mi 2086 87 euro instaltest
TRANSCRIPT
-
8/12/2019 MI 2086 87 Euro Instaltest
1/6
T e s tin gM e a surin
g
An a l y sin g
R e c or din g
EN 61010-1EN 50081-1EN 50082-1
Ultimate In str ument s f or C om plete
T e st in g o f Electrical In stalla t i on s
VDE 0100BS 7671CEI 64.8HD 384
EN 61557VDE 0413
Eurotest 61557, Instaltest 61557Eurotest 61557, Instaltest 61557
No. 118740
-
8/12/2019 MI 2086 87 Euro Instaltest
2/6
Eurotest 61557
No. 118740
Instaltest 61557
No. 118740
N E W
-
8/12/2019 MI 2086 87 Euro Instaltest
3/6
Fuse/fault/cable location
Instrument as a generator Location
Rodless Earth Resistance measurement in urban environment
Three phaseadapter
Order No. A 1111
Three phasecable
Order No. A 1110
Plug Commander
Order No. A 1001
Fuse/fault/cableLocator
Order No. A 1005
TipCommander
Order No. A 1002
TECHNICAL CHARA CTERISTICS Eurot est 61557/Instal test 61557
Insu la t ion Res i s t ance
Display range 0 1000 M (Un250 V) 0 200 M (Un < 250 V)Resolution 0.001 0.01 0.1 1 M
Accuracy (2 % + 2 D)(0 200 M )Test voltage 50 100 250 500 1000 V Generator current capability >1 mA
Cont inu i ty o f P ro tec t ion Conduc to r s (single measurement)
Display range 0.00 19.99 20.0 199.9 200 - 2000 Accuracy (2 % + 2 D).(0 20 )Open-terminal test voltage 4 7 Vd.c.Test current >200 mACompensation of test leads yes
Automatic polarity exchange yes
Cont inu i ty (continuous measurement)Display range 0.0 199.9 200 2000
Accuracy (3 % + 3 D)Short-circuit test current
-
8/12/2019 MI 2086 87 Euro Instaltest
4/6
0 . 5 m A
u p t o
2 0 0 A
1 0 m A
u p t o
2 0 0 A
Earth Resistance or HarmonicsPower Energy
Ord er No . S 2001 Ord er No . S 2002
Earth test set 20 m
LargeEarthing Systems
Earth test set 50 m
Standard-range current ClampOrder No. A 1019
Low-range current ClampOrder No. A 1018
RC D Earth /L o o p Re s is t an c e
Measurement principle with or without probeDisplay range 0 10 k
RCD Trip o ut Tim e
Display range (general type) 0 300 m s (0.5 I N, I N)0 150 ms (2 I N) 0 40 ms (5 I N)
Display range (selective type) 0 500 ms (0.5 I N, I N)0 200ms (2 I N) 0 150 ms (5 I N)
Accuracy 3 msRCD Tripp ing Cu rrent
Display range I (0.2 1.1) I
N Display range t /I 0 300 msDisplay range Uci (Uc/I ) 0 100 V
F a u l t L o o p Impedance / Res i s t ance and Ipsc
Display range Z, R, X 0.00 19.99 20.0 199.9 200 2000
Accuracy Z, R, X Eurotest (2 % + 3 D)Accuracy RInstaltest (5 % + 5 D)Display range Ipsc 0.06 A 24.4 kANominal voltage 100 264 V 45 65 Hz Contac t Vo l t age a t P rospec t ive Shor t - c i r cu i t Cur ren t
Display range 0.00 9.99 10.0 99.9 100 - 264 V Accuracy (3 % + 0.02 Ipsc)
L i n e Impedance / Re s is ta n c e an d Ip s c
Display range Z, R, X 0.00 19.99 20.0 199.9 200 2000
Accuracy Z, R, X Eurotest (2 % + 3 D)Accuracy RInstaltest (5 % + 5 D)Display range Ipsc 0.06 A 42.4 kANominal voltage 100 440 V 45 65 Hz
N-PE Loop / Ea r th Res i s t ance and Ipsc
Test method internal generator (Earth resistance)Display range R l -pe 0.00 19.99 20.0 199.9 200 2000
Accuracy R l-pe (2 % + 3 D)Display range Ipsc 0.06 A 24.4 kA
Phase ro ta t ion
Display of result 1.2.3 or 2.1.3
Vol tage Frequency
Display range 0 440 V 45.0 65.0 Hz Accuracy (2 % + 2 D) 0.2 Hz Nominal frequency range 45 65 Hz
Current (True RMS)
Measurement principle current clampDisplay range 0 200 AResolution 0.1 1 mA 0.01 0.1 1ABasic accuracy (5 %)(0.1 100 A)
Nominal frequency 50/60 Hz
Peak Cur ren t
Display range 5 280 ABasic accuracy (5%)
Varistor Overv oltage Prot . Devices Breakd ow n Voltage
Measurement principle d.c. voltage ramp (500 V /s)Display range 50 1000 V
