miranda damping ratios v5 for seaonc

32
1 Damping Ra*os in Buildings Obtained from Instrumented Buildings in California SEAONC, Structural Engineers Associa5ons of Northern California January 29 th , 2014 Eduardo Miranda Dept. of Civil and Environmental Engineering Stanford University January Mini Seminar Damping Ratios in Buildings 2 ACKNOWLEDGEMENTS SEAONC’S con8nuing educa8on commi;ee Lukki Lam, ARUP Tim Hart, LBL Tony Shakal and Moh Huang, CSMIP, CGS Masume Dana, ForellElsesser Damping Ratios in Buildings 3 Mo5va5on Unlike the sta8c response on structures, the response to dynamic loads (earthquake, wind, blast, etc) depends on the damping in the structure. Our knowledge of damping mechanisms in structures is rather limited and design provisions do not provide a lot of guidance in this respect. Therefore, knowledge of the level of damping in a structure is essen8al for the ra8onal analysis and design of structures subjected to dynamic loads. Damping Ratios in Buildings 4 Mo5va5on I encourage you to do a search on the word damping on, for example, ASCE 710. I found it men8oned on 81 pages. Yet, I do not think there is a lot of guidance Chapter 16 SEISMIC RESPONSE HISTORY PROCEDURES includes the following: 16.1.2 Modeling Mathema8cal models shall conform to the requirements of Sec8on 12.7 But as men8oned above sec8on 12.7 provides no guidance on damping. But none of these sec8ons say anything about damping and in par8cular what damping value to use. Sec*on 12.7 MODELING CRITERIA has sec8ons on 12.7.1 Founda8on modeling 12.7.2 Effec8ve seismic weight 12.7.3 Structural modeling Sec*on 12.9 MODAL RESPONSE SPECTRUM ANALYSIS interes8ngly it doesn’t say anything about damping and just says to use the 5% damped spectrum as input, essen8ally recommending to use 5% damping ra8o for all modes for all structures.

Upload: m-refaat-fath

Post on 05-Feb-2016

12 views

Category:

Documents


0 download

DESCRIPTION

damping

TRANSCRIPT

Page 1: Miranda Damping Ratios v5 for Seaonc

1  

Damping  Ra*os  in  Buildings  Obtained  from  Instrumented  Buildings  in  California    

SEAONC,  Structural  Engineers  Associa5ons  of  Northern  California   January  29th,  2014  

Eduardo  Miranda  Dept.  of  Civil  and  Environmental  Engineering  

Stanford  University  

January  Mini  -­‐Seminar  

Damping Ratios in Buildings 2  

ACKNOWLEDGEMENTS  

SEAONC’S  con8nuing  educa8on  commi;ee  

Lukki  Lam,  ARUP  

Tim  Hart,  LBL  

Tony  Shakal  and  Moh  Huang,  CSMIP,  CGS  

Masume  Dana,  Forell-­‐Elsesser  

Damping Ratios in Buildings 3  

Mo5va5on  

Unlike  the  sta8c  response  on  structures,  the  response  to  dynamic  loads  (earthquake,  wind,  blast,  etc)  depends  on  the  damping  in  the  structure.  

Our  knowledge  of  damping  mechanisms  in  structures  is  rather  limited  and  design  provisions  do  not  provide  a  lot  of  guidance  in  this  respect.  

Therefore,  knowledge  of  the  level  of  damping  in  a  structure  is  essen8al  for  the  ra8onal  analysis  and  design  of  structures  subjected  to  dynamic  loads.  

Damping Ratios in Buildings 4  

Mo5va5on  I  encourage  you  to  do  a  search  on  the  word  damping  on,  for  example,  ASCE  7-­‐10.    I  found  it  men8oned  on  81  pages.  Yet,  I  do  not  think  there  is  a  lot  of  guidance  

Chapter  16  SEISMIC  RESPONSE  HISTORY  PROCEDURES  includes  the  following:  16.1.2  Modeling    Mathema8cal  models  shall  conform  to  the  requirements  of  Sec8on  12.7    But  as  men8oned  above  sec8on  12.7  provides  no  guidance  on  damping.        

But  none  of  these  sec8ons  say  anything  about  damping  and  in  par8cular  what  damping  value  to  use.  

Sec*on  12.7  MODELING  CRITERIA  has  sec8ons  on      12.7.1  Founda8on  modeling  12.7.2  Effec8ve  seismic  weight  12.7.3  Structural  modeling  

Sec*on   12.9   MODAL   RESPONSE   SPECTRUM   ANALYSIS   interes8ngly   it  doesn’t   say   anything   about   damping   and   just   says   to   use   the   5%   damped  spectrum  as  input,  essen8ally  recommending  to  use  5%  damping  ra8o  for  all  modes  for  all  structures.  

Page 2: Miranda Damping Ratios v5 for Seaonc

2  

Damping Ratios in Buildings 5  

Mo5va5on  

Chapter  17    SEISMIC  DESIGN  REQUIREMENTS  FOR  SEISMICALLY  ISOLATED  STRUCTURES  doesn’t  help  a  lot  either.  For  example:  

17.6.3.3  Response-­‐Spectrum  Procedure    Response-­‐spectrum  analysis   shall   be  performed  using  a  modal  damping  value  for   the   fundamental   mode   in   the   direc8on   of   interest   not   greater   than   the  effec8ve  damping  of  the  isola8on  system  or  30  percent  of  cri8cal,  whichever  is  less.  Modal  damping  values  for  higher  modes  shall  be  selected  consistent  with  those   that   would   be   appropriate   for   response-­‐   spectrum   analysis   of   the  structure  above  the  isola8on  system  assuming  a  fixed  base.    

But  what  is  an    “appropriate”    damping  ra5o  for  a  fixed-­‐base  structure?  

Damping Ratios in Buildings 6  

18.6.2.1  Inherent  Damping  Inherent   damping,  β

I,   shall   be   based   on   the  material   type,   configura8on,  

and   behavior   of   the   structure   and   nonstructural   components   responding  dynamically   at   or   just   below   yield   of   the   seismic   force-­‐resis8ng   system.  Unless  analysis  or   test  data   supports  other  values,   inherent  damping   shall  be  taken  as  not  greater  than  5  percent  of  cri8cal  for  all  modes  of  vibra8on.  

Perhaps  the  chapter  where  you  find  a  li;le  bit  more  informa8on  is    

Chapter  18    SEISMIC  DESIGN  REQUIREMENTS  FOR  STRUCTURES  WITH  DAMPING  SYSTEMS      Where  there  is  a  sec8on  that  says    

Mo5va5on  

But  again  that  is  not  a  lot  of  guidance  !  

(Interes8ngly  enough  wind  design  provisions  (4  chapters  and  117  pages)  don’t  provide  any  guidance  either.)    

Damping Ratios in Buildings 7  

Mo5va5on  

Bo\om  line…    Design   provisions   do   not   provide   much  guidance   as   to   what   damping   we   should  use  when  analyzing/designing  buildings    

Fortunately  there  are  some  excep5ons  …  

Damping Ratios in Buildings 8  

Mo5va5on  

Page 3: Miranda Damping Ratios v5 for Seaonc

3  

Damping Ratios in Buildings 9  

(Ager  Newmark  and  Hall,  1973)  

Mo5va5on  

Damping Ratios in Buildings 10  

Mo5va5on  

“Whereas five percent of critical damping has been traditionally assumed for conventional buildings designed by code procedures, there is indisputable evidence that this is higher than the actual damping of modern tall buildings.” “A damping ratio of between 1% and 2% appears reasonable for buildings more than 50 m and less than 250 m in height.”

Damping Ratios in Buildings 11  

Mo5va5on  

L o s A n g e l e s T a l l B u i l d i n g s S t r u c t u r a l D e s i g n C o u n c i l

AN ALTERNATIVE PROCEDURE FOR SEISMIC ANALYSIS AND DESIGN OF TALL BUILDINGS LOCATED IN THE LOS ANGELES REGION

A CONSENSUS DOCUMENT

2011 Edition including 2013 Supplement

C.3.5.2.2  Damping  effects  of  structural  members  that  are  not   incorporated   in   the   analysis   model   (e.g.,   gravity  framing),   founda8on-­‐soil   interac8on,   and   nonstructural  components   that   are   not   otherwise   modeled   in   the  analysis   can   be   incorporated   through   equivalent   viscous  damping.   The   amount   of   viscous   damping   should   be  adjusted   based   on   specific   features   of   the   building  design  and  may  be  represented  by  either  modal  damping,  explicit   viscous   damping   elements,   or   a   combina8on   of  s8ffness   and   mass   propor8onal   damping   (e.g.,   Rayleigh  damping).      

3.5.2.2.  Damping    Significant   hystere8c   energy   dissipa8on   shall   be  captured   directly   by   inelas8c   elements   of   the  model.   A   small   amount   of   equivalent   viscous   or  combined   mass   and   s8ffness   propor8onal  damping   may   also   be   included.   The   effec*ve  addi*onal  modal  or  viscous  damping  should  not  exceed   2.5%   of   cri5cal   for   the   primary  modes  of  response.      

Damping Ratios in Buildings 12  

Mo5va5on  

“A   number   of   studies   have   a;empted   to  characterize  the  effec8ve  damping  in  real  buildings.  These  studies  range  from  evalua8on  of  the  recorded  response   to   low-­‐   amplitude   forced   vibra8ons   to  review   and   analysis   of   strong   mo8on   recordings.  Using   data   obtained   from   eight   strong   mo8on  California   earthquakes,   Goel   and   Chopra   (1997)  found  that  effec8ve  damping  for  buildings  in  excess  of  35  stories  ranged  from  about  2%  to  4%  of  cri8cal  damping.   Using   data   obtained   from   Japanese  earthquakes,   Satake   et   al.   (2003)   found   effec8ve  damping  in  such  structures  to  be  in  the  range  of  1%  to  2%.  Given   this   informa8on  and   the   impossibility  of  precisely  defining  damping  for  a  building  that  has  not   yet   been   constructed,   these   Guidelines  recommend  a  default  value  of  2.5%  damping  for  all  modes  for  use  in  Service  Level  evalua5ons.  “    

TBI Guidelines for

Performance-

Based Seismic

Design of

Tall Buildings !"#$%&'()*+(

,&-"./"#(0+)+(

PEER

Page 4: Miranda Damping Ratios v5 for Seaonc

4  

Damping Ratios in Buildings 13  

Mo5va5on  

Modeling and acceptance criteria

for seismic design and analysis of

tall buildings

Pacific Earthquake Engineering Research Center

Applied Technology Council

PEER/ATC 72-1

foundation

main backstay diaphragm

tower core wall

M

V

foundation

main backstay diaphragm

tower core walltower core wall

M

V

PEER/ATC-72-1 2: General Nonlinear Modeling 2-55

damping should be adjusted based on specific features of the building design,

and may be represented by either modal damping, explicit viscous damping

elements, or a combination of stiffness- and mass-proportional damping (e.g.,

Rayleigh damping). Among the various alternatives, it is generally

recommended to model viscous damping using modal damping, Rayleigh

damping, or a combination of the two. Care should be taken when specifying

stiffness-proportional damping components of Rayleigh damping to avoid

overdamping in higher modes, or force imbalances in gap-type elements and

rigid-plastic materials and components.

Generally, the amount of damping is quantified in terms of a percentage of

critical damping in one or more elastic vibration modes, although it is also

recognized that distinct vibration modes and frequencies do not exist for

nonlinear response as they do with elastic analysis. Existing guidelines

suggest the use of viscous damping values ranging from 2% to 5% of critical

for nonlinear response history analyses of typical buildings subjected to

strong ground motions. Laboratory tests suggest that damping values of

about 1% for steel frame structures and 2% to 3% for reinforced concrete

structures be used to model energy dissipation that occurs in bare structural

systems, under small deformations, that is not accounted for in typical

hysteretic models. Measured data from earthquake induced motions of actual

buildings suggest damping values in the range of 1% to 5% for quasi-elastic

response of buildings over 30 stories tall. Measurements in actual buildings

indicate that the damping in tall buildings is lower than damping in low- to

mid-rise buildings.

The following values of equivalent viscous damping are suggested as

appropriate for use in nonlinear response history analysis of typical

buildings, in which most of the hysteretic energy dissipation is accounted for

in the nonlinear component models of the structural members of the seismic-

force-resisting system:

D = ;/30 (for N < 30) (2-9)

D = ;/N (for N > 30) (2-10)

where D is the maximum percent critical damping, N is the number of

stories, and ;)is a coefficient with a recommended range of ; = 60 to 120. In

general, structural steel systems would tend toward the lower range of

damping (; = 60), and reinforced concrete systems of would tend toward the

upper range (;)= 120). Figure 2-28 shows damping ranges between 2% to

4% for 30-story buildings and 1% to 2% for 70-story buildings. Damping

PEER/ATC-72-1 2: General Nonlinear Modeling 2-47

models. For fiber-type models, the best agreement was obtained using zero

damping. For plastic hinge models, the best agreement was obtained using

5% stiffness-proportional viscous damping, where the damping was based on

the tangent stiffness matrix (i.e., the damping terms were reduced in

proportion to the changes in the tangent stiffness during the analysis). Thus,

when compared to models with constant damping, effective damping in the

plastic hinge models was probably much less than 5%.

Recommendations from Gulkan and Sozen (1971) equate dissipated energy

to equivalent viscous damping. While originally envisioned for elastic

analyses, their recommendations help relate damping effects to displacement

amplitudes. They recommended a threshold value for damping in an

undamaged reinforced concrete structure at 2% of critical damping, and

demonstrated how equivalent damping quickly increased to 5% at an

imposed displacement ductility of 1.4, and 10% at an imposed ductility of

2.8. In the context of nonlinear analysis, these findings suggest a minimum

value of 2% critical damping, where any increase in viscous damping beyond

this value would depend on how well the nonlinear analysis captured

hysteretic energy dissipation in the structural components.

2.4.4 Modeling Techniques for Damping

The quantification and definition of damping are integrally linked with how

damping is modeled. For elastic analyses, damping is defined in terms of

equivalent viscous damping through the velocity dependent term, [C], in the

equation of motion, as follows:

< => ? < => ? < => ? < => ? < =PxMxKxCxM g @23@@ !!!!! (2-3)

This is done for mathematical convenience, since the velocity is out of phase

with displacement and acceleration, and thus provides an easy way to

incorporate a counteracting force to damp out motions in a linear analysis.

To facilitate modal analyses, the damping matrix is often defined using either

the classical Rayleigh damping assumption, where [C] is calculated as a

linear combination of the mass [M] and stiffness [K] matrices, or modal

damping, where [C] is a combination of specified damping amounts for

specific vibration modes (usually elastic vibration modes). These damping

formulations are explained below.

Rayleigh Damping. The damping matrix and resulting critical damping

ratios are calculated as follows:

[ ] [ ] [ ]M KC a M a K3 @ (2-4)

Damping Ratios in Buildings 14  

Mo5va5on  

But   how   good   or   how   bad   are   these  guidelines  ?    

Damping Ratios in Buildings 15  

There  is  not  adequate  guidance  either  as  to  what  change  in  level  of   response   one   may   expect   from   changes   in   the   level   of  damping.      e.g.,      How  much  larger  my  response  will  be  if  my  structure  has  1%  damping  instead  of  5%?    How  much  smaller  my  response  will  be  if  my  structure  has  10%  damping  instead  of  5%?  

Mo5va5on  

Damping Ratios in Buildings 16  

CHAPTER 18 SEISMIC DESIGN REQUIREMENTS FOR STRUCTURES WITH DAMPING SYSTEMS

190

! = "RD

RD

RT2# (18.5-25)

where

!1D = design story velocity due to the fundamental mode of vibration of the structure in the direction of interest

!RD = design story velocity due to the residual mode of vibration of the structure in the direction of interest

18.5.3.5 Maximum Considered Earthquake ResponseTotal and modal maximum fl oor defl ections at

Level i, design story drifts, and design story velocities shall be based on the equations in Sections 18.5.3.1, 18.5.3.3, and 18.5.3.4, respectively, except that design roof displacements shall be replaced by maximum roof displacements. Maximum roof displacements shall be calculated in accordance with Eqs. 18.5-26 and 18.5-27:

D

g S TB

g S TB

T TMMS M

M

MS

EM S1 2 1

12

12 1

12

11

4 4= $

%&'()

* $%&

'()

<# #

+ + ,

(18.5-26a)

D

g S TB

g S TB

T TMM M

M

M

EM S1 2 1

1 1

12 1

1 1

11

4 4= $

%&'()

* $%&

'()

*# #

+ + ,

(18.5-26b)

Dg S T

Bg S T

BRM R

M R

RR

MS R

R

= $%&

'()

, $%&

'()4 42

12

2

# #+ + (18.5-27)

where

SM1 = the MCER, 5 percent damped, spectral response acceleration parameter at a period of 1 s adjusted for site class effects as defi ned in Section 11.4.3

SMS = the MCER, 5 percent damped, spectral response acceleration parameter at short periods adjusted for site class effects as defi ned in Section 11.4.3

B1M = numerical coeffi cient as set forth in Table 18.6-1 for effective damping equal to -mM (m = 1) and period of structure equal to T1M

18.6 DAMPED RESPONSE MODIFICATION

As required in Sections 18.4 and 18.5, response of the structure shall be modifi ed for the effects of the damping system.

