MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division 444 Cedar Street, Suite 145, St. Paul, Minnesota 55101-5145 Phone: 651/215-0500 FAX: 651/215-0525 TTY: 651/282/6555 Internet: http://www.dps.state.mn.us Alcohol & Gambling Enforcement Bureau of Criminal Apprehension Capitol Security Crime Victim Services Driver & Vehicle Services Emergency Management / Emergency Response Commission State Fire Marshal / Pipeline Safety State Patrol Traffic Safety ADULT DAY CARE INFORMATION SHEET SECTION 1 INTRODUCTION This fire safety information sheet is based on the 2003 Minnesota State Fire Code (MSFC), the 2003 Minnesota State Building Code (MSBC) and the 2000 International Residential Code (IRC). It contains a summary of the major rules that apply to adult day care facilities. The requirements outlined in this information sheet apply only to adult day care facilities as defined below: Adult Day Care, Group I-4 –An adult day care center serving ambulatory, non-ambulatory, mobile or non-mobile persons who are not mentally or physically capable of taking appropriate action for self- preservation under emergency conditions as determined by program licensure provisions, each accommodating more than four persons shall be classified as an I-4 occupancy. Adult Day Care, Group E – An adult day care center serving four or more ambulatory and mobile persons who are capable of taking appropriate action for self-preservation under emergency conditions as determined by program licensure provisions shall be classified as a Group E occupancy. Adult Day Care, Group R-4 – Residential occupancies shall include buildings arranged for occupancy as Residential Care/Assisted Living Facilities including more than five but not more than 16 occupants, excluding staff. Adult Day Care, Group R-3 – A residential occupancy housing no more than five unrelated adults that may or may not be capable of self- preservation. An adult day care provider may be required to meet other requirements that are not listed in this publication. This information sheet provides an overview of the major code requirements that apply in this type of occupancy and does not attempt to cover every situation. References to the applicable code sections are found in brackets, [ ]. SFMD Fact Sheet INS-FACT-01 March 31, 2003 Page 1 of 24

Upload: others

Post on 05-Jun-2020

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY · SECTION 2 ⎯ OCCUPANCY CLASSIFICATIONS FOR ADULT DAY CARE 2.1 Occupancy Classifications Adult day care facilities can have several

MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division 444 Cedar Street, Suite 145, St. Paul, Minnesota 55101-5145 Phone: 651/215-0500 FAX: 651/215-0525 TTY: 651/282/6555 Internet: http://www.dps.state.mn.us

Alcohol & Gambling

Enforcement

Bureau of Criminal

Apprehension

Capitol Security

Crime Victim Services

Driver & Vehicle

Services

Emergency Management /

Emergency Response

Commission

State Fire Marshal /

Pipeline Safety

State Patrol

Traffic Safety

ADULT DAY CARE INFORMATION SHEET

SECTION 1 ⎯ INTRODUCTION This fire safety information sheet is based on the 2003 Minnesota State Fire Code (MSFC), the 2003 Minnesota State Building Code (MSBC) and the 2000 International Residential Code (IRC). It contains a summary of the major rules that apply to adult day care facilities. The requirements outlined in this information sheet apply only to adult day care facilities as defined below:

Adult Day Care, Group I-4 –An adult day care center serving ambulatory, non-ambulatory, mobile or non-mobile persons who are not mentally or physically capable of taking appropriate action for self-preservation under emergency conditions as determined by program licensure provisions, each accommodating more than four persons shall be classified as an I-4 occupancy. Adult Day Care, Group E – An adult day care center serving four or more ambulatory and mobile persons who are capable of taking appropriate action for self-preservation under emergency conditions as determined by program licensure provisions shall be classified as a Group E occupancy. Adult Day Care, Group R-4 – Residential occupancies shall include buildings arranged for occupancy as Residential Care/Assisted Living Facilities including more than five but not more than 16 occupants, excluding staff. Adult Day Care, Group R-3 – A residential occupancy housing no more than five unrelated adults that may or may not be capable of self-preservation.

An adult day care provider may be required to meet other requirements that are not listed in this publication. This information sheet provides an overview of the major code requirements that apply in this type of occupancy and does not attempt to cover every situation. References to the applicable code sections are found in brackets, [ ].

SFMD Fact Sheet INS-FACT-01 March 31, 2003 Page 1 of 24

Page 2: MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY · SECTION 2 ⎯ OCCUPANCY CLASSIFICATIONS FOR ADULT DAY CARE 2.1 Occupancy Classifications Adult day care facilities can have several

SFMD Fact Sheet INS-FACT-01 March 31, 2003 Page 2 of 24 For the purpose of this information sheet an “existing” building is any home or facility constructed before March 31, 2003. A “new” building is any home or facility constructed on or after March 31, 2003. Prospective adult day care operators must contact the appropriate licensing agency (county or state) for a site inspection prior to requesting a fire inspection.

More information is available from the Minnesota State Fire Marshal Division at (651) 215-0500. Email questions to [email protected] or check our web page at www.fire.state.mn.us for the latest information on fire in Minnesota.

SECTION 2 ⎯ OCCUPANCY CLASSIFICATIONS FOR ADULT DAY CARE

2.1 Occupancy Classifications Adult day care facilities can have several different occupancy classifications. Below is a summary of the different classifications an adult day care could be given under the Minnesota State Building Code (MSBC) and Minnesota State Fire Code (MSFC). Please read carefully to determine where your facility fits within the four different classifications. These occupancy classifications are based on the number of residents in the home and their capacity to escape the premise without assistance.

Residential (R-3) Occupancy-If five or fewer clients are housed in a residential home that may or may not be capable of self-preservation shall be classified as a Group R-3 Occupancy.

Residential (R-4) Occupancy-Any adult day care with no less than six residents but not more than sixteen housed in a residential home where all the clients are capable of self-preservation shall be classified as a Group R-4 Occupancy.

Educational (E) Occupancy-If an adult day care facility houses four or more ambulatory or mobile persons who are all capable of self-preservation the facility shall be classified as a Group E Occupancy. Centers serving only participants who are capable of taking appropriate action for self-preservation under emergency conditions shall meet all applicable requirements for a Group E occupancy.

Institutional (I-4) Occupancy-If an adult day care facility has five or more residents who are NOT capable of self-preservation the facility shall be classified as a Group I-4 Occupancy. Centers serving only participants who are not capable of taking appropriate action for self-preservation under emergency conditions shall meet all applicable requirements for a Group I-4 occupancy. Centers Serving both participants capable and participants not capable of self

preservation. Centers serving a population that includes both participants who are capable and participants who are not capable of taking appropriate action for self-preservation under emergency conditions shall meet the occupancy requirements for Group I-4 or E occupancies. Should the facility become an E occupancy, the center shall meet ALL the requirements set forth below (not applicable for I-4 occupancies):

Population-Not more than 50% of the center’s licensed capacity shall be made up of participants who are not capable of taking appropriate action for self-preservation under emergency conditions.

