module 2 2 bbs2015- 214.pdf · • definition nfpa 13: 3.4.10 employs automatic sprinklers attached...
TRANSCRIPT
MODULE 2
1
Based on the Ohio Building Code (OBC)National Fire Protection Association (NFPA) &
Ohio Fire Code (OFC)
Water-Based Suppression System Basics
WATER-BASED SUPPRESSION SYSTEM BASICS-PART ONE
This module covers:
• Water supply sources
• Components of fire suppression such as piping, valves, sprinkler
heads, tests, foam system
• Different types of automatic sprinkler systems
• Standpipe systems
• Foam and water mist suppression system
2
Water Supplies
• The typical water supply for a water-based suppression system is a connection to a public waterworks system. However, other sources of water supply are acceptable.
• Sources:
• NFPA 13: 23.2 Water supply types
• NFPA 13D: 6.2 Water supply sources
• NFPA 13R: 9.3 Water supply sources
• NFPA 20: 7.2 Water supplies
3
Water Supplies: Sources
• A public waterworks system
• An elevated tank
• A pressure tank designed to American Society of Mechanical Engineers (ASME) standards for a pressure vessel with a reliable pressure source
• A stored water source with an automatically operated pump
• A well with a pump of sufficient capacity and pressure to meet the sprinkler system demand
4
Example of a water supply source:An elevated tank
Fire Department Connections
• NFPA states: The purpose of the Fire Department Connection is to supplement the water supply, but not necessarily provide the entire sprinkler system demand. Fire Department Connections are not intended to deliver a specific volume of water.
• FDCs are required for most NFPA 13 and 13R automatic sprinkler systems and standpipe systems
• NFPA 13 requires the fire department connection to be located on the street side of buildings
5
• OBC 912.1 Installation. Fire department connections shall be installed in accordance with the NFPA standard applicable to the system design and shall comply withSection 912.2 through 912.5
6
Piping
• In a wet pipe-sprinkler system water is constantly maintained within the piping
• Dry pipe-sprinkler systems prevent the water from entering the sprinkler system piping
Materials
• Above ground piping material examples found in NFPA 13: 6.3 - steel, copper, and chlorinated polyvinyl chloride (CPVC).
• Below ground material examples found in NFPA 13: 10.1 - ductile iron, steel, concrete, plastic, copper
Location
• NFPA 13: 10.6.1 Pipe shall not be run under buildings
• NFPA 13: 10.6.2 Where pipe must be run under buildings, special precautions shall be taken.
7
• A control valve controls the water to the sprinkler system and should be open at all times
• A check valve has two-port valves, one for fluid to enter and the other for fluid to leave.
• Pressure Requirements: NFPA 13: 6.7.1.1 When water exceed 175 psi, valves shall be used in accordance with their pressure rating
Valves
Automatic Sprinkler Systems Handbook , Eighth Edition
8
Backflow Preventers• A device with check valves, air inlets, and/or relief valves installed on water piping designed to
prevent the flow of water or other liquids, mixtures, or substances into the distributing pipes of a potable supply of water from any source or sources other than its intended source
• Means of backflow prevention
• air gap
• atmospheric vacuum breaker (AVB)
• reduced pressure valve assembly (RP)
• double check valve assembly (DC)
• NFPA 13: 7.2.6.5.4 A check valve or other positive backflow prevention device shall be installed in the air supply to each system to prevent airflow or water flow from one system to another.
• NFPA 13: 10.10.2.5.1 The back flow prevention assembly shall be forward flow tested to ensure proper operation.
• NFPA 13: 10.10.2.5.2 The minimum flow rate shall be the system demand, including hose stream demand where applicable
9
NFPA 13: Automatic Sprinkler Systems Handbook, 2013 Edition
10
SPRINKLER Definition
• The component of a fire sprinkler system that discharges water after a fire has been detected
• NFPA 13: 3.6.1 The following are characteristics of a sprinkler that define its ability to control or extinguish a fire:
• Thermal sensitivity
• Temperature rating
• Specific orifice size
• Installation orientation
• Example: sidewall or pendent sprinklers
• Water distribution characteristics
• Special service conditions
• Example: Corrosion-Resistant or Decorative Sprinklers
Nozzle Definition
• NFPA 13: 3.6.4.4 a device for use in applications requiring special water discharge patterns, directional spray, or other unusual discharge characteristics.
