medium voltage products overview bu medium ... - retc.ac.th · june 25, 2015 | slide 22 abb medium...

67
© ABB Group June 25, 2015 | Slide 1 Medium Voltage Products Overview BU Medium Voltage Products © ABB Group June 25, 2015 | Slide 3 Introduction Product Group structure Apparatus Distribution Automation Primary Switchgear Secondary Switchgear Modular Systems Finished Products Service Integrated Products

Upload: buidieu

Post on 01-Dec-2018

213 views

Category:

Documents


0 download

TRANSCRIPT

© ABB GroupJune 25, 2015 | Slide 1

Medium Voltage Products OverviewBU Medium Voltage Products

© ABB GroupJune 25, 2015 | Slide 3

IntroductionProduct Group structure

Apparatus

DistributionAutomation

PrimarySwitchgear

SecondarySwitchgear

ModularSystems

Finished Products

Service

Integrated Products

© ABB GroupJune 25, 2015 | Slide 4

IntroductionValue chain / OEM business model

Original Equipment Manufacturers (Panel Builders)

ABB

BU Medium Voltage ProductsFactories worldwide

CN, Xiamen (2)

CZ, Brno

DE, Ratingen

EE, Maardu

EG, 10th of Ramadan

FI, Vaasa

HU, Budapest

IN, Baroda

IN, Nashik

IT, Dalmine

KR, Chonan

MX, San Luis Potosí

MY, Kuala Lumpur

NO, Skien

NZ, Henderson

PE, Lima

PL, Przasnysz

RU, Moscow

SA, Riyadh

66 production lines in 34 sites in 27 countries

AR, Buenos Aires

AU, Moorebank

BR, Guarulhos

CA, Calgary

CH, Zuzwil

CN, Beijing

CN, Tianjin

TR, Istanbul

US, Coral Springs (FL)

US, Florence (SC)

US, Lake Mary (FL)

US, Pinetops (NC)

VN, Bac Ninh

ZA, Longmedow

DistributionAutomationApparatus

Switchgear

ModularSystems

© ABB GroupJune 25, 2015 | Slide 5

© ABB GroupJune 25, 2015 | Slide 6

ApplicationsWhere medium-voltage products are used

Utilitysubstations

Distribu-tion lines

Industrialplants Ships

Utility generation

Utility transmission

Utility distribution

Transportation

Heavy industrial processplants

Light industrial parks

Hospitals

© ABB GroupJune 25, 2015 | Slide 7

Technical InformationAir-insulated primary switchgear, IEC type

Air-insulated primary switchgear - UniGearTypes and Ratings

Type ZS1, up to 4000 A / 50 kA at 12 kV and2500 A / 31.5 kA at 24 kVType ZVC, compact motor control panelfor ZS1 up to 50 kA and 7,2 kVType ZS2, 36 kV panel for 2500 A and 25 kAType ZS3, 36/40,5 kV up to 3150A and 31,5 kA

Manufactured inIT, CZ, ZA, TR, EG, SA, IN, MY, CN, KR, AU,VE, AR, BR

FeaturesCassette type, fixed or floor rolling breakersSF6 or vacuum interruptionStandard or compact panelsDouble level (2 high CB panels)Double busbar panelsIntegrated sensors and controls as requiredFully arc tested

© ABB GroupJune 25, 2015 | Slide 8

Technical InformationGas-insulated primary switchgear

Gas-insulated primary switchgear ZXTypes and Ratings

Single busbarZX0 , kA)ZX1.2 , kA)ZX1.5 (as ZX1.2 , 95 kV 1 min)

Single or Double busbarZX2 , kA,)ZX2.2 (as ZX2 , ANSI )

Manufactured inGermany, China

FeaturesMedium voltage area shielded fromsurroundingIndependent of environmental conditionsIncreased lifetime & safetyReduced dimensionsBusbar -Plug technologyfor quick and safe installation

© ABB GroupJune 25, 2015 | Slide 9

Technical InformationGas-insulated secondary switchgear

Ratingsup to 36kV

TypesSafering and Safeplus

VersionsWith fuses or vacuum CBOptional built-in sensor technology

Manufactured inNorway, China

FeaturesFlexible connections for quick installationCompletely insulated designCompact

© ABB GroupJune 25, 2015 | Slide 10

ABB Medium Voltage ProductsAir-insulated secondary switchgear

RatingsUp to 1250A / 25kA at 24kV

TypesUniSec, UniSwitch, UniMix

Manufactured inItaly, China, Egypt, Argentina, Indonesia

FeaturesBroad product portfolio, both functionally &accessories-wiseBroad application range, industrial, utility &infrastructure applicationsWithdrawable and removable circuit breakersSwitch disconnectors with fuseFlexible protection and controlsEasy installation & maintenance

© ABB GroupJune 25, 2015 | Slide 11

Technical InformationIndoor apparatus vacuum and SF6 circuit breakers

Ratings1212.5

TypesVD4: Vacuum breaker (spring driven)Vmax: Low end vacuum breaker (spring driven)VM1: Vacuum breaker (magnetic driven)HD4: SF6 breaker (spring driven)

