1 Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note Document Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Related Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Related Concepts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Communications Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Windows 2000 Network and Dial-Up Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Windows XP Network Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Detailed Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Direct Serial Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Direct Serial Communications Checklist Windows 2000 or Windows XP Operating Systems 6 Adding a Null Modem Serial Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Making a New Direct Serial Connection Using Windows 2000 Operating Systems . . . . . . 13 Making a New Direct Serial Connection Using Windows XP Operating Systems . . . . . . . . 16 Completing a New Direct Serial Connection Using Windows 2000 or Windows XP Operating Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Dial-Up Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Dial-Up (Modem) Communications Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Adding a Modem . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Making a New Dial-Up Connection Using Windows 2000 Operating Systems . . . . . . . . . . 32 Making a New Dial-Up Connection Using Windows XP Operating Systems . . . . . . . . . . . . 35 Completing a New Dial-Up Connection Using Windows 2000 or Windows XP Operating Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Enabling Communication with Multiple Internet Addresses . . . . . . . . . . . . . . . . . . . . . . . . . 43 Establishing the Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Error 733 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Error 777 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note Code No. LIT-1201639 Software Release 4.1 Issued October 6, 2008 Supersedes March 17, 2008

Upload: networkingcentral

Post on 15-May-2015

3.171 views

Category:

Documents


4 download

TRANSCRIPT

Page 1: Metasys® System Extended Architecture Direct Connection and

Metasys® System Extended Architecture Direct Connection and Dial-Up ConnectionApplication Note Code No. LIT-1201639

Software Release 4.1 Issued October 6, 2008

Supersedes March 17, 2008

Document Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Related Documentation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Related Concepts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Communications Setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Windows 2000 Network and Dial-Up Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Windows XP Network Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Detailed Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Direct Serial Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Direct Serial Communications Checklist Windows 2000 or Windows XP Operating Systems 6

Adding a Null Modem Serial Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Making a New Direct Serial Connection Using Windows 2000 Operating Systems . . . . . . 13

Making a New Direct Serial Connection Using Windows XP Operating Systems . . . . . . . . 16

Completing a New Direct Serial Connection Using Windows 2000 or Windows XP Operating Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Dial-Up Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Dial-Up (Modem) Communications Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Adding a Modem . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

Making a New Dial-Up Connection Using Windows 2000 Operating Systems . . . . . . . . . . 32

Making a New Dial-Up Connection Using Windows XP Operating Systems. . . . . . . . . . . . 35

Completing a New Dial-Up Connection Using Windows 2000 or Windows XP Operating Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

Enabling Communication with Multiple Internet Addresses . . . . . . . . . . . . . . . . . . . . . . . . . 43

Establishing the Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

Error 733 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

Error 777 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

1Metasys® System Extended Architecture Direct Connection and Dial-UpConnection Application Note

Page 2: Metasys® System Extended Architecture Direct Connection and

Username or Password Not Accepted. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note2

Page 3: Metasys® System Extended Architecture Direct Connection and

Metasys® System Extended Architecture Direct Connection and Dial-Up ConnectionApplication Note

Document IntroductionThis document provides the prerequisites, guidelines, and instructions for establishing direct serial connections and dial-up modem connections between a service person’s laptop computer running Windows® 2000 or Windows XP® Operating Systems (OSs) and one of the following devices:

• Network Automation Engine (NAE)

• Network Integration Engine (NIE)

• Application and Data Server (ADS)

• Extended Application and Data Server (ADX)

The computer with a Web browser that you are connecting to an NAE or NIE can reside on an ADS or an ADX, but we recommend that the computer with a Web browser be a separate computer to achieve optimal performance from the ADS/ADX.

The information in this document is also useful when troubleshooting direct serial connections and dial-up modem connections in Metasys® system extended architecture solutions.

