module no e03 electrical test equipment basic
TRANSCRIPT
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
1/203
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
2/203
DUTY NO 15: TEST INSTRUMENTS
OBJECTIVES
Upon completion of this module, the technician would be able to demonstrate
knowledge and understanding on the following:
1. Safety precautions in test & measurement
2. Basic construction and operation of Multimeter (Digital & Analog)
3. Functional selection, setting of Digital Multimeter
4. Use of digital multimeter and test procedures.5. Theory of Insulation measurement
6. Basic construction and operation of Insulation resistance tester
7. Functional selection, setting of Insulation resistance tester
8. Use of digital Insulation resistance tester and test procedures.
9. Basic construction and operation of Clamp on Ammeter
10. Functional selection, setting & use of Clamp on Ammeter
11. Theory of Earth Resistance measurement
12. Function and operation of Earth Resistance tester
13. Preparation and set-up of Earth Resistance tester
14. Function and operation of Loop tester and RCD tester
15. Preparation and set-up of Loop tester and RCD tester
16. test procedure & circuitry
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
3/203
TABLE OF CONTENT
1.0.0 Introduct ion.............................................................................. 5
2.0.0 Safety........................................................................................ 6
2.1.0 Causes of Electrocut ion ..........................................................................8
2.2.0 Use of High voltage protection equipment ...........................................8
2.2.1 Clearances ..................................................................................................................9
2.3.0 Section 2 Safety of BS 6626: 1985 .......................................................10
2.3.1. Responsib ili ty ..........................................................................................................102.3.2 Rules or procedure for safe systems at work ........................................................10
2.3.3 Isolation and access for maintenance ....................................................................11
2.3.4 Preparing for main tenance work .............................................................................12
2.3.5 Fire extingu ish ing equipment ..................................................................................13
2.3.6 Testing.......................................................................................................................14
2.3.7 Disposal of scrap......................................................................................................14
3.0.0 Mult imeter .............................................................................. 15
3.1.0 Analog Multimeter..................................................................................16
3.2.0 Digital Multimeter ...................................................................................17
3.2.1 Voltage Measurements.............................................................................................20
3.2.2 Current Measurements.............................................................................................21
3 2 3 Resistance Measurements 21
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
4/203
4.8.0 Insulation resistance (IR) test on Motor/Generator............................32
5.0.0 Clamp on meter ..................................................................... 34
5.1.0 Theory of operat ion of AC Clamp on meter ........................................35
5.2.0 Theory of operation of AC/DC Clamp on meter..................................36
5.3.0 Specifications of Digital Clamp on meters..........................................37
5.4.0 Advantages of Digital Clamp on meter................................................37
5.5.0 Advantages of Digital over Conventional Type ..................................37
5.6.0 Applications of Digital Clamp on meters.............................................38
5.7.0 Clamp on meter operations (Fluke model 321/322)............................38
5.8.0 Safety Precautions.................................................................................40
6.0.0 Earth tester, Loop tester & Residual Current Device (RCD)
tester................................................................................................ 42
6.1.0 Earth resistance .....................................................................................43
6.2.0 Principle of Earth resis tance test ing ...................................................44
6.3.0 Earth resistance test methods .............................................................46
6.4.0 Earth Loop resistance ...........................................................................47
6.5.0 Earth Loop resistance test ....................................................................48
6.6.0 Digital Earth Loop resis tance tester from Megger (L T5 and L T6) ..48
6.7.0 Applications & Use of Earth Loop resis tance tester..........................49
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
5/203
1.0.0 IntroductionTesting is performed to verify the integrity of electrical systems. Most of these tests
are non-destructive in nature and can be used to provide a complete look at the status
and age of the equipment. In this module, we will concentrate on the following
electrical tests instruments:
Multimeter (Digital & Analog)
Insulation resistance tester
Clap on Ammeter
Earth resistance tester
Earth loop impedance & RCD tester
In this module included the some specific OEM instruction manuals for the above
mentioned test set. The module basically prepared to train the technicians to read and
interpret the OEM manuals of the test instrument, which is the required to perform the
some of the tasks prescribed in POSS under duty no. 15. In the process, it covers thebasic underpinning knowledge required to perform the required tasks. For gaining the
expertise in the activities, detail study of the Operation & Maintenance manual of
respective test instrument and hands on experience is necessary.
Note:Testing of electrical distribution equipment requires experience and an
understanding of the hazards involved. The test equipment used at your workplace
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
6/203
2.0.0 SafetyIn the interest of safety, all test equipment should be inspected and tested before
being taken to the job site. There is no need to get to the job and find that the test
equipment does not work.
A thorough visual inspection (i.e., checking for broken meters or knobs, damaged
plugs, or frayed cords) is important.
Always perform an operational check. For example:
On an ohmmeter, short the probes and ensure that you can zero the meter.
A voltmeter can be checked against an AC wall receptacle or a battery.
If a meter has a calibration sticker, check to see if it has been recently calibrated.
For precise measurements, a recently calibrated meter is a more reliable instrument.
Every person who works with electrical equipment should be constantly alert to
the hazards to which personnel may be exposed, and should also be capable of rendering
first aid. The hazards are electric shock, burns, and related hazards.
Safety must be the primary responsibility of all personnel. The installation,
maintenance, and operation of electrical equipment enforce a strict safety code.
Carelessness on the part of the technician or operator can result in serious injury or death
due to electrical shock, falls, burns, flying objects, etc. When an accident has occurred,
investigation almost invariably shows that it could have been prevented by the exercise of
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
7/203
equipment commonly has more than one source of power. Be certain that all power
sources are de-energized before servicing the equipment. Do not service any equipment
with the power on unless absolutely necessary. Remember that the 115V power supply
voltage is not a low, relatively harmless voltage but is the voltage that has caused more
deaths than any other medium.
Safety can never be stressed enough. There are times when your life literally
depends on it. The following is a listing of common safety precautions that must be
observed at all times:
Use only one hand when turning power switches on or off.
Keep the doors to switch and fuse boxes closed except when working inside or replacing
fuses.
Use a fuse puller to remove cartridge fuses after first making certain that the circuit is
dead.
Ensure that you are qualified and authorised to work on an electrical circuit (LV or HV).
Do not work with energized equipment by yourself; have another person (safety
observer) that is qualified in first aid for electrical shock present at all times.
The person stationed nearby should also know which circuits and switches control the
equipment, and should be given instructions to pull the switch immediately if
anything unforeseen happens.
Always be aware of the nearness of high-voltage lines or circuits. Use rubber gloves
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
8/203
Do not use bare hands to remove hot vacuum tubes from their sockets. Wear protective
gloves or use a tube puller.
Use a shorting stick (discharge rod) to discharge all high-voltage capacitors.
Make certain that the equipment is properly grounded. Ground all isolated and discharged
circuits of the equipment under test to prevent accidental charging.
Turn off the power before connecting alligator clips to any circuit.
When measuring circuits over 440V, do not hold the insulated test probes with bare
hands.
2.1.0 Causes of ElectrocutionUnsafe Acts:
Accidentally slipping with wrenches, screwdrivers, etc., while working on or
near electrical equipment with live parts (over 50 volts)
Switching off the wrong circuit and then failing to verify that the circuit is de-
energized before beginning work.
Failing to implement lock-out/tag-out procedures or use adequate protective
equipment.
Use of noninsulated tools.
Wearing metal jewelry while working on live circuits.
Using instruments/meters/tools not designed for the system voltage.
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
9/203
rated for electrical resistance, eye protection, safety shoes, and long sleeves.
Gloves that are approved for protection from electrical shock are made of rubber.
A separate leather cover protects the rubber from punctures or other damage. Gloves are
rated as providing protection from certain amounts of voltage. Whenever an individual is
going to be working around exposed conductors, the gloves chosen should be rated for at
least as much voltage as the conductors are carrying. Rubber sleeves are used with gloves
to provide additional protection. The combination of sleeves and gloves protects the
hands and arms from electrical shock.
