MELSECNET/H Interface BoardUser's Manual (For SW0DNC-MNETH-B)

-Q80BD-J71LP21-25-Q80BD-J71LP21S-25-Q81BD-J71LP21-25-Q80BD-J71LP21G-Q80BD-J71BR11

Page 2: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are
Page 3: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

A - 1 A - 1

• SAFETY PRECAUTIONS • (Be sure to read these instructions before using the product.)

Before using this product, read this manual and the relevant manuals introduced in this manual carefully

and handle the product correctly with full attention to safety.

Note that these precautions apply only to this product. Refer to the user's manual of the CPU module for

safety precautions on programmable controller systems.

In this manual, the safety instructions are ranked as " WARNING " and " CAUTION".

WARNING

CAUTION

Indicates that incorrect handling may cause hazardous conditions, resulting in death or severe injury.

Indicates that incorrect handling may cause hazardous conditions, resulting in minor or moderate injury or property damage.

Note that failure to observe the ! CAUTION level instructions may also lead to serious results depending

on the circumstances.

Be sure to observe the instructions of both levels to ensure personal safety.

Please keep this manual in accessible place and be sure to forward it to the end user.

[Design Instructions]

! WARNING

• Make sure to see this manual for information about each station's operating status when a communication error occurs in the network. Erroneous outputs and malfunctions may result in serious accidents.

• If a coaxial cable is disconnected, this may destabilize the line, and a data link communication error may occur in multiple stations. Make sure to create an interlock circuit in the sequence program so that the system will operate safely even if the above error occurs. Failure to do so may result in a serous accident due to faulty output or malfunctions.

• Provide a safety circuit outside the programmable controller so that the entire system will operate on the safety side even when an error occurs with the personal computer. There is a risk of an accident due to faulty output or malfunctioning. (1) Construct circuits outside the programmable controller, including an emergency stop circuit,

protection circuit, interlock circuit for reciprocal operations such as forward and reverse, and interlock circuit for positioning high and low limits to prevent damage to the equipment.

(2) If the station in which the board is installed is disconnected from the data link due to a data link error, the data output from that station and written in other stations will remain the same as immediately before the error occurred in the data link. This data will be retained until the data link for that station is reopened (returned to system). Provide a mechanism to monitor the status of data link and handle errors for each station that is connected to the data link system.

Page 4: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

A - 2 A - 2

[Design Instructions]

! CAUTION

• Do not bunch the control wires or communication cables with the main circuit or power wires, or

install them close to each other.

They should be installed 100 mm (3.94 inch) or more from each other.

Not doing so could result in noise that would cause malfunctioning.

[Installation Instructions]

! CAUTION

• Use the board in an environment as described in the general specifications listed in this

operating manual.

If the board is used in an environment outside the ranges described in the general

specifications, it may result in an electric shock, fire, malfunctioning, damage to or deterioration

of the product.

• Be sure to shut off all phases of the external power supply used by the system before installing

or removing the board. If all power is not turned off, this will result in failure of the board or

malfunctioning.

• Install the board to a personal computer which is compliant with PCI standard or PCI Express R

standard (Refer to "Section 2.5 Operating Environment"). Failure to do so may cause a failure or

malfunction.

• Securely mount the board to the PCI slot of the mounting device.

If the board is not mounted correctly, this may lead to malfunctioning, failure or cause the board

to fall.

• Insert the communication cable securely into the board connector. After it has been inserted,

check to make sure that it is not being lifted up.

A faulty connection can lead to faulty input or output.

• When mounting the board, take care not to become injured by the components that are installed

or surrounding materials.

• Always make sure to touch the grounded metal to discharge the electricity charged in the body,

etc., before touching the board.

Failure to do so may cause a failure or malfunctions of the board.

• When installing the board, take care not to contact with other boards.

Page 5: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

A - 3 A - 3

[Wiring Instructions]

! WARNING

• Be sure to shut off all phases of the external power supply used by the system before

performing work such as installing the board and wiring.

If all power is not turned off, there is a risk of electric shock or damage to the product.

• When turning on the power and operating the module after having installed the board and doing

the wiring, always attach the cover for the device module in which the board is installed.

There is a risk of electric shock if the module cover is not attached.

! CAUTION • Properly solder the parts of a soldering-type coaxial cable connector. Incomplete soldering may

result in malfunction.

• Crimp the parts of a crimping-type coaxial cable connector with proper force at a proper position.

Failure to do so may cause drop of the cable or malfunction.

• For the communication cable, specialized skills and tools are required to connect the plug and

cable. The connector plug itself is a custom part.

When purchasing, consult your local Mitsubishi representative.

If the connection is incomplete, this can result in a short, fire or malfunction.

• Be sure to fix communication cables connecting to the board by placing them in the duct or

clamping them.

Cables not placed in the duct or without clamping may be hang freely and accidentally pulled,

which may cause damage to the board or cable, or malfunction due to bad cable contacts.

• When removing the cable from the board, do not pull the cable.

Pulling the cable that is still connected to the board may cause damage to the board or cable, or

malfunction due to bad cable contacts.

• Prevent foreign matter such as chips or wiring debris from getting on the board.

Failure to do so can result in fire, breakdowns or malfunction.

• Verify the rated voltage and pin assignment of the product and connect the external power

supply cable properly.

Connecting a power supply with a different voltage rating, imperfect cable crimping or faulty

wiring may cause a fire or failure.

• Use a specified tool for crimping of the cable and contacting pin. Imperfect crimping may cause

malfunction.

• Verify the pin assignment and fully insert the crimped contacting pin into the connector.

Imperfect insertion may cause failure or malfunction.

• Insert the wired external power supply cable into the external power supply cable connector until

a click is heard. Imperfect insertion may cause failure or malfunction.

• Keep the external power supply cable away from the main circuit cable, power cables and/or

load cables connected to other than programmable controllers. Ensure a distance of 100mm

(3.94 in.) between them. Failure to do so may result in malfunction due to noise, surge or

induction.

• Always ground the personal computer. Failure to do so may cause malfunction.

Page 6: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

A - 4 A - 4

[Startup/Maintenance Instructions]

! WARNING

• Do not attach or remove the communication cable while the power supply is on.

This may result in malfunctioning.

• Tighten the board fixing screws after turning off the power supply.

There is a risk of electric shock if the screws are tightened while power is on.

! CAUTION

• Thoroughly read the operating manual and carefully check to make sure everything is safe

before performing operations such as making changes to the program while the module is

operating, forced outputs, RUN, STOP and PAUSE.

Operation errors will result in damage to the equipment or accidents.

• Do not dismantle or rebuild the board.

This will result in breakdowns, malfunctioning, injury or fire.

• Be sure to shut off all phases of the external power supply used by the system before installing

or removing the board.

If all power is not turned off, this will result in failure of the board or malfunctioning.

• The board internal microprocessor reaches very high temperatures when it is running. Do not

touch it directly when replacing the board.

This will result in breakdowns, malfunctioning or injury.

• Always make sure to touch the grounded metal to discharge the electricity charged in the body,

etc., before touching the board.

Failure to do so may cause a failure or malfunctions of the board.

[Disposal Instructions]

! CAUTION

• When disposing of this product, treat it as industrial waste.

Page 7: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

A - 5 A - 5

• CONDITIONS OF USE FOR THE PRODUCT •

(1) Mitsubishi programmable controller ("the PRODUCT") shall be used in conditions;

i) where any problem, fault or failure occurring in the PRODUCT, if any, shall not lead to any major or

serious accident; and

ii) where the backup and fail-safe function are systematically or automatically provided outside of the

PRODUCT for the case of any problem, fault or failure occurring in the PRODUCT.

(2) The PRODUCT has been designed and manufactured for the purpose of being used in general

industries.

MITSUBISHI SHALL HAVE NO RESPONSIBILITY OR LIABILITY (INCLUDING, BUT NOT LIMITED

TO ANY AND ALL RESPONSIBILITY OR LIABILITY BASED ON CONTRACT, WARRANTY, TORT,

PRODUCT LIABILITY) FOR ANY INJURY OR DEATH TO PERSONS OR LOSS OR DAMAGE TO

PROPERTY CAUSED BY the PRODUCT THAT ARE OPERATED OR USED IN APPLICATION

NOT INTENDED OR EXCLUDED BY INSTRUCTIONS, PRECAUTIONS, OR WARNING

CONTAINED IN MITSUBISHI'S USER, INSTRUCTION AND/OR SAFETY MANUALS, TECHNICAL

BULLETINS AND GUIDELINES FOR the PRODUCT.

("Prohibited Application")

Prohibited Applications include, but not limited to, the use of the PRODUCT in;

Nuclear Power Plants and any other power plants operated by Power companies, and/or any other

cases in which the public could be affected if any problem or fault occurs in the PRODUCT.

Railway companies or Public service purposes, and/or any other cases in which establishment of a

special quality assurance system is required by the Purchaser or End User.

Aircraft or Aerospace, Medical applications, Train equipment, transport equipment such as Elevator

and Escalator, Incineration and Fuel devices, Vehicles, Manned transportation, Equipment for

Recreation and Amusement, and Safety devices, handling of Nuclear or Hazardous Materials or

Chemicals, Mining and Drilling, and/or other applications where there is a significant risk of injury to

the public or property.

Notwithstanding the above, restrictions Mitsubishi may in its sole discretion, authorize use of the

PRODUCT in one or more of the Prohibited Applications, provided that the usage of the PRODUCT is

limited only for the specific applications agreed to by Mitsubishi and provided further that no special

quality assurance or fail-safe, redundant or other safety features which exceed the general

specifications of the PRODUCTs are required. For details, please contact the Mitsubishi

representative in your region.

Page 8: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

A - 6 A - 6

REVISIONS

The manual number is given on the bottom left of the back cover.

Print Date Manual Number Revision

Nov., 2000 SH (NA)-080128-A First printing Mar., 2001 SH (NA)-080128-B Model addition

Q80BD-J71LP21G, Q80BD-J71LP21GE

Correction

Section 1.3, Appendix 3.1 Jun., 2001 SH (NA)-080128-C Correction

About the Generic Terms and Abbreviations, Section 1.2, Section 1.3, Section 2.5, Section 7.1, Section 7.1.1, Section 7.1.2, Section 7.4, Section 8.2.3, Section 9.1.2, Section 9.2, Section 10.3.2, Section 10.4, Appendix 3, Appendix 3.1

Addition

Section 10.8, Section 12.2, Chapter 13 Jan., 2002 SH (NA)-080128-D Correction

Section 2.5, Section 3.1, Section 3.2, Section 5.6, Section 9.1.2, Section 10.7, Section 12.2, Section 12.2.2

Addition

About the Generic Terms and Abbreviations, Sections 9.1.2, Chapter 13

Dec., 2002 SH (NA)-080128-E Correction

Safety Precautions, Section 8.2.3, Section 8.2.8, Section 8.3.3, Section 9.1.2, Chapter 10, Section 12.2, Appendix 3.1, Appendix 4.1, Appendix 4.2

Addition

Precautions for use, Generic Terms and Abbreviations, Section 1.2, Section 1.3, Section 2.5, Section 5.4.2, Section 7.1.1, Section 7.1.2, Section 7.2, Section 7.3, Section 8.1.1, Section 10.3, Chapter 13, Section 14.3, Section 14.3.1, Section 14.5.4, Section 14.6

May, 2004 SH (NA)-080128-F Correction

Safety Precautions, Precautions for use, Section 3.1, Section 3.2, Section 6.3.1, Section 8.2.5, Section 8.2.10, Section 12.2, Section 12.2.1, Section 12.2.2, Section 12.2.3, Section 12.3.3, Chapter 13, Section 14.4.4, Section 14.7, Appendix 5.1

Addition

Generic Terms and Abbreviations, Section 1.2, Section 1.3, Section 2.4, Section 2.5, Section 4.2.1, Section 5.2.1, Section 5.3, Section 5.4.3, Chapter 6, Section 6.3.6, Section 8.2.1, Section 8.2.3, Section 10.3, Section 10.3.3, Section 10.3.4, Section 10.8, Section 11.3, Chapter 12, Section 14.4, Section 14.5.5, Section 14.6, Appendix 3

Page 9: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

A - 7 A - 7

The manual number is given on the bottom left of the back cover.

Print Date Manual Number Revision

Dec., 2004 SH (NA)-080128-G Chapter numbers of 5 to 14 were changed to 6 to 15 respectively.

Correction

Precautions for use, Generic Terms and Abbreviations, Chapter 1, Section 1.1, Section 1.2, Section 1.3, Section 2.1, Section 2.4, Section 2.5, Section 3.2, Chapter 7, Section 7.1, Section 7.2.4, Section 9.2.2, Section 9.2.3, Section 9.2.5, Section 9.2.10, Section 9.2.11, Section 10.1.2, Section 10.2, Section 13.2.1, Section 15.4.3

Addition

Section 2.6, Chapter 5, Section 15.7 Jun., 2005 SH (NA)-080128-H Model addition

Q80BD-J71LP21S-25

Correction

SAFETY PRECAUTIONS, INTRODUCTION, Generic Terms and Abbreviations, Product List, Section 1.2, Section 2.1, Section 2.5, Section 3.2, Section 4.1, Section 6.1, Section 6.3, Section 6.4, Section 6.5, Section 6.6, Section 7.2.1, Section 8.1.2, Section 9.2.2, Section 9.2.6, Section 9.3.5, Section 11.4, Section 11.6, Section 12.3, Chapter 13, Chapter 14, Section 15.2, Section 15.4.4, Section 15.6, Section 15.7, Section 15.8, Appendix 4, Appendix 5

Addition

Section 6.4.4, Section 15.6, Appendix 4, Appendix 6.2 Jul.,2005 SH(NA)-080128-I Correction

Section 2.5, Appendix 6.2 Oct.,2005 SH(NA)-080128-J Correction

Section 2.5, Section 8.1.1, Section 8.1.2, Section 8.3, Section 9.1, Section 15.2

Mar., 2007 SH(NA)-080128-K Correction

Generic Terms and Abbreviations, Section 2.2.4, Section 2.5, Section 6.4.1, Section 6.4.2, Section 8.1.1, Section 8.1.2, Section 10.1.2, Section 10.2, Section 11.2, Section 11.6, Section 11.8, Section 15.4.5

Addition

Section 11.3.5, Section 11.3.6, Section 11.7 Oct., 2007 SH(NA)-080128-L Correction

Generic Terms and Abbreviations, Section 1.2, Section 1.3, Section 2.5, Chapter 5, Section 8.1.1, Section 8.3, Section 9.1, Chapter 14, Section 15.2, Section 15.3.1 Section 8.1.2 changed to Section 8.1.3

Addition

Section 8.1.2, Appendix 5 Jan., 2008 SH(NA)-080128-M Correction

Generic Terms and Abbreviations, Section 2.5, Section 6.5.1, Section 6.5.2, Section 6.5.3, Section 6.6.1, Section 6.6.2, Section 8.1.1, Section 8.1.3, Section 10.1.2, Section 10.2, Section 11.6, Section 11.7

Page 10: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

A - 8 A - 8

The manual number is given on the bottom left of the back cover.

Print Date Manual Number Revision

May, 2008 SH(NA)-080128-N Model addition

Q81BD-J71LP21-25

Correction

SAFETY PRECAUTIONS, Precautions for Use, INTRODUCTION, Generic Terms and Abbreviations, Product List, Section 1.2, Section 1.3, Section 2.1, Section 2.5, Section 3.1, Section 3.2, Section 6.3, Section 6.4.1, Section 6.4.3, Section 6.5.1, Section 6.5.2, Section 6.5.3, Section 6.6.1, Section 6.6.2, Section 8.1.1, Section 8.1.3, Section 8.2, Section 8.3, Section 9.1, Section 9.1.1, Section 9.2.2, Section 9.2.6, Section 10.1.2, Section 11.3, Section 15.2, Section 15.3, Section 15.4.4 Appendix 3 to 6 changed to Appendix 2 to 5

Addition

Appendix 5.4

Deletion

Appendix 2, Appendix 2.1

Jun., 2008 SH(NA)-080128-O Correction

Section 1.3, Section 2.5, Section 9.2.4, Section 15.4.4, Appendix 4.2

Oct., 2008 SH(NA)-080128-P Addition

Generic Terms and Abbreviations, Section 2.5, Section 10.1.2

Jul., 2009 SH(NA)-080128-Q Addition

Product List, Chapter 5, Appendix 4.1

Oct., 2009 SH(NA)-080128-R Addition

Section 8.1.3, Section 11.4, Section 13.3.4, Section 15.2

Correction

SAFETY PRECAUTIONS, Section 2.6, Section 4.1, Section 11.6, Section 11.7, Section 12.1.1, Section 13, Section 13.1, Section 14

Dec., 2010 SH(NA)-080128-T Correction

Section 2.5

Mar., 2011 SH(NA)-080128-U Addition

Appendix 2

Correction

Product List, Chapter 7, Section 9.2.2, Section 15.2, Appendix 1, Appendix 5.2 Appendix 3 to 6 changed to Appendix 4 to 7

May, 2011 SH(NA)-080128-V Correction

Precautions for Use, Chapter 8

Deletion

Section 8.3

Page 11: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

A - 9 A - 9

The manual number is given on the bottom left of the back cover.

Print Date Manual Number Revision

Sep., 2011 SH(NA)-080128-W Correction

SAFETY PRECAUTIONS, INTRODUCTION, Manuals, How to Use This Manual, Generic Terms and Abbreviations, Product List, Section 1.2, Section 2.1, Section 2.5, Section 3.1, Section 3.2, Section 5.1.1, Section 6.2.1, Chapter 7, Section 8.1, Section 8.1.1, Section 8.1.2, Section 8.1.3, Section 8.2, Section 9.1.1, Section 9.3.5, Section 9.3.6, Section 9.3.7, Section 9.3.8, Chapter 10, Section 10.2, Section 12.3.4, Chapter 13, Section 14.2, Section 14.3.1, Section 14.4.1, Section 14.4.2, Section 14.4.4, Section 14.4.5, Section 14.5.1, Section 14.5.2, Section 14.5.3, Section 14.5.4, Section 14.6, Appendix 2, Appendix 5.1,Appendix 6, Appendix 7, Appendix 8 Chapter 11 to 15 changed to Chapter 10 to 14 Section 2.6 changed to Appendix 7 and 8, Appendix 7 changed to Appendix 9

Deletion

Chapter 10, Section 11.3 to 11.9 Feb., 2012 SH(NA)-080128-X Addition

Appendix 10, Appendix 11

Correction

Section 2.5, Section 8.1.1, Section 8.1.3, Section 8.2 Dec., 2012 SH(NA)-080128-Y Correction

SAFETY PRECAUTIONS, GENERIC TERMS AND ABBREVIATIONS, Section 2.1, Section 2.4, Section 2.5, Section 3.1, Section 3.2, Section 6.4.2, Section 6.4.3, Section 8.1.2, Section 9.2.10

Sep., 2013 SH(NA)-080128-Z Addition

Section 4.3, Section 6.3.3, Section 14.2, Section 14.2.1, Section 14.2.2, Section 14.7.1, Section 14.7.2, Appendix 7, Appendix 9.3

Correction

SAFETY PRECAUTIONS, PRECAUTIONS FOR USE , MANUALS, HOW TO USE THIS MANUAL, GENERIC TERMS AND ABBREVIATIONS, Section 1.1, Section 1.2, Section 2.1, Section 2.5, Section 3.2, Section 4.1, Section 6.1 to 6.5, Section 7.2.6, Section 7.3.1, Section 7.3.2, Section 8.1 to 8.3, Section 9.1 to 9.2, Section 9.3.1, Chapter 10,Section 12.3.1, Section 12.3.4, Chapter 14, Appendix , Section 6.6.1 to 6.6.2, changed 6.5.4 to 6.5.5, Section 8.1.3 changed 14.2.3, Section 8.2 changed 8.3, Section 10.1 to 10.2 changed Chapter10, Section 14.2 changed 14.1, Appendix 1 changed Section 6.3.4, Appendix 2 changed Appendix 3, Appendix 3 to 4 changed Appendix 1 to 2, Appendix 5 changed Appendix 8, Appendix 6 to 8 changed Appendix 4 to 6, Appendix 9 changed Appendix 11, Appendix 10 to 11 changed Appendix 9 to 10

Deletion

Section 6.6, Section 8.1.1, Section 8.1.2, Section 9.1.3, Section 9.1.4, Section 9.4

Page 12: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

A - 10 A - 10

The manual number is given on the bottom left of the back cover.

Print Date Manual Number Revision

Apr., 2015 SH(NA)-080128-AA Correction

GENERIC TERMS AND ABBREVIATIONS, Section 1.1, Section 2.5, Section 8.1, Section 8.2, Section 9.1.1, Section 9.3.1, Section 9.3.2, Section 9.3.3, Section 9.3.5, Section 9.3.6, Section 9.3.8, Section 9.3.10, Section 14.1, Section 14.2.2, Section 14.2.3, Section 14.3.2, Appendix 6.2, Appendix 8.2, Appendix 9.2, Appendix 9.3, Appendix 10 Section 9.3.8 to Section 9.3.11 changed to Section 9.3.7 to Section 9.3.10

Deletion

Section 9.3.7

Sep., 2016 SH(NA)-080128-AB Correction

Section 2.5, Section 8.1, Section 8.2, Section 9.1.1, Section 9.1.2, Section 9.3, Section 14.1, Section 14.2.3, Section 14.2.4, Appendix 7, Appendix 8.2, Appendix 9.1, Appendix 9.2, Appendix 10

Deletion

Section 9.3.1 to Section 9.3.10, Appendix 9.1

Sep., 2017 SH(NA)-080128-AC Correction

Section 2.5, Section 8.1, Section 14.2.3

Jun., 2019 SH(NA)-080128-AD Correction

MANUALS, GENERIC TERMS AND ABBREVIATIONS, Section 2.5, Section 5.1.2, Section 8.1, Appendix 9.1, Appendix 9.2, Appendix 10, Appendix 11.3, Appendix 11.4

Japanese Manual Version SH-080129- AD This manual confers no industrial property rights or any rights of any other kind, nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual.

© 2000 MITSUBISHI ELECTRIC CORPORATION

Page 13: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

A - 11 A - 11

PRECAUTIONS FOR USE

(1) Transfer function between loops and routing transfers The MELSECNET/H board cannot be used as a relay station for the transfer function between data links and during routing transfers. If the transfer function between data links and routing transfers are used, use the network module as a relay station.

(2) Remote I/O Network The MELSECNET/H board cannot be used in a remote I/O net. It can be used only in a PLC to PLC network.

(3) Restrictions for functions depending on the personal computer or the operating system There are some restrictions for the functions or supported versions depending on the operating system or personal computer to be used. For the operating system, refer to Section 2.5.

(4) Driver installation and updating Do not install or update the driver other than the method written in the troubleshooting in this manual. The consistency between the driver and utility cannot be identified, and CC-Link IE Controller Network board may not operate properly.

Page 14: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

A - 12 A - 12

INTRODUCTION

Thank you for purchasing the Q80BD-J71LP21-25, Q81BD-J71LP21-25, Q80BD-J71LP21S-25, Q80BD-J71LP21G, Q80BD-J71LP21GE, Q80BD-J71BR11 MELSECNET/H Interface Board. Before using this product, please read this manual and the relevant manuals carefully and develop

familiarity with the functions and performance of the Q80BD-J71LP21-25, Q81BD-J71LP21-25, Q80BD-J71LP21S-25, Q80BD-J71LP21G, Q80BD-J71LP21GE, Q80BD-J71BR11 MELSECNET/H Interface Board to handle the product correctly.

CONTENTS

SAFETY PRECAUTIONS .............................................................................................................................. A- 1

CONDITIONS OF USE FOR THE PRODUCT ............................................................................................. A- 5 REVISIONS .................................................................................................................................................... A- 6 PRECAUTIONS FOR USE ............................................................................................................................ A-11

INTRODUCTION ............................................................................................................................................ A-12 CONTENTS .................................................................................................................................................... A-12 MANUALS ...................................................................................................................................................... A-17

HOW TO USE THIS MANUAL ...................................................................................................................... A-18 GENERIC TERMS AND ABBREVIATIONS ................................................................................................. A-20 MEANING AND CONTENTS OF THE TERMS ............................................................................................ A-21

PACKING LIST............................................................................................................................................... A-21

1 OVERVIEW 1- 1 to 1- 4

1.1 Overview.................................................................................................................................................. 1- 1 1.2 Features .................................................................................................................................................. 1- 2

2 SYSTEM CONFIGURATION 2- 1 to 2-12

2.1 MELSECNET/H Board System Configuration ....................................................................................... 2- 1 2.2 Single Network System ........................................................................................................................... 2- 3

2.2.1 Optical loop system .......................................................................................................................... 2- 3

2.2.2 Coaxial bus system .......................................................................................................................... 2- 3 2.2.3 Setting items ..................................................................................................................................... 2- 4 2.2.4 Usable device ranges ...................................................................................................................... 2- 4

2.3 Multiple Network System ........................................................................................................................ 2- 5 2.3.1 Configuration .................................................................................................................................... 2- 5 2.3.2 Setting items ..................................................................................................................................... 2- 6

2.3.3 Usable device range ........................................................................................................................ 2- 6 2.4 If used in a Multiple CPU System or Redundant CPU System ............................................................. 2- 7 2.5 Operating Environment ........................................................................................................................... 2- 8

3 SPECIFICATIONS 3- 1 to 3- 4

3.1 General Specifications ............................................................................................................................ 3- 1 3.2 Performance Specifications .................................................................................................................... 3- 2 3.3 Optical Fiber Cable Specification ........................................................................................................... 3- 4

3.4 Coaxial Cable Specification .................................................................................................................... 3- 4

Page 15: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

A - 13 A - 13

4 FUNCTION 4- 1 to 4- 6

4.1 Function List ............................................................................................................................................ 4- 1

4.2 Specifications of the Link Data Sending/Receiving Processing Time ................................................... 4- 2 4.2.1 Link data sending/receiving processing .......................................................................................... 4- 2

4.3 Driver WDT function ................................................................................................................................ 4- 5

5 EMC AND LOW VOLTAGE DIRECTIVE 5- 1 to 5- 6

5.1 Measures to comply with the EMC Directive ......................................................................................... 5- 1 5.1.1 EMC Directive related standards ..................................................................................................... 5- 2 5.1.2 Installation in a control panel ........................................................................................................... 5- 3

5.1.3 Cables ............................................................................................................................................. 5- 4 5.1.4 Ferrite core ....................................................................................................................................... 5- 5 5.1.5 Noise filter (power supply line filter) ................................................................................................. 5- 5

5.2 Requirements for Conformance to Low Voltage Directive .................................................................... 5- 6

6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION 6- 1 to 6-36

6.1 Procedure Up to the Point of Operation ................................................................................................. 6- 1 6.2 Part Names and Settings ........................................................................................................................ 6- 2

6.3 Installation ............................................................................................................................................... 6- 7 6.3.1 Handling precautions ....................................................................................................................... 6- 7 6.3.2 Installation environment ................................................................................................................... 6- 7

6.3.3 Board installation .............................................................................................................................. 6- 8 6.3.4 Channel No. settings ........................................................................................................................ 6- 9

6.4 Wiring ...................................................................................................................................................... 6-10

6.4.1 Optical loop system .......................................................................................................................... 6-12 6.4.2 Coaxial bus system .......................................................................................................................... 6-14 6.4.3 Connecting the connector for the coaxial cable .............................................................................. 6-19

6.4.4 External power supply cable wiring ................................................................................................. 6-23 6.5 Test .......................................................................................................................................................... 6-25

6.5.1 Self-loopback test ............................................................................................................................. 6-26

6.5.2 Internal self-loopback test ................................................................................................................ 6-28 6.5.3 H/W test ............................................................................................................................................ 6-30 6.5.4 Station to station test ........................................................................................................................ 6-31

6.5.5 Forward loop/Reverse loop test ....................................................................................................... 6-34

7 PARAMETER SETTINGS 7- 1 to 7-12

7.1 Board Information Settings ..................................................................................................................... 7- 2 7.2 Network Settings ..................................................................................................................................... 7- 3

7.2.1 Network No. ...................................................................................................................................... 7- 3 7.2.2 Station No. ........................................................................................................................................ 7- 3 7.2.3 Control station/Normal station ......................................................................................................... 7- 3

7.2.4 Group No. ......................................................................................................................................... 7- 4 7.2.5 Mode setting ..................................................................................................................................... 7- 4 7.2.6 Parameter setting example .............................................................................................................. 7- 5

Page 16: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

A - 14 A - 14

7.3 Common Parameters .............................................................................................................................. 7- 6

7.3.1 Send range for each station (LB/LW settings) ................................................................................ 7- 6 7.3.2 Send range for each station (LX/LY settings) ................................................................................. 7- 8 7.3.3 Total station ...................................................................................................................................... 7-10

7.3.4 Designation of the I/O master station .............................................................................................. 7-10 7.3.5 Reserved station setting .................................................................................................................. 7-10 7.3.6 Pairing Setting .................................................................................................................................. 7-10

7.4 Supplementary Setting ........................................................................................................................... 7-11 7.5 Control Station Return Setting ................................................................................................................ 7-12

8 INSTALLING AND UNINSTALLING SOFTWARE PACKAGE 8- 1 to 8- 4

8.1 Installation and Uninstallation Precautions ............................................................................................ 8- 1

8.2 Installation ............................................................................................................................................... 8- 2 8.3 Uninstallation ........................................................................................................................................... 8- 4

9 UTILITY OPERATIONS 9- 1 to 9-22

9.1 Starting and Ending Utility ...................................................................................................................... 9- 1

9.1.1 Starting a utility ................................................................................................................................. 9- 1 9.1.2 Ending a utility .................................................................................................................................. 9- 2

9.2 MNETH Utility .......................................................................................................................................... 9- 2

9.2.1 Screen configuration and basic operations ..................................................................................... 9- 3 9.2.2 Board list screen operation .............................................................................................................. 9- 4 9.2.3 Board information screen operation ................................................................................................ 9- 6

9.2.4 Routing Parameter Setting screen operation .................................................................................. 9- 8 9.2.5 Common parameter setting screen operation ................................................................................. 9- 9 9.2.6 Loop monitor screen operation ........................................................................................................ 9-13

9.2.7 Each station status screen operation .............................................................................................. 9-14 9.2.8 Error history monitor screen operation ............................................................................................ 9-15 9.2.9 Memory, I/O Test screen operation ................................................................................................. 9-18

9.2.10 Target screen operation ................................................................................................................. 9-19 9.2.11 Driver screen operation .................................................................................................................. 9-20

9.3 Device Monitor Utility .............................................................................................................................. 9-22

10 MELSEC DATA LINK LIBRARY 10- 1 to 10- 2

11 PROGRAMMING 11- 1 to 11- 6

11.1 Cautions in Programming ................................................................................................................... 11- 1 11.1.1 Interlock related signals ............................................................................................................... 11- 1

11.2 Cyclic Transmission ............................................................................................................................ 11- 3

11.2.1 Block guarantee of cyclic data per station ................................................................................... 11- 4 11.3 Link Special Relays (SB)/Registers (SW) .......................................................................................... 11- 5

Page 17: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

A - 15 A - 15

12 APPLICATION FUNCTIONS 12- 1 to 12-26

12.1 Direct Access to the Link Devices ...................................................................................................... 12- 1

12.2 Low-Speed Cyclic Transmission Function ......................................................................................... 12- 2 12.2.1 Send range settings ..................................................................................................................... 12- 3 12.2.2 Send timing................................................................................................................................... 12- 4

12.2.3 Startup .......................................................................................................................................... 12- 7 12.3 Transient Transmission Function ....................................................................................................... 12- 9

12.3.1 Communication function .............................................................................................................. 12-10

12.3.2 Routing function ........................................................................................................................... 12-13 12.3.3 Group function .............................................................................................................................. 12-21 12.3.4 SEND/RECV function .................................................................................................................. 12-22

12.4 Multiplex Transmission Function (Optical Loop System) .................................................................. 12-25

13 ERROR CODE 13- 1 to 13- 2

14 TROUBLESHOOTING 14- 1 to 14-28

14.1 Cause Determination Methods by Type of Trouble ........................................................................... 14- 2

14.2 Troubleshooting of Installation and Uninstallation ............................................................................. 14- 5 14.2.1 Installation failed ........................................................................................................................... 14- 5 14.2.2 Uninstallation failed ...................................................................................................................... 14- 5

14.2.3 When the instruction displayed on the screen is not effective at installation ............................. 14- 7 14.2.4 When the driver is not installed.................................................................................................... 14- 8

14.3 When MELSECNET/H Board did not Operate Normally ................................................................... 14-10

14.3.1 Checking personal computer and operating system .................................................................. 14-10 14.3.2 Checking on Event Viewer screen .............................................................................................. 14-11 14.3.3 Checking on Device Manager screen ......................................................................................... 14-13

14.4 Flowchart to Use when Data Link is not Achieved ............................................................................ 14-14 14.4.1 Flowchart to use when RUN LED is unlit .................................................................................... 14-15 14.4.2 Flowchart to use when SD/RD LED does not turn on ................................................................ 14-16

14.4.3 Flowchart to use when L.ERR. LED turns on ............................................................................. 14-17 14.4.4 Flowchart to use when unable to achieve data link for entire system ........................................ 14-18 14.4.5 Flowchart to use when unable to achieve data link for specific station ...................................... 14-20

14.5 Flowchart to Use when Error Occurred During Data Link ................................................................. 14-22 14.5.1 Flowchart to use when unexpected value is input to specific link device .................................. 14-22 14.5.2 Flowchart to use when data cannot be written or read in user program .................................... 14-22

14.5.3 Flowchart to use when communication is disabled from time to time during user program execution ......................................................................................................................... 14-23

14.5.4 Precautions for installing other optional board ............................................................................ 14-24

14.6 When External Power Supply Function does not Work Properly ...................................................... 14-25 14.7 Troubleshooting for WDT Error Occurrence ...................................................................................... 14-26

14.7.1 Board WDT error ........................................................................................................................... 14-26

14.7.2 Driver WDT error ........................................................................................................................... 14-26 14.8 Troubleshooting for Slow PC Operation ............................................................................................ 14-27 14.9 Information Needed when Calling with Inquiry .................................................................................. 14-28

Page 18: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

A - 16 A - 16

APPENDIX App- 1 to App-26

Appendix 1 Cautions for Accessing Redundant CPU System ................................................................ App- 1

Appendix 2 Host Station Status at Power ON/OFF When Using Q80BD-J71LP21S-25 ....................... App- 7 Appendix 3 Procedures for Replacing Boards ......................................................................................... App- 8 Appendix 4 Combinations of Boards with Existing Software ................................................................... App-10

Appendix 5 Checking Serial Number and Function Version .................................................................. App-11 Appendix 6 New and Improved Functions .............................................................................................. App-12

Appendix 6.1 Change of hardware function ......................................................................................... App-12

Appendix 6.2 Update of software package ........................................................................................... App-12 Appendix 7 Restrictions for Operating System ........................................................................................ App-13 Appendix 8 Warning Message Appears on Windows.............................................................................. App-14

Appendix 8.1 Overview of warning message ....................................................................................... App-14 Appendix 8.2 Methods for preventing the warning message ............................................................... App-15

Appendix 9 Behavior When Personal Computer Enters Power Save Mode or Fast Startup ................ App-20

Appendix 9.1 Behavior when the personal computer enters the power save mode (hibernate, sleep) ............................................................................................................ App-20

Appendix 9.2 Behavior when the fast startup function is enabled ....................................................... App-21

Appendix 10 MELSECPowerManager ..................................................................................................... App-22 Appendix 10.1 Installing MELSECPowerManager............................................................................... App-22 Appendix 10.2 Uninstalling MELSECPowerManager .......................................................................... App-22

Appendix 10.3 Checking MELSECPowerManager .............................................................................. App-23 Appendix 11 External Dimensions ........................................................................................................... App-25

Appendix 11.1 Q80BD-J71LP21-25, Q80BD-J71LP21G, Q80BD-J71LP21GE................................. App-25

Appendix 11.2 Q80BD-J71LP21S-25 ................................................................................................... App-25 Appendix 11.3 Q80BD-J71BR11 .......................................................................................................... App-26 Appendix 11.4 Q81BD-J71LP21-25 ..................................................................................................... App-26

Page 19: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

A - 17 A - 17

MANUALS

The following table lists the manuals relevant to this product.

