modern approach to hvac design and its future trend

60
 MODERN APPROACH TO HVAC DESIGN AND ITS FUTURE TREND A dissertation submitted to the Department of Pharmacy, The University of Asia Pacific in the partial fulfillment of the  requirements for the degree of M aster of Pharmacy in Pharmaceutical Technology SUBMITTED BY Md. Hasif Sinha Registration No: 09207021 Roll No: 21 DEPARTMENT OF PHARMACY The University of Asia Pacific Date of Submission: October 18, 2010

Upload: md-hasif-sinha

Post on 09-Oct-2015

27 views

Category:

Documents


0 download

DESCRIPTION

M.Pharm Project

TRANSCRIPT

  • MODERN APPROACH TO HVAC DESIGN AND

    ITS FUTURE TREND

    A dissertation submitted to the Department of Pharmacy,

    The University of Asia Pacific in the partial fulfillment of the

    requirements for the degree of Master of Pharmacy in

    Pharmaceutical Technology

    SUBMITTED BY

    Md. Hasif Sinha

    Registration No: 09207021

    Roll No: 21

    DEPARTMENT OF PHARMACY

    The University of Asia Pacific

    Date of Submission: October 18, 2010

  • Table of Contents

    i

    Table of Contents

    Purpose of the Study _________________________________________ vi

    Abstract ___________________________________________________ vii

    List of Chapters

    Chapter

    No.

    Chapter

    Name

    Page

    No.

    1 Introduction to HVAC 1

    1.1

    1.2

    1.3

    1.4

    1.4.1

    1.4.2

    1.4.3

    1.4.4

    1.4.5

    Introduction

    Objective of HVAC System

    Scope of Modern HVAC

    HVAC System

    Types of HVAC Systems

    Heating

    Ventilating

    Air-Conditioning System

    Efficiency

    1

    1

    1

    2

    2

    3

    3

    3

    4

    2 HVAC System Choosing and Designing 5

    2.1

    2.1.1

    2.2

    2.2.1

    2.2.2

    2.2.3

    2.2.4

    2.2.5

    2.2.6

    2.3

    2.3.1

    2.4

    2.4.1

    2.4.1.1

    2.4.1.2

    2.4.1.3

    2.4.1.4

    2.4.1.4.1

    2.4.1.4.2

    2.4.1.4.3

    Choosing an HVAC System

    HVAC System Selection Guidelines

    Choosing an Air-Conditioning System

    Building Design

    Location Issues

    Utilities: Availability and Cost

    Indoor Requirements and Loads

    Client Issues

    System Choice

    Unitary System Selection Guidelines

    Factors to Consider When Selecting Unitary Systems

    HVAC Design

    Design of an Air Handling Unit

    Sub-Systems of AHU

    Air Flow Patterns

    Filters Positions

    Air Circulation System

    Air Re-Circulation

    Ventilation with 100% fresh air (no air re-circulation)

    Ventilation with re-circulated air with make-up air

    5

    5

    6

    6

    6

    7

    7

    7

    7

    8

    8

    8

    8

    8

    9

    11

    12

    12

    13

    13

  • Table of Contents

    ii

    3 Zoning Design, Central Plants and Hydronic Systems 14

    3.1

    3.1.1

    3.1.2

    3.2

    3.2.1

    3.2.2

    3.2.2.1

    3.2.2.2

    3.2.2.3

    3.2.2.4

    3.3

    3.3.1

    3.3.2

    3.3.3

    3.3.4

    3.3.5

    3.3.6

    3.3.7

    3.4

    3.4.1

    3.4.1.1

    3.4.2

    3.4.3

    3.4.3.1

    3.4.4

    3.5

    3.5.1

    3.5.2

    3.5.3

    3.5.4

    3.5.5

    3.5.6

    3.6

    3.6.1

    3.6.2

    3.6.3

    3.6.4

    3.6.5

    Zone

    Zoning Design

    Controlling the Zone

    Single Zone Air Handlers

    Examples of Buildings with Single-zone Package Air-

    Conditioning Units

    Air-Handling Unit Components

    Refrigeration Equipment

    System Performance Requirements

    Rooftop Units

    Split Systems

    Multiple Zone Air Systems

    Three Deck, Multizone System

    Dual Path, Outside Air System

    Single-Duct, Zoned Reheat, Constant Volume Systems

    Single-Duct, Variable Air Volume Systems

    Dual-Duct, Variable Air Volume System

    By Pass Box Systems

    Constant Volume Dual-Duct, All-Air Systems

    Central Plants

    Boilers

    Boiler Components

    Water Chillers

    Centrifugal Water Chillers

    Central Plant Water Chiller Optimization

    Cooling Towers

    Hydronic Systems

    Natural Convection and Low Temperature Radiation

    Heating Systems

    Panel Heating and Cooling

    Fan Coils

    Fan Curves

    Two Pipe Induction Systems

    Water Source Heat Pumps

    Hydronic System Architecture

    Steam Systems

    Water Systems

    Hot Water Systems

    Chilled Water Systems

    Condenser Water System

    14

    14

    15

    15

    15

    16

    17

    17

    17

    18

    18

    19

    19

    19

    20

    20

    20

    21

    21

    22

    22

    23

    24

    24

    25

    25

    26

    27

    27

    28

    28

    29

    29

    29

    29

    30

    30

    30

  • Table of Contents

    iii

    4 Control Systems and Thermal Comfort 31

    4.1

    4.2

    4.3

    4.4

    4.4.1

    4.4.2

    4.4.3

    4.4.4

    4.4.5

    4.4.5.1

    4.5

    4.5.1

    4.5.1.1

    4.5.1.2

    4.5.1.3

    4.5.1.4

    4.5.1.5

    4.5.1.6

    4.6

    4.7

    4.7.1

    4.7.2

    4.7.3

    4.8

    4.8.1

    4.8.1.1

    4.8.1.2

    4.8.1.3

    4.8.1.4

    4.8.1.5

    4.8.1.6

    4.8.1.7

    4.9

    4.9.1

    4.9.1.1

    4.9.1.2

    4.9.1.2.1

    4.9.1.2.2

    4.9.1.2.3

    4.9.1.3

    4.9.2

    4.9.2.1

    4.9.2.1.1

    4.9.2.1.2

    4.9.2.1.3

    HVAC Control Systems

    Control Loops

    Control Modes

    Control Types

    Self-powered Controls

    Electric Controls

    Pneumatic Controls

    Electronic Controls

    Direct Digital Controls, DDC

    Benefits of DDC

    Control System Components

    Controllers

    Single Pressure Thermostat

    Dead Band Thermostat

    Dual Pressure Thermostat

    Humidistat

    Master/Submaster Controller

    Receiver-controller and Transmitter

    Energy Conservation

    Parameters to Control

    Importance of Humidity Control

    Importance of Temperature Control

    Importance of Dust Particle Control

    Thermal Comfort

    Factors Influencing Thermal Comfort

    Activity Level

    Clothing

    Occupants Expectations

    Air Temperature

    Radiant Temperature

    Humidity

    Air Speed

    Heat Flow and Heat Recovery

    Heat Flow

    Heat Transfer

    Types of Heat Transfer

    Conduction

    Convection

    Radiation

    Heat Transfer Equations

    Heat Recovery

    Heat Recovery Systems

    Comfort- to-Comfort Heat Recovery Systems

    Process-to-Comfort Heat Recovery Systems

    Process-to-Process Heat Recovery Systems

    31

    31

    32

    32

    32

    32

    32

    32

    32

    33

    33

    33

    33

    33

    34

    34

    34

    34

    34

    35

    35

    36

    36

    36

    36

    37

    37

    37

    37

    38

    38

    38

    38

    38

    38

    38

    39

    39

    39

    39

    39

    39

    40

    40

    40

  • Table of Contents

    iv

    5 Future Trend to HVAC 47

    5.1

    5.2

    5.3

    5.4

    5.5

    5.6

    5.7

    Future Trend to HVAC

    Future Revolution in HVAC Design

    Logic of the HVAC Revolution

    Optimized Function HVAC Design

    Central Plant Equipment in Optimized Systems

    Economics of Optimized-Function HVAC

    Onward to the Future

    41

    41

    41

    42

    42

    42

    43

    6 Conclusion 44

    6.1 Conclusion 44

    List of Figures

    Figure

    No.

    Figure

    Headline

    Page

    No.

