medford police station feasibility study appendix: existing conditions

799
POLICE & FIRE STATION STUDY CITY OF MEDFORD 22 January 2013 Page C APPENDIX C ENGINEERS REPORTS & DOCUMENTATION OF EXISTING CONDITIONS STRUCTURAL HVAC PLUMBING FIRE PROTECTION ELECTRICAL, FIRE ALARM, DATA, SECURITY GEOTECHNICAL & ENVIRONMENTAL HEALTH DEPARTMENT REVIEW STATE DPH REVIEW HAZ MAT REPORTS

Upload: alexruppenthal

Post on 24-Nov-2015

39 views

Category:

Documents


6 download

DESCRIPTION

Donham & Sweeney police station feasibility study for Medford Police station. One of six appendices.

TRANSCRIPT

  • POLICE & FIRE STATION STUDY CITY OF MEDFORD

    22 January 2013 Page C

    APPENDIX C ENGINEERS REPORTS & DOCUMENTATION OF EXISTING CONDITIONS

    STRUCTURAL

    HVAC PLUMBING

    FIRE PROTECTION ELECTRICAL, FIRE ALARM, DATA, SECURITY

    GEOTECHNICAL & ENVIRONMENTAL

    HEALTH DEPARTMENT REVIEW STATE DPH REVIEW HAZ MAT REPORTS

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police & Fire Station Building Medford, MA Existing Conditions Systems Report J#640 022 00.00 L#39032/Page 1/November 12, 2012

    TEL 508-998-5700 FAX 508-998-0883 email: [email protected]

    HVAC

    Executive Summary:

    The primary heating and air conditioning equipment within the Medford Police & Fire Station Building have deteriorated beyond normal maintenance and upkeep. It appears that the heating system presently installed is original to the building with the exception of several roof top units. Overall the system is lacking ventilation air and thermal comfort creating hot and cold spots throughout the building. We recommend a complete upgrade of the entire heating system and control system to achieve higher system efficiencies, reduce energy consumption, provide code required ventilation and provide quality temperature control.

    Heating Plant:

    There are two cast iron sectional Weil McLain boilers which are original to the building; they generate hot water as the main heat source for the entire building. The boiler capacity is unknown at this time. Due to the corrosion occurring on the jacket of the boilers, it would appear that the cast iron sections are leaking towards the base of the sections which would indicate thermal shock has occurred. It is obvious that they have reached the end of their serviceable life. The boilers operate on number two fuel oil which is stored in an outdoor underground storage tank. The storage tank oil level is monitored through the use of level gauge found within the boiler room which is in- operable. The burners utilized are of the Power Flame manufacturer and are designed for fuel oil only and have a capacity of 29.0 gallons per hour. The boiler generates hot water which is distributed throughout the building by two base mounted end suction pumps and travels through what appears to be Schedule 40 black steel pipe. Some of the piping system is insulated with what appears to be fiberglass insulation and asbestos elbows, this should be verified. All of the piping insulation in the building appears to be deteriorating and in some cases falling off. The overall condition of the hot water piping system appears to be in need of replacement however, several test cuts should be completed to visually inspect the inner pipe to determine its condition. Combustion gases generated from the boilers exhaust into a black steel breeching system which is wrapped with what appears to be a canvas jacket. The combined breeching system exits the building through an existing masonry chimney. The breeching system is provided with a barometric damper for stack pressure neutralization. Combustion air for the boilers is provided through one wall mounted louver. The louver is not equipped with a damper and appears to be undersized and not code compliant.

    Heating Hot Water Boilers End Suction Pumps

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police and Fire Station Building Medford, MA Existing Conditions Systems Report J#640 022 00.00 L#39032 /Page 2/November 12, 2012

    Hot Water Expansion Tanks Boiler Breeching

    Fuel Oil Piping Existing Masonry Chimney

    Temperature Controls:

    Automatic temperature controls for majority of the building is provided by Cleveland pneumatic control system. Compressed air is provided through a single air storage tank with dual tank mounted compressors and motors. This system provides individual heating controls and is capable of maintaining day/night set points. There was no refrigerant air dryer system associated with the air compressor system. The control system appears to be malfunctioning and the controllability of the system is less then desirable. Each roof top unit is associated with one centrally located electronic thermostat which is programmable, however, due to the location of the thermostats hot and cold spots are experienced throughout. We would recommend removing the pneumatic system and stand alone electronic system and replacing it with a direct digital control system throughout.

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police and Fire Station Building Medford, MA Existing Conditions Systems Report J#640 022 00.00 L#39032 /Page 3/November 12, 2012

    Pneumatic Air Compressor Pneumatic Control Center

    Typical Pneumatic Thermostat Typical Pneumatic Thermostat

    Typical Electronic Thermostat

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police and Fire Station Building Medford, MA Existing Conditions Systems Report J#640 022 00.00 L#39032 /Page 4/November 12, 2012

    Basement:

    The basement level is equipped with an indoor hot water air handling unit which provides heating and ventilation air to the locker room area. Tempered air is distributed throughout the space utilizing a galvanized sheet metal ductwork system. Air is returned back to the unit through a low wall mounted grille, it is unknown if outside air is actually being delivered to the space as the units components are antiquated and have reached the end of its serviceable life. General exhaust is located in the shower area which is adjacent to the locker rooms. Exhaust air enters the ceiling mounted grilles and travels through a galvanized sheet metal ductwork system to a centrifugal exhaust fan mounted high within the mechanical room, from there the air exits the building at a wall mounted louver also located within the mechanical room.

    Indoor Air Handler (Locker Room) Typical Ceiling Mounted Diffuser

    Typical Ceiling Mounted Exhaust Grille

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police and Fire Station Building Medford, MA Existing Conditions Systems Report J#640 022 00.00 L#39032 /Page 5/November 12, 2012 The gun range which is also located within the basement is tempered through the use of an indoor hot water air handling unit which is located in an adjacent storage room. This unit does not provide any outside air to the space and is 100% recirculated air. Air distribution to the space is through a galvanized sheet metal ductwork system which terminates at side wall mounted diffusers. The space is also equipped with an exhaust system which is located behind the shooter, the galvanized ductwork system travels within an underground trench to the adjacent building/garage where it rises up to a roof mounted exhaust fan. Due to this exhaust system creating a negative pressure within the space a somewhat recent roof top make up air unit was installed. This unit is gas fired and is associated with a galvanized ductwork system which travels on the outside of the building where it is exposed to the weather. The duct system travels into the Locker room and across the hall and into the range. The exposed ductwork is deteriorating and in need of replacement. Due to the location and lack of makeup air and exhaust the range is not utilized and has since been abandoned along with all associated equipment.

    Indoor Air Handler (Gun Range) Gun Range Make Up Air Unit

    Gun Range Supply Diffusers Gun Range Exhaust System

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police and Fire Station Building Medford, MA Existing Conditions Systems Report J#640 022 00.00 L#39032 /Page 6/November 12, 2012

    First Floor:

    The garage area/sally port is equipped with vertical propeller style electric unit heaters with stand alone wall mounted thermostats for heating. No ventilation or exhaust systems are provided for these spaces which is not code compliant.

    Garage Electric Unit Heater

    The cell block area is tempered through the use of an indoor hot water air handling unit which provides heating and ventilation air. Tempered air is distributed throughout the corridor area outside the cells utilizing a galvanized sheet metal ductwork system and ceiling mounted diffusers. Air is returned back to the unit through two ceiling mounted grilles located in the back corridor. It is unknown if outside air is actually being delivered to the space as the units components are antiquated and have reached the end of its serviceable life. General exhaust is located within the cells through the use of a wall mounted perforated grille. Exhaust air travels through a galvanized sheet metal ductwork system and rises up through the floor above and up to a roof mounted exhaust fan. There is a thermostat located in the back corridor which does not appear to functioning.

