m2x3c i500c en m c manual gb
TRANSCRIPT
-
8/13/2019 m2x3c i500c en m c Manual Gb
1/88
M2x3&I500CommunicationsManual
Communications Manual
iSTAT M2x3 & I500
Publication Reference: M2x3C+I500C/EN/M/C
M2x3C+I500C/EN/M/C2011.ALSTOM,theALSTOM logoandanyalternativeversionthereofaretrademarksandservicemarksofALSTOM.Theothernamesmentioned,registeredornot,arethepropertyoftheirrespectivecompanies.Thetechnicalandotherdatacontainedinthisdocumentisprovidedforinformationonly.NeitherALSTOM,itsofficersoremployeesacceptresponsibilityfor,orshouldbetakenasmakinganyrepresentationorwarranty(whetherexpressorimplied),astotheaccuracyorcompletenessofsuchdataortheachievementofanyprojectedperformancecriteriawheretheseareindicated.ALSTOMreservestherighttoreviseorchangethisdataatanytimewithoutfurthernotice.
GRID
-
8/13/2019 m2x3c i500c en m c Manual Gb
2/88
-
8/13/2019 m2x3c i500c en m c Manual Gb
3/88
Technical Manual M2x3C+I500C/EN M/C
iSTAT M2x3 & I500 Modbus & DNP3.0 Page 1
CONTENT
1. COMMUNICATIONS SETUP 31.1 Setup communications on the M2x3 and I500 31.2 Ethernet 31.2.1 Using Fixed IP address 31.2.2 Local Port 31.3 Ethernet (XPort) communication 32. MODBUS INFORMATION 62.1 introduction 62.2 Transactions 62.3 Request 62.4 Response 62.5 Request - response cycle example 62.5.1 Request Frame 72.5.2 Response Frame 72.6 Framing 72.7 RTU framing 73. MODBUS SUPPORTED FUNCTIONS AND USAGE 83.1 03 read from holding registers 83.1.1 Request Frame 83.1.2 Response Frame 83.2 04 read from input registers 83.2.1 Request Frame 83.2.2 Response Frame 93.3 06 write to a single holding register 93.3.1 Request Frame 93.3.2 Response Frame 93.4 16 (10 HEX) write to one or more registers 93.4.1 Request Frame 93.4.2 Response Frame 103.5 17 (11HEX) report slave id 103.5.1 Request Frame 103.5.2 Response Frame 103.6 77 (4D HEX) read measurement string 103.6.1 Request Frame 103.6.2 Response Frame 103.6.3 Value Codes 113.7 82 (52 HEX) re-read output buffer 12
-
8/13/2019 m2x3c i500c en m c Manual Gb
4/88
M2x3C+I500C/EN M/C Technical Manual
Page 2 iSTAT M2x3 & I500 Modbus & DNP3.0
3.7.1 Request Frame 123.7.2 Response Frame 124. MODBUS ERROR RESPONSES 134.1 Exception codes 135. MODBUS REGISTER MAPS 146. MODBUS DATA FOR M2X3 AND I5MT/MR/MQ 156.1 SYSTEM DATA 156.2 MEASUREMENTS 176.3 NORMALIZED MEASUREMENTS 276.4 HARMONIC DATA 316.5 MEASUREMENTS (IEEE 754) 336.6 PRODUCT SETTINGS 376.7 OUTPUT PARAMETERS 576.8 OUTTYPES 586.9 MODBUS DATA TYPES 656.10 FLASH DATA 687. MODBUS DATA FOR I5MC/MV/MS/ML 707.1 MEASUREMENTS 707.2 NORMALISED MEASUREMENTS 717.3 MEASUREMENTS (IEEE 754 ) 747.4 PRODUCT SETTINGS 757.5 MODBUS DATA TYPES 758. DNP3.0 PROGRAMMING FOR M2X3 AND I5MT/MR/MQ 778.1 DNP 3.0 DEVICE PROFILE DOCUMENT 778.2 DNP3.0 REGISTER MAP 798.3 DATA TYPES DECODING 818.4 100% VALUE CALCULATIONS 819. RELATED DOCUMENTS 83
-
8/13/2019 m2x3c i500c en m c Manual Gb
5/88
Technical Manual M2x3C+I500C/EN M/C
iSTAT M2x3 & I500 Modbus & DNP3.0 Page 3
1. COMMUNICATIONS SETUP
The Setup of the communications on the I500 or M2x3 is achieved using the QDSPconfiguration software. QDSP can communicate with the iSTAT products via RS232, RS485,USB and Ethernet. The option used will depend on which communication port is fitted to theproduct.
The QDSP software always uses Modbus protocol to communicate with the product.
1.1 Setup communications on the M2x3 and I500
The setup of the communication ports is done using the QDSP software and is detailed in aseparate manual.
It is suggested that the communications channel for the product required by the application isinitially set up using QDSP running on a PC. Then when that is working correctly the productcan be connected to the required intelligent device.
1.2 Ethernet
When using the QDSP over Ethernet the set-up will depend on how the PC and the productare connected. The Communication interface must have a unique IP address in the Ethernetnetwork. Two modes for assigning IP are available:
Fixed IP address: In most installations a fixed IP address is required. A system providerusually defines IP addresses. An IP address should be within a valid IP range, unique foryour network and in the same Subnet mask as your PC.
DHCP: Automatic method of assigning IP addressed (DHCP) is used in most networks. Ifyou are not sure if DHPC is used in your network, check it with your system provider.
1.2.1 Using Fixed IP address
When the PC is directly connected to the Instrument a Fixed IP address will have to be usedwith the PC configured in the local area connection. If the connection is made without a Hub
or Switch, the connection has to be made with a Crossover Ethernet cable.
The fixed IP address can be set in the product using QDSP.
1.2.2 Local Port
Is the physical connector on a device enabling the connection to be made. Use a nonreserved port number from 1025 to 65535. If using Redirector software, the port numbershould be between 14000 and 14009.
Port numbers Function
1 1024, 9999,30718
Reserved numbers
14000 14009 Reserved for Redirector
1.3 Ethernet (XPort) communication
There are 2 types of Ethernet interfaces used on the M2x3. QDSP will always allow thesetting of the IP address, but on the older version it does not allow the setting of Local Portetc. If required this has to be accessed using an internet browser.
Any internet browser available can be used to access the interface in the product, type in theIP address of the product as the required internet address.
The browser will communicate with the instrument and then display a request for password;press OK without entering a password and the XPORT screen will be displayed.
-
8/13/2019 m2x3c i500c en m c Manual Gb
6/88
M2x3C+I500C/EN M/C Technical Manual
Page 4 iSTAT M2x3 & I500 Modbus & DNP3.0
Select to display Network settings where Subnet Mask and Default Gateway canbe modified if required.
Select to show connection settings, where local port can bemodified.
-
8/13/2019 m2x3c i500c en m c Manual Gb
7/88
Technical Manual M2x3C+I500C/EN M/C
iSTAT M2x3 & I500 Modbus & DNP3.0 Page 5
No other settings need to be changed.
When changes are complete select
After downloading the settings it is necessary to reset the M2x3 device to make the changesactive.
-
8/13/2019 m2x3c i500c en m c Manual Gb
8/88
M2x3C+I500C/EN M/C Technical Manual
Page 6 iSTAT M2x3 & I500 Modbus & DNP3.0
2. MODBUS INFORMATION
2.1 introduction
The Modbus protocol is a widely supported open interconnect protocol originally designed byModicon that can be enabled on the M2x3 and I500 via RS232, RS485, USB or Ethernet
communication.
There are two Modbus protocol types: Modbus RTU for serial communication (and USB) andModbus TCP for Ethernet communication. It is also possible to pass Modbus RTUcommunications over Ethernet.
On Serial Communication, Modbus is a single master multiple slave protocol suitable for amulti-drop configuration as provided by the RS485 connection. Up to 32 devices can beconnected in this way. Single - drop RS232 or USB connection is also possible.
2.2 Transactions
Communication operates on a master-slave basis where only one device (the master) caninitiate transactions called 'Requests'. The other devices (slaves) respond by supplying the
requested data to the master. This is called the 'Request - Response Cycle'.Master to slave request:
Device address Function Code nx8 bit data bytes Error check
Slave to master response:
Device address Function Code nx8 bit data bytes Error check
2.3 Request
This Master to Slave transaction takes the form:
Device address: Master addressing a slave (Address 0 is used for the broadcastaddress, which all slave devices recognise.).
Function code: E.g. 04 ask the slave to read its Input Registers and respond withtheir contents.
Data bytes: Tells the slave which register to start at and how many registersto read.
2.4 Response
This Slave to Master transaction takes the form:
Device address: To let the master know which slave is responding.Function code: This is an echo of the request function code.
Data bytes: Contains the data collected from the slave.
2.5 Request - response cycle example
Ia 160.00 A = 16000* 10-2A
Data type T3 32 bitunsigned
FE 00 3E 80(16)
Data held in Modbus
addresses
30036(10) & 30037(10)
30036(10)- 30000 (10)= 36 (10) 00 24 (16)
-
8/13/2019 m2x3c i500c en m c Manual Gb
9/88
Technical Manual M2x3C+I500C/EN M/C
iSTAT M2x3 & I500 Modbus & DNP3.0 Page 7
2.5.1 Request Frame
Starting Register Register Count CRC
Slave AddressHI LO
Function code HI LO LO HI
21 04 00 24 00 02
2.5.2 Response Frame
Register Data CRC
Slave AddressLO HI
Function code Byte Count HI LO HI LO
21 04 04 FE 00 3E 80
2.6 Framing
There are two types of message framing for the serial communications, ASCII or RTU.
iSTAT products supports RTU framing.
2.7 RTU framing
In RTU mode, messages start and end with a silent interval of at least 3.5 character times(t1-t2-t3-t4 as shown below).
The advantage of this mode of framing is that it enables a greater character density and abetter data throughput. However, each message must be transmitted in a continuous stream.If a silent interval of more than 1.5 character times occurs before completion of the frame,the device flushes the incomplete message and assumes that the next byte will be theaddress field of a new message.
Start Address Function Data CRC Check End
t1-t2-t3-t4 8 bits 8 bits n x 8 bits 16 bits t1-t2-t3-t4
The Cyclic Redundancy Check (CRC) field is two bytes, containing a 16 bit binary value. TheCRC value is calculated by the transmitting device, which appends the CRC to the message.The receiving device recalculates a CRC during receipt of the message, and compares thecalculated value to the actual value it received in the CRC field. If the two values are notequal an error results. The CRC-16 calculation is an industry standard method used for errordetection.
One frame is transmitted as 1 start bit, 8 data bits and 2 stop bit. If parity is selected then theframe is transmitted as 1 start bit, 8 data bits, and 1 stop bit.
Where n > 1 data is transmitted most significant byte first.
The CRC check is transmitted least significant byte first.
-
8/13/2019 m2x3c i500c en m c Manual Gb
10/88
M2x3C+I500C/EN M/C Technical Manual
Page 8 iSTAT M2x3 & I500 Modbus & DNP3.0
3. MODBUS SUPPORTED FUNCTIONS AND USAGE
Code Code Function References
DEC HEX
3 03 to read from holding registers (4XXXX memory references)
4 04 to read from input registers (3XXXX memory references)
6 06 to write to a single holding register (4XXXX memory references)
16 10 to write to one or more holding registers (4XXXX memory references)
17 11 report slave ID 6 characters
77 4D read measurement string 1 byte value code (request)
82 52 re-read output buffer Use after broadcast request
3.1 03 read from holding registers
Reads the binary content of holding registers (4X references) in the slave. Broadcast is also
supported.
3.1.1 Request Frame
The query message specifies the starting register and quantity of registers (1 to 28) to beread. Registers are addressed starting at zero.
Here is an example of a request to read registers 40009 ... 40010 from slave device 33:
Starting Register Register Count CRC
Slave Address Function Code HI LO HI LO LO HI
21 03 00 09 00 02
3.1.2 Response Frame
The register data in the response message is packed as two bytes per register, with thebinary contents right justified within each byte. For each register, the first byte contains thehigh order bits and the second contains the low order bits.
Data is scanned in the slave at the rate of 28 registers per scan. The response is returnedwhen the data is completely assembled.
Here is an example of a response to the query:
Register Data CRC
Slave Address Function Code Byte Count HI LO HI LO LO HI
21 03 04 75 03 42 15
The contents of registers 40009 ... 40010 are 75 03 and 42 15 hex.