You can order them as necessary.

Relevant Manuals

Manual Name Manual Number (Model Code)

MELSECNET/H Interface Board User's Manual (For SW0DNC-MNETH-B)

Explains the system configuration, specifications, functions, handling, wiring, and troubleshooting for

MELSECNET/H interface boards. (this manual) (Sold separately)

SH-080128 (13JR24)

Q Corresponding MELSECNET/H Network System Reference Manual (PLC to PLC network)

Explains the system configuration, performance specification, function, handling, wiring and

troubleshooting for MELSECNET/H network system. (Sold separately)

SH-080049 (13JF92)

For QnA/A4AR MELSECNET/10 Network System Reference Manual

Explains the system configuration, performance specification, function, handling, wiring and

troubleshooting for MELSECNET/10 network system. (Sold separately)

IB-66690 (13JF78)

MELSEC Data Link Library Reference Manual

Explains the programming, accessible devices and range, function specifications, sample programming

and error code for MELSEC data link library. (Sold separately)

SH-081035ENG (13JV25)

REMARK

MELSEC Data Link Library Reference Manual is stored on the CD-ROM of software package with PDF file. Manuals in printed form are sold separately for single purchase. Order a manual by quoting the manual number (model code) listed in the table above.

Page 20: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

A - 18 A - 18

HOW TO USE THIS MANUAL

"How to Use This Manual" differs depending on the purpose for which the MELSECNET/H board is used. Use this manual with reference to the following contents.

(1) When desiring an overview or to know the features of the

MELSECNET/H board (Chapter 1) Chapter 1 gives an overview of the MELSECNET/H board and its features.

(2) When desiring to know about the system configuration

(Chapter 2) Chapter 2 gives the system configuration.

(3) When desiring to know the specifications of the MELSECNET/H

board (Chapter 3) Chapter 3 gives the specifications of the MELSECNET/H board.

(4) When desiring to know the functions of the MELSECNET/H board

(Chapter 4) Chapter 4 gives the functions of the MELSECNET/H board.

(5) When desiring to know the procedure up to the point of operation

of the MELSECNET/H board and settings (Chapter 6) Chapter 6 gives the procedures up to the point of operation and the settings.

(6) When desiring to know the parameter settings for the

MELSECNET/H board (Chapter 7) Chapter 7 gives the parameter settings.

(7) When desiring to know the procedure for installing and

uninstalling the software package (Chapter 8) Chapter 8 gives the procedure for installing and uninstalling the software package.

(8) When desiring to know the operation of each utility (Chapter 9)

Chapter 9 gives the operation methods for each utility.

(9) When desiring to know about the MELSEC data link library (Chapter 10) Chapter 10 gives overview concerning the MELSEC data link library.

Page 21: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

A - 19 A - 19

(10) When desiring to know the interlock related signals (Chapter 11)

Chapter 11 gives the interlock related signals.

(11) When desiring to know the application functions (Chapter 12) Chapter 12 gives the MELSECNET/H board's application functions.

(12) When desiring to know about troubleshooting (Chapter 14)

Chapter 14 gives information on troubleshooting.

Page 22: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

A - 20 A - 20

GENERIC TERMS AND ABBREVIATIONS Unless otherwise specified, this manual uses the following generic terms and abbreviations to describe MELSECNET/H interface board.

Generic Term/Abbreviation Description

MELSECNET/H board Generic term for Q80BD-J71LP21-25, Q81BD-J71LP21-25, Q80BD-J71LP21S-25, Q80BD-J71LP21G, Q80BD-J71LP21GE, and Q80BD-J71BR11.

SW0DNC-MNETH-B Product name of the software package for MELSECNET/H interface board. MNETH utility Abbreviation for MELSECNET/H utility GX Developer General product name for product model names SW8D5C-GPPW.

MX Links General product name for product model names SWnD5F-CSKP-E (n denotes the version number)

MX Component General product name for product model names SWnD5C-ACT-E, SWnD5C-ACT-EA (n denotes the version number)

MELSECNET/10 board Abbreviation for A70BDE-J71QLP23/A70BDE-J71QLP23G E/A70BDE-J71QBR13/A70BDE-J71QLR23 MELSECNET/10 interface board.

ACPU Generic term for the CPU of MELSEC-A series. QnACPU Generic term for the CPU of MELSEC-QnA series. QCPU Generic term for the CPU of MELSEC-Q series. RCPU Generic term for the CPU of MELSEC iQ-R series.

QJ71LP21

Abbreviation for QJ71LP21, QJ71LP21G, Q71LP21GE, QJ71LP21-25, QJ71LP21S-25, MELSECNET/H network module. However, if shown for a particular model, QJ71LP21, QJ71LP21G, Q71LP21GE, QJ71LP21-25, QJ71LP21S-25 is entered.

QJ71BR11 Abbreviation for QJ71BR11 MELSECNET/H network module. Network module Generic term for QJ71LP21, QJ71BR11 MELSECNET/H Abbreviation for Q corresponding MELSECNET/H network system. MELSECNET/10 AnU corresponding, QnA/Q4AR corresponding MELSECNET/10 network system. MELSECNET/H (10 Mbps) Abbreviation in case of using MELSECNET/H board with communication rate of 10 Mbps. MELSECNET/H (25 Mbps) Abbreviation in case of using MELSECNET/H board with communication rate of 25 Mbps.

MELSECNET/H mode Abbreviation in case of using MELSECNET/H board and network module with MELSECNET/H.

MELSECNET/H Extended mode

Abbreviation for the extended MELSECNET/H mode, which is extended in the maximum number of link points per station.

MELSECNET/10 mode Abbreviation in case of using MELSECNET/H board and network module with MELSECNET/10.

Board WDT Abbreviation for the watchdog timer that monitors the operation of network board

Driver WDT Abbreviation for the watchdog timer that monitors the communication status between a network board and a personal computer, or operating status of a personal computer

Page 23: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

A - 21 A - 21

MEANING AND CONTENTS OF THE TERMS This section describes meaning and contents of the terms in this manual.

(1) Abbreviations for control station and normal station, and symbol format

This section explains abbreviations for control station and normal station, and symbol format to be used in this manual.

(a) Abbreviation

Abbreviation Name

MP Control station

NS Normal station (Station that can serve as a control station)

(b) Symbol format

Mp —

Group number (1 to 32) : GStation number (1 to 64)AbbreviationNetwork No. (1 to 239)

[Example]1) Network No. 3, control station, station number 6: 3MP62) Network No. 5, normal station, station number 3: 5NS3

PACKING LIST

The packing list of the MELSECNET/H board is given below.

Item Quantity

Board 1

Connector set for external power supply cable(Q80BD-J71LP21S-25 only) 1

F-type connector (A6RCON-F) (Q80BD-J71BR11 only) 1

"Before Using the Product" 1

Software Package (CD-ROM) *1 1

Software license agreement 1

1: Manuals are stored on the CD-ROM in PDF format.

Page 24: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

A - 22 A - 22

MEMO

Page 25: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

1 - 1 1 - 1

MELSEC 1 OVERVIEW

1

1 OVERVIEW

This is a manual you read when using the MELSECNET/H board in the MELSECNET/H mode or MELSECNET/H Extended mode. When using the

MELSECNET/H board in the MELSECNET/H network, refer to "Q Corresponding MELSECNET/H Network System Reference Manual (PLC to PLC network)". Also, when using the board in the MELSECNET/10 network system, refer to "For QnA/Q4AR

Corresponding MELSECNET/10 network system reference manual".

1.1 Overview

The MELSECNET/H is a network system which is used to connect multiple sequencer modules and personal computers, and is equipped with functions and performance

realized in the MELSECNET/10 for general control of a production line. In the MELSECNET/H, there is a network system which includes an optical loop system (communication rates: 10 Mbps, 25 Mbps) and a coaxial bus system

(communications rate: 10 Mbps), enabling large volume communications at high speeds. Also, in order to improve the performance of the MELSECNET/10 network and achieve

upward compatibility, MELSECNET/H supports the MELSECNET/ H and MELSECNET/H Extended modes (high performance, high speed mode) and the MELSECNET/10 Mode (function compatible and performance compatible mode).

Mode Description

MELSECNET/H mode Set this mode when all CPUs within the network are QCPUs and

RCPUs.

MELSECNET/H Extended

mode

The maximum number of link points per station has been increased

compared with the MELSECNET/H mode.

In excess of 2000 bytes, a maximum of 35840 bytes can be set.

Set this mode when the system uses many link points per station.

MELSECNET/10 mode This mode is used to operate the MELSECNET/H board on a

MELSECNET/10 network.

MELSECNET/H

MELSECNET / 10

QCPU QCPU

QCPU QCPU

AnU QnA QCPU QCPU

GX Developer

MELSECNET/10 Mode

1: The multiple CPU system compatible network module is for function version B and subsequent products. 2: In the multiple CPU system, a network module that becomes a relay station is the same as the control CPU.

1

1 2

QCPU

MELSECNET / H

Personal Computer MELSECNET/H Board

(Q80BD-J71BR11) Personal Computer

MELSECNET/H Board (Q80BD-J71LP21-25)

1 2

Page 26: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

1 - 2 1 - 2

MELSEC 1 OVERVIEW

POINT

(1) For MELSECNET/H, select QCPUs, RCPUs, and Q compatible network modules.

(2) If QnACPU or ACPU are included in the same network, select MELSECNET/10 mode which is compatible with MELSECNET/10.

(3) All of network modules and MELSECNET/H boards within the same network must be set to the same mode (network type) 1.

1: MELSECNET/H mode, MELSECNET/H Extended mode and MELSECNET/10 mode are available.

1.2 Features

The features of the MELSECNET/H board are as shown below.

(1) A personal computer can be incorporated into MELSECNET/H. By mounting the MELSECNET/H board in a personal computer, the personal computer can be used as a MELSECNET/H or MELSECNET/10 control station or normal station.

Board model name Supported network Mode

Q80BD-J71LP21-25 Q81BD-J71LP21-25 Q80BD-J71LP21S-25

MELSECNET/H Mode, MELSECNET/H Extended Mode

MELSECNET/H (10 Mbps / 25 Mbps) Optical Loop System

MELSECNET/10 Mode MELSECNET/10 Optical Loop System

Q80BD-J71BR11

MELSECNET/H Mode, MELSECNET/H Extended Mode

MELSECNET/H (10 Mbps) Coaxial Bus System

MELSECNET/10 Mode MELSECNET/10 Coaxial Bus System

Q80BD-J71LP21G Q80BD-J71LP21GE

MELSECNET/H Mode, MELSECNET/H Extended Mode

MELSECNET/H (10 Mbps) Optical Loop System

MELSECNET/10 Mode MELSECNET/10 Optical Loop System

(2) By adopting the PCI/PCI Express R standard, complicated switch

settings are no longer required. The system can be used simply by installing the MELSECNET/H board in the personal computer, then installing the software. The channel No., station No. and other settings can be carried out easily in the MNETH Utility.

(3) Compatibility with the previous MELSECNET/10 board’s operations

is maintained. (a) Upward compatibility of user programs

Since MELSECNET/H board has the same number of the maximum mountable board and channel number as the previous MELSECNET/10 board, the exiting user programs can be utilized.

(b) Compatible with the GX Developer, MX Links and MX Component. It is possible to access the programmable controller CPU using the GX Developer, MX Links and MX Component from a personal computer where the MELSECNET/H board is installed.

1

Page 27: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

1 - 3 1 - 3

MELSEC 1 OVERVIEW

(4) Compatible with multiple CPU systems.

By using station designations of logical station No. on the MNETH utility,

MELSECNET/H board is capable of communicating with a multiple CPU system.

(5) Compatible with redundant CPU systems. Only by specifying whether the destination is a control or standby station using

the user program, access is simply made without considering the current operating system state of the redundant CPU system.

(6) Compatible with MELSECNET/H Extended mode

The MELSECNET/H Extended mode is the extended MELSECNET/H mode, which is extended in the maximum number of link points per station. With this mode, the maximum number of link points per station can be set to 2000 bytes or

more, i.e., up to 35840 bytes. This mode is suitable for the system that needs many number of link points per station.

(7) Drivers are provided for compatibility with each OS.

Each type of driver is provided, so it is easy to build a system that is compatible with the user environment.

For details on the compatible operating system, refer to Section 2.5.

(8) User programming functions are provided. Through Microsoft R Visual Basic R and Microsoft R Visual C++ R compatible functions, it is possible to carry out remote control of a programmable controller CPU or read and write to devices, and user programs can be created easily.

Page 28: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

1 - 4 1 - 4

MELSEC 1 OVERVIEW

(9) External power supply allows continuous network communication

even during power-off of personal computer. (Function of the Q80BD-J71LP21S-25) Since power is supplied externally, the Q80BD-J71LP21S-25 can continue network communication (baton passing) even if a personal computer is powered

off and data link cannot be performed. Therefore, a normally operating station connected between other stations with power-off computers will not be disconnected from the data link.

Another advantage is that the link scan time is stabilized since loopback can be also prevented.

Q80BD-J71LP21-25

QJ71LP21-25

Q80BD-J71

LP21S-25

Q80BD-J71LP21-25

Q80BD-J71

LP21S-25

QJ71LP21-25

QCPU

QCPU

Normal station(Station No.3)

Personalcomputer

External powersupply

Control station(Station No.1)

Personalcomputer

Normal station(Station No.2)

Personalcomputer

Personalcomputer

Normal station(Station No.6)

Normal station(Station No.5)

Normal station(Station No.4)

External powersupply

Data link continued

When station No. 3 and No.5 use MELSECNET/H boards without the external power supply function and if their personal computers are powered off, station

No.4 is cut off from the network as well as No.3 and No.5.

Station No.1 Station No.2 Station No.3

Station No.6 Station No.5 Station No.4

Personal computer

Personal computer

Disconnected

Page 29: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

2 - 1 2 - 1

MELSEC 2 SYSTEM CONFIGURATION

2

2 SYSTEM CONFIGURATION

2.1 MELSECNET/H Board System Configuration

The system configuration when the MELSECNET/H board is mounted to a personal computer is shown below.

MELSECNET/10Optical loop system

MELSECNET/HCoaxial bus system

MELSECNET/10Coaxial bus system

MELSECNET/Hmode,MELSECNET/HExtended mode

MELSECNET/10mode

MELSECNET/Hmode,MELSECNET/HExtended mode

MELSECNET/10mode

Optical fibercable

Coaxial cable

QQ81BD-J71LP21-25

80BD-J71LP21-25

Q80BD-J71LP21S-25

Q80BD-J71BR11

SW0DNC-MNETH-B

Personal Computer

Type of cable : 3C-2V5C-2V5C-FB

Type of cable : SIH-PCFBroad-band H-PCFQSI

MELSECNET/HOptical loop system

Install

Install

MELSECNET/HOptical loop system

MELSECNET/10Optical loop system

MELSECNET/Hmode,MELSECNET/HExtended mode

MELSECNET/10mode

Optical fibercable

Q80BD-J71LP21G

(Type of cable : GI)

MELSECNET/HOptical loop system

MELSECNET/10Optical loop system

MELSECNET/Hmode,MELSECNET/HExtended mode

MELSECNET/10mode

Optical fibercable

Q80BD-J71LP21GE

(Type of cable : 62.5GI)

Page 30: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

2 - 2 2 - 2

MELSEC 2 SYSTEM CONFIGURATION

2

POINT

(1) When using the MELSECNET/H Extended mode (a) Use the MELSECNET/H board of ROM version 2X or later and SW0DNC-

MNETH-B version 11M or later. (b) When assigning 2000 bytes or more to the number of link points sent by a

station, set all stations including control stations and normal stations to the

MELSECNET/H Extended mode. (2) When using the Q80BD-J71LP21S-25

Use the SW0DNC-MNETH-B version 12N or later.

(3) When using the Q80BD-J71LP21-25, Q81BD-J71LP21-25 or Q80BD-J71LP21S-25 at a communication speed of 25Mbps, errors may occur at all stations if multiple boards with the same network number are installed, or the

operating systems are started up/shut down or the boards are reset simultaneously on the adjacent personal computers. In this case, set the communication speed to 10Mbps.

(4) If the QnACPU or ACPU are included in the same network, select MELSECNET/10 mode which is compatible with MELSECNET/10.

Page 31: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

2 - 3 2 - 3

MELSEC 2 SYSTEM CONFIGURATION

2.2 Single Network System

A single network system is one system that connects the control station and the normal stations with an optical fiber cable or a coaxial cable.

2.2.1 Optical loop system

In the optical loop system, 1 control station and 63 normal stations (a total of 64

stations) can be connected. Any station number can be assigned as the control station. However, only one station can be set as the control station per system. In the following sample system, station number 1 has been assigned as the control

station.

Optical fiber cable

Q80BD-J71LP21-25

Station No. 1(control station)

QCPU

Po

wer

sup

ply

QJ71LP21-25

QCPU QJ71LP21

Personalcomputer

Station No. 2(normal station)

Station No. 64(normal station)

Po

wer

sup

ply

2.2.2 Coaxial bus system

In the coaxial bus system, 1 control station and 31 normal stations (a total of 32 stations) can be connected. As in the optical loop system, any station number can be assigned as the control station. However, only 1 station can be assigned as the control

station per system.

QCPU QCPU

Terminal resistorA6RCON-R75

Coaxial cable

Terminal resisterA6RCON-R75

QJ71BR11

QJ71BR11

Q80BD-J71BR11

Station No. 1(control station)

Personalcomputer

Station No. 2(normal station)

Station No. 32(normal station)

Po

wer

su

pply

Po

wer

su

pply

Page 32: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

2 - 4 2 - 4

MELSEC 2 SYSTEM CONFIGURATION

2.2.3 Setting items

In a single network system, the items which need to be set in the case that the MELSECNET/H board is used as the control station or normal station are as follows. MELSECNET/H board settings are set by the MNETH Utility.

Setting item Control station Normal station Reference section

Channel setting Section 9.2.2

Network No.

Section 9.2.3

Group No.

Station No.

Control station/ Normal station

Mode Setting

Routing parameter setting Section 9.2.4

Common

parameter

setting

B, W setting

Section 9.2.5 X, Y setting

Reserved station setting

Supplementary setting

Opposite party setting

(Logical station No.) Section 9.2.10

Driver setting Section 9.2.11

: Setting necessary : Set as necessary : Setting unnecessary 2.2.4 Usable device ranges

The MELSECNET/H board can be used within the following device ranges for the following devices on the MELSECNET/H board.

Device Usable range

LB 0H to 3FFFH

(16384 points)

The function expansion areas of 2000H to 3FFFH are used for the low-speed cyclic transmission. All areas can be used for the normal cyclic transmission. The use ranges for each MELSECNET/H board and network module need to be assigned in the parameter settings for the control station.

LW 0H to 3FFFH

(16384 points)

LX 0H to 1FFFH (8192 points) The use ranges for each MELSECNET/H board and network

module need to be assigned in the parameter settings for the control station.

LY 0H to 1FFFH (8192 points)

If the MELSECNET/H board is used in the MELSECNET/10 mode, the device range for LB/LW becomes 0H to 1FFFH (8192 points).

Page 33: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

2 - 5 2 - 5

MELSEC 2 SYSTEM CONFIGURATION

2.3 Multiple Network System

A multiple network system is a system where multiple networks are connected by relay stations.

POINT

(1) The network No. can be set at any desired No. in the range 1 to 239. (2) The MELSECNET/H board cannot be used as a relay station.

Please use the network module as a relay station.

2.3.1 Configuration

The following example shows how three networks can be connected.

3NS2Normal station

Normal station2NS3

1NS3Normalstation

Network No.1

Normal station1NS2

Pow

er s

upp

ly

Network No.2

Normal station2NS2

Control station1MP1

QCPU

3NS3Normal station

3NS4Normal station

QCPU QJ71LP21

QJ71LP21

Control station2MP1

QJ71LP21-25

QJ71BR11

QCPU QJ71LP21-25

QJ71BR11

QCPU QJ71BR11

QCPU

Network No.3

Q80BD-J71LP21-25

Personalcomputer

Q80BD-J71LP21-25

Personalcomputer

Q80BD-J71BR11

Personalcomputer

Control station3MP1

Pow

er s

upp

ly

Pow

er s

upp

ly

Pow

er s

upp

ly

Pow

er s

uppl

y

Page 34: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

2 - 6 2 - 6

MELSEC 2 SYSTEM CONFIGURATION

2.3.2 Setting items

Setting items in the case that the MELSECNET/H board is used as a control station or normal station in a multiple network system are explained below. MELSECNET/H board settings are performed by the MNETH Utility.

Setting item Control station Normal station Reference section

Channel setting Section 9.2.2

Network No.

Section 9.2.3

Group No.

Station No.

Control station/ Normal station

Mode setting

Routing parameter setting Section 9.2.4

Common Parameter Setting

B, W setting

Section 9.2.5 X, Y setting

Reserved station setting

Supplementary setting

Opposite party setting (Logical station No.)

Section 9.2.10

Driver setting Section 9.2.11

2.3.3 Usable device range

The same device range as is used for a single network system (section 2.2.4) can be used.

Page 35: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

2 - 7 2 - 7

MELSEC 2 SYSTEM CONFIGURATION

2.4 If used in a Multiple CPU System or Redundant CPU System

For cautions in the case of installing MELSECNET/H in a multiple CPU system or redundant CPU system, refer to "Q Corresponding MELSECNET/H Network System Reference Manual (PLC to PLC network)."

POINT

When accessing a multiple CPU system or Redundant CPU system, use the MELSECNET/H board and network module of the following function versions.

MELSECNET/H board Programmable controller

side network module

Access to multiple

CPU system All versions available Function version B or later

Access to Redundant

CPU system, Function version D or later 1 Function version D or later

1: When using a MELSECNET/H board of function version D or earlier, access to a redundant CPU is not performed normally.

Page 36: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

2 - 8 2 - 8

MELSEC 2 SYSTEM CONFIGURATION

2.5 Operating Environment

The following table shows the operating environment for the MELSECNET/H board.

Item Description

Personal computer

Microsoft R Windows R supported personal computer

CPU System requirements of the operating system must be met.

Required memory

PCI bus specifications

For Q80BD-J71LP21-25, Q80BD-J71LP21S-25, Q80BD-J71LP21G, and Q80BD-J71BR11 • Compliant with PCI standard Rev.2.2 (5V DC, 32-bit bus, Reference clock : 33MHz)

PCI Express R Bus specifications

For Q81BD-J71LP21-25 • Compliant with PCI Express R standard Rev.1.0a (3.3 V DC, Link width : 1lane, Reference clock : 100MHz)

Available hard disk space 1GB or more

Disk drive CD-ROM disk drive

Display Resolution: 800 600 dot or higher (Recommended: 1024 768 dot)

Operating system (English version)

Windows Server R 2019 (Standard)

Windows Server 2016 (Standard) 1

Windows 10 (Home, Pro, Enterprise, Education, IoT Enterprise 2016 LTSB 2) Windows 8.1, Windows 8.1 (Pro, Enterprise) Windows Server 2012 R2 (Standard) Windows 8, Windows 8 (Pro, Enterprise) Windows Server 2012 (Standard) Windows 7 (Home Premium, Professional, Ultimate, Enterprise) 3 Windows Server 2008 R2 (Standard, Enterprise) 3

When using any of the following operating systems, use SW0DNC-MNETH-B with the version 29F or earlier. Windows Server 2008 (Standard (x86, x64), Enterprise (x86, x64)) Windows Vista R (Home Basic, Home Premium, Business, Ultimate, Enterprise) 4 Windows Server 2003 R2 (Standard (x86, x64), Enterprise (x86, x64)) Windows XP R (Professional) 4

When using any of the following operating systems, use SW0DNC-MNETH-B with the version 25B or earlier. Windows 2000 (Professional) Windows NT R Workstation 4.0 SP3 or later Windows 98, Windows 98 Second Edition Windows 95

Programming language (English version)

Visual Basic R , Visual C++ R in the following development tools

Visual Studio R 2017,

Visual Studio 2015, Visual Studio 2013, Visual Studio 2012, Visual Studio 2010, Visual Studio 2008, Visual Studio 2005, Visual Studio.NET 2003, Visual Basic 6.0, Visual C++ 6.0, Visual Basic 5.0, Visual C++ 5.0

1: Apply Windows Updates (KB4132216, KB4091664, KB4465659, and KB4480977).

2: 64-bit version only

3: Apply Service Pack1 and Security Update for Windows (KB3033929). Otherwise, use SW0DNC-MNETH-B with the

version 29F or earlier.

4: 32-bit version only

Page 37: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

2 - 9 2 - 9

MELSEC 2 SYSTEM CONFIGURATION

POINT

For the information on how to obtain SW0DNC-MNETH-B of the version 29F or earlier, refer to Appendix 7.

(1) Instructions for personal computer

(a) PCI standard Using a personal computer not compliant with the PCI or PCI Express R standard may result in a problem due to poor electrical contact, erroneous

operation, etc. For details on the number of boards that can be installed, installation slot and occupied slots, refer to Section 3.2.

(b) The functions being added

Operating environment Supported version of SW0DNC-MNETH-B

Hyper-Threading technology 11M or later Multiprocessor 19V or later

(2) Instructions for operating system

(a) Supported version of SW0DNC-MNETH-B

Operating system

Supported version Q80BD-J71LP21-25, Q80BD-J71LP21S-25, Q80BD-J71LP21G, Q80BD-J71BR11

Q81BD-J71LP21-25

Windows Server 2019, Windows Server 2016, Windows 10 (IoT Enterprise 2016 LTSB)

33K or later

Windows 10 (Home, Pro, Enterprise, Education) 30G or later Windows 8.1, Windows Server 2012 R2 27D or later Windows 8, Windows Server 2012 26C or later Windows 7 (64-bit version), Windows Server 2008 R2

23Z or later

Windows 7 (32-bit version) 21X or later Windows Server 2008 (64-bit version) 23Z to 29F Windows Server 2008 (32-bit version) 21X to 29F Windows Vista 17T to 29F 19V to 29F Windows Server 2003 R2 (64-bit version) 23Z to 29F Windows Server 2003 R2 (32-bit version) 19V to 29F Windows XP 70H to 90K, 10L to 29F 19V to 29F Windows 2000 25B or earlier 19V to 25B Windows NT Workstation, Windows 98, Windows 95

25B or earlier Not supported

Page 38: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

2 - 10 2 - 10

MELSEC 2 SYSTEM CONFIGURATION

(b) User authority

Log on as a user having administrator authority.

Installation, uninstallation and usage of utilities are available only by the administrator's authority.

(c) .NET Framework 3.5

When using one of the following operating system, .NET Framework 3.5 is required. • Windows Server 2019

• Windows Server 2016 • Windows 10 • Windows 8.1

• Windows Server 2012 R2 • Windows 8 • Windows Server 2012

Enable the .NET Framework 3.5 (including .NET 2.0 or 3.0) in "Turn Windows features on or off" on the control panel.

(d) Upgrading and updating the operating system

Upgrading the operating system and updating from Windows 8 to Windows 8.1 are not supported.

Install SW0DNC-MNETH-B by following the procedure. 1. Uninstall SW0DNC-MNETH-B. 2. Upgrade or update the operating system.

3. Install SW0DNC-MNETH-B with the version supporting the changed operating system.

Page 39: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

2 - 11 2 - 11

MELSEC 2 SYSTEM CONFIGURATION

(e) The functions cannot be used

If an attempt is made to use any of the following functions, this product may

not operate normally. • Activating the application with Windows R compatible mode. • Simplified user switch-over

• Remote desktop • Power save mode (Hibernate, Sleep) • Fast startup

• The language switching function set by Regional and Language Options • Windows XP Mode • Windows Touch or Touch

• Modern UI • Client Hyper-V • Server Core Installation

• Tablet mode • Virtual desktop • Unified Write Filter

In the following cases, the screen of this product may not work properly. • The size of the text and/or other items on the screen are changed to

values other than default values (such as 96 DPI, 100%, and 9 pt). • The resolution of the screen is changed in operation. • The multi-display is set.

REMARK

• When exiting the operating system, always shut down the computer. • For the behavior when entering the power save mode, refer to Appendix 9.

Page 40: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

2 - 12 2 - 12

MELSEC 2 SYSTEM CONFIGURATION

(3) Instructions for user program

(a) Supported version of SW0DNC-MNETH-B

User program Supported version of SW0DNC-MNETH-B

32-bit version user program*1 All versions

64-bit version user program*2 Version 23Z or later

1: Programs can be created and executed on the 64-bit version operating system.

2: Programs can be created on the 32-bit version operating system, however, the following dialog box appears and cannot be executed.

<When using Windows 7 (32-bit version)>

(b) Language environment

User programs created in the Japanese environment work only in the

Japanese environment. User programs created in the English environment work only in the English environment.

(c) MELSEC data link library

For precautions when using MELSEC data link library, refer to MELSEC

Data Link Library Reference Manual.

Page 41: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

3 - 1 3 - 1

MELSEC3 SPECIFICATIONS

3 SPECIFICATIONS

This section explains the MELSECNET/H board general specifications, performance specifications.

3.1 General Specifications

This section explains the MELSECNET/H board general specifications. Item Specifications

Operating ambient temperature 0 to 55 °C

Storage ambient temperature -25 to 75 °C

Operating ambient humidity

Storage ambient humidity 5 to 95 % RH, non-condensing

Under intermittent vibration

Frequency Constant acceleration

Half amplitude

Sweep count

5 to 8.4 Hz — 3.5 mm

8.4 to 150 Hz 9.8m/s2 —

10 times each in X, Y and Z directions

Under continuous vibration

Frequency Constant

accelerationHalf

amplitude Sweep count

5 to 8.4 Hz — 1.75 mm

Vibration resistance Compliant with JIS B 3502 and IEC 61131-2

8.4 to 150 Hz 4.9m/s2 — —

Shock resistance Compliant with JIS B 3502 and

IEC 61131-2 (147 m/s2, 3 times each in X, Y, and Z directions)

Operating atmosphere i t

No corrosive gases

Operating altitude 1 0 to 2000 m

Installation location Inside a control panel

Over-voltage category 2 II or less

Pollution rate 3 2 or less

1: Do not use or store the board under pressure higher than the atmospheric pressure of altitude 0m. Doing so may cause a malfunction.

2: This indicates the section of the power supply to which the equipment is assumed to be connected between the public electrical power distribution network and the machinery within the premises. Category II applies to equipment for which electrical power is supplied from fixed facilities. The surge voltage withstand level for up to the rated voltage of 300 V is 2500 V.

3: This index indicates the degree to which conductive material is generated in terms of the environment in which the equipment is used. Pollution level 2 is when only non-conductive pollution occurs. A temporary conductivity caused by condensation must be expected occasionally.

REMARK

General specifications both MELSECNET/H board and a personal computer must be satisfied after installation.

3

Page 42: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

3 - 2 3 - 2

MELSEC3 SPECIFICATIONS

3.2 Performance Specifications

MELSECNET/H Board performance specifications are shown below.

(1) Q80BD-J71LP21-25, Q81BD-J71LP21-25, Q80BD-J71LP21S-25, Q80BD-J71LP21G, Q80BD-J71LP21GE

Specifications Item

Q80BD-J71LP21-25 Q81BD-J71LP21-25 1 Q80BD-J71LP21S-25 Q80BD-J71LP21G Q80BD-J71LP21GE

LX/LY 8192 Points LB 16384 Points (When in the MELSECNET/10 Mode 2: 8192 Points)

Maximum links in 1 network

LW 16384 Points (When in the MELSECNET/10 Mode 2: 8192 Points)

Maximum links in 1 station

• MELSECNET/H mode, MELSECNET/10 mode 2 {(LY + LB) / 8 + (2 LW)} ≤ 2000 bytes

• MELSECNET/H Extended mode 2 {(LY + LB) / 8 + (2 LW)} ≤ 35840 bytes

Communications rate 2 25 Mbps / 10 Mbps 10 Mbps Number of stations Connected to 1 network 64 Stations (Control station: 1; Normal station: 63)

Connection cable Optical fiber cable Total extension cable length 30km (98430 ft.)

25 Mbps

SI optical cable : 200m (656.2 ft.) H-PCF optical cable : 400m (1312.4 ft.) Broad-band H-PCF optical cable : 1km (3281 ft.) QSI optical cable : 1km (3281 ft.)

— — Between stations length 3

10 Mbps

SI optical cable : 500m (1640.5 ft.) H-PCF optical cable : 1km (3281 ft.) Broad-band H-PCF optical cable : 1km (3281 ft.) QSI optical cable : 1km (3281 ft.)

GI optical cable : 2km (6562 ft.)

62.5 GI optical cable: 2km (6562 ft.)

Maximum networks 239 Maximum number of groups 32 (When in the MELSECNET/10 Mode: 9) Transmission channel format Duplex loop Communications system Token ring system Synchronization system Frame synchronization system Encoding system NRZI encoding (Non return to Zero inverted) Transfer format HDLC Standard (Frame format) Error control system CRC (X16 + X12 + X5 + 1) and retry by overtime.

RAS function

• Loop back function (optical loop system only) by abnormal detection and cable disconnection. • System down prevention through control station. • Error detection by the link special relay and link special register. etc.