VersionsFixed and withdrawablePrimary and secondary distributionSpring and magnetic actuator mechanismIEC, GB, GOST and ANSI standards

Manufactured inGlobal factories: Germany & ItalyRegional factories: China - India - EgyptCustomization: USA, Poland, Malaysia, South Africa

InnovationsEmbedded pole vacuum technologySF6 autopuffer breaking techniqueCircuit breakers fully interchangeableIntegrated protection device, i.e. eVM1

© ABB GroupJune 25, 2015 | Slide 12

Technical InformationIndoor apparatus vacuum contactors

Ratings

400Aup to 1.000.000 mechanical operations

TypesV-Contact VSC: magnetically driven

VersionsFixed version

SCO (single command operated) [ 1 ]

DCO (double command operated) [ 1 ]

Withdrawable versions for OEM PowerCubemodule and UniGear switchgear

SCO (single command operated) [ 1 ]

DCO (double command operated) [ 1 ]

Manufactured inItaly

InnovationsElectronic feedersMagnetic actuatorSlimline construction

[1] SCO : Electricallatching feature

DCO : Mechanicallatching feature

© ABB GroupJune 25, 2015 | Slide 13

Technical InformationIndoor apparatus SF6 sealed switches

Ratings[ 1 ] ; up to 25kA

TypesSHS2 metal groundable tankSFG - insulated tank

VersionsSwitch-disconnector (single or double spring operatingmechanism [ 2 ] )Switch-disconnector with fuses (double springoperating mechanism [ 2 ] )Isolator (SHS2 only) (no spring operating mechanism)

Manufactured inItaly (SHS2)Finland, China (SFG)

FeaturesThree position (Open/close/earth)SHS2 : Stainless steel enclosureSFG : Epoxy resin enclosureSuitable for panel width 375mmUp to 5000 operation on open/close operationUp to 1000 operation on open/earth operation

[1] SHS2 up to 630A SFG up to 800A

(17kV only)

[2] Both available alsoin motorizedversion

© ABB GroupJune 25, 2015 | Slide 14

Technical InformationIndoor apparatus air insulated switches

Ratings12 36kV [ 1 ]

400 1250A [ 1 ]

up to 30kA [ 1 ]

TypesNAL/NALF - wall mountedAirSwitch - rotary type

VersionsSwitch-disconnector with or without fuses (single ordouble spring operating mechanisms [ 2 ] )Mechanically interlocked earthing switchIsolator (AirSwitch)

Manufactured inPoland

FeaturesGas blast and air pressure integrated arc extinguishingsystemDesigned for easy installation inside panels and kiosksVariety of accessoriesElectrical endurance: class E3 [ 3 ]Up to 2000 operation mechanical lifetime

[1] AirSwitch: up to 24kV, 400/630A andup to 16 kA only

[2] Both available alsoin motorizedversion

[3] For selectedratings only

© ABB GroupJune 25, 2015 | Slide 15

Technical InformationIndoor apparatus fuses

Current limiting fusesRatings

3.6 36kV6 315Aup to 50kA

TypesCEF back up fusesCMF motor protection fusesWBP/BRT VT fusesWBT/BWT railway fuses

VersionsIndoor/outdoorDifferent length

Manufactured inPoland

FeaturesDesigned and tested for cooperation with switchdisconnectors and for SF6 compact switchgearHigh breaking capacityLow power lossesDimensions according to DIN and BSStriker pin medium type

© ABB Group

June 25, 2015 | Slide 16

ABB Medium Voltage ProductsCurrent limiters and Ultra Fast Earthing Switches

[1] Rated interrupting current (RMS)

[2] Short-time withstand current

s-Ratings

rms[1]

VersionsFixed or Truck mounted; Loose component supply

Manufactured inGermany

DescriptionSolves short-circuit problems in new substations and substationextensionsPeak short-circuit current will never be reached

Ratingsrms

[2]

UniGear ZS1; ABB Service retrofit (also as extension for arc

Manufactured inGermany

DescriptionActive internal arc protectionWorks on principle of 3-phase short-circuit earthingExtinction of internal arcs in < 4 ms after detectionDrastic reduction of destructive impacts

© ABB GroupJune 25, 2015 | Slide 17

Technical InformationVacuum interrupters and embedded poles

[1] 4000A with forcedcooling

[2] Embedded polesup to 50 kA

Ratings3.6 40.5kV

4000 A [1]

up to 63 kA [2]

TypesP series EP for indoor applicationsOP series EP for outdoor applicationsVG series VI for circuit breaker applicationsVS series VI for contactor and switch applications

Manufactured inGermany, India

FeaturesComplete product family universal in applicationExcellent switching capabilitiesLong electrical and mechanical lifeSturdy design and compact dimensionsDirect embedding of vacuum interrupters (optimumprotection against dust and dirt)Easy assembly on a switching deviceMaintenance free for life

© ABB GroupJune 25, 2015 | Slide 18

Technical InformationIndoor instrument transformers and sensors

IEC current & voltage transformersRatings

3.6 40.5 kV; 10 8000 ATypes

TPU, TTR, KOKS : current transformerTJC, TJP, TDC :voltage transformer

Manufactured inCzech Republic, Poland

ANSI current & voltage transformersRatings

0.6 34.5 kVVersions

Metering; metering/protection; bushing; controlpower transformer, special application products

