m2x3c i500c en m c manual gb

Upload: dinakaran2020

Post on 04-Jun-2018

324 views

Category:

Documents


2 download

TRANSCRIPT

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    1/88

    M2x3&I500CommunicationsManual

    Communications Manual

    iSTAT M2x3 & I500

    Publication Reference: M2x3C+I500C/EN/M/C

    M2x3C+I500C/EN/M/C2011.ALSTOM,theALSTOM logoandanyalternativeversionthereofaretrademarksandservicemarksofALSTOM.Theothernamesmentioned,registeredornot,arethepropertyoftheirrespectivecompanies.Thetechnicalandotherdatacontainedinthisdocumentisprovidedforinformationonly.NeitherALSTOM,itsofficersoremployeesacceptresponsibilityfor,orshouldbetakenasmakinganyrepresentationorwarranty(whetherexpressorimplied),astotheaccuracyorcompletenessofsuchdataortheachievementofanyprojectedperformancecriteriawheretheseareindicated.ALSTOMreservestherighttoreviseorchangethisdataatanytimewithoutfurthernotice.

    GRID

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    2/88

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    3/88

    Technical Manual M2x3C+I500C/EN M/C

    iSTAT M2x3 & I500 Modbus & DNP3.0 Page 1

    CONTENT

    1. COMMUNICATIONS SETUP 31.1 Setup communications on the M2x3 and I500 31.2 Ethernet 31.2.1 Using Fixed IP address 31.2.2 Local Port 31.3 Ethernet (XPort) communication 32. MODBUS INFORMATION 62.1 introduction 62.2 Transactions 62.3 Request 62.4 Response 62.5 Request - response cycle example 62.5.1 Request Frame 72.5.2 Response Frame 72.6 Framing 72.7 RTU framing 73. MODBUS SUPPORTED FUNCTIONS AND USAGE 83.1 03 read from holding registers 83.1.1 Request Frame 83.1.2 Response Frame 83.2 04 read from input registers 83.2.1 Request Frame 83.2.2 Response Frame 93.3 06 write to a single holding register 93.3.1 Request Frame 93.3.2 Response Frame 93.4 16 (10 HEX) write to one or more registers 93.4.1 Request Frame 93.4.2 Response Frame 103.5 17 (11HEX) report slave id 103.5.1 Request Frame 103.5.2 Response Frame 103.6 77 (4D HEX) read measurement string 103.6.1 Request Frame 103.6.2 Response Frame 103.6.3 Value Codes 113.7 82 (52 HEX) re-read output buffer 12

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    4/88

    M2x3C+I500C/EN M/C Technical Manual

    Page 2 iSTAT M2x3 & I500 Modbus & DNP3.0

    3.7.1 Request Frame 123.7.2 Response Frame 124. MODBUS ERROR RESPONSES 134.1 Exception codes 135. MODBUS REGISTER MAPS 146. MODBUS DATA FOR M2X3 AND I5MT/MR/MQ 156.1 SYSTEM DATA 156.2 MEASUREMENTS 176.3 NORMALIZED MEASUREMENTS 276.4 HARMONIC DATA 316.5 MEASUREMENTS (IEEE 754) 336.6 PRODUCT SETTINGS 376.7 OUTPUT PARAMETERS 576.8 OUTTYPES 586.9 MODBUS DATA TYPES 656.10 FLASH DATA 687. MODBUS DATA FOR I5MC/MV/MS/ML 707.1 MEASUREMENTS 707.2 NORMALISED MEASUREMENTS 717.3 MEASUREMENTS (IEEE 754 ) 747.4 PRODUCT SETTINGS 757.5 MODBUS DATA TYPES 758. DNP3.0 PROGRAMMING FOR M2X3 AND I5MT/MR/MQ 778.1 DNP 3.0 DEVICE PROFILE DOCUMENT 778.2 DNP3.0 REGISTER MAP 798.3 DATA TYPES DECODING 818.4 100% VALUE CALCULATIONS 819. RELATED DOCUMENTS 83

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    5/88

    Technical Manual M2x3C+I500C/EN M/C

    iSTAT M2x3 & I500 Modbus & DNP3.0 Page 3

    1. COMMUNICATIONS SETUP

    The Setup of the communications on the I500 or M2x3 is achieved using the QDSPconfiguration software. QDSP can communicate with the iSTAT products via RS232, RS485,USB and Ethernet. The option used will depend on which communication port is fitted to theproduct.

    The QDSP software always uses Modbus protocol to communicate with the product.

    1.1 Setup communications on the M2x3 and I500

    The setup of the communication ports is done using the QDSP software and is detailed in aseparate manual.

    It is suggested that the communications channel for the product required by the application isinitially set up using QDSP running on a PC. Then when that is working correctly the productcan be connected to the required intelligent device.

    1.2 Ethernet

    When using the QDSP over Ethernet the set-up will depend on how the PC and the productare connected. The Communication interface must have a unique IP address in the Ethernetnetwork. Two modes for assigning IP are available:

    Fixed IP address: In most installations a fixed IP address is required. A system providerusually defines IP addresses. An IP address should be within a valid IP range, unique foryour network and in the same Subnet mask as your PC.

    DHCP: Automatic method of assigning IP addressed (DHCP) is used in most networks. Ifyou are not sure if DHPC is used in your network, check it with your system provider.

    1.2.1 Using Fixed IP address

    When the PC is directly connected to the Instrument a Fixed IP address will have to be usedwith the PC configured in the local area connection. If the connection is made without a Hub

    or Switch, the connection has to be made with a Crossover Ethernet cable.

    The fixed IP address can be set in the product using QDSP.

    1.2.2 Local Port

    Is the physical connector on a device enabling the connection to be made. Use a nonreserved port number from 1025 to 65535. If using Redirector software, the port numbershould be between 14000 and 14009.

    Port numbers Function

    1 1024, 9999,30718

    Reserved numbers

    14000 14009 Reserved for Redirector

    1.3 Ethernet (XPort) communication

    There are 2 types of Ethernet interfaces used on the M2x3. QDSP will always allow thesetting of the IP address, but on the older version it does not allow the setting of Local Portetc. If required this has to be accessed using an internet browser.

    Any internet browser available can be used to access the interface in the product, type in theIP address of the product as the required internet address.

    The browser will communicate with the instrument and then display a request for password;press OK without entering a password and the XPORT screen will be displayed.

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    6/88

    M2x3C+I500C/EN M/C Technical Manual

    Page 4 iSTAT M2x3 & I500 Modbus & DNP3.0

    Select to display Network settings where Subnet Mask and Default Gateway canbe modified if required.

    Select to show connection settings, where local port can bemodified.

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    7/88

    Technical Manual M2x3C+I500C/EN M/C

    iSTAT M2x3 & I500 Modbus & DNP3.0 Page 5

    No other settings need to be changed.

    When changes are complete select

    After downloading the settings it is necessary to reset the M2x3 device to make the changesactive.

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    8/88

    M2x3C+I500C/EN M/C Technical Manual

    Page 6 iSTAT M2x3 & I500 Modbus & DNP3.0

    2. MODBUS INFORMATION

    2.1 introduction

    The Modbus protocol is a widely supported open interconnect protocol originally designed byModicon that can be enabled on the M2x3 and I500 via RS232, RS485, USB or Ethernet

    communication.

    There are two Modbus protocol types: Modbus RTU for serial communication (and USB) andModbus TCP for Ethernet communication. It is also possible to pass Modbus RTUcommunications over Ethernet.

    On Serial Communication, Modbus is a single master multiple slave protocol suitable for amulti-drop configuration as provided by the RS485 connection. Up to 32 devices can beconnected in this way. Single - drop RS232 or USB connection is also possible.

    2.2 Transactions

    Communication operates on a master-slave basis where only one device (the master) caninitiate transactions called 'Requests'. The other devices (slaves) respond by supplying the

    requested data to the master. This is called the 'Request - Response Cycle'.Master to slave request:

    Device address Function Code nx8 bit data bytes Error check

    Slave to master response:

    Device address Function Code nx8 bit data bytes Error check

    2.3 Request

    This Master to Slave transaction takes the form:

    Device address: Master addressing a slave (Address 0 is used for the broadcastaddress, which all slave devices recognise.).

    Function code: E.g. 04 ask the slave to read its Input Registers and respond withtheir contents.

    Data bytes: Tells the slave which register to start at and how many registersto read.

    2.4 Response

    This Slave to Master transaction takes the form:

    Device address: To let the master know which slave is responding.Function code: This is an echo of the request function code.

    Data bytes: Contains the data collected from the slave.

    2.5 Request - response cycle example

    Ia 160.00 A = 16000* 10-2A

    Data type T3 32 bitunsigned

    FE 00 3E 80(16)

    Data held in Modbus

    addresses

    30036(10) & 30037(10)

    30036(10)- 30000 (10)= 36 (10) 00 24 (16)

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    9/88

    Technical Manual M2x3C+I500C/EN M/C

    iSTAT M2x3 & I500 Modbus & DNP3.0 Page 7

    2.5.1 Request Frame

    Starting Register Register Count CRC

    Slave AddressHI LO

    Function code HI LO LO HI

    21 04 00 24 00 02

    2.5.2 Response Frame

    Register Data CRC

    Slave AddressLO HI

    Function code Byte Count HI LO HI LO

    21 04 04 FE 00 3E 80

    2.6 Framing

    There are two types of message framing for the serial communications, ASCII or RTU.

    iSTAT products supports RTU framing.

    2.7 RTU framing

    In RTU mode, messages start and end with a silent interval of at least 3.5 character times(t1-t2-t3-t4 as shown below).

    The advantage of this mode of framing is that it enables a greater character density and abetter data throughput. However, each message must be transmitted in a continuous stream.If a silent interval of more than 1.5 character times occurs before completion of the frame,the device flushes the incomplete message and assumes that the next byte will be theaddress field of a new message.

    Start Address Function Data CRC Check End

    t1-t2-t3-t4 8 bits 8 bits n x 8 bits 16 bits t1-t2-t3-t4

    The Cyclic Redundancy Check (CRC) field is two bytes, containing a 16 bit binary value. TheCRC value is calculated by the transmitting device, which appends the CRC to the message.The receiving device recalculates a CRC during receipt of the message, and compares thecalculated value to the actual value it received in the CRC field. If the two values are notequal an error results. The CRC-16 calculation is an industry standard method used for errordetection.

    One frame is transmitted as 1 start bit, 8 data bits and 2 stop bit. If parity is selected then theframe is transmitted as 1 start bit, 8 data bits, and 1 stop bit.

    Where n > 1 data is transmitted most significant byte first.

    The CRC check is transmitted least significant byte first.

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    10/88

    M2x3C+I500C/EN M/C Technical Manual

    Page 8 iSTAT M2x3 & I500 Modbus & DNP3.0

    3. MODBUS SUPPORTED FUNCTIONS AND USAGE

    Code Code Function References

    DEC HEX

    3 03 to read from holding registers (4XXXX memory references)

    4 04 to read from input registers (3XXXX memory references)

    6 06 to write to a single holding register (4XXXX memory references)

    16 10 to write to one or more holding registers (4XXXX memory references)

    17 11 report slave ID 6 characters

    77 4D read measurement string 1 byte value code (request)

    82 52 re-read output buffer Use after broadcast request

    3.1 03 read from holding registers

    Reads the binary content of holding registers (4X references) in the slave. Broadcast is also

    supported.

    3.1.1 Request Frame

    The query message specifies the starting register and quantity of registers (1 to 28) to beread. Registers are addressed starting at zero.

    Here is an example of a request to read registers 40009 ... 40010 from slave device 33:

    Starting Register Register Count CRC

    Slave Address Function Code HI LO HI LO LO HI

    21 03 00 09 00 02

    3.1.2 Response Frame

    The register data in the response message is packed as two bytes per register, with thebinary contents right justified within each byte. For each register, the first byte contains thehigh order bits and the second contains the low order bits.

    Data is scanned in the slave at the rate of 28 registers per scan. The response is returnedwhen the data is completely assembled.

    Here is an example of a response to the query:

    Register Data CRC

    Slave Address Function Code Byte Count HI LO HI LO LO HI

    21 03 04 75 03 42 15

    The contents of registers 40009 ... 40010 are 75 03 and 42 15 hex.

    3.2 04 read from input registers

    Reads the binary content of input registers (3X references) in the slave. Broadcast is alsosupported

    3.2.1 Request Frame

    The query message specifies the starting register and quantity (1 to 28) of registers to beread. Registers are addressed starting at zero.

