mounting and operating instructions eb 8365 en · dc voltage: 220 v, 0.25 a · 20 v, 6.9 a...
TRANSCRIPT
Mounting and Operating Instructions
EB 8365 EN Edition October 2013
Type 4746 Electric or Pneumatic Limit Switch
Definition of signal words
DANGER!Hazardous situations which, if not avoided, will result in death or seri-ous injury
WARNING!Hazardous situations which, if not avoided, could result in death or se-rious injury
NOTICEProperty damage message or mal-function
Note:Additional information
Tip:Recommended action
2 EB 8365 EN
Note on these mounting and operating instructionsThese mounting and operating instructions (EB) assist you in mounting and operating the de-vice safely. The instructions are binding for handling SAMSON devices.
Î For the safe and proper use of these instructions, read them carefully and keep them for later reference.
Î If you have any questions about these instructions, contact SAMSON's After-sales Service department ([email protected]).
Referenced documentationThe documents for the devices used in combination with the limit switch apply in addition to these mounting and operating instructions.The mounting and operating instructions for all supplied devices are included in the delivery. The latest versions of the documents are available on our website at www.samson.de > Prod-uct documentation.
Contents
EB 8365 EN 3
1 General safety instructions .............................................................................52 Design and principle of operation ..................................................................62.1 Principle of operation .....................................................................................62.1.1 Type 4746-x Inductive Limit Switch ..................................................................62.1.2 Type 4746-x3 Electric Limit Switch ...................................................................62.1.3 Type 4746-04 Pneumatic Limit Switch ..............................................................62.2 Article code and versions ...............................................................................82.3 Technical data .............................................................................................102.4 Accessories .................................................................................................122.5 Summary of explosion protection approvals ...................................................123 Attachment to the valve ...............................................................................143.1 Attachment to valve with cast yoke ................................................................143.2 Attachment to valve with rod-type yoke ..........................................................143.3 AttachmenttoType 3591Valve .....................................................................163.4 Attachment to positioner ...............................................................................184 Connections ................................................................................................194.1 Electrical connection .....................................................................................194.1.1 SwitchingamplifierforType4746-x2 ............................................................214.2 Pneumatic connection for Type 4746-04 ........................................................215 Operation ...................................................................................................225.1 Adjusting the switching point ........................................................................225.1.1 Type 4746-x2 ..............................................................................................225.1.2 Type4746-x3andType 4746-04 .................................................................236 Servicing explosion-protected devices ..........................................................247 Maintenance and calibration .......................................................................248 Dimensions .................................................................................................259 Certificates ..................................................................................................26
EB 8365 EN 5
General safety instructions
1 General safety instructionsFor your own safety, follow these instructions concerning the mounting, start up and opera-tion of the device: − The device is to be mounted, started up or operated only by trained and experienced
personnel familiar with the product.According to these mounting and operating instructions, trained personnel refers to indi-viduals who are able to judge the work they are assigned to and recognize possible dan-gers due to their specialized training, their knowledge and experience as well as their knowledge of the applicable standards.
− Explosion-protected versions of this device are to be operated only by personnel who has undergone special training or instructions or who is authorized to work on explosion-pro-tected devices in hazardous areas. Refer to section 6.
− Any hazards that could be caused in the valve by the process medium and the operating pressure or by moving parts are to be prevented by means of appropriate measures.If inadmissible motions or forces are produced in the pneumatic actuator as a result of the supply pressure level, it must be restricted using a suitable supply pressure reducing station.
To avoid damage to any equipment, the following also applies: − Proper shipping and storage are assumed.
Note:Positioners with a CE marking fulfill the requirements of the Directives 94/9/EC and 2004/108/EC. The Declaration of Conformity is available on request.
6 EB 8365 EN
Design and principle of operation
2 Design and principle of oper-ation
The limit switches are attached to pneumatic controlvalvesaswellastoType 4765andType 4763Positioners.These limit switches have either inductive, electric or pneumatic contacts. They issue a signal when the valve travel exceeds or falls below a limit, especially when a control valvehasreacheditsfinalposition.Thissig-nal is transmitted, e.g. to an alarm or indi-cating system.
2.1 Principle of operationThe valve travel is transmitted either directly to the pin (1.1) and lever (1) of the limit switch by the plate (10) or by a coupling pin when a positioner is attached. The linear travel is converted into a rotary motion by the shaft (2).
2.1.1 Type 4746-x Inductive Limit Switch
In this version, the shaft (2) carries two switch cases (3) with adjustable metal tags (4.1) for non-contact activation of the inte-grated proximity switches (5). For the opera-tion of inductive limit switches (except for Type 4746-0281),appropriateswitchampli-fiersmustbeintegratedintotheoutputcir-cuit.The switching function and switching point are continuously adjustable using the adjust-ment screw (3.1).
2.1.2 Type 4746-x3 Electric Limit Switch
In this version, the shaft (2) carries two switch cases (3) with adjustable cam disks (4.2). Each cam disk activates an electric double-throw switch (7) over the roller (6.1), which is attached to the switch lever (6). The switching function and switching point are continuously adjustable using the adjustment screw (3.1).
2.1.3 Type 4746-04 Pneumatic Limit Switch
In this version, the shaft (2) carries two switch cases (3) with adjustable cam disks (4.2). Each cam disk activates a nozzle/flappersysteminthepneumaticswitch(8).Whenever the cam disk (4.2) activates the switch lever (6) over the roller (6.1), the noz-zle in the pneumatic switch (8) is opened andthesupplyairfromthemicroswitch(9)is switched through to port A1 or A2.The nozzle is closed in the pneumatic switch (8) and the supply air applied to the micro-switchiscutofffirstwhenthecamdiskhasreleased the switch lever (6). As a result, pressure is no longer applied to port A1 or A2.The switching function and switching point are continuously adjustable using the adjust-ment screw (3.1).