18.6.1 Damping Coeffi cientWhere the period of the structure is greater than

or equal to T0, the damping coeffi cient shall be as prescribed in Table 18.6-1. Where the period of the structure is less than T0, the damping coeffi cient shall be linearly interpolated between a value of 1.0 at a 0-second period for all values of effective damping and the value at period T0 as indicated in Table 18.6-1.

18.6.2 Effective DampingThe effective damping at the design displace-

ment, -mD, and at the maximum displacement, -mM, of the mth mode of vibration of the structure in the direction under consideration shall be calculated using Eqs. 18.6-1 and 18.6-2:

- - - µ -mD I Vm D HD= + + (18.6-1)

- - - µ -mM I Vm M HM= + + (18.6-2)

where

-HD = component of effective damping of the structure in the direction of interest due to post-yield hysteretic behavior of the seismic force-resisting system and elements of the damping system at effective ductility demand, µD

-HM = component of effective damping of the struc-ture in the direction of interest due to post-yield hysteretic behavior of the seismic force-resist-ing system and elements of the damping system at effective ductility demand, µM

-I = component of effective damping of the struc-ture due to the inherent dissipation of energy

Table 18.6-1 Damping Coeffi cient, BV+I, B1D, BR, B1M, BmD, BmM (Where Period of the Structure ! T0)

Effective Damping, -(percentage of critical)

Bv+I, B1D, BR, B1M, BmD, BmM

(where period of the structure * T0)

,2 0.85 1.0

10 1.220 1.530 1.840 2.150 2.460 2.770 3.080 3.390 3.6

*100 4.0

c18.indd 190c18.indd 190 4/14/2010 11:03:35 AM4/14/2010 11:03:35 AM

Damping  modifica8on  factors  used  in  U.S.  prac8ce  

For  structures  with  damping  systems  For  seismically  isolated  structures  

Mo5va5on  

CHAPTER 17 SEISMIC DESIGN REQUIREMENTS FOR SEISMICALLY ISOLATED STRUCTURES

170

1. The structure is located on a Site Class A, B, C, or D.

2. The isolation system meets the criteria of Item 7 of Section 17.4.1.

17.4.2.2 Response-History ProcedureThe response-history procedure is permitted for

design of any seismically isolated structure and shall be used for design of all seismically isolated struc-tures not meeting the criteria of Section 17.4.2.1.

17.5 EQUIVALENT LATERAL FORCE PROCEDURE

17.5.1 GeneralWhere the equivalent lateral force procedure is

used to design seismically isolated structures, the requirements of this section shall apply.

17.5.2 Deformation Characteristics of the Isolation System

Minimum lateral earthquake design displacements and forces on seismically isolated structures shall be based on the deformation characteristics of the isolation system. The deformation characteristics of the isolation system shall explicitly include the effects of the wind-restraint system if such a system is used to meet the design requirements of this standard. The deformation characteristics of the isolation system shall be based on properly substantiated tests per-formed in accordance with Section 17.8.

17.5.3 Minimum Lateral Displacements

17.5.3.1 Design DisplacementThe isolation system shall be designed and

constructed to withstand minimum lateral earthquake displacements, DD, that act in the direction of each of the main horizontal axes of the structure using Eq. 17.5-1:

DgS T

BD

D D

D

= 124!

(17.5-1)

where

g = acceleration due to gravity. The units for g are in./s2 (mm/s2) if the units of the design displace-ment, DD, are in. (mm)

SD1 = design 5 percent damped spectral acceleration parameter at 1-s period in units of g-s, as determined in Section 11.4.4

TD = effective period of the seismically isolated structure in seconds, at the design displacement in the direction under consideration, as pre-scribed by Eq. 17.5-2

BD = numerical coeffi cient related to the effective damping of the isolation system at the design displacement, "D, as set forth in Table 17.5-1

17.5.3.2 Effective Period at Design DisplacementThe effective period of the isolated structure at

design displacement, TD, shall be determined using the deformational characteristics of the isolation system and Eq. 17.5-2:

TW

k gD

D

= 2!min

(17.5-2)

where

W = effective seismic weight of the structure above the isolation interface as defi ned in Section 12.7.2

kDmin = minimum effective stiffness in kips/in. (kN/mm) of the isolation system at the design displacement in the horizontal direction under consideration, as prescribed by Eq. 17.8-4

g = acceleration due to gravity

17.5.3.3 Maximum DisplacementThe maximum displacement of the isolation

system, DM, in the most critical direction of horizontal response shall be calculated using Eq. 17.5-3:

DgS T

BM

M M

M

= 124!

(17.5-3)

Table 17.5-1 Damping Coeffi cient, BD or BM

Effective Damping, "D or "M (percentage of critical)a,b BD or BM Factor

#2 0.85 1.0

10 1.220 1.530 1.740 1.9

$50 2.0

a The damping coeffi cient shall be based on the effective damping of the isolation system determined in accordance with the requirements of Section 17.8.5.2.b The damping coeffi cient shall be based on linear interpolation for effective damping values other than those given.

c17.indd 170c17.indd 170 4/14/2010 11:02:59 AM4/14/2010 11:02:59 AM

Page 5: Miranda Damping Ratios v5 for Seaonc

5  

Damping Ratios in Buildings 17  

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

0 20 40 60 80 100 120

Damping Ratio, %

Damping Modification Factor B

Chapter 18

Chapter 17

Damping  modifica8on  factors  used  in  U.S.  prac8ce  

Mo5va5on  

Damping Ratios in Buildings 18  

Damping  modifica8on  factors  used  in  U.S.  prac8ce  

Mo5va5on  

0.0

0.2

0.4

0.6

0.8

1.0

1.2

1.4

0 20 40 60 80 100 120

Damping Ratio, %

1 / B

Chapter 17

Chapter 18

Damping Ratios in Buildings 19  

There  are  various  deficiencies  with  these  factors:  

Mo5va5on  

1.  Even  if  based  on  sta8s8cal  studies  one  must  take  into  account  that:  

E 1B!

"#$

%&≠

1E B[ ]

With  the  difference  increasing  with  the  level  of  dispersion/variability  

Damping Ratios in Buildings 20  

0.0

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

0% 20% 40% 60% 80% 100%

Damping Ratio, %

1 / B

T = 0.2 s

T = 1 s

T = 5 s

Mo5va5on  

2.  They  either  neglect  or  do  not  correctly  account  for  the  effect  of  period/frequency  dependency  on  these  factors.  

(Ager  Lin,  Miranda  and  Chang  2005)  

Page 6: Miranda Damping Ratios v5 for Seaonc

6  

Damping Ratios in Buildings 21  

0.5

0.6

0.7

0.8

0.9

1.0

1.1

1.2

1.3

1.4

1.5

0% 5% 10% 15% 20%

Damping Ratio, %

1 / B

T = 0.2 s T = 1 s T = 5 s Chapter 17 Chapter 18

Mo5va5on  

Despite   these   two   problems   if   one   compares   the   damping  modifica8on   factors   with   expected   values   obtained   from  sta8s8cal  results,  things  don’t  look  too  bad…  

(Ager  Lin,  Miranda  and  Chang  2005)  Damping Ratios in Buildings 22  

0.5

0.6

0.7

0.8

0.9

1.0

1.1

1.2

1.3

1.4

1.5

0% 5% 10% 15% 20%

Damping Ratio, %

1 / B

T = 0.2 s T = 1 s T = 5 s Chapter 17 Chapter 18

Mo5va5on  

How  much  larger  my  response  will  be  if  my  structure  has  1%  damping  instead  of  5%?    

25%  larger    

Damping Ratios in Buildings 23  

0.5

0.6

0.7

0.8

0.9

1.0

1.1

1.2

1.3

1.4

1.5

0% 5% 10% 15% 20%

Damping Ratio, %

1 / B

T = 0.2 s T = 1 s T = 5 s Chapter 17 Chapter 18

Mo5va5on  

How  much  smaller  my  response  will  be  if  my  structure  has  10%  damping  instead  of  5%?  

20%  smaller    

Damping Ratios in Buildings 24  

Mo5va5on  

3.  They  neglect  the  large  effect  of  period  from  record-­‐to-­‐record    OK,  but  …    

0"

200"

400"

600"

800"

1000"

1200"

0" 1" 2" 3" 4" 5"

Sa#[cm/s2]#

Period#[s]#

ξ = 0.01"

ξ = 0.02"

ξ = 0.05"

ξ = 0.1"

ξ = 0.15"

ξ = 0.2"

ξ = 0.25"

ξ = 0.3"

1999  Chi-­‐Chi  TCU136N  

Page 7: Miranda Damping Ratios v5 for Seaonc

7  

Damping Ratios in Buildings 25  

0"

10"

20"

30"

40"

50"

60"

70"

80"

0" 1" 2" 3" 4" 5"

Sd#[cm]#

Period#[s]#

ξ = 0.01"

ξ = 0.02"

ξ = 0.05"

ξ = 0.1"

ξ = 0.15"

ξ = 0.2"

ξ = 0.25"

ξ = 0.3"

Mo5va5on  OK,  but  …    

1999  Chi-­‐Chi  TCU136N  

Damping Ratios in Buildings 26  

0.4$

0.6$

0.8$

1.0$

1.2$

1.4$

1.6$

1.8$

2.0$

2.2$

2.4$

0$ 1$ 2$ 3$ 4$ 5$

Sd#[ξ]/Sd[5%]#

Period#[s]#

ξ = 0.01" ξ = 0.02" ξ = 0.05" ξ = 0.1" ξ = 0.15" ξ = 0.2" ξ = 0.25" ξ = 0.3"

Mo5va5on  OK,  but  …    

1999  Chi-­‐Chi  TCU136N  

Damping Ratios in Buildings 27  

0"

500"

1000"

1500"

2000"

2500"

0" 1" 2" 3" 4" 5"

Sa#[cm/s2]#

Period#[s]#

ξ = 0.01"

ξ = 0.02"

ξ = 0.05"

ξ = 0.1"

ξ = 0.15"

ξ = 0.2"

ξ = 0.25"

ξ = 0.3"

Mo5va5on  OK,  but  …    

1999  Chi-­‐Chi  CHY034N  

Damping Ratios in Buildings 28  

0.4$

0.6$

0.8$

1.0$

1.2$

1.4$

1.6$

1.8$

2.0$

2.2$

2.4$

0$ 1$ 2$ 3$ 4$ 5$

Sd#[ξ]/Sd[5%]#

Period#[s]#

ξ = 0.01" ξ = 0.02" ξ = 0.05" ξ = 0.1" ξ = 0.15" ξ = 0.2" ξ = 0.25" ξ = 0.3"

Mo5va5on  OK,  but  …    

1999  Chi-­‐Chi  CHY034N  

Response  of  1%  damped  is  75%  larger  than  5%  damped  (3  8mes  larger  than  assumed  by  the  code)  

Page 8: Miranda Damping Ratios v5 for Seaonc

8  

Damping Ratios in Buildings 29  

0.4$

0.6$

0.8$

1.0$

1.2$

1.4$

1.6$

1.8$

2.0$

2.2$

2.4$

0$ 1$ 2$ 3$ 4$ 5$

Sd#[ξ]/Sd[5%]#

Period#[s]#

ξ = 0.01" ξ = 0.02" ξ = 0.05" ξ = 0.1" ξ = 0.15" ξ = 0.2" ξ = 0.25" ξ = 0.3"

Mo5va5on  OK,  but  …    

1999  Chi-­‐Chi  CHY034N  

Response  of  1%  damped  is  SMALLER  than  5%  damped  !  (code  assumes  25%  larger)  

Damping Ratios in Buildings 30  

Mo5va5on  

Bo\om  line…    The  effects  of  damping  can  be  much  larger  than  we  typically  assume    

But  when  can  we  expect  larger  effects  and  when  smaller  effects  of  damping?  

Damping Ratios in Buildings 31  

0"

200"

400"

600"

800"

1000"

1200"

1400"

1600"

1800"

0" 1" 2" 3" 4" 5"

Sa#[cm/s2]#

Period#[s]#

ξ = 0.01"

ξ = 0.02"

ξ = 0.05"

ξ = 0.1"

ξ = 0.15"

ξ = 0.2"

ξ = 0.25"

ξ = 0.3"

0"

200"

400"

600"

800"

1000"

1200"

0" 1" 2" 3" 4" 5"

Sa#[cm/s2]#

Period#[s]#

ξ = 0.01"

ξ = 0.02"

ξ = 0.05"

ξ = 0.1"

ξ = 0.15"

ξ = 0.2"

ξ = 0.25"

ξ = 0.3"

1999  Chi-­‐Chi  TCU136N  

0"

500"

1000"

1500"

2000"

2500"

0" 1" 2" 3" 4" 5"

Sa#[cm/s2]#

Period#[s]#

ξ = 0.01"

ξ = 0.02"

ξ = 0.05"

ξ = 0.1"

ξ = 0.15"

ξ = 0.2"

ξ = 0.25"

ξ = 0.3"

1999  Chi-­‐Chi  CHY034N  

1999  Chi-­‐Chi  TCU055E  

0"

200"

400"

600"

800"

1000"

1200"

1400"

0" 1" 2" 3" 4" 5"

Sa#[cm/s2]#

Period#[s]#

ξ = 0.01"

ξ = 0.02"

ξ = 0.05"

ξ = 0.1"

ξ = 0.15"

ξ = 0.2"

ξ = 0.25"

ξ = 0.3"

1999  Chi-­‐Chi  CHY073E  

Mo5va5on   Suppose  T1  =  1.0s  RECORDS  WHERE  Ti  IS  IN  A  PEAK   RECORDS  WHERE  Ti  IS  IN  A  VALLEY  

Damping Ratios in Buildings 32  

Mo5va5on  

Bo\om  line…    The   effects   of   damping   will   be   larger   for  periods   of   vibra5on   located   on   spectral  peaks   while   they   will   be   much   smaller  when  they  are  located  in  spectral  valleys    

Page 9: Miranda Damping Ratios v5 for Seaonc

9  

Damping Ratios in Buildings 33  

0

50

100

150

200

250

300

0.0 1.0 2.0 3.0 4.0 5.0

Sa [cm/s2]

PERIOD [s]

April 26th, 1989 Station 09

Station 01

Station 53

Mo5va5on  

Damping  effects  will  be  par5cularly  large  for  example  for  sof  soil   sites   (that   produce   quasi-­‐harmonic   mo5ons)   and   for  periods  near  the  predominant  period  of  the  site.  

Damping Ratios in Buildings 34  

Mo5va5on  

0

50

100

150

200

250

300

0.0 1.0 2.0 3.0 4.0 5.0

Sa [cm/s2]

PERIOD [s]

April 26th, 1989 Station 09

Station 01

Station 53

Mean

However,   you’ll   miss   not   only   the   shape   of   the   spectra   but  also   damping   effects   if   you   work   with   mean   spectra   from  different  sof  soil  sites  

Damping Ratios in Buildings 35  

Mo5va5on  

0

50

100

150

200

250

300

0.0 0.5 1.0 1.5 2.0

Sa [cm/s2]

T / Tg

April 26th, 1989 Station 09

Station 01

Station 53

Mean

But  if  you  normalized  the  spectra  by  the  predominant  period  of  the  site  not  only  you  will  the  an  excellent  characteriza5on  of   the   spectral   shape   but   also   of   spectral   regions   where  damping  effects  will  be  much  larger  

Damping Ratios in Buildings 36  

Nobel  prize  in  physics  1904  

John  William  Stru;,    Baron  of  Rayleigh  (Lord  Rayleigh)  

Early  work  on  viscous  damping  

First  published  in  1877  

(I  strongly  recommend  at  least  browsing  through  these  extraordinary  books  now  freely  available  on  Google  books)  

Page 10: Miranda Damping Ratios v5 for Seaonc

10  

Damping Ratios in Buildings 37  

Early  work  on  viscous  damping  

From  volume  1  

Damping Ratios in Buildings 38  

284 EFFECTS OF FRICTION. [346.

as .c iucrcascs. Assuming tliat M varies M e' we find as ia§14.8.

lu tho application to air at ordinary pressures ma.y bc con-Hidcred to bo a vury smaM qu:mtity and its square may Le

ue~lected. Thus

It appca-rs th~t to tilis ordcr of a.pproxima.tion tlie vclocity ofsound is unnH'cctcd Ly Huid friction. If we rcptuce M by 27ra\thc expression fur the cocfHcicnt of d(jc:t.y bccomcs

s)icwM)g that tue inimcncc of viscosity is greatest on the wavcs of

short wavc-)L'j)gth. Tlie :unplitudc is ditnhus!tud iu thu ratioC 1, wlicu x =fï" In c. O.S. mca.surc wu may take

Thus the amplitude of wavcs of one centimètre wavc-Icngth isdiminishod in the ratio e 1 after travc)IIng a, distance of 88jnctres. A wave-lcngth of 10 centimètres would

correspond ncarlyto for this case a; = 8800 mètres. It a.ppe:u's therefore thu.t atatmospheric pressures t))e influence of fricLion is not Hkdy to busensible to ordiuary observation, cxcept nc:).r tite upper II)nit of themusical sca)e. 'Die mellowing of soonds by distance, as obscrved Itimountainous countrics, is pcrhaps to bc attribnted to friction, bythé opération of which the higher and Iuu's))cr componcnts arc

gradually climinated. It must oftcn have bccn noticecl that thesuund s is scareciy, if at al], rctnrncd by echos, and I hâve fuund~that at a, distance of 200 nictrcs a powcrfui hiss loses its charactcr,even whcn Uicrc is no refiection. Proba.b!y Uns enect aiso is ducto viscosity.

