M I C R O S Y S T E M

TCAE-THAE: 105÷109Packaged reversible air cooled water chillers and heat pumps with axial fans.

Series featuring hermetic Scroll compressors.

Version TANK&PUMP T / Hwith pumping group and built-in storage tank.

K11014-GB ed. 1a

S E R I EMINI -Q

TECHNICAL CATALOGUETECHNICAL CATALOGUE

Page 2: MICROSYSTEM - Free · MICROSYSTEM TCAE-THAE: 105÷109 Packaged reversible air cooled water chillers and heat pumps with axial fans. Series featuring hermetic Scroll compressors

2

MINI-Q Main features

Index Main features p. 2 Technical features p. 4 Performance p. 5 Operating limits p. 6 Electronic control p. 7 Installation p. 8 Size characteristics p. 9 Hydraulic connection p. 10 Electrical connection p. 11 Intended conditions of use The TCAE-TCAE T/H units are air cooled water chillers with axial fans, complete with pumping group and water tank. The THAE-THAE T/H are air cooled reversible heat pumps with axial fans, complete with pumping group and water tank. They are intended for use in conditioning plants or industrial processes where a supply of chilled water (TCAE) or chilled and hot water (THAE) is required. The unit is designed for outdoor installation.

The units conform to the following directives: • Machine Directive 89/392/CE (MD); • Low voltage Directive 73/23/CE (LVD); • Electromagnetic compatibility Directive 89/336/CE (EMC); • Pressure equipment Directive 97/23/CE (PED).

Model codes

T Version with pumping group, built-in water tank and standard circulation pump. T

Water treatment unit

C Unit for cooling only

A Axial fan E Hermetic

compressor X N. compressors

XX

Approximated cooling capacity (kW)

- R407C Refrigerant fluid

H Version with pumping group, built-in water tank and high pressure circulation pump)

EXAMPLE T C A E 109 T

Page 3: MICROSYSTEM - Free · MICROSYSTEM TCAE-THAE: 105÷109 Packaged reversible air cooled water chillers and heat pumps with axial fans. Series featuring hermetic Scroll compressors

3

MINI-Q Main features

Features ○ Self bearing structure and panels in Peraluman; cataphoresis treated galvanized steel base; sound insulated compressor compartment. ○ Hermetic rotary compressors, Scroll type, complete with internal thermal protection. ○ Air-side heat exchanger composed of copper pipe and aluminium finned coil, complete with protection grille. ○ Water side plate-type heat exchanger, braze welded plates in stainless steel immerged in the water tank. ○ Differential pressure switch to protect the unit if the water flow stops. ○ Axial fan with external rotor equipped with internal thermal protection and complete with internal and external protection grille. ○ Refrigerant circuit with mild copper pipes complete with: filter drier, charge connections, manual reset safety pressure switch on high pressure side (by means of reset on board), thermostatic expansion valve, (2 for THAE), cycle inversion valve, (for THAE), liquid receiver and non-return valve (for THAE). ○ Unit with IP24 degree of protection. ○ Male-threaded hydraulic connections. ○ Unit complete with: • R407C refrigerant charge. • ductable condensate drain (for THAE);

Electrical board ○ Electrical board accessible from the upper left-hand side panel, conforming with current IEC norms, can be opened and closed with special tool and complete with: • general isolator with door interlock on the power supply; • electrical wiring preset for supply voltage 230V-1ph+N-50Hz (for models 105-107-109 single phase) and 400V-3ph+N-50Hz (for models 107-109 three phase); • auxiliary power supply 230V-1ph-50Hz drawn from the main power supply; • device to monitor phase sequence/missing phases (for models 107-109 three phase); • 3-pole automatic switch with overload protection for the compressor; • protection fuse for the fan and for the auxiliary circuit. • power contactor for the compressor; • user interface terminal board. • remotable unit control. • anti-disturbance net filter; • transformer for electronic control; Programmable microprocessor electronic board controlled by the keyboard inserted in the machine. This electronic board controls the following functions: • Regulation and management of the inlet water temperature set points; of cycle reversal (on model THAE); of the safety timer delays; of the circulation pump; of the compressor and pump run-hours meter; of defrost cycles (on THAE) at temperature; of the electronic anti-freeze protection which cuts in automatically when the machine is switched off; and of the functions which control the intervention mode of the individual organs that comprise the machine; • complete protection of the unit, automatic emergency shutdown and display of the alarms which have been activated; • visualisation of set values, of inlet/outlet water temperatures and of alerts, by display; of working devices, of cooling/heating mode and of the defrosting operation by LED(only THAE); • self-diagnosis with continuous monitoring of the functioning of the unit. • User interface menu. ○ Advanced functions: • configured for serial connection, with RS 485 output for interface connection with building management systems, centralised control systems and supervision networks; • monitoring of service schedule and records; • computer-assisted testing of the units.

