Infoblox Appliance Wattage and BTU Data Model: Infoblox Model 250 No Load Max Load Average Load-Calculated Consumption Voltage (Input) 120.7 120.3 Current (True RMS) 0.3 0.32 VA-Rating 36.21 38.5 PFC Rating 0.993 1 Watts 36.1 38.6 37.326265 BTU 123 132 127 BTU/Hour Heat Generated Factor: 3.4129 Air-Conditioning Tonnage 0.0103 0.0110 0.0106 Note: Max Load is calculated at 100% CPU Load Size of the room and geographical conditions will add to Air-Conditioning requirements. Hours Years MTBF: 70,000.00 7.99

Upload: doanhuong

Post on 23-May-2018

233 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Model: Infoblox Model 250infoblox-2.custhelp.com/ci/fattach/get/12061/0/filename/... · Infoblox Appliance Wattage and BTU Data Model: Infoblox Model 250-A No Load Max Load Average

Infoblox Appliance Wattage and BTU Data

Model: Infoblox Model 250

No Load Max Load Average Load-CalculatedConsumption

Voltage (Input) 120.7 120.3Current (True RMS) 0.3 0.32VA-Rating 36.21 38.5PFC Rating 0.993 1Watts 36.1 38.6 37.326265BTU 123 132 127 BTU/Hour Heat Generated

Factor: 3.4129Air-Conditioning Tonnage 0.0103 0.0110 0.0106

Note:Max Load is calculated at 100% CPU LoadSize of the room and geographical conditions will add to Air-Conditioning requirements.

Hours YearsMTBF: 70,000.00 7.99

Page 2: Model: Infoblox Model 250infoblox-2.custhelp.com/ci/fattach/get/12061/0/filename/... · Infoblox Appliance Wattage and BTU Data Model: Infoblox Model 250-A No Load Max Load Average

Infoblox Appliance Wattage and BTU Data

Model: Infoblox Model 250-A

No Load Max Load Average Load-CalculatedConsumption

Voltage (Input) Current (True RMS) VA-Rating PFC Rating Watts 191 248 220BTU 508 558 533 BTU/Hour Heat Generated

Factor: 3.4129Air-Conditioning Tonnage

Note:Max Load is calculated at 100% CPU LoadSize of the room and geographical conditions will add to Air-Conditioning requirements.

Hours YearsMTBF: 26,935 3.07

Page 3: Model: Infoblox Model 250infoblox-2.custhelp.com/ci/fattach/get/12061/0/filename/... · Infoblox Appliance Wattage and BTU Data Model: Infoblox Model 250-A No Load Max Load Average

Infoblox Appliance Wattage and BTU Data

Model: Infoblox Model 500

No Load Max Load Average Load-CalculatedConsumption

Voltage (Input) 121.7 121.1Current (True RMS) 0.569 1.046VA-Rating 69.2 127.3PFC Rating 0.993 1Watts 68.8 127.8 98BTU 235 436 335 BTU/Hour Heat Generated

Factor: 3.4129Air-Conditioning Tonnage 0.0196 0.0363 0.028

Note:Max Load is calculated at 100% CPU LoadSize of the room and geographical conditions will add to Air-Conditioning requirements.

Hours YearsMTBF: 26,935 3.07

Page 4: Model: Infoblox Model 250infoblox-2.custhelp.com/ci/fattach/get/12061/0/filename/... · Infoblox Appliance Wattage and BTU Data Model: Infoblox Model 250-A No Load Max Load Average

Infoblox Appliance Wattage and BTU Data

Model: Infoblox Model 550

No Load Max Load Average Load-CalculatedConsumption

Voltage (Input) 121.7 121.1Current (True RMS) 1.23 1.35VA-Rating 149.69 163.49PFC Rating 0.993 1Watts 148.7 163.6 156.1640815BTU 508 558 533 BTU/Hour Heat Generated

Factor: 3.4129Air-Conditioning Tonnage 0.0423 0.0465 0.0444

Note:Max Load is calculated at 100% CPU LoadSize of the room and geographical conditions will add to Air-Conditioning requirements.