3.2 04 read from input registers
Reads the binary content of input registers (3X references) in the slave. Broadcast is alsosupported
3.2.1 Request Frame
The query message specifies the starting register and quantity (1 to 28) of registers to beread. Registers are addressed starting at zero.
Here is an example of a request to read registers 30036 ... 30037 from slave device 33:
Starting Register Register Count CRC
Slave Address Function Code HI LO HI LO LO HI
21 04 00 24 00 02
-
8/13/2019 m2x3c i500c en m c Manual Gb
11/88
Technical Manual M2x3C+I500C/EN M/C
iSTAT M2x3 & I500 Modbus & DNP3.0 Page 9
3.2.2 Response Frame
The register data in the response message is packed as two bytes per register, with thebinary contents right justified within each byte. For each register, the first byte contains thehigh order bits and the second contains the low order bits.
Data is scanned in the slave at the rate of 28 registers per scan. The response is returned
when the data is completely assembled.
Here is an example of a response to the query:
Register Data CRC
Slave Address Function Code Byte Count HI LO HI LO LO HI
21 04 04 FE 00 3E 80
The contents of registers 30036 ... 30037 are FE 00 and 3E 80 hex.
3.3 06 write to a single holding register
Pre-sets a value into a single holding register (4X reference). When broadcast, the functionpre-sets the same register reference in all attached slaves.
3.3.1 Request Frame
The query message specifies the register reference to be pre-set. Registers are addressedstarting at zero; register 1 is addressed as 0.
Here is an example of a request to pre-set register 40010 to 42 15 hex in slavedevice 33:
Register Address Register Data CRC
Slave Address Function Code HI LO HI LO LO HI
21 06 00 0A 42 15
3.3.2 Response Frame
The normal response is an echo of the query, returned after the register contents have beenpre-set. Here is an example of a response to the query:
Register Address Register Data CRC
Slave Address Function Code HI LO HI LO LO HI
21 06 00 0A 42 15
3.4 16 (10 HEX) write to one or more registers
Pre-sets values into a sequence of holding registers (4x references). When broadcast thefunction pre-sets the same register references in all attached slaves.
3.4.1 Request Frame
The query message specifies the register references to be pre-set. Registers are addressedstarting at zero; register 1 is addressed as 0. Here is an example of a request to pre-set tworegisters starting at 40000 to 41 42 and 43 44 hex (Enter Password ABCD), in slave device33:
SlaveAddress
FunctionCode
StartingRegister
RegisterCount
Byte
Count
Register
DataCRC
HI LO HI LO HI LO HI LO LO HI
21 16 00 00 00 02 04 41 42 4344
-
8/13/2019 m2x3c i500c en m c Manual Gb
12/88
M2x3C+I500C/EN M/C Technical Manual
Page 10 iSTAT M2x3 & I500 Modbus & DNP3.0
3.4.2 Response Frame
The normal response returns the slave address, function code, starting address, andquantity of registers pre-set. Here is an example of a response to the query shown above.
Slave
Address
Function
Code
Starting Register Register Count CRC
HI LO HI LO LO HI
21 16 00 00 00 02
If the password is not correct (L1 or L2 or BP), the response to the query is:
Slave
Address
Function
Code
Starting Register Register Count CRC
HI LO HI LO LO HI
21 16 00 00 00 02
3.5 17 (11HEX) report slave id
Returns a description of the type of controller present at the slave address.
3.5.1 Request Frame
Here is an example of a request to report the ID of slave device 33:
CRC
Slave Address Function Code LO HI
21 11
3.5.2 Response Frame
The format of a normal response is shown below:
Slave Address Function Code Byte Count Register Data CRC
HI LO HI LO HI LO LO HI
21 11 06 20 4D 30 32 32 30
3.6 77 (4D HEX) read measurement string
Reads the measurement value as an ASCII string. Broadcast is also supported. See list ofvalue codes in section 4.6.3
3.6.1 Request Frame
The query message specifies the value code of the measurement to be read.
Here is an example of a response to read Total Real Power from slave device 33:
Slave
Address
Function
Code
Value Code CRC
LO HI
21 4D 04
3.6.2 Response Frame
The ASCII string in the response message is packed as data bytes. The quantity of databytes depends on the value code.
Here is an example of the query:
Slave
Address
Function
Code
Byte Count String Data CRC
1. 2. 3. 4. 5. 6. 7. 8. LO HI
21 4D 08 2B 32 31 2E 31 33 35 6B 49 35
-
8/13/2019 m2x3c i500c en m c Manual Gb
13/88
Technical Manual M2x3C+I500C/EN M/C
iSTAT M2x3 & I500 Modbus & DNP3.0 Page 11
3.6.3 Value Codes
The value codes are described in the following table:
ValueCode DEC
ValueCodeHex
Measurement ValueByteCount
Example String Data
00 00 Energy counter 1 15 "0000004.46kWh"
01 01 Energy counter 2 15 "0000001.24kvarh"
02 02 Energy counter 3 15 "0000005.71kWh"
03 03 Energy counter 4 15 "0000002.86kvarh"
04 04 Total Real Power 8 "+21.135k"
05 05 A Phase Real Power 8 "+7046.3"
06 06 B Phase Real Power 8 "+7037.3"
07 07 C Phase Real Power 8 "+7051.1"
08 08 Total Reactive Power 12 "1208.7 var L"
09 09 A Phase Reactive Power 12 "0400.2 var L"
10 0A B Phase Reactive Power 12 "0406.4 var L"
11 0B C Phase Reactive Power 12 "0400.9 var L"
12 0C Total I 7 "93.671"
13 0D IA 7 "31.227"
14 0E IB 7 "31.222"
15 0F IC 7 "31.222"
16 10 Average V 7 "226.06"
17 11 VA 7 "226.08"
18 12 VB 7 "225.83"
19 13 VC 7 "226.27"
20 14 Total Apparent Power 7 "21.170k"
21 15 A Phase Apparent Power 7 "7057.3"
22 16 B Phase Apparent Power 7 "7049.0"
23 17 C Phase Apparent Power 7 "7062.8"
24 18 Total Power Factor 8 "+0.998 L"25 19 Power Factor A 8 "+0.998 L"
26 1A Power Factor B 8 "+0.998 L"
27 1B Power Factor C 8 "+0.998 L"
28 1C Frequency 7 "46.008"
29 1D Frequency 7 "46.008"
30 1E Frequency 7 "46.008"
31 1F Frequency 7 "46.008"
32 20 Total Power Angle 7 "+003.26"
33 21 Power Angle A 7 "+003.25"
34 22 Power Angle B 7 "+003.30"
35 23 Power Angle C 7 "+003.25"
-
8/13/2019 m2x3c i500c en m c Manual Gb
14/88
M2x3C+I500C/EN M/C Technical Manual
Page 12 iSTAT M2x3 & I500 Modbus & DNP3.0
ValueCode DEC
ValueCodeHex
Measurement ValueByteCount
Example String Data
36 24 IN 6 "93.67"
37 25 Angle AB 7 "+000.00"
38 26 Angle BC 7 "+000.01"
39 27 Angle CA 7 "-000.01"
40 28 Average Vxy 6 "000.3"
41 29 VAB 6 "000.2"
42 2A VBC 6 "000.24"
43 2B VCA 6 "000.2"
44 2C Dynamic Demand Value 1 13 "Pt=+9.818kW"
45 2D Dynamic Demand Value 2 12 "Qt=6.504kvar"
46 2E Dynamic Demand Value 3 12 "St=12.89kVA"
47 2F Dynamic Demand Value 4 12 "It=56.91 A"
48 30 Max Demand Since Reset 1 13 "Pt=+11.26kW"
49 31 Max Demand Since Reset 2 12 "Qt=14.64kvar"
50 32 Max Demand Since Reset 3 12 "St=18.46kVA"
51 33 Max Demand Since Reset 4 12 "It=81.01 A"
52 34 Time Stamp MD 1 12 "03.SEP 14:11"
53 35 Time Stamp MD 2 12 "03.SEP 14:10"
54 36 Time Stamp MD 3 12 "03.SEP 14:10"
55 37 Time Stamp MD 4 12 "03.SEP 14:12"
3.7 82 (52 HEX) re-read output buffer
This function should be used after the broadcast request. The addressed slave transmits theresponse frame of the previous request.
3.7.1 Request Frame
Here is an example of a request to re-read the output buffer of slave device 33:
CRC
Slave Address Function Code LO HI
21 52
3.7.2 Response Frame
The response to the query depends on the previous function code.
-
8/13/2019 m2x3c i500c en m c Manual Gb
15/88
Technical Manual M2x3C+I500C/EN M/C
iSTAT M2x3 & I500 Modbus & DNP3.0 Page 13
4. MODBUS ERROR RESPONSES
When a slave detects an error other than a CRC error, a response will be sent to the master.The most significant bit of the function code byte will be set to 1 (i.e. the function code sentfrom the slave will be equal to the function code sent from the master plus 128). Thefollowing byte will be an exception code indicating the type of error that occurred.
The slave will ignore transmissions received from the master with CRC errors.
An example of an illegal request and the corresponding exception response is shown below.The request in this example is to read registers 0201H to 0209H. If these addresses are notsupported in the slave then the following occurs:
Request Message
Starting Register Register Count
Address Function Code HI LO HI LO CRC
01 01 02 01 00 08 6D B4
Exception Response Message
Address Function Code Exception Code CRC
01 81 02 C1 91
4.1 Exception codes
Code Name Meaning
01 ILLEGAL FUNCTION The function code transmitted is notone of the functions supported by theslave.
02 ILLEGAL DATA ADDRESSES The data address received in therequest is not an allowable value forthe slave.Write to password protected registers.
03 ILLEGAL DATA VALUE The value referenced in the data fieldtransmitted by the master is not withinfamily for the selected data address.The register count is greater than 28(functions 03 and 04).
06 SLAVE DEVICE BUSY The slave is engaged in processing along duration program command. Themaster should re-transmit themessage later when the slave is free.
-
8/13/2019 m2x3c i500c en m c Manual Gb
16/88
M2x3C+I500C/EN M/C Technical Manual
Page 14 iSTAT M2x3 & I500 Modbus & DNP3.0
5. MODBUS REGISTER MAPS
The Modbus register map consists of the following columns:
Code Function codes as described in Section 4.0.
Address 16 bit register address starting from zero.Please Note:
Most Modbus master devices assume that 30001 or 40001 aresubtracted from the defined address for the registers. TheM2x3 and i500 subtract 30000 and 40000, meaning that theaddresses may have to be offset by 1.
Contents Description of parameters assigned to registers.
Data type MODBUS data types T1 etc. are described in section 7.
UNSIGNEDINTEGER
family 0 ... 65535
one 16-bit register
SIGNED INTEGER family 32768 ... 32767one 16-bit register
ASCII Family 32159
16 bit registers (two ASCII codes per register)
BINARY FLAGS Each bit of a 16 bit register can be used as abinary flag
Indicator Each bit of a 16-bit register can be either assigned as flags or filledwith binary data.
Values Definitions of settings, data values and any dependencies that existbetween settings.
Register type Declares whether a register is to be read/write register (setting) or aread register (data).
Min, max step The minimum and maximum numerical family and the incremental stepsize.
Password There is a numerical password that allows save/abort settings and afactory accessible password constructed from the serial number thatallows entry/exit to and from the calibration and configuration settings.