Rubber blankets and floor mats have many uses. Blankets are used to cover
energized conductors while work is going on around them. They might be used to cover
the energized main busses in a breaker panel before you begin working on a deenergized
breaker. Rubber floor mats are used to insulate workers from the ground. If a worker is
standing on a rubber mat and contacts an energized conductor, the current cannot flow
through the body to the ground, so the worker will not get shocked.
2.2.1 Clearances
Adequate clearances are to be maintained between energized and exposed
conductors and personnel. Where DC voltages are involved, clearances specified shall be
used with specified voltages considered as DC line-to-ground values.
If adequate clearances cannot be maintained from exposed live parts of apparatus
in the normal course of free movement within the area during test then access to that area
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
10/203
These distances are listed in Table 1.
Voltage Range Minimum Working and(Phase-to-Phase) Kilovol ts Clear Hot Stick Distance
2.1 to 15 2 ft. 0 in.
15.2 to 35 2 ft. 4 in.
35.1 to 46 2 ft. 6 in.
46.1 to 72.5 3 ft. 0 in.
72.6 to 121 3 ft 4 in.
138 to 145 3 ft. 6 in.
161 to 169 3 ft. 8 in.
230 to 242 5 ft. 0 in.
345 to 362 *7 ft. 0 in.
500 to 552 *11 ft. 0 in.
700 to 765 *15 ft. 0 in.
* For voltages above 345 kV, the minimum working and clear hot stick distances
may be reduced provided that such distances are not less than the shortestdistance between the energized part and a grounded surface.
Table 1. OSHA Working And Hot Stick Distances At Various Voltages
2.3.0 Section 2 Safety of BS 6626: 1985
2.3.1. Responsibility
Electrical equipment should be regarded as being capable of giving rise to danger
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
11/203
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
12/203
Barriers preventing access to enclosures containing live conductors should
normally be kept locked.
Where one person isolates and another does the work, the person responsible for
isolating should demonstrate effectively to the other that the equipment is in fact dead
and safe and that there are adequate safeguards to prevent re energization.
Adequate quantities of suitable locks, cautionary notices and temporary barriers
should be available for use to facilitate safe working and to prevent conductors from
being accidentally electrically charged when persons are working thereon and also to
warn of the presence of any live conductors. Such notices should be clearly legible and
prominently displayed, made from durable; material and kept up-to date. Suitable
precautions should be taken to identify circuits and equipment at the front and back of
switchboards where such identification does not already exist. .
Any disconnectors used for isolation should be locked to prevent movement to the
ON position. Any shutters giving access to live conductors should also be padlocked in
the closed position.
Equipment enclosures frequently contain, circuits having sources of supply
different from that of the main circuit, such as interlocks, alarms, heating and lighting
circuits, etc., and these circuits are not always isolated when the main circuit is
disconnected. Conductors and terminals associated with these circuits should be shrouded
where necessary to prevent accidental contact and identified with warning notices
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
13/203
associated with the equipment or the work to be performed should be housed in proper
receptacles provided for the purpose, and kept in proper condition.
Adequate lighting either fixed portable, or a combination of both should be
provided as necessary to ensure safe access and working.Portable electrical tools and inspection lamps should preferably be operated from
a system with a voltage no greater than 110 V with either the star point of a three phase
or the mid-point of a single-phase transformer low voltage winding earthed. If mains
voltage portable tools need to be used, they should be of all-insulated or double insulated
construction and the use of a residual current device is recommended. All portable
electrical equipment should be regularly inspected and tested.
NOTE. Further advice on the safe use of portable tools is contained in HMG
publication guidance note PM 32 available from HM Stationery Office.
The ingress of moisture, dirt, vermin etc. into electrical equipment can cause
malfunction and danger. Care should be taken to prevent such ingress whilst work is in
progress, and covers should be replaced as soon as access to the chamber is no longerrequired. Before final closure of any compartment is effected, a careful inspection should
be carried out to make sure no foreign matter or loose material is present.
Before work is undertaken in any chamber containing high voltage conductors,
tests using suitable voltage indicators should be carried out. These should include tests
between .each phase and earth to ensure all conductors are dead. Voltage indicators
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
14/203
also include instructions for preventing automatic operation when persons are working
within the protected area. The prevention and restoration of automatic operation should
be subject to appropriate safety procedures, for example by including a reference on the
relevant permits to work. The type of fire extinguishers provided for use on or nearelectrical equipment should be compatible with the equipment and safe to use. Further
advice on fire prevention and fire fighting may be obtained from the local Fire Prevention
Officer.
2.3.6 Testing
2.3.6.1 General
Care should be taken when applying test voltages to ensure that they are the
lowest value required for the purpose with the minimum current output. Where
equipment is capable of storing a charge this should be safely discharged after every test.
NOTE 1: Further advice on electrical testing is available: one publication is
Health and Safety Series Booklet No. HSG (13) 'Electrical testing' available from HM
Stationery Office.
NOTE 2: Electrical equipment may be damaged by the application of test voltages
and currents of incorrect value and polarity. Some electronic equipment is particularly
vulnerable (see clause 40).
2.3.6.2 Use of test instruments (oscilloscopes, etc.)
Instruments should be of a type suitable for the measurements that are to be made
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
15/203
3.0.0 Mult imeterA multimeter measures electrical properties such as AC or DC voltage, current,
and resistance. Rather than have separate meters, a multimeter combines a voltmeter, an
ammeter, and an ohmmeter. Electricians and the general public might use a multimeter
on batteries, components, switches, power sources, and motors to diagnose electrical
malfunctions and narrow down their cause.
It is a black box of electronic circuitry that allows to troubleshoot just about any
type of electrical wiring or device. Simply dial the proper function and scale, touch the
two test leads to the wiring or device in question and check the meter reading. Depending
on the setting, the multimeter will give indication to suggest a broken connection, no
power, poor connections, faulty parts and more.
The two main kinds of a multimeter are analog and digital. A digital multimeter
has an LCD screen that gives a straight forward decimal read out, while an analog display
moves a pointer through a scale of numbers and must be interpreted. Any multimeter will
work over a specific range for each measurement. Select one that is compatible with what
is required, from low-voltage power sources to high-voltage car batteries. Multimeters
are specified with a sensitivity range, so make sure to choose the appropriate one.
Multimeters are handheld devices. Analog multimeters are very cheap but
sometimes difficult to read accurately, especially on resistance scales. Digital output
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
16/203
3.1.0 Analog Mult imeter
The permanent magnet moving coil analogue multimeters are based on the
galvanometer invented by Arsene dArsonval. This device possesses a stationary
permanent magnet, a moving coil, a spring, and a pointer attached to the coil. Figure
below illustrates the way the equipment works. When a current flows through the coil,
there is an induced force on it due to the created electromagnetic field, and the coil
rotates around its central axis until the induced torque is equal and opposite to the spring
torque. The rotation torque, and consequently the angle the pointer rotates is proportional
to the current. The rotation angle is measured on a calibrated scale, and the amount of
current flowing through the meter can be measured. The dArsonval movement is used
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
17/203
3.2.0 Digi tal Mult imeter
Figure shows a block diagram of an electronic digital multimeter.
Note that the block diagram divides the instrument into three major sections: the
SIGNAL CONDITIONING section, the ANALOG-TO- DIGITAL CONVERTER
section, and the DISPLAY section.
The signal conditioning section provides a dc analog voltage, characteristic of the
applied input, to the analog-to-digital converter section. This task is accomplished by the
input voltage divider, current shunts, ac converter, active filter, and associated switching.
The analog-to-digital (a/d) converter section changes the dc output voltage from the
signal conditioning section to digital information. The a/d converter uses a voltage-to-
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
18/203
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
19/203
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
20/203
3.2.1 Voltage Measurements
Plug the black test lead into the COM jack.