Manufactured inUSA

© ABB GroupJune 25, 2015 | Slide 19

ABB Medium Voltage ProductsIndoor sensors

IEC current & voltage sensorsRatings

Current accuracy 0.5 / 5P630Voltage accuracy 0.5 / 3P

TypesCurrent sensors:KEVCD, KECA, KECR, KEVCR, KECLVoltage sensors:KEVA, KEVCY,Combined sensors:KEVCD, KEVCY, KEVCR

VersionsMetering + protection, special applications

Manufactured inCzech Republic

© ABB GroupJune 25, 2015 | Slide 20

ABB Medium Voltage ProductsOutdoor apparatus Circuit Breakers

Live Tank BreakersRatings: up to 40.5 kVTypes: OVB & OHBManufactured in: India and ChinaFeatures:

Vacuum interruption improves reliabilityTelescopic structure for flexible installation

Dead Tank BreakersRatings: up to 38 kVType: R-MAGManufactured in: US and MexicoFeatures:

Magnetic actuation reduces maintenanceVacuum interruption improves reliability & environmentfriendlyElectronic controller reduces setup time and increasesflexibility

Pole Mounted BreakersRatings: up to 12 kVType: PVBManufactured in: ChinaFeatures:

Magnetic actuation reduces maintenanceVacuum interruption improves reliability & environmentfriendlyCompact design for optimized installation

© ABB GroupJune 25, 2015 | Slide 21

Technical InformationOutdoor apparatus reclosers and breakers

Live tank substation breakersRatings: up to 41.5 kVManufactured in: India and ChinaFeatures: Magnetic actuation reduces maintenance

Dead tank substation breakersRatings: up to 38 kVManufactured in: USFeatures: Magnetic actuation reduces maintenance

Reclosers single and three phaseRatings: up to 38 kVManufactured in: US and ChinaFeatures

Magnetic actuation reduces maintenanceSolid dielectric to eliminate maintenance anddielectric concernsSpecial controls available loop schemes,distribution automation schemes, automaticsetting changes to improve reliability

© ABB GroupJune 25, 2015 | Slide 22

ABB Medium Voltage ProductsOutdoor apparatus Switches and Sectionalizers

Overhead single & three phase switchesRatings: up to 38 kVTypes: Sectos, NPS, GridGuard, R, S.Versions

Vacuum, SF6, air interruption for different applicationsSF6 and air insulation

Manufactured in: US, Poland, China, AustraliaFeatures

Complete variants for every market requirementSealed contacts for longer lifeAutomated for many thousands operations lifespanFeeder Automation capabilities

Fused cutouts and single-phase switchesRatings: up to 38 kVTypes: ICX, NCX, LBU, EU, V.Manufactured in: US, China and AustraliaFeatures: Porcelain and silicone insulators

Electronic single & three phase sectionalizersRatings: up to 38 kVType: AutoLinkManufactured in: ArgentinaFeatures

Resettable countsResettable actuation current

© ABB GroupJune 25, 2015 | Slide 23

Technical InformationOutdoor instrument transformers

IEC current & voltage transformersRatings

12 40.5 kV10 2500 A

TypesTPO : current transformerTJO, TDO : voltage transformer

Manufactured inCzech Republic, Poland

ANSI current & voltage transformersRatings

0.6 34.5 kVVersions

Metering; BushingManufactured in

USA

© ABB Group

June 25, 2015 | Slide 24

The Relion family represents the latest generation of ABBprotection and control productsRelion offers the widest range of products for the protection,control, measurement and supervision of power systems for IECand ANSI marketsRelion products have been designed to implement the core valuesof the IEC 61850 standard to ensure interoperable and future-proof solutions

Relion® Protection and ControlComplete Confidence

© ABB Group

June 25, 2015 | Slide 25

Distribution Automation Products

We secure the power distribution byoffering solutions for the followingapplication / protection areas:

Feeder protectionMotor protectionTransformer protectionLine differential protection for feedersArc protectionFeeder automation for recloserprotection and control

Generator protectionVoltage protection and automaticvoltage regulationCapacitor bank protection

Product applications

© ABB GroupJune 25, 2015 | Slide 29

© ABB Group09 April, 2018 | Slide 1

Gas-insulated ring main unit and compact switchgearSafeRing and SafePlus 12/24kV

© ABB Group09 April, 2018 | Slide 3

SafeRing and SafePlus product presentationBasic description

Contents

Basic descriptionApplications

MarineWind powerSolarGreen powerHydro powerGenerationDistributionMeteringInfrastructureIndustry

Picture / artwork size:Height = 12.09 cmWidth = 15.49 cm

Applications

Contents© ABB Group09 April, 2018 | Slide 5

© ABB Group09 April, 2018 | Slide 5

Basic description - SafeRing/SafePlusProduct family overview

SafeRing family

SafeRing up to 24kV

SafeRing up to 40,5kV

SafeRing Air up to 12 kV

SafePlus family

SafePlus up to 24kV

SafePlus up to 40,5kV

SafePlus Air up to 12 kV

Contents

Basic descriptionOperating conditions

© ABB Group09 April, 2018 | Slide 8

Ambient temperature:

Maximal operating temperature: + 40°C

Minimal operating temperature: - 25°C

Nominal operating gas pressure: 1,4 bars absolute at 20°C

Normal operational altitude: 1,500 meters

Expected operating lifetime: 30 years

For special operating conditions, contact ABB sales

Contents

Basic descriptionOperating conditions

Ambient humidity:

Max 24 h average of relative humidity: 95%

Max 24 h average of water vapour pressure: 2.2 kPa

Max monthly average of relative humidity: 90 %

Max monthly average of water vapour pressure: 1.8 kPa

Contents© ABB Group09 April, 2018 | Slide 9

Basic descriptionType tested and certified

Fully type tested and routine tested

Tested for 50 Hz as well as 60 Hz

Minimum lifetime of 30 years

Gas remains inside, leakage rate < 0,1% per year

Recycling 97% of weight

ABB policy for recycling

ABB re-claims gas from discarded switchgears

Contents© ABB Group09 April, 2018 | Slide 11

© ABB Group09 April, 2018 | Slide 12

Basic descriptionDesigned and tested according to IEC-standards

IEC 62271 - 1 Specifications High voltage switchgearIEC 62271-200 Metal enclosed high voltage switchgear 1 56kVIEC 62271-100 Alternating current circuit breakersIEC 62271-102 Alternating current disconnectors and earthing

switchesIEC 62271-103 High voltage switchesIEC 62271-105 Switch fuse cooperationIEC 60529 Degrees of IP protection provided by enclosuresIEC 61243-5 Voltage detection systemIEC 61958 Voltage presence indication systemsIEC 60255 Electronical protection relays

Contents

Basic descriptionDesigned and tested according to IEC-standards

IEC 61869-1 Instrument transformersIEC 61869-2 Current instrument transformersIEC 61869-3 Voltage instrument transformersIEC 60044-8 Current sensorsIEC 60044-7 Voltage sensorsIEC 60282-1 MV fusesCENELEC EN 50180 / EN 50181, Cable connectionIEC 60137, IEC 60502-4IEC 60044-7, IEC 60044-8, CENELEC EN 50181, IEC 62271-206,Iec 61243-5 Combined bushings sensorsCENELEC En 50180 / EN 50181, IEC 61243-5, IEC 62271-206, IEC 60137EDF HN 52-s-61: Bushings

© ABB Group09 April, 2018 | Slide 13

Contents

Basic descriptionType testing IEC 62271-200

Dielectrtic tests (PFWV, BIL and PD)

Measurement og the resistance of circuits

Temperature rise test

Short current and peak withstand current test

Test of making and breaking capacities

Mechanical operation tests

Internal arc test

Tightness test

EMC tests

Test of auxiliary and control circuits

© ABB Group09 April, 2018 | Slide 14

Contents

Basic descriptionRoutine testing IEC 62271-200

Dielectric test on the main circuit (PFWV and PD)

Measurement of the resistance of main circuits

Tightness test

Mechanical operation tests

Design and visual check

Test of auxiliary and control circuits

© ABB Group09 April, 2018 | Slide 15

Contents

© ABB Group09 April, 2018 | Slide 16

SafeRing and SafePlus product presentationRMU in traditional distribution network

PPMV, Skien

Contents

© ABB Group09 April, 2018 | Slide 17

Line description - Secondary distribution

Secondarysubstation

Distributionsubstation

400 kV

40-70 kV

24kV 12kV

400 / 230 V

Contents

Line descriptionDesign philosophy - Example

Contents

Incomer Outgoing Distributiontransformator

Incomer:

Supply connection for RMU

Outgoing:

Connection point for next RMU

Distribution transformer

Connected to distribution transformer

© ABB Group09 April, 2018 | Slide 18

© ABB Group09 April, 2018 | Slide 19

Line descriptionGeneral features

SafeRing SafeRing SafeRing

SafeRing

Contents

© ABB Group09 April, 2018 | Slide 20

Traditional open ring

Compact secondarysubstation (CSS)

Ring main unit(RMU)

Load break-switch

HV fuse

10kV 10kV

NOP

Line descriptionGeneral features

Contents

© ABB Group09 April, 2018 | Slide 21

Traditional open ring

Compact secondarysubstation (CSS)

Ring main unit(RMU)

Load break-switch

HV fuse

10kV 10kV

NOP

Line DescriptionGeneral features

Contents

© ABB Group09 April, 2018 | Slide 22

Traditional open ring

Compact secondarysubstation (CSS)

Ring main unit(RMU)

Load break-switch

HV fuse

10kV 10kV

NOP

Line DescriptionGeneral features

Contents

© ABB Group09 April, 2018 | Slide 23

Traditional open ring

Ring main unit(RMU)