TANK & PUMP version ○ T with standard circulation pump ○ H with high pressure circulation pump ○ Pumping unit complete with: inertial storage tank, standard circulation pump for chilled water (for models TCAE THAE 105-107-109 T) or high pressure (for models TCAE THAE 105-107-109 H), membrane expansion tank, manual air vent, automatic air vent, safety valve. Accessories supplied separately KFI � Low ambient control for continuous control of the fan rotation speed down to outdoor air temperature of -10°C during chiller operation, for ambient air temperatures up to 30°C during heat pump. KSA � Rubber anti-vibration mountings. KPB � Low pressure switch. KTR 1 � Remote keyboard and display with the same functions as the one built into the unit. KFA= Water filter KRAA � Anti-freeze heating element on storage tank KIS � RS 485 serial interface for communication with building automation, centralised systems and supervision networks. KCH � RS 232 hardware key for connection to supervision systems, to be combined with one or more KIS serial interface modules if the units are managed on a centralised basis.

Page 4: MICROSYSTEM - Free · MICROSYSTEM TCAE-THAE: 105÷109 Packaged reversible air cooled water chillers and heat pumps with axial fans. Series featuring hermetic Scroll compressors

4

MINI-Q Technical features

MODEL TCAE – THAE 105 T / H 107 T / H 109 T / H Technical data Nominal cooling capacity TCAE-THAE (*) kW 5,01 6,47 7,94 E.E.R. (+) 2,24 2,45 2,39 Nominal heating capacity THAE(**) kW 6,00 8,13 9,93 C.O.P. (*) 2,65 2,99 3,21 Sound pressure level (***) dB(A) 46 47 47 Scroll compressor n. 1 1 1 Fans n. x kW 1x0,13 1x0,19 1x0,19 Exchanger water content L 0,67 0,89 1,12 Water tank contents L 32 43 43 Water side exchanger nominal capacity L/h 861 1.112 1.366 R 407C refrigerant charge TCAE kg 1,9 2,2 2,2 R 407C refrigerant charge THAE kg 2,5 2,75 2,75 Dimensions Length mm 825 825 825 Height mm 920 1.100 1.100 Depth mm 550 550 550 Empty weight TCAE T � TCAE H kg 145 155 157 Empty weight THAE T � THAE H kg 148 160 162 MODEL TCAE – THAE 105 T 107 T 109 T Pump external static pressure (*) kPa 49 70 69 Electrical data Total absorbed power (summer operation) (*) Kw 2,34 2,89 3,57 Total absorbed power (winter operation)(**) Kw 2,37 2,97 3,34

Power input V-ph-Hz 230 � 1+N � 50 230 � 1+N � 50 400 � 3+N � 50

230 � 1+N � 50 400 � 3+N � 50

Nominal current (summer operation) A 10,9 13,5 / 5,7 17,3 / 7,4 Nominal current (winter operation) A 11,1 13,8 / 5,9 16,7 / 7,1 Maximum current A 13,2 16,7 / 7,1 21,2 / 9,0 Starting current A 61 76 / 40 100 /46 MODEL TCAE – THAE 105 H 1107 H 109 H Pump external static pressure (*) kPa 104 106 100 Electrical data Total absorbed power (summer operation) (*) Kw 2,64 3,04 3,72 Total absorbed power (winter operation)(**) Kw 2,67 3,12 3,49

Power input V-ph-Hz 230 � 1+N � 50 230 � 1+N � 50 400 � 3+N � 50

230 � 1+N � 50 400 � 3+N � 50

Nominal current (summer operation) A 12,5 14,4 / 6,1 18,2 / 7,7 Nominal current (winter operation) A 12,7 14,7 / 6,2 17,6 / 7,5 Maximum current A 14,8 17,6 / 7,5 22,1 / 9,4 Starting current A 61 76 / 40 100 / 46

(*) At the following conditions: condenser inlet air temperature 35°C; chilled water temperature 7°C; temperature differential at evaporator 5°C. (**) In the following conditions: evaporator air inlet temperature 7°C D.B., 6°C W.B.; temperature of hot water 45°C, temperature differential at condenser 5°C.