    Cell Block Area Supply Diffusers Cell Block Exhaust Register

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police and Fire Station Building Medford, MA Existing Conditions Systems Report J#640 022 00.00 L#39032 /Page 7/November 12, 2012

    Ceiling Mounted Return Grille The office areas are equipped with wall mounted fin tube radiation which is the main heat source for the spaces. The fin tube appears antiquated and majority of the fins are bent therefore minimizing performance. The fin tube cover in many locations is bent or broken which also minimizes performance, overall the fin tube is in need of replacement. Temperature control is provided through wall mounted pneumatic thermostats which do not appear to be functioning properly. Tempered ventilation air appears to be provided through the use of roof top units. The units appear to utilize electric for heating purposes and direct expansion refrigerant system for cooling however, it is unknown if these units are functioning since window mounted air conditioning units are currently utilized and air flow was not present at the diffusers. These units are antiquated and not functioning properly or at all therefore they should be replaced, ventilation air does not appear to be provided which is considered a code violation.

    Typical Wall Mounted Fin Tube Radiation Typical Ceiling Mounted Diffuser

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police and Fire Station Building Medford, MA Existing Conditions Systems Report J#640 022 00.00 L#39032 /Page 8/November 12, 2012

    Typical Rooftop Unit The City Wiring & Fire Alarm garages under the communications room which are now utilized by the City Wiring & Fire Alarm Division are tempered through the use of vertical propeller style hot water unit heaters. Piping within this area is not provided with any insulation. At the back of the garages are storage/office spaces which are heated with wall mounted hot water fin tube radiation. There is a toilet room within this area which is equipped with an exhaust system; however, its operation is unknown. General exhaust or ventilation air is not provided within this area which is not code compliant. Temperature control for the unit heaters is through the use of standalone wall mounted thermostats and pneumatic wall mounted thermostats are utilized for the fin tube radiation.

    Typical Hot Water Vertical Style Unit Heater Typical Standalone Unit Heater Control

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police and Fire Station Building Medford, MA Existing Conditions Systems Report J#640 022 00.00 L#39032 /Page 9/November 12, 2012

    Typical Fin Tube in Communication Garage Typical Toilet Room Exhaust in Garage The apparatus bays are heated through the use of ceiling hung propeller style hot water unit heaters which are controlled through wall mounted standalone thermostats. Also, located within the garage area is a Plymovent system which is utilized for vehicle exhaust capture. The garage bays are not provided with any makeup air system which would keep the area in a neutral pressure, this is not code compliant. The kitchen area, weight room, storage rooms, and office spaces are provided with wall mounted hot water fin tube radiation and controlled through the use of wall mounted pneumatic thermostats. There is no CO/NO2 monitoring device installed which is not code compliant. There is, however, carbon monoxide detectors located throughout. There is a toilet room within the apparatus bay which is equipped with a wall mounted hot water fin tube radiation for heating purposes and a general exhaust system, however, its operation is unknown.

    Typical Plymovent Hose Reel Plymovent Filtration/Exhaust Fan

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police and Fire Station Building Medford, MA Existing Conditions Systems Report J#640 022 00.00 L#39032 /Page 10/November 12, 2012

    Typical Ceiling Hung Hot Water Unit Heater Typical Vertical Hot Water Unit Heater

    Typical Toilet Room Exhaust Typical Toilet Room Fin Tube

    Typical Office/Weight Room Fin Tube Typical Carbon Monoxide Sensor

    Second Floor:

    The Police Department section on this floor is mainly office areas which are equipped with wall mounted fin tube radiation. The fin tube appears antiquated and majority of the fins are bent therefore minimizing performance. The fin tube cover in many locations is bent or broken which also minimizes performance, overall the fin tube is in need of replacement. Temperature control for the fin tube is provided through wall mounted pneumatic thermostats which do not appear to be functioning properly.

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police and Fire Station Building Medford, MA Existing Conditions Systems Report J#640 022 00.00 L#39032 /Page 11/November 12, 2012 Tempered ventilation air appears to be provided through the use of roof top units. The units appear to utilize electric for heating purposes and direct expansion refrigerant system for cooling. Temperature control is completed through wall mounted electronic standalone thermostats. It is unknown as to which units serve this upper floor however, according to the floor layout and the roof layout it would appear that the units serving this area are original to the building. The units themselves were not functioning at the time of the visit and in speaking with the personnel it appears there are issues with operation and controllability of the units. Associated ductwork is exposed on the roof and has visible corrosion and deterioration occurring which is causing possible entry points for water, overall the units have reached the end of their serviceable life and should be replaced. There is general exhaust within the toilet rooms which are associated with roof mounted exhaust fans.

    Typical Office Fin Tube Radiation Typical Office Supply Diffuser

    Typical Rooftop Unit Typical Electronic Thermostat The emergency communication center which is shared by both departments utilizes wall mounted fin tube radiation. The fin tube appears to be in good condition. Temperature control is provided through wall mounted electric thermostats which do appear to be antiquated however functioning properly. Tempered ventilation air appears to be provided through the use of a roof top unit. The unit appears to utilize electric for heating purposes and direct expansion refrigerant system for cooling. It appears that a newer roof top unit handles this area since air conditioning is present as well as forced hot air. This unit is of the York manufacturer which appears to have been recently installed and is in good condition. This unit appears to have replaced an older York unit which is abandoned in place on the roof. Both units utilize exterior roof mounted ductwork, some of which appears to be deteriorating and in need of replacement.

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police and Fire Station Building Medford, MA Existing Conditions Systems Report J#640 022 00.00 L#39032 /Page 12/November 12, 2012 The server room and tech data room is located within this section of the building and both are air conditioned through the use of wall mounted ductless split units which have associated roof mounted air cooled condensers. These units are controlled through wireless digital thermostats; these units appear to be in fair condition.

    Typical Supply Diffuser Newer Rooftop Unit for Control Center

    Abandoned Rooftop Unit Exterior Ductwork with Unit Duct Connection

    Server Room/Data Room Condensers Typical Indoor Split Cooling Units

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police and Fire Station Building Medford, MA Existing Conditions Systems Report J#640 022 00.00 L#39032 /Page 13/November 12, 2012

    Wireless Remotes for Cooling Units Typical Fin Tube in Control Room The fire department section of this floor consists of dorm rooms, locker rooms, and office spaces. Wall mounted fin tube radiation is located at the exterior wall of all these spaces. The fin tube appears to be antiquated and in need of replacement. Temperature control for the fin tube is provided through wall mounted pneumatic thermostats which do not appear to be functioning properly as certain spaces are cold and others are extremely warm therefore, they should be replaced. Tempered ventilation air for the locker room area appears to be provided through the use of an indoor hot water air handling unit. Air distribution is accomplished through the use of galvanized sheet metal ductwork which terminates at the ceiling level with diffusers. Air is returned to the unit through a low wall mounted grille. It is unknown if outside air is present in the system considering the unit is original to the building and its components may not be functioning properly. The office areas appear to be tempered through the use of a roof top unit which appears to utilize electric for heating purposes and direct expansion refrigerant system for cooling. The unit appears to be reaching the end of its serviceable life and should be replaced. This unit appears to be controlled through a centrally located electronic thermostat. The toilet rooms within this area appear to have a central exhaust system associated with a roof mounted exhaust fan.

    Fire Department Second Floor Rooftop Unit Typical Second Floor Diffuser

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police and Fire Station Building Medford, MA Existing Conditions Systems Report J#640 022 00.00 L#39032 /Page 14/November 12, 2012

    Typical Fin Tube Radiation Typical Dorm Room Fin Tube

    Typical Toilet Room Exhaust Grilles

    Hallways and Toilet Rooms:

    The hallways and toilet rooms throughout the building are equipped with wall mounted fin tube radiation for heating and wall mounted pneumatic thermostats for control. Corridors do not appear to have any ventilation which is not code compliant. The toilet rooms have ceiling or wall mounted grilles associated with galvanized sheet metal ductwork connected roof mounted exhaust fans. Overall the fin tube radiation is antiquated in need of replacement as well as the roof mounted exhaust fans.