AcofitictU Observations, P/t~. ~/<t.'7., Junc, 1877.

Early  work  on  viscous  damping  

284 EFFECTS OF FRICTION. [346.

as .c iucrcascs. Assuming tliat M varies M e' we find as ia§14.8.

lu tho application to air at ordinary pressures ma.y bc con-Hidcred to bo a vury smaM qu:mtity and its square may Le

ue~lected. Thus

It appca-rs th~t to tilis ordcr of a.pproxima.tion tlie vclocity ofsound is unnH'cctcd Ly Huid friction. If we rcptuce M by 27ra\thc expression fur the cocfHcicnt of d(jc:t.y bccomcs

s)icwM)g that tue inimcncc of viscosity is greatest on the wavcs of

short wavc-)L'j)gth. Tlie :unplitudc is ditnhus!tud iu thu ratioC 1, wlicu x =fï" In c. O.S. mca.surc wu may take

Thus the amplitude of wavcs of one centimètre wavc-Icngth isdiminishod in the ratio e 1 after travc)IIng a, distance of 88jnctres. A wave-lcngth of 10 centimètres would

correspond ncarlyto for this case a; = 8800 mètres. It a.ppe:u's therefore thu.t atatmospheric pressures t))e influence of fricLion is not Hkdy to busensible to ordiuary observation, cxcept nc:).r tite upper II)nit of themusical sca)e. 'Die mellowing of soonds by distance, as obscrved Itimountainous countrics, is pcrhaps to bc attribnted to friction, bythé opération of which the higher and Iuu's))cr componcnts arc

gradually climinated. It must oftcn have bccn noticecl that thesuund s is scareciy, if at al], rctnrncd by echos, and I hâve fuund~that at a, distance of 200 nictrcs a powcrfui hiss loses its charactcr,even whcn Uicrc is no refiection. Proba.b!y Uns enect aiso is ducto viscosity.

AcofitictU Observations, P/t~. ~/<t.'7., Junc, 1877.

From  volume  2  

284 EFFECTS OF FRICTION. [346.

as .c iucrcascs. Assuming tliat M varies M e' we find as ia§14.8.

lu tho application to air at ordinary pressures ma.y bc con-Hidcred to bo a vury smaM qu:mtity and its square may Le

ue~lected. Thus

It appca-rs th~t to tilis ordcr of a.pproxima.tion tlie vclocity ofsound is unnH'cctcd Ly Huid friction. If we rcptuce M by 27ra\thc expression fur the cocfHcicnt of d(jc:t.y bccomcs

s)icwM)g that tue inimcncc of viscosity is greatest on the wavcs of

short wavc-)L'j)gth. Tlie :unplitudc is ditnhus!tud iu thu ratioC 1, wlicu x =fï" In c. O.S. mca.surc wu may take

Thus the amplitude of wavcs of one centimètre wavc-Icngth isdiminishod in the ratio e 1 after travc)IIng a, distance of 88jnctres. A wave-lcngth of 10 centimètres would

correspond ncarlyto for this case a; = 8800 mètres. It a.ppe:u's therefore thu.t atatmospheric pressures t))e influence of fricLion is not Hkdy to busensible to ordiuary observation, cxcept nc:).r tite upper II)nit of themusical sca)e. 'Die mellowing of soonds by distance, as obscrved Itimountainous countrics, is pcrhaps to bc attribnted to friction, bythé opération of which the higher and Iuu's))cr componcnts arc

gradually climinated. It must oftcn have bccn noticecl that thesuund s is scareciy, if at al], rctnrncd by echos, and I hâve fuund~that at a, distance of 200 nictrcs a powcrfui hiss loses its charactcr,even whcn Uicrc is no refiection. Proba.b!y Uns enect aiso is ducto viscosity.

AcofitictU Observations, P/t~. ~/<t.'7., Junc, 1877.

Damping Ratios in Buildings 39  

Early  work  on  viscous  damping  Rayleigh’s  damping  Also  from  volume  1  

Damping Ratios in Buildings 40  

Early  work  on  viscous  damping  

Also  from  volume  1   Rayleigh’s  quo5ent  

Page 11: Miranda Damping Ratios v5 for Seaonc

11  

Damping Ratios in Buildings 41  

Damping  mechanisms  in  buildings  

Our  knowledge  of  damping  mechanisms  in  buildings  is  rather  limited.  Some  of  the  main  mechanisms  are:  

•  Intrinsic  material  damping  (thermoelas8c  damping)  

•  Soil-­‐structure  interac8on,  mainly  radia8on  damping  but  also  intrinsic  damping  in  the  soil  

•  Fric8onal  damping  in  structural  elements  (e.g.,  fric8on  in  bolted  connec8ons,  fric8on  in  nailed  connec8ons,  fric8on  in  micro  and  macro  cracking  of  concrete,  etc.)  

•  Fric8onal  damping  in  nonstructural  components  and  their  connec8ons  to  the  structure  

•  Aerodynamic  damping  

LARGEST  SOURCE  OF  DAMPING  

SECOND  LARGEST  SOURCE  OF  DAMPING  

Damping Ratios in Buildings 42  

Although   it   is   possible   (and   has   been   done   in   a   few   buildings)   to   obtain  damping   ra8o   in   buildings   from   pull   back   tests   and   using   logarithmic  decrement  technique,  in  most  cases  this  method  is  not  used.  

(Ager  Chopra,  1994)  

Methods  to  obtain  damping  ra5os  Logarithmic  decrement  

Damping Ratios in Buildings 43  

This   is  a   frequency-­‐domain  method   in  which  a  power  density   spectrum   is  computed  from  a  measured  response.  The  damping  ra8o  is  obtained  as  half  the  width  of  the  resonance  peak  measured  at  2^0.5  of  the  peak  amplitude  normalized  by  the  resonance  frequency.      

Methods  to  obtain  damping  ra5os  Half-­‐Power  Band  Width  Method    

(Ager  Chopra,  1994)  

Damping Ratios in Buildings 44  

This   is   a   8me-­‐domain   method   which   has   recently   become   popular   for  obtaining   damping   ra8os   in   wind-­‐excited   buildings.   It   is   based   on   the  decomposi8on   of   band-­‐filtered   signals   into   the   superposi8on   of   the   forced  vibra8on  response  with  the  homogeneous  component  or  free  vibra8on  decay  from  given  ini8al  condi8ons  obtaining  a  Random  Decrement  Signature  which  is  propor8onal  to  the  autocorrela8on  func8on  of  the  system.  

Methods  to  obtain  damping  ra5os  Random  Decrement  Technique  

for this lightly damped system. As long as the white noise assumption remains valid (implicationsof this are discussed in [1,7]), the analogs between Eqs. (5) and (6) may be exploited for systemidentification, via least squares minimization to obtain best-fit estimates of damping ! and naturalfrequency fn, letting C=xo/Rx(0). Though this approach was used in this study, logarithmicdecrement or other identification techniques may also be used to determine the damping of thesystem. Though this simplified approach is designated only for SDOF systems, the RDT can beused to analyze multi-degree of freedom (MDOF) systems by the approach described herein withthe incorporation of bandpass filtering [8,9] or by introducing the recently developed vector ran-dom decrement technique [10]. However, as this study is concerned with establishing the relia-bility of RDT estimates of system parameters, it is su!cient for demonstrative purposes toconsider only the SDOF formulation.The resulting RDS will be unbiased with variance that can be expressed by [5]:

var Dxo "! "! "

# E D2xo

"! "h i

$ E Dxo "! "! "2# Rx 0! "=Nr 1$ R2

x "! "=R2x 0! "

! "

!7"

where Nr=the number of segments averaged in the estimate. The presence of noise was ignored inthis idealized derivation, as was the potential correlation between the captured segments. To

Fig. 2. Conceptualization of the random decrement technique.

T. Kijewski, A. Kareem / Structural Safety 24 (2002) 261–280 265

(Ager  Kijweski-­‐Correa,  2002)  

Page 12: Miranda Damping Ratios v5 for Seaonc

12  

Damping Ratios in Buildings 45  

Methods  to  obtain  damping  ra5os  Commonly   used  methods   such   as   the  Half   Power  Band  Width  method  or   the  Random   Decrement   Technique   which   are   commonly   used   techniques   for  extrac8ng  damping  informa8on  from  buildings  subjected  to  wind  loading,  they  may  lead  to  unreliable  results  for  earthquake  loading  given  their  much  shorter  dura5on  or  because  it  required  the  excita5on  frequency  to  be  assumed  to  be  a  white  noise  at   least   in  the  vicinity  of  the  spectral  peak  (HPBW  method)  which  may  not  be  valid  for  earthquake  excita8ons.  

Furthermore,  Stagner  and  Hart  (1971)  found  that  damping  ra8os  obtained  using  the   Half   Power   Band   Width   method   were   affected   by   the   record   dura5on,  insufficient   frequency   resolu5on,   spectral   smoothing   and   zero   padding   can  lead     or   the   Random   Decrement   Technique   which   are   commonly   used  techniques   for   extrac8ng   damping   informa8on   from   buildings   subjected   to  wind  loading,  they  may  lead  to  unreliable  results  for  earthquake  loading  given  their  much  shorter  dura8on.  

Damping Ratios in Buildings 46  

Methods  to  obtain  damping  ra5os  System  Iden5fica5on  Technique  

Although  recently  there  have  been  some  developments  on  output-­‐only  system  iden8fica8on   techniques,   most   methods   infer   dynamic   proper8es   from   the  rela8onship  between  input  and  output  of  the  system.  

STRUCTURE  EXCITATION   RESPONSE  

Damping Ratios in Buildings 47  

Previous  studies  

Despite   its   importance,  very   limited  informa8on  exists  on  damping  ra8os  in  building  as  we  cannot  obtain  this  type  of  informa8on  in  the  lab  or  from  sta8c   tes8ng.  We   primarily   need   to   obtain   them   by  measuring   them   in  actual  buildings  subjected  to  dynamic  loading.  

However,  there  are  some  limita8ons  on  previous  studies:  

1.  There   are   typically   based   on   very   small   number   on   buildings   (e.g.,  Chopra  and  Goel  (1997)  only  studied  22  buildings  and  only  in  one  earthquake,  the  1994  Northridge  earthquake).  

2.  Most  of  the  data  is  based  on  ambient  vibra8on,  small  forced  vibra8on  or  wind  loading  (e.g.,  the  study  by  Satake  (2003)  gathered  informa8on  on    205  Japanese  buildings  but  only  18  building  measurements  were  based  on  earthquake  loading).  

3.  Most   studies   have   gathered   data   from   different   sources   using  different  methods  ogen   leading   to   inconsistent   results   (mixing  “apples  with  oranges”)  

Damping Ratios in Buildings 48  

Previous  studies  

(Ager  Goel  and  Chopra,  1997)  

Page 13: Miranda Damping Ratios v5 for Seaonc

13  

Damping Ratios in Buildings 49  

Previous  studies  

Full-Scale Data on Dynamic Properties of Buildingsin Japan

Collection of Full-Scale DataRecent full-scale data on the dynamic properties of buildingswere provided by over 40 institutes !universities, general contrac-tors, and offices of structural designers". Other full-scale datawere collected through a survey of journals and proceedings onbuilding engineering issued in Japan since 1970.Damping ratios and natural periods were picked up for trans-

lational vibration modes in two orthogonal directions and tor-sional vibration modes, together with amplitudes obtained fromvibration tests and observations. The database includes informa-tion on vibration-testing methods and damping evaluation meth-ods. Data were also compiled on building features that may in-fluence dynamic properties, including building height, number ofstories, building plan, building use, structural type, foundationtype, depth of foundations, and length of piles.

Selection of Reliable Damping Data

Only reliable data were selected from the collected full-scaledamping data. It was intended to confirm or supplement the col-lected full-scale data twice through questionnaires to the institutesthat had performed the vibration tests or observations. However,some full-scale data with unknown data items remained. Somethat contained no information on vibration amplitude for vibrationtests and observations or damping evaluation method were ne-glected. In a few cases, it was determined that damping ratioswere not accurately evaluated when the damping evaluationmethod was applied with an improper measurement condition!Davenport and Hill-Carroll 1986; AIJ 2000". In these cases, datawere also omitted. Data on buildings with odd or complicatedshapes were also discarded.Lastly, data on 137 steel-framed buildings, 25 reinforced con-

crete !RC" buildings, 43 steel-framed reinforced concrete !SRC"buildings, and 79 towerlike structures were compiled in the Japa-nese damping database. Data were categorized by structural type.

Table 1. Number of Buildings in DatabaseStructure Type Steel-Framed Buildings RC/SRC Buildings

Building heightH(m)

250–300

200–250

150–200

100–150

50–100 0–50 Total

150–200

100–150

50–100 0–50 Total

Total 1 5 14 39 60 18 137 1 5 37 25 68

Building use

Office 1 5 11 26 45 11 99 14 6 20Hotel 3 9 12 1 25 2 2

Apartment 1 3 4 1 5 20 9 35School 1 1 2 1 3 4Shops 1 1Hospital 1 1 1 1Laboratory 1 1Unknown 2 1 1 4 6 6

Foundation typePile 1 7 16 22 15 61 1 4 27 18 50Spread 1 4 7 21 38 2 73 1 10 5 16Unknown 2 1 3 2 2

Table 2. Number of Buildings Tested by Each Vibration MethodStructure Type Steel-Framed Buildings RC/SRC Buildings

Building heightH(m)

250–300

200–250

150–200

100–150

50–100 0–50 Total

150–200

100–150

50–100 0–50 Total

Forced vibration testby mechanical shaker

11 27 8 46 1 14 12 27

Forced vibration testby vibration control devices

2 1 3

Free vibration testby mechanical shaker

1 1 2 4 2 10 1 1

Free vibration testby vibration control devices

1 2 1 4

Free vibration testby man power

1 4 9 19 4 37 2 10 5 17

Free vibration testby pull and release

2 2 4

Free vibration test by swing 1 3 5 9Microtremor observation 1 2 8 21 17 5 54 1 3 16 8 28Wind response observation 1 2 2 2 2 9Earthquake observation 1 2 3 3 2 11 1 2 3 1 7

JOURNAL OF STRUCTURAL ENGINEERING © ASCE / APRIL 2003 / 471

J. Struct. Eng. 2003.129:470-477.

Dow

nloa

ded

from

asc

elib

rary

.org

by

STA

NFO

RD

UN

IV o

n 06

/26/

13. C

opyr

ight

ASC

E. F

or p

erso

nal u

se o

nly;

all

right

s res

erve

d.

(Ager  Satake,  2003)  PRIMARY  INTEREST  IN  CALIFORNIA  

Damping Ratios in Buildings 50  

Previous  studies  

Profile of Full-Scale DataStatistics of building features are exemplified in Table 1 as tobuilding height, building use, and foundation type. Most of thesteel-framed buildings in the database are 50–150 m high and areused as offices or hotels. As the building height increases, spreadfoundations become preferable. However, most RC/SRC build-ings in the database are 50–100 m high and are used as apart-ments. Pile foundations are preferred for RC/SRC buildings.As shown in Table 2, various vibration-testing methods were

used. These methods can be divided into two types according tothe excitation method. One uses artificial excitation by mechani-cal shakers, vibration control devices, man power, etc. The otheruses natural excitation, such as microtremors, earthquakes, orwind forces. The former can also be classified as forced vibrationtests and free vibration tests. As shown in Table 2, microtremorobservations, forced vibration tests by mechanical shakers, andman-power free vibration tests were applied to many buildings.Therefore, most of the data in the database were evaluated in thesmall amplitude region.Damping evaluation methods are closely related to the

vibration-testing methods !Davenport and Hill-Carroll 1986; Ka-reem and Gurley 1996; Tamura and Suganuma 1996". For eachvibration-testing method using artificial excitation, the dampingratios were evaluated restrictively by corresponding dampingevaluation methods. A half-power method and curve fitting for aresponse curve were applied most frequently to the forced vibra-tion tests. For most of the free vibration tests, a logarithmic decayfactor method was used. However, various damping evaluationmethods were employed for vibration tests using natural excita-tion. The statistics for applied damping evaluation methods areexemplified in Table 3 as to microtremor observation. A randomdecrement technique, curve fitting for power spectra, half-powerbandwidth method, and autocorrelation decay method are oftenused for microtremor observation.

Damping Properties of Buildings

This section categorizes data for 137 steel-framed buildings and68 RC/SRC buildings, and characteristics of damping ratios foreach structural type are analyzed.

Natural PeriodsBefore presenting damping properties, natural period propertiesare discussed. Fig. 1 shows the relation between natural periods intranslational first-mode T1 and building height H. The tallestbuilding in Japan at present is 282 m high and is included in thedatabase. In Japan, there are not many supertall buildings as in the

United States and some Asian countries !Davenport et al. 1970;Maebayashi et al. 1989". Not only low-rise buildings but alsomost supertall building are compiled in the database. Fig. 2 showsthe relation between T1 and natural periods in torsional first-modeTt1 . Fig. 3 shows the relation between T1 and natural periods intranslational second and third modes, T2 and T3 . Figs. 1–3 alsoindicate a regression line and its correlation factor r. It is clarifiedthat r values for both steel-framed buildings and RC/SRC build-ings in Figs. 1–3 are very high. These results indicate that thenatural periods of buildings in Japan can be predicted from build-ing height.

