Helvar | Data subject to change without notice www.helvar.com 1
Modular LCM Datasheet and Installation GuideOverviewThe modular LCM is a cost effective method of providing power and control for lighting installations in industrial, commercial and retail buildings. The system is designed for ease of installation: mains input is connected using the spacious wiring compartment, DALI control inputs and outputs are pluggable using industry standard connectors. The modular approach allows for between 2 and 16 luminaires to be connected.
System Components
Note: Allow 150mm for total height of unit (including connectors and cable)
159mm 202mm 122mmFixing point
127mm
75mm150mm105mm
146m
m
BVITM6-S2-HELVAR 2 Output Starter Module
BVITM6-S-HELVAR4 Output Starter Module
BVITM6-E-HELVAR4 Output Extender Module
Helvar | Modular LCM Installation Guide www.helvar.com 2
Installation of Box
4 x key slots to accept M6 (1/4”) fixings BESA box fittings
Channel for channel nuts (zebs)
Removable gland plate with 3 x
Ø20mm knockouts
3 x Ø20mm knockouts for rear cable entry
The box should be fixed on a smooth, flat surface or using drop rod fixings attached to channel nuts.
Ensure that there is easy access to the wiring compartment and all connectors once the box is in-situ.
Warning: This device works at mains voltage. Be sure to take care when working with electricity.
Helvar | Data subject to change without notice www.helvar.com 3
Example Network Diagram (Imagine Router System)
L, N
, E
Note
: Rou
ter
supp
ly m
ust b
e pr
otec
ted
at 6
A
max
imum
.
Pow
erPL
, SW
L, N
, E
DALI
DA+,
DA-
PL, N
, E,
DA+,
DA-
SWL,
N, E
, DA
+, D
A-
E
DALI
Em
erge
ncy
Lum
inai
reDA
LI L
umin
aire
Sens
orDA+,
DA- Bu
tton
Mod
ules
Switc
h In
puts
Emer
genc
y Lu
min
aire
Rout
er D
ALI S
ubne
t Lim
itatio
ns
300m
max
cab
le ru
n64
add
ress
es24
0mA
Exam
ple:
Indi
cativ
e sy
stem
sch
emat
ic o
nly.
Max
5 x
LCM
s pe
r DAL
I sub
net (
aver
age
10 p
ort L
CM +
1 s
enso
r + 1
Sw
itch
inpu
t).Co
ntra
ctor
mus
t pro
vide
app
ropr
iate
isol
atio
n, c
ablin
g an
d re
fere
nce
othe
r sys
tem
com
pone
nt in
stal
l gui
des.
PL, N
, E
E
Ethe
rnet
Imag
ine
910
Rout
er(M
ount
ed in
rest
ricte
d ac
cess
loca
tion)
.
Helvar | Modular LCM Installation Guide www.helvar.com 4
Wiring
Cable Clamps
Large cables
Luminaire connectors/Lead colours
Small cables
DIM+ (DALI+) Red
DIM- (DALI -) White
Permanent Live Black (6 core only)
Neutral Blue
Earth Green/Yellow
Switched Live Brown
DALI+ DALI -
Permanent Live
Neutral
Earth
Switched LiveNot for useNot for use
LiveWarning: For correct installation, connector plugs must be fully engaged and latched on both sides.
• All wiring must be mains rated.• Remove wiring compartment cover.• Wire the box using the diagrams below. Switched Live for normal fittings Permanent live feeds emergency fittings• Use the cable clamps to secure the wiring or use cable glands (not supplied). The clamps can be split, and flipped over to clamp different cable diameters.• Replace wiring compartment cover.• Plug in the luminaires ensuring that the connector latches to the box.
Note: Live is NOT internally connected and NOT fed through to outputs. See page 5.
Helvar | Data subject to change without notice www.helvar.com 5
Wiring Layout and Emergency Test
Local lighting switch and local emergency test switch
Emergency test using power interruption
Emergency test using central switch
Warning: Do not wire across phases
DA+
DA-
DA+DA-
Central emergency
test switch or controllable relay
e.g. Helvar 492
Wire link
DA+
DA-Local emergency
test switch
N E L
N E L
N E L Multiple boxes
Helvar | Modular LCM Installation Guide www.helvar.com 6
WDA0057860412 Issue 022019-09-23
Part numbers
Ratings
Modules
BVITM6-S-HELVAR 4 output starter moduleBVITM6-S2-HELVAR 2 output starter moduleBVITM6-E-HELVAR 4 output extender module
Connectors
BVITM6-LPR 6 pole luminaire plug redBVITM6-LPW 6 pole luminaire plug white
Voltage 230VAC +/- 10%Frequency 50HzTerminal Capacity 4mm2 in wiring compartmentTemperature 00C to 350CPower Rating system 16A. Rating of each output 10ACompliance BS5733:2010
?
Helvar Ltd, Hawley Mill, Hawley Road, Dartford. DA2 7SY. UKwww.helvar.com+44 (0) 1322 617200
Warning: For lighting purposes with suitable circuit protection. For fixed wiring only.
Important: This device should be installed by a qualified electrician in accordance with the latest edition of the IEE wiring regulations
UK Patent no. GB2463063EU Patent pendingEU Registered design no. 001587544-0001, 001587544-0002