    Here is an example of a request to read registers 30036 ... 30037 from slave device 33:

    Starting Register Register Count CRC

    Slave Address Function Code HI LO HI LO LO HI

    21 04 00 24 00 02

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    11/88

    Technical Manual M2x3C+I500C/EN M/C

    iSTAT M2x3 & I500 Modbus & DNP3.0 Page 9

    3.2.2 Response Frame

    The register data in the response message is packed as two bytes per register, with thebinary contents right justified within each byte. For each register, the first byte contains thehigh order bits and the second contains the low order bits.

    Data is scanned in the slave at the rate of 28 registers per scan. The response is returned

    when the data is completely assembled.

    Here is an example of a response to the query:

    Register Data CRC

    Slave Address Function Code Byte Count HI LO HI LO LO HI

    21 04 04 FE 00 3E 80

    The contents of registers 30036 ... 30037 are FE 00 and 3E 80 hex.

    3.3 06 write to a single holding register

    Pre-sets a value into a single holding register (4X reference). When broadcast, the functionpre-sets the same register reference in all attached slaves.

    3.3.1 Request Frame

    The query message specifies the register reference to be pre-set. Registers are addressedstarting at zero; register 1 is addressed as 0.

    Here is an example of a request to pre-set register 40010 to 42 15 hex in slavedevice 33:

    Register Address Register Data CRC

    Slave Address Function Code HI LO HI LO LO HI

    21 06 00 0A 42 15

    3.3.2 Response Frame

    The normal response is an echo of the query, returned after the register contents have beenpre-set. Here is an example of a response to the query:

    Register Address Register Data CRC

    Slave Address Function Code HI LO HI LO LO HI

    21 06 00 0A 42 15

    3.4 16 (10 HEX) write to one or more registers

    Pre-sets values into a sequence of holding registers (4x references). When broadcast thefunction pre-sets the same register references in all attached slaves.

    3.4.1 Request Frame

    The query message specifies the register references to be pre-set. Registers are addressedstarting at zero; register 1 is addressed as 0. Here is an example of a request to pre-set tworegisters starting at 40000 to 41 42 and 43 44 hex (Enter Password ABCD), in slave device33:

    SlaveAddress

    FunctionCode

    StartingRegister

    RegisterCount

    Byte

    Count

    Register

    DataCRC

    HI LO HI LO HI LO HI LO LO HI

    21 16 00 00 00 02 04 41 42 4344

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    12/88

    M2x3C+I500C/EN M/C Technical Manual

    Page 10 iSTAT M2x3 & I500 Modbus & DNP3.0

    3.4.2 Response Frame

    The normal response returns the slave address, function code, starting address, andquantity of registers pre-set. Here is an example of a response to the query shown above.

    Slave

    Address

    Function

    Code

    Starting Register Register Count CRC

    HI LO HI LO LO HI

    21 16 00 00 00 02

    If the password is not correct (L1 or L2 or BP), the response to the query is:

    Slave

    Address

    Function

    Code

    Starting Register Register Count CRC

    HI LO HI LO LO HI

    21 16 00 00 00 02

    3.5 17 (11HEX) report slave id

    Returns a description of the type of controller present at the slave address.

    3.5.1 Request Frame

    Here is an example of a request to report the ID of slave device 33:

    CRC

    Slave Address Function Code LO HI

    21 11

    3.5.2 Response Frame

    The format of a normal response is shown below:

    Slave Address Function Code Byte Count Register Data CRC

    HI LO HI LO HI LO LO HI

    21 11 06 20 4D 30 32 32 30

    3.6 77 (4D HEX) read measurement string

    Reads the measurement value as an ASCII string. Broadcast is also supported. See list ofvalue codes in section 4.6.3

    3.6.1 Request Frame

    The query message specifies the value code of the measurement to be read.

    Here is an example of a response to read Total Real Power from slave device 33:

    Slave

    Address

    Function

    Code

    Value Code CRC

    LO HI

    21 4D 04

    3.6.2 Response Frame

    The ASCII string in the response message is packed as data bytes. The quantity of databytes depends on the value code.

    Here is an example of the query:

    Slave

    Address

    Function

    Code

    Byte Count String Data CRC

    1. 2. 3. 4. 5. 6. 7. 8. LO HI

    21 4D 08 2B 32 31 2E 31 33 35 6B 49 35

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    13/88

    Technical Manual M2x3C+I500C/EN M/C

    iSTAT M2x3 & I500 Modbus & DNP3.0 Page 11

    3.6.3 Value Codes

    The value codes are described in the following table:

    ValueCode DEC

    ValueCodeHex

    Measurement ValueByteCount

    Example String Data

    00 00 Energy counter 1 15 "0000004.46kWh"

    01 01 Energy counter 2 15 "0000001.24kvarh"

    02 02 Energy counter 3 15 "0000005.71kWh"

    03 03 Energy counter 4 15 "0000002.86kvarh"

    04 04 Total Real Power 8 "+21.135k"

    05 05 A Phase Real Power 8 "+7046.3"

    06 06 B Phase Real Power 8 "+7037.3"

    07 07 C Phase Real Power 8 "+7051.1"

    08 08 Total Reactive Power 12 "1208.7 var L"

    09 09 A Phase Reactive Power 12 "0400.2 var L"

    10 0A B Phase Reactive Power 12 "0406.4 var L"

    11 0B C Phase Reactive Power 12 "0400.9 var L"

    12 0C Total I 7 "93.671"

    13 0D IA 7 "31.227"

    14 0E IB 7 "31.222"

    15 0F IC 7 "31.222"

    16 10 Average V 7 "226.06"

    17 11 VA 7 "226.08"

    18 12 VB 7 "225.83"

    19 13 VC 7 "226.27"

    20 14 Total Apparent Power 7 "21.170k"

    21 15 A Phase Apparent Power 7 "7057.3"

    22 16 B Phase Apparent Power 7 "7049.0"

    23 17 C Phase Apparent Power 7 "7062.8"

    24 18 Total Power Factor 8 "+0.998 L"25 19 Power Factor A 8 "+0.998 L"

    26 1A Power Factor B 8 "+0.998 L"

    27 1B Power Factor C 8 "+0.998 L"

    28 1C Frequency 7 "46.008"

    29 1D Frequency 7 "46.008"

    30 1E Frequency 7 "46.008"

    31 1F Frequency 7 "46.008"

    32 20 Total Power Angle 7 "+003.26"

    33 21 Power Angle A 7 "+003.25"

    34 22 Power Angle B 7 "+003.30"

    35 23 Power Angle C 7 "+003.25"

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    14/88

    M2x3C+I500C/EN M/C Technical Manual

    Page 12 iSTAT M2x3 & I500 Modbus & DNP3.0

    ValueCode DEC

    ValueCodeHex

    Measurement ValueByteCount

    Example String Data

    36 24 IN 6 "93.67"

    37 25 Angle AB 7 "+000.00"

    38 26 Angle BC 7 "+000.01"

    39 27 Angle CA 7 "-000.01"

    40 28 Average Vxy 6 "000.3"

    41 29 VAB 6 "000.2"

    42 2A VBC 6 "000.24"

    43 2B VCA 6 "000.2"

    44 2C Dynamic Demand Value 1 13 "Pt=+9.818kW"

    45 2D Dynamic Demand Value 2 12 "Qt=6.504kvar"

    46 2E Dynamic Demand Value 3 12 "St=12.89kVA"

    47 2F Dynamic Demand Value 4 12 "It=56.91 A"

    48 30 Max Demand Since Reset 1 13 "Pt=+11.26kW"

    49 31 Max Demand Since Reset 2 12 "Qt=14.64kvar"

    50 32 Max Demand Since Reset 3 12 "St=18.46kVA"

    51 33 Max Demand Since Reset 4 12 "It=81.01 A"

    52 34 Time Stamp MD 1 12 "03.SEP 14:11"

    53 35 Time Stamp MD 2 12 "03.SEP 14:10"

    54 36 Time Stamp MD 3 12 "03.SEP 14:10"

    55 37 Time Stamp MD 4 12 "03.SEP 14:12"

    3.7 82 (52 HEX) re-read output buffer

    This function should be used after the broadcast request. The addressed slave transmits theresponse frame of the previous request.

    3.7.1 Request Frame

    Here is an example of a request to re-read the output buffer of slave device 33:

    CRC

    Slave Address Function Code LO HI

    21 52

    3.7.2 Response Frame

    The response to the query depends on the previous function code.

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    15/88

    Technical Manual M2x3C+I500C/EN M/C

    iSTAT M2x3 & I500 Modbus & DNP3.0 Page 13

    4. MODBUS ERROR RESPONSES

    When a slave detects an error other than a CRC error, a response will be sent to the master.The most significant bit of the function code byte will be set to 1 (i.e. the function code sentfrom the slave will be equal to the function code sent from the master plus 128). Thefollowing byte will be an exception code indicating the type of error that occurred.

    The slave will ignore transmissions received from the master with CRC errors.

    An example of an illegal request and the corresponding exception response is shown below.The request in this example is to read registers 0201H to 0209H. If these addresses are notsupported in the slave then the following occurs:

    Request Message

    Starting Register Register Count

    Address Function Code HI LO HI LO CRC

    01 01 02 01 00 08 6D B4

    Exception Response Message

    Address Function Code Exception Code CRC

    01 81 02 C1 91

    4.1 Exception codes

    Code Name Meaning

    01 ILLEGAL FUNCTION The function code transmitted is notone of the functions supported by theslave.

    02 ILLEGAL DATA ADDRESSES The data address received in therequest is not an allowable value forthe slave.Write to password protected registers.

    03 ILLEGAL DATA VALUE The value referenced in the data fieldtransmitted by the master is not withinfamily for the selected data address.The register count is greater than 28(functions 03 and 04).

    06 SLAVE DEVICE BUSY The slave is engaged in processing along duration program command. Themaster should re-transmit themessage later when the slave is free.

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    16/88

    M2x3C+I500C/EN M/C Technical Manual

    Page 14 iSTAT M2x3 & I500 Modbus & DNP3.0

    5. MODBUS REGISTER MAPS

    The Modbus register map consists of the following columns:

    Code Function codes as described in Section 4.0.

    Address 16 bit register address starting from zero.Please Note:

    Most Modbus master devices assume that 30001 or 40001 aresubtracted from the defined address for the registers. TheM2x3 and i500 subtract 30000 and 40000, meaning that theaddresses may have to be offset by 1.

    Contents Description of parameters assigned to registers.

    Data type MODBUS data types T1 etc. are described in section 7.

    UNSIGNEDINTEGER

    family 0 ... 65535

    one 16-bit register

    SIGNED INTEGER family 32768 ... 32767one 16-bit register

    ASCII Family 32159

    16 bit registers (two ASCII codes per register)

    BINARY FLAGS Each bit of a 16 bit register can be used as abinary flag

    Indicator Each bit of a 16-bit register can be either assigned as flags or filledwith binary data.

    Values Definitions of settings, data values and any dependencies that existbetween settings.

    Register type Declares whether a register is to be read/write register (setting) or aread register (data).

    Min, max step The minimum and maximum numerical family and the incremental stepsize.

    Password There is a numerical password that allows save/abort settings and afactory accessible password constructed from the serial number thatallows entry/exit to and from the calibration and configuration settings.

