Page 1: Manual Motor Starters Magnetic Contactors

Manual Motor StartersMagnetic Contactors

EEH530a

Page 2: Manual Motor Starters Magnetic Contactors

Advanced motor protection and control – FUJI DUO seriesFUJI offers a new motor control system for the international market, designed to IEC standards.

FUJI meets emerging needs with a new form of motor protection.

• Conformance to IEC, UL, CSA and other international standards

• Short-circuit protective coordination between protective devices and the equipment to be protected

• Application of international standards in safety features such as terminals with finger protection

• Use of recycled materials to help conserve theenvironment and save resources

The DUO series adds a new family of compact, high-performance combination starters to its IEC-compliant manual motor starters/BM3 series, magnetic contactors/SC series and thermal overload relays/TK series to form a complete line-up of motor control products.

Three major concepts enable FUJI's motor protection and control equipment to respond fully to market needs.

Response to the international market

Conformance to IEC standards

Safety and ecological consideration

Page 3: Manual Motor Starters Magnetic Contactors

New circuit breakers for motor use that provide optimal protection by integrating the functions of a molded case circuit breaker and thermal overload relay into a highly compact unit.

DUO SERIES

Manual motor starters (MMS)

Contactors and thermal overload relays

SC-M series SC-E series

The ability to configure combination starters for compact, reliable motor protection by combining a manual motor starter and a magnetic contactor.

Combination starters

Magnetic contactors and thermal overload relays featuring terminals with finger protection for 400V AC, 4 to 75kW.

Compact magnetic contactors and ideal thermal overload relays for small capacity motor control for 400V AC, 2.2 to 4kW.

Rated current: 0.16 to 32A, 10 to 63ABreaking capacity: 400/415V

lcu 25, 50, 100kAWidth: 45mm, 55mm

Rated capacity: AC-3 2.2 to 4kW, 400V ACWidth: 45mm

Rated capacity: AC-3 4 to 75kW, 400V ACWidth: 43, 54, 67mm (4 to 40kW)

88, 100, 115mm (55 to 75kW)

BM3 series

Page 4: Manual Motor Starters Magnetic Contactors

Innovative technology has integrated the functions of an MCCB and thermal overload relay.

Manual motor starters/BM3 series

Conforming to international standards and combining compactness with high breaking performance, this versatile series features leading-edge motor protection.

Functions

Performance

Circuit breaker functions

• Short-circuit protection• Overcurrent protection• Line protection

Thermal overload relay functions

• Overload protection• Phase-loss protection• Rated current adjustment• Ambient temperature compensation

Manual motor starter advantages

Compactness

High breaking capacity

Short-circuit protective coordination

Reduction in wiring work

Standards

Ecological design

Mounting space: MCCB + Thermal overload relay: 100%MMS: 43% (57% reduction)

Standard breaking capacity: 25, 50, 100kA 400V ACHigh breaking capacity: 50, 100kA 400V AC

IEC 60947-4-1 Type1, 2

MCCB + Contactor + Thermal overload relay: 100%MMS + Contactor: 50% (50% reduction)

• IEC 60947-1, 60947-2, 60947-4-1, UL 508, CSA C22.2 No.14

• Recyclable thermoplastic resin used in plastic parts• Indication of materials used• Cadmium-free contacts

0 25 50 100kABreaking capacity

100kABreaking capacity

100kABreaking capacity

100kABreaking capacity

32A13A10A

0.1A

Ratedcurrent

Ratedcurrent

Ratedcurrent

Ratedcurrent

BM3RSBBM3RSBK

25kA50kA

100kA

400V AC

0 25 50

32A

13A

0.1ABM3RHBBM3RHBK

50kA

100kA

400V AC

63A

13A

6A

50kA

100kA

0 25 50

0 25 50

63A13A10A

6ABM3VSBBM3VSBK

6 to 63A 55mm wide 25kA50kA

100kA

400V AC

BM3VHBBM3VHBK

400V AC

High breaking capacity achieved with industry-leading technology.

Molded case circuit breaker and thermal overload relay functions integrated into a highly compact unit.

Standard

High-performance

Standard

High-performance

0.1 to 32A 45mm wide

2

Page 5: Manual Motor Starters Magnetic Contactors

Accessories

A wide variety of accessories enables a flexible response to changes in specifications. Snap-on fittings speed up mounting.

Internal deviceFront mounting MMS

45mm

55mm

Enclosures

Emergency-stop handle

Standard operation handle

Auxiliary contact blocks

Undervoltage trip device with early make contacts

Undervoltage trip device with early make contacts

Undervoltagetrip device

Shunt trip device

Aux. contact block

Auxiliary contact blocks

Auxiliary/alarm contact blocks

Short-circuit alarm contact block

Short-circuit alarm contact block

9mm external deviceLeft-side mounting

9mm external deviceRight-side mounting

18mm external deviceRight-side mounting

Alarm contact block

3

Page 6: Manual Motor Starters Magnetic Contactors

Leading the industry with global designs and high levels of reliability, safety and utility.

Magnetic contactors and thermal overload relays

A full line-up consisting of the mini-contactor SC-M series for 400V AC, 2.2 to 4kW use and the SC-E series for 400V AC, 4 to 75kW use.

Dimensions

Performance

20kW0kWMotor capacity [kW](AC-3, 400V) 40kW

4kW

11kW

22kW

40kW

55kW

60kW

75kW

60kW 80kW

Full line-up 2.2 to 75kW at 400V AC

Ideal widths for combination with manual motor starters, and finger protection construction for improved operating safety.

SC-M series SC-E series

SC-M01, M02 SC-E02 to E05 SC-E1 to E2S SC-E3, E4

45mm

54mm

67mm

43mm

SC-E7

SC-E6

SC-E5

SC-E3, E4

SC-E1 to E2S

SC-E02 to E05

SC-M01, M02

Rating: Conforms to IEC standard.

4

Page 7: Manual Motor Starters Magnetic Contactors

Contactors SC-M series Thermal overload relays TK-M series

Contactors SC-E series Thermal overload relays TK-E series

Accessories

A full range of accessories with the emphasis on utility.

Auxiliary contact block(1NO) Thermal overload relay Auxiliary contact block

ContactorSC-M

Auxiliary contact blocksCoil surgesuppression unit

Dial cover

Auxiliary contact block

Contactor SC-E

Trip indicator

Auxiliary contact block

Base unitfor separate mounting

Main circuit surge suppression unit

Main circuitsurge suppression unit

Thermal overload relay Reset release button

Front mounting

Side mounting

Top mounting

Side mounting

Front mounting

Side mounting

Coil surge suppression unitAuxiliary contact blocks Solid state time-delay unit

5

Page 8: Manual Motor Starters Magnetic Contactors

MMSBM3R series

Contactor

Link module Link module

Baseplate

ContactorSC-M series

MMS

ContactorSC-E series

MMSBM3V series

Conforming to IEC standards, complete motor protection with motor control circuits

Combination of manual motor starters and magnetic contactors

A line-up that aims to set a new world standard for compactness, high performance, and utility in combination starters.

Combination of manual motor starters and contactors

Example of combination starters

Combination starters can be easily configured with a manual motor starter, magnetic contactor and other parts.

BM3RSB-010

SC-M02

BM3RHB-025

SC-E05

BM3RHB-032

SC-E1

BM3VHB-050

SC-E2S

400V AC AC-3

4kW 11kW 15kW 22kW

6

Page 9: Manual Motor Starters Magnetic Contactors

52% reduction

1.1kW

4kW

11kW

22kW

7.5kW

18.5kW

Space-saving, reliable motor protection achieved by combining a manual motor starter and magnetic contactor.

Functions

Combination starters can be used to satisfy Types 1 and 2 short-circuit protective coordination as stipulated in IEC standards.

(IEC 60947-4-1 7.2.5)

(Iq=50kA at 400V AC)

Performance

Contactor

Thermal overload relay• Overload protection• Phase-loss protection

Motor

Motor

MCCBMCCB

Combination starter(MMS+Contactor)• Short-circuit protection• Overload protection• Phase-loss protectionMCCB

• Short-circuit protection

Wiring work

+

Mounting space

90% reduction

5kW0kW 10kW 15kW 20kW 25kW

TYPE-1

TYPE 1

TYPE 2

BM3RSB-010SC-M02

TYPE-2

BM3RSB-004SC-M01

TYPE-1

BM3RHB-025SC-E05

TYPE-2

BM3RSB-020SC-E05

TYPE-1

BM3VHB-050SC-E2S

TYPE-2

BM3VHB-040SC-E2

Conventional system New system using an MMS

For control panel

For control panel

7

Page 10: Manual Motor Starters Magnetic Contactors

Example of 8-motor control circuit

Features

Contactor

Thermal overload relay

Used to connect the wire for the power supply circuit.

52% reduction

Combination starters

Application example

Busbar system

Combining modular equipment enables compact control panel configurations. Combination starters and busbar systems help to downsize equipment.

Various wiring materials available to reduce both wiring and wiring steps.

Three-phase feed-in terminal

Connects MMS and contactor electrically and mechanically.

Link module

Combination starter

Busbar cover

Mounting space

Prevents contact with charged parts when part of the busbar is not connected to a manual motor starter.

Busbar

Simple power supply for 2 to 5 manual motor starters without the need for wiring.

MCCB

MCCB

• Reduction in equipment The use of a manual motor starter eliminates the need for a thermal overload relay.• More efficient wiring The busbar system and connecting modules make it possible to reduce complicated wiring work.• Protection against exposure to charged parts A busbar system, busbar cover, and terminals with finger protection prevent exposure to charged parts.• Space-saving design The circuit example shown above enables a 52% reduction in mounting area.

Conventional control panel New control panel

8

Page 11: Manual Motor Starters Magnetic Contactors

CONTENTS

Manual Motor StartersGeneral information ..................................................................... 10

Quick reference guide ................................................................. 12

Adjustable thermal-magnetic trip type ......................................... 14

Instantaneous trip type ................................................................ 16

Optional accessories ................................................................... 19

Dimensions ................................................................................. 25

Busbar system ............................................................................ 29

Enclosures .................................................................................. 32

ContactorsGeneral information ..................................................................... 34

Quick reference guide ................................................................. 36

SC-M series ................................................................................ 38

Optional accessories ................................................................... 41

Dimensions ................................................................................. 42

Thermal overload relays .............................................................. 44

SC-E series ................................................................................. 47

Optional accessories ................................................................... 51

Dimensions ................................................................................. 52

Thermal overload relays .............................................................. 57

Combination StartersDescription and protective coordination ...................................... 63

Optional accessories ................................................................... 66

Dimensions ................................................................................. 68

Page

Page 12: Manual Motor Starters Magnetic Contactors

10

Manual Motor StartersGeneral information

• Eight types available in two different frame sizes-32AF forthe 45mm width and 63AF for the 55mm width

• A wide motor capacity range up to 30kW (400/415V AC,63A)

• Both rocker and rotary handle operators• ON/OFF and trip state indication for all frames• Adjustable thermal-magnetic trip types

32AF: BM3RSB and BM3RHB63AF: BM3VSB and BM3VHB

• Instantaneous trip types32AF: BM3RSBK and BM3RHBK63AF: BM3VSBK and BM3VHBK

• Max. breaking capacity of 100kA (400/415V AC)• Common accessories to reduce inventory• International standards/approvals: IEC, CULUS

BM3VSB and BM3VSBKRated current: 10 to 63ARated insulation voltage: 1000VOperation handle: Rotary handleBreaking capacity Icu at 400/415V:• 100kA up to 10A• 50kA up to 13A• 25kA up to 63A

BM3VHB and BM3VHBKRated current: 10 to 63ARated insulation voltage: 1000VOperation handle: Rotary handleBreaking capacity Icu at 400/415V:• 100kA up to 13A• 50kA up to 63A

Compact starters with a 55m width for rated currents to 63A andmotor capacities to 30kW at 415V AC.

BM3RHB and BM3RHBKRated current: 0.16 to 32ARated insulation voltage: 690VOperation handle: Rotary handleBreaking capacity Icu at 400/415V:• 100kA up to 13A• 50kA up to 32A

BM3RSB and BM3RSBKRated current: 0.16 to 32ARated insulation voltage: 690VOperation handle: Rocker leverBreaking capacity Icu at 400/415V:• 100kA up to 10A• 50kA up to 13A• 25kA up to 32A

KK01-317

AF01-42

AF01-47

AF01-43

Manual motor starters for branch circuit protection

The MMS provides reliable protection for overloading andshort-circuiting in motor branch circuits.

MCCB20A

Motor 2Motor 1

Contactor+

MCCB

MCCB

Contactor+

Motor 1 Motor 2

Thermal overloadrelay

Thermal overloadrelay

MCCB

Contactors

Manual motorstarters

Motors

Page 13: Manual Motor Starters Magnetic Contactors

11

Manual Motor StartersGeneral information

Selecting the appropriate modelThe procedure for selecting the appropriate model is given below.

Typical problem in the conventional system Solution by using MMS system

Short-circuit breaking protectionWhen numerous small and medium motor loads exist in a circuitrequiring high breaking capacity, there is no high-breaking capacitycircuit breaker with a small rated current for short-circuit protection.

Back-up breaking systemWhen a back-up MCCB is installed upstream to slove the probremdescribed in "short-circuit breaking protection" above, a short in oneof the load circuits also trips the upstream breaker and stops theother operating load circuits.

Overload protectionMotor protection breakers cannot be adjusted to match the ratedcurrent of the motor being protected.

Control panel sizeConsiderable space is required to install a back-up circuit breaker ora combination starter consisting of a circuit breaker and a thermaloverload relay. As a result, the panel size has to be increased.

The MMS can be used in 100kA short-circuit current circuitsfor three-phase, 240V motors with rated capacity up to 15kW,and in 50kA short-circuit current circuits for three-phase,415V motors with rated capacity up to 30kW.

Despite their compact size, the 32AF and 63AF MMS providehigh-performance short-circuit current breaking. Theyeliminate the need for an upstream circuit breaker for back-upuse.

Equipped with a wide-range current adjustment dial (withmaximum/minimum ratio of 1.4 to 1.6), the MMS easily adjuststo match the rated current of the motor, for optimumprotection.

The compact size of the MMS, including thermal overloadrelay functions, enables a smaller installation area with lesswiring space, for a reduction in panel size.

1 Confirm the motor's full load current.

3 Select the rated current for the MMS.

5 Confirm the short-circuit current of the circuit.

4 Select the branch circuit cable. Confirm the control panel specifications.

2 Three-phase load 2 Single-phase load

6 Select the operating characteristics.

For application to a single-phase circuit, connect the 3-pole in series.

Same characteristics as a standard thermal overload relay desired

Long-time operating type or quick operatingtype thermal overload relay desired

Adjustable thermal magnetic trip type

Standard breaking capacityBM3RSBBM3VSB

High breaking capacityBM3RHBBM3VHB

Instantaneous trip type

Standard breaking capacityBM3RSBKBM3VSBK

High breaking capacityBM3RHBKBM3VHBK

Note: Use in combination with a magnetic contactor when frequent switching is desired.

Page 14: Manual Motor Starters Magnetic Contactors

12

Manual Motor Starters

32AF types and ratings

Note: * Adjustable thermal-magnetic tirp type only Available – Not available

Quick reference guide

Replace the markin the type numberby current rangecodes.

Standard breaking capacity High breaking capacityAdjustable thermal-magnetic trip type BM3RSB- BM3RHB- Instantaneous trip type BM3RSBK- BM3RHBK-

KK01-317 AF01-42

Number of poles 3 3Handle type Rocker RotaryRated current Ie (A) 0.16 to 32Rated operational voltage Ue (V) 200 to 690Rated frequency (Hz) 50/60Rated insulation voltage Ui (V) 690Rated impulse withstand voltage Uimp (kV) 6Utilization IEC 60947-2 Circuit breaker Cat. Acategory IEC 60947-4-1 Motor starter AC-3Trip class IEC 60947-4-1 * 10Instantaneous trip characteristic 13 le max.Power loss (total of 3-pole) 7W: In=0.16 to 25A 8.5W: In=32AMechanical durability (operations) 100,000: In=0.16 to 25A 70,000: In=32AElectrical durability (operations) 100,000: In=0.16 to 25A 70,000: In=32AMax. operations per hour (motor start-up) 25Phase-loss protection ProvidedTrip indicator ProvidedTest trip function ProvidedRated breaking Adjustable current range 240V 415V 460V 500V 690V 240V 415V 460V 500V 690Vcapacity (kA) Code Ie: Min.–Max. 230V 400V 440V 600V 230V 400V 440V 600V

IEC 60947-2(A) Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics

P16 0.1–0.16 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100P25 0.16–0.25 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100P40 0.25–0.4 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100P63 0.4–0.63 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100001 0.63–1. 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 1001P6 1–1.6 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 1002P5 1.6–2.5 100 100 100 100 100 100 100 100 3 2 100 100 100 100 100 100 100 100 8 6004 2.5–4. 100 100 100 100 100 100 100 100 3 2 100 100 100 100 100 100 100 100 8 66P3 4–6.3 100 100 100 100 50 38 50 38 3 2 100 100 100 100 100 100 100 100 6 5010 6.3–10 . 100 100 100 100 15 11 10 8 3 2 100 100 100 100 50 38 50 38 6 5013 9–13 . 100 100 50 38 10 8 6 5 3 2 100 100 100 100 50 38 42 32 6 5016 11–16 . 100 100 25 19 10 8 6 5 3 2 100 100 50 38 35 27 10 8 4 3020 14–20 . 50 38 25 19 10 8 6 5 3 2 100 100 50 38 35 27 10 8 4 3025 19–25 . 50 38 25 19 10 8 6 5 3 2 100 100 50 38 35 27 10 8 4 3032 24–32 . 50 38 25 19 10 8 6 5 3 2 100 100 50 38 35 27 10 8 4 3040 28–40 . – – – – – – – – – –050 35–50 . – – – – – – – – – –063 45–63 . – – – – – – – – – –

Dimentions (mm) W H D 45 90 66 45 90 79Mass (g) 350 370Optional Auxiliary contact blockaccessory Alarm contact block

Auxiliary and alarm contact blockShort-circuit alarm contact blockShunt trip deviceUndervoltage trip deviceExternal operating handle –

Standard IEC 60947-1, 60947-2, 60947-4-1, UL 508, CSA C22.2 No.14, TÜV

Page 15: Manual Motor Starters Magnetic Contactors

13

Manual Motor Starters

63AF types and ratings

Quick reference guide

Replace the markin the type numberby current rangecodes.

Note: * Adjustable thermal-magnetic tirp type only Available – Not available

Standard breaking capacity High breaking capacityAdjustable thermal-magnetic trip type BM3VSB- BM3VHB- Instantaneous trip type BM3VSBK- BM3VHBK-

AF01-47 AF01-43

Number of poles 3 3Handle type Rotary RotaryRated current Ie (A) 10 to 63Rated operational voltage Ue (V) 200 to 690Rated frequency (Hz) 50/60Rated insulation voltage Ui (V) 1000Rated impulse withstand voltage Uimp (kV) 8Utilization IEC 60947-2 Circuit breaker Cat. Acategory IEC 60947-4-1 Motor starter AC-3Trip class IEC 60947-4-1 * 10Instantaneous trip characteristic 13 le max.Power loss (total of 3-pole ) 11W: In=10 to 32A 15W: In=40 to 50A 17W: In=63AMechanical durability (operations) 50,000Electrical durability (operations) 25,000Max. operations per hour (motor start-up) 25Phase-loss protection ProvidedTrip indicator ProvidedTest trip function ProvidedRated breaking Adjustable current range 240V 415V 460V 500V 690V 240V 415V 460V 500V 690Vcapacity (kA) Code Ie: Min.–Max. 230V 400V 440V 600V 230V 400V 440V 600V

IEC 60947-2(A) Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics Icu Ics

P16 0.1–0.16 – – – – – – – – – –P25 0.16–0.25 – – – – – – – – – –P40 0.25–0.4 – – – – – – – – – –P63 0.4–0.63 – – – – – – – – – –001 0.63–1. – – – – – – – – – –1P6 1–1.6 – – – – – – – – – –2P5 1.6–2.5 – – – – – – – – – –004 2.5–4. – – – – – – – – – –6P3 4–6.3 – – – – – – – – – –010 6.3–10 . 100 100 100 100 15 12 10 8 4 3 100 100 100 100 50 38 50 38 6 5013 9–13 . 100 100 50 38 10 8 6 5 4 3 100 100 100 100 50 38 42 32 6 5016 11–16 . 100 100 25 19 10 8 6 5 4 3 100 100 50 38 50 38 12 9 5 4020 14–20 . 50 38 25 19 10 8 6 5 4 3 100 100 50 38 50 38 12 9 5 4025 19–25 . 50 38 25 19 10 8 6 5 4 3 100 100 50 38 35 27 12 9 5 4032 24–32 . 50 38 25 19 10 8 6 5 4 3 100 100 50 38 35 27 10 8 5 4040 28–40 . 50 38 25 19 10 8 6 5 4 3 100 100 50 38 35 27 10 8 5 4050 35–50 . 50 38 25 19 10 8 6 5 4 3 100 100 50 38 35 27 10 8 5 4063 45–63 . 50 38 25 19 10 8 6 5 4 3 100 100 50 38 35 27 10 8 5 4

Dimentions (mm) W H D 55 110 96Mass (g) 780Optional Auxiliary contact blockaccessory Alarm contact block

Auxiliary and alarm contact blockShort-circuit alarm contact blockShunt trip deviceUndervoltage trip deviceExternal operating handle

Standard IEC 60947-1, 60947-2, 60947-4-1, UL 508, CSA C22.2 No.14, TÜV

Page 16: Manual Motor Starters Magnetic Contactors

14

Manual Motor Starters

Max. motor capacity and full-load current Rated Thermal Instantaneous Rated breaking Type3-phase *1 current *2 current trip current capacity Icu (kA)200-240V AC 380-440V AC In (A) setting range (A)(kW) (A) (kW) (A) Ie (A) 240V AC 415V AC

– – 0.02 0.1 0.16 0.1–0.16 2.1 100 100 BM3RSB-P160.03 0.24 0.06 0.21 0.25 0.16–0.25 3.3 100 100 BM3RSB-P250.06 0.37 0.1 0.34 0.4 0.25–0.4 5.2 100 100 BM3RSB-P400.06 0.37 0.12 0.41 0.63 0.4–0.63 8.2 100 100 BM3RSB-P630.1 0.68 0.2 0.7 1 0.63–1. 13 100 100 BM3RSB-0010.2 1.3 0.4 1.2 1.6 1–1.6 20.8 100 100 BM3RSB-1P60.4 2.3 0.75 1.8 2.5 1.6–2.5 32.5 100 100 BM3RSB-2P50.75 3.6 1.5 3.1 4 2.5–4. 52 100 100 BM3RSB-0041.5 6.1 2.2 4.6 6.3 4–6.3 81.9 100 100 BM3RSB-6P32.2 9.2 3.7 7.5 10 6.3–10 . 130 100 100 BM3RSB-0102.2 9.2 5.5 11 13 9–13 . 169 100 50 BM3RSB-0133.7 15 7.5 15 16 11–16 . 208 100 25 BM3RSB-0163.7 15 7.5 15 20 14–20 . 260 50 25 BM3RSB-0205.5 22.5 11 21 25 19–25 . 325 50 25 BM3RSB-0257.5 29 15 28 32 24–32 . 416 50 25 BM3RSB-032

Types and ratings

• 32AF standard breaking capacity, rocker handle types

Adjustable thermal-magnetic trip types Features

• A wide rated operational current range of up to 32A for the45mm wide and 63A for the 55mm wide starters.