Hours YearsMTBF: 26,935.00 3.07

Page 5: Model: Infoblox Model 250infoblox-2.custhelp.com/ci/fattach/get/12061/0/filename/... · Infoblox Appliance Wattage and BTU Data Model: Infoblox Model 250-A No Load Max Load Average

Infoblox Appliance Wattage and BTU Data

Model: Infoblox Model 550-A

No Load Max Load Average Load-CalculatedConsumption

Voltage (Input) 121.7 121.1Current (True RMS) 1.23 1.35VA-Rating 149.69 163.49PFC Rating 0.993 1Watts 148.7 163.6 156.1640815BTU 508 558 533 BTU/Hour Heat Generated

Factor: 3.4129Air-Conditioning Tonnage 0.0423 0.0465 0.0444

Note:Max Load is calculated at 100% CPU LoadSize of the room and geographical conditions will add to Air-Conditioning requirements.

Hours YearsMTBF: 26,935 3.07

Page 6: Model: Infoblox Model 250infoblox-2.custhelp.com/ci/fattach/get/12061/0/filename/... · Infoblox Appliance Wattage and BTU Data Model: Infoblox Model 250-A No Load Max Load Average

Infoblox Appliance Wattage and BTU Data

Model: Trinzic Model 810

No Load Max Load Average Load-CalculatedConsumption

Voltage (Input) 120 120Current (True RMS) 0.48 0.59VA-Rating PFC Rating Watts 58 71 64.5BTU 197.9 242 219.95 BTU/Hour Heat Generated

Factor: 3.4129Air-Conditioning Tonnage

Note:Max Load is calculated at 100% CPU LoadSize of the room and geographical conditions will add to Air-Conditioning requirements.

Hours YearsMTBF: 34,175 3.9

Page 7: Model: Infoblox Model 250infoblox-2.custhelp.com/ci/fattach/get/12061/0/filename/... · Infoblox Appliance Wattage and BTU Data Model: Infoblox Model 250-A No Load Max Load Average

Infoblox Appliance Wattage and BTU Data

Model: Trinzic Model 820

No Load Max Load Average Load-CalculatedConsumption

Voltage (Input) 120 120Current (True RMS) 0.48 0.59VA-Rating PFC Rating Watts 58 71 64.5BTU 197.9 242 219.95 BTU/Hour Heat Generated

Factor: 3.4129Air-Conditioning Tonnage

Note:Max Load is calculated at 100% CPU LoadSize of the room and geographical conditions will add to Air-Conditioning requirements.

Hours YearsMTBF: 34,175 3.9

Page 8: Model: Infoblox Model 250infoblox-2.custhelp.com/ci/fattach/get/12061/0/filename/... · Infoblox Appliance Wattage and BTU Data Model: Infoblox Model 250-A No Load Max Load Average

Infoblox Appliance Wattage and BTU Data

Model: Infoblox Model 1000

No Load Max Load Average Load-CalculatedConsumption

Voltage (Input) 121.7 121.1Current (True RMS) 0.569 1.046VA-Rating 69.2 127.3PFC Rating 0.993 1Watts 68.8 127.8 98.3BTU 235 436 335 BTU/Hour Heat Generated

Factor: 3.4129Air-Conditioning Tonnage 0.0196 0.0363 0.028

Note:Max Load is calculated at 100% CPU LoadSize of the room and geographical conditions will add to Air-Conditioning requirements.

Hours YearsMTBF:

Page 9: Model: Infoblox Model 250infoblox-2.custhelp.com/ci/fattach/get/12061/0/filename/... · Infoblox Appliance Wattage and BTU Data Model: Infoblox Model 250-A No Load Max Load Average

Infoblox Appliance Wattage and BTU Data

Model: Infoblox Model 1050

No Load Max Load Average Load-CalculatedConsumption

Voltage (Input) 121.7 121.1Current (True RMS) 1.35 1.5VA-Rating 164.30 181.65PFC Rating 0.993 1Watts 163.2 181.8 172.4974675BTU 557 620 589 BTU/Hour Heat Generated

Factor: 3.4129Air-Conditioning Tonnage 0.0464 0.0517 0.0491

Note:Max Load is calculated at 100% CPU LoadSize of the room and geographical conditions will add to Air-Conditioning requirements.