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    17/88

    Technical Manual M2x3C+I500C/EN M/C

    iSTAT M2x3 & I500 Modbus & DNP3.0 Page 15

    6. MODBUS DATA FOR M2X3 AND I5MT/MR/MQ

    6.1 SYSTEM DATA

    Code Address Contents Data Ind Values and Dependencies

    04 30001 30018 Model Number Str_16

    04 30009 30012 Serial Number Str_8

    04 30013 Software Ref 1 T1 Software version

    04 30014 Hardware Ref Str_2 Hardware version

    30015 Calibration voltage T4 mV

    30016 Voltage auto-range T1 1=auto-range

    30017 Calibration current T4 mA

    30018 Current auto-range T1 1=auto-range

    30019 Accuracy class T17 50 = 0.5%20 = 0.2%

    30020 MiNet Flag T1 0

    30021 Language Pack T1

    30022 LCD type T1 0 128x64 yellow green

    1128x64 yellow greennegative

    2 128x64 red negative

    30023 Power supply T1 0 Unknown

    1

    Universal AC 48-276V:

    DC 20 300V

    2 57.64v, 50/60Hz

    3 63.5v, 50/60Hz

    4 100v, 50/60Hz

    5 110v, 50/60Hz

    6 230v, 50/60Hz

    7 400v, 50/60Hz

    8 500v, 50/60Hz

    9Universal AC 48 77V:

    DC 20 100V

    10Universal AC 70 276V;

    DC 70 300V

    30024 COM1: communication type T1 0 No communication

    1 RS232

    2 RS485

    3 RS232 & RS485

    4 Ethernet (X-Port)

    5 Ethernet & USB

    6 Ethernet7 USB

    30025 COM2: communication type T1 0 No communication

    1 RS232

    2 RS485

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    18/88

    M2x3C+I500C/EN M/C Technical Manual

    Page 16 iSTAT M2x3 & I500 Modbus & DNP3.0

    Code Address Contents Data Ind Values and Dependencies

    30026 30027 Reserved

    30028 Memory type T1 0 No memory

    1 2Mb flash

    2 4Mb flash3 8Mb flash

    30029 I/O 1 T1 0 No I/O

    1 Unipolar analogue output

    2 Bipolar analogue output

    3 Jumperless analogue output

    4 Pulse output

    5 Tariff Input

    6 Bistable alarm output

    7 Relay alarm output

    8 Analogue output 20mA

    9 Analogue input

    10 Digital input

    11 Pulse input

    12 S0 output

    13 Fast Analogue Output

    14Jumperless unipolar Analogoutput

    15 Watch dog output

    16 Reserved17 RS232

    18 RS485

    19 Reserved

    20 COM2 - Ex

    30030 I/O 2

    30031 I/O 3

    30032 I/O 4

    30033 30043 Reserved

    30044 Status Register (M2x3 only) T1 0 Locked

    1 Wrong Connection

    2 Low Battery

    3 Low Supply

    4 Clock not Set

    30045 30046 Configuration time stamp T10

    30047 30048 Calibration time stamp T10

    30049 30050 Last upgrade time stamp T10

    30051 Digital input 1 voltage range T1 0 230V

    1 63 110V

    2 48V

    30052 Digital input 2 voltage range T1 See Digital input 1

    30053 Digital input 3 voltage range T1 See Digital input 1

    30054 Digital input 4 voltage range T1 See Digital input 1

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    19/88

    Technical Manual M2x3C+I500C/EN M/C

    iSTAT M2x3 & I500 Modbus & DNP3.0 Page 17

    Code Address Contents Data Ind Values and Dependencies

    30055 30057 Ethernet MAC Address T_Hex6

    30058 Ethernet Software Reference T1 Ethernet Software Version

    30059 30060 Ethernet IP Address T_Hex4 Actual Ethernet IP Address

    30061 30097 Reserved location30098 Active communications port T1 1 COM1

    2 COM2

    30099Modbus max.register read atonce

    T1

    6.2 MEASUREMENTS

    Code Address Contents Data Ind Values and Dependencies

    ACTUAL MEASUREMENTS

    04 30101 30104 Actual time T_Time

    04 30105 30106 Frequency T5

    04 30107 30108 U1 T5

    04 30109 30110 U2 T5

    30111 30112 U3 T5

    04 30113 30114 Uavg (phase to neutral) T5

    04 30115 j12 (angle between U1 and U2) T17

    04 30116 j23 (angle between U2 and U3) T17

    04 30117 j31 (angle between U3 and U1) T17

    04 30118 30119 U12 T5

    04 30120 30121 U23 T5

    04 30122 30123 U31 T5

    04 30124 30125 Uavg (phase to phase) T5

    04 30126 30127 I1 T5

    04 30128 30129 I2 T5

    04 30130 30131 I3 T5

    0430132 30133

    INc T504 30134 30135 INm - reserved T5

    04 30136 30137 Iavg T5

    04 30138 30139 I T5

    30140 30141 Active Power Total (Pt) T6

    30142 30143 Active Power Phase L1 (P1) T6

    30144 30145 Active Power Phase L2 (P2) T6

    30146 30147 Active Power Phase L3 (P3) T6

    30148 30149 Reactive Power Total (Qt) T6

    30150 30151 Reactive Power Phase L1 (Q1) T6

    30152 30153 Reactive Power Phase L2 (Q2) T6

    30154 30155 Reactive Power Phase L3 (Q3) T6

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    20/88

    M2x3C+I500C/EN M/C Technical Manual

    Page 18 iSTAT M2x3 & I500 Modbus & DNP3.0

    Code Address Contents Data Ind Values and Dependencies

    30156 30157 Apparent Power Total (St) T5

    30158 30159 Apparent Power Phase L1 (S1) T5

    30160 30161 Apparent Power Phase L2 (S2) T5

    30162 30163 Apparent Power Phase L3 (S3) T5

    30164 30165 Power Factor Total (PFt) T7

    30166 30167 Power Factor Phase 1 (PF1) T7

    30168 30169 Power Factor Phase 2 (PF2) T7

    30170 30171 Power Factor Phase 3 (PF3) T7

    30172 Power Angle Total(atan2(Pt,Qt))

    T17

    30173 1 (angle between U1 and I1) T17

    30174 2 (angle between U2 and I2) T17

    30175 3 (angle between U3 and I3) T17

    30176 U unbalance T16

    30177 30180 Reserved

    30181 Internal Temperature T17

    THD HARMONIC DATA

    30182 U1 THD% T16

    30183 U2 THD% T16

    30184 U3 THD% T16

    30185 U12 THD% T16

    30186 U23 THD% T16

    30187 U31 THD% T16

    30188 I1 THD% T16

    30189 I2 THD% T16

    30190 I3 THD% T16

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    21/88

    Technical Manual M2x3C+I500C/EN M/C

    iSTAT M2x3 & I500 Modbus & DNP3.0 Page 19

    Code Address Contents Data Ind Values and Dependencies

    I/O STATUS

    30191 Alarm Status Flags (No.116)

    T1 bit-i Alarm i+1

    30192 Alarm Status Flags (No.1732)

    T1 bit-i Alarm i+17

    30193 I/O 1 Value T17

    30194 I/O 2 Value T17

    30195 I/O 3 Value T17

    30196 I/O 4 Value T17

    30197 30200 Reserved

    MAXIMUM MEASUREMENTS

    30201 30204 Last reset time T_Time

    30205 30206 Frequency T5

    30207 30208 U1 T5

    30209 30210 U2 T5

    30211 30212 U3 T5

    30213 30214 Reserved: T5

    30215 Reserved:12 (angle betweenU1 and U2)

    T17

    30216 Reserved: 23 (angle betweenU2 and U3)

    T17

    30217 Reserved: 31 (angle betweenU3 and U1)

    T17

    30218 30219 U12 T5

    30220 30221 U23 T5

    30222 30223 U31 T5

    30224 30225 Reserved: Uavg (phase tophase)

    T5

    30226 30227 I1 T5

    30228 30229 I2 T5

    30230 30231 I3 T5

    30232 30233 Reserved: INc T5

    30234 30235 Reserved: INm T5

    30236 30237 Reserved: Iavg T5

    30238 30239 Reserved: I T5

    30240 30241 Active Power Total (Pt) T6

    30242 30243 Active Power Phase L1 (P1) T6

    30244 30245 Active Power Phase L2 (P2) T6

    30246 30247 Active Power Phase L3 (P3) T6

    30248 30249 Reserved: Reactive Power Total(Qt)

    T6

    30250 30251 Reserved: Reactive Power Phase T6

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    22/88

    M2x3C+I500C/EN M/C Technical Manual

    Page 20 iSTAT M2x3 & I500 Modbus & DNP3.0

    Code Address Contents Data Ind Values and Dependencies

    L1 (Q1)

    30252 30253 Reserved: Reactive Power PhaseL2 (Q2)

    T6

    30254 30255 Reserved: Reactive Power Phase

    L3 (Q3)

    T6

    30256 30257 Apparent Power Total (St) T5

    30258 30259 Apparent Power Phase L1 (S1) T5

    30260 30261 Apparent Power Phase L2 (S2) T5

    30262 30263 Apparent Power Phase L3 (S3) T5

    30264 30265 Reserved: Power Factor Total(PFt)

    T7

    30266 30267 Reserved: Power FactorPhase 1 (PF1)

    T7

    30268 30269 Reserved: Power FactorPhase 2 (PF2)

    T7

    30270 30271 Reserved: Power FactorPhase 3 (PF3)

    T7

    30272 Reserved: Power Angle Total(atan2(Pt,Qt))

    T17

    30273 Reserved: 1 (angle betweenU1 and I1)

    T17

    30274 Reserved: 2 (angle betweenU2 and I2)

    T17

    30275 Reserved: 3 (angle betweenU3 and I3)

    T17

    30276 30280 Reserved

    30281 Internal Temperature T17

    THD HARMONIC DATA

    30282 Reserved: U1 THD% T16

    30283 Reserved: U2 THD% T16

    30284 Reserved: U3 THD% T16

    30285 Reserved: U12 THD% T16

    30286 Reserved: U23 THD% T16

    30287 Reserved: U31 THD% T16

    30288 Reserved: I1 THD% T16

    30289 Reserved: I2 THD% T16

    30290 Reserved: I3 THD% T16

    30291 30300 Reserved

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    23/88

    Technical Manual M2x3C+I500C/EN M/C

    iSTAT M2x3 & I500 Modbus & DNP3.0 Page 21

    Code Address Contents Data Ind Values and Dependencies

    MINIMUM MEASUREMENTS

    30301 30304 Last reset time T_Time

    30305 30306 Frequency T5

    30307 30308 U1 T5

    30309 30310 U2 T5

    30311 30312 U3 T5

    30313 30314 Reserved: Uavg (phase toneutral)

    T5

    30315 Reserved:12 (angle betweenU1 and U2)

    T17

    30316 Reserved: 23 (angle betweenU2 and U3)

    T17

    30317 Reserved: 31 (angle betweenU3 and U1)

    T17

    30318 30319 U12 T5

    30320 30321 U23 T5

    30322 30323 U31 T5

    30324 30325 Reserved: Uavg (phase tophase)

    T5

    30326 30327 I1 T5

    30328 30329 I2 T5

    30330 30331 I3 T5

    30332 30333 Reserved: INc T5

    30334 30335 Reserved: INm T5

    30336 30337 Reserved: Iavg T5

    30338 30339 Reserved: I T5

    30340 30341 Active Power Total (Pt) T6

    30342 30343 Active Power Phase L1 (P1) T6

    30344 30345 Active Power Phase L2 (P2) T6

    30346 30347 Active Power Phase L3 (P3) T630348 30349 Reserved: Reactive Power

    Total (Qt)T6

    30350 30351 Reserved: Reactive PowerPhase L1 (Q1)

    T6

    30352 30353 Reserved: Reactive PowerPhase L2 (Q2)

    T6

    30354 30355 Reserved: Reactive PowerPhase L3 (Q3)

    T6

    30356 30357 Apparent Power Total (St) T5

    30358 30359 Apparent Power Phase L1 (S1) T5

    30360 30361 Apparent Power Phase L2 (S2) T5

    30362 30363 Apparent Power Phase L3 (S3) T5

    30364 30365 Reserved: Power Factor Total T7

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    24/88

    M2x3C+I500C/EN M/C Technical Manual

    Page 22 iSTAT M2x3 & I500 Modbus & DNP3.0

    Code Address Contents Data Ind Values and Dependencies

    (PFt)

    30366 30367 Reserved: Power FactorPhase 1 (PF1)

    T7

    30368 30369 Reserved: Power FactorPhase 2 (PF2)

    T7

    30370 30371 Reserved: Power FactorPhase 3 (PF3)