11
University of Toronto
12
Initiating Devices
• A system component that originates transmission of a change-of-state condition
• Includes smoke detectors, water flow alarm, fixed temperature detectors, rate of rise detectors, and heat detector
13
Test connections
• Verify proper operation of equipment
• Example: NFPA 13: 8.17.4.1 Main drain test connections shall be provided at locations that will permit flow tests of water supplies and connections
• For inspection of sprinkler systems:
• Alarm test connections can be located anywhere downstream of the main control valve on a wet pipe system per NFPA 13: 8.17.4.2.4
• Trip test connections must be located on the highest, most remote branch line of a dry pipe system per NFPA 13: 8.17.4.3.2
• NFPA 13: 26.1 A sprinkler system installed in accordance with this standard shall be properly inspected, tested, and maintained in accordance with NFPA 25.
14
Alarm attachments
• NFPA 13: 8.17 System Attachments
• NFPA 13: A.8.17.1 Central station, auxiliary, remote station, or propriety protective signaling systems are a highly desirable supplement to local alarms, especially from a safety to life standpoint.
• NFPA 13: 8.17.1.1 Local Waterflow Alarms. A local waterflow alarm shall be provided on every sprinkler system having more than 20 sprinklers.
15
• Definition NFPA 13: 3.4.10 Employs automatic sprinklers attached to a piping system containing water and connected to a water supply
• NFPA 13: 7.7.1.3.2 Must be maintained at or above 40 °F (4 °C).
• The water discharges immediately from sprinklers opened by heat from a fire
Fire Systems, Inc
16
Automatic Sprinkler Systems: Wet Pipe
• Definition per NFPA 13: 3.4.5 Employs automatic sprinklers that are attached to a piping stream containing air or nitrogen under pressure
• Are used when there is danger of some or all of the piping freezing.
• The release of pressure permits the water pressure to open a dry pipe valve, and the water then flows into the piping system and out the opened sprinklers
17
Fire Systems, Inc
Automatic Sprinkler System: Dry-Pipe
• Definition per NFPA 13: 3.4.4 Employs open sprinklers that are attached to a piping system that is connected to a water supply through a valve
• Valve is opened by the operation of a detection system installed in the same area
• When valve opens, water flows into the piping system and discharges from all sprinklers
18
Fire Systems, Inc
Automatic Sprinkler System: Deluge
Automatic Sprinkler System: Pre-Action
• Definition per NFPA 13: 3.4.9 A system that employs automatic sprinklers that are attached to a piping system that contains air (under or not under pressure)
• Has a supplemental detection system installed in the same area as the sprinklers
• Per NFPA 13: 7.3.2.1 Three basic types: single interlock, non-interlock, and double inter-lock
• typically used in areas containing high value equipment or contents and spaces which are highly sensitive to the effects of accidental sprinkler water discharge.
19
Automatic Sprinkler System: Other
• Anti-freeze
• Circulating Closed Loop
• Combined Dry Pipe-Preaction
• Gridded
• Looped
• Multi-Cycle
20
Standpipe Systems and Classes: Automatic
• A standpipe system that is attached to a water supply capable of supplying the system demand and that requires no action other than opening a hose valve to provide water at hose connections.
• Standpipe systems are classified by their usage: Class I for heavy stream applications, Class II as first aid fire appliances, and Class III which has the features of both Class I and Class II
• Wet: contains water at all times that is attached to a water supply capable of supplying the system demand at all times and that requires no action other than opening a hose valve to provide water at hose connections.
• Dry: permanently attached to a water supply capable of supplying the system demand at all times, containing air or nitrogen under pressure, the release of which (as from opening a hose valve) opens a dry pipe valve to allow water to flow into the piping system and out of the opened hose valve.
• Semi-automatic Dry: permanently attached to a water supply that is capable of supplying the system demand at all times arranged through the use of a device such as a deluge valve and that requires activation of a remote control device to provide water at hose connections.
21
Standpipe Systems and Classes: Manual
• Standpipe systems are classified by their usage: Class I for heavy stream applications, Class II as first aid fire appliances, and Class III which has the features of both Class I and Class II
• Wet: contains water at all times that relies exclusively on the fire department connection to supply the system demand.