First-Mode Damping RatiosFirst, translational first-mode damping ratios were analyzed. Fig.4 shows the relation between first-mode damping ratios h1 andbuilding heights H. In Fig. 5, the natural periods T1 are adoptedinstead of H. Figs. 4 and 5 show that the larger the H or the T1 ,the smaller the h1 except at one point at 250 m height. Thisparticular piece of data was for a building built on soft groundwhose plan has a large dimension ratio. In order to show thistendency, a curve fit for the plot has been attempted in Figs. 4 and5. It seems that the main reason for the dependency betweendamping ratio and building height may be the effects of soil–structure interaction and radiational damping.The h1 values in many steel-framed buildings are under 2%,

which is frequently assumed in designing high-rise steel-framed

Fig. 1. Building height H versus translational first-mode naturalperiod T1

Fig. 2. First-mode natural period in translational mode T1 versus thatin torsional mode Tt1

Fig. 3. Natural period of first-mode T1 versus that of higher modesT2 , T3 in translational mode

Table 3. Number of Buildings Classified by Each DampingEvaluation Method in Microtremor Observation Data

Structure typeSteel-framedbuildings

RC/SRCbuildings

Logarithmic damping factor method 1 0Autocorrelation decay method 14 4Random decrement technique 26 10Half-power bandwidth method 15 4Curve fitting !power spectra" 8 14Curve fitting !transfer function" 1 5System identification 0 1

472 / JOURNAL OF STRUCTURAL ENGINEERING © ASCE / APRIL 2003

J. Struct. Eng. 2003.129:470-477.

Dow

nloa

ded

from

asc

elib

rary

.org

by

STA

NFO

RD

UN

IV o

n 06

/26/

13. C

opyr

ight

ASC

E. F

or p

erso

nal u

se o

nly;

all

right

s res

erve

d.

(Ager  Satake,  2003)  MOST  RELIABLE  METHOD  

Damping Ratios in Buildings 51  

Previous  studies  

Several   studies   (e.g.,   Stagner   and  Hart,   1971;  Davenport   and  Carroll,   1986;  Lagosmarino  1993;     Kijewski   and  Kareem,  2002)  have   shown   that  different  methods  to  extract  damping  ra8os  in  buildings  from  measured  response  can  lead  to  different  values  and  introduce  bias  in  the  es8mated  damping  ra8os.  

Band Width (HPBW) Technique, while the time domain analysisemploys Analytic Signal Theory using Hilbert Transformsapplied to locally averaged Random Decrement Signatures (RDS)(Kijewski and Kareem, 2003). This implementation of the RandomDecrement Technique (RDT) begins with pre-processing byButterworth bandpass filters to isolate each mode of interestand a positive point trigger value is enforced to select thesegments of the response averaged to generate the RDS (Bashoret al., 2005). As RDT is inherently sensitive to the trigger condi-tions, which directly influence the number of segments capturedand thereby the quality of the RDS, repeated triggering isimplemented, as proposed by Kijewski-Correa (2003) and pre-viously implemented in the context of the CFSMP by Bashor et al.(2005) and Kijewski-Correa and Pirnia (2007). This is accom-plished by generating a suite of RDSs associated with a range ofpositive point triggers that are within a few percent of the desiredtrigger Xp. The resulting RDSs are then processed using the HilbertTransform and the natural frequency and the critical dampingratio are determined from the phase and amplitude of the analyticsignal, respectively. The resulting vector of frequency and damp-ing estimates are then averaged to yield mean estimate andcorresponding coefficient of variation (CoV). The reliability ofthese frequency and time domain approaches for system identi-fication from wind-induced vibration data has been previouslyevaluated by Kijewski and Kareem (2002).

Both of the aforementioned approaches assume stationarity ofthe data, to varying extents. Although in practice wind is oftenviewed as a stationary random process, transient or nonstationaryfeatures are generally present in most field data. Therefore, beforedata is processed by any of the aforementioned techniques, itsstationarity is established using the Run and Reverse Arrange-ments Tests (Bendat and Piersol, 2000). In addition to these twotests, additional verifications are made using a method proposedby Montpellier (1996).

5. In-depth study of two wind events

Before exploring the trends in dynamic properties over multi-ple wind events, two wind events are selected for in-depthdiscussion to evaluate the performance of the system identifica-tion techniques being employed. It should be noted that con-firmation of stationarity by at least two of the three testsdiscussed in the previous section was executed to qualify thetwo wind events featured here as stationary; the same criteriawill be used for all data presented in later sections of the paper.The identified natural frequencies and critical damping ratios arerespectively presented in Tables 2 and 3 for Wind Events 1 and2 with respective mean hourly gradient winds and average winddirections of 20 m/s and 2251 (SW) and 24 m/s and 2881 (WNW).The dynamic properties estimated by the RDT with local trigger-ing are accompanied by their CoV to provide an indicator ofrelative reliability of the estimate.

5.1. Performance of system identification techniques

For both wind events the natural frequency estimates arecompletely consistent between the time and frequency domaintechniques, with RDT CoVs less than 1%. When comparing valuesbetween the wind events, the natural frequencies diminishslightly in the y-sway response of Building 2 in the second event.Note that for this event, the y-axis experiences acrosswind actionand comparatively larger responses; therefore, the reduction infrequency is consistent with the amplitude dependence noted inprevious studies (Kijewski-Correa and Pirnia 2007). On the otherhand, critical damping ratios estimated by RDT have CoVs that areone to two orders of magnitude higher than those associated withnatural frequency estimates. In fact, the CoVs are larger for thesteel buildings, particularly Building 3, which is the building withthe strongest degree of coupling between modes. Interestingly,the time and frequency domain system identification approachesare most consistent in their damping estimate for the concretestructure (within 14%) and show the most significant deviationfor the steel structures whose power spectra are more narrow-band and generated with fewer spectral averages for a fixedduration wind event. Furthermore, given the low bias require-ment placed on the estimation of the power spectra, it is notsurprising that the damping estimates in the frequency domainare not consistently larger than the unbiased time domainestimates, affirming that the residual error source is indeedrandom. When comparing damping values between the twoevents, Building 2 yields the most consistent damping values,regardless of the method employed, with HPBW results beingwithin 22% and RDT results being within 18%. For Building 1,while RDT results are quite consistent (within 12% betweenevents), HPBW results deviate by as much as 50%.The case is similar for Building 3, where RDT damping resultsare within 19% of one another, while HPBW results deviate by asmuch as 48%. This again can be credited to the fact that the twosteel buildings are characterized by considerably more narrow-band spectra and are thereby more susceptible to variance errorsin the presence of limited amounts of data. Interestingly, whileRDT proves to be the more consistent damping estimator, parti-cularly for the two steel buildings, when comparing resultsbetween the two events, the consistency is generally an order ofmagnitude better in the x-axis than the y-axis, which againexperiences higher amplitude acrosswind response in Event 2.As a result the lack of ‘‘consistency’’ may not be the result oferrors inherent to the method but potentially due to the ampli-tude-dependence previously observed in damping values in thesebuildings (Kijewski-Correa and Pirnia, 2007). In particular, in non-symmetric systems, the axes of the buildings typified by greaterframe action tend to manifest more amplitude dependence intheir dynamic properties: Building 1’s x-axis as a result ofpotential shear lag along the elongated floor plate and Building2’s y-axis where primary lateral resistance is derived fromslab and frame elements. The potential effects of amplitude

Table 2Estimated dynamic properties for wind event 1.

Direction Test Building 1 Building 2 Building 3

fn (Hz) z (%) fn (Hz) z (%) fn (Hz) z (%)

x-Sway HPBW 0.204 0.65 0.178 1.62 0.116 1.46RDT 0.204 0.87 0.178 1.42 0.116 1.04(CoV, %) (0.10) (23.88) (0.22) (7.43) (0.25) (20.63)

y-Sway HPBW 0.141 1.14 0.177 2.07 0.116 1.06RDT 0.141 0.88 0.177 2.41 0.116 1.21(CoV, %) (0.19) (8.89) (0.68) (8.01) (0.14) (22.96)

Table 3Estimated dynamic properties for wind event 2.

Direction Test Building 1 Building 2 Building 3

fn (Hz) z (%) fn (Hz) z (%) fn (Hz) z (%)

x-Sway HPBW 0.204 1.37 0.178 1.66 0.117 1.59RDT 0.204 0.89 0.178 1.52 0.117 1.01(CoV, %) (0.13) (12.61) (0.31) (11.33) (0.15) (10.18)

y-Sway HPBW 0.141 0.88 0.176 2.53 0.117 2.01RDT 0.141 1.00 0.176 2.95 0.116 1.44(CoV, %) (0.13) (6.43) (0.96) (5.54) (0.34) (24.20)

R. Bashor et al. / J. Wind Eng. Ind. Aerodyn. 104–106 (2012) 88–9790

(Ager  Bashor  et  al,  2012)  HPBW:  Half  Power  Band  Width  method  RDT:  Random  Decrement  Technique    

Damping Ratios in Buildings 52  

Previous  studies  

(Ager  Reinoso  and  Miranda,  2005)  The building is instrumented by the United States Geological Survey (USGS). There are a total of

21 uniaxial accelerometers installed in the first, 13th, 21st and 30th floor levels (Anderson et al., 1991;Çelebi and Safak, 1992). It was shaken by the 1989 Loma Prieta earthquake, whose epicenter was 96km away, yielding peak ground accelerations of 173 and 208cm/s2 for the NS and the EW compo-nents, respectively.

3.1.2 42-story building in San Francisco (SF42)This is a moment-resisting steel-frame building, 183m high (Figure 4), designed in 1972, slender andrectangular in plan, and founded over 10m long piles (Çelebi, 1998; Anderson and Bertero, 1998).

ESTIMATION OF FLOOR ACCELERATION DEMANDS 115

Copyright © 2005 John Wiley & Sons, Ltd. Struct. Design Tall Spec. Build. 14, 107–130 (2005)

EM30 SF42 SF47

SF48 LA52 LA54

Figure 4. Tall buildings with accelerometric recorded data used in this study. They are located in Emeryville(EM), San Francisco (SF) and Los Angeles (LA)

Page 14: Miranda Damping Ratios v5 for Seaonc

14  

Damping Ratios in Buildings 53  

Objec5ves  of  this  study  

•  To  obtain  informa8on  about  damping  ra8os  in  buildings  to  be  used  when  conduc8ng   seismic   analysis   in   combina8on   with   modal   analysis   (either  response  spectrum  analysis  or  response  history  modal  analysis).  

•  To   use   a   significantly   larger   number   of   buildings   with   different  characteris8cs  (number  of  stories,  materials,  lateral  resis8ng  systems).  

•  To  use  exclusively  data  from  earthquake  loading  and  with  a  wide  range  of  levels  of  intensity.  

•  To  use  a  single  and  reliable  method  for  inferring  the  damping  ra8os.  

Damping Ratios in Buildings 54  

Main  Source  of  Informa5on  

Damping Ratios in Buildings 55  

Summary  of  data  used  in  this  study  

•  74  Buildings  located  in  California      (more  than  three  8mes  of  those  analyzed  by  Chopra  and  Goel,  2003)    (more  than  four  8mes  of  those  analyzed  by  Satake  with  EQ  loading)  

•  12  Earthquakes    ²    6  in  the  San  Francisco  Bay  Area  and  6  from  LA  Metropolitan  area  ²    Magnitudes  ranging  from  4.1  to  7.1  

•  Heights  ranging  from  1  to  54  stories  

•  Wide   range   of   materials   and   lateral   resis8ng  systems  

Damping Ratios in Buildings 56  

Summary  of  data  used  in  this  study  

29  Buildings  in  the  San  Francisco  Bay  Area  

Page 15: Miranda Damping Ratios v5 for Seaonc

15  

Damping Ratios in Buildings 57  

Summary  of  data  used  in  this  study  

45  Buildings  in  the  Los  Angeles  Metropolitan  Area  

Damping Ratios in Buildings 58  

Basics  of  System  Iden5fica5on  Time-­‐invariant  Parametric  System  Iden5fica5on  

Obtain  computed  accelera*on  *me  histories  by  conduc*ng  a  modal  

response  history  analysis  

Store  inferred  damping  ra*os  

Select  structural  parameters  

Obtain  ground  and  structural  response  accelera*on  records  

Computed  response  

≈  Recorded  response  ?  

NO  

YES  

Damping Ratios in Buildings 59  

-200

-100

0

100

200

0 5 10 15 20 25 30

Acc [in/s2]

TIME [s]

Ground Acceleration Time History (Accelerogram)

EXCITATION   RESPONSE  

Basics  of  System  Iden5fica5on  

STRUCTURE  

T  =  ?,  ξ  =  ?  

!200$

!100$

0$

100$

200$

0$ 5$ 10$ 15$ 20$ 25$ 30$

Accel%%[in/s2]%

Time%[s]%

$MEASURED$

Damping Ratios in Buildings 60  

-200

-100

0

100

200

0 5 10 15 20 25 30

Acc [in/s2]

TIME [s]

Ground Acceleration Time History (Accelerogram)

EXCITATION   RESPONSE  

Basics  of  System  Iden5fica5on  

STRUCTURE  

T  =  0.8,  ξ  =  0.05  

!200$

!100$

0$

100$

200$

0$ 5$ 10$ 15$ 20$ 25$ 30$

Accel%%[in/s2]%

Time%[s]%

$MEASURED$$COMPUTED$

Page 16: Miranda Damping Ratios v5 for Seaonc

16  

Damping Ratios in Buildings 61  

-200

-100

0

100

200

0 5 10 15 20 25 30

Acc [in/s2]

TIME [s]

Ground Acceleration Time History (Accelerogram)

EXCITATION   RESPONSE  

Basics  of  System  Iden5fica5on  

STRUCTURE  

T  =  1.0,  ξ  =  0.05  

!200$

!100$

0$

100$

200$

0$ 5$ 10$ 15$ 20$ 25$ 30$

Accel%%[in/s2]%

Time%[s]%

$MEASURED$$COMPUTED$

Damping Ratios in Buildings 62  

-200

-100

0

100

200

0 5 10 15 20 25 30

Acc [in/s2]

TIME [s]

Ground Acceleration Time History (Accelerogram)

EXCITATION   RESPONSE  

Basics  of  System  Iden5fica5on  

STRUCTURE  

T  =  1.2,  ξ  =  0.05  

!200$

!100$

0$

100$

200$

0$ 5$ 10$ 15$ 20$ 25$ 30$

Accel%%[in/s2]%

Time%[s]%

$MEASURED$$COMPUTED$

Damping Ratios in Buildings 63  

-200

-100

0

100

200

0 5 10 15 20 25 30

Acc [in/s2]

TIME [s]

Ground Acceleration Time History (Accelerogram)

EXCITATION   RESPONSE  

Basics  of  System  Iden5fica5on  

STRUCTURE  

T  =  1.37,  ξ  =  0.05  

!200$

!100$

0$

100$

200$

0$ 5$ 10$ 15$ 20$ 25$ 30$

Accel%%[in/s2]%

Time%[s]%

$MEASURED$$COMPUTED$

Damping Ratios in Buildings 64  

-200

-100

0

100

200

0 5 10 15 20 25 30

Acc [in/s2]

TIME [s]

Ground Acceleration Time History (Accelerogram)

EXCITATION   RESPONSE  

Basics  of  System  Iden5fica5on  

STRUCTURE  

T  =  1.37,  ξ  =  0.03  

!200$

!100$

0$

100$

200$

0$ 5$ 10$ 15$ 20$ 25$ 30$

Accel%%[in/s2]%

Time%[s]%

$MEASURED$$COMPUTED$

Page 17: Miranda Damping Ratios v5 for Seaonc

17  

Damping Ratios in Buildings 65  

When   comparing   how   close   the   recorded   (measured)   response   is   to   the  computed  response  we  use  an  objec5ve  func5on  defined  as  :    

where

mj,i is the measured response in the jth sensor during the ith time step

cj,i is the measured response in the jth sensor during the ith time step

J =mj,i − cj,i"# $%

2

mj,i2

i=1

n

∑j=1

N

Basics  of  System  Iden5fica5on  

System   iden5fica5on   is   essen5ally   an   op5miza5on  problem   in  which  we  want   to   find   the   parameters   of   the  model  which  minimize   the   objec5ve  func5on   (that  minimize   the  difference  between  computed  and  measured  response  in  all  sensors)    

Damping Ratios in Buildings 66  

0"

0.02"

0.04"

0.06"

0.08"

0.1"

")"""""1,000"""2,000"""3,000"""4,000"""5,000"""6,000"""7,000"""8,000"""9,000""

"10,000""

0.05"

0.30"

0.55"

0.80"

1.05"

1.30"

1.55"

1.80"

"9,000")"10,000"""8,000")"9,000"""7,000")"8,000"""6,000")"7,000"""5,000")"6,000"""4,000")"5,000"""3,000")"4,000"""2,000")"3,000"""1,000")"2,000""")""")"1,000""