Related DocumentationSee Table 1 for sources of further information on related topics.Table 1: Related DocumentationFor Information On See Document LIT or Part NumberUnderstanding Metasys System Extended Architecture

Metasys System Extended Architecture Overview Technical Bulletin

LIT-1201527

Understanding Network and Information Technology Requirements for Metasys System Extended Architecture

Network and Information Technology Considerations Technical Bulletin

LIT-1201578

Configuring and Troubleshooting an NAE45, NAE55, or NIE

NAE Commissioning Guide LIT-1201519

Configuring and Troubleshooting an ADS

ADS Commissioning Guide LIT-1201645

Reducing the Download Time After Establishing a Connection

Metasys System Extended Architecture Remote Access Installation Instructions

LIT-1201691

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note 1

Page 4: Metasys® System Extended Architecture Direct Connection and

Related ConceptsYou must set the communications parameters before configuring for a connection. See the Communications Setup section in this document.

Direct serial connection, also called direct connect, is a connection made from a computer to another computer or some other device (such as an NAE or NIE) using a null modem cable connected from the serial port on the computer to a serial port on the other computer or device. See the Direct Serial Connection section in this document. Use a direct serial connection for troubleshooting, support, or to obtain information in any of the following circumstances:

• There is no Local Area Network (LAN) or cable modem to use for a connection with the NAE/NIE or ADS/ADX.

• There is a firewall blocking the user from connecting to the NAE/NIE or ADS/ADX.

In a dial-up connection, a computer uses a modem to call and connect to another computer or some other device (such as an NAE or NIE). You must connect the NAE or NIE to a phone line. An example application for a dial-up connection is monitoring a remote site with a computer. See the Dial-Up Connection section in this document. Use a dial-up connection for troubleshooting, support, or to obtain information in any of the following circumstances:

• There is no ADS/ADX.

• The ADS/ADX is located in another part of the building.

• You cannot connect from the Web browser.

Communications SetupThis document only covers the setup for the computer. You must also set up the other devices to which the computer connects. For performance reasons, the external modem Universal Serial Bus (USB) driver is not loaded as a default. For security reasons, Dial In capability is not enabled by default. To successfully configure a direct serial or dial-up connection, you must set up the communications for each device.

The following documents cover how to set up the NAE, NIE, or ADS:

• Establishing the NAE Network Parameters and Establishing the NAE Direct-Connect and Modem Parameters sections of the NAE Commissioning Guide (LIT-1201519)

• Configuring an ADS/ADX to Accept Dial-Up Connections section of the ADS Commissioning Guide (LIT-1201645).

For direct connect communications, you must use identical settings for each NAE or NIE.

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note2

Page 5: Metasys® System Extended Architecture Direct Connection and

For dial-up communications, you must also use identical settings for each NAE or NIE; however, you must either set up a different phone number for each connection when configuring the computer, or you can change the phone number each time you connect to a different NAE/NIE.

Windows 2000 Network and Dial-Up ConnectionsThe Network and Dial-Up Connections feature in the Windows™ 2000 Operating System (OS) allows remote access to other computers and devices. To access this folder, open the Control Panel and double-click the Network and Dial-Up Connections icon.

Windows XP Network Connections

The Network Connections feature in the Windows™ XP OS allows remote access to other computers and devices. To access this folder, open the Control Panel and double-click the Network Connections icon in Classic view or Network and Internet Connections icon in Category view.

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note 3

Page 6: Metasys® System Extended Architecture Direct Connection and

ompleted

Detailed Procedures

Direct Serial ConnectionFor the Metasys system extended architecture, connect a serial port on the computer to the Serial A RS-232 port on the NAE or NIE using a null modem cable. See the Wiring section of the NAE55/NIE55 Installation Instructions (Part No. 24-10051-0) for information on the physical connections.

Direct Serial Communications Checklist Windows 2000 or Windows XP Operating Systems

The setup of communications between a computer and an external device is a multistep process. Table 2 is a guide to verify that all steps required for successful communications using a direct serial connection are complete.

Adding a Null Modem Serial Cable

To add a null modem serial cable:

1. On the Windows Start menu, click Settings > Control Panel. The Control Panel screen appears.

2. Double-click the Phone And Modem Options icon. (In the Windows XP operating system, click the Printers and Other Hardware icon if you are using Category view.) The Phone And Modem Options screen appears.

Note: In a new Windows 2000 OS installation, a screen may appear before the Phone And Modems Options screen, prompting you to enter location information such as the local area code and the number to dial for an outside line. Complete the information on the screen and click OK. This information is stored as a new location in the Dialing Rules tab of the Phone And Modem Options screen. Continue to Step 3.

