0 11.10.2012 Issued for Construction
A 13-07-2012 Issued for Approval
REV. DATE DESCRIPTION DSGN CHKD APPD
PROJECT :
TWO(2) x 500MW MONG DUONG 1 THERMAL POWER PLANT
EMPLOYER :
CONSULTANT :
CONTRACTOR :
DESIGNED BY DATE TITLE :
11.10.2012
EMERGENCY DIESEL GENERATOR SIZINGCALCULATION
CHECKED BY DATE
11.10.2012
APPROVED BY DATE PROJECT NUMBER DOCUMENT NUMBER REV.
11.10.2012 ADB/MD1-TPIP/EPC150911 MD1-0-E-182-06-00001 0
FOR CONSTRUCTION
-
8/12/2019 MD1-0-E-182-06-00001-0
2/6
TWO(2) X 500MW MONG DUONG 1 THERMAL POWER STATION
Emergency Diesel Generator Sizing Calculation Rev. 0
MD1-0-E-182-06-00001 i 11.10.2012
CONTENTS
1.0 GENERAL ...................................................................................................................... 12.0 REFERENCES ............................................................................................................... 13.0 DESIGN CRITERIA & FORMULA ............................................................................ 14.0 CALCULATION OF EDG SIZING ............................................................................. 35.0 CONCLUSION ............................................................................................................... 4
-
8/12/2019 MD1-0-E-182-06-00001-0
3/6
TWO(2) X 500MW MONG DUONG 1 THERMAL POWER STATION
Emergency Diesel Generator Sizing Calculation Rev. 0
MD1-0-E-182-06-00001 1 11-10-2012
1.0 GENERAL
This calculation is prepared to determine the capacity of Emergency Diesel Generator (EDG)
for safe shut down operation and provide power for essential supplies of Mong Duong 1 TPP
in Vietnam.
2.0 REFERENCES
1) Essential Electric Consumer List
2) IEEE Std. 399-1990 Recommended Practice for Industrial and Commercial PowerSystems Analysis.
3.0 DESIGN CRITERIA & FORMULA
3.1 General
To calculate the capacity of EDG, the following cases are considered:
Case I : Capacity during shut down of STGs Case II : Capacity for starting the largest motor while in islanded operation
3.2 Load Profile
3.2.1 Unit Loads
Load NameLoadType
Q'tyRatedPower[kW]
PowerFactor
Eff.Duty
Factor
Input
[kW] [kVA]
STG
Main Seal Oil Pump M 1 18.5 0.85 0.8 1 23.13 27.21Recirculation Seal Oil Pump M 1 7.5 0.85 0.8 1 9.38 11.03
Turning Gear M 1 44.7 0.8 0.92 1 48.59 60.73
Vapor Extractor Motor M 1 5.6 0.85 0.8 1 7.00 8.24
Gland Exhauster Motor M 1 11.2 0.85 0.8 1 14.00 16.47
Bearing Pump Motor M 1 150 0.85 1 1 150.00 176.47
Stator Cooling Pump M 1 45 0.9 0.9 1 50.00 55.56
BOILER
AH Support Bearing Oil Pump
MTRM 2 1.5 0.85 0.8 1 3.75 4.41
AH Guide Bearing Oil Pump
MTR
M 2 1.5 0.85 0.8 1 3.75 4.41
AH Aux. Drive Motor M 2 11.0 0.85 0.8 0 0.00 0.00
AH Sector Plate 1 Drive Motor M 2 0.75 0.85 0.8 0.5 0.94 1.10
AH Sector Plate 2 Drive Motor M 2 0.75 0.85 0.8 0.5 0.94 1.10
AH Sector Plate 3 Drive Motor M 2 0.75 0.85 0.8 0.5 0.94 1.10
PA Fan A Lube Oil Pump A
MTRM 2 3.7 0.85 0.8 1 9.25 10.88
PA Fan A Lube Oil Pump B
MTRM 2 3.7 0.85 0.8 0 0.00 0.00
PA Fan B Lube Oil Pump AMTR
M 2 3.7 0.85 0.8 1 9.25 10.88
PA Fan B Lube Oil Pump B
MTRM 2 3.7 0.85 0.8 0 0.00 0.00
SA Fan A Lube Oil Pump AMTR
M 2 2.2 0.85 0.8 1 5.50 6.47
-
8/12/2019 MD1-0-E-182-06-00001-0
4/6
TWO(2) X 500MW MONG DUONG 1 THERMAL POWER STATION
Emergency Diesel Generator Sizing Calculation Rev. 0
MD1-0-E-182-06-00001 2 11-10-2012
Load NameLoadType
Q'tyRatedPower[kW]
PowerFactor
Eff.Duty
Factor
Input
[kW] [kVA]
SA Fan A Lube Oil Pump BMTR
M 2 2.2 0.85 0.8 0 0.00 0.00
SA Fan B Lube Oil Pump A
MTR M 2 2.2 0.85 0.8 1 5.50 6.47SA Fan B Lube Oil Pump BMTR
M 2 2.2 0.85 0.8 0 0.00 0.00