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police and Fire Station Building Medford, MA Existing Conditions Systems Report J#640 022 00.00 L#39032 /Page 15/November 12, 2012

    Typical Corridor Fin Tube Typical Corridor Thermostat

    Typical Vestibule Unit Heater Typical Toilet Exhaust Grille

    Typical Toilet Room Fin Tube

    Replace existing heating plant with a new high efficiency gas fired condensing boiler plant with premium efficiency hot water pumps with variable frequency drives.

    Recommendations:

    Provide ventilation requirements throughout the building through the use of new gas fired roof top units or indoor hot water air handling units.

    Remove abandoned roof top units and replace with new gas fired units with R410A direct expansion refrigerant system.

    Replace heating hot water piping throughout with Schedule 40 black welded steel.

    Provide fiberglass insulation with vapor barrier on all piping systems.

    Replace all existing fin tube radiation with new slope top style fin tube.

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police and Fire Station Building Medford, MA Existing Conditions Systems Report J#640 022 00.00 L#39032 /Page 16/November 12, 2012 Provide tempered make up air system for the apparatus bay.

    Provide new tempered air handling unit and exhaust system for the range.

    Provide new exhaust system throughout the building for general exhaust.

    Provide individual space temperature control through the use of variable air volume boxes/diffusers.

    Provide a new direct digital control system with web access, full building control of every component and piece of equipment, alarm notifications, trending capabilities for trouble shooting and optimal start/stop of cooling and heating modes for increased energy savings.

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police & Fire Academy Building Medford, MA Existing Conditions Systems Report J#640 022 00.00 L#39159 /Page 1/November 12, 2012

    TEL 508-998-5700 FAX 508-998-0883 email: [email protected]

    HVAC

    Executive Summary:

    The primary heating and air conditioning equipment within the Medford Police and Fire Training/Garage Building has deteriorated beyond normal maintenance and upkeep. It appears that the heating system presently installed is original to the building with the exception of the lower level rooftop unit. Overall the system is lacking ventilation and exhaust air and thermal comfort, creating hot and cold spots throughout the building. We recommend a complete upgrade of the entire heating system and control system to achieve higher system efficiencies, reduce energy consumption, provide code required ventilation and provide quality temperature control.

    Temperature Controls:

    Automatic temperature controls for the building is complete with standalone electronic thermostats. These standalone thermostats are tied directly into each unit and are original to the building. These thermostats were provided by the equipment manufacturer. The garage bay unit heaters have typical dial type thermostats while the rooftop unit associated with the garage bay office area is not a programmable type and does not offer any additional options other than temperature control and unit activation. The rooftop units associated with the building office area are programmable style and allow day/night setback control as well as unit activation. Each rooftop unit is associated with one centrally located electronic thermostat however, due to the location of the thermostats, hot and cold spots are experienced throughout. The control system appears to be malfunctioning and the controllability of the system is less then desirable due to the functionality of the rooftop units. We would recommend removing the stand alone electronic system and replacing it with a direct digital control system throughout.

    Garage Bay Office Area RTU Thermostat Garage Bay Unit Heater Thermostat

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police & Fire Academy Building Medford, MA Existing Conditions Systems Report J#640 022 00.00 L#39159 /Page 2/November 12, 2012

    Office Building Lower Level RTU Thermostat Office Building Upper Level RTU Thermostat

    Office Building Lower Level :

    The office building lower level is tempered with the use of an outdoor roof-mounted air handling unit which is equipped with a gas-fired furnace for heating and direct expansion refrigerant system for cooling. Heating and air conditioning is distributed throughout the lower level spaces utilizing a galvanized sheet metal ductwork system. Air is returned back to the unit through ceiling-mounted return grilles. It does not appear that outside air is actually being delivered to the spaces as the unit did not have any intake or exhaust dampers installed. Due to the black soot on the diffusers and the ceiling tiles, it would confirm that the internal components of the unit are relatively dirty as well as the ductwork. The rooftop associated with this level is not original to the building however, it does not appear to have been installed within the last ten years. Since this unit does not have an outside air intake, no outside air is being delivered therefore this system is not code compliant and should be replaced with a code compliant system. An exhaust air system is present in the bathrooms. Air enters the ceiling-mounted grilles and travels through a galvanized sheet metal ductwork system to a roof-mounted exhaust fan. The exhaust fan appears to be in fair condition however, the bearings or motor shaft appeared misaligned due to the noise being generated by the fan. We would recommend replacing the exhaust fan based on these findings.

    Typical Lower Level Supply Diffuser Typical Stairwell Unit Heater

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police & Fire Academy Building Medford, MA Existing Conditions Systems Report J#640 022 00.00 L#39159 /Page 3/November 12, 2012

    Typical Bathroom Exhaust Register Girls Bathroom Electric Fin Tube

    (left) Office Building Upper Level RTU

    (right) Office Building Lower Level RTU

    Office Building Upper Level :

    The office building upper level is tempered with the use of an outdoor roof-mounted air handling unit which is equipped with a gas-fired furnace for heating and direct expansion refrigerant system for cooling. Heating and air conditioning is distributed throughout the upper level spaces utilizing a galvanized sheet metal ductwork system. Air is returned back to the unit through ceiling-mounted return grilles. It does not appear that outside air is actually being delivered to the spaces as the unit did not have any intake or exhaust dampers installed. Due to the black soot on the diffusers and the ceiling tiles, it would confirm that the internal components of the unit are relatively dirty as well as the ductwork. The rooftop associated with this level is original to the building and is not currently operating at this time. Since this unit does not have an outside air intake and is not operating, no heating or ventilation air is being delivered therefore this system is not code compliant and should be replaced with a code compliant system. The office spaces within this level are utilizing electric plug-in type unit heaters since the rooftop unit is not functional.

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police & Fire Academy Building Medford, MA Existing Conditions Systems Report J#640 022 00.00 L#39159 /Page 4/November 12, 2012 Located on the upper level is the Forensic Lab area. This space has a wall which is adjacent to the garage bays. Due to the lack of exhaust and ventilation air within the garage bays and structural imperfections with the adjoining wall, vehicle exhaust is leaking into this space and could potentially cause a health risk for the occupants.

    Typical Office Building Upper Level Typical Office Building Upper Level Supply Diffuser Electrical Space Heaters

    Typical Office Building Upper Typical Office Building Upper Level Return Register Level Forensic Lab Diffuser

    Typical Office Building Roof-Mounted Exhaust Fan

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police & Fire Academy Building Medford, MA Existing Conditions Systems Report J#640 022 00.00 L#39159 /Page 5/November 12, 2012

    Garage Bay:

    The garage area/sally port is equipped with vertical propeller style gas-fired unit heaters with stand alone wall-mounted thermostats for heating. The space is equipped with wall-mounted propeller style exhaust fans, however, their functionality was unknown at the time of the visit. No ventilation/make up air systems are provided for this space which is not code compliant. Also located within the garage area are two vehicle exhaust capture systems. One of the systems seems to have been installed recently while the other appears original to the building. We were told that both systems function however, due to the amount of combustion products released from the large engines associated with the fire trucks, the existing systems appear undersized. Further calculations would be required to determine compliance with todays code requirements.