Table 2: Direct Serial Communications Checklist Step Task C1 Verify that the null modem serial cable is installed. On the Windows Start menu, select

Settings > Control Panel. Double-click the Phone And Modem Options icon. (In Windows XP OS, click the Printers and Other Hardware icon if you are using Category view.) If Communications cable between two computers is not on the Modems tab of the Phone And Modem Options screen, go to the Adding a Null Modem Serial Cable section in this document.

2 Make a new direct serial connection. See the Making a New Direct Serial Connection Using Windows 2000 Operating Systems section or the Making a New Direct Serial Connection Using Windows XP Operating Systems section in this document.

3 To continue by generating databases for NAE/NIEs, refer to the NAE Commissioning Guide (LIT-1201519).

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note4

Page 7: Metasys® System Extended Architecture Direct Connection and

3. Click the Modems tab (Figure 1). If a null modem serial connection already exists, it appears here, listed as Communications cable between two computers. Click Cancel and continue to the Making a New Direct Serial Connection Using Windows 2000 Operating Systems section or the Making a New Direct Serial Connection Using Windows XP Operating Systems section. Otherwise, continue with Step 4.

4. Click Add. The Install New Modem screen appears (Figure 2).

Figure 1: Modems Tab - Phone And Modem Options Screen

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note 5

Page 8: Metasys® System Extended Architecture Direct Connection and

5. Check the Don’t detect my modem; I will select it from a list check box. Click Next. The next Install New Modem screen appears (Figure 3).

Figure 2: Install New Modem Screen

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note6

Page 9: Metasys® System Extended Architecture Direct Connection and

6. In the Manufacturers list, check [Standard Modem Types]. In the Models list, check Communications cable between two computers. Click Next. The next Install New Modem screen appears (Figure 4).

Figure 3: Install New Modem Screen - Select Manufacturer/Model

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note 7

Page 10: Metasys® System Extended Architecture Direct Connection and

7. Select the port where the null modem serial cable is connected. Click Next. The final Install New Modem screen appears (Figure 5).

Figure 4: Install New Modem Screen - Select Port

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note8

Page 11: Metasys® System Extended Architecture Direct Connection and

8. Click Finish. The Phone And Modem Options screen reappears with the completed null modem serial cable installation (Figure 6).

Figure 5: Install New Modem Screen - Installation Finished

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note 9

Page 12: Metasys® System Extended Architecture Direct Connection and

9. If the communications cable is not automatically selected, select it. Click OK.

10. Close the Control Panel screen.

Go to the Making a New Direct Serial Connection Using Windows 2000 Operating Systems section or the Making a New Direct Serial Connection Using Windows XP Operating Systems section.

Figure 6: Phone And Modem Options Screen - Installation Complete

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note10

Page 13: Metasys® System Extended Architecture Direct Connection and

Making a New Direct Serial Connection Using Windows 2000 Operating Systems

Perform the tasks in this section for the Windows 2000 Operating System (OS). Then follow the instructions in the Completing a New Direct Serial Connection Using Windows 2000 or Windows XP Operating Systems section.

To make a new direct serial connection using Windows 2000 OS:

1. On the Windows Start menu, click Settings > Control Panel. The Control Panel screen appears.

2. Double-click the Network and Dial-Up Connections icon. The Network and Dial-Up Connections screen appears.

3. Select Make New Connection. The Network Connection Wizard Welcome screen appears.

4. Click Next. The Type of Connection screen appears (Figure 7).

5. Select Connect directly to another computer. Click Next. The Host or Guest screen appears (Figure 8).

Figure 7: Type of Connection Screen

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note 11

Page 14: Metasys® System Extended Architecture Direct Connection and

6. Click Guest. Click Next. The Select a Device screen appears (Figure 9).

7. Select Communications cable between two computers from the drop-down menu. Click Next. The Connection Availability screen appears (Figure 10).

Figure 8: Host or Guest Screen

Figure 9: Select a Device Screen

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note12

Page 15: Metasys® System Extended Architecture Direct Connection and

8. Click the appropriate option. Click Next. The Finished screen appears (Figure 11).

9. Enter a name for the new connection entry. Click Finish. Continue with the Completing a New Direct Serial Connection Using Windows 2000 or Windows XP Operating Systems section.