Page 3: MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY · SECTION 2 ⎯ OCCUPANCY CLASSIFICATIONS FOR ADULT DAY CARE 2.1 Occupancy Classifications Adult day care facilities can have several

SFMD Fact Sheet INS-FACT-01 March 31, 2003 Page 3 of 24 Location-The center must be located on a floor level with all exits directly to grade without any intervening stairs. Fire alarm and detection-The center shall be protected with a complete automatic fire detection system consisting of automatic smoke detection in all corridors and at the top of all stairways and automatic detection in boiler and furnace rooms, kitchens, storage rooms, janitor’s closets, laundry rooms, and other hazardous areas. In buildings equipped with manual fire alarm systems, the manual fire alarm and automatic detection systems shall be electrically interconnected. Evacuation time- The center shall demonstrate the ability to evacuate the entire population of the center within three minutes.

SECTION 3 – NUMBER, TYPE AND ACCESS TO EXITS FOR GROUP R-3 OR

R-4 OCCUPANCIES 3.1 General When required, emergency escapes (second means of egress) shall be installed and maintained in Group R occupancies as specified in MSFC (03) Section 1009.1, MSBC (03) Section 1009 and this policy. The second means of escape may be through an adjacent non-lockable space, independent of and remote from the primary exit. The second means of escape shall not be through a furnace room or through a space/area that could become blocked by a malfunctioning furnace or water heater [MSFC (03) Section 1009.1, as amended].

Any one of the following five options will satisfy the requirement for an emergency escape from a room [MSFC (03) Section 1009.1 and MSBC (03) Section 1009]:

1. An escape window is not required if the room has a door that leads directly to the

exterior of the building. 2. Escape windows installed prior to April 11, 1983 and having a clear opening not

less than 20 inches in width, 24 inches in height and 5.0 square feet in area with a finished sill height not more than 48 inches above the floor may be allowed to continue.

3. An escape window is not required if the building is protected through-out by an approved, automatic sprinkler system.

4. Escape windows need not be installed from rooms of existing buildings having two separate means of escape, provided that the means of escape are independent of each other and they pass through one adjacent non-lockable room or area.

5. Existing escape windows at single-story resort buildings installed prior to October 3, 1975 and having a clear opening not less than 20 inches in width, 20 inches in height, and 4.5 square feet in area with a finished sill height not more than 36 inches above the floor may be allowed to continue.

The second means of escape must also be sufficiently separated from the primary means of escape such that a single fire will not block both routes [MSFC (03) Section 1009.1, as amended]. Travel through an attached garage may be permitted as a second separate means of escape if there is no distinct hazard and all of the following conditions are met:

• The primary exit leads directly outside through a side-hinged, swinging door

Page 4: MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY · SECTION 2 ⎯ OCCUPANCY CLASSIFICATIONS FOR ADULT DAY CARE 2.1 Occupancy Classifications Adult day care facilities can have several

SFMD Fact Sheet INS-FACT-01 March 31, 2003 Page 4 of 24

complying with the MSBC (03). • The attached garage is fire-separated from the dwelling as required by the MSFC (03)

or reprinted below in Section 7. • Unobstructed access with an aisle at least 36 inches in clear width is provided from

the dwelling door to the garage service door. • Where appropriate, all unacceptable hazards must be stored in a location remote from

the exit path or must be in an approved storage cabinet. Unacceptable hazards commonly include gasoline, kerosene, fuel oil, LP gas, paint thinners, charcoal lighter materials and hazardous electrical wiring or appurtenances.

• A side-hinged, swinging door to the exterior is provided. Sliding glass doors may be accepted as qualifying exit doors provided that the doors are maintained operational at all times [MSBC (03) Section 1003.3.1.2 and MSFC (03) Section 1003.3.1.2].

3.2 Approved egress windows When used as a second means of egress, windows shall comply with the following minimum size requirements:

For escape windows installed prior to April 11, 1983: • A minimum of 20 inches in width • A minimum of 24 inches in height • A minimum of 720 square inches (5.0 square feet) of clear opening • A maximum of 48 inches from the floor to the sill opening

For newly installed escape windows on levels above or below grade level and windows installed on or after April 11, 1983: • A minimum of 20 inches in width • A minimum of 24 inches in height • A minimum of 820 square inches (5.7 square feet) of clear opening • A maximum of 44 inches from the floor to the sill opening For grade floor egress/escape windows installed on or after March 31, 2003: • A minimum of 20 inches in width • A minimum of 24 inches in height • A minimum of 720 square inches (5.0 square feet) of clear opening • A maximum of 44 inches from the floor to the sill opening Newly installed grade floor escape windows shall have a minimum net clear opening of 5 square feet [IRC (03) Section R310.1.1]. State Fire Marshal Division policy will allow the following for existing windows, windows in new construction shall meet the size requirements of MSFC (03) Section 1009.1 without removing portions of the window and shall meet the requirement for distance off the floor without the installation of a platform. Approved egress/escape windows shall include the following [MSFC (03) Section 1009.1]:

Page 5: MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY · SECTION 2 ⎯ OCCUPANCY CLASSIFICATIONS FOR ADULT DAY CARE 2.1 Occupancy Classifications Adult day care facilities can have several

SFMD Fact Sheet INS-FACT-01 March 31, 2003 Page 5 of 24

• Double hung windows • Sliding windows • Casement windows

Easily removable sashes may be acceptable for existing one and two family dwellings if demonstrated to be openable by the resident or occupant within approximately 60 seconds.

The sashes and/or hardware of the above windows, along with their storm/screens shall be easily removable and provide the clear opening requirements based on the date of construction for the building. Sashes that tip out only and can not be removed from the frame and awning style windows do not meet this requirement.

See the attached diagrams at the end of this information sheet for additional description of acceptable egress windows and a worksheet for determining compliance with the requirements of the MSFC (03). For additional information on escape windows please see the SFMD Policy titled, Egress Windows (Emergency Escapes).

3.3 Access to doors and windows Exit doors from individual dwelling units may be provided with a night latch, dead bolt or security chain provided that such devices are openable from the inside without the use of a key or tool and mounted at a height not to exceed 48 inches above the finished floor. All locking devices shall be of an approved type. Minnesota State Statute § 16B.61 permits the use of double cylinder-keyed dead bolt locks in single family homes. 3.4 Egress window opening height Egress windows with openings up to 52 inches off of the floor may meet the height requirement (for existing windows as applicable from Section 2.3 above) by securing a step, platform or bed to the wall directly underneath the window. This step, platform or bed shall be no more than 44 inches below the opening and must be strong enough to support the weight of the person. The minimum acceptable width shall be the same as the window opening. The minimum acceptable depth away from the wall shall be 18 inches [MSFC (03) Section 1009.1].

3.5 Coverings on egress windows Plastic coverings are allowed to cover egress/escape windows and exterior doors if the plastic covering meets the following requirements [MSFC (03) Section 1009.1]:

• The plastic covering shall be readily transparent. The occupant shall be able to readily see rescuers on the outside and rescuers shall be able to readily see people on the inside.

• The plastic covering may only be attached on the inside and can only be attached to the window frame or structure with two sided tape, hook and loop (Velcro) or static cling.

• The plastic shall have enough material overhanging the attachment on all sides, top and bottom to facilitate grabbing it from any direction and allow easy removal.