• ON/OFF and trip indications ensure instant statusrecognition.

• Suitable for 3-phase motors up to 30kW at 400V AC, AC-3.• Accessories like auxiliary contact blocks, shunt trip devices,

and undervoltage trip devices have been standardized forthe 45mm and 55mm wide frame sizes of the BM3R andBM3V.

• Enclosures and external operating handles are available asoptional accessories.

StandardsIEC 60947-1, 60947-2, 60947-4-1, UL 508,CSA C22.2 No.14, TÜV

Notes: *1 Motor full-load currents are based on FUJI’s standard type totally-enclosed induction motors.*2 Max. thermal current setting value

BM3VHB

AF01-43

BM3RHB

AF01-42

BM3RSB

KK01-317

Max. motor capacity and full-load current Rated Thermal Instantaneous Rated breaking Type3-phase *1 current *2 current trip current capacity Icu (kA)200-240V AC 380-440V AC In (A) setting range (A)(kW) (A) (kW) (A) Ie (A) 240V AC 415V AC

– – 0.02 0.1 0.16 0.1–0.16 2.1 100 100 BM3RHB-P160.03 0.24 0.06 0.21 0.25 0.16–0.25 3.3 100 100 BM3RHB-P250.06 0.37 0.1 0.34 0.4 0.25–0.4 5.2 100 100 BM3RHB-P400.06 0.37 0.12 0.41 0.63 0.4–0.63 8.2 100 100 BM3RHB-P630.1 0.68 0.2 0.7 1 0.63–1. 13 100 100 BM3RHB-0010.2 1.3 0.4 1.2 1.6 1–1.6 20.8 100 100 BM3RHB-1P60.4 2.3 0.75 1.8 2.5 1.6–2.5 32.5 100 100 BM3RHB-2P50.75 3.6 1.5 3.1 4 2.5–4. 52 100 100 BM3RHB-0041.5 6.1 2.2 4.6 6.3 4–6.3 81.9 100 100 BM3RHB-6P32.2 9.2 3.7 7.5 10 6.3–10 . 130 100 100 BM3RHB-0102.2 9.2 5.5 11 13 9–13 . 169 100 100 BM3RHB-0133.7 15 7.5 15 16 11–16 . 208 100 50 BM3RHB-0163.7 15 7.5 15 20 14–20 . 260 100 50 BM3RHB-0205.5 22.5 11 21 25 19–25 . 325 100 50 BM3RHB-0257.5 29 15 28 32 24–32 . 416 100 50 BM3RHB-032

• 32AF high breaking capacity, rotary handle types

Page 17: Manual Motor Starters Magnetic Contactors

15

Manual Motor Starters

Max. motor capacity and full-load current Rated Thermal Instantaneous Rated breaking Type3-phase *1 current *2 current trip current capacity Icu (kA)200-240V AC 380-440V AC In (A) setting range (A)(kW) (A) (kW) (A) Ie (A) 240V AC 415V AC

2.2 9.2 3.7 7.5 10 6.3–10 130 100 100 BM3VHB-0102.2 9.2 5.5 11 13 9–13 169 100 100 BM3VHB-0133.7 15 7.5 15 16 11–16 208 100 50 BM3VHB-0163.7 15 7.5 15 20 14–20 260 100 50 BM3VHB-0205.5 22.5 11 21 25 19–25 325 100 50 BM3VHB-0257.5 29 15 28 32 24–32 416 100 50 BM3VHB-0327.5 29 18.5 34 40 28–40 520 100 50 BM3VHB-040

11 42 22 39 50 35–50 650 100 50 BM3VHB-05015 55 30 54 63 45–63 819 100 50 BM3VHB-063

Max. motor capacity and full-load current Rated Thermal Instantaneous Rated breaking Type3-phase *1 current *2 current trip current capacity Icu (kA)200-240V AC 380-440V AC In (A) setting range (A)(kW) (A) (kW) (A) Ie (A) 240V AC 415V AC

2.2 9.2 3.7 7.5 10 6.3–10 130 100 100 BM3VSB-0102.2 9.2 5.5 11 13 9–13 169 100 50 BM3VSB-0133.7 15 7.5 15 16 11–16 208 100 25 BM3VSB-0163.7 15 7.5 15 20 14–20 260 50 25 BM3VSB-0205.5 22.5 11 21 25 19–25 325 50 25 BM3VSB-0257.5 29 15 28 32 24–32 416 50 25 BM3VSB-0327.5 29 18.5 34 40 28–40 520 50 25 BM3VSB-040

11 42 22 39 50 35–50 650 50 25 BM3VSB-05015 55 30 54 63 45–63 819 50 25 BM3VSB-063

• 63AF standard breaking capacity, rotary handle types

• 63AF high breaking capacity, rotary handle types

Notes: *1 Motor full-load currents are based on FUJI’s standard type totally-enclosed induction motors.*2 Max. thermal current setting value

BM3VHB - 063

Basic type

Frame size

Rated current

Operating characteristicR: 32AF 45mm wideV: 63AF 55mm wide

B: Adjustable thermal-magnetic trip

Breaking capacityS: Standard breaking capacityH: High breaking capacity

Ordering informationSpecify the following:1. Type number2. Accessories if required

Type number nomenclature

Page 18: Manual Motor Starters Magnetic Contactors

16

Manual Motor Starters

Max. motor capacity and full-load current Rated current Instantaneous trip Rated breaking Type3-phase * In (A) current (A) capacity Icu (kA)200-240V AC 380-440V AC(kW) (A) (kW) (A) 240V AC 415V AC

– – 0.02 0.1 0.16 2.1 100 100 BM3RSBK-P160.03 0.24 0.06 0.21 0.25 3.3 100 100 BM3RSBK-P250.06 0.37 0.1 0.34 0.4 5.2 100 100 BM3RSBK-P400.06 0.37 0.12 0.41 0.63 8.2 100 100 BM3RSBK-P630.1 0.68 0.2 0.7 1 13 100 100 BM3RSBK-0010.2 1.3 0.4 1.2 1.6 20.8 100 100 BM3RSBK-1P60.4 2.3 0.75 1.8 2.5 32.5 100 100 BM3RSBK-2P50.75 3.6 1.5 3.1 4 52 100 100 BM3RSBK-0041.5 6.1 2.2 4.6 6.3 81.9 100 100 BM3RSBK-6P32.2 9.2 3.7 7.5 10 130 100 100 BM3RSBK-0102.2 9.2 5.5 11 13 169 100 50 BM3RSBK-0133.7 15 7.5 15 16 208 100 25 BM3RSBK-0163.7 15 7.5 15 20 260 50 25 BM3RSBK-0205.5 22.5 11 21 25 325 50 25 BM3RSBK-0257.5 29 15 28 32 416 50 25 BM3RSBK-032

Instantaneous trip types Features

• Instantaneous trip type for short-circuit or overcurrentprotection of three-phase motors up to 63A (240V AC, 15kW,or 415V AC, 30kW).

• No overload protection function. Allows motor circuitprotection in combination with appropriate thermal overloadrelay depending on the thermal characteristics of the motorwinding and the start-up time of the motor.

• Two modules, 45mm or 55mm wide, cover current ratingsfrom 0.1 to 63A.BM3RSBK, RHBK: 45mm width, rated current of 0.1 to 32ABM3VSBK, VHBK: 55mm width, rated current of 6.3 to 63A

• Rotary handle operator and rocker handle operator for 32AF only.• Versatile accessories

Internal and external auxiliary contact blocks, alarm contact blockShort circuit alarm contact blockShunt-trip deviceUndervoltage trip device

BM3VHBK

AF01-45

BM3RHBK

AF01-46

• 32AF high breaking capacity, rotary handle type

StandardsIEC 60947-1, 60947-2, 60947-4-1, UL 508CSA C22.2 No.14, TÜV

Notes: * Motor full-load currents are based on FUJI’s standard type totally-enclosed induction motors.• Select appropriate thermal overload relay for starter.

Types and ratings

• 32AF standard breaking capacity, rocker handle types

Max. motor capacity and full-load current Rated current Instantaneous trip Rated breaking Type3-phase * In (A) current (A) capacity Icu (kA)200-240V AC 380-440V AC(kW) (A) (kW) (A) 240V AC 415V AC

– – 0.02 0.1 0.16 2.1 100 100 BM3RHBK-P160.03 0.24 0.06 0.21 0.25 3.3 100 100 BM3RHBK-P250.06 0.37 0.1 0.34 0.4 5.2 100 100 BM3RHBK-P400.06 0.37 0.12 0.41 0.63 8.2 100 100 BM3RHBK-P630.1 0.68 0.2 0.7 1 13 100 100 BM3RHBK-0010.2 1.3 0.4 1.2 1.6 20.8 100 100 BM3RHBK-1P60.4 2.3 0.75 1.8 2.5 32.5 100 100 BM3RHBK-2P50.75 3.6 1.5 3.1 4 52 100 100 BM3RHBK-0041.5 6.1 2.2 4.6 6.3 81.9 100 100 BM3RHBK-6P32.2 9.2 3.7 7.5 10 130 100 100 BM3RHBK-0102.2 9.2 5.5 11 13 169 100 100 BM3RHBK-0133.7 15 7.5 15 16 208 100 50 BM3RHBK-0163.7 15 7.5 15 20 260 100 50 BM3RHBK-0205.5 22.5 11 21 25 325 100 50 BM3RHBK-0257.5 29 15 28 32 416 100 50 BM3RHBK-032

Page 19: Manual Motor Starters Magnetic Contactors

17

Manual Motor Starters

Max. motor capacity and full-load current Rated current Instantaneous trip Rated breaking Type3-phase *1 In (A) current (A) capacity Icu (kA)200-240V AC 380-440V AC(kW) (A) (kW) (A) 240V AC 415V AC

2.2 9.2 3.7 7.5 10 130 100 100 BM3VHBK-0102.2 9.2 5.5 11 13 169 100 100 BM3VHBK-0133.7 15 7.5 15 16 208 100 50 BM3VHBK-0163.7 15 7.5 15 20 260 100 50 BM3VHBK-0205.5 22.5 11 21 25 325 100 50 BM3VHBK-0257.5 29 15 28 32 416 100 50 BM3VHBK-0327.5 29 18.5 34 40 520 100 50 BM3VHBK-040

11 42 22 39 50 650 100 50 BM3VHBK-05015 55 30 54 63 819 100 50 BM3VHBK-063

• 63AF high breaking capacity, rotary handle type

Notes: *1 Motor full-load currents are based on FUJI’s standard type totally-enclosed induction motors.• Select appropriate thermal overload relay for starter.

BM3VHBK - 063

Type number nomenclature

• 63AF standard breaking capacity, rotary handle types

Basic type

Frame size

Rated current

Operating characteristicR: 32AF 45mm wideV: 63AF 55mm wide

BK: Instantaneous trip

Breaking capacityS: Standard breaking capacityH: High breaking capacity

Ordering informationSpecify the following:1. Type number2. Accessories if required

Max. motor capacity and full-load current Rated current Instantaneous trip Rated breaking Type3-phase *1 In (A) current (A) capacity Icu (kA)200-240V AC 380-440V AC(kW) (A) (kW) (A) 240V AC 415V AC

2.2 9.2 3.7 7.5 10 130 100 100 BM3VSBK-0102.2 9.2 5.5 11 13 169 100 50 BM3VSBK-0133.7 15 7.5 15 16 208 100 25 BM3VSBK-0163.7 15 7.5 15 20 260 50 25 BM3VSBK-0205.5 22.5 11 21 25 325 50 25 BM3VSBK-0257.5 29 15 28 32 416 50 25 BM3VSBK-0327.5 29 18.5 34 40 520 50 25 BM3VSBK-040

11 42 22 39 50 650 50 25 BM3VSBK-05015 55 30 54 63 819 50 25 BM3VSBK-063

Page 20: Manual Motor Starters Magnetic Contactors

18

Manual Motor Starters

1 10 100

Multiple of rated current (A)

Ope

ratin

g tim

e (s

)

0.001

0.01

0.1

1

10

100

1000

10000

Instantaneous trip1100 to 1560% ofrated current

1 10 100

Multiple of rated current (A)

Ope

ratin

g tim

e (s

)

0.001

0.01

0.1

1

10

100

1000

10000

Instantaneous trip1100 to 1560% ofrated current

• BM3RSB, RHB • BM3VSB, VHB

• BM3RSBK, RHBK • BM3VSBK, VHBK

1 10 100

Multiple of rated current (A)

Ope

ratin

g tim

e (s

)

0.001

0.01

0.1

1

10

100

1000

10000

3-phase cold start

3-phase hot startInstantaneous trip1100 to 1560% ofmax. setting current

1 10 100

Multiple of rated current (A)

Ope

ratin

g tim

e (s

)

0.001

0.01

0.1

1

10

100

1000

10000

3-phase cold start

3-phase hot start Instantaneous trip1100 to 1560% ofmax. setting current

Characteristics curves

Page 21: Manual Motor Starters Magnetic Contactors

19

Manual Motor Starters

Description Starter Mounting Contact Type Masstype arrangement (g)

BM3R Front 1NO BZ0WIA 9BM3V 1NC BZ0WIB

Left side 2NO BZ0WUAAL 451NO+1NC BZ0WUABL2NC BZ0WUBBL

Right side 2NO BZ0WUAAR 451NO+1NC BZ0WUABR2NC BZ0WUBBR

Optional accessories Features

• All accessories can be used with BM3R (45mm wide) andBM3V (55mm wide) frames.

• Accessories are easily mounted.• Internally mountable auxiliary contact blocks and alarm

contact blocks can be frontally mounted.• Externally mountable auxiliary contact blocks can be

mounted on either the right or left side.

These blocks are linked to the ON/OFF operation ofthe MMS. Up to two contact blocks can be mountedto the right/left front, and up to two contact blocks canbe mounted to the right/left sides.

• Shunt trip and undervoltage trip devices are available in awide operating coil voltage range.

• Standard and emergency external handles are available.• IP20 terminal cover prevents accidental finger touch to

electrically charged parts.

Types and ratings

• Auxiliary contact blocks/ W

AF01-60L

AF01-59, 01-58

Description Starter Mounting Contact Type Masstype arrangement (g)

BM3R Front 1NO BZ0KIA 9BM3V 1NC BZ0KIB

AF01-60R

• Alarm contact blocks/K

This block operates when the MMS trips due tooverload, phase-loss, or short-circuit. It is not linkedto the ON/OFF operation of the MMS.

Note: Operation can be checked with the test trip function.

(Rightside only)

Aux. contact block Alarm contact block

AF01-76Aux. contact blocksAux. and alarm contact blockShort-circuit alarm contact block

Aux. contact blocksShunt-trip deviceUndervoltage trip device

Page 22: Manual Motor Starters Magnetic Contactors

20

Manual Motor Starters

Description Starter Mounting Contact Type Masstype arrangement (g)

BM3R Left 1NO (Aux.)+ BZ0WKUAA 45BM3V 1NO (Alarm)

1NC (Aux.)+ BZ0WKUBA1NO (Alarm)

1NO (Aux.)+ BZ0WKUAB1NC (Alarm)

1NC (Aux.)+ BZ0WKUBB1NC (Alarm)

• This contact block combines auxiliary contact and alarmcontact that operate in the event of an overload, phase loss,or short-circuit. Alarm contact is not linked to the ON/OFFoperation of the MMS.

• An alarm is displayed in the contact block’s indicator whenthe alarm contact operates.

Note: Operation can be checked with the test trip function.

• Auxiliary and alarm contact blocks/ WK

AF01-57

Description Starter Mounting Contact Type Masstype arrangement (g)

BM3R Left 1NO+1NC BZ0TKUAB 45BM3V

• The contacts operate only when the MMS has tripped due toa short-circuit.

• When these contacts operate, the blue reset button extendsout, and a trip indication is displayed.

• The power to the MMS can be turned ON after pressing thereset button.

Note: Operation can be checked with the test trip function.Be sure to press the reset button before mounting to the MMS.

• Short-circuit alarm contact block/KI

AF01-56

Description Starter Mounting Coil voltage Type Masstype (g)

BM3R Right 24V 50/60Hz BZ0FAZU 115BM3V 48V 60Hz BZ0FBZU

48V 50Hz/60V 60Hz BZ0FCZU

100V 50Hz/100–110V 60Hz BZ0F1ZU110–127V 50Hz/120V 60Hz BZ0FDZU200V 50Hz/200–220V 60Hz BZ0FEZU220–230V 50Hz/240–260V 60Hz BZ0FFZU240V 50Hz/277V 60Hz BZ0FGZU

380–400V 50Hz/400–440V 60Hz BZ0FHZU415–440V 50Hz/460–480V 60Hz BZ0F4ZU500V 50Hz/600V 60Hz BZ0FJZU24–60V DC * BZ0FKZUD110-240V DC * BZ0FLZUD

AF01-55

• Shunt trip devices/F

This device is used to remotely trip the MMS.

Notes:• This device cannot be used together with an

undervoltage trip device.• When the MMS has been tripped with the shunt trip

device, press the reset button before turning ON thepower.

Note: * The time rating of coil is 5s.

Description Starter Mounting Coil voltage Type Masstype (g)

BM3R Right 24V 50Hz BZ0RAZ1U 115BM3V 24V 60Hz BZ0RAZ2U

48V 50Hz BZ0RBZ1U48V 60Hz BZ0RBZU

100V 50Hz/100–110V 60Hz BZ0R1ZU110–127V 50Hz/120V 60Hz BZ0RDZU200V 50Hz/200–220V 60Hz BZ0REZU220–230V 50Hz/240–260V 60Hz BZ0RFZU240V 50Hz/277V 60Hz BZ0RGZU

380–400V 50Hz/400–440V 60Hz BZ0RHZU415–440V 50Hz/460–480V 60Hz BZ0R4ZU500V 50Hz/600V 60Hz BZ0RJZU

R typesThis device automatically trips the MMS whenthe control circuit voltage drops below thespecified value.

Notes:• This device cannot be used together with a shunt trip

device.• When the MMS has been tripped with the

undervoltage trip device, press the reset buttonbefore turning ON the power.

AF01-54

• Undervoltage trip devices/R

Page 23: Manual Motor Starters Magnetic Contactors

21

Manual Motor Starters

Description Starter Mounting Coil voltage Type Masstype (g)

BM3RS Right 24V 50Hz BZ0RAZ1LKU 11524V 60Hz BZ0RAZ2LKU48V 50Hz BZ0RBZ1LKU48V 60Hz BZ0RBZLKU

100V 50Hz/100–110V 60Hz BZ0R1ZLKU110–127V 50Hz/120V 60Hz BZ0RDZLKU200V 50Hz/200–220V 60Hz BZ0REZLKU220–230V 50Hz/240–260V 60Hz BZ0RFZLKU240V 50Hz/277V 60Hz BZ0RGZLKU

380–400V 50Hz/400–440V 60Hz BZ0RHZLKU415–440V 50Hz/460–480V 60Hz BZ0R4ZLKU500V 50Hz/600V 60Hz BZ0RJZLKU

BM3RH Right 24V 50Hz BZ0RAZ1LTU 115BM3V 24V 60Hz BZ0RAZ2LTU

48V 50Hz BZ0RBZ1LTU48V 60Hz BZ0RBZLTU

100V 50Hz/100–110V 60Hz BZ0R1ZLTU110–127V 50Hz/120V 60Hz BZ0RDZLTU200V 50Hz/200–220V 60Hz BZ0REZLTU220–230V 50Hz/240–260V 60Hz BZ0RFZLTU240V 50Hz/277V 60Hz BZ0RGZLTU

380–400V 50Hz/400–440V 60Hz BZ0RHZLTU415–440V 50Hz/460–480V 60Hz BZ0R4ZLTU500V 50Hz/600V 60Hz BZ0RJZLTU

Description Starter Type Masstype (g)

BM3R BZ0SET 2.0

BM3V BZ0TCV 0.6

BM3R BZ0CFG 1.4

BM3V

• Others

• Used to cover the open space if an internallymountable accessory should becomeunnecessary.