Figure 10: Connection Availability Screen

Figure 11: Finished Screen

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note 13

Page 16: Metasys® System Extended Architecture Direct Connection and

Making a New Direct Serial Connection Using Windows XP Operating Systems

Perform the tasks in this section for the Windows XP operating system. Then follow the instructions in the Completing a New Direct Serial Connection Using Windows 2000 or Windows XP Operating Systems section.

To make a new direct serial connection using Windows XP Operating Systems:

1. On the Windows Start menu, click Settings > Control Panel. The Control Panel screen appears.

2. Double-click the Network Connections icon in Classic view or Network and Internet Connections icon in Category view.

3. Select create a new connection. The Network Connection Wizard Welcome screen appears. Click Next. The Network Connection Type screen appears (Figure 12).

4. Click Set up an advanced connection. Click Next. The Advanced Connection Options screen appears (Figure 13).

Figure 12: Network Connection Type Screen

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note14

Page 17: Metasys® System Extended Architecture Direct Connection and

5. Click Connect directly to another computer. Click Next. The Host or Guest screen appears (Figure 14).

6. Click Guest. Click Next. The Connection Name screen appears (Figure 15).

Figure 13: Advanced Connection Options Screen

Figure 14: Host or Guest Screen

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note 15

Page 18: Metasys® System Extended Architecture Direct Connection and

7. Enter the name for the new connection. Click Next. The Select a Device screen appears (Figure 16).

8. Click Communications cable between two computers (COM1). Click Next. The Completing the New Connection Wizard screen appears with the name you entered for the new connection (Figure 17).

Figure 15: Connection Name Screen

Figure 16: Select a Device Screen

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note16

Page 19: Metasys® System Extended Architecture Direct Connection and

9. Click Finish. For some network configurations, a warning screen appears (Figure 18) after completing the Network Connection Wizard. Click OK .

Continue with the Completing a New Direct Serial Connection Using Windows 2000 or Windows XP Operating Systems section.

Figure 17: Completing the New Connection Wizard Screen

Figure 18: Warning Screen

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note 17

Page 20: Metasys® System Extended Architecture Direct Connection and

Completing a New Direct Serial Connection Using Windows 2000 or Windows XP Operating Systems

Complete the Network Connection Wizard before proceeding. See the Making a New Direct Serial Connection Using Windows 2000 Operating Systems section or the Making a New Direct Serial Connection Using Windows XP Operating Systems section.

To complete a new direct serial connection using Windows 2000 or Windows XP Operating Systems:

1. When the Connect screen appears (Figure 19), click Properties.

The Connection Properties screen appears (Figure 20), indicating Direct Connection in the title bar.

Figure 19: Connect Screen

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note18

Page 21: Metasys® System Extended Architecture Direct Connection and

2. On the General tab, click Configure. The Modem Configuration screen appears (Figure 21).

Figure 20: Connection Properties Screen

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note 19

Page 22: Metasys® System Extended Architecture Direct Connection and

3. In the Maximum speed (bps) drop-down list box, click the speed of the NAE/NIE port to which the computer is connecting.

Note: Use Serial A port on the NAE/NIE for direct serial connections. The default port speed for Serial A port is 115,200 bits per second (bps).

4. In the Hardware features section, verify that the Enable hardware flow control check box is the only check box selected (Figure 21). Click OK. The Connection Properties screen returns (Figure 20).

Figure 21: Modem Configuration Screen

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note20

Page 23: Metasys® System Extended Architecture Direct Connection and

5. Click the Networking tab (Figure 22).

6. In the Components checked are used by this connection list, clear all check boxes except the Internet Protocol (TCP/IP) check box. Click OK. The Connect screen returns (Figure 19).

Note: The check boxes for some components may appear shaded. These check boxes are unavailable and cannot be cleared.

7. Click Cancel. The new direct serial connection is complete.

Go to the Establishing the Connection section.