Load break-switch

HV fuse

10kV 10kV

Open Points

To beclosed

To beclosed

Line DescriptionGeneral features

Contents

© ABB Group09 April, 2018 | Slide 45

SafeRing and SafePlus product presentationProduct line overview - SafeRing

Contents

© ABB Group09 April, 2018 | Slide 46

Product line overview SafeRingAvailable modules

C - cable switch

F switch-fuse disconnector

V - vacuum circuit-breaker

De direct connection with earthing switch

Contents

© ABB Group09 April, 2018 | Slide 47

Product line overviewSafeRing 12/24kV standard configurations

Contents Back to SafeRing modules

© ABB Group09 April, 2018 | Slide 48

Product line overviewSafeRing 12/24kV technical data

C-module F-module V-moduleRated voltage kV 12/15/17,5/24 12/17,5/24 12/15/17,5/24Rated current A 630 200 200Short circuit breaking current kA limited by fuse 16Making capacity kA 52,5/52,5/40/40 limited by fuse 40Short circuit current 3 sec. kA 21/21/16/16 16

Contents Back to SafeRing modules

© ABB Group09 April, 2018 | Slide 49

Product line overviewC - Cable switch

Back to SafeRing modules

Switch disconnectorRated voltage kV 12 15 17,5 24Rated normal current A 630Making capacity kA 52,5 52,5 40 40Short time withstand current 3 sec. kA 21 21 16 16Electrical and mechanical classes E3, C2, M1Number of mechanical operations 1000 close / open manualEarthing switchMaking capacity kA 52,5 52,5 40 40Short time withstand current 1 sec. kA 21 21 16 16Electrical and mechanical classes E2, M1

Depth: 765 mm

Width: 325 mm

Height: 1336/1100 mm

Contents

© ABB Group09 April, 2018 | Slide 50

Product line overviewF - switch-fuse disconnector

Back to SafeRing modules

Depth: 765 mm

Width: 325 mm

Height: 1336/1100 mm

Switch-fuse-disconnectorRated voltage kV 12 17,5 24Rated normal current A 200Making capacity kA Voltage fuse-linksElectrical and mechanical classes E3, M1Number of mechanical operations 1000 close / open manualEarthing switch downstreamMaking capacity kA 12,5Short time withstand current 1 sec. kA 5Electrical and mechanical classes E2, M1

Contents

© ABB Group09 April, 2018 | Slide 51

Product line overviewFuse protection

Optimal short circuit protection:

Fast interruption

Current limiting - reduces stress

Cost efficient

Considerations:

Fuses are consumables

Availability of stock

Transformer size

Switchgear - accounting for thermal

Derating

SafeRing

Back to SafeRing modulesContents

© ABB Group09 April, 2018 | Slide 52

Product line overviewV vacuum circuit-breaker

Switch circuit-breakerRated voltage kV 12 15 17,5 24Rated normal current A 200Making capacity kA 40Short time withstand current 3 sec. kA 16Electrical and mechanical classes E2, C2, S1, M1Number of mechanical operations 2000 close / open manualEarthing switch downstreamMaking capacity kA 40Short time withstand current 3 sec. kA 16Electrical and mechanical classes E2, M1

Depth: 765 mm

Width: 325 mm

Height: 1336/1100 mm

Back to SafeRing modulesContents

© ABB Group09 April, 2018 | Slide 53

Product line overviewDe direct cable connection with earthing switch

Direct cable connection

Earthing switch with making capacity

Rated voltage kV 12 17,5 24Rated normal current A 630Making capacity kA 62,5 50 50Short time withstand current 3 sec. kA 21Number of mechanical operations 1000 close / open manualEarthing switchMaking capacity kA 62,5 50 50Short time withstand current 3 sec. kA 21

Depth: 765 mm

Width: 325 mm

Height: 1336/1100 mm

Back to SafeRing modulesContents

© ABB Group09 April, 2018 | Slide 54

SafeRing and SafePlus product presentationProduct line overview - SafePlus

Contents

Product line overviewSafePlus

© ABB Group09 April, 2018 | Slide 55

Installed in more than 100 countries all

over the world

Installed and sold since 2001

Continuosly under developement

Five modules in one common gas-tank

All operations are carried out from the

front of the cwitchgear

No live parts exposed

Fully sealed for life time

Climatic independent

Submersible solution

Contents

© ABB Group09 April, 2018 | Slide 56

Product line OverviewSafePlus

C cable switch

F switch-fuse disconnector

V vacuum circuit-breaker

CB Circuit-breaker (HD)

Sl busbar sectionaliser with LBS

Sv busbar sectionaliser with VCB

D direct cable connection

De direct cable connection with ES

Be busbar earthing

M metering

Mt metering tariff

Jump to Switchgear Design

SafePlus SafePlus SafePlus SafePlusSafePlusSafePlus

REF541 REF541 REF541

Contents

Product line overviewC Cable switch

© ABB Group09 April, 2018 | Slide 57

Standard features:

Three position load break switch

(switch, disconnect, earth)

