Page 1: ME150P ELecture 1 (04 January 2011)

ME150P/B1 Lectures3rd Term S.Y. 2010-2011

Group 1

Page 2: ME150P ELecture 1 (04 January 2011)

Orientation 04 January 2011

Page 3: ME150P ELecture 1 (04 January 2011)

I. PsychrometryII. Air Conditioning SystemIII. Heat Load EstimationIV. Practical Air Conditioning SystemV. Air Distribution SystemVI. Piping SystemVII. Equipment SelectionVIII. Refrigerated LoadIX. Ice Manufacturing

Lecture Outline

Page 4: ME150P ELecture 1 (04 January 2011)

I. Heat LoadII. Air DistributionIII. Equipment Selection

Report Outline

Page 5: ME150P ELecture 1 (04 January 2011)

Refrigeration and Air Conditioning (Chapters 14 & 15) by C.P. Arora

Carrier System Design Manual Part I, II, & III Mechanical Engineering Tables and Charts

Latest Edition by MRII Refrigeration (Chapter X: Cooling Load

Calculation) by Dossat (SI Edition) Ken’t Handbook – Power Volume (Section

11: Ice Manufacturing)

Textbooks & References

Page 6: ME150P ELecture 1 (04 January 2011)

Psychrometry08 January 2011

Page 7: ME150P ELecture 1 (04 January 2011)

Chapter 14: Properties of Moist Air; Refrigeration and Air Conditioning by C.P. Arora

Dry air and water vapor form a binary mixture. The properties of moist air are called psychrometric properties and the subject which deals with the behavior of moist air is known as psychrometry.

PSYCHROMETRIC PROPERTIES

Page 8: ME150P ELecture 1 (04 January 2011)

Specific or absolute humidity or humidity ratio or moisture content as it is variously called denoted by the symbol ω is defined as the ratio of the mass of water vapor (w.v.) to the mass of dry air (d.a.) in a given volume of the mixture. Thus

Where the subscripts a and v refer to dry air and water vapor respectively.

Specific Humidity or Humidity Ratio

v a

a v

m

m

Page 9: ME150P ELecture 1 (04 January 2011)

Since p denotes the actual total atmospheric pressure, then from Dalton’s Law

So that,

Specific Humidity or Humidity Ratio

a vp p p

0.622 v

v

p

p p

Page 10: ME150P ELecture 1 (04 January 2011)

The concept of specific humidity is that if we take 1 kg of dry air

Then the mass of water vapor associated with this dry air, in the same volume is

so that the total mass of this volume of moist air is

.

Specific Humidity or Humidity Ratio

1am kg

vm kg

(1 )m kg

Page 11: ME150P ELecture 1 (04 January 2011)

The temperature is called the dew point temperature (DPT). It is the temperature to which moist air must be cooled at constant pressure before condensation of moisture takes place.

The DPT can be found by knowing, from the steam tables, the saturation temperature at the partial pressure of the water vapor.

Dew Point Temperature

dt

dtvp

Page 12: ME150P ELecture 1 (04 January 2011)

PROBLEM◦ In a dew point apparatus a metal beaker is

cooled by gradually adding ice water to the water initially at room temperature. The moisture from the room air begins to condense on the beaker when its temperature is 12.8˚C. If the room temperature is 21˚C and the barometric pressure is 1.01325 bar, find the partial pressure of water vapor in the room air and parts by mass of water vapor in the room air.

Example 14.2, page 454

Page 13: ME150P ELecture 1 (04 January 2011)

SOLUTION◦ Partial pressure of water vapor at DPT 12.8˚C

◦ Partial pressure of dry air

◦ Specific humidity

Example 14.2, page 454

21.479 kN/mvp

2101325 1479 99846 N/m

a v

a

p p p

p

14790.622 0.622

99846v v

a a

m p

m p

Page 14: ME150P ELecture 1 (04 January 2011)

SOLUTION◦ Specific humidity

◦ Parts by mass of water vapor

Example 14.2, page 454

w.v.0.009214

d.a.

kg

kg

0.009214 w.v.0.00913

1 1.009214 mixturevm kg

m kg

Page 15: ME150P ELecture 1 (04 January 2011)

The degree of saturation is a measure of the capacity of air to absorb moisture.