DAMPING

 RATIO  

PERIOD  

OBJECTIVE  FUNCTION  J  (ERROR)  

Basics  of  System  Iden5fica5on  

Damping Ratios in Buildings 67  

1.20%

1.22%

1.24%

1.26%

1.28%

1.30%

1.32%

1.34%

1.36%

1.38%

1.40%

0%600%1200%1800%2400%3000%3600%4200%4800%5400%6000%

0.010%

0.013%

0.016%

0.019%

0.022%

0.025%

0.028%

5400,6000%

4800,5400%

4200,4800%

3600,4200%

3000,3600%

2400,3000%

1800,2400%

1200,1800%

600,1200%

0,600%

DAMP

ING  RA

TIO  

PERIOD  

Basics  of  System  Iden5fica5on  

OBJECTIVE  FUNCTION  J  (ERROR)  

Damping Ratios in Buildings 68  

1.30%

1.31%

1.32%

1.33%

1.34%

1.35%

1.36%

1.37%

1.38%

1.39%

1.40%

0%50%100%150%200%250%300%350%400%450%500%

0.010%

0.013%

0.016%

0.019%

0.022%

0.025%

0.028%

450-500%

400-450%

350-400%

300-350%

250-300%

200-250%

150-200%

100-150%

50-100%

0-50%

DAMPING

 RAT

IO  

PERIOD  

Basics  of  System  Iden5fica5on  OBJECTIVE  FUNCTION  J  (ERROR)  

T  =  1.37,  ξ  =  0.021  

Page 18: Miranda Damping Ratios v5 for Seaonc

18  

Damping Ratios in Buildings 69  

0"

5000"

10000"

15000"

20000"

25000"

0" 0.5" 1" 1.5" 2"

Obje%ve'Func%on,'J,'(error)'

Period'[s]'

Basics  of  System  Iden5fica5on  

T  =  1.37s  

ξ  =  0.021  

∂J∂T

Damping Ratios in Buildings 70  

0"

100"

200"

300"

400"

0.000" 0.005" 0.010" 0.015" 0.020" 0.025" 0.030"

Objec&ve(Func&on(J((error)(

Damping(Ra&o(

Basics  of  System  Iden5fica5on  

T  =  1.37s  

ξ  =  0.021  

∂J∂ξ

∂J∂ξ

Damping Ratios in Buildings 71  

0"

100"

200"

300"

400"

0.000" 0.005" 0.010" 0.015" 0.020" 0.025" 0.030"

Objec&ve(Func&on(J((error)(

Damping(Ra&o(

Basics  of  System  Iden5fica5on  

T  =  1.37s  

ξ  =  0.021  

0"

5000"

10000"

15000"

20000"

25000"

0" 0.5" 1" 1.5" 2"

Obje%ve'Func%on,'J,'(error)'

Period'[s]'

T  =  1.37s  

ξ  =  0.021  

These   slope   (formally   par5al   deriva5ves   of   an   N-­‐dimensional   objec5ve   func5on)   will  control   how   fast   you   converge   to   the   minimum   (inferred   parameters)   but   more  importantly  the  accuracy  on  your  parameters.  

Damping Ratios in Buildings 72  

0.030.04

0.050.06

0.070.08

0.7 0.8 0.9 1 1.1 1.2 1.3 1.4 1.5

0

1

2

3

4

5

6

7

8

9

10

ξ [%]

T [s]

Objec*ve  func*on:  

α  =  50  ξi  >  1  =  5%  15-­‐Mass  

T [s]

ξ [%

]

Objective Function J

0.85 0.9 0.95 1 1.05 1.13

3.5

4

4.5

5

5.5

6

6.5

7

7.5

8

(Ager  C.  Cruz  and  E.  Miranda,  2014)  

Page 19: Miranda Damping Ratios v5 for Seaonc

19  

Damping Ratios in Buildings 73  

-200

-100

0

100

200

0 5 10 15 20 25 30

Acc [in/s2]

TIME [s]

Ground Acceleration Time History (Accelerogram)

EXCITATION   RESPONSE  

Basics  of  System  Iden5fica5on  

STRUCTURE  

T  =  1.37,  ξ  =  0.021  

!200$

!100$

0$

100$

200$

0$ 5$ 10$ 15$ 20$ 25$ 30$

Accel%%[in/s2]%

Time%[s]%

$MEASURED$$COMPUTED$

Damping Ratios in Buildings 74  

CSMIP Station: 58354 Earthquake: Loma Prieta Building parameters:Location: Hayward Component: EWref T1 = 1.34 [ = 0.025 D0 = 15Number of stories: 13 Lateral Resisting System: Steel & RConcrete MRF

Use/Type: CSUH Admin Building

ROOF

-5-4-3-2-1012345

0 5 10 15 20 25 30 35 40Time [s]

Displ. [cm]

CHAN4 - CHAN14Computed

5TH FLOOR

-5-4-3-2-1012345

0 5 10 15 20 25 30 35 40Time [s]

Disp. [cm]

CHAN6 - CHAN14Computed

2ND FLOOR

-5-4-3-2-1012345

0 5 10 15 20 25 30 35 40Time [s]

Disp. [cm]

CHAN9 - CHAN14Computed

1ST FLOOR

-5-4-3-2-1012345

0 5 10 15 20 25 30 35 40Time [s]

Disp. [cm]

CHAN12 - CHAN14

Computed

BASE

-5-4-3-2-1012345

0 5 10 15 20 25 30 35 40Time [s]

Disp. [cm]

CHAN14 - CHAN14

Computed

Examples  of  System  Iden5fica5on  

Damping Ratios in Buildings 75  

CSMIP Station: 58354 Earthquake: Loma Prieta Building parameters: 1.9

Location: Hayward Component: NSref T1 = 1.25 [ = 0.03 D0 = 29.5 Manual

Number of stories: 13 Lateral Resisting System: Steel & RConcrete MRF

Use/Type: CSUH Admin Building

ROOF

0

250

500

750

1000

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

ROOF

-250-200-150-100

-500

50100150200250

0 5 10 15 20 25 30Time [s]

Accel. [cm/s2]

CHAN3Computed

5TH FLOOR

-250-200-150-100

-500

50100150200250

0 5 10 15 20 25 30Time [s]

Accel. [cm/s2]

CHAN5Computed

2ND FLOOR

-250-200-150-100

-500

50100150200250

0 5 10 15 20 25 30Time [s]

Accel. [cm/s2]

CHAN8Computed

5TH FLOOR

0

250

500

750

1000

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

2ND FLOOR

0

250

500

750

1000

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

0 1 2 3 4PFA / PGA

x=z/H

Recorded Computed

1ST FLOOR

-250-200-150-100

-500

50100150200250

0 5 10 15 20 25 30Time [s]

Accel. [cm/s2]CHAN11Computed

1ST FLOOR

0

250

500

750

1000

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

BASE

-250-200-150-100

-500

50100150200250

0 5 10 15 20 25 30Time [s]

Accel. [cm/s2]

CHAN16Computed

BASE

0

250

500

750

1000

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

Examples  of  System  Iden5fica5on  

Damping Ratios in Buildings 76  

CSMIP Station: 58354 Earthquake: Loma Prieta Building parameters: 1.9

Location: Hayward Component: NSref T1 = 1.25 [ = 0.03 D0 = 29.5 Manual

Number of stories: 13 Lateral Resisting System: Steel & RConcrete MRF

Use/Type: CSUH Admin Building

ROOF

0

250

500

750

1000

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

ROOF

-250-200-150-100

-500

50100150200250

0 5 10 15 20 25 30Time [s]

Accel. [cm/s2]

CHAN3Computed

5TH FLOOR

-250-200-150-100

-500

50100150200250

0 5 10 15 20 25 30Time [s]

Accel. [cm/s2]

CHAN5Computed

2ND FLOOR

-250-200-150-100

-500

50100150200250

0 5 10 15 20 25 30Time [s]

Accel. [cm/s2]

CHAN8Computed

5TH FLOOR

0

250

500

750

1000

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

2ND FLOOR

0

250

500

750

1000

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

0 1 2 3 4PFA / PGA

x=z/H

Recorded Computed

1ST FLOOR

-250-200-150-100

-500

50100150200250

0 5 10 15 20 25 30Time [s]

Accel. [cm/s2]CHAN11Computed

1ST FLOOR

0

250

500

750

1000

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

BASE

-250-200-150-100

-500

50100150200250

0 5 10 15 20 25 30Time [s]

Accel. [cm/s2]

CHAN16Computed

BASE

0

250

500

750

1000

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

Examples  of  System  Iden5fica5on  

Main  ques*on  I  was   interested   in  answering:  (and   its  what  dis*guishes  this  research  from  other  apart  from  using  a  much  larger  number  of  buildings  excited  by  earthquake  loading)  What  is  the  modal  damping  ra5o  I  should  use  if  I  am  interested  in  reproducing  the  measured  response  when:  a)  I  am  compu5ng  the  response  with  a  modal  response  history  analysis;  b)  I  am  using  a  linear  elas5c  model  fixed  at  the  base;  

Page 20: Miranda Damping Ratios v5 for Seaonc

20  

Damping Ratios in Buildings 77  

CSMIP Station: 58354 Earthquake: Loma Prieta Building parameters:Location: Hayward Component: EWref T1 = 1.34 [ = 0.025 D0 = 15Number of stories: 13 Lateral Resisting System: Steel & RConcrete MRF

Use/Type: CSUH Admin Building

ROOF

-5-4-3-2-1012345

0 5 10 15 20 25 30 35 40Time [s]

Displ. [cm]

CHAN4 - CHAN14Computed

5TH FLOOR

-5-4-3-2-1012345

0 5 10 15 20 25 30 35 40Time [s]

Disp. [cm]

CHAN6 - CHAN14Computed

2ND FLOOR

-5-4-3-2-1012345

0 5 10 15 20 25 30 35 40Time [s]

Disp. [cm]

CHAN9 - CHAN14Computed

1ST FLOOR

-5-4-3-2-1012345

0 5 10 15 20 25 30 35 40Time [s]

Disp. [cm]

CHAN12 - CHAN14

Computed

BASE

-5-4-3-2-1012345

0 5 10 15 20 25 30 35 40Time [s]

Disp. [cm]

CHAN14 - CHAN14

Computed

Examples  of  System  Iden5fica5on  

ξ  =  0.025  

Damping Ratios in Buildings 78  

CSMIP Station: 58261 Earthquake: Loma Prieta Building parameters: 1.9

Location: San Francisco Component: NSref T1 = 0.66 [ = 0.035 D0 = 5.9 Manual

Number of stories: 4 Lateral Resisting System: Steel MRF

Use/Type: Office Building

ROOF

0

800

1600

2400

3200

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

ROOF

-600-450-300-150

0150300450600

0 5 10 15 20 25 30 35 40Time [s]

Accel. [cm/s2]

CHAN10Computed

2ND FLOOR

-600

-450

-300

-150

0

150

300

450

600

0 5 10 15 20 25 30 35 40Time [s]

Accel. [cm/s2]

CHAN7Computed

BASE

-600

-450

-300

-150

0

150

300

450

600

0 5 10 15 20 25 30 35 40Time [s]

Accel. [cm/s2]

CHAN3Computed

2ND FLOOR

0

800

1600

2400

3200

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

BASE

0

800

1600

2400

3200

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

0 1 2 3 4 5PFA / PGA

x=z/H

Recorded Computed

Examples  of  System  Iden5fica5on  

Damping Ratios in Buildings 79  

Examples  of  System  Iden5fica5on  

CSMIP Station: 58261 Earthquake: Loma Prieta Building parameters: 1.9

Location: San Francisco Component: NSref T1 = 0.66 [ = 0.035 D0 = 5.9 Manual

Number of stories: 4 Lateral Resisting System: Steel MRF

Use/Type: Office Building

ROOF

0

800

1600

2400

3200

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

ROOF

-600-450-300-150

0150300450600

0 5 10 15 20 25 30 35 40Time [s]

Accel. [cm/s2]

CHAN10Computed

2ND FLOOR

-600

-450

-300

-150

0

150

300

450

600

0 5 10 15 20 25 30 35 40Time [s]

Accel. [cm/s2]

CHAN7Computed

BASE

-600

-450

-300

-150

0

150

300

450

600

0 5 10 15 20 25 30 35 40Time [s]

Accel. [cm/s2]

CHAN3Computed

2ND FLOOR

0

800

1600

2400

3200

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

BASE

0

800

1600

2400

3200

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

0 1 2 3 4 5PFA / PGA

x=z/H

Recorded Computedξ  =  0.03  

Damping Ratios in Buildings 80  

Examples  of  System  Iden5fica5on  ξ  =  0.03  

CSMIP Station: 58261 Earthquake: Loma Prieta Building parameters:Location: San Francisco Component: NSref T1 = 0.66 [ = 0.035 D0 = 5.9Number of stories: 4 Lateral Resisting System: Steel MRF

Use/Type: Office Building

ROOF

-8

-6

-4

-2

0

2

4

6

8

0 5 10 15 20 25 30 35 40Time [s]

Displ. [cm]

CHAN10 - CHAN3Computed

2ND FLOOR

-8

-6

-4

-2

0

2

4

6

8

0 5 10 15 20 25 30 35 40Time [s]

Disp. [cm]

CHAN7 - CHAN3Computed

BASE

-8

-6

-4

-2

0

2

4

6

8

0 5 10 15 20 25 30 35 40Time [s]

Disp. [cm]

CHAN3 - CHAN3Computed

Page 21: Miranda Damping Ratios v5 for Seaonc

21  

Damping Ratios in Buildings 81  

Examples  of  System  Iden5fica5on  

CSMIP Station: 58264 Earthquake: Loma Prieta Building parameters: 1.8

Location: Palo Alto Component: NSref T1 = 0.28 [ = 0.2 D0 = 10 Manual

Number of stories: 2 Lateral Resisting System: Masonry SW

Use/Type: Office Building

ROOF

0

200

400

600

800

1000

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

ROOF

-400-300-200-100

0100200300400

0 5 10 15 20 25 30 35 40Time [s]

Accel. [cm/s2]

CHAN7Computed

BASE

-400

-300

-200

-100

0

100

200

300

400

0 5 10 15 20 25 30 35 40Time [s]

Accel. [cm/s2]

CHAN1Computed

BASE

0

200

400

600

800

1000

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

0 1 2 3 4PFA / PGA

x=z/H

Recorded Computed

Damping Ratios in Buildings 82  

Examples  of  System  Iden5fica5on  

CSMIP Station: 58264 Earthquake: Loma Prieta Building parameters: 1.8

Location: Palo Alto Component: NSref T1 = 0.28 [ = 0.2 D0 = 10 Manual

Number of stories: 2 Lateral Resisting System: Masonry SW

Use/Type: Office Building

ROOF

0

200

400

600

800

1000

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

ROOF

-400-300-200-100

0100200300400

0 5 10 15 20 25 30 35 40Time [s]

Accel. [cm/s2]

CHAN7Computed

BASE

-400

-300

-200

-100

0

100

200

300

400

0 5 10 15 20 25 30 35 40Time [s]

Accel. [cm/s2]

CHAN1Computed

BASE

0

200

400

600

800

1000

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

0 1 2 3 4PFA / PGA

x=z/H

Recorded Computedξ  =  0.20  

Damping Ratios in Buildings 83  

Examples  of  System  Iden5fica5on  

CSMIP Station: 58364 Earthquake: Loma Prieta Building parameters: 1.9

Location: Walnut Creek Component: EWref T1 = 0.78 [ = 0.032 D0 = 7.5 Manual

Number of stories: 10 Lateral Resisting System: Shear Walls

Use/Type: Commercial Building

ROOF

0

300

600

900

1200

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

ROOF

-300

-200

-100

0

100

200

300

0 5 10 15 20 25 30 35 40Time [s]

Accel. [cm/s2]

CHAN3Computed

8TH FLOOR

-300

-200

-100

0

100

200

300

0 5 10 15 20 25 30 35 40Time [s]

Accel. [cm/s2]

CHAN7Computed

3RD FLOOR

-300

-200

-100

0

100

200

300

0 5 10 15 20 25 30 35 40Time [s]

Accel. [cm/s2]

CHAN10Computed

8TH FLOOR

0

300

600

900

1200

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

3RD FLOOR

0

300

600

900

1200

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

0 1 2 3 4 5PFA / PGA

x=z/H

Recorded Computed

BASE

-300

-200

-100

0

100

200

300

0 5 10 15 20 25 30 35 40Time [s]

Accel. [cm/s2]CHAN16Computed

BASE

0

300

600

900

1200

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

Damping Ratios in Buildings 84  

Examples  of  System  Iden5fica5on  

CSMIP Station: 58364 Earthquake: Loma Prieta Building parameters: 1.9

Location: Walnut Creek Component: EWref T1 = 0.78 [ = 0.032 D0 = 7.5 Manual

Number of stories: 10 Lateral Resisting System: Shear Walls

Use/Type: Commercial Building

ROOF

0

300

600

900

1200

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

ROOF

-300

-200

-100

0

100

200

300

0 5 10 15 20 25 30 35 40Time [s]

Accel. [cm/s2]

CHAN3Computed

8TH FLOOR

-300

-200

-100

0

100

200

300

0 5 10 15 20 25 30 35 40Time [s]

Accel. [cm/s2]