Plug the red test lead into the V jack.
Set the function/range switch to either DC volts in the upper left, or AC volts
in the upper right.
If you do not know the approximate voltage about to be measured, use the
largest voltage range available.
Connect the free ends of the red and black test leads ACROSS the device to
the measured. Voltage is always measured with the meter in PARALLEL with
the device
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
21/203
3.2.2 Current Measurements
Turn the power off to the device and discharge any capacitors.
Plug the black test lead into the COM jack.
Plug the red test lead into either the 200 mA jack for small current
measurements, or the 10 A jack for large current measurements.
If you do not know the approximate current about to be measured, use the 10 A
jack.
Set the function/range switch to either DC amperes in the lower right, or AC
amperes in the middle right.
Break open the circuit at the point where you want to measure the current by
removing one of the wires.
Connect the free end of the red test lead to one place at which the wire was
attached.
Connect the free end of the black test lead to the other place at which the wire
was attached.
Current is always measured with the meter in SERIES with the device.
Using the current meter incorrectly will blow the fuse or damage the meter
Reapply the power to the device.
If the LCD displays either "1." or "-1." with all other digits blank, the current is
beyond the selected range. Use the switch to select a larger range.
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
22/203
Once you know the approximate resistance of the device, and then use the
switch to select the lowest range that will still accommodate the resistance of
the device.
Important note: The most common mistake when using a multimeter is not
switching the test leads when switching between current sensing and any other
type of sensing (voltage, resistance). It is critical that the test leads be in the
proper jacks for the measurement you are making.
3.3.0 Digital vs. Analog Multimeters
Digital multimeters have LCD readouts, do audible continuity testing. Some
digital multimeters also feature auto-ranging and overload protection and other
advantages analog multimeters lack.
Analog multimeters have multiple scales on the dial , a moving needle and many
manual settings on the function switch. It is a tricky spotting the correct scale to read on
the dial, and sometimes have to multiply the reading by 10 or 100 to get your final value
3.4.0 Safety Precautions
Be sure the test leads and rotary switch are in the correct position for the desired
measurement.
Never use the meter if the meter or the test leads look damaged.
Never measure resistance in a circuit when power is applied.
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
23/203
4.0.0 Insulation resistance tester (Megohmmeter)The Insulation resistance tester (IRT) also known as a megohmmeter, is a portable
instrument used to measure insulation resistance. It is a lightweight, simple and in
minutes can help to determine the damaged installation. Checking the integrity of
insulation is not only a good idea for a new installation, its a tremendous tool in ongoing
maintenance, allowing to spot a problem wiring/equipment, before it creates arcing and
damages the equipment or shuts everything down.
The principle of operation of IRTs is as basic as Ohms Law: V=IR or R=V/I. The
tester generates a known dc voltage (250 V, 500 V, 1k V or higher), chosen by the user,and measures the leakage current from the conductor through the insulation. The
resistance is then calculated. The better the insulation, the lower the leakage current and
the higher the amount of resistance present.
For example, if 500 V is applied and 0.5 mA measured, then R=1 M. If only one
hundredth of that current, 5 A, is measured, then R=100 M
The newest generation of IRTs is microprocessor-based and battery-powered.
They are more precise than the older hand-cranked analog testers.
4.1.0 Analog Megohmmeter
It consists of a hand-driven DC generator and a direct reading ohm meter. A
simplified circuit diagram of this instrument is shown in Figure below
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
24/203
will tend to set itself at right angles to the field of the permanent magnet. With the test
terminals open, giving an infinite resistance, no current flows in Coil A. Thereby, Coil B
will govern the motion of the rotating element, causing it to move to the extreme counter-
clockwise position, which is marked as infinite resistance.Coil A is wound in a manner to produce a clockwise torque on the moving
element. With the terminals marked "line" and "earth" shorted, giving a zero resistance,
the current flow through the Coil A is sufficient to produce enough torque to overcome
the torque of Coil B. The pointer then moves to the extreme clockwise position, which is
marked as zero resistance. Resistance (R1) will protect Coil A from excessive current
flow in this condition.
When an unknown resistance is connected across the test terminals, line and earth,
the opposing torques of Coils A and B balance each other so that the instrument pointer
comes to rest at some point on the scale. The scale is calibrated such that the pointer
directly indicates the value of resistance being measured.
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
25/203
Some of the common features are:
Lightweight. Tough and robust
Shrouded safety terminals with right angled test lead connector.
Hands-free operation
Voltage ranges of 250, 500, and 1000 V.
Resistance measurement range of 200 G
Combined insulation & Continuity tester
Default Voltmeter
B di i
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
26/203
4.3.0 Insulation resistance test
Insulation resistance tests give an indication of the condition of insulation,
particularly with regard to moisture and dirt. The actual value of the resistance varies
greatly in different types of machines, depending on the type, size, voltage rating, etc.
The principal worth of such measurements, therefore, is in the relative values of
insulation resistance of the same apparatus taken under similar conditions at various
times. Such tests usually reveal how well the machine has been maintained.
Measuring insulation resistance is rather straightforward. Identify any two points
between which there is insulation and make a connection with a megohmmeter. Take a
measurement; the measured value represents the equivalent resistance of all the insulation
that exists between the two points and any component resistance that might also be
connected between the two points.
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
27/203
but much more quickly. It is this current which in most cases determines how long it
takes to make an accurate megohm measurement. When the reading appears to stabilize,
it means that the charging current has decayed to a point where it is negligible with
respect to the leakage current.
The current that flows through the insulation is the leakage current. The voltage
across the insulation divided by the leakage current through it equals the insulation
resistance. Thus, to accurately measure insulation resistance, we must wait until the
dielectric absorption current and the charging current have decayed to the point where
they are truly negligible with respect to the leakage current.
The total current that flows is the sum of the three components just mentioned. It
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
28/203
Polarization index = resistance after 10 minutes resistance after one minute
The recommended minimum value of polarization index for AC and DC motors and
generators is 2.0. Machines having windings with a lower index are less likely to be
suited for operation.
The polarization index is useful in evaluating windings for:
Buildup of dirt or moisture
Gradual deterioration of the insulation (by comparing results of tests made
earlier on the same machine)
Fitness for overpotential tests
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
29/203
4.3.4 Insulation Contamination
In order to obtain reliable test figures, windings should be free of dirt and
moisture as both of these contaminants result in a lower value of resistance being
indicated. If a machine has recently been taken out of service, it is likely to be hot and
therefore free from moisture.
However, the windings may be quite dirty from dust and oil in the atmosphere.
Conversely, if the machine has been out of service for some time, the winding insulation
may well have absorbed a certain amount of moisture. Indeed, if the insulation resistance
is indicated as low, it may be necessary to dry out the windings. All of these items must
be taken into consideration when assessing the reliability of insulation resistance readings
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
30/203
4.4.2 Step voltage test
Various test voltage in steps of (in increasing order), usually for the same period
of time (60 Secs). The insulation values are recorded on the graph. The insulation is
exposed to increased electrical stress that can reveal information about flaws in the
insulation such as pinholes, physical damage or brittleness.
4.4.3 Time resis tance test
This test is carried out to compare the absorption characteristic of contaminated
insulation with the absorption characteristic of good insulation. The test voltage is
applied for the 10 mins and after every 10 secs the data is recorded for first one minute
and then after every one minute. The interpretation of the slope of the plotted graph
determines the condition of the insulation.
The polarisation index is another test in this category for determining the quality
of insulation. This is discussed in earlier part of this chapter.
4.5.0 Safety Precautions
Be sure the test leads and rotary switch are in the correct position for the desired
measurement.
Never use the meter if the meter or the test leads look damaged.
Never measure insulation resistance in a energised circuit.