It is denoted by the symbol μ

Degree of Saturation

1

1v s

s s v

p p p

p p p

Page 16: ME150P ELecture 1 (04 January 2011)

Relative humidity denoted by the symbol φ or RH is defined as the ratio of the mass of water vapor in a certain volume of moist air at a given temperature to the mass of water vapor in the same volume of saturated air at the same temperature.

Relative Humidity

v s

s v

pRH

p

Page 17: ME150P ELecture 1 (04 January 2011)

The enthalpy of moist air is obtained by the summation of the enthalpies of the constituents. Thus, the enthalpy of moist air h is equal to the sum of the enthalpies of dry air and associated water vapor, i.e.,

per kg of dry air, where subscripts a are for dry air and v are for the water vapor part.

Enthalpy of Moist Air

a vh h h

Page 18: ME150P ELecture 1 (04 January 2011)

◦ Where t is in ˚C

◦ Where t is in ˚C

Enthalpy of Moist Air

1.005 (2500 1.88 ) kJ/kg d.a. h t t

0.24 (1061 0.444 ) Btu/lbm d.a. h t t

Page 19: ME150P ELecture 1 (04 January 2011)

PROBLEM: A mixture of dry air and water vapor is at a temperature of 21˚C under a total pressure of 736 mmHg. The dew point temperature is 15˚C. Find:i. Partial pressure of water vaporii. Relative humidityiii. Specific humidityiv. Specific enthalpy of water vapor by the three

methods of Fig. 14.5v. Enthalpy of air per kg of dry airvi. Specific volume of air per kg of dry air

Example 14.3, page 458

Page 20: ME150P ELecture 1 (04 January 2011)

SOLUTION:i. From steam tables, the partial pressure of

water vapor at 15˚C DPT is

ii. Saturation pressure of water vapor at 21˚C DBT

Relative humidity

.

Example 14.3, page 458

212.79 mmHg = 12.79 (133.5) = 1707.5 N/mvp

218.65 mmHg = 18.65 (133.5) = 2489.8 N/msp

12.79100 100 68.58%

18.56v

s

p

p

Page 21: ME150P ELecture 1 (04 January 2011)

iii. Specific humidity

iv. Latent heat of vaporization of water at dry bulb and dew-point temperatures of air

Example 14.3, page 458

(12.79)0.622 0.622

(736 12.79)

0.011 kg w.v./kg d.a.

v

a

p

p

21

15

( ) 2452 kJ/kg

( ) 2466.2 kJ/kg

fg C

fg C

h

h

Page 22: ME150P ELecture 1 (04 January 2011)

Specific enthalpy of water vapor from Fig. 14.5 by the three methods

Note: The three values are extremely close to each other.

Example 14.3, page 458

(4.1868)(21) 2452 2450 kJ/kg w.v.

(4.1868)(15) 2466.2 1.88(21 15)

2540.3 kJ/kg w.v.

2501 1.88(21) 2540.5 kJ/kg w.v.

C

A

A

B

h

h

h

h

Page 23: ME150P ELecture 1 (04 January 2011)

v. Enthalpy of air using the value of specific enthalpy of water vapor from the empirical relation

vi. Specific volume of air is equal to the volume of 1 kg of dry air or 0.011 kg of water vapor. Based on the dry air part

.

Example 14.3, page 458

1.005(21) 0.011(2540.5)

21.1 27.9 49.0 kJ/kg d.a.

a vh h h

h

h

3287.3(273 21)0.875 m /kg d.a.

(723.21)(133.5)a

aa

R T

p

Page 24: ME150P ELecture 1 (04 January 2011)

The dry bulb thermometer is directly exposed to the air and measures the actual temperature of air.

The bulb of the wet bulb thermometer is covered by a wick thoroughly wetted by water.

The temperature which is measured by the wick-covered bulb of such a thermometer indicates the temperature of liquid-water in the wick and is called the wet bulb temperature.

WET BULB TEMPERATURE (WBT)

Page 25: ME150P ELecture 1 (04 January 2011)

All data essential for the complete thermodynamic and psychrometric analysis of air-conditioning processes can be summarized in a psychrometric chart.

The chart which is most commonly used is the ω-t chart, i.e., a chart which has specific humidity or water vapor pressure along the ordinate and the dry bulb temperature along the abscissa.

The chart is normally constructed for a standard atmospheric pressure of 760 mm Hg or 1.0132 bar, corresponding to the pressure at the mean sea level.