Page 6: MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY · SECTION 2 ⎯ OCCUPANCY CLASSIFICATIONS FOR ADULT DAY CARE 2.1 Occupancy Classifications Adult day care facilities can have several

SFMD Fact Sheet INS-FACT-01 March 31, 2003 Page 6 of 24 3.6 Window wells Escape and rescue windows with a finished sill height below the adjacent ground elevation shall have a window well. Window wells at escape or rescue windows shall comply with the following [MSFC (03) Section 1009.1]. See the attached diagrams for additional description or acceptable window wells and a worksheet for determining compliance with the requirements of the MSFC (03).

3.6.1 Window well size For window wells installed prior to June 29, 1998.

The State Fire Marshall will accept existing window well dimensions that are at least as wide as the window. The distance the window well extends away from the building shall be at least 22 inches. In all cases, the window well shall allow the opening of the window to the full 90 degrees. Window wells with a vertical depth of more than 44 inches shall be equipped with an approved permanently affixed ladder or stairs that is accessible with the window in the fully open position. The ladder or stairs shall not encroach into the required dimensions of the window well.

For window wells installed on or after June 29, 1998.

The window well shall have clear horizontal dimensions that allow the window to be fully opened and provide a minimum accessible net clear opening of 9 square feet with minimum dimensions of 36 inches. Any window opening into the window well shall open to one side and may not intrude into the window well clear opening by more than 6 inches. In addition, a minimum of 30 inches shall be provided between the window in its open position and the opposite well wall. Window wells with a vertical depth of more than 44 inches shall be equipped with an approved permanently affixed ladder or stairs that is accessible with the window in the fully open position. The ladder shall not encroach more than 6 inches into the 36-inch clear open space. The ladder is also not allowed to encroach into the 30 inches between the open window and the opposite wall.

3.7 Obstructions and covers on window wells Emergency escape or rescue windows, doors or window wells required for day care shall be maintained free of any obstruction, including bars, grates or similar devices that would impair egress [MSFC (2003) Section 1009.1.1]. Window wells may be covered as necessary to keep the window well clear of debris, snow, and rain water and to help prevent people from falling in if the building owner wishes. However, the cover shall comply with the following requirements:

a. The covering shall not interfere with the opening of the window in any way. b. The covering shall be supported in such a way that it can not become frozen to the

ground, window well or structure. c. The covering shall be readily removable without the use of tools or special

knowledge from the window well area by the building occupants.

SECTION 4 – NUMBER, TYPE AND ACCESS TO EXITS FOR GROUP E AND I-4 OCCUPANCIES

4.1 New and Existing Buildings The means of egress requirements within this section pertain to both new and existing buildings. Exception: Means of egress conforming to the requirements of the building code under which they were constructed shall be considered as complying means of egress if, in the opinion of the code official, they do not constitute a distinct hazard to life [MSFC (03) Section 1010.1].

Page 7: MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY · SECTION 2 ⎯ OCCUPANCY CLASSIFICATIONS FOR ADULT DAY CARE 2.1 Occupancy Classifications Adult day care facilities can have several

SFMD Fact Sheet INS-FACT-01 March 31, 2003 Page 7 of 24 4.2 Number and Type of Exits – New and Existing Every room or area shall have access to at least one approved exit. Access to at least two exits shall be provided when the occupant load exceeds 50 for those adult day care facilities classified as Group E Occupancies, or when the occupant load exceeds 10 for those adult day care facilities classified as Group I-4 Occupancies [MSFC (03) Section 1004.2.1]. Floor areas shall be provided with exits as required by MSFC (03) Section 1005.2. To determine the occupant load, divide the total net square footage of the rooms or areas to be used for adult care by the occupant load factor in Table 4.2.

Table 4.2 Minimum Egress Requirements Adult Day Care Occupancy Type

Minimum of Two Exits Required When the

Number of Occupants Exceeds

Minimum of Two Exits Required When the

Square Footage Exceeds

Occupant Load Factor (square feet

per person)

E 50 1000 square feet 20 I-4 10 200 square feet 20

4.3 Locking Devices – New and Existing Exit doors shall be openable from the inside without the use of a key or any special knowledge or effort. Exit doors shall not be locked, chained, bolted, barred, latched or otherwise rendered unusable. All locking devices shall be of an approved type [MSFC (03) Section 1003.3.1.8]. Any exit or exit access door serving an occupant load of 100 or more within Group E adult day care centers shall not be provided with a latch or lock unless such components are integral with approved panic hardware or fire exit hardware [MSFC (03) Section 1003.3.1.9]. 4.4 Exit Doors – New and Existing Doors within the means of egress shall be side-hinged swinging. Doors shall swing in the direction of egress travel where serving an occupant load of 50 or more persons [MSFC (03) Section 1003.3.1.2]. 4.5 Exit Width – New and Existing The means of egress width shall not be less than required by the MSFC as determined by the occupant load served [MSFC (03) Section 1003.2.3]. The minimum width of each door opening shall be sufficient for the occupant served as determined by MSFC (03) Section 1003.2.3 or shall provide a clear width of not less than 32 inches, whichever is greater [MSFC (03) Section 1003.3.1.1]. Corridor width shall be as determined in MSFC (03) Section 1003.2.3, but shall not be less than 36 inches when serving an occupant load of 50 or less, and not less than 44 inches when serving an occupant load of greater than 50 [MSFC (03) Section 1004.3.2.2]. Exception: Corridors within Group E adult day care centers serving an occupant load of 100 or more shall not be less than 72 inches. 4.6 Dead End Corridors – New and Existing Where more than one exit or exit access doorway is required, the exit access shall be arranged such that dead end corridors do not exceed 20 feet in length [MSFC (03) Section 1004.3.2.3, new; MSFC (03) Section 1010.17.2, existing].

Page 8: MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY · SECTION 2 ⎯ OCCUPANCY CLASSIFICATIONS FOR ADULT DAY CARE 2.1 Occupancy Classifications Adult day care facilities can have several

SFMD Fact Sheet INS-FACT-01 March 31, 2003 Page 8 of 24 Exception: Fully sprinklered Group E Occupancies constructed prior to 1975 are allowed to have dead end corridors up to 35 feet in length. 4.7 Common Path of Egress Travel – New and Existing The maximum travel distance from any point within a building to a point where two separate and distinct paths of egress travel are available shall not exceed 75 feet [MSFC (03) Section 1004.2.5]. 4.8 Exit Access Travel Distance – New and Existing Exits shall be located so that the maximum length of exit access travel, measured from any point within a building to an exit or the entrance of an exit component along the natural and unobstructed path of egress travel, shall not exceed the following distances [MSFC (03) Section 1004.2.4].

