Page 1: MITSUBISHI Numerical Protection Relay...MITSUBISHI Numerical Protection Relay. -DSeries. Benefits. Improving reliability of power distribution system is critical for buildings, factories

MELPROTM

SE-E849(19.10-1.0)ROS Published Oct.2019This printed matter has been published in October 2019. Please note that specifications are subject to change without notice.

MITSUBISHI Numerical Protection Relay

MELPROTM-D Series

MITSUBISHI Numerical Protection Relay

-D Series

Page 2: MITSUBISHI Numerical Protection Relay...MITSUBISHI Numerical Protection Relay. -DSeries. Benefits. Improving reliability of power distribution system is critical for buildings, factories

Benefits

Improving reliability of power distribution system is critical for buildings, factories and any other facilities.To enhance protective and control systems and prevent major power outages, protection relays are essential. With a tendency toward a more advanced, complicated power distribution system in recent years, flexibility and accuracy are required for protection relays more than ever.With its enhanced functions added to the old models, the new “MELPRO-D Series” meets a variety of needs for power distribution system.

User Interface that is Easy to Use and Understand

Flexible and Rich Protection Functions Provide Flexibility inManaging Complicated Facilities

PLC (Programmable Logic Controller) Function Enables Reduction ofExternal Equipment and Wiring

Position of New MELPRO-D Series

VFD Indicator

VFD (Vacuum Florescent Display) is used for a numerical and character indicator.Its ability to display characters means that comparison between item numbers and reference table is no longer required, and its higher brightness and wider viewing angle ensures perfect readability even if the protection relay is located at a lower or higher place.Also, PC-HMI* (via USB 2.0) allows you to check various protection elements, output status, and the amount of input power. Setting values can be loaded and written through PC.Note: *PC-HMI is setting and monitoring software exclusively for the new “MELPRO-D Series” and available at “Mitsubishi Electric FA Site.” The protection relay supports USB Type B connection.

With increasingly complicated facilities, more and more timers and self-holding circuits are added to the outside of a protection relay as a condition for operation, closing, or warning of a breaker.To reduce such external equipment and wiring, the new “MELPRO-D Series” provides PLC function.PC-HMI allows you to build sequences based on the logic (e.g. AND/OR/NOT), timer (ON, OFF, One-shot), flip-flop (for holding) and other within the protection relay.

Excellent Compatibility with Our Existing Models Helps EasyReplacement

Dimensions for board processing of our existing “MULTICAP Series” and “MELPRO-D Series” are identical. They are easy to replace without an adapter. Also, excellent compatibility with existing models means minimal changes in design specifications. (except for some models*)Its pull-out structure makes it easy to slide out the main unit of the relay for testing in the maintenance process without disconnecting the wiring from the housing.Note: *D2 type models, such as CAC1-A01D2, among the existing models have different dimensions for board processing and require an adapter for replacement. For the adapter, please contact us.

Enhanced Recording Function Supports Analysis of AccidentFactors and Early Recovery

After an accident occurs, analyzing the factors and recovering equipment can take time. Delay in recovery may extend the damage from the accident even further.With its enhanced recording function, the new “MELPRO-D Series” supports analysis of accident factors and early recovery.

Ensuring a protection relay operates at the time of an accident and minimizing power outage areas require a coordinated protection with other equipment. With increasingly larger capacity of electrical equipment and complicated facilities, however, a coordinated protection is becoming harder and harder.To flexibly address this challenge in the settings even with complicated facilities or facilities with rigid constraints on coordinated protection, this product provides multi-staged settings for many protective elements. The overcurrent element in particular has 14 different types of operating time characteristics and 3-staged definite time-delayed characteristics.

Multi-stage Protective Elements

Group setting function allows you to set another group of setting values in addition to the values for regular operation.This makes it easy to change all setting values for regular operation to the values for periodical inspection just by switching between groups.