PSYCHROMETRIC CHART

Page 26: ME150P ELecture 1 (04 January 2011)

PSYCHROMETRIC CHART Skeleton

Page 27: ME150P ELecture 1 (04 January 2011)

Dry-bulb temperature = The temperature of air as registered by an ordinary thermometer.

Wet-bulb temperature = The temperature registered by a thermometer whose bulb is covered by a wetted wick and exposed to a current of rapidly moving air.

Dewpoint temperature = The temperature at which condensation of moisture begins when the air is cooled.

Definition of Terms

Page 28: ME150P ELecture 1 (04 January 2011)

Relative Humidity = Ratio of the actual water vapor pressure of the air to the saturated water vapor pressure of the air at the same temperature.

Specific Humidity or Moisture Content = The weight of water vapor in grains or pounds of moisture per pound of dry air.

Definition of Terms

Page 29: ME150P ELecture 1 (04 January 2011)

Enthalpy = A thermal property indicating the quantity of heat in the air above an arbitrary datum, in Btu per pound of dry air. The datum for dry air is 0˚F, and for the moisture content, 32˚F water.

Specific Volume = The cubic feet of the mixture per pound of dry air.

Sensible Heat Factor = The ratio of sensible to total heat.

Definition of Terms

Page 30: ME150P ELecture 1 (04 January 2011)

Pounds of Dry Air = The basis for all psychrometric calculations. Remains constant during all psychrometric processes.

◦ Note: The dry-bulb, wet-bulb, and dewpoint temperatures and the relative humidity are so related that, if two properties are known, all other properties shown may then be determined. When air is saturated, dry-bulb, wet-bulb, and dewpoint temperatures are all equal.

Definition of Terms

Page 31: ME150P ELecture 1 (04 January 2011)

CARRIER PSYCHROMETRIC CHART

Page 32: ME150P ELecture 1 (04 January 2011)

PSYCHROMETRIC CHART Skeleton

Page 33: ME150P ELecture 1 (04 January 2011)

Edited

Page 34: ME150P ELecture 1 (04 January 2011)
Page 35: ME150P ELecture 1 (04 January 2011)
Page 36: ME150P ELecture 1 (04 January 2011)
Page 37: ME150P ELecture 1 (04 January 2011)
Page 38: ME150P ELecture 1 (04 January 2011)
Page 39: ME150P ELecture 1 (04 January 2011)
Page 40: ME150P ELecture 1 (04 January 2011)
Page 41: ME150P ELecture 1 (04 January 2011)
Page 42: ME150P ELecture 1 (04 January 2011)
Page 43: ME150P ELecture 1 (04 January 2011)
Page 44: ME150P ELecture 1 (04 January 2011)
Page 45: ME150P ELecture 1 (04 January 2011)
Page 46: ME150P ELecture 1 (04 January 2011)
Page 47: ME150P ELecture 1 (04 January 2011)
Page 48: ME150P ELecture 1 (04 January 2011)
Page 49: ME150P ELecture 1 (04 January 2011)
Page 50: ME150P ELecture 1 (04 January 2011)

Psychrometry of Air-Conditioning Processes

Page 51: ME150P ELecture 1 (04 January 2011)

Cooling coilMixing Box

12

2

Blower

In RA

m

1

2

DB1

DB2

WB2

WB1

h2

h1

RC = m(h1 – h2)

FIGURE 1

Page 52: ME150P ELecture 1 (04 January 2011)

RETURN AIR

SUPPLY AIR

Cooling coil

Mixing Box

1

2

3

1

2

DB1

DB2

WB2

WB1

h2

h1

DB3

WB3

h3

3

w1

w2

w3

FIGURE 2

Page 53: ME150P ELecture 1 (04 January 2011)

Equations that can be derived based on the Psychrometric Chart (Figure 2):

Page 54: ME150P ELecture 1 (04 January 2011)

Sample Problem Example 15.1 (p. 475)

30 m3 /min of a stream of moist air at 15C DBT and 13C WBT is mixed with 12 m3 /min of a second stream at 25C DBT and 18C WBT. Barometric Pressure is one standard atmosphere. Determine the dry bulb and wet bulb temperatures of the resulting mixture.