Make sure that the systems under test have been completely discharged to
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
31/203
4.6.0 Insulation resistance (IR) test on Cables
Prior to testing required permits must be secured. All safety precautions should be
observed while testing. Cable must be discharged and disconnected form the equipment
in the field.
IR should be measured as illustrated in the figure below:
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
32/203
4.7.0 Insulation resistance (IR) test on Transformer
Prior to testing required permits must be secured. All safety precautions should be
observed while testing.
4.8.0 Insulation resistance (IR) test on Motor/Generator
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
33/203
Measuring insulation resistance is rather straightforward. Identify any two points
between which there is insulation and make a connection with a the test instrument is
often referred to as a Megger, after the manufacturers trademark. Take a measurement;
the measured value represents the equivalent resistance of all the insulation that exists
between the two points and any component resistance that might also be connected
between the two points.Megger s are available in several varieties. Some are powered by
a hand-cranked generator, while others are battery powered. Most common is 500V
output, with some going as high as 10,000V. The power supply, in all cases, is DC.
1kV
500V
250V
100V
50V
OFF
V
k
TEST
M
ZERO
AVO
MEGGERXXXX
IR measurement on Cage type Induction motor
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
34/203
5.0.0 Clamp on meterA clamp meter (clamp-on ammeter) is a type of ammeter which measures
electrical current without the need to disconnect the wiring through which the current is
flowing.
Clamp meters are also known as tong testers or Amprobes (after Amprobe
Instrument Company, one of the first vendors of such devices).
The most common forms of clamp meter are:
A probe for use with a multimeter.
A self-contained unit.
A built-in part of a specialised multimeter used by electricians.
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
35/203
other direction.
Only one (1) conductor can be measured at a time, and the cable can either be
bare or insulated. The current in the conductor to be measured is (carefully) segregated
from other current-carrying conductors, and shifted enough so that the jaws of the clamp-
on ammeter can be opened, slipped around the cable, and then closed. As soon as the
jaws close, a clear and accurate reading is registered on the scale. The jaws are insulated,
and the Bakelite handle and shield protect the technician from shock.
5.1.0 Theory of operation of AC Clamp on meter
The meter is operated by the magnetic field set up by the current. Basic
construction of the meter is a clamp on current probes and the ammeter (Analog or
digital) connected to it.
The clamp on current probe works on the principle of current transformer. The
d i h i il f f
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
36/203
5.2.0 Theory of operation of AC/DC Clamp on meter
More modern designs of clamp-on ammeters utilize a small magnetic field
detector device called a Hall-effect sensor to accurately determine field strength. The two
matched sensors provide an output signal which is independent of the location of the
current conductor in the clamp opening. The conductor does not have to be exactly at the
center of the opening. A battery-operated circuit is required to provide the excitation and
amplification of the signal generated by the HALL-EFFECT sensor
Hall effect principle : AC/DC current sensing is achieved by measuring thestrength of the magnetic field created by a current carrying conductor in a semiconductor
chip using Hall effect principle. When a thin semiconductor is placed at right angle to a
magnetic field (B), and a current (Id) is applied to it, a voltage (Vh) is developed across
the semiconductor. This voltage is known as the Hall voltage, named after the US
scientist Edwin Hall
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
37/203
Some clamp-on meters contain electronic amplifier circuitry to generate a small
voltage proportional to the current in the wire between the jaws, that small voltage
connected to a voltmeter for convenient readout by a technician. Thus, a clamp-on unit
can be an accessory device to a voltmeter, for current measurement.
5.3.0 Specifications of Digital Clamp on meters
AC Current: It is the measuring value of the alternating current taken by
the load of a clamp on meter
AC Voltage : It is defined as the alternating voltage measured by the
clamp on meter.
DC Current : It is the measuring value of the direct current read by the
clamp on meter
DC Voltage: It is defined as the direct voltage measured by the clamp on
meter
Resistance : It is the resistance offered by the clamp on meter to the
current flow
Frequency range : It is the range of frequency at which the current or
voltage is measured.
Distortion factor: It is defined as a measure of non linear distortion.
Total harmonic distortion : It is defined as the ratio of the sum of the
f ll h i f i b h f d l f
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
38/203
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
39/203
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
40/203
5.8.0 Safety Precautions
To avoid possible electric shock or personal injury, and to avoid possible damage
to the Meter or the equipment under test, adhere to the following practices:
Avoid working alone as far as possible, and render the assisstance.
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
41/203
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
42/203
6.0.0 Earth tester, Loop tester & Residual Current Device(RCD) tester
A practical earth electrode that provides a low ground resistance is not always
easy to obtain. The metallic body in the earth is often referred to as an electrode even
though it may be a water-pipe system, buried strips or plates, or wires. Such
combinations of metallic bodies are called a grid. The earth resistance is the resistance to
current from the electrode into the surrounding earth.
To appreciate why earth resistance must be low, you need only use Ohms Law: E
= R x I where E is volts; R, the resistance in ohms; and I, the current in amperes. Assume
that you have a 4000-V supply (2300 V to ground) with a resistance of 13 (see Fig.
below). Now, assume that an exposed wire in this system touches a motor frame that is
connected to a grounding system which has a 10-ohm resistance to earth.
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
43/203
installation is of insufficient level and the protection device would thus take too long to
activate. The delay can be disastrous for life and property. It is therefore necessary to
know if the impedance of the path that any fault current would take is low enough to
allow sufficient current to flow in the event of a fault and that any installed protective
device will operate within a safe time limit. The earth loop impedance of each individual
circuit a path from the point of use back to the incoming supply connection point. As
measurement of circuit loop impedance is made with the supply normally on, precautions
must be taken to avoid the possibility of electric shock and danger to personnel working
in the vicinity of the circuit under test.
In IEC 60364, fault loop testing falls under the category of Verifying protection
by automatic supply disconnection. This covers verification of the effectiveness of
protective measures (such as test on RCD), and the test methods applied to measure the
fault loop impedance.
Conventional techniques for measuring loop impedance can often trip RCDs,
preventing further measurement. Often the only way around this is to bridge the RCD
or replace the RCD with an equivalent rated MCB for the duration of the test both of
which are potentially dangerous and time consuming practices. To overcome this
manufacturers of earth loop tester have applied innovative technology to ensure that both
electromechanical and electronic type RCDs do not trip during earth loop impedance
measurements.
d h h h b l h b k i ff i f h h l d
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
44/203
rusted through, the part below the break is not effective as a part of the earth electrode.
Resistance of Surrounding Earth: An electrode driven into earth of uniform
resistivity radiates current in all directions. Think of the electrode as being surrounded by
shells of earth, all of equal thickness. The earth shell nearest the electrode naturally has
the smallest surface area and so offers the greatest resistance. The next earth shell is
somewhat larger in area and offers less resistance. Finally, a distance from the electrode
will be reached where inclusion of additional earth shells does not add significantly to the
resistance of the earth surrounding the electrode. It is this critical volume of soil that
determines the effectiveness of the ground electrode and which therefore must be
effectively measured in order to make this determination. Ground testing is distinct when
compared to more familiar forms of electrical measurement, in that it is a volumetric
id ti
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
45/203
consideration.
Because the formulas are complicated, and earth resistivity is neither uniform or
constant, a simple and direct method of measuring earth resistance is needed. This is
where Earth Resistance Tester, a self-contained portable instrument is used. This test
instrument is reliable and easy to use. With it, one can check the resistance of the earth
electrode while it is being installed; and, by periodic tests, observe any changes with
time.
To understand the principle of earth testing, consider the schematic diagram in
Fig. below. As explained earlier with the earth shell diagram, with increased distance
from an electrode, the earth shells are of greater surface area and therefore of lower
resistance. Now, assume that there are three rods driven into the earth some distance apart
and a voltage applied, as shown in Fig. The current between rods 1 and 2 is measured by
an ammeter; the potential difference (voltage) between rods 1 and 3 is measured by a
voltmeter.