Transient transmission N: N communications Special cyclic transmission Low speed cyclic transmission Number of boards that can be installed Maximum 4 boards

Installation slot PC PCI bus slot (half size)

PC PCI Express R X1, X2, X4, X8, X16 slot (half size)

PC PCI bus slot (half size)

Exclusive slots 1 slot 2 slot 1 slot Voltage — 20.4 to 31.2 V DC — Current — 0.16 A —

Connector — Connector set (Accessory) —

External power supply

Suitable cable size — 0.50 to 1.25 mm2

[AWG#20-16] —

5 V DC Internal current consumption 0.46 A — 0.46 A 0.45 A

3.3 V DC Internal current consumption — 0.95 A — —

Weight 0.10 kg 0.20 kg 0.11 kg

3

Page 43: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

3 - 3 3 - 3

MELSEC3 SPECIFICATIONS

1: The CPU usage may be higher compared to that of Q80BD-J71LP21-25, Q80BD-J71LP21S-25, Q80BDJ71LP21G,

Q80BD-J71LP21GE, or Q80BD-J71BR11. (For the solutions to slow PC performance, refer to Section 14.8.) 2: MELSECNET/H board communications rate and Mode settings are performed using the MNETH Utility.

(For details, refer to Section 9.2.3) 3: L type and H type of the previous optical fiber cable (A-2- ) differ in the distances between stations. (For details, refer

to Section 6.4.1)

(2) Q80BD-J71BR11

Specifications Item Q80BD-J71BR11

LX/LY 8192 Points LB 16384 Points (When in the MELSECNET/10 Mode 1: 8192 Points)

Maximum links in 1 network

LW 16384 Points (When in the MELSECNET/10 Mode 1: 8192 Points)

Maximum links in 1 station

• MELSECNET/H mode, MELSECNET/10 mode 1 {(LY + LB) / 8 + (2 LW)} ≤ 2000 bytes

• MELSECNET/H Extended mode 1 {(LY + LB) / 8 + (2 LW)} ≤ 35840 bytes

Communications rate 1 10 Mbps Number of stations Connected to 1 network 32 Stations (Control station: 1; normal station: 31)

Connection cable Optical fiber cable Coaxial cable

Total extension cable length in 1 network

Cable name

3C-2V

5C-2V

300 m 2

500 m 2

Total extensioncable length

Length betweenstations

5C-FB Can be extended to 2.5 km (8202.5 ft.) using a repeater unit (A6BR10, A6BR10-DC).

Maximum networks 239 Maximum number of groups 32 (When in the MELSECNET/10 Mode: 9) Transmission channel format Single Bus Communications system Token bus system Synchronization system Frame synchronization system Encoding system NRZI encoding (Non return to Zero inverted) Manchester encoding Transfer format HDLC Standard (Frame format) Error control system CRC (X16 + X12 + X5 + 1) and retry by overtime.

RAS function

• Loop back function (optical loop system only) by abnormal detection and cable disconnection. • System down prevention through control station. • Error detection by the link special relay and link special register. etc.

Transient transmission N:N communications Special cyclic transmission Low speed cyclic transmission Number of boards that can be installed Maximum 4 boards

Installation slot PC PCI bus slot (half size) Exclusive slots 1 slot 5 V DC Internal current consumption 0.67 A

Weight 0.11 kg 1: MELSECNET/H board communications rate and Mode settings are performed using the MNETH Utility.

(For details, refer to Section 9.2.3) 2: Depending on the number of stations connected, there are limits to the cable length between stations. (For details, refer

to Section 6.4.2)

Page 44: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

3 - 4 3 - 4

MELSEC3 SPECIFICATIONS

3.3 Optical Fiber Cable Specification

For the optical fiber cable specification, refer to "Q Corresponding MELSECNET/H Network System Reference Manual (PLC to PLC network)".

3.4 Coaxial Cable Specification

For the coaxial cable specification, refer to "Q Corresponding MELSECNET/H Network System Reference Manual (PLC to PLC network)".

Page 45: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

4 - 1 4 - 1

MELSEC 4 FUNCTION

4 FUNCTION

This chapter explains the function of MELSECNET/H board. 4.1 Function List

The following flowchart shows the function list for MELSECNET/H board.

·········································································

RAS function

Control station switch function

Control station return control function

Loopback function (optical loop system)

Diagnostic function

Multiple transmission function (optical loop system)

Group function

Direct access to link devicesApplicationfunctions

Cyclic transmission function(Periodical communication)

Basicfunctions

Cyclic transmission function(Periodical communication)

Transient transmission function(Non-periodical communication)

Communication LX/LY

Automatic return function

Communication LB/LW

Low-speed cyclic transmission

Communication function

Routing function

Section 6.5

······································································Driver WDT function Section 4.3

···········································································

·········································································

·······································································

···························································

·······················································

················································································································ Section 12.1

Section 12.2

Section 12.3.1

Section 12.3.2

Section 12.3.3

Section 12.4

Prevention of station failure by using externalpower supply (optical loop system)

Refer to Q CorrespondingMELSECNET/H Network SystemReference Manual(PLC to PLC network)

4

Page 46: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

4 - 2 4 - 2

MELSEC 4 FUNCTION

4.2 Specifications of the Link Data Sending/Receiving Processing Time

This section explains the link data sending/receiving processing in the MELSECNET/H network system with MELSECNET/H board.

4.2.1 Link data sending/receiving processing

(1) Link data sending/receiving processing In the cyclic transmission, communication is performed using the LB/LW/LX/LY devices of the network module and MELSECNET/H board. This section explains the case when the link relay (B) is used on the personal computer side.

1) B0 on the sending station (personal computer) turns on. 2) By a link refresh, the B0 information is stored in the refresh data

storage area (LB) of the MELSECNET/H board. 3) The B0 information in the refresh data storage area (LB) is stored in

the link data storage area (LB). 4) By a link scan, the B0 information in the link data storage area (LB) is

stored in the link data storage area (LB) of the network module on the receiving station.

5) The B0 information in the link data storage area (LB) is stored in the refresh data storage area (LB).

6) By a link refresh, the B0 information is stored in the device memory storage area (B) of the CPU module.

7) B0 on the receiving station turns on.

1: The link refresh interval is set on the "Driver" screen in the MNETH Utility. 2: Set by the GX Developer’s "Station Inherent Parameters." (If not set, they are stored in the common

parameters state.) 3: If the MELSECNET/H board is a control station, it is set in the "Common Parameter Setting" screen in

the MNETH Utility. If the network module is a control station, it is set in the GX Developer’s "Common Parameters."

4: Set in the GX Developer’s "Network Refresh Parameters."

4

Page 47: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

4 - 3 4 - 3

MELSEC 4 FUNCTION

(2) Link scan and link refresh

The link scan is executed "asynchronous" with the sequence scan of the CPU

module. The link refresh is executed by the "END processing" of the CPU module.

END0Sequence scan

Link scan

END0 END0 END0

Link refresh Link refresh Link refresh

(3) Link data when a communication error station or communication stop station occurs on the network When a communication error or communication stop station occur on the network

during the data link, the receive data from those stations immediately before the error occurrence is retained. (A "communication stop station" refers to a station whose cyclic transmission has

been stopped by a peripheral device.)

(a) The receive data from a communication error station or communication stop station is retained by a normally communicating station.

(b) The receive data from other station is retained by a communication stop

station.

(Example) When a communication error has occurred to 1NS2 due to cable disconnection

1NS3

1MP1 1NS2Cable disconnection

Communication error station

1MP1

1NS2

1NS3

1NS2

1MP1

1NS2

1NS3

1MP1

1NS2

1NS3

· · · · · · Area where the link data is retained

1MP1 1NS3

Link data status after disconnection

Link data Link data Link data

Cable disconnection

Page 48: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

4 - 4 4 - 4

MELSEC 4 FUNCTION

(4) SB/SW when a communication error station/communication stop

station occurs on the network The status of whether there are any communication error/communication stop stations on the network can be checked with the link special relay/register (SB/SW).

Use them as interlocks for programs. For interlock program examples, refer to the following manual. Q Corresponding MELSECNET/H Network System

Reference Manual (PLC to PLC network)

Link special relays and registers

Link special

relay/register Description

Signal status

Off On

SB20 Indicates the communication status between

MELSECNET/H board and personal computer. Normal Abnormal

SB47 Shows the baton pass execution status of the

host.

The baton pass is

being executed

The baton pass is

stopped

SB49 Shows the cyclic transmission status of the host. Normal Abnormal

SB70

Shows the baton pass execution status of all

stations (including the host). However, it only

shows the status for the number of stations set

with parameters.

The baton pass is

being executed on

all stations

Occurrence of

communication

stop station

SW70 to 73

Shows the baton pass execution status of each

station.

Each bit corresponds to the status of each

station.

The baton pass is

being executed

The baton pass is

stopped

SB74

Shows the cyclic transmission status of all

stations (including the host). However, it only

shows the status for the number of stations set

with parameters.

All stations

normal

Occurrence of

abnormal station

SW74 to 77

Shows the cyclic transmission status of each

station.

Each bit corresponds to the status of each

station.

Normal Abnormal

SB7A, 7B

Shows the low-speed cyclic transmission status.

The transmission completion is indicated by the

on/off status of either bit SB7A or 7B.

SB7A

SB7B

Low-speed cyclic interval

SW1FC to SW1FF

Shows the redundant CPU system status

(Control or Standby) of each station.

Each bit corresponds to each station status.

Control system 1 Standby system

1: Stations in other than the redundant CPU system configuration are OFF.

Page 49: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

4 - 5 4 - 5

MELSEC 4 FUNCTION

4.3 Driver WDT function

Driver WDT function monitors the operation of the software (operating system, driver) inside the hardware by the timer function on MELSECNET/H board. When the driver cannot reset the timer of the board within the specified driver WDT monitoring time, MELSECNET/ board detects driver WDT error. Driver WDT function detects driver operation delay due to the access error from the driver to MELSECNET/H board or system high load.

(1) Driver WDT settings

For the setting method, refer to section 9.2.11.

REMARK

The driver WDT function is set to invalid as a default.

(2) When the driver WDT error has occurred The following shows the operation when driver WDT error has occurred. 1) MELSECNET/H board and the driver stop communication and are

disconnected from the network in order to avoid an erroneous output. A CPU stop error occurs when checking the MELSECNET/H board from other station on which the driver WDT error has occurred.

2) RUN LED flicks and SD LED turns ON on the MELSECNET/H board. 3) "-28158 (9202H) Driver WDT error" occurs when accessing MELSECNET/H

board from the application program in which the MELSECNET/H utility and MELSEC data link library function are used.

POINT

(1) When the multiple applications in which MELSEC data link library is used are executed, driver WDT error is returned to all the programs. However, only the

MELSECNET/H board in which the driver WDT error has occurred is recognized as an error station on the network. When using driver WDT function, set the monitoring timer considering the

margin of the personal computer load. (2) For the troubleshooting, refer to section 14.7.2.

Page 50: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

4 - 6 4 - 6

MELSEC 4 FUNCTION

MEMO

Page 51: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

5 - 1 5 - 1

MELSEC 5 EMC AND LOW VOLTAGE DIRECTIVE

5 EMC AND LOW VOLTAGE DIRECTIVE

Compliance with the EMC Directive, which is one of the EU directives, has been mandatory for the products sold within EU member states since 1996 as well as compliance with the Low Voltage Directive since 1997. To prove the compliance, manufactures must issue an EC Declaration of Conformity and the products must bear a CE marking. (1) Sales representative in EU member states

The authorized representative in EU member states will be:

Company name: Mitsubishi Electric Europe BV Address: Mitsubishi-Electric-Platz 1, 40882 Ratingen, Germany

5.1 Measures to comply with the EMC Directive

The EMC Directive sets two requirements for compliance: emission (conducted and radiated electromagnetic energy emitted by a product) and immunity (the ability of a product to not be influenced by externally generated electromagnetic energy). This section summarizes the precautions for machinery constructed with the MELSECNET/H board to comply with the EMC Directive. These precautions are based on the requirements of the EMC Directive and the harmonized standards. However, they do not guarantee that the entire machinery constructed according to the descriptions complies with the EMC Directive. The manufacture of the machinery must determine the testing method for compliance and declare conformity to the EMC Directive.

5

Page 52: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

5 - 2 5 - 2

MELSEC 5 EMC AND LOW VOLTAGE DIRECTIVE

5.1.1 EMC Directive related standards

The standards applicable to the EMC Directive are listed below. All test items were tested by installing each device on a personal computer bearing a CE certification logo. (1) Emission requirements

Standard Test item Test description Value specified in standard

EN61131-2 : 2007

CISPR16-2-3

Radiated emission 1

The electromagnetic wave which the product emits to the external space is measured.

• 30M-230MHz

QP: 40dB V/m (10m in measurement range) 2

• 230M-1000MHz QP: 47dB V/m (10m in measurement range)

CISPR16-2-1, CISPR16-1-2

Conducted emission 1

The noise level which the product emits to the power line is measured.

• 0.15 to 0.5MHz, QP: 79dB, Mean: 66dB 2

• 0.5 to 30MHz, QP: 73dB, Mean: 60dB

1: The tests were conducted installed in a control panel.

2: QP: Quasi-peak value, Mean: Average value

(2) Immunity requirements

Standard Test item Test description Value specified in standard

EN61131-2 : 2007

EN61000-4-2 Electrostatic discharge

immunity 1

An electrostatic discharge is applied to the enclosure of the equipment.

• 8kV Air discharge • 4kV Contact discharge

EN61000-4-3 Radiated, radio-frequency, electromagnetic field

immunity 1

An electric field is radiated to the product.

80% AM modulation@1kHz • 80 to 1000MHz: 10V/m • 1.4 to 2.0GHz: 3V/m • 2.0 to 2.7GHz: 1V/m

EN61000-4-4 Fast transient burst

immunity 1

Burst noise is applied to power lines and signal lines.

• AC/DC power, I/O power, and AC I/O (unshielded) lines: 2kV

• DC I/O, analog, and communication lines: 1kV

EN61000-4-5

Surge immunity 1 Lightning surge is applied to power lines and signal lines.

• AC power, AC I/O power, and AC I/O (unshielded) lines: 2kV CM, 1kV DM

• DC power and DC I/O power lines: 0.5kV CM, 0.5kV DM

• DC I/O, AC I/O (shielded), analog, communication: 1kV CM

EN61000-4-6

Conducted RF immunity 1 High-frequency noise is applied to power lines and signal lines.

0.15 to 80MHz, 80% AM modulation @1kHz, 10Vrms

EN61000-4-8 Power-frequency magnetic

field immunity 1

The product is immersed in the magnetic field of an induction coil.

50Hz/60Hz, 30A/m

EN61000-4-11 Voltage dips and

interruption immunity 1

Power voltage is momentarily interrupted.

• 0%, 0.5 period, starting at zero-crossing • 0%, 250/300 period (50/60Hz) • 40%, 10/12 period (50/60Hz) • 70%, 25/30 period (50/60Hz)

1: The tests were conducted installed in a control panel.

5

Page 53: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

5 - 3 5 - 3

MELSEC 5 EMC AND LOW VOLTAGE DIRECTIVE

5.1.2 Installation in a control panel

The installation in the control board ensures safety as well as effective shielding of personal computer-emitted electromagnetic noise. (1) Control panel

(a) Use a conductive control panel. (b) Mask off the area used for grounding when securing the top or bottom plate

to the control panel using bolts. (c) To ensure electrical contact between the inner plate and the control panel,

mask off the bolt installation areas of an inner plate so that conductivity can be ensured in the largest possible area.

(d) Ground the control panel with a thick ground cable so that low impedance can be ensured even at high frequencies.

(e) Keep the diameter of the holes on the control panel to 10cm or less. If the diameter is larger than 10cm, electromagnetic wave may be emitted. In addition, because electromagnetic wave leaks through a clearance between the control panel and its door, reduce the clearance as much as possible. Use of EMI gaskets (sealing the clearance) can suppress undesired radiated emissions. The tests by Mitsubishi were conducted using a control panel having the damping characteristics of 37dB (maximum) and 30dB (average) (measured at 3m distance, 30 to 300MHz).

(2) Wiring power and ground cables

The power supply cable and ground cable for a personal computer should be laid

out as follows: (a) Provide a ground point to the control panel near the power supply module.

Ground the LG and FG terminals of the power supply module to the ground point with the thickest and shortest ground cable possible (a thickness at least 2mm2, a length of 30cm or shorter).

(b) Twist the ground cable leading to the ground point with the power supply cable. By twisting it with the ground cable, the noise leaking from the power supply cable may be grounded at a higher rate. However, twisting the power supply cable with the ground cable may not be necessary if a noise filter is installed on the power supply cable.

Page 54: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

5 - 4 5 - 4

MELSEC 5 EMC AND LOW VOLTAGE DIRECTIVE

5.1.3 Cables

Use a shielded cable for the cable extended out of the control panel. If a shielded cable is not used or not grounded correctly, the noise immunity will not meet the required value.

(1) Grounding a shield cable (a) Ground the shield of the shield cable as near the exit as possible from the

control panel. If the ground point is not near the outlet, the cables after the ground point will cause electromagnetic induction, and will generate a higher harmonic

noise. (b) Ground the exposed shield to large area on the control panel. A clamp fitting

can be used as shown below. In this case, mask off the inner wall surface of the control panel, where comes in contact with the fitting.

Screw

Clamp fitting

Shielded cable

Paint mask

POINT Grounding with a vinyl-coated wire soldered onto the shield of the shielded cable as shown below is not recommended.

Doing so will raise the high-frequency impedance, resulting in loss of the shielding effect.

Shielded cable

Wire

Crimp terminal

(2) Treatment of the coaxial cable ground

(a) Always use a double-shielded coaxial cable (MITSUBISHI CABLE : 5C-2V-CCY) for the coaxial cables Q80BD-J71BR11. Ground the double-shielded coaxial cable by connecting its outer shield to the ground. Refer to (1) for the grounding of the shield.

Ground hereShield

(b) Make sure to install a ferrite core for the cable.

Page 55: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

5 - 5 5 - 5

MELSEC 5 EMC AND LOW VOLTAGE DIRECTIVE

(3) Grounding cables with a cable clamp

Ground the shield of the external wiring cable to the control panel with the

AD75CK cable clamp (Mitsubishi).(Ground the shield within 20 to 30cm from the module.).

Inside the control panel

20 to 30cm

AD75CK

MELSECNET/H board

For details on the AD75CK, refer to the following.

• AD75CK-type Cable Clamping Instruction Manual

5.1.4 Ferrite core

Ferrite core is effective for reducing radiated noise in the 30MHz to 100MHz frequency band. It is recommended to install a ferrite core if a shield cable extended out of the control

panel does not provide sufficient shielding effects. Install a ferrite core to the cable in the position immediately before the cable is extended out of the control panel. If the installation position is not appropriate, the

ferrite core will not produce any effect. (Ferrite core used for the tests conducted by Mitsubishi: TDK ZCAT3035-1330)

5.1.5 Noise filter (power supply line filter)

Noise filter is effective for reducing conducted noise in the 10MHz or less frequency.

(Use of a noise filter can suppress noise.) The installation precautions are described below.

(1) Do not bundle the cables on the input side and output side of the noise filter. If bundled, the output side noise will be induced into the filtered cable on the input side.

Filter

Induction

Input side(power supply side)

Output side (device side)

Filter

Input side (power supply side)

Output side (device side)

Noise will be induced when the inputand output cables are bundled.

Separately install the input andoutput cables.

Page 56: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

5 - 6 5 - 6

MELSEC 5 EMC AND LOW VOLTAGE DIRECTIVE

(2) Ground the ground terminal of the noise filter to the ground point of the control

panel with the shortest ground wire possible (approximately 10cm).

5.2 Requirements for Conformance to Low Voltage Directive

The MELSECNET/H board is out of the requirement for conformance to the Low Voltage Directive, since it does not use the power supply in the range of 50 to 1000V AC and 75 to 1500V DC.

Page 57: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 1 6 - 1

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

This section explains the operating procedure up to the point the MELSECNET/H board is operated.

6.1 Procedure Up to the Point of Operation

An outline of the procedure up to the point of MELSECNET/H board operation is explained below.

Start

Check ↓

□ Install the software package

Install the software package on a personal computer. • • • Section 8.2 Installation

Install the board

Install the board to a slot on the personal computer. • • • Section 6.3.3 Board installation

For the board with external power supply function, wire the

external power supply cable.

• • • Section 6.4.4 External power

supply cable wiring

□ Set the channel No.

Set the channel No. and confirm it with the utility. • • • Section 6.3.4 Channel No. settings

□ Check the board

Test the hardware of the installed board. • • • Section 6.5 Test

□ Wire the cables

Wire the network cables for the installed board. • • • Section 6.4 Wiring

□ Set the parameters

Set the parameters and confirm them with the utility. • • • Chapter 7 PARAMETER SETTINGS

□ Check the network

Test the cable connection and data link on the network. • • • Section 6.5 Test

□ Execute a user program

Execute a user program or utility.

Operation

REMARK

It is necessary to perform settings on the control station side in order to use the MELSECNET/H board as a normal station. Set the control station side as required. Refer to manuals listed below for the setting on the control station side. • Q Corresponding MELSECNET/H Network System Reference Manual (PLC to

PLC network) • For QnA/Q4AR MELSECNET/10 Network System Reference Manual

6

Page 58: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 2 6 - 2

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

6.2 Part Names and Settings

The names of each part of the MELSECNET/H board and their settings are explained below.

<Q80BD-J71LP21-25, Q81BD-J71LP21-25, Q80BD-J71LP21G, Q80BD-J71LP21GE, Q80BD-J71BR11>

<Q80BD-J71LP21S-25>

6

Page 59: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 3 6 - 3

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

No. Name Description

1) Indicator LED Indicates the operating status of the MELSECNET/H board. Refer to (1) in this Section.

2) Connector for connecting optical fiber cable

Connector for connecting optical fiber cable. The cable terminal is as shown below.

Optical fiber cable connection connector

LEDIN

OUT

RUNL ERR.

SD RD

IN Forward loop reception

IN Reverse loop transmission

Reverse loop receptionOUT

Forward loop transmissionOUT

Refer to Section 6.4, "Cable Connections." for wiring of the optical fiber cable.

3) Connector for connecting coaxial cable

Connector for connecting coaxial cable. The cable terminal is as shown below. Refer to Section 6.4, "Cable Connections." for wiring of the coaxial cable.

4)

Jumper 1

RP LB

Use prohibited (Fixed to RP side)

5)

DIP switch

Use prohibited (Fixed to OFF)

6) External power supply indicator LED

Indicates the status of external power supply. Refer to (2) in this Section.

7) External power supply cable connector

Connector for connecting external power supply cable The cable terminal assignment is as shown below.

EXT.PWCLASS2 ONLY

24V

24G

EXT.PW

(With the board top facing up)

LED

Coaxial cable connection connector

RUNLERR.

SD RD

Page 60: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 4 6 - 4

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

1: The jumper is provided for all of the Q80BD-J71LP21S-25, Q81BD-J71LP21-25, and the Q80BD-J71LP21-25 and

Q80BD-J71LP21G of the following serial No.

Q80BD-J71LP21-25:

The sixth digit (from the left) of the serial No. is 7 or higher.

7 -

Q80BD-J71LP21G, Q80BD-J71LP21GE: The sixth digit (from the left) of the serial No. is 4 or higher.

4 -

The serial No. of the board can be verified at the part shown in the illustration.

Page 61: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 5 6 - 5

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

(1) Indicator LED

Display the operating status of the MELSECNET/H board status.

RUNL

ERR.

SD RD

(a) When the RUN LED is ON or OFF

The same LED display as a network module.

Name Status Description

RUN ON Operating normally

OFF One of the following error has occurred.

• Board WDT error (Hardware failure)

• Board resetting (The driver is not started.) L.ERR.

ON

Communication error

One of the following error has occurred. Confirm the error with LED

status displayed on "Board information" screen of MELSECNET/H utility.

CRC: An error has occurred by a fault such as a cable fault and noise.

OVER: This error occurs when the next data is received before the last

received data is loaded into the module, and the previous data is

lost. It is caused by hardware failure in the receive area of the

network module.

AB.IF: This error occurs when the number of receive bit data indicating

"1" in the frame is more than or equal to the specified number of

data, or when the receive data is shorter than the specified data

length.

TIME: This error occurs when a baton pass was not handed to the host

station within the monitoring time.

DATA: This error occurs when abnormal code data is received.

UNDER: This error occurs when the internal processing of the send data

was not executed at a fixed interval.

LOOP: This error occurs when the forward loop line or reverse loop line

is faulty and the power to the adjacent station, which sends data

to the host station, is turned off or the hardware of the sending

station part in the loop is faulty.

OFF Operating normally SD ON Sending data

OFF Not sending data RD ON Receiving data

OFF Not receiving data

Page 62: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 6 6 - 6

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

(b) When the RUN LED is flashing

An error which is peculiar to boards has occurred.

Check on the "Event Viewer" screen and take corrective action. (Refer to Section 14.3.2)

Name Status Description

RUN Flashing

One of the following error has occurred.

(Check L ERR.LED, SD LED and RD LED.)

L.ERR. ON Operating system startup error has occurred.

SD ON Driver WDT error has occurred.(Refer to 14.7.2)

RD ON PCI bus error has occurred.

(c) When checking channel number

The status is displayed as shown below according to the current channel number while opening the "Channel No. Setting" screen. (Refer to 9.2.2)

(2) External power supply indicator LED Display the status of external power supply.

EXT.PW

Name Status Description

EXT.PW ON External power supply is being supplied.

OFF External power supply is not supplied.

Page 63: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 7 6 - 7

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

6.3 Installation

This section explains precautions when handling the MELSECNET/H board and the installation environment.

6.3.1 Handling precautions

The following are precautions to be noted when handling the MELSECNET/H board.

WARNING • While energizing, do not touch the connector.

Doing so may result in electric shock or cause malfunctioning.

CAUTION • Do not directly touch the conductive section of the board.

Doing so could result in malfunctioning or breakdown of the board. • Before handling the board, touch a grounded metal object to discharge the static

electricity from the human body. Failure to do so may cause failure or malfunction of the board.

• Handle the board in a location where there is no static electricity. Static electricity could result in failure or malfunctioning.

• The board is packed in a bag for preventing static electricity. Always place the board in this bag when storing or transporting. Otherwise, failure or malfunctioning may result.

• Take care that foreign objects such as chips or wiring debris do not get into the PC. This could result in fire, breakdowns or malfunctioning.

• Do not dismantle or rebuild the board. This will result in failure, malfunctioning, injury or fire.

• When disposing of the product, handle it as an industrial waste. • Do not drop the board or subject it to strong impact.

This will result in failure or malfunctioning of the board.

6.3.2 Installation environment

Refer to the instruction manual accompanying the PC module regarding installation of

the PC module in which the MELSECNET/H board is mounted.

CAUTION • Always ground the PC module using grounding type D (Class 3 grounding).

Otherwise, there is the risk of malfunctioning.

Page 64: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 8 6 - 8

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

6.3.3 Board installation

The following flowchart shows the board installation procedure.

Start

Power OFF

Power OFF the personal computer.

Install the board

Install the board to a slot on the personal computer.

Fix the board Fix the board to a slot on the personal computer using the board-fixing screws.

Wiring the external power supply cable

For the board with external power supply function, wire the external power supply cable.

Refer to Section 6.4.4

Power ON

Power ON the personal computer.

End

For the installation method of the board to a slot, refer to the instruction manual provided with the personal computer.

WARNING • Be sure to shut off all phases of the external power supply used by the system before performing work such as installing the board and wiring. If all power is not turned off, there is a risk of electric shock or damage to the product.

• When turning on the power and operating the module after having installed the board and doing the wiring, always attach the cover for the device module in which the board is installed. There is a risk of electric shock if the module cover is not attached.

CAUTION • Fix the board by tighten the board-fixing screws within the specified torque range. Under tightening may cause malfunction, short circuit, or malfunction. Over tightening may damage the screw and/or module, resulting in drop, short circuit, or malfunction. For the tightening torque of the board fixing screws, refer to the manual supplied with the personal computer.

• Always make sure to touch the grounded metal to discharge the electricity charged in the body, etc., before touching the board. Failure to do so may cause a failure or malfunctions of the board.

• Install the board to a personal computer which is compliant with PCI standard or PCI Express R standard (Refer to "Section 2.5 Operating Environment"). Failure to do so may cause a failure or malfunction.

• Securely mount the board to the PCI slot of the mounting device. If the board is not mounted correctly, this may lead to malfunctioning, failure or cause the board to fall.

Page 65: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 9 6 - 9

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

CAUTION • When installing the board, take care not to contact with other boards. • When mounting the board, take care not to become injured by the components

that are installed or surrounding materials.

6.3.4 Channel No. settings

Channel No. is set to each board in order to discriminate the board. The number can be set within the range of 51 to 54. Channel No. is used to specify the target board when setting parameter or executing

MELSEC data link library function. (1) Setting method

The following explains the channel No. assignment method of MELSECNET/H board. (a) Automatic assignment of channel No.

The channel No. is automatically assign to MELSECNET/H boards installed in a personal computer in the order of the PCI slot No., from 51 to 54. Check your personal computer's manual concerning the order of the PCI slot numbers.

(b) User specified assignment method

In user specified assignment, the user changes the channel No. in the "Channel No. Setting" screen in the "Board List" screen of the MNETH utility. After the change, the set assignment in "Channel No. Setting" becomes valid.

POINT

As MNETH utility products (SW0DNC-MNETH-B) (version 19V or later) store channel numbers assigned to each MELSECNET/H board, these channel numbers will automatically be set when a PCI slot is changed.

Channel numbers will automatically be assigned as follows: <When using a MELSECNET/H board that has not assigned channel numbers> • Channel numbers will be assigned in a PCI slot number order. <When using a MELSECNET/H board that has assigned channel numbers> • Previously used channel numbers will be assigned. • If previously used channel numbers are used already, unused channel numbers

will be assigned. As the utility software stores channel numbers corresponding to a MELSECNET/H board, if the utility software is reinstalled, the board will be the status that any

channel numbers are not assigned.

Page 66: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 10 6 - 10

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

6.4 Wiring

This section explains precautions when connecting cables to MELSECNET/H board. (1) Precautions on general wiring

WARNING • Be sure to shut off all phases of the external power supply used by the system

before performing work such as installing the board and wiring. If all power is not turned off, there is a risk of electric shock or damage to the product.

• When turning on the power and operating the module after having installed the board and doing the wiring, always attach the cover for the device module in which the board is installed.

There is a risk of electric shock if the module cover is not attached.

CAUTION • When removing the cable from the board, do not pull the cable.

Pulling the cable that is still connected to the board may cause damage to the board or cable, or malfunction due to bad cable contacts.

• Prevent foreign matter such as chips or wiring debris from getting on the board.

Failure to do so can result in fire, breakdowns or malfunction.

(2) Precautions on communication cable wiring

CAUTION • Solder the coaxial cable properly.

If the soldering is incomplete, it may cause the module malfunction. • For the communication cable, specialized skills and tools are required to connect

the plug and cable. The connector plug itself is a custom part.

When purchasing, consult your local Mitsubishi representative. If the connection is incomplete, this can result in a short, fire or malfunction.

• Be sure to fix communication cables connecting to the board by placing them in the

duct or clamping them. Cables not placed in the duct or without clamping may be hang freely and accidentally pulled, which may cause damage to the board or cable, or malfunction

due to bad cable contacts.

REMARK

Refer to "Q Corresponding MELSECNET/H Network System Reference Manual

(PLC to PLC network)" for details of each communication cable.

Page 67: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 11 6 - 11

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

(3) Precautions on external power supply cable wiring

CAUTION • Verify the rated voltage and pin assignment of the product and connect the external

power supply cable properly. Connecting a power supply with a different voltage rating, imperfect cable crimping or faulty wiring may cause a fire or failure.

• Use a specified tool for crimping of the cable and contacting pin. Imperfect crimping may cause malfunction.

• Verify the pin assignment and fully insert the crimped contacting pin into the connector. Imperfect insertion may cause failure or malfunction.

• Insert the wired external power supply cable into the external power supply cable connector until a click is heard. Imperfect insertion may cause failure or malfunction.

• Keep the external power supply cable away from the main circuit cable, power cables and/or load cables connected to other than programmable controllers. Ensure a distance of 100mm between them. Failure to do so may result in malfunction due to noise, surge or induction.

Page 68: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 12 6 - 12

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

6.4.1 Optical loop system

The precautions for connecting the optical fiber cable with Q80BD-J71LP21-25, Q81BD-J71LP21-25, Q80BD-J71LP21S-25, Q80BD-J71LP21G and Q80BD-J71LP21GE in an optical loop system are given below.

(1) Precautions for connecting

(a) The types of optical fiber cables that can be used vary depending on the

distance between stations.

Type

Distance between stations (m)

Q80BD-J71LP21-25,

Q81BD-J71LP21-25,

Q80BD-J71LP21S-25

Q80BD-J71LP21G

10Mbps (fixed)

Q80BD-J71LP21GE

10Mbps (fixed)

10Mbps 25Mbps

SI type optical fiber cable

(Old type: A-2P- )

L type 500 (1640.5 ft.) 200 (656.2 ft.)

Not allowed Not allowed

H type 300 (984.3 ft.) 100 (328.1 ft.)

SI optical fiber cable 500 (1640.5 ft.) 200 (656.2 ft.)

H-PCF optical fiber cable 1000 (3281 ft.) 400 (1312.4 ft.)

Broad-band H-PCF optical fiber cable 1000 (3281 ft.) 1000 (3281 ft.)

QSI optical fiber cable 1000 (3281 ft.) 1000 (3281 ft.)

GI optical fiber cable Not allowed Not allowed

2000 (6562 ft.)

62.5 GI optical fiber cable Not allowed 2000 (6562 ft.)

(b) When connecting an optical fiber cable to Q80BD-J71LP21-25, Q81BD-

J71LP21-25, Q80BD-J71LP21S-25, Q80BD-J71LP21G and Q80BD-

J71LP21GE the restrictions on the bending radius should be observed. For bending radius details, check with the cable to use.

(c) Maintain the bending radius of the optical fiber cable within the allowable

range using a tool for securing the optical fiber cable bending radius. This tool may be purchased from Mitsubishi Electric System Service, Inc, or your nearest dealer. Please inquire for more information.

(d) When laying the optical-fiber cables, do not touch the fiber cores of the cable and module connectors, and do not let dust or particles collect on them.

If oil from hands, dust or particles adhere to the cores, the accumulated transmission loss may cause malfunctions in the data link. Do not detach the cover until the cable is attached.

(e) When attaching or detaching the optical fiber cable to/from the module, pull or insert the cable by holding the cable connector securely with your hand.

( f) Connect the cable and module connectors securely until you hear a "click"

sound. (g) When attaching or detaching the optical fiber cable to/from the module,

make sure to power off the personal computer and external power supply.