-
8/13/2019 m2x3c i500c en m c Manual Gb
17/88
Technical Manual M2x3C+I500C/EN M/C
iSTAT M2x3 & I500 Modbus & DNP3.0 Page 15
6. MODBUS DATA FOR M2X3 AND I5MT/MR/MQ
6.1 SYSTEM DATA
Code Address Contents Data Ind Values and Dependencies
04 30001 30018 Model Number Str_16
04 30009 30012 Serial Number Str_8
04 30013 Software Ref 1 T1 Software version
04 30014 Hardware Ref Str_2 Hardware version
30015 Calibration voltage T4 mV
30016 Voltage auto-range T1 1=auto-range
30017 Calibration current T4 mA
30018 Current auto-range T1 1=auto-range
30019 Accuracy class T17 50 = 0.5%20 = 0.2%
30020 MiNet Flag T1 0
30021 Language Pack T1
30022 LCD type T1 0 128x64 yellow green
1128x64 yellow greennegative
2 128x64 red negative
30023 Power supply T1 0 Unknown
1
Universal AC 48-276V:
DC 20 300V
2 57.64v, 50/60Hz
3 63.5v, 50/60Hz
4 100v, 50/60Hz
5 110v, 50/60Hz
6 230v, 50/60Hz
7 400v, 50/60Hz
8 500v, 50/60Hz
9Universal AC 48 77V:
DC 20 100V
10Universal AC 70 276V;
DC 70 300V
30024 COM1: communication type T1 0 No communication
1 RS232
2 RS485
3 RS232 & RS485
4 Ethernet (X-Port)
5 Ethernet & USB
6 Ethernet7 USB
30025 COM2: communication type T1 0 No communication
1 RS232
2 RS485
-
8/13/2019 m2x3c i500c en m c Manual Gb
18/88
M2x3C+I500C/EN M/C Technical Manual
Page 16 iSTAT M2x3 & I500 Modbus & DNP3.0
Code Address Contents Data Ind Values and Dependencies
30026 30027 Reserved
30028 Memory type T1 0 No memory
1 2Mb flash
2 4Mb flash3 8Mb flash
30029 I/O 1 T1 0 No I/O
1 Unipolar analogue output
2 Bipolar analogue output
3 Jumperless analogue output
4 Pulse output
5 Tariff Input
6 Bistable alarm output
7 Relay alarm output
8 Analogue output 20mA
9 Analogue input
10 Digital input
11 Pulse input
12 S0 output
13 Fast Analogue Output
14Jumperless unipolar Analogoutput
15 Watch dog output
16 Reserved17 RS232
18 RS485
19 Reserved
20 COM2 - Ex
30030 I/O 2
30031 I/O 3
30032 I/O 4
30033 30043 Reserved
30044 Status Register (M2x3 only) T1 0 Locked
1 Wrong Connection
2 Low Battery
3 Low Supply
4 Clock not Set
30045 30046 Configuration time stamp T10
30047 30048 Calibration time stamp T10
30049 30050 Last upgrade time stamp T10
30051 Digital input 1 voltage range T1 0 230V
1 63 110V
2 48V
30052 Digital input 2 voltage range T1 See Digital input 1
30053 Digital input 3 voltage range T1 See Digital input 1
30054 Digital input 4 voltage range T1 See Digital input 1
-
8/13/2019 m2x3c i500c en m c Manual Gb
19/88
Technical Manual M2x3C+I500C/EN M/C
iSTAT M2x3 & I500 Modbus & DNP3.0 Page 17
Code Address Contents Data Ind Values and Dependencies
30055 30057 Ethernet MAC Address T_Hex6
30058 Ethernet Software Reference T1 Ethernet Software Version
30059 30060 Ethernet IP Address T_Hex4 Actual Ethernet IP Address
30061 30097 Reserved location30098 Active communications port T1 1 COM1
2 COM2
30099Modbus max.register read atonce
T1
6.2 MEASUREMENTS
Code Address Contents Data Ind Values and Dependencies
ACTUAL MEASUREMENTS
04 30101 30104 Actual time T_Time
04 30105 30106 Frequency T5
04 30107 30108 U1 T5
04 30109 30110 U2 T5
30111 30112 U3 T5
04 30113 30114 Uavg (phase to neutral) T5
04 30115 j12 (angle between U1 and U2) T17
04 30116 j23 (angle between U2 and U3) T17
04 30117 j31 (angle between U3 and U1) T17
04 30118 30119 U12 T5
04 30120 30121 U23 T5
04 30122 30123 U31 T5
04 30124 30125 Uavg (phase to phase) T5
04 30126 30127 I1 T5
04 30128 30129 I2 T5
04 30130 30131 I3 T5
0430132 30133
INc T504 30134 30135 INm - reserved T5
04 30136 30137 Iavg T5
04 30138 30139 I T5
30140 30141 Active Power Total (Pt) T6
30142 30143 Active Power Phase L1 (P1) T6
30144 30145 Active Power Phase L2 (P2) T6
30146 30147 Active Power Phase L3 (P3) T6
30148 30149 Reactive Power Total (Qt) T6
30150 30151 Reactive Power Phase L1 (Q1) T6
30152 30153 Reactive Power Phase L2 (Q2) T6
30154 30155 Reactive Power Phase L3 (Q3) T6
-
8/13/2019 m2x3c i500c en m c Manual Gb
20/88
M2x3C+I500C/EN M/C Technical Manual
Page 18 iSTAT M2x3 & I500 Modbus & DNP3.0
Code Address Contents Data Ind Values and Dependencies
30156 30157 Apparent Power Total (St) T5
30158 30159 Apparent Power Phase L1 (S1) T5
30160 30161 Apparent Power Phase L2 (S2) T5
30162 30163 Apparent Power Phase L3 (S3) T5
30164 30165 Power Factor Total (PFt) T7
30166 30167 Power Factor Phase 1 (PF1) T7
30168 30169 Power Factor Phase 2 (PF2) T7
30170 30171 Power Factor Phase 3 (PF3) T7
30172 Power Angle Total(atan2(Pt,Qt))
T17
30173 1 (angle between U1 and I1) T17
30174 2 (angle between U2 and I2) T17
30175 3 (angle between U3 and I3) T17
30176 U unbalance T16
30177 30180 Reserved
30181 Internal Temperature T17
THD HARMONIC DATA
30182 U1 THD% T16
30183 U2 THD% T16
30184 U3 THD% T16
30185 U12 THD% T16
30186 U23 THD% T16
30187 U31 THD% T16
30188 I1 THD% T16
30189 I2 THD% T16
30190 I3 THD% T16
-
8/13/2019 m2x3c i500c en m c Manual Gb
21/88
Technical Manual M2x3C+I500C/EN M/C
iSTAT M2x3 & I500 Modbus & DNP3.0 Page 19
Code Address Contents Data Ind Values and Dependencies
I/O STATUS
30191 Alarm Status Flags (No.116)
T1 bit-i Alarm i+1
30192 Alarm Status Flags (No.1732)
T1 bit-i Alarm i+17
30193 I/O 1 Value T17
30194 I/O 2 Value T17
30195 I/O 3 Value T17
30196 I/O 4 Value T17
30197 30200 Reserved
MAXIMUM MEASUREMENTS
30201 30204 Last reset time T_Time
30205 30206 Frequency T5
30207 30208 U1 T5
30209 30210 U2 T5
30211 30212 U3 T5
30213 30214 Reserved: T5
30215 Reserved:12 (angle betweenU1 and U2)
T17
30216 Reserved: 23 (angle betweenU2 and U3)
T17
30217 Reserved: 31 (angle betweenU3 and U1)
T17
30218 30219 U12 T5
30220 30221 U23 T5
30222 30223 U31 T5
30224 30225 Reserved: Uavg (phase tophase)
T5
30226 30227 I1 T5
30228 30229 I2 T5
30230 30231 I3 T5
30232 30233 Reserved: INc T5
30234 30235 Reserved: INm T5
30236 30237 Reserved: Iavg T5
30238 30239 Reserved: I T5
30240 30241 Active Power Total (Pt) T6
30242 30243 Active Power Phase L1 (P1) T6
30244 30245 Active Power Phase L2 (P2) T6
30246 30247 Active Power Phase L3 (P3) T6
30248 30249 Reserved: Reactive Power Total(Qt)
T6
30250 30251 Reserved: Reactive Power Phase T6
-
8/13/2019 m2x3c i500c en m c Manual Gb
22/88
M2x3C+I500C/EN M/C Technical Manual
Page 20 iSTAT M2x3 & I500 Modbus & DNP3.0
Code Address Contents Data Ind Values and Dependencies
L1 (Q1)
30252 30253 Reserved: Reactive Power PhaseL2 (Q2)
T6
30254 30255 Reserved: Reactive Power Phase
L3 (Q3)
T6
30256 30257 Apparent Power Total (St) T5
30258 30259 Apparent Power Phase L1 (S1) T5
30260 30261 Apparent Power Phase L2 (S2) T5
30262 30263 Apparent Power Phase L3 (S3) T5
30264 30265 Reserved: Power Factor Total(PFt)
T7
30266 30267 Reserved: Power FactorPhase 1 (PF1)
T7
30268 30269 Reserved: Power FactorPhase 2 (PF2)
T7
30270 30271 Reserved: Power FactorPhase 3 (PF3)
T7
30272 Reserved: Power Angle Total(atan2(Pt,Qt))
T17
30273 Reserved: 1 (angle betweenU1 and I1)
T17
30274 Reserved: 2 (angle betweenU2 and I2)
T17
30275 Reserved: 3 (angle betweenU3 and I3)
T17
30276 30280 Reserved
30281 Internal Temperature T17
THD HARMONIC DATA
30282 Reserved: U1 THD% T16
30283 Reserved: U2 THD% T16
30284 Reserved: U3 THD% T16
30285 Reserved: U12 THD% T16
30286 Reserved: U23 THD% T16
30287 Reserved: U31 THD% T16
30288 Reserved: I1 THD% T16
30289 Reserved: I2 THD% T16
30290 Reserved: I3 THD% T16
30291 30300 Reserved
-
8/13/2019 m2x3c i500c en m c Manual Gb
23/88
Technical Manual M2x3C+I500C/EN M/C
iSTAT M2x3 & I500 Modbus & DNP3.0 Page 21
Code Address Contents Data Ind Values and Dependencies
MINIMUM MEASUREMENTS
30301 30304 Last reset time T_Time
30305 30306 Frequency T5
30307 30308 U1 T5
30309 30310 U2 T5
30311 30312 U3 T5
30313 30314 Reserved: Uavg (phase toneutral)
T5
30315 Reserved:12 (angle betweenU1 and U2)
T17
30316 Reserved: 23 (angle betweenU2 and U3)
T17
30317 Reserved: 31 (angle betweenU3 and U1)
T17
30318 30319 U12 T5
30320 30321 U23 T5
30322 30323 U31 T5
30324 30325 Reserved: Uavg (phase tophase)
T5
30326 30327 I1 T5
30328 30329 I2 T5
30330 30331 I3 T5
30332 30333 Reserved: INc T5
30334 30335 Reserved: INm T5
30336 30337 Reserved: Iavg T5
30338 30339 Reserved: I T5
30340 30341 Active Power Total (Pt) T6
30342 30343 Active Power Phase L1 (P1) T6
30344 30345 Active Power Phase L2 (P2) T6
30346 30347 Active Power Phase L3 (P3) T630348 30349 Reserved: Reactive Power
Total (Qt)T6
30350 30351 Reserved: Reactive PowerPhase L1 (Q1)
T6
30352 30353 Reserved: Reactive PowerPhase L2 (Q2)
T6
30354 30355 Reserved: Reactive PowerPhase L3 (Q3)
T6
30356 30357 Apparent Power Total (St) T5