(***) Level of sound pressure in dB(A) refers to a measurement taken at a distance of 5m from the unit with a directionality factor of 2. (to obtain the value in an open field, subtract 3 dB(A)). (+) C.O.P. and E.E.R. calculation does not include the absorbed electrical power of the circulator.

Page 5: MICROSYSTEM - Free · MICROSYSTEM TCAE-THAE: 105÷109 Packaged reversible air cooled water chillers and heat pumps with axial fans. Series featuring hermetic Scroll compressors

5

MINI-Q Performances

Cooling capacity TCAE – TCAES 20 25 30 35 42 45

QF P QF P QF P QF P QF P QF P MODEL Ta (°C) kW kW kW kW kW kW kW kW kW kW kW kW

Tue (°C) 5 5,68 1,60 5,33 1,78 4,98 1,98 4,59 2,22 4,03 2,63 3,77 2,85 7 6,16 1,59 5,80 1,77 5,42 1,97 5,01 2,24 4,40 2,62 4,13 2,83 9 6,68 1,58 6,29 1,77 5,89 1,96 5,46 2,20 4,81 2,60 4,52 2,81 11 7,22 1,57 6,82 1,76 6,39 1,95 5,93 2,19 5,24 2,59 4,92 2,79 13 7,81 1,56 7,38 1,74 6,91 1,94 6,43 2,17 5,70 2,58 5,36 2,77

TCAE THAE 105

15 8,43 1,55 7,97 1,73 7,77 1,92 6,95 2,15 6,18 2,55 5,83 2,75 5 7,43 1,83 6,90 2,05 6,43 2,30 5,94 2,59 5,20 3,09 4,87 3,34 7 7,96 1,83 7,49 2,04 6,99 2,29 6,47 2,64 5,69 3,07 5,33 3,32 9 8,62 1,81 8,12 2,03 7,58 2,28 7,03 2,56 6,19 3,05 5,81 3,31 11 9,31 1,80 8,79 2,01 8,22 2,26 7,63 2,54 6,73 3,03 6,33 3,28 13 10,05 1,78 9,48 1,99 8,89 2,24 8,26 2,52 7,31 3,00 6,89 3,25

TCAE THAE 107

15 10,83 1,76 10,23 1,97 9,60 2,22 8,92 2,49 7,93 2,97 7,48 3,22 5 8,81 2,42 8,36 2,68 7,85 2,98 7,28 3,34 6,37 3,93 5,94 4,21 7 9,47 2,40 9,03 2,66 8,51 2,96 7,94 3,32 7,03 3,91 6,61 4,19 9 10,14 2,38 9,69 2,64 9,18 2,94 8,60 3,30 7,69 3,89 7,27 4,17 11 10,80 2,36 10,35 2,62 9,84 2,92 9,27 3,28 8,36 3,87 7,93 4,15 13 11,46 2,34 11,01 2,60 10,50 2,90 9,93 3,26 9,02 3,85 8,59 4,13

TCAE THAE 109

15 12,12 2,32 11,68 2,58 11,16 2,88 10,59 3,24 9,68 3,83 9,26 4,11

Heating capacity THAE 35 40 45 55

QT P QT P QT P QT P MODEL Tuc (°C) kW kW kW kW kW kW kW kW

Ta (°C) UR (%) -5 90 4,29 1,84 4,27 2,05 4,26 2,31 - - 0 90 5,04 1,83 4,97 2,05 4,92 2,30 - - 5 90 5,90 1,82 5,78 2,03 5,67 2,28 5,56 2,95 7 90 6,29 1,82 6,14 2,03 6,00 2,27 5,84 2,93 10 90 6,90 1,80 6,72 2,01 6,55 2,26 6,29 2,91 15 90 8,07 1,77 7,81 1,98 7,57 2,22 7,16 2,85

THAE 105

20 90 9,39 1,73 9,07 1,93 8,75 2,16 8,16 2,78 -5 90 5,79 2,18 - - - - - - 0 90 6,80 2,17 6,71 2,44 6,65 2,75 - - 5 90 7,96 2,16 7,80 2,42 7,67 2,73 - - 7 90 8,48 2,15 8,29 2,41 8,13 2,72 7,92 3,54 10 90 9,31 2,14 9,08 2,40 8,86 2,71 8,54 3,51 15 90 10,89 2,12 10,56 2,38 10,24 2,68 9,69 3,44