Group Setting

Screen Image of the PC Software (in DI/DO mode)

Group Setting

Screen Image of PLC Setting on PC-HMI

Pull-out Structure

Input current/voltage waveform of the protection relay in operation and detection/operation status of each protective element can be recorded* for up to 5 events. Waveform and status of each protective element can be checked by using PC-HMI.Instantaneous value, effective value, frequency, harmonic, vector diagram will be shown when the cursor is moved over on the screen.Note: *Recording specification: a total of 5 seconds, 24 segments/1 cycle.

Waveform Recording and Analysis Tool

Operation/recovery of each protective element and each output contact can be recorded with time stamp* for up to 512 events. Also, the information can be recorded for up to 200 events in the case where abnormality is detected by continuous self-diagnosis function which detects abnormality in the protection relay.Note: *Time stamp is recorded at intervals of 1 ms.

Event Recording

Single-function type

Function Series Standard Application

A few MELPRO-A Series JIS or JEC Distribution protection for HV

Many NewMELPRO- JEC

Distribution protection for HV/EHVMotor protectionTransformer protectionSystem linkage protectionGenerator protection

JEC

Distribution protection for HV/EHVMotor protectionTransformer protectionSystem linkage protectionGenerator protection

MELPRO-D Series

D Series

Operational Time Characteristics of the Overcurrent Element

Setting values for operation・OCR Ope. Value: 3A・OCR Ope. Time: 0.2setc...

Setting values for inspection・OCR Ope. Value: 1A・OCR Ope. Time: 0.1setc...Switching

Screen Image of Waveform Analysis by PC-HMI

2

Page 3: MITSUBISHI Numerical Protection Relay...MITSUBISHI Numerical Protection Relay. -DSeries. Benefits. Improving reliability of power distribution system is critical for buildings, factories

Benefits

Improving reliability of power distribution system is critical for buildings, factories and any other facilities.To enhance protective and control systems and prevent major power outages, protection relays are essential. With a tendency toward a more advanced, complicated power distribution system in recent years, flexibility and accuracy are required for protection relays more than ever.With its enhanced functions added to the old models, the new “MELPRO-D Series” meets a variety of needs for power distribution system.

User Interface that is Easy to Use and Understand

Flexible and Rich Protection Functions Provide Flexibility inManaging Complicated Facilities

PLC (Programmable Logic Controller) Function Enables Reduction ofExternal Equipment and Wiring

Position of New MELPRO-D Series

VFD Indicator

VFD (Vacuum Florescent Display) is used for a numerical and character indicator.Its ability to display characters means that comparison between item numbers and reference table is no longer required, and its higher brightness and wider viewing angle ensures perfect readability even if the protection relay is located at a lower or higher place.Also, PC-HMI* (via USB 2.0) allows you to check various protection elements, output status, and the amount of input power. Setting values can be loaded and written through PC.Note: *PC-HMI is setting and monitoring software exclusively for the new “MELPRO-D Series” and available at “Mitsubishi Electric FA Site.” The protection relay supports USB Type B connection.

With increasingly complicated facilities, more and more timers and self-holding circuits are added to the outside of a protection relay as a condition for operation, closing, or warning of a breaker.To reduce such external equipment and wiring, the new “MELPRO-D Series” provides PLC function.PC-HMI allows you to build sequences based on the logic (e.g. AND/OR/NOT), timer (ON, OFF, One-shot), flip-flop (for holding) and other within the protection relay.

Excellent Compatibility with Our Existing Models Helps EasyReplacement

Dimensions for board processing of our existing “MULTICAP Series” and “MELPRO-D Series” are identical. They are easy to replace without an adapter. Also, excellent compatibility with existing models means minimal changes in design specifications. (except for some models*)Its pull-out structure makes it easy to slide out the main unit of the relay for testing in the maintenance process without disconnecting the wiring from the housing.Note: *D2 type models, such as CAC1-A01D2, among the existing models have different dimensions for board processing and require an adapter for replacement. For the adapter, please contact us.

