary component summary
B−13Festo P.BE−MPA−EN en 0802c
Fitting Proceed as follows:
1. Make sure the seals are not damaged. Replace the seals ifthey are damaged.
2. Place the seal onto the guide pins of the pneumaticinterface.
1 Guide pins
2 Pneumaticsub−bases
3 Seal
4 Pneumaticinterface
1
234 1
Fig.�B/3: Fitting the MPA−S valve terminal to the pneumatic interface
3. Push the pneumatic interface together with the pneumaticsub−bases. Make sure that the seal and the componentsare correctly positioned.
B. Supplementary component summary
B−14 Festo P.BE−MPA−EN en 0802c
4. Insert the fastening screws in the appropriate holes.Tighten the screws in the sequence 1, 2, 3 (see following figure) at first slightly and then with1.62���1.98 Nm.
2
1
3
Fig.�B/4: Fastening the MPA−S valve terminal to thepneumatic interface
5. Fasten the MPA−S valve terminal onto the fasteningsurface (see CPX system manual).
6. Complete the electrical and pneumatic connections of theMPA−S valve terminal with CPX terminal. Information onthis can be found as follows:
� in the electrics section of the CPX system manual
� in the pneumatics section in chapter 3 of this manual.
Index
C−1Festo P.BE−MPA−EN en 0802c
Appendix C
C. Index
C−2 Festo P.BE−MPA−EN en 0802c
Contents
C. Index C−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C. Index
C−3Festo P.BE−MPA−EN en 0802c
A
Abbreviations, product−specific XIV . . . . . . . . . . . . . . . . . . . .
Accessories A−17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Address assignmentMPA−S valve terminal with CPX terminal 3−30 . . . . . . . . . . . MPA−S valve terminal with CPI module 3−32 . . . . . . . . . . . . MPA−S valve terminal with multipin plug connection 3−32 . Outputs 3−30 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Air humidityPermitted A−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Approvals VII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
AS−Interface X, 1−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C
CE identification VII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CleaningLarge surface−mounted silencer 5−6 . . . . . . . . . . . . . . . . . . .
Common tubing 3−24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ComponentsMaterials A−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Weights A−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Compressed airRequirements 3−4, A−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ConnectionsCode number 3−23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electric 1−32, 1−35, 1−36 . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pneumatic 1−30 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Size 3−23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Corrosion protection A−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cover plateDismantle/fit 5−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CPI module X, 1−6, 3−32 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C. Index
C−4 Festo P.BE−MPA−EN en 0802c
CPX terminal 1−5, 1−13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connections 1−32 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Display elements 1−32 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fitting/dismantling the MPA−S valve terminal B−11 . . . . . .
Current consumption A−15 . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D
Designated use VII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Display elements 1−32, 1−35, 1−36 . . . . . . . . . . . . . . . . . . . . . .
E
Electric supply plateConnecting the load voltage 3−26 . . . . . . . . . . . . . . . . . . . .
Electromagnetic compatibility A−15 . . . . . . . . . . . . . . . . . . . . .
Electronic moduleDismantle/fit 5−12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EMERGENCY STOP 4−21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
End plateDismantle/fit 5−19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ExhaustCentral 3−24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Exhaust plateDismantle/fit 5−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
F
Fitting variantsH−rail mounting 2−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Wall mounting 2−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Flow curvesProportional pressure regulator A−14 . . . . . . . . . . . . . . . . .
H
H−rail 2−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Clamping unit 2−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fit/remove 2−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C. Index
C−5Festo P.BE−MPA−EN en 0802c
I
Impairment of function 4−19 . . . . . . . . . . . . . . . . . . . . . . . . . .
Important user instructions XII . . . . . . . . . . . . . . . . . . . . . . . . .
Inscription label holderFit/remove 2−13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
IP protection class A−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
L
Large surface−mounted silencerCleaning 5−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Dismantle/fit 5−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LEDFault display 4−14, 4−16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Position of the LEDs 4−13, 4−17 . . . . . . . . . . . . . . . . . . . . . . . Proportional pressure regulator 4−16 . . . . . . . . . . . . . . . . . Switching status display of the valve coil 4−14, 4−15 . . . . . .
Load voltage A−16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Low−pressure operation 3−19, 4−21 . . . . . . . . . . . . . . . . . . . . . .