THAE 107

20 90 12,68 2,06 12,27 2,31 11,84 2,60 11,36 3,36 -5 90 7,07 2,47 7,04 2,78 - - - - 0 90 8,30 2,46 8,20 2,76 8,13 3,13 - - 5 90 9,73 2,45 9,54 2,75 9,38 3,10 - - 7 90 10,36 2,44 10,13 2,74 9,93 3,09 9,67 4,02 10 90 11,38 2,43 11,10 2,72 10,82 3,07 10,43 3,99 15 90 13,30 2,39 12,90 2,68 12,52 3,02 11,85 3,92

THAE 109

20 90 15,51 2,33 14,98 2,61 14,47 2,95 13,52 3,82 Tue = Evaporator outlet water temperature (inlet/outlet ∆t = 5°C) Tuc = Condenser outlet water temperature (inlet/outlet ∆t = 5°C) UR=Relative humidity

Ta= Dry bulb ambient temperature QF=Cooling capacity with a fouling factor at the evaporator of 0.35 x 10 �4 m2 °C/W QT=Heating capacity with a fouling factor at the condenser of 0.35 x 10 �4 m2 °C/W

P=Absorbed electrical power NB To obtain the total absorbed power add the circulation pump power input values (see Electrical connections).

Pump external static pressure G (l/h) 1.434 1.260 1.107 972 861 822 663 502 TCAE THAE

105 T ∆pu (kPa) 23 31 39 45 49 51 57 62 G (l/h) 1.477 1.354 1.231 1.107 984 861 738 615 492TCAE THAE

105 H ∆pu (kPa) 76 82 88 94 100 104 108 112 115G (l/h) 2.024 1.706 1.608 1.366 1.112 1.032 856 730 567TCAE THAE

107 T ∆pu (kPa) 38 50 54 62 70 72 77 80 83G (l/h) 1.999 1.625 1.375 1.112 1.000 900 750 600TCAE THAE

107 H ∆pu (kPa) 75 90 100 106 110 112 115 118G (l/h) 2.481 2.240 2.128 1.953 1.666 1.500 1.366 1.350 1.156TCAE THAE

109 T ∆pu (kPa) 33 41 45 52 60 65 69 69 74G (l/h) 2.536 2.232 1.925 1.659 1.378 1.366 1.146 830TCAE THAE

109 H ∆pu (kPa) 60 71 82 90 99 100 105 111 G=Water flow ∆pu =Pump external static pressure

T = Standard circulation pump H = High pressure circulation pump

Page 6: MICROSYSTEM - Free · MICROSYSTEM TCAE-THAE: 105÷109 Packaged reversible air cooled water chillers and heat pumps with axial fans. Series featuring hermetic Scroll compressors

6

MINI-Q operation limits and use of antifreeze solutions

Summer operating limits Winter operating limits

Standard operation (R407C)

Standard operation THAE 105 (R407C)

Operation with condensation control (KFI)

Standard operation THAE 107 (R407C)

T (°C)= outdoor air temperature D.B. t (°C)= evaporator outlet water temperature Temperature differential at evaporator: ∆t=3÷8 °C

Standard operation THAE 109 (R407C)

Operation with condensation control (KFI accessory)

T (°C)= outdoor air temperature D.B. t (°C)= outlet water temperature Temperature differential at evaporator: ∆t=3÷8 °C

N.B. Maximum inlet water temperature 49°C N.B. We can also provide units on demand to supply chilled water at less than 4°C. Use of antifreeze solutions The use of ethylene glycol is foreseen in those cases in which the discharge of the water from the hydraulic circuit is desired during winter shutdown period. The glycol solution modifies the physical features of the water and, consequently, the unit performances in terms of efficiency. The proper glycol percentage to be put into the system can be obtained from the most demanding operating conditions chosen from those detailed hereunder.