30358 30359 Apparent Power Phase L1 (S1) T5
30360 30361 Apparent Power Phase L2 (S2) T5
30362 30363 Apparent Power Phase L3 (S3) T5
30364 30365 Reserved: Power Factor Total T7
-
8/13/2019 m2x3c i500c en m c Manual Gb
24/88
M2x3C+I500C/EN M/C Technical Manual
Page 22 iSTAT M2x3 & I500 Modbus & DNP3.0
Code Address Contents Data Ind Values and Dependencies
(PFt)
30366 30367 Reserved: Power FactorPhase 1 (PF1)
T7
30368 30369 Reserved: Power FactorPhase 2 (PF2)
T7
30370 30371 Reserved: Power FactorPhase 3 (PF3)
T7
30372 Reserved: Power Angle Total(atan2(Pt,Qt))
T17
30373 Reserved: 1 (angle betweenU1 and I1)
T17
30374 Reserved: 2 (angle betweenU2 and I2)
T17
30375 Reserved: 3 (angle betweenU3 and I3) T17
30376 30380 Reserved
30381 Internal Temperature T17
THD HARMONIC DATA
30382 Reserved: U1 THD% T16
30383 Reserved: U2 THD% T16
30384 Reserved: U3 THD% T16
30385 Reserved: U12 THD% T16
30386 Reserved: U23 THD% T16
30387 Reserved: U31 THD% T16
30388 Reserved: I1 THD% T16
30389 Reserved: I2 THD% T16
30390 Reserved: I3 THD% T16
30391 30400 Reserved
ENERGY
30401 Energy Counter 1 Exponent T2
30402 Energy Counter 2 Exponent T2
30403 Energy Counter 3 Exponent T2
30404 Energy Counter 4 Exponent T2
30405 Current Active Tariff T1
30406 30407 Energy Counter 1 T3
30408 30409 Energy Counter 2 T3
30410 30411 Energy Counter 3 T3
30412 30413 Energy Counter 4 T3
30414 30415 Energy Counter 1 Tariff 1 T330416 30417 Energy Counter 2 Tariff 1 T3
30418 30419 Energy Counter 3 Tariff 1 T3
30420 30421 Energy Counter 4 Tariff 1 T3
-
8/13/2019 m2x3c i500c en m c Manual Gb
25/88
Technical Manual M2x3C+I500C/EN M/C
iSTAT M2x3 & I500 Modbus & DNP3.0 Page 23
Code Address Contents Data Ind Values and Dependencies
30422 30423 Energy Counter 1 Tariff 2 T3
30424 30425 Energy Counter 2 Tariff 2 T3
30426 30427 Energy Counter 3 Tariff 2 T3
30428 30429 Energy Counter 4 Tariff 2 T3
30430 30431 Energy Counter 1 Tariff 3 T3
30432 30433 Energy Counter 2 Tariff 3 T3
30434 30435 Energy Counter 3 Tariff 3 T3
30436 30437 Energy Counter 4 Tariff 3 T3
30438 30439 Energy Counter 1 Tariff 4 T3
30440 30441 Energy Counter 2 Tariff 4 T3
30442 30443 Energy Counter 3 Tariff 4 T3
30444 30445 Energy Counter 4 Tariff 4 T3
30446 30447 Energy Counter 1 Cost T3
30448 30449 Energy Counter 2 Cost T3
30450 30451 Energy Counter 3 Cost T3
30452 30453 Energy Counter 4 Cost T3
30454 30500 Reserved
DEMAND VALUES
DYNAMIC DEMAND VALUES
30501 Time Into Period (minutes) T130502 30503 I1 T5
30504 30505 I2 T5
30506 30507 I3 T5
30508 30509 Apparent Power Total (St) T5
30510 30511 Active Power Total (Pt) -(positive)
T6
30512 30513 Active Power Total (Pt) -(negative)
T6
30514 30515 Reactive Power Total (Qt) - L T630516 30517 Reactive Power Total (Qt) - C T6
MAX DEMAND SINCE LAST RESET
30518 30519 I1 T5
30520 30523 Time Stamp T_Time
30524 30525 I2 T5
30526 30529 Time Stamp T_Time
30530 30531 I3 T5
30532 30535 Time Stamp T_Time
30536 30537 Apparent Power Total (St) T5
30538 30541 Time Stamp T_Time
30542 30543 Active Power Total (Pt) -(positive)
T6
-
8/13/2019 m2x3c i500c en m c Manual Gb
26/88
M2x3C+I500C/EN M/C Technical Manual
Page 24 iSTAT M2x3 & I500 Modbus & DNP3.0
Code Address Contents Data Ind Values and Dependencies
30544 30547 Time Stamp T_Time
30548 30549 Active Power Total (Pt) -(negative)
T6
30550 30553 Time Stamp T_Time30554 30555 Reactive Power Total (Qt) - L T6
30556 30559 Time Stamp T_Time
30560 30561 Reactive Power Total (Qt) - C T6
30562 30565 Time Stamp T_Time
30566 30579 Reserved
FLICKERS (M253 & i5MQ only)
30580 Flicker Pst1 T17
-
8/13/2019 m2x3c i500c en m c Manual Gb
27/88
Technical Manual M2x3C+I500C/EN M/C
iSTAT M2x3 & I500 Modbus & DNP3.0 Page 25
Code Address Contents Data Ind Values and Dependencies
30610 Frequency Variations 1: % /Period
T16
30611 Frequency Variations 1: % /Year
T16
30612 Frequency Variations 2: % /Period
T16
30613 Frequency Variations 2: % /Year
T16
30614 Voltage Unbalances: % /Period
T16
30615 Voltage Unbalances: % / Year T16
30616 Voltage Variations 1 - L1: % /Period
T16
30617 Voltage Variations 1 - L1: % /Year T16
30618 Voltage Variations 1 - L2: % /Period
T16
30619 Voltage Variations 1 - L2: % /Year
T16
30620 Voltage Variations 1 - L3: % /Period
T16
30621 Voltage Variations 1 - L3: % /Year
T16
30622 Voltage Variations 2 - L1: % /Period T16
30623 Voltage Variations 2 - L1: % /Year
T16
30624 Voltage Variations 2 - L2: % /Period
T16
30625 Voltage Variations 2 - L2: % /Year
T16
30626 Voltage Variations 2 - L3: % /Period
T16
30627 Voltage Variations 2 - L3: % /Year
T16
30628 THD's - L1: % / Period T16
30629 THD's - L1: % / Year T16
30630 THD's - L2: % / Period T16
30631 THD's - L2: % / Year T16
30632 THD's - L3: % / Period T16
30633 THD's - L3: % / Year T16
30634 Harmonics - L1: % / Period T16
30635 Harmonics - L1: % / Year T16
30636 Harmonics - L2: % / Period T16
30637 Harmonics - L2: % / Year T16
30638 Harmonics - L3: % / Period T16
-
8/13/2019 m2x3c i500c en m c Manual Gb
28/88
M2x3C+I500C/EN M/C Technical Manual
Page 26 iSTAT M2x3 & I500 Modbus & DNP3.0
Code Address Contents Data Ind Values and Dependencies
30639 Harmonics - L3: % / Year T16
30640 Short term Flickers - L1: % /Period
T16
30641 Short term Flickers - L1: % /Year T16
30642 Short term Flickers - L2: % /Period
T16
30643 Short term Flickers - L2: % /Year
T16
30644 Short term Flickers - L3: % /Period
T16
30645 Short term Flickers - L3: % /Year
T16
30646 Long term Flickers - L1: % /Period T16
30647 Long term Flickers - L1: % /Year
T16
30648 Long term Flickers - L2: % /Period
T16
30649 Long term Flickers - L2: % /Year
T16
30650 Long term Flickers - L3: % /Period
T16
30651 Long term Flickers - L3: % /Year T16
30652 Transients - L1: No. / Period T1
30653 Transients - L1: No. / Year T1
30654 Transients - L2: No. / Period T1
30655 Transients - L2: No. / Year T1
30656 Transients - L3: No. / Period T1
30657 Transients - L3: No. / Year T1
30658 Temporary Overvoltages - L1:
No. / Period
T1
30659 Temporary Overvoltages - L1:No. / Year
T1
30660 Temporary Overvoltages - L2:No. / Period
T1
30661 Temporary Overvoltages - L2:No. / Year
T1
30662 Temporary Overvoltages - L3:No. / Period
T1
30663 Temporary Overvoltages - L3:No. / Year
T1
30664 Voltage Dips - L1: No. / Period T1
30665 Voltage Dips - L1: No. / Year T1
30666 Voltage Dips - L2: No. / Period T1
-
8/13/2019 m2x3c i500c en m c Manual Gb
29/88
Technical Manual M2x3C+I500C/EN M/C
iSTAT M2x3 & I500 Modbus & DNP3.0 Page 27
Code Address Contents Data Ind Values and Dependencies
30667 Voltage Dips - L2: No. / Year T1
30668 Voltage Dips - L3: No. / Period T1
30669 Voltage Dips - L3: No. / Year T1
30670 Short Interruptions - L1: No. /Period
T1
30671 Short Interruptions - L1: No. /Year
T1
30672 Short Interruptions - L2: No. /Period
T1
30673 Short Interruptions - L2: No. /Year
T1
30674 Short Interruptions - L3: No. /Period
T1
30675 Short Interruptions - L3: No. /Year
T1
30676 Long Interruptions - L1: No. /Period
T1
30677 Long Interruptions - L1: No. /Year
T1
30678 Long Interruptions - L2: No. /Period
T1
30679 Long Interruptions - L2: No. /Year
T1
30680 Long Interruptions - L3: No. /Period
T1
30681 Long Interruptions - L3: No. /Year
T1
30682 30700 Reserved
PREVIOUS PERIOD QUALITY (M253 & i5MQ only)
30701 30781 Last finished period quality See Actual period quality
6.3 NORMALIZED MEASUREMENTS
Code Address Contents Data Ind Values and Dependencies
NORMALIZED ACTUAL MEASUREMENTS
30801 U1 T16
30802 U2 T16
30803 U3 T16
30804 Uavg (phase to neutral) T16
30805 U12 T16
30806 U23 T1630807 U31 T16
30808 Uavg (phase to phase) T16
30809 I1 T16
-
8/13/2019 m2x3c i500c en m c Manual Gb
30/88
M2x3C+I500C/EN M/C Technical Manual
Page 28 iSTAT M2x3 & I500 Modbus & DNP3.0
Code Address Contents Data Ind Values and Dependencies
30810 I2 T16
30811 I3 T16
30812 I T16
30813 I neutral (calculated) T16
30814 I neutral (measured) T16
30815 Iavg T16
30816 Active Power Phase L1 (P1) T17
30817 Active Power Phase L2 (P2) T17
30818 Active Power Phase L3 (P3) T17
30819 Active Power Total (Pt) T17
30820 Reactive Power Phase L1 (Q1) T17
30821 Reactive Power Phase L2 (Q2) T17
30822 Reactive Power Phase L3 (Q3) T17
30823 Reactive Power Total (Qt) T17
30824 Apparent Power Phase L1 (S1) T16
30825 Apparent Power Phase L2 (S2) T16
30826 Apparent Power Phase L3 (S3) T16
30827 Apparent Power Total (St) T16
30828 Power Factor Phase 1 (PF1) T17
30829 Power Factor Phase 2 (PF2) T1730830 Power Factor Phase 3 (PF3) T17