Th i f i t l b l tt d i t di t t bt i
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
46/203
The series of resistance values can be plotted against distance to obtain a curve as
shown in Fig. below. Note that as rod 3 is moved away from rod 1, the resistance values
increase, but the amount of increase gets less and less until a point is reached where the
rate of increase becomes so small that I can almost be considered constant (20 in Fig.).
The earth shells between the two rods (1 and 3) have so great a surface area that they add
little to the total resistance. Beyond this point, as rod 3 approaches the earth shells of rod
2, resistance gradually picks up. Near rod 2, the values rise sharply.
Now, lets say that rod 1 is the earth electrode under test. From a typical earth-
resistance curve, such as Fig. above, what is the resistance to earth of this rod? We call
rod 2 current-reference probe C and rod 3, potential reference probe P (simply forconvenience in identification). The correct resistance is usually obtained if P (rod 3) is
placed at a distance from the center of the earth electrode (rod 1) about 62 percent of the
distance between the earth electrode and C (rod 2). Finally, rod C should be far enough
away from the earth electrode system so that the 62 percent distance is out of the sphere
of influence of the earth electrode.
For the test, the electrode should be isolated from the electrical system that it is
protecting; otherwise, the whole system is tested which (depending on local practices)
may include the pole ground, system neutral, and transformer ground. This obscures the
specific effect of the local ground.
X to the earth electrode it may be better to use all four terminals by a lead from the P1
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
47/203
X to the earth electrode. it may be better to use all four terminals by a lead from the P1
terminal to the test electrode (connecting it inside the lead from C1). This is a true four
wire test configuration which eliminates all lead resistance from the measurement.
The driven reference rod C should be placed as far from the earth electrode as
practical; this distance may be limited by the length of extension wire available, or the
geography of the surroundings. Leads should be separated and not run close and parallel
to each other, to eliminate mutual inductance.
Potential-reference rod P is then driven at mid point on a straight line between the
earth electrode (X) and C. The subsequent two readings are taken moving the rod P closer
to the earth electrode, say 1 meter and away from the earth electrode by same distance (1
meter). Resistance readings are logged for each of the points and average of the readings
are taken, if the three readings do not differ from each other (within 5%) by large margin.
the earth return path back to the supply transformer and its winding; the phase conductor
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
48/203
the earth return path back to the supply transformer and its winding; the phase conductor
back to the point of the fault.
6.5.0 Earth Loop resistance test
An earth fault loop test on an installation is performed by switching a known lowvalue of resistance between the phase and earth conductors at the desired point test and
measuring the voltage drop across the resistance. In effect this is simulating a fault
between phase and earth and calculation made around the supply voltage and voltage
drop across the test resistor enable the earth fault loop impedance to be indicated.
The same tester may also be used for the determination of prospective earth fault
current, which is the maximum current able to flow in a phase-earth fault in an
installation, and they may also be used to indicate the prospective short circuit current
which is the maximum current able to flow in the event of a phase-neutral fault.
The earth loop testers available in the market, offer both traditional measuring
techniques and state of the art "non-RCD Tripping" technology.
6.6.0 Digital Earth Loop resistance tester from Megger (L T5 and L T6)
The MEGGER@ L T5 and L T6 Digital Loop Testers have been designed for
quickly, accurately and reliably testing newly established and existing wiring
installations. They are simple to use, both with the standard lead for socket tests and with
the optional safety leads for performing tests on lighting installations and testing earth
V a c 10% and automatically compensate for supply variations The test current up to
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
49/203
V a.c. 10% and automatically compensate for supply variations. The test current, up to
25 A, is dependent on the impedance of the phase-earth loop being measured and flows
for two half cycles of the supply voltage. The circuit is fuse protected and fitted with an
internal thermal switch to prevent excessive heating caused by tests repeated too
frequently.
Testing is very simple as there is no initial setting up to be done and no
pushbutton to operate. A test is automatically executed in about 4 seconds after the
selector switch is set to a measuring range and connection made to the circuit under test.
(Either step may be performed first.) Neons illuminate to show that there are no open
circuits in the installation wiring and that a correct phase conductor connection exists. If
the earth connection is not present, the test will not be performed.
Use of a large, 3 digit L.C.D. makes measurement readings easy with less
chance of ambiguity. It also results in a much more rugged and robust test instrument
that, because of its strong plastic case, will withstand the rough treatment expected of an
installation engineer's tool.
The lightweight, hand-held tester also incorporates a fold-away support
stand/suspension hook for use when the operator requires both hands for using the "flying
leads".
6.7.0 Applications & Use of Earth Loop resistance tester
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
50/203
6.8.0 Residual Current devices (RCDs)
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
51/203
6.8.0 Residual Current devices (RCDs)
Increasingly in modern installations, earth leakage circuit breakers are used to
provide protection in additional to conventional fuses and circuit breakers. These devices
are referred to by a variety of different names including RCD (Residual Current Device),
RCCB (Residual Current Circuit Breaker), ELCH (Earth Leakage Circuit Breaker) and
GFI (Ground Fault Interrupt), to name but a few.
The devices operate by sensing when the current in the phase and neutral
conductors within an installation are not equal and opposite. Any imbalance would imply
that an additional path existed for the flow of current, invariably through the earth due to
excessive leakage and/or a fault situation.
pressed even though a real ground fault may not cause it to trip.
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
52/203
p g g y p
RCD testers are designed to simulate a range of fault currents, with restrictions on
the duration of the fault current, and to time the operation of the device. This will indicate
the ability of the RCD to interrupt a particular fault current within time certain limits to
ensure protection against fire, damage and electrocution.
6.10.0 Digi tal RCD tester from Megger (CBT3 and CBT4)
The CBT3 and CBT4 are hand-held instruments for testing residual current
protective devices (RCDs) in wiring installations. The instruments are connected through
a normal mains socket outlet or directly via the RCDs terminals. Neon lamp indicate if
there are no open circuits in the installation and if the phase connections are correct.
A rotary switch selects the RCD rating from one of six values available and a
Membrane push-buttons are used to select the type of test. The 'ABC' key selects
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
53/203
p yp y
type of breaker to be tested. The phase key selects the point on the a.c. waveform from
where the test will start, i.e. the positive or negative zero crossing point. The 'I' key, will
allow one of three current multipliers or a 150 mA specific test to be selected. The test
key will initiate a test.
The 4 digit LCD shows the time value that the RCD takes to trip. For a successful
'no trip' test the maximum time of test current flow is given. For unsuccessful tests on 'B'
and 'C' type devices the display shows the word 'FAIL' as the test result.
The instrument circuit is microprocessor controlled and will always assume the
default setting when switched on or when the rotary switch is moved out of the stand-byposition. The maximum current that can flow is 500 mA. The instrument has a thermal
cut out to prevent overheating caused by rapidly repeated tests at high current. Also, it is
hardware and software protected against hazardous live voltages. If in the event prior to a
test the earth neutral potential is greater than 50 V,' or a test current causes earth potential
to rise greater than 50 V above neutral, the instrument will then turn the test current off
within 40 ms and show >50 V on the display. The rotary switch has a 'Standby' position
which, when selected (with the instrument connected to the supply), renders the LCD
blank but the microprocessor in the reset state.
6.11.0 Safety Precautions
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
54/203
y
There is an inherent safety problem in earth resistance testing that requires care
and planning by the user of the earth resistance test set.
The possibility exists that a fault in the power system will cause a high current to
flow into the ground system while the test is in progress. This may cause unexpected high
voltages to appear at the current and voltage probes and also at the terminals of the test
set.