Anti-freeze protection during seasonal stop Table “A” shows the multipliers to obtain the changes of the unit performance according to the necessary percentages of ethylene glycol. The multipliers refer to the following conditions: condenser inlet air temperature 35°C; chilled water temperature 7°C; water ∆t at the evaporator 5°C. For different operating conditions the same multipliers can be used since the amount of their change is negligible. Table “A” Min. outdoor air temperature °C 2 0 -3 -6 -10 -15 -20 % glycol in weight 10 15 20 25 30 35 40 Freezing temperature °C -5 -7 -10 -13 -16 -20 -25 fc G 1,008 1,028 1,051 1,074 1,100 1,126 1,153 fc ∆w 1,053 1,105 1,184 1,237 1,316 1,421 1,500 fc QF 0,991 0,987 0,982 0,978 0,974 0,969 0,960 fc P 0,996 0,995 0,993 0,991 0,989 0,987 0,984

fc G correction factor of the glycol water flow to the evaporator fc ∆w = correction factor of the pressure drops through the evaporator fc QF correction factor of the cooling capacity fc P correction factor of the total absorbed current

Page 7: MICROSYSTEM - Free · MICROSYSTEM TCAE-THAE: 105÷109 Packaged reversible air cooled water chillers and heat pumps with axial fans. Series featuring hermetic Scroll compressors

7

MINI-Q Microprocessor electronic control

Keyboard and display description

Fig. 1 The keyboard allows the user to visualise the operation temperature and all the process variables of the unit, and also allows the visualisation and modification of the set points; for technical service it allows, with a password, the access to all parameters of the unit (access allowed to authorized personnel only). KTR 1- Remote keyboard with display for remote control

11 10 3 24

1

6

78

5

9

Fig. 2

The remote keyboard with display (KTR1), allows the remote control and display of all the process variables, both digital and analogue, of the unit. It is therefore possible to control all functions of the unit directly from the room. KIS – Serial interface RS485 (accessory) KCH – Hardware key RS232 (accessory)

Fig. 3

1 = DISPLAY: displays the value of all the parameters (e.g. outlet water temperature etc.), the codes of the possible alarms and the status of all the resources. 2/11 = ON/OFF, RESET - DOWN key: allows the unit to be switched on and off, and any alarms to be reset. It is also used for altering parameters downwards. 3/10 = MODE - UP key: allows selection of the operating mode of the unit (standby, summer or winter cycle). It is also used for altering the parameters upwards. 4 = Summer LED: indicates that the unit is working in cooling mode. 5 = Winter LED: indicates that the unit is working in heating mode. 6 = Compressor LED: indicates operation or time delay of compressor. 7 = Defrosting LED: indicates that the unit is executing a defrost cycle (active only on THAE). 8 = Plate exchanger heater LED: indicates operation of the electrical heater. 9 = Power supply LED: indicates the presence of power supply to the unit. 10/11 = Up, down keys: they are used to look through the list of parameters and any alarms, and to change the set values. The units are equipped with an electronic controller that is compatible with an external system through a serial communication line. The communication protocol allows the access to all the functions of the unit, as: ○ setting all the values accessible by the keyboard; ○ reading all the process variables of the digital as well as analogue inputs and outputs; ○ read the various alarm codes and if necessary reset them; ○ read all the parameters for programming or change some of them.

KIS

KIS

KIS

KCH Personal Computer

Page 8: MICROSYSTEM - Free · MICROSYSTEM TCAE-THAE: 105÷109 Packaged reversible air cooled water chillers and heat pumps with axial fans. Series featuring hermetic Scroll compressors

8

MINI-Q Installation

Handling ○ Movement of the unit should be performed with care, in order to avoid damage to the external structure and to the internal mechanical and electrical components. For proper movement refer to the instructions in the use and maintenance manual. ○ The unit should be correctly levelled and positioned on a supporting surface capable of sustaining its full weight. ○ The unit cannot be installed on brackets or shelves. ○ Do not stack the units.

Fig. 4

Fig. 5

Clearances and positioning ○ The unit is designed for outdoor installation. ○ Segregate the units if installed in areas accessible to persons under 14 years of age. ○ The unit must be installed in compliance with the minimum recommended technical spaces shown in fig. 6, allowing sufficient room for access to the refrigerant and electrical connections on the right hand side.