Figure 22: Connection Properties Screen - Networking Tab

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note 21

Page 24: Metasys® System Extended Architecture Direct Connection and

ompleted

Dial-Up ConnectionFor the Metasys system extended architecture, you can use the following dial-up connections:

• External Modem - Connect a supported external Universal Serial Bus (USB) modem to the USB A port on the NAE/NIE or connect an external USB modem to the USB port on the ADS/ADX.

• Internal Modem - Connect a phone line to the Modem RJ-11 port on the NAE/NIE.

Refer to the Wiring section of the NAE55/NIE Installation Instructions (Part No. 24-10051-0) or NAE35/NAE45 Installation Instructions(Part No. 24-10050-6) for information on these connections.

Dial-Up (Modem) Communications Checklist

The setup of dial-up (modem) communications on a computer is a multistep process. Table 3 is a guide to verify that all steps required for successful communications using a dial-up connection are complete.

Adding a ModemIf available, follow the manufacturer’s instructions to add a modem. Otherwise, use the following instructions.

To add a modem:

1. On the Windows Start menu, click Settings > Control Panel.

2. Double-click the Phone And Modem Options icon. (In the Windows XP operating system, click the Printers and Other Hardware icon if you are using Category view.) The Phone And Modem Options screen appears.

Table 3: Dial-Up (Modem) Communications ChecklistStep Task C1 Verify that the modem you are using is installed. On the Windows Start menu, click

Settings > Control Panel. Double-click the Phone And Modem Options icon. (In Windows XP OS, click the Printers and Other Hardware icon if you are using Category view.) If the modem you want to use is not on the Modems tab of the Phone And Modem Options screen, go to Adding a Modem in this document.

2 Make a new dial-up connection. Each site to which you want to establish a dial-up connection must have its own connection. See the Making a New Dial-Up Connection Using Windows 2000 Operating Systems section or the Making a New Dial-Up Connection Using Windows XP Operating Systems section in this document.

3 To continue by generating databases for NAE/NIEs, refer to the Configuring the NAE55 Technical Bulletin (LIT-1201519).

4 Complete the connection. See the Making a New Direct Serial Connection Using Windows XP Operating Systems section in this document.

5 Establish the connection. See the Establishing the Connection section in this document.

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note22

Page 25: Metasys® System Extended Architecture Direct Connection and

3. Click the Modems tab (Figure 23).

Note: If a modem is already installed, it appears here. Click Cancel and continue to the Making a New Dial-Up Connection Using Windows 2000 Operating Systems or the Making a New Dial-Up Connection Using Windows XP Operating Systems section in this document. Otherwise, go to Step 4.

4. Click Add. The Install New Modem screen appears (Figure 24).

Figure 23: Phone And Modem Options Screen - Modems Tab

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note 23

Page 26: Metasys® System Extended Architecture Direct Connection and

5. Choose one of the following options:

• To allow Windows OS to detect your modem automatically, click Next (this process may require a few minutes). Windows OS detects and lists your modem (Figure 25). Continue to Step 6.

• To select the modem manually, select the Don’t detect my modem; I will select it from a list check box. Click Next. The Install New Modem screen appears (Figure 26). Continue to Step 7.

Figure 24: Install New Modem Screen

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note24

Page 27: Metasys® System Extended Architecture Direct Connection and

6. In the Detected modems list (Figure 25), verify that the manufacturer and model are correct.

a. If the information is correct, click Next. The final Install New Modem screen appears (Figure 28). Continue to Step 9.

b. If the information is not correct or the modem is indicated as Unknown Modem, click Change. The Install New Modem screen appears (Figure 26). Continue to Step 7.

Figure 25: Install New Modem Screen - Modem Detection

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note 25

Page 28: Metasys® System Extended Architecture Direct Connection and

7. Select the Manufacturer and Model of your modem. Click OK.

Figure 26: Install New Modem Screen

Figure 27: Install New Modem Screen - Select Port

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note26

Page 29: Metasys® System Extended Architecture Direct Connection and

8. Choose the appropriate option (Figure 27):

• If you allowed Windows OS to automatically detect your modem, the Install New Modem screen reappears with the corrected modem information. Click Next. The final Install New Modem screen appears (Figure 28). Continue to Step 9.

• If you selected the modem manually, the Install New Modem screen appears prompting you to select the port for the modem. Click the appropriate port and click Next. The final Install New Modem screen appears (Figure 28). Continue to Step 9.