Enhanced Recording Function Supports Analysis of AccidentFactors and Early Recovery

After an accident occurs, analyzing the factors and recovering equipment can take time. Delay in recovery may extend the damage from the accident even further.With its enhanced recording function, the new “MELPRO-D Series” supports analysis of accident factors and early recovery.

Ensuring a protection relay operates at the time of an accident and minimizing power outage areas require a coordinated protection with other equipment. With increasingly larger capacity of electrical equipment and complicated facilities, however, a coordinated protection is becoming harder and harder.To flexibly address this challenge in the settings even with complicated facilities or facilities with rigid constraints on coordinated protection, this product provides multi-staged settings for many protective elements. The overcurrent element in particular has 14 different types of operating time characteristics and 3-staged definite time-delayed characteristics.

Multi-stage Protective Elements

Group setting function allows you to set another group of setting values in addition to the values for regular operation.This makes it easy to change all setting values for regular operation to the values for periodical inspection just by switching between groups.

Group Setting

Screen Image of the PC Software (in DI/DO mode)

Group Setting

Screen Image of PLC Setting on PC-HMI

Pull-out Structure

Input current/voltage waveform of the protection relay in operation and detection/operation status of each protective element can be recorded* for up to 5 events. Waveform and status of each protective element can be checked by using PC-HMI.Instantaneous value, effective value, frequency, harmonic, vector diagram will be shown when the cursor is moved over on the screen.Note: *Recording specification: a total of 5 seconds, 24 segments/1 cycle.

Waveform Recording and Analysis Tool

Operation/recovery of each protective element and each output contact can be recorded with time stamp* for up to 512 events. Also, the information can be recorded for up to 200 events in the case where abnormality is detected by continuous self-diagnosis function which detects abnormality in the protection relay.Note: *Time stamp is recorded at intervals of 1 ms.

Event Recording

Single-function type

Function Series Standard Application

A few MELPRO-A Series JIS or JEC Distribution protection for HV

Many NewMELPRO- JEC

Distribution protection for HV/EHVMotor protectionTransformer protectionSystem linkage protectionGenerator protection

JEC

Distribution protection for HV/EHVMotor protectionTransformer protectionSystem linkage protectionGenerator protection

MELPRO-D Series

D Series

Operational Time Characteristics of the Overcurrent Element

Setting values for operation・OCR Ope. Value: 3A・OCR Ope. Time: 0.2setc...

Setting values for inspection・OCR Ope. Value: 1A・OCR Ope. Time: 0.1setc...Switching

Screen Image of Waveform Analysis by PC-HMI

3

Page 4: MITSUBISHI Numerical Protection Relay...MITSUBISHI Numerical Protection Relay. -DSeries. Benefits. Improving reliability of power distribution system is critical for buildings, factories

Lineups

Dimensions

Terminals (M3.5 screw)

Panel mount (4-M5 screw)

For Power supply and DO

For DI

For CT/VT inputs

Optional terminalsFor DO

Earth (M4 screw)

Overcurrent Relay Feeder Protection RelayDescription

COC1-A41D1 COC3-A41D1 COC4-A41D1 CFP1-A42D1 CFP1-A43D1

Protectionelement

Instantaneous overcurrent (50) ✔ (1phase, 3step) ✔ (3phase, 3step) ✔ (3phase, 3step) ✔ (2phase, 3step) ✔ (3phase, 3step)

2 of 3 steps are with 2nd harmonic restraint function.

Definite time or IDMT overcurrent (51) ✔ (1phase, 1step) ✔ (3phase, 1step) ✔ (3phase, 1step) ✔ (2phase, 1step) ✔ (3phase, 1step)

With 2nd harmonic restraint function, 14 kinds of operating time characteristics.

Instantaneous ground fault overcurrent (50G) - - ✔ (3step) - -

2 of 3 steps are with 2nd harmonic restraint function.

Definite time or IDMT ground fault overcurrent (51G) - - ✔ (1step) - -

With 2nd harmonic restraint function, 14 kinds of operating time characteristics.