    Typical Garage Bay Gas-Fired Unit Heater Typical Garage Bay Unit Heater Flue

    Garage Bay Vehicle Exhaust Fan Garage Bay Vehicle Exhaust Hose (Recent Installation) (Recent Installation)

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police & Fire Academy Building Medford, MA Existing Conditions Systems Report J#640 022 00.00 L#39159 /Page 6/November 12, 2012

    Typical Garage Bay General Exhaust Fan Garage Bay Vehicle Exhaust Flue (Recent Installation)

    Garage Bay Vehicle Exhaust Flue

    (Old Installation)

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police & Fire Academy Building Medford, MA Existing Conditions Systems Report J#640 022 00.00 L#39159 /Page 7/November 12, 2012 The office and tool crib area adjacent to the garage bay is tempered with the use of an outdoor roof- mounted air handling unit which is equipped with a gas-fired furnace for heating and direct expansion refrigerant system for cooling. Heating, ventilation and air conditioning is distributed throughout this area utilizing a galvanized sheet metal ductwork system which is not insulated. Air is returned back to the unit through ceiling-mounted return grilles. This unit appears to have an outside air intake however, it is unknown if the code required outside air amount being delivered is compliant. Due to the black soot on the diffusers and the ceiling tiles it would confirm that the internal components of the unit are relatively dirty as well as the ductwork. This rooftop appears to have been installed recently and is in fair condition. Associated ductwork and unit should be cleaned and components verified for proper operation. The control system for this unit appears antiquated and does not have any programmable features for added energy savings and its functionality is less than desirable.

    Garage Bay Office Area/Tool Crib RTU Garage Bay Office Area/Tool Crib Ductwork (Return & Supply)

    Typical Garbage Bay Office Area

    Supply Diffuser

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police & Fire Academy Building Medford, MA Existing Conditions Systems Report J#640 022 00.00 L#39159 /Page 8/November 12, 2012

    Provide heating, ventilation and air conditioning requirements throughout the building through the use of new gas-fired rooftop units.

    Recommendations:

    Provide new galvanized sheet metal ductwork with fiber glass insulation.

    Provide tempered make up air system for the apparatus bay.

    Provide one new vehicle exhaust capture system and verify if recently installed system is adequate.

    Provide new exhaust system throughout the building for general exhaust with new roof-mounted exhaust fans.

    Provide individual space temperature control for office areas through the use of variable air volume diffusers.

    Provide a new direct digital control system with web access providing full building control of every component and piece of equipment, alarm notifications, trending capabilities for trouble shooting and optimal start/stop of cooling and heating modes for increased energy savings.

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police & Fire Station Building Medford, MA Plumbing Existing Conditions Systems Report J#640 022 00.00 L#39039/Page 1/November 12, 2012

    TEL 508-998-5700 FAX 508-998-0883 email: [email protected]

    PLUMBING Executive Summary: The Medford Police and Fire Station was originally constructed in 1962. Several minor renovation projects have occurred over the years. The building is predominantly a two story building. A portion of the building has a basement section. Presently, the plumbing systems serving the building are cold water, hot water, sanitary waste and vent system, garage waste piping, compressed air, storm drain piping, and natural gas. The building is serviced by municipal water and sewer systems. Rain water from the roof areas is discharged with a series of roof drains connected to rain leaders and storm drains discharging to a collection system. Existing Fixtures: Plumbing fixtures are mostly the original fixtures. A few fixtures have been modified to be accessible. The water closets are wall mounted vitreous china, flush valve type with siphon jet action. The cell area fixtures are stainless steel combination units several of the fixtures are not in operation. Water closets are not water conserving type fixtures.

    Typical Wall Hung Water Outlet Cell Combination Toilet/Lav Urinals are wall hung flush valve type vitreous china with siphon jet action and do not have privacy partitions in the police station. Urinals located in the fire department portion of the building have privacy partitions installed. The urinals are original fixtures flush valves some have been replaced with 1.0 GPF flush valves. The urinals are in reasonable condition. Urinals are not water conserving type.

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police & Fire Station Building Medford, MA Plumbing Existing Conditions Systems Report J#640 022 00.00 L#39039/Page 2/November 12, 2012

    Typical Wall Hung Urinal Gang Wall Hung Urinals Lavatories are wall hung vitreous china. Sink faucets are 4 in. center set, non-metering type faucets two handle, non-water conserving faucets.

    Wall Hung Lav Typical Gang Lavatories Typical Drinking fountains are wall hung vitreous china. Drinking fountain units are handicapped accessible type fixtures.

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police & Fire Station Building Medford, MA Plumbing Existing Conditions Systems Report J#640 022 00.00 L#39039/Page 3/November 12, 2012

    Drinking Fountain w/ Typical Drinking Fountain Adjacent Bottled Water

    Showers units are original units in glazed block walls separate enclosures. In several areas showers are not being used. Some shower valve units are original others have been replaced. Shower heads do not appear to be water conserving type.

    Gang Showers Share Floor Drain Typical Shower

    Janitor's sinks are located throughout the facilities. Janitors sinks are enameled cast iron floor mounted. Some faucets are not equipped with vacuum breakers. Proper backflow devices are not installed at cleaning dispensing units

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police & Fire Station Building Medford, MA Plumbing Existing Conditions Systems Report J#640 022 00.00 L#39039/Page 4/November 12, 2012

    Typical Service Sink No Backflow Preventer

    Staff sinks are counter mounted stainless sinks with hot and cold water faucets. Most of the sinks are not accessible. The sink unit located in the 911 Area that was a modification to the existing building is an accessible installation.

    Kitchen Sink Typical Counter Sink

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police & Fire Station Building Medford, MA Plumbing Existing Conditions Systems Report J#640 022 00.00 L#39039/Page 5/November 12, 2012 Water Systems: Building is served by a 4 in. water service entering the mechanical room from Union Street at the back of the building. There is a 2 in. water meter installed on the service. Almost all hose connections are not protected with vacuum breakers.

    Water Service and Meter Washdown Hose Piping, where exposed, is mainly copper with sweat joints. The piping insulation appears to be fiberglass and to have asbestos insulation on some joints and fittings. Concealed piping with original insulation may be asbestos along with joints and fittings. Most of the valves are original and are in need of replacement. The majority of the piping is insulated.

    Existing Insulation Domestic Water Piping

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police & Fire Station Building Medford, MA Plumbing Existing Conditions Systems Report J#640 022 00.00 L#39039/Page 6/November 12, 2012 Domestic water heating is a gas-fired water heater a 75 gallon storage tank. The tank has a natural gas input of 75,000 btuh. The domestic hot water system has a circulator pump installed in the building system. The original tank and associated piping system has been taken out of service and abandoned in place. Asbestos insulation remains on the tank and piping. There is no thermostatic mixing valve to control hot water temperature for scald protection.

    Domestic Water Heater Original Water Heater (Abandoned)

    Drainage Systems:

    Cast iron with hub and spigot joints is used for sanitary and storm drainage. The smaller sanitary waste and vent piping is a mixture of copper and galvanized steel piping. Where visible, the cast iron pipe appears to be in reasonable condition. Horizontal rain leaders are insulated however, insulation is missing in several areas.

    Rain Leader Piping at Ceiling

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police & Fire Station Building Medford, MA Plumbing Existing Conditions Systems Report J#640 022 00.00 L#39039/Page 7/November 12, 2012 Generally, the cast iron could be reused even in a major renovation provided it is sized appropriately. Floor drains are located in mechanical room. In a few areas spaces have changed use and floor drains are no longer required for this new use floor drains have not been properly capped. Floor drains in the fire station are missing tops allowing debris to enter into the system. Cleanout covers have been damaged.

    Floor Drain Missing Strainer Original Floor Drain Duplex sump pumps and duplex sewerage pumps are located in the basement area. The sump pump system has open cover allowing debris to enter the system. The access cover on the sewerage ejector has a loose cover that could allow sewer gas to enter the building. During the walk-through there was mention of back-ups and flooding from the pumping systems from time to time.