BFP
Lube Oil Pump for Feed WaterPump
M 1 18 0.87 0.91 1 19.78 22.74
STACK
Ground Floor Lighting NM 1 0.8 1 1 1 0.80 0.80Platforms Lighting NM 1 1.2 1 1 1 1.20 1.20Aircraft Warning Lights NM 1 7.2 1 1 1 7.20 7.20PDP (internal) NM 1 2.4 1 1 1 2.40 2.40Ladders Lighting NM 1 1.2 1 1 1 1.20 1.20Emergency Lights NM 1 1.6 1 1 1 1.60 1.60PDP (internal) NM 1 2.4 1 1 1 2.40 2.40Stack Spare (20%) NM 1 3.4 1 1 1 3.36 3.36
I.D FAN
I.D Fan Lube Oil Pump Motor M 4 3.7 0.75 0.87 1 17.01 22.68
I.D Fan Fluid CouplingActuator
M 4 1.2 0.75 0.87 0.5 2.76 3.68
Sum of Motor Load 381.47 451.63
Sum of Non-Motor Load 20.16 20.16
Sum of All Load 401.63 471.79
Notes: 1. Load type: M (Motor load), NM (Non-motor load)2. Input power[kW]: Qty x Rated Power x Duty Factor / Efficiency3. Input power[kVA]: Qty x Rated Power x Duty Factor / Efficiency / Power Factor4. Duty factor: Continuous (1), Intermittent (0.5), Stand-by (0)
3.2.2 DC & UPS, BOP Loads
Load NameLoadType
Q'tyRatedPower[kW]
PowerFactor
Eff.Duty
Factor
Input
[kW] [kVA]
ELEC
DC UPS for Power Plant NM 1 250 1 1 1 250.00 250.00DC UPS for Cooling Water NM 1 20 1 1 1 20.00 20.00
WT
Potable Water Pump A M 1 22 0.85 0.8 1 23.91 28.81
Potable Water Pump B M 1 22 0.85 0.8 0 0 0
HVAC
Precision Air Conditioner NM 1 11 1 1 1 11.00 11.00
Air Cooled Water Chiller NM 1 116 1 1 1 116.00 116.00
Chilled Water Pump M 1 19 1 1 1 19.00 19.00
CHLORINATION
Absortion tower blower A M 1 11 0.85 0.89 1 12.36 14.54
Circulating pump_A M 1 5.5 0.88 0.89 1 6.25 7.10
-
8/12/2019 MD1-0-E-182-06-00001-0
5/6
TWO(2) X 500MW MONG DUONG 1 THERMAL POWER STATION
Emergency Diesel Generator Sizing Calculation Rev. 0
MD1-0-E-182-06-00001 3 11-10-2012
Sum of Motor Load 61.52 69.45
Sum of Non-Motor Load 397.00 397.00
Sum of All Load 458.52 466.45
Notes: 1. Load type: M (Motor load), NM (Non-motor load)
2. Input power: Qty x Rated Power x Duty Factor / Efficiency3. Input power[kVA]: Qty x Rated Power x Duty Factor / Efficiency / Power Factor4. Duty factor: Continuous (1), Intermittent (0.5), Stand-by (0)
4.0 CALCULATION OF EDG SIZING
4.1 Calculation for Case I
The capacity required for continuous operation during shutdown of STG Unit is calculated by
the following formula;
Where,
PG1 : Generator capacity [kVA]
pfG : Generator power factor (0.85)
P : Output of load [kW]
: Efficiency of load
a : Coefficienct considering load factor, demand factor, margin of capacity, etc
(Motor: 0.9, Non-motor: 1.0)
4.2 Calculation for Case II
The EDG shall also be capable of starting the largest motor (Bearing pump motor for STG
Unit 1, 150kW or 176.47kVA) as the remaining loads are running;
Where,
PG2 : Generator capacity [kVA]
0W : Summation of operating load [kVA] (938.25-176.47=761.77kVA)
Lcos : Power factor during starting of the largest motor (0.25)
K : Overload capacity of generator (1.1)
][82.95985.0
1)}16.417(1)99.442(9.0{
][1........3
3
2
2
1
11
kVA
kVApf
PPPPPGGn
n
][27.973
1.1
)25.029.1235(77.761
][]cos[ max0
2
kVA
kVAK
QWPG
LL
][29.123585.0
]][1507][
][7max kVA
kWkVA
pf
kWinputQ
L
L
-
8/12/2019 MD1-0-E-182-06-00001-0
6/6
TWO(2) X 500MW MONG DUONG 1 THERMAL POWER STATION
Emergency Diesel Generator Sizing Calculation Rev. 0
MD1-0-E-182-06-00001 4 11-10-2012
5.0 CONCLUSION
ITEM
DESCRIPTION
CALCULATED
CAPACITY
SELECTED
CAPACITY
CAPACITY WITH
20% MARGIN
Emergency Diesel
Generator
PG1: 959.82kVAPG2: 973.27kVA 1167.92kVA
PG2: 973.27kVA
Based on the calculated capacities and considering sufficient margin, the rated capacity of
both EDG Unit 1 & 2 will be selected as 1200kVA at 0.85PF.