EB 8365 EN 7
Design and principle of operation
3.13
5
L
10
4.1 1 1.12
L
3.13
1076.26.16
4.2 1 1.12
L
3.13
4.2 1 1.12
1086.26.16
A1 A29 9
8.2 8.1 8.1 8.2
pz
Inductive limit switch
Electric limit switch
Pneumatic limit switch with switching function
1 Lever for valve travel1.1 Pin2 Shaft3 Switch case3.1 Adjustment screw4.1 Metal tag4.2 Cam disk5 Proximity switch6 Switch lever6.1 Roller6.2 Spring7 Electric switch8 Pneumatic switch8.1 Nozzle (in switch)8.2 Flapper (in switch)9 Pneumaticmicroswitch10 Plate attached either to
actuator stem or plug stem
Fig. 1: Functional drawings
8 EB 8365 EN
Design and principle of operation
2.2 Article code and versionsLimit switch (device index .07 and higher) Type 4746- x x x x x x x 0 x x x x
Explosion protectionWithout 0Ex II 2G Ex ia IIC T6 acc. to ATEX 1CSA/FM intrinsically safe/non incendive 3Ex II 3G Ex nA II T6 acc. to ATEX 8
TypeInductive 2 1/2Electric 3 2Pneumatic 0 4 2
ContactsProximity switch SC3,5-N0-YE 1) 2 0 0 1 0Proximity switch SJ3,5-SN 2 1 0 1 0Proximity switch SJ3,5-S1N 2 1 1 1 0SAIA, electric microswitch XGK 3 3 2 0 2 1 0SAIA, electric microswitch XGK3-81 3 2 1 2 1 0Pneumatic microswitch 0 4 4 0 2 0Proximity switch SB3,5-E2 0 2 8 1 2 1 0
Switching elementsWith one switching element 1With two switching elements 2
Electrical connectionWithout 0 4 4 0 0Plastic cable gland M20 x 1.5, black 1 0
Pneumatic connectionsWithout 0ISO 221/1-G 1/8 0 4 4 0 0 11/8 -27 NPT 0 4 4 0 0 2
Special versionsWithout 0 0 0NEPSI approval Ex ia, Type 4746-12 inductive 1 2 2 0 0 9NEPSI approval Ex nL, Type 4746-82 inductive 8 2 2 0 1 0GOST approval Ex ia, Type 4746-1... 1 2/3 0 1 3KOSHA approval Ex ia 1 2/3 0 1 5INMETRO approval, Ex ia 1 2/3 0 1 7
1) Type 4746-3200onlywithFMapproval
EB 8365 EN 9
Design and principle of operation
Compatibility with paintWithout 0Free from substances that impair paint adhesion 1
Limit switch (device index .06 or lower) Type 4746- x x x x
Type
Inductive, no explosion protection 1
Inductive, Ex ib IIC T6 2
Electric 3
Pneumatic 4
Electrical connection/lever
Without 0
Cable gland, lever I (device index .04 or higher without lever) 1
Cable gland, lever II for positioner attachment 2
½” USA cable gland, lever I 3
½” USA cable gland, lever II for positioner attachment 4
Contacts
SJ3,5-N 0
SJ3,5-SN 1
SAIA electric microswitch XGK 3 2
Pneumatic microswitch with ISO 228/1-G 1/8 connecting thread 3
Pneumatic microswitch with 1/8-27 NPT connecting thread 4
SJ3,5-N (white dot of paint), max. hysteresis with 100 mm lever = 0.6 mm 5
Microswitch (gold contacts) 6
SJ3,5-E2 with LED (three-wire switch) without explosion protection, NO contact 1 8
SB3,5-E2 (three-wire switch) without explosion protection, NO contact 1 9
Switching elements
With one switching element 1
With two switching elements 2
Note:When replacing devices with index .00 to .03, a mounting unit with lever must also be ordered. See section 2.4.
10 EB 8365 EN
Design and principle of operation
2.3 Technical dataInductive Limit Switch Type 4746-x2 Type 4746-0281
Control circuit SwitchingamplifieraccordingtoEN60947-5-6 Three-wire switchOperatingvoltage10to30V
Proximity switch SC3,5-N0-YE 2) SJ3,5-SN SJ3,5-S1N SB3,5-E2
Permissible ambient temperature 1) –20 to 70 °C –20 to 100 °C –20 to 100 °C –20 to 70 °C
with metal cable gland –40 to 70 °C –50 to 100 °C –40 to 100 °C –25 to 70 °C
Electrical connections One M20x1.5 cable gland for 5.5 to 13 mm clamping rangeScrew terminals for 0.2 to 2.5 mm² wire cross-section
Degree of protection IP 65
Weight Approx. 0.7 kg
Type 4746-x3 Electric Limit Switch · Specifications apply to silver and gold-plated contacts
Switching element Electric limit switch: changeover/SPDT (single-pole/double-throw type)
Permissible load ACvoltage:220V,6.9ADCvoltage:220V,0.25A·20V,6.9A
Permissible ambient temperature 1) –20 to 85 °C
with metal cable gland –40 to 85 °C
Electrical connections One M20x1.5 cable gland for 5.5 to 13 mm clamping rangeScrew terminals for 0.2 to 2.5 mm² wire cross-section
Degree of protection IP 65
Weight Approx. 0.7 kg
Type 4746-04 Pneumatic Limit Switch
Switching element Pneumatic limit switch with downstream pneumatic microswitch
Supply air 1.4bar(20psi),canbebrieflyoverloadedupto4bar(60psi)
Air consumption 0.04 mn3/h
Output 0 or 1.4 bar (20 psi)
Air capacity One switch closed: 0.7 mn3/h·Twoswitchesclosed:1.0mn
3/h
Permissible ambient temperature –20 to 60 °C
Degree of protection IP 54
Weight Approx. 0.75 kg
EB 8365 EN 11
Design and principle of operation
Materials
Housing and cover Powder-coated aluminum
Lever and shaft 1.4571
Cable gland M20x1.5, black polyamide
Travel range
Attachment according to IEC 60534-6(NAMUR) LeverI:7.5to60mm·LeverII:60to180mm
Attachment to Type 4763 and Type 4765 Positioner Travel same as positioner
Compliance ·
1) ObservethelimitsspecifiedintheEC-typeexaminationcertificate.2) Models manufactured until 2006 with SJ3,5-N proximity switch.