30831 Power Factor Total (PFt) T17
30832 CAP/IND P. F. Phase 1 (PF1) T17
30833 CAP/IND P. F. Phase 2 (PF2) T17
30834 CAP/IND P. F. Phase 3 (PF3) T17
30835 CAP/IND P. F. Total (PFt) T17
30836 1 (angle between U1 and I1) T17
30837 2 (angle between U2 and I2) T17
30838 3 (angle between U3 and I3) T17
30839Power Angle Total(atan2(Pt,Qt))
T17
30840 12 (angle between U1 and U2 T17
30841 23 (angle between U2 and U3 T17
30842 31 (angle between U3 and U1 T17
30843 Frequency T17
30844 U unbalance T16
30845 I1 THD% T16
30846 I2 THD% T16
30847 I3 THD% T16
30848 U1 THD% T16
-
8/13/2019 m2x3c i500c en m c Manual Gb
31/88
Technical Manual M2x3C+I500C/EN M/C
iSTAT M2x3 & I500 Modbus & DNP3.0 Page 29
Code Address Contents Data Ind Values and Dependencies
30849 U2 THD% T16
30850 U3 THD% T16
30851 U12 THD% T16
30852 U23 THD% T16
30853 U31 THD% T16
MAX DEMAND SINCE LAST RESET
30854Active Power Total (Pt) -(positive) T16
30855Active Power Total (Pt) -(negative) T16
30856 Reactive Power Total (Qt) - L T16
30857 Reactive Power Total (Qt) - C T16
30858 Apparent Power Total (St) T16
30859 I1 T16
30860 I2 T16
30861 I3 T16
DYNAMIC DEMAND VALUES
30862Active Power Total (Pt) -(positive) T16
30863Active Power Total (Pt) -(negative) T16
30864 Reactive Power Total (Qt) - L T16
30865 Reactive Power Total (Qt) - C T16
30866 Apparent Power Total (St) T16
30867 I1 T16
30868 I2 T16
30869 I3 T16
ENERGY
30870 Energy Counter 1 T17
30871 Energy Counter 2 T17
30872 Energy Counter 3 T17
30873 Energy Counter 4 T17
30874 Energy Counter 1 Cost T17
30875 Energy Counter 2 Cost T17
30876 Energy Counter 3 Cost T17
30877 Energy Counter 4 Cost T17
30878 Total Energy Counter Cost T17
30879 Active Tariff T130880 Internal Temperature T17
30881 30900 Reserved
-
8/13/2019 m2x3c i500c en m c Manual Gb
32/88
M2x3C+I500C/EN M/C Technical Manual
Page 30 iSTAT M2x3 & I500 Modbus & DNP3.0
Code Address Contents Data Ind Values and Dependencies
FAST RESPONCE normalised actual measurements
30901 U1 T16
30902 U2 T16
30903 U3 T16
30904 Uavg (phase to neutral) T16
30905 U12 T16
30906 U23 T16
30907 U31 T16
30908 Uavg (phase to phase) T16
30909 I1 T16
30910 I2 T16
30911 I3 T16
30912 I T16
30913 I neutral (calculated) T16
30914 I neutral (measured) T16
30915 Iavg T16
30916 Active Power Phase L1 (P1) T17
30917 Active Power Phase L2 (P2) T17
30918 Active Power Phase L3 (P3) T17
30919 Active Power Total (Pt) T17
30920Reactive Power Phase L1(Q1)
T17
30921Reactive Power Phase L2(Q2)
T17
30922Reactive Power Phase L3(Q3)
T17
30923 Reactive Power Total (Qt) T17
30924Apparent Power Phase L1(S1)
T16
30925Apparent Power Phase L2(S2)
T16
30926Apparent Power Phase L3(S3)
T16
30927 Apparent Power Total (St) T16
30928 Power Factor Phase 1 (PF1) T17
30929 Power Factor Phase 2 (PF2) T17
30930 Power Factor Phase 3 (PF3) T17
30931 Power Factor Total (PFt) T17
30932 CAP/IND P. F. Phase 1 (PF1) T17
30933 CAP/IND P. F. Phase 2 (PF2) T17
30934 CAP/IND P. F. Phase 3 (PF3) T17
30935 CAP/IND P. F. Total (PFt) T17
-
8/13/2019 m2x3c i500c en m c Manual Gb
33/88
Technical Manual M2x3C+I500C/EN M/C
iSTAT M2x3 & I500 Modbus & DNP3.0 Page 31
Code Address Contents Data Ind Values and Dependencies
30936 1 (angle between U1 and I1) T17
30937 2 (angle between U2 and I2) T17
30938 3 (angle between U3 and I3) T17
30939Power Angle Total(atan2(Pt,Qt))
T17
3094012 (angle between U1 andU2)
T17
3094123 (angle between U2 andU3)
T17
3094231 (angle between U3 andU1)
T17
30943 Frequency T17
30944U unbalance
T1630945 I1 THD% T16
30946 I2 THD% T16
30947 I3 THD% T16
30948 U1 THD% T16
30949 U2 THD% T16
30950 U3 THD% T16
30951 U12 THD% T16
30952 U23 THD% T16
30953 U31 THD% T16
30954 31000 Reserved
6.4 HARMONIC DATA
Code Address Contents Data Ind Values and Dependencies
PHASE VOLTAGE HARMONIC DATA
U1 Harmonic Data
31001 31002 Base for % calculation T531003 U1 1 Harmonic Abs % T16
31004 U1 1 Harmonic Phase Angle T17
31006 31126 U1 Harmonics from 2 to 62 T17
31127 U1 63 Harmonic Abs % T16
31128 U1 63 Harmonic Phase Angle T17
U2 Harmonic Data
31129 31130 Base for % calculation T5
31131 U2 1 Harmonic Abs % T16
31132 U2 1 Harmonic Phase Angle T17
31134 31254 U2 Harmonics from 2 to 62 T17
31255 U2 63 Harmonic Abs % T16
-
8/13/2019 m2x3c i500c en m c Manual Gb
34/88
M2x3C+I500C/EN M/C Technical Manual
Page 32 iSTAT M2x3 & I500 Modbus & DNP3.0
Code Address Contents Data Ind Values and Dependencies
31256 U2 63 Harmonic Phase Angle T17
U3 Harmonic Data
31257 31258 Base for % calculation T5
31259 U3 2 Harmonic Abs % T16
31260 U3 2 Harmonic Phase Angle T17
31262 31382 U3 Harmonics from 2 to 62 T17
31383 U3 63 Harmonic Abs % T16
31384 U3 63 Harmonic Phase Angle T17
LINE VOLTAGE HARMONIC DATA
U12 Harmonic Data
31385 31386 Base for % calculation T5
31387 U12 1 Harmonic Abs % T16
31388 U12 1 Harmonic Phase Angle T17
31390 31510 U12 Harmonics from 2 to 62 T17
31511 U12 63 Harmonic Abs % T16
31512 U12 63 Harmonic Phase Angle T17
U23 Harmonic Data
31513 31514 Base for % calculation T5
31515 U23 1 Harmonic Abs % T16
31516 U23 1 Harmonic Phase Angle T1731518 31638 U23 Harmonics from 2 to 62 T17
31639 U23 63 Harmonic Abs % T16
31640 U23 63 Harmonic Phase Angle T17
U31 Harmonic Data
31641 31642 Base for % calculation T5
31643 U31 2 Harmonic Abs % T16
31644 U31 2 Harmonic Phase Angle T17
31646 31766 U31 Harmonics from 2 to 62 T17
31767 U31 63 Harmonic Abs % T16
31768 U31 63 Harmonic Phase Angle T17
PHASE CURRENT HARMONIC DATA
I1 Harmonic Data
31769 31770 Base for % calculation T5
31771 I1 1 Harmonic Abs % T16
31772 I1 1 Harmonic Phase Angle T17
31774 31894 I1 Harmonics from 2 to 62 T17
31895 I1 63 Harmonic Abs % T16
31896 I1 63 Harmonic Phase Angle T17
I2 Harmonic Data
31897 31898 Base for % calculation T5
-
8/13/2019 m2x3c i500c en m c Manual Gb
35/88
Technical Manual M2x3C+I500C/EN M/C
iSTAT M2x3 & I500 Modbus & DNP3.0 Page 33
Code Address Contents Data Ind Values and Dependencies
31899 I2 1 Harmonic Abs % T16
31900 I2 1 Harmonic Phase Angle T17
31902 32022 I2 Harmonics from 2 to 62 T17
32023 I2 63 Harmonic Abs % T16
32024 I2 63 Harmonic Phase Angle T17
I3 Harmonic Data
32025 32026 Base for % calculation T5
32027 I3 1 Harmonic Abs % T16
32028 I3 1 Harmonic Phase Angle T17
32030 32150 I3 Harmonics from 2 to 62 T17
32151 I3 63 Harmonic Abs % T16
32152 I3 63 Harmonic Phase Angle T17
32153 32483 Reserved
6.5 MEASUREMENTS (IEEE 754)
Code Address Contents Data Ind Values and Dependencies
MEASUREMENTS (IEEE 754)
32484 32485 Uavg (phase to neutral) T_float
32486 32487 Uavg (phase to phase) T_float
32488 32489 I T_float
32490 32491 Active Power Total (Pt) T_float
32492 32493 Reactive Power Total (Qt) T_float
32494 32495 Apparent Power Total (St) T_float
32496 32497 Power Factor Total (PFt) T_float
32498 32499 Frequency T_float
32500 32501 U1 T_float
32502 32503 U2 T_float
32504 32505 U3 T_float32506 32507 Uavg (phase to neutral) T_float
32508 32509 U12 T_float
32510 32511 U23 T_float
32512 32513 U31 T_float
32514 32515 Uavg (phase to phase) T_float
32516 32517 I1 T_float
32518 32519 I2 T_float
32520 32521 I3 T_float
32522 32523 I T_float
32524 32525 I neutral (calculated) T_float
32526 32527 I neutral (measured) T_float
-
8/13/2019 m2x3c i500c en m c Manual Gb
36/88
M2x3C+I500C/EN M/C Technical Manual
Page 34 iSTAT M2x3 & I500 Modbus & DNP3.0
Code Address Contents Data Ind Values and Dependencies
32528 32529 Iavg T_float
32530 32531 Active Power Phase L1 (P1) T_float
32532 32533 Active Power Phase L2 (P2) T_float
32534 32535 Active Power Phase L3 (P3) T_float
32536 32537 Active Power Total (Pt) T_float
32538 32539 Reactive Power Phase L1 (Q1) T_float
32540 32541 Reactive Power Phase L2 (Q2) T_float
32542 32543 Reactive Power Phase L3 (Q3) T_float
32544 32545 Reactive Power Total (Qt) T_float
32546 32547Apparent Power Phase L1(S1) T_float
32548 32549Apparent Power Phase L2(S2) T_float
32550 32551Apparent Power Phase L3(S3) T_float
32552 32553 Apparent Power Total (St) T_float
32554 32555 Power Factor Phase 1 (PF1) T_float
32556 32557 Power Factor Phase 2 (PF2) T_float
32558 32559 Power Factor Phase 3 (PF3) T_float
32560 32561 Power Factor Total (PFt) T_float
32562 32563 CAP/IND P. F. Phase 1 (PF1) T_float
32564 32565 CAP/IND P. F. Phase 2 (PF2) T_float
32566 32567 CAP/IND P. F. Phase 3 (PF3) T_float
32568 32569 CAP/IND P. F. Total (PFt) T_float
32570 32571 1 (angle between U1 and I1) T_float
32572 32573 2 (angle between U2 and I2) T_float
32574 32575 3 (angle between U3 and I3) T_float