9. Click Finish. The Phone And Modem Options screen reappears with the completed modem installation (Figure 29).

Figure 28: Install New Modem Screen - Installation Finished

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note 27

Page 30: Metasys® System Extended Architecture Direct Connection and

10. Click Properties. The Modem Properties screen appears (Figure 30).

Figure 29: Phone And Modem Options Screen - Installation Complete

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note28

Page 31: Metasys® System Extended Architecture Direct Connection and

11. In the Maximum Port Speed list, click the speed of the NAE/NIE port to which the computer is connecting.

Note: The default port speed for the NAE/NIE is 115,200 bps. Use this port speed for communication via a USB port. Use 57,600 bps as the maximum port speed if you are connecting to an NAE/NIE using a 56k modem. (Remember to configure the NAE/NIE to communicate at 57,600 bps for use with a 56k modem.)

12. Click OK. The Phone And Modem Options screen reappears (Figure 29).

13. Click OK. The Control Panel screen reappears.

14. Close the Control Panel screen.

Go to the Making a New Dial-Up Connection Using Windows 2000 Operating Systems section or the Making a New Dial-Up Connection Using Windows XP Operating Systems section in this document.

Figure 30: Modem Properties Screen

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note 29

Page 32: Metasys® System Extended Architecture Direct Connection and

Making a New Dial-Up Connection Using Windows 2000 Operating SystemsPerform the tasks in this section. Then follow the instructions in the Completing a New Dial-Up Connection Using Windows 2000 or Windows XP Operating Systems section.

To make a new dial-up connection using Windows 2000 Operating System:

1. On the Windows Start menu, click Settings > Control Panel. The Control Panel screen appears.

2. Double-click the Network and Dial-Up Connections icon. The Network and Dial-Up Connections screen appears.

3. Select Make New Connection. The Network Connection Wizard Welcome screen appears. Click Next. The Type of Connection screen appears (Figure 31).

4. Click Dial-up to private network. Click Next. The Phone Number to Dial screen appears (Figure 32).

Note: If more than one dial-up device is installed on the computer, the Select a Device screen appears. Select the check box for the appropriate device and click Next. Continue to Step 5.

Figure 31: Type of Connection Screen

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note30

Page 33: Metasys® System Extended Architecture Direct Connection and

5. Type the phone number for the computer to dial. To have a computer determine how to dial from different locations, select the Use dialing rules check box. Click Next. The Connection Availability screen appears (Figure 33).

Note: The Dialing Rules feature allows you to create rules for dialing from different locations. Dialing Rules can include options such as dialing 9 for an outside line. To set up Dialing Rules, open the Phone And Modem Options screen as described in the procedure. Use the Dialing Rules tab to set rules for different locations.

Figure 32: Phone Number to Dial Screen

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note 31

Page 34: Metasys® System Extended Architecture Direct Connection and

6. Click the appropriate option. Click Next. The Finished screen appears with the name you entered for the new connection entry (Figure 34).

7. Click Finish. Continue with the Completing a New Dial-Up Connection Using Windows 2000 or Windows XP Operating Systems section.

Figure 33: Connection Availability Screen

Figure 34: Finished Screen

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note32

Page 35: Metasys® System Extended Architecture Direct Connection and

Making a New Dial-Up Connection Using Windows XP Operating SystemsPerform the tasks in this section. Then follow the instructions in the Completing a New Dial-Up Connection Using Windows 2000 or Windows XP Operating Systems section.

To make a new dial-up connection using Windows XP OS:

1. On the Windows Start menu, click Settings > Control Panel. The Control Panel screen appears.

2. Double-click the Network Connections icon in Classic view or Network and Internet Connections icon in Category view, then click on the network Connections icon. The Network Connections screen appears.