Type 4746-1 with type of protection Ex ia (ATEX)Maximumvaluesforconnectiontocertifiedintrinsicallysafecircuits
Limit Switch Type 4746-12 Type 4746-13
Limit contacts Inductive Electric
Ui 16V 16V 45V
Ii 52 mA 25 mA –
Pi 169mW 64 mW 2 W
Ci - effective inner capacitance 60 nF 50 nFNegligibly small
Li - effective internal inductance 160 µH 250 µH
Temperature classes AmbienttemperaturerangeaccordingtoEC-typeexaminationcertificate(technicaldataspecifiedinabovetableadditionallyapply)
T4 –45 to 80 °C –45 to 100 °C –45 to 80 °C
T5 –45 to 70 °C –45 to 81 °C –45 to 70 °C
T6 –45 to 60 °C –45 to 66 °C –45 to 60 °C
12 EB 8365 EN
Design and principle of operation
2.4 AccessoriesAccessories for attachment according to IEC 60534-6Valve Cast yoke (NAMUR rib)
(see section 3.1)Rod-type yoke (18 to 32 mm rod diameter)
(see section 3.2)Travel Up to 60 mm Up to 180 mm Up to 60 mm Up to 180 mmMounting kit order no. 1400-6713
(lever I)1400-6714
(lever II)1400-6713 (lever I)
plus 1400-53421400-6714 (lever II)
plus 1400-5342Accessories for attachment to Type 4763 and Type 4765 Positioner (see section 3.4)Mounting kit order no. 1400-6710Accessories for attachment to Type 3351 Valve (see section 3.2)Nominal size DN 15 to 50 DN 65 to 100Mounting kit order no. 1400-6585 1400-6586Accessories for attachment to Type 3591 Valve with lever II (see section 3.3)Mounting kit order no. 1402-0662Vent plugs
Technical data G ¼connection,–50to+80 °C,material1.4404, degreeofprotectionIP 65
Order no. 1991-2110
2.5 Summary of explosion protection approvalsType Certificate Type of protection
4746
Number IEx 13.0040
Ex ia IIC T GbDate 17.05.2013
Validuntil 16.05.2016
STCC Number No.977 0Ex ia IIC T6X2Ex s II T6XValiduntil 01.10.2017
4746-1
Number RU C.DE.08.00744
1Ex ia IIC T6/T5/T4 Gb XDate 27.01.2015
Validuntil 26.01.2020
Number 3-KB4BO-0038
Ex ia IIC T6/T5/T4Date 31.01.2013
Validuntil 31.01.2016
EB 8365 EN 13
Design and principle of operation
Type Certificate Type of protection
4746-12
CCoE (on request)
Number GYJ15.1221
Ex ia IIC T4~T6 GbDate 16.06.2015
Validuntil 15.06.2020
4746-1x
Number PTB98ATEX2114
II 2G Ex ia IIC T6 GbDate 07.03.2003EC type examination certificate
4746-3Number 1607226 Ex ia IIC T6; Class I, Zone 0;
Class I,II, Div.1, Groups A,B,C,D,E,F,G;Class I,II, Div.2, Groups A,B,C,D,E,F,G;Date 16.09.2005
4746-324746-33
Number 3020228 Class I, Zone 0 AEx ia IICClass I,II,III; Div.1, Groups A,B,C,D,E,F,GClass I, Div.2, Groups A,B,C,D;Class II, Div,2 Groups F,G; Class III;
Date 28.02.2005
4746-8
Number RU C.DE.08.007442Ex nA IIC T6/T5/T4 Gc X2Ex ic IIC T6/T5/T4 Gc XDate 27.01.2015
Validuntil 26.01.2020
4746-82
Number GYJ15.1222XEx ic IIC T4~T6 GcEx nA IIC T4~T6 GcDate 16.06.2015
Validuntil 15.06.2020
Number PTB 02 ATEX 2012 X
II 3G Ex nA II T6Date 05.04.2002Statement of conformity
4746-83
Number PTB 02 ATEX 2012 X
II 3G Ex nA II T6Date 05.04.2002Statement of conformity
14 EB 8365 EN
Attachment to the valve
3 Attachment to the valveThe accessories listed in section 2.4 are re-quired for attachment.
Î The lever (I or II) must be installed before the limit switch is attached to the control valve. To do so, slide the lever clamping plate (1.1) over the lever (1) and slip them onto the shaft (2). Tighten the fas-tening screw (1.2).