32576 32577Power Angle Total(atan2(Pt,Qt)) T_float
32578 3257912 (angle between U1 andU2) T_float
32580 3258123 (angle between U2 andU3) T_float
32582 3258331 (angle between U3 andU1) T_float
32584 32585 Frequency T_float
32586 32587 U unbalace T_float
32588 32589 I1 THD% T_float
32590 32591 I2 THD% T_float32592 32593 I3 THD% T_float
32594 32595 U1 THD% T_float
32596 32597 U2 THD% T_float
-
8/13/2019 m2x3c i500c en m c Manual Gb
37/88
Technical Manual M2x3C+I500C/EN M/C
iSTAT M2x3 & I500 Modbus & DNP3.0 Page 35
Code Address Contents Data Ind Values and Dependencies
32598 32599 U3 THD% T_float
32600 32601 U12 THD% T_float
32602 32603 U23 THD% T_float
32604 32605 U31 THD% T_float
MAX DEMAND SINCE LASTRESET
32606 32607Active Power Total (Pt) -(positive) T_float
32608 32609Active Power Total (Pt) -(negative) T_float
32610 32611 Reactive Power Total (Qt) - L T_float
32612 32613 Reactive Power Total (Qt) - C T_float
32614 32615 Apparent Power Total (St) T_float32616 32617 I1 T_float
32618 32619 I2 T_float
32620 32621 I3 T_float
DYNAMIC DEMAND VALUES
32622 32623Active Power Total (Pt) -(positive) T_float
32624 32625Active Power Total (Pt) -(negative) T_float
32626 32627 Reactive Power Total (Qt) - L T_float32628 32629 Reactive Power Total (Qt) - C T_float
32630 32631 Apparent Power Total (St) T_float
32632 32633 I1 T_float
32634 32635 I2 T_float
32636 32637 I3 T_float
ENERGY
32638 32639 Energy Counter 1 T_float
32640 32641 Energy Counter 2 T_float
32642 32643 Energy Counter 3 T_float
32644 32645 Energy Counter 4 T_float
32646 32647 Energy Counter 1 Cost T_float
32648 32649 Energy Counter 2 Cost T_float
32650 32651 Energy Counter 3 Cost T_float
32652 32653 Energy Counter 4 Cost T_float
32654 32655 Total Energy Counter Cost T_float
32656 32657 Active Tariff T_float
32658 32659 Internal Temperature T_float
ANALOGUE INPUTS
-
8/13/2019 m2x3c i500c en m c Manual Gb
38/88
M2x3C+I500C/EN M/C Technical Manual
Page 36 iSTAT M2x3 & I500 Modbus & DNP3.0
Code Address Contents Data Ind Values and Dependencies
32660 32661 Analog input 1 T_float
32662 32663 Analog input 2 T_float
32664 32665 Analog input 3 T_float
32666 32667 Analog input 4 T_float
32668 33000 Reserved
-
8/13/2019 m2x3c i500c en m c Manual Gb
39/88
Technical Manual M2x3C+I500C/EN M/C
iSTAT M2x3 & I500 Modbus & DNP3.0 Page 37
6.6 PRODUCT SETTINGS
Address Contents Data Ind Values/Dependencies Min Max P.level
SYSTEM COMMANDS
40001 40002 User Password (L1,L2)
T_Str4AZ
Password to attempt user accesslevel upgrade
0
40003 40005 Factory Password(FAC)
T_Str6 AZ Password to attempt factory accesslevel upgrade 0
40006 40007 Level 1 - Userpassword
T_Str4 AZ 1
40008 40009 Level 2 - Userpassword
T_Str4 AZ 2
40010 40011 Reserved
40012 Operator CommandRegister
T1 1Save Settings
2
2 Abort Settings3 Restart Instrument
4 Restart Ethernet
5 Save Settings and Restart Ethernet
40013 Reset commandregister 1
T1 Bit-0 Reset counter 1 1
Bit-1 Reset counter 2
Bit-2 Reset counter 3
Bit-3 Reset counter 4
Bit-4 Reset counter 1 Cost
Bit-5 Reset counter 2 Cost
Bit-6 Reset counter 3 Cost
Bit-7 Reset counter 4 Cost
Bit-8 Reset Minimum/Maximum values
Bit-9 Synchronize MD
Bit-10 Reset last period MD
Bit-11 Reset MD values
40014Reset commandregister 2
T1 Bit-0 Reset alarm output relay 1 1
Bit-1 Reset alarm output relay 2
Bit-2 Reset alarm output relay 3
Bit-3 Reset alarm output relay 4
40015 40100 Reserved
GENERAL SETTINGS
40101 40120 Description Str_40 2
40121 40140 Location Str_40 2
40141 Password activation Reserved
40142 Password lock time T1 Minutes, 0 = No lock 0 60 2
40143 Conection Mode T1 0 No mode 1 5 2
1 1b - Single Phase2 3b - 3 phase 3 wire balanced
3 4b - 3 phase 4 wire balanced
4 3u - 3 phase 3 wire unbalanced
5 4u - 3 phase 4 wire unbalanced
-
8/13/2019 m2x3c i500c en m c Manual Gb
40/88
M2x3C+I500C/EN M/C Technical Manual
Page 38 iSTAT M2x3 & I500 Modbus & DNP3.0
Address Contents Data Ind Values/Dependencies Min Max P.level
40144 CT Secondary T4 mA 2
40145 CT Primary T4 A/10 2
40146 VT Secundary T4 mV 2
40147 VT Primary T4 V/10 240148 Current input range
(%)T16 10000 for 100% 5.00 260.00 2
40149Voltage input range(%)
T16 10000 for 100% 2.50 100.00 2
40150Frequency nominalvalue
T1 Hz 10 1000 2
40151 CT Connection T1 0 Normal 0 1 1
1 Disable wrong connectionchecking
40152 MD Time constant T1 minutes (0=disabled) 0 255 2
40153 MD Number ofsliding windows
T1 0=thermal 0 15 2
40154Starting total currentfor PFt & Pat
T16 2000 for 20mA 0 10000 2
40155Starting current forall powers
T16 200 for 2mA 0 4000 2
40156 Language T1 0 English 0 12 0
1 French
2 German
3 Spanish
4
5 Russian
6 Danish
7 Italian
8 US English
9
10 Polish
11 Portuguese
12
40157 40158 Currency Str_4 2
40159 Temperature unit T1 0 C 0 1 2
1 F
40160 Date format T1 0 DD.MM.YYYY 0 1 1
1 MM/DD/YYYY
40161 40162 Time T9 1
40163 40164 Date T10 1
40165 Reserved T1 Reserved
40166Automatic changeS/W time
T1 0 No 0 1 1
1 Yes
40167
Starting voltage for
SYNC
T1 5000 for 5V 1000 16000
2
40168 Min/Max reset mode T1 0 Manual reset 0 4 2
1 Day reset (00:00)
2 Week reset (Monday, 00:00)
-
8/13/2019 m2x3c i500c en m c Manual Gb
41/88
Technical Manual M2x3C+I500C/EN M/C
iSTAT M2x3 & I500 Modbus & DNP3.0 Page 39
Address Contents Data Ind Values/Dependencies Min Max P.level
3 Month reset (First day of the month,00:00)
4 Year reset (January 1st, 00:00)
40169
Harmonics
calculation
T1 0 % of RMS 0 1 2
1 % of 1st Harmonics
40170 Comm. & LCDaverage interval
T1 3 8 periods (0.16s @50Hz) 3 8 2
4 16 periods (0.32s @50Hz)
5 32 periods (0.64s @50Hz)
6 64 periods (1.28s @50Hz) default
7 128 periods (2.56s @50Hz)
8 256 periods (5.12s @50Hz)
40171 LCD Contrast T2 -10 10 2
40172 LCD Back LightIntesnity
T1 0=No Backlight 0 102
40173 LCD Back Light TimeOff
T1 Minutes (0=Always on) 0 602
40174 LCD Demo cyclingperiod
T1 Seconds 1 602
40175LCD Custom screen1 - Line 1
T1 See OutTypes 0 1002
40176LCD Custom screen1 - Line 2
T1 See OutTypes 0 1002
40177LCD Custom screen1 - Line 3
T1 See OutTypes 0 1002
40178LCD Custom screen2 - Line 1
T1 See OutTypes 0 1002
40179LCD Custom screen2 - Line 2
T1 See OutTypes 0 1002
40180LCD Custom screen2 - Line 3
T1 See OutTypes 0 1002
40181LCD Custom screen3 - Line 1
T1 See OutTypes 0 1002
40182LCD Custom screen3 - Line 2
T1 See OutTypes 0 1002
40183LCD Custom screen3 - Line 3
T1 See OutTypes 0 1002
40184 40200 Reserved
-
8/13/2019 m2x3c i500c en m c Manual Gb
42/88
M2x3C+I500C/EN M/C Technical Manual
Page 40 iSTAT M2x3 & I500 Modbus & DNP3.0
Address Contents Data Ind Values/Dependencies Min Max P.level
COMMUNICATION
40201 Port 1: DeviceAddress (DNP3)
T1 0 65519 2
40202 Port 1: DeviceAddress (Modbus)
T1 1 247 2
40203 Port 1: Baud Rate T1 0 Baud rate 1200 1 7 2
1 Baud rate 2400
2 Baud rate 4800
3 Baud rate 9600
4 Baud rate 19200
5 Baud rate 38400
6 Baud rate 57600
7 Baud rate 115200
40204 Port 1: Stop Bit T1 0 1 Stop bit 0 1 2
1 2 Stop bits
40205 Port 1: Parity T1 0 No parity 0 2 2
1 Odd parity
2 Even parity
40206 Port 1: Data Bits T1 0 8 bits 0 1 2
1 7 bits
40207 Port 1: TCP Port T1 1024 65535 2
4020840227
Port 1: IP Host NameT_Str_40
40228 40229 Port 1: IP Address T_Hex4
40230 40231 Port 1: Subnet Mask T_Hex4
40232 40233Port 1: DefaultRouter
T_Hex4
40233 40250 Reserved
40251Port 2: DeviceAddress (DNP3)
T1 0 65519 1
40252Port 2: DeviceAddress (Modbus)
T1 1 247 2
40253 Port 2: Baud Rate T1 See PORT 1 1 7 2
40254 Port 2: Stop BitT1
See PORT 1 0 1 2
40255 Port 2: Parity T1 See PORT 1 0 2 2
40256 Port 2: Data Bits T1 See PORT 1 0 0 2
40257 40300 Reserved
40301 40400 Reserved Port 3 -Port 4
ENERGY
40401 Active Tariff T1 0 Tariff input 0 5 1
1..4 Tariff 1..4
5 Tariff clock
40402 Common EnergyCounter Exponent
T2 -3 42
40403 Common EnergyCost Exponent
T2 -6 32
-
8/13/2019 m2x3c i500c en m c Manual Gb
43/88
Technical Manual M2x3C+I500C/EN M/C
iSTAT M2x3 & I500 Modbus & DNP3.0 Page 41
40404 Common Tariff PriceExponent
T2 -6 32
40405 Tariff 1: 1kWh Price T1 0 65500 2
40406 Tariff 2: 1kWh Price T1 0 65500 2
40407 Tariff 3: 1kWh Price T1 0 65500 2
40408 Tariff 4: 1kWh Price T1 0 65500 2
40409 Tariff 1: 1kvarh Price T1 0 65500 2
40410 Tariff 2: 1kvarh Price T1 0 65500 2
40411 Tariff 3: 1kvarh Price T1 0 65500 2
40412 Tariff 4: 1kvarh Price T1 0 65500 2
40413 Tariff 1: 1kVAh Price T1 0 65500 2
40414 Tariff 2: 1kVAh Price T1 0 65500 2
40415 Tariff 3: 1kVAh Price T1 0 65500 2
40416 Tariff 4: 1kVAh Price T1 0 65500 2
40417 40419 Reserved
40420Reactive powercalculation