This risk must be evaluated by the person responsible for the tests, taking into
account the fault current available and expected step-and-touch potentials. IEEE Standard
80 entitled IEEE Guide for Safety in AC Substation Grounding fully covers thissubject. It is recommended that the operator should wear rubber protective gloves while
handling connections and use a rubber safety mat while operating the earth resistance test
set.
Following safety precautions must be taken before and while performing the earth
loop impedance test or testing RCD.
Safety Warnings and Precautions recommended by manufacturer must be
read and understood before the instrument is used. They must be observed
during use.
Continuity of protective conductors and earthed equipotential bonding of
new or modified installations must be verified before carrying out RCD
7.0.0 Attachments
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
55/203
7.1.1 Fluke multimeter manual
7.12 Megger Manual BM80
7.13 Fluke Clamp on meter Instruction sheet
7.14 Megger Digital Earth Tester
7.15 Megger Digi tal Loop Tester
7.16 Megger RCD Tester
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
56/203
80 Series IIIMultimeters
Users Manual
October 1997 Rev.4, 6/021997-2002 Fluke Corporation, All rights reserved. Printed in U.S.A.
All product names are trademarks of their respective companies.
Lifetime Limited Warranty
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
57/203
y
Each Fluke 20, 70, 80, 170 and 180 Series DMM will be free from defects in material and workmanship for its lifetime. As used herein,
lifetime is defined as seven years after Fluke discontinues manufacturing the product, but the warranty period shall be at least ten years from
the date of purchase. This warranty does not cover fuses, disposable batteries, damage from neglect, misuse, contamination, alteration,
accident or abnormal conditions of operation or handling, including failures caused by use outside of the products specifications, or normal
wear and tear of mechanical components. This warranty covers the original purchaser only and is not transferable.
For ten years from the date of purchase, this warranty also covers the LCD. Thereafter, for the lifetime of the DMM, Fluke will replace theLCD for a fee based on then current component acquisition costs.
To establish original ownership and prove date of purchase, please complete and return the registration card accompanying the product, or
register your product onhttp://www.fluke.com.Fluke will, at its option, repair at no charge, replace or refund the purchase price of a
defective product purchased through a Fluke authorized sales outlet and at the applicable international price. Fluke reserves the right to
charge for importation costs of repair/replacement parts if the product purchased in one country is sent for repair elsewhere.
If the product is defective, contact your nearest Fluke authorized service center to obtain return authorization information, then send the
product to that service center, with a description of the difficulty, postage and insurance prepaid (FOB Destination). Fluke assumes no risk
for damage in transit. Fluke will pay return transportation for product repaired or replaced in-warranty. Before making any non-warranty
repair, Fluke will estimate cost and obtain authorization, then invoice you for repair and return transportation.
THIS WARRANTY IS YOUR ONLY REMEDY. NO OTHER WARRANTIES, SUCH AS FITNESS FOR A PARTICULAR PURPOSE, ARE
EXPRESSED OR IMPLIED. FLUKE SHALL NOT BE LIABLE FOR ANY SPECIAL, INDIRECT, INCIDENTAL OR CONSEQUENTIAL
DAMAGES OR LOSSES, INCLUDING LOSS OF DATA, ARISING FROM ANY CAUSE OR THEORY. AUTHORIZED RESELLERS ARE
NOT AUTHORIZED TO EXTEND ANY DIFFERENT WARRANTY ON FLUKES BEHALF. Since some states do not allow the exclusion or
limitation of an implied warranty or of incidental or consequential damages, this limitation of liability may not apply to you. If any provision of
this warranty is held invalid or unenforceable by a court or other decision-maker of competent jurisdiction, such holding will not affect the
validity or enforceability of any other provision.
Fluke Corporation Fluke Europe B.V.
P.O. Box 9090 P.O. Box 1186Everett WA 5602 B.D. Eindhoven
2/02 98206-9090 The Netherlands
http://www.fluke.com/http://www.fluke.com/http://www.fluke.com/ -
8/10/2019 Module No E03 Electrical Test Equipment Basic
58/203
i
Table of Contents
Title Page
Introduction.................................................................................................................... 1
Safety Information ...................................... ............................................. ...................... 1
Your Meters Features ............................................. ............................................. ......... 4
Power-Up Options .......................................... ............................................. ............. 11
Automatic Power-Off................................................................................................. 11
Input Alert Feature ............................................ ............................................. ....... 12
Making Measurements ........................................ ............................................. ............. 12
Measuring AC and DC Voltage................................................................................. 12
Testing for Continuity................................................................................................ 14
Measuring Resistance ............................................ ............................................. ..... 16
Using Conductance for High Resistance or Leakage Tests ..................................... 18
Measuring Capacitance............................................................................................ 18
Testing Diodes.......................................................................................................... 21
Measuring AC or DC Current.................................................................................... 22Measuring Frequency............................................................................................... 25
Measuring Duty Cycle............................................................................................... 27
Determining Pulse Width ........................................... ............................................. .. 28
80 Series IIIUsers Manual
A l B G h 28
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
59/203
ii
Analog Bar Graph ......................................... ............................................. .................... 28
Model 87 Bar Graph.................................................................................................. 28
Models 83 and 85 Bar Graph.... ............................................. ................................... 29
4-1/2 Digit Mode (Model 87) .......................................................................................... 29
MIN MAX Recording Mode ............................................ ............................................. ... 30
Touch Hold
Mode....................................................................................................... 32Relative Mode................................................................................................................ 32
Zoom Mode (Models 83 and 85)....................................... ........................................ 32
Uses for the Zoom Mode (Models 83 and 85)........................................................... 33
Maintenance ........................................... ............................................. .......................... 33
General Maintenance................................................................................................ 33
Testing the Fuses...................................................................................................... 34
Replacing the Battery................................................................................................ 35
Replacing the Fuses ............................................ ............................................. ........ 35
Service and Parts........................................................................................................... 36
Specifications................................................................................................................. 41
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
60/203
iii
List of Tables
Table Title Page
1. International Electrical Symbols ......................................................................................... 2
2. Inputs ................................................................................................................................. 4
3. Rotary Switch Positions ..................................................................................................... 5
4. Pushbuttons ....................................................................................................................... 6
5. Display Features ................................................................................................................ 9
6. Estimating Capacitance Values Over 5 Microfarads.......................................................... 20
7. Functions and Trigger Levels for Frequency Measurements............................................. 268. MIN MAX Functions ........................................................................................................... 31
9. Replacement Parts............................................................................................................. 38
10. Accessories........................................................................................................................ 40
11. Models 85 and 87 AC Voltage Function Specifications...................................................... 42
12. Model 83 AC Voltage Function Specifications ................................................................... 43
13. DC Voltage, Resistance, and Conductance Function Specifications ................................. 44
14. Current Function Specifications ......................................................................................... 45
15. Capacitance and Diode Function Specifications................................................................ 47
16. Frequency Counter Specifications ..................................................................................... 47
17. Frequency Counter Sensitivity and Trigger Levels............................................................. 4818. Electrical Characteristics of the Terminals ......................................................................... 49
19. MIN MAX Recording Specifications ................................................................................... 50
80 Series IIIUsers Manual
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
61/203
iv
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
62/203
v
List of Figures
Figure Title Page
1. Display Features (Model 87 Shown).......................................................... 82. Measuring AC and DC Voltage.................................................................. 133. Testing for Continuity................................................................................. 154. Measuring Resistance ............................................................................... 17
5. Measuring Capacitance............................................................................. 196. Testing a Diode ......................................................................................... 217. Measuring Current..................................................................................... 238. Components of Duty Cycle Measurements ............................................... 279. Testing the Current Fuses......................................................................... 3410. Battery and Fuse Replacement ................................................................. 3711. Replaceable Parts ..................................................................................... 39
80 Series IIIUsers Manual
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
63/203
vi
Introduction
Introduction In this manual a Warning identifies conditions and
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
64/203
1
Introduction
Warning
Read "Safety Information" before you use
the meter.