Table 4.8 Exit Access Travel Distance Occupancy Classification Without Sprinkler System With Sprinkler System

E 200 FT 250 FT

I-4 150 FT 200 FT

4.9 Egress through Intervening Spaces – New and Existing Egress from a room or space shall not pass through adjoining or intervening rooms or areas, except where such rooms or areas are accessory to the area served; are not a high-hazard occupancy; and provide a discernible path of egress travel to an exit. Egress shall not pass through kitchens, store rooms, closets or spaces used for similar purposes. An exit access shall not pass through a room which can be locked to prevent egress [MSFC (03) Section 1004.2.3]. 4.10 Means of Egress Illumination – New and Existing The means of egress in all new and existing buildings shall be illuminated at all times the building is occupied [MSFC (03) Section 1003.2.11]. In the event of primary power loss, an approved back-up power source shall be provided for those areas requiring two or more means of egress [MSFC (03) Section 1003.2.11.2, new construction; MSFC (03) Section 1010.5, existing]. 4.11 Means of Egress Identification – New and Existing Exit and exit access doors shall be marked by approved exit signs readily visible from any direction of egress travel for both new and existing buildings in rooms or areas requiring more than one exit or exit access. Access to exits shall be marked by readily visible exit signs in cases where the exit or path of egress travel in not immediately visible to occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet from the nearest visible exit sign [MSFC (03) Section 1003.2.10.1, new and existing]. Exit signs shall be internally or externally illuminated at all times. In the event of primary power loss, an approved back-up power source shall be provided [MSFC (03) Section 1003.2.10.5, new; MSFC Section 1010.4, existing]. 4.12 Means of Egress Obstructions – New and Existing Obstructions shall not be placed in the required width of a means of egress. The required capacity of a means of egress system shall not be diminished along the path of egress [MSFC (03) Section 1003.2.8].

Page 9: MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY · SECTION 2 ⎯ OCCUPANCY CLASSIFICATIONS FOR ADULT DAY CARE 2.1 Occupancy Classifications Adult day care facilities can have several

SFMD Fact Sheet INS-FACT-01 March 31, 2003 Page 9 of 24 SECTION 5 ⎯ STAIRS AND PROTECTION OF OPENINGS IN GROUP R-3 AND R-4

OCCUPANCIES 5.1 Guardrails – New buildings (constructed after March 31, 2003) Unguarded floor openings, open and glazed sides of stairways, landings and ramps and balconies or porches that are more than 30 inches above grade or the floor below shall be protected by guardrails in accordance with the MSBC [MSFC (2003) Section 1003.2.12 and MSBC (2003) Section 1003.2.12]. The top of the guard for a one and two family dwellings may be constructed not less than 36 inches (914 mm) in height. The guards shall have balusters or ornamental patterns such that a 4-inch diameter (102 mm) sphere cannot pass through any opening up to a height of 34 inches. From 34-36 inches, a sphere 8-inch in diameter (203 mm) shall not pass.

Guardrails – Existing buildings (constructed before March 31, 2003)

Guards shall be provided at the open sides of means of egress that are more than 30 inches (762 mm) above the floor or grade below. The guards shall form a protective barrier not less than 36 inches high. Existing guards on the open side of stairs shall be not less than 30 inches (760 mm) high. Open guards shall have balusters or ornamental patterns such that a 6-inch diameter (152 mm) sphere cannot pass through any opening up to a height of 34 inches (864 mm). Existing open guards may be acceptable if approved by the code official [MSFC (03) Section 1010.6].

5.2 Stairways – New Stairways shall have a handrail on at least one side and the rise and run shall be in accordance with the 2000 International Residential Code (IRC). Stairways shall not be less than 36 inches (914 mm) in clear width at all points above the permitted handrail height and below the required headroom height. The minimum clear width of the stairway at and below the handrail height, including treads and landings, shall not be less than 31.5 inches (787 mm) where a handrail is installed on one side and 27 inches (698 mm) where handrails are provided on both sides. The maximum riser height shall be 8 inches and the minimum tread depth shall be 9 inches. The riser heights shall be measured vertically between leading edges of the adjacent treads. The tread depth shall be measured horizontally between the vertical planes of the foremost projection of adjacent treads and at a right angle to the tread’s leading edge. For additional information on spiral stairs or circular stairways, please review IRC Section R314. Stairways – Existing

Existing stairs in buildings shall be permitted to remain if the rise does not exceed 8 ¼ inches (210 mm) and the run is not less than 9 inches (229 mm). Existing stairs can be rebuilt. Existing stairs may be acceptable if approved by the code official [MSFC (03) Section 1010.10].

5.3 Handrails – New Handrails shall not project more than 4.5 inches (114 mm) on either side of the stairway. Handrails should have a minimum and maximum height of 34 inches and 38 inches (864 mm and 965 mm), respectively, measured vertically from the nosing of the treads, shall be provided on at least one side of the stairways. All required handrails shall be continuous running the full length of the stairs with two or more risers from a point directly above the top riser of a flight to a point directly above the lowest riser of the flight. Handrails shall not have sharp points at each end

Page 10: MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY · SECTION 2 ⎯ OCCUPANCY CLASSIFICATIONS FOR ADULT DAY CARE 2.1 Occupancy Classifications Adult day care facilities can have several

SFMD Fact Sheet INS-FACT-01 March 31, 2003 Page 10 of 24 and those located adjacent to a walls shall have a space of not less than 1.5 inches (38 mm) between the wall and the handrail [IRC (00) Section R315]. Handrails – Existing

Stairways shall have handrails on at least one side. Handrails shall be located so that all portions of the stairway width required for egress capacity are within 44 inches (1118 mm) of a handrail. The height of these handrails measured above stair tread nosings, shall be uniform, not less than 30 inches (762 mm) and not more than 42 inches (1067 mm). Exception: Aisle stairways provided with a center handrail are not required to have additional handrails.

5.4 Storage under stairways Storage under stairway is permitted in one and two family dwellings; for details, see the State Fire Marshal Division Policy INS-31 titled, Storage Under Stairs.

SECTION 6 – FIRE RESISTIVE CONSTRUCTION FOR ADULT DAY CARE

OCCUPANCIES

6.1 Fire resistive construction for adult day cares classified as Group R-3 or R-4 6.1.1 Occupancy separations – new and existing A home with an attached garage must be provided with a separation wall between the dwelling and garage is required to prevent the spread of smoke and fire from the garage into the home. The separation must extend from floor to ceiling and must be constructed in accordance with the following [IRC Section R309]:

• A single layer of 1/2” gypsum wall board applied on the garage side for both new and existing construction.

Doors must be constructed in one of the following ways:

• solid-wood door at least 1-3/8 inches in thickness, or • insulated steel door at least 1-3/8 inches in thickness, or • labeled door having a fire-protection rating of not less than 20 minutes.

6.1.2 Fire-resistive construction – new and existing

Fire-resistive construction, including occupancy separations, area separation walls, and exterior walls due to location on property, fire-resistive requirements based on type of construction, draft-stop partitions and roof coverings may be required in some occupancies. When required, they shall be maintained as specified in the MSFC (03) and MSBC (03) and shall be properly repaired, restored or replaced when damaged, altered, breached, penetrated, removed or improperly installed [MSFC (03) Section 703.1]. In general, the only fire-resistive construction in most one and two family dwellings involves the garage separation as described in Section 7.1.