Snap action or latched mechanism

Cable test bushings in front available

Arc quenching by SF6 gas

Rough and reliable with a minimum of parts

Back to SafeRing modulesContents

© ABB Group09 April, 2018 | Slide 58

Product line overviewC Cable switch

Back to SafePlus modules

Switch disconnectorRated voltage kV 12 17,5 24Rated normal current A 630Making capacity kA 62,5 52,5 52,5Short time withstand current 3 sec. kA 25 21 21Electrical and mechanical classes E3, C2, M1Number of mechanical operations 1000 close / open manualEarthing switchMaking capacity kA 62,5 50 50Short time withstand current 1 sec. kA 25 21 21Electrical and mechanical classes E2, M1

Depth: 765 mm

Width: 325 mm

Height: 1336/1100 mm

Contents

Product line overviewC Cable switch Interlocking

© ABB Group09 April, 2018 | Slide 59

Contents Back to SafePlus modulesPersonnel safety

Product line overviewF switch-fuse disconnector

© ABB Group09 April, 2018 | Slide 60

Standard features:

Switch-fuse combination

Three phase fuse tripping

Mechanism pre-charged for tripping

No jammed fuse covers open by handle

Fuse tripping in front real blown fuse indicator

Fuse canisters isolated in gas

Fuse cover interlock no hazardous access

Back to SafeRing modulesContents

© ABB Group09 April, 2018 | Slide 61

Product line overviewF switch-fuse disconnector

Back to SafePlus modules

Switch-fuse-disconnectorRated voltage kV 12 17,5 24Rated normal current A 200Making capacity kA Voltage fuse-linksElectrical and mechanical classes E3, M1Number of mechanical operations 1000 close / open manualEarthing switch downstreamMaking capacity kA 12,5Short time withstand current 1 sec. kA 5Electrical and mechanical classes E2, M1

Depth: 765 mm

Width: 325 mm

Height: 1336/1100 mm

Contents

Product line overviewF switch-fuse disconnector Interlocking

© ABB Group09 April, 2018 | Slide 62

Contents Back to SafePlus modulesPersonnel safety

Product line overviewV Vacuum circuit-breaker

© ABB Group09 April, 2018 | Slide 63

Standard features:

Interruption in vacuum

630A or 200A vacuum circuit breaker

Insulation provided by gas

No consumable parts

Separate earthing switch

Latched mechanism

Close and open coil

Tripping facilitated for a wide range of self

powered relays

Combisensor available

Back to SafeRing modulesContents

© ABB Group09 April, 2018 | Slide 64

Product line overviewV vacuum circuit-breaker

Back to SafePlus modules

Switch circuit-breakerRated voltage kV 12 17,5 24Rated normal current A 200 / 630(bushing)Making capacity kA 52,5 40 40Short time withstand current 3 sec. kA 21 16 16Electrical and mechanical classes E2, C2, S1, M1Number of mechanical operations 2000 close / open manualEarthing switch downstreamMaking capacity kA 52,5 40 40Short time withstand current 3 sec. kA 21 16 16Electrical and mechanical classes E2, M1

Depth: 765 mm

Width: 325 mm

Height: 1336/1100 mm

Contents

Product line overviewV vacuum circuit-breaker Interlocking

© ABB Group09 April, 2018 | Slide 65

Contents Back to SafePlus modulesPersonnel safety

Product line overviewV20, V25

© ABB Group09 April, 2018 | Slide 66

Vacuum circuit-breakerRated voltage kV 12 24Rated normal current A 630 630Making capacity kA 65 50Short time withstand current 3 sec. kA 25 21Electrical and mechanical classesNumber of mechanical operations 2000 close/open manualEarthing switch downstreamMaking capacity kA 62,5 50Short time withstand current 1 sec. ** kA 25 ** 21Electrical and mechanical classes E2, M1

E2, C2, S1 M1, *

Depth: 765 mm

Width: 325 mm

Height:1460 mm (optional:1224 mm)

*Classes varries for different operation sequence and voltage levels

** 3s available as an option

Interlocking: Rules are same as for V-module, except for lockable push buttons

Contents Back to SafePlus modules

© ABB Group09 April, 2018 | Slide 67

Product line overviewCB, VD4 circuit-breaker

M

M

3

VD4

SafePlus

REF541

Switch disconnectorRated voltage kV 12 24Rated normal current A 630 / 1250(bushing)Making capacity kA 62,5 50Short time withstand current 3 sec. kA 25 20Electrical and mechanical classes E3, C2, M2Number of mechanical operations 30000 close/open manualEarthing switchMaking capacity kA 62,5 50Short time withstand current 3 sec. kA 25 20

Depth: 800 mm

Width: 650 mm

Height: 1336 mm

Back to SafePlus modulesContents

Product line overviewCB, VD4 circuit-breaker - Interlocking

© ABB Group09 April, 2018 | Slide 68

Contents Back to SafePlus modules

Product line overviewCircuit breaker VD4 X.0

© ABB Group09 April, 2018 | Slide 69

Vacuum circuit-breaker VD4 X.0

Rated current 630A or 1250A

Mechanical endurance 30.000 operations

Offers auto-reclosing 0-0,3s co 15s co

Interlocked disconnector/earthing switch

Current and voltage sensor techniques

Variety of protection relays

Motor operated circuit breaker

Back to SafePlus modulesContents

© ABB Group09 April, 2018 | Slide 70

Product line overviewSl busbar sectionaliser

Back to SafePlus modules

Busbar sectionalizer SIRated voltage kV 12 17,5 24Rated normal current A 630Making capacity kA 62,5 52,5 52,5Short time withstand current 3 sec. kA 25 21 21Electrical and mechanical classes E3, C2, M1Number of mechanical operations 1000 close / open manualEarthing switchMaking capacity kA 62,5 50 50Short time withstand current 3 sec. kA 21Electrical and mechanical classes E2, M1