Except where noted, the descriptions and instructions in
this manual apply to Series III Models 83, 85, 87, and
87/E multimeters. Model 87 is shown in all illustrations.
Safety Information
This meter complies with:
EN61010.1:1993
ANSI/ISA S82.01-1994 CAN/CSA C22.2 No. 1010.1-92
1000 V Overvoltage Category III, Pollution Degree 2
600 V Overvoltage Category IV, Pollution Degree 2
UL3111-1
Use the meter only as specified in this manual, otherwise
the protection provided by the meter may be impaired.
In this manual, a Warningidentifies conditions and
actions that pose hazards to the user. A Caution
identifies conditions and actions that may damage the
meter or the equipment under test.
International symbols used on the meter and in this
manual are explained in Table 1.
Warning
To avoid possible electric shock or personal
injury, follow these guidelines:
Do not use the meter if it is damaged.
Before you use the meter, inspect the
case. Look for cracks or missing plastic.
Pay particular attention to the insulationsurrounding the connectors.
Make sure the battery door is closed and
latched before you operate the meter.
Replace the battery as soon as the
battery indicator () appears.
80 Series III
Users Manual
Table 1. International Electrical Symbols
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
65/203
2
Table 1. International Electrical Symbols
AC (Alternating Current) Earth ground
DC (Direct Current) Fuse
AC or DC Conforms to European Union directives
Refer to the manual for information
about this feature.
Conforms to relevant Canadian
Standards Association directives
Battery Double insulated
Inspected and licensed by TV Product Services.
Safety Information
Remove test leads from the meter before Caution
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
66/203
3
Remove test leads from the meter before
you open the battery door.
Inspect the test leads for damaged
insulation or exposed metal. Check the
test leads for continuity. Replace
damaged test leads before you use the
meter.
Do not use the meter if it operates
abnormally. Protection may be impaired.
When in doubt, have the meter serviced.
Do not operate the meter around
explosive gas, vapor, or dust.
Use only a single 9 V battery, properlyinstalled in the meter case, to power the
meter.
When servicing the meter, use only
specified replacement parts.
To avoid possible damage to the meter or to
the equipment under test, follow these
guidelines:
Disconnect circuit power and dischargeall high-voltage capacitors before testing
resistance, continuity, diodes, or
capacitance.
Use the proper terminals, function, and
range for your measurements.
Before measuring current, check the
meters fuses. (See "Testing the Fuses".)
80 Series III
Users Manual
To protect yourself, use the following guidelines: Table 2. Inputs
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
67/203
4
p y g g
Use caution when working with voltages above 30 V
ac rms, 42 V ac peak, or 60 V dc. Such voltages
pose a shock hazard.
When using the probes, keep your fingers behind thefinger guards.
Connect the common test lead before you connect
the live test lead. When you disconnect test leads,
disconnect the live test lead first.
Avoid working alone.
When measuring current, turn off circuit power
before connecting the meter in the circuit. Rememberto place the meter in series with the circuit.
Your Meters Features
Tables 2 through 5 briefly describe your meters features
and give page numbers where you can find more detailed
information about the features.
p
Terminal Description Page
A Input for 0 A to 10.00 Acurrent measurements
22
mA A Input for 0 A to 400 mAcurrent measurements
22
COM Return terminal for allmeasurements
NA
V Input for voltage,continuity, resistance,
diode, capacitance,
frequency, and duty
cycle measurements
V:12
:16
:21:18Frequency: 25
Duty cycle: 27
Your Meters Features
Table 3. Rotary Switch Positions
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
68/203
5
Switch Position Function Page
AC voltage measurement 12
DC voltage measurement 12
mV400 mV dc voltage range 12
Continuity test 14
Resistance measurement 16
Capacitance measurement 18
Diode test 21mAA
DC or AC current measurements from 0 mA to 10.00 A 22
A DC or AC current measurements from 0 A to 4000 A 22
80 Series III
Users Manual
Table 4. Pushbuttons
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
69/203
6
Button Function Button Function Page
(Bluebutton)
mA/A, APower-up
Selects capacitance.
Switches between dc and ac current.Disables automatic power-off feature.
18
2211
Any switchposition
Power-up
Starts recording of minimum and maximum values. Steps the display throughMIN, MAX, AVG (average), and present readings.
Enables high-accuracy 1-second response time for MIN MAX recording.
30
30
Any switchposition
Switches between the ranges available for the selected function. To return toautoranging, hold the button down for 1 second.
Manually selecting a range causes the meter to exit the Touch Hold, MINMAX, and REL (relative) modes.
See ranges inspecifications.
Power-up For servicing purposes only. NA
Any switchposition
MIN MAXrecording
Frequency
counter
Touch Hold captures the present reading on the display. When a new, stablereading is detected, the meter beeps and displays the new reading.
Stops and starts recording without erasing recorded values.
Stops and starts the frequency counter.
32
30
25
Your Meters Features
Table 4. Pushbuttons (cont)
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
70/203
7
Button Function Button Function Page
Model 87:yellow button
Models 83,85: gray
button
Any switchposition
Turns the backlight on and off.
For Model 87, hold the yellow button down for one second to enter the4-1/2 digit mode. To return to the 3-1/2 digit mode, hold the button downonly until all display segments turn on (about one second).
NA
29
Continuity
MIN MAXrecording
Power-up
Turns the continuity beeper on and off.
On Model 87, switches between 250 s and 100 ms or 1 s responsetimes.
Disables the beeper for all functions.
14
30
NA
(Relativemode)
Any switchposition
Power-up
Stores the present reading as a reference for subsequent readings. Thedisplay is zeroed, and the stored reading is subtracted from allsubsequent readings.
For Models 83 and 85, enables zoom mode for the bar graph.
32
32
Any switchposition
Power-up
Starts the frequency counter.
Press again to enter duty cycle mode.
Provides >4000 Minput impedance for the 400 mV dc range.
25
27
NA
80 Series III
Users Manual
6 7 8 9
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
71/203
8
13
6 7 8 9
5
1010
10
1
2
3
4
12
11
iy1f.eps
Figure 1. Display Features (Model 87 Shown)
Your Meters Features
Table 5. Display Features
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
72/203
9
Number Feature Indication Page
Polarity indicator for the analog bar graph. 28
Relative (REL) mode is active. 32
The continuity beeper is on. 14
- Indicates negative readings. In relative mode, this sign indicates that thepresent input is less than the stored reference. 32 The battery is low. Warning: To avoid false readings, which could lead
to possible electric shock or personal injury, replace the battery as soon
as the battery indicator appears.
35
AUTO The meter is in autorange mode and automatically selects the range with thebest resolution.
NA
100 msMAX MIN AVG
Indicators for minimum-maximum recording mode. 30
Touch Hold is active. 32
AC DC Indicator for ac or dc voltage or current. AC voltage and current is displayed asan rms (root mean square) value. 12,22
80 Series III
Users Manual
Table 5. Display Features (continued)
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
73/203
10
Number Feature Indication Page
A, A, mA A: Amperes (amps). The unit of current.A: Microamp. 1 x 10-6or 0.000001 amperes.
mA: Milliamp. 1 x 10-3or 0.001 amperes.
22
V, mV V: Volts. The unit of voltage.mV: Millivolt. 1 x 10-3or 0.001 volts.
12
F, nF F: Farad. The unit of capacitance.F: Microfarad. 1 x 10-6or 0.000001 farads.
nF: Nanofarad. 1 x 10-9 or 0.000000001 farads.
18
nS S: Siemen. The unit of conductance.nS: Nanosiemen. 1 x 10-9 or 0.000000001 siemens.
18
% Percent. Used for duty cycle measurements. 27
, M, k : Ohm. The unit of resistance.M: Megohm. 1 x 106or 1,000,000 ohms.
k: Kilohm. 1 x 103or 1000 ohms.