Page 69: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 13 6 - 13

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

(2) Cable connection

(a) How to connect the cable Connect the IN and OUT terminals with optical fiber cables as shown below. Stations do not have to be connected in the order of station numbers. Any station number can be assigned as the control station.

Control station

IN OUT

Station No. 1

QCPU QJ71LP21-25

Normal station

IN OUT

QCPU QJ71LP21-25

Normal station

IN OUT

StationNo. 1

StationNo. 2

StationNo. n

Pow

er s

upp

ly

Pow

er s

upp

ly

n ≤ 64

Q80BD-

J71LP21-25

Personalcomputer

(b) Installing the optical fiber cable The following shows how to install the optical fiber cable:

Insert the plug by aligning the groove of the plug with the projection of the jack.

Push the plug in until the plug fixing hole catches the hook of the jack.

Pull the plug lightly in the direction of the arrow to make sure that it is securely connected.

Power off the personal computer and external power supply.

Start (Installation)

Complete

Jack

Projection

Plug

Q80BD-J71LP21-25

Groove

(c) Removing the optical fiber cable

The following shows how to remove the optical fiber cable:

Press the fixed sections of the plug in the directions ofthe arrows and pull out the plug.

Put the covers, which were attached to the plug before installation, back on both the plug and jack to store.

Power off the personal computer and external power supply.

Start (Removal)

Complete

Plug

Cover

POINT Data link operation may be executed even if IN and IN or OUT and OUT are connected with an optical fiber cable. However, the loopback function, the network diagnostic function and some of other functions do not operate normally. So, make sure to connect IN and OUT.

Page 70: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 14 6 - 14

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

6.4.2 Coaxial bus system

This section explain precautions for connection of the coaxial cable and Q80BD-J71BR11 in the coaxial bus system. (1) Precautions in connecting

(a) Restrictions on the cable length between the stations 1) When connecting between the network modules, the cable lengths

indicated in the table below should be used according to the number of stations connected. A communication error may occur if a cable length other than the lengths indicated in the table is used.

Number of stations connected

Station-to-station cable length

2 to 9 stations 10 to 33 stations

Cable type 3C – 2V 5C – 2V 5C – FB 3C – 2V 5C – 2V 5C – FB

0 to 1 m (3.28 ft.) (cable less than 1m (3.28 in.) in length cannot be used.)

1 (3.28 ft.) to 5 m (16.4 ft.)

5 (16.4 ft.) to 13 m (42.65 ft.)

13 (42.65 ft.) to 17 m (55.78 ft.)

17 (55.78 ft.) to 25 m (175.63 ft.)

25 (175.63 ft.) to 300 m (984.3 ft.)

300 (984.3 ft.) to 500 m (1640.5 ft.)

: Allowed : Not allowed 2) If there is a possibility of adding more stations to expand the existing

system, the cables should be installed by considering restriction 1) mentioned above in advance.

3) When using a repeater module (models A6BR10 or A6BR10-DC), use the station-to-station cable length for "10 to 33" stations, regardless of the number of stations connected or the number of repeater modules.

(b) Cable installation precautions

1) Install the coaxial cables at least 100 mm (3.94 in.) away from other power cables and control cables.

2) Consider to use double-shielded coaxial cables in locations where there is excessive noise.

Ground

Mitsubishi Cable · · · 5C-2V-CCY

Double-shielded coaxial cable

5C-2V connector plug can be applied to double-shielded coaxial cable.

Connect the plug to the coaxial cable inside the double-shielded coaxial cable. Ground the shielded section, external part of the double-shielded

coaxial cable, as shown above.

Page 71: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 15 6 - 15

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

(c) When connecting a coaxial cable, the following restrictions on the bending

radius must be observed.

A

r

Cable type Allowable bending radius

r [mm (in.)]

Connector

A (mm (in.))

3C – 2V 23 (0.91)

55 (2.17) 5C – 2V 30 (1.18)

5C – FB

(d) Do not pull any of the connected coaxial cables.

This may cause a faulty contact and cable disconnection, or damage the Q80BD-J71BR11.

(e) In the coaxial bus type network system be sure to connect terminal resistors in both end terminals in the network.

( f) There is a possibility that of a white oxidation product forming on the type F connector due to the use environment, but it does not occur on the portions that are fitted together, so functionally, there will be no problem.

(g) When attaching or detaching the coaxial cable to/from the module, make sure to power off the personal computer.

Page 72: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 16 6 - 16

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

(2) Cable connection

(a) Connection method

Connect the coaxial cable as shown below.

Always install a terminal resistor (sold separately: A6RCON-R75) to the stations connected at both ends. The F-type connector comes with the Q80BD-J71BR11.

1) Without a repeater module

Personalcomputer

QJ71BR11QJ71BR11Control stationStation No. 1

Normal stationStation No. n

Normal stationStation No. 2

F-type connector

Coaxial cable

Terminal resistor A6RCON-R75

(sold separately)

F-type connector F-type connector

Terminal resistor A6RCON-R75

(sold separately)

n ≤ 32

Q80BD-

J71BR11

2) With a repeater module (series connection)

A6BR10

Personalcomputer

Control station

Station No. 1 QJ71BR11

Normal station

Station No. 2

QJ71BR11

Normal station

Station No. 3

QJ71BR11

Normal station

Station No. n

F-type connector

Coaxial cable

T-type

connector

(A6BR10 accessory)

T-type

connector

(A6BR10 accessory)

Coaxial cableTerminal resistor A6RCON-R75

(sold separately)

Terminal resistor A6RCON-R75 (sold separately)

F-type connector F-type connector F-type connector

Terminal resistor A6RCON-R75

(sold separately)

n ≤ 32

Q80BD-

J71BR11

REMARK

For details about the repeater module (A6BR10), refer to the following user's manual

attached to the product: Model A6BR10/A6BR10-DC MELSECNET/10 Coaxial Bus System Repeater Module User's Manual (IB-66499)

Page 73: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 17 6 - 17

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

3) With a repeater module (branch connection)

Personalcomputer

QJ71BR11 QJ71BR11

QJ71BR11 QJ71BR11

F-type connector

Coaxial cable A6BR10

T-type connector

(A6BR10 accessory)

T-type connector

(A6BR10 accessory)

Terminal resistor A6RCON-R75

(sold separately)

Control station

Station No. 1

Normal station

Station No. 2

Normal station

Station No. 3

F-type connector F-type connector

Coaxial cable Terminal resistor A6RCON-R75

(sold separately)

Terminal resistor A6RCON-R75

(sold separately) F-type connector F-type connector

Normal station

Station No. 4

Normal station

Station No. n

Coaxial cable Terminal resistor A6RCON-R75

(sold separately)

n ≤ 32

Q80BD-

J71BR11

POINT (1) By setting stations that will be connected in future (stations that are included in

the number of stations but not actually connected) as reserved stations, a communication error can be prevented and the link scan time will not be affected.

(2) The two connectors of the F-type connector are not dedicated to IN and OUT.

A coaxial cable can be connected to either of them.

(3) A terminal resistor can be placed on either side of the F-type connector.

or

Page 74: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 18 6 - 18

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

(b) Installing the coaxial cable

The following shows how to install the coaxial cable:

Insert the plug by aligning the groove of the plug with the projection of the jack.

Rotate the plug in the direction of the arrow (clockwise) securely to the position shown in the second figure from above.

Power off the personal computer.

Start (Installation)

Complete

Plug

Jack

Groove

Projection

Q80BD-J71BR11

(c) Removing the coaxial cable

The following shows how to remove the coaxial cable:

Rotate the plug in the direction of the arrow and unhook it.

Hold the plug by hand and pull it out in the direction of the arrow as shown in the bottom diagram.

Power off the personal computer.

Start (Removal)

Complete

Q80BD-J71BR11Plug

(d) Terminal resistor Coaxial bus system needs the terminal resistor at the both ends of the

network. The user need to arrange the terminal resistor (A6RCON-R75) as it is not included in Q80BD-J71BR11.

Page 75: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 19 6 - 19

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

6.4.3 Connecting the connector for the coaxial cable

The following section explains how to attach the BNC connector (connector plug for the coaxial cable) to the cable. (1) Using a BNC connector manufactured by DDK Ltd.

The following explains how to connect the BNC-P-3-NiCAu or BNC-P-5-NiCAu to the cable.

CAUTION • Correctly solder coaxial cable connectors. Incorrect soldering may result in

malfunction.

(a) Structure of the BNC connector and coaxial cable

Parts comprising the BNC connector

Nut Washer Gasket

Plug shell

Clamp Contact

Structure of the coaxial cable

External conductor

Internal conductor

Outer sheathInsulating material

(b) How to attach the BNC connector and the coaxial cable

1) Cut the portion of the outer sheath of the coaxial cable as shown in the

figure below.

A

Cut this portion of the outer sheath. 2) Fit the nut, washer, gasket, and clamp onto the coaxial cable, as

shown below, and then loosen the external conductor.

Clamp

GasketWasher

Nut

3) Cut the external conductor, insulation material and internal conductor

to the dimensions shown below. However, cut the external conductor to the same dimension as the tapered section of the clamp and smooth it down to the clamp.

Insulation material

Internal conductor

Clamp and external conductor

C

B

Cable A

3C-2V 15mm (0.59 in.) 5C-2V, 5C-2V-CCY 10mm (0.39 in.)

Cable B C

3C-2V 6mm

(0.24 in.) 3mm

(0.12 in.)

5C-2V, 5C-2V-CCY 7mm

(0.28 in.) 5mm

(0.20 in.)

Page 76: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 20 6 - 20

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

4) Solder the contact to the internal conductor.

Solder here.

5) Insert the connector assembly in 4) into the plug shell and screw the nut into the plug shell.

POINT

(1) Note the following precautions when soldering the internal conductor and contact. • Make sure that the solder does not bead up at the soldered section.

• Make sure there are no gaps between the connector and cable insulator or they do not cut into each other.

• Perform soldering quickly so the insulation material does not become

deformed. (2) Before connecting or disconnecting the coaxial connector, touch a grounded

metal object to discharge the static electricity from the human body. Failure to

do so may result in a MELSECNET/H board malfunction.

Page 77: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 21 6 - 21

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

(2) Using a BNC connector manufactured by Canare Electric Co., Ltd.

The following explains how to connect the BCP-C3B, BCP-C5B, or BCP-C5FA to

the cable. (a) Structure of the BNC connector and coaxial cable

Crimp sleevePlug

Components of the BNC connector

Center contact pin

Structure of the coaxial cable

External conductor

Internal conductor

Outer sheathInsulating material

(b) How to connect the BNC connector and the coaxial cable 1) Thread a coaxial cable through a crimping sleeve as shown in the

figure below. When using a cable with aluminum tape, cut the tape as shown in the figure below.

Crimp sleeve

Unit: mm (inches)19 (0.75)

9(0.36)

3.5(0.14)

When cutting the tape, make a clean cut, without leaving any stray pieces or loose strands. Failure to do so may cause a short circuit or result in an improper crimp.

Cut the aluminumtape up to here.

2) Insert a center contact pin into the internal conductor. Crimp the pin

using a crimp tool to seal the gap between the center contact pin and the insulating material.

Center contact pin

Crimp

POINT

(1) Use a crimp tool specified for a BNC connector. (2) Do not crimp the junction of the insulating material and the center contact pin. (3) Horizontally insert the center contact pin into the insulating material and crimp

the pin. If the pin is on the tilt, straight it.

Page 78: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 22 6 - 22

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

3) After the crimp, check the crimp height of the crimp part. When the

crimp height at the measurement position is between 1.4mm and 1.5mm, the pin is properly crimped. If the crimp height is not between 1.4mm and 1.5mm, adjust the crimp tool and crimp the center contact pin again.

Measurement position ofcrimp height

Cross section ofthe measurement position

Crimp height value= mmA+B

2

A

B

Crimp part

1.5mm to 2.0mm

4) Hold the root of the coaxial cable and fully insert the cable into a plug. After inserting the cable, pull it lightly to check that the center contact pin is fixed. Move the crimp sleeve until it contacts with the plug.

5) Crimp the crimp sleeve using the crimp tool with attention paid to the orientations of the crimp tool and connector. Do not pull the cable when crimping the sleeve.

Crimp

POINT

Before connecting or disconnecting the coaxial connector, touch a grounded metal object to discharge the static electricity from the human body. Failure to do so may result in a MELSECNET/H board malfunction.

Page 79: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 23 6 - 23

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

6.4.4 External power supply cable wiring

This section explains how to connect the external power supply cable to the Q80BD-J71LP21S-25. (1) Connection steps

Connect the external power supply cable to the Q80BD-J71LP21S-25 in the following steps:

Refer to (2) in this sectionCheck if necessary parts have been prepared.

Connect the external power supply cableto the Q80BD-J71LP21S-25.

Make an external power supply cable.

Start

End

Refer to (3) in this section

Refer to (4) in this section

(2) Parts and tool required for making an external power supply cable To make an external power supply cable, the following parts and a tool are

required. (a) Connector set (Accessory)

Check that the following parts are contained in the connector set supplied with the product.

Parts Model Applicable cable size Quantity

Connector 1-178288-3 ---- 1

Contacting pin 175218-2 AWG#20-16 3 (1 spare)

(b) Cable Use an external power supply cable with heat-resistant vinyl sheath of 0.50 to 1.25mm2 [AWG#20-16].

(c) Tool

Be sure to use the following specified tool. Model Applicable cable size Inquiry

91558-1 AWG#20-16 Tyco Electronics

Page 80: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 24 6 - 24

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

(3) Making external power supply cable

Make an external power supply cable as follows: (a) Crimping to the contacting pin

Using a crimping tool, crimp the cable and contacting pin.

Set the contacting pin and cable in the grooves of the crimping tool and squeeze the handle tightly. For details, refer to the instructions of the crimping tool.

(b) Check the crimped condition

Check if the cable (including a part of the sheath) is evenly crimped to the contacting pin.

If only wire part is crimped and not the sheath part, or if the cable is stuck out, the cable can be cut off or

malfunction may occur. Cable

Contacting pin

(c) Connecting to the connector According to the following pin assignment, fully insert the crimped

cable to the connector until a click is heard.

1 2 3

24V 24G

Connector

Contacting pin

Pin No. Description

1 24V

2 24G

3 Open

(4) Connecting external power supply cable to board

Properly insert the completed external power supply cable to the external power supply cable connector of the Q80BD-J71LP21S-25 until a click is heard. Keep the external power supply cable away from the main circuit cable, power

cables and/or load cables connected to other than programmable controllers. (Ensure a distance of 100mm (3.94 in.) between them.)

POINT

Be sure to twist the external power supply cable.

Page 81: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 25 6 - 25

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

6.5 Test

Before executing the data link operation, check the MELSECNET/H board and the cables. Select a test item using the mode setting switch on the "Board information" screen in the MNETH Utility. The MELSECNET/H board test has the following five types.

Item Test type Description Reference

Board

confirmation Self-loopback test

This test checks the hardware of the internal circuits,

including the send/receive circuit of the MELSECNET/H

board, as well as the cables.

Section 6.5.1

Internal self-loopback test

This test checks the hardware of the internal circuits,

including the send/receive circuit of the MELSECNET/H

board.

Section 6.5.2

Hardware test This test checks the hardware inside the MELSECNET/H

board.

Section 6.5.3

Network

confirmation Test between master station

Test between slave station

This test checks the hardware of the MELSECNET/H

board, network modules and cables between two adjacent

stations can be checked.

Section 6.5.4

Forward loop test

Reverse loop test

This test checks the Q80BD-J71LP21-25, Q81BD-

J71LP21-25, Q80BD-J71LP21S-25, Q80BD-J71LP21G,

Q80BD-J71LP21GE network module and cable hardware

after all the stations have been connected with optical fiber

cable, and can also check if the IN and OUT cables have

been connected correctly.

Section 6.5.5

REMARK

The test modes are equivalent to offline. The data link cannot be executed if one station is set to the test mode during data link. Set the mode to "Online (auto. reconnection)" when performing data link.

Page 82: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 26 6 - 26

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

6.5.1 Self-loopback test

In this section, a check of the hardware, including the MELSECNET/H board itself, the transmission and reception lines in the transmission system and the cable, is conducted.

(1) Connect optical fiber cables to the IN and OUT connectors of the Q80BD-

J71LP21-25, Q81BD-J71LP21-25, Q80BD-J71LP21S-25, Q80BD-J71LP21G

and Q80BD-J71LP21GE. In the case of the Q80BD-J71BR11 (for the coaxial bus system), connect terminal resistors to the two Type F connectors.

(2) Set the mode setting in the "Board Information" screen of the MNETH Utility on

"Self-loopback test. "

Page 83: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 27 6 - 27

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

(3) Click the Board Set button in the "Board Information" screen of the MNETH

utility to run the self-loopback test, checking the LED status in the "Board Information" screen to confirm the execution state.

T. PASS blinks during the test. If T. PASS blinks 20 times and ERROR LED does not blink, the test is completed normally.

Also, if the test ends abnormally, the ERROR LED will blink as shown below to indicate the relevant error information.

(a) Optical Loop System

(Q80BD-J71LP21-25, Q81BD-J71LP21-25, Q80BD-J71LP21S-25, Q80BD-J71LP21G, Q80BD-J71LP21GE) 1) "TIME" LED lights up

• The forward loop cable is broken. • The forward loop's transmission side and reception side cables are

not connected. 2) "DATA" LED lights up

• The reverse loop cable is broken.

• The reverse loop's transmission side and reception side cables are not connected.

3) The "CRC", "OVER" and "AB.IF" LEDs light up on the F.LOOP and R.LOOP sides • The cable is defective.

4) "UNDER" LED lights up • Hardware error. • The cable was disconnected during the test.

• The cable was broken during the test.

(b) Coaxial Bus System (Q80BD-J71BR11) 1) "TIME" LED lights up

• The connector is disconnected. 2) The "CRC", "OVER" and "AB.IF" LEDs light up on the F.LOOP and

R.LOOP sides • The connector is defective.

3) "DATA" and "UNDER" LED lights up • Hardware error. • The connector was disconnected during the test.

(4) Corrective action when the test completes abnormally

Check if the cable failure is not occurred, the connector is not disconnected, and

the wiring is appropriate. If there is any error, correct the connection. When the cable has been disconnected, replace the cable. When the hardware error has occurred, replace the board.

Page 84: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 28 6 - 28

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

6.5.2 Internal self-loopback test

In this section, a check of the hardware, including the transmission and reception lines in the transmission on the MELSECNET/H board itself, is conducted.

(1) Optical fiber cables are not connected to the Q80BD-J71LP21-25, Q81BD-J71LP21-25, Q80BD-J71LP21S-25, Q80BD-J71LP21G and Q80BD-J71LP21GE (for the optical loop system). However, be careful that no external light enters

from outside the connectors. In the case of the Q80BD-J71BR11 (for the coaxial bus system), do not connect terminal resistors to the two Type F connectors.

(2) Set the mode setting in the "Board Information" screen of the MNETH utility on

"Internal self-loopback test."

Page 85: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 29 6 - 29

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

(3) Click the Board Set button in the "Board Information screen of the MNETH

utility to run the Internal self-loopback test, checking the LED status in the "Board Information" screen to confirm the execution state.

T. PASS blinks during the test. If T. PASS blinks 20 times and ERROR LED does not blink, the test is completed normally.

Also, if the test ends abnormally, the ERROR LED will blink as shown below to indicate the relevant error information.

(a) Optical Loop System

(Q80BD-J71LP21-25, Q81BD-J71LP21-25, Q80BD-J71LP21S-25, Q80BD-J71LP21G, Q80BD-J71LP21GE) 1) The "CRC", "OVER", "AB.IF", "TIME", "DATA" and "UNDER" LEDs

light up. • Hardware error.

(b) Coaxial Bus System (Q80BD-J71BR11)

2) The "CRC", "OVER", "AB.IF", "TIME", "DATA" and "UNDER" LEDs light up. • Hardware error.

(4) Corrective action when the test completes abnormally

Replace the MELSECNET/H board.

REMARK

If an error occurs in the coaxial bus system, the "M/S.E" LED or "PRM.E" LED may light up besides the "CRC", "OVER", "AB.IF", "TIME", "DATA" and "UNDER" LEDs

lighting up. When requesting repairs of the MELSECNET/H board, be sure to inform the service technician of the LED lighting state.

Page 86: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 30 6 - 30

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

6.5.3 H/W test

This test checks the internal hardware on the MELSECNET/H board.

(1) Connect the optical fiber cables to the IN and OUT sides of the Q80BD-J71LP21-25, Q81BD-J71LP21-25, Q80BD-J71LP21S-25, Q80BD-J71LP21G and Q80BD-J71LP21GE (for the optical loop system). In the case of the Q80BD-J71BR11 (for the coaxial bus system), do not connect a Type F connector or any terminal resistors.

(2) Set the "H/W test" in the mode settings in the "Board Information" screen of the

MNETH utility.

(3) Click the Board Set button in the "Board Information" screen in the MNETH

utility to run the H/W test, and check the execution state by the status of the LED's in the "Board Information" screen. T. PASS blinks during the test. If T. PASS blinks 20 times and ERROR LED does not blink, the test is completed normally. Also, if the test ends abnormally, the ERROR LED will blink as shown below to indicate the relevant error information. (a) Both the optical loop system (Q80BD-J71LP21-25, Q81BD-J71LP21-25,

Q80BD-J71LP21S-25, Q80BD-J71LP21G, Q80BD-J71LP21GE) and the coaxial bus system (Q80BD-J71BR11) in common If the following LED's light up, it means that the corresponding error has occurred, so replace the MELSECNET/H board. 1. "CRC" LED lights up ·······ROM Check Error 2. "OVER" LED lights up ······RAM Check Error 3. "AB.IF" LED lights up ·······Timer, interrupt function check error

(b) Optical loop system (Q80BD-J71LP21-25, Q81BD-J71LP21-25, Q80BD-J71LP21S-25, Q80BD-J71LP21G, Q80BD-J71LP21GE) only 1. "TIME" LED lights up ·······Forward loop broken line check error 2. "DATA" LED lights up ······Reverse loop broken line check error

(4) Corrective action when the test completes abnormally

Replace the MELSECNET/H board

Page 87: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 31 6 - 31

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

6.5.4 Station to station test

In the station to station test, the hardware of the MELSECNET/H board, network

modules and cables between two adjacent stations can be checked. The following explains how to conduct the station to station test:

REMARK

This section explains concerning the MELSECNET/H board. Refer to the following manuals concerning network module settings. • Q corresponding MELSECNET/H Network System Reference Manual (PLC to

PLC network) • QnA/Q4AR Corresponding MELSECNET/10 Network System Reference Manual

(1) Connecting the cable

(a) Optical loop system Connect IN and OUT of network modules, Q80BD-J71LP21-25, Q81BD-

J71LP21-25, Q80BD-J71LP21S-25, Q80BD-J71LP21G or Q80BD-J71LP21GE with an optical fiber cable.

Side

Station No. n

Optical fiber cable

Station to execute test

IN

OUT

Station to be tested

Side

Station No. n+1

IN

OUT

(b) Coaxial bus system Connect network modules or Q80BD-J71BR11 with a coaxial cable.

Terminal resistor

Coaxial cable

Side

Station No. n

Station to be tested

Side

Station No. n+1

Station to execute test

Terminal resistor

Page 88: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 32 6 - 32

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

REMARK

Before conducting the station to station test when three or more stations are connected by the coaxial bus system, any stations that are not tested should be

switched to offline or powered off.

Offline or powered off

Station to be tested

Station to execute test

(2) Test mode settings In the mode settings in the MNETH utility's "Board Information" screen, set the Station No. n, Station No. n + 1 stations' respective "Test between master station" and "Test between slave station" settings.

(3) Start of inter-station test

Set the mode setting on "Test between master station" or "Test between slave

station" and click the Board Set button.

This operation is performed in the order of control station normal station.

Page 89: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 33 6 - 33

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

(4) Click the Board Set button in the "Board Information" screen of the MNETH

utility to run the station to station test, checking the LED status in the "Board Information" screen to confirm the execution state. If T. PASS blinks 20 times and ERROR LED does not blink, the test is completed normally.

Also, if the test ends abnormally, the following ERROR LED or L. ERR. LED will blink as shown below to indicate the relevant error information.

(a) Optical Loop System

(Q80BD-J71LP21-25, Q81BD-J71LP21-25, Q80BD-J71LP21S-25, Q80BD-J71LP21G, Q80BD-J71LP21GE) 1) "TIME" LED lights up

• The forward loop cable is broken.

• The forward loop's transmission side and reception side cables are not connected.

2) "DATA" LED lights up • The reverse loop cable is broken. • The reverse loop's transmission side and reception side cables are

not connected. 3) The "CRC", "OVER" and "AB.IF" LEDs light up on the F.LOOP and

R.LOOP sides • The cable is defective.

4) "UNDER" LED lights up • Hardware error. • The cable was disconnected during the test. • The cable was broken during the test.

(b) Coaxial Bus System (Q80BD-J71BR11)

1) "TIME" LED lights up

• The connector is disconnected. 2) The "CRC", "OVER" and "AB.IF" LEDs light up on the F.LOOP and

R.LOOP sides • The connector is defective.

3) "DATA" and "UNDER" LED lights up • Hardware error.

• The connector was disconnected during the test.

(5) Corrective action when the test completes abnormally Check if the cable failure is not occurred, the connector is not disconnected, and

the wiring is appropriate. If there is any error, correct the connection. When the cable has been disconnected, replace the cable. When the hardware error has occurred, replace the board.

For the error occurred in the other station, check the other station.

Page 90: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 34 6 - 34

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

6.5.5 Forward loop/Reverse loop test

Using the forward loop / reverse loop test you can check the Q80BD-J71LP21-25, Q81BD-J71LP21-25, Q80BD-J71LP21S-25, Q80BD-J71LP21G, Q80BD-J71LP21GE network module and cable hardware after all the stations have been connected with optical fiber cable, and can also check if the IN and OUT cables have been connected correctly.

POINT The forward loop/reverse loop test can be used only when the Q80BD-J71LP21-25, Q81BD-J71LP21-25, Q80BD-J71LP21S-25, Q80BD-J71LP21G or Q80BD-J71LP21GE is used as the control station. If it is a normal station, carry out the test from the control station of the network where the normal station is connected.

REMARK

This section explains concerning the MELSECNET/H board.

Refer to the following manuals concerning network module settings. • Q corresponding MELSECNET/H Network System Reference Manual (PLC to

PLC network)

• QnA/Q4AR Corresponding MELSECNET/10 Network System Reference Manual

(1) Test mode settings If you are performing the forward loop test, set the station executing the forward loop test on "Forward loop test" in the mode settings in the "Board Information" screen of the MNETH utility. Also, for stations other than the station where the test is being run, treat them as Online. If you are performing the reverse loop test, set the station executing the forward loop test on "Reverse loop test" in the mode settings in the "Board Information" screen of the MNETH utility.

(2) Start of the test

Set the mode setting on "Forward loop test," "Reverse loop test" or "Online", then

click the Board Set button.

This operation is performed in the order of control station normal station.

Page 91: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 35 6 - 35

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

(3) Checking the test results

Click the Board Set button in the "Board Information" screen in the MNETH

utility to run the forward loop/reverse loop test, and check the execution state by the status of the LED's in the "Board Information" screen. If T. PASS blinks 20 times and ERROR LED does not blink, the test is completed normally. Also, if the test ends abnormally, the ERROR LED or the L.ERR.LED will blink as shown below to indicate the relevant error information. 1) The "TIME," "DATA" and "UNDER" LED's blink on the F.LOOP and

R.LOOP sides. • The cable or the other station is abnormal and loop back occurred.

2) The "CRC", "OVER" and "AB.IF" LED's blink on the F.LOOP and R.LOOP sides. • The cable is defective.

3) The "TIME" and "DATA" LED's blink on the F.LOOP and R.LOOP sides. • The wiring is wrong.

Check and correct the cable connections before and after the station where the error occurred.

(4) Corrective action when the test completes abnormally

Check if the cable failure is not occurred, the connector is not disconnected, and the wiring is appropriate. If there is any error, correct the connection. When the cable has been disconnected, replace the cable.

For the error occurred in the other station, check the other station.

Page 92: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

6 - 36 6 - 36

MELSEC 6 PROCEDURE AND SETTINGS UP TO THE POINT OF OPERATION

MEMO

Page 93: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

7 - 1 7 - 1

MELSEC7 PARAMETER SETTINGS

7 PARAMETER SETTINGS

It is necessary to set the MELSECNET/H board's parameters using the MNETH utility in order to operate the MELSECNET/H. In setting of the parameters, after the MELSECNET/H is selected, it can be set even to the details of the application functions. A flow chart of the settings is shown below.

Network settings

1) Network No.·············1 to 2392) Station No.···············1 to 64 (Optical loop),

1 to 32 (Coaxial bus)3) Control station / Normal station settingsSet the following items as necessary.4) Group No.················1 to 32

Board information settings1) Channel···············MELSECNET/H (1st board to 4th board)2) Network type·······MNET/H mode, MNET/H EX mode,

MNET/10 mode

Control station?

No

Set the following functionsas necessary.

Routing parameter setting/transmission

MELSECNET/H board information update

Connection of cables

Notnecessary

Necessary

Yes

Common parameters1) Transmission range of each station (LB/LW, LX/LY settings)2) Total number of link stationsSet the following items as necessary.3) I/O master station setting4) Reserved station setting

Supplementary settings

Control station return setting

Transmitting the common parameters to the MELSECNET/H board.

··········Refer to Section 6.4.

Opposite party setting (when accessing a multipleCPU system or redundant CPU system)

POINT

When replacing a board, you may need the channel numbers and parameter settings that were used before the replacement. When reinstalling the software package, you need to reset the channel numbers and the parameter settings. Be sure to record channel numbers and parameter settings when you have set parameters.

7

Page 94: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

7 - 2 7 - 2

MELSEC7 PARAMETER SETTINGS

REMARK

Data links can be executed even if the parameters are not set. In that case, the MELSECNET/H board operates with the default state displayed in the "Board Information" screen for the channel, network type, network No., station No., control station/normal station settings and group No. When the network type of the control station is the MELSECNET/H Extended mode, the following condition occurs in a normal station with no parameters set. In the case of a programmable controller: LINK PARA ERROR occurs. In the case of a MELSECNET/H board: "L.ERR." LED lights up. In such a case, set parameters to the normal station.

7.1 Board Information Settings

This sets the channel and network type for the MELSECNET/H board that is being used. Perform the settings in the "Board Information" screen of the MNETH utility.

(1) Channel

Select the MELSECNET/H board for which settings are performed in the MNETH utility. A maximum of 4 MELSECNET/H boards can be installed in one personal computer. The channels that are assigned to each MELSECNET/H board can be checked by clicking the Channel No. Confirm button in the "Board List"

screen.

(2) Network type The settings in the mode for the network system where the MELSECNET/H board is connected can be changed.

Item Corresponding network

MNET/H mode, MNET/H EX mode MELSECNET/H MNET/10 mode MELSECNET/10

(3) Precautions

(a) Set an identical network type for stations within the same network. If any different network type is included, the system does not operate normally.

(b) For the MELSECNET/H Extended mode, use the MELSECNET/H board of ROM version 2X or later and the SW0DNC-MNETH-B of version 11M or later. When a MELSECNET/H board incompatible with the MELSECNET/H Extended mode is used, the system does not operate normally.

(c) When connecting a QnA or A series MELSECNET/10 network module, use it in the MELSECNET/10 mode. If used in any other mode, the system does not operate normally.

(d) Set a transmission speed matched with that of the network. When an incorrect transmission speed is set, the system does not operate normally.

7

Page 95: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

7 - 3 7 - 3

MELSEC7 PARAMETER SETTINGS

7.2 Network Settings

These are the parameters used to build the MELSECNET/H network. The MELSECNET/H board’s network No., station No., control station/normal station setting and group No. are set.

7.2.1 Network No.

Set the Network No. of the network which the MELSECNET/H board is connected to. To set the network No, set it in the "Board Information" screen in the MNETH utility. (1) Valid setting range

1 to 239

(2) Caution (a) Set the same network No. to all of the devices connected to the same

network.

2NS1 CPU QJ71

1MP2 1NS3 1NS4

NetworkNo.1

CPU QJ71 QJ71

NetworkNo.1

NetworkNo.1

NetworkNo.2

7.2.2 Station No.

Set the station No. of the MELSECNET/H board. Set the station No. in the "Board Information" screen of the MNETH utility. (1) Effective setting range

The effective setting range differs depending on the type of network. • Optical loop system··········1 to 64 • Coaxial bus system··········1 to 32

(2) Caution

(a) Make settings so that the same station No. does not exist in more than one place in the same network.

7.2.3 Control station/Normal station

Set the Control station / Normal station setting on the MELSECNET/H board. Set the Control station / Normal station setting in the "Board Information" screen of the MNETH utility.

Page 96: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

7 - 4 7 - 4

MELSEC7 PARAMETER SETTINGS

7.2.4 Group No.

This sets the MELSECNET/H board's group No. Set the group No. setting in the "Board Information" screen of the MNETH utility. (1) Valid setting range

0: No group setting 1 to 9: When in the MELSECNET/10 Mode 1 to 32: When in the MELSECNET/H Mode and MELSECNET/H Extended Mode

(2) Cautions

(a) Only one Group No. can be set for 1 station.

Personal computer

MP1CPU

NS2CPU

NS3CPU

NS4

CPUNS8

CPUNS7 Personal

computer

NS6 CPUNS5

Group No. 1 Group No. 2

7.2.5 Mode setting

This sets the MELSECNET/H board's operating mode. Selection item Content

Online (auto. reconnection) Normal operation (return to system) is selected. When the system is started up, data communications is started and automatic return to system operations, etc. are carried out.

Offline Operation stop (disconnecting the station) is selected. Handshake and data communications with other stations is not done.

Forward loop test The connection state with the forward loop side's optical fiber cable is checked. The hardware test operation is selected. For details, refer to section 6.5.5, "Forward loop / Reverse loop test."

Reverse loop test The connection state with the reverse loop side's optical fiber cable is checked. The hardware test operation is selected. For details, refer to section 6.5.5, "Forward loop / Reverse loop test."

Test between master station Selects the control station side for performing the hardware test for checking the lines between two stations. For details, refer to section 6.5.4, "Station to station test."

Test between slave station Selects the normal station side for performing the hardware test for checking the lines between two stations. For details, refer to section 6.5.4, "Station to station test."

Self-loopback test Selects a hardware test of the MELSECNET/H board itself with the connection cables. For details, refer to section 6.5.1, "Self-loopback test."

Internal self-loopback test Selects a hardware test of the MELSECNET/H board itself. For details, refer to section 6.5.2, "Internal self-loopback test."

H/W test Selects the internal hardware test for the MELSECNET/H board itself. For details, refer to section 6.5.3, "H/W test."