6.2 Fire resistive construction for adult day cares classified as Group E or I-4

6.2.1 Occupancy Separation – New Adult day care centers shall be separated from other occupancies with fire-resistive occupancy separations in accordance with the Minnesota State Building Code [MSFC

Page 11: MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY · SECTION 2 ⎯ OCCUPANCY CLASSIFICATIONS FOR ADULT DAY CARE 2.1 Occupancy Classifications Adult day care facilities can have several

SFMD Fact Sheet INS-FACT-01 March 31, 2003 Page 11 of 24

(03) Section 701.1]. Table 5.1 lists the required time rating for fire-resistive occupancy separations dependent upon the classification of the adult day care center (Group E or Group I-4) and the occupancy to be separated [MSFC (03) 701.1; MSBC (03) 302.3.3].

Exception: Except for Group H and I-2 areas, where the building is equipped throughout with an approved automatic sprinkler system, the fire-resistance ratings shall be reduced by one-hour but to not less than one-hour and to not less than that required for floor construction according to the type of construction.

Table 5.1 Required Fire-Resistive Occupancy Separations

Group E Adult Day Care Occupancy

U A, B, F-2, H-4, I, M, R, S-2

F-1, H-3, H-5, S-1

H-2 H-1

Separation 1 HR

2 HR 3 HR 4 HR Not Permitted

Group I-4 Adult Day Care Occupancy

U A, B, E, F-2, I, M, R, S-2

F-1, H-3, H-5, S-1

H-2, H-4

H-1

Separation 1 HR

2 HR 3 HR 4 HR Not Permitted

6.2.2 Occupancy Separation – Existing Existing Group E and Group I-4 adult day care occupancies shall be separated from Group I and Group R occupancies in accordance with the State Building Code. See Table 5.1 of this document for details [MSFC (03) Section 705]. In addition, because Group H (Hazardous) occupancies are classified as such due to the presents of sufficient quantities of hazardous materials, existing Group E and Group I-4 adult day care occupancies shall also be separated from all Group H occupancies in accordance with the State Building Code [MSFC (03) Section 102.2].

Previous editions of the MUFC required occupancy separations between adult day care centers and most other occupancy types. Therefore, most existing adult day care centers that are lacking proper occupancy separations as prescribed by previous MUFC editions shall be provided with separations in accordance with the MSBC [MSFC (03) Section 102.1].

6.3 Accessory Use Areas – New and Existing Except where required for incidental use areas, fire-resistive construction shall not be required for accessory use areas not occupying more than 10 percent of the area of any floor of a building [MSFC (03) Section 701.1; MSBC (03) 302.2]. 6.4 Incidental Use Areas – New New adult day care centers shall have their incidental use areas separated from the rest of the building by fire-resistive construction in accordance with the State Building Code [MSFC (03) Section 701.1; MSBC (03) 302.1.1]. Examples of incidental use areas include furnace rooms (over 400,000 Btu input); boiler rooms (over 15 psi and 10 hp); parking garages; laboratories and

Page 12: MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY · SECTION 2 ⎯ OCCUPANCY CLASSIFICATIONS FOR ADULT DAY CARE 2.1 Occupancy Classifications Adult day care facilities can have several

SFMD Fact Sheet INS-FACT-01 March 31, 2003 Page 12 of 24 shops; waste, linen, laundry or storage rooms over 100 square feet.

6.4.1 Incidental Use Areas-Existing In existing adult day care centers, shops; laboratories containing hazardous materials; storage rooms over 100 square feet; and rooms containing boilers or central heating plants (over 400,000 Btu input) shall be separated from the rest of the building by one-hour fire resistive construction [MSFC (03) Section 705.3].

6.5 Corridor Construction – New All corridors serving an occupant load greater than 30 within adult day care centers classified as Group E shall be of one-hour fire-resistive construction. Regardless of the occupant load served, all corridors within adult day care centers classified as Group I-4 shall be of one-hour fire-resistive construction [MSFC (03) Section 1004.3.2.1]. All openings within one-hour fire-resistive corridors shall be protected with listed 20-minute fire-rated assemblies. Fire doors shall be self-closing [MSFC (03) Section 1004.3.2.1; SBC (03) Section 714.2]. Exceptions: 1. Group E and I-4 adult day care centers where the building is equipped throughout with an

approved automatic sprinkler system. 2. Group E adult day care centers where each room used for child care has at least one door

directly to the exterior at ground level and rooms for assembly purposes have at least one-half of the required means of egress doors opening directly to the exterior at ground level.

6.6 Corridor Construction – Existing All corridors serving an occupant load greater than 30 within adult day care centers classified as Group E shall be of one-hour fire-resistive construction. All corridors serving an occupant load greater than 10 within adult day care centers classified as Group I-4 shall be of one-hour fire-resistive construction. Door openings within one-hour fire-resistive construction shall be protected by 20-minute fire-rated assemblies, insulated steel doors, or solid core wood doors not less than 1-3/4 inches thick. Fire doors shall self-closing [MSFC (03) Section 1010.17]. Exceptions: 1. Group E and I-4 adult day care centers where the building is equipped throughout with an

approved automatic sprinkler system. 2. Group E adult day care centers where the building is protected with an approved automatic

fire alarm system which is monitored by an approved central station service. The fire alarm system shall include automatic smoke detection throughout the exiting system and approved detection in all rooms and areas other than classrooms, child care areas and offices.

6.7 Vertical Opening & Shaft Construction – New Vertical openings and shafts within new adult day care centers shall be constructed in accordance with the State Building Code, Section 707 [MSFC (03) Section 701.1]. Generally, all openings through a floor/ceiling assembly shall be protected with a fire-resistance rated construction. Vertical openings and shafts shall have a fire-resistance rating of not less than 2 hours where connecting four stories or more and 1 hour where connecting less than four stories. Shaft enclosures shall have a fire-resistance rating of no less than the floor assembly penetrated, but need not exceed 2 hours. 6.8 Vertical Opening & Shaft Construction – Existing Vertical openings and shafts within existing adult day care centers shall be protected with fire-

Page 13: MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY · SECTION 2 ⎯ OCCUPANCY CLASSIFICATIONS FOR ADULT DAY CARE 2.1 Occupancy Classifications Adult day care facilities can have several

SFMD Fact Sheet INS-FACT-01 March 31, 2003 Page 13 of 24 resistance rated construction in accordance with table 5.5.1 [MSFC (03) Section 704.1].