3.1 Attachment to valve with cast yoke
1. Attach the plate (10) to the valve's stem connector using two screws (10.1).
2. Attach the pin (11) to the plate (10) us-ing two nuts (11.1).
3. Unscrew the cover of the limit switch. At-tach the limit switch to the valve yoke us-ing the mounting screw (12), washer (13) and O-ring (14). Make sure that the pin (11) is inserted through the wire strap (1.3) of the lever (1).
3.2 Attachment to valve with rod-type yoke
1. Attach the plate (10) to the valve's stem connector using two screws (10.1).
2. Attach the pin (11) to the plate (10) us-ing two nuts (11.1).
3. Fasten the support (15) and the rod clamping plate (16) loosely to the rod.
In the valve travel mid-position, move the support until the center of the plate (10) and the support (15) are aligned.
4. Fasten the rod clamping plate.5. Attach the limit switch to the support us-
ing the mounting screw (12), washer (13) and O-ring (14). Make sure that the pin (11) is inserted through the wire strap (1.3) of the lever (1).
Î After attaching the limit switch, make sure that the vent plug of the housing cover faces downward when the valve is installed
EB 8365 EN 15
Attachment to the valve
12 13 14
1.12 1.2 1 1.3 11 11.1 1010.1
12 13 15 16
1.12 1.2 1 1.3 11 11.1 1010.1
14
Attachment to valve with cast yoke (NAMUR rib)
Attachment to valve with rod-type yoke
1 Lever1.1 Clamping plate1.2 Screw1.3 Wire strap2 Shaft10 Plate10.1 Screws11 Pin11.1 Nuts12 Screw13 Washer14 O-ring15 Support16 Rod clamping plate
Fig. 2: Attachment to the valve
16 EB 8365 EN
Attachment to the valve
3.3 Attachment to Type 3591 Valve
Î Use the supplied washers for all screw connections.
1. Fasten the round brackets (1) using the clamps (3) and nuts (2) lightly onto the valve yoke.
2. Screw tight the bar (4) using the screws (5) onto the clamps (3).
3. Fasten the limit switch (6) onto the bar (4) as described in step 3 of section 3.1. Use the thread (7) in the bar.
4. Fastenthemountingbracket(9)usingthescrews(10)totheanti-rotationfixture(8)of the valve.
5. Screw the follower clamp (11) to the mountingbracket(9)usingthenutandbolt (12).
6. Insert the pin (13) into the oblong hole of the follower clamp (11). Make sure that the pin is inserted through the wire strap of the follower clamp.
7. Thread the nut (14) onto the pin (13). Place the clamp (16) over the lever (15) of the limit switch (6).
8. Use the nut (17) to fasten the lever (15) onto the lever extension (18).
9. Fasten the other end of the lever exten-sion (18) to the follower clamp (11).
10. Perform alignment.The following applies concerning attach-ment:
Î Perform the alignment in such a way that the lever (15), lever extension (18) and
oblong hole of the follower clamp (11) are in line with each other.
Î After attaching the limit switch, make sure that the vent plug of the housing cover faces downward when the valve is installed.
EB 8365 EN 17
Attachment to the valve
7
1614138
9
10
11
17
121 Round clamp2 Nut3 Clamp4 Bar5 Screws6 Limit switch7 Thread8 Anti-rotationfixture9 Mountingbracket10 Screws11 Follower clamp12 Nut and bolt13 Pin14 Nut15 Lever II16 Clamp (for lever)17 Nut18 Lever extension
Fig. 3: Attachment to Type 3591 Valve
815
11
18
10
9
453
1
2
6
18 EB 8365 EN
Attachment to the valve
3.4 Attachment to positionerFor attachment of the limit switch to the Type 4763or4765PositioneraccordingtoFig. 4, a short lever (1) and an intermediate piece (31) are required as accessories (order no. 1400-6710).1. Insert one O-ring (30) into both the left
and the right side of the intermediate piece (31).
2. Pushthetwofillisterheadscrews(33)through the limit switch and intermediate piece, and insert them into the positioner.
3. Insert the nuts (32) into the positioner housingandscrewtightthetwofillisterhead screws (33).
Make sure that the short lever (1) slides over the pin (16) of the positioner.
4. Replace the vent plug (17) in the posi-tioner housing with the screw plug in-cluded in the accessories (order no. 1400-6710).In exchange, insert the vent plug into the housing of the limit switch. This ensures that the degree of protection of the limit switch corresponds to that of the posi-tioner.
Î To achieve degree of protection IP 65, a checkvalve(orderno.1790-7408)needs to be installed in the housing of the limit switch.
17
A B
3031
161
31
32
33
NOTICEAttach the housing cover to the limit switch ensuring that the vent plug (17) faces downward after the valve is installed.
Lever with spring
Sectional view A – B
Fig. 4: Attachment with intermediate piece, e.g. to Type 4765 or Type 4763 Positioner
EB 8365 EN 19
Connections
4 Connections
4.1 Electrical connection
DANGER!For electrical installation, observe the relevant electrotechnical regulations and the accident prevention regula-tions that apply in the country of use. In Germany, these are the VDE regu-lations and the accident prevention regulations of the employers’ liability insurance.The following regulations apply to installation in hazardous areas: EN 60079-14:2008 (VDE 0165, Part 1) Explosive Atmospheres – Elec-trical Installations Design, Selection and Erection.