• Mounts to either the left-front or right-front position.

• Undervoltage trip device/Re

With early make contacts/Re typesThis device automatically trips the MMS whenthe control circuit voltage drops below thespecified value.The control circuit voltage can be turnedcompletely OFF by turning OFF the MMS.

Notes:• This device cannot be used together with a

shunt trip device.• When the MMS has been tripped with the

undervoltage trip device, press the reset buttonbefore turning ON the power.

AF01-52

AF01-53

Push-in lug

Terminal cover for IP20

Dummy cover

KK02-39

Prevents accidental finger touch to charged parts.

Used for screw mounting.

Note: Refer to page 27 for details on how this device operates with the MMS, and on its external connection.

Description Starter Handle type Type Masstype (g)

BM3RH Standard BZ0VBBL 160(black)

Emergency BZ0VYRL 160(red/yellow)

BM3V Standard BZ0VBBM 160(black)

Emergency BZ0VYRM 160(red/yellow)

• Used to operate an MMS installed inside a panel, from theoutside of the panel.

• Equipped with an interlock mechanism that prevents someonefrom mistakenly opening the panel door when the MMS is in theON state.

• The shaft can be cut to match the distance between the MMSand the panel door.

• Door interlock function • OFF lock function• Can be locked OFF with up to three padlocks.

Note: Padlocks are to be provided by the customer.

• Release screw allows the door to be opened with the handle inthe ON position.

• IP54 enclosure

• External operating handles

KK02-306

KK02-305

Page 24: Manual Motor Starters Magnetic Contactors

22

Manual Motor Starters

Accessory type Auxiliary contact Auxiliary contact Alarm contact Aux. and alarm Short-circuit alarmblock/front block/side block contact block contact block

BZ0WI BZ0WU BZ0KI BZ0WKU BZ0TKUABStandard IEC 60947-5-1, UL 508Rated operational current 48V.AC AC-15 5 6 5 6 6(A) 125V AC 3 4 3 4 4

230V AC 1.5 4 1.5 4 4400V AC – 2.2 – 2.2 2.2500V AC – 1.5 – 1.5 1.5690V AC – 0.6 – 0.6 0.6

48V.DC DC-13 1.38 5 1.38 5 5110V.DC 0.55 1.3 0.55 1.3 1.3220V.DC 0.27 0.5 0.27 0.5 0.5

Contact rating code UL 508 B300 A600 B300 A600 A600Q300 P300 Q300 P300 P300

Min. voltage and current 17V 5mA

Ratings of accessories

Accessory type Shunt trip device Undervoltage deviceBZ0F BZ0R

Standard IEC 60947-1, UL 508Rated insulation voltage IEC 60947 690(V AC) UL 508 600No. of ON-OFF operations 5000Operating time (ms) 20Power consumption Inrush (VA / W) 21/12

Shealed (VA / W) 8/1.2Voltage range Tripping voltage (V) 0.7 to 1.1Ue 0.35 to 0.7Ue

Closing voltage (V) – 0.85 to 1.1UeTime rating of coil (s) AC: Continuous Continuous

DC: 5

Page 25: Manual Motor Starters Magnetic Contactors

23

Manual Motor Starters

Note: Do not use an alarm contact block/K together with an undervoltage trip device with early make contacts/Re for the BM3RSB frame. If used together, the alarmcontact block will not operate correctly when the MMS is automatically tripped due to undervoltage.

External device(Right)

External device(Left)

Internal deviceMMS

WW

W2

W2(Left)

W2(Right)

K W+W W+K

W2WW2W W2K W2WW W2WK

W2 W2WW2W W2K W2WW W2WK W2 W2WW2W W2K W2WW W2WK

W2F

W2R

W2WFW2WF W2KF W2WWF W2WKF

W2WRW2WR W2KR W2WWR W2WKR

WKF WKWFWKWF WKKF WKWWF WKWKF

WKR WKWRWKWR WKKR WKWWR WKWKR

WK WKWWKW WKK WKWW WKWK

KI KIWKIW KIK KIWW KIWK

F WFWF KF WFWF KFWWF WKF

R WRWR KR WWR WKR

KIF KIWF KIKF KIWWF KIWKFKIWF

KIR KIWR KIKR KIWWR KIWKRKIWR

W2W2 W2W2W W2W2K W2W2WW W2W2WKW2W2W

W2W2 W2W2W W2W2K W2W2WW W2W2WKW2W2W

WW

W2

K W+W W+K

W2WW2W W2K W2WW W2WK

W2F

W2R

W2WFW2WF W2KF W2WWF W2WKF

W2WRW2WR W2KR W2WWR W2WKR

WKF WKWFWKWF WKKF WKWWF WKWKF

WKR WKWRWKWR WKKR WKWWR WKWKR

WK WKWWKW WKK WKWW WKWK

KI KIWKIW KIK KIWW KIWK

F WWF WKF

R WRWR KR WWR WKR

KIF KIWF KIKF KIWWF KIWKFKIWF

KIR KIWR KIKR KIWWR KIWKRKIWR

W2W2 W2W2W W2W2K W2W2WW W2W2WKW2W2W

W2W2 W2W2W W2W2K W2W2WW W2W2WKW2W2W

Adj. thermal-magnetic trip type MMS

Instantaneous trip type MMS

Internal accessory

External accessory

BM3RSB, BM3RHB

BM3RSBK, BM3RHBK

BM3VSB, BM3VHB

BM3VSBK, BM3VHBK

WK(Left)

KI(Left)

F(Right)

R(Right)

W2 (Left)+F

W2 (Left)+R

WK+F

WK+R

KI+F

KI+R

W2 (Left)+W2 (Left)

W2 (Left)+W2 (Right)

Shunt trip device (F)Undervoltage trip device (R) or undervoltage trip device with early make contacts (Re)

Internal devicesAuxiliary contact block (W) Alarm contact block (K)

External devices

Auxiliary contact (W2) Short-circuit alarm contact block (KI)Auxiliary and alarm contact block (WK)

Available accessory configuration

Page 26: Manual Motor Starters Magnetic Contactors

24

Manual Motor Starters

Internal accessory

External accessory

Adj. thermal-magnetic trip type MMS

Instantaneous trip type MMS

Shunt trip device (F)Undervoltage trip device (R) or undervoltage trip device with early make contacts (Re)

Internal devicesAuxiliary contact block (W) Alarm contact block (K)

External devices

Auxiliary contact (W2) Short-circuit alarm contact block (KI)Auxiliary and alarm contact block (WK)

WW K W+W W+K WW K W+W W+K

W2W2

W2 (Right)+W2 (Right)

W2 (Left)+WK

W2W2WW2W2W W2W2K W2W2WW W2W2WK

W2W2F

W2W2R

W2W2WFW2W2WF W2W2KF W2W2WWF W2W2WKF

W2W2WRW2W2WR W2W2KR W2W2WWR W2W2WKR

W2WKF W2WKWFW2WKWF W2WKKF W2WKWWF W2WKWKF

W2WKR W2WKWRW2WKWR W2WKKR W2WKWWR W2WKWKR

W2WK W2WKWW2WKW W2WKK W2WKWW W2WKWK

W2WK W2WKWW2WKW W2WKK W2WKWW W2WKWK

W2KI

W2KIWW2KIW W2KIK W2KIWW W2KIWK

W2KIWW2KIW W2KIK W2KIWW W2KIWK

W2KI

KIWK KIWKWKIWKW KIWKK KIWKWW KIWKWK

W2KIF W2KIWF W2KIKF W2KIWWF W2KIWKFW2KIWF

W2KIR W2KIWR W2KIKR W2KIWWR W2KIWKRW2KIWR

KIWKF KIWKWF KIWKKF KIWKWWF KIWKWKFKIWKWF

KIWKR KIWKWR KIWKKR KIWKWWR KIWKWKRKIWKWR

W2W2 W2W2WW2W2W W2W2K W2W2WW W2W2WK

W2W2F

W2W2R

W2W2WFW2W2WF W2W2KF W2W2WWF W2W2WKF

W2W2WRW2W2WR W2W2KR W2W2WWR W2W2WKR

W2WKF W2WKWFW2WKWF W2WKKF W2WKWWF W2WKWKF

W2WKR W2WKWRW2WKWR W2WKKR W2WKWWR W2WKWKR

W2WK W2WKWW2WKW W2WKK W2WKWW W2WKWK

W2WK W2WKWW2WKW W2WKK W2WKWW W2WKWK

W2KI

W2KIWW2KIW W2KIK W2KIWW W2KIWK

W2KIWW2KIW W2KIK W2KIWW W2KIWK

W2KI

KIWK KIWKWKIWKW KIWKK KIWKWW KIWKWK

W2KIF W2KIWF W2KIKF W2KIWWF W2KIWKFW2KIWF

W2KIR W2KIWR W2KIKR W2KIWWR W2KIWKRW2KIWR

KIWKF KIWKWF KIWKKF KIWKWWF KIWKWKFKIWKWF

KIWKR KIWKWR KIWKKR KIWKWWR KIWKWKRKIWKWR

BM3RSB, BM3RHB

BM3RSBK, BM3RHBK

BM3VSB, BM3VHB

BM3VSBK, BM3VHBK

W2 (Right)+WK

W2 (Left)+KI

W2 (Right)+KI

KI+WK

W2 (Left)+W2 (Left)+F

W2 (Left)+W2 (Left)+R

W2 (Left)+WK+F

W2 (Left)+WK+R

W2 (Left)+KI+F

W2 (Left)+KI+R

KI+WK+F

KI+WK+R

External device(Right)

External device(Left)

Internal deviceMMS

Note: Do not use an alarm contact block/K together with an undervoltage trip device with early make contacts/Re for the BM3RSB frame. If used together, the alarmcontact block will not operate correctly when the MMS is automatically tripped due to undervoltage.

Available accessory configuration (continued)

Page 27: Manual Motor Starters Magnetic Contactors

25

Manual Motor Starters

• Auxiliary contact blocks, side mountingBZ0WU

18.7M3.5

70.4

53.6

47.2

9045

6648.7

35.72.82.

3 9

• Auxiliary and alarm contact blocksBZ0WKU

35.718.7

M3.5

70.4

53.6

45 47.2

90

6648.7Indication

window

2.89

2.3

Dimensions, mm

• Rotary handle types BM3RHB

91

ø5

27

27

4575.3 3.7

4514.3 14.3

M4

5.5

90 75 45

3.3

95

14.3

105

For mountingscrew

35mm Top hat railHight 15mm(TH35-15)

• Rocker handle types BM3RSB45

14.3

13

5.5

14.3ø5

90 75 45

13.5

6

95 105

14.3

M4

35mm Top hat railHight 15mm(TH35-15)

45

27

27

71

62.3 3.7

27

For mountingscrew

• Rotary handle types BM3VSB, BM3VHB

92.3107.8

88.3

4.281.3

5516.5

110

84

3.3

45

4.5

5

66 120

16.5

M6

ø5

5.5

42

33.8

33.8

35mm Top hat railHight 15mm(TH35-15)

Accessories• Auxiliary contact blocks, front mountingBZ0WI

M3.59

21.510.5

16.7

38.8

8.518.9

• Alarm contact blocks, front mountingBZ0KI

M3.59

21.510.5

8.518.91

16.7

38.8

Page 28: Manual Motor Starters Magnetic Contactors

26

Manual Motor Starters

Dimensions, mmAccessories• Short-circuit alarm contact blockBZ0TKUAB

35.7

6648.7

18.7M3.5

Reset button

2.89 6

70.4

53.6

47.2

90

45

2.3

MMS with accessories• BM3RSB + BZ0

81

90 45 95

10.5

45 18 71

45

62.3 3.7

99

• BM3RHB + BZ0

8145 18

9162.3

45

75.3 3.7

9

90 45 95

10.5

9

• Shunt trip devices BZ0FUndervoltage trip devices BZ0R

2.3

70.4

47.2

45 90

M3.5

6648.7

18.75.2

182.8

• BM3RSB + BZ0R LKU (Undervoltage trip device)

Max.7.5

Min

. 66

Max

. 78.

5

45

95 616

.5 12

19.4

45 90

18

21

• BM3V B + BZ0

91

55 18184399

110

45 90 120

92.3107.8 4.2

79.362

13.3

Type X min. X max.BZ0VBBL, BZ0VYRL 139±2 289±2BZ0VBBM, BZ0VYRM 156±2 306±2

Panel

66

66

3.3

5.545

Mounting screw

Shaft

Top of handle

Panel thickness 1.5 to 5

Xof handleCLof MMSCL

of MMSCL

of handleCL

Min. 75Door hinge

Max

. 68

TypeBM3RHBM3V

A48.558.5

4-ø3.5

ø28

CL

CL 52.6

52.6

Locked

of handleCL

of handleCL

A

External operation handle BZ0VPanel drilling

Page 29: Manual Motor Starters Magnetic Contactors

27

Manual Motor Starters

Wiring diagrams• MMS

L1

1

L2

3

L3

T1 T2 T3

5

2 4 6

• Auxiliary contact blocksFront mountingBZ0WIA BZ0WIB

11(21)

12(22)

13(23)

14(24)

• Alarm contact blocksFront mounting

BZ0KIBBZ0KIA25

26

27

28

• Undervoltage trip devicesBZ0R

D1

D2

U<

In addition to the functions of theundervoltage trip device, thisdevice completely opens themain circuit and control circuitwhen the MMS is turned OFF.However, when the MMS istripped by a drop in the controlcircuit voltage, it must be reset.

There may be no trip indicationand no opening of the auxiliarycontact even though the MMS istripped due to short-circuit,overcurrent, or phase-loss.

External connectionBZ0RD1 07

D2 08

U<

or

08

D2D2

08

07D1

U<

• Undervoltage trip devices with contact blocks

• Short-circuit alarm contact blocksBZ0TKUAB

8587

8886

• Shunt trip devicesBZ0F

C1

C2

53(153) 63(163)

54(154)64(164)

BZ0WUAAL BZ0WUABL BZ0WUBBL

BZ0WUAAR BZ0WUABR BZ0WUBBR

43(143)33(133)

34(134)44(144)

43(143)31(131)

32(132)44(144)

41(141)

32(132)42(142)

31(131)

51(151) 63(163)

52(152) 64(164)

51(151)61(161)

52(152) 62(162)

Side mounting • Auxiliary and alarm contact blocks

BZ0WKUAB

7573

7476

BZ0WKUBB

7571

7276

BZ0WKUBA

7771

7278

BZ0WKUAA

7773

7478

Page 30: Manual Motor Starters Magnetic Contactors

28

Manual Motor Starters

Standard operating conditionsAmbient Operating: –5 to +55°Ctemperature Storage: –40 to +65°CHumidity 45 to 85%RHAltitude 2000m or lowerAtmosphere No excessive dust, smoke, corrosive gases, flammable

gases, steam or salt.

Vibration 10 to 55Hz 15m/s2

Shock 50m/s2

Type Rated operational Min. distance to groundedvoltage Ue metal (mm)(V) A, B C, D

BM3RS Up to 460 15 20500 15 30Up to 690 40 40

BM3RH Up to 500 15 30Up to 690 40 50

BM3V Up to 500 15 40Up to 690 40 50

Mountings• Rail mountingThe MMS can be mounted to a 35mm top hat rail. Secure therail with screws at mounting pitch of less than 400mm for theBM3R type and less than 300mm for the BM3V type.Applicable rail:Use a 15mm-high TH35-15 rail conforming to EN-50022 andIEC715.The standard rail mounting direction is horizontal. When usingthe MMS on a vertically mounted rail, use FUJI end clamp kits.

Mounting Removing15mm

35mm wide rail

Snap

1

1

2

ø5mm or less

• Screw mountingThe separately sold push-in lug (BZ0SET) is required forscrew mounting the BM3R frame. The BM3V frame can bescrew mounted directly to the panel.

BM3RSB, RSBK BM3VSB, VSBKBM3RHB, RHBK BM3VHB, VHBK

M4

M4

M4

M4

Push-in lugBZ0SET

Mounting angle

180° 180°

30°

90°

When frames are mounted side-by-side, operating conditions such as ahigh ambient temperature or using themaximum setting for continuouscarrying current may cause slightchanges in operating characteristicsdue to temperature rises.Under such conditions, it isrecommended that the frames beseparated by at least 5mm.

Type BM3R BM3V BZ0Accessories

Solid wire (mm) ø1.6 to 2.6 ø1.6 to 2.6 ø1 to 1.6Stranded Single-wire 1 to 10 1 to 25 0.5 to 2.5wire (mm2) 2-wire 1 to 6 1 to 16 0.5 to 2.5AWG Single-wire 18 to 8 18 to 4 18 to 14

2-wire 18 to 10 18 to 4 18 to 14Sheath stripping Approx.10 Approx.13 Approx.10length (mm)

Terminal screw Pan head Pan head Pan headscrew (PZ2) screw (PZ2) screw (PZ2)

M4 M6 M3.5Tightening torque 2 4 0.8(N·m)

Arc spaceThe arc space required when mounting is shown in the tablebelow.

WiringsWhile pressing the wire with a screwdriver, tighten the screwto the specified tightening torque.

No sudden temperaturechanges resulting incondensation or icing.

No abnormal shock orvibration

Note: There is no need for a crimp terminal or any other terminal on the end ofthe connection wire.

CA

D

B

Grounded metal

Page 31: Manual Motor Starters Magnetic Contactors

29

Manual Motor Starters

Description Used with Specification Type Mass (g)Busbar BM3R Continuous current: 2-BM3R, modular space: 45mm BZ0BR02A 30

64A max. 3-BM3R, modular space: 45mm BZ0BR03A 50Pin connection 4-BM3R, modular space: 45mm BZ0BR04A 70

5-BM3R, modular space: 45mm BZ0BR05A 90

BM3R+1-external 2-BM3R, modular space: 54mm BZ0BR12A 30accessory, 9mm wide 3-BM3R, modular space: 54mm BZ0BR13A 55

4-BM3R, modular space: 54mm BZ0BR14A 805-BM3R, modular space: 54mm BZ0BR15A 105

BM3R+2-external Continuous current: 2-BM3R, modular space: 63mm BZ0BR22A 45accessory, 9mm wide 64A max. 4-BM3R, modular space: 63mm BZ0BR24A 100or Fork connectionBM3R+1-externalaccessory, 18mm wide

BM3V Continuous current: 2-BM3V, modular space: 55mm BZ0BV02A 140126A max. 3-BM3V, modular space: 55mm BZ0BV03A 240Pin connection 4-BM3V, modular space: 55mm BZ0BV04A 340

BM3V+1-external 2-BM3V, modular space: 64mm BZ0BV12A 150accessory, 9mm wide 3-BM3V, modular space: 64mm BZ0BV13A 270

4-BM3V, modular space: 64mm BZ0BV14A 380

BM3V+2-external 2-BM3V, modular space: 73mm BZ0BV22A 165accessory, 9mm wide 4-BM3V, modular space: 73mm BZ0BV24A 425orBM3V+1-externalaccessory, 18mm wide

3-phase feed-in terminal BM3R Continuous current: 64A max. BZ0BFRA 40Applicable cable size: 25mm2 max.

BM3V Continuous current: 126A max. BZ0BFVA 170Applicable cable size: 50mm2 max.

Busbar cover BZ0BR For pin connection BZ0BCRA 10For fork connection BZ0BCRB 5

BZ0BV For pin connection BZ0BCVA 5

Busbar system Features

• The busbar system reduces wiring time and savesfloorspace.

• The busbar makes it easy to power from 2 to 5 manual motorstarters – with no wiring needed.

• The 3-phase feed-in terminals are used to connect the wirefor the power supply circuit.

• The busbar cover guards against accidental touching of non-connected busbar terminals (charged parts).

Busbar cover

Busbar3-phase feed-in terminals

Manual motorstarter

Connecting module

Contactor

Reverse connection kitKK02-159

Types and ratings

AF01-70R

AF01-70L

KK02-164

Page 32: Manual Motor Starters Magnetic Contactors

30

Manual Motor Starters

Dimensions, mm• For BM3RBZ0BR0 Without external accessory

80125

170215

12

2 12.5

13

27.5

2 4

45

1414

13.5

BZ0BR02A: 80mmBZ0BR03A: 125mmBZ0BR04A: 170mmBZ0BR05A: 215mm

BZ0BR1 With 1-external accessory

12

13

2 12.5

14 14

54

27.5

13.5

197143

89

2 4

251

BZ0BR12A: 89mmBZ0BR13A: 143mmBZ0BR14A: 197mmBZ0BR15A: 251mm

BZ0BR2 With 2-external accessory, 9mm wideWith 1-external accessory, 18mm wide

14 144.52

18

63

235109

1932

.5

1.5

11

BZ0BR22A: 109mmBZ0BR24A: 235mm

• For BM3VBZ0BV0 Without external accessory

17 174 2.5

205

23

97151

16 20

243033

5

55

BZ0BV02A: 97mmBZ0BV03A: 151mmBZ0BV04A: 205mm

BZ0BV1 With 1-external accessory, 9mm wide

4

16

17 172.5

64

23

232

106169

20

243033

5

BZ0BV12A: 106mmBZ0BV13A: 169mmBZ0BV14A: 232mm

BZ0BV2 With 2-external accessory, 9mm wideWith 1-external accessory, 18mm wide

4

23

260

73

16

17 172.5

20

243033

5

116

BZ0BV22A: 116mmBZ0BV24A: 260mm

Page 33: Manual Motor Starters Magnetic Contactors

31

Manual Motor Starters

BZ0BFVA

(10-4 AWG)

29

17

7 17 17 6

17 17

54

48.5

4

M4

10-50mm2

2

Hexagon socket head bolt

54

Dimensions, mm• 3-phase feed-in terminalsBZ0BFRA

2724

38.5

1.5

14.514.5

3 14.5 14.5 3.8

1.9

2513.5

5

6.5

M4

44.5

6-25mm2

(10-4 AWG)

Page 34: Manual Motor Starters Magnetic Contactors

32

Manual Motor Starters

Enclosures Features

• Accommodates a variety of manual motor starters(BM3RSB-P16 to 025). Put the manual motor starter insidean enclosure for use in harsh environments. Surfacemounting and flush mounting types available.