Directional ground fault (67G) - - - ✔ (2step) ✔ (2step)

Metering

Current ✔ (1phase) ✔ (3phase) ✔ (3phase) ✔ (2phase) ✔ (3phase)Zero-sequence current - - ✔ ✔ ✔Zero-sequence voltage - - - ✔ ✔Phase - - - ✔ ✔

Number of Digital Output For trip : 4 For alarm : 4

For trip : 4 For alarm : 4

For trip : 4 For alarm : 4

For trip : 4 For alarm : 4

For trip : 4 For alarm : 4

Existing productCOC1-A01D1COC1-A02D1 (*)

COC2-A01D1COC3-A01D1COC3-A03D1

COC4-A01D1COC4-A02D1COC4-A03D1

CFP1-A01D1CFP1-A02D1

CDG1-A01D1

Description

(*) There are some differences about operating current.

ZCT, EVT: Commercially available (JEC1201 standardized oods)

EVT: Commercially available (JEC1201 standardized goods)

Voltage Relay Motor Protection Relay Transformer Protection Relay Description

CBV2-A41D1 CBV3-A41D1 CMP1-A42D1 CMP1-A43D1 CAC1-A42D1

Protectionelement

Undervoltage (27) ✔ (3phase, 2step) ✔ (1phase, 2step) - - - Phase voltage or Line voltage

Overvoltage (59) ✔ (3phase, 2step) ✔ (1phase, 2step) - - - Phase voltage or Line voltage

Ground fault overvoltage (64) ✔ (2step) ✔ (2step) - - -Negative sequence overvoltage (47)

✔ (2step) - - - - Detection of open phase

Reverse phase protection (47) ✔ (1step) - - - -Instantaneous overcurrent (50) - - ✔ (3phase, 1step) ✔ (3phase, 1step) ✔ (3phase, 3step)Definite time or IDMT overcurrent (51) - - ✔ (3phase, 1step) ✔ (3phase, 1step) ✔ (3phase, 1step)Ground fault overcurrent (51G) - - - ✔ (2step) -Directional ground fault (67G) - - ✔ (2step) — -Negative sequence overcurrent (46) - - ✔ (2step) ✔ (2step) -Open phase (46) - - ✔ (1step) ✔ (1step) -Undercurrent (37) - - ✔ (2step) ✔ (2step) -Overload (49) - - ✔ (1step) ✔ (1step) -Limitation of the number of starts (66)

- - ✔ (2type) ✔ (2type) - Accumulated heat type Number of starts type

Current ratio differential (87T) - - - - ✔ (3phase, 1step)Differential overcurrent (87TH) - - - - ✔ (3phase, 1step)

Metering

Voltage ✔ (3phase) ✔ (1phase) - - - Phase voltage or Line voltage

Zero-sequence voltage ✔ ✔ ✔ - -Positive-sequence voltage ✔ - - - -Negative-sequence voltage ✔ - - - -

Current - - ✔ (3phase) ✔ (3phase) ✔ (3phase) (HV-side, LV-side)

Zero-sequence current - - ✔ ✔ ✔ (S/W calculation) (HV-side, LV-side)

Positive-sequence current - - ✔ ✔ ✔ (HV-side, LV-side)Negative-sequence current - - ✔ ✔ ✔ (HV-side, LV-side)Phase ✔ - ✔ ✔ ✔Differential current - - - - ✔ (3phase)

Number of Digital Output For trip : 4For alarm : 4

For trip : 4For alarm : 4

For trip : 4For alarm : 4

For trip : 4For alarm : 4

For trip : 4For alarm : 4

Existing productCBV2-A01D1CBV4-A01D1CUB1-A01D1

CBV3-A01D1 CMP1-A01D1 CMP1-A02D1 CAC1-A01D2

Description

ZCT, EVT: Commercially available (JEC1201 standardized goods)

50 and 51elements can be applied to HV-side and LV-side respectively.