NOTICEAdhere to the terminal assignment! Switching the assignment of the elec-trical terminals may cause the explo-sion protection to become ineffec-tive. Do not loosen enameled screws in or on the housing. The maximum permissible values specified in the EC-type examination certificates ap-ply when interconnecting intrinsically safe electrical equipment. (Ui and U0, Ii and I0, Pi and P0, Ci and C0 as well as Li and L0)
Note on the selection of cables and wires:Observe clause 12 of EN 60079-14 (VDE 0165, Part 1) for installation of the intrinsically safe circuits. Clause 12.2.2.7 applies when run-ning multi-core cables and wires with more than one intrinsically safe cir-cuit.The radial thickness of the insulation of a conductor for common insulating materials (e.g. polyethylene) must not be smaller than 0.2 mm. The diame-ter of an individual wire in a fine-stranded conductor must not be smaller than 0.1 mm. Protect the con-ductor ends against splicing, e.g. by using wire-end ferrules.When two separate cables are used for connection, an additional cable gland can be installed. Seal cable en-tries left unused with plugs. Fit equip-ment used in ambient temperatures be-low –20 °C with metal cable entries.
20 EB 8365 EN
Connections
Note concerning equipment for use in zone 2:In equipment operated according to type of protection Ex nA II (non-sparking equipment) according to EN 60079-15:2003, circuits may be connected, interrupted or switched while energized only during installa-tion, maintenance or repair.Equipment connected to energy-lim-ited circuits with type of protection Ex nL (energy-limited equipment) ac-cording to EN 60079-15:2003 may be switched under normal operating conditions. The maximum permissi-ble values specified in the statement of conformity or its addenda apply when interconnecting the equipment with energy-limited circuits in type of protection Ex nL IIC.
EB 8365 EN 21
Connections
Cable entryThe cables for the electric control signal must be routed through the cable gland on the housing and connected to the input terminals marked+and–asillustratedinFig.5orac-cording to the adhesive label on the inside of the cover.The following accessories are available:Cable gland M20 x 1.5:Black plastic, with washer Order no. 8808-0180Blue plastic, with washer Order no. 8808-0181Nickel-platedbrass Orderno.1890-4875Adapter M20x1.5 to ½ NPT:Powder-coated aluminum Orderno.0310-2149Device index .06 and lowerBlack plastic Order no. 8808-0178Blueplastic Orderno.8808-0179
4.1.1 Switching amplifier for Type 4746-x2
For operation of the inductive limit switches, switchingamplifiersinaccordancewithEN 60947-5-6havetobeconnectedintheoutputcircuit(notforType 4746-0281).Observe the relevant regulations for installa-tion in hazardous areas.
4.2 Pneumatic connection for Type 4746-04
The air connections are tapped holes with G 1/8 ISO 228 or 1/8-27 NPT thread.Customaryfittingsformetaltubingorplastichoses can be used.
41 42 51 52 42 41 43 52 51 53
GW1 GW2
+ _ _+GW1 GW2
41 42L+ L- 51 52
+ _ _+
GW1 GW2
Type 4746-x2 Type 4746-x3Type 4746-0281
Switchingamplifieracc.toEN60947-5-6 Three-wire version
Voltagesupply10to30V
Fig. 5: Electrical connection
22 EB 8365 EN
Operation
5 Operation
5.1 Adjusting the switching point
The limit switches attached to control valves are usually adjusted in such a way that a signalisissuedwhenthefinaltravelposi-tions are reached. Optionally, the switching point can also be adjusted to any position within the travel range, e.g. if an intermedi-ate position is to be indicated.The adjusted switch positions can be record-ed on the supplied adhesive labels marked A, B and C, and assigned to the correspond-ing switching elements.
3.14.1, 4.2
42(52)
42(52)
41(51)43(53)
41(51)43(53)
A A
3.1 Adjustment screw4.1 Metal tag4.2 Cam disk
Type 4746-x2Inductive Limit Switch
Type 4746-0281Close three-wire sensor PNP
Type 4746-x3Electric Limit Switch
Type 4746-04Pneumatic Limit Switch
Open
Supply air applied
Open
Closed
Supply air cut off
Closed
Fig. 6: Limit contacts
5.1.1 Type 4746-x2 Î Move the valve to the switching position and turn the adjustment screw (3.1) until the metal tag (4.1) reaches the switching point.
Î Alwaysmovethevalvetothefinaltravelpositions from an intermediate position on adjusting or checking the switching point!
EB 8365 EN 23
Operation
Note:The switching elements and the le-vers required to activate them react to temperature fluctuations. To ensure reliable switching, the switching hys-teresis between the mechanical stop (e.g. plug in the seat) and the switch-ing point of the limit switch must be larger than the displacement of the switching point caused by the tem-perature change.
Distance between switching points for 100 mm lever:ContactSC3,5-N0-YE ≥2mm,ContactSJ3,5-SN ≥0.75mm.With other lever lengths, adjust the switching point to the changed lever length.For example, if the lever length changes from 100to160 mm,thedistancebetweentheswitching points is increased from 2.0 to 3.2 mmcorrespondingly.
Simplified adjustment of the inductive limit switches:Valve CLOSED:Close the valve until the plug sits in the seat.Valve OPEN:Move the valve to the desired travel position, e.g.finalposition. − Turn the adjustment screw (3.1) to slowly
move the metal tag (4.1) towards the contact until the switching point is reached.