Hours YearsMTBF: 26,935.00 3.07

Page 10: Model: Infoblox Model 250infoblox-2.custhelp.com/ci/fattach/get/12061/0/filename/... · Infoblox Appliance Wattage and BTU Data Model: Infoblox Model 250-A No Load Max Load Average

Infoblox Appliance Wattage and BTU Data

Model: Infoblox Model 1050-A

No Load Max Load Average Load-CalculatedConsumption

Voltage (Input) 121.7 121.1Current (True RMS) 1.35 1.5VA-Rating 164.30 181.65PFC Rating 0.993 1Watts 163.2 181.8 172.4974675BTU 557 620 589 BTU/Hour Heat Generated

Factor: 3.4129Air-Conditioning Tonnage 0.0464 0.0517 0.0491

Note:Max Load is calculated at 100% CPU LoadSize of the room and geographical conditions will add to Air-Conditioning requirements.

Hours YearsMTBF: 26,935.00 3.07

Page 11: Model: Infoblox Model 250infoblox-2.custhelp.com/ci/fattach/get/12061/0/filename/... · Infoblox Appliance Wattage and BTU Data Model: Infoblox Model 250-A No Load Max Load Average

Infoblox Appliance Wattage and BTU Data

Model: Infoblox Model 1200

No Load Max Load Average Load-CalculatedConsumption

Voltage (Input) 121.7 121.1Current (True RMS) 0.9 1.35VA-Rating 109.53 163.49PFC Rating 0.993 1Watts 108.9 163.6 136.224145BTU 372 558 465 BTU/Hour Heat Generated

Factor: 3.4129Air-Conditioning Tonnage 0.031 0.0465 0.0387

Note:Max Load is calculated at 100% CPU LoadSize of the room and geographical conditions will add to Air-Conditioning requirements.

Hours YearsMTBF:

Page 12: Model: Infoblox Model 250infoblox-2.custhelp.com/ci/fattach/get/12061/0/filename/... · Infoblox Appliance Wattage and BTU Data Model: Infoblox Model 250-A No Load Max Load Average

Infoblox Appliance Wattage and BTU Data

Model: Trinzic Model 1410

No Load Max Load Average Load-CalculatedConsumption

Voltage (Input) 120 120Current (True RMS) 0.88 1.11VA-Rating PFC Rating Watts 106 133 119.5BTU 361.7 453.8 407.75 BTU/Hour Heat Generated

Factor: 3.4129Air-Conditioning Tonnage

Note:Max Load is calculated at 100% CPU LoadSize of the room and geographical conditions will add to Air-Conditioning requirements.

Hours YearsMTBF: 44,021 5.03

Page 13: Model: Infoblox Model 250infoblox-2.custhelp.com/ci/fattach/get/12061/0/filename/... · Infoblox Appliance Wattage and BTU Data Model: Infoblox Model 250-A No Load Max Load Average

Infoblox Appliance Wattage and BTU Data

Model: Trinzic Model 1410 w/2nd Power Supply

No Load Max Load Average Load-CalculatedConsumption

Voltage (Input) 120 120Current (True RMS) 1.03 1.21VA-Rating PFC Rating Watts 123 145 134BTU 419.7 494.8 457.2 BTU/Hour Heat Generated

Factor: 3.4129Air-Conditioning Tonnage

Note:Max Load is calculated at 100% CPU LoadSize of the room and geographical conditions will add to Air-Conditioning requirements.

Hours YearsMTBF: 63,063 7.20

Page 14: Model: Infoblox Model 250infoblox-2.custhelp.com/ci/fattach/get/12061/0/filename/... · Infoblox Appliance Wattage and BTU Data Model: Infoblox Model 250-A No Load Max Load Average

Infoblox Appliance Wattage and BTU Data

Model: Trinzic Model 1420

No Load Max Load Average Load-CalculatedConsumption

Voltage (Input) 120 120Current (True RMS) 0.88 1.11VA-Rating PFC Rating Watts 106 133 119.5BTU 361.7 453.8 407.75 BTU/Hour Heat Generated

Factor: 3.4129Air-Conditioning Tonnage

Note:Max Load is calculated at 100% CPU LoadSize of the room and geographical conditions will add to Air-Conditioning requirements.