    1.1 Air-Conditioning Plant 4

    2.1

    2.2

    2.3

    2.4

    2.5

    2.6

    2.7

    2.8

    2.9

    Sub-systems of AHU

    (a) Turbulent Air Flow, (b)Uni-directional or Laminar Air Flow

    Room 1, 2 & 3 with different air flow patterns and exhaust systems

    AHU mounted final filter

    Filter in terminal position

    HVAC installation feeding 3 rooms

    HVAC installation feeding 2 rooms

    Ventilation with 100% fresh air (no air re-circulation)

    Ventilation with re-circulated air with make-up air

    9

    10

    10

    11

    11

    12

    12

    13

    13

    3.1

    3.2

    3.3

    3.4

    3.5

    3.6

    3.7

    3.8

    3.9

    3.10

    3.11

    3.12

    3.13

    3.14

    3.15

    3.16

    3.17

    3.18

    3.19

    3.20

    Building Plan

    Single Zone Rooftop Air-Conditioning Unit, Energy Supplies

    Air-Conditioning System: Single-Zone Air Handler

    Basic Vapor Compression Refrigeration Cycle

    Rooftop Unit

    Split System

    Mixing at the Air Conditioning Unit in a Multizone System

    Reheat System

    Variable Air Volume System

    By-Pass Boxes on Each Zone

    Dual-Duct System, Double Line Diagram

    Hot Water Heating System with Two Boilers

    Water Chiller with Water Cooled Condenser

    Two Chiller Piping with Constant Chiller Flow

    Centrifugal Mechanical Chiller

    Typical Natural-Draft Open Cooling Tower

    Induced Draft, Closed Circuit Cooling Tower

    Wall-Mounted Single and Double Panel Radiators

    Concrete Radiant Floor

    Typical Fan-Coil Unit

    14

    16

    16

    17

    18

    18

    19

    20

    20

    21

    21

    22

    23

    24

    24

    25

    25

    27

    27

    28

  • Table of Contents

    v

    3.21

    3.22

    3.23

    3.24

    Induction Unit

    Steam System

    Chiller System with Decoupled Flows

    Evaporative Cooling Tower

    28

    29

    30

    30

    4.1

    4.2

    Diagram of Control Loop

    DDC Control Schematic

    31

    33

    References

  • Purpose of the study

    vi

    Purpose of the Study

    The purpose of the study on the topic Modern Approach HVAC Design and its

    Future Trend is enormous. The main focus is on the proper choosing and designing

    of HVAC systems in order to achieve more reliable, dynamic and successful future in

    the pharmaceutical industries HVAC systems. To maintaining the air cleanliness we

    need to prepare perfect HVAC design and control systems. The air pressure, air flow

    velocity, direction of air flow, make-up and fresh air flow system, air filtration and

    other environmental factors such as temperature and humidity should be controlled

    properly. The HVAC systems are divided into components and controls for air, water,

    heating, ventilating and air conditioning to clearly illustrate the way in which each

    system, subsystem, control or component contributes to providing the desired indoor

    environment. There are several zone air systems in the pharmaceutical industry like

    single zone air system and multiple zone air systems. The building, zoning areas,

    machineries, and equipments should be design perfectly to control the air cleanliness,

    particle contaminations, and cGMP regulations. We also need to focus on cost

    effectiveness of the HVAC system. Some of the many cost concerns include initial or

    installation cost, operating and maintenance cost, and equipment replacement costs.

    Another cost concern that may be overlooked by the designer is the cost associated

    with equipment failure. The best situation is when designer and owner are both

    involved in the HVAC selection process. So the proper designing of an HVAC system

    is not an easy process. The core purpose of an HVAC system is to provide and

    maintain environmental conditions within an area. The type of system selected is

    determined by the mechanical designers knowledge of systems and the building

    owners financial and functional goals.

  • Abstract

    vii

    Abstract

    HVAC is particularly important in the design of medium to large industrial and office

    buildings where safe and healthy building conditions are regulated with temperature

    and humidity, as well as "fresh air" from outdoors. Depending on the complexity of

    the requirements, the HVAC designer must consider many more issues than simply

    keeping temperatures comfortable. The proper design of HVAC system is one of the

    most fundamental factors for the pharmaceutical industries. The engineers are trying

    to modernization the HVAC design on the focusing of various important factors such

    as zoning design, central plants, hydronic systems, thermal comfort, and control

    systems. Systems have been designed for greatest assurance of consistent

    environmental conditions, with constant volume or reheat and high air change rates

    the order of the day. Steps to prevent cross-contamination in multi-product plants

    have been draconian, ranging from 100% fresh air or exhaust to multiple series HEPA

    filters in supply and exhaust. Developments in processing equipment, isolation

    technology and a risk or science-based approach to ensuring parameters of "strength,

    identity, safety, purity, and quality," open a new world of possibilities for HVAC in

    pharmaceutical facilities.

  • CHAPTER ONE

    Introduction to HVAC

  • Chapter - 1 Introduction to HVAC

    Modern Approach to HVAC Design and its Future Trend 1

    1.1 Introduction

    HVAC an initialism that stands for the closely related functions of "Heating,

    Ventilating, and Air Conditioning" the technology of indoor or automotive

    environmental comfort. HVAC system design is a major sub-discipline of mechanical

    engineering, based on the principles of thermodynamics, fluid mechanics, and heat

    transfer. Refrigeration is sometimes added to the field's abbreviation as HVAC&R or

    HVACR, or ventilating is dropped as in HACR.

    HVAC is particularly important in the design of medium to large industrial and

    office buildings where safe and healthy building conditions are regulated with

    temperature and humidity, as well as "fresh air" from outdoors.

    Depending on the complexity of the requirements, the HVAC designer must

    consider many more issues than simply keeping temperatures comfortable. We need

    to discuss about the fundamental concepts that are used by designers to make

    decisions about system design, operation, and maintenance.

    1.2 Objective of HVAC System

    The goal for a HVAC system is to provide proper air flow, heating, and cooling to

    each room. In HVAC Industries there are so many standard organizations such as

    ASHRAE, SMACNA, ACCA, Uniform Mechanical Code, International Mechanical

    Code, and AMCA have been established to support the industry and encourage high

    standards and achievement.

    It is important that the objective criteria for system success are clearly identified

    at the start of the project, because different requirements need different design

    considerations.

    1.3 Scope of Modern HVAC

    Although there have been great advances in HVAC, there are several areas where

    active research and debate continue.

    Indoor air quality is one that directly affects us. In many countries of the world

    there is a rapid rise in asthmatics and increasing dissatisfaction with indoor-air-quality

    in buildings and planes. A significant scientific and engineering field has developed to

    investigate and address these issues.

  • Chapter - 1 Introduction to HVAC

    Modern Approach to HVAC Design and its Future Trend 2

    Energy conservation is an ongoing challenge to find novel ways to reduce

    consumption in new and existing buildings without compromising comfort and indoor

    air quality. Energy conservation requires significant cooperation between disciplines.

    1.4 HVAC System

    Commercial heating, ventilating, and air conditioning (HVAC) systems provide the

    people working inside buildings with conditioned air so that they will have a

    comfortable and safe work environment. Air quality and the condition of the air

    are two very important factors. By conditioned air and good air quality, we mean

    that air should be clean and odor-free and the temperature, humidity, and movement

    of the air will be within certain acceptable comfort ranges.

    ASHRAE, the American Society of Heating, Refrigerating and Air

    Conditioning Engineers, has established standards which outline indoor comfort

    conditions that are thermally acceptable to 80% or more of a commercial buildings

    occupants. Generally, these comfort conditions, sometimes called the comfort zone,

    are between 68F and 75F for winter and 73F to 78F during the summer. Both

    these ranges are for room air at approximately 50% relative humidity and moving at a

    slow speed (velocity) of 30 feet per minute or less.

    An HVAC system is simply a group of components working together to move

    heat to where it is wanted, or remove heat from where it is not wanted, and put it

    where it is unobjectionable (the outside air).

    1.4.1 Types of HVAC Systems

    The basic types of HVAC systems used in commercial buildings are all-air, air and

    water, all-water, and unitary. Water systems are also called hydronic systems.

    Hydronic is the term used for heating and cooling with liquids. All-air systems

    provide heated or cooled air to the conditioned space through a ductwork system. The

    basic types of all-air duct systems are: single-zone, multizone, dual or double duct,

    terminal reheat, constant air volume, variable air volume (VAV), and combination

    systems.

  • Chapter - 1 Introduction to HVAC

    Modern Approach to HVAC Design and its Future Trend 3

    1.4.2 Heating

    Heating is one of the most important fact in the HVAC system. Heating should be

    provide properly to maintain the desire temperature. There are many different types of

    standard heating systems. The main components of heating systems are: Boilers,

    Furnaces and Heating Coils.

    1.4.3 Ventilating

    Ventilating is the process of "changing" or replacing air in any space to control

    temperature or remove moisture, odors, smoke, heat, dust, airborne bacteria, carbon

    dioxide, and to replenish oxygen. Ventilation includes both the exchange of air to the

    outside as well as circulation of air within the building. It is one of the most important

    factors for maintaining acceptable indoor air quality in buildings. Methods for

    ventilating a building may be divided into mechanical/forced and natural types.