    Open Cover Sump Pump Duplex Sewer Ejector

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police & Fire Station Building Medford, MA Plumbing Existing Conditions Systems Report J#640 022 00.00 L#39039/Page 8/November 12, 2012 Natural Gas:

    There is a natural gas service supplying a roof top unit along with the water heater located in the mechanical room. The gas meter is located inside the building in what is not being used as a gym area.

    Service will need to be further investigated to verify if the system is large enough to support expansion. The existing gas piping is steel with a combination of welded and threaded joints.

    Gas Meter

    Compressed Air:

    The building is supplied with two compressors one in the police station for controls and the other in the fire station to supply hose reels and outlet connections.

    The existing compressed air piping system is steel with threaded joints.

    Air Hose Reel on Column

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police & Fire Station Building Medford, MA Plumbing Existing Conditions Systems Report J#640 022 00.00 L#39039/Page 9/November 12, 2012 Recommendations:

    All the plumbing fixtures are in need of replacement. All original fixtures are recommended to be replaced new fixtures. All new fixtures are to be water conservation type.

    Fixture counts and quantities are to be verified and installed to meet the current Plumbing Code requirements.

    All fixture locations that do not meet the current Access Code requirements for accessible plumbing fixtures are to be provided. All new faucets and fixtures are to be water conservation type.

    In general, all the drainage and vent piping systems may be reused. Should the decision be made to reuse the existing piping systems the piping needs to be tested to verify reuse. Reuse will also be based on the piping systems being adequately sized for the intended new use. The existing sanitary and roof drainage systems should also be videoed to verify the condition of the piping.

    Properly cap and make safe all unused plumbing connections.

    All new valves are to be provided on any existing water piping to remain.

    Install any new fixtures to meet program requirements.

    We recommend replacement of the existing units with high-efficiency type gas-fired domestic water heater.

    Relocate gas service and meters to outside the building. Provide new piping, valves to suit new program requirements.

    Abate all asbestos on existing piping, fittings, and storage tank.

    Where existing fixtures are connected to the existing sewerage ejectors, additional electrical costs occur due to frequent pumping with the use of non-water conserving type fixtures.

    Existing fixtures and trim are not water conserving type fixtures. Although, most fixtures are operable they are showing signs of wear and deterioration. Fixtures are over 50 years old and have reached their projected useful life.

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police & Fire Station Building Medford, MA Fire Protection Existing Conditions Systems Report J#640 022 00.00 L#39039/Page 1/November 12, 2012

    TEL 508-998-5700 FAX 508-998-0883 email: [email protected]

    FIRE PROTECTION Executive Summary:

    The Building currently contains no fire protection systems.

    Recommendations:

    Massachusetts Code requires that any new building or substantially renovated building of this type of use, 12,000 square feet or more, must be sprinklered. This building will meet those thresholds and will need sprinklers. New fire service to the building will be required.

    Any concealed combustible spaces will require sprinklers.

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police & Fire Station Academy Building Medford, MA Plumbing Existing Conditions Systems Report J#640 022 00.00 L#39163/Page 1/November 12, 2012

    TEL 508-998-5700 FAX 508-998-0883 email: [email protected]

    PLUMBING Executive Summary: The Medford Police Training and Fire Equipment Garage was originally constructed in 1978. Minor renovation projects have occurred over the years. The building is predominantly a two story building. A portion of the building has a three story fire training stairwell attached to the building. Presently, the plumbing systems serving the building are cold water, hot water, sanitary waste and vent system, garage waste piping, compressed air, grease piping, diesel piping, oil piping, automatic transmission fluid, storm drain piping, and natural gas. The building is serviced by municipal water and sewer systems. Garage wastes appear to be piped to a gas-oil separator located in the garage area and vented separate through the roof. Rain water from the roof areas is discharged with a series of roof drains connected to rain leaders and storm drains discharging to a collection system. There is an existing waste oil underground tank size unknown that has been abandoned in place. Need to verify if tank and piping has been properly abated. Existing Fixtures: Plumbing fixtures are the original fixtures. The water closets are wall mounted vitreous china, flush valve type with siphon jet action. The water closets are in reasonable condition. Water closets are not water conserving type fixtures. All accessible fixtures need to be verified to make sure they conform to current ADA requirements.

    Typical Wall Hung Water Outlet Accessible Wall Hung Water Outlet

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police & Fire Station Academy Building Medford, MA Plumbing Existing Conditions Systems Report J#640 022 00.00 L#39163/Page 2/November 12, 2012 Urinal is wall hung flush valve type vitreous china with siphon jet action with privacy partition located on one side. Partition is metal and surface is rusting and hard to keep clean and sanitary looking. Urinal is located in the toilet room for the police training area of the building. The urinal is in reasonable condition. Urinal is not water conserving type. All accessible fixtures need to be verified to make sure they conform to current ADA requirements.

    Wall Hung Urinal Lavatories are wall hung vitreous china. Sink faucets are 4 in. center set, non-metering, two handle type faucets. Accessible lavatories are wall hung vitreous china. Sink faucets are 8 in. center set, non-metering, two handle type faucets. All faucets are non-water conserving faucets. All accessible fixtures need to be verified to make sure they conform to current ADA requirements.

    Wall Hung Lavatory Accessible Wall Hung Lavatory Typical

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police & Fire Station Academy Building Medford, MA Plumbing Existing Conditions Systems Report J#640 022 00.00 L#39163/Page 3/November 12, 2012 Drinking fountain is wall hung vitreous china. Drinking fountain unit is missing in the police training portion of the building. Drinking fountain does not meet current ADA requirements. Units are not water cooled type units.

    Drinking Fountain Missing Drinking Fountain

    Showers unit is original fiberglass located in the fire department garage maintenance portion of the building. Some shower valve units are original others have been replaced. Shower head does not appear to be water conserving type.

    Shower Unit

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police & Fire Station Academy Building Medford, MA Plumbing Existing Conditions Systems Report J#640 022 00.00 L#39163/Page 4/November 12, 2012 Janitor's sinks are located in each portion of the facilities. Janitors sinks are enameled cast iron floor mounted. Faucets are equipped with vacuum breakers.

    Typical Service Sink

    Staff sinks are Dwyer enameled steel units with integral sink and two handle hot and cold water faucets. The sink units are not accessible. In various areas the enameled finish coating has been damaged. Faucets are non-water conserving faucets.

    Kitchen Units

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police & Fire Station Academy Building Medford, MA Plumbing Existing Conditions Systems Report J#640 022 00.00 L#39163/Page 5/November 12, 2012 Water Systems: Building is served by a 2 in. water service entering the mechanical/storage room at the rear of the building from Union Street. There is a 2 in. water meter installed on the service. Most hose connections are not protected with vacuum breakers. Exterior wall hydrants are not freeze-proof and do not have vacuum breakers installed.

    Water Service Hose connection without Vacuum Breaker Piping, where exposed, is mainly copper with sweat joints. The piping insulation is fiberglass a majority of the exposed piping is insulated only in a few areas has pipe insulation been removed. Most of the valves are original and are in reasonable condition. The majority of the piping is insulated.

    Existing Piping Insulation

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police & Fire Station Academy Building Medford, MA Plumbing Existing Conditions Systems Report J#640 022 00.00 L#39163/Page 6/November 12, 2012 Domestic water heating is provided by two electric water heaters a 40 gallon storage tank is located in the police training area. A 65 gallon storage tank is located in the fire department garage maintenance area. Both systems do not have a circulation pump installed. There is no thermostatic mixing valve to control hot water temperature for scald protection on the units.

    Police Training Area Water Heater Fire Department Garage Water Heater Drainage Systems:

    Cast iron with hub and spigot joints is used for sanitary, waste, vent, garage waste and vent piping, and storm drainage systems. The smaller sanitary waste and vent piping is a mixture of copper and galvanized steel piping. Where visible, the cast iron pipe appears to be in reasonable condition. Horizontal rain leaders are not insulated.