• IP41 and IP55 enclosure protection degree available• Manual motor starters (BM3RSB-P16 to 025) equipped with

internal accessories and the following external accessoriescan be used inside an enclosure.Left side: One auxiliary contact block or one auxiliary/

alarm contact blockRight side: One shunt trip device or one undervoltage trip

device• A wide variety of enclosure accessories are available.

Padlocking device, emergency mushroom pushbutton,conversion kit, and indicator lamps

Types and ratingsEnclosures for BM3RSB-P16 to 025Mounting Specification Type Mass (g)Surface IP41 BZ0CSLA 320

IP55 (with conversion kit) BZ0CSLB 340

Flush IP41 BZ0CFLA 240IP55 (with conversion kit) BZ0CFLB 260

Accessories for enclosuresDescription Specification Type Mass (g)

Padlocking device OFF locking possible using up to three padlocks with a 5 to 8mm shackle diameter. BZ0CKA 90

Emergency pushbutton Momentary BZ0CPM 55Push-lock turn reset BZ0CPL 55Key operated BZ0CPK 90

Conversion kit Converts IP41 to IP55 BZ0CCA 25

Adaptor set For BM3RS + undervoltage trip device with auxiliary contact. BZ0CUA 20

Neutral connector Used inside the enclosure for neutral and ground connection. BZ0CNA 10

Indication lamp Green, 100–120V AC BZ0CLGA 15Green, 200–240V AC BZ0CLGB 15Green, 380–440V AC BZ0CLGC 15Green, 480–500V AC BZ0CLGD 15Green, 500–600V AC BZ0CLGE 15

Red, 100–120V AC BZ0CLRA 15Red, 200–240V AC BZ0CLRB 15Red, 380–440V AC BZ0CLRC 15Red, 480–500V AC BZ0CLRD 15Red, 500–600V AC BZ0CLRE 15

White, 100–120V AC BZ0CLCA 15White, 200–240V AC BZ0CLCB 15White, 380–440V AC BZ0CLCC 15White, 480–500V AC BZ0CLCD 15White, 500–600V AC BZ0CLCE 15

Surface mountingenclosure

Flush mountingenclosures

Padlocking device

Emergency pushbuttons

Adaptor set

Neutral connector Conversion kitsIP41 to IP55

Indication lamps

Notes: • The padlocking device cannot be used together with the emergency pushbutton or undervoltage trip device with auxiliary contact.• The emergency pushbutton cannot be used together with the undervoltage trip device with auxiliary contact.

Page 35: Manual Motor Starters Magnetic Contactors

33

Manual Motor Starters

Dimensions, mm• Surface mountingFor without accessory

ø4.

5

ø4.5

145

20.4

45

1.5

150

2.2

ø21

98

69 28 1.6

18.8

85

155

7.8

52

For with padlocking device

17.8

ø8.5

150

155

167.

5

11.5

Non locked OFF locked

Padlocks with 5-8mm dia.11.5

20.4

45

18.8

52

85

ø4.5

145

11.8

2.2

150

12.5

69 28113

98

1.5

1

82

ø4.

5

1.6

ø2

For with emergency pushbutton

Push-locked20203919

Non locked26264525

X dimensions MomentaryPush-lock turn resetWith keyWithout key

X

ø4.

5

ø4.530 69

2.2

150

128

145

155

13.5

52

20.4

45

85

98 1.6

18.8

18 ø2

1.5

• Flush mountingFor without accessory

82.5

125*

81.5*15.6

115

96.5

139

Max

. 6M

in. 1

.5

18.8

7.8

52

82–84

R3 max.

126–

128

Panel cutting

For with padlocking device

ø8.5

OFF lockedNon locked

2316

2

82 125*

81.5*30.5

15.6

82.5

115

12.5

139 7.

852

96.518.8

Max

. 6M

in. 1

.5

11.5 11.5

Padlocks with 5-8mm dia.

82–84

R3 max.

126–

128

Panel cutting

For with emergency pushbutton

18 81.5*

40.1

18.8 15.630

X

13.5

52

139

115

125*

Max

. 6M

in. 1

.5

82.5

96.5

Push-locked20203919

Non locked26264525

X dimensions MomentaryPush-lock turn resetWith keyWithout key

82–84

R3 max.

126–

128

Panel cutting

Page 36: Manual Motor Starters Magnetic Contactors

34

Contactors/SC-M and SC-E series

2.2 to 75kW at 400V ACThe SC-M and SC-E series further enhance the high reliability of the SC serieswith full conformance to IEC standards.

International standardizationIEC 60947-4-1, EN 60947-4-1, VDE 0660UL 508, CSA C 22.2, JIS C 8201-4-1

Compactness• SC-M01, M02: 45mm wide

SC-E02 to E05: 43mm wide, SC-E1 to E2S: 54mm wideSC-E3, E4: 67mm wide, SC-E5: 88mm wide

• Reducing mounting area

Safety• Terminals with finger-touch protection (DIN 57106/

VDE 0106 Teil100)

Utility• Box lug terminal construction• Long electrical life• Reduction of wiring work

Ecology• Reducing power consumption• Recycled thermoplastic resin used for plastic parts.• The names of materials are indicated on all major

parts to facilitate their recycling.

In addition to the five basic concepts of the existing SC seriesof magnetic contactors and motor starters — internationalstandardization, compactness, safety, utility, and ecology —the SC-M and SC-E series take the line-up to the next step inutility with a new finger protection terminal and box lugterminal construction.

48

5645mm 54mm

96

90

67mm

111

112

100mm

138

169

SC-M series SC-E series

SC-M01, M02 SC-E1 to E2S SC-E3, E4 SC-E6 with SUPER magnet

General information

International standardization

Fin

ger

protection terminal Box lug terminal co

nstr

uct

ion

CompactnessCompactness EcologyEcology

SafetySafety UtilityUtility

Page 37: Manual Motor Starters Magnetic Contactors

35

Contactors/SC-M and SC-E seriesGeneral information

SC-M series2.2 to 4kW, 400V AC

DescriptionOptimal 45mm-wide mini-magnetic contactors for small-capacity induction motor control.A wide range of accessories ensures the flexibility to meetuser needs.

Features• Best suitable for D.O.L. starter up to 4kW, 400V AC.• Two models with low power consumption (1.2W and 2W at

24V DC) as well as standard DC operated models• A wide variety of optional accessories available, flexibly

specification changes available• A finely divided scale for the current adjustment dial enables

easy and exact current settings.• Terminal block with easy wiring• Snap-on mounting to top hat rail

Optional accessories

Auxiliary contact blocks

AF01-21 AF01-25

Coil surge suppression unit Solid-state time-delay unit

AF01-24 AF01-23

SC-E series4 to 75kW, 400V AC

DescriptionModels SC-E02 to SC-E4 have a 3-pole main circuit structure.Available in three frame sizes, 43mm, 54mm, and 67mm wide,they enable a significantly reduced mounting area.Models SC-E5 to SC-E7 use an IC-controlled SUPERmagnet to ensure high operating reliability.

Features• In addition to meeting IEC and JIS standards, these models

also have UL and CSA approval and bear the CE mark.• Models SC-E02 to SC-E4 have 3-pole main circuits and

come in three sizes with widths of 43mm (up to 25A), 54mm(up to 50A), and 67mm (up to 80A).

• Models SC-E1 to SC-E7 employ a box terminal structurethat allows wires to be connected directly to the main circuit.

• Equipped with a finger-protection terminal structure thatprevents the exposure of live parts.

• Models SC-E5 to SC-E7 use a SUPER magnet (AC/DC-input/DC-energizing operation) to achieve high operatingreliability.

Optional accessories

Auxiliary contact blocks

KK02-081 AF88-080 KK01-090

Main circuit surge suppression units

KK02-077 KK02-079

Coil surge suppression unit

AF88-766

Page 38: Manual Motor Starters Magnetic Contactors

36

Contactors/SC-M and SC-E series

Quick reference guide

R

Quick reference guide

R

Contactor SC-M01 SC-M02 SC-E02 SC-E03 SC-E04 SC-E05 SC-E1

KK02-292 KK02-292 AF01-12 AF01-11 AF01-10 KK01-105 AF01-8

Rating of 3-phase motor AC-3 (kW)200–240V 1.5 3 2.2 3 4 5.5 7.5380–440V 2.2 4 4 5.5 7.5 11 15

Rated operational current AC-3 (A)200–240V 6 9 9 12 18 25 32380–440V 6 9 9 12 18 25 32

Rated thermal current AC-1 (A) 20 20 20 20 25 32 50

Auxiliary contact 1NO, 1NC 1NO, 1NC – – – – –

Dimensions AC operated 45 48 56 43 80 81 54 90 96W H D (mm) DC operated 45 48 68 43 80 108 54 90 121.5

Standard IEC 60947-1, EN 60947-4-1, VDE 0660, UL 508, CSA C22.2

Further information Page 38 Page 47

Thermal overload relay TK-M0 TK-M0 TK-E02 TK-E02 TK-E02 TK-E02 TK-E2(standard type)

KK02-295 KK02-295 KK01-86 KK01-86 KK01-86 KK01-86 KK01-88

Ampere setting range (A) 0.11–0.17 0.11–0.17 0.1–0.15 0.1–0.15 0.1–0.15 0.1–0.15 4–60.17–0.26 0.17–0.26 0.13–0.2 0.13–0.2 0.13–0.2 0.13–0.2 5–80.26–0.43 0.26–0.43 0.15–0.24 0.15–0.24 0.15–0.24 0.15–0.24 6–90.43–0.65 0.43–0.65 0.2–0.3 0.2–0.3 0.2–0.3 0.2–0.3 7–110.65–1.0 0.65–1.0 0.24–0.36 0.24–0.36 0.24–0.36 0.24–0.36 9–130.85–1.3 0.85–1.3 0.3–0.45 0.3–0.45 0.3–0.45 0.3–0.45 12–18 1.1–1.6 1.1–1.6 0.36–0.54 0.36–0.54 0.36–0.54 0.36–0.54 18–261.35–2.0 1.35–2.0 0.48–0.72 0.48–0.72 0.48–0.72 0.48–0.72 24–36 1.7–2.4 1.7–2.4 0.64–0.96 0.64–0.96 0.64–0.96 0.64–0.96 2.2–3.2 2.2–3.2 0.8–1.2 0.8–1.2 0.8–1.2 0.8–1.2 2.5–4.0 2.5–4.0 0.95–1.45 0.95–1.45 0.95–1.45 0.95–1.45 3.0–4.7 3.0–4.7 1.4–2.2 1.4–2.2 1.4–2.2 1.4–2.2 4.0–6.3 4.0–6.3 1.7–2.6 1.7–2.6 1.7–2.6 1.7–2.6

5.5–8.0 2.2–3.4 2.2–3.4 2.2–3.4 2.2–3.4 7.5–10.5 2.8–4.2 2.8–4.2 2.8–4.2 2.8–4.2

4–6 4–6 4–6 4–6 5–8 5–8 5–8 5–8 6–9 6–9 6–9 6–9 7–11 7–11 7–11 7–11

9–13 9–13 9–13 12–18 12–18

16–22 20–25

Dimensions W H D (mm) 45 68.5 53 53 60.5 80.5 54 78.5 97

Standard IEC 60947-1, EN 60947-4-1, VDE 0660, UL 508, CSA C22.2

Further information Page 44 Page 57

Page 39: Manual Motor Starters Magnetic Contactors

37

Contactors/SC-M and SC-E series

Contactors SC-E2 SC-E2S SC-E3 SC-E4 SC-E5 SC-E6 SC-E7

AF01-7 AF01-6 AF01-5 AF01-4 AF01-3 AF01-2 AF01-1

Rating of 3-phase motor AC-3 (kW)200–240V 11 15 18.5 22 30 37 45380–440V 18.5 22 30 40 55 60 75

Rated operational current AC-3 (A)200–240V 40 50 68 80 105 125 150380–440V 40 50 65 80 105 125 150

Rated thermal current AC-1 (A) 60 65 100 105 150 150 200

Auxiliary contact – – – – 2NO+2NC 2NO+2NC 2NO+2NC

Dimensions AC operated 54 90 96 67 112 111 88 155 132 100 169 138 115 175 140W H D (mm) DC operated 54 90 121.5 67 112 130

Standard IEC 60947-1, EN 60947-4-1, VDE 0660, UL 508, CSA C22.2

Further information Page 47

Thermal overload relay TK-E2 TK-E2 TK-E3 TK-E3 TK-E5 TK-E6 TK-E6(standard type)

KK01-88 KK01-88 KK01-87 KK01-87 KK01-85 KK01-84 KK01-84

Ampere setting range (A) 4–6 4–6 7–11 7–11 18–26 45–65 45–65 5–8 5–8 9–13 9–13 24–36 53–80 53–80 6–9 6–9 12–18 12–18 28–40 65–95 65–95 7–11 7–11 18–26 18–26 34–50 85–125 85–125 9–13 9–13 24–36 24–36 45–65 110–16012–18 12–18 28–40 28–40 65–9518–26 18–26 34–50 34–50 85–10524–36 24–36 45–65 45–6532–42 32–42 48–68 48–68

40–50 64–8044–54

Dimensions W H D (mm) 54 78.5 97 68 89.5 107.5 76.5 105 106 100 122 123

Standard IEC 60947-1, EN 60947-4-1, VDE 0660, UL 508, CSA C22.2

Further information Page 57

R

Quick reference guide

R

Page 40: Manual Motor Starters Magnetic Contactors

Contactors/SC-M series

38

Type number nomenclature

SC-M01/G

SC-M series magnetic contactors Features

• 45mm-wide compact magnetic contactors• Terminal block with easy wiring that prevents the accidental

finger touch to live parts.• Snap-on mounting to top hat rail (DIN)• Electrical durability of one million operations• Two models with low power consumption (1.2W and 2W at

24V DC) as well as standard DC-operation models• Many optional accessories: Auxiliary contact block, coil surge

suppression unit, and solid-state time-delay unit

StandardsIEC 60947-4-1, EN 60947-4-1, VDE 0660UL 508, CSA C 22.2, JIS C 8201-4-1, JEM 1038

Types and ratings• Non-reversing

AC operatedSC-M01

DC operatedSC-M01/G

AF00-71 AF00-73

Operating coil Rated capacity (kW) Rated operational current (A) Type3-phase motor AC-3 3-phase motor AC-3 Resistive load AC-1

AC operated 20 20 20 1NO SC-M011NC

20 20 20 1NO SC-M021NC

DC operated 20 20 20 1NO SC-M01/G1NC

20 20 20 1NO SC-M02/G1NC

20 20 20 1NO SC-M01/G11NC

20 20 20 1NO SC-M02/G11NC

20 20 20 1NO SC-M01/G21NC

20 20 20 1NO SC-M02/G21NC

Note: Ratings conform to IEC 60947-4-1

DC operated(Low powerconsumption24V DC 1.2W)

DC operated(Low powerconsumption24V DC 2W)

Auxiliarycontactarrangement

Rated thermal current

(A)380440V

200240V

200240V6

9

6

9

6

9

6

9

380440V6

9

6

9

6

9

6

9

600690V3.5

5

3.5

5

3.5

5

3.5

5

200240V1.5

3

1.5

3

1.5

3

1.5

3

380440V2.2

4

2.2

4

2.2

4

2.2

4

500V

3

4

3

4

3

4

3

4

600690V3

4

3

4

3

4

3

4

500V

5

6.5

5

6.5

5

6.5

5

6.5

Ordering informationSpecify the following:1. Type number2. Operating coil order voltage (See page 39)3. Auxiliary contact arrangement

Operating coil voltageBlank: AC operatedG: 12–220V DC operated, power consumption 3WG1: 24V DC operated, low power consumption 1.2WG2: 24V DC operated, low power consumption 2W

Rated capacityM01: 2.2kW at 380–440VM02: 4kW at 380–440V

Page 41: Manual Motor Starters Magnetic Contactors

Contactors/SC-M series

39

Rated thermal current Making and breaking Rated operational current Minimum voltagecurrent AC DC and current

Voltage AC-15(Ind. load) Voltage DC-13(Ind. load)16A 120V AC 60A 120V 6A 24V 5A 17V DC 5mA

220V AC 60A 220V 6A 48V 3.5A440V AC 30A 440V 3A 110V 1.2A600V AC 15A 600V 1.5A 220V 0.6A

Auxiliary contact ratingsConforming to IEC 60947 5-1, BSEN 60947 5-1 VDE 0660

Frame size Making capacity Breaking capacity Operating cycles Voltage Durability (operations)(A) (A) per hour Electrical Mechanical

M01 72 60 1200 200/240V AC 1 million 5 million380/440V AC

M02 108 90 1200 200/240V AC 1 million 5 million380/440V AC

Performance data

Order voltage Coil operating voltage and frequencyAC24V 24V AC 50Hz / 24–26V AC 60HzAC48V 48V AC 50Hz / 48–52V AC 60HzAC100V 100V AC 50Hz / 100–110V AC 60HzAC110V 100–110V AC 50Hz / 110–120V AC 60Hz

AC120V 110–120V AC 50Hz / 120–130V AC 60HzAC200V 200V AC 50Hz / 200–220V AC 60HzAC220V 200–220V AC 50Hz / 220–240V AC 60HzAC240V 220–240V AC 50Hz / 240–260V AC 60Hz

AC380V 346–380V AC 50Hz / 380–420V AC 60HzAC400V 380–400V AC 50Hz / 400–440V AC 60HzAC440V 415–440V AC 50Hz / 440–480V AC 60HzAC500V 480–500V AC 50Hz / 500–550V AC 60Hz

Operating coil• AC coil

Order voltage Coil operating voltageDC12V 12V DCDC24V 24V DCDC48V 48V DCDC60V 60V DC

DC100V 100V DCDC110V 110V DCDC120V 120V DCDC200V 200V DC

DC210V 210V DCDC220V 220V DC

• DC coil

Notes: *1 Coil ratings: 200V 50Hz, 220V 60Hz*2 Us: Coil rated voltage

Type Power consumption (VA) *1 Watt loss (W) Operating voltage range (V) Operating time (ms)Inrush Sealed Pick-up voltage Drop-out voltage Coil ON Coil OFF50/60Hz 50/60Hz 50/60Hz Contact ON Contact OFF

SC-M01 32/36 6/6 1.5/1.6 0.8–1.1Us *2 0.35–0.55Us *1 7–12 6–13SC-M02

Coil characteristics• AC operated

Note: * Us: Coil rated voltage

Type Power consumption (W) Time constant (ms) Operating voltage range (V) Operating time (ms)Pick-up Drop-out Coil ON Coil OFF

Inrush Sealed Sealed voltage voltage Contact ON Contact OFFSC-M01/G 3 3 35 0.8–1.1Us * 0.2–0.4Us * 24–27 5–8SC-M02/GSC-M01/G1 1.2 1.2 55 0.8–1.25Us * 0.2–0.3Us * 25–45 5–9SC-M02/G1SC-M01/G2 2 2 45 0.7–1.25Us * 0.2–0.35Us * 25–45 5–8SC-M02/G2

• DC operated

Note: For G1, G2 types, 24V DC only

Page 42: Manual Motor Starters Magnetic Contactors

Contactors/SC-M series

40

Operating coil Rated capacity (Hp) Rated operational current (A) Type3-phase motor 3-phase motor

AC operated 1.5 1.5 3 3 6.9 6 4.8 3.9 20 1NO SC-M011NC

3 3 5 5 11 9.6 7.6 6.1 20 1NO SC-M021NC

DC operated 1.5 1.5 3 3 6.9 6 4.8 3.9 20 1NO SC-M01/G1NC

3 3 5 5 11 9.6 7.6 6.1 20 1NO SC-M02/G1NC

1.5 1.5 3 3 6.9 6 4.8 3.9 20 1NO SC-M01/G11NC

3 3 5 5 11 9.6 7.6 6.1 20 1NO SC-M02/G11NC

1.5 1.5 3 3 6.9 6 4.8 3.9 20 1NO SC-M01/G21NC

3 3 5 5 11 9.6 7.6 6.1 20 1NO SC-M02/G21NC

Auxiliarycontact

Rated thermal current (A)

DC operated(Low powerconsumption24V DC 1.2W)

DC operated(Low powerconsumption24V DC 2W)

220240V

200V 400480V

550600V

220240V

200V 400480V

550600V

• AC-1 duty / 380 to 440V AC

10

100

20

30

50

1000

200

300

500

10000

2000

3000

5000

1 2 3 20 30 50 100 5 10

SC-M01 SC-M02

Breaking current (A)

Mak

e / B

reak

ope

ratio

ns (

103 )

• AC-3 duty / 380 to 440V AC

10

100

20

30

50

1000

200

300

500

10000

2000

3000

5000

1 2 3 20 30 50 100 5 6A 9A 10

SC

-M01

SC

-M02

Breaking current (A)

Mak

e / B

reak

ope

ratio

ns (

103 )

UL and CSA approved• Contactor ratings Conforming to UL 508, CSA 22.2

• Auxiliary contact ratings

Rated thermal current Making and breaking current (A)(A) AC (Rating code: A600) DC (Rating code: Q600)

Volts Make Break Volts Make Break16 120 60 6 125 0.55 0.55

240 30 3 250 0.27 0.27480 15 1.5 301–600 0.1 0.1600 12 1.2

Electrical durability

Page 43: Manual Motor Starters Magnetic Contactors

Contactors/SC-M series

41

Optional accessories• Auxiliary contact blocksThe front mounting auxiliary contact block allows two or fourauxiliary contacts to be added without increasing the mountingarea of the magnetic contactors. The side mounting auxiliary

The auxiliary contact blocks can be used in combination withthe magnetic contactors listed in the following table. The frontmounting and side mounting auxiliary contact blocks cannotbe used together.