4

Page 5: MITSUBISHI Numerical Protection Relay...MITSUBISHI Numerical Protection Relay. -DSeries. Benefits. Improving reliability of power distribution system is critical for buildings, factories

Lineups

Dimensions

Terminals (M3.5 screw)

Panel mount (4-M5 screw)

For Power supply and DO

For DI

For CT/VT inputs

Optional terminalsFor DO

Earth (M4 screw)

System Linkage Protection Relay Generator Protection RelayCPP1-A41D1 CPP1-A43D1 CGP1-A41D1 CGP1-A42D1 CGP2-A41D1 CGP2-A42D1

Protectionelement

Undervoltage (27) ✔ (3phase, 2step) ✔ (3phase, 2step) ✔ (3phase, 2step) ✔ (3phase, 2step) - -Overvoltage (59) ✔ (1phase, 2step) ✔ (1phase, 2step) ✔ (1phase, 2step) ✔ (1phase, 2step) - -Ground fault overvoltage (64) ✔ (2step) ✔ (2step) ✔ (2step) - - -Underfrequency (91L) ✔ (2step) ✔ (2step) ✔ (2step) ✔ (2step) - -Overfrequency (91H) ✔ (2step) ✔ (2step) ✔ (2step) ✔ (2step) - -Directional short circuit (67S) ✔ (3phase, 2step) ✔ (3phase, 2step) - - - -Underpower (91L) ✔ (2step) ✔ (2step) - - - -Reverse power (67P) ✔ (2step) ✔ (2step) ✔ (2step) ✔ (2step) - -Islanding detection (df/dt) - ✔ (2step) - - - -Instantaneous overcurrent (50) - - ✔ (2phase, 3step) ✔ (3phase, 3step) - -Definite time or IDMT overcurrent (51) - - ✔ (2phase, 1step) ✔ (3phase, 1step) - -Instantaneous unbalance current (46-1) ✔ (1step) ✔ (1step)IDMT unbalance current (46-2) - - ✔ (1step) ✔ (1step) - -Directional ground fault (67G) - - ✔ (2step) - - -Ground fault overcurrent (51G) - - - ✔ (2step) - -Voltage detection (84) - - ✔ (1step) ✔ (1step) - -Current ratio differential (87G) - - - - ✔ (1step) ✔ (1step)Loss of field (40) - - - - ✔ (1step) -

Metering

Line voltage ✔ (3phase) ✔ (3phase) ✔ (3phase) ✔ (3phase) ✔ (1phase) -Zero-sequence voltage ✔ ✔ ✔ - - -Positive-sequence voltage ✔ ✔ ✔ ✔ - -Negative-sequence voltage ✔ ✔ ✔ ✔ - -

Current ✔ (3phase) ✔ (3phase) ✔ (2phase) ✔ (3phase) ✔ (3phase)(Both sides)

✔ (3phase)(Both sides)

Zero-sequence current - - ✔ ✔ - -Positive-sequence current ✔ ✔ ✔ ✔ - -Negative-sequence current ✔ ✔ ✔ ✔ - -Phase ✔ ✔ ✔ ✔ ✔ ✔Active power ✔ ✔ ✔ ✔ - -Reactive power ✔ ✔ ✔ ✔ - -Apparent power ✔ ✔ ✔ ✔ - -Power factor ✔ ✔ ✔ ✔ - -Active electric energy ✔ ✔ ✔ ✔ - -Reactive electric energy ✔ ✔ ✔ ✔ - -System frequency ✔ ✔ ✔ ✔ - -Differential current - - - - ✔ (3phase) ✔ (3phase)

Number of Digital Output For trip : 4For alarm : 9

For trip : 4For alarm : 9

For trip : 4For alarm : 9

For trip : 4For alarm : 9

For trip : 4For alarm : 4

For trip : 4For alarm : 4

Existing product CPP1-A01D2 CPP1-A11D2 CGP1-A01D2 CGP1-A03D2 CGP2-A01D2 CGP2-A02D2

Description

EVT: Commercially available (JEC1201 standardized goods)

EVT: Commercially available (JEC1201 standardized goods)

ZCT, EVT: Commercially available (JEC1201 standardized goods)

Please refer to the instruction manuals for details.