3. Select create a new connection. The Network Connection Wizard Welcome screen appears.

4. Click Next. The Network Connection Type screen appears (Figure 35).

5. Click Connect to the network at my workplace. Click Next. The Network Connection screen appears (Figure 36).

Figure 35: Network Connection Type Screen

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note 33

Page 36: Metasys® System Extended Architecture Direct Connection and

6. Click Dial-up connection. Click Next. The Connection Name screen appears (Figure 37).

7. Enter a name for the new connection. Click Next. The Phone Number to Dial screen appears (Figure 38).

Figure 36: Network Connection Screen

Figure 37: Connection Name Screen

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note34

Page 37: Metasys® System Extended Architecture Direct Connection and

8. Enter a phone number (without hyphens) to dial for the new connection. Click Next. The Completing the New Connection Wizard screen appears (Figure 39).

Figure 38: Phone Number to Dial Screen

Figure 39: Completing the New Connection Wizard Screen

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note 35

Page 38: Metasys® System Extended Architecture Direct Connection and

9. Click Finish. For some network configurations, a warning screen appears (Figure 40) after completing the Network Connection Wizard. Click OK and continue to Completing a New Direct Serial Connection Using Windows 2000 or Windows XP Operating Systems.

Continue with the Completing a New Dial-Up Connection Using Windows 2000 or Windows XP Operating Systems section.

Figure 40: Warning Screen

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note36

Page 39: Metasys® System Extended Architecture Direct Connection and

Completing a New Dial-Up Connection Using Windows 2000 or Windows XP Operating Systems

Complete the Network Connection Wizard before proceeding. See the Making a New Dial-Up Connection Using Windows 2000 Operating Systems section or the Making a New Dial-Up Connection Using Windows XP Operating Systems section.

To complete the new dial-up connection:

1. When the Connect screen appears indicating the name of the new connection in the title bar (Figure 41), click Properties. The Connection Properties screen appears (Figure 42).

Note: Use the standard MetasysSysAgent username and its current password. The password is case sensitive. The default password for MetasysSysAgent is XMG3-Rel.1.

Figure 41: Connect Screen

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note 37

Page 40: Metasys® System Extended Architecture Direct Connection and

2. On the General tab, click Configure. The Modem Configuration screen appears (Figure 43).

Figure 42: Connection Properties Screen

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note38

Page 41: Metasys® System Extended Architecture Direct Connection and

3. In the Maximum speed list, select the speed of the NAE/NIE port to which the computer is connecting.

Note: The default port speed for the NAE/NIE is 115,200 bps. Use this port speed for communication via a USB port. Use 57,600 bps as the maximum port speed if you are connecting to an NAE/NIE using a 56k modem. (Remember to configure the NAE/NIE to communicate at 57,600 bps for use with a 56k modem.)

4. In the Hardware features section, clear the Enable modem compression check box (Figure 43). Click OK. The Connection Properties screen returns (Figure 42).

Figure 43: Modem Configuration Screen

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note 39

Page 42: Metasys® System Extended Architecture Direct Connection and

5. Click the Networking tab (Figure 44).

6. In the Components checked are used by this connection list, clear all check boxes except the Internet Protocol (TCP/IP) check box. Click OK. The Connect screen returns (Figure 41).

Note: The check boxes for some components may appear shaded. These check boxes are unavailable and cannot be cleared.

7. Click OK. The new dial-up connection is complete.

Go to the Enabling Communication with Multiple Internet Addresses section in this document.

Figure 44: Connection Properties Screen - Networking Tab

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note40

Page 43: Metasys® System Extended Architecture Direct Connection and

Enabling Communication with Multiple Internet AddressesTo enable the computer to communicate with multiple Internet addresses (other than the Metasys device):

1. On the Windows Start menu, click Settings > Control Panel. The Control Panel screen appears.

2. Double-click the Network And Dial-Up Connections icon. The Network And Dial-Up Connections screen appears (see Figure 45).

3. Double-click the modem used. The Connect Modem screen appears.

Figure 45: Network And Dial-Up Connections Screen

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note 41

Page 44: Metasys® System Extended Architecture Direct Connection and

4. Select Properties. The Modem Properties screen appears (see Figure 46).

Figure 46: Modem Properties Screen

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note42

Page 45: Metasys® System Extended Architecture Direct Connection and

5. On the Networking tab, click Properties (Figure 47). The Internet Protocol TCP/IP Properties screen appears (Figure 48).