• Coil surge suppression unitThe coil surge suppression unit on to the magnetic contactor.

• Solid-state time-delay unitThe solid-state time-delay unit used with the magneticcontactor works as an on-delay timer.

contact block allows two auxiliary contacts to be added to themagnetic contactors without increasing the depth.

Auxiliary contact block Used withMounting Type SC-M01, SC-M02 SC-M01/G, SC-M02/G SC-M01/G1, SC-M02/G1 SC-M01/G2, SC-M02/G2

1NO 1NC 1NO 1NC 1NO 1NC 1NO 1NCFront 4 4NO SZ-MA40 5NO 4NO+1NC 5NO 4NO+1NC – – – –mounting 3NO+1NC SZ-MA31 4NO+1NC 3NO+2NC 4NO+1NC 3NO+2NC

2NO+2NC SZ-MA22 3NO+2NC 2NO+3NC 3NO+2NC 2NO+3NC1NO+3NC SZ-MA13 2NO+3NC 1NO+4NC 2NO+3NC 1NO+4NC4NC SZ-MA04 1NO+4NC 5NC 1NO+4NC 5NC

2 2NO SZ-MA20 3NO 2NO+1NC 3NO 2NO+1NC – – 3NO 2NO+1NC1NO+1NC SZ-MA11 2NO+1NC 1NO+2NC 2NO+1NC 1NO+2NC 2NO+1NC 1NO+2NC2NC SZ-MA02 1NO+2NC 3NC 1NO+2NC 3NC – – 1NO+2NC 3NC

Side 1 1NO SZ-MAS10 2NO 1NO+1NC 2NO 1NO+1NC – – 2NO 1NO+1NCmounting 1 1NC SZ-MAS01 1NO+1NC 2NC 1NO+1NC 2NC – – 1NO+1NC 2NC

2 2 1NO 2 SZ-MAS10 3NO 2NO+1NC 3NO 2NO+1NC – – 3NO 2NO+1NC1NO+1NC SZ-MAS10 2NO+1NC 1NO+2NC 2NO+1NC 1NO+2NC – – 2NO+1NC 1NO+2NC

+SZ-MAS012 1NC 2 SZ-MAS01 1NO+2NC 3NC 1NO+2NC 3NC – – 1NO+2NC 3NC

No. ofadditionalcontacts

Contactarrangement

Device Operating coil voltage and frequency TypeCR 12–60V AC 50/60Hz SZ-MZ1

72–250V AC 50/60Hz SZ-MZ2Diode 6–250V DC SZ-MZ3

Operation Operating coil voltage and frequency Timing range TypeOn-delay 24–250V AC/DC 50/60Hz 0.2–24s SZ-MT2

0.5–60s SZ-MT5

Mounting No. of contacts Contact arrangement TypeFront mounting 4 4NO SZ-MA40

3NO+1NC SZ-MA312NO+2NC SZ-MA221NO+3NC SZ-MA134NC SZ-MA04

2 2NO SZ-MA201NO+1NC SZ-MA112NC SZ-MA02

Side mounting 1 1NO SZ-MAS101NC SZ-MAS01

Side mountingSZ-MAS01

AF01-25

Front mountingSZ-MA22

AF01-21

Coil surge suppression unitSZ-MZ2

AF01-24 AF01-23

Solid-state time-delay unitSZ-MT5

Page 44: Manual Motor Starters Magnetic Contactors

Contactors/SC-M series

42

Dimensions, mm• Non-reversing/AC operatedSC-M01, SC-M02

1NO

1NC

1/L1 3/L2 5/L3 13

1/L1 3/L2 5/L3 21

2/T1 4/T2 6/T3 14

2/T1 4/T2 6/T3 22

A1

A2

A1

A2

Mounting hole2-M4

Use the two mounting holes on a diagonalline 1 or 2 to mount a contactor.

21

56

7.5

7.6 8.8

4824.3

45(9.8)*2 (9.8)*2

5

4

42.3

Coil terminalM3.5

Panel drillingAux.terminalM3.5

Main terminalM3.5

(37.5)*1

35

40

67(Mounting rail height 15)

Mass: 0.17kg

*1 Front mounting aux. contact block*2 Side mounting aux. contact block

Aux. contact

Wiring diagrams

• Non-reversing/DC operatedSC-M01/G, M01/G1, M01/G2SC-M02/G, M02/G1, M02/G2

Mounting hole2-M4

Panel drillingCoil terminalM3.5

Aux.terminalM3.5

Main terminalM3.5

Mass: 0.23kg

*1 Front mounting aux. contact block*2 Side mounting aux. contact block

1NO

1NC

1/L1 3/L2 5/L3 13 A1

A2 2/T1 4/T2 6/T3 14

1/L1 3/L2 5/L3 21

2/T1 4/T2 6/T3 22

A1

A2

21

68

7.5

7.6 8.8

4824.3

45(9.8)*2 (9.8)*2

54

79(Mounting rail height 15)

54.3

(37.5)*1

3540

Use the two mounting holes on a diagonalline 1 or 2 to mount a contactor.

Aux. contact

• Auxiliary contact blocks/Front mountingSZ-MA40, MA31, MA22, MA13, MA04

45

32.5

37.5

10.8

7.6

Aux.terminalM3.5

Mass: 40g

SZ-MA20, MA11, MA02 45

32.5

37.5

10.8

7.6

M3.5Aux. terminal

Mass: 30g

53 63 73 83

54 64 74 84

53 61 73 83

54 62 74 84

53 61 71 83

54 62 72 84

53 61 71 81

54 62 72 82

51 61 71 81

52 62 72 82

4NO

4NC

3NO+1NC

1NO+3NC

2NO+2NC

53 63

54 64

53 61

54 62

51 61

52 62

2NO 1NO+1NC

2NC

Page 45: Manual Motor Starters Magnetic Contactors

Contactors/SC-M series

43

Dimensions, mm• Aux. contact blocks (Side mounting)SZ-MAS10, MAS01

46

7.6

9.8 45 9.8

24.3

56Aux. terminalM3.5

Mass: 18g

• Coil surge suppression unitSZ-MZ1, MZ2, MZ3

21.5

9

17.5

77.5 (SC-M01, M02)89.5 (SC-M01/G, M02/G)

Mass: 5g

• Solid-state time-delay unitSZ-MT2, MT5

88 (SC-M01, M02)100 (SC-M01/G, M02/G)

4532

18

Mass: 38g

Standard operating conditions

Ambienttemperature

HumidityAltitudeAtmosphere

VibrationShockMountingMounting angle

Standard

Operating: –5 to 55˚CNo sudden temperature changes resulting in condensation or icing (The average temperature over a 24-hour period must not exceed 35˚C)

Storage: –40 to 65˚C45 to 85%RH2000m or lowerNo excessive dust, smoke, corrosive gases, flammable gases, steam, or salt.10 to 55Hz 15m/s2

50m/s2

Screw mounting, 35mm-wide top hat rail (DIN)

IEC 60947-4-1, EN 60947-4-1, VDE 0660 JIS C 8201-4-1, UL 508, CSA C22.2 TÜV (EN60947-4-1)

30˚30˚ 30˚30˚

Wiring diagramsAux. contact

63

64

61

62

53

54

51

52

• Mounted on the right side

1NO 1NC

• Mounted on the left side

1NO 1NC

Internal circuit

A1

A2

+A1

-A2

• Built-in CR • Built-in diode

Internal circuit

L2

L1

A1

A2

1314

Wiring

Terminal screwConnectable wire sizeApplicable round crimp terminalTightening torque

M3.51.25 to 2mm2

(ø1.2 to 2mm)7.5mm (R2-3.5)0.8 to 1.0N·m

Page 46: Manual Motor Starters Magnetic Contactors

Contactors/SC-M series

44

Applicable contactor Operation Type Aux. Trip No. of Power Provided functionNon-reversing *1 contact category heater consumption

arrangement elements per element

SC-M01, M01/G, M01/G1 Standard TK-M0 1b INC 10A 3 2.3 VA

SC-M01/G2 operation

SC-M02, M02/G, M02/G1 Quick TK-M0Q 1b INC 5 *2 3 2.3 VA

SC-M02/G2 operation

Type number nomenclature

TK-M0 3A 1b

TK-M series with phase-loss protective device Features

• This relay protects motor windings from burning due tooverloads, locked rotor currents, or phase-loss.

• A finely divided scale for the current adjustment dial enableseasy and exact current settings.

• Operating status can be visually checked with ease.• The reset method after tripping can be set either manually

or automatically.• By mounting an auxiliary contact block, 1NO+1NC auxiliary

contact arrangement is possible. In this case, thermaloverload relay cannot be used with automatic reset.

• Test buttons can be pressed or released to turn the NCcontact (terminal No. 95 and 96) OFF and ON.

• Adding the optional accessories (the base unit and inputterminal) enables separate-mounting types of the thermaloverload relays.

TK-M0

AF00-179

Ordering informationSpecify the following :1. Type number

Thermal overload relays

Overload, phase-loss protectionAmbient temperature compensationManual/auto reset selectableManual trip mechanismTrip indicator

Auxiliary contact arrangement1b: 1NC

Ampere setting range ordercurrentSee the table above0.11A: 0.11–17

7.5A: 7.5–10.5

OperationM0: Standard operationM0Q: Quick operation

• Ampere setting rangeStandard operation type

Ampere setting range Order current Ampere setting Order current(A) (A)0.11–0.17 0.11A 1.7–2.4 1.7A0.17–0.26 0.17A 2.2–3.2 2.2A0.26–0.43 0.26A 2.5–4.0 2.5A0.43–0.65 0.43A 3.0–4.7 3A

0.65–1.0 0.65A 4.0–6.3 4A 0.85–1.3 0.85A 5.5–8.0 5.5A1.1–1.6 1.1A 7.5–10.5 7.5A1.35–2.0 1.35A

Ampere setting range Order current(A)1.35–2.0 1.35A1.7–2.4 1.7A2.2–3.2 2.2A3.0–4.7 3A

4.0–6.3 4A5.5–8.0 5.5A7.5–10.5 7.5A

Quick operation type

Types and specifications• Performance

Notes: *1 Replace the mark by the ampere setting range order current. *2 According to JIS C8201-4-1For operating characteristics, see page 45.

• Auxiliary contact ratings

Rated thermal Rated operational current Rated insulation voltagecurrent IEC, JIS UL, CSA rating code IEC UL

AC (AC-15) DC (DC-13) AC DC JIS CSA

6A 120V 3A 24V 0.5A B600 R300 750V 600V220V 3A 48V 0.5A440V 2A 110V 0.2A550V 0.6A 220V 0.1A

Page 47: Manual Motor Starters Magnetic Contactors

Contactors/SC-M series

45

Operating characteristics• Standard operating type/TK-M0

Mean value

10.80.6

0.40.3

10 8 643

2

4030

20

60

2

3

5

810

20

30

50

80

0.8 1 1.5 2 3 4 5 6 7 8 9 10 15

Multiple of setting value x Ie (A)

3-phase cold start

3-phase (hot start)

Single-phase (open-phase) cold start

Sec

ond

Ope

ratin

g tim

eM

inut

e

Note: For auto reset type, same as the standard type.

• Quick operating type/TK-M0Q

Mean value

10.80.6

0.40.3

10 8 643

2

4030

20

60

2

3

5

810

20

30

50

80

0.8 1 1.5 2 3 4 5 6 7 8 9 10 15

Multiple of setting value x Ie (A)

3-phase cold start

3-phase (hot start)

Single-phase (open-phase) cold start

Sec

ond

Ope

ratin

g tim

eM

inut

e

Note: For auto reset type, same as the standard type.

Operating range

0.8 1 1.5 2 3 4 5 6 7 8 9 10 15

10.80.6

0.40.3

10 8 6

43

2

4030

20

60

2

3

5

810

20

30

50

80

Multiple of setting value x Ie (A)

3-phase cold start

3-phase (hot start)

Sec

ond

Ope

ratin

g tim

eM

inut

e

Operating range

0.8 1 1.5 2 3 4 5 6 7 8 9 10 15

10.80.6

0.40.3

10 8 6

43

2

4030

20

60

2

3

5

810

20

30

50

80

Multiple of setting value x Ie (A)

3-phase cold start

3-phase (hot start)

Sec

ond

Ope

ratin

g tim

eM

inut

e

Thermal overload relays

Page 48: Manual Motor Starters Magnetic Contactors

Contactors/SC-M series

46

Optional accessories

• Input terminal for separate mountingType: SZ-MHT

• Base unit for separate mountingThe base unit modifies thermal overload relay to separatemounting types that can be mounted to 35mm-wide top hat rail(DIN) or secured with screws.Type: SZ-MHB

• Auxiliary contact block (1NO)Easily add 1NO auxiliary contact to the thermal overloadrelays. A trip indicator is provided.Type: TZ-MA10

Ratings of auxiliary contact block (1NO)

Rated Rated operational current Rated insulation voltagethermal IEC, JIS UL, CSA rating code IEC ULcurrent AC (AC-15) DC (DC-13) AC DC JIS CSA

6A 220V 1A 48V 0.1A D300 R300 750V 600V440V 0.5A 110V 0.05A

Dimensions, mm• SZ-MHT, SZ-MHB

45

8.7

35.5

44.5

16.7 26

58.3

83.5

36.8

35

40 50 60

Main terminalM3.5SZ-MHT

SZ-MHB

Mounting hole2-M4Mass: SZ-MHT 34g, SZ-MHB 12g

• TZ-MA10

32

1227

.5

5

35

10 1674 2

M3.5Aux. terminalReset button

(Resetting stroke 3.5mm)

97

98

Wiring diagram

Mass: 13g

Dimensions, mmTK-M0, TK-M0Q

Main terminalM3.5

Aux. terminal(95/96)M3.5

Aux. terminal(14/22)M3.5

Reset button(Resetting stroke 3.5mm)

68.5

27.5

11

24.5

21.5

10.7

53 45

101

7

5

13

Mass: 98g

Wiring diagram3-element

96

95 2/T1 4/T2 6/T3

Note on useWhen using a thermal overload relay in combination with acontactor, the terminals are connected as described in 1) and2) below and shown in the following diagram.

1) Connected between the auxiliary terminal (14NO or 22NC)on the load side of the contactor and the junction terminal(14/22) of the thermal overload relay.

2) Connected between the coil terminal (A2) on the load sideof the contactor and the NC contact (96NC) of the thermaloverload relay.

Notes:• When using the thermal overload relay to directly turn OFF the contactor:

Connect the operating coil circuit A1 and 95NC.• When using the thermal overload relay not to directly turn OFF the contactor:

Connect the operating coil circuit A1 and A2/96NC.• To detect the NC contact signal of the thermal overload relay, connect 95NC and

A2/96NC.• The junction terminal 14/22 is not used when installing only the thermal

overload relay.

1L1

2T1

2T1

3L2

4T2

4T2

5L3

6T3

6T3

13NO

14NO

14/22

A1

A2

95NC 98NO

(Aux. 1NO optional)

A2/96NC 97NO

ContactorExamble: NO aux. contact

Thermal overload relay(Aux. 1NC standard)

Thermal overload relays

Input terminal Base unit Aux. contact blockSZ-MHT SZ-MHB TZ-MA10

AF01-26 AF01-181 AF01-27

Page 49: Manual Motor Starters Magnetic Contactors

Contactors/SC-E series

47

SC-E series magnetic contactors Features

• Models SC-E02 to SC-E4 have 3-pole main circuits andcome in three sizes with widths of 43mm (up to 25A), 54mm(up to 50A), and 67mm (up to 80A).

• Models SC-E1 to SC-E7 employ a box type terminal thatallows wires to be connected directly to the main circuit.

• Equipped with a finger-protection terminal structure (IP20)that prevents accidental finger touch to live parts.

• Models SC-E5 to SC-E7 use a SUPER magnet (AC/DC-input/DC-energizing operation) to achieve high operatingreliability.

StandardsIEC 60947-4-1, EN60947-4-1, VDE 0660, JISC 8201-4-1UL 508, CSA C22.2

Types and ratings

SC-E2S SC-E7

AF01-6 AF01-1

Operating coil Rated capacity (kW) Rated operating current (A)3-phase motor AC-3 3-phase motor AC-3 Resistive load AC-1

AC operated 20 20 20 – SC-E0220 20 20 – SC-E03

25 25 25 – SC-E0432 32 32 – SC-E0550 50 50 – SC-E160 60 60 – SC-E265 65 65 – SC-E2S

100 100 100 – SC-E3105 105 105 – SC-E4

AC/DC 150 150 150 2NO+2NC SC-E5operated 150 150 150 2NO+2NC SC-E6

200 200 200 2NO+2NC SC-E7DC operated 20 20 20 – SC-E02/G

20 20 20 – SC-E03/G25 25 25 – SC-E04/G32 32 32 – SC-E05/G50 50 50 – SC-E1/G60 60 60 – SC-E2/G65 65 65 – SC-E2S/G

100 100 100 – SC-E3/G105 105 105 – SC-E4/G

Note : Ratings conform to IEC 60947-4-1

Aux. contactarrangement

Contactortype

Rated thermal current(A)

380440V

200240V

200240V

91218253240506880

105125150

91218253240506880

380440V

91218253240506580

105125150

91218253240506580

600690V

5799

15192638446472

1035799

1519263844

200240V2.2345.57.5

111518.5223037452.2345.57.5

111518.522

380440V45.57.5

111518.522304055607545.57.5

111518.5223040

500550V45.57.5

111518.525373755607545.57.5

111518.5253737

600690V45.57.57.5

111522303755609045.57.57.5

1115223037

500550V

79

131724293860608590

12079

13172429386060

Frame size Making current (A) Breaking current (A) Operating cycles Durability (operations)220V 440V 220V 440V per hour Electrical Mechanical

SC-E02 108 108 90 90 1800 2 million 10 millionSC-E03 144 144 120 120 1800 1.5 million 10 million

SC-E04 216 216 180 180 1800 1.5 million 10 millionSC-E05 250 250 200 200 1200 1.5 million 10 million

SC-E1 384 384 320 320 1200 1.5 million 10 millionSC-E2 480 480 400 400 1200 1.5 million 10 million

SC-E2S 500 500 400 400 1200 1.5 million 10 millionSC-E3 816 780 680 650 1200 1.5 million 5 million

SC-E4 816 800 680 650 1200 1 million 5 millionSC-E5 1260 1260 1050 1050 1200 1 million 5 million

SC-E6 1500 1500 1250 1250 1200 1 million 5 millionSC-E7 1800 1800 1500 1500 1200 1 million 5 million

Performance data

Page 50: Manual Motor Starters Magnetic Contactors

Contactors/SC-E series

48

Order voltage Coil operating voltage and frequencyAC24V 24V AC 50Hz / 24–26V AC 60HzAC48V 48V AC 50Hz / 48–52V AC 60HzAC100V 100V AC 50Hz / 100–110V AC 60HzAC110V 100–110V AC 50Hz / 110–120V AC 60Hz

AC120V 110–120V AC 50Hz / 120–130V AC 60HzAC200V 200V AC 50Hz / 200–220V AC 60HzAC220V 200–220V AC 50Hz / 220–240V AC 60HzAC240V 220–240V AC 50Hz / 240–260V AC 60Hz

AC380V 346–380V AC 50Hz / 380–420V AC 60HzAC400V 380–400V AC 50Hz / 400–440V AC 60HzAC440V 415–440V AC 50Hz / 440–480V AC 60HzAC500V 480–500V AC 50Hz / 500–550V AC 60Hz

• AC/DC coil (SUPER MAGNET), SC-E5 to SC-E7Order voltage Coil operating voltage and frequency24V 24–25V AC 50/60Hz, 24V DC48V 48–50V AC 50/60Hz, 48V DC

100V 100–127V AC 50/60Hz, 100–120V DC *1

200V 200–250V AC 50/60Hz, 200–240V DC *2

400V 380–450V AC 50/60Hz500V 460–575V AC 50/60HzNotes: • Other voltages are available in 24 to 575V AC (24 to 240V DC) on request.

*1 The coil voltage from DC power supply with single-phase full-waverectification will be 100–110V.*2 The coil voltage from DC power supply with single-phase full-waverectification will be 200–220V.

Operating coil• AC coil, SC-E02 to SC-E4

Order voltage Coil operating voltageDC12V 12V DCDC24V 24V DCDC48V 48V DCDC60V 60V DC

DC100V 100V DCDC110V 110V DCDC120V 120V DCDC200V 200V DC

DC210V 210V DCDC220V 220V DC

• DC coil, SC-E02/G to SC-E4/G

Ordering informationSpecify the following :1. Type number2. Operating coil order voltage3. Auxiliary contact arrangement

• DC operatingFrame size Power consumption (VA) Time constant Pick-up voltage (V) Drop-out voltage (V) Operating time (ms)

Inrush Sealed (ms) 200V DC 200V DC Coil ON Coil OFF200V 200V Sealed Contact ON Contact OFF

E02/G to E05/G 7 7 50 92–130 30–60 45–49 10–26E1/G to E2S/G 9 9 60 80–120 30–70 40–50 8–17E3/G, E4/G 12 12 70 80–120 24–60 60–70 14–21E5 90 2.8 1 140–160 40–100 35–41 26–32E6, E7 225 3.2 1 140–160 40–100 28–34 27–33

Frame size Power consumption (VA) Power loss (W) Pick-up voltage (V) Drop-out voltage (V) Operating time (ms)Inrush Sealed 200V 220V 200V 220V 200V 220V Coil ON Coil OFF200V 50Hz 200V 50Hz 50Hz 60Hz 50Hz 60Hz 50Hz 60Hz Contact ON Contact OFF

E02 to E05 90 9 2.7 2.8 105–136 116–146 75–106 88–120 9–20 5–16E1 to E2S 120 12.7 3.6 3.8 110–130 120–140 75–105 85–115 10–17 6–13E3, E4 180 13.3 4.5 5 115–135 130–150 85–110 100–125 10–18 8–18E5 80 4 3.2 3.6 140–150 140–150 60–100 60–100 39–45 27–33E6, E7 190 4.9 3.4 3.7 140–150 140–150 60–100 60–100 31–37 30–36

Coil characteristics• AC operating

Note: Other voltages are available in 24 to 600V AC on request.