Hours YearsMTBF: 44,021 5.03

Page 15: Model: Infoblox Model 250infoblox-2.custhelp.com/ci/fattach/get/12061/0/filename/... · Infoblox Appliance Wattage and BTU Data Model: Infoblox Model 250-A No Load Max Load Average

Infoblox Appliance Wattage and BTU Data

Model: Trinzic Model 1420 w/2nd Power Supply

No Load Max Load Average Load-CalculatedConsumption

Voltage (Input) 120 120Current (True RMS) 1.03 1.21VA-Rating PFC Rating Watts 123 145 134.0BTU 419.7 494.8 457.2 BTU/Hour Heat Generated

Factor: 3.4129Air-Conditioning Tonnage

Note:Max Load is calculated at 100% CPU LoadSize of the room and geographical conditions will add to Air-Conditioning requirements.

Hours YearsMTBF: 63,063 7.20

Page 16: Model: Infoblox Model 250infoblox-2.custhelp.com/ci/fattach/get/12061/0/filename/... · Infoblox Appliance Wattage and BTU Data Model: Infoblox Model 250-A No Load Max Load Average

Infoblox Appliance Wattage and BTU Data

Model: Infoblox Model 1550

No Load Max Load Average Load-CalculatedConsumption

Voltage (Input) 121.7 121.1Current (True RMS) 1.53 2VA-Rating 186.2 242.2PFC Rating 0.993 1Watts 185 242.3 213.6487965BTU 631 827 729 BTU/Hour Heat Generated

Factor: 3.4129Air-Conditioning Tonnage 0.0526 0.0689 0.0608

Note:Max Load is calculated at 100% CPU LoadSize of the room and geographical conditions will add to Air-Conditioning requirements.

Hours YearsMTBF: 26,464.00 3.02

Page 17: Model: Infoblox Model 250infoblox-2.custhelp.com/ci/fattach/get/12061/0/filename/... · Infoblox Appliance Wattage and BTU Data Model: Infoblox Model 250-A No Load Max Load Average

Infoblox Appliance Wattage and BTU Data

Model: Infoblox Model 1550-A

No Load Max Load Average Load-CalculatedConsumption

Voltage (Input) 121.7 121.1Current (True RMS) 1.53 2VA-Rating 186.2 242.2PFC Rating 0.993 1Watts 185 242.3 213.6487965BTU 631 827 729 BTU/Hour Heat Generated

Factor: 3.4129Air-Conditioning Tonnage 0.0526 0.0689 0.0608

Note:Max Load is calculated at 100% CPU LoadSize of the room and geographical conditions will add to Air-Conditioning requirements.

Hours YearsMTBF: 26,464.00 3.02

Page 18: Model: Infoblox Model 250infoblox-2.custhelp.com/ci/fattach/get/12061/0/filename/... · Infoblox Appliance Wattage and BTU Data Model: Infoblox Model 250-A No Load Max Load Average

Infoblox Appliance Wattage and BTU Data

Model: Infoblox Model 1552

No Load Max Load Average Load-CalculatedConsumption

Voltage (Input) 121.7 121.1Current (True RMS) 1.75 2.25VA-Rating 212.98 272.48PFC Rating 0.993 1Watts 211.6 272.6 242.0795875BTU 722 930 826 BTU/Hour Heat Generated

Factor: 3.4129Air-Conditioning Tonnage 0.0602 0.0775 0.0688

Note:Max Load is calculated at 100% CPU LoadSize of the room and geographical conditions will add to Air-Conditioning requirements.