CHAN7Computed

3RD FLOOR

-300

-200

-100

0

100

200

300

0 5 10 15 20 25 30 35 40Time [s]

Accel. [cm/s2]

CHAN10Computed

8TH FLOOR

0

300

600

900

1200

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

3RD FLOOR

0

300

600

900

1200

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

0 1 2 3 4 5PFA / PGA

x=z/H

Recorded Computed

BASE

-300

-200

-100

0

100

200

300

0 5 10 15 20 25 30 35 40Time [s]

Accel. [cm/s2]CHAN16Computed

BASE

0

300

600

900

1200

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

ξ  =  0.032  

Page 22: Miranda Damping Ratios v5 for Seaonc

22  

Damping Ratios in Buildings 85  

Examples  of  System  Iden5fica5on  

CSMIP Station: 58364 Earthquake: Loma Prieta Building parameters:

Location: Walnut Creek Component: EWref T1 = 0.78 [ = 0.032 D0 = 7.5Number of stories: 10 Lateral Resisting System: Shear Walls

Use/Type: Commercial Building

ROOF

-4

-3

-2

-1

0

1

2

3

4

0 5 10 15 20 25 30 35 40Time [s]

Displ. [cm]

CHAN3 - CHAN16

Computed

8TH FLOOR

-4

-3

-2

-1

0

1

2

3

4

0 5 10 15 20 25 30 35 40Time [s]

Disp. [cm]

CHAN7 - CHAN16

Computed

3RD FLOOR

-4

-3

-2

-1

0

1

2

3

4

0 5 10 15 20 25 30 35 40Time [s]

Disp. [cm]

CHAN10 - CHAN16

Computed

BASE

-4

-3

-2

-1

0

1

2

3

4

0 5 10 15 20 25 30 35 40Time [s]

Disp. [cm]

CHAN16 - CHAN16

Computed

ξ  =  0.032  

Damping Ratios in Buildings 86  

CSMIP Station: 58532 Earthquake: Loma Prieta Building parameters: 1.9

Location: San Francisco Component: EWref T1 = 6.70 [ = 0.011 D0 = 30 Manual

Number of stories: 47 Lateral Resisting System: Steel MRF

Use/Type: Office Building

ROOF

0

300

600

900

1200

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

ROOF

-400-300-200-100

0100200300400

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Accel. [cm/s2]

CHAN16Computed

16th FLOOR

-400

-300

-200

-100

0

100

200

300

400

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Accel. [cm/s2]

CHAN11Computed

BASE

-400

-300

-200

-100

0

100

200

300

400

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Accel. [cm/s2]

CHAN7Computed

16th FLOOR

0

300

600

900

1200

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

BASE

0

300

600

900

1200

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

0 1 2 3 4PFA / PGA

x=z/H

Recorded Computed

Examples  of  System  Iden5fica5on  

Damping Ratios in Buildings 87  

Examples  of  System  Iden5fica5on  

CSMIP Station: 58532 Earthquake: Loma Prieta Building parameters: 1.9

Location: San Francisco Component: EWref T1 = 6.70 [ = 0.011 D0 = 30 Manual

Number of stories: 47 Lateral Resisting System: Steel MRF

Use/Type: Office Building

ROOF

0

300

600

900

1200

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

ROOF

-400-300-200-100

0100200300400

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Accel. [cm/s2]

CHAN16Computed

16th FLOOR

-400

-300

-200

-100

0

100

200

300

400

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Accel. [cm/s2]

CHAN11Computed

BASE

-400

-300

-200

-100

0

100

200

300

400

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Accel. [cm/s2]

CHAN7Computed

16th FLOOR

0

300

600

900

1200

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

BASE

0

300

600

900

1200

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

0 1 2 3 4PFA / PGA

x=z/H

Recorded Computedξ  =  0.011  

Damping Ratios in Buildings 88  

Examples  of  System  Iden5fica5on  ξ  =  0.011  

CSMIP Station: 58532 Earthquake: Loma Prieta Building parameters:Location: San Francisco Component: EWref T1 = 6.26 [ = 0.012 D0 = 30Number of stories: 47 Lateral Resisting System: Steel MRF

Use/Type: Office Building

ROOF

-60

-45

-30

-15

0

15

30

45

60

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Displ. [cm]

CHAN16 - CHAN7Computed

16th FLOOR

-60

-45

-30

-15

0

15

30

45

60

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Disp. [cm]

CHAN11 - CHAN7Computed

BASE

-60

-45

-30

-15

0

15

30

45

60

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Disp. [cm]

CHAN7 - CHAN7Computed

Page 23: Miranda Damping Ratios v5 for Seaonc

23  

Damping Ratios in Buildings 89  

CSMIP Station: 24602 Earthquake: Landers Building parameters:Location: Los Angeles Component: EWref T1 = 6.04 [ = 0.009 D0 = 6.6Number of stories: 52 Lateral Resisting System: Steel MRF

Use/Type: Office Building

ROOF

-80-60-40-20

020406080

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80Time [s]

Displ. [cm]

CHAN19 - CHAN05Computed

49th FLOOR

-80-60

-40-20

0

2040

6080

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80Time [s]

Disp. [cm]

CHAN16 - CHAN05Computed

35th FLOOR

-80-60-40-20

020406080

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80Time [s]

Disp. [cm]

CHAN13 - CHAN05Computed

22nd FLOOR

-80

-60-40

-200

20

4060

80

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80Time [s]

Disp. [cm]

CHAN10 - CHAN05

Computed

14th FLOOR

-80-60

-40-20

020

4060

80

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80Time [s]

Disp. [cm]

CHAN08 - CHAN05

Computed

BASE

-80

-60-40

-200

20

4060

80

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80Time [s]

Disp. [cm]

CHAN05 - CHAN05

Computed

Examples  of  System  Iden5fica5on  

Damping Ratios in Buildings 90  

Examples  of  System  Iden5fica5on  

CSMIP Station: 24602 Earthquake: Landers Building parameters:Location: Los Angeles Component: EWref T1 = 6.04 [ = 0.009 D0 = 6.6Number of stories: 52 Lateral Resisting System: Steel MRF

Use/Type: Office Building

ROOF

-80-60-40-20

020406080

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80Time [s]

Displ. [cm]

CHAN19 - CHAN05Computed

49th FLOOR

-80-60

-40-20

0

2040

6080

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80Time [s]

Disp. [cm]

CHAN16 - CHAN05Computed

35th FLOOR

-80-60-40-20

020406080

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80Time [s]

Disp. [cm]

CHAN13 - CHAN05Computed

22nd FLOOR

-80

-60-40

-200

20

4060

80

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80Time [s]

Disp. [cm]

CHAN10 - CHAN05

Computed

14th FLOOR

-80-60

-40-20

020

4060

80

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80Time [s]

Disp. [cm]

CHAN08 - CHAN05

Computed

BASE

-80

-60-40

-200

20

4060

80

0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80Time [s]

Disp. [cm]

CHAN05 - CHAN05

Computed

ξ  =  0.009  

Damping Ratios in Buildings 91  

0.00#0.05#0.10#0.15#0.20#0.25#0.30#0.35#0.40#

0# 50# 100# 150# 200# 250#

ξ"

Data#Number#

Results  from  all  buildings/earthquakes  

244  Damping  ra8os  

Characterized  by  very  large  variability  and  values  ranging  from  much  lower  (e.g.,  <1%)  to  much  larger  (e.g.,  >20%)  than  the  5%  commonly  used      

Damping Ratios in Buildings 92  

0.0#

0.2#

0.4#

0.6#

0.8#

1.0#

0.00# 0.05# 0.10# 0.15# 0.20# 0.25# 0.30#

P(ξ<x)#

Damping#Ra8o,#ξ"

#Data#

#Lognormal#

Results  from  all  buildings/earthquakes  

Mean  ξ  =  6.7%                    σξ  =  6.1%            COV  =  0.92  

GeoMean  ξ  =  5.0%                    σLn  ξ  =  0.73          

This  level  of  variability  is  much  larger  than  for  example  the  one  in  a  GMPE  (spectral   ordinate   for   a   given  magnitude   and   distance)   which   is   typically  between  0.45  and  0.60.  

Variability  and  probability  distribu8on  

Median  ξ  =  5.0%  

Page 24: Miranda Damping Ratios v5 for Seaonc

24  

Damping Ratios in Buildings 93  

0.00#0.05#0.10#0.15#0.20#0.25#0.30#0.35#0.40#

0# 50# 100# 150# 200# 250#

ξ"

Data#Number#

Results  from  all  buildings/earthquakes  

0.00#0.05#0.10#0.15#0.20#0.25#0.30#0.35#0.40#

0# 50# 100# 150# 200# 250#

ξ"

Data#Number#

Results  from  N>3  (elimina8ng  data  from  1  and  2  story  buildings)  

Then  the  average  damping  ra5o  from  all  buildings  drops  from  6.7%  to  5.4%  which   is   a   reduc5on  of   20%   (afer  elimina5ng  about  one  fifh  of   the  data  from  one  and  two-­‐story  buildings)  

Damping Ratios in Buildings 94  

Results  from  all  buildings/earthquakes  

Many  ques8ons  “under  this  head”.  For  example:  

How  different  are  the  damping  ra5os  in  steel  buildings  compared  to  RC  buildings?  

0.00#

0.05#

0.10#

0.15#

0.20#

0# 50# 100# 150# 200# 250#

ξ"

Data#Number#

#RC#Bldgs.#

#Steel#Bldgs.#

Damping Ratios in Buildings 95  

0.00#

0.05#

0.10#

0.15#

0.20#

0# 50# 100# 150# 200# 250#

ξ"

Data#Number#

#RC#Bldgs.#

#Steel#Bldgs.#

Results  from  all  buildings/earthquakes  

Are  the  differences  sta5s5cally  significant  ?  

ξ  =  0.066  ξ  =  0.041  

Average  Values  

YES,  THEY  ARE  

This   suggest   that   a   more   ra5onal   approach   would   be   to   use   a   lower   level   of  damping  for  steel  structures  than  for  reinforced  concrete  buildings.  Some  of  this  is  already  acknowledged  by  ASCE  41  but  not  by  ASCE  7,  so  is  different  whether  you  are  designing   a   new   building   or   evalua5ng   an   exis5ng   one   when   in   reality   an  earthquake  will  not  ask  you  which  document  you  are  using.  

Damping Ratios in Buildings 96  

0.00#0.05#0.10#0.15#0.20#0.25#0.30#0.35#0.40#

0# 100# 200# 300# 400# 500# 600# 700# 800#

ξ"

Height#[3]#

#All#Bldgs.#

Changes  in  damping  ra5o  with  building  height  

ρ  =  -­‐0.36  

There   is   indisputable   evidence   both   from   wind   and   seismic   loading   that  damping   ra5o   tends   to  decrease  as  building  height   increases.  Therefore   it  doesn’t  make  sense  to  use  a  damping  ra5o  of  5%  for  all  buildings  regardless  of  their  height.    

Page 25: Miranda Damping Ratios v5 for Seaonc

25  

Damping Ratios in Buildings 97  

0.00#

0.05#

0.10#

0.15#

0.20#

0# 50# 100# 150# 200# 250#

ξ"

Height#[.]#

!RC!Bldgs.!

#RC#Bldgs.#

Changes  in  damping  ra5o  with  building  height  

Damping Ratios in Buildings 98  

Changes  in  damping  ra5o  with  building  height  

y"="0.0862e*0.005x"R²"="0.15679"

0.00"

0.05"

0.10"

0.15"

0.20"

0" 50" 100" 150" 200" 250"

ξ"

Height"[8]"

!!"RC"Bldgs."

y"="0.2506x*0.341"R²"="0.14925"

0.00"

0.05"

0.10"

0.15"

0.20"

0" 50" 100" 150" 200" 250"

ξ"

Height"[8]"

!RC!Bldgs.!"RC"Bldgs."

Two  possible  models:  

Cau8on  should  be  exercised  when  using  this  type  of  models  as  their  associated  coefficient  of  determina8on  is  rather  low  due  to  the  large  variability  in  the  data.  A  beFer  approach  is  to  bracket  your  analysis  and  use  two  values  

Damping Ratios in Buildings 99  

Changes  in  damping  ra5o  with  building  height  

0.00#

0.05#

0.10#

0.15#

0.20#

0# 100# 200# 300# 400# 500# 600# 700# 800#

ξ"

Height#[3]#

!Steel!Bldgs.!

#Steel#Bldgs.#

Damping Ratios in Buildings 100  

Changes  in  damping  ra5o  with  building  height  

0.00#

0.05#

0.10#

0.15#

0.20#

0# 100# 200# 300# 400# 500# 600# 700# 800#

ξ"

Height#[3]#

#RC#Bldgs.#

#Steel#Bldgs.#

No8ce   that   we   do   not   have   data   on   very   tall   reinforced   concrete   buildings.   One  excep8on  in  Northern  California  is  the  PPP,  but  fortunately  this  has  been  iden8fied  and  both  CSMIP  and  USGS  have  recently  instrumented  several  tall  RC  buildings  (we  now  just  need  EQs  to  learn  more  about  their  damping  ra8os  J  )  

Page 26: Miranda Damping Ratios v5 for Seaonc

26  

Damping Ratios in Buildings 101  

Changes  in  damping  ra5o  with  building  height  

y"="0.0534e*0.003x"R²"="0.60853"

0.00"

0.05"

0.10"

0.15"

0.20"

0" 100" 200" 300" 400" 500" 600" 700" 800"

ξ"

Height"[9]"

!!

"Steel"Bldgs."

y"="0.5066x)0.576"R²"="0.58953"

0.00"

0.05"

0.10"

0.15"

0.20"

0" 100" 200" 300" 400" 500" 600" 700" 800"

ξ"

Height"[:]"

"Steel"Bldgs."

Two  possible  models:  

Even  though  the  number  of  data  points   is  smaller,   the  coefficients  of  determina8on  are  are  much  larger  than  for  RC  buildings,  so  one  can  use  these  models  with  more  confidence.    No8ce  that  for  H>500  N  the  damping  ra8os  are  1%  or  less  which  agrees  with  the  level  of  damping  measured  in  strong  wind  storms.  

Damping Ratios in Buildings 102  

Damping  mechanisms  and  varia5on  of  damping  ra5os  with  height  

Which  of  these  mechanisms  would  explain  a  decrease  in  damping  ra8o  with  increasing  height  ?  

•  Intrinsic  material  damping  (thermoelas8c  damping)  

•  Soil-­‐structure  interac8on,  mainly  radia8on  damping  but  also  intrinsic  damping  in  the  soil  

•  Fric8onal  damping  in  structural  elements  (e.g.,  fric8on  in  bolted  connec8ons,  fric8on  in  nailed  connec8ons,  fric8on  in  micro  and  macro  cracking  of  concrete,  etc.)  