Depth: 765 mm

Width: 325 mm

Height: 1336/1100 mm

Three position load break switch

Manual or motor operation

Only 325mm wide when placed between other modules

Interlocking: See slide for C-module. Except for lockable

push buttons

Contents

© ABB Group09 April, 2018 | Slide 71

Product line overviewSv busbar sectionaliser with vacuum circuit-breaker

Back to SafePlus modules

630A vacuum circuit breaker

Separate isolator/earthing switch

Interlocking: See slide for V-module

Switch disconnectorRated voltage kV 12 17,5 24Rated normal current A 630Making capacity kA 52,5 40 40Short time withstand current 3 sec. kA 21 16 16Electrical and mechanical classes E2, C2, S1, M1Number of mechanical operations 2000 close / open manualEarthing switchMaking capacity kA 52,5 40 40Short time withstand current 3 sec. kA 21 16 16Electrical and mechanical classes E2, M1

Depth: 765 mm

Width: 650 mm

Height: 1336/1100 mm

Contents

© ABB Group09 April, 2018 | Slide 72

Product line overviewDe Direct cable connection with earthing switch

Earthing switchRated voltage kV 12 17,5 24Rated normal current A 630Making capacity kA 62,5 50 50Short time withstand current 3 sec. kA 25 21 21Number of mechanical operations 1000 close / open manualMaking capacity kA 62,5 50 50

Depth: 765 mm

Width: 325 mm

Height: 1336/1100 mm

Back to SafeRing modulesContents

Product line overviewDe Direct cable connection with earthing switch

© ABB Group09 April, 2018 | Slide 73

Contents Back to SafePlus modules

© ABB Group09 April, 2018 | Slide 74

Product line overviewD direct cable connection

Back to SafePlus modules

Switch disconnectorRated voltage kV 12 17,5 24Rated normal current A 630Short time withstand current 3 sec. kA 25 21

Depth: 765 mm

Width: 325 mm

Height: 1336/1100 mm

Contents

© ABB Group09 April, 2018 | Slide 75

Product line overviewBe busbar earthing

Back to SafePlus modules

Busbar earthing

Earthing switch with making capacity

Interlocking: See slide for De - Module

Switch disconnectorRated voltage kV 12 17,5 24Rated normal current A 630Making capacity kA 62,5 50 50Short time withstand current 1 sec. kA 25Short time withstand current 3 sec. kA 21Electrical and mechanical classesNumber of mechanical operations 1000 close / open manualEarthing switchMaking capacity kAShort time withstand current 1 sec. kAElectrical and mechanical classes

Depth: 765 mm

Width: 325 mm

Height: 1336/1100 mm

Contents

© ABB Group09 April, 2018 | Slide 76

Product line overviewM Metering panel

Back to SafePlus modules

A

V

SafePlus

Switch disconnectorRated voltage kV 12 17,5 24Rated normal current A 630Short time withstand current 1 sec. 25Short time withstand current 3 sec. kA 21

Depth: 802 mmWidth: 696 mmHeight: 1806 mm

Contents

IAC classification AFL 16 kA / 1s, 20 kA / 0,5sPadlock or key lock on front door to preventaccess to live parts

Product line overviewM Metering panel

© ABB Group09 April, 2018 | Slide 77

Air-insulated and factory assembled module

Type tested

Fuses on VT primary (optional)

400 series bushings for bus bar connection

Bottom cable entry available

Back to SafePlus modulesContents

Product line overviewMini-Metering

© ABB Group09 April, 2018 | Slide 78

Space saving with one common SF6 gas tanksolution

Factory mounted solution with integrated VTs & CTsfor reduced installation time on site

Compact dimensions

Cost saving with reduced footprint

Standard design with short lead time

Different solutions with or without IAC classification*Base frame orcable trench needed

Contents

© ABB Group09 April, 2018 | Slide 79

SafeRing and SafePlus product presentationComponents and features

Contents

Components and featuresVoltage presence systems

© ABB Group09 April, 2018 | Slide 80

Voltage presence indication system (VPIS)Conforms to IEC 61958Positively indicates presence of the mediumvoltage

Voltage detection system (VDS) High resistance(HR)VIM-1 and VIM-3 can be connected to indicatevoltage or / and compare phases

Contents

VIM 3 VIM 1

Components and featuresVoltage presence systems

© ABB Group09 April, 2018 | Slide 81

Voltage detection system (VDS), low resistance(LRM)Conforms to IEC 61243-5Positively indicates:

Overvoltage presenceMedium voltage presenceIsolation problemsNo voltage presenceBroken signal lead