Required: WB3 and DB3

Page 55: ME150P ELecture 1 (04 January 2011)

SOLUTION

Cooling coil

Mixing Box

15C DB13C WB30 m3 /min

25C DB18C WB12 m3 /min

1

2

25C

15C

13C

18CV1= 0.86

V2= 0.825

Page 56: ME150P ELecture 1 (04 January 2011)

Then,

Page 57: ME150P ELecture 1 (04 January 2011)

Example 15.2 (p.476)

A stream of moist air at 2C DBT and 80% RH mixes with another stream of moist air at 30C DBT and 10C DPT in the ratio by mass of one part of the first to tow parts of the second. Calculate the temperature and specific humidity of the air after mixing.

Page 58: ME150P ELecture 1 (04 January 2011)

BYPASS FACTOR

Page 59: ME150P ELecture 1 (04 January 2011)

SOLUTION

Cooling coil

Mixing Box

15C DB13C WB30 m3 /min

25C DB18C WB12 m3 /min

1

2

25C

15C

13C

18C

Page 60: ME150P ELecture 1 (04 January 2011)

Definition

The following figure shows the process that the moist air undergoes while flowing over a surface .

The air enters at 1 and leaves at 2 when the surface is maintained at S.

The state of the contacted air is that of saturated air at the temperature of the surface. There is thus the equivalent of perfect contact of a definite portion of the air particles with the surface.

Page 61: ME150P ELecture 1 (04 January 2011)

The uncontacted air remains at the entering state.

The end state of the air is the same as that produced by the complex entering of the contacted and uncontacted particles.

hs

h2

h1

S w3

1

t1t2ts

2 w2

w1

t

w

Page 62: ME150P ELecture 1 (04 January 2011)

Thus one can define a bypass factor of the apparatus representing the fraction of “uncontacted air” in terms of 1,2,and S as:

Conversely, one can define a contact factor (1-X) representing a fraction of the contacted air.

Page 63: ME150P ELecture 1 (04 January 2011)

Simple Air conditioning system and state and mass rate of

supply air

Page 64: ME150P ELecture 1 (04 January 2011)

RETURN AIR AT t1, w1

SUPPLY AIR AT ts, ws

Room at t1, w1

AHU

Cooling coil

Mixing Box

Page 65: ME150P ELecture 1 (04 January 2011)

Formulas:

Sensible Heat Balance:

Latent Heat Balance:

Base on Enthalpy:

Page 66: ME150P ELecture 1 (04 January 2011)

Sample problems Find the resulting dry bulb temperature of

the mixture given the following conditions:

OUTDOOR AIR RETURN AIRm= 2 kg/s m= 3kg/s35OCDB 24OCDB25OCWB 50% RH

Page 67: ME150P ELecture 1 (04 January 2011)

SOLUTION

2kg/s35OCDB25OCWB

Figure

m= 3kg/s50% RH24OCDB

Page 68: ME150P ELecture 1 (04 January 2011)

WBm

Wm

35oC28.4oC

24oC

25oC

OA

50%RM

MIX

Page 69: ME150P ELecture 1 (04 January 2011)

Equation:

Page 70: ME150P ELecture 1 (04 January 2011)
Page 71: ME150P ELecture 1 (04 January 2011)

Cooling Load Calculations

By: Bautista, Norman George V.

Page 72: ME150P ELecture 1 (04 January 2011)

Cooling Load Results from any one single source of heat. Summation of the heat which evolves from

different sources.

Page 73: ME150P ELecture 1 (04 January 2011)

Common Sources of Heat

Heat that leaks from the outside space. Heat that enters the space by radiation. Heat that enters the space through doors

and windows. Heat given of by a warm product. Heat given by people. Heat given by equipments.

Page 74: ME150P ELecture 1 (04 January 2011)

Refrigerated Load In cases where the refrigerated load was

calculated on a 24 hour basis the load may be determined directly in KW.

Equation:

Where Q = required equipment capacity, KWRT= running time, hrs.qt = total cooling load, KW

Page 75: ME150P ELecture 1 (04 January 2011)

Wall Gain Load A measure of the heat flow rate by

conduction through walls of the refrigerated space from outside to the inside.