•  Fric8onal  damping  in  nonstructural  components  and  their  connec8ons  to  the  structure  

•  Aerodynamic  damping  

Damping Ratios in Buildings 103  

CSMIP Station: 24322 Earthquake: Landers Building parameters:Location: Sherman Oaks Component: EWref T1 = 2.54 [ = 0.045 D0 = 29.5Number of stories: 13 Lateral Resisting System: RConcrete MRF

Use/Type: Commercial Building

ROOF

-15

-10

-5

0

5

10

15

0 5 10 15 20 25 30 35 40Time [s]

Displ. [cm]

CHAN01 - CHAN10Computed

8TH FLOOR

-15

-10

-5

0

5

10

15

0 5 10 15 20 25 30 35 40Time [s]

Disp. [cm]

CHAN04 - CHAN10Computed

2ND FLOOR

-15

-10

-5

0

5

10

15

0 5 10 15 20 25 30 35 40Time [s]

Disp. [cm]

CHAN07 - CHAN10Computed

BASE

-15

-10

-5

0

5

10

15

0 5 10 15 20 25 30 35 40Time [s]

Disp. [cm]

CHAN10 - CHAN10

Computed

Evalua5on  Changes  with  Amplitude  

Damping Ratios in Buildings 104  

CSMIP Station: 24322 Earthquake: Whittier Building parameters:Location: Sherman Oaks Component: EWref T1 = 2.57 [ = 0.04 D0 = 29.5Number of stories: 13 Lateral Resisting System: RConcrete MRF

Use/Type: Commercial Building

ROOF

-15

-10

-5

0

5

10

15

0 5 10 15 20 25 30 35 40Time [s]

Displ. [cm]

CHAN01 - CHAN10Computed

8th FLOOR

-15

-10

-5

0

5

10

15

0 5 10 15 20 25 30 35 40Time [s]

Disp. [cm]

CHAN04 - CHAN10Computed

2nd FLOOR

-15

-10

-5

0

5

10

15

0 5 10 15 20 25 30 35 40Time [s]

Disp. [cm]

CHAN07 - CHAN10Computed

BASE

-15

-10

-5

0

5

10

15

0 5 10 15 20 25 30 35 40Time [s]

Disp. [cm]

CHAN10 - CHAN10

Computed

ξ  =  0.04  CSMIP Station: 24322 Earthquake: Whittier Building parameters:Location: Sherman Oaks Component: EWref T1 = 2.57 [ = 0.04 D0 = 29.5Number of stories: 13 Lateral Resisting System: RConcrete MRF

Use/Type: Commercial Building

ROOF

-15

-10

-5

0

5

10

15

0 5 10 15 20 25 30 35 40Time [s]

Displ. [cm]

CHAN01 - CHAN10Computed

8th FLOOR

-15

-10

-5

0

5

10

15

0 5 10 15 20 25 30 35 40Time [s]

Disp. [cm]

CHAN04 - CHAN10Computed

2nd FLOOR

-15

-10

-5

0

5

10

15

0 5 10 15 20 25 30 35 40Time [s]

Disp. [cm]

CHAN07 - CHAN10Computed

BASE

-15

-10

-5

0

5

10

15

0 5 10 15 20 25 30 35 40Time [s]

Disp. [cm]

CHAN10 - CHAN10

Computed

Evalua5on  Changes  with  Amplitude  

Page 27: Miranda Damping Ratios v5 for Seaonc

27  

Damping Ratios in Buildings 105  

CSMIP Station: 24322 Earthquake: Northridge Building parameters:Location: Sherman Oaks Component: EWref T1 = 2.92 [ = 0.05 D0 = 29.5Number of stories: 13 Lateral Resisting System: RConcrete MRF

Use/Type: Commercial Building

ROOF

-60

-40

-20

0

20

40

60

0 5 10 15 20 25 30 35 40Time [s]

Displ. [cm]

CHAN01 - CHAN10Computed

8th FLOOR

-60

-40

-20

0

20

40

60

0 5 10 15 20 25 30 35 40Time [s]

Disp. [cm]

CHAN04 - CHAN10Computed

2nd FLOOR

-60

-40

-20

0

20

40

60

0 5 10 15 20 25 30 35 40Time [s]

Disp. [cm]

CHAN07 - CHAN10Computed

BASE

-60

-40

-20

0

20

40

60

0 5 10 15 20 25 30 35 40Time [s]

Disp. [cm]

CHAN10 - CHAN10

Computed

CSMIP Station: 24322 Earthquake: Northridge Building parameters:Location: Sherman Oaks Component: EWref T1 = 2.92 [ = 0.05 D0 = 29.5Number of stories: 13 Lateral Resisting System: RConcrete MRF

Use/Type: Commercial Building

ROOF

-60

-40

-20

0

20

40

60

0 5 10 15 20 25 30 35 40Time [s]

Displ. [cm]

CHAN01 - CHAN10Computed

8th FLOOR

-60

-40

-20

0

20

40

60

0 5 10 15 20 25 30 35 40Time [s]

Disp. [cm]

CHAN04 - CHAN10Computed

2nd FLOOR

-60

-40

-20

0

20

40

60

0 5 10 15 20 25 30 35 40Time [s]

Disp. [cm]

CHAN07 - CHAN10Computed

BASE

-60

-40

-20

0

20

40

60

0 5 10 15 20 25 30 35 40Time [s]

Disp. [cm]

CHAN10 - CHAN10

Computed

ξ  =  0.05  Evalua5on  Changes  with  Amplitude  

Damping Ratios in Buildings 106  

CSMIP Station: 24322 Earthquake: Landers Building parameters:Location: Sherman Oaks Component: EWref T1 = 2.54 [ = 0.045 D0 = 29.5Number of stories: 13 Lateral Resisting System: RConcrete MRF

Use/Type: Commercial Building

ROOF

-15

-10

-5

0

5

10

15

0 5 10 15 20 25 30 35 40Time [s]

Displ. [cm]

CHAN01 - CHAN10Computed

8TH FLOOR

-15

-10

-5

0

5

10

15

0 5 10 15 20 25 30 35 40Time [s]

Disp. [cm]

CHAN04 - CHAN10Computed

2ND FLOOR

-15

-10

-5

0

5

10

15

0 5 10 15 20 25 30 35 40Time [s]

Disp. [cm]

CHAN07 - CHAN10Computed

BASE

-15

-10

-5

0

5

10

15

0 5 10 15 20 25 30 35 40Time [s]

Disp. [cm]

CHAN10 - CHAN10

Computed

CSMIP Station: 24322 Earthquake: Landers Building parameters:Location: Sherman Oaks Component: EWref T1 = 2.54 [ = 0.045 D0 = 29.5Number of stories: 13 Lateral Resisting System: RConcrete MRF

Use/Type: Commercial Building

ROOF

-15

-10

-5

0

5

10

15

0 5 10 15 20 25 30 35 40Time [s]

Displ. [cm]

CHAN01 - CHAN10Computed

8TH FLOOR

-15

-10

-5

0

5

10

15

0 5 10 15 20 25 30 35 40Time [s]

Disp. [cm]

CHAN04 - CHAN10Computed

2ND FLOOR

-15

-10

-5

0

5

10

15

0 5 10 15 20 25 30 35 40Time [s]

Disp. [cm]

CHAN07 - CHAN10Computed

BASE

-15

-10

-5

0

5

10

15

0 5 10 15 20 25 30 35 40Time [s]

Disp. [cm]

CHAN10 - CHAN10

Computed

ξ  =  0.045  Evalua5on  Changes  with  Amplitude  

Damping Ratios in Buildings 107  

Evalua5on  Changes  with  Amplitude  

Earthquake Date Mw Epic.1Dist1[km] Roof1displ.1[in] RDR1Long.1Ewref ξ T T/TWT ξ/ξWT

Whittier 1-Oct-87 6.1 38 4.92 0.00250 0.040 2.54 1.00 1.00

Landers 28-Jun-92 7.3 187 4.88 0.00248 0.045 2.52 0.99 1.13

Northridge 17-Jan-94 6.7 9 12.87 0.00640 0.050 2.92 1.15 1.25

0.00#

0.01#

0.02#

0.03#

0.04#

0.05#

0.06#

0.07#

0.08#

0.000# 0.001# 0.002# 0.003# 0.004# 0.005# 0.006# 0.007#

ξ"

Roof#Dri2#Ra4o#

NR  WT  

LD  

About  three  5mes  the  amplitude  of  response  and  somewhat  similar  level  of  damping  

Damping Ratios in Buildings 108  

CSMIP Station: 24601 Earthquake: Landers Building parameters:

Location: Los Angeles Component: EWref T1 = 0.94 [ = 0.031 D0 = 1.4Number of stories: 17 Lateral Resisting System: Shear Walls

Use/Type: Residential Building

ROOF

-6.0

-4.5

-3.0

-1.5

0.0

1.5

3.0

4.5

6.0

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Displ. [cm]

CHAN12 - CHAN04

Computed

13th FLOOR

-6.0

-4.5

-3.0

-1.5

0.0

1.5

3.0

4.5

6.0

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Disp. [cm]

CHAN09 - CHAN04

Computed

7th FLOOR

-6.0

-4.5

-3.0

-1.5

0.0

1.5

3.0

4.5

6.0

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Disp. [cm]

CHAN07 - CHAN04

Computed

BASE

-6.0

-4.5

-3.0

-1.5

0.0

1.5

3.0

4.5

6.0

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Disp. [cm]

CHAN04 - CHAN04

Computed

Evalua5on  Changes  with  Amplitude  

Page 28: Miranda Damping Ratios v5 for Seaonc

28  

Damping Ratios in Buildings 109  

CSMIP Station: 24601 Earthquake: Landers Building parameters:

Location: Los Angeles Component: EWref T1 = 0.94 [ = 0.031 D0 = 1.4Number of stories: 17 Lateral Resisting System: Shear Walls

Use/Type: Residential Building

ROOF

-6.0

-4.5

-3.0

-1.5

0.0

1.5

3.0

4.5

6.0

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Displ. [cm]

CHAN12 - CHAN04

Computed

13th FLOOR

-6.0

-4.5

-3.0

-1.5

0.0

1.5

3.0

4.5

6.0

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Disp. [cm]

CHAN09 - CHAN04

Computed

7th FLOOR

-6.0

-4.5

-3.0

-1.5

0.0

1.5

3.0

4.5

6.0

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Disp. [cm]

CHAN07 - CHAN04

Computed

BASE

-6.0

-4.5

-3.0

-1.5

0.0

1.5

3.0

4.5

6.0

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Disp. [cm]

CHAN04 - CHAN04

Computed

CSMIP Station: 24601 Earthquake: Landers Building parameters:

Location: Los Angeles Component: EWref T1 = 0.94 [ = 0.031 D0 = 1.4Number of stories: 17 Lateral Resisting System: Shear Walls

Use/Type: Residential Building

ROOF

-6.0

-4.5

-3.0

-1.5

0.0

1.5

3.0

4.5

6.0

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Displ. [cm]

CHAN12 - CHAN04

Computed

13th FLOOR

-6.0

-4.5

-3.0

-1.5

0.0

1.5

3.0

4.5

6.0

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Disp. [cm]

CHAN09 - CHAN04

Computed

7th FLOOR

-6.0

-4.5

-3.0

-1.5

0.0

1.5

3.0

4.5

6.0

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Disp. [cm]

CHAN07 - CHAN04

Computed

BASE

-6.0

-4.5

-3.0

-1.5

0.0

1.5

3.0

4.5

6.0

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Disp. [cm]

CHAN04 - CHAN04

Computed

ξ  =  0.031  Evalua5on  Changes  with  Amplitude  

Damping Ratios in Buildings 110  

ξ  =  0.033  

CSMIP Station: 24601 Earthquake: Northridge Building parameters:

Location: Los Angeles Component: EWref T1 = 1.08 [ = 0.033 D0 = 1.8Number of stories: 17 Lateral Resisting System: Shear Walls

Use/Type: Residential Building

ROOF

-12

-9

-6

-3

0

3

6

9

12

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Displ. [cm]

CHAN12 - CHAN04

Computed

13th FLOOR

-12

-9

-6

-3

0

3

6

9

12

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Disp. [cm]

CHAN09 - CHAN04

Computed

7th FLOOR

-12

-9

-6

-3

0

3

6

9

12

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Disp. [cm]

CHAN07 - CHAN04

Computed

BASE

-12

-9

-6

-3

0

3

6

9

12

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Disp. [cm]

CHAN04 - CHAN04

Computed

CSMIP Station: 24601 Earthquake: Northridge Building parameters:

Location: Los Angeles Component: EWref T1 = 1.08 [ = 0.033 D0 = 1.8Number of stories: 17 Lateral Resisting System: Shear Walls

Use/Type: Residential Building

ROOF

-12

-9

-6

-3

0

3

6

9

12

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Displ. [cm]

CHAN12 - CHAN04

Computed

13th FLOOR

-12

-9

-6

-3

0

3

6

9

12

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Disp. [cm]

CHAN09 - CHAN04

Computed

7th FLOOR

-12

-9

-6

-3

0

3

6

9

12

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Disp. [cm]

CHAN07 - CHAN04

Computed

BASE

-12

-9

-6

-3

0

3

6

9

12

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Disp. [cm]

CHAN04 - CHAN04

Computed

Evalua5on  Changes  with  Amplitude  

Damping Ratios in Buildings 111  

ξ  =  0.035  CSMIP Station: 24601 Earthquake: Sierra Madre Building parameters: 1.9

Location: Los Angeles Component: EWref T1 = 0.95 [ = 0.035 D0 = 0.3 Manual

Number of stories: 17 Lateral Resisting System: Shear Walls

Use/Type: Residential Building

ROOF

0

250

500

750

1000

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

ROOF

-160-120

-80-40

04080

120160

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Accel. [cm/s2]

CHAN12Computed

13th FLOOR

-160

-120

-80

-40

0

40

80

120

160

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Accel. [cm/s2]

CHAN09Computed

7th FLOOR

-160

-120

-80

-40

0

40

80

120

160

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Accel. [cm/s2]

CHAN07Computed

13th FLOOR

0

250

500

750

1000

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

7th FLOOR

0

250

500

750

1000

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

0 1 2 3 4PFA / PGA

x=z/H

Recorded Computed

BASE

-160

-120

-80

-40

0

40

80

120

160

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Accel. [cm/s2]CHAN04Computed

BASE

0

250

500

750

1000

0.0 1.0 2.0 3.0 4.0 5.0 6.0PERIOD [s]

Accel. [cm/s2]

From recorded resp. From computed resp.

CSMIP Station: 24601 Earthquake: Sierra Madre Building parameters:

Location: Los Angeles Component: EWref T1 = 0.95 [ = 0.035 D0 = 0.3Number of stories: 17 Lateral Resisting System: Shear Walls

Use/Type: Residential Building

ROOF

-4

-3

-2

-1

0

1

2

3

4

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Displ. [cm]

CHAN12 - CHAN04

Computed

13th FLOOR

-4

-3

-2

-1

0

1

2

3

4

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Disp. [cm]

CHAN09 - CHAN04

Computed

7th FLOOR

-4

-3

-2

-1

0

1

2

3

4

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Disp. [cm]

CHAN07 - CHAN04

Computed

BASE

-4

-3

-2

-1

0

1

2

3

4

0 5 10 15 20 25 30 35 40 45 50 55 60Time [s]

Disp. [cm]

CHAN04 - CHAN04

Computed

Evalua5on  Changes  with  Amplitude  

Damping Ratios in Buildings 112  

Earthquake Date Mw Epic.1Dist1[km] Roof1displ.1[in] RDR1Long.1Ewref ξ T

Sierra Madre 28-Jun-91 5.8 32 1.06 0.0006 0.035 0.95

Landers 28-Jun-92 7.3 168 1.18 0.0007 0.031 0.94

Northridge 17-Jan-94 6.7 32 3.94 0.0022 0.033 1.08

Evalua5on  Changes  with  Amplitude  

0.00#

0.01#

0.02#

0.03#

0.04#

0.05#

0.06#

0.07#

0.08#

0.0000# 0.0005# 0.0010# 0.0015# 0.0020# 0.0025#

ξ"

Roof#Dri2#Ra4o#

NR  SM  

LD  

Almost  four  5mes  the  amplitude  of  response  and  yet  similar  level  of  damping  

Page 29: Miranda Damping Ratios v5 for Seaonc

29  

Damping Ratios in Buildings 113  

Changes  in  damping  ra8o  in  structures  tested  in  shake  tables  

(Ager  ATC  72-­‐2)  

Evalua5on  Changes  with  Amplitude  

2-46 2: General Nonlinear Modeling PEER/ATC-72-1

undergone modest levels of shaking (less than 1% drift) and sustained slight

damage (i.e., hairline cracking, minor spalling), damping values increase to

about 4%. Following significant damage, damping increases beyond 5% up

to a maximum measured value of 11% of critical. In steel braced frames,

damping in the undamaged state is about 0.7% to 1.3% of critical, or about

half of that measured in the reinforced concrete structures.

Table 2-2 Measured Damping versus Level of Damage from Shaking Table Tests

Test Description Measured Damping (% critical)

versus Level of Damage Reference

RC Frames (2) 1-story, 3-bay (1/2 scale)

Undamaged: 1.4% to 1.9% Yielded: 2.1% to 3.7% Significant: 3.9% to 5.4%

Elwood and Moehle (2003)

RC Wall-Frame 7-story (1/5 scale)

Undamaged: 1.9% to 2.2% Slight: 3.5% to 3.7% Significant: 6.9% to 7.5%

Aktan et al. (1983); Bertero et al. (1984)

RC Flat Plate-Frame 2-story, 3-bay (1/3 scale)

Undamaged: 1.2% to 1.7% (negligible drift) Slight: 2.4% to 2.6% (0.002 to 0.011 drift) Moderate: 5.0% (0.017 to 0.034 drift) Significant: 7.2% (0.053 drift)

Diebold and Moehle (1984)

RC Frame 2-story, 1-bay (1/3 scale)

Undamaged: 1.9 to 2.2% Damaged: 3.9 to 5.3%

Oliva (1980)

RC Frame 3- to 6-story, 2-bay (1/3 scale)

Undamaged: 2.7% to 3.7% (0.001 to 0.003 drift) Moderate: 4.9% to 6.4% (0.012 drift) Significant: 9.6% to 11.1% (0.015 to 0.02 drift)

Shahrooz and Moehle, (1987)

RC Frames (12) 1-story, 3-bay (1/3 scale)

Undamaged: 1.4% to 2.9% (2.1% avg., 0.31 COV)

Shin and Moehle (2007)

RC Frame 3-story, 3-bay, (1/3 scale)

Undamaged: 1.9% Moehle et al. (2006)

Steel EBF 1 bay, 6-story (1/3 scale)

Undamaged: 0.7% Whittaker et al. (1987)

Steel CBF 1 bay, 6-story (1/3 scale)

Undamaged: 0.7% to 1.3% Whittaker et al. (1988)

Damping effects measured in shaking table tests can also be inferred from

comparisons with nonlinear analyses of the tests. For example, nonlinear

analyses with 2% viscous damping resulted in accurate comparisons to the

shake table tests by Shin and Moehle (2007). For shaking table tests of a

reinforced concrete bridge pier, Petrini et al. (2008) compared various

viscous damping assumptions made using fiber-type and plastic hinge

Damping Ratios in Buildings 114  

Evalua5on  Changes  with  Amplitude  

Damping Ratios in Buildings 115  

Evalua5on  Changes  with  Amplitude  

1985   1991  

Damping Ratios in Buildings 116  

(Ager  Miranda,  1991)  Fundamental   period   more   than   50%   longer.   Small   ambient   vibra5on   more  than  two  5mes  larger  than  the  EQ  inferred  lateral  s5ffness  (about  55%  of  the  lateral  s5ffness  “vanished”)  

Evalua5on  Changes  with  Amplitude  

Page 30: Miranda Damping Ratios v5 for Seaonc

30  

Damping Ratios in Buildings 117  

Changes  in  period  of  vibra8on  in  structures  tested  in  shake  tables  

(Ager  Miranda,  1991)  

Evalua5on  Changes  with  Amplitude  

Damping Ratios in Buildings 118  

ξ =c

2mω

Evalua5on  Changes  with  Amplitude  From  the  defini8on  of  damping  ra8o  

Suppose  that  my  period  changes  15%  with  higher  amplitude  of  response  

Small  amplitude   Large  amplitude  

1.15ω

Subs8tu8ng  

ξ =c

2mωSmall  amplitude  

1.15ξ = 1.15c2mω

Large  amplitude  

Assuming   the   mass   is   the   same   (a   reasonable   assump5on)   then   a   period  elonga5on   lead   to   an   equal   increase   in   damping   ra5o,   but   your   damping  coefficient,  c,  (what  you  actually  use  in  your  analysis)  has  not  increased  !  