    Rain Leader Piping at Ceiling Garage Waste Vent Piping

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police & Fire Station Academy Building Medford, MA Plumbing Existing Conditions Systems Report J#640 022 00.00 L#39163/Page 7/November 12, 2012 Generally, the cast iron could be reused even in a major renovation provided it is sized appropriately. Floor drains are located in toilet rooms, mechanical rooms, and garage area. Roof drain is missing strainer allowing debris to enter into the system. There are several areas in the roof where ponding around the roof drains is visible. Cleanout covers have been damaged.

    Roof Drain Missing Strainer Proper Clean Out Cover Missing

    Evidence of Ponding at Roof Drains Natural Gas:

    There is a natural gas service supplying roof top units, generator, and garage ceiling mounted heaters. The gas meter is located outside the building at the rear of the building on Union Street. Gas piping on the roof is not protected and is rusting.

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police & Fire Station Academy Building Medford, MA Plumbing Existing Conditions Systems Report J#640 022 00.00 L#39163/Page 8/November 12, 2012 Service will need to be further investigated to verify if the system is large enough to support expansion.

    The existing gas piping is steel with threaded joints.

    Gas Meter

    Compressed Air:

    The fire department maintenance garage has a duplex air compressor to supply tools and equipment for the garage area. Each compressor has a 5 hp motor and are located above the receiver. Compressed air system appears to be in reasonable condition.

    The existing compressed air piping system is steel with threaded joints.

    Air Compressors Mounted Above Tank

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police & Fire Station Academy Building Medford, MA Plumbing Existing Conditions Systems Report J#640 022 00.00 L#39163/Page 9/November 12, 2012 Garage Systems:

    Grease piping, diesel oil piping, oil piping and automatic transmission fluid systems are provided in the fire department maintenance garage. Each system is piped from tanks located in the fluid storage room to hose reels located in the garage area. Systems appear to be in reasonable condition.

    Hose Reels for Air and Fluids Fluid Storage Tanks

    Recommendations:

    Existing fixtures and trim are not water conserving type fixtures.

    Although most fixtures are still operable they are showing signs of wear and deterioration.

    All the plumbing fixtures are in need of replacement. All original fixtures are recommended to be replaced new fixtures. All new fixtures are to be water conservation type.

    Fixture counts and quantities are to be verified and installed to meet the current Plumbing Code requirements assembly use.

    All fixture locations that do not meet the current Access Code requirements for accessible plumbing fixtures are to be provided. All new faucets and fixtures are to be water conservation type.

    In general, all the drainage and vent piping systems may be reused. Should the decision be made to reuse the existing piping systems the piping needs to be tested to verify reuse. Reuse will also be based on the piping systems being adequately sized for the intended new use. The existing sanitary, garage waste and roof drainage systems should also be videoed to verify the condition of the piping.

    Properly cap and make safe all unused plumbing connections.

    All new valves should be provided on any existing water, compressed air, and fluid piping to remain.

    Install any new fixtures to meet program requirements.

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police & Fire Station Academy Building Medford, MA Plumbing Existing Conditions Systems Report J#640 022 00.00 L#39163/Page 10/November 12, 2012 We recommend replacement of the existing electric water heating units be replaced with high-efficiency type gas-fired domestic water heaters.

    Provide new piping, valves to suit new program requirements.

    The existing underground waste oil storage tank and piping system, if not properly abated, needs to be removed and abated to conform to the State of Massachusetts requirements.

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police & Fire Station Academy Building Medford, MA Fire Protection Existing Conditions Systems Report J#640 022 00.00 L#39164/Page 1/November 12, 2012

    TEL 508-998-5700 FAX 508-998-0883 email: [email protected]

    FIRE PROTECTION Executive Summary: The Medford Police Training and Fire Equipment Garage was originally constructed in 1978. Minor renovation projects have occurred over the years. The building is predominantly a two story building. A portion of the building has a three story fire training stairwell attached to the building. Presently, the building is protected with a partial wet sprinkler system for the garage portion of the building only. The three story fire training stair tower contains a sprinkler and standpipe training systems. Systems for this area are drained when not being used for training. A fire department connection used for training is located on this portion of the building. Fire Protection System: The building is served by a 6 inch fire water service entering the mechanical/storage room at the rear of the building from Union Street. There is no back flow prevention device on the incoming fire service. The system is a wet system with a 4 inch alarm valve with water motor gong. The incoming pressure is approximately 70 psi based on pressure gauge on the inlet of the alarm valve. The fire department connection for the system is located outside the mechanical/storage room at the rear of the building on Union Street. Valves on the system are chained and locked and are not electrically supervised. The existing sprinkler piping is steel with flanged and threaded joints.

    Building Fire Service

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police & Fire Station Academy Building Medford, MA Fire Protection Existing Conditions Systems Report J#640 022 00.00 L#39164/Page 2/November 12, 2012 Recommendations:

    Massachusetts Code requires that any new building or substantially renovated building of this type of use, 12,000 square feet or more, must be sprinklered. This building will meet those thresholds and will need to have sprinklers installed based on the extent of renovation.

    Any concealed combustible spaces will require sprinklers.

    In general, the existing sprinkler piping systems may be reused. Should the decision be made to reuse the existing piping systems the piping needs to be tested to verify reuse. Reuse will also be based on the piping systems being adequately sized for the intended new use.

    All new and existing valves to remain are to be electrically supervised.

    Install any new wet sprinkler system in all areas to meet program requirements.

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police and Fire Station Building Medford, MA Electrical Existing Conditions Systems Report J#640 022 00.00 L#39033/Page 1/November 12, 2012

    TEL 508-998-5700 FAX 508-998-0883 email: [email protected]

    ELECTRICAL Executive Summary: In general, the electrical systems range from original vintage to more recent upgrades such as the service equipment. The electrical service is adequate in capacity and voltage characteristics. It is our recommendation, taking into consideration the age and general condition of the existing equipment, that most systems be replaced with new energy efficient code compliant systems, such as fire alarm, emergency lighting, interior lighting, exterior lighting, generator, power distribution equipment, and panelboards. Electrical Distribution System: There is one service present at the facility. The service is rated at 800A, 120/208V, 3, 4W and has adequate capacity for the building with its present needs. The existing service equipment is manufactured by Seimens and is relatively new. The site is on one secondary meter located in the main electric room. The service is overhead to the building from utility pole mounted transformers.

    Overhead Service Meter There are electrical sub-panels located throughout the facility. The panels are circuit breaker type and are original to the building. The panels are manufactured by Federal Pacific and are in poor condition. Federal Pacific breakers have a history of failing and not providing the rated over current protection as required by code. Some panels have breakers that are missing with no blank covers and spare breakers are not readily available.

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police and Fire Station Building Medford, MA Electrical Existing Conditions Systems Report J#640 022 00.00 L#39033/Page 2/November 12, 2012

    TEL 508-998-5700 FAX 508-998-0883 email: [email protected]

    Main Service Panel Main Distribution Panel

    Electrical Panel Boiler Room Panels

    Original Panel Corridor Panels

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police and Fire Station Building Medford, MA Electrical Existing Conditions Systems Report J#640 022 00.00 L#39033/Page 3/November 12, 2012

    TEL 508-998-5700 FAX 508-998-0883 email: [email protected]

    Branch Circuits: Some receptacles provided throughout the building appear to have been replaced and some are original. Most receptacles are in fair condition but do not provide sufficient quantities for the stations present needs. A few receptacles are broken and need to be replaced.