5

Page 6: MITSUBISHI Numerical Protection Relay...MITSUBISHI Numerical Protection Relay. -DSeries. Benefits. Improving reliability of power distribution system is critical for buildings, factories

Technical Data<Compliance standards> JEC2500 (2010), JEC2501 (2010)<Ratings> AC: 5A, 100V~125V (line voltage), 50 or 60Hz Power supply: DC 100~220V / AC 100~220V (common use)

Item Guaranteed conditions Compliance standard

Common conditions of use

Ambient temperature0 ~ +40°C(-10 ~ 50°C is allowable temporarily within few hours a day, but use under the state where dew condensation or freezing does not occur.)

JEC2500 (2010)

Relative humidity 30 ~ 80% on daily averageAltitude 2000m or lower

Others

Abnormal vibration, shock, inclination, magnetic field are not applied.It is not exposed to harmful smoke/gas, gas containing salt, water droplet or vapor, excessive dust or fine powder, explosive gas or fine powder, wind & rain.

Storage conditionAmbient temperature: –20 to +60 °CDew condensation or freezing does not occur.

Power supplyRatings DC: 100, 110, 125, 220V

JEC2500 (2010)Variation range

DC: 85 ~ 242V (80 ~ 286V is allowable temporarily.)AC: 85 ~ 242V (85 ~ 253V is allowable temporarily.)

Contact capacity

Trip contact Annunciation contact

JEC2500 (2010)

Make Break Make Break

DC110V: 15ADC220V: 10A0.5s (L/R = 0)

DC110V: 0.3ADC220V: 0.15A(L/R = 40ms)

Make / Break circuit capacity:500VA(cosφ = 0.4), 60W(L/R = 7ms)Max. current: 5AMax. voltage: AC 380V, DC 125V

Dust proof (IP code) Front: IP51, Side and Back: IP30

Withstand overload

CT Rated current × 40 times, for 1 s, twice, at intervals of 1 min

JEC2500 (2010)ZCT Rated current × 40 times, for 1 s, twice, at intervals of 1 minVT Rated voltage × 1.15 times, for 3 h, once

EVT Rated voltage × 1.15 times, for 3 h, oncePower supply Max. voltage, for 3 h, once

Power supply voltage disturbance Withstand power supply voltage disturbance of open/close, short interruption and slow voltage change JEC2500 (2010)

Insulation resistance DC500V Megger

Between all terminals and earth(Except for serial communication terminal)

More than 10M ohm

JEC2500 (2010)Between independent circuitsBetween contact terminals(Except for serial communication terminal)

More than 5M ohm

Withstand voltageat commercial frequency

AC2000V, 1minBetween all terminals and earthBetween independent circuits.(Except for serial communication terminal) JEC2500 (2010)

AC1000V, 1min Between contact terminals

Impulse voltage withstandThree positive and three negative impulse of 1.2/50us

4.5kV

Between all terminals and earthBetween CT/VT circuitsBetween CT/VT circuit and DI circuit(Except for serial communication terminal)

JEC2500 (2010)

3.0kV

Between DI circuitBetween terminals of CT/VT circuitBetween contact terminalsBetween terminals of power supply circuit(Except for serial communication terminal)

Vibration JEC2500 (2010)

Shock

・Shock acceleration: 300m/s2

・Duration of pulse: 11ms・Direction of pulses: Back / Forth, Right / Left, Up / Down (6 directions)・Number of pulses: 3 times for 6 directions (In total: 18 times)

JEC2500 (2010)

BurdenCT: Less than 0.6VAVT: Less than 0.1VAPower supply: Less than 10W

Frequency[Hz]

1016.7

30600

5 2.50.4

10 52

Amplitude [mm]