Contents

Components and featuresManometers

© ABB Group09 April, 2018 | Slide 82

Increases assurance and

safety

Different scale ranges

Temperature compensated

Overpressure indication

Signalling contact for signalling of

pressure drops

Signalling contact without indicative

scale

Contents

© ABB Group09 April, 2018 | Slide 83

Components and featuresBase frames

SafePlus

REF 610

SafeP lus

R E F 61 0

SafeP lus

R E F 61 0

Base frame 450 mm

Additional set of CTs and residual CT

IAC AFLR tested up to 25kA/1s

Suitable for mini-metering

Allows side and back cable connection

Base frame 290 mm

Additional set of CTs

Installation of residual CT

IAC AFL tested up to 20kA/1s

Contents

© ABB Group09 April, 2018 | Slide 84

Components and featuresExternal busbars

Up to 1250 A

Easy installation

Extensible on both sides

Safe and reliable

Sealed & screened

Completed

Additional cover available

Contents

© ABB Group09 April, 2018 | Slide 85

Components and featuresCable termination

Interface ASerie 200 plug inRated current up to 200ARated short current up to 12,5 kA /1sUsed for F-module

Interface CSerie 400 boltedRated current 630A or 1250ARated short current up to 25 kA /3sUsed for other modules

Contents

© ABB Group09 April, 2018 | Slide 86

Components and featuresCable termination

Switchgear is suitable for following connectors:ABB KabeldonSüdkabelEuromoldEstimoldNkt cablesTyco ElektronicsPrysmian3M

Contents

*Not scope of switchgear supplies

© ABB Group09 April, 2018 | Slide 87

Cable compartment allows up to 2 cables per

phase

Simplified installation:

Complete installation performed from front

Cables cut to one length

Revolving

Adjustable cable support

Various cable clamps

Double adapters and surge arresters fitsbehind cable cover

Deeper front covers available

Components and featuresCable termination

Contents

Components and featuresMotor operation

© ABB Group09 April, 2018 | Slide 88

Remote control of the load-break

switches

Remote control of the circuit breaker and

the switch-fuse combination

Additional signaling contacts

All the features are possible to retrofit

Contents

Components and featuresFault passage indicators

© ABB Group09 April, 2018 | Slide 96

For high flexibility and grid automation applications

Reliable and effective fault detection and location

Standard packages with different levels of

automation available

Effective net management

Communication with GPRS gateway

Contents

Components and featuresLow voltage compartment

© ABB Group09 April, 2018 | Slide 97

SafePlus

REF541

SafeRing

Low voltage equipment can either be located

behind front covers, or in a top entry box

May be equipped with protection relays, position

switches, contactors, batteries and terminal

blocks

Cable entry from either left or right hand side

Available heights 124, 470 and 700 mm

Contents

© ABB Group09 April, 2018 | Slide 98

Components and featuresFeeder protection auxiliary powered relays

Broad range of protection, controlling,

monitoring and communication functions

Advanced protection functions

Possible use of sensors (REF 601, 615)

Auxiliary power required

Delivery range:

REF601, REF611, REF 615, REF 630

Others on request

Contents

© ABB Group09 April, 2018 | Slide 99

Components and featuresFeeder protection REF 615

Overcurrent protection functions

Voltage based protection functions

Internal arc protection function

Thermal protection functions

Power monitoring and measurement

Communication protocols IEC 61850-8-1,

IEC 60870-5-103, modbus and other

Supports « GOOSE » messaging (Genergic

Object Oriented Substation Event).

Large programable display

Withdrawable with make before break terminals

Contents

© ABB Group09 April, 2018 | Slide 100

Components and featuresFeeder protection self-powered relays

CT powered protection relay

Independent on auxiliary voltage

Basic protection functions:Overcurrent protection

Short circuit protection

Earth fault protection

Available relays:

REJ 603 r.1.5, WIC1, WIB 1, WIP 1, IKI 30

Contents

© ABB Group09 April, 2018 | Slide 101

Components and featuresFeeder protection REJ 603 r.1.5

Ideal solution for switchgears withoutauxiliary voltage or back-up batteries

Short wake-up time

Trip indication on the relay

Compact relay embedded in RMU

No need of LV top entry box or additionalLV box

Simple settings through dip switches infront of protection relay

IP54 protection degree

Touch-screen display with light

Contents

© ABB Group09 April, 2018 | Slide 128

Contents

© ABB GroupApril 25, 2014 | Slide 39

© ABB GroupApril 25, 2014 | Slide 42

© ABB22/07/2009 | Slide 44

© ABB22/07/2009 | Slide 47

© ABB GroupApril 25, 2014 | Slide 51

© ABB22/07/2009 | Slide 53

© ABB22/07/2009 | Slide 55

© ABB22/07/2009 | Slide 58

Month DD, Year | Slide 62© ABB Group

Month DD, Year | Slide 64© ABB Group

Month DD, Year | Slide 66© ABB Group

© ABB22/07/2009 | Slide 68

Month DD, Year | Slide 70© ABB Group

Month DD, Year | Slide 73© ABB Group

Month DD, Year | Slide 75© ABB Group

Month DD, Year | Slide 77© ABB Group

Month DD, Year | Slide 79© ABB Group