Hours YearsMTBF: 34,080.00 3.89

Page 19: Model: Infoblox Model 250infoblox-2.custhelp.com/ci/fattach/get/12061/0/filename/... · Infoblox Appliance Wattage and BTU Data Model: Infoblox Model 250-A No Load Max Load Average

Infoblox Appliance Wattage and BTU Data

Model: Infoblox Model 1552-A

No Load Max Load Average Load-CalculatedConsumption

Voltage (Input) 121.7 121.1Current (True RMS) 1.75 2.25VA-Rating 212.98 272.48PFC Rating 0.993 1Watts 211.6 272.6 242.0795875BTU 722 930 826 BTU/Hour Heat Generated

Factor: 3.4129Air-Conditioning Tonnage 0.0602 0.0775 0.0688

Note:Max Load is calculated at 100% CPU LoadSize of the room and geographical conditions will add to Air-Conditioning requirements.

Hours YearsMTBF: 34,080.00 3.89

Page 20: Model: Infoblox Model 250infoblox-2.custhelp.com/ci/fattach/get/12061/0/filename/... · Infoblox Appliance Wattage and BTU Data Model: Infoblox Model 250-A No Load Max Load Average

Infoblox Appliance Wattage and BTU Data

Model: Infoblox Model 1852-A

No Load Max Load Average Load-CalculatedConsumption

Voltage (Input) 121.7 121.1Current (True RMS) 1.75 2.75VA-Rating 212.975 333.025PFC Rating 0.993 1Watts 211.6 333.1 275BTU 722 930 826 BTU/Hour Heat Generated

Factor: 3.4129Air-Conditioning Tonnage 0.0602 0.0775 0.0688

Note:Max Load is calculated at 100% CPU LoadSize of the room and geographical conditions will add to Air-Conditioning requirements.

Hours YearsMTBF: 34,076.00 3.89

Page 21: Model: Infoblox Model 250infoblox-2.custhelp.com/ci/fattach/get/12061/0/filename/... · Infoblox Appliance Wattage and BTU Data Model: Infoblox Model 250-A No Load Max Load Average

Infoblox Appliance Wattage and BTU Data

Model: Infoblox Model 2000

No Load Max Load Average Load-CalculatedConsumption

Voltage (Input) 119.2 119.2Current (True RMS) 2.5 3.2VA-Rating 298.00 381.44PFC Rating 0.993 1Watts 296 381.5 338.777BTU 1010 1302 1156 BTU/Hour Heat Generated

Factor: 3.4129Air-Conditioning Tonnage 0.0842 0.1085 0.0964

Note:Max Load is calculated at 100% CPU LoadSize of the room and geographical conditions will add to Air-Conditioning requirements.

Single P/S Module Current 1.28 2.99

Hours YearsMTBF: 101,078 11.54

Page 22: Model: Infoblox Model 250infoblox-2.custhelp.com/ci/fattach/get/12061/0/filename/... · Infoblox Appliance Wattage and BTU Data Model: Infoblox Model 250-A No Load Max Load Average

Infoblox Appliance Wattage and BTU Data

Model: Infoblox Model 2000-A

No Load Max Load Average Load-CalculatedConsumption

Voltage (Input) 121.7 121.1Current (True RMS) 2.5 3.5VA-Rating 304.25 423.85PFC Rating 0.993 1Watts 302 423.9 380BTU 1010 1302 1156 BTU/Hour Heat Generated

Factor: 3.4129Air-Conditioning Tonnage 0.0842 0.1085 0.0964

Note:Max Load is calculated at 100% CPU LoadSize of the room and geographical conditions will add to Air-Conditioning requirements.

Single P/S Module Current 1.28 2.99

Hours YearsMTBF: 101,090 11.54

Page 23: Model: Infoblox Model 250infoblox-2.custhelp.com/ci/fattach/get/12061/0/filename/... · Infoblox Appliance Wattage and BTU Data Model: Infoblox Model 250-A No Load Max Load Average

Infoblox Appliance Wattage and BTU Data

Model: Trinzic Model 2210

No Load Max Load Average Load-CalculatedConsumption

Voltage (Input) 120 120Current (True RMS) 1.5 1.9VA-Rating PFC Rating Watts 165 218 191.5BTU 563 743.8 653.4 BTU/Hour Heat Generated

Factor: 3.4129Air-Conditioning Tonnage

Note:Max Load is calculated at 100% CPU LoadSize of the room and geographical conditions will add to Air-Conditioning requirements.