Fig. 6

Model 105 107 109 a mm 300 300 300 b mm 20 20 20 c mm 500 500 500 d mm 500 500 500 e mm with wide neck

Page 9: MICROSYSTEM - Free · MICROSYSTEM TCAE-THAE: 105÷109 Packaged reversible air cooled water chillers and heat pumps with axial fans. Series featuring hermetic Scroll compressors

9

MINI-Q Dimensional characteristics

TCAE - THAE 105T - 107T - 109T TCAE - THAE 105H - 107H - 109H

Fig. 7

TCAE-THAE T/H 105 107 109 a mm 550 550 b mm 920 1100 c mm 30 30 d mm 458 458 e mm 475 475 f mm 75 75 g mm 103 103 h mm 530 660 i mm 768 898 l mm 150 150 m mm 825 825 n mm 785 785 TCAE Weight (*) kg 145 155 157 THAE Weight (*) kg 148 160 162

1. Control panel 2. Main switch 3. Compressor 4. Wire passage holes 5. Anti-vibration supports (accessory KSA) 6. Water inlet 7. Water outlet 8. Air vent 9. Pump unblock 10. Water charge connection 11. Condensate discharge 12. Fan 13. Electrical board 14. Pump 15. Tank 16. Expansion tank 17. Finned coil

KSA – Anti-vibration mountings The unit can be equipped with anti-vibration rubber mountings supplied on demand (KSA accessory ref. 5). N.B.: Model 105 107 109 Water connections ¾ “G M 1 “G M Condensate drain ∅ , 30 mm Storage tank discharge ½ “G F

○ The unit is fitted with condensate drain pan with ductable discharge (for THAE). (*) The weight of the unit refers to a fully equipped machine with an empty tank (the weight of a fully charged unit is obtained by adding the water content included in the Hydraulic Connection Chapter).

Page 10: MICROSYSTEM - Free · MICROSYSTEM TCAE-THAE: 105÷109 Packaged reversible air cooled water chillers and heat pumps with axial fans. Series featuring hermetic Scroll compressors

10

MINI-Q Hydraulic connection

Connection to the system

○ The unit is equipped with: male threaded hydraulic connections, manual air vent located inside the shell near the hydraulic connections, inertial storage tank, circulation pump, membrane expansion tank (sized for the water content of the machine only) and safety valve. ○ The installation of intercepting valves to insulate the unit from the system is recommended ○ It is compulsory to fit an external mesh filter at the point of entry of the water into the machine (KFA accessory) ○ The water flow through the heat-exchanger should not go below a rate corresponding to a temperature differential of 8°C. ○ Discharging the water from the system is advisable for seasonal shutdown. ○ Water discharge can be carried out by adding ethylene glycol to the hydraulic circuit (see use of antifreeze solutions).

TCAE - THAE 105T - 107T - 109T TCAE - THAE 105H - 107H - 109H

Fig. 8

CE � Microprocessor electronic control CF � Refrigeration circuit ECH � Plate evaporator/condenser FA � Water filter (KFA accessory to be handled by installer) PD � Differential pressure switch PU � Circulation pump R � Interception cock (to be handled by the installer) RE � Storage tank anti-freeze heating element (KRAA accessory to be handled by installer) S � Charging and discharging cock (to be handled by installer)

SA � Storage tank ST1 � Summer-winter working temperature probe ST2 � Antifreeze safety temperature probe ST3 � Temperature probe for defrosting control TP � Pressure transducer (KFI accessory) VE � Expansion tank VS � Safety valve VSA � Automatic air vent VSM � Manual air vent

Hydraulic data MODEL TCAE – THAE T/H 105 107 109 Exchanger water contents L 0,67 0,89 1,12 Water tank contents L 32 43 43 Safety valve kPa 300 300 300

Page 11: MICROSYSTEM - Free · MICROSYSTEM TCAE-THAE: 105÷109 Packaged reversible air cooled water chillers and heat pumps with axial fans. Series featuring hermetic Scroll compressors

11

MINI-Q Electrical connection

Electrical connection TCAE-THAE 105T – 107T - 109T TCAE-THAE 105H – 107H – 109H 230V-1ph-50Hz

Electrical connection TCAE-THAE 107T - 109T TCAE-THAE 107H – 109H 400V-3ph-50Hz

Fig. 9 Fig. 10

○ The electrical board can be accessed from the machine’s side panel. ○ The connections have to be carried out as per rules in force and electrical wiring diagram included. ○ Always install a general isolator in a protected area near the appliance with a delayed characteristic curve of a suitable capacity and breaking capacity. Make sure the general isolator includes a 3mm minimum opening distance between contacts. ○ Earth connection is compulsory by law to ensure user safety while the machine is in use.