16
Hz, kHz, MHz Hz: Hertz. The unit of frequency.kHz: Kilohertz. 1 x 103or 1000 hertz.
MHz: Megahertz. 1 x 106or 1,000,000 hertz.
25
Your Meters Features
Table 5. Display Features (continued)
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
74/203
11
Number Feature Indication Page
4000 mV Displays the currently selected range. See specificationsfor ranges for each
function.
Analog bar graph Provides an analog indication of the present inputs. 28
The input (or the relative value when in relative mode) is too largefor the selected range. For duty cycle measurements OL is
displayed when the input signal stays high or low.
Duty cycle: 27
Power-Up Options
Holding a button down while turning the meter onactivates a power-up option. Table 4 includes the power-
up options available. These options are also listed on the
back of the meter.
Automatic Power-Off
The meter automatically turns off if you do not turn therotary switch or press a button for 30 minutes. To disable
automatic power-off, hold down the blue button while
turning the meter on. Automatic power-off is always
disabled in MIN MAX recording mode.
80 Series III
Users Manual
Input Alert Feature Measuring AC and DC Voltage
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
75/203
12
If a test lead is plugged into the mA/Aor Aterminal, but
the rotary switch is not correctly set to the mA/Aor A
position, the beeper warns you by making a chirping
sound. This warning is intended to stop you from
attempting to measure voltage, continuity, resistance,capacitance, or diode values when the leads are plugged
into a current terminal. Placing the probes across (in
parallel with) a powered circuit when a lead is plugged into
a current terminal can damage the circuit you are testing
and blow the meters fuse.This can happen because the
resistance through the meters current terminals is very
low, so the meter acts like a short circuit.
Making MeasurementsThe following sections describe how to take
measurements with your meter.
Voltage is the difference in electrical potential between
two points. The polarity of ac (alternating current) voltage
varies over time, while the polarity of dc (direct current)
voltage is constant over time. The meter presents ac
voltage values as rms (root mean square) readings. Therms value is the equivalent dc voltage that would produce
the same amount of heat in a resistance as the measured
sinewave voltage. Models 85 and 87 feature true rms
readings, which are accurate for other wave forms (with
no dc offset) such as square waves, triangle waves, and
staircase waves.
The meters voltage ranges are 400 mV, 4 V, 40 V, 400 V,
and 1000 V. To select the 400 mV dc range, turn the
rotary switch to mV.
To measure ac or dc voltage, set up and connect the
meter as shown in Figure 2.
Making Measurements
The following are some tips for measuring voltage:
AC Voltage
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
76/203
13
When you measure voltage, the meter acts
approximately like a 10 M(10,000,000 )
impedance in parallel with the circuit. This loading
effect can cause measurement errors in high-
impedance circuits. In most cases, the error isnegligible (0.1% or less) if the circuit impedance is
10 k(10,000 ) or less.
For better accuracy when measuring the dc offset of
an ac voltage, measure the ac voltage first. Note the
ac voltage range, then manually select a dc voltage
range equal to or higher than the ac range. This
procedure improves the accuracy of the dc
measurement by ensuring that the input protection
circuits are not activated.
M IN MAX R AN GE H OLD H
HzREL
mAA
mV
V
V
OFF
!
!
1000V MAX
400mA MAXFUSED
10A MAXFUSED
PEAKMINMAX
A
CAT II
V
87 TRUERMSMULTIMETER
M IN M AX R AN GE H OL DH
HzREL
mAA
mV
V
V
OFF
!
!
A COM VmA A
A COM VmA A
1000V MAX
400mA MAXFUSED
10A MAXFUSED
PEAKMINMAX41/2 DIGITS
1 Second
41/2 DIGITS
1 Second
A
CAT II
Switch Box
V
+
g
DC Voltage
III
87 TRUERMSMULTIMETERIII
iy2f.eps
Figure 2. Measuring AC and DC Voltage
80 Series III
Users Manual
Testing for Continuity The continuity function detects intermittent opens andshorts lasting as little as 1 millisecond (0.001 second).
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
77/203
14
Caution
To avoid possible damage to the meter or to
the equipment under test, disconnect circuit
power and discharge all high-voltagecapacitors before testing for continuity.
Continuity is the presence of a complete path for current
flow. The continuity test features a beeper that sounds if a
circuit is complete. The beeper allows you to perform
quick continuity tests without having to watch the display.
To test for continuity, set up the meter as shown in
Figure 3.
Pressto turn the continuity beeper on or off.
g ( )
These brief contacts cause the meter to emit a short beep.
Making Measurements
For in-circuit tests turn circuit power off
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
78/203
15
M IN M AX R AN GE HO LD H
HzREL
mAA
mV
V
V
OFF
!
!
1000VMAX
400mAMAX
FUSED10AMAX
FUSED
PEAK MIN MAX
A
CATII
Activatescontinuity
beeper
ON(closed)
MI N MAX R ANG E H OL DH
HzREL
mAA
mV
V
V
OFF
!
!
1000VMAX
400mAMAXFUSED
10AMAXFUSED
PEAK MIN MAX4 1/2 DIGITS1 Seconds4 1/2 DIGITS
1 Seconds
A
CATII
OFF(open)
A COM VmA A
For in circuit tests, turn circuit power off.
87 TRUE RMS MULTIMETERIII87 TRUE RMS MULTIMETERIII
iy4f.eps
Figure 3. Testing for Continuity
80 Series III
Users Manual
Measuring Resistance
C ti
The following are some tips for measuring resistance:
Because the meters test current flows through all
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
79/203
16
Caution
To avoid possible damage to the meter or to
the equipment under test, disconnect circuit
power and discharge all high-voltagecapacitors before measuring resistance.
Resistance is an opposition to current flow. The unit of
resistance is the ohm (). The meter measures resistance
by sending a small current through the circuit. Because
this current flows through all possible paths between the
probes, the resistance reading represents the total
resistance of all paths between the probes.
The meters resistance ranges are 400 , 4 k, 40 k,400 k, 4 M, and 40 M.
To measure resistance, set up the meter as shown in
Figure 4.
Because the meters test current flows through all
possible paths between the probe tips, the measured
value of a resistor in a circuit is often different from
the resistors rated value.
The test leads can add 0.1 to 0.2 of error to
resistance measurements. To test the leads, touch
the probe tips together and read the resistance of the
leads. If necessary, you can use the relative (REL)
mode to automatically subtract this value.
The resistance function can produce enough voltage
to forward-bias silicon diode or transistor junctions,
causing them to conduct. To avoid this, do not use
the 40 Mrange for in-circuit resistancemeasurements.
Making Measurements
In-Circuit Resistance Measurements
Isolating a Potentiometer
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
80/203
17
MI N MA X R AN GE HOL DH
HzREL
mAA
mV
V
V
OFF
!
!
A COM VmA A
1000VMAX
400mAMAX
FUSED10AMAX
FUSED
PEAK MIN MAX
A
CAT II
Circuit Power
OFF
Disconnect
1 2
3
1 3 2
Disconnect
Isolating a Resistor4 1/2 DIGITS
1 Seconds
87 TRUE RMS MULTIMETERIII
iy6f.eps
Figure 4. Measuring Resistance
80 Series III
Users Manual
Using Conductance for High Resistance orLeakage Tests
The following are some tips for measuring conductance:
High-resistance readings are susceptible to electrical
-
8/10/2019 Module No E03 Electrical Test Equipment Basic
81/203
18
Conductance, the inverse of resistance, is the ability of a
circuit to pass current. High values of conductance
correspond to low values of resistance.
The unit of conductance is the Siemen (S). The meters
40 nS range measures conductance in nanosiemens
(1 nS = 0.000000001 Siemens). Because such small
amounts of conductance correspond to extremely high
resistance, the nS range lets you de