model fd-140 1 - pottorff · 2014. 11. 24. · the fd-140 fire damper employs triple-v blades for...

2
Ratings UL 555 Fire Resistance Rating: 1 1 /2 hour (vertical and horizontal) UL HNLN: Ventilation Duct Assemblies Maximum Dynamic Closure Velocity: 4,000 fpm (20.3 m/s) Maximum UL555S Rated Pressure: 6 in.wg. (1.5 kPa) Listings UL 555 listing: R11767 CSFM listing: 3225-0368:110 New York City MEA listing: 295-98-E Meets NFPA Standards: 90A, 92A, 92B and 101 Meets Building Code Standards: IBC, NBC, NFPA, SBC and UBC model FD-140 1 1 /2 hour — fire damper triple-V blade Fire Smoke Dampers FD140 (1/2) March 2014 Application The FD-140 fire damper employs triple-V blades for point-of- origin control of fire in static and dynamic HVAC systems. The FD-140 is qualified to 4,000 ft/min (20.3 m/s) and 6 in.wg. (1.5 kPa) and may be installed in vertical walls or partitions, or horizontally in floors or assemblies with fire resistance ratings up to 2 hours. Standard Construction Frame: 5" ¥ 1" (127 ¥ 25) galvanized steel hat channel with interlocking corner gusset. Equivalent to 13 gauge (2.4) channel frame. Low profile head and sill are used on sizes less than 13" (330) high. Blades: 6" ¥ 16 gauge (152 ¥ 1.6) galvanized steel — triple-V. Axles: 1 /2" (13) diameter plated steel hex. Linkage: Concealed in frame. Bearings: Stainless steel oilite, sleeve-type. Seals: Flexible metal jamb seals. Fire Closure Device: Fusible link. Fire Closure Temperature: 165°F (75°C). Minimum Size: 6" ¥ 6" (152 ¥ 152) Maximum Size: Single section: 36" ¥ 48" (914 ¥ 1219) Vertical mount: 144" ¥ 96" (3658 ¥ 2438) Horizontal mount: 108" ¥ 48" (2743 ¥ 1219) Stainless steel (vertical/horizontal): 36" ¥ 48" (914 ¥ 1219) Options o PI-50 — Dual position indicator switch package. o Factory installed sleeve: Gauge:  o 20 (1.0) o 18 (1.3) o 16 (1.6) o 14 (2.0) o 10 (3.5) Length:  o 12" (305) o 16" (406) o 24" (610) o Other______ o Transitions (sleeve required): o Flanged o Round o Oval o Duct connections: o 1" (25) S-clip  o DM25  o DM35 o S & Drive o WARD o Retaining angle systems: Gauge:  o 20 (1.0) o 16 (1.6) Picture frame: o SSPF (single-side)  o DSPF (2-sided) Individual angle sets: o SS (single-side)  o DS (2-sided) o Alternate fire closure temperature: o 212°F (100°C) o Duct access door factory mounted in common sleeve. o Generic mullion for oversized masonry or concrete openings. o Type-304 stainless steel construction. o Manual locking quadrant. o Actuator for multi-section sizes o Internal o External o 24VAC o 120VAC *Sizes larger than 72" x 48" (1828 x 1219) or 36" x 96" (914 x 2438) require electric actuators and a HS-10 fire closure device. 2" (51) Std. W H D * 2" (51) Std. * Type R (optional) Round duct transitions are standard with D=W=H. (available with D<W and H) Model FD-140 (standard) L I S T I N G S E R V I C E S T A T E OF C A LIF O R NI A S TAT E F IR E M A R S H A L L POTTORFF ® 5101 Blue Mound Road, Fort Worth, Texas 76106 www.pottorff.com Information is subject to change without notice or obligation. NOTE: Dimensions in parentheses ( ) are millimeters. *Damper dimensions furnished approximately 1/4" (6) undersize. (sleeve thickness not included) Type O (optional) Oval duct transitions are standard with W and H equal to damper width and height dimensions. (available with W and H smaller than damper width and height) *

Upload: others

Post on 18-Aug-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: model FD-140 1 - Pottorff · 2014. 11. 24. · The FD-140 fire damper employs triple-V blades for point-of-origin control of fire in static and dynamic HVAC systems. The FD-140 is

RatingsUL 555 Fire Resistance Rating: 11/2 hour (vertical and horizontal)

UL HNLN: Ventilation Duct Assemblies

Maximum Dynamic Closure Velocity: 4,000 fpm (20.3 m/s)

Maximum UL555S Rated Pressure: 6 in.wg. (1.5 kPa)

ListingsUL 555 listing: R11767

CSFM listing: 3225-0368:110

New York City MEA listing: 295-98-E

Meets NFPA Standards: 90A, 92A, 92B and 101

Meets Building Code Standards: IBC, NBC, NFPA, SBC and UBC

model FD-14011/2 hour — fire damper

triple-V blade

Fire

Sm

oke

Dam

pers

FD14

0(1

/2) M

arch

201

4

ApplicationThe FD-140 fire damper employs triple-V blades for point-of-origin control of fire in static and dynamic HVAC systems. TheFD-140 is qualified to 4,000 ft/min (20.3 m/s) and 6 in.wg. (1.5 kPa)and may be installed in vertical walls or partitions, or horizontallyin floors or assemblies with fire resistance ratings up to 2 hours.