Table 6.8 Required Protection for Vertical Openings and Shafts Occupancy

Classification Conditions Protection Required

Group E vertical openings connecting 2 stories

no protection required

Group E vertical openings connecting 3 to 5 stories

1-hour protection or automatic sprinklers throughout

Group E vertical openings connecting more than 5 stories

1-hour protection

Group I-4 vertical openings connecting 2 or more stories

1-hour protection

6.9 Maintenance of Fire-Resistive Construction – New and Existing All required fire-resistive construction and assemblies, including occupancy separations, area separation walls, exterior walls due to location on property, draft-stop partitions, separations of special hazards and hazardous areas, vertical opening protection and smoke barriers shall be provided and maintained as specified within the Minnesota State Building Code and the Minnesota State Fire Code and shall be properly repaired, restored or replaced when necessary [MSFC (03) Section 703.1 & 703.2]. 6.10 Height and area limitations 6.10.1 Group R-3 occupancies

Group R-3 occupancies shall be constructed in accordance with the International Residential Code. 6.10.2 Group R-4 occupancies Group R-4 occupancies shall meet the requirements for a Group R-3 occupancy and shall be constructed in accordance with the International Residential Code. 6.10.3 Group E and I-4 occupancies Height and area limitations for Group E and I-4 occupancies shall comply with State Building Code Table 503 below. Table 503 – Height and Area Limitations

Occupancy Type Type I Type II Type III Type IV Type V

A B A B A B A A B

Height (feet) UL 160 65 55 65 55 65 50 40

E S (stories) UL UL 3 2 3 2 3 1 1

A (area in sq. ft.) UL UL 26,500 14,500 23,500 14,500 25,500 18,500 9,500

Page 14: MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY · SECTION 2 ⎯ OCCUPANCY CLASSIFICATIONS FOR ADULT DAY CARE 2.1 Occupancy Classifications Adult day care facilities can have several

SFMD Fact Sheet INS-FACT-01 March 31, 2003 Page 14 of 24

I-4 S (stories) UL 5 3 2 3 2 3 1 1

A (area in sq. ft.) UL 60,500 26,500 13,000 23,500 13,000 25,500 18,500 9,000

UL=Unlimited

SECTION 7 – INTERIOR FINISH AND DECORATIONS

7.1 Interior finish and decoration requirements for R-3 or R-4 occupancies – new and existing Interior finish on walls and ceilings shall be Class A, B, or C (Class I, II, or III) [MSFC (03) Section 806.3]. 7.2 Interior finish and decoration requirements for E or I-4 occupancies – new and existing In general, interior finish within new and existing adult day care centers shall meet the following flame spread requirements [MSFC (03) Section 801.1.1, new; MSFC (03) Section 806, existing]. Group E Adult Day Care Centers Sprinklered Buildings Rooms and Enclosed Spaces…………………….Class C Exit Access Corridors and Exitways…….………Class C Vertical Exits and Exit Passageways…………….Class B Unsprinklered Buildings Rooms and Enclosed Spaces…………………….Class C Exit Access Corridors and Exitways…………….Class B Vertical Exits and Exit Passageways…………….Class A Group I-4 Adult Day Care Centers Sprinklered Buildings Rooms and Enclosed Spaces……………………Class B Exit Access Corridors and Exitways…………… Class B Vertical Exits and Exit Passageways……………Class B Unsprinklered Buildings Rooms and Enclosed Spaces…………………… Class B Exit Access Corridors and Exitways…………… Class A Vertical Exits and Exit Passageways……………Class A

Exception: In vertical exits of buildings less than three stories in height, Class B interior finish for unsprinklered buildings and Class C for sprinklered buildings shall be permitted.

7.3 Interior Decorative Materials in I-4 occupancies Curtains, drapes, hangings and other decorative materials suspended from walls or ceilings shall be flame resistant or noncombustible within Group I-4 adult day care centers [MSFC (03) Section 805.1].

Page 15: MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY · SECTION 2 ⎯ OCCUPANCY CLASSIFICATIONS FOR ADULT DAY CARE 2.1 Occupancy Classifications Adult day care facilities can have several

SFMD Fact Sheet INS-FACT-01 March 31, 2003 Page 15 of 24 7.4 Artwork and other miscellaneous combustible materials on walls and ceilings Artwork and teaching materials shall be limited on walls and corridors to not more than 20 percent of the wall area for Group E and I-4 adult day care centers [MSFC (03) Section 803.3.2 & 803.4.2]. 7.5 Storage in Corridors and Lobbies Clothing and personal effects shall not be stored in corridors and lobbies of adult day care centers [MSFC (03) Section 803.3.1 & 803.4.1]. Exceptions:

1. Corridors protected by an approved automatic sprinkler system. 2. Storage in metal lockers provided the minimum required egress width is maintained.

SECTION 8 – DETECTION SYSTEMS IN GROUP R-3 AND R-4 OCCUPANCIES

8.1 Detection requirements for Group R-3 or R-4 occupancies Experience and full scale testing has shown that typical residential fires produce detectable quantities of smoke prior to detectable levels of heat in nearly all cases. In addition, slowly developing, smoldering fires may produce incapacitating and even lethal levels of smoke and toxic gases without any significant increase in room temperature. The State Fire Marshal will not accept heat detectors as an alternative or equal to smoke detectors in locations requiring the installations of smoke detectors. 8.2 Location In homes built prior to March 31, 2003. Smoke detectors shall be installed in hallways or areas giving access to each separate sleeping area. Where sleeping rooms are on an upper level only, the detector shall be placed at the center of the ceiling directly above the stairway. Smoke detectors shall also be installed in the basement of dwelling units having a stairway, which opens from the basement into the dwelling unit [MSFC (03) Section 907.3.6]. In homes built on or after March 31, 2003. A smoke detector shall be installed in each sleeping room and at a point centrally located in the corridor or area giving access to each separate sleeping area. When the dwelling unit has more than one story and in dwellings with a basement, a detector shall be installed on each story and in the basement. In dwelling units where a story or basement is split into two or more levels, the smoke detector shall be installed on the upper level, except that when the lower level contains a sleeping area a detector shall be installed on each level. When sleeping rooms are on an upper level, the detector shall be placed at the ceiling of the upper level in close proximity to the stairway. In dwelling units where the ceiling height of a room open to the hallway serving the bedrooms exceeds that of the hallway by 24 inches or more, smoke detectors shall be installed in the hallway and in the adjacent room. Where more than one smoke alarm is required to be installed in a single family home, the smoke alarms shall be interconnected in such a manner that the activation of one alarm will activate all the alarms in the dwelling unit. [MSFC (03) Section 907.2.10.3].

Page 16: MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY · SECTION 2 ⎯ OCCUPANCY CLASSIFICATIONS FOR ADULT DAY CARE 2.1 Occupancy Classifications Adult day care facilities can have several

SFMD Fact Sheet INS-FACT-01 March 31, 2003 Page 16 of 24 8.3 Power supply In homes constructed prior to August 1, 1989. Smoke detectors may be battery powered only [MSFC (03) Section 907.3.6, as amended]. When new bedrooms are created in homes built prior to August 1, 1989, the detector in the bedroom is allowed to be battery-operated [MSFC (98) Section 907.2.10 and MSBC (03) Section 907.2.10]. In homes constructed on or after August 1, 1989 and before March 31, 2003. Smoke detectors shall receive their primary power supply from a centralized power source [Minn. Stat. § 299F.362, subd. 3a]. Wiring shall be permanent and without a disconnecting switch other than those required for over current protection. When new bedrooms are created, the detector in the new bedroom shall receive its primary power supply from a centralized power source and be equipped with a battery backup. In homes constructed on or after March 31, 2003. Smoke detectors shall receive their primary power from the building wiring when such wiring is served from a commercial source and shall be equipped with a battery backup. Wiring shall be permanent and without disconnecting switch other than those required for over-current protection [MSFC (03) Section 907.2.10 and MSBC (03) Section 907.2.10]. When new bedrooms are created, the detector in the new bedroom shall receive its primary power from the building wiring when such wiring is served from a commercial source and shall be equipped with a battery backup.