Page 97: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

7 - 5 7 - 5

MELSEC7 PARAMETER SETTINGS

7.2.6 Parameter setting example

An example of setting the MELSECNET/H board parameters is shown below.

(1) System example

1Ns81Ns2

Control Station (1Mp1) Port No. 51

MELSECNET/H (25 Mbps) Network No. 1

to

(2) Setting screen (Board information screen)

Page 98: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

7 - 6 7 - 6

MELSEC7 PARAMETER SETTINGS

7.3 Common Parameters

The common parameters are used to set the cyclic transmission ranges of LB, LW, LX and LY that can be sent by each station in a single network. The common parameter settings are required only for the control station. The data of the common parameters are sent to the normal stations when the network starts up.

7.3.1 Send range for each station (LB/LW settings)

Assign the send ranges of the link devices (LB/LW) for each station in 16 point units for LB (start 0 to end F) and in one point unit for LW. The following example shows send range for each station (LB/LW settings) when each of 512 points is assigned to station numbers 1 to 8. (1) Setting example

1MP1 Host'ssend range

1NS2

1NS3

1NS4

1NS5

1NS6

1NS7

1NS8

1MP1

1NS2

1NS3

1NS4

1NS5

1NS6

1NS7

1NS8

1MP1

1NS2

1NS3

1NS4

1NS5

1NS6

1NS7

1NS8

1MP1

1NS2

1NS3

1NS4

1NS5

1NS6

1NS7

1NS8

1MP1

1NS2

1NS3

1NS4

1NS5

1NS6

1NS7

1NS8

Send range for each station

0

1FF200

3FF400

5FF600

7FF800

9FFA00

BFFC00

DFFE00

FFF

3FFF

1MP1 1NS2 1NS3 1NS4

1NS51NS61NS71NS8

Network No. 1

to

to

to

to

to

to

to

to

Host'ssend range

Host'ssend range

Host'ssend range

Page 99: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

7 - 7 7 - 7

MELSEC7 PARAMETER SETTINGS

(2) Screen settings (Common parameter setting screen)

Perform the setting of each station's transmission range (LB/LW settings) in the "Common parameter setting" screen in the MNETH utility.

POINT In order to validate the guarantee of 32-bit data, it is necessary that the number of points in each station's transmission range be a multiple of 20H for LB and a multiple of 2 for LW and that each station's top device No. be set so that the LB is a multiple of 20H and the LW is a multiple of 2. (For details on guaranteeing 32-bit data, refer to the "Q Corresponding MELSECNET/H Network System Reference Manual (PLC to PLC Network)".)

Page 100: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

7 - 8 7 - 8

MELSEC7 PARAMETER SETTINGS

7.3.2 Send range for each station (LX/LY settings)

Set send ranges for each station of LX/LY, which represent the amount of data that can be sent by each station in a single network in one (two) block units. The link devices (LX/LY) between the I/O master station (M station) and other station (L station) are assigned 1:1. The following example shows send ranges for each station (LX/LY settings) when each of 512 points of link devices (LX/LY) is assigned to station numbers 2 to 4, using station number 1 (host) as the I/O master station of block 1. (1) Setting example

1MP1 1NS2 1NS3 1NS4 1NS8X0 Y0 X Y X Y X Y X Y

X1FFF Y1FFF

X1000

X11FFX1200

X13FFX1400

X15FF

Y1400

Y15FF

Y1000

Y11FFY1200

Y13FF

Block 1

1MP1(M station)

I/O master station(MNELSECNET/H board)

1NS2(L station)

1NS3(L station)

1NS4(L station)

1NS8

Network No. 1

Actual I/O Actual I/O Actual I/OActual I/O

to

to

to

to

to

to

Page 101: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

7 - 9 7 - 9

MELSEC7 PARAMETER SETTINGS

(2) Screen settings (Common parameter settings)

To set the transmission range for each station (LX/LY settings), perform the settings in "Common parameter settings" in the MNETH utility.

(3) Precaution Duplicate link device ranges cannot be assigned to each station between block 1 and block 2. If the network module is the I/O master station, they must be set not to duplicate with the actual I/O (the range of input/output numbers to which the actual module is installed) of the of the CPU module mounted.

500H

7FFH

200H

5FFH

LX/LY settings (1) LX/LY settings (2)

Block 2

Block 1

Link deviceCPU device

X/Y

Duplicate

Duplicate

0

1FFFH

2FFH

1FFFH 1FFFH

ActualI/O

Page 102: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

7 - 10 7 - 10

MELSEC7 PARAMETER SETTINGS

7.3.3 Total station

This sets the total number of control stations, normal stations and reserved stations in a single network. Set the total number of link stations in the "Common parameter settings" screen in the MNETH utility.

CPU QJ71

1Ns3

Reserved Station

CPU QJ71

1Ns2

CPU QJ71

1Ns4

CPU QJ71

1Ns6

CPU QJ71

1Ns7

CPU QJ71

1Ns8

CPU QJ71

1Ns5

Total station8 MELSECNET/H Board

1Mp1

7.3.4 Designation of the I/O master station

The master station in each block for 1:1 communication using LX/LY can be specified as I/O master station regardless of either the control station or the normal station. Each of block 1 and block 2 has one I/O master station, which is set by the send range (LX/LY) of each station in each block. Specify the I/O master station with the "Common parameter setting" screen of the MNETH utility if the MELSECNET/H board is control station.

7.3.5 Reserved station setting

The reserved station designation function is used to prevent stations to be connected in future (stations that are not actually connected but included in the total number of (slave) stations of a network) from being treated as faulty stations. The reserved stations do not affect the link scan time; they do not slow down the network even if used as reserved stations. Specify the reserved station with the "Common parameter setting" screen of the MNETH utility.

7.3.6 Pairing Setting

In the pairing setting, station numbers of network modules composing a redundant CPU system can be set as pairs.

Q Corresponding MELSECNET/H Network System Reference Manual (PLC to PLC network)

Page 103: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

7 - 11 7 - 11

MELSEC7 PARAMETER SETTINGS

7.4 Supplementary Setting

The supplementary settings are included in the common parameter settings. They can be used when more specific applications are required. The default settings should normally be used. The supplementary settings (common parameter settings) are required only for the control station. The parameters are sent from the control station to normal stations when the network starts up. Perform the supplementary settings with the "Common parameter setting" screen of the MNETH utility.

Page 104: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

7 - 12 7 - 12

MELSEC7 PARAMETER SETTINGS

7.5 Control Station Return Setting

This parameter is used to designate the type of station used by the control station when returning to the network in the control station return control. Select this parameter to make the control station return as a normal station without stopping the baton pass in the system in operation. The control station return setting is required only for the control station.

(1) When "Return as control station" is selected (default)

The baton pass (cyclic transmission, transient transmission, etc.) temporarily stops because the control station sends the parameters to the normal stations and returns to the network.

(2) When "Return as normal station" is selected

The control station returns to the network as a normal station, without stopping the baton pass in the network.

Select

REMARK

• When "Return as control station" is selected, the network stop time becomes longer because the baton pass is stopped, but the common parameters can easily be changed only by resetting the Board of the control station.

• If "Return as normal station" is selected, the network does not stop because the control station returns to the network without stopping the baton pass. However, it is necessary to reset the CPUs of all the stations after changing the common parameters of the control station while the network is in operation. If only the board resetting is performed, the MELSECNET/H board (Control station) detects the parameter mismatch error and disconnects it.

Page 105: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

8 - 1 8 - 1

MELSEC 8 INSTALLING AND UNINSTALLING SOFTWARE PACKAGE

8 INSTALLING AND UNINSTALLING SOFTWARE PACKAGE

The methods for installing and uninstalling the software package are explained. 8.1 Installation and Uninstallation Precautions

The following are the precautions when installing and uninstalling the software

package. • Log on as a user having administrator authority. • Make sure to close other applications running on Windows (including resident

software such as antivirus software) before installation and uninstallation. • The installer may not work normally because the update program of operating

system or other companies' software such as Windows Update and Java update may

start automatically. Please install the driver after changing the setting of the update program not to start automatically.

• Check if the display settings on the [Device Manager] or other relevant functions are

correct, and install an appropriate display driver. Or update the Windows operating system.

• The language switching function of the operation system set by "Regional and

Language Options" on the Control Panel screen is not supported. The installation or uninstallation may not work normally if the language setting is changed.

• Default settings are set to the channel numbers and the parameters at the installation.

Therefore, when a reinstallation of the software package is required, record the existing settings in advance, and reset the settings after the reinstallation. (Refer to Chapter 7)

• Enable the .NET Framework 3.5 (including .NET 2.0 or 3.0) in "Turn Windows features on or off" on the control panel.

• When the software package has been installed in the environment that the creation

of 8.3 filename is disabled, the software package may not be uninstalled. Enable the creation of 8.3 filename before installing the software package. For the method on how to check and change the status of 8.3 filename creation to

enable/disable, refer to the website of Microsoft Corporation. • A network drive cannot be specified as the installation destination. • When using SW0DNC-MNETH-B version 30G or later, apply Service Pack1 and

Security Update for Windows (KB3033929) in Windows 7 and Windows Server 2008 R2.

• In Windows Server 2016, apply Windows Updates (KB4132216, KB4091664,

KB4465659, and KB4480977). • When installing the software package, enable "User Account Control: Detect

application installations and prompt for elevation" in 'Local Security Policy' in

Windows.

8

Page 106: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

8 - 2 8 - 2

MELSEC 8 INSTALLING AND UNINSTALLING SOFTWARE PACKAGE

8.2 Installation

This section explains a procedure for installing software package. (1) Installation

1) Insert the CD-ROM to the CD-ROM drive. 2) Double click the "Setup.exe" file on the CD-ROM. 3) By following the on-screen instructions, select or enter the necessary

information. (When the instruction displayed on the screen is not effective, refer to 14.2.3) 4) Restart the personal computer.

(2) When installation is completed normally

When the installation is completed normally, the following utilities are registered.

(a) Utility

When the installation is completed normally, the utilities shown below are

registered in the "Start" *1 of Windows.

*1: [Start screen] - [All apps] or [Start] - [All Programs]

Folder Name Description

[MELSEC]

MELSECNET_H Utility (Board) Starts MELSECNET/H Utility.

It is a utility to set boards and display the status.

Device Monitor Utility (Board) Starts Device Monitor Utility.

It is a utility to monitor devices and change the current value.

MELSEC Data Link Library Reference Manual

(Board) Displays MELSEC Data Link Library Reference Manual.

When the MELSEC Data Link Function HELP and a manual are registered

both, refer to the manual.

Name SW0DNC-MNETH-B SW1DNC-CCBD2-B SW1DNC-MNETG-B SW1DNC-CCIEF-B

MELSEC Data Link Library

Reference Manual (Board) 27D or later 1.15R or later 1.17T or later 1.06G or later

MELSEC Data Link Library

Reference Manual 23Z to 26C 1.11M to 1.14Q 1.12N to 1.16S 1.02C to 1.05F

MELSEC Data Link Function

HELP 22Y or earlier 1.10L or earlier 1.11M or earlier -

POINT

• In order to view the manuals, Adobe Reader is required. Adobe Reader can be downloaded from the Adobe Systems Incorporated web site.

• When using 64-bit version operating system, the icon may not be displayed even when Adobe Reader is installed.

8

Page 107: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

8 - 3 8 - 3

MELSEC 8 INSTALLING AND UNINSTALLING SOFTWARE PACKAGE

(b) MELSEC Data Link Library

MELSEC data link library is used for the following software packages in

common. When the utilities are installed on the same personal computer, the newer MELSEC data link library of the software package is enabled.

• SW0DNC-MNETH-B • SW1DNC-CCBD2-B • SW1DNC-MNETG-B

• SW1DNC-CCIEF-B

(c) Driver When installing the board on the personal computer after the installation of the software package, the driver is installed automatically.

When the driver installation is completed normally, the following driver is displayed on the Device Manager screen of Windows.

Device Driver

MELSECNET/H Device PCI MELSECNET/H Controller

(d) Service application To prevent a personal computer from entering the power save mode

(hibernate, sleep), MELSECPowerManager is installed automatically. For details of MELSECPowerManager, refer to Appendix 10.

(3) When installation is aborted or failed

When the installation is aborted or failed, take corrective actions following the

troubleshooting. (Refer to Section 14.2.1)

Page 108: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

8 - 4 8 - 4

MELSEC 8 INSTALLING AND UNINSTALLING SOFTWARE PACKAGE

8.3 Uninstallation

This section explains a procedure for uninstalling the software package. (1) Uninstallation procedure

Uninstall the software package from the control panel of Windows.

POINT

• If the dialog box confirming the deletion of common files appears at uninstallation, make the setting to keep all common files.

If deleting common files, other applications may not operate normally. • MELSECPowerManager may not be uninstalled depending on the installation

state which affects the other installed software packages.

For details of MELSECPowerManager, refer to Appendix 10.

(2) When uninstallation is completed normally

When the uninstallation is completed normally, the icons registered in the

Windows Start menu are deleted.

(3) When uninstallation is failed When the installation is aborted or failed, take corrective actions following the troubleshooting. (Refer to Section 14.2.2)

Page 109: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

9 - 1 9 - 1

MELSEC 9 UTILITY OPERATIONS

9 UTILITY OPERATIONS

9.1 Starting and Ending Utility

The following explains the operating method to start/end the utility.

9.1.1 Starting a utility

Start the MNETH utility by clicking [MELSEC] — [MELSECNET_H Utility(Board)] registered in the start*1 of Windows R .

*1: [Start screen] - [All apps] or [Start] - [All Programs]

POINT

When a utility is run while user account control (UAC) is available, the following

warning screen appears. Select "Allow" or YES button to run the utility.

For details on how to prevent this screen from being displayed, refer to Appendix 8.

9

Page 110: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

9 - 2 9 - 2

MELSEC 9 UTILITY OPERATIONS

9.1.2 Ending a utility

The following explains how to end the utility.

To end the MNETH utility, click the Exit button at the bottom of the utility screen.

Click!

9.2 MNETH Utility

This section explains the MNETH utility's screen explanations and operation methods.

9

Page 111: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

9 - 3 9 - 3

MELSEC 9 UTILITY OPERATIONS

9.2.1 Screen configuration and basic operations

The following explains the screen configuration displayed at starting the MNETH utility.

Item Description Reference

Tab

Board list Displays the list of MELSECNET/H boards installed in the

personal computer. Section9.2.2

Board information Sets the own station information and each setting item. Section 9.2.3 to 9.2.5

Loop monitor Displays the loop status of the host station. Section 9.2.6

Each sta. status Displays the status of each station. Section 9.2.7

Error history monitor Displays the error history. Section 9.2.8

Memory I/O Test Diagnoses the dual-port memory and I/O ports used by the

MELSECNET/H board.

Section 9.2.9

Target Sets the access target for accessing a multiple CPU system or

redundant CPU system.

Section 9.2.10

Driver Sets the link device access method and each monitoring time. Section 9.2.11

Version Displays the utility version. -

Device Monitor button Starts device monitor utility. -

Exit button Ends the MNETH utility. -

Manual button Displays this manual. 1 -

The common screens configuration for other setting are as shown below.

Item Description

Check button Checks the settings.

OK / Cancel button Applies/discards the settings and closes the window.

Manual button Displays this manual. 1

1: Adobe Reader is required. Adobe Reader can be downloaded from the Adobe Systems Incorporated web site.

Page 112: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

9 - 4 9 - 4

MELSEC 9 UTILITY OPERATIONS

9.2.2 Board list screen operation

This operation displays the hardware information, and confirms and sets the channel No. set in the MELSECNET/H board. (1) Board List Screen

Item Content

Channel No. Displays the MELSECNET/H board's channel No.

Board Name

Displays the model name of the connected MELSECNET/H board. The contents displayed on the screen and the corresponding MELSECNET/H board's model name are as shown below.

Screen Display Model Name

MNET/H (Optical fiber) Q80BD-J71LP21-25

Q81BD-J71LP21-25

Q80BD-J71LP21S-25

Q80BD-J71LP21G

Q80BD-J71LP21GE

MNET/H (Coaxial) Q80BD-J71BR11

IRQ No. Displays the IRQ used by the MELSECNET/H board.

Port Memory Displays the range of dual-port memory occupied by the MELSECNET/H board.

I/O Port Displays the range of the I/O ports occupied by the MELSECNET/H board.

Version Displays the MELSECNET/H board's ROM version.

Channel No. Confirm Button Displays the "Channel No. Confirm" screen. For details, refer to (2), "Channel No. Confirm."

Channel No. Setting Button Displays the "Channel No. Setting" screen. For details, refer to (3), "Channel No. Setting."

REMARK

Channel numbers may change due to board replacements or alternations of PC

device configurations. In such cases, check channel numbers and parameter settings with the “Board list” and “Board information” screens.

Page 113: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

9 - 5 9 - 5

MELSEC 9 UTILITY OPERATIONS

(2) Channel No. Confirm Screen

Clicking the Channel No. Confirm screen in the "Board List" screen displays

the following dialog box, and enables the user to check the channel No. by the status of the display LED's on the MELSECNET/H board.

Item Content

Channel No. Displays the channel No. of the installed MELSECNET/H board.

LED Displays the display LED lighting on status on the MELSECNET/H board.

(3) Channel No. Setting Screen

Clicking the Channel No. Setting screen in the "Board List" screen displays

the following dialog box, and enables the user to change the channel No. of the MELSECNET/H board installed in the personal computer 1.

Item Content

Channel Current Value Displays the current channel No.

Setting Value Changes the channel No. (Setting range: 51 to 54)

1: Before changing channel No., exit Device Monitor Utility and all of user programs that are using the MELSEC data link library.

Page 114: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

9 - 6 9 - 6

MELSEC 9 UTILITY OPERATIONS

9.2.3 Board information screen operation

The Board information screen is used to set and display various information about the installed MELSECNET/H board.

Item Content

Channel Sets a channel (MELSECNET/H board) to be used. Own Station Information Displays information and changes setting on the host.

Board Set button Resets the MELSECNET/H board to renew the information of the MELSECNET/H board selected in Channel.

Mode

Performs mode setting for the MELSECNET/H board, and displays the present value. Mode Description

Online (auto. reconnection) Used for normal communication.

Offline Enters the state in which there is no connection to the network.

Forward loop Check the forward loop status. Reverse loop Check the reverse loop status.

Test between master station Perform station to station test. (Select at control station)

Test between slave station Perform station to station test (Select at normal station)

Self-loopback test Check the hardware including the cable and communication circuit for transmission system by the MELSECNET/H board.

Internal self-loopback test Check the hardware including the communication circuit for transmission system by the MELSECNET/H board.

H/W test Check the hardware of the MELSECNET/H board.

Transmission Speed

Selects the transmission speed. When the Q80BD-J71LP21G, Q80BD-J71LP21GE and Q80BD-J71BR11 is used and when "MNET10 Mode" is selected in the NET Mode, "25 Mbps" cannot be selected. Transmission speed Description

10 Mbps Selected when the MELSECNET/H (10 Mbps) is connected. 25 Mbps Selected when the MELSECNET/H (25 Mbps) is connected.

Page 115: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

9 - 7 9 - 7

MELSEC 9 UTILITY OPERATIONS

Item Content

NET mode

Selects the network where the MELSECNET/H board is connected. When "25 Mbps" is selected in the transmission speed item above, this item cannot be selected. Net Mode Description

MNET/H Mode Selected when the MELSECNET/H is connected. MNET/10 Mode Selected when the MELSECNET/10 is connected. MELSECNET/H Extended mode 1

Selected when the MELSECNET/H is connected and MELSECNET/H Extended mode is used.

Reconnect

Designates by station type when a control station reconnects. This item is displayed on the screen and can be selected only when the MELSECNET/H board is a control station. Reconnect Description

Return as control station Causes the MELSECNET/H board to reconnect as a control station.

Return as normal station Causes the MELSECNET/H board to reconnect as a normal station.

LED

Display the operation status of the MELSECNET/H board. LED name LED status

RUN Normal data link MNG Control station

S.MNG Sub-control station D.LINK During data link

T.PASS Baton pass execution 2

SW.E Switch setting error

M/S.E. Duplicate error on station number and control station

PRM.E. Parameter error CRC Code check error

OVER Data entry delay error AB.IF All receiving data are 1. TIME Time over DATA Reception data error

UNDER Transmission data error LOOP Forward/reverse loop receiving error

SD Data being transmitted

RD Data being received

Routing Param. Setting

Button

Displays the "Routing Parameter Setting" screen. Refer to section 9.2.4 Routing Parameter Setting operation for details.

Routing Param. Transfer

Button Transfers the routing parameter that has been set.

Common Param. Setting

Button

Displays the "Common Parameters Setting" screen This button is displayed only when the MELSECNET/H board is a control station. Refer to section 9.2.5, "Common Parameters Setting Screen operation" for details.

Common Param. Transfer

Button

Transmits the set common parameters. This button is displayed only when the MELSECNET/H board is a control station.

1: When assigning 2000 bytes or more to the number of link points sent by a station,

set all stations including control stations and normal stations to the MELSECNET/H Extended mode.

2: If T.PASS LED flickers at uncertain intervals, take the corrective action by referring to Section 14.4.

Page 116: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

9 - 8 9 - 8

MELSEC 9 UTILITY OPERATIONS

9.2.4 Routing Parameter Setting screen operation

The routing parameter setting screen is used to set the transfer destination, relay destination network number, and relay destination station number.

POINT

(1) The routing parameters are common with channels No. 51 to 54. They cannot be set one channel No. at a time.

(2) Up to 64 routine parameters can be set.

Item Content

No. Input the number of the line to set or change. (Setting range : 1 to 64)

Transfer to Network No. Input the transfer destination network number

Intermediate Network No. Input the relay destination network number

Intermediate Sta. No. Input the relay destination station number.

Set button Enters the data that has been set in Set data.

Setting Data Displays a list of data that has been set so far.

Change button Selecting a line to be changed and clicking the button will change the entered set data. (Double-clicking the line to be changed also does the same operation.)

Delete button Selecting a line to delete and clicking the button will delete the entered set data.

Channel

Selects the channel No. where the settings are to be changed for the network configuration. If MELSECNET/10 does not exist on the routing path, select "Composition without

MELSECNET/10 network" 1.

1: If a MELSECNET/10 board exists in the network, do not select the checkbox. Due to the maximum transmitted data size (1920 byte for the configuration which is not including MELSECNET/10 and 960 byte for the configuration which is

including MELSECNET/10) differs depending on the network system configuration, the data will be missed at transmission via MELSECNET/10.

Page 117: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

9 - 9 9 - 9

MELSEC 9 UTILITY OPERATIONS

9.2.5 Common parameter setting screen operation

This operation sets the common parameters necessary for establishing data links. Display is possible only when the MELSECNET/H board is in the control station.

(1) B, W setting screen

Item Content

Channel Selects the channel (MELSECNET/H board) performing the settings.

Total Station Input the total number of stations (including the control station) in the network that the MELSECNET/H board is the control station for.

Monitoring Time Sets the link scan time monitoring time.

Send Range for Each Station

Sta. No. Input the station No. of the station to be set or changed.

Pairing

Set whether pairing is enabled or not. • If "Do Pairs" is selected, settings for the next station No. become the same as those for

the current one, being displayed with its "Send Range for Each Station" area masked. • Pairing is not available if the last station No. is selected for "Sta. No. "

LB Input the LB (Link relay) range.

LW Input the LW (Link register) range.

Low Speed LB Input the range of the LB (link relay) used in the low speed cyclic transmission function.

Low Speed LW Input the range of the LW (link register) used in the low speed cyclic transmission function.

Set button Registers the set contents in each station's transmission range.

Send Range for Each Station Displays the set data contents up to the present time in one list.

Change button Select the line to change, then when the button is clicked, the data which are registered can be changed. (If the line to be changed is double clicked, the same operation can be performed.)

Delete button Select the line to change, then when the button is clicked, the data which are set can be deleted.

Settings Clear Button Initializes the contents of all the B and W settings registered in the "Common parameter setting" screen.

Page 118: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

9 - 10 9 - 10

MELSEC 9 UTILITY OPERATIONS

(2) X, Y setting screen

Item Content

Channel Selects the channel (MELSECNET/H board) performing the settings.

Block 1 setting (Block 2 setting) Switches the block that is set.

Total station Input the total number of stations (including the control station) in the network that the MELSECNET/H board is the control station for.

Monitoring Time Sets the link scan time monitoring time.

I/O Master Sta. Input the station No. of the I/O master station.

Send Range for Each Station

Sta. No. Input the station No. of the station to be set or changed.

Sending Range (M L)

Assigns link devices (LX, LY) 1 to 1 between the I/O master station (M station) and other stations.

Sending Range (M L)

Assigns link devices (LX, LY) 1 to 1 between the I/O master station (M station) and other stations.

Set button Registers the set contents in each station's transmission range.

Send Range for Each Station Displays the set data contents up to the present time in one list.

Change button Select the line to change, then when the button is clicked, the data which are registered can be changed. (If the line to be changed is double clicked, the same operation can be performed.)

Delete button Select the line to change, then when the button is clicked, the data which are set can be deleted.

Setting Clear Button Initializes the contents of all the X and Y settings registered in the "Common parameter setting" screen.

Page 119: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

9 - 11 9 - 11

MELSEC 9 UTILITY OPERATIONS

(3) Reserved station setting screen

Item Content

Channel Selects the channel (MELSECNET/H board) performing the settings.

Sta. No. This sets reserve stations. If a check mark is placed in the check box, that station is set as a reserve station.

Page 120: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

9 - 12 9 - 12

MELSEC 9 UTILITY OPERATIONS

(4) Supplementary setting screen

Item Content

Channel Selects the channel (MELSECNET/H board) performing the settings.

Constant scan Sets a constant link scan. (Setting range: 1 to 500 ms) If it is not run, do not input anything.

Maximum No. of returns to system stations in 1 scan

Sets the number of stations with transmission errors that can undergo return to system in 1 link scan.

With multiplex transmission Set when running the multiplex transmission function.

There is a data link through the sub-controlling station when the controlling station is down.

Set when executing the control station move function.

Secured data send Set when preventing data separation of link data in station units in cyclic transmissions. 1 Secured data receive

Transient setting

Maximum No. of transients in 1 scan.

Sets the number of transients that can be executed in one link scan by one network (total for 1 network as a whole). (Valid setting: 1 to 255 times; Default: 2 times)

Maximum No. of transients in one station.

Sets the number of transients that can be executed in one link scan by one station. (Valid setting: 1 to 10 times; Default: 2 times)

Specification of low speed cyclic transmission

Transmit data of one station in 1 scan

Set in cases such as when data to be transmitted to another station are collected and sent one station at a time in 1 link scan.

Fixed time cycle interval setting

Carries out low speed cyclic transmission at the preset intervals. (Valid setting interval: 1 to 65535 s.)

System times Carries out low speed cyclic transmission in accordance with the preset time. (Settings: Year, Month, Day, Hour, Minute, Second)

1: Data separation prevention is when older data with the meaning of 2-word (32 bit) link data such as the positioning unit’s current position are prevented from being separated into new data with 1-word (16 bit)

units due to cyclic transmission timing.

Page 121: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

9 - 13 9 - 13

MELSEC 9 UTILITY OPERATIONS

9.2.6 Loop monitor screen operation

This screen is used to monitor the loop status of the host.

Item Content

Channel Sets the channel (MELSECNET/H board) perform loop monitor.

Own Station Information Displays the host information.

Loop Status

Displays the host's loop status using characters and graphics.

Also, images are changed as shown below according to the connection status.

Forward loop : NormalReverse loop : Normal

Display the same regardless of the loop status.

>

<For Q80BD-J71BR11>

Forward loop : NormalReverse loop : Abnormal

Forward loop : AbnormalReverse loop : Normal

Data link by loop-back Forward loop : AbnormalReverse loop : Abnormal

<For Q80BD-J71LP21-25,Q81BD-J71LP21-25,Q80BD-J71LP21S-25,Q80BD-J71LP21G and Q80BD-J71LP21GE

Loop Information Displays current loop status.

Datalink Information Displays the current data link status.

Page 122: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

9 - 14 9 - 14

MELSEC 9 UTILITY OPERATIONS

9.2.7 Each station status screen operation

This screen displays communication status and loop status for each station.

Item Content

Channel Sets the channel (MELSECNET/H board) perform each station status.

Own Station Information Displays the host information.

Each Station Status

Displays the communication status and loop status for every link station that is set using parameters.

(Red)

(Yellow)

(Gray)

Transfer Status Invalid Sta.·············· Indicates a baton-pass status error.

Loop Status Invalid Sta.··················· Indicates a forward/reverse loopstatus error.

Reserve Sta.···································· Indicates the station that is set as a reserved station. However, this is valid only when the host is executing cyclic communication.

(White) Transfer Status Normal Sta.············ Indicates the station in normal communication.

(Aqua) Current Control Sta.························· Indicates the station that is actually operating as the control station.

(Blue) Select Control Sta.··························· Indicates the station that is set as the control station.

Page 123: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

9 - 15 9 - 15

MELSEC 9 UTILITY OPERATIONS

9.2.8 Error history monitor screen operation

This screen displays the history of loop errors, communication errors, and transient transmission errors.

POINT (1) Up to 16 items are stored in the loop switch data history.

When there are more than 16 items, items will be erased from the history, starting with the oldest one. (From old to new: No. 1 to No. 16)

(2) Refer to the following manuals for details on the error code and error type of a specific transient transmission error that may be displayed: • Q Corresponding MELSECNET/H Network System Reference Manual (PLC

to PLC network) • For QnA/Q4AR MELSECNET/10 Network System Reference Manual

Item Content

Channel Sets the channel (MELSECNET/H board) perform error history monitor.

Own Station Information Displays the host information.

Loop Switching

Displays the loop change factors and status after changing. (For optical loop)

Item Description

Sta. No. Displays the station number that requested a loop switch and loop back.

Factor Displays the factor by which loop switch and loop back were executed.

Switched to Displays the data link status after a loop switch.

Page 124: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

9 - 16 9 - 16

MELSEC 9 UTILITY OPERATIONS

Item Content

Transient Transmission Error

Displays the error code occurring when transient transmission was executed at the host.

Item Description

Error code Displays the code of the error occurring due to transient transmission.

Error type Displays the type of the error occurring due to transient transmission.

Error Count 1

Displays the number of error occurrences. Item Description

Loop Switching Displays the number of loop switch/loopback.

Transient Transmission

Displays the number of error occurrence due to transient transmission.

Retry Displays the number of retries (retry at communication error).

Link Trouble Displays the number of line error occurrence.

Communication Error

Item Description

UNDER Displays the number of UNDER errors.

CRC Displays the number of CRC errors.

OVER Displays the number of OVER errors.

Short Frame Displays the number of short frame (data message is too short.) errors.

Abort Displays the number of AB.IF errors.

Time Out Displays the number of Time Out errors.

Exceeding 2 kb Displays the number of Exceeding 2Kb errors.

DPLL Error Displays the number of DPLL (Cannot identify data normally due to synchronization/modulation) errors.

Page 125: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

9 - 17 9 - 17

MELSEC 9 UTILITY OPERATIONS

1 : The following explains the error causes and the corresponding corrective actions.

In addition to Error history monitor screen, they can be confirmed using the following link special registers (SW). For

more information of each link special registers (SW), refer to "Q Corresponding MELSECNET/H Network System

Reference Manual (PLC to PLC network)".

Item Link special

register Error cause Corrective action

Loop Switching SW00CEH Power ON/OFF status of the station, cable fault, noise, etc. 2

Transient

transmission SW00EEH

Power ON/OFF status or CPU module error of the external

station, cable fault, noise, etc.

Confirm the error code of

the transient transmission

error, and then take the

corrective action.

Retry SW00C8H,

SW00C9H Power ON/OFF status of the station, cable fault, noise, etc. 2

Link Trouble SW00CCH,

SW00CDH

Power ON/OFF status of the adjacent station, cable fault, noise,

etc. 2

UNDER SW00B8H,

SW00C0H Power ON/OFF status of the adjacent station, cable fault, etc. 2

CRC SW00B9H,

SW00C1H

Disconnection status of the station that sends data to the

corresponding station, cable fault, hardware error, noise, etc. 2

OVER SW00BAH,

SW00C2H Cable fault, Hardware error, noise, etc.

2

Short Frame SW00BBH,

SW00C3H 2

Abort SW00BCH,

SW00C4H

Disconnection status of the station that sends data to the

corresponding station, cable fault, hardware error, noise, etc. 2

Time Out SW00BDH,

SW00C5H Insufficient data link monitor time, cable fault, noise, etc. 2

Exceeding 2Kb SW00BEH,

SW00C6H Cable fault, Hardware error, noise, etc.

2

DPLL Error SW00BFH,

SW00C7H 2

2 : Basically, the number of times for each error occurrence does not matter. However, following corrective actions are

required, if the count value raises frequently during operation.

(1) Confirm the power ON/OFF statuses of the host station and other station.

(2) Check the cable and connector (connector disconnection, loose connection, cable breakage, cable length, etc.).

(3) Conduct self - loopback test, internal self-loopback test and hardware test.

(4) Conduct station to station test and forward/reverse loop test.

(5) Wire the cable again with reference to the network module manual and MELSECNET/H board manual. In addition,

install the devices again with reference to the user’s manual for the CPU module.

Page 126: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

9 - 18 9 - 18

MELSEC 9 UTILITY OPERATIONS

9.2.9 Memory, I/O Test screen operation

This operation diagnoses between the MELSECNET/H board and personal computer.

POINT

(1) If you are starting the diagnosis, do so after disconnecting the external cables.

(2) If you desire to switch screens during the diagnosis, click the Stop button,

switching screens after stopping the diagnosis.

Item Content

Channel Sets the channel (MELSECNET/H board) perform the memory, I/O diagnosis.

Diagnosis Displays the address where the diagnosis is being performed, the number of times it is being performed and the status.

Start Button Starts the memory, I/O diagnosis.

Stop Button Stops the memory, I/O diagnosis.

Board Reset Button Resets the MELSECNET/H board.

Page 127: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

9 - 19 9 - 19

MELSEC 9 UTILITY OPERATIONS

9.2.10 Target screen operation

This operation sets the logical station No. for access to a multiple CPU system or Redundant CPU system.

Item Content

Channel Sets the channel (MELSECNET/H board) perform the target settings.

Logical Sta. No. Input the logical sta. No. which is setting or changing the settings.

Network No. Input the network No. of the station doing the accessing.

Sta. No. Input the station No. of the network module controlled by the multiple CPU system or redundant CPU system.

Multiple PLC specify Specify a target programmable controller CPU No. in the multiple CPU system.

Redundant PLC specify Specify a target redundant CPU in the redundant CPU system.

Set Button Registers the setting contents in the list of external devices.

Change Button Select the line to change. When this button is clicked, the data that are registered can be changed. (The same operation is performed when the line being changed is double clicked.)

