Metro Wastewater Reclamation District

Digester ComplexWhat works and what doesn’t.

Page 2: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

• Load - Design• Configuration• Feed/Recirculation• Effluent• Gas system• Gas mixing

• Digester #4 modifications

• Strategy, feed, foam• Construction effects• Digester upsets• What works and what

doesn,t

Page 3: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Plant Load 2002 Averages

• Flow, 140 MGD

• Suspended Solids, 145 Tons/day

• BOD, 136 Tons/day

Page 4: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Design Criteria

Peak 2-week loads• TS, 202.5 Tons/day• VS, 155 Tons/day• 0.13 LbsVS/cuft/day• Hydraulic, 1.129

MGD

2002 load• TS, 162

Tons/day(80%)• VS, 131

Tons/day(85%)• 0.12 #VS/cf/d (92%)• .915 MGD (81%)

Page 5: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

January 2003

Digester data• VS 194 Tons/D (max)• VS 81 Tons/D (min)• 0.176 #VS/cf/d (max)• 0.064 #VS/cf/d (min)• Effects of varying

digester feed rate.

Page 6: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

60

80

100

120

140

160

180

SHT#1 in Dig Complex Dewater

Tons/day

Primary SolidsSecondary SolidsDig Solids inDig Solids out

Page 7: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Sludge Holding Tank #1• Feed tank for digesters• Capacity, 382,000 gals• 4 progressive cavity

pumps @ 450 gpm ea.

Page 8: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Sludge Holding Tanks 2 and 3

• De-water and future feed

• capacity 1,500,000 gals each

• 4 disc-flo/4 PC pumps

Page 9: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Anaerobic Digesters• 10 digesters• Capacity, 1,650,000

gals each.@ 28 ft operating level (summer)

• 1,472,000 gals each @ 25 ft (winter)

Page 10: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Typical Digester Gas System

Flame Traps Vent PRV’sTo Digester Gas Header

Page 11: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

• Digesters feed is sequenced

• Feed volume by set point

• Feed rate; manual flow set point or auto flow by SHT level

• Feeding is continuos 24 hr/d

Page 12: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester ComplexSludge Holding Tank #1

Raw Sludge Flow

Digester #9

Electric valves

Valve opens – sludge flowinto feed box

Page 13: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester ComplexDigester

Recirculation pump

Sludge feed enters through feed pipe that opens to atmosphere. The raw sludge blends withheated recirculated digester contents.

Page 14: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Page 15: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Page 16: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Page 17: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Page 18: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

• Digester effluent is withdrawn through a snorkel

• Snorkels can rotate 90 degrees

• Snorkels can be adjusted to control liquid level of digester

• Snorkels plug often

Page 19: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester ComplexDigester effluent is withdrawn through a snorkel.

The snorkel can rotate 90 degrees using a rotary joint. The digester liquid level can beadjusted between 17 – 31 feet. This allows for seasonal level control.

Page 20: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Page 21: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Page 22: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

• Atari gas mixing system

• Gas bubble mixing

• Uses bubble cannons

• Gas compressor

• Uses digester gas for bubble generation

Page 23: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Page 24: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Page 25: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Page 26: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Gas mixing effects

• Digester contents expands

• Contents specific gravity less than water

• Entrained gas in contents causes pumping problems

• Can generate foam

Page 27: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Operational Precautions

• Digester contents can expand 2 - 3 feet in depth

• Standard centrifugal pumps are not effective moving this liquid

• Gas compressor piping critical

Page 28: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Original gas mixer piping configuration

Flame trap

To gas system

Gas cannonsGas mixer

Page 29: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Page 30: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

When foam enters the gas system the flame traps become plugged.This prevents pressure build-up within digester from exiting.If pressure is not relieved by some device, auto or manually,Structural damage will occur.

Page 31: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Digester #4 Modifications

• Roof

• Gas compressor

• Foam trough

• Foam suppression

• Foam detection and alarm

• Pressure relief manhole

Page 32: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Page 33: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Re-designed gas mixer piping configuration

Separate withdrawal pipes

To gas system To gas system

Page 34: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Page 35: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester ComplexPWC spray Foam trough

Effluent

Gas system and compressor

Page 36: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Page 37: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Page 38: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester ComplexDigester Radar

Capacitance probeRadar sees top of foam High level alarm

Liquid level transmitter Digester contents Foam

Page 39: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Page 40: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester ComplexPressure Relief Manhole CoverRelief range: 16 – 18 inches of water column (.42 - .47 psi)Digester roof: 7850 ft2 = 1,130,400 in2 X .45 psi =254.34 Tons of upward forceDigester roof weight approx. 350 TonsFoam can exit without cracking the roof

Page 41: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Page 42: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Foam Strategy

• Lower digester levels to 25 feet - 6 feet headspace

• Control digester feed to meet 15 day SRT

• Pump foam out of digester to sludge holding tank

• Deal with foam in sludge holding tank

Page 43: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Page 44: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Page 45: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Digester Feed Strategy

• Maintain constant flow rate

• Do not use SHT level as a pump control

• Control WAS solids / primary solids ratio

• Maintain continuos de-watering operations

• Maintain continuos even digester effluent flow

Page 46: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Foam Pumping Strategy

• Find a pump that will pump foam - a double diaphragm air actuated works well

• Pump foam to SHT and de-water

• Pump foam to digester #4 - use suppression equipment

• Pump foam back into itself

Page 47: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Page 48: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Page 49: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Page 50: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Aggressive Construction Schedule

• Construction caused process interruptions

• Holding solids back in process areas

• Backing up digestion process

• Increases load to digesters

• Causes overload foaming (upset foam)

• Backed up secondary Nocardia foam

Page 51: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Page 52: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Upset Approach

• Stop all scheduled process interruptions

• Control digester feed rate

• Control WAS / Primary solids ratio

• Chlorinate RAS to control Nocardia

• Clean up mess daily until process stable

Page 53: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Page 54: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Page 55: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Page 56: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Page 57: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Page 58: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Page 59: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

Page 60: Metro Wastewater Reclamation District Digester Complex What works and what doesnt

MWRD Digester Complex

What Works• WAS/PRI solids

control• Digester temperature

control• Steady continuos

digester flow • Pressure relief

manholes

What Doesn’t• Too much WAS not

enough Primary• 1 degree F swing/24Hr

more than 5 days• Too many process

interruptions• No pressure relief