M
Manifold boardsReplace 5−22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Manual override 1−30 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fit/remove the cover cap 2−15 . . . . . . . . . . . . . . . . . . . . . . . Operating the non−locking manual override 4−11, 4−12 . . . . Variants 4−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Manuals IX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Materials A−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
MediumRequirements 3−4, A−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting kit, H−rail 2−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting rail 2−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
MPA electronic modulesOverview 5−15, 5−16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C. Index
C−6 Festo P.BE−MPA−EN en 0802c
MPA−S valve terminalAddress assignment of the outputs 3−30 . . . . . . . . . . . . . . Components XI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Dismantling/fitting the CPX terminal B−11 . . . . . . . . . . . . . Earthing the valve terminal 3−28 . . . . . . . . . . . . . . . . . . . . . Electric components 1−13 . . . . . . . . . . . . . . . . . . . . . . . . . . . Overview of variants 1−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pneumatic components 1−9, 1−10, 1−11, 1−12 . . . . . . . . . . . Sizes 1−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . With AS−Interface 1−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . With CPI module 1−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . With CPX terminal 1−5, 1−32 . . . . . . . . . . . . . . . . . . . . . . . . . . With multipin plug connection 1−7, 1−35, 1−36 . . . . . . . . . . .
Multipin connection 1−7, 1−13 . . . . . . . . . . . . . . . . . . . . . . . . . .
Multipin sub−baseDismantle/fit 5−28 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
N
Non−return valve 3−24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Notes on the use of this manual IX . . . . . . . . . . . . . . . . . . . . . .
O
Operating elementsPneumatic 1−30 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating pressure A−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating states 4−21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating voltage A−16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
P
Pictograms XIII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pilot air supplyBranched internally/supplied externally 3−12 . . . . . . . . . . Diagram A−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C. Index
C−7Festo P.BE−MPA−EN en 0802c
Pilot controlConversion to internal/external pilot air 5−26 . . . . . . . . . . . Diagram A−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pressure range A−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Type of pilot control 3−12 . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pneumatic interface, dismantle/fit B−12 . . . . . . . . . . . . . . . .
Pressure range A−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pressure regulator plate 1−22, 1−23 . . . . . . . . . . . . . . . . . . . . . Flow diagram A−11, A−12, A−13 . . . . . . . . . . . . . . . . . . . . . . . Pressure regulator A/B 1−25 . . . . . . . . . . . . . . . . . . . . . . . . Pressure regulator P 1−24 . . . . . . . . . . . . . . . . . . . . . . . . . . Reversible 3−16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Reversible pressure regulator A/B 1−27 . . . . . . . . . . . . . . . Set 3−16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pressure sensor plate 5−39 . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pressure zones 1−18, 3−13, 4−21, 5−31 . . . . . . . . . . . . . . . . . . . Seals 1−33, 1−34 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Proportional pressure regulator 5−40 . . . . . . . . . . . . . . . . . . . Dismantle/fit 5−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
R
Rated flows A−9, A−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Response times A−9, A−10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ReversiblePressure regulator plates 3−16 . . . . . . . . . . . . . . . . . . . . . .
S
Service VIII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Start−up pressurization 4−6 . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sub−base 1−22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Dismantle/fit 5−19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Supply plate, dismantle/fit 5−19 . . . . . . . . . . . . . . . . . . . . . . .
Supply plate (electric) 5−38 . . . . . . . . . . . . . . . . . . . . . . . . . . . Connecting the load voltage 3−26 . . . . . . . . . . . . . . . . . . . .
Supply pressureInternal/external pilot air supply 3−12 . . . . . . . . . . . . . . . . .
C. Index
C−8 Festo P.BE−MPA−EN en 0802c
T
Target group VIII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Temperature rangePermitted A−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Text markings XIII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tightening torques A−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Torques A−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Tubing 3−23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fit/remove 3−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V
Vacuum operation 3−19, 4−21 . . . . . . . . . . . . . . . . . . . . . . . . . .
Valve locationsMaximum number 3−30 . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Valve solenoid coilsCurrent consumption A−15 . . . . . . . . . . . . . . . . . . . . . . . . . .
Valves 1−14, 1−16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Dismantle/fit 5−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Identification code (Ident. code) 1−14, 1−16 . . . . . . . . . . . . . Overview B−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Vertical stacking 1−22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Identification in the type code 1−23 . . . . . . . . . . . . . . . . . . . Pressure regulator plate 1−31 . . . . . . . . . . . . . . . . . . . . . . .
Vibration and shock A−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Voltage supplyLoad voltage supply for the valves A−16 . . . . . . . . . . . . . . . Operating voltage supply for the electronics A−16 . . . . . . .
W
Wall mountingFit/remove 2−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
WeightsComponents A−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .