modern approach to hvac design and its future trend
DESCRIPTION
M.Pharm ProjectTRANSCRIPT
-
MODERN APPROACH TO HVAC DESIGN AND
ITS FUTURE TREND
A dissertation submitted to the Department of Pharmacy,
The University of Asia Pacific in the partial fulfillment of the
requirements for the degree of Master of Pharmacy in
Pharmaceutical Technology
SUBMITTED BY
Md. Hasif Sinha
Registration No: 09207021
Roll No: 21
DEPARTMENT OF PHARMACY
The University of Asia Pacific
Date of Submission: October 18, 2010
-
Table of Contents
i
Table of Contents
Purpose of the Study _________________________________________ vi
Abstract ___________________________________________________ vii
List of Chapters
Chapter
No.
Chapter
Name
Page
No.
1 Introduction to HVAC 1
1.1
1.2
1.3
1.4
1.4.1
1.4.2
1.4.3
1.4.4
1.4.5
Introduction
Objective of HVAC System
Scope of Modern HVAC
HVAC System
Types of HVAC Systems
Heating
Ventilating
Air-Conditioning System
Efficiency
1
1
1
2
2
3
3
3
4
2 HVAC System Choosing and Designing 5
2.1
2.1.1
2.2
2.2.1
2.2.2
2.2.3
2.2.4
2.2.5
2.2.6
2.3
2.3.1
2.4
2.4.1
2.4.1.1
2.4.1.2
2.4.1.3
2.4.1.4
2.4.1.4.1
2.4.1.4.2
2.4.1.4.3
Choosing an HVAC System
HVAC System Selection Guidelines
Choosing an Air-Conditioning System
Building Design
Location Issues
Utilities: Availability and Cost
Indoor Requirements and Loads
Client Issues
System Choice
Unitary System Selection Guidelines
Factors to Consider When Selecting Unitary Systems
HVAC Design
Design of an Air Handling Unit
Sub-Systems of AHU
Air Flow Patterns
Filters Positions
Air Circulation System
Air Re-Circulation
Ventilation with 100% fresh air (no air re-circulation)
Ventilation with re-circulated air with make-up air
5
5
6
6
6
7
7
7
7
8
8
8
8
8
9
11
12
12
13
13
-
Table of Contents
ii
3 Zoning Design, Central Plants and Hydronic Systems 14
3.1
3.1.1
3.1.2
3.2
3.2.1
3.2.2
3.2.2.1
3.2.2.2
3.2.2.3
3.2.2.4
3.3
3.3.1
3.3.2
3.3.3
3.3.4
3.3.5
3.3.6
3.3.7
3.4
3.4.1
3.4.1.1
3.4.2
3.4.3
3.4.3.1
3.4.4
3.5
3.5.1
3.5.2
3.5.3
3.5.4
3.5.5
3.5.6
3.6
3.6.1
3.6.2
3.6.3
3.6.4
3.6.5
Zone
Zoning Design
Controlling the Zone
Single Zone Air Handlers
Examples of Buildings with Single-zone Package Air-
Conditioning Units
Air-Handling Unit Components
Refrigeration Equipment
System Performance Requirements
Rooftop Units
Split Systems
Multiple Zone Air Systems
Three Deck, Multizone System
Dual Path, Outside Air System
Single-Duct, Zoned Reheat, Constant Volume Systems
Single-Duct, Variable Air Volume Systems
Dual-Duct, Variable Air Volume System
By Pass Box Systems
Constant Volume Dual-Duct, All-Air Systems
Central Plants
Boilers
Boiler Components
Water Chillers
Centrifugal Water Chillers
Central Plant Water Chiller Optimization
Cooling Towers
Hydronic Systems
Natural Convection and Low Temperature Radiation
Heating Systems
Panel Heating and Cooling
Fan Coils
Fan Curves
Two Pipe Induction Systems
Water Source Heat Pumps
Hydronic System Architecture
Steam Systems
Water Systems
Hot Water Systems
Chilled Water Systems
Condenser Water System
14
14
15
15
15
16
17
17
17
18
18
19
19
19
20
20
20
21
21
22
22
23
24
24
25
25
26
27
27
28
28
29
29
29
29
30
30
30
-
Table of Contents
iii
4 Control Systems and Thermal Comfort 31
4.1
4.2
4.3
4.4
4.4.1
4.4.2
4.4.3
4.4.4
4.4.5
4.4.5.1
4.5
4.5.1
4.5.1.1
4.5.1.2
4.5.1.3
4.5.1.4
4.5.1.5
4.5.1.6
4.6
4.7
4.7.1
4.7.2
4.7.3
4.8
4.8.1
4.8.1.1
4.8.1.2
4.8.1.3
4.8.1.4
4.8.1.5
4.8.1.6
4.8.1.7
4.9
4.9.1
4.9.1.1
4.9.1.2
4.9.1.2.1
4.9.1.2.2
4.9.1.2.3
4.9.1.3
4.9.2
4.9.2.1
4.9.2.1.1
4.9.2.1.2
4.9.2.1.3
HVAC Control Systems
Control Loops
Control Modes
Control Types
Self-powered Controls
Electric Controls
Pneumatic Controls
Electronic Controls
Direct Digital Controls, DDC
Benefits of DDC
Control System Components
Controllers
Single Pressure Thermostat
Dead Band Thermostat
Dual Pressure Thermostat
Humidistat
Master/Submaster Controller
Receiver-controller and Transmitter
Energy Conservation
Parameters to Control
Importance of Humidity Control
Importance of Temperature Control
Importance of Dust Particle Control
Thermal Comfort
Factors Influencing Thermal Comfort
Activity Level
Clothing
Occupants Expectations
Air Temperature
Radiant Temperature
Humidity
Air Speed
Heat Flow and Heat Recovery
Heat Flow
Heat Transfer
Types of Heat Transfer
Conduction
Convection
Radiation
Heat Transfer Equations
Heat Recovery
Heat Recovery Systems
Comfort- to-Comfort Heat Recovery Systems
Process-to-Comfort Heat Recovery Systems
Process-to-Process Heat Recovery Systems
31
31
32
32
32
32
32
32
32
33
33
33
33
33
34
34
34
34
34
35
35
36
36
36
36
37
37
37
37
38
38
38
38
38
38
38
39
39
39
39
39
39
40
40
40
-
Table of Contents
iv
5 Future Trend to HVAC 47
5.1
5.2
5.3
5.4
5.5
5.6
5.7
Future Trend to HVAC
Future Revolution in HVAC Design
Logic of the HVAC Revolution
Optimized Function HVAC Design
Central Plant Equipment in Optimized Systems
Economics of Optimized-Function HVAC
Onward to the Future
41
41
41
42
42
42
43
6 Conclusion 44
6.1 Conclusion 44
List of Figures
Figure
No.
Figure
Headline
Page
No.
1.1 Air-Conditioning Plant 4
2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
Sub-systems of AHU
(a) Turbulent Air Flow, (b)Uni-directional or Laminar Air Flow
Room 1, 2 & 3 with different air flow patterns and exhaust systems
AHU mounted final filter
Filter in terminal position
HVAC installation feeding 3 rooms
HVAC installation feeding 2 rooms
Ventilation with 100% fresh air (no air re-circulation)
Ventilation with re-circulated air with make-up air
9
10
10
11
11
12
12
13
13
3.1
3.2
3.3
3.4
3.5
3.6
3.7
3.8
3.9
3.10
3.11
3.12
3.13
3.14
3.15
3.16
3.17
3.18
3.19
3.20
Building Plan
Single Zone Rooftop Air-Conditioning Unit, Energy Supplies
Air-Conditioning System: Single-Zone Air Handler
Basic Vapor Compression Refrigeration Cycle
Rooftop Unit
Split System
Mixing at the Air Conditioning Unit in a Multizone System
Reheat System
Variable Air Volume System
By-Pass Boxes on Each Zone
Dual-Duct System, Double Line Diagram
Hot Water Heating System with Two Boilers
Water Chiller with Water Cooled Condenser
Two Chiller Piping with Constant Chiller Flow
Centrifugal Mechanical Chiller
Typical Natural-Draft Open Cooling Tower
Induced Draft, Closed Circuit Cooling Tower
Wall-Mounted Single and Double Panel Radiators
Concrete Radiant Floor
Typical Fan-Coil Unit
14
16
16
17
18
18
19
20
20
21
21
22
23
24
24
25
25
27
27
28
-
Table of Contents
v
3.21
3.22
3.23
3.24
Induction Unit
Steam System
Chiller System with Decoupled Flows
Evaporative Cooling Tower
28
29
30
30
4.1
4.2
Diagram of Control Loop
DDC Control Schematic
31
33
References
-
Purpose of the study
vi
Purpose of the Study
The purpose of the study on the topic Modern Approach HVAC Design and its
Future Trend is enormous. The main focus is on the proper choosing and designing
of HVAC systems in order to achieve more reliable, dynamic and successful future in
the pharmaceutical industries HVAC systems. To maintaining the air cleanliness we
need to prepare perfect HVAC design and control systems. The air pressure, air flow
velocity, direction of air flow, make-up and fresh air flow system, air filtration and
other environmental factors such as temperature and humidity should be controlled
properly. The HVAC systems are divided into components and controls for air, water,
heating, ventilating and air conditioning to clearly illustrate the way in which each
system, subsystem, control or component contributes to providing the desired indoor
environment. There are several zone air systems in the pharmaceutical industry like
single zone air system and multiple zone air systems. The building, zoning areas,
machineries, and equipments should be design perfectly to control the air cleanliness,
particle contaminations, and cGMP regulations. We also need to focus on cost
effectiveness of the HVAC system. Some of the many cost concerns include initial or
installation cost, operating and maintenance cost, and equipment replacement costs.
Another cost concern that may be overlooked by the designer is the cost associated
with equipment failure. The best situation is when designer and owner are both
involved in the HVAC selection process. So the proper designing of an HVAC system
is not an easy process. The core purpose of an HVAC system is to provide and
maintain environmental conditions within an area. The type of system selected is
determined by the mechanical designers knowledge of systems and the building
owners financial and functional goals.
-
Abstract
vii
Abstract
HVAC is particularly important in the design of medium to large industrial and office
buildings where safe and healthy building conditions are regulated with temperature
and humidity, as well as "fresh air" from outdoors. Depending on the complexity of
the requirements, the HVAC designer must consider many more issues than simply
keeping temperatures comfortable. The proper design of HVAC system is one of the
most fundamental factors for the pharmaceutical industries. The engineers are trying
to modernization the HVAC design on the focusing of various important factors such
as zoning design, central plants, hydronic systems, thermal comfort, and control
systems. Systems have been designed for greatest assurance of consistent
environmental conditions, with constant volume or reheat and high air change rates
the order of the day. Steps to prevent cross-contamination in multi-product plants
have been draconian, ranging from 100% fresh air or exhaust to multiple series HEPA
filters in supply and exhaust. Developments in processing equipment, isolation
technology and a risk or science-based approach to ensuring parameters of "strength,
identity, safety, purity, and quality," open a new world of possibilities for HVAC in
pharmaceutical facilities.
-
CHAPTER ONE
Introduction to HVAC
-
Chapter - 1 Introduction to HVAC
Modern Approach to HVAC Design and its Future Trend 1
1.1 Introduction
HVAC an initialism that stands for the closely related functions of "Heating,
Ventilating, and Air Conditioning" the technology of indoor or automotive
environmental comfort. HVAC system design is a major sub-discipline of mechanical
engineering, based on the principles of thermodynamics, fluid mechanics, and heat
transfer. Refrigeration is sometimes added to the field's abbreviation as HVAC&R or
HVACR, or ventilating is dropped as in HACR.
HVAC is particularly important in the design of medium to large industrial and
office buildings where safe and healthy building conditions are regulated with
temperature and humidity, as well as "fresh air" from outdoors.
Depending on the complexity of the requirements, the HVAC designer must
consider many more issues than simply keeping temperatures comfortable. We need
to discuss about the fundamental concepts that are used by designers to make
decisions about system design, operation, and maintenance.
1.2 Objective of HVAC System
The goal for a HVAC system is to provide proper air flow, heating, and cooling to
each room. In HVAC Industries there are so many standard organizations such as
ASHRAE, SMACNA, ACCA, Uniform Mechanical Code, International Mechanical
Code, and AMCA have been established to support the industry and encourage high
standards and achievement.
It is important that the objective criteria for system success are clearly identified
at the start of the project, because different requirements need different design
considerations.
1.3 Scope of Modern HVAC
Although there have been great advances in HVAC, there are several areas where
active research and debate continue.
Indoor air quality is one that directly affects us. In many countries of the world
there is a rapid rise in asthmatics and increasing dissatisfaction with indoor-air-quality
in buildings and planes. A significant scientific and engineering field has developed to
investigate and address these issues.
-
Chapter - 1 Introduction to HVAC
Modern Approach to HVAC Design and its Future Trend 2
Energy conservation is an ongoing challenge to find novel ways to reduce
consumption in new and existing buildings without compromising comfort and indoor
air quality. Energy conservation requires significant cooperation between disciplines.
1.4 HVAC System
Commercial heating, ventilating, and air conditioning (HVAC) systems provide the
people working inside buildings with conditioned air so that they will have a
comfortable and safe work environment. Air quality and the condition of the air
are two very important factors. By conditioned air and good air quality, we mean
that air should be clean and odor-free and the temperature, humidity, and movement
of the air will be within certain acceptable comfort ranges.
ASHRAE, the American Society of Heating, Refrigerating and Air
Conditioning Engineers, has established standards which outline indoor comfort
conditions that are thermally acceptable to 80% or more of a commercial buildings
occupants. Generally, these comfort conditions, sometimes called the comfort zone,
are between 68F and 75F for winter and 73F to 78F during the summer. Both
these ranges are for room air at approximately 50% relative humidity and moving at a
slow speed (velocity) of 30 feet per minute or less.
An HVAC system is simply a group of components working together to move
heat to where it is wanted, or remove heat from where it is not wanted, and put it
where it is unobjectionable (the outside air).
1.4.1 Types of HVAC Systems
The basic types of HVAC systems used in commercial buildings are all-air, air and
water, all-water, and unitary. Water systems are also called hydronic systems.
Hydronic is the term used for heating and cooling with liquids. All-air systems
provide heated or cooled air to the conditioned space through a ductwork system. The
basic types of all-air duct systems are: single-zone, multizone, dual or double duct,
terminal reheat, constant air volume, variable air volume (VAV), and combination
systems.
-
Chapter - 1 Introduction to HVAC
Modern Approach to HVAC Design and its Future Trend 3
1.4.2 Heating
Heating is one of the most important fact in the HVAC system. Heating should be
provide properly to maintain the desire temperature. There are many different types of
standard heating systems. The main components of heating systems are: Boilers,
Furnaces and Heating Coils.
1.4.3 Ventilating
Ventilating is the process of "changing" or replacing air in any space to control
temperature or remove moisture, odors, smoke, heat, dust, airborne bacteria, carbon
dioxide, and to replenish oxygen. Ventilation includes both the exchange of air to the
outside as well as circulation of air within the building. It is one of the most important
factors for maintaining acceptable indoor air quality in buildings. Methods for
ventilating a building may be divided into mechanical/forced and natural types.
Ventilation is used to remove unpleasant smells and excessive moisture, introduce
outside air, to keep interior building air circulating, and to prevent stagnation of the
interior air.
1.4.4 Air-Conditioning System
Air Conditioning within the HVAC system refers to the removal of heat from a room
or building in order to cool the air to a desired temperature. The heat transfer process
works through mediums like ice, air, water, and chemicals that are naturally cooler
than the air in the room. The air conditioning system also controls humidity levels
within the building and cools the air through a process of condensing and evaporating
a desired liquid through a series of coils, much like a refrigerator. Central air
conditioning systems that cool entire buildings can work through the same ductwork
as some central heating systems. The air is forced through the ductwork and back to
the air conditioner where it is cooled and sent back through the system. Central
cooling systems often incorporate an evaporator that collects the condensation from
the cooling coils and therefore dehumidifies the air. The resulting condensation can
then be manually removed or drained outside.
-
Chapter - 1 Introduction to HVAC
Modern Approach to HVAC Design and its Future Trend 4
Figure 1.1 - Air-Conditioning Plant
1.4.5 Efficiency
Although most HVAC systems utilize the same ductwork for both heating and
cooling, forced-air ventilation is not necessarily the most energy efficient. By creating
zones central heating and cooling units can be better utilized through a variety of
thermostats that regulate heat and air when needed. With zones, rooms that require
heat and air can maintain comfortable while unused areas can minimize temperature
control and save energy. The most energy efficient form of heating is geothermal
heating, a method of using natural heat sources to warm buildings. Although
using HVAC systems help save some cost and energy through the use of proper air
flow and thermodynamics, the best way to maximize the efficiency of an HVAC
system is to install it in a properly designed building. Buildings need to be designed
around the potential benefits of solar energy and passive heating and cooling
opportunities. Without proper architecture, HVAC systems work harder and waste
energy.
-
CHAPTER TWO
HVAC System Choosing and Designing
-
Chapter - 2 HVAC System Choosing and Designing
Modern Approach to HVAC Design and its Future Trend 5
2.1 Choosing an HVAC System
The purpose of an HVAC system is to provide and maintain environmental conditions
within an area called the conditioned space. The type of system selected is
determined by the mechanical designers knowledge of systems and the building
owners financial and functional goals.
It is the designers responsibility to consider the various systems and select the
one that will provide the best combination of initial cost, operating cost, performance,
and reliability based on his understanding of the owners needs and goals. In the
selection process all factors must be analyzed, but cost of installation and operation
are usually foremost.
Some of the many cost concerns include initial or installation cost, operating
and maintenance cost, and equipment replacement costs. Another cost concern that
may be overlooked by the designer is the cost associated with equipment failure. The
best situation is when designer and owner are both involved in the HVAC selection
process.
The goals of choosing of an HVAC system are-
To provide an acceptable level of occupancy comfort
To provide temperature and humidity control for process function
To maintain good indoor air quality (IAQ)
To minimize energy requirements and costs
2.1.1 HVAC System Selection Guidelines
Each of the following issues should be taken into consideration each time an HVAC
system is selected.
1) Financial factors
Initial cost
Operating costs
Maintenance and repair cost
Equipment replacement or upgrading cost
Equipment failure cost
Return on investment (ROI)
Energy costs
-
Chapter - 2 HVAC System Choosing and Designing
Modern Approach to HVAC Design and its Future Trend 6
2) Building conditions
New or existing building or space
Location
Orientation
Architecture
Climate and shading
Configuration
Construction
Codes and standards
3) Usage
Occupancy
Process equipment
4) Energy availability
Types
Reliability
5) Control scheme
Zone control
Individual control
2.2 Choosing an Air-Conditioning System
The factors or parameters that influence system choice can conveniently be divided
into the following groups:
2.2.1 Building Design
The design of the building has a major influence on system choice.
2.2.2 Location Issues
The building location determines the weather conditions that will affect the building
and its occupants. For the specific location we will need to consider factors like:
site conditions
peak summer cooling conditions
summer humidity
peak winter heating conditions
-
Chapter - 2 HVAC System Choosing and Designing
Modern Approach to HVAC Design and its Future Trend 7
wind speeds
sunshine hours
typical snow accumulation depths
The building location and, at times, the client, will determine what national, local, and
facility specific codes (Building code, Fire code, Energy code) must be followed.
Typically, the designer must follow the local codes.
2.2.3 Utilities: Availability and Cost
The choice of system can be heavily influenced by available utilities and their costs to
supply and use. So, if chilled water is available from the adjacent building, it would
probably be cost advantageous to use it, rather than install new unitary refrigerant-
based units in the new building.
2.2.4 Indoor Requirements and Loads
The location effects and indoor requirements provide all the necessary information for
load calculation for the systems.
The thermal and moisture loads
Outside ventilation air
Zoning
2.2.5 Client Issues
The designer has to consider the clients requirements both for construction and for
in-use costs. The client may wish to finance a very sophisticated and more expensive
system to achieve superior performance, or to reduce in-use costs. In addition to cost
structures, the availability of maintenance staff must be considered. A building at a
very remote site should have simple, reliable systems, unless very competent and
well-supported maintenance staff will be available.
2.2.6 System Choice
While all the above factors are considered when choosing a system, the first step in
making a choice is to calculate the system loads and establish the number and size of
the zones. Typically, after some systems have been eliminated for specific reasons,
one needs to do a point-by-point comparison to make a final choice.
-
Chapter - 2 HVAC System Choosing and Designing
Modern Approach to HVAC Design and its Future Trend 8
2.3 Unitary System Selection Guidelines
Unitary systems are selected when it is decided that a central HVAC system is too
large or too expensive for a particular project, or a combination system is needed for
certain areas or zones to supplement the central system.
2.3.1 Factors to Consider When Selecting Unitary Systems
i. Control of Temperature and Airflow
ii. One Manufacturer is Responsible for the Final Unit
iii. Maintenance and Operation
iv. Costs and Energy Efficiency
2.4 HVAC Design
Best-in-class HVAC system design and analysis are critical elements of creating the
optimal building environment. Given the level of control and the performance
demands of todays sophisticated HVAC systems, seemingly incremental efficiencies
result in significant reductions of resource requirements. Accurate analysis and
specifications translate into substantial savings and optimal performance for building
owners. Conducting comprehensive load analyses, considering air supply
requirements, weather conditions, determining optimum HVAC system, piping and
duct configurations, and then applying those considerations to specifications are all
critical to high performance building design.
Pharmaceutical manufacturing is generally conducted in environments that are
cleaner and are carefully controlled at a required temperature, humidity and pressure.
The HVAC system assumes a large part of the responsibility in maintaining these
clean environments.
2.4.1 Design of an Air Handling Unit
Choosing of an Air Handling System is very important for a pharmaceutical industry.
Air Handling Units are designed to create a symbiosis of heat, ventilation and air
filtration. The result is a perfectly balanced environment for people and industry.
2.4.1.1 Sub-Systems of AHU
A conventional Air Handling System has 4 sub-systems:
-
Chapter - 2 HVAC System Choosing and Designing
Modern Approach to HVAC Design and its Future Trend 9
1. Air handling of the incoming (fresh) air, elimination of coarse contaminants
and protection from frost if necessary. In the case of air re-circulation, the
fresh air is also called make-up air.
2. Central air handling unit (AHU), where the air will be conditioned (heated,
cooled, humidified or de-humidified and filtered), and where fresh air and re-
circulated air, if any, (indicated here by the dotted line) will be mixed.
3. Air handling in the rooms under consideration (pressure differential system,
additional filtration, air distribution)
4. Air exhaust system (filtration)
Figure 2.1 - Sub-systems of AHU
2.4.1.2 Air Flow Patterns
There are 2 ways to supply air to a room: Turbulent air flow and Uni-
directional flow, often called laminar flow
The air speed in the uni-directional flow is defined by the WHO at: 0.45 m/s
for horizontal units and 0.30 m/s for vertical units (most commonly used)
For the air exhaust, in case of a vertical unit, a low return is more favorable, as
the air is better distributed in the room
Objects in the room can significantly disturb the flow of air, and even block it,
so that there might be pockets without air circulation.
-
Chapter - 2 HVAC System Choosing and Designing
Modern Approach to HVAC Design and its Future Trend 10
(a)
(b)
Figure 2.2 - (a) Turbulent Air Flow, (b)Uni-directional or Laminar Air
Flow
Filtered air entering a production room or covering a process can be meet
GMP aspects and Economical aspects
Figure shows an HVAC installation feeding 3 rooms, each one with terminal
filters, all terminal filters protected by a remote pre-filter. Room 1 has a
turbulent air flow, with low level exhaust. Room 2 has a uni-directional air
flow, over the largest part of the surface, hence the large number of filters,
with low level air returns.
Due to the high cost of the ventilation in class A areas, the tendency is to keep
these areas as small as possible. Room 3 has a turbulent air flow, with ceiling
exhaust.
Figure 2.3 - Room 1, 2 & 3 with different air flow patterns and exhaust
systems
Uni-directional (laminar) flow units exist mostly as vertical, but also as
horizontal, units.
In some cases, the units can be integrated into the ceiling of a room and also
connected to the central air conditioning system.
Laminar flow units are comparatively expensive. Surfaces covered by them
should be reduced to a minimum. Only the product in a critical production
-
Chapter - 2 HVAC System Choosing and Designing
Modern Approach to HVAC Design and its Future Trend 11
phase, and not the personnel, should be under laminar flow (aseptic filling,
sterile blending, etc.).
2.4.1.3 Filters Positions
The filtered air entering a production room can be coming from:
an air-handling unit, equipped with pre-filtration and the main (HEPA) filter,
but at some distance from that room;
an air-handling unit, equipped with pre-filtration in the AHU, and an
additional filter (HEPA) situated immediately on the air outlet.
the terminal positioning is more expensive; provides a better protection; is the
preferred method in clean room classes with high requirements.
Figure 2.4 - AHU mounted final filter
Figure 2.5 - Filter in terminal position
Filters can be in different positions, when one considers the central AHU and
the rooms.
The figure shows an HVAC installation feeding 3 rooms, each one with
terminal filters, all filters protected by a remote pre-filter.
Room 1 has a turbulent air flow, with low level exhaust. Room 2 has a uni-
directional (laminar) air flow over the largest part of the surface, hence the
large number of filters. Room 3 has a turbulent air flow, with ceiling exhaust.
-
Chapter - 2 HVAC System Choosing and Designing
Modern Approach to HVAC Design and its Future Trend 12
Figure 2.6 - HVAC installation feeding 3 rooms
The figure shows an HVAC installation feeding two rooms, each one without
terminal filters, but with remote final filters protected by a pre-filter.
Room 1 has a turbulentair flow, with low level exhaust. Room 2 has a
turbulent air flow, with ceiling exhaust.
If there is no filter in terminal position, it should be ascertained that there are
no elements between the main filter and the air outlets which could add
contamination.
Figure 2.7 - HVAC installation feeding 2 rooms
2.4.1.4 Air Circulation System
2.4.1.4.1 Air Re-Circulation
Re-circulated air must be filtered, at an efficiency rate which is such that
cross-contamination can be excluded.
In case of re-circulation, every possible measure of protection must be taken to
ensure that the air coming from a production unit and loaded with product
particles does not flow to other production units, thereby contaminating them.
It makes sense to re-circulate the air for reasons of energy conservation, but
there can be a contradiction between pharmaceutical requirements and energy
conservation.
-
Chapter - 2 HVAC System Choosing and Designing
Modern Approach to HVAC Design and its Future Trend 13
There are also cases, in which air re-circulation is prohibited, for example if
solvents are used or cytotoxic products are manufactured.
2.4.1.4.2 Ventilation with 100% fresh air (no air re-circulation)
A typical 100% fresh air setup, where a central unit distributes the fresh,
treated air to different production rooms.
The exhaust air is collected in a central duct, treated (filtered or washed) and
eliminated. The degree of exhaust air filtration will depend on contaminants in
the exhaust air and also on environmental regulations.
Figure 2.8 - Ventilation with 100% fresh air (no air re-circulation)
2.4.1.4.3 Ventilation with re-circulated air with make-up air
A typical re-circulated air setup, where a central unit distributes a mixture of
fresh and re-circulated air to different production rooms.
A part of the exhaust air is collected in a central duct, treated (filtered) and
exhausted. The rest is re-circulated (dotted line).
With control dampers, the proportions of fresh and re-circulated air can be
adjusted.
Figure 2.9 - Ventilation with re-circulated air with make-up air
-
CHAPTER THREE
Zoning Design, Central
Plants and Hydronic
Systems
-
Chapter - 3 Zoning Design, Central Plants and Hydronic Systems
Modern Approach to HVAC Design and its Future Trend 14
3.1 Zone
To maximize thermal comfort, systems can be designed to provide independent
control in the different spaces, based on their users and requirements. Each space or
group of spaces that has an independent control is called a zone.
A zone is a part of a building whose HVAC system is controlled by a single
sensor. The single sensor is usually, but not always, a thermostat. Either directly or
indirectly, a thermostat controls the temperature at its location.
3.1.1 Zoning Design
There are several types of zones. These zones are differentiated based on what is to be
controlled, and the variability of what is to be controlled. The most common control
parameters are: thermal, humidity, ventilation, operating periods, freeze protection,
pressure and importance.
The most common reason for needing zones is variation in thermal loads.
Consider the simple building floor plan shown in Figure 3.1. Let us assume it has the
following characteristics:
Well-insulated
A multi-story building, identical plan on every floor
Provided with significant areas of window for all exterior spaces
Low loads due to people and equipment in all spaces
Located in the northern hemisphere
The designers objective is to use zones to keep all spaces at the set-point
temperature.
Figure 3.1 - Building Plan
-
Chapter - 3 Zoning Design, Central Plants and Hydronic Systems
Modern Approach to HVAC Design and its Future Trend 15
Zones are designed on the basis of some factors:
Zoning Design Considerations
Interior and Roof Zones
Thermal Variation
Ventilation with Outside Air
Time of Operation
Humidity
Pressure
Zoning Problems
3.1.2 Controlling the Zone
The most common zone control is the thermostat. It should be placed where it is most
representative of the occupants thermal experience. A thermostat does its best to
keep a constant temperature where it is.
3.2 Single Zone Air Handlers
The single zone air handler, or air-handling unit, often abbreviated to AHU. The air
handler draws in and mixes outside air with air that is being recirculated, or returned
from the building, called return air. Once the outside air and the return air are mixed,
the unit conditions the mixed air, blows the conditioned air into the space and
exhausts any excess air to outside, using the return-air fan.
3.2.1 Examples of Buildings with Single-zone Package Air-Conditioning Units
Building A: This unit has only an electrical supply. This single electrical supply
provides all the power for heating, cooling, humidifying, and for driving the fans.
Building B: This unit has the electrical supply for cooling, humidifying, and for
driving the fans, while the gas line, shown as gas supply, provides heating.
Building C: This unit has the electrical supply for cooling, humidifying, and for
driving the fans. It also has supply and return hot-water pipes coming from a boiler
room in another building. The unit contains a hot-water heating coil and control valve,
which together take as much heat as needed from the hot water supply system.
Building D: In the same way, there may be a central chiller plant that produces cold
water at 42F 48F, called chilled water. This chilled water is piped around the
-
Chapter - 3 Zoning Design, Central Plants and Hydronic Systems
Modern Approach to HVAC Design and its Future Trend 16
building, or buildings, to provide the air-handling units with cooling. Like the heating
coil and control valve in Building C, there will be a cooling coil and control valve in
each unit, to provide the cooling and dehumidification.
Figure 3.2 - Single Zone Rooftop Air-Conditioning Unit, Energy Supplies
3.2.2 Air-Handling Unit Components
Components of the unit can include: inlet louver screen, the parallel blade damper,
opposed blade damper, the relief air damper, actuator, the mixed temperature sensor,
filter, heating coil, cooling coil, humidifier, fan, and return fan.
Figure 3.3 - Air-Conditioning System: Single-Zone Air Handler
-
Chapter - 3 Zoning Design, Central Plants and Hydronic Systems
Modern Approach to HVAC Design and its Future Trend 17
3.2.2.1 Refrigeration Equipment
The vapor compression refrigeration cycle is generally the basis of mechanical
refrigeration. The vapor compression refrigeration system comprises four
components: compressor, condenser, expansion valve, and evaporator. This system
can be used directly, to provide cooling to, typically, a local coil.
Figure 3.4 - Basic Vapor Compression Refrigeration Cycle
3.2.2.2 System Performance Requirements
Before choosing a system, we need an understanding of the types of loads we want
the system to manage. Summer cooling loads will be the main determinant of the
choice of unit to determine the summer load: outside design temperature; outside
design humidity; inside design temperature and humidity; inside generation of heat
and moisture; ventilation requirements.
3.2.2.3 Rooftop Units
In a typical rooftop unit, the return air is drawn up into the base of the unit and the
supply air is blown vertically down from the bottom of the unit into the space below.
As an alternative, the ducts can come out of the end of the unit to run across the roof
before entering the building. Choice factors to choose a rooftop unit: inside and
outside design temperatures, required airflow, mixed air temperature, and the required
sensible and latent cooling loads.
-
Chapter - 3 Zoning Design, Central Plants and Hydronic Systems
Modern Approach to HVAC Design and its Future Trend 18
Figure 3.5 - Rooftop Unit
3.2.2.4 Split Systems
In the split system, the compressor/condenser part of the refrigeration system separate
from the evaporator coil and connected by the refrigerant lines to the air system,
which includes the evaporator.
Figure 3.6 - Split System
3.3 Multiple Zone Air Systems
In many buildings, the unit must serve several zones, and each zone has its own
varying load. To maintain temperature control, each zone has an individual thermostat
that controls the volume and/or temperature of the air coming into the zone.
A system thermodynamically similar to the dual-duct system, the multizone
system features a different layout. The multizone system is not as energy efficient as
the VAV system, and requires a separate duct to each zone. However, the multizone
system has the advantage of requiring no maintenance outside the mechanical room,
except for the zone temperature-sensors and associated cable.
All-air systems advantages:
Centrally located equipment
-
Chapter - 3 Zoning Design, Central Plants and Hydronic Systems
Modern Approach to HVAC Design and its Future Trend 19
Least infringement on conditioned floor space
Greatest potential for the use of an economizer cycle
Zoning flexibility and choice
Full design freedom
Generally good humidity control
All-air systems disadvantages:
Increased space requirements
Construction dust
Closer coordination required
Figure 3.7 - Mixing at the Air Conditioning Unit in a Multizone System
3.3.1 Three Deck, Multizone System
The more modern introduction of the third, neutral duct to the multizone system,
avoids the conflict of concurrent heating and cooling.
3.3.2 Dual Path, Outside Air System
This system could be used to reduce the problem with excess moisture in the air that
arises in warm/hot, humid climates.
3.3.3 Single-Duct, Zoned Reheat, Constant Volume Systems
Reheat is the simplest system, known for both its reliability and the down side, its
high energy wastage. The reheat system permits zone control by reheating the cool
airflow to the temperature required for a particular zone.
-
Chapter - 3 Zoning Design, Central Plants and Hydronic Systems
Modern Approach to HVAC Design and its Future Trend 20
Figure 3.8 - Reheat System
3.3.4 Single-Duct, Variable Air Volume Systems
The variable air volume system is designed with a volume control damper, controlled
by the zone thermostat, in each zone. VAV system adjusts for varying cooling loads
in different zones by individually throttling the supply air volume to each zone.
Figure 3.9 - Variable Air Volume System
3.3.5 Dual-Duct, Variable Air Volume System
A modification of the dual-duct system, this system uses variable volume dual-duct
boxes to provide the thermal efficiency of the VAV system, while maintaining higher
air flows, and thus better room air circulation when heating is required.
3.3.6 By Pass Box Systems
A variation on the VAV system, the bypass system, is suitable for providing good
control in smaller systems and for constant flow over a direct-expansion cooling coil.
Designers must be cautious to ensure that bypassed air goes straight back to the air
conditioning unit, but it is generally a simple system to design.
-
Chapter - 3 Zoning Design, Central Plants and Hydronic Systems
Modern Approach to HVAC Design and its Future Trend 21
Figure 3.10 - By-Pass Boxes on Each Zone
3.3.7 Constant Volume Dual-Duct, All-Air Systems
In a dual-duct system, cooling and heating coils are placed in separate ducts, and the
hot and cold air flow streams are mixed, as needed, for temperature control within
each zone. A very attractive feature of the dual-duct system is that there are no reheat
coils near the zones, so the problems of leaking hot water coils is avoided.
Figure 3.11 - Dual-Duct System, Double Line Diagram
3.4 Central Plants
Central plants include boilers, producing steam or hot water, and chillers, producing
chilled water. These pieces of equipment can satisfy the heating and cooling
requirements for a complete building. In a central plant, the boilers and chillers are
located in a single space in the building, and their output is piped to all the various air-
conditioning units and systems in the building. Their initial cost is often higher than
-
Chapter - 3 Zoning Design, Central Plants and Hydronic Systems
Modern Approach to HVAC Design and its Future Trend 22
packaged units and they require installation floor area as well as space through the
buildings for distribution pipes.
The main items of equipment found in central plants are:
Boilers are pressure vessels and their installation and operation are strictly
prescribed by codes.
Chillers come in a huge range of sizes and types. Their particular
requirements for chilled water piping and specialized control. The job of the
chiller is to remove heat from the chilled water and reject it to the condenser.
Cooling towers are devices used to cool water by evaporation. Water is
sprayed or dripped over material with a large surface area, while outdoor air is
drawn through.
3.4.1 Boilers
Boilers are pressure vessels used to produce steam or hot water. The critical design
factor for boilers is pressure. A low-pressure steam boiler operates at a pressure of no
more than 15 psig. Low-pressure hot water boilers are allowed up to 160 psig.
3.4.1.1 Boiler Components
Boilers have two sections: The combustion section is the space where the fuel air
mixture burns; the second section of the boiler is the heat transfer section. In all
boilers there is a need to modulate the heat input.
In steam systems, there is a constant loss of water in the condensate return
system. To prevent problems with solids build-up in the boiler and distribution pipe
corrosion, continuous high quality water treatment is required.
Figure 3.12 - Hot Water Heating System with Two Boilers
-
Chapter - 3 Zoning Design, Central Plants and Hydronic Systems
Modern Approach to HVAC Design and its Future Trend 23
3.4.2 Water Chillers
The chiller includes an evaporator or liquid cooler, a condenser, and a compressor.
The main energy-using components of chiller plant are the motors that drive the
compressors, chilled water pumps, condenser water pumps, air-cooled condenser fans,
and cooling tower fans.
The water that flows through the evaporator coil gives up heat, and becomes
cooler. The cooled water is referred to as chilled water. The water that flows
through the condenser, called the condenser water, becomes warmer and is piped
away to a cooling tower to be cooled before returning to the condenser to be warmed
again.
The two categories of water chillers used in HVAC systems are:
i. Mechanical chiller
ii. Absorption chiller
Figure 3.13 - Water Chiller with Water Cooled Condenser
Variable chilled water flow arrangement is shown in the figure. In the diagram, at full
load, both chillers and pumps are running, and the valves in the coil circuits are fully
open. As the load decreases, the temperature sensors, in front of each coil, start to
close their valve, restricting the flow through the coil.
-
Chapter - 3 Zoning Design, Central Plants and Hydronic Systems
Modern Approach to HVAC Design and its Future Trend 24
Figure 3.14 - Two Chiller Piping with Constant Chiller Flow
3.4.3 Centrifugal Water Chillers
The centrifugal refrigeration machine was the first practical method of air
conditioning large spaces. The heart of a centrifugal water chiller is the centrifugal
compressor.
Figure 3.15 - Centrifugal Mechanical Chiller
3.4.3.1 Central Plant Water Chiller Optimization
To determine if the central plant can be optimized, the first step is to conduct an
energy survey and testing of the systems operating performance. The second step is
-
Chapter - 3 Zoning Design, Central Plants and Hydronic Systems
Modern Approach to HVAC Design and its Future Trend 25
to consider the options. The third step to any proposed retrofit is to consider the
consequences of the retrofit before starting the project.
The following are some ways to optimize the chiller plant:
Select Proper Air Quantities and Heat Transfer Surfaces for the Cooling Coils
Raise the Evaporator Temperature
Lower Condenser Water Temperature
Optimize Chillers in Series
Optimize Chillers in Parallel
Install Water-side Economizers
3.4.4 Cooling Towers
Cooling towers are a particular type of big evaporative cooler. In the cooling tower,
warm water is exposed to a flow of air, causing evaporation and therefore, cooling of
the water. The psychrometric chart can be used to illustrate the workings of the
cooling tower.
Figure 3.16 - Typical Natural-Draft
Open Cooling Tower
Figure 3.17 - Induced Draft, Closed
Circuit Cooling Tower
3.5 Hydronic Systems
In some buildings, these systems will use low-pressure steam instead of hot water for
heating. The performance is generally similar to hot water systems, with higher
outputs due to the higher temperature of the steam.
-
Chapter - 3 Zoning Design, Central Plants and Hydronic Systems
Modern Approach to HVAC Design and its Future Trend 26
Hydronic systems are most commonly used where high and variable sensible
heating and/or cooling loads occur. These are typically
Perimeter zones, with high solar heat gains or
Perimeter areas in cooler to cold climates where there are substantial
perimeters heat losses
Hydronic systems advantages:
i. Noise reduction virtually silent operation
ii. Economy due to limited operational costs large amounts of heat from small
local equipment
iii. Economy due to limited first costs pipes are small compared to ducts for
the same heat transfer around a building
iv. Energy efficiency low energy consumption at low load
Hydronic systems disadvantages:
i. Ventilation provision of outside air for ventilation is either absent or poor
ii. System failure danger from freezing and from leaks
iii. Humidity control is either absent or generally poor
3.5.1 Natural Convection and Low Temperature Radiation Heating Systems
The very simplest water heating systems consist of pipes with hot water flowing
through them. The output from a bare pipe is generally too low to be effective, so an
extended surface is used to dissipate more heat. The radiator emits heat by both
radiation and convection. These water heaters can all be controlled by varying the
water flow or by varying the water supply temperature.
-
Chapter - 3 Zoning Design, Central Plants and Hydronic Systems
Modern Approach to HVAC Design and its Future Trend 27
Figure 3.18 - Wall-Mounted Single and Double Panel Radiators
3.5.2 Panel Heating and Cooling
Radiant floors use the floor surface for heating. Ceilings can also be used for heating
and/or cooling. The system has the advantage of taking up no floor or wall space and
it collects no more dirt than a normal ceiling.
Figure 3.19 - Concrete Radiant Floor
3.5.3 Fan Coils
Fan coils can be used for just heating or for both heating and cooling. When the fan-
coil is used for heating, the hot water normally runs through the unit continuously.
When the thermostat switches the fan on, full output is achieved. Some units are
provided with two or three speed controls for the fan, allowing adjustment in output
of heat and generated noise. Types of fan coils include: Hot-water fan coils,
changeover systems, and four-pipe systems.
-
Chapter - 3 Zoning Design, Central Plants and Hydronic Systems
Modern Approach to HVAC Design and its Future Trend 28
Figure 3.20 - Typical Fan-Coil Unit
3.5.4 Fan Curves
A fan curve shows the performance of a fan at various static pressures and volumes of
airflow. At the top left of the curve is the block tight static pressure condition at
maximum static pressure and zero airflow.
3.5.5 Two Pipe Induction Systems
The two-pipe induction system uses ventilation air at medium pressure to entrain
room air across a coil that either heats or cools. The units are typically installed under
a window, and when the air system is turned off, the unit will provide some heat by
natural convection if hot water is flowing through the coil.
Figure 3.21 - Induction Unit
-
Chapter - 3 Zoning Design, Central Plants and Hydronic Systems
Modern Approach to HVAC Design and its Future Trend 29
3.5.6 Water Source Heat Pumps
Water source heat pumps are refrigeration units that can either pump heat from water
into the zone or extract heat from the zone and reject it into water. This ability finds
two particular uses in building air conditioning:
a) The use of heat from the ground
b) The transfer of heat around a building
3.6 Hydronic System Architecture
The basic layout options for heating and cooling piping arrangements that distribute
water or steam, hydronic circuits. In each case, a flow of water or steam is distributed
from a either a central boiler or a chiller, the refrigeration equipment used to produce
chilled water, to the hydronic circuits.
3.6.1 Steam Systems
Principal ideas of this section include: how steam is used; its behavior as a gas and
how it condenses as it gives up its latent heat; how the resultant condensate is drained
out of the steam pipes by traps and then returned to the boiler, to be boiled into steam
again.
Figure 3.22 - Steam System
3.6.2 Water Systems
In the water systems, we need economical direct arrangement and the more costly, but
largely self-balancing, reverse-return piping arrangement. The advantages of water
over steam include the fact that water is safer and more controllable than steam.
Water System Design Issues are: Pipe Construction and Pipe Distribution.
-
Chapter - 3 Zoning Design, Central Plants and Hydronic Systems
Modern Approach to HVAC Design and its Future Trend 30
3.6.3 Hot Water Systems
Within buildings, hot water is the fluid that is most commonly used for heat
distribution. The amount of heat that is transferred is proportional to the temperature
difference between supply and return.
3.6.4 Chilled Water Systems
Because chilled water systems need constant water flow through the chiller
evaporator, the economies of variable flow can be achieved through decoupled and
distributed piping arrangements.
Figure 3.23 - Chiller System with Decoupled Flows
3.6.5 Condenser Water System
Condenser water is water that flows through the condenser of a chiller to cool the
refrigerant. Condenser water from a chiller typically leaves the chiller at 95F and
returns from the cooling tower at 85F or cooler.
Figure 3.24 - Evaporative Cooling Tower
-
CHAPTER FOUR
Control Systems and
Thermal Comforts
-
Chapter - 4 Control Systems and Thermal Comforts
Modern Approach to HVAC Design and its Future Trend 31
4.1 HVAC Control Systems
The purpose of an HVAC automatic control system is to start, stop or regulate the
flow of air, water or steam and to provide stable operation of the system by
maintaining the desired temperature, humidity and pressure. The automatic control
system is a group of components, each with a definite function designed to interact
with the other components so that the system is self-regulating. HVAC control
systems are classified according to the source of power used for the operation of the
various components. Whether the controls are a factory package or built-up on site,
well-designed controls are a critical part of any HVAC system.
The classifications and power sources are:
a) Pneumatic Systems:
Compressed air.
b) Electric Systems:
Low voltage electricity (normally 24 Volts)
Line voltage electricity (normally 110 to 220 Volts)
c) Electronic Systems (DDC):
Low voltage electricity (normally 5 to 15 Volts).
d) Electric- or Electronic-to-Pneumatic Systems:
Electricity and compressed air.
4.2 Control Loops
Information flows in a circle from the sensor measuring the controlled variable to the
controller where the current value of the controlled variable is compared to the
desired value or set point.
Figure 4.1 - Diagram of Control Loop
-
Chapter - 4 Control Systems and Thermal Comforts
Modern Approach to HVAC Design and its Future Trend 32
4.3 Control Modes
All controllers are designed to take action in the form of an output signal to the
controlled device. The output signal is a function of the error signal, which is the
difference between the control point and the setpoint. The type of action the controller
takes is called the control mode or control logic, of which there are three basic types:
i. Two-position control
ii. Floating control
iii. Modulating control
4.4 Control Types
4.4.1 Self-powered Controls
Self-powered Controls require no external power. Various radiator valves and ceiling
VAV diffusers have self-powered temperature controls.
4.4.2 Electric Controls
Electric Controls are powered by electricity.
On/off Electric Control
Modulating Electric Controls.
4.4.3 Pneumatic Controls
Pneumatic controls, which use compressed air as the power source, are very simple
and inherently analog, making them ideal for controlling temperature, humidity, and
pressure.
4.4.4 Electronic Controls
Electronic Controls, use varying voltages and currents in semiconductors to provide
modulating controls. They have never found great acceptance in the HVAC industry,
since DDC offered much more usability at a much lower price.
4.4.5 Direct Digital Controls, DDC
Direct Digital Controls, DDC, are controls operated by one, or more, small computer
processors. The computer processor uses a software program of instructions to make
-
Chapter - 4 Control Systems and Thermal Comforts
Modern Approach to HVAC Design and its Future Trend 33
decisions based on the available input information. The processor operates only with
digital signals and has a variety of built-in interface components so that it can receive
information and output control signals.
Figure 4.2 - DDC Control Schematic
4.4.5.1 Benefits of DDC:
Direct Control, Precise Control, Dead Band and Control Sequence, Schedule
Changes, Flexibility
4.5 Control System Components
4.5.1 Controllers
A controller is a proportioning device designed to control dampers or valves to
maintain temperature, humidity, or pressure. A controller may be direct acting or
reverse acting. Types of controllers: thermostats, humidistats for humidity,
pressurestats for pressure, master controllers to control submaster controllers, and
receiver-controllers.
4.5.1.1 Single Pressure Thermostat
A single pressure thermostat may be a one-pipe, bleed-type or a two pipe, relay-type
controller. The main air is introduced through a restrictor into the branch line between
the thermostat and the controlled device.
4.5.1.2 Dead Band Thermostat
A dead band thermostat is a two-pipe controller that operates in the same manner as a
single pressure, single temperature thermostat. Its used for energy conservation when
-
Chapter - 4 Control Systems and Thermal Comforts
Modern Approach to HVAC Design and its Future Trend 34
a temperature span or dead band is required between the heating and cooling
setpoints.
4.5.1.3 Dual Pressure Thermostat
The summer/winter system provides for the seasonal requirements of either cooling or
heating and, depending on the season, either chilled water or hot water is supplied to
the water coil in the air handing unit.
4.5.1.4 Humidistat
Humidistats are similar in appearance to thermostats; however, instead of using a
bimetal strip as the sensor, humidity is sensed by a hygroscopic, or water absorbing,
material such as human hair, nylon, silk, wood or leather.
4.5.1.5 Master/Submaster Controller
A master controller is one which transmits its output signal to another controller. The
second controller is called the submaster. The submasters setpoint will change as the
signal from the master controller changes. This is a reset type of control.
4.5.1.6 Receiver-controller and Transmitter
The receiver-controller and transmitter is the controlling device used most often in
present day pneumatic HVAC control systems. The receiver-controller, like the other
controllers, receives a signal from a sensor and then varies its branch output pressure
to the controlled device. The sensing device for receiver-controllers is the transmitter.
Transmitters are one-pipe, direct acting, bleed-type devices which use a restrictor in
the supply line to help maintain the proper volume of compressed air between the
transmitter and the receiver-controller.
4.6 Energy Conservation
The objective of energy conservation is to use less energy. This is accomplished by
various methods, including recycling energy where useful. Energy conservation
should be part of the entire life cycle of a building: it should be a consideration during
the initial conception of a building, through its construction, during the operation and
maintenance of the building throughout its life, and even in deconstruction. Energy
-
Chapter - 4 Control Systems and Thermal Comforts
Modern Approach to HVAC Design and its Future Trend 35
efficient the system as initially designed and installed the energy efficiency will
degrade unless it is operated correctly and deliberately maintained.
4.7 Parameters to Control
4.7.1 Importance of Humidity Control
1) Stability and longer shelf life: Humidity control is important for the stability
and longer shelf life of products. Controlled humidity decreases the
decomposition rate of drugs. It will also help to maintain the physical stability
of dosage form. As a result the shelf life of the dosage form will increase.
2) Comfort requirement: Humidity is a comfort requirement. Suitable moisture
level is required to offer a comfortable working environment for the operators.
3) To inhibit microbial growth: Above 60% RH promotes bacterial growth. So
relative Humidity should be maintained < 55% to inhibit microbial growth in
various production areas.
4) To facilitate various processes: Less humidity makes some problems to
disinfect an area. On the other hand less humidity is required for drying
process. Materials can be effectively dried in controlled humidity.
5) Storage of EHGCS & water sensitive materials: Ideal storage condition of
EHGCS is 45% - 60% RH. At low humidity the capsules become brittle and at
high humidity they become flaccid and lose their shape. Moisture sensitive
materials should also be stored in lower humidity.
6) Production and packing of various dosage forms: Humidity control is
essential for the manufacturing of various dosage forms.
Capsule preparation: RH should be maintained 45% - 55% for proper
encapsulation. Otherwise capsules will absorb moisture and become soft.
Dry syrup preparation: < 50% RH is required for dry syrup
preparation. Lump formation is possible due to over moisture.
Hygroscopic tablet preparation: Controlled humidity is required for the
granulation, compression, coating and packing of hygroscopic tablets.
Over moisture may dissolve the materials.
7) Maintenance of equipment: Humidity control is essential to maintain
sophisticated QC instruments.
-
Chapter - 4 Control Systems and Thermal Comforts
Modern Approach to HVAC Design and its Future Trend 36
4.7.2 Importance of Temperature Control
1) Stability and longer shelf life: Temperature control is important for the
stability and longer shelf life of product. Controlled temperature decreases the
decomposition rate of drugs. It will also help to maintain the physical stability
of dosage form. As a result the shelf life of the dosage form will increase.
2) Comfort requirement: Temperature is a comfort requirement. Suitable
temperature is required to offer a comfortable working environment for the
operators.
3) To inhibit microbial growth: Microbial growth is accelerated by the
optimum temperature. 370c temperature promotes the bacterial growth.
Microbial growth can be inhibited by controlling temperature.
4) Storage of EHGCS & thermo labile materials: Ideal storage condition of
EHGCS is 25 - 300c. They lose their shape at high temperature. Moisture
sensitive materials should also be stored in lower temperature.
5) Production and packing of various dosage forms: Temperature control is
essential for the manufacturing of various dosage forms.
4.7.3 Importance of Dust Particle Control
1) Purity of product
2) Patients safety
3) To inhibit microbial load
4) Production and packing of various dosage forms
4.8 Thermal Comfort
Thermal comfort is primarily controlled by a buildings heating, ventilating and air-
conditioning systems, though the architectural design of the building may also have
significant influences on thermal comfort. Standard 55 defines thermal comfort as
that condition of mind which expresses satisfaction with the thermal environment
and is assessed by subjective evaluation.
4.8.1 Factors Influencing Thermal Comfort
There are seven factors which are influencing the thermal comfort. They are:
-
Chapter - 4 Control Systems and Thermal Comforts
Modern Approach to HVAC Design and its Future Trend 37
Personal
1. Activity level
2. Clothing
Individual Characteristics
3. Expectation
Environmental Conditions and Architectural Effects
4. Air temperature
5. Radiant temperature
6. Humidity
7. Air speed
4.8.1.1 Activity Level
The human body continuously produces heat through a process call metabolism.
This heat must be emitted from the body to maintain a fairly constant core
temperature, and ideally, a comfortable skin temperature. As activity increases, from
sitting to walking to running, so the metabolic heat produced increases.
4.8.1.2 Clothing
In occupied spaces, clothing acts as an insulator, slowing the heat loss from the body.
To predict thermal comfort we must have an idea of the clothing that will be worn by
the occupants. Due to the large variety of materials, weights, and weave of fabrics,
clothing estimates are just rough estimates.
4.8.1.3 Occupants Expectations
Peoples expectations affect their perception of comfort in a building. Standard 55
recognizes that the expectations for thermal comfort are significantly different in
buildings where the occupants control opening windows, as compared to a
mechanically cooled building.
4.8.1.4 Air Temperature
When we are referring to air temperature in the context of thermal comfort, we are
talking about the temperature in the space where the person is located.
-
Chapter - 4 Control Systems and Thermal Comforts
Modern Approach to HVAC Design and its Future Trend 38
4.8.1.5 Radiant Temperature
Radiant heat is heat that is transmitted from a hotter body to a cooler body with no
effect on the intervening space. For internal spaces, where the temperature of the
walls, floor and ceiling are almost the same as the air temperature, the radiant
temperature will be constant in all directions and virtually the same as the air
temperature.
4.8.1.6 Humidity
Low humidity: For some people, low humidity can cause specific problems,
like dry skin, dry eyes and static electricity. However, low humidity does not
generally cause thermal discomfort.
High humidity: Standard 55 does define the maximum humidity ratio for
comfort at 0.012 lb/lb. Since it is equivalent to 100% relative humidity at
62F.
4.8.1.7 Air Speed
The higher the air speed over a persons body, the greater the cooling effect.
4.9 Heat Flow and Heat Recovery
4.9.1 Heat Flow
Heat is energy in the form of molecules in motion. Heat flows from a warmer
substance to a cooler substance. Heat energy flows downhill. Heat does not rise,
heated air rises.
4.9.1.1 Heat Transfer
Heat naturally flows from a higher energy level to a lower energy level. When there is
a temperature difference between two substances, heat transfer will occur. The greater
the temperature difference, the greater the heat transfer.
4.9.1.2 Types of Heat Transfer
The three types of heat transfer are conduction, convection and radiation.
-
Chapter - 4 Control Systems and Thermal Comforts
Modern Approach to HVAC Design and its Future Trend 39
4.9.1.2.1 Conduction
Conduction heat transfer is heat energy traveling from one molecule to another. A
heat exchanger in an HVAC system uses conduction to transfer heat.
4.9.1.2.2 Convection
Heat transfer by convection is when some substance that is readily movable such as
air, water, steam, or refrigerant moves heat from one location to another. An HVAC
system uses convection in the form of air, water, steam and refrigerants in ducts and
piping to convey heat energy to various parts of the system.
4.9.1.2.3 Radiation
Heat transferred by radiation travels through space without heating the space.
Radiation or radiant heat does not transfer the actual temperature value.
4.9.1.3 Heat Transfer Equations
1) Air System - Sensible Heat Transfer Equation
Btuh = cfm 1.08 TD
2) Air Syatems - Total Heat Transfer Equation
Btuh = cfm 4.5 h
3) Water System - Heat Transfer Equation
Btuh = gpm 500 TD
4.9.2 Heat Recovery
The objective of heat-recovery systems is to reduce the energy consumption and cost
of operating a building by transferring heat between two fluids, such as exhaust air
and outside air. In many cases, the proper application of heat-recovery systems can
result in reduced energy consumption and lower energy bills, while adding little or no
additional cost to building maintenance or operations.
4.9.2.1 Heat Recovery Systems
There are three basic types of heat recovery systems: comfort- to-comfort, process-to-
comfort, and process-to-process.
-
Chapter - 4 Control Systems and Thermal Comforts
Modern Approach to HVAC Design and its Future Trend 40
4.9.2.1.1 Comfort- to-Comfort Heat Recovery Systems
Comfort-to-comfort systems are typically used in HVAC applications. These heat
recovery systems capture a buildings exhaust air and reuse the energy in that waste
heat to precondition the outside air coming into the building. In comfort-to-comfort
applications, the energy recovery process is reversible. To determine the amount of
heat transferred, use the sensible heat transfer equation.
Btuh = cfm 1.08 T
4.9.2.1.2 Process-to-Comfort Heat Recovery Systems
Process-to-comfort systems are generally sensible heat recovery only. Therefore, they
are used only during the spring, fall, and winter month but there is no heat recovery
during the summer months.
4.9.2.1.3 Process-to-Process Heat Recovery Systems
Process-to-process systems also perform sensible heat recovery only, usually full
recovery, but in some cases, partial recovery can be performed if circumstances
dictate.
-
CHAPTER FIVE
Future Trend to HVAC
-
Chapter 5 Future Trend to HVAC
Modern Approach to HVAC Design and its Future Trend 41
5.1 Future Trend to HVAC
Modern building and HVAC systems are required to be more energy efficient while
adhering to an ever-increasing demand for better indoor air quality and performance.
Economical consideration and environmental issues also need to be taken into
account. These factors, as well as an increase in design liability and requirement to
complete designs quickly, have placed unprecedented pressure on designer.
Computers are seen as an important design tool that can reduce some of the strain.
5.2 Future Revolution in HVAC Design
Contemporary practice in heating, ventilation, and air conditioning (HVAC) is
inadequate to fulfill the stringent demands of the 21st century. It is deficient in
comfort, ventilation, indoor air quality, fire safety, energy efficiency, and resistance to
terrorism.
For several decades now, HVAC designers have known that they must make
their systems more energy efficient, but combining efficiency with high standards of
comfort and health has proven to be an elusive goal. It may seem that performance
compromises are inescapable, but that is not true. Present problems stem from
continuing along an evolutionary design path that took a wrong turn in the past.
In this series of two articles, we will recognize flawed premises in present
HVAC practice, make a major change in HVAC design, and eliminate the defects of
HVAC equipment. We will find that it is possible to satisfy all the requirements that
HVAC must meet during this century.
5.3 Logic of the HVAC Revolution
The accumulation of unsolved problems in contemporary HVAC requires us to stop
and take a fresh look. While we exploit the lessons of past experience, we will
abandon assumptions that are no longer relevant and change practices that fail to
achieve optimum performance.
HVAC today uses two broad approaches. For compartmentalized buildings, the
dominant design approach is using centralized air handling systems that serve
multiple zones. For smaller buildings, and for individual spaces whose conditioning
requirements do not match the rest of the building, the dominant approach is using
single-zone systems.
-
Chapter 5 Future Trend to HVAC
Modern Approach to HVAC Design and its Future Trend 42
The first step toward optimum HVAC is recognizing that multiple-zone air
handling systems inherently cannot optimize all HVAC functions, nor can they
operate with a high level of energy efficiency unless they seriously degrade the
comfort and health functions of the systems. This is a theoretical limitation, not just a
practical one. Therefore, multiple-zone HVAC systems must be abandoned.
5.4 Optimized Function HVAC Design
HVAC for this century must become fully optimized. Each comfort, health, and safety
function required for each zone in the facility must be executed perfectly, and no
energy waste is permitted. This criterion is entirely achievable by a disciplined design
process that focuses on the system functions.
This is the design sequence for optimized-function HVAC:
i. Define all the conditioning functions that are needed for each application in
the facility.
ii. Define the spatial zones that correspond to each function.
iii. For each zone, identify the kinds of equipment that can fulfill each function
optimally.
iv. Consolidate the equipment for each zone without compromising optimum
performance.
v. Provide optimum control for all operating conditions.
5.5 Central Plant Equipment in Optimized Systems
In the strictest sense, centralized plants especially cooling plants cannot optimize
energy efficiency. A chiller must make water cold enough to serve the zone that needs
the coldest water. This reduces the COP of the chiller in serving other zones. Also,
central plants require pump energy. Hydronic systems provide advantages such as
compact equipment and quiet operation. If central energy plants are used, the capable
engineer will seek to minimize the tendency of individual zone requirements to
degrade the efficiency of the central plant.
5.6 Economics of Optimized-Function HVAC
The idealized performance of optimized-function HVAC extends to its economics.
Human productivity is the highest cost associated with HVAC. By definition,
-
Chapter 5 Future Trend to HVAC
Modern Approach to HVAC Design and its Future Trend 43
optimized-function HVAC provides the best comfort and health, so it offers the
greatest productivity. The second-highest cost of HVAC is energy. Life-cycle cost is
greatly reduced because optimized systems operate with the least possible energy.
Optimized HVAC reduces the cost of equipment space and increases rentable space.
Air handling rooms are eliminated. Duct space is minimized or eliminated.
5.7 Onward to the Future
Important changes in engineering often occur as seismic shifts, in which current
practices are abruptly abandoned and nascent approaches quickly rise to dominance.
Such upsets occur after years of increasing tension, when important realities grow too
strong to ignore. We are now at such a point in the design of HVAC systems. A
revolution in HVAC is needed to make buildings survivable in a century of very high
energy costs and terrorist threats.
The coming jolt in HVAC design is analogous to the extinction of the dinosaurs,
which grew too large and unadoptable and were replaced by small, versatile
mammals. Similarly, multiple zone air handling will be replaced by a versatile new
design concept that we have called optimized-function HVAC. The change begins
now. Design your HVAC systems for this century, not the last one.
-
CHAPTER SIX
Conclusion
-
Chapter 6 Conclusion
Modern Approach to HVAC Design and its Future Trend 44
6.1 Conclusion
The proper design of HVAC system is one of the most fundamental factors for the
pharmaceutical industries. Systems have been designed for greatest assurance of
consistent environmental conditions, with constant volume or reheat and high air
change rates the order of the day. Steps to prevent cross-contamination in multi-
product plants have been draconian, ranging from 100% fresh air or exhaust to
multiple series HEPA filters in supply and exhaust. Developments in processing
equipment, isolation technology and a risk or science-based approach to ensuring
parameters of "strength, identity, safety, purity, and quality," open a new world of
possibilities for HVAC in pharmaceutical facilities.
The engineers are trying to modernization the HVAC design. Now more than
ever, regulators and quality professionals are open to the idea of managing the risks
inherent in environmental control rather than attempting to eliminate them and
creating new ones in the process. This requires a cross-functional approach, engaging
the departments of quality, devel