Delete Button Select the line to be deleted. When this button is clicked, the registered logical station No. can be deleted.

Page 128: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

9 - 20 9 - 20

MELSEC 9 UTILITY OPERATIONS

9.2.11 Driver screen operation

This operation sets the combination settings between the MELSECNET/H board and MELSECNET/10 board and sets the link device access method and the time for each type of monitoring.

Item Content

Channel Sets the channel (MELSECNET/H board) which sets the link device access method.

Link Device Access Method

Setting

Sets the access method to link devices (LX, LY, LB, LW). (Refer to (1) in this section)

When Link Refresh is selected, specify the link refresh interval.

Transient Timeout Monitoring

Time Setting

Displays the current value for the transient time out monitoring time and inputs the setting

value.

Driver WDT Monitoring Time

Select "Use driver WDT function" to enable the function.

Displays the current value for the Driver WDT Monitoring Time and inputs the setting value.

(1 to 32767)

Set Button Enables the setting contents.

The channel No. settings are reassigned after the Set button is clicked.

Default Value Button Returns the set contents to the default values.

Page 129: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

9 - 21 9 - 21

MELSEC 9 UTILITY OPERATIONS

(1) Link Device Access Method

Item Description

Link Refresh

Makes access to the MELSECNET/H driver buffer. Data in the MELSECNET/H driver buffer and the refresh data storage area on the MELSECNET/H board are updated by link refresh. When secured data handling is specified with the control station parameter,

data consistency 1 of link device data is ensured.

Personal computer MELSECNET/H board

Refresh datastorage area

Userprogram drive buffer

Reading

Writing Link refresh

MELSECNET/H

Direct Access

Provided for MELSECNET/10 compatibility. Makes access to the refresh data storage area on the MELSECNET/H board.

Data consistency 1 of link device data is not ensured even if secured data

handling is specified with the control station parameter.

MELSECNET/H boardPersonal computer

Reading

Writing

Refresh datastorage area

Userprogram

1: Data consistency function prevents 2-word (32 bits) link data (e.g. current value of a positioning module) from being

divided into two 1-word (16bits) data (old and new data) by certain cyclic transmission timing.

(a) Link Refresh Interval

Link refresh is performed at intervals of the specified value multiplied by link

scan time. The load of the link refresh processing by the MELSECNET/H driver on the PC decrease in inverse proportion to this value. The specified interval value changes the delay time, which is duration from

when link device data arrive at the refresh data storage area on the MELSECNET/H board until they are read out into the user program. (Refer to POINT.)

Page 130: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

9 - 22 9 - 22

MELSEC 9 UTILITY OPERATIONS

POINT

(1) Relation between link refresh interval value and delay time in data reading The maximum delay time (TD(MAX)) from when link device data arrive at the

refresh data storage area on the MELSECNET/H board until they are read out into the user program can be obtained from the following formula.

Maximum delay time, TD(MAX) = TUP + (n-1) x TLS TUP : Interval for reading link device data from user program n : Specified interval value

TLS : Link scan time The following shows an example of accessing LB0 under conditions: TUP =

100ms, n = 3, TLS = 120ms. The maximum delay time, TD(MAX) is:

TD(MAX) = 100ms + (3-1) x 10ms = 120ms

(n-1) TLS=20ms

TUP=100ms

TD(MAX)

TLS=10ms

User program

Read timing

MELSECNET/H driver buffer

Link refresh(When n=3)

Refresh data storage area (LB0)

Link scan

9.3 Device Monitor Utility

For the operation and setting method for the device monitor utility, refer to "MELSEC

Data Link Library Reference Manual".

Page 131: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

10 - 1 10 - 1

MELSEC10 MELSEC DATA LINK LIBRARY

10 MELSEC DATA LINK LIBRARY

This chapter describes the functional overview offered by the library. These functions are used when creating a user program that communicates with a programmable controller CPU. With the functions, the user can perform communication without being conscious of the hardware type on the opposite side or the communication protocol. The following table lists the MELSEC data link library that is provided with the MELSECNET/H board.

Function name Description

mdOpen Opens a communication line. mdClose Closes a communication line. mdSendEx Batch writes devices. (Extended function 1) mdReceiveEx Batch reads devices. (Extended function 1) mdRandWEx Writes devices randomly. (Extended function 1) mdRandREx Reads devices randomly. (Extended function 1) mdDevSetEx Sets a bit device. (Extended function 1) mdDevRstEx Resets a bit device. (Extended function 1) mdTypeRead Reads the type of programmable controller CPU. mdControl Remote operation of programmable controller CPU.

(RUN/STOP/PAUSE). mdBdRst Resets the board. mdBdModSet Sets the mode of the board. mdBdModRead Reads the mode of the board. mdBdLedRead Reads the LED information of the board. mdBdSwRead Reads the switch status of the board. mdBdVerRead Reads the version information of the board. mdInit Initializes programmable controller information table.

Batch writes devices. mdSend Sends data (SEND function). Batch reads devices. mdReceive Receives data (RECV function).

mdRandW Writes devices randomly. mdRandR Reads devices randomly. mdDevSet Sets a bit device.

1 : A function in which the access range is extended according to the extension of the device points at the access target. It is accessible to all device numbers. Use extended functions when creating a new program.

POINT Refer to "MELSEC Data Link Library Reference Manual" for the details of the functions.

10

Page 132: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

10 - 2 10 - 2

MELSEC10 MELSEC DATA LINK LIBRARY

MEMO

10

Page 133: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

11 - 1 11 - 1

MELSEC11 PROGRAMMING

11 PROGRAMMING

11.1 Cautions in Programming

This section explains concerning cautions in the case that a program is created using data on a network.

11.1.1 Interlock related signals

Show a list of the interlock signal devices used in the user program. For other hosts and other stations, refer to the "Q Corresponding MELSECNET/H Network System Reference Manual (PLC to PLC network)" about the operating status and setting status, etc.

11

Page 134: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

11 - 2 11 - 2

MELSEC11 PROGRAMMING

Assignment of link special relays (SB) and link special registers (SW) when multiple boards are installed

Device status Device Name Description

Off (0) On (1)

SB20 Module status Indicates the communication status between MELSECNET/H board and personal computer.

Normal Abnormal

SB47 Baton pass status of host

Indicates the baton pass status of the host. It is in a status that the cyclic transmission and transient transmission can be performed when it is normal.

Normal (Data link enabled)

Abnormal (Host disconnected)

SB49 Data link status of host

Indicates the data link status (cyclic transmission status) of the host.

Data link being executed (Executing cyclic

transmission)

Data link being stopped(Set after refresh

completion)

SB70 Baton pass status of each station

Indicates the baton pass status of each station (including the host). Reserved stations and stations having numbers higher than the maximum station number are not included. This device turns off when SW70 to 73 are all "0".

All stations normal One or more stations are

abnormal

SB74 Data link status of each station

Indicates the data link (cyclic transmission) status of each station (including the host). Reserved stations and stations having numbers higher than the maximum stations number are not included. This device turns off when SW74 to 77 are all "0".

All stations executing data link

(All stations executing cyclic transmission)

One or more stations are not executing data link

Stores the baton pass status of each station (including the host).

SW70 to 73

Baton pass status of each station (per station number)

16

32

48

64

15 14 13 5 4 3 2 1

31 30

47 46

63 62

29

45

61

21 20 19 18 17

37 36 35 34 33

53 52 51 50 49

b15 b14 b13 b12 b4 b3 b2 b1 b0SW70

SW71

SW72

SW73

Numbers 1 to 64 in the table denote station numbers.

toto

to

to

to

Baton pass normal (including reserved

stations during online and stations having

numbers higher than the maximum station

number)

Baton pass abnormal (including reserved

stations during offline test and stations having numbers higher than the

maximum station number)

Stores the data link (cyclic transmission) status of each station. (Including the host)

SW74 to 77

Data link status of each station (per station number)

SW74

SW75

SW76

SW77

16

32

48

64

15 14 13 5 4 3 2 1

31 30

47 46

63 62

29

45

61

21 20 19 18 17

37 36 35 34 33

53 52 51 50 49

b15 b14 b13 b12 b4 b3 b2 b1 b0

Numbers 1 to 64 in the table denote station numbers.

toto

to

to

to

Executing data link (including reserved

stations and stations having numbers higher

than the maximum station number)

Station not executing data link

11

Page 135: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

11 - 3 11 - 3

MELSEC11 PROGRAMMING

11.2 Cyclic Transmission

The link scan of the MELSECNET/H and the programmable controller of the user program operate asynchronously. Depending on the timing of the user program execution, link data with data types of more than 32 bits (two words), such as the ones below, may be broken up into new and old data, which may coexist in 16 bit (one word) units. • Floating point data • Current values of positioning module, command speed. The MELSECNET/H provides the following functions for making handling of the link data easy. • 32 bit data guarantee (Refer to "Q corresponding MELSECNET/H network system

reference manual (PLC to PLC network)" for details.) • Block guarantee of cyclic data per station (Refer to Section 11.2.1 Block guarantee

of cyclic data per station for details)

Page 136: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

11 - 4 11 - 4

MELSEC11 PROGRAMMING

11.2.1 Block guarantee of cyclic data per station

By enabling the parameter settings shown below, handshaking for the cyclic data is performed between the PC and the MELSECNET/H board and then the network is refreshed. Through the cyclic data handshaking, the link data block is guaranteed for each station (to prevent link data separation per station 1). As shown below, set the send and receive parameters as needed. The MELSECNET/H board can be set in the MNETH utility's "Common Parameter Setting (Supplementary Settings)" screen only when it is the control station. (It is not necessary to set it if the board is a normal station.)

By selecting both [Secured data send] and [Secured data receive], an interlock for the link data between the stations to be set becomes unnecessary.

MELSECNET/H board and

Network module LWPC and CPU module device W

Refresh A

Refresh B

Updated portion of refresh A

Refresh C

Updated portion of refresh B

Updated portion of refresh C

Station number 1

Station number 2(Host)

Station number 3

Station number 4

POINT

The block guarantee per station applies only to the refresh processing. To use the direct access of the link devices, the programs should be interlocked.

1: The separation prevention refers to a prevention of link data with double

word precision (32 bits), such as the current value of the positioning module, from being separated into new data and old data in one word (16 bits) units due to the cyclic transmission timing.

Page 137: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

11 - 5 11 - 5

MELSEC11 PROGRAMMING

11.3 Link Special Relays (SB)/Registers (SW)

The data linking information is stored in the link special relays (SB)/registers (SW). They can be used by the user program, or used for investigating faulty areas and the causes of errors by monitoring them. The following table shows which SB and SW can be used to check which information. For more details, refer to "Q Corresponding MELSECNET/H Network System Reference Manual (PLC to PLC network)". (1) To know the information about the host

Item SB SW

Personal computer status of the host (normal/abnormal)

SB004AH SB004BH

SW004BH

The external power supply status of the host SB0042H ---- Communication status between MELSECNET/H board and personal computer.

SB0020H SW0020H

Setting status of the MELSECNET/H board SB0040H to 44H SB0058H to 69H

SW0040H to 46H SW0054H to 68H

Running status of the MELSECNET/H board SB0047H to 49H SW0047H to 4AH

(2) To know information about the entire network

Item SB SW

CPU and personal computer status of each station (normal/abnormal)

SB0080H SB0088H

SW0080H to 83H

SW0088H to 8BH CPU and personal computer operation status of each station (RUN/STOP)

SB0084H SW0084H to 87H

Cyclic transmission status of each station SB0074H SW0074H to 77H The external power supply status of each station SB008CH SW008CH to 8FH

Link scan, communication mode SB0068H SB0069H

SW0068H to 6DH

Setting information of the network SB0054H to 69H SW0054H to 68H Running information of the network SB0070H SW0070H to 73H Line status SB0090H to 9AH SW0090H to 9FH

(3) To know redundant CPU system information

Item SB SW

Operating mode of redundant CPU SB01F4H SW01F4H to 1F7H Pairing setting of each station SB01F8H SW01F8H to 1FBH System status in redundant CPU system SB01FCH SW01FCH to 1FFH

Page 138: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

11 - 6 11 - 6

MELSEC11 PROGRAMMING

MEMO

Page 139: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

12 - 1 12 - 1

MELSEC 12 APPLICATION FUNCTIONS

12 APPLICATION FUNCTIONS

Communication LX/LY

Automatic return function

Control station switch function

Control station return control function

Loopback function (optical loop system)

Diagnostic function

Low-speed cyclic transmission

Applicationfunctions

Communication LB/LWBasicfunctions

Refer to Q CorrespondingMELSECNET/H Network SystemReference Manual(PLC to PLC network)

········································································· Section 6.5

Driver WDT function ······································································· Section 4.3

·············································································

·····································································

···································································

······················································

·······················································

················································································································ Section 12.1

Section 12.2

Section 12.3.1

Section 12.3.2

Section 12.3.3

Section 12.4

Prevention of station failure by using externalpower supply (optical loop system)

Cyclic transmission function(Periodical communication)

RAS function

Multiple transmission function (optical loop system)

Cyclic transmission function(Periodical communication)

Transient transmission function(Non-periodical communication)

Direct access to link devices

Routing function

Group function

Communication function

12.1 Direct Access to the Link Devices

The link devices (LB, LW, LX, LY, SB, SW) of the MELSECNET/H board can be

directly read from/written to the user program by the driver setting. By directly accessing the link devices, the link refresh time and the transmission delay time can be shortened.

However, in direct access, since block guarantees are not applicable in station units, it is necessary to establish an interlock. For the direct access setting, set it in the "Driver" in the MNETH utility.

POINT

The direct access of the link devices LX/LY is limited to the communication with the block I/O master station set with the common parameters. By limiting the communication, data cannot be shared among multiple stations, such as link device

LB/LW, but 1:1 communication between predefined stations is allowed.

12

Page 140: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

12 - 2 12 - 2

MELSEC 12 APPLICATION FUNCTIONS

12.2 Low-Speed Cyclic Transmission Function

POINT The Q00J/Q00/Q01CPU does not support the low-speed cyclic transmission function. Therefore, the low-speed cyclic transmission function cannot be used in MELSECNET/H that connects the Q00J/Q00/Q01CPU.

The low-speed cyclic transmission function is convenient when sending data that does not require high-speed transfer to other stations in a batch mode using the cyclic

devices (LB/LW). A station can transmit data only once in a single link scan. Simultaneous data transmission from multiple stations requires more scan time than the following:

Low-speed cyclic link scan time = normal link scan time (number of send stations + 1) In the low-speed cyclic transmission, send range for each station is set with the

"Common parameters setting (B, W setting)" screen of the MNETH utility.

Low-speed cyclic send range for each station

The sending to other stations can be activated by three methods: 1): "Transmit data of one station in 1 scan", 2): "Fixed term cycle interval setting", and 3):" System times" and those three method are set in the "Common parameter setting" screen (bus setting). Only one of them can be selected.

1)

2)

3)

12

Page 141: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

12 - 3 12 - 3

MELSEC 12 APPLICATION FUNCTIONS

12.2.1 Send range settings

Each station's send range of link devices (low-speed LB, low-speed LW) is assigned to

the extended area (2000 to 3FFF) in 16-point units for LB (start : 0 to end

F) and in one-point units for LW. Each station's send range can also be assigned using a random station number

assignment sequence.

(1) Device range

MELSECNET/H Board LB

0H 2000H3FFFH

(8192) (16383)

Normal cyclic transmission area Extended function area

(2) Screen settings

This shows in the case where 768 points of the transmission range for each station is assigned to (Low Speed LB, Low Speed LW) in the "Common parameter setting (B, W Setting)" screen in the MNETH utility.

Send range(2000 to 3FFF)

POINT (1) The total of the send ranges per station must not exceed 2000 bytes in the low-

speed cyclic transmission. (The send range for the normal cyclic transmission is not included.)

(2) The LX and LY cannot be set as low-speed cyclic devices. (3) Low-speed cyclic transmission function cannot be used during

MELSECNET/10 mode.

Page 142: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

12 - 4 12 - 4

MELSEC 12 APPLICATION FUNCTIONS

12.2.2 Send timing

The low-speed cyclic transmission is executed separately from the normal cyclic transmission. This section describes the setting, processing interval and link cycle of the low-speed cyclic transmission.

(1) Transmission setting

The link cycle of the low-speed cyclic transmission varies depending on its

transmission setting. The setting can be made at "Specification of low speed cyclic transmission" on "Supplementary setting". (Refer to Section 12.3.1.)

The following lists the setting options.

Setting item Description

Transmit data of one station

in 1 link scan

Low-speed cyclic data of max. one station are sent during

one link scan of normal cyclic transmission.

Fixed term cycle interval

setting

Low-speed cyclic data are sent at a specified time

interval. 1

System times Low-speed cyclic data are sent at a specified time. 1

1: Maximum no. of stations capable of sending data during 1 link scan of normal cyclic transmission varies depending on the "Maximum no. of

transients in 1 scan" setting. Refer to Section 12.3.1 for the "Maximum no. of transients in 1 scan" setting.

Page 143: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

12 - 5 12 - 5

MELSEC 12 APPLICATION FUNCTIONS

(2) Transmission processing interval

The following system configuration example is used for subsequent explanations.

NS4

normalstation

NS3normalstation

NS2normalstation

MP1control station

(a) When "Transmit data of one station in 1 link scan", "Fixed term cycle interval setting (Maximum no. of transients: 1)" and "System times (Maximum no. of transients: 1)" are set

LB/

LW

LB/

LW

LB/

LW

LB/

LW

LB/

LW

LB/

LW

LB/

LW

LB/

LW

LB/

LW

MP1 sending

NS2 sending

NS3 sending

NS4 sending

Low-speed cyclic transmission

Normal link scan

Low

-spe

ed d

ata

MP

1NS

2NS

3NS

4L

ow-s

peed

dat

a

Low

-spe

ed d

ata

Low

-spe

ed d

ata

LB/

LW

Low

-spe

ed d

ata

LB/

LW

Low

-spe

ed d

ata

LB/

LW

Normal link scan

Normal link scan

Normal link scan

LB/

LW

Low

-spe

ed d

ata

LB/

LW

LB/

LW

LB/

LW

Low

-spe

ed d

ata

Transmission processing interval

Page 144: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

12 - 6 12 - 6

MELSEC 12 APPLICATION FUNCTIONS

(b) When "Fixed term cycle interval (Maximum no. of transients: 2)" and

"System times (Maximum no. of transients: 2)" are set

MP1 sending

NS2 sending

NS3 sending

NS4 sending

Normal link scan

LB/

LW

Low

-spe

ed d

ata

Transmission processing interval

LB/

LWL

ow-s

peed

dat

a

LB/

LW

LB/

LW

LB/

LW

Low

-spe

ed d

ata

LB/

LW

Low

-spe

ed d

ata

LB/

LW

Low

-spe

ed d

ata

LB/

LW

LB/

LW

Normal link scan

Low-speed cyclic transmission

Low

-spe

ed d

ata

MP

1NS

2NS

3NS

4

Low

-spe

ed d

ata

Low

-spe

ed d

ata

Low

-spe

ed d

ata

(3) Link cycle Link cycle examples of the low-speed transmission are as shown below.

(a) When "Transmit data of one station in 1 link scan" is set

Normallink scan

Transmission processinginterval in (2)

Link cycle

(b) When "Fixed term cycle interval setting" is set

Transmission processing

interval in (2)Waiting time

Link cycle (Fixed time interval)

(c) When "System times" is set

Transmission processing

interval in (2)

Specified time

Page 145: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

12 - 7 12 - 7

MELSEC 12 APPLICATION FUNCTIONS

12.2.3 Startup

(1) Sending of data for one station per link scan (default) The low-speed cyclic data for a maximum of one station is sent in one link scan of the normal cyclic transmission. [Setting method]

1) Click ( ) "Transmit data of one station in 1 scan" to select.

POINT

The fastest link scan time in the low-speed cyclic transmission can be calculated by

the following equation: LSL = LS number of stations + LS

= LS (number of stations + 1)

LSL : The fastest link scan time in the low-speed cyclic transmission

LS : Normal link scan time

(2) Fixed term cycle interval setting The low-speed cyclic data is sent in the link cycle of the designated time frequency. Valid setting frequency: 1 to 65535 s (18 h, 12 min and 15 s) [Setting method]

1) Click ( )"Fixed term cycle interval setting" to select. 2) Set the time in seconds (the screen shows a value of 600).

Page 146: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

12 - 8 12 - 8

MELSEC 12 APPLICATION FUNCTIONS

(3) System timer interval

The low-speed cyclic data are sent in the link cycle at the designated time.

By omitting year, month, and day in the setting, the low-speed cycle transmission can be activated yearly (or monthly, or daily). Hour, minute and second values must be entered.

Setting points: 1 to 8 points [Setting method]

1) Click ( )"System times" to select.

2) Set year, month, day, hour, minute and second to the designated time. In the following screen example: Points 1 to 3 : By omitting year, month and day, data is sent every

day at the designated time. Points 4 and 5 : By omitting year and month, data is sent at the

designated time monthly.

Point 6 : By omitting the year, data is sent at the designated time every year.

Points 7 and 8 : Data is sent only once at the designated time.

POINT (1) The system timer operates based on the host's clock.

If used without matching the clocks on the sending station and receiving station, there may be a time gap between the stations.

(2) When handling multiple data without the block guarantee per station function, new and old data may coexist. Apply interlocks to prevent the coexistence.

Page 147: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

12 - 9 12 - 9

MELSEC 12 APPLICATION FUNCTIONS

12.3 Transient Transmission Function

The transient transmission function performs data communication only when it is requested between stations. In the MELSECNET/H, data communication can be performed with other stations

having the same network number (the same network as where the host is connected), as well as with stations having other network numbers.

1) Transient transmission function to a station on the same network

1NS21MP1

1NS51NS6

1NS3

1NS4

Network No.1

2) Transient transmission to stations on other networks (routing function) In this case, the routing parameters must be set for the request source and relay stations.

1MP1 1NS2 1NS3

1NS6 1NS5

Network No. 1

Requestsource

1NS4 2MP1

Relay station

3MP1

Network No. 3

Requestdestination

3NS42NS3

3NS2

3NS3

2NS2

Network No. 2

Stations for which the routing parameters are set

Required

Required Required

Relay station

Page 148: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

12 - 10 12 - 10

MELSEC 12 APPLICATION FUNCTIONS

12.3.1 Communication function

(1) Parameter settings Set the execution conditions for the transient transmission with the parameters listed below.

In the default settings, both the number of transients that one network can execute in one link scan ("Maximum no. of transients in 1 scan") and the number of transients that one station can execute in one link scan ("Maximum no. of

transients in one station") are set to 2 times. Change the number of transients that can be executed in a link scan as necessary (Refer to Points below).

Setting value

Setting item Valid setting times Default setting

Maximum no. of transients in 1 scan 1 to 255 times Twice

Maximum no. of transients in one station 1 to 10 times Twice

Transient setting

POINT (1) By increasing the number of transients, multiple transient instructions can be

executed at the same time (in one link scan). (2) If the number of transients is increased and the transient request was issued in

each station at the same time, the link scan time becomes temporarily longer and the cyclic transmission is also affected. Do no set unnecessarily large values.

(3) When the transient transmission and the low-speed cyclic transmission are used at the same time, these transient setting parameters limit the total number of transient and low-speed cyclic transmissions.

Page 149: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

12 - 11 12 - 11

MELSEC 12 APPLICATION FUNCTIONS

(2) Transient transmission range

In a multiple network system of the MELSECNET/H, communication can be

performed with stations in a maximum of eight networks by setting the routing parameters described in Section 12.3.2. The following diagram illustrates the transient transmission range using an

example where the destinations are limited to eight networks.

QCPU 1MP1

Network No. 1

PC 1NS3 QCPU 1NS4

QCPU 1NS2 2MP1

Network No. 2

QCPU 2NS3

QCPU 2NS2 3NS3

Network No. 3

QCPU 3MP1

QCPU 3NS2 4MP1

QCPU 4NS2 5MP1

QCPU 5NS2 6MP1

QCPU 7MP1 6NS2

Network No. 9

QCPU 9NS2

QCPU 9NS3 QCPU 9MP1 8NS2

Network No. 8

QCPU 8NS4

QCPU 8NS3

QCPU 8MP1 7NS2

Network No. 4

(Gate 4)

Network No. 5

(Gate 5)

Network No. 6

(Gate 6)

Network No. 7

(Gate 7)

(Gate 1) (Gate 2) (Gate 3)

Page 150: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

12 - 12 12 - 12

MELSEC 12 APPLICATION FUNCTIONS

[Transient transmission valid range] The following table shows the valid ranges of send/receive by transient transmission

using the network configuration on the previous page. In the table below, , , and indicate whether or not the transient transmission between the request source (destination) listed in the column at the left and the

request destination (source) listed in the row at the bottom is possible. For example, the valid range between 9NS2 of network number 9 and 1NS2 of network number 1 is indicated by 1 (communication is possible by designating a network

module that is close to the request source of the same programmable controller).

9NS2Request source (destination)

1NS2

Request destination (source)

1

: Possible

: Possible by setting the routing parameter

: Not possible

1: Communication is possible by designating a network module that is close to the request source of the same programmable controller

Network No. 1

Network No. 2

Network No. 3

Network No. 9

Network No. 8

1MP1

1NS2

1NS3

1NS4

2MP1

2NS2

2NS3

3MP1

3NS2

3NS3

8MP1

8NS2

8NS3

8NS4

9MP1

9NS2

9NS3

Host

Request source(destination)

Request destination (source)

1MP1 1NS2 1NS3 1NS4 2MP12NS2 2NS3 3MP13NS2 3NS3

NetworkNo. 1

8MP18NS2 8NS3 8NS4 9MP19NS2 9NS3

NetworkNo. 2

1

1

1

1

1

1

1

1

• • • • •

• • • • •

• • • • •

• • • • •

• • • • •

• • • • •

• • • • •

Host

• •

• •

• •

• •

• •

• •

• •

• •

• •

• •

• •

• •

• •

• •

• •

• •

• •

• •

• •

• •

• •

• •

• •

• •

• •

• •

• •

• •

• •

• •

• •

• •

• •

• •

• •

• •

NetworkNo. 3

• • • • •

• • • • •Network

No. 8Network

No. 9

Host

Host

Host

HostHost

Host

Host

Host

Host

Host

HostHost

Host

Host

Host

Host

HostHost

Page 151: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

12 - 13 12 - 13

MELSEC 12 APPLICATION FUNCTIONS

12.3.2 Routing function

The routing function is used to execute transient transmissions to stations having other network numbers in a multiple network system. In order to execute the routing function, it is necessary to set the "routing parameters"

to associate the network numbers of the request source and the station that will function as a bridge 1 between the networks.

1: The bridge function refers to sending data via an adjacent network.

POINT

MELSECNET/H board cannot be used as a relay station that function as a bridge.

Use the network module for the relay station.

(1) Stations that require routing parameter setting

(a) The setting is required for both the transient transmission request source and relay stations.

(b) For the relay stations, two routing settings are required: one from the request source to the request destination, and the other from the request destination back to the request source.

(c) The setting is not required for the request destination.

In the example shown in the diagram below where the transient transmission is executed from 1NS3 to 3NS4, the setting is required for the following three stations:

1) Setting for 1NS3 that requests the transient transmission Designate the network number (3) of the Transfer to, the relay station (1NS4), and the relay network number (1) to the relay station.

2) Setting for 1NS4 that functions as a bridge Designate the network number (3) of the Transfer to, the relay station (2NS4), and the relay network number (2) to the relay station. It is not necessary to set the return route because it is designated in the setting

for 2NS4.

Page 152: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

12 - 14 12 - 14

MELSEC 12 APPLICATION FUNCTIONS

3) Setting for 2NS4 that function as a bridge

It is not necessary to set the routing to the Transfer to because the host is on the same network as the destination transfer (3). However, it is

necessary to set the Transfer from network number (1) as the Transfer to network number and to designate the relay station (2MP1) and the relay network number (2) to the relay station in order to trace a route

back to the request source.

13

Intermediate network No.

Transfer to

network No.

4

Routing parameter setting

The setting is required only for the transfer to network No. (3).

···· Stations for which the routing parameters are set

Request source

1MP1

1NS6

1NS2

1NS5

1NS3

1NS4 2MP1

Network No. 1

3MP1

3NS5

3NS2

3NS4 3NS3

Network No. 3

2NS4

2NS2 2NS3

Network No. 2

Intermediate station No.

23

Intermediatenetwork No.

Transfer to

network No.

4

Routing parameter setting

Intermediatestation No.

21

Intermediatenetwork No.

Transfer to

network No.

1

Routing parameter setting

Intermediatestation No.

Requestdestination

1: The bridge function refers to sending data via an adjacent network.

Page 153: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

12 - 15 12 - 15

MELSEC 12 APPLICATION FUNCTIONS

(2) Routing parameter settings

(a) Setting screen A maximum of 64 "Transfer to Network No." can be set on the "Routing Parameter Setting" of the MNETH utility. Note that the same Transfer to network number cannot be designated more than once (multiple). Therefore, the host can become the request source or can be accessed to other station through the host with 64 types of different "Transfer to Network No."

Setting item Valid setting range

Transfer to Network No. 1 to 239

Intermediate Network No. 1 to 239

Intermediate Station No. 1 to 64

(b) Setting method Set the routing parameters according to the procedure described below.

Requestsource

Network No. Relay station

Network No.

To access "network No. ," it is necessary to route through station No. of network No. .

Transfer to

network No.

1

2

Requestdestination

Intermediatenetwork No.

Intermediatestation No.

Page 154: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

12 - 16 12 - 16

MELSEC 12 APPLICATION FUNCTIONS

(3) Settings for different network system configurations and setting

contents The stations to set for the transient transmission and the contents of the routing parameters vary depending on the system configuration. (a) Single network system It is not necessary to set the routing parameters for the transient transmission to the same network.

Requestsource

Network No. 1

Requestdestination

(b) Multiple network system: two networks Set the routing parameters only for the request source station. The route for reaching the request destination (network number 2) must be set for the request source station.

Relay station

Requestsource

Network No. 1

Requestdestination

Network No. 2

(c) Multiple network system: three networks Set the routing parameters for the request source and the relay stations. The route for reaching the request destination (network number 3) must be set for the request source. The route for reaching the request destination (network number 3) must be set for relay station 1).

The route for reaching the request source (network number 1) must be set for relay station 2).

Relay station 1)

Requestsource

Network No. 1

Requestdestination

Network No. 2 Network No. 3

Relay station 2)

(d) Multiple network system: four networks Set the routing parameters for the request source station and the relay stations. The route for reaching the request destination (network number 4) must be set for the request source station.

The route for reaching the request destination (network number 4) must be set for relay station 1) (the relay station that is closest to the request source).

The route for reaching the request source (network number 1) must be set for relay station 2) (the relay station that is closest to the request destination). The routes for reaching the request destination (network 4) and the request source (network number 1) must be set for relay station 3) (relay station other than 1) and 2)).

Relay station 1)

Requestsource

Network No. 1 Network No. 2

Relay station 3)

Network No. 3 Network No. 4

Relay station 2)

Requestdestination

Page 155: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

12 - 17 12 - 17

MELSEC 12 APPLICATION FUNCTIONS

POINT (1) When a network is connected in a loop as shown in the figure below, make

sure to set the routing parameters so that the same relay station is routed for both the "route from request source to request designation" and the "route back from request destination to request source." Do not set the destination and returning paths to circle the entire loop. The first relay station in the return path from the request destination is determined by the relay station in the forward path; thus, data cannot be transferred to a station beyond that relay station and an error occurs.

Requestsource

1

2 4

32

11

23

3 4

15

42

31

No.1 No.8

No.7

No.6Request

destination

No.5No.4

No.3

No.2

C

B

A

A indicates the path from the request source to the request destination.B and C indicate the path from the request destination to the request source.Avoid path C when setting the return path.

(2) When data is sent to a remote network by transient transmission using the routing parameters, data is transferred through many networks; thus, the amount of transmission data and the number of transmissions may affect the entire system. For example, in network No. 2 to 5 in the figure above, the link scan time may become temporarily longer and there may be delays in the transient transmission of the host because of the transient transmissions from other networks. When using the routing parameters, design the transient transmission by considering the entire system.

(3) When multiple network systems are connected with the routing function, the

request source can send requests to destinations in up to eight network systems (the maximum number of relay stations is seven stations).

Page 156: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

12 - 18 12 - 18

MELSEC 12 APPLICATION FUNCTIONS

(4) Calculation of transmission delay time

The processing time of the transient transmission instruction to access a station on other network in a multiple network system can be obtained by adding the following transmission delay factors.

(Routing transmission delay time) = (processing time from request source to relay station)

+ (processing time from relay station to request destination)

(a) Processing time from request source to relay station This is the transmission delay time from the request source (the station that executed the instruction) to the relay station that performs the routing. In the following example, it is the time required for the data to be transmitted from station 1MP1 to station 1NS3. Refer to "Q Corresponding MELSECNET/H Network System Reference Manual (PLC to PLC network)" for the calculation of translation of delay time.

(b) Processing time from relay station to request destination This is the transmission delay time from the relay station to the request destination (the station accessed with the instruction). In the following example, it is the time required for the data to be transmitted from station 2MP1 to station 2NS3. Refer to "Q Corresponding MELSECNET/H Network System Reference Manual (PLC to PLC network)" for the calculation of translation of delay time.

1NS3 2MP1

Network No. 1 Network No. 2

1MP1 1MP2 2NS2 2NS3

READrequestsource

READrequest

destination

READ completionREAD execution

PC processing timeof request source

Link scan on request source side

Link scan on request destination side

Sequence scan of request destination side

REMARK

When three or more networks are relayed through by means of routing, add the processing time from one relay station to the other relay station to the routing transmission delay time.

Page 157: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

12 - 19 12 - 19

MELSEC 12 APPLICATION FUNCTIONS

(5) Setting example

The routing parameter setting examples (A and B) are explained using the

system configuration explained in Section 12.3.2.

QCPU 1MP1

Network No. 1

PC 1NS3 QCPU 1NS4

QCPU 1NS2 2MP1

Network No. 2

QCPU 2NS3

QCPU 2NS2 3NS3

Network No. 3

QCPU 3MP1

QCPU 3NS2 4MP1

QCPU 4NS2 5MP1

QCPU 5NS2 6MP1

QCPU 7MP1 6NS2

Network No. 9

QCPU 9NS2

QCPU 9NS3 QCPU 9MP1 8NS2

Network No. 8

QCPU 8NS4

PC

8NS3

QCPU 8MP1 7NS2

Network No. 4

5) Relay station

Network No. 5

6) Relay station

Network No. 6

7) Relay station

Network No. 7

8) Relay station

10) Request source11) Relay station12) Request destination

9) Request destination

1) Request source

2) Relay station 3) Relay station 4) Relay station

A

B

(a) Setting example A The routing parameter must be set for request source 10).

