Managing the impact of supply disruption on electricity customers Marie Hayden Manager Power System Operational Planning

Upload: others

Post on 02-Oct-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Managing the impact of supply disruption on electricity

Managing the impact of supply disruption

on electricity customers

Marie HaydenManager Power System Operational Planning

Page 2: Managing the impact of supply disruption on electricity

Presentation

ā€¢ Managing Security of Supply

ā€¢ What can go wrong?

ā€¢ Capacity schemes for large users

ā€¢ Where can I find out more?

Page 3: Managing the impact of supply disruption on electricity

Security of Supply

Long Term

Generation Adequacy

Transmission Adequacy

Short Term

Operational Security

Page 4: Managing the impact of supply disruption on electricity

GENERATION &

TRANSMISSION ADEQUACY

Long Term Security of Supply

Page 5: Managing the impact of supply disruption on electricity

Long Term Security of Supply

ā€¢ Generation Adequacy Report

ā€¢ Grid 25

ā€¢ East West Interconnector

Page 6: Managing the impact of supply disruption on electricity

OPERATIONAL SECURITY

Short Term Security of Supply

Page 7: Managing the impact of supply disruption on electricity

EirGridā€™s National Control Centre

Page 8: Managing the impact of supply disruption on electricity

Load changes through the day ā€¦

Hz

50

49 51

Hz

50

49 51

ā€¦Generation output must match this

Demand ā€“ Generation Balance

Page 9: Managing the impact of supply disruption on electricity

Demand is usually Predictable Impact of Grand Slam Rugby: Saturday 14th March v. Saturday 21st March

2000

2200

2400

2600

2800

3000

3200

3400

3600

3800

00:00:00

00:30:00

01:00:00

01:30:00

02:00:00

02:30:00

03:00:00

03:30:00

04:00:00

04:30:00

05:00:00

05:30:00

06:00:00

06:30:00

07:00:00

07:30:00

08:00:00

08:30:00

09:00:00

09:30:00

10:00:00

10:30:00

11:00:00

11:30:00

12:00:00

12:30:00

13:00:00

13:30:00

14:00:00

14:30:00

15:00:00

15:30:00

16:00:00

16:30:00

17:00:00

17:30:00

18:00:00

18:30:00

19:00:00

19:30:00

20:00:00

20:30:00

21:00:00

21:30:00

22:00:00

22:30:00

23:00:00

23:30:00

00:00:00

MW

14thMarch

21stMarch

Ireland Wales

Grand Slam Final, 2009

17 : 15

Page 10: Managing the impact of supply disruption on electricity

What can go wrong?

Generation and Transmission Events

Page 11: Managing the impact of supply disruption on electricity

What can go wrong?

A generation unit or units trip

There is not enough generation scheduled on to meet the

demand

Demand is much higher than expected

Wind Generation is much lower than expected

There is not enough capacity installed (long term)

Page 12: Managing the impact of supply disruption on electricity

ā€¢ Operating Reserve is used to manage the unexpected loss of the largest generation unit

Operating Reserve could be called on to operate several times a week

ā€¢ Under-frequency load shedding relays are used to disconnect up to 60% of demand for larger losses

UF Relays were last called on to operate in August 2006

ā€¢ Rota Load Shedding is used when shortfalls are significant and foreseen

Rota Load Shedding was last called on to operate in April 1991

Managing generation events

Page 13: Managing the impact of supply disruption on electricity

Transmission Faults

ā€¢ Environmental Factors

ā€“ Lightning

ā€“ Storms

ā€“ Wind

ā€¢ Indirect Causes

ā€“ Mal Operation of Protection

ā€“ Trips for un-cleared faults

ā€¢ Equipment Failure

ā€¢ Human Error

Page 14: Managing the impact of supply disruption on electricity

A less predictable event

Page 15: Managing the impact of supply disruption on electricity

Feeder Fault Rates

Voltage

Level

10 Year Average

Faults per KM per

year

2009

Faults per KM

per year

2009

Number of

Faults

400kV439 kilometres

0.21 0.23 1

220kV1725 kilometres

0.93 0.46 8

110kV3890 kilometres

1.13 0.44 17

63% of faults that impact the transmission system occur on the

transmission system with the remainder originating elsewhere

Page 16: Managing the impact of supply disruption on electricity

What can go wrong?

ā€¢ The system is operated to ensure that it remains stable

following the loss of any one item of transmission plant

ā€¢ Protection Relays are used to clear faults off the system very

quickly to minimise power quality issues

Page 17: Managing the impact of supply disruption on electricity

Worst Case ā€“ The Blackout

This part should

not be black!

Page 18: Managing the impact of supply disruption on electricity

Planning to Manage a Blackout

ā€¢ Typically power system blackouts are caused by

one of two things:

1. A major generation event

2. A major transmission event ā€“ more common

ā€¢ We plan and operate the transmission system in

a way that aims to prevent a blackout.

ā€¢ In the event that we fail to prevent a blackout, we

have a plan to manage one.

Page 19: Managing the impact of supply disruption on electricity

Power System Restoration Plan

ā€¢ A plan to restore the power system following a total

blackout

ā€¢ Assumes no generation station has any power supply

ā€¢ Based on ā€œBlackstartā€ stations ā€“ power stations that can

start without any external supply

ā€¢ Continually reviewed and updated

ā€¢ Regular Testing & Training

Page 20: Managing the impact of supply disruption on electricity

Crisis Communications

ā€¢ Having effective communications plans and systems in place is critical to managing emergencies

ā€¢ At EirGrid there is a strong focus on reviewing, testing and training our emergency communications plans

ā€¢ This renewed focus is also happening at a government level and we closely work with

ā€“ Task Force for Emergency Procedures

ā€“ Department of Communications, Energy and Natural Resources

ā€“ Commission for Energy Regulation

Page 21: Managing the impact of supply disruption on electricity

Capacity Schemes for Large Energy Users

Page 22: Managing the impact of supply disruption on electricity

Capacity Schemes Involving

Large Energy Users

Demand Side Management Schemes

ā€¢ Short Term Active Response (STAR)

ā€“ Customers make some/all of their load available for interruptions (day hours only).

ā€“ Immediate interruption, without notice.

ā€¢ Winter Peak Demand Reduction (WPDRS)

ā€“ Rewards reduction in customer loads from 17:00 to 19:00 each business day over the November to February winter period.

ā€¢ Power Save

ā€“ Incentivises voluntary reduction in customer loads at times when a shortage is foreseen by EirGrid

Page 23: Managing the impact of supply disruption on electricity