− Turn the adjustment screw in the opposite direction to achieve that the switching point reaches the stop after
− contactSC3,5-N0-YE ≥1/6 turncontactSJ3,5-SN ≥1/16 to 1/10 turn
If the adjustment is performed carefully, the distances between the switching points speci-fiedaboveapply.
5.1.2 Type 4746-x3 and Type 4746-04
Î For adjustment, the cam disk (4.2) has to be positioned in such a way that its cam moves towards the roller (6.1, Fig. 1) in accordance with the direction of travel.
1. Move the valve to the desired switching position(e.g.finaltravelposition"valveOPEN"or"valveCLOSED").
2. Adjust the switch which is assigned to the upper or lower switching point.
3. Turn the adjustment screw (3.1) until the cam of the cam disk (4.2) reaches the roller (6.1, Fig. 1) and the switch chang-es over.
4. To accurately check the switching point, move the valve slightly back and then move it to the switching position again.
24 EB 8365 EN
Servicing explosion-protected devices
6 Servicing explosion-protected devices
If a part of the device on which the explosion protection is based needs to be serviced, the device must not be put back into operation untilaqualifiedinspectorhasassesseditac-cording to explosion protection require-ments,hasissuedaninspectioncertificateorgiven the device a mark of conformity.Inspectionbyaqualifiedinspectorisnotre-quired if the manufacturer performs a rou-tine test on the device prior to putting it back into operation. Document the passing of the routine test by attaching a mark of conformi-ty to the device.Replace explosion-protected components on-ly by original, routine-tested components provided by the manufacturer.Devices that have already been used outside hazardous areas and are intended for future use inside hazardous areas must comply with the safety requirements placed on ser-viced devices. Before being operated inside hazardous areas, test the devices according tothespecificationsforservicingexplosion-protected devices.
7 Maintenance and calibrationInterconnection with intrinsically safe circuits to check or calibrate the equipment inside or outside hazardous areas is to be performed only with intrinsically safe current/voltage calibrators and measuring instruments to rule out any damage to components relevant to explosion protection.
Î Observe the maximum permissible val-uesspecifiedinthecertificatesforintrin-sically safe circuits.
EB 8365 EN 25
Dimensions
8 Dimensions
27.5
9444
.5
1837
1883
7492
1583
20.6
27,5
74 189
15
9464
44.5
M 20x1.5
7771 30
148
7771 30
148
Type 4746-x2 and Type 4746-x3Air connection for separate air supply, tapped hole G 1/8
Intermediate piece for attachment to positioner
M8 fastening screw M8 fastening screw
Output
Supply air
Pneumatic connections
L I/L
II
L I/L
II
NAMUR rib NAMUR rib
Type 4746-04Air connections, tapped hole G 1/8 or 1/8 NPT
Lever length L I/L IILeverI: 149mmLever II: 202 mm
26 EB 8365 EN
Certificates
9 Certificates
Note:The type designations of the Types 4746-2 and 4746-3 Limit Switches have been changed. The certificates of conformity remain valid. See the following confirmation for details.
EB 8365 EN 27
28 EB 8365 EN
EB 8365 EN 29
30 EB 8365 EN
EB 8365 EN 31
32 EB 8365 EN
EB 8365 EN 33
34 EB 8365 EN
Ad
den
du
m P
ag
e 5
Revi
sion
s C
on
trol N
um
ber:
2 S
epte
mb
er
20
15
A
dd
en
du
m t
o E
B 8
365
EN
Inst
alla
tion
Ma
nu
al
for
ap
pa
ratu
s a
pp
rove
d b
y FM
for
use
in
ha
zard
ous
loca
tion
s.
Elec
tric
al r
atin
g of
intr
insi
cally
saf
e ap
para
tus
and
appa
ratu
s fo
r in
stal
latio
n in
haz
ardo
us
loca
tions
. Ta
ble
1:
Ma
xim
um
va
lues
U
i or
Vm
ax
Ii or
Ima
x P
i or
Pm
ax
Ci
Li
Lim
it s
wit
ches
(i
nd
uct
ive)
Typ
e S
J3,5
…
16 V
25
/52
mA
64
/169
mW
60
nF
250
µH
Lim
it s
wit
ches
(i
nd
uct
ive)
Typ
e S
C3,5
…
16 V
25
mA
34
mW
15
0 nF