Damping Ratios in Buildings 119  

Period  Elonga8on  

Evalua5on  Changes  with  Amplitude  

Amplitude  of  Response  

Most  of  the  change  (increase)   in  period  occurs  at  very  small   levels  of   lateral  deforma5on  

(Ager  Duran  and  Miranda,  1998)  

Damping Ratios in Buildings 120  

Evalua5on  Changes  with  Amplitude  

(Ager  Mosquera  and  Miranda,  2006)  

Page 31: Miranda Damping Ratios v5 for Seaonc

31  

Damping Ratios in Buildings 121  

Evalua5on  Changes  with  Amplitude  Period  Elonga8on  

           Roof  Drig  Ra8o                                    

Period  Elonga8on  

           Roof  Drig  Ra8o                                    

           Roof  Drig  Ra8o                                                Roof  Drig  Ra8o                                    

Most  of  the  change  (increase)  in  period  occurs  at  very  small  levels  of  lateral  deforma5on  (Ager  Mosquera  and  Miranda,  2006)  

Damping Ratios in Buildings 122  

Evalua5on  Changes  with  Amplitude  

clear evidence of a strongly linear and decreasing trend with noapparent plateau over the range of amplitudes considered.

As discussed in the previous section, the discrepancies betweenpredicted and in-situ natural frequencies for Building 2 could beattributed to numerous modeling assumptions. For example, giventhe age of the building, it is quite likely that the degree of crackingincluded in finite element models intended to represent thestructure at key design limit states are not yet realized in thestructure at present. To observe if the structure’s frequencies havereduced with time as the result of the natural process of cracking,Building 2’s frequency estimates are presented with time in Fig. 5.While there is potentially a slight softening evident from thisfigure, given the comparatively limited time span of these observa-tions in comparison with the expected life cycle of the building, a

definitive conclusion on the evolution of permanent softeningcannot be reached.

6.2. Overall trends in damping ratios

The resulting damping values for Buildings 1, 2 and 3 arepresented in Figs. 6, 7 and 8, respectively. As expected, the dampingestimates show significantly more scatter than the frequencyestimates for all three buildings and, consistent with the observa-tions in Section 5, the scatter is more pronounced for HPBW. This ofcourse emphasizes the importance of evaluating damping over asuite of events. To facilitate discussion, the average damping valuesfor each building are reported in Table 4. The average dampingestimate for Building 1 is within approximately 10% for the two

0.176

0.177

0.178

0.179

0.18

0.181

0.182

0.183

0.184

0.185

0.170.1720.1740.1760.178

0.180.1820.1840.1860.188

0.19

0 0.1 0.2 0.3 0.4 0.5

HPBWRDTFEM

0 0.2 0.4 0.6 0.8

Normalized Acceleration Normalized Acceleration

Freq

uenc

y (H

z)

Fig. 3. Natural frequency estimates for Building 2 in the in fundamental x-sway mode (left) and y-sway mode (right). The FEM estimated natural frequency for x-sway(not shown) is 0.148 Hz.

0.115

0.116

0.117

0.118

0.119

0.12

0.121

0.122

0 1 2 3 4 50.115

0.116

0.117

0.118

0.119

0.12

0.121

0.122

0.123

0.124

0 1 2 3 4 5

HPBWRDTFEM

Normalized Acceleration Normalized Acceleration

Freq

uenc

y (H

z)

Fig. 4. Natural frequency estimates for Building 3 in the fundamental x-sway mode (left) and y-sway mode (right).

0.176

0.177

0.178

0.179

0.18

0.181

0.182

0.183

0.184

0.185

10/2002 6/2003 3/2004 11/2004 7/2005 3/2006 11/2006 8/2007

Date of Event

10/2002 6/2003 3/2004 11/2004 7/2005 3/2006 11/2006 8/2007

Date of Event

HPBWRDT

0.17

0.172

0.174

0.176

0.178

0.18

0.182

0.184

0.186

0.188

0.19HPBWRDT

Freq

uenc

y (H

z)

Fig. 5. Fundamental frequency estimates for Building 2 plotted against date of event for x-sway mode (left) and y-sway mode (right).

R. Bashor et al. / J. Wind Eng. Ind. Aerodyn. 104–106 (2012) 88–9792

(Ager  Bashor  et  al,  2012)  

Most  of  the  change  (increase)  in  period  occurs  at  very  small  levels  of  lateral  deforma5on  

dependence may be evidenced by the fact that RDT dampingvalues in the y-axis of all three buildings are larger in Event 2 thanEvent 1.

In previous analysis of the data from these buildings, dampingvalues similar to the RDT results reported here were observed forBuilding 1, which tends to manifest comparable levels of dampingon both axes. In the case of Building 2, y-sway damping valueswere previously observed to be larger than x-sway (Kijewski-Correa and Pirnia, 2007), and this was affirmed by the RDT resultsin this study. While Building 2 would be generally expected tohave greater damping than Building 1, by virtue of its use ofconcrete, what is more interesting is the stark difference indamping values between the two axes of this concrete building.Reasons for this variation in damping along the two axes of thisbuilding were explored in Kijewski-Correa and Pirnia (2007) forthis building and for other buildings in Erwin et al. (2007) andBentz and Kijewski-Correa (2008). These studies have demon-strated that structural systems with greater degrees of frameaction tend to dissipate more energy than systems that aredominated by cantilever action (member level axial deforma-tions). In Building 2, shear walls and outriggers engage theexterior columns to achieve global cantilever action in thex-direction, whereas the y-direction is dominated by compara-tively more frame action as the beams and slabs are the primarymechanisms to engage the lateral resistance of the building.Therefore the in-situ observations reported herein are consistentwith the hypothesis that frame-dominated systems yield higherlevels of damping. Even when comparing the RDT damping levelsin the two steel buildings, one may hypothesize that Building 1,which has been observed to be dominated by cantilever action asan essentially pure tube (Bentz and Kijewski-Correa, 2008) wouldhave less damping than Building 3, whose panel zone sheardeformations have been extensively studied (Bentz et al., 2010).In total these observations help to provide a more rational basisfor the levels of damping to be assumed in design, as opposed tothe crude respective assumptions of 1% or 2% critical for steel andconcrete.

5.2. Comparison of results with finite element models

One of the primary objectives of the CFSMP is to validateassumptions made in the development of finite element modelsused in design by comparing their predictions and in-situ values.Comparisons of the results in Tables 2 and 3 to the designpredictions in Table 1 affirms that Building 1’s in-situ funda-mental sway frequencies show excellent agreement with thedesign predictions, which may be explained by the fact that, asmentioned previously, the structure’s elements are engagedprimarily axially as a structural tube and may thereby be less

susceptible to uncertainties in modeling material, section orconnection details. Building 2 is 20% stiffer in-situ in the x-direction and 13% stiffer in-situ in the y-direction than originallypredicted by the finite element model, while the converse is truefor Building 3 (11% softer in-situ), reaffirming observations inprevious studies (Kijewski-Correa et al., 2006). Moreover, the in-situ values for Building 2 suggest a greater consistency betweenthe fundamental mode frequencies in sway than predicted byfinite element models. A variety of sources have been andcontinue to be explored to determine the causes of this discre-pancy, from rigid off sets in connection modeling, to the influenceof panel zones, to the assumptions regarding in-situ materialproperties and the degree of cracking in concrete elements(Kijewski-Correa et al., 2006; Bentz et al., 2010).

6. Analysis of overall trends in dynamic properties

In the following, several hundred wind events were identifiedas stationary, i.e., having 80% of triggered data in a given eventpass the aforementioned tests, and were analyzed using the samesystem identification approaches discussed previously. The num-ber of records available for analysis varies for each building,depending on the number of times it triggers. In this study, 500events will be analyzed for Building 1 and 200 for each ofBuildings 2 and 3—events are defined as those having at leastfive triggered 1 h time histories.

6.1. Overall trends in frequency estimates

The natural frequency estimates for Buildings 1, 2, and 3 fromboth HPBW and RDT are shown in Figs. 2, 3 and 4, respectively.For reference, the natural frequency assumed for the finiteelement model is indicated in the figures by a thick horizontalline except in instances where discrepancies between in-situ dataand predictions are so great that they cannot be reasonablyshown on the same figure. It should be noted that the amplitudeof responses for each of the buildings varies widely, as does thenumber of triggered events displayed. While more pronouncedscattering may be evident with increasing amplitude, particularlywith Building 2, this cannot be fully concluded given the limitedamount of data. Still, clear evidence of amplitude dependence andsoftening with increased response is displayed for all threebuildings, consistent with initial observations from a narrowersubset of CFSMP data in Kijewski-Correa and Pirnia (2007).Interestingly, in some cases, though recognizing the limitedextent of the amplitude ranges available for analysis here, thefrequency softening appears to plateau (see Building 1 x-axis andboth axes of Building 2), whereas in the case of Building 3, there is

0.202

0.203

0.204

0.205

0.206

0.207

0.208

0.209

0.21

0 0.2 0.4 0.6 0.8Normalized Acceleration Normalized Acceleration

Freq

uenc

y (H

z)

0.14

0.141

0.142

0.143

0.144

0.145

0.146

0 0.5 1 1.5 2 2.5

HPBWRDTFEM

Fig. 2. Natural frequency estimates for Building 1 in fundamental x-sway mode (left) and y-sway mode (right).

R. Bashor et al. / J. Wind Eng. Ind. Aerodyn. 104–106 (2012) 88–97 91

Damping Ratios in Buildings 123  

Evalua5on  Changes  with  Amplitude  

(Ager  Fang  et  al,  1999)  

Several  wind  studies  have  also  documented  that  increments  in  period  and  damping  tend  to  saturate  once  you  reach  a  certain  amplitude  

2-44 2: General Nonlinear Modeling PEER/ATC-72-1

focus of wind studies, there are more data available for tall buildings

subjected to wind vibrations than to earthquake shaking, worldwide.

Information from these studies, however, is still limited by the number of

instrumented buildings and relatively small displacement amplitudes.

Moreover, there are some differences in the loading effects between wind

and earthquakes that can affect response. For example, wind introduces

aero-elastic damping associated with fluid dynamics of airflow, which is not

present under earthquake shaking. Also, nonlinearities in the soil-

foundation-structure interface are expected to have a larger effect on

earthquake-induced motions than wind-induced motions.

The amplitude dependence of damping for wind vibration in buildings has

been well established by Jeary (1986) and others. Figure 2-26 shows a plot

of damping measured by Fang et al. (1999) in a 30-story (120 meter)

building that demonstrates the typical amplitude dependence considered in

wind engineering. In this example, damping was calculated from wind

vibration data collected over a two year period, which provided

measurements at various amplitudes. As shown, damping increases from

negligible amounts, to about 0.5% critical damping in the so-called “high

amplitude plateau.”

It should be noted, however, that even the largest recorded amplitudes in the

high amplitude plateau are on the order of 0.02% roof drift. This is well

below the amplitudes associated with serviceability or safety limit states for

strong ground motions (i.e., drifts on the order of yield-level drifts of 0.5% to

1%). Unfortunately, there are no studies relating damping at the high

amplitude plateau for wind loading to damping at larger drifts expected under

earthquake shaking.

Figure 2-26 Illustration of amplitude dependence of measured damping

under wind loading (Fang et al., 1999).

Damping Ratios in Buildings 124  

Summary  and  Conclusions  

•  Results   from   a   comprehensive   study   on   damping   ra8os   inferred   from   records  obtained  in  instrumented  buildings  subjected  to  earthquakes.  

•  This  study  is  different  from  previous  studies  in  a  number  of  ways:  o  It   exclusively   uses   data   from   earthquake   loading   that   was   large   enough   to  

digi8ze  the  analog  data.  o  Much  larger  number  of  data  points  both  in  number  of  buildings  and  number  of  

damping  ra8os  o  All  data  was  inferred  using  a  common  method  for  all  data  which  avoids  mixing  

data  from  different  methods.  o  Uses  a   system   ID  which   is  directly   relevant   to  how  most   structural   engineers  

will  be  using  the  data  (modal  response  history  analysis  assuming  a  fixed-­‐base).  

•  Damping   ra8os   are   characterized   by   very   large   variability,   which   means   that  recommending   or   using   “a   value”   could   lead   to   significant   errors.   A   simple   but  smarter  approach  is  to  contemplate  a  range  of  values  (not  necessarily  max  and  min,  it  could  be  plus  or  minus  one  standard  devia8on).  

 •  Damping   ra8os   are   highly   skewed   to   larger   values   which   together   with   the   large  

variability  means  than  mean  values  can  be  quite  a  bit  larger  than  median  values.  

Page 32: Miranda Damping Ratios v5 for Seaonc

32  

Damping Ratios in Buildings 125  

Summary  and  Conclusions  

•  Mean   damping   ra8os   from   RC   building   are   sta8s8cally   higher   than   concrete  buildings,   indica8ng   that   the   common   prac8ce   of   assuming   5%   damping   for   all  buildings  is  not  very  good.  

•  Similar  to  previous  studies,  this  study  has  shown  there   is  an   important  decrease   in  damping  ra8os  with  height.  This  reduc8on  is  primarily  due  to  reduc8on  in  radia8on  damping  with  decreasing   frequency   (increasing  period)   and   increasing   slenderness  ra8o.  

•  Results  from  this  study  suggest  that  recent  recommenda8ons  of  using  2  or  2.5%  for  very   tall   buildings  may   lead   to   overes8ma8ons  of   the   level   of   damping  present   in  very  tall  buildings.  

•  Data   does   not   support   the   common   idea   of   important   increments   in   level   of  damping   with   increasing   response   amplitude.   Although   increments   do   occur,   a  significant  por8on  of  this   increment  in  damping  ra5o  occurs  at  very  small   levels  of  deforma8on  and  is  possibly  due  to  period  elonga8ons  in  these  ranges  of  amplitudes  but  are  not  necessarily  increments  in  the  actual  level  of  damping  in  the  structure.    

Damping Ratios in Buildings 126  

Some  references  on  previous  work  

Hart,  G.  C.,  &  Vasudevan,  R.   (1975).  Earthquake  design  of  buildings:  damping.Journal  of  the  Structural  Division,  101(1),  11-­‐30.      Haviland,   R.   (1976).   A   study   of   the   uncertain8es   in   the   fundamental   transla8onal  periods  and  damping  values  for  real  buildings.  Massachuse;s  Ins8tute  of  Technology,  Department  of  Civil  Engineering,  Constructed  Facili8es  Division.      Lagomarsino,   S.   (1993).   Forecast   models   for   damping   and   vibra8on   periods   of  buildings.  Journal  of  Wind  Engineering  and  Industrial  Aerodynamics,  48(2),  221-­‐239.      Tamura,   Y.,   &   Suganuma,   S.   Y.   (1996).   Evalua8on   of   amplitude-­‐dependent   damping  and  natural   frequency  of   buildings   during   strong  winds.   Journal   of  wind   engineering  and  industrial  aerodynamics,  59(2),  115-­‐130.    Suda,   K.,   Satake,  N.,  Ono,   J.,  &   Sasaki,   A.   (1996).  Damping  proper8es  of   buildings   in  Japan.  Journal  of  wind  engineering  and  industrial  aerodynamics,59(2),  383-­‐392.      

Damping Ratios in Buildings 127  

Some  references  on  previous  work  

   Goel,  R.  K.,  &  Chopra,  A.  K.  (1997).  Vibra8on  proper8es  of  buildings  determined  from  recorded   earthquake  mo8ons.   Earthquake   Engineering   Research   Center,  University  of  California.      Satake,   N.,   Suda,   K.   I.,   Arakawa,   T.,   Sasaki,   A.,   &   Tamura,   Y.   (2003).   Damping  evalua8on   using   full-­‐scale   data   of   buildings   in   Japan.   Journal   of   structural  engineering,  129(4),  470-­‐477.      Fritz,  W.  P.,   Jones,  N.  P.,  &   Igusa,   T.   (2009).  Predic8ve  models   for   the  median  and  variability  of  building  period  and  damping.  Journal  of  structural  engineering,135(5),  576-­‐586.      Smith,  R.,  Merello,  R.,  &  Willford,  M.  (2010).  Intrinsic  and  supplementary  damping  in  tall  buildings.  Proceedings  of  the  ICE-­‐Structures  and  Buildings,163(2),  111-­‐118.