8NS3 9NS38NS2 9MP1

10) Request source 11) Relay station 12) Request destination

No. Transfer to network

No.

Intermediate

network No.

Intermediate

station No.

10) Request source 1 [9] [8] [2]

Page 158: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

12 - 20 12 - 20

MELSEC 12 APPLICATION FUNCTIONS

(b) Setting example B

The routing parameters must be set for the request source 1), relay station 2), relay station 3), relay station 4), relay station 5), relay station 6), relay

station 7), and relay station 8). In addition, there are two types of routing parameter settings; one is used when sending data from the request source to the request destination

(when sending a request), and the other is used when returning from the request destination to the request source (when sending a response). Either one of them or both must be set for each station.

1NS3 1NS2 2MP1 2NS2 3NS3 3NS2 4MP1

7MP1 6NS2 6MP1 5NS2 5MP1 4NS2

7NS2 8MP1 8NS4

1) Request source 2) Relay station 3) Relay station 4) Relay station

5) Relay station6) Relay station7) Relay station

8) Relay station 9) Request destination

1) Request source No.

Transfer to network

No.

Intermediate

network No.

Intermediate

station No.

1 [8] [1] [2] Used when sending a request

2) Relay station 1 [8] [2] [2] Used when sending a request

3) Relay station 1 [8] [3] [2] Used when sending a request

2 [1] [2] [1] Used when sending a response

4) Relay station 1 [8] [4] [2] Used when sending a request

2 [1] [3] [3] Used when sending a response

5) Relay station 1 [8] [5] [2] Used when sending a request

2 [1] [4] [1] Used when sending a response

6) Relay station 1 [8] [6] [2] Used when sending a request

2 [1] [5] [1] Used when sending a response

7) Relay station 1 [8] [7] [2] Used when sending a request

2 [1] [6] [1] Used when sending a response

8) Relay station 1 [1] [7] [1] Used when sending a response

Page 159: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

12 - 21 12 - 21

MELSEC 12 APPLICATION FUNCTIONS

12.3.3 Group function

The group function is used to group the target stations of a transient transmission and send data to all of the stations in a group with a single instruction. One network may have a maximum of 32 groups. By setting a group designation to the target station number in the control data of a dedicated instruction, stations with the matching group number retrieve the transient data. Note that whether or not the transient transmission is normally completed cannot be verified because the data are transmitted to multiple stations.

(1) Visual representation of the function

The following figure shows an example of grouping. When a transient

transmission is executed by designating group No. 1, all of the three stations, 1NS3, 1NS5 and 1NS6, retrieve the transient data.

1MP1 1NS2 1NS3

Group No. 1

1NS6 1NS5 1NS4

Group No. 1 Group No. 1

(2) Setting method Set the group number of the MELSECNET/H board using the "Board information" screen of the MNETH utility. Setting range : 1 to 32 (Default : 0 (no group designation))

Set the desired group number.

(3) Transient transmission instructions that allows group designation Use mdSend to execute the transient transmission instruction in the user program.

CAUTION [Precautions when executing the transient transmission by a group function] When a group is designated, the execution of the transient transmission cannot be verified. When this mode of transient transmission is executed successively, a "no reception buffer space error" (error code: F222) may occur. Design the system thoroughly to allow for a sufficient interval between executions, and make sure to test (debug) to confirm that successive executions can be performed without generating any error.

Page 160: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

12 - 22 12 - 22

MELSEC 12 APPLICATION FUNCTIONS

12.3.4 SEND/RECV function

The SEND/RECV function sends/receives data to/from other station's programmable

controller using the MELSEC data link library function. This function supports the SEND/RECV instruction of link dedicated instruction.

POINT

For details of the functions, refer to "MELSEC Data Link Library Reference Manual".

(1) SEND function The SEND function sends data from the own station to the specified channel of the specified station using the mdSend function. Two execution types, "arrival acknowledgment" and "no arrival acknowledgment", are available for the SEND function. When sending data with "no arrival acknowledgment" execution type, all stations in group numbers can be specified as target stations.

CPU module

RECV

Target station

Channel 1Channel 2Channel 3Channel 4Channel 5Channel 6Channel 7Channel 8

Board Driver User application

Channel 1Channel 2Channel 3Channel 4Channel 5Channel 6Channel 7Channel 8

main() {

mdOpen( 51, -1, &path );

mdSend( path, 255, , );

mdClose( path );}

POINT (1) An error occurs when data are sent to the same channel which is being used.

Board Driver User application

Channel 1Channel 2Channel 3Channel 4Channel 5Channel 6Channel 7Channel 8

CPU module

RECV

Target station

Channel 1Channel 2Channel 3Channel 4Channel 5Channel 6Channel 7Channel 8

Error

main() {

mdOpen( 51, -1, &path );

mdSend( path, 255, , );

mdClose( path );}

(2) Only an even number byte can be specified for a send data size. (3) Logical station numbers cannot be specified. (4) Even if the process of data send is completed normally with "arrival

acknowledgment" execution type, data may not be received when the target station is a board. For details, refer to the RECV function.

Page 161: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

12 - 23 12 - 23

MELSEC 12 APPLICATION FUNCTIONS

POINT (5) The multiple network modules are installed on the target station

Specify the network number and station number of the network module which is to be received request from the own station. Specify 1NS2 in the following example. (2MP1 cannot be specified.)

1MP1 1NS2

1NS31NS4

2MP1 2NS2

Network No.1 Network No.2

(Own station) (Target station)

Specify 1NS2 as the target station.2MP1 cannot be specified.

(6) When the target network is CC-Link IE Controller or CC-Link IE Field Network,

specify the transmission data within the range of 2 to 960 byte. When the data larger than 960 byte is transmitted, an error will be occurred on the receive side even though the transmission completed normally on the transmit side. For the errors, refer to the following table.

Network Error

CC-Link IE Controller Board No received data error (47H)

Module Network module error (E274H)

CC-Link IE Field Board

Not received Transient data improper (D25DH)

Received No received data error (47H)

Module Transient data improper (D25DH)

(2) RECV function

The RECV function reads data received by the board from the other station using the mdReceive function. < RECV function overview >

Board

Driver User application

Channel 1Channel 2Channel 3Channel 4Channel 5Channel 6Channel 7Channel 8

Sending station

Data sent from other station by

the SEND instruction Received data

are stored to the target station channel specified by the sending station.

RECV instruction

*1

Received data of Channel 3

Received data of Channel 7

Received data of Channel 1

Received data of Channel 5

Received data of Channel 4

Reception buffer of driver

Received data can be stored up to 128

disregarding the channel numbers.

Read by the mdReceive

function

Received data storage (data)

Send target network No.

Send source station No.

Send source channel No.

Received message (Actual data)

*1: Executed automatically by the driver.

3

21

The board receives data sent from the other station by the

SEND instruction/SEND function, and stores data to the

target station channel specified at the sending side. After the board receives the data, the driver automatically

executes the RECV instruction and stores the received data to the reception buffer of the driver. All data received and

individually stored to channels of the board are stored to the one reception buffer of the driver which can store up to 128 of data.

Reads data of the specified channel number in the received

order from the data stored in the reception buffer of the driver using mdReceive function.

Page 162: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

12 - 24 12 - 24

MELSEC 12 APPLICATION FUNCTIONS

< Operation when 128 received data are already stored in the reception buffer of the driver >

When 128 received data are already stored in the reception buffer of the driver, the subsequent data are received by the board once, but the driver automatically discards those received data at the time of storage to the

reception buffer of the driver. When the sending side sent data with "arrival acknowledgment" execution type, the process of send data is completed normally at the sending side,

but data are discarded.

Board

Driver

Channel 1Channel 2Channel 3Channel 4Channel 5Channel 6Channel 7Channel 8

Sending station

Data sent from other station by

the SEND instruction

Received data of Channel 3

Received data of Channel 7

Received data of Channel 1

Received data of Channel 5

Received data of Channel 4

Received data of Channel 2

Received data of Channel 6

Reception buffer of driver

Received data can be stored up to 128 disregarding the

channel numbers.

・・・・・

Discards received data

< Precautions for using RECV function > When receiving data to the multiple channels of the board,

create a user program to read data from all channels that receive data.

If a channel from which data are not read exists in the channel from which data are received, the received data of the channel from which data are not read are accumulated in

the reception buffer of the driver and all areas of 128 data are occupied. In this case, the received data of other channels cannot be

read because the driver automatically discards subsequent data received by the board.

When attempting data read by executing the mdReceive

function immediately after the send data completion at the sending station, an error, "71 (0047H): No reception data error", occurs because the driver has not completed the

RECV function and thus the receive data have not yet stored to the reception buffer of the driver. Retry the operation after waiting for a while.

Page 163: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

12 - 25 12 - 25

MELSEC 12 APPLICATION FUNCTIONS

12.4 Multiplex Transmission Function (Optical Loop System)

The multiplex transmission function allows high-speed communications using duplex

transmission paths (both the forward and reverse loops) in the optical loop system. In order to execute the multiplex transmission function, setting for the "Supplementary settings" of the common parameters is required. Note that this setting is not allowed

unless the total number of link stations is four stations or more.

(1) Using the multiplex transmission function, the high-speed communication is performed using both the forward and reverse loops effectively.

1MP1

1NS6

1NS2

1NS5

1NS3

1NS4

Forward loop

Reverse loop

IN OUT IN OUT IN OUT

OUT INOUT INOUT IN

(2) If an error occurs in the transmission path while the multiplex transmission function is used, data linking continues by communicating only using the transmission path on one side of either the forward or reverse loop, or by switching to the communication using loopback. The transmission speed in this case is 10 Mbps or 25 Mbps.

1MP1

1NS6

1NS2

1NS5

1NS3

1NS4

Forward loop

Reverse loop

Loopback

DownLoopback

IN OUT

OUT IN

IN OUT

OUT IN

IN OUT

OUT IN

REMARK

The multiplex transmission function is effective only in reducing the link scan time when the number of connected stations is 16 or more and the link devices assigned

with common parameters is 2,048 bytes or more. The link scan time will be 1.1 to 1.3 times faster compared to when the multiplex transmission function is not used.

Page 164: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

12 - 26 12 - 26

MELSEC 12 APPLICATION FUNCTIONS

MEMO

Page 165: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

13 - 1 13 - 1

MELSEC13 ERROR CODE

13 ERROR CODE

For details of error codes displayed on the error messages of the utility, refer to the following manual. MELSEC Data Link Library Reference Manual

For details of error codes displayed on the Error history monitor screen (Section 9.2.8) of the utility, refer to the following manual. Q Corresponding MELSECNET/H Network System Reference Manual (PLC to PLC network) For QnA/Q4AR MELSECNET/10 Network System Reference Manual

13

Page 166: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

13 - 2 13 - 2

MELSEC13 ERROR CODE

MEMO

13

Page 167: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

14 - 1 14 - 1

MELSEC 14 TROUBLESHOOTING

14 TROUBLESHOOTING

This section explains the identification of the causes and troubleshooting when an error occurred. (1) Basic checking procedure

Check if there is a corresponding error symptom written in "Cause Determination Methods by Type of Trouble".

(Refer to Section 14.1) If the corresponding error could not be found, check the cause by following the procedure shown below.

1. Check if all the boards installed on a personal computer are displayed with the utility. • Check on the board list screen (Refer to Section 9.2.2)

• Check on the Event Viewer screen (Refer to Section 14.3.2) • Check on the Device Manager screen (Refer to Section 14.3.3)

2. Check the LED display of the board. • Check the LED status (Refer to Section 6.2)

3. Check the error occurring at the utility. • Check with test (Refer to Section 6.5)

• Check the network status with loop monitor (Refer to Section 9.2.6) • Check the each station status (Refer to Section 9.2.7) • Check the error history (Refer to Section 9.2.8)

4. Check the access target device. • Check if the board operates as set to the parameter or program by

checking whether the link devices perform communication, or transient

send/receive performs normally with the device monitor utility. (Refer to "MELSEC Data Link Library Reference Manual".)

• When unexpected value is input to the specific link device, refer to Section

14.5.1. 5. Check the user program.

• Check the arguments and returned values of the communication function.

(Refer to "MELSEC Data Link Library Reference Manual")

(2) When error cannot be solved If the troubleshooting above does not help, refer to Section 14.9.

14

Page 168: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

14 - 2 14 - 2

MELSEC 14 TROUBLESHOOTING

14.1 Cause Determination Methods by Type of Trouble

When an error occurs, use the table below to find the section that describes an appropriate method to determine the cause.

No. Error detail Cause determination method/Corrective action

1

MELSECNET/H board did not operate normally upon

startup.

When executing a user program, system down (blue

screen) or system reset occurred on the operating

system.

Refer to Section 14.3.

2

Data link is not achieved after the MELSECNET/H board

and control station as well as other normal stations were

connected.

Refer to the flowchart in Section 14.4.

3

An error occurred while conducting data link.

1) An unexpected value is input to a specific link device

(B, W, X, Y).

2) Data cannot be written or read even though device

access has been performed using communication

functions with the user program.

3) Communication is occasionally disabled while

running the user program.

Refer to the flowchart in Section 14.5.

4 The external power supply function does not work

properly. Refer to Section 14.6.

5

The personal computer has slowed down.

1) Operations with the mouse or keyboard are slow.

2) Operations of other applications are slow.

3) The CPU usage is high.

4) Operations by the sound function are unstable.

Refer to Section 14.8.

6 The software is not normally installed. Refer to Section 14.2.1.

7 Uninstallation is not executed normally. Refer to Section 14.2.2.

14

Page 169: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

14 - 3 14 - 3

MELSEC 14 TROUBLESHOOTING

No. Error detail Cause determination method/Corrective action

8

The driver is not normally installed.

A " ! " mark is displayed next to the icon of the driver on

the Windows R Device Manager screen.

Refer to Section 14.3.3.

9

An error message is displayed in utility.

1) "It failed to read the utility file version" is displayed.

2) "It failed to read the driver package version" is

displayed.

3) "It is failed to write the board setting data" is

displayed.

4) "It is failed to write the target setting data" is

displayed.

Logon as a user with administrator authority and

execute utility

(Refer to POINT in Section 9.1.) or reinstall the

operating system.

10

The password is requested on the User Account Control

screen when the utility is activated.

When the utility is activated, and if the following User

Account Control screen is displayed requesting a

selection of user with administrator authority and password entry 1, the user who is logging on to the

system does not have an administrator authority.

Log off the system and login again as a user with administrator authority, and activate the utility. 2

1: If only one user account with administrator authority is available, the User Account Control screen requests the

password entry of its user only.

2: For details on how to prevent this screen from being displayed, refer to Appendix 5.

Page 170: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

14 - 4 14 - 4

MELSEC 14 TROUBLESHOOTING

No. Error detail Cause determination method/Corrective action

11 CPU modules other than QCPU cannot be accessed.

CPU modules other than QCPU (Q mode) cannot be

accessed to the 64-bit version of user application. Use

32-bit version of user application.

12 The utility screen is not displayed properly.

The operations of utility cannot be performed.

1) Check if the display settings on the [Device

Manager] or other relevant functions are correct,

and install an appropriate display driver.

Or update the Windows R operating system.

2) Close the other applications.

3) Change the Hardware accelerator setting of the

display setting.

13

When transmitting the data using SEND function of

mdSend function, the transmission is completed

normally, however, the data is not received at the

destination.

Refer to section 12.3.4.

14 The driver does not start up.

1) Install the board.

2) Check if the board is recognized normally on the

"Device Manager" screen. (Refer to Section 14.3.3)

3) When the board is recognized normally on the

Device Manager screen, check if an error has

been occurred on the Event Viewer screen. (Refer

to Section 14.3.2)

Page 171: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

14 - 5 14 - 5

MELSEC 14 TROUBLESHOOTING

14.2 Troubleshooting of Installation and Uninstallation

The following explains the troubleshooting for error at installation and uninstallation.

14.2.1 Installation failed

When the installation is aborted or failed, reinstall the utility by the following procedure. 1. Check the installation and uninstallation precautions. (Refer to Section 8.1)

2. Restart the personal computer. 3. If the utility can be uninstalled, uninstall it.

After the uninstallation, restart the personal computer.

4. Install the utility again by following the installation procedure. (Refer to Section 8.2) (When the instruction displayed on the screen is not effective, refer to Section 14.3.3)

5. If the personal computer does not operate normally after the reinstallation, check if the personal computer has any problem. • Operating Environment (Refer to Section 2.5)

• Checking personal computer and operating system (Refer to Section 14.3.1) If the troubleshooting above does not help, refer to Section 14.9.

14.2.2 Uninstallation failed

When the uninstallation is failed, uninstall the utility after the reinstallation by the following procedure. 1. Check the installation and uninstallation precautions. (Refer to Section 8.1) If the

creation of 8.3 filename is disabled, perform the operation (1) in this section.

2. Insert the CD-ROM in the CD-ROM drive. 3. Display the "Run" screen from the Start menu or Quick Access Menu of Windows R . 4. Append "-A" and execute "Disk1\Setup.exe" of the CD-ROM.

5. Install the utility again by following the installation procedure. (Refer to Section 8.2) 6. Perform the uninstallation. 7. If the utility cannot be uninstalled normally, check if the personal computer has any

problem. • Operating Environment (Refer to Section 2.5) • Checking personal computer and operating system (Refer to Section 14.3.1)

If the troubleshooting above does not help, refer to Section 14.9.

Page 172: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

14 - 6 14 - 6

MELSEC 14 TROUBLESHOOTING

(1) Operation for the creation of 8.3 filename is disabled

1. Enable the creation of 8.3 filename.

2. Insert the CD-ROM in the CD-ROM drive. 3. Display the "Run" screen from the Start menu or Quick Access Menu of

Windows R .

4. Append "-G" and execute "Disk1\Setup.exe" on the CD-ROM. 5. Perform the uninstallation.

POINT

The option to append "-G" to Setup.exe is supported only by SW0DNC-MNETH-B

Version 27D or later.

Page 173: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

14 - 7 14 - 7

MELSEC 14 TROUBLESHOOTING

14.2.3 When the instruction displayed on the screen is not effective at installation

The following tables show the instruction when the screen is displayed.

Screens Instructions

This screen is displayed when user account control is enabled.

Click "Allow" or the Yes button.

Click the Yes button.

MELSECPowerManager is installed and the

Windows R Power Options settings are changed automatically. For details of MELSECPowerManager, refer to

Appendix 11.

If this screen is displayed during the installation or at

the installation completion, click "This program installed correctly". If this screen is displayed when the installation is

aborted, click the Cancel button and close the

screen. Do not select "Reinstall using recommended settings". An incorrect module may be installed.

Page 174: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

14 - 8 14 - 8

MELSEC 14 TROUBLESHOOTING

Screens Instructions

Click "Install this driver software anyway"

Confirm the publisher is "MITSUBISHI ELECTRIC CORPORATION", and click the Install button.

This screen may be displayed a couple of times.

The message is displayed when .NET Framework 3.5 (including .NET 2.0 and 3.0) is set to disabled. Reinstall the utility after searching the "Turn Windows features on or off" on the control panel and enabling the function of ".NET Framework 3.5 (including .NET 2.0 and 3.0)". The procedure when .NET Framework 3.5 (including .NET 2.0 and 3.0) is disabled is the same procedure as MELSOFT products. For details of the procedure, refer to the technical bulletin FA-A-0153 or FA-A-0207.

The message is displayed when a function that is necessary for installation has been set to disabled in Windows. Enable the setting by following the procedure shown below. 1. Select [Control Panel] - [System and Security] -

[Administrative Tools] - [Local Security Policy]. 2. Select [Local Policies] - [Security Options]. 3. Select "Enable" for "User Account Control: Detect

application installations and prompt for elevation". 4. Restart the personal computer.

14.2.4 When the driver is not installed

The driver is installed automatically when installing the board on the personal computer after installing the software package.

Page 175: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

14 - 9 14 - 9

MELSEC 14 TROUBLESHOOTING

When the "Found New Hardware Wizard" screen is not displayed automatically after the board installation, update the driver on the "Device Manager" screen.

1) Open the Windows R Device Manager screen. Right-click on

"Network Controller" and select "Update Driver Software".

2) Click "Install from a list or specific location (Advanced)".

3) Insert the CD-ROM of the software package to the CD-ROM drive.

4) Specify the driver software for "Search for driver software in

this location" according to the following information, and click

the Next button.

<For 32-bit version operating system*1>

Specify "\Drivers\x86" of the CD-ROM drive to be used.

(Example: "D:\Drivers\x86")

<For 64-bit version operating system*1>

Check "Include this location in the search" and specify

"\Drivers\x64" of the CD-ROM drive to be used.

(Example: "D:\Drivers\x64") *1: The operating system can be checked by Windows system

information. For details, refer to the Microsoft R Knowledge Base. support.microsoft.com/kb/827218 (As of August 2013)

(End)

If the troubleshooting above does not help, refer to Section 14.9.

POINT

If "Block - Never install unsigned driver software" is selected under [Control Panel] - [System] - [Hardware] - [Driver Signing], the driver may not be installed. Select "Ignore - Install the software anyway and don't ask for my approval", or

"Warn - Prompt me each time to choose an action", and install the driver.

Page 176: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

14 - 10 14 - 10

MELSEC 14 TROUBLESHOOTING

14.3 When MELSECNET/H Board did not Operate Normally

When the personal computer on which the board is installed is not started, or the system shut down or system reset is occurred, check the items following the procedure shown below.

1. Uninstall the board and check if the personal computer is started. • Checking personal computer and operating system (Refer to Section 14.3.1)

2. After restarting the personal computer, check if there is any error.

• Checking on Event Viewer screen (Refer to Section 14.3.2) 3. Install the board and restart the personal computer.

• Checking the board installation status (Refer to Section 6.3.3)

• Checking on the Device Manager screen (Refer to Section 14.3.3)

If the troubleshooting above does not help, refer to Section 14.9.

After starting the personal computer on which the board is installed, check the items following the procedure written in "Basic checking procedure". (Refer to Chapter 14(1))

(1) The system shutdown occurred when driver is uninstalled or

disabled Do not uninstall or disable the driver on the "Device Manager" screen when the board is normally recognized. If it is uninstalled or disabled, the operating system may shut down (blue screen).

14.3.1 Checking personal computer and operating system

Check if the personal computer or operating system has any problem.

Item Corrective action

Is the power supply ensured? Check the power outlet and power cable of the personal computer.

Does the board operate normally if uninstall the other

optional boards?

• Change the installation location of the board.

• Check the resource acquisition status of other board and change

the resource on the BIOS setting screen or "Device Manager"

screen.

• Reinstall the driver of the other optional boards.

• Replace the other optional boards.

Does the board operate normally on another personal

computer?

• Reinstall the operating system after formatting HD.

• Repair or replace the personal computer.

For the problem of the personal computer or operating system, contact the personal computer or operating system manufacturer.

Page 177: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

14 - 11 14 - 11

MELSEC 14 TROUBLESHOOTING

14.3.2 Checking on Event Viewer screen

Event logs related to the MELSECNET/H board are displayed as "AMneth" in the Source field on the "Event Viewer" screen. The following table lists the errors displayed in the event viewer.

Event ID

(0 to FFFFH) Error content Corrective action

0 (0H)

Failed to start the MELSEC network service.

Failed to register the main thread of service, or failed to set

the service status.

Restart the PC. If the error persists, reinstall

WindowsR

.

257 (101H) The MELSECNET/H board is not loaded, or the I/O address is

overlapping with other hardware.

Change the I/O address setting for the

MELSECNET/H board or other hardware. 1

258 (102H) No response from hardware. Replace the MELSECNET/H board.

259 (103H) The number of MELSECNET/H boards detected exceeds the

maximum number that can be loaded.

Remove MELSECNET/H boards until the number

falls within the maximum limit

260 (104H) The board conflicts with other device. Check for overlapping setting with other optional

board.

261 (105H) An attempt to create a device object has failed. Increase the system memory.

262 (106H) An attempt to link the device name has failed. Reinstall WindowsR

.

263 (107H) An attempt to secure dual-port memory has failed. Check for overlapping setting with other optional

board. 264 (108H) An attempt to perform interrupt registration has failed.

265 (109H) An error occurred when reading I/O. Replace the MELSECNET/H board.

266 (10AH) An error occurred when writing I/O.

267 (10BH) An error occurred during memory transfer. Reinstall WindowsR

.

268 (10CH) An error occurred during receiving process. ——

269 (10DH) An error occurred during sending process. ——

270 (10EH) An error occurred during interrupt process.

Reinstall WindowsR

.

271 (10FH) An error occurred during UNLOAD process.

272 (110H) An error occurred during StartIo process.

273 (111H) An error occurred during critical session.

274 (112H) An error occurred during IoTimer process.

275 (113H) An error occurred during IoCompletion process.

276 (114H) An error occurred during DPC process.

277 (115H) An error occurred when opening registry database.

278 (116H) An error occurred when reading from registry database.

Page 178: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

14 - 12 14 - 12

MELSEC 14 TROUBLESHOOTING

Event ID

0 to FFFFH Error content Corrective action

279 (117H) An error occurred when writing to registry database.

• After installing SW0DNC-MNETH-B, restart the computer and confirm that this error does not occur.

• Increase the system memory and disk capacity. • When the error has occurred at updating

Windows R

8.1 or upgrading the operating system with the software package installed, reinstall the software package.

280 (118H) A request that cannot be processed was received from other

station. ——

281 (119H) Retry transmission was executed during transmission

process. ——

286 (11EH) Failed to allocate the Memory Area. Increase the memory.

287 (11FH) Link Parameter is nothing or has abnormal data. Set the parameter with MELSECNET/H utility,

and reset the board.

288 (120H) The Driver WDT error occurred on the MELSECNET/H board

driver side.

Remove another option board.

Take corrective actions for the Driver WDT error.

(Refer to Section 14.7.2.)

295 (127H) The Board WDT error had occurred.

Replace the MELSECNET/H board. 296 (128H) The CLOCK STOP error had occurred.

297 (129H) The Target Abort error had occurred on the PCI bus.

304 (130 H) The Data Parity error had occurred on the PCI bus.

305 (131 H)

Entering sleep mode or hibernation mode, or fast startup is

detected.

The board is not operated normally because the sleep mode,

hibernation mode, and fast startup is not supported by the

board.

Change the power option not to enter the sleep

mode, hibernation mode, or disable the fast

startup function and restart the personal

computer.

33027 (8103H) The driver is not yet started, or an error occurred while

opening the driver.

Correct the cause of the driver error, then restart

the PC.

33029 (8105H)

An error occurred while resetting the MELSECNET/H board.

One of the following two conditions is suspected as the cause.

1) The common memory area used by the MELSECNET/H

board may be in contention with other device.

2) No response was received from the MELSECNET/H

board.

1) Check for overlapping setting with other

optional board.

2) Perform memory and I/O diagnosis using the

MNETH utility. If the error persists, replace the

MELSECNET/H board.

1 : If an event error occurs in event viewer, make the following setup setting on the PC.

(Limited to the PC includes those setup setting items.)

Example)

BIOS Setup Utility

Plug & Play O/S : [YES] [No]

Reset Configuration Data : [No] [YES]

Then, restart the PC.

Page 179: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

14 - 13 14 - 13

MELSEC 14 TROUBLESHOOTING

14.3.3 Checking on Device Manager screen

Check if the board is displayed on the Windows R Device Manager screen.

Item Corrective action

Is the driver name of the board not displayed on the

"Device Manager" screen?

The board or driver is not installed.

• If the board is not installed, install the board.

• If the board is already installed, check the board installation

status and reinstall the board.

• Reinstall the software package.

• If the board operates normally on other personal computer,

the personal computer may have any problems. In this case,

repair or replace the personal computer.

• If the board does not operate normally on other personal

computer, replace the board.

Is "!" displayed next to the icon on the "Device Manager"

screen?

The board installation failed.

• Reinstall the software package.

• Check the board installation status and reinstall the board.

• If the board operates normally on other personal computer,

the personal computer may have any problems. In this case,

repair or replace the personal computer.

• If the board does not operate normally on other personal

computer, replace the board.

If the corrective action above does not help, refer to Section 14.9.

Remarks

"?" is displayed next to the icon, however, the MELSECNET/H board is recognized normally.

POINT

Do not uninstall or disable the driver of the board on the Device Manager when the board is normally recognized. If it is uninstalled or disabled, the operating system may shut down (blue screen).

Status after the installation of the MELSECNET/H board.

Page 180: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

14 - 14 14 - 14

MELSEC 14 TROUBLESHOOTING

14.4 Flowchart to Use when Data Link is not Achieved

The following describes a flowchart that must be checked when no data link is achieved after the MELSECNET/H board and Control station as well as normal stations were connected.

YES

YES

Refer to Section 14.4.5, "Flowchart touse when unable to achieve data link forfor specific station".

YES

Refer to Section 14.4.4, "Flowchart touse when unable to achieve data linkfor entire system".

YES

Refer to Section 14.4.3, "Flowchart touse when L.ERR LED turns on".

YES

Refer to Section 14.4.2, "Flowchart touse when SD/RD LED does not turn on".

YES

Refer to Section 14.4.1, "Flowchart touse when RUN LED is unlit".

START

Check the MELSECNET/H board LED

Is the "RUN" LED unlit?

Does the "SD/RD" LEDremain unlit?

Is the "L.ERR" LED lit?

Start the MNETH utility and select"8Board Information" screen.

Is "T. PASS" LED ofcurrent station lit?

Select "Each station status" screen.

Can data link be achievedfor the entire system?

Can data link be achievedfor a specific station?

END

NO

Current station normal

Baton passing of current station normal

NO

NO

NO

NO

NO

END

POINT

Refer to the following when the "T. PASS" LED lights up and goes out randomly.

<Cause> The line may have been in an unstable condition.

<Action>

1) Check the connector for disconnection and the cable for breakage. 2) Verify that the specified cable is used. 3) Check that the overall extension cable length and station-to-station distance is

within the specified range.

Page 181: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

14 - 15 14 - 15

MELSEC 14 TROUBLESHOOTING

14.4.1 Flowchart to use when RUN LED is unlit

NO (The "RUN" LED has been off since the power was turned on.)

YES

NO (The "RUN" LED turned offwhile communicating)

Did the LED turnoff even when communicationwith other station was being

performed?

Is communication withother station continued?

Replace the MELSECNET/H boardsince the MELSECNET/H board's"RUN" LED is broken.

Is therea WDT (288) error log 1

remaining?

Did the "RUN"LED turn on after replacing the

MELSECNET/Hboard?

Check PC hardware, etc.

Lengthen the driver WDT monitoring time(Refer to Section 14.7.)

Complete

An error occurs.

YES

NO

YES

YES

NO

1: WDT error logs can be checked on the event viewer. (Refer to 14.3.2)

Page 182: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

14 - 16 14 - 16

MELSEC 14 TROUBLESHOOTING

14.4.2 Flowchart to use when SD/RD LED does not turn on

The board information screen of MNETH utility displays SD and RD LED status. This function is the same as the MELSECNET/H board's LED messages.

YES

NO

NO

NO

NO

NO

NO

YES

YES

NO

NO

YES

YES YES

YES

YES

An error occurs.

Is the L.ERR LED lit? Go to Section 14.4.3.

Is thecontrol station

parameterOK?

Check the control stationparameter.

Does the"SD" LED remain

unlit?

Does the"RD" LED remain

unlit?

NormalTurn on/off the B, X and Yassigned to the host viaPC.

Turn on/off the B, X and Yused by PC at otherstations.

Monitor B, X and Y atother stations.

Monitor B, X and Y via PC.

Does the B,X and Y turn on/off at

other stations?

Replace the PC MELSECNET/H board.

Does the B,X and Y turn on/off

at PC?

Check the monitorcondition or user program.

Are themonitor conditionand user program

normal?

Replace the MELSECNET/Hboard since the "SD" and"RD" LEDs are broken.

Did the SD/RDturn on?

Consult with the dealerregarding the problem.

Complete

Page 183: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

14 - 17 14 - 17

MELSEC 14 TROUBLESHOOTING

14.4.3 Flowchart to use when L.ERR. LED turns on

YES

NO

An error occurs.

Has the MNETH utility standard?

Stop the user program and activatethe MNETH utility.

Select "Board Information" screen andidentify the error type from LED status.

Select "Loop monitor" screen.

NOIs forward loop normal?

YES

Check the cable for the host forward loop.

Did the data link begin?

Complete

Check the cable for the host reverse loop.

Consult with dealer regarding the problem.

Check for the following error causes:(1)(2)(3)

(4)

Is the error type "PRM.E"?

Remove the error cause(s).

Duplication of station No. for MELSECNET/H board.Coexistence of any different network types within the same network.In the case of MELSECNET/H Extended mode, use of theMELSECNET/H board of ROM version 2X or later.(For checking the ROM version, refer to Appendix 5)Error code stored in SW0055.

NO

YES

YES

NO

1

1: For the error code in SW0055, refer to the "Q Corresponding MELSECNET/H Network System Reference Manual (PLC to PLC network)".

The error code in SW0085 can be also checked by monitoring SD85 with Device Monitor Utility. (Refer to "MELSEC Data Link Library Reference Manual".)

Page 184: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

14 - 18 14 - 18

MELSEC 14 TROUBLESHOOTING

14.4.4 Flowchart to use when unable to achieve data link for entire system

NO

YES

YES

NO

YES

NO

YES

NO

NO

YES

YES

YES

YES

NO

NO

NO

1) 2) 3)

An error occurs.

Is parameter setto the control station?

Set the parameter.

Did the data link begin?

Is the controlstation mode set to "Online" ?And is its station number set

to 1 to 64 ?

Correct the control station mode andstation number then reset the programmablecontroller CPU and MELSECNET/H board.

Did the data link begin?

Is the watchdog timesetting for parametergreater than the link

scan time?

Complete

Correct the set value for watchdogtime.

Did the data link begin?

Is the control station's"RUN" LED lit?

Are the "RUN" LEDsof the first station through

the last station lit?

Go to the next page. Go to the next page. Go to the next page.

Page 185: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

14 - 19 14 - 19

MELSEC 14 TROUBLESHOOTING

YES

YES

NO

NO

YES

NO

YES

NO

1) 2) 3)

Replace the MELSECNET/H board network module of the faulty station among the control station and first through last stations.

Did the data link begin?

Perform self-loopback tests for the control station and first through last stations.

Is there any station with error?

Replace the MELSECNET/H board network module of the faulty station.

Did the data link begin?

Check the loop line using a station-to-station test.

Replace the faulty cable. Did the data link begin?

Consult with the dealer regarding the problem.

Complete

REMARK

For the Q80BD-J71LP21-25, Q81BD-J71LP21-25 or Q80BD-J71LP21S-25 with the communication speed set to 25 Mbps, mounting multiple boards with the same network No. is not allowed. Doing so may cause errors at all stations at the time of

OS startup/shutdown or when resetting the board. If multiple boards with the same network No. should be installed, set the communication speed to 10Mbps.