15
0 µH
Lim
it s
wit
ches
(e
lect
rica
l)
28 V
11
5 m
A
2 W
0
nF
0 µH
Note
s: U
0 o
r V
0C o
r V
t ≤
Ui or
Vm
ax /
I0 o
r I0
C o
r It
≤ I
i or
Ima
x
P0
or
Pm
ax
≤ P
i or
Pm
ax
Tab
le 2
: FM
- a
pp
rove
d b
arr
ier
pa
ram
ete
rs o
f ele
ctri
cal
lim
it s
wit
ch c
ircu
its
Ba
rrie
r Su
pp
ly b
arr
ier
Eva
lua
tion
ba
rrie
r
V0
C
Rm
in
I0C
Pm
ax
V0
C
Rm
in
I0C
Lim
it s
wit
ches
(e
lect
rica
l)
≤ 28
V
≥ 98
Ω
≤ 11
5 m
A
≤ 2
W
≤ 28
V
# 0
mA
Tab
le 3
: Th
e co
rrel
atio
n be
twee
n te
mpe
ratu
re c
lass
ifica
tion
and
perm
issi
ble
ambi
ent
tem
pera
ture
ran
ges
is s
how
n in
the
tabl
e be
low
:
Tem
pera
ture
cla
ss
Perm
issi
ble
am
bie
nt
tem
pera
ture
ra
ng
e
T6
T5
T4
- 45
°C …
60
°C
- 45
°C …
70
°C
- 45
°C …
80
°C
Ad
den
du
m P
ag
e 6
Revi
sion
s C
on
trol N
um
ber:
2 S
epte
mb
er
20
15
A
dd
en
du
m t
o E
B 8
365
EN
Tab
le 4
: F
or t
he M
odel
474
6 –
32
Lim
it Sw
itch
with
typ
e SJ
3,5
… s
enso
rs t
he c
orre
latio
n
be
twee
n te
mpe
ratu
re c
lass
ifica
tion,
per
mis
sibl
e am
bien
t tem
pera
ture
ran
ges
and
max
imum
sho
rt-
circ
uit c
urre
nt is
sho
wn
in t
he ta
ble
belo
w:
Tem
pera
ture
cla
ss
Perm
issi
ble
am
bie
nt
tem
pera
ture
ra
ng
e
Ma
xim
um
sh
ort
-cir
cuit
cu
rren
t
T6
T5
T4
- 45
°C …
45
°C
- 45
°C …
60
°C
- 45
°C …
75
°C
52m
A
T6
T5
T4
- 45
°C …
60
°C
- 45
°C …
80
°C
- 45
°C …
80
°C
25m
A
Tab
le 4
: F
or t
he M
odel
474
6 –
32
Lim
it Sw
itch
with
typ
e SC
3,5
… s
enso
rs t
he c
orre
latio
n
be
twee
n te
mpe
ratu
re c
lass
ifica
tion,
per
mis
sibl
e am
bien
t tem
pera
ture
ran
ges
and
max
imum
sho
rt-
circ
uit c
urre
nt is
sho
wn
in t
he ta
ble
belo
w:
Tem
pera
ture
cla
ss
Perm
issi
ble
am
bie
nt
tem
pera
ture
ra
ng
e
Ma
xim
um
sh
ort
-cir
cuit
cu
rren
t
T6
T5
T4
- 45
°C …
55
°C
- 45
°C …
67
°C
- 45
°C …
80
°C
25m
A
Intr
insi
cally
safe
if
inst
all
ed
as
speci
fied
in
ma
nu
fact
ure
r’s
inst
alla
tion
ma
nu
al.
FM
- a
pp
rove
d f
or
ha
zard
ous
loca
tion
s
Cla
ss I
, Z
on
e 0
A E
x ia
IIC
T6,
C
lass
I, II
, II
I, D
ivis
ion
1, G
rou
ps
A,
B,
C,
D, E,
F +
G
NEM
A 3
R
Note
s:
1.)
The
appa
ratu
s m
ay b
e in
stal
led
in in
trin
sica
lly s
afe
circ
uits
onl
y w
hen
used
in c
onju
nctio
n w
ith t
he F
M a
ppro
ved
appa
ratu
s.
For
max
imum
val
ues
of U
i or
Vm
ax
; Ii o
r Im
ax;
Pi o
r Pm
ax
; Ci a
nd L
i o
f th
e va
riou
s ap
para
tus
see
Tabl
e 1
. 2
.) Th
e ap
para
tus
may
be
inst
alle
d in
intr
insi
cally
saf
e ci
rcui
ts o
nly
whe
n us
ed in
con
junc
tion
with
the
FM
app
rove
d in
trin
sica
lly s
afe
barr
ier.
Fo
r ba
rrie
r se
lect
ion
see
Tabl
e 2
. 3
.) Th
e in
stal
latio
n sh
all b
e in
acc
orda
nce
with
the
Nat
iona
l Ele
ctri
cal C
ode
AN
SI/N
FPA
70
an
d A
NSI
/ISA
RP
12
.06.
01.
4
.) Sa
fety
Bar
rier
sha
ll be
FM
-App
rove
d. E
ach
pair
of
I.S.
wir
es s
hall
be p
rote
cted
by
a sh
ield
th
at is
gro
unde
d at
the
I.S.
Gro
und.
The
shi
eld
shal
l ext
end
as c
lose
to th
e te
rmin
als
as
poss
ible
. 5
.) U
se o
nly
supp
ly w
ires
sui
tabl
e fo
r 5
°C a
bove
am
bien
t te
mpe
ratu
re.
EB 8365 EN 35
Ad
den
du
m P
ag
e 7
Revi
sion
s C
on
trol N
um
ber:
2 S
epte
mb
er
20
15
A
dd
en
du
m t
o E
B 8
365
EN
Vers
ion
: M
odel
474
6-3
3 E
lect
rica
l Lim
it Sw
itch.
Sup
ply
and
eval
uatio
n ba
rrie
r FM
app
rove
d.
Cab
le e
ntry
M 2
0 x
1.5
or
met
al c
ondu
it ac
cord
ing
to d
raw
ing
N
o. 1
050
– 0
539
T o
r 10
50 –
054
0 T
FM-
ap
pro
ved
for
ha
zard
ous
loca
tion
s
Cla
ss I
, D
ivis
ion
2, G
rou
ps
A,
B, C
, D
NEM
A 3
R
Cla
ss I
I D
ivis
ion
2, G
rou
ps
F +
G, C
lass
III
H
AZ
AR
DO
US
SAFE
LO
CA
TIO
N (
Div
. 2
) LO
CA
TIO
N
sup
ply
ba
rrie
r
eva
lua
tion
ba
rrie
r
Model 4746-3 Limit Switch
41
+
42-
41+
42-
51+
52-
51+
52-
elec
tric
al li
mit
switc
h
Mod
el 4
746-
33
indu
ctiv
e lim
it sw
itch
Mod
el 4
746-
32
indu
ctiv
e lim
it sw
itch
Mod
el 4
746-
32
elec
tric
al li
mit
switc
h
Mod
el 4
746-
33
Term
inal
No.