Also called as the “wall leakage load”

Page 76: ME150P ELecture 1 (04 January 2011)

Wall Gain Load Equation:

Where: Q = rate of heat transferred, W.A = outside surface area of wall, m2

U = overall coefficient of heat transmission (W/ m2 – K), “Table 10-2”

TD = temperature difference across the wall

))()(( TDUAQ

Page 77: ME150P ELecture 1 (04 January 2011)

Example 1 Determine the heat flow rate in watts

through a wall 3m by 6m. If the U factor for the wall is 0.37 W/ m2 – K and the temperature on one side of the wall is 4 °C while the temperature on the other side is 35 °C.

Page 78: ME150P ELecture 1 (04 January 2011)

Cont... Given: U = 0.37 W/ m2-K

T1 = 4 °C

T2 = 35 °C

Solution :Total Wall Area = 3m x 6m = 18 m2 TD = T2 - T1 = 35-4 = 31 K

Q = AUTD = 18 m2 (0.37 W/ m2-K)(31 K) Q = 206 W or 0.206 kW

Page 79: ME150P ELecture 1 (04 January 2011)

Thermal Conductivity, k Is the property of a material describing its

ability to conduct heat. W/(K·m) Can be found on Table 10-1. Equation:

Where: C = thermal conductance k = thermal conductivity

x = thickness

xkC /

Page 80: ME150P ELecture 1 (04 January 2011)

Example 2 Determine the thermal conductance for a

125 mm thickness of polyurathane.

Solution: From table 10-1, k = 0.125 W/m-KC = 0.025 / 0.125C = 0. 2 W/m2 – K

Page 81: ME150P ELecture 1 (04 January 2011)

Thermal Resistance Thermal resistance is a measure of a

material's ability to resist heat transfer. The more a material is able to block heat transfer through its surface, the greater its thermal resistance.

Equation:

kxkcUR //1/1/1

Page 82: ME150P ELecture 1 (04 January 2011)

Cont.. When a wall is constructed of several layers

of different materials,

Where: = convection coefficient of inside wall.

= convection coefficient of outside wall. 1/fi

Page 83: ME150P ELecture 1 (04 January 2011)

Example 3 Assuming a wind velocity of 3.35 m/s,

calculate the value of U for a wall constructed of 200 mm sand aggregate building blocks insulated with 75 mm of polyurethane and finished on the inside with 13 mm of cement plaster.

Page 84: ME150P ELecture 1 (04 January 2011)

Cont.. Solution: From table 10 – 1:200 mm sand aggregate block, C = 5.11Polyurethane, k = 0.025Cement plaster, k = 0.72fi = 9.37 fo = 22.7

Page 85: ME150P ELecture 1 (04 January 2011)

Cont..

1/U = 3.37U = 0.297 W/ m2 - K

37.9/172.0/013.0025.0/075.011.5/17.22/1/1 U

Page 86: ME150P ELecture 1 (04 January 2011)

Example 4 A walk-in cooler 5m x 7m x 3m high is

located in the southeast corner of a store building in an area where the outdoor design DB temperatures in summer and winter are 35 °C and -6 °C. The south and east walls of the cooler are adjacent to and a part of the south and east walls of the store building. The store has a 4 m ceiling so that there is a 1 m clearance between the top of the cooler and the ceiling of the store.

Page 87: ME150P ELecture 1 (04 January 2011)

The store is air conditioned and the temperature inside the store is maintained at approximately 26 °C. The inside design temperature for the cooler is 2 °C. The north and west (inside) walls, floor and ceiling are insulated with 75 mm of closed-cell (smooth surface) polystyrene, and the south and east walls are insulated with 100 mm of closed-cell polystyrene. Determine the wall gain load in kilowatts.

Page 88: ME150P ELecture 1 (04 January 2011)

7 m

5 m

Outdoor Design Temp, 35 °C

150 mm clay tile

150 mm polystyrene

Cooler 2 °C 3m ceiling

Partitions insulated with

75 mm polystyrene

Inside Temperature 26 °C

Ceiling 4m

Page 89: ME150P ELecture 1 (04 January 2011)

Solution

K (polystyrene) = 0.029 W/m-KU (north and west) = 0.346 W/m2 - K U (south and east) = 0.267 W/m2 – K

N, W, ceiling = (71)(0.346)(26-2) = 589.6 WS = (15)(0.267)(37-2) = 140.2 WE = (21)(0.267)(38-2) = 201.9 WFloor = (35)(0.346)(25-2) = 215 WTotal wall gain load = 1147 W or 1.147 kW

Page 90: ME150P ELecture 1 (04 January 2011)

Air Change Load A warm outside air enters the space to

replace the more dense cold air which is lost from the refrigerated space through the open door.