Figure 47: Modem Properties Screen - Networking Tab

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note 43

Page 46: Metasys® System Extended Architecture Direct Connection and

6. Click the Advanced button. (See Figure 48.) The Advanced TCP/IP Properties screen appears. (See Figure 49.)

Figure 48: Internet Protocol (TCP/IP) Properties Screen

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note44

Page 47: Metasys® System Extended Architecture Direct Connection and

7. Clear the Use default gateway on remote network box (see Figure 49).

8. Click OK.

Go to the Establishing the Connection section in this document.

Figure 49: Advanced TCP/IP Settings Screen

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note 45

Page 48: Metasys® System Extended Architecture Direct Connection and

Establishing the Connection

If you are using a dial-up connection, check that the NAE/NIE is set for dial-up connections before you establish the connection. Refer to the NAE Commissioning Guide (LIT-1201519) or the NAE85/NIE85 Commissioning Guide (LIT-12011044) for details.

To establish the connection:

1. Change the NAE/NIE to enable and allow incoming connections on the modem used for the dial-up connection.

2. Reboot the NAE/NIE to load the USB drivers if the connection uses an external modem.

3. Double-click the icon on the desktop for the connection you created. If you did not create an icon on the desktop, access the icon in the Network and Dial-Up Connections (Windows 2000 OS) folder or the Network Connections (Windows XP OS) folder.

Use the following default user names and passwords to access the Metasys system:

Standard Access:

username: MetasysSysAgent

password: XMG3-Rel.1

Basic Access:

username: BasicSysAgent

password: XMG3-Bas1c

Note: The passwords are case sensitive.

Note: The Johnson Controls disclaimer statement appears the first time you log in.

Note: The Basic Access password is disabled by default and must be enabled before you use it to access the system.

IMPORTANT: The download process can take up to 1.5 hours. Use the Metasys Remote Access utility to reduce the time required for downloading. Refer to the Metasys System Extended Architecture Remote Access Installation Instructions (LIT-1201691) for more information.

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note46

Page 49: Metasys® System Extended Architecture Direct Connection and

4. Double-click the icon on the desktop for the connection you created and select Status (Figure 50).

If you did not create an icon on the desktop, browse to and double-click the icon in the Network and Dial-Up Connections (Windows 2000 OS) folder or the Network Connections (Windows XP OS) folder.

5. The Dialup to NAE Status dialog box appears (Figure 51).

Figure 50: Desktop Connection Icon

Figure 51: Dialup to NAE Status Dialog Box

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note47

Page 50: Metasys® System Extended Architecture Direct Connection and

6. On the Details tab, note the address in the Server IP address field (Figure 52).

7. Click Close.

8. Log on to the user interface of the NAE/NIE from your Web browser using the URL:

http://[insert IP address here]/Metasys/

Replace [insert IP address here] with the IP address found in Step 5.

Note: The dial-up connection does not automatically disconnect when you exit Metasys software. Close the connection with the disconnect command. See Figure 50.

Figure 52: Details Tab

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note48

Page 51: Metasys® System Extended Architecture Direct Connection and

TroubleshootingUse the information here to troubleshoot direct or dial-up connections. See Table 1 for documents that contain troubleshooting information for the NAE/NIE and ADS/ADX.

Error 733

See Table 4 for information on causes and resolution of this error.

Error 777

See Table 5 for information on causes and resolution of this error.

Table 4: Error 733 - PPP Control Protocol DisagreementWhen using this hardware...

This error results occurs because...

To resolve this error...

NAE/NIE IPS/IPX protocol is selected. Select a different communications protocol.

Figure 53: Error 733 - PPP Control Protocol Disagreement

Figure 54: Error 777 - Connection Device Out of Order

Metasys® System Extended Architecture Direct Connection and Dial-Up Connection Application Note 49

Page 52: Metasys® System Extended Architecture Direct Connection and

Username or Password Not Accepted

To correct this error, obtain a correct Metasys system username or password and repeat the login procedure.

Table 5: Error 777When using this hardware...

This error results occurs because...

To resolve this error...

NAE/NIE Maximum communication speed is set incorrectly.

Change the communication speed to match the correct setting for the modem used.

NAE/NIE The COM PORT setting is incorrect.

Select a different COM PORT.

Figure 55: Username or Password Not Accepted