T10 Standard calculation (Q
2=S
2 P
2)
0 1 2
1 Delayed Current method
40421Energy Counter 1Parameter
T10 No Parameter
0 19 2
1 Active Power
2 Reactive power
3 Apparent Power
5 Active Power Phase 1
6 Reactive power Phase 1
7 Apparent Power Phase 1
9 Active Power Phase 2
10 Reactive power Phase 2
11 Apparent Power Phase 2
13 Active Power Phase 3
14 Reactive power Phase 3
15 Apparent Power Phase 3
16 Pulse input 1 (reg 40402 not used)
17 Pulse input 2 (reg 40402 not used)
18 Pulse input 3 (reg 40402 not used)19 Pulse input 4 (reg 40402 not used)
40422Energy Counter 1Configuration
T1 Bit-0Quadrant I Enabled
0 63 2
Bit-1 Quadrant II Enabled
Bit-2 Quadrant III Enabled
Bit-3 Quadrant IIII Enabled
Bit-4 Absolute Value
Bit-5 Invert Value
40423Energy Counter 1Divider
T1 01
0 4 2
1 10
2 100
3 1000
4 10000
-
8/13/2019 m2x3c i500c en m c Manual Gb
44/88
M2x3C+I500C/EN M/C Technical Manual
Page 42 iSTAT M2x3 & I500 Modbus & DNP3.0
40424Energy Counter 1Tariff Selector
T1Bit-0
Tariff 1 Enabled0 15
2
Bit-1 Tariff 2 Enabled
Bit-2 Tariff 3 Enabled
Bit-3 Tariff 4 Enabled
40425 40430 Reserved
40431Energy Counter 2Parameter
T1see Energy Counter 1 Parameter
0 192
40432Energy Counter 2Configuration
T1see Energy Counter 1 Configuration
0 632
40433Energy Counter 2Divider
T1see Energy Counter 1 Divider
0 42
40434Energy Counter 2Tariff Selector
T1 see Energy Counter 1 TariffSelector
0 152
40435 40440 Reserved
40441Energy Counter 3Parameter
T1see Energy Counter 1 Parameter
0 192
40442Energy Counter 3Configuration
T1see Energy Counter 1 Configuration
0 632
40443Energy Counter 3Divider
T1see Energy Counter 1 Divider
0 42
40444Energy Counter 3Tariff Selector
T1 see Energy Counter 1 TariffSelector
0 152
40445 40450 Reserved
40451Energy Counter 4Parameter
T1see Energy Counter 1 Parameter
0 192
40452Energy Counter 4Configuration
T1see Energy Counter 1 Configuration
0 632
40453Energy Counter 4Divider
T1see Energy Counter 1 Divider
0 42
40454Energy Counter 4Tariff Selector
T1 see Energy Counter 1 TariffSelector
0 152
40455 40500 Reserved
TARIFF CLOCK
40501 Tariff Table 1 DaySelector
T1 Bit-0 Monday 0 1023 2
Bit-1 Tuesday
Bit-2 Wednesday
Bit-3 Thursday
Bit-4 Friday
Bit-5 Saturday
Bit-6 Sunday
Bit-7 Holiday
Bit-8 Hebrew Holiday 1
Bit-9 Hebrew Holiday 2
40502 Tariff Table 2 DaySelector
T1 see Tariff Table 1 Day Selector 0 1023 2
40503 Tariff Table 3 DaySelector
T1 see Tariff Table 1 Day Selector 0 1023 2
40504 Tariff Table 4 DaySelector
T1 see Tariff Table 1 Day Selector 0 1023 2
40505 Start date of Season 1 T10A 0.0. for unused season 2
40506 Start date of Season 2 T10A 0.0. for unused season 2
40507 Start date of Season 3 T10A 0.0. for unused season 2
-
8/13/2019 m2x3c i500c en m c Manual Gb
45/88
Technical Manual M2x3C+I500C/EN M/C
iSTAT M2x3 & I500 Modbus & DNP3.0 Page 43
40508 Start date of Season 4 T10A 0.0. for unused season 2
SEASON 1, TARIFF TABLE 1
40509 Time 1 T9A 24:00 for unused time 2
40510 Tariff Value 1 T1 1 4 2
40511 Time 2 T9A 24:00 for unused time 240512 Tariff Value 2 T1 1 4 2
40513 Time 3 T9A 24:00 for unused time 2
40514 Tariff Value 3 T1 1 4 2
40515 Time 4 T9A 24:00 for unused time 2
40516 Tariff Value 4 T1 1 4 2
40509 Time 1 T9A 24:00 for unused time 2
SEASON 1, TARIFF TABLE 2
40517 40524 TARIFF TABLE 2 See TARIFF TABLE 1 2
SEASON 1, TARIFF TABLE 3
40525 40532 TARIFF TABLE 3 See TARIFF TABLE 1 2
SEASON 1, TARIFF TABLE 4
40533 40540 TARIFF TABLE 4 See TARIFF TABLE 1 2
SEASON 2, TARIFF TABLE 1..4
40541 40572 SEASON 2,
TABLE 14
See SEASON 1
2
SEASON 3, TARIFF TABLE 1..4
40573 40604 SEASON 3,
TABLE 14
See SEASON 1
2
SEASON 4, TARIFF TABLE 1..4
40605 40636 SEASON 4,
TABLE 14
See SEASON 1
2
HOLIDAY DAY TABLE
40637 Holiday Date 1 T10A 0.0. for unused date 2
40638 Holiday Date 2 T10A 0.0. for unused date 2
40639 Holiday Date 3 T10A 0.0. for unused date 2
40640 Holiday Date 4 T10A 0.0. for unused date 2
40641 Holiday Date 5 T10A 0.0. for unused date 2
40642 Holiday Date 6 T10A 0.0. for unused date 2
40643 Holiday Date 7 T10A 0.0. for unused date 2
40644 Holiday Date 8 T10A 0.0. for unused date 2
40645 Holiday Date 9 T10A 0.0. for unused date 2
40646 Holiday Date 10 T10A 0.0. for unused date 2
40647 Holiday Date 11 T10A 0.0. for unused date 2
40648 Holiday Date 12 T10A 0.0. for unused date 2
40649 Holiday Date 13 T10A 0.0. for unused date 2
40650 Holiday Date 14 T10A 0.0. for unused date 2
40651 Holiday Date 15 T10A 0.0. for unused date 2
40652 Holiday Date 16 T10A 0.0. for unused date 2
40653 Holiday Date 17 T10A 0.0. for unused date 2
40654 Holiday Date 18 T10A 0.0. for unused date 2
40655 Holiday Date 19 T10A 0.0. for unused date 2
-
8/13/2019 m2x3c i500c en m c Manual Gb
46/88
M2x3C+I500C/EN M/C Technical Manual
Page 44 iSTAT M2x3 & I500 Modbus & DNP3.0
40656 Holiday Date 20 T10A 0.0. for unused date 2
40657 40700 Reserved
INPUTS / OUTPUTS
PULSE OUTPUTS
40701 Pulse Output 1Energy Counter T1 0 Alarm output 0 5 2
1 Counter 1
2 Counter 2
3 Counter 3
4 Counter 4
5 Tariff Clock
40702Pulse Output 1 No.Of pulses
T1 1 65535 2
40703Pulse Output 1Energy unit
T1 * 10^(Common Energy CounterExponent)
1 65535 2
40704Pulse Output 1 Pulselength
T1 ms 2 1000 2
40705Pulse Output 1 TariffSelector
T1 Bit-0 Tariff 1 enabled 0 15 2
Bit-1 Tariff 2 enabled
Bit-2 Tariff 3 enabled
Bit-3 Tariff 4 enabled
40706Pulse Output 2Energy Counter T1
0 5 2
40707Pulse Output 2 No.Of pulses
T1 1 65535 2
40708Pulse Output 2Energy unit
T1 * 10^(Common Energy CounterExponent)
1 65535 2
40709Pulse Output 2 Pulselength T1 ms
2 1000 2
40710Pulse Output 2 TariffSelector
T1 0 15 2
40711Pulse Output 3Energy Counter T1
0 5 2
40712Pulse Output 3 No.Of pulses
T1 1 65535 2
40713Pulse Output 3Energy unit
T1 * 10^(Common Energy CounterExponent)
1 65535 2
40714Pulse Output 3 Pulselength T1 ms
2 1000 2
40715Pulse Output 3 TariffSelector
T1 0 15 2
40716Pulse Output 4Energy Counter T1
0 5 2
40717Pulse Output 4 No.Of pulses
T1 1 65535 2
40718Pulse Output 4Energy unit
T1 * 10^(Common Energy CounterExponent)
1 65535 2
40719Pulse Output 4 Pulselength T1 ms
2 1000 2
40720Pulse Output 4 TariffSelector
T1 0 15 2
ALARM OUTPUT, OUTPUT 1
40721Enabled Alarmgroups
T1 Bit-0 Alarm group 1 enabled 0 15 2
-
8/13/2019 m2x3c i500c en m c Manual Gb
47/88
Technical Manual M2x3C+I500C/EN M/C
iSTAT M2x3 & I500 Modbus & DNP3.0 Page 45
Bit-1 Alarm group 2 enabled
Bit-2 Alarm group 3 enabled
Bit-3 Alarm group 4 enabled
40722 Output signal T1 0 Normal 0 8 2
1 Permanent
2 Pulsed
3 Always ON
4 Always OFF
5 Normal inverse
6 Permanent Inverse
7 Pulse Inverse
8 Start
40723 Output pulse length T1 Seconds 1 999 2
ALARM OUTPUT, OUTPUT 2
40724 40726 ALARM OUTPUT 2 See ALARM OUTPUT 1 2
ALARM OUTPUT, OUTPUT 3
40727 40729 ALARM OUTPUT 3 See ALARM OUTPUT 1 2
ALARM OUTPUT, OUTPUT 4
40730 40732 ALARM OUTPUT 4 See ALARM OUTPUT 1 2
40733 40800 Reserved
ANALOGUE OUTPUT, OUTPUT 1
40801 40802 Reserved
40803 Output 1 Type T1 0 1 mA 0 5 2
1 5 mA
2 10 mA
3 20 mA (Constant for M2x3)
4 1 V
5 10 V
40804 Output 1 Parameter T1 See OutTypes 0 110 2
40805Output 1 FunctionType T1
0Linear
0 1 2
1 Quadratic
40806
Output 1 Number of
Breakpoints T1 0 6
2
40807Output 1 Lower XPoint (X0) T17
% of parameter value-300 300
2
40808Output 1 Lower YPoint (Y0) T17
% of output type-300 300
2
40809Output 1 XBreakpoint 1 (X1) T17
% of parameter value-300 300
2
40810Output 1 YBreakpoint 1 (Y1) T17
% of output type-300 300
2
40811Output 1 XBreakpoint 2 (X2) T17
% of parameter value-300 300
2
40812
Output 1 Y
Breakpoint 2 (Y2) T17
% of output type
-300 300
2
40813Output 1 XBreakpoint 3 (X3) T17
% of parameter value-300 300
2
40814Output 1 YBreakpoint 3 (Y3) T17
% of output type-300 300
2
-
8/13/2019 m2x3c i500c en m c Manual Gb
48/88
M2x3C+I500C/EN M/C Technical Manual
Page 46 iSTAT M2x3 & I500 Modbus & DNP3.0
40815Output 1 XBreakpoint 4 (X4) T17
% of parameter value-300 300
2
40816Output 1 YBreakpoint 4 (Y4) T17
% of output type-300 300
2
40817Output 1 XBreakpoint 5 (X5) T17
% of parameter value-300 300
2
40818Output 1 YBreakpoint 5 (Y5) T17
% of output type-300 300
2
40819Output 1 XBreakpoint 6 (X6) T17
% of parameter value-300 300
2
40820Output 1 YBreakpoint 6 (Y6) T17
% of output type-300 300
2
40821Output 1 Averageinterval (i5xx only) T1 0 1 period (0.02s@ 50Hz) default 0 8 2
1 2 period (0.04s@ 50Hz)
2 4 period (0.08s@ 50Hz)
3 8 period (0.16s@ 50Hz)
4 16 period (0.32s@ 50Hz)
5 32 period (0.64s@ 50Hz)
6 64 period (1.28s@ 50Hz)
7 128 period (2.56s@ 50Hz)
8 256 period (05.12s@ 50Hz)