Hours YearsMTBF: 93,541 10.68

Page 24: Model: Infoblox Model 250infoblox-2.custhelp.com/ci/fattach/get/12061/0/filename/... · Infoblox Appliance Wattage and BTU Data Model: Infoblox Model 250-A No Load Max Load Average

Infoblox Appliance Wattage and BTU Data

Model: Trinzic Model 2220

No Load Max Load Average Load-CalculatedConsumption

Voltage (Input) 120 120Current (True RMS) 1.5 1.9VA-Rating PFC Rating Watts 165 218 191.5BTU 563 743.8 653.4 BTU/Hour Heat Generated

Factor: 3.4129Air-Conditioning Tonnage

Note:Max Load is calculated at 100% CPU LoadSize of the room and geographical conditions will add to Air-Conditioning requirements.

Hours YearsMTBF: 93,541 10.68

Page 25: Model: Infoblox Model 250infoblox-2.custhelp.com/ci/fattach/get/12061/0/filename/... · Infoblox Appliance Wattage and BTU Data Model: Infoblox Model 250-A No Load Max Load Average

Infoblox Appliance Wattage and BTU Data

Model: Trinzic Model 4010 (IB-4010)

No Load Max Load Average Load-CalculatedConsumption

Voltage (Input) 120 120Current (True RMS) 5.09 6.36VA-Rating PFC Rating Watts 610.5 763.2 687BTU 2083 2604 2344 BTU/Hour Heat Generated

Factor: 3.4129Air-Conditioning Tonnage

Note:Max Load is calculated at 100% CPU LoadSize of the room and geographical conditions will add to Air-Conditioning requirements.

Hours YearsMTBF: 116,901 13.34

Page 26: Model: Infoblox Model 250infoblox-2.custhelp.com/ci/fattach/get/12061/0/filename/... · Infoblox Appliance Wattage and BTU Data Model: Infoblox Model 250-A No Load Max Load Average

Infoblox Appliance Wattage and BTU Data

Model: Infoblox Model 4030

No Load Max Load Average Load-CalculatedConsumption

Voltage (Input) 120 120Current (True RMS) 5.11 6.94VA-Rating PFC Rating Watts 613 833 723BTU 2090 2843 2467 BTU/Hour Heat Generated

Factor: 3.4129Air-Conditioning Tonnage

Note:Max Load is calculated at 100% CPU LoadSize of the room and geographical conditions will add to Air-Conditioning requirements.

Hours YearsMTBF: 80,824 9.23

Page 27: Model: Infoblox Model 250infoblox-2.custhelp.com/ci/fattach/get/12061/0/filename/... · Infoblox Appliance Wattage and BTU Data Model: Infoblox Model 250-A No Load Max Load Average

Infoblox Appliance Wattage and BTU Data

Model: NetMRI-1102-A

No Load Max Load Average Load-CalculatedConsumption

Voltage (Input) 121.7 121.1Current (True RMS) 1.8 2.3VA-Rating PFC Rating Watts 220 280 250BTU 725 950 830 BTU/Hour Heat Generated

Factor: 3.4129Air-Conditioning Tonnage

Note:Max Load is calculated at 100% CPU LoadSize of the room and geographical conditions will add to Air-Conditioning requirements.

Hours YearsMTBF:

Page 28: Model: Infoblox Model 250infoblox-2.custhelp.com/ci/fattach/get/12061/0/filename/... · Infoblox Appliance Wattage and BTU Data Model: Infoblox Model 250-A No Load Max Load Average

Infoblox Appliance Wattage and BTU Data

Model: PortIQ-1050-A

No Load Max Load Average Load-CalculatedConsumption

Voltage (Input) 121.7 121.1Current (True RMS) 1.35 1.5VA-Rating 164.3 181.65PFC Rating 0.993 1Watts 163.2 181.8 172.4974675BTU 557 620 589 BTU/Hour Heat Generated

Factor: 3.4129Air-Conditioning Tonnage 0.0464 0.0517 0.0491

Note:Max Load is calculated at 100% CPU LoadSize of the room and geographical conditions will add to Air-Conditioning requirements.