LFC – Compressor operation indicator light (power supply 24 Vac) KIS – Serial interface RS485 (accessory) KCH – Hardware key RS232 (accessory) KTR1 – Remote keyboard (accessory) KRAA – Electrical heating element (accessory) KPB – Low pressure switch (accessory) KFI – Condensation control (accessory) LBG – General shutdown indicator light (power supply 24 Vac)

L – Line MEU – User external terminal board MIQE – Electrical board internal terminal board N – Neutral PC – Personal computer PE – Earthing clamp SCR – Remote control selector (control with dry contact) SEI – Summer-winter selector (control with dry contact)

Electrical data MODEL TCAE T/H – THAE T/H 105 107 109 105 107 109 Power input V-ph-Hz 230-1+N-50 400-3+N-50 Maximum absorbed current TCAE T - THAE T A 13,2 16,7 21,2 - 7,1 9 Maximum absorbed current TCAE H - THAE H A 14,8 17,6 22,1 - 7,5 9,4 Starting current A 61 76 100 - 40 46 Line sections mm2 4 4 6 - 2,5 2,5 PE section mm2 4 4 6 - 2,5 2,5 Remote control line section mm2 1,5 1,5 1,5 - 1,5 1,5

Pump electrical data The table shows the absorption of single a pump MODELLO TCAE – THAE 105 107 109 105 107 109 Power input V-ph-Hz 230-1+N-50 400-3+N-50 Absorbed power TCAE T - THAE T kW 0,1 0,25 0,25 - 0,25 0,25 Absorbed current TCAE T - THAE T A 0,4 1,08 1,08 - 1,08 1,08 Absorbed power TCAE H - THAE H kW 0,4 0,4 0,4 - 0,4 0,4 Absorbed current TCAE H - THAE H A 1,95 1,95 1,95 - 1,95 1,95

KRAA Electrical Data – Storage tank anti-freeze heating element MODEL TCAE – THAE T/H 105 107 109 Absorbed power W 130 130 130

Page 12: MICROSYSTEM - Free · MICROSYSTEM TCAE-THAE: 105÷109 Packaged reversible air cooled water chillers and heat pumps with axial fans. Series featuring hermetic Scroll compressors

TCAE-THAE: 105÷109

K11

014-

GB

/ 12

.04

/ 00

0 -

Sta

mpa

:

T E C H N I C A L C A T A L O G U E

RHOSS S.P.A.Via Oltre Ferrovia - 33033 Codroipo (UD) - Italiatel. 0432.911611 - fax 0432.911600 - [email protected] - www.rhoss.it - www.rhoss.com

IRSAP-RHOSS Clima Integral S.L.C/ Leonardo da Vinci, 4 - Pol. Ind. Camí Ral - 08850 Gavà (Barcelona)telf. ++34-93-6334733 - fax ++34-93-6334734 - [email protected]

IR GROUP S.a.r.l.7 rue du Pont à Lunettes - 69390 Vourlestél. ++33-04-72318631 - fax ++33-04-72318632 - [email protected]

RHOSS Deutschland GmbHHölzlestraße 23, D-72336 Balingen, OT Engstlatttel. ++49-7433-260270 - fax ++49-7433-2602720 - [email protected] - www.rhoss.de

RHOSS CHINA Representative OfficeRM. 804 - Building A - Everbright City N. 218, Tianmuxi Road - Shanghai 200070 - Chinatel. 0086-21-63531696; 0086-21-33030011 - fax 0086-21-63531697 - [email protected]

Branch offices

Area Nord-Est: 33033 Codroipo (UD) - Via Oltre Ferroviatel. 0432.911611 - fax 0432.911600

Area Nord-Ovest: 20041 Agrate B. (MI) - Centro Colleoni - pal. Taurus, 1tel. 039.6898394 - fax 039.6898395

Area Centro-Nord: 50127 Firenze - Via F. Baracca, 148/Rtel. 055.4360492 - fax 055.413035

Area Centro-Sud: 00199 Roma - Viale Somalia, 148tel. 06.8600699-06.8600707 - fax 06.8600747

Area Sud-Ovest: 80026 Casoria (NA) - Via Nazionale delle Puglie, 259tel. 081.5846102 - fax 081.5846078

Area Sud: 70123 Bari - Viale dei Maestri del Lavoro, 4tel. 080.5311034 - fax 080.5311000

RHOSS S.P.A. declines all responsabilities for possible mistakes inthe catalogue and reserves the right to alter the features of theirproducts without notice in the interests of continuous improvement.