    T7

    30372 Reserved: Power Angle Total(atan2(Pt,Qt))

    T17

    30373 Reserved: 1 (angle betweenU1 and I1)

    T17

    30374 Reserved: 2 (angle betweenU2 and I2)

    T17

    30375 Reserved: 3 (angle betweenU3 and I3) T17

    30376 30380 Reserved

    30381 Internal Temperature T17

    THD HARMONIC DATA

    30382 Reserved: U1 THD% T16

    30383 Reserved: U2 THD% T16

    30384 Reserved: U3 THD% T16

    30385 Reserved: U12 THD% T16

    30386 Reserved: U23 THD% T16

    30387 Reserved: U31 THD% T16

    30388 Reserved: I1 THD% T16

    30389 Reserved: I2 THD% T16

    30390 Reserved: I3 THD% T16

    30391 30400 Reserved

    ENERGY

    30401 Energy Counter 1 Exponent T2

    30402 Energy Counter 2 Exponent T2

    30403 Energy Counter 3 Exponent T2

    30404 Energy Counter 4 Exponent T2

    30405 Current Active Tariff T1

    30406 30407 Energy Counter 1 T3

    30408 30409 Energy Counter 2 T3

    30410 30411 Energy Counter 3 T3

    30412 30413 Energy Counter 4 T3

    30414 30415 Energy Counter 1 Tariff 1 T330416 30417 Energy Counter 2 Tariff 1 T3

    30418 30419 Energy Counter 3 Tariff 1 T3

    30420 30421 Energy Counter 4 Tariff 1 T3

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    25/88

    Technical Manual M2x3C+I500C/EN M/C

    iSTAT M2x3 & I500 Modbus & DNP3.0 Page 23

    Code Address Contents Data Ind Values and Dependencies

    30422 30423 Energy Counter 1 Tariff 2 T3

    30424 30425 Energy Counter 2 Tariff 2 T3

    30426 30427 Energy Counter 3 Tariff 2 T3

    30428 30429 Energy Counter 4 Tariff 2 T3

    30430 30431 Energy Counter 1 Tariff 3 T3

    30432 30433 Energy Counter 2 Tariff 3 T3

    30434 30435 Energy Counter 3 Tariff 3 T3

    30436 30437 Energy Counter 4 Tariff 3 T3

    30438 30439 Energy Counter 1 Tariff 4 T3

    30440 30441 Energy Counter 2 Tariff 4 T3

    30442 30443 Energy Counter 3 Tariff 4 T3

    30444 30445 Energy Counter 4 Tariff 4 T3

    30446 30447 Energy Counter 1 Cost T3

    30448 30449 Energy Counter 2 Cost T3

    30450 30451 Energy Counter 3 Cost T3

    30452 30453 Energy Counter 4 Cost T3

    30454 30500 Reserved

    DEMAND VALUES

    DYNAMIC DEMAND VALUES

    30501 Time Into Period (minutes) T130502 30503 I1 T5

    30504 30505 I2 T5

    30506 30507 I3 T5

    30508 30509 Apparent Power Total (St) T5

    30510 30511 Active Power Total (Pt) -(positive)

    T6

    30512 30513 Active Power Total (Pt) -(negative)

    T6

    30514 30515 Reactive Power Total (Qt) - L T630516 30517 Reactive Power Total (Qt) - C T6

    MAX DEMAND SINCE LAST RESET

    30518 30519 I1 T5

    30520 30523 Time Stamp T_Time

    30524 30525 I2 T5

    30526 30529 Time Stamp T_Time

    30530 30531 I3 T5

    30532 30535 Time Stamp T_Time

    30536 30537 Apparent Power Total (St) T5

    30538 30541 Time Stamp T_Time

    30542 30543 Active Power Total (Pt) -(positive)

    T6

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    26/88

    M2x3C+I500C/EN M/C Technical Manual

    Page 24 iSTAT M2x3 & I500 Modbus & DNP3.0

    Code Address Contents Data Ind Values and Dependencies

    30544 30547 Time Stamp T_Time

    30548 30549 Active Power Total (Pt) -(negative)

    T6

    30550 30553 Time Stamp T_Time30554 30555 Reactive Power Total (Qt) - L T6

    30556 30559 Time Stamp T_Time

    30560 30561 Reactive Power Total (Qt) - C T6

    30562 30565 Time Stamp T_Time

    30566 30579 Reserved

    FLICKERS (M253 & i5MQ only)

    30580 Flicker Pst1 T17

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    27/88

    Technical Manual M2x3C+I500C/EN M/C

    iSTAT M2x3 & I500 Modbus & DNP3.0 Page 25

    Code Address Contents Data Ind Values and Dependencies

    30610 Frequency Variations 1: % /Period

    T16

    30611 Frequency Variations 1: % /Year

    T16

    30612 Frequency Variations 2: % /Period

    T16

    30613 Frequency Variations 2: % /Year

    T16

    30614 Voltage Unbalances: % /Period

    T16

    30615 Voltage Unbalances: % / Year T16

    30616 Voltage Variations 1 - L1: % /Period

    T16

    30617 Voltage Variations 1 - L1: % /Year T16

    30618 Voltage Variations 1 - L2: % /Period

    T16

    30619 Voltage Variations 1 - L2: % /Year

    T16

    30620 Voltage Variations 1 - L3: % /Period

    T16

    30621 Voltage Variations 1 - L3: % /Year

    T16

    30622 Voltage Variations 2 - L1: % /Period T16

    30623 Voltage Variations 2 - L1: % /Year

    T16

    30624 Voltage Variations 2 - L2: % /Period

    T16

    30625 Voltage Variations 2 - L2: % /Year

    T16

    30626 Voltage Variations 2 - L3: % /Period

    T16

    30627 Voltage Variations 2 - L3: % /Year

    T16

    30628 THD's - L1: % / Period T16

    30629 THD's - L1: % / Year T16

    30630 THD's - L2: % / Period T16

    30631 THD's - L2: % / Year T16

    30632 THD's - L3: % / Period T16

    30633 THD's - L3: % / Year T16

    30634 Harmonics - L1: % / Period T16

    30635 Harmonics - L1: % / Year T16

    30636 Harmonics - L2: % / Period T16

    30637 Harmonics - L2: % / Year T16

    30638 Harmonics - L3: % / Period T16

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    28/88

    M2x3C+I500C/EN M/C Technical Manual

    Page 26 iSTAT M2x3 & I500 Modbus & DNP3.0

    Code Address Contents Data Ind Values and Dependencies

    30639 Harmonics - L3: % / Year T16

    30640 Short term Flickers - L1: % /Period

    T16

    30641 Short term Flickers - L1: % /Year T16

    30642 Short term Flickers - L2: % /Period

    T16

    30643 Short term Flickers - L2: % /Year

    T16

    30644 Short term Flickers - L3: % /Period

    T16

    30645 Short term Flickers - L3: % /Year

    T16

    30646 Long term Flickers - L1: % /Period T16

    30647 Long term Flickers - L1: % /Year

    T16

    30648 Long term Flickers - L2: % /Period

    T16

    30649 Long term Flickers - L2: % /Year

    T16

    30650 Long term Flickers - L3: % /Period

    T16

    30651 Long term Flickers - L3: % /Year T16

    30652 Transients - L1: No. / Period T1

    30653 Transients - L1: No. / Year T1

    30654 Transients - L2: No. / Period T1

    30655 Transients - L2: No. / Year T1

    30656 Transients - L3: No. / Period T1

    30657 Transients - L3: No. / Year T1

    30658 Temporary Overvoltages - L1:

    No. / Period

    T1

    30659 Temporary Overvoltages - L1:No. / Year

    T1

    30660 Temporary Overvoltages - L2:No. / Period

    T1

    30661 Temporary Overvoltages - L2:No. / Year

    T1

    30662 Temporary Overvoltages - L3:No. / Period

    T1

    30663 Temporary Overvoltages - L3:No. / Year

    T1

    30664 Voltage Dips - L1: No. / Period T1

    30665 Voltage Dips - L1: No. / Year T1

    30666 Voltage Dips - L2: No. / Period T1

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    29/88

    Technical Manual M2x3C+I500C/EN M/C

    iSTAT M2x3 & I500 Modbus & DNP3.0 Page 27

    Code Address Contents Data Ind Values and Dependencies

    30667 Voltage Dips - L2: No. / Year T1

    30668 Voltage Dips - L3: No. / Period T1

    30669 Voltage Dips - L3: No. / Year T1

    30670 Short Interruptions - L1: No. /Period

    T1

    30671 Short Interruptions - L1: No. /Year

    T1

    30672 Short Interruptions - L2: No. /Period

    T1

    30673 Short Interruptions - L2: No. /Year

    T1

    30674 Short Interruptions - L3: No. /Period

    T1

    30675 Short Interruptions - L3: No. /Year

    T1

    30676 Long Interruptions - L1: No. /Period

    T1

    30677 Long Interruptions - L1: No. /Year

    T1

    30678 Long Interruptions - L2: No. /Period

    T1

    30679 Long Interruptions - L2: No. /Year

    T1

    30680 Long Interruptions - L3: No. /Period

    T1

    30681 Long Interruptions - L3: No. /Year

    T1

    30682 30700 Reserved

    PREVIOUS PERIOD QUALITY (M253 & i5MQ only)

    30701 30781 Last finished period quality See Actual period quality

    6.3 NORMALIZED MEASUREMENTS

    Code Address Contents Data Ind Values and Dependencies

    NORMALIZED ACTUAL MEASUREMENTS

    30801 U1 T16

    30802 U2 T16

    30803 U3 T16

    30804 Uavg (phase to neutral) T16

    30805 U12 T16

    30806 U23 T1630807 U31 T16

    30808 Uavg (phase to phase) T16

    30809 I1 T16

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    30/88

    M2x3C+I500C/EN M/C Technical Manual

    Page 28 iSTAT M2x3 & I500 Modbus & DNP3.0

    Code Address Contents Data Ind Values and Dependencies

    30810 I2 T16

    30811 I3 T16

    30812 I T16

    30813 I neutral (calculated) T16

    30814 I neutral (measured) T16

    30815 Iavg T16

    30816 Active Power Phase L1 (P1) T17

    30817 Active Power Phase L2 (P2) T17

    30818 Active Power Phase L3 (P3) T17

    30819 Active Power Total (Pt) T17

    30820 Reactive Power Phase L1 (Q1) T17

    30821 Reactive Power Phase L2 (Q2) T17

    30822 Reactive Power Phase L3 (Q3) T17

    30823 Reactive Power Total (Qt) T17

    30824 Apparent Power Phase L1 (S1) T16

    30825 Apparent Power Phase L2 (S2) T16

    30826 Apparent Power Phase L3 (S3) T16

    30827 Apparent Power Total (St) T16

    30828 Power Factor Phase 1 (PF1) T17

    30829 Power Factor Phase 2 (PF2) T1730830 Power Factor Phase 3 (PF3) T17

    30831 Power Factor Total (PFt) T17

    30832 CAP/IND P. F. Phase 1 (PF1) T17

    30833 CAP/IND P. F. Phase 2 (PF2) T17

    30834 CAP/IND P. F. Phase 3 (PF3) T17

    30835 CAP/IND P. F. Total (PFt) T17

    30836 1 (angle between U1 and I1) T17

    30837 2 (angle between U2 and I2) T17

    30838 3 (angle between U3 and I3) T17

    30839Power Angle Total(atan2(Pt,Qt))

    T17

    30840 12 (angle between U1 and U2 T17

    30841 23 (angle between U2 and U3 T17

    30842 31 (angle between U3 and U1 T17

    30843 Frequency T17

    30844 U unbalance T16

    30845 I1 THD% T16

    30846 I2 THD% T16

    30847 I3 THD% T16

    30848 U1 THD% T16

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    31/88

    Technical Manual M2x3C+I500C/EN M/C

    iSTAT M2x3 & I500 Modbus & DNP3.0 Page 29

    Code Address Contents Data Ind Values and Dependencies

    30849 U2 THD% T16

    30850 U3 THD% T16

    30851 U12 THD% T16

    30852 U23 THD% T16

    30853 U31 THD% T16

    MAX DEMAND SINCE LAST RESET

    30854Active Power Total (Pt) -(positive) T16

    30855Active Power Total (Pt) -(negative) T16

    30856 Reactive Power Total (Qt) - L T16

    30857 Reactive Power Total (Qt) - C T16

    30858 Apparent Power Total (St) T16

    30859 I1 T16

    30860 I2 T16

    30861 I3 T16

    DYNAMIC DEMAND VALUES

    30862Active Power Total (Pt) -(positive) T16

    30863Active Power Total (Pt) -(negative) T16

    30864 Reactive Power Total (Qt) - L T16

    30865 Reactive Power Total (Qt) - C T16

    30866 Apparent Power Total (St) T16

    30867 I1 T16

    30868 I2 T16

    30869 I3 T16

    ENERGY

    30870 Energy Counter 1 T17

    30871 Energy Counter 2 T17

    30872 Energy Counter 3 T17

    30873 Energy Counter 4 T17

    30874 Energy Counter 1 Cost T17

    30875 Energy Counter 2 Cost T17

    30876 Energy Counter 3 Cost T17

    30877 Energy Counter 4 Cost T17

    30878 Total Energy Counter Cost T17

    30879 Active Tariff T130880 Internal Temperature T17

    30881 30900 Reserved

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    32/88

    M2x3C+I500C/EN M/C Technical Manual

    Page 30 iSTAT M2x3 & I500 Modbus & DNP3.0

    Code Address Contents Data Ind Values and Dependencies

    FAST RESPONCE normalised actual measurements

    30901 U1 T16

    30902 U2 T16

    30903 U3 T16

    30904 Uavg (phase to neutral) T16

    30905 U12 T16

    30906 U23 T16

    30907 U31 T16

    30908 Uavg (phase to phase) T16

    30909 I1 T16

    30910 I2 T16

    30911 I3 T16

    30912 I T16

    30913 I neutral (calculated) T16

    30914 I neutral (measured) T16

    30915 Iavg T16

    30916 Active Power Phase L1 (P1) T17

    30917 Active Power Phase L2 (P2) T17

    30918 Active Power Phase L3 (P3) T17

    30919 Active Power Total (Pt) T17

    30920Reactive Power Phase L1(Q1)