8.4 Installation Detector location and spacing shall be as follows, in addition to the manufacturer’s instructions [NFPA 72 (1999 Edition) 2-3.4]:

a. Smoke detectors in rooms with ceiling slopes greater than 1-foot rise per 8 feet horizontally shall be located at the high side of the room.

b. A smoke detector installed in a stairwell shall be so located as to ensure that smoke rising in the stairwell cannot be prevented from reaching the detector by an intervening door or obstruction.

c. A smoke detector installed to detect a fire in the basement shall be located in close proximity to the stairway leading to the floor above.

d. Smoke detectors shall be mounted on the ceiling at least 4 inches from a wall or on a wall with the top of the detector not less than 4 inches or more than 12 inches, below the ceiling.

e. Smoke detectors shall not be located within kitchens, garages, or in other spaces where temperatures can fall below 32 oF, or exceed 100 oF.

f. Smoke detectors shall not be located within 3 feet of supply registers of a forced air heating or cooling system and doors to a kitchen or bathroom with tub or shower.

g. For peaked ceilings, the smoke detector must be installed within 3 feet of the peak.

UL or FM (Factory Mutual) listed and approved fire-alarm systems both hardwired and wireless are also acceptable. Detectors with a battery shall emit a signal when the battery is low. 8.5 Alterations, Repairs and Additions to a One and Two Family Dwelling When interior alterations, repairs or additions requiring a permit occur, or when one or more sleeping rooms are added or created in existing dwellings, the individual dwelling unit shall be provided with smoke alarms located as required for new dwellings; the smoke alarms shall be interconnected and hard-wired (IRC Section R317.1.1).

Page 17: MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY · SECTION 2 ⎯ OCCUPANCY CLASSIFICATIONS FOR ADULT DAY CARE 2.1 Occupancy Classifications Adult day care facilities can have several

SFMD Fact Sheet INS-FACT-01 March 31, 2003 Page 17 of 24 Exceptions:

1. Smoke alarms in existing areas shall not be required to be interconnected and hard-wired where the alterations or repairs do not result in the removal of interior wall or ceiling finishes exposing the structure, unless there is an attic, crawl space, or basement available which could provide access for hard wiring and interconnection without the removal of interior finishes.

2. Repairs to exterior surfaces of dwellings are exempt from the requirements of this section.

SECTION 9 – FIRE PROTECTION SYSTEMS FOR GROUP R-4, E AND I-4

OCCUPANCIES

9.1 Required Fire Alarm Systems – New and Existing 9.1.1 Group R-4 adult day care centers Please refer to section 8 for the specific smoke alarm requirements for Group R-4 occupancies. 9.1.2 Group E adult day care centers Group E adult day care centers having an occupant load of 50 or more shall be provided with an approved fire alarm system [MSFC (03) Section 907.2.3, new; MSFC (03) Section 907.3.2, existing]. Initiation. Initiation of the system shall be by manual and automatic means. Approved automatic fire detectors shall be provided in laundry rooms, boiler and furnace rooms, mechanical and electrical rooms, shops, laboratories, kitchens, locker rooms, janitor closets, trash-collection rooms, storage rooms, lounges and similar areas.

Exceptions: 1. Buildings protected throughout by an approved automatic sprinkler system, manual fire

alarm boxes are only required in the main office and in a custodial area. 2. Where the exiting systems are protected by approved automatic smoke detection with

alarm verification, manual fire alarm boxes are only required near exits serving shops, chemistry and physics laboratories, boiler rooms, industrial technology and industrial arts rooms, kitchens, custodian’s office, and the main office.

Travel through adjoining rooms. Where the only means of egress travel from an interior room or rooms having an aggregate occupant load of more than 10 occupants is through an adjoining or intervening room, automatic smoke detectors shall be installed throughout the common atmosphere through which the path of egress travel passes. Notification. Activation of the fire alarm system or automatic sprinkler systems shall initiate a general evacuation signal. 9.1.3 Group I-4 adult day care centers Group I-4 adult day care centers shall be provided with an approved fire alarm system [MSFC (03) Section 907.2.6, new; MSFC (03) Section 9907.3.3, existing].

Page 18: MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY · SECTION 2 ⎯ OCCUPANCY CLASSIFICATIONS FOR ADULT DAY CARE 2.1 Occupancy Classifications Adult day care facilities can have several

SFMD Fact Sheet INS-FACT-01 March 31, 2003 Page 18 of 24

Initiation. Initiation of the system shall be by manual and automatic means. Approved automatic fire detectors shall be provided in laundry rooms, boiler and furnace rooms, mechanical and electrical rooms, shops, laboratories, kitchens, locker rooms, janitor closets, trash-collection rooms, storage rooms, lounges and similar areas. Automatic smoke detection shall be shall be provided in waiting areas that are open to corridors. Notification. Activation of the fire alarm system or automatic sprinkler systems shall initiate a general evacuation signal. In addition, activation of the fire alarm system shall immediately transmit an alarm to an approved central station or remote station service.

9.2 Required Fire Sprinkler Systems – New Group R-4 An automatic sprinkler system shall be provided throughout all buildings containing a Group R-4 fire area with more than eight occupants. Group E An automatic sprinkler system shall be provided throughout all Group E fire areas greater than 20,000 square feet in area. An automatic sprinkler system shall also be provided for every Group E area below the level of exit discharge [MSFC (03) Section 903.2.2].

Exception: Where each classroom or care area has at least one exterior exit door at ground level.

Group I-4 An automatic sprinkler system shall be provided throughout all buildings containing a Group I-4 adult day care center [MSFC (03) Section 903.2.5].

9.2.1 Special Fire Sprinkler Requirements – New Fire sprinkler protection may also be required for stories and basements in excess of 1500 square feet not provided with adequate openings to the exterior [MSFC (03) Section 903.2.12].

9.3 Special Fire Sprinkler Requirements – Existing A fire sprinkler system shall be provided in basements containing a Group E or Group I-4 adult day care center when such areas exceed 2500 square feet in size and do not have 20 square feet of opening entirely above the adjoining ground level in each 50 lineal feet or fraction thereof of exterior wall on at least one side of the building. Required openings shall have a minimum dimension of 30 inches. If any portion of the basement is located more than 75 feet from required openings, the basement shall be provided with an approved automatic sprinkler system throughout [MSFC (03) Section 903.6.2].

9.4 Fire Extinguisher Type and Location – New and Existing At least one portable fire extinguisher having a minimum rating of 2A-10BC shall be available within 75 feet of all occupied areas. Travel to another floor level to obtain the extinguisher is not acceptable. Extinguishers shall be mounted and located in conspicuous locations where they will be readily accessible and immediately available for use [MSFC (03) Section 906.1]. In kitchens containing commercial cooking equipment that produces grease-laden vapors, a

Page 19: MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY · SECTION 2 ⎯ OCCUPANCY CLASSIFICATIONS FOR ADULT DAY CARE 2.1 Occupancy Classifications Adult day care facilities can have several

SFMD Fact Sheet INS-FACT-01 March 31, 2003 Page 19 of 24 minimum rated 40B fire extinguisher shall be provided within 30 feet of travel distance. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable fire extinguisher [MSFC (03) Section 904.11.5]. Fire extinguishers shall be serviced and tagged by qualified personnel annually [MSFC (03) Section 906.2] NOTE: Fire extinguishers are not required in adult day care facilities classified as Group R-3 or R-4 unless specifically required by the licensing agency.