Note: Other voltages are available in 12 to 250V DC on request.

Page 51: Manual Motor Starters Magnetic Contactors

Contactors/SC-E series

49

Auxiliary contact ratingsBased on IEC 60974-4-1, EN 60947-4-1, JIS C 8201-4-1Frame size Rated insulation Rated thermal Making and Rated operational current (A) Minimum operating

voltage (V) current (A) breaking capacity AC DC voltage and currentat AC (A) Voltage AC-15 Voltage DC-13

Ind. load Ind. loadE02 to E4 – – – – – –E02/G to E4/GE5 to E7 690 10 120V 60 120V 6 24V 3 5V DC, 3mA

220V 30 220V 3 48V 1.5440V 15 440V 1.5 110V 0.55600V 12 600V 1.2 220V 0.27

Types and ratings for UL and CSA

Operating coil Rated capacity (Hp) Rated operating current (A) Type3-phase motor 3-phase motor

AC operated 600 2 2 5 5 7.8 6.8 7.6 6.1 20 SC-E023 3 7.5 7.5 11 9.6 11 9 20 SC-E035 5 10 10 17.5 15.2 14 11 25 SC-E045 7.5 15 15 17.5 22 21 17 32 SC-E057.5 10 25 25 25.3 28 34 27 50 SC-E1

10 15 30 30 32.2 42 40 32 60 SC-E215 20 30 30 48.3 54 40 32 65 SC-E2S20 25 50 50 62.1 68 65 52 100 SC-E325 30 50 50 78.2 80 65 52 105 SC-E4

AC/DC 600 30 30 60 75 92 80 77 77 150 SC-E5operated 40 40 75 100 119.6 104 96 99 150 SC-E6

50 50 100 125 149.5 130 124 125 200 SC-E7DC operated 600 2 2 5 5 7.8 6.8 7.6 6.1 20 SC-E02/G

3 3 7.5 7.5 11 9.6 11 9 20 SC-E03/G5 5 10 10 17.5 15.2 14 11 25 SC-E04/G5 7.5 15 15 17.5 22 21 17 32 SC-E05/G7.5 10 25 25 25.3 28 34 27 50 SC-E1/G

10 15 30 30 32.2 42 40 32 60 SC-E2/G15 20 30 30 48.3 54 40 32 65 SC-E2S/G20 25 50 50 62.1 68 65 52 100 SC-E3/G25 30 50 50 78.2 80 65 52 105 SC-E4/G

Rated thermal current (A)

Rated insulation voltage (V)

220240V

200V 400480V

550600V

220240V

200V 400480V

550600V

Frame size Rated insulation Rated thermal Making and breaking current (A)voltage (V) current (A) AC (rating code A600) DC (rating code Q300)

Voltage Making Breaking Voltage Making BreakingE02 to E4 – – – – – – – –E02/G to E4/GE5 to E7 600 10 120V 60 6 125V 0.55 0.55

240V 30 3 250V 0.27 0.27480V 15 1.5600V 12 1.2

Auxiliary contact ratings for UL and CSA

Page 52: Manual Motor Starters Magnetic Contactors

Contactors/SC-E series

50

Electrical durability• AC-3 duty / SC-E02 to SC-E05

1 2 3 20 30 50 100 200 300 500 1000105

380 - 440V

200 - 240V

10

100

20

30

50

1000

200

300

500

10000

2000

3000

5000

Breaking current (A)

SC

-E02

SC

-E05

SC

-E04

SC

-E03

9A 12A

18A

25A

10

100

20

30

50

1000

200

300

500

10000

2000

3000

5000

200 - 240V 380 - 440V

4kW

5.5k

W

7.5k

W

11kW

2.2k

W

3kW

4kW

5.5k

W

3-phase motor capacity (kW)and full-load current (A)

Mak

e/br

eak

oper

atio

ns (

103 )

• AC-3 duty / SC-E1 to SC-E7

10 20 30 200 300 500 1000 2000 3000 5000 1000010050

200 - 240V

380 - 440V

10

100

20

30

50

1000

200

300

500

10000

2000

3000

5000

SC

-E1

SC

-E2

SC

-E2S

32A

40A

50A

65A

80A

105A

150A

10

100

20

30

50

1000

200

300

500

10000

2000

3000

5000

200 - 240V 380 - 440V

15kW

11kW

15kW

18.5

kW

7.5k

W

18.5

kW

30kW

40kW

55kW

75kW

60

kW

22kW

125A

22kW

30kW

37kW

45

kW

SC

-E7

SC

-E3

SC

-E4

SC

-E5

SC

-E6

Breaking current (A)3-phase motor capacity (kW)and full-load current (A)

Mak

e/br

eak

oper

atio

ns (

103 )

• AC-1 duty / SC-E02 to SC-E7

32A

20A

60A

100A

150A

50A

25A

65A

105A

200A

100

1000

200

300

500

10000

2000

3000

5000

100

1000

200

300

500

2000

3000

5000

200 - 240V

1 2 3

SC

-E02

SC

-E03

SC

-E05

SC

-E04

SC

-E1

SC

-E2

SC

-E2S

380 - 440V

SC

-E3

SC

-E4

SC

-E5

SC

-E6

SC

-E7

20 30 50 100 200 300 500 1000105

10000

Breaking current (A)

Mak

e/br

eak

oper

atio

ns (

103 )

Page 53: Manual Motor Starters Magnetic Contactors

Contactors/SC-E series

51

Optional accessories• Auxiliary contact blocks with terminal coversThe front mounting auxiliary contact block allows two or four auxiliary contacts to beadded without increasing the mounting area of the magnetic contactors. The sidemounting auxiliary contact block allows two auxiliary contacts to be added to themagnetic contactors without increasing the depth.

Applicable contactor Mounting No. of contacts Contact arrangement TypeSC-E02 to E4 Front mounting 4 4NO SZ-A40/T

3NO+1NC SZ-A31/T2NO+2NC SZ-A22/T

2 2NO SZ-A20/T1NO+1NC SZ-A11/T2NC SZ-A02/T

SC-E02 to E4 Side mounting 2 1NO+1NC SZ-AS1/TSC-E5, E6, E7 2 1NO+1NC SZ-AS2/T

• Main circuit surge suppression unitsWhen contactor is energized or de-energized, a surge voltage is generated frommotor circuit. This unit suppresses this surge voltage and protects electronicequipment from malfunction or damage.

Applicable Mounting Rated voltage CR constant Applicable Typecontactor and frequency 3-phase motorSC-E02 to E05 Front mounting 250V AC C=0.22µF 200–240V AC SZ-ZM1E

Side mounting 50/60Hz R=100 0.1–5.5kW SZ-ZM2E

SC-E1 to E4 Front mounting 250V AC C=0.33µF 200–240V AC SZ-ZM3ESide mounting 50/60Hz R=47 0.1–22kW SZ-ZM4E

• Coil surge suppression unitsThis unit suppresses surge voltage due to contactor ON-OFF operations, and can beeasily connected to contactor coil terminals.

Applicable contactor Operating Device Operation TypeAC operated DC operated coil voltage indicatorSC-E02 to E05 SC-E02/G to E05/G 24–48V AC/DC Varistor – SZ-Z1

100–250V AC/DC – SZ-Z2– 380–440V AC – SZ-Z3

SC-E02 to E05 SC-E02/G to E05/G 24–48V AC/DC Red LED SZ-Z6100–250V AC/DC Red LED SZ-Z7

SC-E1 to E4 SC-E1/G to E4/G 24–48V AC/DC – SZ-Z31100–250V AC/DC – SZ-Z32

– 380–440V AC – SZ-Z33

SC-E02 to E05 SC-E02/G to E05/G 24–48V AC/DC CR – SZ-Z4100–250V AC/DC – SZ-Z5

SC-E02 to E05 SC-E02/G to E05/G 24–48V AC/DC Red LED SZ-Z8100–250V AC/DC Red LED SZ-Z9

SC-E1 to E4 – 24–48V AC – SZ-Z34100–250V AC – SZ-Z35

– SC-E1/G to E4/G 24–48V DC – SZ-Z36100–250V DC – SZ-Z37

Main circuit surge suppression units

Contact ratings• Based on IEC and JISRated Making and Rated operational current (A)thermal breaking AC DCcurrent (A) capacity Voltage AC-15 Voltage DC-13

at AC (A) Ind. load Ind. load10 120V 60 120V 6 24V 3 5V DC

220V 30 220V 3 48V 1.5 3mA440V 15 440V 1.5 110V 0.55600V 12 600V 1.2 220V 0.27

• Based on UL and CSARated Making and breaking current (A)thermal AC (rating code A600) DC (rating code Q300)current (A) Volts Making Breaking Volts Making Breaking10 120V 60 6 125V 0.55 0.55

240V 30 3 250V 0.27 0.27480V 15 1.5600V 12 1.2

SZ-A11/TAF88-080

SZ-A22/TKK02-081

Front mounting

Side mounting

SZ-AS1/TSZ-AS2/T

Side mountingSZ-ZM4E

Front mountingSZ-ZM1E

CRSZ-Z4

Coil surge suppression unit

AF88-766

KK01-090

KK02-079

KK02-077

Minimumoperatingvoltage andcurrent

Page 54: Manual Motor Starters Magnetic Contactors

Contactors/SC-E series

52

Dimensions, mm• Non-reversing/AC operatedSC-E02, E03, E04, E05 Panel drilling

34

13

60

(48

to)5

2

35

18.5

(to

20.5

)

14.543

804920

(28)

8.56181

91(68)

10.5

*1

Mounting hole 2-M4

(Rail height 15)

*2

*1*2 Main terminal M4

Coil terminal M3.5

2

1

Mass: 0.33kg

SC-E1, E2, E2S106 (Rail height 15)

18.5

90

(28)

65.596

80

45(38 to 46)

45

75

16.5

57

5410.5

9.5

5

(79)

2

2

1

Panel drilling

Mounting hole 2-M4

Main terminal

Coil terminal M3.5

*1

*1

*2

*2

Mass : 0.58kg

SC-E3, E4

9013

72.5

20.5

7719

.511

2

(28)

10.5 67

(55 to)60

(54 to)60

121 (Rail height 15)111

2.5(91)

2

1

Panel drilling

Mounting hole 2-M4

Main terminal

Coil terminal M3.5

*2

*2*1

*1

Mass: 1.1kg

SC-E5

75

7732.7 70

132

88

32

155

13.5

129

(113)4 Auxiliary

terminalM3.5

Panel drilling

Mounting hole 2-M4

Main terminal

Coil terminal M3.5*1

Mass: 2.0kg

*1 Side mounting aux. contact block*2 Front mounting aux. contact block

Wiring diagrams

*1*1

6/T3 4/T2 2/T1

53 61 1/L1 3/L2 5/L3 83 71

A1 A2

72846254

*1 In case of aux. contact 2NO+2NC

*1 In case of aux. contact 2NO+2NC

*1*1

6/T3 4/T2 2/T1

53 61 1/L1 3/L2 5/L3 83 71

A1 A2

72846254

*1 In case of aux. contact 2NO+2NC

*1*1

6/T3 4/T2 2/T1

53 61 1/L1 3/L2 5/L3 83 71

A1 A2

72846254

*1 In case of aux. contact 4NO+4NC

6/T3 4/T2 2/T1

*1

53 61 13 21 1/L1 3/L2 5/L3 43 31 83 71A1 A2

7284324422146254

*1

Use the two mounting holes on a diagonal line or to mount contactor : 35 60 : 34 (48 to) 52

Use the two mounting holes on a diagonal line or to mount contactor : 45 75 : 45 (38 to 46) 80

Use the two mounting holes on a diagonal line or to mount contactor : (55 to) 60 90 : (54 to) 60 90

Page 55: Manual Motor Starters Magnetic Contactors

Contactors/SC-E series

53

Dimensions, mm• Non-reversing/AC operatedSC-E6

(80 to)90

110

3216

914

313

.510038.8

13877 (125)

4 AuxiliaryterminalM3.5

Panel drilling

Mounting hole 2-M5

Main terminal

Coil terminal M3.5*1

Mass: 2.6kg

SC-E7

35

140

38.876.8

146

14.5

175

(140)115 (80 to)90

110

AuxiliaryterminalM3.5

Panel drilling

Mounting hole 2-M5

Main terminal

Coil terminal M3.5

*1

Mass: 2.9kg

• Non-reversing/DC operatedSC-E02/G, E03/G, E04/G, E05/G Panel drilling

Mounting hole2-M4

Main terminal M4

Coil terminal M3.5

*1

*1

*2

*2

(28)

8.588

108118 (Rail height 15)

13

43

804920

(68)

10.5

34

60

(48

to)5

2

35

18.5

(to

20.5

)

14.5

2

1

Mass: 0.59kg

SC-E1/G, E2/G, E2S/G130 (Rail height 15)

18.5

90

(28)

16.5

57

10.5

121.591

254

(79)

5 9.5

75

45

45(38 to 46)

80

1

2

Panel drilling

Mounting hole2-M4

Main terminal

Coil terminal M3.5

*2

*2

*1

*1

Mass: 0.79kg

*1 Side mounting aux. contact block*2 Front mounting aux. contact block

Wiring diagrams

*1 In case of aux. contact 4NO+4NC

6/T3 4/T2 2/T1

*1

53 61 13 21 1/L1 3/L2 5/L3 43 31 83 71A1 A2

7284324422146254

*1

*1 In case of aux. contact 4NO+4NC

6/T3 4/T2 2/T1

*1

53 61 13 21 1/L1 3/L2 5/L3 43 31 83 71A1 A2

7284324422146254

*1

*1*1

6/T3 4/T2 2/T1

53 61 1/L1 3/L2 5/L3 83 71

A1 A2

72846254

*1 In case of aux. contact 2NO+2NC

*1 In case of aux. contact 2NO+2NC

*1*1

6/T3 4/T2 2/T1

53 61 1/L1 3/L2 5/L3 83 71

A1 A2

72846254

Use the two mounting holes on a diagonal line or to mount contactor : 35 60 : 34 (48 to) 52

Use the two mounting holes on a diagonal line or to mount contactor : 45 75 : 45 (38 to 46) 80

Page 56: Manual Motor Starters Magnetic Contactors

Contactors/SC-E series

54

Dimensions, mm• Non-reversing/DC operatedSC-E3/G, E4/G

20.5

7719

.511

2

(28)

91.5130

140 (Rail height 15)

10.5 2.5 67(91) (54 to)60

(55 to)60

1390

1

2

Panel drilling

Mounting hole2-M4

Coil terminal M3.5

*2

*2

*1

*1

Mass: 1.4kg

Main terminal

• Auxiliary contact blocks/Front mountingSZ-A40/T, A31/T, A22/T, A20/T, A11/T, A02/T for SC-E02 to E4

5 25 431011

7.7

1024

7.7

49

M3.5 M3.5

28 49 28

Approx3

AC Approx3

B

Contactor with aux. contact blockA

B

SZ-A40/T, A31/T, A22/T Mass: 36gSZ-A20/T, A11/T, A02/T Mass: 20g

• Auxiliary contact blocks/Side mountingSZ-AS1/T, for SC-E02 to E4

284359.5

7.712 7.5

45

M3.5

A

B

C12 12D

Contactor with aux. contact block

Mass: 28g

SZ-AS2/T, for SC-E5 to E7

C12 12

A

B

64.5

127.7

M3.5

2847

747.5

Contactor with aux. contact block

D

Mass: 33g

TypeSC-E02, E03, E04, E05SC-E1, E2, E2SSC-E3, E4

A435467

B 80 90112

C109124139

TypeSC-E02, E03, E04, E05SC-E1, E2, E2SSC-E3, E4

A687991

B 80 90112

C 81 96111

D435467

TypeSC-E5SC-E6SC-E7

A113125140

B155169175

C132138140

D 88100115

Wiring diagrams

53 63 73 83

54 64 74 84

53 61 73 83

54 62 74 84

53 61 71 83

54 62 72 84

4NO

3NO+1NC

2NO+2NC

53 63

54 64

53 61

54 62

51 61

52 62

2NO

1NO+1NC

2NC

1NO+1NC

1NO+1NC

53 61

54 62

71 83

72 84

Mounted on right side

Mounted on left side

53 61

54 62

71 83

72 84

Mounted on right side

Mounted on left side

Use the two mounting holes on a diagonal line or to mount contactor : (55 to) 60 90 : (54 to) 60 90

*1 In case of aux. contact 2NO+2NC

*1*1

6/T3 4/T2 2/T1

53 61 1/L1 3/L2 5/L3 83 71

A1 A2

72846254

*1 Side mounting aux. contact block*2 Front mounting aux. contact block

Page 57: Manual Motor Starters Magnetic Contactors

Contactors/SC-E series

55

Dimensions, mm• Main circuit surge suppression units

TypeSC-E02+SZ-ZM1ESC-E03+SZ-ZM1ESC-E04+SZ-ZM1ESC-E05+SZ-ZM1ESC-E1+SZ-ZM3ESC-E2+SZ-ZM3ESC-E2S+SZ-ZM3ESC-E3+SZ-ZM3ESC-E4+SZ-ZM3E

A43

54

67

B 80

90

112

C121

136

151

344.

5

4345

27

344.

5

4345

27

A

B

C Min.5

45

34

SZ-ZM3E

SZ-ZM1E Contactor with surge suppression unit

Mass: 60g

6022

3739

6022

3739

C A

B

22

39

D

TypeSC-E02+SZ-ZM2ESC-E03+SZ-ZM2ESC-E04+SZ-ZM2ESC-E05+SZ-ZM2ESC-E1+SZ-ZM2ESC-E2+SZ-ZM4ESC-E2S+SZ-ZM4ESC-E3+SZ-ZM4ESC-E4+SZ-ZM4E

A65

76

89

B 80

90

112

C 81

96

111

D43.5

49

55.5

SZ-ZM4E

SZ-ZM2E Contactor with surge suppression unit

Mass: 60g

Connection diagram

531

6

42

Contactor

Thermal overload relay

M

Motor

WVU

Main circuit surge suppression unit

• Coil surge suppression unitsSZ-Z1, Z2, Z3, Z4, Z5

27 10

14

15

26

Mass: 14g

SC-E02 to E05 + SZ-Z1 to Z3(Built-in varistor)

SC-E02 to E05 + SZ-Z4, Z5(Built-in CR)

CR

SZ-Z6, Z7, Z8, Z9

27 10

14

LED LED35

15

Mass: 16g

SC-E02 to E05 + SZ-Z6, Z7(Built-in varistor with operating indicator)

R

SC-E02 to E05 + SZ-Z8, Z9(Built-in CR with operating indicator)

R2

R1C

SZ-Z31, Z32, Z33, Z34, Z35, Z36, Z37

30

3712.526

13.5

Mass: 15g

SC-E1 to E4 + SZ-Z31 to Z33(Built-in varistor)

SC-E1 to E4 + SZ-Z34, Z35(Built-in CR)SC-E1/G to E4/G + SZ-Z36, Z37(Built-in CR)

CR

Page 58: Manual Motor Starters Magnetic Contactors

56

Contactors/SC-E series

Standard operating conditionsThe magnetic contactors are manufactured for use in thestandard operating conditions given in the table at the right.Consult FUJI before using the magnetic contactors in differentconditions.

Wirings• Connection wires and terminal processingBe sure to perform wiring correctly with reference to theconnections diagram. Main terminals for models SC-E02 toSC-E7 are wired using solid wires or stranded wires.Stranded wires or flexible stranded wires can be connectedby twisting them together, crimping a sleeve (ferrule) ontothem before connecting.

• Tightening torqueIf wires are not tightened sufficiently, they may become hot orcome loose and result in a fire, short-circuit, electric shock, orsome other potentially dangerous situation. Be sure to tightenthe wires to the torques specified in the tables below.