Page 186: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

14 - 20 14 - 20

MELSEC 14 TROUBLESHOOTING

14.4.5 Flowchart to use when unable to achieve data link for specific station

NO

YESNO

YES

NO

YES

NO NO

YES

YES

1) 2) 3)

Is the faulty station's"RUN" LED lit?

Is the faulty station a PC?

Refer to Section 14.4.1. Refer to the Q Corresponding MELSECNET/HNetwork System Reference Manual(PLC to PLC network).

Did the data linkreturn to normal?

Complete

Is the link modeset to "ONLINE"?

Is it a PC?

Go to the next page. Go to the next page. Go to the next page.

YES YES

NO

NO

NO

YES

NO

YES

An error occurs.

Detect a faulty station using MNETH utilityand each station status screen.

Is there any faulty station with error? Is the parameter correct? Check the control station's parameter.

Is the data link disabled station PC?

(programmable controller)

Is it the MNETH utility?

MNETH utility

Check each setting for MNETH utility.

User program

Check the user program.

1: When a faulty station is detected, check if the data link cable of the faultystation is connected properly.If the data link cable is disconnected, make sure to power off the personalcomputer and external power supply before reconnecting the cable.

1

Check the programmable controller program.

Page 187: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

14 - 21 14 - 21

MELSEC 14 TROUBLESHOOTING

NO

YES

NO

YES

YES

NO

YES

YESNO

1) 2) 3)

YESNO

YES

NO

NO

User program

User program

Set to "ONLINE" in the"Board information" settingscreen.

Stop the user program andperform the same operationas for the MNETH utility.

Set the PLC data link modeto ONLINE, and reset.reset.

Did the data linkreturn to normal?

Did the data linkreturn to normal?

Did the data linkreturn to normal?

Did the data linkreturn to normal?

Is the station numberset correctly?

Is it a PC?

Complete

Complete

Complete

Complete

Power off the PC, then setthe correct station number.Power on the power again.

Power off the PC, then setthe correct station number.Power on the power again.

Power off the PLC, then setthe correct station number.Power on the power again.

Check with a self-loopback test at thefaulty station.

Is there any error?

Replace the MELSECNET/H boardnetwork module of the faulty station.

Check the link cables before and afterthe faulty station using a station-to-station test.

Replace the faulty link cable.

Consult with the dealer regardingthe problem.

MNETH utility

MNETH utility

Page 188: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

14 - 22 14 - 22

MELSEC 14 TROUBLESHOOTING

14.5 Flowchart to Use when Error Occurred During Data Link

The following explains corrective actions when an error occurred during data link. 14.5.1 Flowchart to use when unexpected value is input to specific link device

Check the following items. (1) Check for a station with link error using the each station status screen. (2) Check the parameter assignment range at the control station. (3) Check the device range used in the programmable controller program at the

programmable controller. (4) Check, in the user program, argument data for the Data Link function accessing

the specific link device. 14.5.2 Flowchart to use when data cannot be written or read in user program

YES

NO

YES

NO

YES

NO

YES

NO

START

Is the communicationfunction's return value

abnormal?

Check the error with the error code table.Refer to MELSEC Data Link LibraryReference Manual.

Check the error with the error code table.Refer to MELSEC Data Link LibraryReference Manual.

Monitor the device to be accessed fromthe device monitor utility.Also, perform a data change to seeif data can be written.

Can the device be monitored?(Was the data written?)

Check the user program.

Did an error occur?

Was it host access?

Check the MELSECNET/H board isoverlapping with the system and otherboards.

Check according to the flowcharts inSection 14.4.

Page 189: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

14 - 23 14 - 23

MELSEC 14 TROUBLESHOOTING

14.5.3 Flowchart to use when communication is disabled from time to time during user

program execution

YES

NO

YES

NO

NO

YES

START

Did the user programreturn an error code?

Confirm the definition of the error usingthe error code table, and check the userprogram and access station.Refer to MELSEC Data Link LibraryReference Manual.Start MNETH utility and check the each

station status.

Is there any faulty station?

Replace the link cable or faultystation.

Set a system configuration thatincludes only the control station andhost station.

Is the link normal?

Replace the link cable or additionalstation connected.

Add adjacent stations one after theother and perform link monitor for asufficient period.

Page 190: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

14 - 24 14 - 24

MELSEC 14 TROUBLESHOOTING

14.5.4 Precautions for installing other optional board

Executing user programs (including the device monitor utility) for each board simultaneously under the following condition may cause an error. When an error occurs in the user program, take the action shown below.

<Condition>

A personal computer into which the MELSECNET/H board and other optional

board are installed and where the resources were allocated automatically by Plug-and-Play is used.

<Action> (1) Change the positions where the MELSECNET/H board and other optional

board are installed.

(2) In the BIOS setup, exchange the IRQs between the MELSECNET/H board and other optional board or change their IRQs.

Page 191: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

14 - 25 14 - 25

MELSEC 14 TROUBLESHOOTING

14.6 When External Power Supply Function does not Work Properly

When the external power supply does not operate properly, check the following items.

Item Corrective action

Is the LED of external power supply OFF? Review the wiring of the external power supply cables. Inset the

connectors and contacts until they click. (Refer to 6.4.4)

Is the voltage output to the connector of the external

power supply cable?

Set the voltage between the pins of the connector (cable side)

is within the range of the specification (Section 3.2).

Check the external power supply.

If any of the corrective actions above do not help, refer to Section 14.9.

Page 192: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

14 - 26 14 - 26

MELSEC 14 TROUBLESHOOTING

14.7 Troubleshooting for WDT Error Occurrence

14.7.1 Board WDT error

When the board WDT error occurred, check the following items.

Item Corrective action

Is the board installed properly? • Check the board installation status.

Does the board operate on other personal computer? • After formatting the HD, install the operating system again.

• Repair or replace the personal computer.

If any of the corrective actions above do not help, refer to Section 14.9. 14.7.2 Driver WDT error

When the driver WDT error occurred, check the following items.

Item Corrective action

Has the error occurred due to the system overload

temporarily?*1

• Reset the board. (Refer to Section 9.2.9)

• Restart the personal computer

Is the same error occurred repeatedly?

(Is the system overloaded constantly?)

• Remove the factor of system overload.

• Disable the driver WDT function or increase the driver WDT

monitoring time. (Refer to Section 9.2.11)

1: A driver WDT error may occur when the system is overloaded temporarily due to the following factors.

• Windows R start processing at the personal computer startup

• Operation of a device driver such as a graphic board

• Operation of other software applications

If any of the corrective actions above do not help, refer to Section 14.9.

Page 193: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

14 - 27 14 - 27

MELSEC 14 TROUBLESHOOTING

14.8 Troubleshooting for Slow PC Operation

This section explains probable causes and troubleshooting when a PC becomes slow. (1) Possible causes for slow PC operation

The MELSECNET/H driver refreshes link device data assigned to another station from the refresh data storage area on the MELSECNET/H board to the

MELSECNET/H drive buffer, and those assigned to the host station from the drive buffer to the refresh data storage area at specified intervals. 1 If more than one of the following causes occurs, the processing time for the

above link refresh is increased in the total PC processing and causes slow operation:

• Too many link device points are set for the entire network.

• The link scan time value is too small.

• The computational power of the PC is low. 1: It indicates the case where Link Refresh is selected in the Link Device

Access Method setting on the MNETH utility’s "Driver" screen.

(2) Troubleshooting When the PC becomes slow, perform the following:

• Increase the link refresh interval value on the MNETH utility’s "Driver" screen.

• Set the constant link scan in Common parameter setting of the control station.

• Decrease the number of link device points in Common parameter setting of the control station.

Page 194: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

14 - 28 14 - 28

MELSEC 14 TROUBLESHOOTING

14.9 Information Needed when Calling with Inquiry

When the troubleshooting cannot solve the problem, or a board failure occurs, please consult your local Mitsubishi service center or representative. Inform the following conditions and situations when inquiring the problems.

(1) Product information

(a) Product version Inform the model name and version of the board and utility.

(b) Personal computer Inform the following descriptions. • Name of the personal computer (manufacturer) • CPU

• Memory size • Operating system

(c) Other option board Inform the following descriptions. • Existence (If exist, type, the number of boards and so on)

• Situation checked with disconnecting other option boards

(2) Failure content (a) Failure description (details)

Example) The LINK LED does not turn on even though the computer is turned on.

(b) Occurrence frequency

(c) Occurrence condition

If the failure occurs only in the specific case, inform the occurrence condition noticed.

(c) Troubleshooting result

Inform the following descriptions.

• The result of troubleshooting performed • The situation when checking with other boards or computers Example) Event ID 295 "The Board WDT error had occurred." error is

displayed on the event viewer when the personal computer is started. It also occurs when mounting the problem board with another computer. Other boards mounted with the computer works properly.

Page 195: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

App - 1 App - 1

MELSEC APPENDIX

APPENDIX

Appendix 1 Cautions for Accessing Redundant CPU System

This section explains the cautions for accessing a Redundant CPU system using the MELSECNET/H board.

Access to Redundant CPU system

(1) Redundant CPU specify

When the system (control system, standby system, System A, System B) of the

Redundant CPU is specified to access the Redundant CPU, the Logical Sta. No. set on the "target" screen of the MELSECNET/H utility is used for access. Refer to Section 9.2.10 for the setting of the Logical Sta. No.

App.

Page 196: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

App - 2 App - 2

MELSEC APPENDIX

(2) Operation at occurrence of system switching

When system switching occurs during access to the Redundant CPU, access to the Redundant CPU set for the Logical Sta. No. is continued. (Example) When the following Logical Sta. No.66 was specified for access

Logical Sta. No.66 Network No.: 1 Sta. No.: 1 Multiple PLC specify: No specification Redundant PLC specify: Control system

Before system switching

MELSECNET/H(Network No.1)

Tracking cable

Station No. 3

Control system Standby system

Station No. 2Station No. 1

Personal computer(MELSECNET/H board)

After system switching

MELSECNET/H(Network No.1)

Tracking cable

Station No. 3

Control system Standby system

Station No. 2Station No. 1

Control systemStandby system

Personal computer(MELSECNET/H board)

POINT To judge which system in the Redundant CPU system is being accessed by MELSECNET/H board, create a program to monitor the following special relays. (1) When checking which system is being accessed, System A or System B

SM1511

System A identification

flag

• Identifies system A/system B of a redundant system. • Remains ON/OFF even if the tracking cable is disconnected while the redundant system

is running.

System A System B At the time of TRK.CABLE ERR.(Error code: 6120) occurrence (System not determined.)

SM1512 System B

identification flag

SM1511 ON OFF OFF

SM1512 OFF ON OFF

(2) When checking the operation system status

SM1515

Control/ Standby system status

• Indicates the CPU module operation status • Remains ON/OFF even if the tracking cable is disconnected while the redundant system

is running.

Control system

Standby system

At the time of TRK.CABLE ERR.(Error code: 6120) occurrence (System not determined.)

SM1516 SM1515 ON OFF OFF

SM1516 OFF ON OFF

App.

Page 197: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

App - 3 App - 3

MELSEC APPENDIX

(3) Retry processing for error that will occur during system switching

processing When the MELSEC data link library is used to access the Redundant CPU during system switching being processed by the Redundant CPU, a system switching error (error code 4248H), CPU starting error (error code 4004H), other system

CPU module error (error code 4245H),access destination illegal error (error code FFDFH) or similar error occurs. Create a program that will check the error code and perform retry processing as

necessary in that case.

(a) The following indicates the functions that will result in error if executed during system switching.

Functions that will result in error by system switching

MELSEC data link library mdControl,mdDevRst,mdDevSet,mdRandR,mdRandW,

mdReceive,mdSend,mdTypeRead

(b) The following example gives a flowchart for error occurrence

at batch write.

START

END

YES

NO

YES

NO

Wait processingis executed.

Has error occurred?

Normal processing is executed.

Error code is checked.*

Does the errorrequire retry processing?

Error handling is executed.*

Retry processing

Write processing(mdSend instruction), etc.

1

2

*1: For the details and corrective action of the error code, refer to "Error code returned to request source during communication with CPU module" in the QCPU User's Manual (Hardware Design, Maintenance

and Inspection). *2: Execute retry processing as required depending on the system

specifications.

Page 198: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

App - 4 App - 4

MELSEC APPENDIX

(4) Automatic switching of communication route

If a communication error occurs during access to the Redundant CPU connected to MELSECNET/H, the communication route is automatically switched to continue access to the control system. Hereinafter, this automatic switching of the communication route is referred to as route switching.

The following describes the route switching conditions, how to check for route switching occurrence, and access to the control system by route switching.

(a) Route switching conditions

When access is being made under the following conditions, access to the Redundant CPU is continued by route switching if a communication error occurs. Conditions for continued access

Operation mode Backup mode, Separate mode

Target system Control system, Standby system, System A, System B

However, if a tracking error 1 had already occurred at a start of communication, access to the control system is not continued by route switching even if tracking is recovered after that.

1: Includes the status in which either Redundant CPU is powered off or reset.

(b) How to check whether route switching occurred or not and

examples of access by route switching 1) How to check whether route switching occurred or not

When communication is being made in Target system, whether communication is continued by route switching due to communication error can be estimated. Create a program that will monitor the following special relay and special registers.

<Special relay and special registers to be monitored and estimated possibility of route switching>

SM1600 1 SD1590 2 SD1690 2 Possibility of route switching Reference

OFF Either one is other than 0 Since a system switching request from the network module was detected, route switching may have been executed. 2) Fig. 1

ON 0 0 Since an other system fault occurred, route switching may have been executed. 2) Fig. 2

ON Either one is other than 0 Since an other system fault occurred or a system switching request from the network module was detected, route switching may have been executed.

2) Fig. 2 2) Fig. 1

1: Even if SM1600 is ON, route switching does not occur when the

CPU is not accessed via the tracking cable. 2: When using SM1600, SD1590 and SD1690 to estimate whether

route switching has occurred or not for the Redundant CPU connected to MELSECNET/H, check the following items in the redundant setting of the network parameter dialog box of GX Developer. • Issue a system switching request at disconnection detection. • Issue a system switching request at communication error.

Check the following based on the statuses of the above special relay and special registers, and remove the error cause. • Check the Redundant CPU for an error. • Check the tracking cable status and whether the tracking cable is

correctly connected. • Check the relevant network module for an error and the network

where the relevant network module is connected for an error.

Page 199: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

App - 5 App - 5

MELSEC APPENDIX

2) Examples of access by route switching

The following shows examples of route switching during access to the control system.

<When system switching occurs at communication error>

Control system

MELSECNET/H

Control systemStandby system

Tracking cable

Tracking cable

MELSECNET/H

Personal computer(MELSECNET/H board) Connection to control system

Standby systemerror

Personal computer(MELSECNET/H board) Connection to control system

communication

Fig. 1 Route switching example 1

<When standby system fault occurs>

MELSECNET/H

MELSECNET/H

Control system

Control systemStandby system

Tracking cable

Tracking cable

Personal computer(MELSECNET/H board) Connection to control system

Standby system

Personal computer(MELSECNET/H board) Connection to control system

errorStandby system

Fig. 2 Route switching example 2

Page 200: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

App - 6 App - 6

MELSEC APPENDIX

POINT • Route switching is not executed if a communication error has already occurred at

a communication start*1 for the Redundant CPU specified for the Logical Sta. No. (A communication error occurs.) If a communication error has occurred, refer to (b) in (4) Automatic switching of communication route, and remove the communication disturbance. *1: First communication after execution of the mdOpen function in the MELSEC

data link library (communication using the mdReceive, mdSend, mdControl, mdDevRst, mdDevSet, mdRandR, mdRandW or mdTypeRead function).

• If other station access (including the programmable controller CPU other than the Redundant CPU) is made to nine or more stations simultaneously, automatic switching of communication route may not be executed.

REMARK

The following indicates details of the special relay and special registers to be

monitored when estimating whether route switching occurred or not.

Number Name Meaning Explanation

SM1600 Other system error flag

OFF: No error ON: Error

• Turns on when an error occurs during redundant system error check. (Turns on when either of bits for SD1600.)

• Remains off when no errors are present.

SD1590

Module No. for network module requesting route switching in host system

Module No. for network module requesting route switching in host system

• Any of the following bits turns on corresponding to module No. for network module requesting route switching in host system.

• Turns off by the system after recovery from error of the relevant module by user.

b1 b0b15 b11to to

to

0 0/1 00/1SD16900: OFF1: ON

Bit status

Module No. 0: Invalid, as CPU moduleuses 2 slots.

Module No. 1: Indicates the module tothe right of CPU module

Module No.11: Indicates the module atthe right end of a 12-I/Oslot base (Q312B)

• Refer to SD1690 for module No. for network module requesting route switching in other system.

SD1690

Module No. for network module requesting route switching in other system

Module No. for network module requesting route switching in other system

• Any of the following bits turns on corresponding to module No. for network module requesting route switching in other system.

• Turns off by the system after recovery from error of the relevant module by user.

b1 b0b15 b11to to

to

0 0/1 00/1SD16900: OFF1: ON

Bit status

Module No. 0: Invalid, as CPU moduleuses 2 slots.

Module No. 1: Indicates the module tothe right of CPU module

Module No.11: Indicates the module atthe right end of a 12-I/Oslot base (Q312B)

• Refer to SD1590 for module No. for network module requesting route switching in host system.

Page 201: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

App - 7 App - 7

MELSEC APPENDIX

Appendix 2 Host Station Status at Power ON/OFF When Using Q80BD-J71LP21S-25

When using the Q80BD-J71LP21S-25, the host station status varies depending on the ON/OFF status of the external power supply and personal computer as shown below. (1) When the system is started

No. Status External power supply

PC power

Host station status

Loop status 1 Communication

status 2 Data link 3

1 External power supply OFF before ON OFF OFF Loopback occurred

Abnormal (Disconnected)

Not executed

2 External power supply ON before PC startup (power-ON)

ON OFF

Normal Abnormal

(Disconnected) Not executed

3 PC startup (power-ON) before MELSECNET/H driver startup

ON ON

4 After MELSECNET/H driver startup ON ON Normal Normal

communication Executed

(2) When the personal computer is started

No. Status External power supply

PC power

Host station status

Loop status 1 Communication

status 2 Data link 3

5 4 PC power OFF before PC startup (power-ON)

ON OFF Normal Normal

communication Not executed

6 PC power startup (power-ON or restart) before MELSECNET/H driver startup

ON ON Normal Abnormal

(Disconnected) Not executed

7 After MELSECNET/H driver startup ON ON Normal Normal

communication Executed

(3) When the system is shut down

No. Status External power supply

PC power

Host station status

Loop status 1 Communication

status 2 Data link 3

8 PC power OFF before external power supply OFF

ON OFF Normal Normal

communication Not executed

9 External power supply OFF OFF OFF Loopback occurred

Abnormal (Disconnected)

Not executed

1: The status can be checked on the network monitor screen of the MELSECNET/H utility, the Network diagnostics of GX

Developer connected to other station’s PLC or at areas SW91 to SW9A.

2: The status can be checked on each station status screen of the MELSECNET/H utility, the Network diagnostics of GX

Developer connected to other station’s PLC or at areas SW70 to SW73.

3: The status can be checked on the Network diagnostics of GX Developer connected to other station’s PLC or at areas

SW74 to SW77.

4: This status is irrelevant when rebooting the personal computer without turning off its power.

Page 202: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

App - 8 App - 8

MELSEC APPENDIX

Appendix 3 Procedures for Replacing Boards

This section explains the procedure to replace a MELSECNET/H board. (1) Replacement procedure

Start

Record the settings before the replacement

Record the channel numbers and parameter settings that were used

before the replacement.

• • • Chapter 7 PARAMETER SETTINGS

Section 9.2.2 Board list screen operation

Power OFF

Power OFF the personal computer.

Uninstall the board

Remove the target board from the personal computer.

Install the board

Install the target board to a slot of the personal computer.

Fix the board

Fix the board to a slot on the personal computer using the board fixing screws.

Wire the external power supply cables

For the board with external power supply function, wire the external

power supply cables.

• • • Section 6.4.4 External power supply

cable wiring

Power ON

Power ON the personal computer.

Set the Channel No.

Set the channel No. recorded before the replacement. • • • Section 6.3.4 Channel No. Settings

Check the board

Test the hardware of the installed board. • • • Section 6.5 Test

Wire the cables

Wire the network cables for the installed board. • • • Section 6.4 Wiring

Page 203: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

App - 9 App - 9

MELSEC APPENDIX

Set the parameters

Set the parameters recorded before the replacement. • • • Chapter 7 PARAMETER SETTINGS

Check the network

Test the cable connection and data link on the network. • • • Section 6.5 Test

Execute a user program

Execute a user program or utility.

Operation

(2) Precautions

When a MELSECNET/H board is replaced, channel numbers are automatically

re-assigned. For details on the channel number to be assigned, refer to Section 6.3.4. As parameter settings (Refer to Chapter 7) correspond to channel numbers, the

replaced board works with the parameter settings shown below. • When un-used channel numbers are newly assigned:

Works with the default status.

• When channel numbers that were used are assigned: Works with the parameter settings corresponding to the channel numbers.

When replacing a MELSECNET/H board, check the parameter settings with the “Board information setting” screen.

Page 204: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

App - 10 App - 10

MELSEC APPENDIX

Appendix 4 Combinations of Boards with Existing Software

There is no restriction when using MELSECNET/H board with other MELSEC interface boards or MELSOFT products on the same personal computer. For the restrictions of the applicable operating environment and applicable access target, refer to the manual

of each product.

Page 205: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

App - 11 App - 11

MELSEC APPENDIX

Appendix 5 Checking Serial Number and Function Version

This section explains how to check serial number, the function version and ROM version of the MELSECNET/H board and the SW0DNC-MNETH-B version. (1) Checking serial number, function version, and ROM version of the

MELSECNET/H board (a) Checking serial number and function version

The function version of the MELSECNET/H board can be checked at "Serial" section as shown below.

(b) Checking ROM version The ROM version of the MELSECNET/H board is shown on "Board list" tab

in the MNETH utility.

Page 206: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

App - 12 App - 12

MELSEC APPENDIX

(2) Checking the SW0DNC-MNETH-B version

The SW0DNC-MNETH-B version is shown on "Version" tab in the MNETH utility.

Click!

Appendix 6 New and Improved Functions

Appendix 6.1 Change of hardware function

The following table shows the new and the improved functions in the MELSECNET/H board.

New and improved function First five digits of the serial

number

Software version of

SW0DNC-MNETH-B

MELSECNET/H Extended mode 06112 or higher 11M or later

Appendix 6.2 Update of software package

For details of the update version software and the functions which are added or changed, please consult your local Mitsubishi representative.

POINT

For the precautions when installing the software package, refer to Section 8.1.

Page 207: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

App - 13 App - 13

MELSEC APPENDIX

Appendix 7 Restrictions for Operating System

For the following applicable operating systems, use SW0DNC-MNETH-B with the supported version. The following version of software and manuals are provided continuously.

Operating system Supported version

SW0DNC-MNETH-B Manual number

Windows Server 2008 Windows Vista Windows Server 2003 R2

Windows XP

29F SH-080128-AA

Windows 2000

Windows NT Windows 98 Windows 95

25B SH-080128-X

Do not use a function added by a version newer than the supported version. (1) How to obtain the supported version

Please consult your local Mitsubishi representative.

(2) Manual For the function and handling method, refer to the manual of the product.

Page 208: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

App - 14 App - 14

MELSEC APPENDIX

Appendix 8 Warning Message Appears on Windows

Appendix 8.1 Overview of warning message

When an operating system with the user account control function is used, a warning

message appears when you run the MELSECNET/H utility or the Device monitor utility. (Refer to Section 9.1)

Page 209: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

App - 15 App - 15

MELSEC APPENDIX

Appendix 8.2 Methods for preventing the warning message

POINT The user account control (UAC) function prevents a crash (e.g. prevention of start-up of a program which executes unintended operation). Before setting this function, grasp that the security function offered by UAC will be disabled and fully understand the risk.

The following two methods are available for preventing a warning message.

(1) Disabling the user account control function

The following shows a procedure for disabling the user account control function.

1) Open the Control Panel.

2) Select [System and Security].

(To next page)

3) Select [Change User Account Control settings].

Page 210: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

App - 16 App - 16

MELSEC APPENDIX

(From preceding page)

(Setting completion)

4) Set the slide bar "Never notify" and click the "OK"

button.

Page 211: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

App - 17 App - 17

MELSEC APPENDIX

(2) Allowing the warning message without showing it

The following shows a procedure for allowing a warning message without

showing it.

1) Open the Control Panel.

2) Select [System and Security].

(To next page)

3) Select [Administrative Tools].

Page 212: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

App - 18 App - 18

MELSEC APPENDIX

(From preceding page)

4) Select [Local Security Policy]. REMARKS

When user account control is enabled the following screen appears. Click the Continue or Yes button.

5) Select [Local Policies].

(To next page)

6) Select [Security Options].

Page 213: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

App - 19 App - 19

MELSEC APPENDIX

(From preceding page)

7) Select [User Account Control: Behavior of the elevation prompt for administrators in Admin Approval Mode Prompt for consent].

(Setting completion)

8) Select [Elevate without prompting] on the <<Local Security Setting>> tab, and click the OK button.

Page 214: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

App - 20 App - 20

MELSEC APPENDIX

Appendix 9 Behavior When Personal Computer Enters Power Save Mode or Fast Startup

MELSECNET/H board does not support the power save mode (hibernate, sleep) and the fast startup function. The following explains the behavior of the personal computer when the personal computer enters each mode.

Appendix 9.1 Behavior when the personal computer enters the power save mode

(hibernate, sleep)

(1) Target operating system The following operating systems have the power save mode (hibernate, sleep)

• Windows 10, Windows Server 2016, Windows Server 2019 • Windows 8.1, Windows Server 2012 R2 • Windows 8, Windows Server 2012

• Windows 7, Windows Server 2008 R2

(2) Behavior when entering the hibernation mode/sleep mode The following explains the behavior of the board when the power save mode (hibernate, sleep) is entered on the personal computer. • The MELSECNET/H board stops its operation and is disconnected from the

network. • The board is not reconnected even after the personal computer returns from

the power save mode (hibernate, sleep).

• After the personal computer returns from the power save mode (hibernate, sleep), "-28141(9213H) : System sleep error" occurs when accessing MELSECNET/H board from the MELSECNET/H utility or an application

program, which includes MELSEC data link library function.

(3) Countermeasure When the personal computer is set to enter the power save mode (hibernate, sleep), the setting is changed by MELSECPowerManager. For details of MELSECPowerManager, refer to Appendix 10.

Page 215: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

App - 21 App - 21

MELSEC APPENDIX

Appendix 9.2 Behavior when the fast startup function is enabled

(1) Target operating system The following operating systems have the fast startup function. • Windows 10, Windows Server 2016, Windows Server 2019

• Windows 8.1, Windows Server 2012 R2 • Windows 8, Windows Server 2012

(2) Behavior when the fast startup function is enabled The following explains the behavior of the board when the fast startup function is enabled.

• The board is not reconnected even after the fast startup. • After the fast startup, "-28141(9213H) : System sleep error" occurs when

accessing MELSECNET/H board from the MELSECNET/H utility or an

application program, which includes MELSEC data link library function.

(3) Countermeasure When the fast startup function is enabled, the setting is changed to disabled by MELSECPowerManager. For details of MELSECPowerManager, refer to Appendix 10.

Page 216: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

App - 22 App - 22

MELSEC APPENDIX

Appendix 10 MELSECPowerManager

MELSECPowerManager is a service application which monitors the Windows R Power Options settings every 30 seconds to prevent the personal computer from entering the power save mode (hibernate, sleep).

MELSECPowerManager is applicable for the following operating systems. • Windows 10, Windows Server 2016, Windows Server 2019 • Windows 8.1, Windows Server 2012 R2

• Windows 8, Windows Server 2012 • Windows 7, Windows Server 2008 R2

When a personal computer is set to enter the power save mode (hibernate, sleep) or the fast startup function is enabled, the following message is displayed and the setting is changed by MELSECPowerManager.

Appendix 10.1 Installing MELSECPowerManager

MELSECPowerManager is installed automatically when the software package is installed to a personal computer

The operation starts after the personal computer is restarted.

Appendix 10.2 Uninstalling MELSECPowerManager

MELSECPowerManager is uninstalled automatically when the software package is uninstalled.

However, it is not uninstalled when another software package of MELSEC interface board is installed to the personal computer. Uninstall all software packages for MELSEC interface board installed on the personal

computer to uninstall MELSECPowerManager.

Page 217: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

App - 23 App - 23

MELSEC APPENDIX

Appendix 10.3 Checking MELSECPowerManager

The following explains how to check the installation and operating status of MELSECPowerManager. The following is a setting example when using Windows R 7.

1) Open the Control Panel and select [System and Security].

2) Select [Administrative Tools].

(To next page)

3) Double-click [Services].

Page 218: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

App - 24 App - 24

MELSEC APPENDIX

(From preceding page)

(Setting completion)

4) Check if MELSECPowerManager is registered.

POINT

• When MELSECPowerManager is disabled, the personal computer may enter the power save mode (hibernate, sleep) automatically depending on the settings on the

personal computer. Do not disable MELSECPowerManager because the MELSECNET/H board does not function normally if the personal computer enters the power save mode (hibernate, sleep). For the behavior of the board when the

personal computer enters the power save mode (hibernate, sleep), or the fast startup function is enabled, refer to Appendix 9.

• If MELSECPowerManager is disabled accidentally, right-click

"MELSECPowerManager" on the "Services (Local)" screen and select "Start" from the menu.

Page 219: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

App - 25 App - 25

MELSEC APPENDIX

Appendix 11 External Dimensions

Appendix 11.1 Q80BD-J71LP21-25, Q80BD-J71LP21G, Q80BD-J71LP21GE

140

153

19

147

12

1

99

90

21.65

5

3.2

RUN ERR.L

SD RDIN

OUT

BD808C394G51

(unit: mm)

Appendix 11.2 Q80BD-J71LP21S-25

20.32

21.63.2

5

5

147153

42140

99

75

153

12

1

BD808C394G51

CLASS2 ONLY

BD808C515G51

NC

+ 24V

24G

SD RD

RUN ERR.L

OUT

EXT.PW

EXT.PW

IN

(unit: mm)

Page 220: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

App - 26 App - 26

MELSEC APPENDIX

Appendix 11.3 Q80BD-J71BR11

21.6

121

90

99

141

147

153

19

3.2

4 6.5

6.5

4

(unit: mm)

Appendix 11.4 Q81BD-J71LP21-25

19

12

1

140

147

153

91

10

3.5

5 5

3.2

(unit: mm)

Page 221: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

WARRANTY

Please confirm the following product warranty details before using this product.

1. Gratis Warranty Term and Gratis Warranty RangeIf any faults or defects (hereinafter "Failure") found to be the responsibility of Mitsubishi occurs during use of the product within the gratis warranty term, the product shall be repaired at no cost via the sales representative or Mitsubishi Service Company.However, if repairs are required onsite at domestic or overseas location, expenses to send an engineer will be solely at the customer's discretion. Mitsubishi shall not be held responsible for any re-commissioning, maintenance, or testing on-site that involves replacement of the failed module.[Gratis Warranty Term]The gratis warranty term of the product shall be for one year after the date of purchase or delivery to a designated place.Note that after manufacture and shipment from Mitsubishi, the maximum distribution period shall be six (6) months, and the longest gratis warranty term after manufacturing shall be eighteen (18) months. The gratis warranty term of repair parts shall not exceed the gratis warranty term before repairs.[Gratis Warranty Range](1) The range shall be limited to normal use within the usage state, usage methods and usage environment, etc., which

follow the conditions and precautions, etc., given in the instruction manual, user's manual and caution labels on the product.

(2) Even within the gratis warranty term, repairs shall be charged for in the following cases.1. Failure occurring from inappropriate storage or handling, carelessness or negligence by the user. Failure caused

by the user's hardware or software design.2. Failure caused by unapproved modifications, etc., to the product by the user.3. When the Mitsubishi product is assembled into a user's device, Failure that could have been avoided if functions

or structures, judged as necessary in the legal safety measures the user's device is subject to or as necessary by industry standards, had been provided.

4. Failure that could have been avoided if consumable parts (battery, backlight, fuse, etc.) designated in the instruction manual had been correctly serviced or replaced.

5. Failure caused by external irresistible forces such as fires or abnormal voltages, and Failure caused by force majeure such as earthquakes, lightning, wind and water damage.

6. Failure caused by reasons unpredictable by scientific technology standards at time of shipment from Mitsubishi.7. Any other failure found not to be the responsibility of Mitsubishi or that admitted not to be so by the user.

2. Onerous repair term after discontinuation of production(1) Mitsubishi shall accept onerous product repairs for seven (7) years after production of the product is discontinued.

Discontinuation of production shall be notified with Mitsubishi Technical Bulletins, etc.(2) Product supply (including repair parts) is not available after production is discontinued.

3. Overseas serviceOverseas, repairs shall be accepted by Mitsubishi's local overseas FA Center. Note that the repair conditions at each FA Center may differ.

4. Exclusion of loss in opportunity and secondary loss from warranty liabilityRegardless of the gratis warranty term, Mitsubishi shall not be liable for compensation to:(1) Damages caused by any cause found not to be the responsibility of Mitsubishi.(2) Loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi products.(3) Special damages and secondary damages whether foreseeable or not, compensation for accidents, and

compensation for damages to products other than Mitsubishi products.(4) Replacement by the user, maintenance of on-site equipment, start-up test run and other tasks.

5. Changes in product specificationsThe specifications given in the catalogs, manuals or technical documents are subject to change without prior notice.

Page 222: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

Microsoft, Visual Basic, Visual C++, Visual Studio, Windows, Windows NT, Windows Server, Windows Vista, and

Windows XP are either registered trademarks or trademarks of Microsoft Corporation in the United States and/or other

countries.

Oracle and Java are registered trademarks of Oracle and/or its affiliates.

The company names, system names and product names mentioned in this manual are either registered trademarks or

trademarks of their respective companies.

In some cases, trademark symbols such as 'TM' or '®' are not specified in this manual.

Page 223: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are
Page 224: MELSECNET/H Interface Board User's Manual (For ......quality assurance or fail-safe, redundant or other safety features which exceed the general specifications of the PRODUCTs are

SH(NA)-080128-AD(1906)KWIX

MODEL: SW0-MNETH-B-U-E

MODEL CODE: 13JR24

Specifications subject to change without notice.

When exported from Japan, this manual does not require application to theMinistry of Economy, Trade and Industry for service transaction permission.

HEAD OFFICE : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPANNAGOYA WORKS : 1-14 , YADA-MINAMI 5-CHOME , HIGASHI-KU, NAGOYA , JAPAN