    T17

    30921Reactive Power Phase L2(Q2)

    T17

    30922Reactive Power Phase L3(Q3)

    T17

    30923 Reactive Power Total (Qt) T17

    30924Apparent Power Phase L1(S1)

    T16

    30925Apparent Power Phase L2(S2)

    T16

    30926Apparent Power Phase L3(S3)

    T16

    30927 Apparent Power Total (St) T16

    30928 Power Factor Phase 1 (PF1) T17

    30929 Power Factor Phase 2 (PF2) T17

    30930 Power Factor Phase 3 (PF3) T17

    30931 Power Factor Total (PFt) T17

    30932 CAP/IND P. F. Phase 1 (PF1) T17

    30933 CAP/IND P. F. Phase 2 (PF2) T17

    30934 CAP/IND P. F. Phase 3 (PF3) T17

    30935 CAP/IND P. F. Total (PFt) T17

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    33/88

    Technical Manual M2x3C+I500C/EN M/C

    iSTAT M2x3 & I500 Modbus & DNP3.0 Page 31

    Code Address Contents Data Ind Values and Dependencies

    30936 1 (angle between U1 and I1) T17

    30937 2 (angle between U2 and I2) T17

    30938 3 (angle between U3 and I3) T17

    30939Power Angle Total(atan2(Pt,Qt))

    T17

    3094012 (angle between U1 andU2)

    T17

    3094123 (angle between U2 andU3)

    T17

    3094231 (angle between U3 andU1)

    T17

    30943 Frequency T17

    30944U unbalance

    T1630945 I1 THD% T16

    30946 I2 THD% T16

    30947 I3 THD% T16

    30948 U1 THD% T16

    30949 U2 THD% T16

    30950 U3 THD% T16

    30951 U12 THD% T16

    30952 U23 THD% T16

    30953 U31 THD% T16

    30954 31000 Reserved

    6.4 HARMONIC DATA

    Code Address Contents Data Ind Values and Dependencies

    PHASE VOLTAGE HARMONIC DATA

    U1 Harmonic Data

    31001 31002 Base for % calculation T531003 U1 1 Harmonic Abs % T16

    31004 U1 1 Harmonic Phase Angle T17

    31006 31126 U1 Harmonics from 2 to 62 T17

    31127 U1 63 Harmonic Abs % T16

    31128 U1 63 Harmonic Phase Angle T17

    U2 Harmonic Data

    31129 31130 Base for % calculation T5

    31131 U2 1 Harmonic Abs % T16

    31132 U2 1 Harmonic Phase Angle T17

    31134 31254 U2 Harmonics from 2 to 62 T17

    31255 U2 63 Harmonic Abs % T16

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    34/88

    M2x3C+I500C/EN M/C Technical Manual

    Page 32 iSTAT M2x3 & I500 Modbus & DNP3.0

    Code Address Contents Data Ind Values and Dependencies

    31256 U2 63 Harmonic Phase Angle T17

    U3 Harmonic Data

    31257 31258 Base for % calculation T5

    31259 U3 2 Harmonic Abs % T16

    31260 U3 2 Harmonic Phase Angle T17

    31262 31382 U3 Harmonics from 2 to 62 T17

    31383 U3 63 Harmonic Abs % T16

    31384 U3 63 Harmonic Phase Angle T17

    LINE VOLTAGE HARMONIC DATA

    U12 Harmonic Data

    31385 31386 Base for % calculation T5

    31387 U12 1 Harmonic Abs % T16

    31388 U12 1 Harmonic Phase Angle T17

    31390 31510 U12 Harmonics from 2 to 62 T17

    31511 U12 63 Harmonic Abs % T16

    31512 U12 63 Harmonic Phase Angle T17

    U23 Harmonic Data

    31513 31514 Base for % calculation T5

    31515 U23 1 Harmonic Abs % T16

    31516 U23 1 Harmonic Phase Angle T1731518 31638 U23 Harmonics from 2 to 62 T17

    31639 U23 63 Harmonic Abs % T16

    31640 U23 63 Harmonic Phase Angle T17

    U31 Harmonic Data

    31641 31642 Base for % calculation T5

    31643 U31 2 Harmonic Abs % T16

    31644 U31 2 Harmonic Phase Angle T17

    31646 31766 U31 Harmonics from 2 to 62 T17

    31767 U31 63 Harmonic Abs % T16

    31768 U31 63 Harmonic Phase Angle T17

    PHASE CURRENT HARMONIC DATA

    I1 Harmonic Data

    31769 31770 Base for % calculation T5

    31771 I1 1 Harmonic Abs % T16

    31772 I1 1 Harmonic Phase Angle T17

    31774 31894 I1 Harmonics from 2 to 62 T17

    31895 I1 63 Harmonic Abs % T16

    31896 I1 63 Harmonic Phase Angle T17

    I2 Harmonic Data

    31897 31898 Base for % calculation T5

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    35/88

    Technical Manual M2x3C+I500C/EN M/C

    iSTAT M2x3 & I500 Modbus & DNP3.0 Page 33

    Code Address Contents Data Ind Values and Dependencies

    31899 I2 1 Harmonic Abs % T16

    31900 I2 1 Harmonic Phase Angle T17

    31902 32022 I2 Harmonics from 2 to 62 T17

    32023 I2 63 Harmonic Abs % T16

    32024 I2 63 Harmonic Phase Angle T17

    I3 Harmonic Data

    32025 32026 Base for % calculation T5

    32027 I3 1 Harmonic Abs % T16

    32028 I3 1 Harmonic Phase Angle T17

    32030 32150 I3 Harmonics from 2 to 62 T17

    32151 I3 63 Harmonic Abs % T16

    32152 I3 63 Harmonic Phase Angle T17

    32153 32483 Reserved

    6.5 MEASUREMENTS (IEEE 754)

    Code Address Contents Data Ind Values and Dependencies

    MEASUREMENTS (IEEE 754)

    32484 32485 Uavg (phase to neutral) T_float

    32486 32487 Uavg (phase to phase) T_float

    32488 32489 I T_float

    32490 32491 Active Power Total (Pt) T_float

    32492 32493 Reactive Power Total (Qt) T_float

    32494 32495 Apparent Power Total (St) T_float

    32496 32497 Power Factor Total (PFt) T_float

    32498 32499 Frequency T_float

    32500 32501 U1 T_float

    32502 32503 U2 T_float

    32504 32505 U3 T_float32506 32507 Uavg (phase to neutral) T_float

    32508 32509 U12 T_float

    32510 32511 U23 T_float

    32512 32513 U31 T_float

    32514 32515 Uavg (phase to phase) T_float

    32516 32517 I1 T_float

    32518 32519 I2 T_float

    32520 32521 I3 T_float

    32522 32523 I T_float

    32524 32525 I neutral (calculated) T_float

    32526 32527 I neutral (measured) T_float

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    36/88

    M2x3C+I500C/EN M/C Technical Manual

    Page 34 iSTAT M2x3 & I500 Modbus & DNP3.0

    Code Address Contents Data Ind Values and Dependencies

    32528 32529 Iavg T_float

    32530 32531 Active Power Phase L1 (P1) T_float

    32532 32533 Active Power Phase L2 (P2) T_float

    32534 32535 Active Power Phase L3 (P3) T_float

    32536 32537 Active Power Total (Pt) T_float

    32538 32539 Reactive Power Phase L1 (Q1) T_float

    32540 32541 Reactive Power Phase L2 (Q2) T_float

    32542 32543 Reactive Power Phase L3 (Q3) T_float

    32544 32545 Reactive Power Total (Qt) T_float

    32546 32547Apparent Power Phase L1(S1) T_float

    32548 32549Apparent Power Phase L2(S2) T_float

    32550 32551Apparent Power Phase L3(S3) T_float

    32552 32553 Apparent Power Total (St) T_float

    32554 32555 Power Factor Phase 1 (PF1) T_float

    32556 32557 Power Factor Phase 2 (PF2) T_float

    32558 32559 Power Factor Phase 3 (PF3) T_float

    32560 32561 Power Factor Total (PFt) T_float

    32562 32563 CAP/IND P. F. Phase 1 (PF1) T_float

    32564 32565 CAP/IND P. F. Phase 2 (PF2) T_float

    32566 32567 CAP/IND P. F. Phase 3 (PF3) T_float

    32568 32569 CAP/IND P. F. Total (PFt) T_float

    32570 32571 1 (angle between U1 and I1) T_float

    32572 32573 2 (angle between U2 and I2) T_float

    32574 32575 3 (angle between U3 and I3) T_float

    32576 32577Power Angle Total(atan2(Pt,Qt)) T_float

    32578 3257912 (angle between U1 andU2) T_float

    32580 3258123 (angle between U2 andU3) T_float

    32582 3258331 (angle between U3 andU1) T_float

    32584 32585 Frequency T_float

    32586 32587 U unbalace T_float

    32588 32589 I1 THD% T_float

    32590 32591 I2 THD% T_float32592 32593 I3 THD% T_float

    32594 32595 U1 THD% T_float

    32596 32597 U2 THD% T_float

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    37/88

    Technical Manual M2x3C+I500C/EN M/C

    iSTAT M2x3 & I500 Modbus & DNP3.0 Page 35

    Code Address Contents Data Ind Values and Dependencies

    32598 32599 U3 THD% T_float

    32600 32601 U12 THD% T_float

    32602 32603 U23 THD% T_float

    32604 32605 U31 THD% T_float

    MAX DEMAND SINCE LASTRESET

    32606 32607Active Power Total (Pt) -(positive) T_float

    32608 32609Active Power Total (Pt) -(negative) T_float

    32610 32611 Reactive Power Total (Qt) - L T_float

    32612 32613 Reactive Power Total (Qt) - C T_float

    32614 32615 Apparent Power Total (St) T_float32616 32617 I1 T_float

    32618 32619 I2 T_float

    32620 32621 I3 T_float

    DYNAMIC DEMAND VALUES

    32622 32623Active Power Total (Pt) -(positive) T_float

    32624 32625Active Power Total (Pt) -(negative) T_float

    32626 32627 Reactive Power Total (Qt) - L T_float32628 32629 Reactive Power Total (Qt) - C T_float

    32630 32631 Apparent Power Total (St) T_float

    32632 32633 I1 T_float

    32634 32635 I2 T_float

    32636 32637 I3 T_float

    ENERGY

    32638 32639 Energy Counter 1 T_float

    32640 32641 Energy Counter 2 T_float

    32642 32643 Energy Counter 3 T_float

    32644 32645 Energy Counter 4 T_float

    32646 32647 Energy Counter 1 Cost T_float

    32648 32649 Energy Counter 2 Cost T_float

    32650 32651 Energy Counter 3 Cost T_float

    32652 32653 Energy Counter 4 Cost T_float

    32654 32655 Total Energy Counter Cost T_float

    32656 32657 Active Tariff T_float

    32658 32659 Internal Temperature T_float

    ANALOGUE INPUTS

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    38/88

    M2x3C+I500C/EN M/C Technical Manual

    Page 36 iSTAT M2x3 & I500 Modbus & DNP3.0

    Code Address Contents Data Ind Values and Dependencies

    32660 32661 Analog input 1 T_float

    32662 32663 Analog input 2 T_float

    32664 32665 Analog input 3 T_float

    32666 32667 Analog input 4 T_float

    32668 33000 Reserved

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    39/88

    Technical Manual M2x3C+I500C/EN M/C

    iSTAT M2x3 & I500 Modbus & DNP3.0 Page 37

    6.6 PRODUCT SETTINGS

    Address Contents Data Ind Values/Dependencies Min Max P.level

    SYSTEM COMMANDS

    40001 40002 User Password (L1,L2)

    T_Str4AZ

    Password to attempt user accesslevel upgrade

    0

    40003 40005 Factory Password(FAC)