    Ventilation is used to remove unpleasant smells and excessive moisture, introduce

    outside air, to keep interior building air circulating, and to prevent stagnation of the

    interior air.

    1.4.4 Air-Conditioning System

    Air Conditioning within the HVAC system refers to the removal of heat from a room

    or building in order to cool the air to a desired temperature. The heat transfer process

    works through mediums like ice, air, water, and chemicals that are naturally cooler

    than the air in the room. The air conditioning system also controls humidity levels

    within the building and cools the air through a process of condensing and evaporating

    a desired liquid through a series of coils, much like a refrigerator. Central air

    conditioning systems that cool entire buildings can work through the same ductwork

    as some central heating systems. The air is forced through the ductwork and back to

    the air conditioner where it is cooled and sent back through the system. Central

    cooling systems often incorporate an evaporator that collects the condensation from

    the cooling coils and therefore dehumidifies the air. The resulting condensation can

    then be manually removed or drained outside.

  • Chapter - 1 Introduction to HVAC

    Modern Approach to HVAC Design and its Future Trend 4

    Figure 1.1 - Air-Conditioning Plant

    1.4.5 Efficiency

    Although most HVAC systems utilize the same ductwork for both heating and

    cooling, forced-air ventilation is not necessarily the most energy efficient. By creating

    zones central heating and cooling units can be better utilized through a variety of

    thermostats that regulate heat and air when needed. With zones, rooms that require

    heat and air can maintain comfortable while unused areas can minimize temperature

    control and save energy. The most energy efficient form of heating is geothermal

    heating, a method of using natural heat sources to warm buildings. Although

    using HVAC systems help save some cost and energy through the use of proper air

    flow and thermodynamics, the best way to maximize the efficiency of an HVAC

    system is to install it in a properly designed building. Buildings need to be designed

    around the potential benefits of solar energy and passive heating and cooling

    opportunities. Without proper architecture, HVAC systems work harder and waste

    energy.

  • CHAPTER TWO

    HVAC System Choosing and Designing

  • Chapter - 2 HVAC System Choosing and Designing

    Modern Approach to HVAC Design and its Future Trend 5

    2.1 Choosing an HVAC System

    The purpose of an HVAC system is to provide and maintain environmental conditions

    within an area called the conditioned space. The type of system selected is

    determined by the mechanical designers knowledge of systems and the building

    owners financial and functional goals.

    It is the designers responsibility to consider the various systems and select the

    one that will provide the best combination of initial cost, operating cost, performance,

    and reliability based on his understanding of the owners needs and goals. In the

    selection process all factors must be analyzed, but cost of installation and operation

    are usually foremost.

    Some of the many cost concerns include initial or installation cost, operating

    and maintenance cost, and equipment replacement costs. Another cost concern that

    may be overlooked by the designer is the cost associated with equipment failure. The

    best situation is when designer and owner are both involved in the HVAC selection

    process.

    The goals of choosing of an HVAC system are-

    To provide an acceptable level of occupancy comfort

    To provide temperature and humidity control for process function

    To maintain good indoor air quality (IAQ)

    To minimize energy requirements and costs

    2.1.1 HVAC System Selection Guidelines

    Each of the following issues should be taken into consideration each time an HVAC

    system is selected.

    1) Financial factors

    Initial cost

    Operating costs

    Maintenance and repair cost

    Equipment replacement or upgrading cost

    Equipment failure cost

    Return on investment (ROI)

    Energy costs

  • Chapter - 2 HVAC System Choosing and Designing

    Modern Approach to HVAC Design and its Future Trend 6

    2) Building conditions

    New or existing building or space

    Location

    Orientation

    Architecture

    Climate and shading

    Configuration

    Construction

    Codes and standards

    3) Usage

    Occupancy

    Process equipment

    4) Energy availability

    Types

    Reliability

    5) Control scheme

    Zone control

    Individual control

    2.2 Choosing an Air-Conditioning System

    The factors or parameters that influence system choice can conveniently be divided

    into the following groups:

    2.2.1 Building Design

    The design of the building has a major influence on system choice.

    2.2.2 Location Issues

    The building location determines the weather conditions that will affect the building

    and its occupants. For the specific location we will need to consider factors like:

    site conditions

    peak summer cooling conditions

    summer humidity

    peak winter heating conditions

  • Chapter - 2 HVAC System Choosing and Designing

    Modern Approach to HVAC Design and its Future Trend 7

    wind speeds

    sunshine hours

    typical snow accumulation depths

    The building location and, at times, the client, will determine what national, local, and

    facility specific codes (Building code, Fire code, Energy code) must be followed.

    Typically, the designer must follow the local codes.

    2.2.3 Utilities: Availability and Cost

    The choice of system can be heavily influenced by available utilities and their costs to

    supply and use. So, if chilled water is available from the adjacent building, it would

    probably be cost advantageous to use it, rather than install new unitary refrigerant-

    based units in the new building.

    2.2.4 Indoor Requirements and Loads

    The location effects and indoor requirements provide all the necessary information for

    load calculation for the systems.

    The thermal and moisture loads

    Outside ventilation air

    Zoning

    2.2.5 Client Issues

    The designer has to consider the clients requirements both for construction and for

    in-use costs. The client may wish to finance a very sophisticated and more expensive

    system to achieve superior performance, or to reduce in-use costs. In addition to cost

    structures, the availability of maintenance staff must be considered. A building at a

    very remote site should have simple, reliable systems, unless very competent and

    well-supported maintenance staff will be available.

    2.2.6 System Choice

    While all the above factors are considered when choosing a system, the first step in

    making a choice is to calculate the system loads and establish the number and size of

    the zones. Typically, after some systems have been eliminated for specific reasons,

    one needs to do a point-by-point comparison to make a final choice.

  • Chapter - 2 HVAC System Choosing and Designing

    Modern Approach to HVAC Design and its Future Trend 8

    2.3 Unitary System Selection Guidelines

    Unitary systems are selected when it is decided that a central HVAC system is too

    large or too expensive for a particular project, or a combination system is needed for

    certain areas or zones to supplement the central system.

    2.3.1 Factors to Consider When Selecting Unitary Systems

    i. Control of Temperature and Airflow

    ii. One Manufacturer is Responsible for the Final Unit

    iii. Maintenance and Operation

    iv. Costs and Energy Efficiency

    2.4 HVAC Design

    Best-in-class HVAC system design and analysis are critical elements of creating the

    optimal building environment. Given the level of control and the performance

    demands of todays sophisticated HVAC systems, seemingly incremental efficiencies

    result in significant reductions of resource requirements. Accurate analysis and

    specifications translate into substantial savings and optimal performance for building

    owners. Conducting comprehensive load analyses, considering air supply

    requirements, weather conditions, determining optimum HVAC system, piping and

    duct configurations, and then applying those considerations to specifications are all

    critical to high performance building design.

    Pharmaceutical manufacturing is generally conducted in environments that are

    cleaner and are carefully controlled at a required temperature, humidity and pressure.

    The HVAC system assumes a large part of the responsibility in maintaining these

    clean environments.

    2.4.1 Design of an Air Handling Unit

    Choosing of an Air Handling System is very important for a pharmaceutical industry.

    Air Handling Units are designed to create a symbiosis of heat, ventilation and air

    filtration. The result is a perfectly balanced environment for people and industry.

    2.4.1.1 Sub-Systems of AHU

    A conventional Air Handling System has 4 sub-systems:

  • Chapter - 2 HVAC System Choosing and Designing

    Modern Approach to HVAC Design and its Future Trend 9

    1. Air handling of the incoming (fresh) air, elimination of coarse contaminants

    and protection from frost if necessary. In the case of air re-circulation, the

    fresh air is also called make-up air.

    2. Central air handling unit (AHU), where the air will be conditioned (heated,

    cooled, humidified or de-humidified and filtered), and where fresh air and re-

    circulated air, if any, (indicated here by the dotted line) will be mixed.

    3. Air handling in the rooms under consideration (pressure differential system,

    additional filtration, air distribution)

    4. Air exhaust system (filtration)

    Figure 2.1 - Sub-systems of AHU

    2.4.1.2 Air Flow Patterns

    There are 2 ways to supply air to a room: Turbulent air flow and Uni-

    directional flow, often called laminar flow

    The air speed in the uni-directional flow is defined by the WHO at: 0.45 m/s

    for horizontal units and 0.30 m/s for vertical units (most commonly used)

    For the air exhaust, in case of a vertical unit, a low return is more favorable, as

    the air is better distributed in the room

    Objects in the room can significantly disturb the flow of air, and even block it,

    so that there might be pockets without air circulation.

  • Chapter - 2 HVAC System Choosing and Designing

    Modern Approach to HVAC Design and its Future Trend 10

    (a)

    (b)

    Figure 2.2 - (a) Turbulent Air Flow, (b)Uni-directional or Laminar Air

    Flow

    Filtered air entering a production room or covering a process can be meet

    GMP aspects and Economical aspects

    Figure shows an HVAC installation feeding 3 rooms, each one with terminal

    filters, all terminal filters protected by a remote pre-filter. Room 1 has a

    turbulent air flow, with low level exhaust. Room 2 has a uni-directional air

    flow, over the largest part of the surface, hence the large number of filters,

    with low level air returns.

    Due to the high cost of the ventilation in class A areas, the tendency is to keep

    these areas as small as possible. Room 3 has a turbulent air flow, with ceiling

    exhaust.

    Figure 2.3 - Room 1, 2 & 3 with different air flow patterns and exhaust

    systems

    Uni-directional (laminar) flow units exist mostly as vertical, but also as

    horizontal, units.

    In some cases, the units can be integrated into the ceiling of a room and also

    connected to the central air conditioning system.

    Laminar flow units are comparatively expensive. Surfaces covered by them

    should be reduced to a minimum. Only the product in a critical production

  • Chapter - 2 HVAC System Choosing and Designing

    Modern Approach to HVAC Design and its Future Trend 11

    phase, and not the personnel, should be under laminar flow (aseptic filling,

    sterile blending, etc.).

    2.4.1.3 Filters Positions

    The filtered air entering a production room can be coming from:

    an air-handling unit, equipped with pre-filtration and the main (HEPA) filter,

    but at some distance from that room;

    an air-handling unit, equipped with pre-filtration in the AHU, and an

    additional filter (HEPA) situated immediately on the air outlet.

    the terminal positioning is more expensive; provides a better protection; is the

    preferred method in clean room classes with high requirements.

    Figure 2.4 - AHU mounted final filter

    Figure 2.5 - Filter in terminal position

    Filters can be in different positions, when one considers the central AHU and

    the rooms.

    The figure shows an HVAC installation feeding 3 rooms, each one with

    terminal filters, all filters protected by a remote pre-filter.

    Room 1 has a turbulent air flow, with low level exhaust. Room 2 has a uni-

    directional (laminar) air flow over the largest part of the surface, hence the

    large number of filters. Room 3 has a turbulent air flow, with ceiling exhaust.

  • Chapter - 2 HVAC System Choosing and Designing

    Modern Approach to HVAC Design and its Future Trend 12

    Figure 2.6 - HVAC installation feeding 3 rooms

    The figure shows an HVAC installation feeding two rooms, each one without

    terminal filters, but with remote final filters protected by a pre-filter.

    Room 1 has a turbulentair flow, with low level exhaust. Room 2 has a

    turbulent air flow, with ceiling exhaust.

    If there is no filter in terminal position, it should be ascertained that there are

    no elements between the main filter and the air outlets which could add

    contamination.

    Figure 2.7 - HVAC installation feeding 2 rooms

    2.4.1.4 Air Circulation System

    2.4.1.4.1 Air Re-Circulation

    Re-circulated air must be filtered, at an efficiency rate which is such that

    cross-contamination can be excluded.

    In case of re-circulation, every possible measure of protection must be taken to

    ensure that the air coming from a production unit and loaded with product

    particles does not flow to other production units, thereby contaminating them.

    It makes sense to re-circulate the air for reasons of energy conservation, but

    there can be a contradiction between pharmaceutical requirements and energy

    conservation.

  • Chapter - 2 HVAC System Choosing and Designing

    Modern Approach to HVAC Design and its Future Trend 13

    There are also cases, in which air re-circulation is prohibited, for example if

    solvents are used or cytotoxic products are manufactured.

    2.4.1.4.2 Ventilation with 100% fresh air (no air re-circulation)

    A typical 100% fresh air setup, where a central unit distributes the fresh,

    treated air to different production rooms.

    The exhaust air is collected in a central duct, treated (filtered or washed) and

    eliminated. The degree of exhaust air filtration will depend on contaminants in

    the exhaust air and also on environmental regulations.

    Figure 2.8 - Ventilation with 100% fresh air (no air re-circulation)

    2.4.1.4.3 Ventilation with re-circulated air with make-up air

    A typical re-circulated air setup, where a central unit distributes a mixture of

    fresh and re-circulated air to different production rooms.

    A part of the exhaust air is collected in a central duct, treated (filtered) and

    exhausted. The rest is re-circulated (dotted line).

    With control dampers, the proportions of fresh and re-circulated air can be

    adjusted.

    Figure 2.9 - Ventilation with re-circulated air with make-up air

  • CHAPTER THREE

    Zoning Design, Central

    Plants and Hydronic

    Systems

  • Chapter - 3 Zoning Design, Central Plants and Hydronic Systems

    Modern Approach to HVAC Design and its Future Trend 14

    3.1 Zone

    To maximize thermal comfort, systems can be designed to provide independent

    control in the different spaces, based on their users and requirements. Each space or

    group of spaces that has an independent control is called a zone.

    A zone is a part of a building whose HVAC system is controlled by a single

    sensor. The single sensor is usually, but not always, a thermostat. Either directly or

    indirectly, a thermostat controls the temperature at its location.

    3.1.1 Zoning Design

    There are several types of zones. These zones are differentiated based on what is to be

    controlled, and the variability of what is to be controlled. The most common control

    parameters are: thermal, humidity, ventilation, operating periods, freeze protection,

    pressure and importance.

    The most common reason for needing zones is variation in thermal loads.

    Consider the simple building floor plan shown in Figure 3.1. Let us assume it has the

    following characteristics:

    Well-insulated

    A multi-story building, identical plan on every floor

    Provided with significant areas of window for all exterior spaces

    Low loads due to people and equipment in all spaces

    Located in the northern hemisphere

    The designers objective is to use zones to keep all spaces at the set-point

    temperature.

    Figure 3.1 - Building Plan

  • Chapter - 3 Zoning Design, Central Plants and Hydronic Systems

    Modern Approach to HVAC Design and its Future Trend 15

    Zones are designed on the basis of some factors:

    Zoning Design Considerations

    Interior and Roof Zones

    Thermal Variation

    Ventilation with Outside Air

    Time of Operation

    Humidity

    Pressure

    Zoning Problems

    3.1.2 Controlling the Zone

    The most common zone control is the thermostat. It should be placed where it is most

    representative of the occupants thermal experience. A thermostat does its best to

    keep a constant temperature where it is.

    3.2 Single Zone Air Handlers

    The single zone air handler, or air-handling unit, often abbreviated to AHU. The air

    handler draws in and mixes outside air with air that is being recirculated, or returned

    from the building, called return air. Once the outside air and the return air are mixed,

    the unit conditions the mixed air, blows the conditioned air into the space and

    exhausts any excess air to outside, using the return-air fan.

    3.2.1 Examples of Buildings with Single-zone Package Air-Conditioning Units

    Building A: This unit has only an electrical supply. This single electrical supply

    provides all the power for heating, cooling, humidifying, and for driving the fans.

    Building B: This unit has the electrical supply for cooling, humidifying, and for

    driving the fans, while the gas line, shown as gas supply, provides heating.

    Building C: This unit has the electrical supply for cooling, humidifying, and for

    driving the fans. It also has supply and return hot-water pipes coming from a boiler

    room in another building. The unit contains a hot-water heating coil and control valve,

    which together take as much heat as needed from the hot water supply system.

    Building D: In the same way, there may be a central chiller plant that produces cold

    water at 42F 48F, called chilled water. This chilled water is piped around the

  • Chapter - 3 Zoning Design, Central Plants and Hydronic Systems

    Modern Approach to HVAC Design and its Future Trend 16

    building, or buildings, to provide the air-handling units with cooling. Like the heating

    coil and control valve in Building C, there will be a cooling coil and control valve in

    each unit, to provide the cooling and dehumidification.

    Figure 3.2 - Single Zone Rooftop Air-Conditioning Unit, Energy Supplies

    3.2.2 Air-Handling Unit Components

    Components of the unit can include: inlet louver screen, the parallel blade damper,

    opposed blade damper, the relief air damper, actuator, the mixed temperature sensor,

    filter, heating coil, cooling coil, humidifier, fan, and return fan.

    Figure 3.3 - Air-Conditioning System: Single-Zone Air Handler

  • Chapter - 3 Zoning Design, Central Plants and Hydronic Systems

    Modern Approach to HVAC Design and its Future Trend 17

    3.2.2.1 Refrigeration Equipment

    The vapor compression refrigeration cycle is generally the basis of mechanical

    refrigeration. The vapor compression refrigeration system comprises four

    components: compressor, condenser, expansion valve, and evaporator. This system

    can be used directly, to provide cooling to, typically, a local coil.