I.S.
Gro
un
d
rela
y or
tra
nsi
stor
ou
tpu
t
HA
ZA
RD
OU
S
LOC
ATI
ON
SAFE
LOC
ATI
ON
sup
ply
ba
rrie
r
eva
lua
tion
ba
rrie
r
Model 4746-3 Limit Switch
41+
52-
41+
42-
limit
switc
h
circ
uit 1
limit
switc
h
Circ
uit 2
Term
ina
l N
o.
Gro
un
d
UNSPECIFIED APPARATUS
e. g. transistor relay, transmitter
Ad
den
du
m P
ag
e 8
Revi
sion
s C
on
trol N
um
ber:
2 S
epte
mb
er
20
15
A
dd
en
du
m t
o E
B 8
365
EN
Note
s:
1.)
For
the
max
imum
val
ues
for
the
indi
vidu
al c
ircu
its s
ee T
able
1 a
nd 2
. 2
.) C
able
ent
ry M
20
x 1
.5 m
etal
con
duit
acco
rdin
g to
dra
win
g
No.
105
0-0
539
T a
nd 1
050
-054
0 T
3.)
The
inst
alla
tion
shal
l be
in a
ccor
danc
e w
ith t
he N
atio
nal E
lect
rica
l Cod
e A
NSI
/NFP
A 7
0
Inst
alla
tion
dra
win
g C
on
trol
Rela
y H
ab
– c
Ex d
e w
ith
Mod
el SJ
-b-N
Pro
xim
ity
Sen
sors
Con
tro
l R
ela
y Te
rmin
al N
o.
Gro
up
s L
[ m
H ]
C
[ µ
F ]
V0C
[ V
]
ISC
[ m
A ]
1-3
; 2
-3
4-6
; 5
-6
A +
B
84
,8
1,2
7
12
,9
19
,8
C +
E
29
9
3,8
2
D, F,
G
74
4
10
,2
HA
ZA
RD
OU
S
LOC
ATI
ON
SAFE
LOC
ATI
ON
contact
Cla
ss I
,
Div
isio
n 1
, G
rou
ps
A, B
, C
, D
C
lass
II,
D
ivis
ion
1,
Gro
up
s E
, F
an
d G
C
lass
II
I, D
ivis
ion
1
to in
trin
sica
lly
safe
outp
ut
Model 4746-3 Inductive limit switch circuit
+ -
pro
xim
ity
sen
sor
1+
2+
3- 4+
5+
6-
intr
insi
cally
safe
outp
ut
to s
enso
r o
r co
nta
ct
cha
nn
el 3
to o
ne c
om
mon
lin
e p
oss
ible
Sw
itch
-Iso
lato
rs
Typ
e K
Ha
b –
c E
xd
Typ
e K
Ha
b –
c E
xde
12
+
11
+
10
-
9+
8+
7-
supply and output terminals
Mo
del d
esi
gn
ati
on
co
de T
ype K
Ha
b –
cEx
d
Term
inal
s 1-
3, 2
-3, 4
-6, 5
-6
a=
Su
pp
ly V
olt
ag
e t
ype A
or
D
a
=A
C, d
=D
C
b=
Su
pp
ly L
evel
2=
24V
DC
±15%
; 5=
120V
AC
+10%
-15%
;
6=
230V
AC+
10%
-15%
; c=
Ou
tput
typ
e O
T1;
TA2 o
r TA
1;
d=
Nu
mb
er
of
cha
nn
els
1 o
r 2
Mo
del d
esi
gn
ati
on
co
de T
ype K
Ha
b –
cEx
de
a=
Su
pp
ly V
olt
ag
e t
ype A
or
D
a
=A
C, d
=D
C
b=
Su
pp
ly L
evel
2=
24V
DC
±15%
; 5=
120V
AC
+10%
-15%
;
6=
230V
AC+
10%
-15%
; c=
Ou
tput
typ
e R
TA/;
RW
1/;
SS1
/; S
S2/;
RS1
/;
SR
/; S
T-o
r SO
T d
= N
um
ber
of
cha
nn
els
1 o
r 2
e=
Pow
er
rail d
esi
gn
ati
on
, P
, 2S.
P o
r G
S.P
(i
ncl
ud
es
Mo
del K
HD
2-E
B-P
B P
ow
er
Feed
M
od
ule
) o
r B
lan
k
ma
xim
um
ca
pa
cita
nce
of
ea
ch in
du
ctiv
e s
enso
r 60n
F m
axi
mum
in
du
cta
nce
of
ea
ch in
du
ctiv
e s
enso
r 25
0µ
H
The
tota
l ser
ies
indu
ctan
ce a
nd s
hunt
cap
acita
nce
of s
hiel
d w
iring
sha
ll be
rest
ricte
d to
the
follo
win
g m
axim
um v
alue
s
36 EB 8365 EN
EB 8365 EN 37
38 EB 8365 EN
EB 8365 EN 39
SAMSON AG · MESS- UND REGELTECHNIKWeismüllerstraße 3 · 60314 Frankfurt am Main, GermanyPhone: +49 69 4009-0 · Fax: +49 69 [email protected] · www.samson.de EB 8365 EN 20
16-02-02·English