Standard ConstructionFrame: 5" ¥ 1" (127 ¥ 25) galvanized steel hat channel with

interlocking corner gusset. Equivalent to 13 gauge (2.4)channel frame. Low profile head and sill are used on sizesless than 13" (330) high.

Blades: 6" ¥ 16 gauge (152 ¥ 1.6) galvanized steel — triple-V.

Axles: 1/2" (13) diameter plated steel hex.

Linkage: Concealed in frame.

Bearings: Stainless steel oilite, sleeve-type.

Seals: Flexible metal jamb seals.

Fire Closure Device: Fusible link.

Fire Closure Temperature: 165°F (75°C).

Minimum Size: 6" ¥ 6" (152 ¥ 152)

Maximum Size: Single section: 36" ¥ 48" (914 ¥ 1219) Vertical mount: 144" ¥ 96" (3658 ¥ 2438) Horizontal mount: 108" ¥ 48" (2743 ¥ 1219)

Stainless steel (vertical/horizontal): 36" ¥ 48" (914 ¥ 1219)

Optionso PI-50 — Dual position indicator switch package.o Factory installed sleeve:

Gauge:  o 20 (1.0) o 18 (1.3) o 16 (1.6)o 14 (2.0) o 10 (3.5)

Length:  o 12" (305) o 16" (406) o 24" (610)o Other______

o Transitions (sleeve required): o Flangedo Round o Ovalo Duct connections: o 1" (25) S-clip o DM25  o DM35 o S & Drive o WARD

o Retaining angle systems:Gauge:  o 20 (1.0) o 16 (1.6)Picture frame: o SSPF (single-side)  o DSPF (2-sided)Individual angle sets: o SS (single-side)  o DS (2-sided)

o Alternate fire closure temperature:o 212°F (100°C)

o Duct access door factory mounted in common sleeve.

o Generic mullion for oversized masonry or concrete openings.

o Type-304 stainless steel construction.

o Manual locking quadrant.

o Actuator for multi-section sizeso Internal o Externalo 24VAC o 120VAC

*Sizes larger than 72" x 48" (1828 x 1219) or 36" x 96" (914 x 2438)require electric actuators and a HS-10 fire closure device.

2" (51)

Std.

W

H

D

*

2" (51)

Std.*

Type R (optional)Round duct transitions arestandard with D=W=H.(available with D<W and H)

Model FD-140(standard)

L I S T I N G

S

E R V I C E

ST

ATE OF CALIFORNIA

STATE FIR E M ARSHALL

POTTORFF® 5101 Blue Mound Road, Fort Worth, Texas 76106 www.pottorff.com

Information is subject to change without notice or obligation. NOTE: Dimensions in parentheses ( ) are millimeters.

*Damper dimensions furnishedapproximately 1/4" (6) undersize.(sleeve thickness not included)

Type O (optional)Oval duct transitions arestandard with W and H equalto damper width and heightdimensions. (available with Wand H smaller than damperwidth and height)

*

Page 2: model FD-140 1 - Pottorff · 2014. 11. 24. · The FD-140 fire damper employs triple-V blades for point-of-origin control of fire in static and dynamic HVAC systems. The FD-140 is

Fire

Sm

oke

Dam

pers

FD14

0(2

/2) M

arch

201

4

5D 6D 5D

Pressure drop testing was performedin accordance with AMCA Standard500-D using the three configurationsshown. All data has been corrected torepresent air density of 0.075 lb/ft.Actual pressure drop in any ductedHVAC system is a combination ofmany elements. This information,along with analysis of other systeminfluences, should be used toestimate actual pressure losses for adamper installed in a given HVACsystem.

Sleeve Length12" (305)Standard

3-1/2"(89)

X

6"(152)

5"(127)

3/4"(19)

Airflow Performance Data Pressure Loss vs. Velocity

Figure 5.3 — Ducted Inlet and Outlet Figure 5.2 — Ducted Inlet Figure 5.5 Plenum Mount

Ducted Inlet and OutletAMCA Figure 5.3 Illustrates a fully ducteddamper. This configuration represents thelowest pressure drop of the three testconfigurations because entrance and exitlosses are minimized by straight duct runsupstream and downstream of the damper.

Ducted InletAMCA Figure 5.2 Illustrates a ducteddamper exhausting air into an open area.This configuration has a lower pressuredrop than Figure 5.5 because entrancelosses are minimized by a straight duct runupstream of the damper.

Plenum MountAMCA Figure 5.5 Illustrates a plenummounted damper. This configuration hasthe highest pressure drop because ofextremely high entrance and exit lossesdue to the sudden changes of area in thesystem.

POTTORFF® 5101 Blue Mound Road, Fort Worth, Texas 76106 www.pottorff.com

Information is subject to change without notice or obligation. NOTE: Dimensions in parentheses ( ) are millimeters.

NOTE: 1. The entire damper frame is not required to be installed within the wall, partitionor floor. However, the closed plane of the damper blades must be inside the wall, partition or floor.

Typical Damper Dimensional DataThe drawings and corresponding table show the position of the damper when mounted in afactory sleeve. The standard mounting locations provide enough space for installation ofretaining angles and duct connections.

DamperHeight <8"≥8"

2"3-3/8"

1-1/2"1/8"

J X