• Connectable wire sizes, tightening tools, tightening torquesMain circuit

Contactor typeSolid wire(mm2)Stranded wire(mm2)AWG

Sheath stripping length(mm)Terminal screw sizeTool

Tightening torque (N·m)

OneTwoOneTwoOneTwo

SC-E02, SC-E03, SC-E04, SC-E050.75 to 61 to 4 or 1.5 to 60.75 to 61 to 4 or 1.5 to 618 to 1018 to 12 or 16 to 10

M4+ Phillips screwdriver, H-type, No. 2 (ISO 8764) – Flat-blade screwdriver, 1 5.5 L-type, B (ISO 2830)1.2 to 1.5

11

SC-E74 to 1202.5 to 954 to 9512 to 250MCM28.5

4 to 1202.5 to 954 to 9512 to 250MCM28.5

4 to 1202.5 to 95

4 to 95

12 to 250MCM

10

Contactor type SC-E1, E2, E2S0.75 to 350.75 to 250.75 to 2518 to 215

0.75 to 250.75 to 160.75 to 1618 to 312.5

0.75 to 250.75 to 16

0.75 to 16

18 to 3 + Phillips screwdriver, H-type, No. 2 (ISO 8764) – Flat-blade screwdriver, 1 5.5 L-type, B (ISO 2830)2.51

SC-E3, E41 to 701 to 501 to 5016 to 2/019.5

1 to 501 to 351 to 3516 to 1/016

1 to 501 to 35

1 to 35

16 to 1/0 Hex. wrench 4 (ISO 2936)

82

Tool

Tightening torque (N·m)Self-locking torque (N·m) *2

SC-E5, E62.5 to 702.5 to 502.5 to 5012 to 2/026.5

2.5 to 702.5 to 502.5 to 5012 to 2/026.5

2.5 to 702.5 to 50

2.5 to 50

12 to 2/0

Top-only connection

Bottom-onlyconnection

Top/bottomconnection

Solid or stranded wire (mm2) *1

Flexible stranded wire with sleeve (mm2) *1

Flexible stranded wire without sleeve (mm2) *1

AWGSolid or stripping length (mm)

Single stranded wire (mm2) *1

Flexible stranded wire with sleeve (mm2) *1

Flexible stranded wire without sleeve (mm2) *1

AWGSheath stripping length (mm)

Solid or stranded wire (mm2) *1

Flexible stranded wirewith sleeve (mm2) *1

Flexible stranded wirewithout sleeve (mm2) *1

AWG

Top/bottomTop/bottom

Top/bottom

Top/bottom

Operating: –5 to 55˚CNo sudden temperature changes resulting in condensation or icing (The average temperature over a 24-hour period must not exceed 35˚C)

Storage: –40 to 65˚C45 to 85%RH2000m or lowerNo excessive dust, smoke, corrosive gases, flammable gases, steam, or salt10 to 55Hz 15m/s2

50m/s2

Screw mounting, 35mm IEC top hat rail mounting (SC-E02 to SC-E4)

IEC 60947-4-1, EN 60947-4-1, VDE 0660 JIS C 8201-4-1, UL 508, CSA C22.2TÜV (EN60947-4-1)

Ambienttemperature

HumidityAltitudeAtmosphere

VibrationShockMounting

Mounting angle

Standard

30˚30˚30˚30˚

Solid or stranded wire (mm2)AWG

Sheath stripping length(mm)

Fork terminalTerminal screw sizeTool

Tightening torque (N·m)

0.75 to 2.5 (ø1 to 1.6)0.75 to 1.5 or 1.5 to 2.518 to 1418 to 14

Max. 7.7mm wide M3.5+ Phillips screwdriver, H-type, No. 2 (ISO 8764) – Flat-blade screwdriver, 1 5.5 L-type, B (ISO 2830)0.8 to 1

OneTwoOneTwo

10

Notes: *1 Stranded wire (0 to 35mm2) consists of 7 wires or less.Stranded wire (38 to 120mm2) consists of 19 wires or less.Flexible stranded wire consists of more number wires than the above.

*2 The tightening bolt must be loosened in order to insert the wire. However, stoploosening the bolt when the anti-drop attachment on the bottom of the boltreaches the top edge of the terminal. If a torque exceeding that given in thetable is applied in this state, the retaining bracket may come loose.

Control circuit

Page 59: Manual Motor Starters Magnetic Contactors

Contactors/SC-E series

57

Thermal overload relays

TK-E series with phase-loss protective device Features

• This relay protects motor windings from burning due tooverloads, locked rotor current, or phase-loss.

• Maintenance and inspection safety has been improved byemploying a finger protection mechanism to cover exposedterminals (conforms to DIN 57106, VDE 0106 Teil 100).

• Isolated NO and NC contacts can be used with differentpotentials.

• A high-precision scale for the current adjustment dial enableseasy and exact current setting.

• The operating status can be visually checked with ease.• The relays can be manually tripped. A trip-free mechanism is

also provided.• Base unit can be added to enable separate-mounting types

of the TK-E02, E2, and E3 models.

TK-E02 TK-E6

AF01-86 AF01-84

Ampere setting range

4–6 5–8 6–9 7–11 9–1312–18

18–26

24–36

32–42

40–5044–54

0.10.130.150.20.240.30.360.480.640.80.951.41.72.22.845679

1216182024283234404445485364658585

110

TK-E02 0.1–0.150.13–0.20.15–0.24 0.2–0.30.24–0.36 0.3–0.450.36–0.540.48–0.720.64–0.96 0.8–1.20.95–1.45 1.4–2.2 1.7–2.6 2.2–3.4 2.8–4.2 4–6 5–8 6–9 7–11 9–13 12–18 16–22

20–25

TK-E3TK-E2 TK-E5 TK-E6, E6H *

45–65

53–80

65–95

85–125110–160

7–11 9–1312–18

18–26

24–3628–40

34–50

45–6548–68

64–8065–95 *85–105 *

18–26

24–3628–40

34–50

45–65

65–9585–105

Order current Thermal overload relay type(A)

Types and specificationsApplicable contactor Type Aux. contact Trip category No. of heater Power consumption Provided functionsNon-reversing (JIS) elements per poleSC-E02, E03, E04, E05 TK-E02 1NO+1NC 10A 3 2.2VA Overload, phase-loss protectionSC-E1, E2, E2S TK-E2 3.8VA Ambient temperature compensationSC-E3, E4 TK-E3 6.6VA Manual/auto reset setectableSC-E5 TK-E5 6.6VA Manual trip mechanismSC-E6, E7 TK-E6 8.0VA Trip indicatorSeparate mounting type TK-E6H

StandardsIEC 60947-4-1, EN60947-4-1VDE 0660, JIS C 8201-4-1UL 508, CSA C22.2TÜV (EN60947-4-1)

Ordering informationSpecify the following:1. Type number2. Order current for ampere setting

range

Note: * Applicable only for separate-mounting type. Not applicable for use in combination with a magnetic contactor.

Page 60: Manual Motor Starters Magnetic Contactors

Contactors/SC-E series

58

Thermal overload relays

Auxiliary contact ratings• Based on JIS and IECType Rated insulation Rated thermal Rated operational current (A) Minimum voltage

voltage (V) current (A) AC DC and currentVoltage AC-15 Voltage DC-13(V) Ind. load (V) Ind. load

TK-E02 690 5 24 3 (0.3) * 24 1.1 (0.3) 3V DC, 5mA100–120 2.5 (0.3) * 100–120 0.28200–240 2 (0.3) * 200–240 0.14380–440 1 (0.3) *500–600 0.6 (0.3) *

TK-E2 690 5 24 3 (0.5) * 24 1.1 (0.3) 3V DC, 5mATK-E3 100–120 2.5 (0.5) * 100–120 0.28TK-E5 200–240 2 (0.5) * 200–240 0.14TK-E6 380–440 1 (0.5) *

500–600 0.6 (0.5) *

Note: * In case of auto reset type NO contact.

• Based on UL and CSA

Type Rated insulation Rated thermal Making and breaking current (A)voltage (V) current (A) AC (rating code B600) DC (rating code R300)

Voltage Making Breaking Voltage Making Breaking(V) (A) (A) (V) (A) (A)

TK-E02 600 5 120 30 3 120 0.22 0.22TK-E2, E3 240 15 1.5 250 0.11 0.11TK-E5 480 7.5 0.75TK-E6 600 6 0.6

Operating characteristics (mean value)• TK-E02 • TK-E2 to E6, E6H

Sec

ond

Min

ute

Reference temperature: 20°C

Multiple of setting value

10.80.6

0.40.3

10 8 643

2

4030

20

60

2

3

5

810

20

30

50

80

0.8 1 1.5 2 3 4 5 6 7 8 9 10 15

Overcurrent (cold start)

Open-phase (cold start)

Overcurrent (hot start)

x Ie (A)

Ope

ratin

g tim

e

Sec

ond

Min

ute

Reference temperature: 20°C

Multiple of setting value

10.80.6

0.40.3

10 8 643

2

4030

20

60

2

3

5

810

20

30

50

80

0.8 1 1.5 2 3 4 5 6 7 8 9 10 15

Overcurrent (cold start)

Open-phase (cold start)

Overcurrent (hot start)

x Ie (A)

Ope

ratin

g tim

e

Page 61: Manual Motor Starters Magnetic Contactors

Contactors/SC-E series

59

Thermal overload relays

Operational accessories• Base units for separate mountingThe base unit modifies thermal overload relays to separatemounting types that can be mounted to 35mm-wide IEC tophat rail or secured with screws.

Applicable thermal overload relay Type

TK-E02 SZ-HCETK-E2 SZ-HDETK-E3 SZ-HEE

• Trip indicatorReports any tripping action at a thermal overload relay throughits LED display.

Applicable thermal Rated voltage Typeoverload relayTK-E02 100–110V AC, 50/60Hz SZ-L100

200–220V AC, 50/60Hz SZ-L200

TK-E2 to TK-E6 100–110V AC, 50/60Hz SZ-L100N2200–220V AC, 50/60Hz SZ-L200N2

• Reset release buttonReset a thermal overload relay from the rear side of the boardor a distant location.

Applicable thermal Load length Typeoverload relay (mm)TK-E02 300 SZ-R1

500 SZ-R2700 SZ-R3

TK-E2 to TK-E6 300 SZ-R4500 SZ-R5700 SZ-R6

Base unitSZ-HDE

Trip indicatorSZ-L200N2

KK01-108 AF00-291

Reset release buttonSZ-R1

Dial coverSZ-DA

AF88-585 AF88-1056

• Dial coverProtects the setting current value of a thermal overload relayfrom being changed unintentionally.

Applicable thermal overload relay Type

TK-E02 to TK-E6 SZ-DA

Page 62: Manual Motor Starters Magnetic Contactors

Contactors/SC-E series

60

Thermal overload relays

TK-E5 On-contactor mounting only

67 83

9.83232

29

4.9

20.5 20.5 13.510.4

6850

59101 5

3.7

76.5

115

105

106

106.

5 235

Main terminalMounting hole2-M4

Aux. terminalM3.5(NO)

Aux. terminalM3.5(NO)

(Resetting stroke: 4mm)

Reset button

Mass: 0.37kg

TK-E6 On-contactor mounting only

Aux. terminalM3.5(NO)

Reset button(Resettingstroke: 4mm)

Aux. terminalM3.5(NO)

Main terminal

107.

577

.5

4.9

32 329.8

43 60

10015

3232 18118

745

A

CB

122

D

35

Mass: 0.71kg

TK-E6H For separate mounting only

248.

5

45.5

14.4

6075

.5

22.432 32

105

1535

32 32 18100

74118 5 Main

terminal

Aux. terminalM3.5(NO)

Mounting hole2-M5

Aux. terminalM3.5(NO)

Reset button(Resetting stroke: 4mm)11

Mass: 0.82kg

Wiring diagrams3-heater element

(NO) (NC)

(NO) (NC)

97 95

98 96 2/T1 4/T2 6/T3

Dimensions, mmTK-E02

28 10 13 7.714

14

3746

.5

53

26.5

A

B

C

77 3D

M3.5(NC)

Aux. terminal

Mainterminal M4

(Resetting stroke: 3mm)

Reset button

M3.5(NO)Aux. terminal

Mass: 0.13kg

TK-E2

Aux. terminalM3.5(NC)

Mainterminal

Reset button(Resetting stroke: 4mm)

M3.5(NO)

A

C

B

59250.5

16.5 16.57.8

67.5

53

16.5

4.9

10.5

54

7.316.5

78.5

27.5

D

Aux. terminal

Mass: 0.25kg

TK-E3

29

20.5 20.5 13.568

10.4

4.9

7660

20.59.8

20.5

55.597.5 5

AB

C

D89

.5

Aux. terminalM3.5(NO)

Reset button

Main terminal

Aux. terminalM3.5(NO)

(Resetting stroke: 4mm)

Mass: 0.34kg

D149149

ContactorSC-E1 to E2SSC-E1/G to E2S/G

A97–

B–123

C63.563.5

D180180

ContactorSC-E3, E4SC-E3/G, E4/G

A107.5–

B–126.5

C79.579.5

C266.5274

ContactorSC-E6SC-E7

A123123

B124129

D4550

ContactorSC-E02 to 05SC-E02/G to 05/G

A80.5–

B–107.5

C4949

D127.5127.5

Page 63: Manual Motor Starters Magnetic Contactors

Contactors/SC-E series

61

Thermal overload relays

Dimensions, mm• Base units for separate mountingSZ-HCE

Mountinghole2-M4

MainterminalM47

67.5

7

8435

3

8 13 1310 5

60

53

51

8

5.5

72

83

47

35

Mass: 55g

SZ-HDE

Mainterminal

Mountinghole2-M4

61

14.2

4.5

90 99

77.316.5 16.510.5

54

4054

8.575.5

99

8.5

100.559

5

Mass: 0.1kg

SZ-HEE

Mainterminal

Mountinghole2-M4

68

510

010

9.5

10.420.5 20.513.5

9

68

5068

8.578

104

8.5

10664

5

16

Mass: 0.15kg

• Trip indicatorsSZ-L100, L200

113.5

26

Approx.4408 3Approx.140

SZ-L100N2, L200N2

Approx.4508

11

26

Approx.250

• Reset release buttonSZ-R1, R2, R3

12 8

Locking nutM10

Resetbutton

L 23.5

6.5

Panel drilling 10.5 to 11

9

TypeSZ-R1SZ-R2SZ-R3

L300500700

SZ-R4, R5, R6

8

6.5

1612

Locking nutM10

Resetbutton

L

9

TypeSZ-R4SZ-R5SZ-R6

L300500700

Panel drilling 10.5 to 11

• Dial coverSZ-DA

2

14

Page 64: Manual Motor Starters Magnetic Contactors

Contactors/SC-E series

62

Thermal overload relays

Standard operating conditionsThe thermal overload relays are manufactured for use in thestandard operating conditions given in the table at the right.Consult FUJI before using the thermal overload relays indifferent conditions.

Wirings• Connection-wires and terminal processingBe sure to perform wiring correctly with reference to theconnections diagram. Main terminals for models TK-E02 toTK-E6 are wired using solid wires or stranded wires.Stranded wires or flexible stranded wires can be connectedby twisting them together, crimping a sleeve (ferrule) ontothem before connecting.

• Tightening torqueIf wires are not tightened sufficiently, they may become hot orcome loose and result in a fire, short-circuit, electric shock, orsome other potentially dangerous situation. Be sure to tightenthe wires to the torques specified in the tables below.

• Connectable wire sizes, tightening tools, tightening torquesMain circuitThermal overload relay typeBase unit typeSolid wire(mm2)Stranded wire(mm2)AWG

Sheath stripping length (mm)Terminal screw sizeTool

Tightening torque [N·m]

TK-E02SZ-HCE0.75 to 41 to 40.75 to 41 to 412 max.12 max.

M4+ Phillips screwdriver, H-type, No. 2 (ISO 8764) – Flat-blade screwdriver, 1 5.5 L-type, B (ISO 2830)1.2 to 1.5

OneTwoOneTwoOneTwo

11

Operating: –5 to 55˚CNo sudden temperature changes resulting in condensation or icing (The average temperature over a 24-hour period must not exceed 35˚C)

Storage: –40 to 65˚C45 to 85%RHNo excessive dust, smoke, corrosive gases, flammable gases, steam, or salt10 to 55Hz 15m/s2

50m/s2

Ambienttemperature

HumidityAtmosphere

VibrationShock

Control circuitSingle stranded wire (mm2)AWG

Sheath stripping length(mm)Fork terminalTerminal screw sizeTool

Tightening torque [N·m(lb·in)]

0.75 to 2.5 (ø1 to ø1.6)0.75 to 1.5 or 1.5 to 2.518 to 1418 to 14

Max. 7.7mm wide (R2-3.5)M3.5+ Phillips screwdriver, H-type, No. 2 (ISO 8764) – Flat-blade screwdriver, 1 5.5 L-type, B (ISO 2830)0.8 to 1

OneTwoOneTwo

10

Thermal overload relay typeBase unit type

Single stranded wire (mm2) *1

Flexible stranded wire with sleeve (mm2) *1

Flexible stranded wire without sleeve (mm2)AWG

TK-E2SZ-HDE0.75 to 220.75 to 220.75 to 224 max.18

+ Phillips screwdriver, H-type, No. 2 (ISO 8764) – Flat-blade screwdriver, 1 5.5 L-type, B (ISO 2830)2.5

TK-E3SZ-HEE1 to 381 to 381.5 to 380 max.21

Hex. wrench 4 (ISO 2936)

6

TK-E5–

TK-E6, E6H–16 to 7016 to 7016 to 703/0 max.23

10

Sheath stripping length (mm)

Tool

Tightening torque (N·m)

Notes: *1 Stranded wire (0 to 25mm2) consists of 7 wires or less.Stranded wire (35 to 120mm2) consists of 19 wires or less.Flexible stranded wire consists of more number wires than the above.

Page 65: Manual Motor Starters Magnetic Contactors

63

Combination Starters

KK02-162 KK02-152

Description• The user can assemble a combination starter by combining a

BM3 series manual motor starter and an SC series magneticcontactor according to the load motor capacity.

• The manual motor starter provides overload, phase-loss, andshort-circuit protections for the motor circuit, andincorporates a dial for flexible adjustment to match the totalload current of the motor.

• The magnetic contactor allows remote ON/OFF operation ofthe motor circuit with high frequency, and features a electricaldurability of one million operations.

• The manual motor starter and magnetic contactor areconnected via link module and mounted to a base plate.

Features• The combination starter consists of a manual motor starter

and magnetic contactor that can be assembled by the user toachieve a compact motor control circuit.

• The combination starter protects the motor from short-circuitand overcurrent accidents in the three-phase motor circuitwithin a range between 15kW at 240V AC and 22kW at 415VAC, up to a current level of 50A.

• The combination starter conforms to IEC 60947 requirementsfor magnetic motor starters and short circuit protective deviceof coordination types 1 and 2, thus greatly reducing thepossibility of an accident spreading to affect other equipment.

• The combination starter can be mounted to IEC top hat railusing the base plate.

• The modular wiring system reduces wiring works, shortensrequired mounting time, and decreases the mounting area.

IEC 60947-4-1

Type 1:Co-ordination requiers that, under short-circuit conditions, thecontactor or starter shall cause no danger to persons or installationand may not be suitable for further service without repair andreplacement of parts.

Type 2:Co-ordination requiers that, under short-circuit conditions, thecontactor or starter shall cause no danger to persons or installationand shall be suitable for further use. The risk of contact welding isrecognized, in which case the manufacturer shall indicate themeasures to be taken as regards the maintenance of the equipment.

Protective coordination between MMSs and contactors

• IEC 60947-4-1 Type 1 The rated conditional short-circuit current Iq=50kA/240V AC, 415V AC

Notes: • The full-load current of each three-phase motor is a reference value. Check the actual full-load current of the motor before use.

Motor capcity and full load current 3-phase200–240V ACCapacity(kW)0.03

0.06

0.12

0.25

0.37

0.75

Manual motor starterType

BM3RSB-P25

BM3RSB-P40

BM3RSB-P63

BM3RSB-001

BM3RSB-001

BM3RSB-1P6

BM3RSB-1P6

BM3RSB-2P5

BM3RSB-004

BM3RSB-004

Magnetic contactorType

SC-M01SC-E02SC-M01SC-E02SC-M01SC-E02SC-M01SC-E02SC-M01SC-E02SC-M01SC-E02SC-M01SC-E02SC-M01SC-E02SC-M01SC-E02SC-M01SC-E02

0.16 to 0.25

0.25 to 0.4

0.4 to 0.63

0.63 to 1.0

0.63 to 1.0

1.0 to 1.6

1.0 to 1.6

1.6 to 2.5

2.5 to 4.0

2.5 to 4.0

69696969696969696969

Base plate

–BZ0BPRE22A–BZ0BPRE22A–BZ0BPRE22A–BZ0BPRE22A–BZ0BPRE22A–BZ0BPRE22A–BZ0BPRE22A–BZ0BPRE22A–BZ0BPRE22A–BZ0BPRE22A

Link module

BZ0LRC09AABZ0LRE22AABZ0LRC09AABZ0LRE22AABZ0LRC09AABZ0LRE22AABZ0LRC09AABZ0LRE22AABZ0LRC09AABZ0LRE22AABZ0LRC09AABZ0LRE22AABZ0LRC09AABZ0LRE22AABZ0LRC09AABZ0LRE22AABZ0LRC09AABZ0LRE22AABZ0LRC09AABZ0LRE22AA

Current(A)0.24

0.37

0.72

1.4

2

3.6

380–415V ACCapacity(kW)0.06

0.09

0.12

0.18

0.25

0.37

0.55

0.75

1.1

1.5

Current(A)0.21

0.31

0.41

0.63

0.8

1.1

1.5

1.9

2.5

3.4

Adjustable current range (A)

Rated operationalcurrent AC-3 (A)

BM3RSB-010 + SC-M02 BM3VHB-050 + SC-E2S

• The above table shows combinations with AC operated type magnetic contactors. The link module will differ if the magnetic contactor is a DC operated type.