    Broken Receptacle Additional Receptacles Interior Lighting System: Lighting in the corridor and offices are 2ft. x 2 ft. recessed prismatic fluorescent fixtures. The Maintenance bay and the Apparatus bay has surface industrial fluorescent fixtures and wall mounted fluorescent fixtures. Toilet rooms have a 1 ft. x 4ft. surface of fluorescent fixtures with no lens. The Storage rooms and Stairs have surface drum type light fixtures.

    Apparatus Bay Lighting Corridor Lighting

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police and Fire Station Building Medford, MA Electrical Existing Conditions Systems Report J#640 022 00.00 L#39033/Page 4/November 12, 2012

    TEL 508-998-5700 FAX 508-998-0883 email: [email protected]

    Apparatus Bay Wall Lighting Storage Room

    Toilet Room Stairs Sleeping quarters consists of recessed 2 ft. x 4 ft. fluorescent fixtures. Corridors in the upper level are surface mounted drum fluorescent fixtures. The Boiler room has industrial fluorescent fixtures with T12 lamps and some with T8 lamps. Booking has surface 1 ft. x 4 ft. wraparound surface fluorescent fixtures.

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police and Fire Station Building Medford, MA Electrical Existing Conditions Systems Report J#640 022 00.00 L#39033/Page 5/November 12, 2012

    TEL 508-998-5700 FAX 508-998-0883 email: [email protected]

    Boiler Room Booking Emergency Lighting System: There is an exterior emergency generator present. The generator appears to be original to the building. The generator is rated at 275 kW, 120/208 V, 3, 4W and is manufactured by Kohler with a diesel base tank. There is one transfer switch which covers the entire building. The transfer switch appears relatively new and is in good condition and is manufactured by ASCO.

    Exterior Generator Transfer Switch

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police and Fire Station Building Medford, MA Electrical Existing Conditions Systems Report J#640 022 00.00 L#39033/Page 6/November 12, 2012

    TEL 508-998-5700 FAX 508-998-0883 email: [email protected]

    Exit signs appear to be fluorescent type, are in poor condition, and are not lit. Most areas are lacking exit signs which are required to meet current codes.

    Exit Sign Site Lighting System: The lighting at the site consists of perimeter lighting which lights the area walkways from the exterior walls of the building. They are original to the building and appear to provide adequate lighting.

    Exterior Perimeter Lighting Exterior Entrance Lighting Fire Alarm System: The fire alarm panel is manufactured by Notifier and is a non-addressable system. The system is not ADA compliant due to the horn/strobe ratings. ADA requires strobes to have a specific candela and decibel rating for a specific room or space configuration. Transmission is via a local master box.

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police and Fire Station Building Medford, MA Electrical Existing Conditions Systems Report J#640 022 00.00 L#39033/Page 7/November 12, 2012

    TEL 508-998-5700 FAX 508-998-0883 email: [email protected]

    Master Box Fire Alarm Control Panel

    The coverage of fire alarm devices is lacking in most areas. Heat detectors and smoke detectors are not present in most rooms. The Massachusetts State Building Code requires all rooms or spaces to be provided with automatic alarm devices in non-sprinklered buildings. The spacing of devices must comply with NFPA 72.

    Smoke Detector Heat Detector

    Pull Station and Horn/Strobe

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police and Fire Station Building Medford, MA Electrical Existing Conditions Systems Report J#640 022 00.00 L#39033/Page 8/November 12, 2012

    TEL 508-998-5700 FAX 508-998-0883 email: [email protected]

    Data/Telephone/Security System: There is a telephone system present which is used throughout the stations. The telephone service is provided overhead from a utility pole into the electrical shop. Service runs to the recently renovated 911Dispatch Center on the second floor. 911 Dispatch Center: The 911 Dispatch Center consists of recessed fluorescent downlights, 2 ft. x 2 ft. fluorescent fixtures and edge-lit exit signs. The panelboard is new and receptacles are provided throughout the space. Smoke detectors, manual pull stations, and horn/strobe units are present. All equipment is relatively new and in good condition with the exception of the non-addressable fire alarm equipment and devices.

    911 Dispatch, Smoke Detector and Exit Sign New Panel

    Lighting 911 Dispatch

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police and Fire Station Building Medford, MA Electrical Existing Conditions Systems Report J#640 022 00.00 L#39033/Page 9/November 12, 2012

    TEL 508-998-5700 FAX 508-998-0883 email: [email protected]

    Recommendations Electrical Distribution System: The existing service is relatively new and sufficient for the present needs of the station. It provides some future capacity. Panelboards throughout the facility are in poor condition as described on Page 1 of this report. The panelboards need to be replaced. Branch Circuit: Receptacles throughout the facility are not sufficient for the present needs. Additional outlets should be provided in the sleeping quarters and other areas throughout the building to eliminate the need for extension cords. This would not require an increase to the existing electrical service. Interior Lighting: The existing lighting is not the most energy efficient type. Additional energy savings would be achieved by replacing the lighting system and controls. Emergency Lighting: The existing generator is sufficiently sized to provide emergency power to the entire building at the present time including some additional future outlets. The automatic transfer switch is in good condition. The generator is original to the building, is in fair condition and is at the end of its useful life. The existing generator should be replaced with a new exterior unit. Additional emergency lighting needs to be provided throughout the building. A second transfer switch should be provided to include life safety loads only. Site Lighting: The existing exterior lighting appears to provide sufficient coverage. However, existing fixtures are original to the building and are not the latest energy efficient type. Additional energy savings can be achieved with newer fixtures and control. Fire Alarm System: Existing fire alarm system does not meet todays code requirements for full coverage and strobe levels. A new addressable system should be provided with new addressable devices and ADA Horn/Strobe units meeting current code requirements. Data/Telephone/Security System: Existing system appears to provide adequate devices to accommodate current needs. Additional devices should be provided as the need arrives.

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police and Fire Academy Building Medford, MA Electrical Existing Conditions Systems Report J#640 022 00.00 L#39174/Page 1/November 14, 2012

    TEL 508-998-5700 FAX 508-998-0883 email: [email protected]

    ELECTRICAL Executive Summary:

    The existing electrical systems, in general although functioning, are at the end or have exceeded their useful life. Even with regular maintenance, systems have deteriorated over the years to the point of disrepair. Most systems are of original vintage, approximately 35 years old, and are in poor condition. The life safety systems, due to code changes over the lifespan of the facility, are no longer in compliance with current code. Switchgear is obsolete and not suited for expansion. The generator system no longer functions in the automatic mode. Fire alarm system is not code compliant. In general, due the age and condition of the facilitys electrical systems, we recommend a total replacement of these systems. Electrical Distribution System: The primary service originates on utility company Pole #4, located at the rear of the police station where it drops and runs underground across the parking lot in two 4 inch conduits (one spare) to a utility company owned pad-mounted transformer.

    Primary Utility Pole Pad-Mounted Transformer

    The secondary service then runs underground between the pad-mounted transformer and a 600 ampere main circuit breaker and C/T cubicle located in the Main Electric Room. An 800 ampere main distribution panel distributes power to the remainder of the facility. Panelboards exist throughout the facility. Most panels have no space/spare capacity for added circuits. NSTAR Meter #82124509 is located in the Electric Room.

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police and Fire Academy Building Medford, MA Electrical Existing Conditions Systems Report J#640 022 00.00 L#39174/Page 2/November 14, 2012

    TEL 508-998-5700 FAX 508-998-0883 email: [email protected]

    Switchgear was manufactured by Federal Pacific (FPE) , is obsolete, and in poor condition.

    600A MCB/CT Cubicle Main Distribution Panel

    Double tub panelboard in Maintenance Garage has surface conduit penetrations through the garage floor with no electrical seals. The panelboard in the Oil Room has foreign piping over the panel, which is a code violation. Service grounding electrode is not connected to main water service in violation of code.