    T_Str6 AZ Password to attempt factory accesslevel upgrade 0

    40006 40007 Level 1 - Userpassword

    T_Str4 AZ 1

    40008 40009 Level 2 - Userpassword

    T_Str4 AZ 2

    40010 40011 Reserved

    40012 Operator CommandRegister

    T1 1Save Settings

    2

    2 Abort Settings3 Restart Instrument

    4 Restart Ethernet

    5 Save Settings and Restart Ethernet

    40013 Reset commandregister 1

    T1 Bit-0 Reset counter 1 1

    Bit-1 Reset counter 2

    Bit-2 Reset counter 3

    Bit-3 Reset counter 4

    Bit-4 Reset counter 1 Cost

    Bit-5 Reset counter 2 Cost

    Bit-6 Reset counter 3 Cost

    Bit-7 Reset counter 4 Cost

    Bit-8 Reset Minimum/Maximum values

    Bit-9 Synchronize MD

    Bit-10 Reset last period MD

    Bit-11 Reset MD values

    40014Reset commandregister 2

    T1 Bit-0 Reset alarm output relay 1 1

    Bit-1 Reset alarm output relay 2

    Bit-2 Reset alarm output relay 3

    Bit-3 Reset alarm output relay 4

    40015 40100 Reserved

    GENERAL SETTINGS

    40101 40120 Description Str_40 2

    40121 40140 Location Str_40 2

    40141 Password activation Reserved

    40142 Password lock time T1 Minutes, 0 = No lock 0 60 2

    40143 Conection Mode T1 0 No mode 1 5 2

    1 1b - Single Phase2 3b - 3 phase 3 wire balanced

    3 4b - 3 phase 4 wire balanced

    4 3u - 3 phase 3 wire unbalanced

    5 4u - 3 phase 4 wire unbalanced

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    40/88

    M2x3C+I500C/EN M/C Technical Manual

    Page 38 iSTAT M2x3 & I500 Modbus & DNP3.0

    Address Contents Data Ind Values/Dependencies Min Max P.level

    40144 CT Secondary T4 mA 2

    40145 CT Primary T4 A/10 2

    40146 VT Secundary T4 mV 2

    40147 VT Primary T4 V/10 240148 Current input range

    (%)T16 10000 for 100% 5.00 260.00 2

    40149Voltage input range(%)

    T16 10000 for 100% 2.50 100.00 2

    40150Frequency nominalvalue

    T1 Hz 10 1000 2

    40151 CT Connection T1 0 Normal 0 1 1

    1 Disable wrong connectionchecking

    40152 MD Time constant T1 minutes (0=disabled) 0 255 2

    40153 MD Number ofsliding windows

    T1 0=thermal 0 15 2

    40154Starting total currentfor PFt & Pat

    T16 2000 for 20mA 0 10000 2

    40155Starting current forall powers

    T16 200 for 2mA 0 4000 2

    40156 Language T1 0 English 0 12 0

    1 French

    2 German

    3 Spanish

    4

    5 Russian

    6 Danish

    7 Italian

    8 US English

    9

    10 Polish

    11 Portuguese

    12

    40157 40158 Currency Str_4 2

    40159 Temperature unit T1 0 C 0 1 2

    1 F

    40160 Date format T1 0 DD.MM.YYYY 0 1 1

    1 MM/DD/YYYY

    40161 40162 Time T9 1

    40163 40164 Date T10 1

    40165 Reserved T1 Reserved

    40166Automatic changeS/W time

    T1 0 No 0 1 1

    1 Yes

    40167

    Starting voltage for

    SYNC

    T1 5000 for 5V 1000 16000

    2

    40168 Min/Max reset mode T1 0 Manual reset 0 4 2

    1 Day reset (00:00)

    2 Week reset (Monday, 00:00)

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    41/88

    Technical Manual M2x3C+I500C/EN M/C

    iSTAT M2x3 & I500 Modbus & DNP3.0 Page 39

    Address Contents Data Ind Values/Dependencies Min Max P.level

    3 Month reset (First day of the month,00:00)

    4 Year reset (January 1st, 00:00)

    40169

    Harmonics

    calculation

    T1 0 % of RMS 0 1 2

    1 % of 1st Harmonics

    40170 Comm. & LCDaverage interval

    T1 3 8 periods (0.16s @50Hz) 3 8 2

    4 16 periods (0.32s @50Hz)

    5 32 periods (0.64s @50Hz)

    6 64 periods (1.28s @50Hz) default

    7 128 periods (2.56s @50Hz)

    8 256 periods (5.12s @50Hz)

    40171 LCD Contrast T2 -10 10 2

    40172 LCD Back LightIntesnity

    T1 0=No Backlight 0 102

    40173 LCD Back Light TimeOff

    T1 Minutes (0=Always on) 0 602

    40174 LCD Demo cyclingperiod

    T1 Seconds 1 602

    40175LCD Custom screen1 - Line 1

    T1 See OutTypes 0 1002

    40176LCD Custom screen1 - Line 2

    T1 See OutTypes 0 1002

    40177LCD Custom screen1 - Line 3

    T1 See OutTypes 0 1002

    40178LCD Custom screen2 - Line 1

    T1 See OutTypes 0 1002

    40179LCD Custom screen2 - Line 2

    T1 See OutTypes 0 1002

    40180LCD Custom screen2 - Line 3

    T1 See OutTypes 0 1002

    40181LCD Custom screen3 - Line 1

    T1 See OutTypes 0 1002

    40182LCD Custom screen3 - Line 2

    T1 See OutTypes 0 1002

    40183LCD Custom screen3 - Line 3

    T1 See OutTypes 0 1002

    40184 40200 Reserved

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    42/88

    M2x3C+I500C/EN M/C Technical Manual

    Page 40 iSTAT M2x3 & I500 Modbus & DNP3.0

    Address Contents Data Ind Values/Dependencies Min Max P.level

    COMMUNICATION

    40201 Port 1: DeviceAddress (DNP3)

    T1 0 65519 2

    40202 Port 1: DeviceAddress (Modbus)

    T1 1 247 2

    40203 Port 1: Baud Rate T1 0 Baud rate 1200 1 7 2

    1 Baud rate 2400

    2 Baud rate 4800

    3 Baud rate 9600

    4 Baud rate 19200

    5 Baud rate 38400

    6 Baud rate 57600

    7 Baud rate 115200

    40204 Port 1: Stop Bit T1 0 1 Stop bit 0 1 2

    1 2 Stop bits

    40205 Port 1: Parity T1 0 No parity 0 2 2

    1 Odd parity

    2 Even parity

    40206 Port 1: Data Bits T1 0 8 bits 0 1 2

    1 7 bits

    40207 Port 1: TCP Port T1 1024 65535 2

    4020840227

    Port 1: IP Host NameT_Str_40

    40228 40229 Port 1: IP Address T_Hex4

    40230 40231 Port 1: Subnet Mask T_Hex4

    40232 40233Port 1: DefaultRouter

    T_Hex4

    40233 40250 Reserved

    40251Port 2: DeviceAddress (DNP3)

    T1 0 65519 1

    40252Port 2: DeviceAddress (Modbus)

    T1 1 247 2

    40253 Port 2: Baud Rate T1 See PORT 1 1 7 2

    40254 Port 2: Stop BitT1

    See PORT 1 0 1 2

    40255 Port 2: Parity T1 See PORT 1 0 2 2

    40256 Port 2: Data Bits T1 See PORT 1 0 0 2

    40257 40300 Reserved

    40301 40400 Reserved Port 3 -Port 4

    ENERGY

    40401 Active Tariff T1 0 Tariff input 0 5 1

    1..4 Tariff 1..4

    5 Tariff clock

    40402 Common EnergyCounter Exponent

    T2 -3 42

    40403 Common EnergyCost Exponent

    T2 -6 32

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    43/88

    Technical Manual M2x3C+I500C/EN M/C

    iSTAT M2x3 & I500 Modbus & DNP3.0 Page 41

    40404 Common Tariff PriceExponent

    T2 -6 32

    40405 Tariff 1: 1kWh Price T1 0 65500 2

    40406 Tariff 2: 1kWh Price T1 0 65500 2

    40407 Tariff 3: 1kWh Price T1 0 65500 2

    40408 Tariff 4: 1kWh Price T1 0 65500 2

    40409 Tariff 1: 1kvarh Price T1 0 65500 2

    40410 Tariff 2: 1kvarh Price T1 0 65500 2

    40411 Tariff 3: 1kvarh Price T1 0 65500 2

    40412 Tariff 4: 1kvarh Price T1 0 65500 2

    40413 Tariff 1: 1kVAh Price T1 0 65500 2

    40414 Tariff 2: 1kVAh Price T1 0 65500 2

    40415 Tariff 3: 1kVAh Price T1 0 65500 2

    40416 Tariff 4: 1kVAh Price T1 0 65500 2

    40417 40419 Reserved

    40420Reactive powercalculation

    T10 Standard calculation (Q

    2=S

    2 P

    2)