• Dry: has no permanently attached water supply that relies exclusively on the fire department connection to supply the system demand.
22
Foam Proportioning Systems
• NFPA 11: 3.3.23 Proportioning. The continuous introduction of foam concentrate at the recommended ratio into the water stream to form foam solution.
• Foam concentrate shall be introduced into the water flow by a concentrate controller utilizing balanced-pressure injection.
• Types of Foam Proportioning System (NFPA 11: 3.3.23)
• Balance Pressure Pump-Type Proportioning
• In-Line Balanced Pressure Proportioning
• Direct Injection Variable Pump Output Proportioning
23
Foam Concentrate
• NPFA 11.3.3.12 Foam Concentrate. A concentrated liquid foaming agent as received from the manufacturer.
• Types of Foam Concentrate (NFPA 11: 3.3.12)
• Alcohol-Resistant Foam Concentrate
• Aqueous Film-Forming Foam Concentrate (AFFF)
• Fluoroprotein Foam Concentrate
• Film-Forming Fluoroprotein Foam Concentrate (FFFP)
24
Foam Generators
• Foam Generator Types (NFPA 11: 3.3.14)
• Aspirator Type
Jet streams of foam solutions aspirate sufficient amounts of air that is then entrained on the screens to produce foam
• Blower Type
Foam solution is discharged as a spray onto screens through which an airstream developed by a fan or blower is passing
25
NFPA 11 Standard for Low-, Medium-, and High-Expansion Foam 2005 Edition
26
Foam-Water Suppression Systems
• Foam-water sprinkler system or foam-water spray systems are outlined in NFPA 16.
• Foam-water sprinkler:
• A special system that is pipe-connected to a source of foam concentrate and to a water supply. The system is equipped with appropriate discharge devices for extinguishing agent discharge and for distribution over the area to be protected.
• Foam-water spray:
• A special system that is pipe-connected to a source of foam concentrate and to a water supply. The system is equipped with foam-water spray nozzles for extinguishing agent discharge (foam followed by water or in reverse order) and for distribution over the area to be protected.
27
Foam-Water Suppression Systems
• (NFPA 11: 5.1) Low-expansion foam to protect outdoor storage tanks, interior flammable liquid hazards, loading racks, diked areas, and non diked spill areas
• (NFPA 11: 6.3) Medium and high-expansion foam shall be permuted to protect: (1) ordinary combustibles, (2) flammable and combustible liquids, combinations of (1) and (2), and liquefied natural gas (high-expansion only)
28
http://www.moody.af.mil/news/story.asp?id=123132709
29
Foam-Water Suppression Systems: Dry
• Employs automatic sprinklers or nozzles that are attached to a piping system that contains air or nitrogen under pressure
• The release of the pipe permits the water pressure to open a valve known as a dry pipe valve.
• The water then flows into the piping system and out the opened sprinklers.
30
In Control Fire Protection
31
Foam-Water Suppression Systems: Preaction
• Employs automatic sprinklers or nozzles attached to a piping system containing air that might or might not be under pressure, with a supplemental detection system installed in the same area as the sprinklers.
• Actuation of the detection system opens a valve that permits water to flow into the sprinkler piping system and to be discharged from any sprinklers that have activated.
32
33
In Control Fire Protection
Foam-Water Suppression Systems: Deluge
• Employs open discharge devices, which are attached to a piping system that is connected to a water supply through a valve that is opened by the operation of a detection system, which is installed in the same areas as the discharge devices.
• When the valve opens, water flows into the piping system and discharges from all discharge devices attached thereto
34
35
In Control Fire Protection
Water Mist Suppression Systems
• A distribution system connected to a water supply or water and atomizing media supplies
• Is equipped with one or more nozzles capable of delivering water mist intended to control, suppress, or extinguish fires
• NFPA 750 is the appropriate standard for the installation of water mist systems
36
• There are many types of water supplies for water-based suppression systems, such as elevated tanks and water transported from a lake or spring.
• A wet pipe automatic sprinkler system should not be installed in an area that goes below freezing and must be maintained at or about 40 degrees Fahrenheit.
• Foam concentrate is a foam fire-fighting agent that must be diluted with water
• There are two types of foam generators, blower and aspirator.
• It is important to be familiar with the OBC, NFPA, OFC, and OPC.
Lessons Learned from Module 2
37