SECTION 10 – BUILDING SERVICES AND SYSTEMS, HEATING AND ELECTRICAL

EQUIPMENT

10.1 Heating appliances Heating appliances shall be listed by a nationally recognized testing agency [MSFC (03) Section 603.5].

Exception: Unlisted appliances may be installed where permitted by the code official, provided clearances from combustibles are maintained in accordance with the Mechanical Code.

Heating appliances shall be installed in accordance with the manufacturer’s instructions and the State Building, Mechanical and Electrical Codes [MSFC (03) Section 603.5.2]. Portable unvented fuel-fired heating equipment are prohibited within adult day care centers [MSFC (03) Section 603.4]. 10.2 Electrical Services – New and Existing Identified electrical hazards shall be corrected in accordance with the MSFC (03) Section 605 and the State Electrical Code [MSFC (03) 605.1]. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the State Electrical Code shall be prohibited [MSFC (03) Section 605.4]. Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed [MSFC (03) Section 605.4.1]. Extension cords shall not be used as a substitute for permanent wiring. Extension cords shall be used only with portable appliances [MSFC (03) Section 605.5]. Electrical appliances and fixtures shall be tested and listed by an approved agency and installed in accordance the manufacture’s instructions [MSFC (03) Section 605.7]. 10.3 Gas Meters and Piping – New and Existing Above-ground gas meters, regulators and piping subject to damage shall be protected by a barrier complying with MSFC (03) Section 312 or otherwise protected in an approved manner [MSFC (03) 603.9].

Page 20: MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY · SECTION 2 ⎯ OCCUPANCY CLASSIFICATIONS FOR ADULT DAY CARE 2.1 Occupancy Classifications Adult day care facilities can have several

Egress Window Worksheet for Windows Installed Before April 11, 1983

1) Check Window Height and Width CASEMENTDOUBLE HUNG SLIDING

SFMD Fact Sheet INS-FACT-01 March 31, 2003 Page 20 of 24

Is the distance,

Is the clear openable height,

2) Check Window Opening Area (fill in the three blanks)

at least 24 inches?

Is the clear openable width, at least 20 inches?

XOpenable height (inches) Openable width (inches)

=Openable area (square inches)

Is the clear openable area, Yes Noat least 720 square inches?

3) Check the distance from the floor to the bottom of opening

Yes No

Yes No

Yes No

(bottom of opening) 48 inches or less? from the floor to the finished sill

If you answered yes to all questions then the window should comply with the 2003 Minnesota State Fire Code. For assistance: Minnesota State Fire Marshal Division (651) 215-0500; TTY: (651) 282-6555; [email protected]

Page 21: MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY · SECTION 2 ⎯ OCCUPANCY CLASSIFICATIONS FOR ADULT DAY CARE 2.1 Occupancy Classifications Adult day care facilities can have several

Egress Window Worksheet for Ground Floor Windows Installed On or After March 31, 2003

1) Check Window Height and Width CASEMENTDOUBLE HUNG SLIDING

SFMD Fact Sheet INS-FACT-01 March 31, 2003 Page 21 of 24

Is the distance,

Is the clear openable height,

2) Check Window Opening Area (fill in the three blanks)

at least 24 inches?

Is the clear openable width, at least 20 inches?

XOpenable height (inches) Openable width (inches)

=Openable area (square inches)

Is the clear openable area, Yes Noat least 720 square inches?

3) Check the distance from the floor to the bottom of opening

Yes No

Yes No

Yes No

(bottom of opening) 44 inches or less? from the floor to the finished sill

If you answered yes to all questions then the window should comply with the 2003 Minnesota State Fire Code. For assistance: Minnesota State Fire Marshal Division (651) 215-0500; TTY: (651) 282-6555; [email protected]

Page 22: MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY · SECTION 2 ⎯ OCCUPANCY CLASSIFICATIONS FOR ADULT DAY CARE 2.1 Occupancy Classifications Adult day care facilities can have several

Egress Window Worksheet for Windows Installed Above or Below Grade On or After April 11, 1983

1) Check Window Height and Width CASEMENTDOUBLE HUNG SLIDING

SFMD Fact Sheet INS-FACT-01 March 31, 2003 Page 22 of 24

Is the distance,

Is the clear openable height,

2) Check Window Opening Area (fill in the three blanks)

at least 24 inches?

Is the clear openable width, at least 20 inches?

XOpenable height (inches) Openable width (inches)

=Openable area (square inches)

Is the clear openable area, Yes Noat least 820 square inches?

3) Check the distance from the floor to the bottom of opening

Yes No

Yes No

Yes No

(bottom of opening) 44 inches or less? from the floor to the finished sill

If you answered yes to all questions then the window should comply with the 2003 Minnesota State Fire Code. For assistance: Minnesota State Fire Marshal Division (651) 215-0500; TTY: (651) 282-6555; [email protected]

Page 23: MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY · SECTION 2 ⎯ OCCUPANCY CLASSIFICATIONS FOR ADULT DAY CARE 2.1 Occupancy Classifications Adult day care facilities can have several

Window Well Worksheet When Installed Before June 29, 1998

SFMD Fact Sheet INS-FACT-01 March 31, 2003 Page 23 of 24

If the distance,

1) Check Window Well Dimensions

Is the clear horizontal distance, at least 22 inches?

Is the clear horizontal distance, at least as wide as the window?

2) Check the vertical depth of the window well

Yes No

Yes No

Yes No

NoYesIs the window well large enough to allow the window to be opened fully?

from the bottom of the well to the top at grade is more than 44 inches, a ladder is required. If a ladder is required, is one provided?

If you answered yes to all questions then the window should comply with the 2003 Minnesota State Fire Code For assistance: Minnesota State Fire Marshal Division (651) 215-0500; TTY: (651) 282-6555; [email protected]

Page 24: MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY · SECTION 2 ⎯ OCCUPANCY CLASSIFICATIONS FOR ADULT DAY CARE 2.1 Occupancy Classifications Adult day care facilities can have several

Window Well Worksheet When Installed On or After June 29, 1998

1) Check Window Well Dimensions

at least 36 inches? Yes No

Is the clear horizontal distance,

No Yes Is the clear horizontal distance, at least 36 inches?

No Is the clear horizontal distance, with the window open at least 30 inches? Yes 2) Check Window Well Opening Area (fill in the three blanks)

X =

Horizontal distance (inches) Horizontal distance (inches) Net horizontal opening (square inches)

Is the clear openable area, Yes No at least 1,080 square inches?

If the distance,

3) Check the vertical depth of the window well

from the bottom of the well to the top at grade is more than 44 inches, a ladder is required. If a ladder is required, is one provided?

No Yes

SFMD Fact Sheet INS-FACT-01 March 31, 2003 Page 24 of 24 If you answered yes to all questions then the window should comply with the 2003 Minnesota State Fire Code For assistance: Minnesota State Fire Marshal Division (651) 215-0500; TTY: (651) 282-6555; [email protected]