    Figure 3.4 - Basic Vapor Compression Refrigeration Cycle

    3.2.2.2 System Performance Requirements

    Before choosing a system, we need an understanding of the types of loads we want

    the system to manage. Summer cooling loads will be the main determinant of the

    choice of unit to determine the summer load: outside design temperature; outside

    design humidity; inside design temperature and humidity; inside generation of heat

    and moisture; ventilation requirements.

    3.2.2.3 Rooftop Units

    In a typical rooftop unit, the return air is drawn up into the base of the unit and the

    supply air is blown vertically down from the bottom of the unit into the space below.

    As an alternative, the ducts can come out of the end of the unit to run across the roof

    before entering the building. Choice factors to choose a rooftop unit: inside and

    outside design temperatures, required airflow, mixed air temperature, and the required

    sensible and latent cooling loads.

  • Chapter - 3 Zoning Design, Central Plants and Hydronic Systems

    Modern Approach to HVAC Design and its Future Trend 18

    Figure 3.5 - Rooftop Unit

    3.2.2.4 Split Systems

    In the split system, the compressor/condenser part of the refrigeration system separate

    from the evaporator coil and connected by the refrigerant lines to the air system,

    which includes the evaporator.

    Figure 3.6 - Split System

    3.3 Multiple Zone Air Systems

    In many buildings, the unit must serve several zones, and each zone has its own

    varying load. To maintain temperature control, each zone has an individual thermostat

    that controls the volume and/or temperature of the air coming into the zone.

    A system thermodynamically similar to the dual-duct system, the multizone

    system features a different layout. The multizone system is not as energy efficient as

    the VAV system, and requires a separate duct to each zone. However, the multizone

    system has the advantage of requiring no maintenance outside the mechanical room,

    except for the zone temperature-sensors and associated cable.

    All-air systems advantages:

    Centrally located equipment

  • Chapter - 3 Zoning Design, Central Plants and Hydronic Systems

    Modern Approach to HVAC Design and its Future Trend 19

    Least infringement on conditioned floor space

    Greatest potential for the use of an economizer cycle

    Zoning flexibility and choice

    Full design freedom

    Generally good humidity control

    All-air systems disadvantages:

    Increased space requirements

    Construction dust

    Closer coordination required

    Figure 3.7 - Mixing at the Air Conditioning Unit in a Multizone System

    3.3.1 Three Deck, Multizone System

    The more modern introduction of the third, neutral duct to the multizone system,

    avoids the conflict of concurrent heating and cooling.

    3.3.2 Dual Path, Outside Air System

    This system could be used to reduce the problem with excess moisture in the air that

    arises in warm/hot, humid climates.

    3.3.3 Single-Duct, Zoned Reheat, Constant Volume Systems

    Reheat is the simplest system, known for both its reliability and the down side, its

    high energy wastage. The reheat system permits zone control by reheating the cool

    airflow to the temperature required for a particular zone.

  • Chapter - 3 Zoning Design, Central Plants and Hydronic Systems

    Modern Approach to HVAC Design and its Future Trend 20

    Figure 3.8 - Reheat System

    3.3.4 Single-Duct, Variable Air Volume Systems

    The variable air volume system is designed with a volume control damper, controlled

    by the zone thermostat, in each zone. VAV system adjusts for varying cooling loads

    in different zones by individually throttling the supply air volume to each zone.

    Figure 3.9 - Variable Air Volume System

    3.3.5 Dual-Duct, Variable Air Volume System

    A modification of the dual-duct system, this system uses variable volume dual-duct

    boxes to provide the thermal efficiency of the VAV system, while maintaining higher

    air flows, and thus better room air circulation when heating is required.

    3.3.6 By Pass Box Systems

    A variation on the VAV system, the bypass system, is suitable for providing good

    control in smaller systems and for constant flow over a direct-expansion cooling coil.

    Designers must be cautious to ensure that bypassed air goes straight back to the air

    conditioning unit, but it is generally a simple system to design.

  • Chapter - 3 Zoning Design, Central Plants and Hydronic Systems

    Modern Approach to HVAC Design and its Future Trend 21

    Figure 3.10 - By-Pass Boxes on Each Zone

    3.3.7 Constant Volume Dual-Duct, All-Air Systems

    In a dual-duct system, cooling and heating coils are placed in separate ducts, and the

    hot and cold air flow streams are mixed, as needed, for temperature control within

    each zone. A very attractive feature of the dual-duct system is that there are no reheat

    coils near the zones, so the problems of leaking hot water coils is avoided.

    Figure 3.11 - Dual-Duct System, Double Line Diagram

    3.4 Central Plants

    Central plants include boilers, producing steam or hot water, and chillers, producing

    chilled water. These pieces of equipment can satisfy the heating and cooling

    requirements for a complete building. In a central plant, the boilers and chillers are

    located in a single space in the building, and their output is piped to all the various air-

    conditioning units and systems in the building. Their initial cost is often higher than

  • Chapter - 3 Zoning Design, Central Plants and Hydronic Systems

    Modern Approach to HVAC Design and its Future Trend 22

    packaged units and they require installation floor area as well as space through the

    buildings for distribution pipes.

    The main items of equipment found in central plants are:

    Boilers are pressure vessels and their installation and operation are strictly

    prescribed by codes.

    Chillers come in a huge range of sizes and types. Their particular

    requirements for chilled water piping and specialized control. The job of the

    chiller is to remove heat from the chilled water and reject it to the condenser.

    Cooling towers are devices used to cool water by evaporation. Water is

    sprayed or dripped over material with a large surface area, while outdoor air is

    drawn through.

    3.4.1 Boilers

    Boilers are pressure vessels used to produce steam or hot water. The critical design

    factor for boilers is pressure. A low-pressure steam boiler operates at a pressure of no

    more than 15 psig. Low-pressure hot water boilers are allowed up to 160 psig.

    3.4.1.1 Boiler Components

    Boilers have two sections: The combustion section is the space where the fuel air

    mixture burns; the second section of the boiler is the heat transfer section. In all

    boilers there is a need to modulate the heat input.

    In steam systems, there is a constant loss of water in the condensate return

    system. To prevent problems with solids build-up in the boiler and distribution pipe

    corrosion, continuous high quality water treatment is required.

    Figure 3.12 - Hot Water Heating System with Two Boilers

  • Chapter - 3 Zoning Design, Central Plants and Hydronic Systems

    Modern Approach to HVAC Design and its Future Trend 23

    3.4.2 Water Chillers

    The chiller includes an evaporator or liquid cooler, a condenser, and a compressor.

    The main energy-using components of chiller plant are the motors that drive the

    compressors, chilled water pumps, condenser water pumps, air-cooled condenser fans,

    and cooling tower fans.

    The water that flows through the evaporator coil gives up heat, and becomes

    cooler. The cooled water is referred to as chilled water. The water that flows

    through the condenser, called the condenser water, becomes warmer and is piped

    away to a cooling tower to be cooled before returning to the condenser to be warmed

    again.

    The two categories of water chillers used in HVAC systems are:

    i. Mechanical chiller

    ii. Absorption chiller

    Figure 3.13 - Water Chiller with Water Cooled Condenser

    Variable chilled water flow arrangement is shown in the figure. In the diagram, at full

    load, both chillers and pumps are running, and the valves in the coil circuits are fully

    open. As the load decreases, the temperature sensors, in front of each coil, start to

    close their valve, restricting the flow through the coil.

  • Chapter - 3 Zoning Design, Central Plants and Hydronic Systems

    Modern Approach to HVAC Design and its Future Trend 24

    Figure 3.14 - Two Chiller Piping with Constant Chiller Flow

    3.4.3 Centrifugal Water Chillers

    The centrifugal refrigeration machine was the first practical method of air

    conditioning large spaces. The heart of a centrifugal water chiller is the centrifugal

    compressor.

    Figure 3.15 - Centrifugal Mechanical Chiller

    3.4.3.1 Central Plant Water Chiller Optimization

    To determine if the central plant can be optimized, the first step is to conduct an

    energy survey and testing of the systems operating performance. The second step is

  • Chapter - 3 Zoning Design, Central Plants and Hydronic Systems

    Modern Approach to HVAC Design and its Future Trend 25

    to consider the options. The third step to any proposed retrofit is to consider the

    consequences of the retrofit before starting the project.

    The following are some ways to optimize the chiller plant:

    Select Proper Air Quantities and Heat Transfer Surfaces for the Cooling Coils

    Raise the Evaporator Temperature

    Lower Condenser Water Temperature

    Optimize Chillers in Series

    Optimize Chillers in Parallel

    Install Water-side Economizers

    3.4.4 Cooling Towers

    Cooling towers are a particular type of big evaporative cooler. In the cooling tower,

    warm water is exposed to a flow of air, causing evaporation and therefore, cooling of

    the water. The psychrometric chart can be used to illustrate the workings of the

    cooling tower.

    Figure 3.16 - Typical Natural-Draft

    Open Cooling Tower

    Figure 3.17 - Induced Draft, Closed

    Circuit Cooling Tower

    3.5 Hydronic Systems

    In some buildings, these systems will use low-pressure steam instead of hot water for

    heating. The performance is generally similar to hot water systems, with higher

    outputs due to the higher temperature of the steam.

  • Chapter - 3 Zoning Design, Central Plants and Hydronic Systems

    Modern Approach to HVAC Design and its Future Trend 26

    Hydronic systems are most commonly used where high and variable sensible

    heating and/or cooling loads occur. These are typically

    Perimeter zones, with high solar heat gains or

    Perimeter areas in cooler to cold climates where there are substantial

    perimeters heat losses

    Hydronic systems advantages:

    i. Noise reduction virtually silent operation

    ii. Economy due to limited operational costs large amounts of heat from small

    local equipment

    iii. Economy due to limited first costs pipes are small compared to ducts for

    the same heat transfer around a building

    iv. Energy efficiency low energy consumption at low load

    Hydronic systems disadvantages:

    i. Ventilation provision of outside air for ventilation is either absent or poor

    ii. System failure danger from freezing and from leaks

    iii. Humidity control is either absent or generally poor

    3.5.1 Natural Convection and Low Temperature Radiation Heating Systems

    The very simplest water heating systems consist of pipes with hot water flowing

    through them. The output from a bare pipe is generally too low to be effective, so an

    extended surface is used to dissipate more heat. The radiator emits heat by both

    radiation and convection. These water heaters can all be controlled by varying the

    water flow or by varying the water supply temperature.

  • Chapter - 3 Zoning Design, Central Plants and Hydronic Systems

    Modern Approach to HVAC Design and its Future Trend 27

    Figure 3.18 - Wall-Mounted Single and Double Panel Radiators

    3.5.2 Panel Heating and Cooling

    Radiant floors use the floor surface for heating. Ceilings can also be used for heating

    and/or cooling. The system has the advantage of taking up no floor or wall space and

    it collects no more dirt than a normal ceiling.

    Figure 3.19 - Concrete Radiant Floor

    3.5.3 Fan Coils

    Fan coils can be used for just heating or for both heating and cooling. When the fan-

    coil is used for heating, the hot water normally runs through the unit continuously.

    When the thermostat switches the fan on, full output is achieved. Some units are

    provided with two or three speed controls for the fan, allowing adjustment in output

    of heat and generated noise. Types of fan coils include: Hot-water fan coils,

    changeover systems, and four-pipe systems.

  • Chapter - 3 Zoning Design, Central Plants and Hydronic Systems

    Modern Approach to HVAC Design and its Future Trend 28

    Figure 3.20 - Typical Fan-Coil Unit

    3.5.4 Fan Curves

    A fan curve shows the performance of a fan at various static pressures and volumes of

    airflow. At the top left of the curve is the block tight static pressure condition at

    maximum static pressure and zero airflow.

    3.5.5 Two Pipe Induction Systems

    The two-pipe induction system uses ventilation air at medium pressure to entrain

    room air across a coil that either heats or cools. The units are typically installed under

    a window, and when the air system is turned off, the unit will provide some heat by

    natural convection if hot water is flowing through the coil.

    Figure 3.21 - Induction Unit

  • Chapter - 3 Zoning Design, Central Plants and Hydronic Systems

    Modern Approach to HVAC Design and its Future Trend 29

    3.5.6 Water Source Heat Pumps

    Water source heat pumps are refrigeration units that can either pump heat from water

    into the zone or extract heat from the zone and reject it into water. This ability finds

    two particular uses in building air conditioning:

    a) The use of heat from the ground

    b) The transfer of heat around a building

    3.6 Hydronic System Architecture

    The basic layout options for heating and cooling piping arrangements that distribute

    water or steam, hydronic circuits. In each case, a flow of water or steam is distributed

    from a either a central boiler or a chiller, the refrigeration equipment used to produce

    chilled water, to the hydronic circuits.

    3.6.1 Steam Systems

    Principal ideas of this section include: how steam is used; its behavior as a gas and

    how it condenses as it gives up its latent heat; how the resultant condensate is drained

    out of the steam pipes by traps and then returned to the boiler, to be boiled into steam

    again.

    Figure 3.22 - Steam System

    3.6.2 Water Systems

    In the water systems, we need economical direct arrangement and the more costly, but

    largely self-balancing, reverse-return piping arrangement. The advantages of water

    over steam include the fact that water is safer and more controllable than steam.

    Water System Design Issues are: Pipe Construction and Pipe Distribution.

  • Chapter - 3 Zoning Design, Central Plants and Hydronic Systems

    Modern Approach to HVAC Design and its Future Trend 30

    3.6.3 Hot Water Systems

    Within buildings, hot water is the fluid that is most commonly used for heat

    distribution. The amount of heat that is transferred is proportional to the temperature

    difference between supply and return.

    3.6.4 Chilled Water Systems

    Because chilled water systems need constant water flow through the chiller

    evaporator, the economies of variable flow can be achieved through decoupled and

    distributed piping arrangements.

    Figure 3.23 - Chiller System with Decoupled Flows

    3.6.5 Condenser Water System

    Condenser water is water that flows through the condenser of a chiller to cool the

    refrigerant. Condenser water from a chiller typically leaves the chiller at 95F and

    returns from the cooling tower at 85F or cooler.

    Figure 3.24 - Evaporative Cooling Tower

  • CHAPTER FOUR

    Control Systems and

    Thermal Comforts

  • Chapter - 4 Control Systems and Thermal Comforts

    Modern Approach to HVAC Design and its Future Trend 31

    4.1 HVAC Control Systems

    The purpose of an HVAC automatic control system is to start, stop or regulate the

    flow of air, water or steam and to provide stable operation of the system by

    maintaining the desired temperature, humidity and pressure. The automatic control

    system is a group of components, each with a definite function designed to interact

    with the other components so that the system is self-regulating. HVAC control

    systems are classified according to the source of power used for the operation of the

    various components. Whether the controls are a factory package or built-up on site,

    well-designed controls are a critical part of any HVAC system.

    The classifications and power sources are:

    a) Pneumatic Systems:

    Compressed air.

    b) Electric Systems:

    Low voltage electricity (normally 24 Volts)

    Line voltage electricity (normally 110 to 220 Volts)

    c) Electronic Systems (DDC):

    Low voltage electricity (normally 5 to 15 Volts).

    d) Electric- or Electronic-to-Pneumatic Systems:

    Electricity and compressed air.

    4.2 Control Loops

    Information flows in a circle from the sensor measuring the controlled variable to the

    controller where the current value of the controlled variable is compared to the

    desired value or set point.

    Figure 4.1 - Diagram of Control Loop

  • Chapter - 4 Control Systems and Thermal Comforts

    Modern Approach to HVAC Design and its Future Trend 32

    4.3 Control Modes

    All controllers are designed to take action in the form of an output signal to the

    controlled device. The output signal is a function of the error signal, which is the

    difference between the control point and the setpoint. The type of action the controller

    takes is called the control mode or control logic, of which there are three basic types:

    i. Two-position control

    ii. Floating control

    iii. Modulating control

    4.4 Control Types

    4.4.1 Self-powered Controls

    Self-powered Controls require no external power. Various radiator valves and ceiling

    VAV diffusers have self-powered temperature controls.

    4.4.2 Electric Controls

    Electric Controls are powered by electricity.

    On/off Electric Control

    Modulating Electric Controls.

    4.4.3 Pneumatic Controls

    Pneumatic controls, which use compressed air as the power source, are very simple

    and inherently analog, making them ideal for controlling temperature, humidity, and

    pressure.

    4.4.4 Electronic Controls

    Electronic Controls, use varying voltages and currents in semiconductors to provide

    modulating controls. They have never found great acceptance in the HVAC industry,

    since DDC offered much more usability at a much lower price.

    4.4.5 Direct Digital Controls, DDC

    Direct Digital Controls, DDC, are controls operated by one, or more, small computer

    processors. The computer processor uses a software program of instructions to make

  • Chapter - 4 Control Systems and Thermal Comforts

    Modern Approach to HVAC Design and its Future Trend 33

    decisions based on the available input information. The processor operates only with

    digital signals and has a variety of built-in interface components so that it can receive

    information and output control signals.

    Figure 4.2 - DDC Control Schematic

    4.4.5.1 Benefits of DDC:

    Direct Control, Precise Control, Dead Band and Control Sequence, Schedule

    Changes, Flexibility

    4.5 Control System Components

    4.5.1 Controllers

    A controller is a proportioning device designed to control dampers or valves to

    maintain temperature, humidity, or pressure. A controller may be direct acting or

    reverse acting. Types of controllers: thermostats, humidistats for humidity,

    pressurestats for pressure, master controllers to control submaster controllers, and

    receiver-controllers.

    4.5.1.1 Single Pressure Thermostat

    A single pressure thermostat may be a one-pipe, bleed-type or a two pipe, relay-type

    controller. The main air is introduced through a restrictor into the branch line between

    the thermostat and the controlled device.

    4.5.1.2 Dead Band Thermostat

    A dead band thermostat is a two-pipe controller that operates in the same manner as a

    single pressure, single temperature thermostat. Its used for energy conservation when

  • Chapter - 4 Control Systems and Thermal Comforts

    Modern Approach to HVAC Design and its Future Trend 34

    a temperature span or dead band is required between the heating and cooling

    setpoints.

    4.5.1.3 Dual Pressure Thermostat

    The summer/winter system provides for the seasonal requirements of either cooling or

    heating and, depending on the season, either chilled water or hot water is supplied to

    the water coil in the air handing unit.

    4.5.1.4 Humidistat

    Humidistats are similar in appearance to thermostats; however, instead of using a

    bimetal strip as the sensor, humidity is sensed by a hygroscopic, or water absorbing,

    material such as human hair, nylon, silk, wood or leather.

    4.5.1.5 Master/Submaster Controller

    A master controller is one which transmits its output signal to another controller. The

    second controller is called the submaster. The submasters setpoint will change as the

    signal from the master controller changes. This is a reset type of control.

    4.5.1.6 Receiver-controller and Transmitter

    The receiver-controller and transmitter is the controlling device used most often in

    present day pneumatic HVAC control systems. The receiver-controller, like the other

    controllers, receives a signal from a sensor and then varies its branch output pressure

    to the controlled device. The sensing device for receiver-controllers is the transmitter.

    Transmitters are one-pipe, direct acting, bleed-type devices which use a restrictor in

    the supply line to help maintain the proper volume of compressed air between the

    transmitter and the receiver-controller.

    4.6 Energy Conservation

    The objective of energy conservation is to use less energy. This is accomplished by

    various methods, including recycling energy where useful. Energy conservation

    should be part of the entire life cycle of a building: it should be a consideration during

    the initial conception of a building, through its construction, during the operation and

    maintenance of the building throughout its life, and even in deconstruction. Energy

  • Chapter - 4 Control Systems and Thermal Comforts

    Modern Approach to HVAC Design and its Future Trend 35

    efficient the system as initially designed and installed the energy efficiency will

    degrade unless it is operated correctly and deliberately maintained.

    4.7 Parameters to Control

    4.7.1 Importance of Humidity Control

    1) Stability and longer shelf life: Humidity control is important for the stability

    and longer shelf life of products. Controlled humidity decreases the

    decomposition rate of drugs. It will also help to maintain the physical stability

    of dosage form. As a result the shelf life of the dosage form will increase.

    2) Comfort requirement: Humidity is a comfort requirement. Suitable moisture

    level is required to offer a comfortable working environment for the operators.

    3) To inhibit microbial growth: Above 60% RH promotes bacterial growth. So

    relative Humidity should be maintained < 55% to inhibit microbial growth in

    various production areas.

    4) To facilitate various processes: Less humidity makes some problems to

    disinfect an area. On the other hand less humidity is required for drying

    process. Materials can be effectively dried in controlled humidity.

    5) Storage of EHGCS & water sensitive materials: Ideal storage condition of

    EHGCS is 45% - 60% RH. At low humidity the capsules become brittle and at

    high humidity they become flaccid and lose their shape. Moisture sensitive

    materials should also be stored in lower humidity.

    6) Production and packing of various dosage forms: Humidity control is

    essential for the manufacturing of various dosage forms.

    Capsule preparation: RH should be maintained 45% - 55% for proper

    encapsulation. Otherwise capsules will absorb moisture and become soft.

    Dry syrup preparation: < 50% RH is required for dry syrup

    preparation. Lump formation is possible due to over moisture.

    Hygroscopic tablet preparation: Controlled humidity is required for the

    granulation, compression, coating and packing of hygroscopic tablets.

    Over moisture may dissolve the materials.

    7) Maintenance of equipment: Humidity control is essential to maintain

    sophisticated QC instruments.

  • Chapter - 4 Control Systems and Thermal Comforts

    Modern Approach to HVAC Design and its Future Trend 36

    4.7.2 Importance of Temperature Control

    1) Stability and longer shelf life: Temperature control is important for the

    stability and longer shelf life of product. Controlled temperature decreases the

    decomposition rate of drugs. It will also help to maintain the physical stability

    of dosage form. As a result the shelf life of the dosage form will increase.

    2) Comfort requirement: Temperature is a comfort requirement. Suitable

    temperature is required to offer a comfortable working environment for the

    operators.

    3) To inhibit microbial growth: Microbial growth is accelerated by the

    optimum temperature. 370c temperature promotes the bacterial growth.

    Microbial growth can be inhibited by controlling temperature.

    4) Storage of EHGCS & thermo labile materials: Ideal storage condition of

    EHGCS is 25 - 300c. They lose their shape at high temperature. Moisture

    sensitive materials should also be stored in lower temperature.

    5) Production and packing of various dosage forms: Temperature control is

    essential for the manufacturing of various dosage forms.

    4.7.3 Importance of Dust Particle Control

    1) Purity of product

    2) Patients safety

    3) To inhibit microbial load

    4) Production and packing of various dosage forms

    4.8 Thermal Comfort

    Thermal comfort is primarily controlled by a buildings heating, ventilating and air-

    conditioning systems, though the architectural design of the building may also have

    significant influences on thermal comfort. Standard 55 defines thermal comfort as

    that condition of mind which expresses satisfaction with the thermal environment

    and is assessed by subjective evaluation.

    4.8.1 Factors Influencing Thermal Comfort

    There are seven factors which are influencing the thermal comfort. They are:

  • Chapter - 4 Control Systems and Thermal Comforts

    Modern Approach to HVAC Design and its Future Trend 37

    Personal

    1. Activity level

    2. Clothing

    Individual Characteristics

    3. Expectation

    Environmental Conditions and Architectural Effects

    4. Air temperature

    5. Radiant temperature

    6. Humidity

    7. Air speed

    4.8.1.1 Activity Level

    The human body continuously produces heat through a process call metabolism.

    This heat must be emitted from the body to maintain a fairly constant core

    temperature, and ideally, a comfortable skin temperature. As activity increases, from

    sitting to walking to running, so the metabolic heat produced increases.

    4.8.1.2 Clothing

    In occupied spaces, clothing acts as an insulator, slowing the heat loss from the body.

    To predict thermal comfort we must have an idea of the clothing that will be worn by

    the occupants. Due to the large variety of materials, weights, and weave of fabrics,

    clothing estimates are just rough estimates.

    4.8.1.3 Occupants Expectations

    Peoples expectations affect their perception of comfort in a building. Standard 55

    recognizes that the expectations for thermal comfort are significantly different in

    buildings where the occupants control opening windows, as compared to a

    mechanically cooled building.

    4.8.1.4 Air Temperature

    When we are referring to air temperature in the context of thermal comfort, we are

    talking about the temperature in the space where the person is located.

  • Chapter - 4 Control Systems and Thermal Comforts

    Modern Approach to HVAC Design and its Future Trend 38

    4.8.1.5 Radiant Temperature

    Radiant heat is heat that is transmitted from a hotter body to a cooler body with no

    effect on the intervening space. For internal spaces, where the temperature of the

    walls, floor and ceiling are almost the same as the air temperature, the radiant

    temperature will be constant in all directions and virtually the same as the air

    temperature.

    4.8.1.6 Humidity

    Low humidity: For some people, low humidity can cause specific problems,

    like dry skin, dry eyes and static electricity. However, low humidity does not

    generally cause thermal discomfort.

    High humidity: Standard 55 does define the maximum humidity ratio for

    comfort at 0.012 lb/lb. Since it is equivalent to 100% relative humidity at

    62F.

    4.8.1.7 Air Speed

    The higher the air speed over a persons body, the greater the cooling effect.

    4.9 Heat Flow and Heat Recovery

    4.9.1 Heat Flow

    Heat is energy in the form of molecules in motion. Heat flows from a warmer

    substance to a cooler substance. Heat energy flows downhill. Heat does not rise,

    heated air rises.