Hours YearsMTBF: 26,935 3.07

Page 29: Model: Infoblox Model 250infoblox-2.custhelp.com/ci/fattach/get/12061/0/filename/... · Infoblox Appliance Wattage and BTU Data Model: Infoblox Model 250-A No Load Max Load Average

Infoblox Appliance Wattage and BTU Data

Model: PortIQ-1550-A

No Load Max Load Average Load-CalculatedConsumption

Voltage (Input) 121.7 121.1Current (True RMS) 1.53 2VA-Rating 186.2 242.20PFC Rating 0.993 1Watts 185 242.3 172.4974675BTU 631 827 729 BTU/Hour Heat Generated

Factor: 3.4129Air-Conditioning Tonnage 0.0526 0.0689 0.0608

Note:Max Load is calculated at 100% CPU LoadSize of the room and geographical conditions will add to Air-Conditioning requirements.

Hours YearsMTBF: 24,464 3.03

Page 30: Model: Infoblox Model 250infoblox-2.custhelp.com/ci/fattach/get/12061/0/filename/... · Infoblox Appliance Wattage and BTU Data Model: Infoblox Model 250-A No Load Max Load Average

Infoblox Appliance Wattage and BTU Data

Model: PortIQ-1552-A

No Load Max Load Average Load-CalculatedConsumption

Voltage (Input) 121.7 121.1Current (True RMS) 1.75 2.25VA-Rating 212.98 272.48PFC Rating 0.993 1Watts 211.6 272.6 242.0795875BTU 722 930 826 BTU/Hour Heat Generated

Factor: 3.4129Air-Conditioning Tonnage 0.0602 0.0775 0.0688

Note:Max Load is calculated at 100% CPU LoadSize of the room and geographical conditions will add to Air-Conditioning requirements.

Hours YearsMTBF: 34,080 3.89

Page 31: Model: Infoblox Model 250infoblox-2.custhelp.com/ci/fattach/get/12061/0/filename/... · Infoblox Appliance Wattage and BTU Data Model: Infoblox Model 250-A No Load Max Load Average

Infoblox Appliance Wattage and BTU Data

Model: Trinzic Reporting 1400

No Load Max Load Average Load-CalculatedConsumption

Voltage (Input) 120 120Current (True RMS) 1.03 1.21VA-Rating PFC Rating Watts 123 145 134BTU 419.7 494.8 457.2 BTU/Hour Heat Generated

Factor: 3.4129Air-Conditioning Tonnage

Note:Max Load is calculated at 100% CPU LoadSize of the room and geographical conditions will add to Air-Conditioning requirements.

Hours YearsMTBF: 63,063 7.20

Page 32: Model: Infoblox Model 250infoblox-2.custhelp.com/ci/fattach/get/12061/0/filename/... · Infoblox Appliance Wattage and BTU Data Model: Infoblox Model 250-A No Load Max Load Average

Infoblox Appliance Wattage and BTU Data

Model: Trinzic Reporting 2200

No Load Max Load Average Load-CalculatedConsumption

Voltage (Input) 120 120Current (True RMS) 1.5 1.9VA-Rating PFC Rating Watts 165 218 191.5BTU 563 743.8 653.4 BTU/Hour Heat Generated

Factor: 3.4129Air-Conditioning Tonnage

Note:Max Load is calculated at 100% CPU LoadSize of the room and geographical conditions will add to Air-Conditioning requirements.

Hours YearsMTBF: 93,541 10.68

Page 33: Model: Infoblox Model 250infoblox-2.custhelp.com/ci/fattach/get/12061/0/filename/... · Infoblox Appliance Wattage and BTU Data Model: Infoblox Model 250-A No Load Max Load Average

Infoblox Appliance Wattage and BTU Data

Model: Trinzic Reporting 4000

No Load Max Load Average Load-CalculatedConsumption

Voltage (Input) 120 120Current (True RMS) 5.09 6.36VA-Rating PFC Rating Watts 610.5 763.2 687.0BTU 2083 2604 2344 BTU/Hour Heat Generated

Factor: 3.4129Air-Conditioning Tonnage

Note:Max Load is calculated at 100% CPU LoadSize of the room and geographical conditions will add to Air-Conditioning requirements.

Hours YearsMTBF: 116,901 13.34