    Magtech Electromagnetic Flowmeter Troubleshooting Guide

    1. First of all, check the flowmeter indicator whether SYS alarmappeared. If appeared, pleasecheck the sensor that side junction box termination whether the terminal is affected by water ormoisture.If none of the alarm symbol appear on flow indicator, kindly proceeds to GUIDE 2.

    GUIDE 2

    First, run the pump to fully filled the pipeline with the medium and also ensure that theflowmeter section is fully filled with medium as well.

    After the pipeline fully filled, stop the pump and let the medium static in the pipeline forabout 3 minute which mean no flow movement within the pipeline.

    After about 3minutes, goto flowmeter indicator to perform zero calibration by following thesteps on the next page:

  • 7/25/2019 Magtech Electromagnetic Flowmeter-zeroing

    2/2

    Main PV

    Flow + Totalizer

    Password

    00000

    Password

    03210

    + Shift positionor +

    or Edit value

    Set the password to 03210

    +

    Language.

    .

    .

    .

    Flow Rspns

    Flow Direct

    Flow Zero

    Parameters Set

    -Proceed to parameter Flow Zero

    or

    Previous parameter

    Next parameter

    Enter into Flow Zero setting

    FS=XXXXX

    0000

    *Edit the value 00000 until you observe the value of FS become 0,

    then ENTER and Save the setting.

    + Shift positionor +

    or Edit value

    Flow Cutoff

    Press & hold 5sec till exit to main PV page

    Enter & save

    Electromagnetic Flowmeter Setting Procedure

    +