    0 1 2

    1 Delayed Current method

    40421Energy Counter 1Parameter

    T10 No Parameter

    0 19 2

    1 Active Power

    2 Reactive power

    3 Apparent Power

    5 Active Power Phase 1

    6 Reactive power Phase 1

    7 Apparent Power Phase 1

    9 Active Power Phase 2

    10 Reactive power Phase 2

    11 Apparent Power Phase 2

    13 Active Power Phase 3

    14 Reactive power Phase 3

    15 Apparent Power Phase 3

    16 Pulse input 1 (reg 40402 not used)

    17 Pulse input 2 (reg 40402 not used)

    18 Pulse input 3 (reg 40402 not used)19 Pulse input 4 (reg 40402 not used)

    40422Energy Counter 1Configuration

    T1 Bit-0Quadrant I Enabled

    0 63 2

    Bit-1 Quadrant II Enabled

    Bit-2 Quadrant III Enabled

    Bit-3 Quadrant IIII Enabled

    Bit-4 Absolute Value

    Bit-5 Invert Value

    40423Energy Counter 1Divider

    T1 01

    0 4 2

    1 10

    2 100

    3 1000

    4 10000

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    44/88

    M2x3C+I500C/EN M/C Technical Manual

    Page 42 iSTAT M2x3 & I500 Modbus & DNP3.0

    40424Energy Counter 1Tariff Selector

    T1Bit-0

    Tariff 1 Enabled0 15

    2

    Bit-1 Tariff 2 Enabled

    Bit-2 Tariff 3 Enabled

    Bit-3 Tariff 4 Enabled

    40425 40430 Reserved

    40431Energy Counter 2Parameter

    T1see Energy Counter 1 Parameter

    0 192

    40432Energy Counter 2Configuration

    T1see Energy Counter 1 Configuration

    0 632

    40433Energy Counter 2Divider

    T1see Energy Counter 1 Divider

    0 42

    40434Energy Counter 2Tariff Selector

    T1 see Energy Counter 1 TariffSelector

    0 152

    40435 40440 Reserved

    40441Energy Counter 3Parameter

    T1see Energy Counter 1 Parameter

    0 192

    40442Energy Counter 3Configuration

    T1see Energy Counter 1 Configuration

    0 632

    40443Energy Counter 3Divider

    T1see Energy Counter 1 Divider

    0 42

    40444Energy Counter 3Tariff Selector

    T1 see Energy Counter 1 TariffSelector

    0 152

    40445 40450 Reserved

    40451Energy Counter 4Parameter

    T1see Energy Counter 1 Parameter

    0 192

    40452Energy Counter 4Configuration

    T1see Energy Counter 1 Configuration

    0 632

    40453Energy Counter 4Divider

    T1see Energy Counter 1 Divider

    0 42

    40454Energy Counter 4Tariff Selector

    T1 see Energy Counter 1 TariffSelector

    0 152

    40455 40500 Reserved

    TARIFF CLOCK

    40501 Tariff Table 1 DaySelector

    T1 Bit-0 Monday 0 1023 2

    Bit-1 Tuesday

    Bit-2 Wednesday

    Bit-3 Thursday

    Bit-4 Friday

    Bit-5 Saturday

    Bit-6 Sunday

    Bit-7 Holiday

    Bit-8 Hebrew Holiday 1

    Bit-9 Hebrew Holiday 2

    40502 Tariff Table 2 DaySelector

    T1 see Tariff Table 1 Day Selector 0 1023 2

    40503 Tariff Table 3 DaySelector

    T1 see Tariff Table 1 Day Selector 0 1023 2

    40504 Tariff Table 4 DaySelector

    T1 see Tariff Table 1 Day Selector 0 1023 2

    40505 Start date of Season 1 T10A 0.0. for unused season 2

    40506 Start date of Season 2 T10A 0.0. for unused season 2

    40507 Start date of Season 3 T10A 0.0. for unused season 2

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    45/88

    Technical Manual M2x3C+I500C/EN M/C

    iSTAT M2x3 & I500 Modbus & DNP3.0 Page 43

    40508 Start date of Season 4 T10A 0.0. for unused season 2

    SEASON 1, TARIFF TABLE 1

    40509 Time 1 T9A 24:00 for unused time 2

    40510 Tariff Value 1 T1 1 4 2

    40511 Time 2 T9A 24:00 for unused time 240512 Tariff Value 2 T1 1 4 2

    40513 Time 3 T9A 24:00 for unused time 2

    40514 Tariff Value 3 T1 1 4 2

    40515 Time 4 T9A 24:00 for unused time 2

    40516 Tariff Value 4 T1 1 4 2

    40509 Time 1 T9A 24:00 for unused time 2

    SEASON 1, TARIFF TABLE 2

    40517 40524 TARIFF TABLE 2 See TARIFF TABLE 1 2

    SEASON 1, TARIFF TABLE 3

    40525 40532 TARIFF TABLE 3 See TARIFF TABLE 1 2

    SEASON 1, TARIFF TABLE 4

    40533 40540 TARIFF TABLE 4 See TARIFF TABLE 1 2

    SEASON 2, TARIFF TABLE 1..4

    40541 40572 SEASON 2,

    TABLE 14

    See SEASON 1

    2

    SEASON 3, TARIFF TABLE 1..4

    40573 40604 SEASON 3,

    TABLE 14

    See SEASON 1

    2

    SEASON 4, TARIFF TABLE 1..4

    40605 40636 SEASON 4,

    TABLE 14

    See SEASON 1

    2

    HOLIDAY DAY TABLE

    40637 Holiday Date 1 T10A 0.0. for unused date 2

    40638 Holiday Date 2 T10A 0.0. for unused date 2

    40639 Holiday Date 3 T10A 0.0. for unused date 2

    40640 Holiday Date 4 T10A 0.0. for unused date 2

    40641 Holiday Date 5 T10A 0.0. for unused date 2

    40642 Holiday Date 6 T10A 0.0. for unused date 2

    40643 Holiday Date 7 T10A 0.0. for unused date 2

    40644 Holiday Date 8 T10A 0.0. for unused date 2

    40645 Holiday Date 9 T10A 0.0. for unused date 2

    40646 Holiday Date 10 T10A 0.0. for unused date 2

    40647 Holiday Date 11 T10A 0.0. for unused date 2

    40648 Holiday Date 12 T10A 0.0. for unused date 2

    40649 Holiday Date 13 T10A 0.0. for unused date 2

    40650 Holiday Date 14 T10A 0.0. for unused date 2

    40651 Holiday Date 15 T10A 0.0. for unused date 2

    40652 Holiday Date 16 T10A 0.0. for unused date 2

    40653 Holiday Date 17 T10A 0.0. for unused date 2

    40654 Holiday Date 18 T10A 0.0. for unused date 2

    40655 Holiday Date 19 T10A 0.0. for unused date 2

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    46/88

    M2x3C+I500C/EN M/C Technical Manual

    Page 44 iSTAT M2x3 & I500 Modbus & DNP3.0

    40656 Holiday Date 20 T10A 0.0. for unused date 2

    40657 40700 Reserved

    INPUTS / OUTPUTS

    PULSE OUTPUTS

    40701 Pulse Output 1Energy Counter T1 0 Alarm output 0 5 2

    1 Counter 1

    2 Counter 2

    3 Counter 3

    4 Counter 4

    5 Tariff Clock

    40702Pulse Output 1 No.Of pulses

    T1 1 65535 2

    40703Pulse Output 1Energy unit

    T1 * 10^(Common Energy CounterExponent)

    1 65535 2

    40704Pulse Output 1 Pulselength

    T1 ms 2 1000 2

    40705Pulse Output 1 TariffSelector

    T1 Bit-0 Tariff 1 enabled 0 15 2

    Bit-1 Tariff 2 enabled

    Bit-2 Tariff 3 enabled

    Bit-3 Tariff 4 enabled

    40706Pulse Output 2Energy Counter T1

    0 5 2

    40707Pulse Output 2 No.Of pulses

    T1 1 65535 2

    40708Pulse Output 2Energy unit

    T1 * 10^(Common Energy CounterExponent)

    1 65535 2

    40709Pulse Output 2 Pulselength T1 ms

    2 1000 2

    40710Pulse Output 2 TariffSelector

    T1 0 15 2

    40711Pulse Output 3Energy Counter T1

    0 5 2

    40712Pulse Output 3 No.Of pulses

    T1 1 65535 2

    40713Pulse Output 3Energy unit

    T1 * 10^(Common Energy CounterExponent)

    1 65535 2

    40714Pulse Output 3 Pulselength T1 ms

    2 1000 2

    40715Pulse Output 3 TariffSelector

    T1 0 15 2

    40716Pulse Output 4Energy Counter T1

    0 5 2

    40717Pulse Output 4 No.Of pulses

    T1 1 65535 2

    40718Pulse Output 4Energy unit

    T1 * 10^(Common Energy CounterExponent)

    1 65535 2

    40719Pulse Output 4 Pulselength T1 ms

    2 1000 2

    40720Pulse Output 4 TariffSelector

    T1 0 15 2

    ALARM OUTPUT, OUTPUT 1

    40721Enabled Alarmgroups

    T1 Bit-0 Alarm group 1 enabled 0 15 2

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    47/88

    Technical Manual M2x3C+I500C/EN M/C

    iSTAT M2x3 & I500 Modbus & DNP3.0 Page 45

    Bit-1 Alarm group 2 enabled

    Bit-2 Alarm group 3 enabled

    Bit-3 Alarm group 4 enabled

    40722 Output signal T1 0 Normal 0 8 2

    1 Permanent

    2 Pulsed

    3 Always ON

    4 Always OFF

    5 Normal inverse

    6 Permanent Inverse

    7 Pulse Inverse

    8 Start

    40723 Output pulse length T1 Seconds 1 999 2

    ALARM OUTPUT, OUTPUT 2

    40724 40726 ALARM OUTPUT 2 See ALARM OUTPUT 1 2

    ALARM OUTPUT, OUTPUT 3

    40727 40729 ALARM OUTPUT 3 See ALARM OUTPUT 1 2

    ALARM OUTPUT, OUTPUT 4

    40730 40732 ALARM OUTPUT 4 See ALARM OUTPUT 1 2

    40733 40800 Reserved

    ANALOGUE OUTPUT, OUTPUT 1

    40801 40802 Reserved

    40803 Output 1 Type T1 0 1 mA 0 5 2

    1 5 mA

    2 10 mA

    3 20 mA (Constant for M2x3)

    4 1 V

    5 10 V

    40804 Output 1 Parameter T1 See OutTypes 0 110 2

    40805Output 1 FunctionType T1

    0Linear

    0 1 2

    1 Quadratic

    40806

    Output 1 Number of

    Breakpoints T1 0 6

    2

    40807Output 1 Lower XPoint (X0) T17

    % of parameter value-300 300

    2

    40808Output 1 Lower YPoint (Y0) T17

    % of output type-300 300

    2

    40809Output 1 XBreakpoint 1 (X1) T17

    % of parameter value-300 300

    2

    40810Output 1 YBreakpoint 1 (Y1) T17

    % of output type-300 300

    2

    40811Output 1 XBreakpoint 2 (X2) T17

    % of parameter value-300 300

    2

    40812

    Output 1 Y

    Breakpoint 2 (Y2) T17

    % of output type

    -300 300

    2

    40813Output 1 XBreakpoint 3 (X3) T17

    % of parameter value-300 300

    2

    40814Output 1 YBreakpoint 3 (Y3) T17

    % of output type-300 300

    2

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    48/88

    M2x3C+I500C/EN M/C Technical Manual

    Page 46 iSTAT M2x3 & I500 Modbus & DNP3.0

    40815Output 1 XBreakpoint 4 (X4) T17

    % of parameter value-300 300

    2

    40816Output 1 YBreakpoint 4 (Y4) T17

    % of output type-300 300

    2

    40817Output 1 XBreakpoint 5 (X5) T17

    % of parameter value-300 300

    2

    40818Output 1 YBreakpoint 5 (Y5) T17

    % of output type-300 300

    2

    40819Output 1 XBreakpoint 6 (X6) T17

    % of parameter value-300 300

    2

    40820Output 1 YBreakpoint 6 (Y6) T17

    % of output type-300 300

    2

    40821Output 1 Averageinterval (i5xx only) T1 0 1 period (0.02s@ 50Hz) default 0 8 2

    1 2 period (0.04s@ 50Hz)

    2 4 period (0.08s@ 50Hz)

    3 8 period (0.16s@ 50Hz)

    4 16 period (0.32s@ 50Hz)

    5 32 period (0.64s@ 50Hz)

    6 64 period (1.28s@ 50Hz)

    7 128 period (2.56s@ 50Hz)

    8 256 period (05.12s@ 50Hz)

    40822 40823 Reserved

    ANALOGUE OUTPUT, OUTPUT 2

    40824 40842 ANALOG OUTPUT 2 See ANALOG OUTPUT 1 2

    40843 40844 Reserved

    ANALOGUE OUTPUT, OUTPUT 3

    40845 40863 ANALOG OUTPUT 3 See ANALOG OUTPUT 1 2

    40864 40865 Reserved

    ANALOGUE OUTPUT, OUTPUT 4

    40866 40884 ANALOG OUTPUT 4 See ANALOG OUTPUT 1 2

    40885 41000 Reserved

    ANALOGUE INPUTs

    40901 Input 1 Serial number T1 0 0 65535 r.o.

    40902 Input 1 Type T1 0 Unknown 0 3 r.o.

    1 DC Current 20mA

    2 DC Voltage 10V

    3 Resistance / Temperature

    40903Input 1 ZeroCalibration point(Type 3) T17 wire resistance (Ohm) -25 25 2

    40904 Input 1 Function T1 Input type 1 (DC Current 20mA) 0 7 2

    0 DC Curent 20mA

    1 DC Curent 2mA

    Input type 2 (DC Voltage 10V)

    0 DC Voltage 10V

    1 DC Voltage 1V

    Input type 3 (Resistance /Temperature)

    0 Resistance 2 Kohm (2 wire)

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    49/88

    Technical Manual M2x3C+I500C/EN M/C

    iSTAT M2x3 & I500 Modbus & DNP3.0 Page 47

    1 Resistance 200 ohm (2 wire)

    2 Resistance 2 Kohm (3 wire)

    3 Resistance 200 ohm (3 wire)

    4 Pt 1000 (2 wire)

    5 Pt 100 (2 wire)

    6 Pt 1000 (3 wire)

    7 Pt 100 (3 wire)

    40905 40906 Input 1 Unit Str_4 2

    40907 Input 1 Exponent T2 -12 12 2

    40908 Input 1 Zero Point T17 value at 0% input -300 300 2

    40909 Input 1 End Point T17 value at 100% input -300 300 2

    40910 40916 Reserved

    40917 40932 Input 2 See Input 1

    40933 40948 Input 3 See Input 1

    40949 40964 Input 4 See Input 1

    40965 41000 Reserved

    ALARMS

    41001Alarm Enable Flags116

    T1 Bit-iEnable Alarm i

    2

    41002Alarm Enable Flags1732

    T1 Bit-iEnable Alarm i

    2

    ALARM GROUP 1 (1..8)

    41003Thermal function timeconstant

    T1minutes

    1 255 2

    41004 Compare time delay T1 seconds 0 900 2

    41005Hysteresis

    T16% of compare value, if 0 then % ofnominal value

    0 1000 2

    41006 41007 Reserved

    ALARM 1

    41008 Alarm 1 parameter T1 See OutTypes 0 1023 2

    41009 Alarm 1 function T1 Bit-1 Reserved: Store into memory (all) 0 255 2

    Bit-2 Store into memory (1 per minute)

    Bit-3 Activate LED

    Bit-4 Activate Alarm Output

    Bit-5 Activate Beep Output

    Bit-6 Alarm Condition > (< if 0)

    Bit-7 Use Thermal function

    41010Alarm 1 comparevalue

    T17 % of parameter value -300 300 2

    ALARM 2

    41011 41013 ALARM 2 See ALARM 1 2

    ALARM 3

    41014 41016 ALARM 3 See ALARM 1 2

    ALARM 4

    41017 41019 ALARM 4 See ALARM 1 2

    ALARM 5

    41020 41022 ALARM 5 See ALARM 1 2

    ALARM 6

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    50/88

    M2x3C+I500C/EN M/C Technical Manual

    Page 48 iSTAT M2x3 & I500 Modbus & DNP3.0

    41023 41025 ALARM 6 See ALARM 1 2

    ALARM 7

    41026 41028 ALARM 7 See ALARM 1 2

    ALARM 8

    41029 41031 ALARM 8 See ALARM 1 2

    ALARM GROUP 2 (9..16)

    41032 41060

    ALARM GROUP 2

    (No. 916) See ALARM GROUP 1 2

    ALARM GROUP 3 (17..24)

    41061 41089

    ALARM GROUP 3

    (No. 1724) See ALARM GROUP 1 2

    ALARM GROUP 4 (25..32)