    4.9.1.1 Heat Transfer

    Heat naturally flows from a higher energy level to a lower energy level. When there is

    a temperature difference between two substances, heat transfer will occur. The greater

    the temperature difference, the greater the heat transfer.

    4.9.1.2 Types of Heat Transfer

    The three types of heat transfer are conduction, convection and radiation.

  • Chapter - 4 Control Systems and Thermal Comforts

    Modern Approach to HVAC Design and its Future Trend 39

    4.9.1.2.1 Conduction

    Conduction heat transfer is heat energy traveling from one molecule to another. A

    heat exchanger in an HVAC system uses conduction to transfer heat.

    4.9.1.2.2 Convection

    Heat transfer by convection is when some substance that is readily movable such as

    air, water, steam, or refrigerant moves heat from one location to another. An HVAC

    system uses convection in the form of air, water, steam and refrigerants in ducts and

    piping to convey heat energy to various parts of the system.

    4.9.1.2.3 Radiation

    Heat transferred by radiation travels through space without heating the space.

    Radiation or radiant heat does not transfer the actual temperature value.

    4.9.1.3 Heat Transfer Equations

    1) Air System - Sensible Heat Transfer Equation

    Btuh = cfm 1.08 TD

    2) Air Syatems - Total Heat Transfer Equation

    Btuh = cfm 4.5 h

    3) Water System - Heat Transfer Equation

    Btuh = gpm 500 TD

    4.9.2 Heat Recovery

    The objective of heat-recovery systems is to reduce the energy consumption and cost

    of operating a building by transferring heat between two fluids, such as exhaust air

    and outside air. In many cases, the proper application of heat-recovery systems can

    result in reduced energy consumption and lower energy bills, while adding little or no

    additional cost to building maintenance or operations.

    4.9.2.1 Heat Recovery Systems

    There are three basic types of heat recovery systems: comfort- to-comfort, process-to-

    comfort, and process-to-process.

  • Chapter - 4 Control Systems and Thermal Comforts

    Modern Approach to HVAC Design and its Future Trend 40

    4.9.2.1.1 Comfort- to-Comfort Heat Recovery Systems

    Comfort-to-comfort systems are typically used in HVAC applications. These heat

    recovery systems capture a buildings exhaust air and reuse the energy in that waste

    heat to precondition the outside air coming into the building. In comfort-to-comfort

    applications, the energy recovery process is reversible. To determine the amount of

    heat transferred, use the sensible heat transfer equation.

    Btuh = cfm 1.08 T

    4.9.2.1.2 Process-to-Comfort Heat Recovery Systems

    Process-to-comfort systems are generally sensible heat recovery only. Therefore, they

    are used only during the spring, fall, and winter month but there is no heat recovery

    during the summer months.

    4.9.2.1.3 Process-to-Process Heat Recovery Systems

    Process-to-process systems also perform sensible heat recovery only, usually full

    recovery, but in some cases, partial recovery can be performed if circumstances

    dictate.

  • CHAPTER FIVE

    Future Trend to HVAC

  • Chapter 5 Future Trend to HVAC

    Modern Approach to HVAC Design and its Future Trend 41

    5.1 Future Trend to HVAC

    Modern building and HVAC systems are required to be more energy efficient while

    adhering to an ever-increasing demand for better indoor air quality and performance.

    Economical consideration and environmental issues also need to be taken into

    account. These factors, as well as an increase in design liability and requirement to

    complete designs quickly, have placed unprecedented pressure on designer.

    Computers are seen as an important design tool that can reduce some of the strain.

    5.2 Future Revolution in HVAC Design

    Contemporary practice in heating, ventilation, and air conditioning (HVAC) is

    inadequate to fulfill the stringent demands of the 21st century. It is deficient in

    comfort, ventilation, indoor air quality, fire safety, energy efficiency, and resistance to

    terrorism.

    For several decades now, HVAC designers have known that they must make

    their systems more energy efficient, but combining efficiency with high standards of

    comfort and health has proven to be an elusive goal. It may seem that performance

    compromises are inescapable, but that is not true. Present problems stem from

    continuing along an evolutionary design path that took a wrong turn in the past.

    In this series of two articles, we will recognize flawed premises in present

    HVAC practice, make a major change in HVAC design, and eliminate the defects of

    HVAC equipment. We will find that it is possible to satisfy all the requirements that

    HVAC must meet during this century.

    5.3 Logic of the HVAC Revolution

    The accumulation of unsolved problems in contemporary HVAC requires us to stop

    and take a fresh look. While we exploit the lessons of past experience, we will

    abandon assumptions that are no longer relevant and change practices that fail to

    achieve optimum performance.

    HVAC today uses two broad approaches. For compartmentalized buildings, the

    dominant design approach is using centralized air handling systems that serve

    multiple zones. For smaller buildings, and for individual spaces whose conditioning

    requirements do not match the rest of the building, the dominant approach is using

    single-zone systems.

  • Chapter 5 Future Trend to HVAC

    Modern Approach to HVAC Design and its Future Trend 42

    The first step toward optimum HVAC is recognizing that multiple-zone air

    handling systems inherently cannot optimize all HVAC functions, nor can they

    operate with a high level of energy efficiency unless they seriously degrade the

    comfort and health functions of the systems. This is a theoretical limitation, not just a

    practical one. Therefore, multiple-zone HVAC systems must be abandoned.

    5.4 Optimized Function HVAC Design

    HVAC for this century must become fully optimized. Each comfort, health, and safety

    function required for each zone in the facility must be executed perfectly, and no

    energy waste is permitted. This criterion is entirely achievable by a disciplined design

    process that focuses on the system functions.

    This is the design sequence for optimized-function HVAC:

    i. Define all the conditioning functions that are needed for each application in

    the facility.

    ii. Define the spatial zones that correspond to each function.

    iii. For each zone, identify the kinds of equipment that can fulfill each function

    optimally.

    iv. Consolidate the equipment for each zone without compromising optimum

    performance.

    v. Provide optimum control for all operating conditions.

    5.5 Central Plant Equipment in Optimized Systems

    In the strictest sense, centralized plants especially cooling plants cannot optimize

    energy efficiency. A chiller must make water cold enough to serve the zone that needs

    the coldest water. This reduces the COP of the chiller in serving other zones. Also,

    central plants require pump energy. Hydronic systems provide advantages such as

    compact equipment and quiet operation. If central energy plants are used, the capable

    engineer will seek to minimize the tendency of individual zone requirements to

    degrade the efficiency of the central plant.

    5.6 Economics of Optimized-Function HVAC

    The idealized performance of optimized-function HVAC extends to its economics.

    Human productivity is the highest cost associated with HVAC. By definition,

  • Chapter 5 Future Trend to HVAC

    Modern Approach to HVAC Design and its Future Trend 43

    optimized-function HVAC provides the best comfort and health, so it offers the

    greatest productivity. The second-highest cost of HVAC is energy. Life-cycle cost is

    greatly reduced because optimized systems operate with the least possible energy.

    Optimized HVAC reduces the cost of equipment space and increases rentable space.

    Air handling rooms are eliminated. Duct space is minimized or eliminated.

    5.7 Onward to the Future

    Important changes in engineering often occur as seismic shifts, in which current

    practices are abruptly abandoned and nascent approaches quickly rise to dominance.

    Such upsets occur after years of increasing tension, when important realities grow too

    strong to ignore. We are now at such a point in the design of HVAC systems. A

    revolution in HVAC is needed to make buildings survivable in a century of very high

    energy costs and terrorist threats.

    The coming jolt in HVAC design is analogous to the extinction of the dinosaurs,

    which grew too large and unadoptable and were replaced by small, versatile

    mammals. Similarly, multiple zone air handling will be replaced by a versatile new

    design concept that we have called optimized-function HVAC. The change begins

    now. Design your HVAC systems for this century, not the last one.

  • CHAPTER SIX

    Conclusion

  • Chapter 6 Conclusion

    Modern Approach to HVAC Design and its Future Trend 44

    6.1 Conclusion

    The proper design of HVAC system is one of the most fundamental factors for the

    pharmaceutical industries. Systems have been designed for greatest assurance of

    consistent environmental conditions, with constant volume or reheat and high air

    change rates the order of the day. Steps to prevent cross-contamination in multi-

    product plants have been draconian, ranging from 100% fresh air or exhaust to

    multiple series HEPA filters in supply and exhaust. Developments in processing

    equipment, isolation technology and a risk or science-based approach to ensuring

    parameters of "strength, identity, safety, purity, and quality," open a new world of

    possibilities for HVAC in pharmaceutical facilities.

    The engineers are trying to modernization the HVAC design. Now more than

    ever, regulators and quality professionals are open to the idea of managing the risks

    inherent in environmental control rather than attempting to eliminate them and

    creating new ones in the process. This requires a cross-functional approach, engaging

    the departments of quality, devel