Equation:

Where: Q = air change load, kWm = mass of air entering, kgho = enthalpy of outside airhi = enthalpy of inside air

)( hihomQ

Page 91: ME150P ELecture 1 (04 January 2011)

Example 5 The rate of air infiltration into a refrigerated

space is 8 L/s. If the inside of the cooler is maintained at 2 °C and the outside dry bulb temperature and humidity are 30 °C and 50% respectively, determine the air change load in kilowatts.

Page 92: ME150P ELecture 1 (04 January 2011)

Cont... Solution: By interpolation in Table 10-6A, the enthalpy

change factor is 0.0598 kJ/L

Air change load = (8L/s)(0.0598 kJ/L)Air change load = 0.478 kW

Page 93: ME150P ELecture 1 (04 January 2011)

Product Load When a product enters a storage space at a

temperature above the temperature of the space, the product will give off heat to the space until it cools to the space temperature.

Page 94: ME150P ELecture 1 (04 January 2011)

Cont... Equation:

Where: Q = quantity of heat, kJ/kgm = mass of the product, kgCp = specific heat Above freezing Temp.TD = temperature change in the product

temperature, K

)(TDmCpQ

Page 95: ME150P ELecture 1 (04 January 2011)

Cont...

This equation is used to know the product load at a specific time.

Page 96: ME150P ELecture 1 (04 January 2011)

Example 6 Thirty-five hundred kilograms of fresh beef

enter a chilling cooler at 39°C and are chilled to 7°C each day. Compute the product load in kilojoules.

Solution: Q= mCp(TD) = (3500)(3.14)(39-7)

Q = 351,680 kJ

Page 97: ME150P ELecture 1 (04 January 2011)

Example 7 Determine the product load in kilowatts

assuming that the beef described in the previous example is chilled in 20h.

Solution:

Page 98: ME150P ELecture 1 (04 January 2011)

Cont...

Q = 4.88 kW

Page 99: ME150P ELecture 1 (04 January 2011)

Respiration Heat Fruits and vegetables are still alive after

harvesting and continue to undergo changes while in storage.

Respiration is a process during which oxygen from the air combines with the carbohydrates in the plant tissue and results in the release of carbon dioxide and heat.

Page 100: ME150P ELecture 1 (04 January 2011)

Cont... Equation:

Where: m = mass of product, kg rh = respiration rate, W/kg

Page 101: ME150P ELecture 1 (04 January 2011)

Example 8 A storage cooler 6m x 4m x 3.4m high is

insulated with 100 mm of glass fiberboard. Overall wall thickness is approximately 200 mm. The outside temperature is 30°C and usage is average. Twelve hundred and fifty kilograms of wet mixed vegetables are cooled, 25°C to the storage temperature of 5°C each day. Compute the required equipment capacity based on a 16-h/day.

Page 102: ME150P ELecture 1 (04 January 2011)

Solution

Outside surface area = 2(6x4)+2(6x3.4)+2(4x3.4) = 116 m2 Inside Volume = 5.6 x 3.6 x 3 m = 60.5 m3 Glass fiberboard, k = 0.036 W/m – K100 mm thick insulation, k = 0.035 W/m-kU = 0.31 W/m2 -K

Page 103: ME150P ELecture 1 (04 January 2011)

Cont... By interpolation, (table 10-7) Infiltration Rate = 8.13 L/s

Assume a 50 % RH, enthalpy change factor = 0.0536 kJ/LCp of wet mixed veg = 3.77 kJ/kg-Lrh = 0.097 W/kg

Page 104: ME150P ELecture 1 (04 January 2011)

Wall gain load = (116)(0.31)(30-5) = 899 W or 0.899 kW

Air change load = (8.13)(0.0536) = 0.43kW

Product cooling load =Respiration load = (1250)(0.097) = 121.5

W or 0.121 kWSum of heat loads = 1.729 kWSafety factor (10%) = 0.173 kWTotal cooling load = 1.902 kWRequired equipment capacity =

Page 105: ME150P ELecture 1 (04 January 2011)
Page 106: ME150P ELecture 1 (04 January 2011)
Page 107: ME150P ELecture 1 (04 January 2011)
Page 108: ME150P ELecture 1 (04 January 2011)