    41090 41118

    ALARM GROUP 4

    (No. 2532) See ALARM GROUP 1 241119 41998 Reserved

    MEMORY

    41999 42500 Memory Settings

    POWER SUPPLY QUALITY (M253 & i5MQ only)

    42501 Monitoring mode T1 0 No mode 0 1 2

    1 EN50160

    42502 Energetic system T1 0 Low voltage 0 1

    1 Medium voltage

    2 Low voltage (Islanded system)

    3 Medium voltage (Islanded system)

    42503Nominal SupplyVoltage

    T16 % of VT Primary 5.00 120.00 2

    42504Nominal PowerFrequency T1 0 50 Hz 0 1 2

    1 60 Hz

    42505 Monitoring period T1 Weeks 1 10 2

    42506 Monitoring start day T1 0 Monday 0 6 2

    1 Tuesday

    2 Wednesday

    3 Thursday

    4 Friday

    5 Saturday

    6 Sunday

    42507 Voltage Hysteresis T16 %o of Nominal Supply Voltage 0.00 5.00 2

    42508 42509 Reserved

    FREQUENCY VARIATIONS

    42510 Average interval T1 0 10 sec

    42511

    Frequency variation 1

    Upper Limit %

    T16 0.01 25.00 2

    42512Frequency variation 1Lower Limit %

    T16 0.01 25.00 2

    42513Frequency variation 1Required Quality

    T16 75.00 100.00 2

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    51/88

    Technical Manual M2x3C+I500C/EN M/C

    iSTAT M2x3 & I500 Modbus & DNP3.0 Page 49

    42514Frequency variation 1Period T1 0 No monitoring

    0 3 2

    1 Info only

    2 Monitoring time

    3 Year

    42515 42515 Reserved

    42516 Frequency variation 2Upper Limit %

    T16 0.01 25.00 2

    42517 Frequency variation 2Lower Limit %

    T16 0.01 25.00 2

    42518 Frequency variation 2Required Quality

    T16 75.00 100.00 2

    42519 Frequency variation 2Period

    T1 See Frequency variation 1 Period 0 3 2

    42520 42529 Reserved

    VOLTAGE VARIATIONS

    42530 Average interval T1 2 10 min

    42531 Voltage variation 1Upper Limit %

    T16 0.01 25.00 2

    42532 Voltage variation 1Lower Limit %

    T16 0.01 25.00 2

    42533 Voltage variation 1Required Quality

    T16 75.00 100.00 2

    42534 Voltage variation 1Period

    T1 See Frequency variation 1 Period 0 3 2

    42535 42535 Reserved

    VOLTAGE VARIATIONS

    42536 Voltage variation 2Upper Limit %

    T16 0.01 25.00 2

    42537 Voltage variation 2Lower Limit %

    T16 0.01 25.00 2

    42538 Voltage variation 2Required Quality

    T16 75.00 100.00 2

    42539 Voltage variation 2Period

    T1 See Frequency variation 1 Period 0 3 2

    42540 42540 Reserved

    42541 Voltage AsymmetryLimit %

    T16 0.01 25.00 2

    42542 Symmetry RequiredQuality

    T16 75.00 100.00 2

    42543 Symmetry Period T1 See Frequency variation 1 Period 0 3 2

    42544 42550 Reserved

    VOLTAGE INTERRUPTIONS

    42551 Voltage Dip Limit % T16 50.00 99.00 2

    42552 Allowed No. ofVoltage Dips

    T1 0 10000 2

    42553 Voltage Dips Period T1 See Frequency variation 1 Period 0 3 2

    42554 Interruption Limit % T16 1.00 25.00 2

    42555 Short Interruption

    time

    T1 Seconds 1 300 2

    42556 Allowed No. of ShortInterruptions

    T1 0 10000 2

    42557 Short InterruptionsPeriod

    T1 See Frequency variation 1 Period 0 3 2

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    52/88

    M2x3C+I500C/EN M/C Technical Manual

    Page 50 iSTAT M2x3 & I500 Modbus & DNP3.0

    42558 Allowed No. of LongInterruptions

    T1 0 10000 2

    42559 Long InterruptionsPeriod

    T1 See Frequency variation 1 Period 0 3 2

    42560 42560 Reserved

    TRANSIENTS42561 Transient Limit % T16 1.0 10.00 2

    42562 Transient Rate of rice T16 5.00 600.00 2

    42563 Allowed No. ofTransients

    T1 0 10000 2

    42564 Transients Period T1 See Frequency variation 1 Period 0 3 2

    42565 42566 Reserved

    OVERVOLTAGES AND FLICKERS

    42567 Average interval(Flicker)

    T1 2 10 min

    42568 Short term Pst FlickerLimit % T16 0.01 25.00 2

    42569 Flicker Pst RequiredQuality

    T16 75.00 100.00 2

    42570 Flicker Pst Period T1 See Frequency variation 1 Period 0 3 2

    42571 Average interval(Flicker)

    T1 4 2 hour

    42572 Long term Plt FlickerLimit %

    T16 0.01 25.00 2

    42573 Flicker Plt RequiredQuality

    T16 75.00 100.00 2

    42574 Flicker Plt Period T1 See Frequency variation 1 Period 0 3 2

    42575 TemporaryOvervoltage Limit %

    T16 101.00 150.00 2

    42576 Allowed No. ofOvervoltages

    T1 0 10000 2

    42577 Overvoltage Period T1 See Frequency variation 1 Period 0 3 2

    42578 42580 Reserved

    HARMONICS & THD

    42581 Average interval T1 2 10 min

    42582 THD Limit % T16 0.01 25.00 2

    42583THD RequiredQuality

    T1675.00 100.00 2

    42584 THD Period T1 See Frequency variation 1 Period 0 3 2

    42585 Harmonics RequiredQuality

    T16 75 100 2

    42586 Harmonics Period T1 See Frequency variation 1 Period 0 3 2

    42587 2. Harmonic Limit % T16 0.01 25.00 2

    42588 3. Harmonic Limit % T16 0.01 25.00 2

    42589 4. Harmonic Limit % T16 0.01 25.00 2

    42590 5. Harmonic Limit % T16 0.01 25.00 2

    42591 6. Harmonics Limit % T16 0.01 25.00 2

    42592 7. Harmonic Limit % T16 0.01 25.00 242593 9. Harmonic Limit % T16 0.01 25.00 2

    42594 11. Harmonic Limit % T16 0.01 25.00 2

    42595 13. Harmonic Limit % T16 0.01 25.00 2

    42596 15. Harmonic Limit % T16 0.01 25.00 2

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    53/88

    Technical Manual M2x3C+I500C/EN M/C

    iSTAT M2x3 & I500 Modbus & DNP3.0 Page 51

    42597 17. Harmonic Limit % T16 0.01 25.00 2

    42598 19. Harmonic Limit % T16 0.01 25.00 2

    42599 21. Harmonic Limit % T16 0.01 25.00 2

    42600 23. Harmonic Limit % T16 0.01 25.00 2

    42601 25. Harmonic Limit % T16 0.01 25.00 2

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    54/88

    M2x3C+I500C/EN M/C Technical Manual

    Page 52 iSTAT M2x3 & I500 Modbus & DNP3.0

    Values/Dependencies Min Max Step Pass

    M233 0

    Software version 208 0

    (=6 if incorrect divider @40025)(1)

    -6 9 1 0

    (=6 if incorrect divider @40026)(1) -6 9 1 0

    (=6 if incorrect divider @40027)(1) -6 9 1 0

    (=6 if incorrect divider @40028)(1)

    -6 9 1 0

    Total export active energy (default) -99999999 899999999 1 0

    Total import reactive energy (default) -99999999 899999999 1 0

    Pulse output 1 -99999999 899999999 1 0

    Pulse output 2 -99999999 899999999 1 0

    W 0

    W 0

    W 0

    W 0

    var L(if > 0); var C (if < 0) 0

    var L(if > 0); var C (if < 0) 0

    var L(if > 0); var C (if < 0) 0

    var L(if > 0); var C (if < 0) 0

    A 0

    A 0

    A 0

    A 0V 0

    V 0

    V 0

    V 0

    VA 0

    VA 0

    VA 0

    VA 0

    mHz 00.000 65.535 0.001 Hz 0

    mHz 00.000 65.535 0.001 Hz 0

    mHz 00.000 65.535 0.001 Hz 0

    mHz 00.000 65.535 0.001 Hz 0

    0.01 deg -180.00 +179.99 0.01 deg 0

    0.01 deg -180.00 +179.99 0.01 deg 0

    0.01 deg -180.00 +179.99 0.01 deg 0

    0.01 deg -180.00 +179.99 0.01 deg 0

    A 0

    0.01 deg -180.00 +179.99 0.01 deg 0

    0.01 deg -180.00 +179.99 0.01 deg 0

    0.01 deg -180.00 +179.99 0.01 deg 0

    V 0

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    55/88

    Technical Manual M2x3C+I500C/EN M/C

    iSTAT M2x3 & I500 Modbus & DNP3.0 Page 53

    Values/Dependencies Min Max Step Pass

    V 0

    V 0

    V 0

    Total active power 0

    Total absolute reactive power 0

    Total apparent power 0

    Total I 0

    Total active power 0

    Total absolute reactive power 0

    Total apparent power 0

    Total I 0

    0.01 % 0.00 400.00 0.01 % 00.01 % 0.00 400.00 0.01 % 0

    0.01 % 0.00 400.00 0.01 % 0

    0.01 % 0.00 400.00 0.01 % 0

    0.01 % 0.00 400.00 0.01 % 0

    0.01 % 0.00 400.00 0.01 % 0

    0.01 % 0.00 400.00 0.01 % 0

    0.01 % 0.00 400.00 0.01 % 0

    0.01 % 0.00 400.00 0.01 % 0

    Reset Counter 1 1

    Reset Counter 1

    Reset pulse output Counter 1

    Reset pulse output Counter 2

    Synchronise MD

    Reset last period MD

    Reset MD Values

    1 V 0

    10 A/10 = 1 A 50 A/10 = 5 A 0.1 V 0

    2300 for 230 V 0.1 V 2

    Unsigned integer value 1 15999 1

    Unsigned exponent 0 3 1

    10 775 1 V, 5 V 2

    1 4000 1 2

    Single phase 2

    3 phase 3 wire balanced

    3 phase 4 wire balanced

    3 phase 3 wire unbalanced

    3 phase 4 wire unbalanced1200 baud 2

    2400 baud

    4800 baud

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    56/88

    M2x3C+I500C/EN M/C Technical Manual

    Page 54 iSTAT M2x3 & I500 Modbus & DNP3.0

    Values/Dependencies Min Max Step Pass

    9600 baud

    19200 baud

    38400 baud

    57600 baud115200 baud

    1 => 2 stop bits; 0 => 1 stop bit

    1 => Odd parity; 0 => Even parity

    1 => Parity; 0 => No parity

    1 => 7 bits; 0 => 8 bits (read only)

    > 10 ms response time

    Disable 2

    Time constant (window period;interval of sub-period)

    Thermal function

    Fixed window

    Sliding window; # of periods

    Enable quadrant 1 2

    Enable quadrant 2

    Enable quadrant 3

    Enable quadrant 4

    Absolute value

    Inverted value

    1 => Reactive energy; 0 => Activeenergy

    Enable quadrant 1

    Enable quadrant 2

    Enable quadrant 3

    Enable quadrant 4

    Absolute value

    Inverted value

    1 => Reactive energy; 0 => Activeenergy

    Same as Counter 2 mode 2

    Same as Counter 1 mode

    1, 10, 100, 1000, 10000(1)

    2

    1, 10, 100, 1000, 10000(1)

    2

    1, 2, 5, 10, 20, 50, , 50000(1)

    2

    1, 2, 5, 10, 20, 50, , 50000(1)

    2

    320 for 0.2% 3-128 127 1 3

    I1, family HI 3

    I2, family HI

  • 8/13/2019 m2x3c i500c en m c Manual Gb

    57/88

    Technical Manual M2x3C+I500C/EN M/C

    iSTAT M2x3 & I500 Modbus & DNP3.0 Page 55

    Values/Dependencies Min Max Step Pass

    I3, family HI

    I1, family LO

    I2, family LO

    I3, family LO

    U1

    U2

    U3

    Power angle phase L1, family HI

    Power angle phase L2, family HI

    Power angle phase L3, family HI

    Power angle phase L1, family LO

    Power angle phase L2, family LOPower angle phase L3, family LO

    Calibrate voltage inputs 3

    Calibrate current inputs

    Calibrate phase angles

    English 2

    French

    German

    Spanish

    Russian

    Danish

    Only 0 can be written 0 3 1 0

    Counter 1 must be halted -99999999 899999999 1 2

    Counter 2 must be