Back /Forth

Right /Left

UP /Down

Back /Forth

Right /Left

UP /Down

Acceleration [m/s2]Time

[s]

6

Page 7: MITSUBISHI Numerical Protection Relay...MITSUBISHI Numerical Protection Relay. -DSeries. Benefits. Improving reliability of power distribution system is critical for buildings, factories

Technical Data

Item Guaranteed conditions Compliance standard

Electrostatic discharge8kV: At discharging in contact15kV: At discharging in the air10 times of each of positive and negative pole at intervals of more than 1 s

JEC2501 (2010)

Commercial (power)frequency disturbance

300V for 10 s applied to ports in common mode (between line and ground)150V for 10 s applied to ports in differential mode (between lines)

JEC2501 (2010)

Damped oscillatory wave disturbance

・Peak value of 1st wave: 2.5kV・Vibration frequency: 1MHz ± 10%・Damping time to 1/2: 3 ~ 6 cycles・Frequency of repetition: 6 ~ 10 times / 1 cycle of commercial frequency (asynchronous)・Output impedance of test circuit: 200Ω ± 10%・Applied point:-Between all CT/VT circuits and earth-Between power supply circuit and earth-Between terminals of power supply circuit

JEC2501 (2010)

Electric fast transient/Burst(EFT/B) disturbance

Applied voltage: ± 2.0kVRepetition frequency: 5.0kHz-Between power supply circuit and earth

JEC2501 (2010)Applied voltage: ±1.0kVRepetition frequency: 5.0kHz-Between all CT/VT circuits and earth-Between all DI/DO circuits and earth

Square wave impulse disturbance

・Applied voltage: 1.0kV ± 10%・Test time: 2s・Pulse duration: 100 ns ± 30%・Pulse rise time: 1 ns ± 30%・Applied point:-Between all CT/VT circuits and earth-Between power supply circuit and earth-Between terminals of power supply circuit-Between all DI/DO circuits and earth

JEC2501 (2010)

Surge immunity

Applied time: 1.2/50us at open circuit condition, 8/20us at short circuit conditionEffective output impedance: 2Ω5 times of each of positive and negative pole at intervals 1min・Applied point and voltage:-Between terminals of power supply circuit: 0.5, 1kV (0Ω, 18uF)-Between power supply circuit and earth: 0.5, 1, 2kV (10Ω, 9uF)-Between terminals of CT/VT circuit: 0.5, 1kV (40Ω, 0.5uF)-Between all CT/VT circuits and earth: 0.5, 1, 2kV (40Ω, 0.5uF)-Between terminals of DI/DO circuit: 0.5, 1kV (40Ω, 0.5uF)-Between all DI/DO circuits and earth: 0.5, 1, 2kV (40Ω, 0.5uF)

JEC2501 (2010)

Commercial (power)frequency magnetic field immunity

Magnetic field intensity:30A/m, continuously300A/m, 1 ~ 3s

JEC2501 (2010)

RF electromagnetic field immunity

Frequency range: Sweep test: 150 kHz ~ 80MHz Spot test: 27, 68MHzVoltage level: 10VAmplitude modulation: 1kHz, ±80%

JEC2501 (2010)

Radiated electromagneticfield immunity

Frequency range: Sweep test: 80 MHz ~ 1.0GHz, 1.4GHz ~ 2.7GHz Spot test: 80, 160, 380, 450, 900, 1850, 2150MHzVoltage level: 10V/mAmplitude modulation: 1kHz, ±80%

JEC2501 (2010)

7

Page 8: MITSUBISHI Numerical Protection Relay...MITSUBISHI Numerical Protection Relay. -DSeries. Benefits. Improving reliability of power distribution system is critical for buildings, factories

MELPROTM

SE-E849(19.10-1.0)ROS Published Oct.2019This printed matter has been published in October 2019. Please note that specifications are subject to change without notice.

MITSUBISHI Numerical Protection Relay

MELPROTM-D Series

MITSUBISHI Numerical Protection Relay

-D Series