Accuracy (5 % + 10 V)
Fau l t , Fuse , Conduc to r L oca to r
Principle Loading of mains voltage or applying a test signal Loading Is
-
8/12/2019 MI 2086 87 Euro Instaltest
5/6
FUNCTION Instaltest 61557 Eurotes t
61557 REQUIRED ACCESSORIES Insu la t ion Res i s t ance Tip Commander or Universal CableCont inu i ty o f P ro tec t ion Condu c to r s Tip Commander or Universal CableCont inu i ty Tip Commander or Universal CableEar th Res i s t ance (Four-terminal method) Earth Test Set - 20 m or Earth Test Set - 50 mEar th Res i s t ance (Four-terminal method Earth Test Set - 20 m or Earth Test Set - 50 m+ clamp) Low-range Current ClampEar th Res i s t ance (Two-clamp method) Clamp Test Set Spec i f i c Ear th Res i s t ance Earth Test Set - 20 m or Earth Test Set - 50 mFau l t Loop Imp edance , Ipsc Universal CableLine Impedance , Ipsc Universal CableContac t Voltage at Ipsc (SEV 3569) Universal Cable
Probe Test Lead Fau l t Loop Res i s t ance , Ipsc Tip Commander or Universal CableLine Resis tanc e, Ipsc Tip Commander or Universal CableRCD Cont act Volt age at I n RCD Trip o ut Tim e Universal CableRCD Trippin g Curr ent RCD Loo p Resis t ance RCD Earth Resi s tance Universal Cable
Probe Test Lead and Earth Rod Phase Ro ta t ion Universal Cable or Three-Phase CableFuse , Fau l t , Conduc to r Trac ing Universal Cable
Locator Power, cos , Energy Universal CableH a r m o n i c s
Standard-range current Clamp
True RMS Current Standard-range curr. Clamp or Low-range curr. ClampVar i s to r Overvo l t age Dev ice Universal CableBreakdown Vol tage Vol t age Logg ing Universal Cable
S a v e 3 0 % o f
y o u r t i m e a n d
b e
c o m p e t i t i
v e.
U s e r
f r i e n d l y T h e E u r o
- L i n k P r o d i s t i n
c t i o n s
Eurotest 61557
START
-
8/12/2019 MI 2086 87 Euro Instaltest
6/6
Order No . MI 2087 ST Order No . MI 2086 ST Order No . MI 2086 EU
Ins ta l t e s t Standard Set Euro tes t Standard Set Euro tes t Euro Set
ORDERING INFORMA TION Euro test 61557 Euro Set Euro test 61557
Standard Set Instal test 61557
Standard Set Ord er No . MI 2086 EU MI 2086 ST MI 2087 ST
Scope o f supp ly Plug Commander Universal test cable 3 1.5 m Low-range Clamp 1 A/1 mA
Probe test lead 4 m Alligator clip
Test tip (blue) Test tip (black) RS232 cable
PC SW Euro Link - Pro (for Windows 95/98/2000/NT/XP) PC SW Euro Link - St (for Windows 95/98/2000/NT/XP)
PC SW Instal Link (for Windows 95/98/2000/NT/XP) Neck and back belts Soft carrying bag
Instruction manual Handbook Measurements on electric installationsin theory and practice
Declaration of conformity Production verification data Declaration of warranty
Optional accessor ies Tip Commander Order No. A 1002 Fuse / fault / cable Locator Order No. A 1005 LUX meter probe Order No. A 1102
Probe test lead 4 m Order No. A 1012 Earth test set 20 m Order No . S 2001 General cable 4 1 m H test lead 20 m S test lead 20 m ES test lead 4.5 m E test lead 4.5 m Earth test rod 4pcs Small soft carrying bag Earth test set 50 m Order No . S 2002 General cable 4 1 m H test lead 50 m vound up on spool support S test lead 50 m vound up on spool support ES test lead 4.5 m E test lead 4.5 m Earth test rod 4pcs Soft carrying bag Low-range Clamp 1 A/1 mA Order No . A 1018 Standard-range Clamp 1 A/1 mA Order No. A 1019
Three phase cable Ref. No. A 1110 Three phase adapter Ref. No. A 1111
General cable 4 1 m Ref. No. A 1021
Measuring and Regulating EquipmentManufacturer, d.d.
Horjul 188, 1354 Horjul - SLOVENIA Tel.: +386 1 755 82 00; Fax: +386 1 754 92 26Internet: http://www.metrel.si; E-mail: [email protected]