40822 40823 Reserved
ANALOGUE OUTPUT, OUTPUT 2
40824 40842 ANALOG OUTPUT 2 See ANALOG OUTPUT 1 2
40843 40844 Reserved
ANALOGUE OUTPUT, OUTPUT 3
40845 40863 ANALOG OUTPUT 3 See ANALOG OUTPUT 1 2
40864 40865 Reserved
ANALOGUE OUTPUT, OUTPUT 4
40866 40884 ANALOG OUTPUT 4 See ANALOG OUTPUT 1 2
40885 41000 Reserved
ANALOGUE INPUTs
40901 Input 1 Serial number T1 0 0 65535 r.o.
40902 Input 1 Type T1 0 Unknown 0 3 r.o.
1 DC Current 20mA
2 DC Voltage 10V
3 Resistance / Temperature
40903Input 1 ZeroCalibration point(Type 3) T17 wire resistance (Ohm) -25 25 2
40904 Input 1 Function T1 Input type 1 (DC Current 20mA) 0 7 2
0 DC Curent 20mA
1 DC Curent 2mA
Input type 2 (DC Voltage 10V)
0 DC Voltage 10V
1 DC Voltage 1V
Input type 3 (Resistance /Temperature)
0 Resistance 2 Kohm (2 wire)
-
8/13/2019 m2x3c i500c en m c Manual Gb
49/88
Technical Manual M2x3C+I500C/EN M/C
iSTAT M2x3 & I500 Modbus & DNP3.0 Page 47
1 Resistance 200 ohm (2 wire)
2 Resistance 2 Kohm (3 wire)
3 Resistance 200 ohm (3 wire)
4 Pt 1000 (2 wire)
5 Pt 100 (2 wire)
6 Pt 1000 (3 wire)
7 Pt 100 (3 wire)
40905 40906 Input 1 Unit Str_4 2
40907 Input 1 Exponent T2 -12 12 2
40908 Input 1 Zero Point T17 value at 0% input -300 300 2
40909 Input 1 End Point T17 value at 100% input -300 300 2
40910 40916 Reserved
40917 40932 Input 2 See Input 1
40933 40948 Input 3 See Input 1
40949 40964 Input 4 See Input 1
40965 41000 Reserved
ALARMS
41001Alarm Enable Flags116
T1 Bit-iEnable Alarm i
2
41002Alarm Enable Flags1732
T1 Bit-iEnable Alarm i
2
ALARM GROUP 1 (1..8)
41003Thermal function timeconstant
T1minutes
1 255 2
41004 Compare time delay T1 seconds 0 900 2
41005Hysteresis
T16% of compare value, if 0 then % ofnominal value
0 1000 2
41006 41007 Reserved
ALARM 1
41008 Alarm 1 parameter T1 See OutTypes 0 1023 2
41009 Alarm 1 function T1 Bit-1 Reserved: Store into memory (all) 0 255 2
Bit-2 Store into memory (1 per minute)
Bit-3 Activate LED
Bit-4 Activate Alarm Output
Bit-5 Activate Beep Output
Bit-6 Alarm Condition > (< if 0)
Bit-7 Use Thermal function
41010Alarm 1 comparevalue
T17 % of parameter value -300 300 2
ALARM 2
41011 41013 ALARM 2 See ALARM 1 2
ALARM 3
41014 41016 ALARM 3 See ALARM 1 2
ALARM 4
41017 41019 ALARM 4 See ALARM 1 2
ALARM 5
41020 41022 ALARM 5 See ALARM 1 2
ALARM 6
-
8/13/2019 m2x3c i500c en m c Manual Gb
50/88
M2x3C+I500C/EN M/C Technical Manual
Page 48 iSTAT M2x3 & I500 Modbus & DNP3.0
41023 41025 ALARM 6 See ALARM 1 2
ALARM 7
41026 41028 ALARM 7 See ALARM 1 2
ALARM 8
41029 41031 ALARM 8 See ALARM 1 2
ALARM GROUP 2 (9..16)
41032 41060
ALARM GROUP 2
(No. 916) See ALARM GROUP 1 2
ALARM GROUP 3 (17..24)
41061 41089
ALARM GROUP 3
(No. 1724) See ALARM GROUP 1 2
ALARM GROUP 4 (25..32)
41090 41118
ALARM GROUP 4
(No. 2532) See ALARM GROUP 1 241119 41998 Reserved
MEMORY
41999 42500 Memory Settings
POWER SUPPLY QUALITY (M253 & i5MQ only)
42501 Monitoring mode T1 0 No mode 0 1 2
1 EN50160
42502 Energetic system T1 0 Low voltage 0 1
1 Medium voltage
2 Low voltage (Islanded system)
3 Medium voltage (Islanded system)
42503Nominal SupplyVoltage
T16 % of VT Primary 5.00 120.00 2
42504Nominal PowerFrequency T1 0 50 Hz 0 1 2
1 60 Hz
42505 Monitoring period T1 Weeks 1 10 2
42506 Monitoring start day T1 0 Monday 0 6 2
1 Tuesday
2 Wednesday
3 Thursday
4 Friday
5 Saturday
6 Sunday
42507 Voltage Hysteresis T16 %o of Nominal Supply Voltage 0.00 5.00 2
42508 42509 Reserved
FREQUENCY VARIATIONS
42510 Average interval T1 0 10 sec
42511
Frequency variation 1
Upper Limit %
T16 0.01 25.00 2
42512Frequency variation 1Lower Limit %
T16 0.01 25.00 2
42513Frequency variation 1Required Quality
T16 75.00 100.00 2
-
8/13/2019 m2x3c i500c en m c Manual Gb
51/88
Technical Manual M2x3C+I500C/EN M/C
iSTAT M2x3 & I500 Modbus & DNP3.0 Page 49
42514Frequency variation 1Period T1 0 No monitoring
0 3 2
1 Info only
2 Monitoring time
3 Year
42515 42515 Reserved
42516 Frequency variation 2Upper Limit %
T16 0.01 25.00 2
42517 Frequency variation 2Lower Limit %
T16 0.01 25.00 2
42518 Frequency variation 2Required Quality
T16 75.00 100.00 2
42519 Frequency variation 2Period
T1 See Frequency variation 1 Period 0 3 2
42520 42529 Reserved
VOLTAGE VARIATIONS
42530 Average interval T1 2 10 min
42531 Voltage variation 1Upper Limit %
T16 0.01 25.00 2
42532 Voltage variation 1Lower Limit %
T16 0.01 25.00 2
42533 Voltage variation 1Required Quality
T16 75.00 100.00 2
42534 Voltage variation 1Period
T1 See Frequency variation 1 Period 0 3 2
42535 42535 Reserved
VOLTAGE VARIATIONS
42536 Voltage variation 2Upper Limit %
T16 0.01 25.00 2
42537 Voltage variation 2Lower Limit %
T16 0.01 25.00 2
42538 Voltage variation 2Required Quality
T16 75.00 100.00 2
42539 Voltage variation 2Period
T1 See Frequency variation 1 Period 0 3 2
42540 42540 Reserved
42541 Voltage AsymmetryLimit %
T16 0.01 25.00 2
42542 Symmetry RequiredQuality
T16 75.00 100.00 2
42543 Symmetry Period T1 See Frequency variation 1 Period 0 3 2
42544 42550 Reserved
VOLTAGE INTERRUPTIONS
42551 Voltage Dip Limit % T16 50.00 99.00 2
42552 Allowed No. ofVoltage Dips
T1 0 10000 2
42553 Voltage Dips Period T1 See Frequency variation 1 Period 0 3 2
42554 Interruption Limit % T16 1.00 25.00 2
42555 Short Interruption
time
T1 Seconds 1 300 2
42556 Allowed No. of ShortInterruptions
T1 0 10000 2
42557 Short InterruptionsPeriod
T1 See Frequency variation 1 Period 0 3 2
-
8/13/2019 m2x3c i500c en m c Manual Gb
52/88
M2x3C+I500C/EN M/C Technical Manual
Page 50 iSTAT M2x3 & I500 Modbus & DNP3.0
42558 Allowed No. of LongInterruptions
T1 0 10000 2
42559 Long InterruptionsPeriod
T1 See Frequency variation 1 Period 0 3 2
42560 42560 Reserved
TRANSIENTS42561 Transient Limit % T16 1.0 10.00 2
42562 Transient Rate of rice T16 5.00 600.00 2
42563 Allowed No. ofTransients
T1 0 10000 2
42564 Transients Period T1 See Frequency variation 1 Period 0 3 2
42565 42566 Reserved
OVERVOLTAGES AND FLICKERS
42567 Average interval(Flicker)
T1 2 10 min
42568 Short term Pst FlickerLimit % T16 0.01 25.00 2
42569 Flicker Pst RequiredQuality
T16 75.00 100.00 2
42570 Flicker Pst Period T1 See Frequency variation 1 Period 0 3 2
42571 Average interval(Flicker)
T1 4 2 hour
42572 Long term Plt FlickerLimit %
T16 0.01 25.00 2
42573 Flicker Plt RequiredQuality
T16 75.00 100.00 2
42574 Flicker Plt Period T1 See Frequency variation 1 Period 0 3 2
42575 TemporaryOvervoltage Limit %
T16 101.00 150.00 2
42576 Allowed No. ofOvervoltages
T1 0 10000 2
42577 Overvoltage Period T1 See Frequency variation 1 Period 0 3 2
42578 42580 Reserved
HARMONICS & THD
42581 Average interval T1 2 10 min
42582 THD Limit % T16 0.01 25.00 2
42583THD RequiredQuality
T1675.00 100.00 2
42584 THD Period T1 See Frequency variation 1 Period 0 3 2
42585 Harmonics RequiredQuality
T16 75 100 2
42586 Harmonics Period T1 See Frequency variation 1 Period 0 3 2
42587 2. Harmonic Limit % T16 0.01 25.00 2
42588 3. Harmonic Limit % T16 0.01 25.00 2
42589 4. Harmonic Limit % T16 0.01 25.00 2
42590 5. Harmonic Limit % T16 0.01 25.00 2
42591 6. Harmonics Limit % T16 0.01 25.00 2
42592 7. Harmonic Limit % T16 0.01 25.00 242593 9. Harmonic Limit % T16 0.01 25.00 2
42594 11. Harmonic Limit % T16 0.01 25.00 2
42595 13. Harmonic Limit % T16 0.01 25.00 2
42596 15. Harmonic Limit % T16 0.01 25.00 2
-
8/13/2019 m2x3c i500c en m c Manual Gb
53/88
Technical Manual M2x3C+I500C/EN M/C
iSTAT M2x3 & I500 Modbus & DNP3.0 Page 51
42597 17. Harmonic Limit % T16 0.01 25.00 2
42598 19. Harmonic Limit % T16 0.01 25.00 2
42599 21. Harmonic Limit % T16 0.01 25.00 2
42600 23. Harmonic Limit % T16 0.01 25.00 2
42601 25. Harmonic Limit % T16 0.01 25.00 2
-
8/13/2019 m2x3c i500c en m c Manual Gb
54/88
M2x3C+I500C/EN M/C Technical Manual
Page 52 iSTAT M2x3 & I500 Modbus & DNP3.0
Values/Dependencies Min Max Step Pass
M233 0
Software version 208 0
(=6 if incorrect divider @40025)(1)
-6 9 1 0
(=6 if incorrect divider @40026)(1) -6 9 1 0
(=6 if incorrect divider @40027)(1) -6 9 1 0
(=6 if incorrect divider @40028)(1)
-6 9 1 0
Total export active energy (default) -99999999 899999999 1 0
Total import reactive energy (default) -99999999 899999999 1 0
Pulse output 1 -99999999 899999999 1 0
Pulse output 2 -99999999 899999999 1 0
W 0
W 0
W 0
W 0
var L(if > 0); var C (if < 0) 0
var L(if > 0); var C (if < 0) 0
var L(if > 0); var C (if < 0) 0
var L(if > 0); var C (if < 0) 0
A 0
A 0
A 0
A 0V 0
V 0
V 0
V 0
VA 0
VA 0
VA 0
VA 0
mHz 00.000 65.535 0.001 Hz 0
mHz 00.000 65.535 0.001 Hz 0
mHz 00.000 65.535 0.001 Hz 0
mHz 00.000 65.535 0.001 Hz 0
0.01 deg -180.00 +179.99 0.01 deg 0
0.01 deg -180.00 +179.99 0.01 deg 0
0.01 deg -180.00 +179.99 0.01 deg 0
0.01 deg -180.00 +179.99 0.01 deg 0
A 0
0.01 deg -180.00 +179.99 0.01 deg 0
0.01 deg -180.00 +179.99 0.01 deg 0
0.01 deg -180.00 +179.99 0.01 deg 0
V 0
-
8/13/2019 m2x3c i500c en m c Manual Gb
55/88
Technical Manual M2x3C+I500C/EN M/C
iSTAT M2x3 & I500 Modbus & DNP3.0 Page 53
Values/Dependencies Min Max Step Pass
V 0
V 0
V 0
Total active power 0
Total absolute reactive power 0
Total apparent power 0
Total I 0
Total active power 0
Total absolute reactive power 0
Total apparent power 0
Total I 0
0.01 % 0.00 400.00 0.01 % 00.01 % 0.00 400.00 0.01 % 0
0.01 % 0.00 400.00 0.01 % 0
0.01 % 0.00 400.00 0.01 % 0
0.01 % 0.00 400.00 0.01 % 0
0.01 % 0.00 400.00 0.01 % 0
0.01 % 0.00 400.00 0.01 % 0
0.01 % 0.00 400.00 0.01 % 0
0.01 % 0.00 400.00 0.01 % 0
Reset Counter 1 1
Reset Counter 1
Reset pulse output Counter 1
Reset pulse output Counter 2
Synchronise MD
Reset last period MD
Reset MD Values
1 V 0
10 A/10 = 1 A 50 A/10 = 5 A 0.1 V 0
2300 for 230 V 0.1 V 2
Unsigned integer value 1 15999 1
Unsigned exponent 0 3 1
10 775 1 V, 5 V 2
1 4000 1 2
Single phase 2
3 phase 3 wire balanced
3 phase 4 wire balanced
3 phase 3 wire unbalanced
3 phase 4 wire unbalanced1200 baud 2
2400 baud
4800 baud
-
8/13/2019 m2x3c i500c en m c Manual Gb
56/88
M2x3C+I500C/EN M/C Technical Manual
Page 54 iSTAT M2x3 & I500 Modbus & DNP3.0
Values/Dependencies Min Max Step Pass
9600 baud
19200 baud
38400 baud
57600 baud115200 baud
1 => 2 stop bits; 0 => 1 stop bit
1 => Odd parity; 0 => Even parity
1 => Parity; 0 => No parity
1 => 7 bits; 0 => 8 bits (read only)
> 10 ms response time
Disable 2
Time constant (window period;interval of sub-period)
Thermal function
Fixed window
Sliding window; # of periods
Enable quadrant 1 2
Enable quadrant 2
Enable quadrant 3
Enable quadrant 4
Absolute value
Inverted value
1 => Reactive energy; 0 => Activeenergy
Enable quadrant 1
Enable quadrant 2
Enable quadrant 3
Enable quadrant 4
Absolute value
Inverted value
1 => Reactive energy; 0 => Activeenergy
Same as Counter 2 mode 2
Same as Counter 1 mode
1, 10, 100, 1000, 10000(1)
2
1, 10, 100, 1000, 10000(1)
2
1, 2, 5, 10, 20, 50, , 50000(1)
2
1, 2, 5, 10, 20, 50, , 50000(1)
2
320 for 0.2% 3-128 127 1 3
I1, family HI 3
I2, family HI
-
8/13/2019 m2x3c i500c en m c Manual Gb
57/88
Technical Manual M2x3C+I500C/EN M/C
iSTAT M2x3 & I500 Modbus & DNP3.0 Page 55
Values/Dependencies Min Max Step Pass
I3, family HI
I1, family LO
I2, family LO
I3, family LO
U1
U2
U3
Power angle phase L1, family HI
Power angle phase L2, family HI
Power angle phase L3, family HI
Power angle phase L1, family LO
Power angle phase L2, family LOPower angle phase L3, family LO
Calibrate voltage inputs 3
Calibrate current inputs
Calibrate phase angles
English 2
French
German
Spanish
Russian
Danish
Only 0 can be written 0 3 1 0
Counter 1 must be halted -99999999 899999999 1 2
Counter 2 must be