    Garage Panels Oil Room Panel Water Meter (Not Grounded)

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police and Fire Academy Building Medford, MA Electrical Existing Conditions Systems Report J#640 022 00.00 L#39174/Page 3/November 14, 2012

    TEL 508-998-5700 FAX 508-998-0883 email: [email protected]

    Interior Lighting: Training Room lighting consists of 2 x 4 recessed fixtures with acrylic lenses with three T8 lamps and electronic ballasts. Audio/visual lighting consists of recessed down lights with incandescent par lamps. Training Room lights are controlled with two key switches and two occupancy sensors. Recessed lights are controlled with two wall dimmers. Office areas have the same fixtures as the Training Room, some with a missing lens. Offices generally have single switches and no occupancy sensors.

    Consumer Affairs Office First Floor Offices

    Training Room The Maintenance Garage has 12 in. x 4 ft open-bottom suspended fixtures with four T4HO lamps with plug-in cords. Fixtures plug into dedicated outlets mounted to trusses adjacent to fixtures. Garage lights are breaker controlled with no local switches. Fixtures are mounted over 12 ft. AFF. Open lamp strips also exist in garage over work benches and are mounted below 12 ft. AFF. Maintenance support spaces and various offices have open strips and utility wraparound fixtures. Most spaces are controlled with a single switch.

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police and Fire Academy Building Medford, MA Electrical Existing Conditions Systems Report J#640 022 00.00 L#39174/Page 4/November 14, 2012

    TEL 508-998-5700 FAX 508-998-0883 email: [email protected]

    Maintenance Garage Overhead Lights Maintenance Garage Work Bench Stair lighting consists of industrial strips with local switches.

    Stairwell Exterior Lighting: Exterior lighting consists mainly of minimal building-mounted flood lights, some with integral photocell, on a time clock. There are no pole-mounted light fixtures in parking areas. Open junction boxes exist with missing light fixtures. Door entries have wall sconces. Fixtures are not of the cut-off type. Exterior lighting is inadequate and virtually nonexistent.

    Flood Light Training Tower Exterior Flood Light

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police and Fire Academy Building Medford, MA Electrical Existing Conditions Systems Report J#640 022 00.00 L#39174/Page 5/November 14, 2012

    TEL 508-998-5700 FAX 508-998-0883 email: [email protected]

    Exterior Open Junction Box, Missing Light Entry Door Sconce Emergency Standby System: The existing emergency standby generator is rated at 30kW, 37.5 KVA, 120/208V, 3 phase, 4W, natural gas fired. The generator is original to the building and was manufactured by Kohler (Model #30RZB2). There is only one Kohler transfer switch which is currently not able to start automatically and requires manual intervention to start the generator and transfer power. The generator and ATS are located in the same room as the electrical switchgear and air compressor which is in violation of current codes. Life safety lighting and optional equipment share the same panel, also a code violation.

    Generator with Through-Wall Exhaust Generator Panel Various exit signs are not functioning. Battery units with integral heads exist in the Police Department side of the building which are in poor condition and are missing heads. Emergency lighting is inadequate and non code-compliant.

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police and Fire Academy Building Medford, MA Electrical Existing Conditions Systems Report J#640 022 00.00 L#39174/Page 6/November 14, 2012

    TEL 508-998-5700 FAX 508-998-0883 email: [email protected]

    Battery Unit with One Head

    Fire Alarm System: The fire alarm system consists of an FCI 12 zone, six active, non-addressable control panel located in the Electric Room. The horn/strobes are not ADA compliant and have inadequate coverage. Smoke detectors exist in the Training Room and in corridors. Heat detectors exist in various spaces throughout the building including stairwells. There are no heat detectors in the garage. Pull stations exist at exit discharge doors. An LED annunciator exists in the corridor. A sprinkler system pressure switch is connected to the fire alarm. Tampers are not monitored, but are chain locked. No CO detector was noted in the Staff Room where a bunk exists.

    Fire Alarm Control Panel Pull Station & Horn/Strobe Unit Fire Alarm Annunciator

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police and Fire Academy Building Medford, MA Electrical Existing Conditions Systems Report J#640 022 00.00 L#39174/Page 7/November 14, 2012

    TEL 508-998-5700 FAX 508-998-0883 email: [email protected]

    General Wiring Devices: Wiring devices are generally sparsely located throughout the facility. The Training Room has had additional surface receptacles added to perimeter walls. Tele/power poles exist in Consumer Affairs Office area. Breakers have been tripping due to plug-in electric heaters used in the Consumer Affairs space.

    Training Room Outlets Tele/Power Pole, CA Offices

    Portable Electric Heater

    Receptacles in the maintenance garage, kitchen, and boiler room are not GFI type. Receptacles are mounted at 48 in above the floor. Receptacles are required to be GFI type.

    Garage Receptacles

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police and Fire Academy Building Medford, MA Electrical Existing Conditions Systems Report J#640 022 00.00 L#39174/Page 8/November 14, 2012

    TEL 508-998-5700 FAX 508-998-0883 email: [email protected]

    General Wiring: The general wiring method is pipe and wire and AC/MC cable.

    Telephone Backboard Data Patch Panel Forensics Lab

    Data/Telephone/Security Systems:

    Overhead telephone cable exists between adjacent Police Station and telephone backboard in Water Service Room. Cable terminates in a protected entrance terminal cabinet, 3M 4188. A northern telecom Meridian telephone switch services the facility.

    Cable TV Service originates on Pole #4 at the rear of the parking lot and runs overhead into the Water Service Room.

    Data infrastructure wiring is CAT 5e. Patch panels exist in Water Service Room. Fiber interconnection exists between Police and Academy Buildings. Data wiring typically runs exposed within working spaces.

    A closed circuit TV (CCTV) system exists with interior and exterior cameras connected to a 500GB, 16-channel DVR located on top of a locker in the Water Service Room.

    There is a card access system on the police side of the facility with a handful of proximity readers including exterior door and Training Room but none on the Forensics Lab.

    The existing facilities intrusion system is not functioning. The keypad in the garage is hanging by its own wires.

    The Forensics Lab has its own intrusion system, a Magnum Alert 1000 series with control panel located within the lab, over the door. A keypad exists at the door into the lab. The lab has two passive infrared sensors and door magnetic contact.

    A ground mounted fixed, three post lift exists with local control station.

    The Training Room has a portable local sound system.

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police and Fire Academy Building Medford, MA Electrical Existing Conditions Systems Report J#640 022 00.00 L#39174/Page 9/November 14, 2012

    TEL 508-998-5700 FAX 508-998-0883 email: [email protected]

    Security Keypad- Garage Security Keypad-Forensics Lab Local Sound System Rack Miscellaneous: There is no lightning protection system for the facility.

    There are no electrical systems, including lighting or receptacles, in the training tower.

    Maintenance Garage:

    o Two vehicle exhaust systems exist in the maintenance garage. o There is a through-wall exhaust fan with local switch. o An overhead crane exists, traveling front to rear of the garage bay. o Two 50A/2P welder outlets exist. o Overhead doors are electrically operated with local control stations. It is unclear if safety

    door sensors are functioning or exist.

    Recommendations:

    General:

    In general, the electrical systems will require full replacement under a renovation program. Due to inability to conceal raceways, under a renovation program we recommend the use of a surface metal raceway system in finished spaces equal to wiremold. Mechanical rooms, storage rooms, maintenance garage, etc will require surface conduits.

    Electrical Distribution System:

    The existing secondary service and switchgear , due to its poor condition, should be replaced. Service capacity ratings are designed for a demand load of 10 watts/s.f. New lighting and power panels will be provided to accommodate respective loads and located in electric rooms. A system of computer grade panelboards with double neutrals and integral surge protective devices will be utilized to mitigate the harmonic effects caused by computers and other electronics.

  • GARCIA GALUSKA DESOUSA Consulting Engineers Inc.

    Medford Police and Fire Academy Building Medford, MA Electrical Exi