Page 66: Manual Motor Starters Magnetic Contactors

64

Combination Starters

• IEC 60947-4-1 Type 1 The rated conditional short-circuit current Iq=50kA/240V AC, 415V AC (Continue)Motor capcity and full load current 3-phase200–240V ACCapacity(kW) –

1.5

2.2

3 4 5.5 7.5

1115

Manual motor starterType

BM3RSB-6P3

BM3RSB-010

BM3RSB-010

BM3RSB-013BM3RHB-020BM3RHB-025BM3RHB-032BM3VHB-032BM3VHB-040BM3VHB-050

Magnetic contactorType

SC-M01SC-E02SC-M02SC-E02SC-M02SC-E02SC-E03SC-E04SC-E05SC-E1

SC-E2SC-E2S

4.0 to 6.3

6.3 to 10

6.3 to 10

9 to 1314 to 2019 to 2524 to 32

28 to 4035 to 50

6 9 9 9 9 912182532

4050

Base plate

–BZ0BPRE22A–BZ0BPRE22A–BZ0BPRE22ABZ0BPRE22ABZ0BPRE22ABZ0BPRE22ABZ0BPRE32ABZ0BPVE51ABZ0BPVE51ABZ0BPVE51A

Link module

BZ0LRC09AABZ0LRE22AABZ0LRC09AABZ0LRE22AABZ0LRC09AABZ0LRE22AABZ0LRE22AABZ0LRE22AABZ0LRE22AABZ0LRE32AABZ0LVE51AABZ0LVE51AABZ0LVE51AA

Current(A) –

6.1

9.2

12162229

3850

380–415V ACCapacity(kW) 2.2

3

4

5.5 7.51115

18.522

Current(A) 4.5

6.5

8

11142128

3545

Adjustable current range (A)

Rated operationalcurrent AC-3 (A)

• IEC 60947-4-1 Type 2 The rated conditional short-circuit current Iq=50kA/240V AC, 415V ACMotor capacity and full load current 3-phase200–240V ACCapacity(kW) 0.03

0.06

0.12

0.25

0.37

0.75 1.5 – 2.2 3 4 5.5

7.5

11

Manual motor starterType

BM3RSB-P25

BM3RSB-P40

BM3RSB-P63

BM3RSB-001

BM3RSB-001

BM3RSB-1P6

BM3RSB-1P6

BM3RSB-2P5

BM3RSB-004

BM3RSB-004BM3RSB-6P3BM3RSB-010BM3RSB-010BM3RSB-013BM3RHB-020BM3RHB-025BM3VHB-025BM3RHB-032BM3VHB-032BM3VHB-040

Magnetic contactorType

SC-M01SC-E02SC-M01SC-E02SC-M01SC-E02SC-M01SC-E02SC-M01SC-E02SC-M01SC-E02SC-M01SC-E02SC-M01SC-E02SC-M01SC-E02SC-E03SC-E04SC-E04SC-E04SC-E05SC-E05SC-E1

SC-E1

SC-E2

0.16 to 0.25

0.25 to 0.4

0.4 to 0.63

0.63 to 1.0

0.63 to 1.0

1.0 to 1.6

1.0 to 1.6

1.6 to 2.5

2.5 to 4.0

2.5 to 4.04.0 to 6.36.3 to 106.3 to 109 to 1314 to 2019 to 25

24 to 32

28 to 40

6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 9 6 912181818252532

32

40

Base plate

–BZ0BPRE22A–BZ0BPRE22A–BZ0BPRE22A–BZ0BPRE22A–BZ0BPRE22A–BZ0BPRE22A–BZ0BPRE22A–BZ0BPRE22A–BZ0BPRE22ABZ0BPRE22ABZ0BPRE22ABZ0BPRE22ABZ0BPRE22ABZ0BPRE22ABZ0BPRE22ABZ0BPRE32ABZ0BPVE51ABZ0BPRE32ABZ0BPVE51ABZ0BPVE51A

Link module

BZ0LRC09AABZ0LRE22AABZ0LRC09AABZ0LRE22AABZ0LRC09AABZ0LRE22AABZ0LRC09AABZ0LRE22AABZ0LRC09AABZ0LRE22AABZ0LRC09AABZ0LRE22AABZ0LRC09AABZ0LRE22AABZ0LRC09AABZ0LRE22AABZ0LRC09AABZ0LRE22AABZ0LRE22AABZ0LRE22AABZ0LRE22AABZ0LRE22AABZ0LRE22AABZ0LRE22AABZ0LRE32AABZ0LVE51AABZ0LRE32AABZ0LVE51AABZ0LVE51AA

Current(A) 0.24

0.37

0.72

1.4

2

3.6 6.1 – 9.2121622

29

38

380–415V ACCapacity(kW) 0.06

0.09

0.12

0.18

0.25

0.37

0.55

0.75

1.1

1.5 2.2 3 4 5.5 7.511

15

18.5

Current(A) 0.21

0.31

0.41

0.63

0.8

1.1

1.5

1.9

2.5

3.4 4.5 6.5 8111421

28

35

Adjustable current range (A)

Rated operationalcurrent AC-3 (A)

Notes: • The full-load current of each three-phase motor is a reference value. Check the actual full-load current of the motor before use.

• The above table shows combinations with AC operated type magnetic contactors. The link module will differ if the magnetic contactor is a DC operated type.

Page 67: Manual Motor Starters Magnetic Contactors

65

Combination Starters

Combinations meeting for UL market• BM3RSB, BM3RHB3-phase motor

0.5

0.75

1.5

3557.5

10

Manual motor starters

BM3RSB-P16

BM3RSB-P25

BM3RSB-P40

BM3RSB-P63

BM3RSB-001

BM3RSB-1P6

BM3RSB-2P5

BM3RSB-004

BM3RSB-6P3

BM3RSB-010

BM3RSB-013BM3RSB-016BM3RSB-020BM3RSB-025BM3RSB-032

Adjustablecurrent range (A)

0.1 to 0.16

0.16 to 0.25

0.25 to 0.4

0.4 to 0.63

0.63 to 1.0

1.0 to 1.6

1.6 to 2.5

2.5 to 4

4 to 6.3

6.3 to 10

9 to 1311 to 1614 to 2019 to 2524 to 32

BM3RHB-P16

BM3RHB-P25

BM3RHB-P40

BM3RHB-P63

BM3RHB-001

BM3RHB-1P6

BM3RHB-2P5

BM3RHB-004

BM3RHB-6P3

BM3RHB-010

BM3RHB-013BM3RHB-016BM3RHB-020BM3RHB-025BM3RHB-032

Magnetic contactor

SC-M01SC-E02SC-M01SC-E02SC-M01SC-E02SC-M01SC-E02SC-M01SC-E02SC-M01SC-E02SC-M01SC-E02SC-M01SC-E02SC-M01SC-E02SC-M02SC-E02SC-E03SC-E04SC-E04SC-E05SC-E1

Base plate

–BZ0BPRE22A–BZ0BPRE22A–BZ0BPRE22A–BZ0BPRE22A–BZ0BPRE22A–BZ0BPRE22A–BZ0BPRE22A–BZ0BPRE22A–BZ0BPRE22A–BZ0BPRE22ABZ0BPRE22ABZ0BPRE22ABZ0BPRE22ABZ0BPRE22ABZ0BPRE32A

Link module

BZ0LRC09AABZ0LRE22AABZ0LRC09AABZ0LRE22AABZ0LRC09AABZ0LRE22AABZ0LRC09AABZ0LRE22AABZ0LRC09AABZ0LRE22AABZ0LRC09AABZ0LRE22AABZ0LRC09AABZ0LRE22AABZ0LRC09AABZ0LRE22AABZ0LRC09AABZ0LRE22AABZ0LRC09AABZ0LRE22AABZ0LRE22AABZ0LRE22AABZ0LRE22AABZ0LRE22AABZ0LRE32AA

2.2

3.2

6

9.615.215.22228

0.75

1

2

3

5

7.510101520

1.6

2.1

3.4

4.8

7.6

1114142127

Rated capacity(HP)220–240V AC

Rated operationalcurrent (A)

Rated operationalcurrent (A)

Rated capacity(HP)440–480V AC

• BM3VSB, BM3VHB3-phase motor

3 3 5 5 7.510101520

Manual motor starters

BM3VSB-010BM3VSB-013BM3VSB-016BM3VSB-020BM3VSB-025BM3VSB-032BM3VSB-040BM3VSB-050BM3VSB-063

Adjustablecurrent range (A)

6.3 to 109 to 1311 to 1614 to 2019 to 2524 to 3228 to 4035 to 5045 to 63

BM3VHB-010BM3VHB-013BM3VHB-016BM3VHB-020BM3VHB-025BM3VHB-032BM3VHB-040BM3VHB-050BM3VHB-063

Magneticcontactor

SC-E1SC-E1SC-E1SC-E1SC-E1SC-E1SC-E2SC-E2SSC-E3

Base plate

BZ0BPVE51ABZ0BPVE51ABZ0BPVE51ABZ0BPVE51ABZ0BPVE51ABZ0BPVE51ABZ0BPVE51ABZ0BPVE51ABZ0BPVE65A

Link module

BZ0LVE51AABZ0LVE51AABZ0LVE51AABZ0LVE51AABZ0LVE51AABZ0LVE51AABZ0LVE51AABZ0LVE51AABZ0LVE65AA

9.6 9.615.215.22228284254

5 7.510101520303040

7.61114142127404052

Rated capacity(HP)220–240V AC

Rated operationalcurrent (A)

Rated operationalcurrent (A)

Rated capacity(HP)440–480V AC

Page 68: Manual Motor Starters Magnetic Contactors

66

Combination Starters

Optional accessories• Link modules

ApplicableMMSBM3R

BM3V

Applicable magnetic contactor

SC-M01, M02SC-M01/G, M02/GSC-E02, E03, E04, E05SC-E02/G, E03/G, E04/G, E05/GSC-E1SC-E1/GSC-E1, E2, E2SSC-E1/G, E2/G, E2S/GSC-E3SC-E3/G

Operatingcoil

ACDCACDCACDCACDCACDC

Mass(g)

25252535456045606580

Type

BZ0LRC09AABZ0LRC09AABZ0LRE22AABZ0LRE22GABZ0LRE32AABZ0LRE32GABZ0LVE51AABZ0LVE51GABZ0LVE65AABZ0LVE65GA(No.KK01-153)

The link module connects the manual motor starter and magnetic contactor electrically and mechanically.

Description

MMSBM3RSB

Link module

ContactorSC-M01, M02

Combinationstarter

MMSBM3RSB

Link module

ContactorSC-E02 to E05

Combinationstarter

Base plate

MMSBM3RHB

Link module

ContactorSC-E04, E05

Combinationstarter

Base plate

• Base platesApplicableMMSBM3R

BM3V

Applicable magnetic contactor

SC-E02, E03, E04, E05SC-E02/G, E03/G, E04/G, E05/GSC-E1SC-E1/GSC-E1, E2, E2SSC-E1/G, E2/G, E2S/GSC-E3SC-E3/G

Operatingcoil

ACDCACDCACDCACDC

Mass(g)

100100160160160160195195

Type

BZ0BPRE22ABZ0BPRE22ABZ0BPRE32ABZ0BPRE32ABZ0BPVE51ABZ0BPVE51ABZ0BPVE65ABZ0BPVE65A(No.KK01-155)

The base plate is a plastic plate to which the combination starter is mounted. The base plate can then be mounted to a panel with screws or to a IEC top hat rail.

Description

Combination starter configurations

• BM3RSB+SC-M01, M02 • BM3RSB+SC-E02 to E05 • BM3RHB+SC-E04, E05

Page 69: Manual Motor Starters Magnetic Contactors

67

Combination Starters

• BM3RHB+SC-E1 • BM3V B+SC-E1 to E2S • BM3V B+SC-E3

Base plate

MMSBM3RHB

Link module

ContactorSC-E1

Combinationstarter

MMSBM3VHBBM3VSB

Link module

ContactorSC-E1 to E2S

Combinationstarter

Base plate

MMSBM3VHBBM3VSB

Link module

ContactorSC-E3

Combinationstarter

Base plate

Note to mount an MMS and contactorWhen the manual motor starter and magnetic contactor areconfigured as a combination starter, the nameplate ends upfacing the wrong direction because the coil terminal of themagnetic contactor faces downward. Use the followingprocedure to turn the nameplate upside down.

For SC-E02 to SC-E05 magnetic contactors• Insert a flat-blade screwdriver between the arc-chamber of

the S phase or V phase and the terminal screw, and lift thearc-chamber to remove it.

• After removing the cover, turn the cover 180 degrees (top tobottom), then re-mount it onto the magnetic contactor.

• Align the cover with the top and bottom terminals and pressit on firmly by hand.

For SC-E1 to SC-E3 magnetic contactors• Use a Phillips screwdriver to remove the two screws

securing the front and back bodies.• Remove the front body and turn it 180 degrees (top to

bottom), then re-mount it with the screws.• Make sure that no foreign matter enters the interior of the

magnetic contactor during this removal/re-mountingprocedure.

Coil terminal

Page 70: Manual Motor Starters Magnetic Contactors

68

Combination Starters

Dimensions, mm• Base platesBZ0BPRE22A

Base platetypeBZ0BPRE32A

Applicable typeMMSBM3RSBBM3RHB

ContactorSC-E1, E1/G

Mounting hole3-M4

55

39 (to 48)8

8

523

5

247

8

8

4012

5

102.

5

4.5

25

1 35mm wide rail (hight 15mm) x 22 75mm wide rail (hight 25mm) x 1

Base platetypeBZ0BPVE65A

Applicable typeMMSBM3VSBBM3VHB

ContactorSC-E3, E3/G

66

260

270

5

9

9 48 (to 56)

4012

5

102.

5

8

Mounting hole3-M4

4

25

1 35mm wide rail (hight 15mm) x 22 75mm wide rail (hight 25mm) x 1

Base platetypeBZ0BPVE51A

Applicable typeMMSBM3VSBBM3VHB

ContactorSC-E1, E2, E2S,E1/G, E2/G, E2S/G

88

4012

5

102.

5

8

247

235

5

8 39 (to 48)55 Mounting hole

3-M4

4.5

25

1 35mm wide rail (hight 15mm) x 22 75mm wide rail (hight 25mm) x 1

BZ0BPRE32A

BZ0BPVE65A

Base platetypeBZ0BPRE22A

Applicable typeMMSBM3RSBBM3RHB

ContactorSC-E02, E03, E04, E05E02/G, E03/G, E04/G, E05/G

Mounting hole3-M4

195

205

45

5

4012

5

7

(26 to)30

57

2

21.3

1 35mm wide rail (hight 15mm) x 2

BZ0BPVE51A

Page 71: Manual Motor Starters Magnetic Contactors

69

Combination Starters

Dimensions, mm• CombinationBM3RSB + SC-M01, M02

+ SC-M01/G, M01/G1, M01/G2+ SC-M02/G, M02/G1, M02/G2

MMSBM3RSB

ContactorsSC-E02/G, E03/G, E04/G, E05/G

Link moduleBZ0LRE22GA

Base plateBZ0BPRE22A

Mass (g)1,065

14.3

6

17.6

5

5

(26 to)3052

138.8

4012

5

162.

8

109.3

129.3

Mounting hole3-M4

13

70

87.396.2

13.5

4555

.2

27

13

195

205

5

45

7

7

5.5

1 35mm wide rail (hight 15mm) x 2

BM3RSB + SC-E02/G to E05/G

MMSBM3RSB

ContactorsSC-E02, E03, E04, E05

Link moduleBZ0LRE22AA

Base plateBZ0BPRE22A

Mass (g)820

14.3

6

17.6

5

5

(26 to)3052

111.8

4012

5

162.

8

82.3

102.3

Mounting hole3-M4

13

70

87.396.2

13.5

4555

.2

27

13

195

205

5

45

7

7

5.5

1 35mm wide rail (hight 15mm) x 2

BM3RSB + SC-E02 to E05

MMSBM3RSB

ContactorsSC-M01, M02SC-M01/G, M01/G1, M01/G2SC-M02/G, M02/G1, M02/G2

Link moduleBZ0LRC09AABZ0LRC09AA

Mass(g)540600

47.5

71

4562.3

273.7

15

54.368

8.8

4514.3 7.15

157.

8

156.

75.

1

613.5

345

47.5

Mounting hole3-M4

135

35

27

135.5

10

Push-in lug *

Spacer * Note: * Dimensions for mounting of an optional push-in lug/BZ0SET and 2-spacer supplied with link module/BZ0LRC09AA, when screw-mounting BM3RSB with SC-M01 or SC-M02.

Page 72: Manual Motor Starters Magnetic Contactors

70

Combination Starters

MMSBM3RHB

ContactorsSC-E02/G, E03/G, E04/G, E05/G

Link moduleBZ0LRE22GA

Base plateBZ0BPRE22A

Mass (g)1,085

14.3

17.6

5

5

(26 to)3052

138.8

4012

5

162.

8

109.3

129.3

Mounting hole3-M4

13

70

100.3

3.3

4555

.2

5.5

195

205

5

45

7

7

1 35mm wide rail (hight 15mm) x 2

115.8

BM3RHB + SC-E02/G to E05/G

MMSBM3RHB

ContactorsSC-E02, E03, E04, E05

Link moduleBZ0LRE22AA

Base plateBZ0BPRE22A

Mass (g)840

14.3

17.6

5

57

(26 to)3052

111.8

4012

5

162.

8

82.3

102.3

Mounting hole3-M4

13

70

100.3

3.3

4555

.2

5.5

195

205

5

45

7

1 35mm wide rail (hight 15mm) x 2

115.8

BM3RHB + SC-E02 to E05

14.3

13.5

45

70

27

135.5

32.4

55

839 (to 48)

523

524

7

8 16.5

185.

1

Mounting hole3-M4

MMSBM3RSB

ContactorsSC-E1/G

Link moduleBZ0LRE32GA

Base plateBZ0BPRE32A

Mass (g)1,360

74.591.8

100.7

8

8116

56.5

4012

510

2.5

162.8146.5 1 35mm wide rail (hight 15mm) x 2

2 75mm wide rail (hight 25mm) x 1

BM3RSB + SC-E1/G

Dimensions, mm• CombinationBM3RSB + SC-E1

Mounting hole3-M4 14.3

613

.545

70

27

135.5

32.4

55

839 (to 48)

523

5

247

8 16.5

185.

1

MMSBM3RSB

ContactorsSC-E1

Link moduleBZ0LRE32AA

Base plateBZ0BPRE32A

Mass (g)1,135

74.591.8100.7

8

890.5

56.5

4012

510

2.5

137.5121 1 35mm wide rail (hight 15mm) x 2

2 75mm wide rail (hight 25mm) x 1

Page 73: Manual Motor Starters Magnetic Contactors

71

Combination Starters

BM3RHB + SC-E1/G

BM3V B + SC-E1, E2, E2S

MMSBM3VSBBM3VHB

ContactorsSC-E1, E2, E2S

Link moduleBZ0LVE51AA

Base plateBZ0BPVE51A

Mass (g)1,580

189.

5

90.5

4012

510

2.5

137.5

63

121

117.5121.5

137

28

16.5

5.5

3.3

456670

Mounting hole3-M4

55

16.5

8 39 (to 48)

235

247

8

8 8

5

1 35mm wide rail (hight 15mm) x 22 75mm wide rail (hight 25mm) x 1

MMSBM3VSBBM3VHB

ContactorsSC-E1/G, E2/G, E2S/G

Link moduleBZ0LVE51GA

Base plateBZ0BPVE51A

Mass (g)1,810

189.

5

116

4012

510

2.5

162.8

63

146.5

117.5121.5

137

28

16.5

5.5

3.3

456670

Mounting hole3-M4

55

16.5

8 39 (to 48)

235

247

8

8 8

5

1 35mm wide rail (hight 15mm) x 22 75mm wide rail (hight 25mm) x 1

558 39 (to 48)

14.3

22.5

5.5

16.58

Mountinghole3-M4

7045

3.3

32.4

518

5.1

235

247

MMSBM3RHB

ContactorsSC-E1/G

Link moduleBZ0LRE32GA

Base plate BZ0BPRE32A

Mass (g)1,380

74.5104.8

120.3

8

8116

56.5

4012

510

2.5

162.8

146.5 1 35mm wide rail (hight 15mm) x 22 75mm wide rail (hight 25mm) x 1

BM3V B + SC-E1/G, E2/G, E2S/G

Dimensions, mm• CombinationBM3RHB + SC-E1

MMSBM3RHB

ContactorsSC-E1

Link moduleBZ0LRE32AA

Base plateBZ0BPRE32A

Mass (g)1,155

74.5104.8

8

890.5

56.5

4012

510

2.5

137.5

121

120.3

558 39 (to 48)

14.3

22.5

5.5

16.58

Mounting hole3-M4

70

453.

3

32.4

518

5.1

235

247

1 35mm wide rail (hight 15mm) x 22 75mm wide rail (hight 25mm) x 1

Page 74: Manual Motor Starters Magnetic Contactors

72

Combination Starters

Dimensions, mm• CombinationBM3V B + SC-E3

MMSBM3VSBBM3VHB

ContactorsSC-E3/G

Link moduleBZ0LVE65GA

Base plateBZ0BPVE65A

Mass (g)2,400

66

260

270

9

67 (SC-E3/G)20.58

215.

5

4012

510

2.5

116.5

171.2155

117.5

638

121.5137

Mounting hole3-M4

48 (to 56)9 16.5

28

11

3.3

456670

5

1 35mm wide rail (hight 15mm) x 22 75mm wide rail (hight 25mm) x 1

BM3V B + SC-E3/G

MMSBM3VSBBM3VHB

ContactorsSC-E3

Link moduleBZ0LVE65AA

Base plateBZ0BPVE65A

Mass (g)2,080

66

260

270

9

67 (SC-E3)20.58

215.

5

4012

510

2.5

97.5

152.2136

117.5

638

121.5137

Mounting hole3-M4

48 (to 56)9 16.5

28

11

3.3

456670

5

1 35mm wide rail (hight 15mm) x 22 75mm wide rail (hight 25mm) x 1

Page 75: Manual Motor Starters Magnetic Contactors

Printed in Japan 2003-3(02-10) M50 FISInformation in this catalog is subject to change without notice.

● For safe operation, before using the product read the instruction manual or that comes with the product carefully or consult the Fuji sales representative from which you purchased the product.

● Some of the products listed in this catalog may have limits on their use or location or may require periodic inspections. Contact Fuji's sales representative for further information.

● For safe operation, wiring should be conducted only by qualified engineers who have sufficient technicalknowledge about electrical work or wiring.

Safety Considerations

Printed on 100% recycled paper using soy-based ink